(Always read these instructions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual
carefully and pay full attention to safety to handle the product correctly.
The instructions given in this manual are concerned with this product. For the safety instructions of the
programmable controller system, please read the CPU module User's Manual.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
DANGER
!
CAUTION
!
Note that the !CAUTION level may lead to a serious consequence according to t he circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forw ard it to the end user.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight personal injury or physical damage.
[Design Precautions]
!
DANGER
• Do not write data into the "read-only area" in t he buffer me mory of the int elligent function
module. In addition, do not turn on/off the "reserved" signals among the I/O signals transferred
to/from the PLC CPU.
Doing so can malfunction the PLC system.
• Depending on the malfunction of the external output transistor, there may be cases where the
output is ON or OFF status. Install external monitoring circuitry for output signals that may lead
to major accidents.
!
CAUTION
• Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other.
They should be installed 100 mm(3.94 inch) or more from each other.
Not doing so could result in noise that may cause malfunction.
A - 1 A - 1
[Installation Precautions]
!
CAUTION
• Use the PLC in an environment that meets the general specifications cont ained in the CP U
User's Manual.
Using this PLC in an environment outside the range of the general specificat ions may cause
electric shock, fire, malfunction, and damage to or deterioration of the product.
• When installing the module, securely insert the module fixing tabs int o the mountin g holes of the
base module while pressing the installation lever located at the bottom of the module downward.
Improper installation may result in malfunction, breakdown or the module co ming loose and
dropping. Securely fix the module with screws if it is subject to vibration during use.
• Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
• Switch all phases of the external power supply off when mounting or removing the modu le.
Not ding so may cause electric shock or damage to the module.
The system that uses the QnPHCPU allows y ou to change a module online. Not e that there are
restrictions on the modules that can be changed online and each module has a predetermined
changing procedure. For details, refer to the chapter of online module change in this manual.
• Do not directly touch the conductive area or electronic components of the module.
Doing so may cause malfunction or failure in the module.
[Wiring Precautions]
!
CAUTION
• Be careful not to let foreign matters such as sawdust or wire chips get inside the module.
They may cause fires, failure or malfunction.
• The top surface of the module is covered with protective film to prevent foreign objects such as
cable offcuts from entering the module when wiring.
Do not remove this film until the wiring is complete.
Before operating the system, be sure to remove the film to provide adequate heat ventilation.
• Be sure to fix communication cables or power supply cables leading from the module by placing
them in the duct or clamping them.
Cables not placed in the duct or without clamping may hang or shift, allow ing them to be
accidentally pulled, which may cause a module malfunctio n and cable da mage.
• Do not grab on the cable when removing the communication or power cable connected to the
module.
When disconnecting a cable without a connector, first loosen the screws on the part that is
connected to the module.
Pulling the cable when it is still connected to the module may cause damage to t he module or
cable, or misoperation due to cable contact failure.
A - 2 A - 2
[Wiring Precautions]
!
DANGER
• Always ground the shielded cable for the PLC.
There is a risk of electric shock or malfunction.
• When wiring, be sure to verify the rated voltage of the product as well as the terminal layout. Fire
or failure may result if incorrect voltage is input or incorrect wiring is performed.
• Connecting terminals with incorrect voltage may result in malfunction or mechanica l failure.
[Startup/Maintenance Precautions]
!
CAUTION
• Do not disassemble or modify the module.
Doing so could cause failure, malfunction, injury or fire.
• Switch all phases of the external power supply off when mounting or removing the modu le.
Not doing so may cause failure or malfunction of the module.
The system that uses the QnPHCPU allows y ou to change a module online. Not e that there are
restrictions on the modules that can be changed online and each module has a predetermined
changing procedure. For details, refer to the chapter of online module change in this manual.
• Do not touch the connector while the power is on.
Doing so may cause malfunction.
• Switch all phases of the external power supply off when cleaning or retightening the terminal
screws and module installation screws.
Not doing so may cause failure or malfunction of the module.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damages to the screws and/or the module,
resulting in the module falling out, short circuits or malfunct ion.
• Always make sure to touch the grounded metal to discharge the electricity charged in the body ,
etc., before touching the module.
Failure to do so may cause a failure or malfunctions of the module.
[Disposal Precautions]
!
CAUTION
• When disposing of the product, handle it as industrial wast e.
A - 3 A - 3
REVISIONS
* The manual number is given on the bottom left of the back cover.
Print Date Manual NumberRevision
Oct., 2000SH (NA)-080121-A First edition
Jun., 2001SH (NA)-080121-B S tandardize the name from software package (GPP function) to Product
name (GX Developer).
Standardize the name from utility package (QTCU) to Product name (GX
Configurator-TC).
Addition
Section 1.4, Section 2.1, 2.2
Correction
Conformation to the EMC Directive and Low Voltage Instruction, About
the Generic Terms and Abbreviations, Product Structure, Section 3.5.47,
Section 5.2, 5.2.1, 5.2.2, 5.3.3, 5.6
Feb., 2002SH (NA)-080121-C Add the contents of the function version C
Addition
Chapter 7
Renumbering
Chapter 7
Chapter 8
Aug., 2002SH (NA)-080121-D
Feb., 2003SH (NA)-080121-E
Correction
SAFETY PRECAUTIONS, About the Generic Terms and Abbreviations,
Section 2.1, 2.2, Section 3.1.1, 3.2, 3.2.1, 3.2.10, 3.2.11, 3.5.1, 3.5.11,
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
2000 MITSUBISHI ELECTRIC CORPORATION
A - 4 A - 4
INTRODUCTION
Thank you for the purchasing the MELSEC-Q series PLC.
Before using the equipment, please read this manual carefully to develop full familiarity with the functions
and performance of the Q series PLC you have purchased, so as to ensure correct use.
1.1 Features ...................................................................................................................................................1- 3
1.2 The PID Control System..........................................................................................................................1- 5
1.3 About the PID Operation..........................................................................................................................1- 6
1.3.1 Operation method and formula.........................................................................................................1- 6
1.3.2 The Q64TC actions...........................................................................................................................1- 7
3.1.1 Performance specifications of the Q64TC ....................................................................................... 3- 1
3.1.2 Usable temperature sensor types, measurement temperature ranges and data resolutions........ 3- 3
3.2 Function Summary...................................................................................................................................3- 4
3.2.1 Auto tuning function...........................................................................................................................3- 5
3.2.2 Reverse/Forward action select function ...........................................................................................3- 9
3.2.12 Control output setting at CPU stop error occurrence.....................................................................3-19
3.2.13 Q64TC control status controlling output signal and
buffer memory settings and control status.....................................................................................3-20
3.3 Sampling Period and Control Output Period...........................................................................................3-21
3.4 I/O Signals Transferred to/from the PLC CPU........................................................................................3-22
3.4.1 I/O signal list......................................................................................................................................3-22
3.4.2 Input signal functions.........................................................................................................................3-23
3.4.3 Output signal functions......................................................................................................................3-26
3.5.1 Buffer memory list .............................................................................................................................3-28
3.5.2 Write data error code (buffer memory address: 0
3.5.3 Decimal point position (buffer memory address: 1
3.5.4 Alert definition (buffer memory address: 5
H
3.5.5 Temperature process value (PV value, buffer memory address: 9
3.5.6 Manipulated value (MV value, buffer memory address: D
3.5.7 Temperature rise judgment flag (buffer memory address: 11
3.5.8 Transi s to r ou tp ut fl ag (bu ffe r me mory add r e ss: 15
3.5.9 Cold junction temperature process value (buffer memory address: 1D
3.5.10 MAN mode shift completion flag (buffer memory address: 1E
3.5.11 E
3.5.12 Inpu t ra nge ( bu ffe r me mory address: 20
2
PROM's PID constant read/write flag (buffer memory address: 1FH)....................................... 3-34
4.2 Procedure Before Starting the Operation................................................................................................4- 2
4.3 Parts Identification....................................................................................................................................4- 3
5.2 Installing and Uninstalling the Utility Package.........................................................................................5- 3
5.2.1 User precautions ...............................................................................................................................5- 3
5.5 Auto Refresh ............................................................................................................................................5-15
6.2.2 Program example..............................................................................................................................6- 4
6.3 Program Example Written without Using GX Configurator-TC ..............................................................6- 5
Conformation to the EMC Directive and Low Voltage Instruction
For details on making Mitsubishi PLC conform to the EMC directive and low voltage
instruction when installin g it in your pro duct, ple as e see Cha pter 3, "EM C Dir ec tive
and Low Voltage Instruction" of the User's Manual (Hardware) of the PLC CPU to
use.
The CE logo is printed on the rating plate on the main body of the PLC that conforms
to the EMC directive and low voltage instruction.
The following wiring is required for conformance of this product with the EMC
Directive and Low Voltage Directive.
(1) Use shielded cables for all external wiring and use the AD75CK cable clamp to
ground this product to an enclosure.
Inside control box
Q64TC
20cm (7.88 inch) to
30cm (11.82 inch)
AD75CK
Strip the sheath.
(2) Using the AD75CK, you can tie four cables of about 7mm outside diameter
together for grounding.
(3) The following number of AD75CKs will be needed.
(Assuming that 7mm-diameter cables are used for all wiring)
Unless otherwise specified, this manual uses the following generic terms and
abbreviations to describe the Temperature control module.
Generic term/abbreviationDescription
Personal computerDOS/V-compatible personal computer of IBM PC/ATR or its compatible
Generic product name of the product types SWnD5C-GPPW-E, SWnD5C-GPPW-EA,
GX Developer
QCPU (Q mode)
QnPHCPUGeneric term of the Q12PHCPU and Q25PHCPU.
GX Configurator-TC
Q64TCTTAbbreviation of Type Q64TCTT temperature control module
Q64TCTTBW
Q64TCRTAbbreviation of Type Q64TCRT temperature control module
Q64TCRTBW
Q64TCGeneric term of Type Q64TCTT, Q64TCTTBW, Q64TCRT and Q64TCRTBW
SWnD5C-GPPW-EV and SWnD5C-GPPW-EVA.
"n" in the model name is 4 or greater.
Generic term of the Q00JCPU, Q00CPU, Q01CPU, Q02CPU, Q02HCPU, Q06HCPU,
Q12HCPU, Q25HCPU, Q12PHCPU and Q25PHCPU.
Generic term of temperature control module setting/monitoring tool GX ConfiguratorTC(SW0D5C-QTCU-E)
Abbreviation of Type Q64TCTTBW temperature control module with disconnection
detection function
Abbreviation of Type Q64TCRTBW temperature control module with disconnection
detection function
Product Structure
The product structure of the product is given in the table below.
Model codeProduct nameQuantity
Q64TCTTType Q64TCTT temperature control module1
Q64TCTTBW
Q64TCRTType Q64TCRT temperature control module1
Q64TCRTBW
SW0D5C-QTCU-EGX Configurator-TC Version 1 (1-license product) (CD-ROM)1
SW0D5C-QTCU-EAGX Configurator-TC Version 1 (Multiple-license product) (CD-ROM)1
Type Q64TCTTBW temperature control module w ith dis con nec tion
detection function
Type Q64TCRTBW temperature control module with disconnection
detection function
1
1
A - 10 A - 10
1 GENERAL DESCRIPTION
1 GENERAL DESCRIPTION
MELSEC-Q
PLC CPU
This manual deals with the specifications, handling and instructions wiring and
programming methods of the following temperature control modules used with the
MELSEC-Q series PLC CPU module (hereafter abbreviated to the PLC CPU).
• Type Q64TCTT temperature control module
• Type Q64TCRT temperature control module
• Type Q64TCTTBW temperature control module with disconnection detection function
• Type Q64TCRTBW temperature control module with disconnection detection function
(1)What are Q64TCTT and Q64TCRT?
(a) The Q64TCTT and Q64TCRT are modules designed to convert input values
from external temperature sensors into 16-bit signed BIN (binary) data,
perform PID operations to attain target temperatures, and provide transistor
outputs for temperature control.
(b) The Q64TCTT and Q64TCRT have an auto tuning function which
automatically sets the proportional band (P), integral time (I) and derivative
time (D) for PID operations.
(c) The Q64TCTT accepts K, J, T, B, S, E, R, N, U, L, PL II and W5Re/W26Re
type thermocouples. The Q64TCRT accepts Pt100 and JPt100 type platinum
temperature-measuring resistors.
Q64TCTT,Q64TCRT
Buffer memory
1
Initial
setting
(TO
instruction)
Input from temperature
sensor
Transistor output
(ON/OFF pulse)
Temperature
Device
to be
controlled
PID
operation
Set value
Process
value
Manipulated
value
CH1
CH4
Process value
CH1
value
CH4
Manipulated
CH1
Set value
CH4
Manipulated value
CH1
CH1
Fig. 1.1 Q64TCTT or Q64TCRT Processing Outline
REMARK
1) Refer to Se ctio n 3 .2 .1 fo r th e au to tu nin g fun cti on
2) Refer to Section 3.1.2 for the measured temperature ranges of the temperature
sensors that can be connected to the Q64TC.
1 - 1 1 - 1
1 GENERAL DESCRIPTION
1
MELSEC-Q
(2)What are Q64TCTTBW and Q64TCRTBW?
The Q64TCTTBW and Q64TCRTBW are Q64TCTT and Q64TCRT-based
modules which have the additional function to detect a heater wire disconnection
using inputs from external current sensors.
