Mitsubishi Electronics MR-J2M-P8B User Manual

General-Purpose AC Servo
SSCNET Compatible
MODEL
MR-J2M-P8B MR-J2M- DU MR-J2M-BU
SERVO AMPLIFIER INSTRUCTION MANUAL
G

Safety Instructions

(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the units until you have read through this Instruction Manual, Installation Guide, Servo Motor Instruction Manual and appended documents carefully and can use the equipment properly. Do not use the units until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols:
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight injury to personnel or may cause physical
damage.
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this Instruction Manual, always keep it accessible to the operator.
.
.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, switch power off and wait for more than 15 minutes. Then, confirm the voltage is safe with voltage tester. Otherwise, you may get an electric shock.
Connect the base unit and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire for each unit and the servo motor until they are installed. Otherwise, you can obtain the electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Do not install the base unit, servo motor and regenerative brake resistor on or near combustibles. Otherwise a fire may cause.
When each unit has become faulty, switch off the main base unit power side. Continuous flow of a large current may cause a fire.
When a regenerative brake resistor is used, use an alarm signal to switch main power off. Otherwise, a regenerative brake transistor fault or the like may overheat the regenerative brake resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the servo amplifier heat sink, regenerative brake resistor, servo motor, etc.since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their masses.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport each unit. Each unit may drop.
Install the each unit in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The controller and servo motor must be installed in the specified direction.
Leave specified clearances between the base unit and control enclosure walls or other equipment.
Do not install or operate the unit and servo motor which has been damaged or has any parts missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering each unit and servo motor.
Do not drop or strike each unit or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Environment
During Ambient temperature
Ambient humidity
Ambience Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt Altitude Max. 1000m (3280 ft) above sea level
(Note) Vibration
Note. Except the servo motor with reduction gear.
operation
In storage
During
operation
In storage 90%RH or less (non-condensing)
[ ] 0 to 55 (non-freezing) 0 to 40 (non-freezing) [
] 32 to 131 (non-freezing) 32 to 104 (non-freezing) [ ] 20 to 65 (non-freezing) 15 to 70 (non-freezing) [
] 4 to 149 (non-freezing) 5 to 158 (non-freezing)
90%RH or less (non-condensing) 80%RH or less (non-condensing)
[m/s2] 5.9 or less
2
] 19.4 or less
[ft/s
Each unit Servo motor
Conditions
HC-KFS Series HC-MFS Series
HC-UFS13 to 43
HC-KFS Series HC-MFS Series
HC-UFS13 to 43
X Y : 49
X Y : 161
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
A - 3
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo motor and drive unit.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W) directly. Do not let a magnetic contactor, etc. intervene.
Drive unit
U
V
W
Servo Motor
U
V
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in the specified direction. Otherwise, the forced stop and other protective circuits may not operate.
Interface unit
VIN
SG
Control output
signal
Interface unit
VIN
SG
Control output
signal
RARA
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
A - 4
(4) Usage
CAUTION
Provide a emergency stop circuit to ensure that operation can be stopped and power switched off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by electronic equipment used near MELSERVO-J2M.
Burning or breaking each unit may cause a toxic gas. Do not burn or break each unit.
Use the drive unit with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ballscrew and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the interface unit signals but also by a forced stop (EM1).
Contacts must be open when servo-off, when an alarm occurrence and when an electromagnetic brake interlock (MBR).
Servo motor
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
Circuit must be opened during forced stop (EM1).
EM1RA
24VDC
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the drive unit will deteriorate. To prevent a secondary accident due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general environment. Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Instruction Manual.
A - 6

About processing of waste

When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
A - 7

COMPLIANCE WITH EC DIRECTIVES

1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment into which servo (MELSERVO-J2M is contained) have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment. This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to MELSERVO-J2M. Hence, they are designed to comply with the low voltage directive. MELSERVO-J2M is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, MELSERVO-J2M need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Unit and servo motors used
Use each units and servo motors which comply with the standard model.
Drive unit :MR-J2M­Interface unit :MR-J2M-P8B Base unit :MR-J2M-BU Servo motor :HC-KFS
HC-MFS HC-UFS
(2) Configuration
DU
Reinforced insulating transformer
No-fuse breaker
NFB
Control box
Magnetic contactor
Reinforced insulating type
24VDC power supply
MELSERVO­J2M
MC
Servo motor
M
A - 8
(3) Environment
Operate MELSERVO-J2M at or above the contamination level 2 set forth in IEC60664-1. For this purpose, install MELSERVO-J2M in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
(4) Power supply
(a) Operate MELSERVO-J2M to meet the requirements of the overvoltage category II set forth in
IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC or EN standard should be used in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been
insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked
base unit to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal. Always connect the
cables to the terminals one-to-one.
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
of the base unit must be connected to the corresponding earth terminals.
) of the
(d) The protective earth (PE) of the servo motor is connected to the protective earth of the base unit via
the screw which fastens the drive unit to the base unit. When fixing the drive unit to the base unit, therefore, tighten the accessory screw securely.
(6) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in Section 12.2.2.
(b) The sizes of the cables described in Section 12.2.1 meet the following requirements. To meet the
other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [ ( )] Sheath: PVC (polyvinyl chloride) Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(7) Performing EMC tests
When EMC tests are run on a machine/device into which MELSERVO-J2M has been installed, it must conform to the electromagnetic compatibility (immunity/emission) standards after it has satisfied the operating environment/electrical equipment specifications. For the other EMC directive guidelines on MELSERVO-J2M, refer to the EMC Installation Guidelines(IB(NA)67310).
A - 9

CONFORMANCE WITH UL/C-UL STANDARD

The MELSERVO-J2M complies with UL508C.
(1) Unit and servo motors used
Use the each units and servo motors which comply with the standard model. Drive unit :MR-J2M­Interface unit :MR-J2M-P8B Base unit :MR-J2M-BU Servo motor :HC-KFS
HC-MFS HC-UFS
DU
(2) Installation
Install a fan of 100CFM (2.8m
3
/min)air flow 4 in (10.16 cm) above MELSERVO-J2M or provide cooling
of at least equivalent capability.
(3) Short circuit rating
MELSERVO-J2M conforms to the circuit whose peak current is limited to 5000A or less. Having been
subjected to the short-circuit tests of the UL in the alternating-current circuit, MELSERVO-J2M
conforms to the above circuit.
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for
15 minutes after power-off.
Base unit Discharge time [min]
MR-J2M-BU4 3 MR-J2M-BU6 4 MR-J2M-BU8 5
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual are required if you use MELSERVO-J2M for the first time. Always purchase them and use the MELSERVO-J2M safely. Also read the manual of the servo system controller.
Relevant manuals
Manual name Manual No.
MELSERVO-J2M Series To Use the AC Servo Safely (Packed with the MR-J2M-P8B, MR-J2M­MELSERVO Servo Motor Instruction Manual SH(NA)3181 EMC Installation Guidelines IB(NA)67310
BU and MR-J2M-BU )
IB(NA)0300027
In this Instruction Manual, the drive unit, interface unit and base unit may be referred to as follows: Drive unit : DRU Interface unit : IFU Base unit : BU
A - 10