PLC CPU
Initial
setting
(TO
instruction)
PID
operation
Set value
Process
value
Manipulated
value
Q64TCTTBW,Q64TCRTBW
Buffer memory
CH1
CH4
Process value
CH1
value
CH4
Manipulated
CH1
Set value
CH4
CH1
Alarm
CH4
Manipulated value
Disconnection
detection
Input from temperature
CH1
Transistor output
(ON/OFF pulse)
CH1
sensor
Current
sensor
Temperature
Device
to be
controlled
Fig. 1.2 Q64TCTTBW or Q64TCRTBW Processing Outline
REMARK
1) Refer to Section 3.2.7 for the disconnection detection function of the
Q64TCTTBW and Q64TCRTBW.
1 - 2 1 - 2
1 GENERAL DESCRIPTION
1.1 Features
The Q64TC has the following features.
(1)Optimum temperature adjustment contr ol (PID contr ol )
(a) The Q64TC exercises temperature adjustment control automatically by
merely setting the PID constants (proportional band (P), integral time (I),
derivative time (D)) and temperature set value (set value: SV) necessary for
PID operations.
Therefore, no special instructions are needed to perform PID control.
(b) Using the auto tuning function enables the PID constants to be set
automatically by the Q64TC.
Hence, you can use the equipment without being conscious of cumbersome
PID operation expressions to find the PID constants.
(2)4 loops on 1 module
The module provides a maximum of four loops at the same time for temperature
adjustment control.
MELSEC-Q
(3)RFB limiter function
The RFB (Reset FeedBack) limiter suppresses overshooting which is liable to
occur at a startup or when a temperature set value (SV) is increased.
(4)Sensor compensation function
By setting a sensor compensation value, the sensor compensation function
eliminates a difference between a temperature process value (PV) and an actual
temperature, if any.
(5)Connection of thermocouples compatible w ith JIS, IEC , N BS,
ASTM and DIN Standards
(a) The Q64TCTT(BW) accepts the following thermocouples compatible with the
JIS, IEC, NB S, ASTM an d DI N St an da r d s.
• JIS Standards : R, K, J, S, B, E, T • IEC Standards: R, K, J, S, B, E, T, N
(b) The Q64TCTT(BW) allows you to set the temperature measurement ranges
which meet the operating temperatures of the above thermocouples.
(6)Connection of Pt100 and JPt100 platinum temp er atur e-measur i ng
resistors
The Q64TCTT(BW) allows you to set the temperature measurement ranges
which meet the operating temperatures of the Pt100 and JPt100.
1 - 3 1 - 3
1 GENERAL DESCRIPTION
(7)Choice of fine temperature measurement units a n d v ar i ous contr ol
temperature ranges
The temperature measurement unit of each loop can be set to 1°C or 0.1°C in
Centigrade or to 1°F or 0.1°F in Fahrenheit, enabling you to choose appropriate
resolution for control. Also, the controllable temperature range can be selected
from 0.0 to 400.0°C (when K type thermocouple is used), 0.0 to 3000.0°C (when
R type thermocouple is used) and others, enabling you to make adequate setting
for the object to be con t roll e d.
(8)E2PROM for backing up set values
The set values in buffer memory can be stored into E2PROM for data backup.
Using the test function of GX Developer to write data directly to the buffer
memory, what i s requi r ed in a sequ en ce prog r a m is "LD
minimum.
(9)Detection of disconnection
The Q64TCTTBW and Q64TCRTBW can detect the disconnection of a heater.
MELSEC-Q
" + "OUT Yn1" at the
(10) Utility package for ease of setting
The optional utility package (GX Configurator-TC) is available.
Though you are not required to use the utility package, it allows initial and
automatic refresh settings to be made on the screen, reducing sequence
programs and also enabling you to check the setting and operating states and
execute auto t uni ng ea sily .
1 - 4 1 - 4
1 GENERAL DESCRIPTION
v
1.2 The PID Control System
(1)The PID control system
Figure 1.3 indicates the system configuration when performing PID control.
MELSEC-Q
Q64TC
Set value data
storage
process value
data storage
SV
PV
PID operation
MV
Manipulated value
data storage
Fig. 1.3 The PID control system
(2)PID control procedure
The PID control is performed in the procedure shown in Figure 1.4 below:
Read the PV value
Perform PID
operation
Output MV
Import a signal from the temperature sensor and write
it to the process value storage area as a PV value.
Perform PID operation using the SV/PV values in the
set value/process value storage area.
Convert MV value obtained by the PID operation
to transistor -output on time and output it.
Control
object
Sensor
Fig. 1.4 PID cont r ol p roced u re
(3)PID control (simplified two-level response selection)
In general, when the P, I, and D constants to improve the "response to the
setting" are set, the "response to the disturbance" degrades by the PID control.
Conversely, when the P, I, and D constants to improve the "response to the
disturbance" are set, the "response to the setting" degrades by the PID control.
In the PID control (simplified two-level response selection) of this module, "fast",
"normal", or "slow" can be selected for the "response to the setting" while the P, I,
and D constants for better "response for the disturbance" are selected.
Fast
Slow
Normal
Set
value
(SV)
Response to the disturbance
Set
alue
(SV)
Response to the change of the set value
Fig. 1.5 simplified tw o-l evel re spo nse sele ct ion
1 - 5 1 - 5
1 GENERAL DESCRIPTION
M
1.3 About the PID Operation
The Q64TC can perform PID control in process-value incomplete differentiation.
1.3.1 Operation method and formula
The PID control in process-value incomplete differentiation is an operation method
which puts the first-order delay filter as the input for derivative control action, and
performs PID operation with the error value (E) after deleting the high-frequency noise
component.
(1)The algorithm of the PID control in process-value incomplete
differentiation is shown in Figur e 1.6.
MELSEC-Q
Disturbance D
Q64TC
SV(Set value)
Kp
: Proportional gain
Ti
: Integral time
T
D
: Derivative time
Control response
parameters
Slow
Normal control
Fast
: Derivative gain
S
: Laplace transform conversion
+
-
Kp(1+ )
1
Ti s
-
Kp T
1+ T
+
MV
s
D
D S
PV(Process value)
Fig. 1.6 Algorithm of PID control in process-value incomplete differentiation
(2)The formula used for Q64TC is shown bel ow:
T
D
(PV
- PV n) -
V n = MV
n-1
+
+
T
n-1
D
: Sampling period
MV : Incomple te de riv ative ou tp ut
PV: Process value
T
D
: Derivative time
: Derivative gain
MV
T
n-1
D
Control object
G(s)
1 - 6 1 - 6
1 GENERAL DESCRIPTION
1.3.2 The Q64TC actions
The Q64TC performs PID operations in reverse action and forward action.
(1)Reverse action
In a reverse action, the process value (PV) increases toward the set value (SV)
as the manipulation value (MV) increases.
The reverse action is effective for heat control.
(2)Forward action
In a forward action, the process value (PV) decreases toward the set value (SV)
as the manipulation value (MV) increases.
The forward action is effective for cooler control.
MELSEC-Q
Temperature
Process value
Reverse action
(when used for heat control)
Set
value
Time
Temperature
Process value
Forward action
(when used for cooling control)
Fig. 1.7 Process control example in reverse action and forward action
Set
value
Time
1 - 7 1 - 7
1 GENERAL DESCRIPTION
1.3.3 Proportional action (P-action)
(1) The proportional action is an action to obtain the manipulation value proportional to
the deviation (difference between set value and process value).
(2) With the proportional action, the relationship between the changes in the deviation
and manipulation value can be expressed in the following formula:
K
EMV =
P
where Kp is a proportional constant and is called the proportional gain.
(3) The proportional action for the step response when the error value is constant is
shown in Figure 1.8.
(4) The manipulation value changes between -5.0% and 105.0 %. As the Kp
increases, the manipulation value for the same error value becomes larger, and the
corrective action becomes stron ger .
MELSEC-Q
(5) The proportional action will generate an offset (remaining deflection).
Deviation
Time
Manipulated
value
Time
E
K
E
P
Fig. 1.8 Propo r ti on al action for step respon se
1 - 8 1 - 8
1 GENERAL DESCRIPTION
1.3.4 Integral action (I-action)
(1) The integral action is an action which continuously changes the manipulation value
to eliminate the deviation when there is an deviation.
The offset produced by the proportional action can be eliminated.
(2) In the integral action, the time from the deviation occurrence until the manipulation
value of the integral action becomes that of the proportional control action is called
the integral time, and is indicated by Ti.
(3) The integral action for the step response when the error value is constant is shown
in Figure 1.9.
(4) The integral action is used as a PI action in combination with the proportional
action, or PID action in combination with the proportional and derivative actions.
The integral action cannot be used alone.
MELSEC-Q
Time
K
P
Time
E
Manipulated value of the Proportional
action + Integral action
Manipulated value of the Integral
action
E
Manipulated value of the Proportional
action
Deviation
Manipulated
value
T
I
Fig. 1.9 Integ r al acti on fo r st ep re spo nse
1 - 9 1 - 9
1 GENERAL DESCRIPTION
1.3.5 Derivative action (D-action)
(1) The derivative action adds the manipulation value proportional to the change speed
to eliminate error when an deviation occurs.
The derivative control action can prevent the control target from changing
significantly due to disturbance.
(2) In the derivative action, the time from the deviation occurrence until the
manipulation value of the derivative action becomes that of the proportional action
is called the der iva ti ve ti me, and is in di cated by T
(3) The derivative action for the step response when the deviation is constant is shown
in Figure 1.10.
(4) The derivative action is used as a PD action in combination with the proportional
action, or PID action in combination with the proportional and integral actions.
The derivative action cannot be used alone.
MELSEC-Q
D
.
Time
Time
E
K
E
P
Manipulated value of the Proportional
action
Deviation
Manipulated
value
T
D
Fig. 1.10 Deri va tiv e a ction for step response
1 - 10 1 - 10
1 GENERAL DESCRIPTION
n
1.3.6 PID action
(1) The PID action performs control using the manipulation value obtained by merging
proportional action, integral action and derivative action.
(2) The PID action fo r th e st ep re spon se w hen th e de viation is constant is shown in
Figure 1.11.
MELSEC-Q
Deviation
Time
PI action
Manipulated
value
D action
Fig. 1.11 PID a ctio n fo r st ep re sp on se
PID actio
I action
P action
Time
1 - 11 1 - 11
1 GENERAL DESCRIPTION
1.4 Functions Added to Function Version B and Later
(1) Functions added to function version B Q64TC
MELSEC-Q
FunctionFunction summary
Multiple PLC system
support
Auto tuning mode selection
Control from any desired PLC CPU by a multiple
PLC system.
Auto tuning mode selection corresponding to the
response characteristics of the control object.
Reference
section
—
Section 3.5.47
(2) Functions added to function version C Q64TC
FunctionFunction summary
Online module changeChange the module without stopping the system.Chapter 7
Reference
section
POINT
See Section 2.2 for the confirmation methods of the function version.
1 - 12 1 - 12
2 SYSTEM CONFIGURATION
2 SYSTEM CONFIGURATION
This chapter explains the system configuration of the Q64TC.
2.1 Applicable Systems
MELSEC-Q
(1)Applicable modules and numbers o f Q64TC mod ules that m ay be
mounted
The following table indicates the CPU modules and network modules (for remote
I/O stations) which accept the Q64TC, and the number of Q64TC modules that
can be mounted.
CPU module
Network module
1 See User's Manual (Function Explanation, Program Fundamentals) for the CPU module to use.
2 See Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O
network).
Applicable module
Q12PHCPU
Q25PHCPU
QJ72LP25-25
QJ72LP25G
QJ71LP25GE
Number of modules that
can be installed
Q00JCPUMaximum 16
Q00CPU
Q01CPU
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
QJ72BR15
Maximum 24
Maximum 64
Maximum 64
Maximum 64
Can be installed in Q mode only
1
(
)
MELSECNET/H Remote I/O
station (
Remarks
(
(
2
)
1
)
1
)
2
(2)Base unit which the conversion can be installed
The Q64TC can be mounted in any I/O slot(
However, combining it with other mounted modules may result in a power supply
shortage depending on the number of modules to be mounted. Thus, always
take into consideration the power supply capacity when mounting modules.
Within the I/O point ranges of the CPU modules and network modules (for
3
remote I/O stations)
) of a base unit.
3
(3) Compatibility with a multiple PLC system
First read the QCPU (Q mode) User's Manual (Function Explanation, Program
Fundamentals) if the Q64TC is used with a multiple PLC system.
(a) Compatible Q64TC
Use a Q64TC with function version B or higher if using the module in a
multiple PLC system.
(b) Intelligent function module parameters
Perform PLC write of the intelligent function module parameters to the
control PLC of the Q64TC only.
2 - 1 2 - 1
2 SYSTEM CONFIGURATION
(4) Compatibility with online module change
2
(5) Software packages supported
MELSEC-Q
To make an online module change, use the module of function version C or later.
POINT
The products of function version C include the functions of the products function
versions A and B.
Correspondence between systems which use Q64TC and software packages are
as shown below.
The GX Developer is necessary when using a Q64TC.
Software Version
GX Developer
GX Configurator-TC
Single PLC
Q00J/Q00/Q01CPU
Q02/Q02H/Q06H/
Q12H/Q25HCPU
Q12PH/Q25PHCPU
If installed in a MELSECNET/H
remote I/O station
system
Multiple PLC
system
Single PLC
system
Multiple PLC
system
Single PLC
system
Multiple PLC
system
Version 7 or later
Version 8 or later
Version 4 or later
Version 6 or later
Version 7.10L or later
Version 6 or later
Version 1.10L or later
(cannot be used with the
SW0D5C-QTCU-E 30D or
earlier versions).