CONTENTS

1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-10
1.1 Overview................................................................................................................................................... 1- 1
1.2 Function block diagram ..........................................................................................................................1- 2
1.3 Unit standard specifications................................................................................................................... 1- 3
1.4 Function list ............................................................................................................................................. 1- 4
1.5 Model code definition .............................................................................................................................. 1- 5
1.6 Combination with servo motor............................................................................................................... 1- 6
1.7 Parts identification.................................................................................................................................. 1- 7
1.8 Servo system with auxiliary equipment................................................................................................ 1- 9
2. INSTALLATION AND START UP 2- 1 to 2-10
2.1 Environmental conditions....................................................................................................................... 2- 1
2.2 Installation direction and clearances .................................................................................................... 2- 2
2.3 Keep out foreign materials .....................................................................................................................2- 3
2.4 Cable stress .............................................................................................................................................. 2- 3
2.5 Mounting method ....................................................................................................................................2- 4
2.6 When switching power on for the first time.......................................................................................... 2- 6
2.7 Start up..................................................................................................................................................... 2- 7
2.8 Control axis selection .............................................................................................................................. 2- 9
3. SIGNALS AND WIRING 3- 1 to 3-28
3.1 Connection example of control signal system ....................................................................................... 3- 2
3.2 I/O signals of interface unit .................................................................................................................... 3- 4
3.2.1 Connectors and signal arrangements .............................................................................................3- 4
3.2.2 Signal explanations .......................................................................................................................... 3- 5
3.2.3 Interfaces ...........................................................................................................................................3- 6
3.3 Signals and wiring for extension IO unit ..............................................................................................3- 9
3.3.1 Connection example ......................................................................................................................... 3- 9
3.3.2 Connectors and signal configurations ........................................................................................... 3-11
3.3.3 Output signal explanations ............................................................................................................3-12
3.4 Signals and wiring for base unit ........................................................................................................... 3-14
3.4.1 Connection example of power line circuit...................................................................................... 3-14
3.4.2 Connectors and signal configurations ........................................................................................... 3-16
3.4.3 Terminals.......................................................................................................................................... 3-17
3.4.4 Power-on sequence........................................................................................................................... 3-18
3.5 Connection of drive unit and servo motor ............................................................................................3-19
3.5.1 Connection instructions ..................................................................................................................3-19
3.5.2 Connection diagram ........................................................................................................................ 3-19
3.5.3 I/O terminals .................................................................................................................................... 3-20
3.6 Alarm occurrence timing chart .............................................................................................................3-21
3.7 Servo motor with electromagnetic brake ............................................................................................. 3-22
3.8 Grounding................................................................................................................................................ 3-26
3.9 Instructions for the 3M connector......................................................................................................... 3-27
1
4. OPERATION AND DISPLAY 4- 1 to 4-10
4.1 Normal indication.................................................................................................................................... 4- 1
4.1.1 Display sequence............................................................................................................................... 4- 2
4.1.2 If alarm/warning occurs ................................................................................................................... 4- 3
4.2 Status display mode of interface unit.................................................................................................... 4- 4
4.2.1 Display flowchart.............................................................................................................................. 4- 4
4.2.2 Status display of interface unit .......................................................................................................4- 5
4.2.3 Diagnostic mode of interface unit ................................................................................................... 4- 6
4.2.4 Alarm mode of interface unit........................................................................................................... 4- 7
4.2.5 Interface unit parameter mode ....................................................................................................... 4- 8
4.2.6 Output signal (DO) forced output ................................................................................................... 4- 9
5. PARAMETERS 5- 1 to 5-26
5.1 Drive unit .................................................................................................................................................5- 1
5.1.1 Parameter write inhibit ...................................................................................................................5- 1
5.1.2 Lists.................................................................................................................................................... 5- 2
5.2 Interface unit ..........................................................................................................................................5-15
5.2.1 IFU parameter write inhibit........................................................................................................... 5-15
5.2.2 Lists...................................................................................................................................................5-15
5.2.3 Analog monitor................................................................................................................................. 5-21
5.2.4 Test operation mode ........................................................................................................................5-24
6. GENERAL GAIN ADJUSTMENT 6- 1 to 6-12
6.1 Different adjustment methods ...............................................................................................................6- 1
6.1.1 Adjustment on a MELSERVO-J2M................................................................................................ 6- 1
6.1.2 Adjustment using MR Configurator (servo configuration software) ........................................... 6- 3
6.2 Auto tuning ..............................................................................................................................................6- 4
6.2.1 Auto tuning mode .............................................................................................................................6- 4
6.2.2 Auto tuning mode operation ............................................................................................................ 6- 5
6.2.3 Adjustment procedure by auto tuning............................................................................................ 6- 6
6.2.4 Response level setting in auto tuning mode .................................................................................. 6- 7
6.3 Manual mode 1 (simple manual adjustment)....................................................................................... 6- 8
6.3.1 Operation of manual mode 1 ........................................................................................................... 6- 8
6.3.2 Adjustment by manual mode 1 ....................................................................................................... 6- 8
6.4 Interpolation mode ................................................................................................................................. 6-11
7. SPECIAL ADJUSTMENT FUNCTIONS 7- 1 to 7-10
7.1 Function block diagram ..........................................................................................................................7- 1
7.2 Machine resonance suppression filter ................................................................................................... 7- 1
7.3 Adaptive vibration suppression control................................................................................................. 7- 3
7.4 Low-pass filter ......................................................................................................................................... 7- 4
7.5 Gain changing function........................................................................................................................... 7- 5
7.5.1 Applications ...................................................................................................................................... 7- 5
7.5.2 Function block diagram ...................................................................................................................7- 5
7.5.3 Parameters........................................................................................................................................ 7- 6
7.5.4 Gain changing operation .................................................................................................................7- 8
8. INSPECTION 8- 1 to 8- 2
2
9. TROUBLESHOOTING 9- 1 to 9-10
9.1 Alarms and warning list ......................................................................................................................... 9- 1
9.2 Remedies for alarms................................................................................................................................ 9- 3
9.3 Remedies for warnings........................................................................................................................... 9-10
10. OUTLINE DRAWINGS 10- 1 to 10- 10
10.1 MELSERVO-J2M configuration example.........................................................................................10- 1
10.2 Unit outline drawings .........................................................................................................................10- 2
10.2.1 Base unit (MR-J2M-BU
)........................................................................................................... 10- 2
10.2.2 Interface unit (MR-J2M-P8B) .....................................................................................................10- 2
10.2.3 Drive unit (MR-J2M-
DU)......................................................................................................... 10- 3
10.2.4 Extension IO unit (MR-J2M-D01) ..............................................................................................10- 4
10.2.5 Battery unit (MR-J2M-BT).......................................................................................................... 10- 4
10.3 Connector .............................................................................................................................................10- 5
11. CHARACTERISTICS 11- 1 to 11- 6
11.1 Overload protection characteristics ...................................................................................................11- 1
11.2 Power supply equipment capacity and generated loss ....................................................................11- 2
11.3 Dynamic brake characteristics...........................................................................................................11- 4
11.4 Encoder cable flexing life ....................................................................................................................11- 6
12. OPTIONS AND AUXILIARY EQUIPMENT 12- 1 to 12-36
12.1 Options.................................................................................................................................................. 12- 1
12.1.1 Regenerative brake options ......................................................................................................... 12- 1
12.1.2 Cables and connectors ..................................................................................................................12- 8
12.1.3 Maintenance junction card (MR-J2CN3TM) ............................................................................12-21
12.1.4 MR Configurator (servo configurations software) ....................................................................12-23
12.2 Auxiliary equipment ..........................................................................................................................12-25
12.2.1 Recommended wires ....................................................................................................................12-25
12.2.2 No-fuse breakers, fuses, magnetic contactors........................................................................... 12-26
12.2.3 Power factor improving reactors ................................................................................................12-27
12.2.4 Relays............................................................................................................................................ 12-28
12.2.5 Surge absorbers ...........................................................................................................................12-28
12.2.6 Noise reduction techniques.........................................................................................................12-28
12.2.7 Leakage current breaker ............................................................................................................ 12-34
12.2.8 EMC filter..................................................................................................................................... 12-35
13. ABSOLUTE POSITION DETECTION SYSTEM 13- 1 to 13- 4
13.1 Features................................................................................................................................................ 13- 1
13.2 Specifications .......................................................................................................................................13- 2
13.3 Confirmation of absolute position detection data............................................................................. 13- 3
APPENDIX App- 1 to App- 2
App 1. Status indication block diagram ................................................................................................. App- 1
3
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is introduced here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in this Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULATION METHODS FOR DESIGNING
4