SW0D5C-QTCU-E 00A or
later
SW0D5C-QTCU-E 30D or
later
Version 1.13P or later
(cannot be used with the
SW0D5C-QTCU-E 30D or
earlier versions).
SW0D5C-QTCU-E 30D or
later
(6)Current sensors
Only the following current sensors of URD, Ltd. are usable with the Q64TCTTBW
and Q64TCRTBW.
• CTL-12-S36-8(0.0 to 100.0A)
• CTL-6-P-H(0.0 to 20.00A) (The conventional model CTL-6-P is also usable.)
2 - 2 2 - 2
2 SYSTEM CONFIGURATION
2.2 How to Check the Function Version and Softw ar e Ver si on
This section describes how to check the function version of the Q64TC and the GX
Configuration-TC software version.
(1) How to check the function version of the Q64TC
(a) To check the version using the "SERIAL column of the rating plate" located
on the side of the module
MELSEC-Q
(b) To check the version using the GX Developer
See Section 8.10 of this manual.
Function version
(2) How to check the GX Configuration-TC software ver si on
The GX Configuration-TC software version can be checked in GX Developer's
"Product information" screen.
[Startup procedure]
GX Developer "Help" Product information
Software version
(In the case of GX Developer Version 7)
2 - 3 2 - 3
2 SYSTEM CONFIGURATION
REMARK
The version indi cat io n for th e GX Confi gu r ato r -TC ha s b een chan ge d as show n
below from the SW0D5C-QTCU-E 30D upgrade product.
Previous productUpgrade and subsequent versions
SW0D5C-QTCU-E 30D
MELSEC-Q
GX Configurator-TC Version 1.10L
2 - 4 2 - 4
3 SPECIFICATIONS
MELSEC-Q
3 SPECIFICATIONS
This chapter provides the performance specifications of the Q64TC, I/O signals
transferred to/from the PLC CPU and the specifications of buffer memory.
For the general specifications of the Q64TC, refer to the User's Manual (hardware) of
the CPU module use d.
3.1 Performance Specifications
3.1.1 Performance specifications of the Q64TC
Table 3.1 Q64TC performance specification list
Specifications
Q64TCTTQ64TCRTQ64TCTTBWQ64TCRTBW
Control outputTransistor output
Number of temperature input points4 channels/module
Sampling period0.5s/4 channels (constant independently of the number of channels used)
Control output period1 to 100s
Input impedance
Input filter0 to 100s (0: Input filter off)
Sensor compensation value setting-50.00 to 50.00%
Operation at sensor input
disconnection
Temperature control systemPID ON/OFF pulse or 2-position control
PID constant
range
Set value setting rangeWithin temperature range set to the used thermocouple/platinum temperature-measuring resistor
Dead band setting range0.1 to 10.0%
Transistor
output
E2PROM write count
Insulation method
Dielectric strength
Insulation re sista n ce
Ambient
temperature:
25°C±5°C
Ambient
temperature:
0 to 55°C
Temperature
measurement
value:
-100°C or more
Temperature
measurement
value:
-150 to -100°C
Temperature
measurement
value:
-200 to -150°C
PID constant settingSetting can be made by auto tuning
Proportional band (P)0.0 to 1000.0% (0: 2-position control)
Integral time (I)1 to 3600s
Derivative time (D)0 to 3600s (set 0 for PI control.)
Between input and grounding : Transformer insulation
Between input and channel: Transformer insulation
Between input and grounding : 500VAC for 1 minute
Between input and channel: 500VAC for 1 minute
Between input and grounding : 500VDC 20M
Between input and channel: 500VDC 20M
Refer to Section 3.1.2.
Full-scale x (±0.3%)
Full-scale x (±0.7%)
————
Within ±3.0°C
1M
Upscale processing
0.1mA or less
ON: 2ms or less, ON OFF: 2ms or l e ss
Max. 100 thousand times
or more
or more
————
3
3 - 1 3 - 1
3 SPECIFICATIONS
Specifications
Q64TCTTQ64TCRTQ64TCTTBWQ64TCRTBW
Heater
disconnection
detection
specifications
Number of input points occupied 2
Connection terminal18-point terminal blockTwo 18-point terminal blocks
Applicable wire size0.3 to 0.75mm
Applicable crimping terminalR1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A
Internal current consumption0.55A0.64A
Weight0.20kg0.30kg
3
Outline dimensions
1: Calculate the accuracy in the following method.
(Accuracy) = (indication accuracy) + (cold junction temperature compensation accuracy)
Example) Accuracy at the input range setting of "38", operating ambient temperature of 35°C and temperature measurement value of
2: When the Q64TCTTBW or Q64TCRTBW is used, the device numbers of the I/O signals increase by 16 points depending on how many
free points the left-hand side slots have.
Hence, as I/O signals are given as indicated below in this manual, read them according to the module used.
Example) When a signal is given as Yn1
3: For the noise immunity, dielectric withstand voltage, insulation resistance and others of the PLC system which uses this module, refer
to the power supply module specifications given in the User's Manual of the CPU module used.
Current sensorRefer to Section 2.1
Input accuracyFull scale x (±1.0%)
Number of alert
Auto-tuning function• The temperature control module automatically sets the optimal PID constants.3.2.1
Forward action/reverse action
selection function
RFB limiter function
Sensor compensation function
Unused channel setting
PID control forced stop• Stops the PID operation for channels that is performing temperature adjustment.3.2.6
Heater disconnection detection
function
Current error detection function
when output is off
Loop disconnection detection
function
Data storage in E2PROM
Alert alarm• Monitors the process value (PV) and alerts the user.3.2.11
Control output setting for CPU
stop error occurrence
Q64TC control status
Online module change• A module change is made without the system being stopped.Chapter 7
• Heat control (reverse action) or cooling control (forward action) can be selected and
controlled.
• Limit the manipulation value overshoot which frequently occurs when the set value (SV)
is changed or control target is changed.
• Reduces the difference between the measured value and actual temperature to zero
when these two are different due to measurement conditions, etc.
• Sets the PID operation for channels that do not perform temperature adjustment to "not
execute."
• Measures the current that flows in the heater main circuit and detects disconnection
when Q64TCTTBW or the Q64TCRTBW is used.
• When the Q64TCTTBW or the Q64TCRTBW is used, this function measures the
current in the heater's main circuit while the transistor's output is off, and checks if there
is a current error when output is off.
• Afunction to detect errors in the control system (control loop) caused by a load (heater)
disconnection, abnormal external operation device (such as magnet relay), or a
thermocouple disconnection.
• By backing up the buffer memory contents to E
can be reduced.
• This function continues/stops temperature adjustment control output at CPU stop error
occurrence.
• The Q64TC can be controlled by the output signal of Q64TC and the settings in the
buffe r memory .
°C°F
Data resolution
0.1
0.1
2
PROM, the load of sequence program
Measurement
temperature range
-300 to 11001
-300.0 to 300.00.1
-300 to 9001
-300.0 to 300.00.1
Data resolution
3.2.2
3.2.3
3.2.4
3.2.5
3.2.7
3.2.8
3.2.9
3.2.10
3.2.12
3.2.13
3 - 4 3 - 4
3 SPECIFICATIONS
3.2.1 Auto tuning function
(1)What is the auto tuning function?
MELSEC-Q
(a) The auto tuning function is designed for the Q64TC to set the optimum PID
constants automatically.
In auto tuning, the PID constants are calculated according to the hunting
cycle and amplitude which take place when a manipulated value turned on/off
alternates be twee n ov e r sho oti ng and un de rsho ot in g a set value .
(b) Setting the fo llowing data enable s aut o tuni ng to be exe cut ed . N ote t ha t sin ce
actual control starts on completion of auto tuning, the other data should be
preset to the values used for actual operation.
When "0" has been set to the proportional band (P), auto tuning is not
executed.
Buffer memory address name
CH.1CH.2CH.3CH.4
Input range20
Set value (SV) setting22
Upper output limiter2A
Lower output limiter2B
Output variation limiter2C
Sensor compensation value
setting
Control output period setting2F
Primary delay digital filter setting30
AUTO/MAN mode switching32
AT bias35
Forward/reverse action setting36
Auto tuning mode selectionB8
Addresses (Hexadecimal)
2D
H
H
H
H
H
H
H
H
H
H
H
H
40
42
4A
4B
4C
4D
4F
50
52
55
56
B9
H
H
H
H
H
H
H
H
H
H
H
H
60
62
6A
6B
6C
6D
6F
70
72
75
76
BA
H
H
H
H
H
H
H
H
H
H
H
H
80
82
8A
8B
8C
8D
8F
90
92
95
96
BB
H
H
H
H
H
H
H
H
H
H
H
H
(c) On completion of auto tuning, calculated values are set to the following buffer
memory addresses.
Buffer memory address name
CH.1CH.2CH.3CH.4
Proportional band (P) setting23
Integral time (I) setting24
Derivative time (D) setting25
Loop disconnection detection
judgment time
: As the loop disconnection detection judgment time, a value tw ice greater than the
calculated integral time is set. Howev er, the loop disconnectio n detecti on
judgment time remains unchanged from 0 when it is 0 at an auto tuni ng start.
Addresses (Hexadecimal)
3B
H
H
H
H
43
44
45
5B
H
H
H
H
63
64
65
7B
H
H
H
H
83
84
85
9B
H
H
H
H
3 - 5 3 - 5
3 SPECIFICATIONS
(2)Execution of auto tuning
MELSEC-Q
(a) Auto tuning is performed in the following procedure.
Q64TC data setting
Operation mode setting
Auto tuning start
Auto tuning in progress
Auto tuning completion
(PID constants set)
Temperature control using
PID constants set
Set to the buffer memory addresses
indicated in (1), (b).
Turn on the setting/operation mode
command (Yn1).
Confirm that the setting/operation
mode status (Xn1) is on.
Turn on the auto tuning command
(Yn4, Yn5, Yn6, Yn7).
The auto tuning status flag
(Xn4, Xn5, Xn6, Xn7) turns on.
The auto tuning executing flag
(Xn4, Xn5, Xn6, Xn7) turns off and
the calculated values are set to
the buffer memo ry addresses
indicated in (1), (c).
POINT
After powering off the PLC CPU, you can use the set PID constants in the following
method.
• Write the values directly to the buffer memory using the sequence program.
• Store the PID constants into E
PLC CPU.
• Use the initial settings of the GX Configurator-TC.
2
PROM and transfer them when powering on the
3 - 6 3 - 6
3 SPECIFICATIONS
Process value (PV)
MELSEC-Q
(b) Auto tuning operation
Auto tuning performs operation as shown below.
1) Auto tuning output is provided.
2) Data collection starts when the process value returns to the set value after
the first ove r shoot an d un de r sho o t .
3) After data collection, auto tuning ends when PID constants and loop
disconnection detection judgment time are set.
The first overshoot and
undershoot are ignored.
End of auto tuning
(Temperature set value)
Start of auto tuning
Yn4,Yn5,Yn6,Yn7
Xn4,Xn5,Xn6,Xn7
Set value (SV)
OFF
OFF
Data collection
Temperature
Auto tuning in execution
ON
ON
(c) Precautions for auto tuning
The following indicate the conditions under which auto tuning will result in
abnormal termination.
1) The buffer memory addresses of the corresponding channels have been
changed.
2) The forced PID control stop command (YnC to YnF) was turned on.
3) The setting/operation mode command (Yn1) was turned off. (Except when
the PID continuation flag (buffer memory address: A9H) is "Continue")
4) Switched to the Manual mode (MAN).
5) A hardware error occurred.
6) The temperature process value (PV) fell out of the input range.
Time
control
3 - 7 3 - 7
3 SPECIFICATIONS
(3)Operation at termination of auto tuni ng
(4)Adjustment after auto tuning
MELSEC-Q
(a) Operation at no r mal ter min a tion
• The auto tuning status flag (Xn4 to Xn7) turns off.
• The PID constants are set.
• The loop disconnection detection judgment time (buffer memory addresses:
3B
H
, 5BH, 7BH, 9BH) is set. (If the loop disconnection detection judgment
time is 0 at the start of auto tuning, it remains unchanged from 0.)
(b) Operation at abnormal termination
• The auto tuning status flag (Xn4 to Xn7) turns off.
• The PID constants are not set.
(a) Specific readjustment is not needed for the PID constants calculated by auto
tuning.
(b) Use the control response parameters (buffer memory addresses: 31
H
71
, 91H) to change the control response for the PID constants calculated by
H
, 51H,
auto tuning.
REMARK
1) The time between the start and completion of auto tuning depends on the object
to be controlled.
2) You can confirm that auto tuning has been completed by checking that the auto
tuning status flag (Xn4, Xn5, Xn6, Xn7) has turned from on to off.
3) When the automatic backup setting (3F
tuning start to be made valid after auto tuning of the PID constants, the PID
constants and loop disconnection detection judgment time are automatically
backed up by E
2
PROM on completion of auto tuning.
H
, 5FH, 7FH, 9FH) is preset at an auto
3 - 8 3 - 8
3 SPECIFICATIONS
3.2.2 Reverse/Forward action select function
With the Q64TC, "reverse action" or "forward action" can be selected to perform the
PID operations.
(1)Q64TC default
The default is set at "reverse action" for Q64TC.
When performing the PID operations with the "forward action," set to the forward
action in the reverse/forward action selection buffer memory(36
H
).