1. FUNCTIONS AND CONFIGURATION

)
1. FUNCTIONS AND CONFIGURATION

1.1 Overview

The Mitsubishi general-purpose AC servo MELSERVO-J2M series is an AC servo which has realized wiring-saving, energy-saving and space-saving in addition to the high performance and high functions of the MELSERVO-J2-Super series. Connected with a servo system controller or like by a serial bus (SSCNET), the equipment reads position data directly to perform operation. Data from a command unit are used to control the speeds and directions of servo motors and execute precision positioning. The MELSERVO-J2M series consists of an interface unit (abbreviated to the IFU) to be connected with a servo system controller, drive units (abbreviated to the DRU) for driving and controlling servo motors, and a base unit (abbreviated to the BU) where these units are installed. A torque limit is applied to the drive unit by the clamp circuit to protect the main circuit power transistors from overcurrent caused by abrupt acceleration/deceleration or overload. In addition, the torque limit value can be changed as desired using the parameter. The interface unit has an RS-232C serial communication function to allow the parameter setting, test operation, status indication monitoring, gain adjustment and others of all units to be performed using a personal computer or like where the MR Configurator (servo configuration software) is installed. By choosing the axis number of the drive unit using the MR Configurator (servo configuration software), you can select the unit to communicate with, without changing the cabling. The real-time auto tuning function automatically adjusts the servo gains according to a machine. The MELSERVO-J2M series supports as standard the absolute position encoders which have 131072 pulses/rev resolution, ensuring control as accurate as that of the MELSERVO-J2-Super series. Simply adding the optional battery unit configures an absolute position detection system. Hence, merely setting a home position once makes it unnecessary to perform a home position return at power-on, alarm occurrence or like. The MELSERVO-J2M series has a control circuit power supply in the interface unit and main circuit converter and regenerative functions in the base unit to batch-wire the main circuit power input, regenerative brake connection and control circuit power input, achieving wiring-saving. In the MELSERVO-J2M series, main circuit converter sharing has improved the capacitor regeneration capability dramatically. Except for the operation pattern where all axes slow down simultaneously, the capacitor can be used for regeneration. You can save the energy which used to be consumed by the regenerative brake resistor.
Regenerative brake option
Control circuit power input
Bus cable connections
Main circuit power input
Extension IO unit MR-J2M-D01
Encoder pulse output extension DIO (Axes 1 to 4)
Encoder cable
Encoder pulse output extension DIO (Axes 5 to 8
Servo motor power cable
Personal computer connection Analog monitor Forced stop input Electromagnetic brake interlock output
1 - 1
1. FUNCTIONS AND CONFIGURATION

1.2 Function block diagram

Base unit Interface unit
CNP1B
Power supply 3-phase 200 to
NFB MC
FR-BAL
230VAC (Note) 1-phase 200 to 230VAC
Regenerative brake option
CNP1A
L11
L
L1
L2
L
21
P
N
C
CNP3
3
Regener-
ative TR
Inrush
I/F Control
Controller or Servo amplifier
Position command
I/F Control
CN1ACN1BCN3CNP2CN2CNP2CN2
Servo amplifier or termination connector
current
suppression
circuit
RS-232C
D/A
Personal computer
Analog monitor (3 channels)
Drive unit
Dynamic
Servo motor
brake
(Earth)
U V W
Encoder
M
Base amplifier
Actual position control
Position command input
Model position
Model position control
Overcurrent
protection
Actual speed control
Model speed
Model speed control
Current control
Model torque
Virtual servo motor
Current detector
Current
detection
Virtual encoder
Drive unit
Drive unit
CON3A-3H CON3A-3H CON3A-3H
Note. For 1-phase 200 to 230VAC, connect the power supply to L
1 - 2
Dynamic brake
Current
detection
Dynamic brake
Current
detection
, L2 and leave L3 open.
1
CNP2CN2
Servo motor
(Earth)
U V
M
W
Encoder
Servo motor
(Earth)
U V
M
W
Encoder
1. FUNCTIONS AND CONFIGURATION