96
(2)Reverse/forward action control details
(a) Reverse action : Used for heating control to increase temperature.
(b) Forward action : Used for cooling control to decrease temperature.
3.2.3 RFB limiter function
MELSEC-Q
H
,56H,76H, and
(1)RFB(Reset feed back) limiter function
The RFB limiter function limits the PID operation result (manipulated value : MV)
not to exceed the valid range by the integral control action when an error
continues for a long time.
With the RFB limiter function, if the PID operation result exceeds the upper/lower
output limiter value, the amount exceeded is fed back to the integral value and
the PID operation result is kept at the limit value.
3.2.4 Sensor compensation function
(1)Sensor compensation function
The sensor compensation function compensates the difference between the
measured temperature and actual temperature caused by measurement
conditions.
(2)Sensor compensation value setting
When there is a difference between the measured temperature and actual
temperature, the full-scale percentage (-50.00 to 50.00%) is set in the buffer
memory for sensor compensation value setting (2D
sensor compensation value.
For example, when the input range is at -200°C to 200°C and there is a 2°C
error, the full-scale is 400°C(200°C-(-200°C)=400°C).
Therefore, 2/400 x 100 = 0.5% is set.("50" is set in the buffer memory.)
H
, 4DH, 6DH and 8DH) as the
3 - 9 3 - 9
3 SPECIFICATIONS
3.2.5 Unused channel setting
(1)Channels where temperature sensors are not connected
The Q64TC performs upscale processing on the channels where temperature
sensors (thermocouples/platinum temperature-measuring resistors) are not
connected.
Hence, when a temperature sensor is not connected to the channel which will not
exercise temperature control, the PV value is judged as higher than the
temperature measurement range of the input range, and the "ALM" LED is lit by
alert processing.
(2)Unused channel setting
(a) To make unused channel setting, write "1" to the unused channel setting
(b) After the unused channel setting has been made, no alert will occur at the
MELSEC-Q
buff er memor y.
channel with no temperature sensor connected and the "ALM" LED will not
be lit.
The sampling period remains unchanged if the unused channel setting is
performed.
3.2.6 Forced PID control stop
(1)Forced PID control stop
Forced PID control stop is a function to stop PID operations temporarily from the
PLC CPU.
The action to be taken by the Q64TC at a PID operation stop depends on the
setting of the stop mode setting buffer memory (21
(2)Executing forced PID control stop
To execute a forced PID control stop, turn on the forced PID control stop
command (YnC to YnF).
At this time, th e mani pu la te d val ue sto r age bu ffe r me mory (D
50 (-5.0%).
(3)Canceling forced PID control stop
When the forced PID control stop command is turned off, a forced PID control
stop is canceled and PID operations are resumed at the manipulated value which
was output during the forced PID control stop.
POINT
Setting the PLC CPU to the STOP status turns off the forced PID control stop
command, "canceling the forced PID control stop".
H
, 41H, 61H, 81H).
H
to 10H) value is -
3 - 10 3 - 10
3 SPECIFICATIONS
3.2.7 Heater disconnection detection function (supported only by Q64TCTTBW,
Q64TCRTBW)
(1)Heater disconnection detection function
(a) This is a function to check if there is a heater wire breakage using the
standard heater current value (load current value detected by the current
sensor (CT)), when the transistor output is on.
(b) The heater disconnection detection function compares the current values of
standard heater and heater disconnection alert, and determines that there is a
heater wire breakage when the current value of standard heater is below that
of heater disconnection alert.
However, when the transistor turned-on time is less than 0.5 seconds, the
heater disconnection detection is not performed.
(2)Heater disconnection compensation function
(a) Heater disconnection compensation
When the heater voltage drops, the heater current decreases as well.
The Q64TCTTBW, Q64TCRTBW heater disconnection detection measures
the heater current and determines the heater disconnection.
Therefore, when the heater voltage drops, there are possibilities that a false
alarm may be set due to the voltage change.
Therefore, the Q64TCTTBW, Q64TCRTBW compensates for a drop in heater
current (heater breakage compensation) so that the drop in heater current
does not activate the break detection.
MELSEC-Q
(b) Heater disconnection compensation method
The heater disconnection compensation calculates "the heater current for
each channel" - "standard current," and the largest positive value is set as the
compensation value.
When there is no positive values, the value with the smallest negative value is
used as the compensation value.
The heater current for each channel is compensated with the compensation
value and a heater disconnection is detected when the compensated value
exceeds the specified heater disconnection detection setting value.
Example 1: When the difference from the standard current at each channel is:
Channel 1: -2 %, Cha nn el 2: 5%, Channel 3: -1% , Cha nn el 4: - 1 7%, the
compensation value becomes 5%.
The heater disconnection detection is performed from the values after a 5%
compensation: Channel 1: -7%, Channel 2: 0%, Channel 3: -6%, Channel 4: 22%.
Thus, when the heater disconnection detection setting value is at 80%, only
channel 4 is detected as disconnected.
Heater
Channel No.
1-2% -7%No
25% 0%No
3-1% -6%No
4
disconnection
detection setting
value
80%
Difference from the
standard current
-17%
Compensation
value
5%
Difference from the
standard current
after compensation
-22%Yes
Disconnected
3 - 11 3 - 11
3 SPECIFICATIONS
MELSEC-Q
Example 2: The difference from the standard current at each station is: Channel
1: -16%, Channel 2: -17 %, Channel 3: -22%, Cha nnel 4: -1 9%, the compensation
value b e come s -16 %.
The heater disconnection det ection i s perfor med from the v alues a fter a - 16%
compensation: Channel 1: 0%, Channel 2: -1%, Channel 3: -6 %, Channel 4: -3%.
Thus, when the heater di sconnection det ection setting value is at 80%, none of
the channels are detected a s disconnected.
Heater
Channel No.
1-16%0No
2-17%-1%No
3-22%-6%No
4
disconnection
detection setting
value
80%
Difference from the
standard current
-19%
Compensation
value
-16%
Difference from the
standard current
after compensation
-3%No
Disconnected
(c) Restrictions
• The heater-disconnection compensation function will not work if only one
channel is used.
• The heater-disconnection compensation function will not work if only one
channel is used to keep the heater on while the others are used to keep it
off.
The module may detect a disconnection even when the heater is not
disconnected.
• The heater disconnection detection compensation value is up to 20%.
Therefore, when there is a voltage drop by more than 40%, a disconnection
is detected even with a 20% compensation.
3.2.8 Output off-time current error detection function (av ail able for Q64TC TTBW and
Q64TCRTBW only)
(1) Using the reference heater current value (load current value detected by the
current sensor (CT)), this function checks for a transistor output off-time current
error when the transistor output is off.
(2) The transistor output off-time current error detection function compares the
reference heater current value and the current value of the heater disconnection
alert, and judges it as an output off-time current error if the reference heater current
value is higher than the current value of the output off-time current alert.
Note that output off-time current error detection will not be made if the transistor
output off period is within 0.5 seconds.
3.2.9 Loop disconnection detection function
The loop disconnection detection function detects errors in the control system (control
loop) caused by a load (heater) disconnection, external operation device (e.g.
magnetic relay) fault, input disconnection and others.
When the PID operation value has reached 100% or 0%, this function starts monitoring
the variation of the process value per loop disconnection detection judgment time to
detect a heater or input disconnection.
(1) When the heater is disconnected, when the input is disconnected or shorted, or
when the external operation device contact does not turn on, it is judged as an
error since the temperature will not rise despite the control output provided.
In this case, an alert is output if a temperature rise of 2°C or more is not observed
within the preset loop disconnection detection judgment time after the control
output is provided 100%.
3 - 12 3 - 12
3 SPECIFICATIONS
(2) When the input is disconnected or when the external operation device contact is
MELSEC-Q
welded, it is judged as an error since the temperature will rise though the control
output is not provided.
In this case, an alert is output if a temperature fall of 2°C or more is not observed
within the preset loop disconnection detection judgment time after the control
output has dropped to 0%.
(In either case, inverse operation will be performed for forward action: cooling
control.)
POINT
(1) When not using the loop disconnection detection function, set the loop
disconnection detection judgment time to "0".
(2) Setting the loop disconnection detection dead band will not cause a loop
disconnection if there is no temperature variation of 2°C or more when the
control output is provided 100% or 0% at the set value. (Refer to Section
3.5.32.)
3.2.10 Data storage on E2PROM
(1)Data storage on E2PROM
(a) The Q64TC buffer memory data can be stored onto E2PROM for backup.
The whole write-enabled area of the buffer memory can be backed up. Refer
to Section 3.5 for details of the buffer memory.
Write to E2PROM can be used to back up the PID constants set by auto
tuning and the data written directly to the buffer memory using a peripheral
device.
Write to E
H
H
AF
B0
B5
H
H
H
H
H
H
—————
Q64TCTTBW,
Q64TCRTBW only
A4H to AA
108H to 11F
2
PROM eliminates the program used to set data to the Q64TC.
2
(b) The backed up data is transferred from E
PROM to buffer me mo ry when the
PLC CPU is pow e red on (pow e r i s switched on) or reset .
Hence, temperature control can be exercised without data being written when
the PLC CPU is powered on or reset.
3 - 13 3 - 13
3 SPECIFICATIONS
(2)Writing data to E2PROM
MELSEC-Q
(a) When writing data to E2PROM, turn on the E2PROM backup command
(Yn8).
• The E
• The E
(b) Make changes to buffer memory when the E
off.
PLC CPU
2
PROM write completion flag (Xn8) turns on at completion of data
write to E
2
PROM.
2
PROM write fai lu r e fl ag ( XnA ) tu r n s on if w rit e of da t a to E2PROM is
not completed normally.
1) Yn8 : ON
(Write command)
3) Xn8 : ON
(completed)
OS
Buffer
memory
data
2
PROM write completion flag is
Q64TC
2
E PROM
2) Write
Read
At power-on
or reset
(3) Reading data from E2PROM
E2PROM data read occurs under either of the following conditions.
• When the PLC CPU is powered on or reset.
• When the E
on. Note tha t the re ad da ta ar e on ly the PID con st an ts and loop disconnection
detection judgment time of the corresponding channel.
(1) The alert alarm is a function which sets the system in an alert status when the
MELSEC-Q
process value (PV) or deviation reaches the alert set value. It is used to turn on
the device's hazard signal or operate the safety device.
The alert alarm is classified as follows:
1) Upper limit input alert
When the process value (PV) is equal to or greater
than the alert set value, the system is put in an alert
status.
Process value (PV)
lert set value
Alert status
Process value (PV)
(b) Deviation alerts
1) Upper limit deviation alert
When the deviation [process value (PV) - set value (SV)] is equal to or
greater than the alert set value, the system is put in an alert status.
[When alert set value is positive]
Process value (PV)
Process value (PV)
2) Lower limit input alert
When the process value (PV) is equal to or less
than the alert set value, the system is put in an
alert status.
Process value (PV)
Alert set value
Time
Alert status
Process value (PV)
Process value (PV)
Time
Non-alert statusAlert status
[When alert set value is negative]
Process value (PV)
Time
Alert set value
Temperature
set value (SV)
Alert status
Temperature
set value (SV)
Alert set value
Time
Alert status
Non-alert statusAlert status
3 - 15 3 - 15
3 SPECIFICATIONS
MELSEC-Q
2) Lower limit deviation alert
When the deviation [process value (PV) - set value (SV)] is equal to or less
than the alert set value, the system is put in an alert status.
Process value (PV)
Alert set value
Temperature
set value (SV)
Alert status
[When alert set value is positive]
Process value (PV)
3) Upper/lower limit deviation alert
When the deviation [process value (PV) - set value (SV)] is equal to or
greater than the alert set value, the system is put in an alert status.
Process value (PV)
Alert set value
Temperature
set value (SV)
Alert set value
Time
[When alert set value is negative]
Process value (PV)
Process value (PV)
Temperature
set value (SV)
Alert set value
Time
Alert status
Non-a lert sta tusAlert status
Process value (PV)
Alert status
4) Within-range alert
When the deviation [process value (PV) - set value (SV)] is equal to or less
than the alert set value, the system is put in an alert status.
Process value (PV)
Alert set value
Temperature
set value (SV)
Alert set value
Alert status
Process value (PV)
Time
Time
Non-alert status
Alert status
Non-alert status
Alert status
3 - 16 3 - 16
3 SPECIFICATIONS
(2) The Q64TC allows the alert alarm in (1) to be set with the addition of an alert dead
[When alert dead band value is not set]
Process value (PV)
MELSEC-Q
band, alert delay count or wait/re-wait.
The following t abl e indi ca te s th e ale rt ala rms w hi ch can be used wi th th e ad di tio n
of alert dead band, alert delay count and wait/re-wait.
When the process value (PV)/deviation is close to the alert set value, the alert
status may alterna te w i th th e non- ale rt statu s du e to input instabi lity o r th e l i ke.
Setting the alert dead band prevents the alert status and non-alert status from
alternating with each other due to input instability or the like when the process
value (PV)/deviation is near the alert set value.
Example: When the dead band value is set to the upper limit input alert, the
system is placed in the alert status when the upper limit of the input
rises to or above the alert set value. The system is put in the nonalert status when the upper limit falls below the alert dead band.