1.3 Unit standard specifications

(1) Base unit
Model MR-J2M-BU4 MR-J2M-BU6 MR-J2M-BU8
Number of slots 4 6 8
(Note)
Control circuit power supply
Main circuit power supply
Function Converter function, regenerative control, rushing into current control function
Protective functions
Mass
Note. The control circuit power supply is recorded to the interface unit.
Voltage/frequency 3-phase 200 to 230VAC or 1-phase 200 to 230VAC, 50/60Hz Permissible voltage fluctuation 1-phase 170 to 253VAC Permissible frequency fluctuation Within 5%
Inrush current 20A (5ms)
Voltage/frequency 3-phase 200 to 230VAC or 1-phase 200 to 230VAC, 50/60Hz Permissible voltage fluctuation 3-phase 170 to 253VAC or 1-phase 170 to 253VAC, 50/60Hz Permissible frequency fluctuation Within 5% Maximum servo motor connection capacity [W] Continuous capacity [W] 1280 1920 2560 Inrush current 62.5A (15ms)
[kg] 1.1 1.3 1.5
[lb] 2.4 2.9 3.3
1600 2400 3200
Regenerative overvoltage shut-off, regenerative fault protection,
undervoltage /instantaneous power failure protection
(2) Drive unit
Model MR-J2M-10DU MR-J2M-20DU MR-J2M-40DU MR-J2M-70DU
Power supply
Control system Sine-wave PWM control, current control system Dynamic brake Built-in
Protective functions
Structure Open (IP00) Cooling method Self-cooled Force-cooling (With built-in fan unit)
Mass
Voltage/frequency 270 to 311VDC Permissible voltage fluctuation 230 to 342VDC
Overcurrent shut-off, functions overload shut-off (electronic thermal relay),
servo motor overheat protection, encoder fault protection, overspeed
protection, excessive error protection
[kg] 0.4 0.4 0.4 0.7
[lb] 0.89 0.89 0.89 1.54
(3) Interface unit
Model MR-J2M-P8B
Control circuit power supply Power supply circuit for each unit(8 slots or less) Interface SSCNET interface 1channel RS-232C interface 1channel
DIO
AIO Analog monitor 3channel Structure Open (IP00)
Mass
[kg] 0.5
[lb] 1.10
Forced stop input(1 point), Electromagnetic brake sequence output
(1 point)
1 - 3
1. FUNCTIONS AND CONFIGURATION

1.4 Function list

The following table lists the functions of this servo. For details of the functions, refer to the Reference field.
(1) Drive unit (Abbreviation DRU)
Function Description Reference
High-resolution encoder High-resolution encoder of 131072 pulses/rev is used as a servo motor encoder.
Auto tuning
Adaptive vibration suppression control
Low-pass filter
Slight vibration suppression control Forced stop signal automatic ON
Torque limit Servo motor torque can be limited to any value.
Automatically adjusts the gain to optimum value if load applied to the servo motor shaft varies. MELSERVO-J2M detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration. Suppresses high-frequency resonance which occurs as servo system response is increased.
Suppresses vibration of 1 pulse produced at a servo motor stop.
Forced stop (EM1) can be automatically switched on internally to invalidate it.
Chapter 6
Section 7.3
Section 7.4
DRU Parameter No.24 DRU Parameter No.23 DRU Parameters No.10, No.11
(2) Interface unit (Abbreviation IFU)
Function Description Reference
Forced stop signal input Disconnect forced stop (EM1) to bring the servo motor to a forced stop state, in
which the servo is switched off and the dynamic brake is operated.
In the servo-off or alarm status, this signal is disconnected. Electromagnetic brake output
Analog monitor Servo status is output in terms of voltage in real time. Section 5.2.3
When an alarm occurs, they are disconnected, independently of the base circuit
status.
It is possible to use it to excite an electromagnetic brake.
Section 3.2.2
Section 3.2.2
(3) Base unit (Abbreviation BU)
Function Description Reference
Regenerative brake option
Used when the built-in regenerative brake resistor of the unit does not have
sufficient regenerative capability for the regenerative power generated.
Section 12.1.1
(4) MR Configurator (servo configuration software)
Function Description Reference
Machine analyzer function Analyzes the frequency characteristic of the mechanical system.
Machine simulation
Gain search function Can simulate machine motions on the basis of the machine analyzer results. Test operation mode JOG operation and positioning operation are possible.
Can simulate machine motions on a personal computer screen on the basis of the
machine analyzer results.
(5) Option unit
Function Description Reference
Absolute position detection system
Encoder pulse output
Merely setting a home position once makes home position return unnecessary at
every power-on.
Battery unit MR-J2M-BT is necessary.
The encoder feedback is output from enhancing IO unit MR-J2M-D01 by the
B Z phase pulse. The number of pulses output by the parameter can be
A
changed.
1 - 4
1. FUNCTIONS AND CONFIGURATION