Process value (PV)
Dead band
setting
Process value (PV)
Alert delay
count
[When alert dead band value is set]
WaitRe-wait
————————
Process value (PV)
————
Alert set value
Alert status
Temperature set value (SV)
(b) Alert delay count setting
Process value (PV)
Alert set value
Input sampling
Alert status
Alert set value
Time
Alert status
Dead band
Time
The system is set in the alert status when the process value (PV) that has
reached the alert set value remains in the alert range until the sampling count
becomes equal to or greater than the preset number of alert delays.
Example: When the number of alert delays set to the input upper limit alert is
5, the system is not placed in the alert status if the sampling count
is 4 or less.
Process value (PV)
Time
3 times5 times
3 - 17 3 - 17
3 SPECIFICATIONS
)
MELSEC-Q
(c) Wait alert
Choosing the wait alert ignores the alert status if the process value
(PV)/deviation is in that status when the setting mode is changed to the
operation mode, and makes the alert function invalid until the process value
comes out of the alert status once.
Example: Selecting the lower limit deviation alert with wait makes the alert
function invalid until the process value exceeds the alert set value.
Process value (PV)
Temperature
set value (SV)
Alert set valu e
Alert status
[Lower deviation alert]
Process value (PV)
Time
Non-a lert sta tusAlert status
Temperature
set value (SV)
Alert set value
Alert status
[Lower deviation alert with wait]
Process value (PV)
Wait operation region
Process value (PV)
Time
POINT
When the system has reached the non-alert status even once after an alert
judgment start following the setting of the alert mode, the alert function with wait will
be invalid if you choose the mode with wait.
(d) Re-wait alert
The re-wait alert is a wait alert-based feature which has the additional
function to make t h e ale rt fu ncti on inva li d ag ai n wh en th e se t val ue (SV ) i s
changed.
For set value changing control, choosing the re-wait alert avoids the alarm
status reached when the set value is changed.
Example: If the process value (PV) is at the position as shown below before
the setting i s chan ge d, cha n gi ng th e te mpe ra t u re set val ue (SV) for
deviation alert will put the process value in the alert region and turn
on the alert. To prevent this, the function makes the alert wait
operation valid and the alert output to wait.
Process value (PV)
Before temperature
set value (SV) change
After temperature
set value (SV) change
Alert region
Alert set valueTemperature set value (SV)
Process value (PV)
Alert region
Alert set valueTemperature set value (SV
Temperature
set value (SV) change
3 - 18 3 - 18
3 SPECIFICATIONS
(3) The Q64TC allows four different alerts (alert alarms 1 to 4) to be selected and
(4) Set the alert set value, alert dead band value and alert delay count at the following
MELSEC-Q
used from among the alert alarms, wait alert alarm and re-wait alert alarm.
Set the alert alarms used as alert alarms 1 to 4 at the following buffer memory
addresses:
• Alert alarm 1: C0
• Alert alarm 2: D0H to D3
buffer memory addresses:
H
to C3
H
• Alert alarm 3: E0H to E3
H
• Alert alarm 4: F0H to F3
H
H
Channel No.
126
246
366
486
Alert set valueAlert dead band v alueAlert delay count
H
to 29
H
to 49
H
to 69
H
to 89
Buffer memory addresses
H
H
H
H
3.2.12 Control output setting at CPU stop error occurr ence
(1) You can set the Q64TC control output (HOLD/CLEAR) to be provided when the
PLC CPU has generated a stop error.
(2) To make this setting, use the intelligent function module switch setting on GX
Developer.
• CLEAR : Stops the PID control, temperature judgement and alert judgement
functions and turns off external outputs.
• HOLD: Holds the control status prior to a PLC CPU stop. For example, when
PID control was exercised before a PLC CPU stop, PID control is
continued if the PLC CPU stops.
Refer to Section 4.5 for details of the setting method.
A4
H
A5
H
3 - 19 3 - 19
3 SPECIFICATIONS
MELSEC-Q
3.2.13 Q64TC control status controlling output signal and buffer memory settings and control
status
The Q64TC has the output signals (Y), buffer memory and intelligent function module
switch which set its control status.
The control status of the Q64TC is governed as indicated below by the settings of the
output signals, buffer memory and intelligent function module switch.
(1)Intelligent function module switch setting
Output setting for CPU stop error (refer to Section 4.5)
Intelligent function module switch
If a CPU stop error occurs at the setting of "CLEAR"———
Other than above
PID contro l
(2)Unused channel setting
Unused channel setting (refer to Section 3.5.33)
3DH, 5DH, 7DH, 9D
Unused———
Used
H
PID contro l
(3)Other settings
Setting/operation
mode command
(refer to Section 3.4)
Yn1, Xn1A9
1)
Setting mode
(at power-on)
2)
Operation mode
(during operation)
3)
Setting mode
(after operation)
PID continuation flag
(refer to Section 3.5.41)
H
Stop/continueOFF/ON
Stop/continue
StopOFF/ON
Continue
: The settings of the setting/operation mode command will be explained in the following three different modes.
Forced PID control
stop command
(refer to Section 3.4.3)
YnC to YnF21H, 41H, 61H, 81
OFFStop/monitor/alert
ON
OFFStop/monitor/alert
ON
Stop mode setting
(refer to Section 3.5.13)
PID contro l
H
Stop———
Monitor——
Alert—
Stop———
Monitor——
Alert—
Stop———
Monitor——
Alert—
Stop———
Monitor——
Alert—
Control status
Temperature
judgment
In accordance with control
status of other setting items
: Executed, —: Not executed
Control status
Temperature
judgment
In accordance with control
status of other setting items
: Executed, —: Not executed
Control status
Temperature
judgment
: Executed, —: Not executed
Alert
judgment
Alert
judgment
Alert
judgment
ON
Setting/operation
mode command
OFF
1) Setting mode
2) Operation
mode
3) Setting mode
3 - 20 3 - 20
3 SPECIFICATIONS
3.3 Sampling Period and Control Output Peri od
(1) Sampling period
(a) The Q64TC performs PID operations in order of CH1, CH2, CH3, CH4, CH1,
CH2 .....
The time from when PID operation is started on the current channel (CHn)
until PID ope rati on is re sta rt ed on th e cu rr en t chan nel (CHn) is called a
sampling period.
(b) The sampling period is 0.5 seconds regardless of the number of channels
used.
Since error check and other processings are also performed on unused
channels, the sampling period will not change if you make unused channel
setting.
MELSEC-Q
CH1 PID
operation
CH2 PID
operation
0.5 seconds (sampling period)
CH3 PID
operation
0.5 seconds (sampling period)
CH4 PID
operation
CH1 PID
operation
CH2 PID
operation
(2)Control output period
(a) The control output period indicates the ON/OFF cycle of transistor output.
OFF
Transistor output
The manipulated value (MV) represents the ON time of this control output
period as a percentage. (Refer to Section 3.5.6)
(b) Set the control output period to the control output period setting buffer
memory (2F
H
ONON
Control output periodControl output period
, 4FH, 6FH, 8FH) in the range 1 to 100s.
OFF
3 - 21 3 - 21
3 SPECIFICATIONS
3.4 I/O Signals Transferred to/from the PLC CPU
This section explains the allocation and applications of the Q64TC I/O signals.
3.4.1 I/O signal list
(1) The Q64TC uses 16 input points and 16 output points to transfer signals to/from
the PLC CPU.
(2) Table 3.4 lists the I/O signals used by the Q64TC.
Inputs (X) mean the signals from the Q64TC to the PLC CPU and outputs (Y) the
signals from the PLC CPU to the Q64TC.
(3) The I/O signals (X, Y) indicated in this manual assume that the module is loaded
on the I/O slot 0 of the main base unit.
If the Q64TC is mou nt ed on o th e r tha n th e I/ O slot 0, ch ange th e I/ O signa l s fo r
those of the slot where the module is mounted.
MELSEC-Q
(4) When the Q64TCTTBW or Q64TCRTBW is used, the device numbers of the I/O
signals increa se by 16 po int s d ep en din g on how many free poi n t s the le ft -h and
side slots have.
Hence, as I/O signals are given as indicated below in this manual, read them
according to the module used.
Example) When a signal is given as Yn1
When Q64TCTT or Q64TCRT is used: Y1
When Q64TCTTBW or Q64TCRTBW is used: Y11
Table 3.4 I/O signal list
Input signal (Signal direction: Q64TC PLC CPU)Output signal (Signal direction: Q64TC PLC CPU)
Device No.Signal nameDevice No.Signal name
Xn0Module ready flagYn0Reserved
Xn1Setting/operation mode statusYn1Setting/operation mode command
Xn2Write error flagYn2Error reset command
Xn3Hardware error flagYn3R eserved
Xn4CH1 auto tuning statusYn4CH1 auto tuning com mand
Xn5CH2 auto tuning statusYn5CH2 auto tuning com mand
Xn6CH3 auto tuning statusYn6CH3 auto tuning com mand
Xn7CH4 auto tuning statusYn7CH4 auto tuning com mand
Xn8
Xn9Default value write completion flagYn9Default setting registration command
XnA
XnBSetting change complet ion flagYnBSetting change comm and
XnCCH1 alert occurrence flagYnCCH1 forced PID control stop command
XnDCH2 alert occurrence flagYnDCH2 forced PID control stop command
XnECH3 alert occurrence flagYnECH3 forced PID control stop command
XnFCH4 alert occurrence flagYnFCH4 forced PID control stop command
2
PROM write completion flag
E
2
PROM write failure flag
E
Yn8
YnAReserved
E2PROM backup command
POINT
We cannot guarantee the functions of the Q64TC if any of the reserved areas is
turned on/off in a sequence program.
3 - 22 3 - 22
3 SPECIFICATIONS
3.4.2 Input signal functions
(1) Module ready flag (Xn0)
(a) This signal turns on as soon as the Q64TC is ready when the PLC CPU is
(b) Read/write of Q64TC buffer memory data from the PLC CPU is performed
MELSEC-Q
powered on or reset.
when the temperature control module ready flag is on.
Write command
X1
TOP H0 H22 K100 K1
Used as buffer memory read/write interlock.
(c) This signal turns off on detection of a watchdog timer error. The Q64TC stops
temperature control operation and turns off the output.
(2)Setting/operation mode status (Xn1)
This signal turns on in the operation mode and turns off in the setting mode.
Do not change the set value during mode shift processing.
Yn1
Xn1
Setting modeOperation modeSetting mode
During mode
shift processing
(3)Write error flag (Xn2)
This signal turns on at write error occurrence.
A write error occurs under any of the following conditions.
• When data is set to the reserved area.
• When a setting change made to the area write-enabled in the setting mode only
is made in the operation mode.
• When data outside the setting range is set.
• When data setting is changed during default setting registration.
(4) Hardware (H/W) error flag (Xn3)
This signal turns on when the temperature control module results in a hardware
error.
3 - 23 3 - 23
3 SPECIFICATIONS
Yn8Xn8X
(5)Auto tuning status flag (Xn4 to Xn7)
(6)E2PROM write completion flag (Xn8)
MELSEC-Q
(a) This signal tu rns on when aut o tu ni ng of th e co rre sp on di ng ch annel is
executed.
ChannelAuto tuning status flagON/OFF status
1Xn4
2Xn5
3Xn6
4Xn7
(b) Auto tuning is executed using the auto tuning command (Yn4 to Yn7).
(c) This signal turns "on" while auto tuning is being executed and turns "off"
automatically on completion of auto tuning.
(a) This signal turns on after completion of write of buffer memory contents to
2
E
PROM which starts when the E2PROM backup command (Yn8) turns on.
(b) When the E
2
PROM backup command turns off, the E2PROM write
completion flag also turns off.
ON : Auto tuning in execution
OFF: Auto tuning not in execution or
completed
ON
OFF
ON
OFF
OFF
nA
During write to E PROM
2
Completion of write to E PROM
(7)Default value write completion flag ( X n9)
(a) Turns on after completion of write of Q64TC default values to buffer memory
which starts when the default setting registration command (Yn9) turns on.
(b) When the default setting registration command (Yn9) turns off, the default
value write completion flag (Xn9) also turns off.
(c) Perform unused channel setting to unused channels after completion of
default value write.
If unused channel setting is not made to unused channels, the "ALM" LED of
the Q64TC is lit.
2
3 - 24 3 - 24
3 SPECIFICATIONS
X
A
s
m
)
(8)E2PROM write failure flag (XnA)
MELSEC-Q
(a) This sign al tu rn s on at a fa ilu re of w ri te o f bu ffe r memory contents to E2PROM
which starts when the E
• OFF : Completion of write to E
• ON: Failure of write to E
ON
Yn8
OFF
nA
OFF
Xn8
OFF
During write
2
to E PROM
(b) The E2PROM write failure flag turns off at normal completion of write to
2
PROM.
E
(c) When the E
2
PROM write failure flag has turned on, the E2PROM contents
are undefined.
Hence, powering on the PLC CPU again or resetting it with the E
write failu re fl ag on will make t h e bu ffe r memory contents undefi ne d, caus ing
the Q64TC to ope rat e wi th the de fa ul t valu e s.
2
PROM backup command (Yn8) turns on.
Error detection of write to E PROM
2
PROM
2
PROM (Write could not be completed normally)
ON
2
2
PROM
(9)Setting change completion flag (X nB)
(a) This signal turns on after completion of reflection of buffer memory settings on
control which starts when the setting conversion command (YnB) turns on.
(b) When the setting change command (YnB) turns off, the setting change
completion flag also turns off.
ON
OFF
YnB
ON
OFF
XnB
(10) Alert occurrence flag (XnC to XnF)
(a) This signal turns on at alarm occurrence on the corresponding channel.