1.5 Model code definition

(1) Drive unit
(a) Rating plate
SON
MODEL
MR-J2M-40DU
POWER INPUT OUTPUT SERIAL TC300A***G51
MITSUBISHI ELECTRIC
(b) Model code
ALM
400W DC270V-311V 170V 0-360Hz 2.3A N9Z95046
MR-J2M- DU
Rating plate
Model Capacity Applicable power supply Rated output current Serial number
Rating plate
Rated output
Symbol Capacity of applied servo motor
10 20 40 70
100 200 400 750
(2) Interface unit
(a) Rating plate
MITSUBISHI
MODEL
POWER : AC INPUT:
OUTPUT : SERIAL :A5*******
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
(b) Model code
AC SERVO
MR-J2M-P8B
75W 2PH AC200-230V 50Hz 2PH AC200-230V 60Hz
DC5/12/20 4.6A/1.2/0.7A
TC3**AAAAG52
PASSED
MR-J2M-P8B
Model
Input capacity
Applicable power supply
Output voltage / current
Serial number
SSCNET compatible
1 - 5
Rating plate
1. FUNCTIONS AND CONFIGURATION
(3) Base unit
(a) Rating plate
Rating plate
MITSUBISHI
MODEL
MR-J2M-BU4
INPUT :
SERIAL:
N87B95046 BC336U246
MITSUBISHI ELECTRIC
MADE IN JAPAN
(b) Model code
MR-J2M-BU
3PH 200-230 14A 50/60Hz
PASSED
Model Applicable power supply Serial number
Symbol
Number of slots
4 61920 8
Maximum servo motor connection capacity [W]
4 6 8
1600 2400 3200
Continuous capacity [W]
1280
2560

1.6 Combination with servo motor

The following table lists combinations of drive units and servo motors. The same combinations apply to the models with electromagnetic brakes and the models with reduction gears.
Drive unit
MR-J2M-10DU 053 13 053 13 13 MR-J2M-20DU 23 23 23 MR-J2M-40DU 43 43 43 MR-J2M-70DU 73 73 73
HC-KFS
Servo motor
HC-MFS HC-UFS
1 - 6
1. FUNCTIONS AND CONFIGURATION

1.7 Parts identification

(1) Drive unit
Status indicator LED
Indicates the status of the drive unit. Blinking green: Servo off status Steady green: Servo on status Blinking red: Warning status Steady red: Alarm status
CN2 Encoder connector Connect the servo motor encoder
CNP2 Servo motor connector
For connection of servo motor power line cable
(2) Interface unit
Mounting screw
Rating plate
CN1A Bus cable connector
For connection of servo system controller or preceding-axis servo amplifier.
CN3 For connection of personal computer (RS-232C). Outputs analog monitor.
Display Indicates operating status or alarm.
Pushbutton switches Used to change status indication or set IFU parameters.
Mounting screw
Display/setting cover
CN1B Bus cable connector For connection of subsequent-axis servo
amplifier or MR-A-TM termination connector.
Charge lamp Lit when main circuit capacitor carries electrical charge. When this lamp is on, do not remove/reinstall any unit from/to base unit and do not unplug/plug cable and connector from/into any unit.
1 - 7
1. FUNCTIONS AND CONFIGURATION
r
(3) Base unit
The following shows the MR-J2M-BU4.
CNP1B Control circuit power input connector
CNP1A Regenerative brake option connector
CON3A First slot connector
CON3C Third slot connector
CNP3 Main circuit power input connector
CON1,CON2 Interface unit connectors
CON3B Second slot connector
CON4 Option slot connector
CON5 Battery unit connecto
CON3D Fourth slot connector
1 - 8
1. FUNCTIONS AND CONFIGURATION
r

1.8 Servo system with auxiliary equipment

WARNING
3-phase 200V to 230VAC (Note) 1-phase 200V to 230VAC power supply
No-fuse breake (NFB) or fuse
Magnetic contactor (MC)
To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor MR Configurator
(servo configuration software)
11
L
L
21
Regenerative brake option
Control circuit power supply
) of the base unit to the protective earth (PE) of the control box.
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.4
Servo system
controller
or Preceding axis servo amplifier
To CN1A To CN1B
Options and auxiliary equipment
Regenerative brake option
Cables
Power factor improving reactor
Subsequent axis
servo amplifier
or
Termination
connector
Reference
Section 12.1.1
Section 12.2.1
Section 12.2.3
Power factor improving reactor (FR-BAL)
1
L
L2
L3
Main circuit power supply
MR Configurator (servo configuration software)
P C
To CNP1A
To CNP1B
Encoder cable
To CNP3
To CN3
Personal computer
Power supply lead
Note. For 1-phase 200 to 230VAC, connect the power supply to L
, L2 and leave L3 open.
1
1 - 9
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 10