Channel
Alert occurrence
flag
1XnC5
2XnD6
3XnE7
4XnF
ON/OFF status
OFF: Without alarm
occurrence
ON : With alarm
occurrence
(b) When an alert occurs, the alert occurrence data is stored into buffer memory
H
to 08H) and the alert occurrence flag turns on.
(05
ON
Alert occurrence data storage
buffer memory address
H
H
H
H
8
Alert occurrence flag
(XnC)
lert occurrence data
torage buffer
emory (05H
OFF
0Detected alert data
3 - 25 3 - 25
3 SPECIFICATIONS
)
3.4.3 Output signal functions
(1)Setting mode/operation mode command ( Y n1)
(a) This signal is used to set the operation mode of the temperature control
(b) This signal is set to all 4 ch a nnel s to ge the r.
(c) The following setting ite ms may be chan ge d only when Yn1 is off.
(d) Refer to Section 3.2.13 for the Q64TC operation governed by ON/OFF of the
(2)Error reset command (Yn2)
This signal is used to turn off the write error flag (Xn2) and clear (reset) the write
data error code storage buffer memory.
MELSEC-Q
function.
• OFF : Setting mode
• ON: Operation mode
• Input range (20
• Alert 1 to 4 mode setting (C0
A write data error (error code 3) will occur if any of these items is changed in
the operation mode.
setting mode/operation mode command.
H
, 40H, 60H, 80H)
ON
H
to C3H, D0H to D3H, E0H to E3H, F0H to F3H)
Xn2
Buffer memory(00
Yn2
OFF
H
)
H
00
OFF
(3)Auto tuning command (Yn4 to Yn7)
(a) This signal is used to star t auto t uni ng .
(b) Turning on the auto tuning command (Yn4 to Yn7) starts auto tuning and
turns on the auto tuning status flag (Xn4 to Xn7).
When auto tuning is completed, the auto tuning status flag (Xn4 to Xn7) turns
off.
(c) Keep the auto tuning command on while auto tuning is in execution, and turn
it off on completion of auto tuning.
(d) Turning off the auto tuning command during auto tuning execution stops auto
tuning.
When auto tuning is stopped, the PID constants in buffer memory do not
change.
uto tuning command
Yn4 to Yn7)
Error code
ON
00
H
uto tuning status flag
Xn4 to Xn7
During auto tuning
(e) Auto tuning is not performed when the proportional band (P) setting buffer
memory (23
H
, 43H, 63H, 83H) setting is 0.
3 - 26 3 - 26
3 SPECIFICATIONS
(4)E2PROM backup command (Yn8)
(5)Default setting registration command (Yn9)
MELSEC-Q
(a) This signal is used to write buffer memory contents to E2PROM.
(b) Turning on the E
2
PROM.
E
1) The "E
2
of write.
2) If write to E
flag (XnA)" turns on.
If XA has turned on, turn on the E
data to E
POINT
The number of writes to E2PROM is up to 100,00 0 ti mes.
When setting the PID constants, etc. at a PLC CPU startup, reduce the number of
writes by avoiding write to E
(a) This signal is used to return buffer memory contents to default values.
Turning on the default setting registration command writes the default values
of the Q64TC to buffer memory and the default value write completion flag
(Xn9) turns on at its completion .
(b) Make default setting in the setting mode (Xn1: OFF).
You cannot make default setting in the operation mode (Yn1: ON).
2
PROM backup command writes buffer memory contents to
PROM write completion flag (Xn8)" turns on at normal completion
2
PROM is not completed normally, the "E2PROM write failure
2
2
PROM.
2
PROM, for example.
PROM backup command again to write
DANGER
(6)Setting change command (YnB)
(a) This signal is used to determine the following buffer memory contents as set
values.
• Input range setting (20
• Alert 1 to 4 mode setting (C0
H
, 40H, 60H, 80H)
H
to C3H, D0H to D3H, E0H to E3H, F0H to F3H)
(b) For the setting items indicated in (a), their set values are not reflected on the
module operation if they are written to the corresponding buffer memory
addresses. To determine them as set values, this device must be turned on
after the values are written to buffer memory.
(c) Turning on the setting change command starts the operation as set in the
corresponding buffer memory address. The setting change completion flag
(XnB) turns on at completion of the setting change.
For setting items other than the above, their set values are determined by
merely writin g values to the buffer memory.
(d) This device is usable as an interlock for the setting/operation mode command
(Yn1).
(7)Forced PID control stop command (YnC to Y nF)
(a) This signal is used to stop the PID operation of the corresponding channel
forcibly.
(b) The mode in which PID operation stops is governed by the stop mode setting
buff er memor y (21
If the forced PID control stop command (YnC to YnF) is turned on to stop PID
operation, placing the PLC CPU in a STOP status will execute PID operation on the
channel where the PID operation was stopped by the forced PID control stop
command.
When putting the PLC CPU in a STOP status, set "unused" to the channel whose
forced PID control stop command is on.
H
, 41H, 61H, 81H) setting.
3 - 27 3 - 27
3 SPECIFICATIONS
3.5 Buffer Memory
3.5.1 Buffer memory list
(1)Buffer memory common to Q64TCs
MELSEC-Q
Addresses (Hexadecimal)
CH1CH2CH3CH4
H
0
H
H
1
2
H
5
6
H
9
A
H
D
E
H
3
4
H
H
7
H
H
8HAlert definition——Read only
H
B
CHTemperature process value (PV)——Read only
H
F
10HManipulated value (MV)——Read only
SettingsRange
Write data error code——Read only
Decimal point
H
position
Q64TCTT(BW)—0
Q64TCRT(BW)—1
Initial
value
Read/write
Read only
11H12H13H14HTemperature rise judgment flag——Read only
15H16H17H18HTransistor output flag——Read only
19H1AH1BH1CHReserved———
Cold junction
H
1D
H
1E
H
1F
20H40H60H80
Q64TCTT(BW)
temperature
process value
——
Q64TCRT(BW)Reserved
MAN mode shift completion flag——Read only
E2PROM's PID constant
read/write completion flag
H
Input range
Q64TCTT(BW)2
Q64TCRT(BW)
Refer to Section 3.5.12.
——Read only
7
Read only
—
Read/write enabled
21H41H61H81HStop mode setting0: Stop,1: Monitor,2: Warning1Read/write enabled
22H42H62H82HSet value (SV) settin g
In accordance with input
range setting
0Read/write enabled
23H43H63H83HProportional band (P) setting0 to 10000(0.0 to 1000.0%)30Read/write enabled
24H44H64H84HIntegral time (I) setting1 to 3600(s)240Read/write enabled
25H45H65H85HDerivative time (D) setting0 to 3600(s)60Read/write enabled
26H46H66H86HAlert set value 1
27H47H67H87HAlert set value 2
28H48H68H88HAlert set value 3
In accordance with alert mode
setting and input range setting
0Read/write enabled
29H49H69H89HAlert set value 4
2AH4AH6AH8AHUpper output limiter1000Read/write enabled
2BH4BH6BH8BHLower output limiter
-50 to 1050(-5.0 to 105.0%)
0Read/write enabled
2CH4CH6CH8CHOutput variation limiter0 to 1000(0.0 to 100.0%/s)0Read/write enabled
2DH4DH6DH8D
2EH4EH6EH8E
Sensor compensation value
H
setting
Adjustment sensitivity (dead band)
H
setting
-5000 to 5000
(-50.00 to 50.00%)
0Read/write enabled
1 to 100(0.1 to 10.0%)5Read/write enabled
2FH4FH6FH8FHControl output period setting1 to 100(s)30Read/write enabled
30H50H70H90HPrimary delay digital filter setting0 to 100(s)0Read/write enabled
31H51H71H91HControl response parameter0: Slow, 1: Normal, 2: Fast0Read/write enabled
auto tuning of PID constants
Reserved
Reserved
Reserved
Reserved
Alert dead band setting0 to 100(0.0 to 10.0%)5Read/write enabled
Alert delay count0 to 255 (times)0Read/write enabled
0: Without command,
1: With command
0Read/write enabled
0: OFF, 1: ON0Read/write enabled
———
Heater disconnection/output off-
H
A6
time current error detection delay
3 to 255 (times)3Read/write enabled
count
A7
A8
A9
AA
H
H
H
H
Temperature rise completion
range setting
Temperature rise completion soak
time setting
3.5.2 Write data error code (buffer memory address: 0H)
Stores the error code and error-detected buffer memory address of the error detected
when write from PLC CPU to Q64TC buffer memory was performed.
MELSEC-Q
b15
b4b2 b0
Error code
Error occurrence addres
(1)When data is written from the PLC CPU, the Q64TC checks:
• Whether write destination is read-only area or not
• Whether write destination is reserved area or not
• Whether write data range is proper or not
(2)The following processings are performed at write error occurrence.
• Error code is stored (refer to Section 8.1 for error code details).
• Write error occurrence flag (Xn2) turns on.
(3) If more than one error has occurred, the error code and error occurrence address
of the error having the highest priority are stored. (Refer to Section 8.2 for details
of processing at error occurrence.)
(4)Refer to Section 8.1 for error resetting.
3.5.3 Decimal point position (buffer memory address: 1H to 4H)
(1) The decimal point position for the following data is stored according to the input
range setting which determines the measured temperature range.
• Temperature process value (PV)
• Set value (SV)
• Alert set value
"1" is stored if the input range of the measured temperature range with a decimal
point was set.
"0" is stored if the input range of the measured temperature range without a
decimal point was set.
(2) Refer to the following table when performing write/read of the above data from the
PLC CPU.
Decimal point
position
0
1
Buffer memory data is read as is and
used in sequence programs, etc.
One/tenth of the value read from a
sequence program or the like is used
as the actual value.
For readFor write
The specified value is written as is.
The value 10 times the specified
value is written.
3 - 30 3 - 30
3 SPECIFICATIONS
3.5.4 Alert definition (buffer memory addr ess: 5H to 8H)
(1) The bit associated with the alert detected on the corresponding channel turns to
"1".
MELSEC-Q
Associated bit
number
b0
b1
b2 to b7Unused
b8Alert 1 turned on.
b9Alert 2 turned on.
b10Alert 3 turned on.
b11Alert 4 turned on.
b12Heater disconnection was detected.
b13Loop disconnection was detected (at LBA error).
b14Output off-time current error was detected.
b15Unused
: The temperature measurement range represents the range from the lower limit of -5%
to the upper limit of +5% relative to the full-scale of the input range.
Example) Input range 38
PV rose above the temperature measurement range
preset input range.
PV fell below the temperature measurement range
input range.
Input range: -200.0 to 400.0
Temperature measurement range : -230.0 to 430.0
(An alert occurs at the temperature of lower than -230.0°C or higher than
430.0°C.)
Alert definition
of the
of the preset
3.5.5 Temperature process value (PV value, buffer memory addr ess: 9H to CH)
(1) Stores the Q64TC-detected value on which the following processings have been
performed:
• Linearizatio n
• Sensor compensation
(2) The value stored varies with the decimal point position (buffer memory address: 1
to 4H) as indicated below:
• If the decimal point position is 0, the value is stored as is.
• If the decimal point position is 1, 10 times that value is stored.
POINT
The following value is stored if the temperature detected by the temperature sensor
falls outside the temperature measurement range:
• If the value is higher than the temperature measurement range: +5% of the (input
range upper limit)
• If the value is lower than the temperature measurement range: -5% of the (input
range upper limit)
H
3 - 31 3 - 31
3 SPECIFICATIONS
t
3.5.6 Manipulated value (MV value, buffer memory address: DH to 10H)
(1) Stores the result of PID operation performed on the basis of the temperature value
imported from the temperature sensor.
(2) The value sto red i s in the r a nge -50 to 10 50 (-5 .0 % t o 10 5. 0 %).
However, the value is in the range 0% to 100% for external output.
• Less than 0%: 0%
• More than 100% : 100%
(3) The manipulated value represents the ON time of the control output period (buffer
memory address: 2F
At the control output period of 30s (seconds) and the manipulated value of 600
(60.0%), the pulse turns on for 18 seconds and turns off for 12 seconds.
H
, 4FH, 6FH, 8FH) as a percentage.
MELSEC-Q
ransistor output
18s
ON
OFF
30s
12s
3.5.7 Temperature rise judgment flag (buffer memor y address: 11H to 14H)
(1) This flag checks whether the temperature process value (PV) is within the
temperature rise completion range or not.
(2) This flag turns to "1" when the temperature process value (PV) is within the
temperature rise completion range.
Setting the temperature rise completion soak time (buffer memory address: A8
will cause this flag to turn to "1" when the temperature process value remains
within the temperature rise completion range of the preset temperature rise
completion soak ti me.
3.5.8 Transistor output flag (buffer memory address: 15H to 18H)
(1) Stores the ON/OFF statuses of the transistor output and ON delay output.
H
)
b8 b0
Transistor outpu
ON delay output
(2) The following values are stored as the ON/OFF statuses of the transistor output
and ON delay outp ut .
• ON: 1
• OFF : 0
3 - 32 3 - 32
3 SPECIFICATIONS
3.5.9 Cold junction temperature process value (buffer memor y address: 1DH)
(1) Stores the measured temperature (0 to 55°C) of the cold junction compensation
resistor fi tt ed to th e Q 64 TCT T( BW).
3.5.10 MAN mode shift completion flag (buffer memor y address: 1EH)
(1) This flag checks whether switching from the automatic mode (AUTO) to the
manual mode (MAN) has been completed or not.
The bit associate d with th e co rr e spon di ng chan nel t u rns to "1" on co mpl et ion o f
switching to the manu al mode.
• Channel 1: Bit 0 ( b0 )
• Channel 2: Bit 1 ( b1 )
• Channel 3: Bit 2 ( b2 )
• Channel 4: Bit 3 ( b3 )
(2) When setting the manipulated value (MV) in the manual mode, make setting after
confirming that the manual mode shift completion flag has turned to "1".
The read failure flag (b8 to b11) turns off on normal completion of read on the
corresponding channel.
(3) The following chart shows the ON/OFF timings of this flag relative to the automatic
H
backup setting after auto tuning of PID constants (3E
, 5EH, 7EH, 9EH).
(For channel 1)
0
0
1
01
Auto tuning completion
Write failure
Auto tuning completion
Normal completion of write
Browsing this flag on completion of auto tuning allows you to check whether
automatic backup was completed normally or failed.
The write failure flag (b11 to b15) turns off on normal completion of write on the
corresponding channel.
3 - 34 3 - 34
3 SPECIFICATIONS
3.5.12 Input range (buffer memory address: 20H, 40H, 60H, 80H)
(1) The following table indicates the types and input range settings of the temperature
sensors to be connected to the Q64TC.
Set the input range setting value according to the temperature sensor and
operating temperature range used.
Always set the input range in the setting mode (Yn1: OFF).
(a) For use of Q64TCTT(BW)
°C°F
Thermocou
ple type
R0 to 1700110 to 30001051
K
J
T
S0 to 17001510 to 30001061
B0 to 18001610 to 30001071
N0 to 13002210 to 23001111
L
PL II0 to 12002310 to 23001121
Wre5-260 to 23002410 to 30001131
Measured
temperature
range
0 to 5001110 to 10001001
0 to 8001210 to 24001011
0 to 1300210.0 to 1000.01300.1
-200.0 to 400.0380.1
0.0 to 400.0360.1
0.0 to 500.0400.1
0.0 to 800.0410.1
0 to 5001310 to 10001021
0 to 8001410 to 16001031
0 to 1200310 to 21001041
0.0 to 400.0370.10.0 to 1000.01310.1
0.0 to 500.0420.1
0.0 to 800.0430.1
-200 to 400410 to 7001091
-200 to 200211-300 to 4001101
0 to 2001910.0 to 700.01320.1
0 to 400201
-200.0 to 400.0390.1
0.0 to 400.0450.1
0 to 4001710 to 18001081
0 to 1000181E
0.0 to 700.0440.1
0 to 4002510 to 7001141
-200 to 200261-300 to 4001151U
0.0 to 600.0460.1———
0 to 4002710 to 8001161
0 to 9002810 to 16001171
0.0 to 400.0470.1
0.0 to 900.0480.1
Input
range
setting
Setting
increments
temperature
MELSEC-Q
Measured
range
———
———
———
———
———
Input
range
setting
Setting
increments
3 - 35 3 - 35
3 SPECIFICATIONS
MELSEC-Q
(b) For use of Q64TCRT(BW)
Platinum
temperature-
measuring
resistor type
Pt100
JPt100
Measured
temperature
range
-200.0 to 600.07-300 to 1100141
-200.0 to 200.08-300.0 to 300.0143
-200.0 to 500.05-300 to 900140
-200.0 to 200.06-300.0 to 300.0142
°C°F
Input range
setting
Measured
temperature
range
(2) After the input range setting is changed, the temperature measurement value
turns to "0" for about 8 second s.
(3) When changing the input range, make setting so that the upper and lower setting
limiter values are within the temperature measurement range.
(4) To determine the set value change, you must turn on the setting change
(1) Sets the mode to be entered at a PID operation stop.
The default value (initial value) is set to "monitor".
Input range
setting
(2) Operation varies with the mode setting made as indicated below.
Operation
Setting mode Set value
Stop0
Monitor1
Alert2
PID
operation
Temperature
judgment
Alert
judgment
: Executed
: Not executed
Operation is governed by the unused channel setting, setting/operation mode
setting, PID continuation flag, forced stop command and CPU error stop-time
control output setting. (Refer to Section 3.2.13.)
(a) Temperature judgment: A temperature is input from the temperature sensor to
check whether it is within the temperature measurement range of the input
range setting.
(b) Alert judgment: Alert checks 1 to 4 in Section 3.5.4 are made.
POINT
The default value (initial value) of the stop mode is set to "monitor".
Hence, the channel without a temperature sensor connected results in a sensor
input disconnection and the "ALM" LED is lit.
For the channel to which a temperature sensor is not connected, set "1 (unused)"
to the unused channel setting buffer memory (3D
H
, 5DH, 7DH, 9DH).
3 - 36 3 - 36
3 SPECIFICATIONS
3.5.14 Set value (SV) setting (buffer memory addr ess: 22H, 42H, 62H, 82H)
(1) Sets the temperature for the set value of PID operation.
(2) The setting range is within the temperature setting range specified in the input
range setting (refer to Section 3.5.12).
(3) Setting a value outside the setting range will result in a write error, turn on the
write error flag (Xn2), and store the error code (4) to address 0 of the buffer
memory.
3.5.15 PID constant setting
(buffer memory address: 23H to 25H, 43H to 45H, 63H to 65H, 83H to 85H)
(1) Sets the proportional band (P), integral time (I) and derivative time (D) for
performing PID operation.
(2) As the proportional band (P), integral time (I) and derivative time (D), set values
within the following ranges.
Item
Proportional band
(P) setting
Integral time (I)
setting
Derivative time (D)
setting
Addresses (Hexadecimal)
CH.1CH.2CH.3CH.4
23
24
25
H
H
H
43
44
45
H
H
H
63
64
65
H
83
H
84
H
85
Setting range
H
0 to 10000
H
1 to 36001 to 3600 s
H
0 to 36000 to 3600 s
MELSEC-Q
Constant for
PID operation
0.0 to
1000.0%
(a) For two-position control, set the proportional band to "0".
(b) For PI control , set the de r iva tive time to "0".
(3) When executing auto tuning, do not set "0" to the proportional band.
If its setting is "0", auto tuning will not be executed.
REMARK
Two-position control is a control method in which ON and OFF alternate with each
other at two manipulated values of 0% and 100% with respect to the set value to
keep the temperature constant.
3.5.16 Alert alarm 1 to 4 setting
(buffer memory address: 26H to 29H, 46H to 49H, 66H to 69H, 86H to 89H)
(1) Sets the temperature at which the alert alarm 1 to 4 mode setting (buffer memory
address: C0
H
to C3H, D0H to D3H, E0H to E3H, F0H to F3H) will turn on.
(2) The setting range is within the temperature setting range specified in the input
range setting (refer to Section 3.5.12).
(3) Setting a value outside the setting range or setting a value other than 0 to the
setting range in mode setting 0 will result in a write error, turn on the write error
flag (Xn2), and store the error code (4) to address 0 of the buffer memory.
(1) This function suppresses the variation of the manipulated value updated every
second.
(2) The setting range is 1 to 1000 (0.1 to 100.0%).
For example, when the output variation limiter is set to 10 (1.0%), the output
variation will be 1% pe r seco nd at a sudden man ip ula t ed valu e ch ang e of 50% ,
and it will take 50 seconds until the output value changes to 50% actually.
(3) Setting 0 disables the outp u t va ri atio n limiter function.
(4) When two-position control is exercised, the output variation limiter function setting
(1) This setting is made to select the manipulated value between the PID operation-
calculated value and the user-set value.
• AUTO: The manipulated value calculated by PID operation is used to
calculate the ON ti me o f t he cont rol pe ri od .
• MAN: The manipulated value written to the manual output setting buffer
memory (33
control period.
(2) When AUTO is switched to MAN, the PID operation-calculated value is transferred
to the manual output setting buffer memory to prevent a sudden manipulated
value change. (Bumpless switching)
On completion of switching to the manual mode, the corresponding bit of the
manual mode shift completion flag (buffer memory address: 1E
Set the manipulated value in the MAN mode after making sure that the
corresponding bit of the manual mode shift completion flag has turned on.
H
, 53H, 73H, 93H) is used to calculate the ON time of the
Slow
H
) turns to 1 (ON).
Time
(3) When executing auto tuning, set "0: Auto (AUTO)".
When the setting is "1: Manual (MAN)", auto tuning will not be executed.
(1) This area is used to set the manipulated value in the "MAN" mode.
(2) Write a value to the MAN output setting buffer memory after confirming that the
corresponding bit of the manual mode shift completion flag (buffer memory
address: 1E
If this setting is made when the manual mode shift completion flag is off, the
system will rewrite it to the manipulated value calculated by PID operation.
(1) This setting is made to perform auto tuning centering on a shifted point (AT point).
Make this setting when shifting the point of the set value (SV) for auto tuning.
Make this setting if an excess of the process value over the set value (SV) will be
inconvenien t fo r auto t uning.
(2) Set the range which has minimal PID operation fluctuations and will not affect the
control results.
Otherwise, exa ct PI D con st ants may not be provi de d de pe ndin g on th e ob je ct to
be controlled.
t
[Setting of AT bias on negative side (for reverse action)]
(1) The loop disconnection detection function detects errors in the control system due
to a load disconnection, external operation device fault, sensor disconnection and
the like.
No temperature change of greater than 2°C (2°F) within the loop disconnection
detection judgment time is judged as a loop disconnection.
(2) As the loop disconnection detection judgment time, set a value longer than the
time taken to vary the temperature 2°C (2°F).
(3) Performing auto tuning automatically sets a value twice longer than the integral
time as the loop disconnection detection judgment time.
However, if the loop disconnection detection judgment time was set to 0 at the
auto tuning, the loop disconnection detection judgment time is not stored.
3 - 42 3 - 42
3 SPECIFICATIONS
3.5.32 Loop disconnection detection dead band setting
(buffer memory address: 3C
(1) To prevent the false alarm of loop disconnection detection, set the non-alarm area
(temperature width where loop disconnection will not be detected) around the set
value.
Process value (PV)
Set value (SV)
(2) The setting range is within the temperature setting range defined by the input
range setting (refer to Section 3.5.12).
For example, if the loop disconnection detection dead band setting is "50" at the
input range setting of 38, loop disconnection detection judgment is not made
within the set value
(1) Used to specify as unused the channels where temperature control will not be
performed and temperature sensors will not be connected.
(2) For the channels set as unused, the "ALM" LED will not be lit if a temperature
sensor is not connected.
(3) Making default setting regi st ra ti on (Y n9: ON ) clea rs th e unu sed chan ne l se tt ing.
When there are channels where temperature control is not performed and
temperature sensors are not connected, make unused channel setting after
completion of default setting registration.
3.5.34 E2PROM's PID constant read command
(buffer memory address: 3EH, 5EH, 7EH, 9EH)
(1) This command reads PID constants from E2PROM to buffe r memory.
Turn on this command to read E
addresses.
Buffer memory address name
Proportional band (P) setting23
Integral time (I) se ttin g24
Derivative time (D ) se ttin g25
Loop disconnection detection judgment
time
(2) This function is the most suitable for use when you want to use the initial settings
of the utility and the PID constants backed up on E
(3) When this command is on, do not make a set value change, E
default setting registration.
3 - 43 3 - 43
2
PROM values to th e fo l l ow ing bu ffe r me mory
Addresses (Hexadecimal)
CH1CH2CH3CH4
3B
H
H
H
H
H
43
H
44
H
45
H
5B
2
PROM together.
H
63
H
64
H
65
H
7B
2
PROM backup and
83
84
85
9B
H
H
H
H
3 SPECIFICATIONS
3.5.35 Automatic backup setting after auto tuning of PID constants
(buffer memory address: 3F
, 5FH, 7FH, 9FH)
H
MELSEC-Q
(1) With this function, the PID constants set at completion of auto tuning are backed
up automatically by E
2
PROM.
When 1 is written to this setting and auto tuning then started, data at the following
buffer memory addresses are automatically backed up by E
of auto tuning.
Buffer memory address name
Proportional band (P) setting23
Integral time (I) setting24
Derivative time (D) setting25
Loop disconnection detection
judgment time
CH1CH2CH3CH4
H
H
H
H
3B
(2) Do not change this setting during execution of auto tuning.
(3) While auto tu ni ng is bei ng exe cut ed wi th thi s se tt in g val i d, do no t make a se t valu e
change, E
2
PROM backup and default setting registration.
3.5.36 Alert dead band setting (buffer memory address: A4H)
(1) Sets the dead band for alerts in Section 3.2.11.
(1) Sets the sampling count for ju dgi ng an ale rt.
When the number of alert delay times has been set, the system is placed in an
alert status if the sampling count remains within the alert range between when the
process value (PV) has fallen within the alert range and when the sampling count
reaches or exceeds the number of alert delay times.
Refer to Sect ion 3 .2 .1 3 fo r d eta il s .
(1) Sets the method of making heater current measurement.
Choosing the ON current/OFF current measures the present current value of the
CT.
Choosing the ON current holds (retains) the previous heater ON-time current
value when the heater is OFF.
• 0: ON current/OFF current (default)
• 1: ON current
3.5.45 Manipulated value
(MV value, 0 to 4000/0 to 12000/0 to 16000, bu ffer me mor y address: B1H to B4H)
(1) Stores the value of the manipulated value at the buffer memory address (DH to
10
H
) to be output to the digital-to-analog converter module.
(2) The value stored is in the range 0 to 16000.