2. INSTALLATION AND START UP

2. INSTALLATION AND START UP
Stacking in excess of the limited number of products is not allowed. Install the equipment to incombustibles. Installing them directly or close to
combustibles will led to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury. Use the equipment within the specified environmental condition range. Provide an adequate protection to prevent screws, metallic detritus and other
CAUTION
conductive matter or oil and other combustible matter from entering each unit.
Do not block the intake/exhaust ports of each unit. Otherwise, a fault may occur. Do not subject each unit to drop impact or shock loads as they are precision
equipment.
Do not install or operate a faulty unit. When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the
corners of the servo amplifier.

2.1 Environmental conditions

The following environmental conditions are common to the drive unit, interface unit and base unit.
Environment Conditions
During Ambient temperature
Ambient humidity
Ambience
Altitude Max. 1000m (3280 ft) above sea level
Vibration
operation
In storage
During operation
In storage
[ ]0 to 55 (non-freezing)
] 32 to 131 (non-freezing)
[ [ ] 20 to 65 (non-freezing)
] 4 to 149 (non-freezing)
[
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
[m/s2] 5.9 [m/s2] or less
2
[ft/s
] 19.4 [ft/s2] or less
2 - 1
2. INSTALLATION AND START UP

2.2 Installation direction and clearances

The equipment must be installed in the specified direction. Otherwise, a fault may
CAUTION
(1) Installation of one MELSERVO-J2M
occur.
Leave specified clearances between each unit and control box inside walls or other
equipment.
40mm(1.57inch) or more
40mm(1.57inch) or more
40mm(1.57inch) or more
40mm(1.57inch) or more
(2) Installation of two or more MELSERVO-J2M
When installing two units vertically, heat generated by the lower unit influences the ambient temperature of the upper unit. Suppress temperature rises in the control box so that the temperature between the upper and lower units satisfies the environmental conditions. Also provide adequate clearances between the units or install a fan.
40mm(1.57inch) or more
40mm(1.57inch) or more
Leave 100mm(3.94inch) or more clearance or install fan for forced air cooling.
40mm(1.57inch) or more
40mm(1.57inch) or more
2 - 2
2. INSTALLATION AND START UP
(3) Others
When using heat generating equipment such as the regenerative brake option, install them with full consideration of heat generation so that MELSERVO-J2M is not affected. Install MELSERVO-J2M on a perpendicular wall in the correct vertical direction.

2.3 Keep out foreign materials

(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering each
unit.
(2) Prevent oil, water, metallic dust, etc. from entering each unit through openings in the control box or a
fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an
air purge (force clean air into the control box from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the control box.

2.4 Cable stress

(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own mass
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner
or stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as
large as possible. Refer to section 11.4 for the flexing life.
2 - 3
2. INSTALLATION AND START UP

2.5 Mounting method

(1) Base unit
As shown below, mount the base unit on the wall of a control box or like with M5 screws.
Wall
(2) Interface unit/drive unit (MR-J2M-40DU or less)
The following example gives installation of the drive unit to the base unit. The same also applies to the interface unit.
Sectional view
Drive unit
Base unit
Catch
1) Hook the catch of the drive unit in the positioning hole of the base unit.
Sectional view
2)
Drive unit
Wall
1)
Positioning hole
Base unit
Wall
2) Using the catch hooked in the positioning hole as a support, push the drive unit in.
2 - 4
2. INSTALLATION AND START UP
Sectional view
3)
3)
3) Tighten the M4 screw supplied for the base unit to fasten the drive unit to the base unit.
POINT
Securely tighten the drive unit fixing screw.
Sectional view
Wall
Wall
(3) Drive unit (MR-J2M-70DU)
When using the MR-J2M-70DU, install it on two slots of the base unit. The slot number of this drive unit is that of the left hand side slot of the two occupied slots, when they are viewed from the front of the base unit.
2 - 5
Loading...
+ 165 hidden pages