(3) When the equipment to be heated or cooled is analog input equipment, output the
manipulated value to the digital-to-analog converter module to convert it into an
analog value.
MELSEC-Q
3.5.46 Manipulated value resolution switchi ng (buffer me mor y address: B5H)
(1) Choose any of the following th r ee different resoluti on s fo r th e man i pul a ted v al ue
(buffer memory address: B1
• 0: 0 to 4000 (default)
• 1: 0 to 12000
• 2: 0 to 16000
H
to B4 H).
3.5.47 Auto tuning mode selection (buffer memory address: B8H to BBH)
According to the controlled object to be used, choose the auto tuning mode from the
"standard mode" and "fast response mode".
The standard mode is compatible with almost all controlled objects.
(1) Standard mode
This mode is compatible with almost all controlled objects. This mode is
especially effective for controlled objects which give an extremely slow response
or which may be affected by noise or interference.
For the controlled object where either the ON or OFF time during auto tuning is
about only 10 seconds, slow-response (low-gain) PID constants may be
calculated. In this case, fast-response PID constants can be calculated by
executing auto tuning in the fast response mode.
(2)Fast response mode
This mode calculates faster-response (higher-gain) PID constants for the
controlled object which gives a fast response where the ON or OFF time during
auto tuning is about only 10 seconds.
Note that the gains of the calculated PID constants may become so high that the
control temperature (PV) may oscillate near the set value (SV). In this case,
execute auto tuning in the standard mode.
POINT
(1) If auto tuning mode selection is performed using the utility package, Version
1.10L or a subsequent product version is necessary.
(2) Error code 2 (A valu e o t her t han 0 w a s inpu t to th e rest ri cted a rea .) o ccur s i f th e
high response mode is set for a function version A unit. Set the standard mode.
3.5.51 CT selection (buffer memory address: 110H to 117H)
(1) Chooses the current sensor connected to the Q64TCTTBW or Q64TCRTBW.
• 0: When CTL-12-S36-8 is used (0 to 100.0A) (default)
• 1: When CTL-6-P(-H) is used (0 to 20.00A)
(2) To determine a change in the set value, the setting change command (YnB) must
be turned on.
POINT
Refer to Section 2.1 for the current sensors that can be used with the Q64TCTTBW
and Q64TCRTBW.
We cannot guarantee operation if any other current sensor (CT) is used.
3.5.52 Reference heater current value (buffer memor y address: 118H to 11FH)
(1) Sets the heater ON-time heater current measurement value (buffer memory
H
address: 100
(2) The setting ranges are indicated below.
• When CTL-12-S36-8 is used : 0 to 1000 (0 to 100.0A)
• When CTL-6-P(-H) is used: 0 to 2000 (0 to 20.00A)
to 107H).
3 - 48 3 - 48
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
MELSEC-Q
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
The following describes the procedure prior to the Q64TC operation, the name and
setting of each part of the Q64TC, and wiring method.
4.1 Handling Precautions
The following are the precautions for handling the Q64TC.
(1) Do not drop the module casing or connector, or do not subject it to strong impact.
(2) Do not remove the PCB of each module from its case. Doing so may cause
breakdowns.
(3) Be careful not to let foreign particles such or wire chips get inside the module.
These may cause fire, breakdowns and malfunctions.
(4) The top surface of the module is covered with a protective film to prevent foreign
objects such as wire chips from entering the module when wiring. Do not remove
this film until the wiring is complete.
Before operating the system, be sure to remove the film to provide adequate heat
ventilation.
(5) Tighten the mounting and terminal screws of the module to the following specified
torques.
Undertightening can cause a short circuit, failure or malfunction.
Screw locationTightening torque range
Module mounting screw (M3 screw)36 to 48N•cm
Terminal block terminal screw (M3 screw)42 to 58N•cm
Terminal block mounting screw (M3.5 screw )66 to 89N•cm
(6) To mount the module on the base, securely insert the module mounting latches
into the mounting holes on the base unit. Improper installation may result in a
malfunction or breakdown of the module, or may cause the module to fall off.
4
4 - 1 4 - 1
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.2 Procedure Before Starting the Operation
The figure below shows the steps that should be followed before starting the Q64TC
operation.
Start
Module mounting
Mount the Q64TC in the specified slot.
Wiring
Wire the Q64TC.
Intelligent function module switch setting
Perform settings using the GX Developer
(see Section 4.5)
MELSEC-Q
4
Execution of auto tuning
Perform auto tuning to set PID constants.
Use the GX Configurator-TC?
No
Initial setting
Using the FROM/TO command s , create
a sequence program for w riting initial values.
Programming
Create and check a program using the
FROM/TO commands.
Yes
Initial setting
Perform the initial setting using the GX
Configurator-TC (see Section 5.4).
No
Automatic refres h setting
Perform the automatic refresh setting using
the GX Configurator-TC (see Section 5.5).
Programming
Create and check a program without using the
FROM/TO commands.
Perform automatic
refresh setting?
Yes
Warmup operation
(when Q64TCTT(BW) is used)
Perform warmup operation about 15
minutes before starting operation.
Operation
POINT
When using the Q64TCTT(BW) which uses a thermocouple as a temperature
sensor, perform warmup operation about 15 minutes before starting operation to
make temperature compensation properly.
4 - 2 4 - 2
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
)5)5)5)5)
)
4.3 Parts Identification
This section explains the names of the Q64TC parts.
MELSEC-Q
3)
1)
)
NC
)
5
1)
2)
NC
5
3)4)1)
2)
6)
3) 1)
2)
3)
4)
NumberNameDescription
Indicates the operating status of the Q64TCTT(BW).
On: Operating normally.
1)RUN LED
Off: 5V power is off, watchdog timer error occurred, or CPU stop
error occurred with intelligent function module switches of all
channels set to "CLEAR".
Indicates the error status of the Q64TCTT(BW).
2)ERR. LED
On: Hardware fault
Flicker : Write data error occurring
Off: Operating normally.
Indicates the alert status of the Q64TCTT(BW).
On: Alert occurring
Flicker : Process value (PV) came out of measured temperature
3)ALM LED
range.
Loop disconnection was detected.
Sensor is not connected.
Off: Alert not occurring
Indicates the heater disconnection detection status of the
4)HBA LED
Q64TCTT(BW).
On: Heater disconnection was detected.
Off: Heater disconnection is not detected.
5)Terminal block
Cold junction
6)
compensation resistor
Used for temperature sensor input, transistor output and current
sensor (CT) input.
Used when cold junction compensation is made.
: The terminal block layout varies with the module used.
Respective terminal block layouts are indicated on the fo llowing
pages.
4 - 3 4 - 3
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.4 Wiring
This section provides wiring instructions and module connection examples.
4.4.1 Wiring precautions
External wiring must be noise-resistant as one of the conditions to fully exhibit the
Q64TC functions and configure a highly reliably system.
The instructions given below should be followed in wiring.
(1) Use separate cables with the AC control circuit and Q64TC's external input
signals to avoid the influence of AC side surges and induction.
(2) Do not run the cables close t o , or bu ndl e t he m wi th , the mai n circuit and high-
voltage cables and the load cables from other than the PLC.
Always keep temperature sensors at least 100mm(3.94inch) away from the main
circuit cables and AC control circuit.
Fully keep them away from high-voltage cables and circuits which include high
frequencies, e.g. inverter load's main circuit.
Failure to do so will make the cables susceptible to noise, surges and induction.
MELSEC-Q
(3) Ground the shield wires or shield cables to FG of the PLC. Note that it may be
better to establish a ground on the external side depending on the external noise
conditions.
(4) When you want the equipment to conform with the EMC Directive/Low Voltage
Directive, refer to "Conformance with the EMC Directive and Low Voltage
Directive" in this manual and carry out wiring.
4 - 6 4 - 6
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.4.2 External wiring
(1)For use of Q64TCTT
Q64TCTT
MELSEC-Q
R
Controlled
object
L1
L2
L4
COM-
24VDC
CH1+
CH1-
CH2+
CH2-
CH4+
CH4-
: Always use shielded cables.
Internal circuit
Filter
FilterFilter
Internal circuit
4 - 7 4 - 7
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
(2)For use of Q64TCTTBW
Q64TCTTBW
MELSEC-Q
R
Current sensor
(CT)
Controlled
object
1
24VDC
L1
L2
L4
COM-
CH1+
CH1-
CH2+
CH2-
CH4+
CH4-
CT1+
CT1-
CT2+
CT2-
Internal circuitInternal circuit
FilterFilterFilter
Connector
Connector
CT input circuit
CT8+
CT8-
: Always use shielded cables.
POINT
To use the heater disconnection detection function, CT input channel assignment
setting must be made.
Since the above wiring example uses the CT1 in the loop of channel 1, set 1
(channel 1) to the CT1 channel assignment setting buffer memory (108H
).
4 - 8 4 - 8
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
(3)For use of Q64TCRT
Q64TCRT
MELSEC-Q
R
Controlled
object
L1
L2
L4
COM-
24VDC
A
B
b
A1
B1
b1
A2
B2
b2
A4
B4
b4
FilterFilterFilter
Internal circuitInternal circuit
: Always use shielded cables.
4 - 9 4 - 9
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
(4)For use of Q64TCRTBW
MELSEC-Q
Q64TCRTBW
R
Current sensor
(CT)
Controlled
object
L1
L2
L4
COM-
24VDC
A
B
b
A1
B1
b1
A2
B2
b2
A4
B4
b4
FilterFilterFilter
Internal circuitInternal circuit
Connector
Connector
CT1+
CT1-
CT2+
CT2-
CT8+
CT8-
CT input circuit
: Always use shielded cables.
POINT
To use the heater disconnection detection function, CT input channel assignment
setting must be made.
Since the above wiring example uses the CT1 in the loop of channel 1, set 1
(channel 1) to the CT1 channel assignment setting buffer memory (108H
).
4 - 10 4 - 10
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
MELSEC-Q
4.4.3 Heater disconnection detection wiring and setting ex ample for use o f three-phase
heater
The following wiring and setting example given below is designed to detect a threephase heater disconnection using the heater disconnection detection function.
Three-phase hater disconnection detection is made by measuring the currents of two
of the three conductors.
In the above wiring example, make CT input channel assignment setting (buffer
memory: 108
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.5 Switch Settings for the Intelligent Function Module
This section explains the intelligent function module switch settings.
Make intelligent function module switch settings in I/O assignment setting on GX
Developer.
Making intelligent function module switch settings allows you to set to the Q64TC the
output status to be established when the PLC CPU has comes to an error stop.
Refer to Sectio n 3 .2 .1 2 fo r s ett in g de ta il s .
(1)Setting items
Five switches (switch numbers 1 to 5) are available for the intelligent function
module and they are set with 16 bit data.
If the switches for the intelligent function module are not set, the default value of
0 is used for switches 1 to 5.
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
(2)Operating procedure
Perform settings, starting with the GX Developer I/O assignment screen.
(a) I/O assignment screen
Specify the following for the slot where theQ64TC is
mounted.
Type: Select "Intel li ."
Model name : Enter the module's model name.
Points: Select 16 points.
Start XY: Enter the start I/O sig nal fo r th e
Q64TC.
MELSEC-Q
(b) Switch setting for I/O and intelligent function module
Click on Switch Setting
screen to display the screen at left and set switches
1 to 5. The settin g can ea sil y be done if values are
entered in hexadecimal. Change the input format to
hexadecimal and enter values.
on the I/O assignment
REMARK
You need not set the "error-time output mode" and "hardware error-time CPU
operation mode" in the intelligent function module detailed setting as they are invalid
for the Q64TC .
4 - 13 4 - 13
5 UTILITY PACKAGE (GX Configur ator-TC)
5 UTILITY PACKAGE (GX Configurator-TC)
5.1 Utility Package Functions
Table 5.1 shows a list of the utility package functions.
Table 5.1 Utility Package (GX Configurator-TC) Function List
MELSEC-Q
5
FunctionDescription
(1) Make initial setting for operating the temperature control module channel-by-channel.
Set the values of the items which require initial setting.
•CH Input Range
•CH
Target Value Setting(SV)
•CH
Proportion(P) Setting
•CH
Integral Time(I) Setting
•CH
Differential Time(D) Setting
•CH
Output Control Cycle Setting
•CH
Control Response Parameter
•CH
Stop Mode Setting
•PID Continue Flag
•CH
Warning1 Mode Setting
•CH
Warning Setting Value1
•CH
Warning 2 Mode Setting
•CH
Initial setting
Warning Setting Value2
•CH
Warning 3 Mode Setting
•CH
Warning Setting Value3
•CH
Warning 4 Mode Setting
•CH
Warning Setting Value4
•Warning Non Sensitive Zone Setting
•Warning Delay Count
•CH
Loop Down Detect Decision Time
•CH
Loop Down Detect Dead Band
•CH
Heater Down Warning Setting
•Heater Down/OFF Time Abnormal Current
Detect Delay Count
•Heater Down Correcttion Function Select
•CT Monitor Format Change
•CT
Channel Layout Setting
•CT
CT Select
•CT
Standard Heater Current Value
•CH
Upper Limit Setting Limiter
•CH
Lower Limit Setting Limiter
•CH
Forward/Reverse Operation Setting
•CH
Chage Rate Limiter Setting
•CH
Sensor Correction Value Setting
•CH
Temporary Delay Digital Filter Setting
•CH
Upper Limit Output Limiter
•CH
Lower Limit Output Limiter
•CH
Output Change Level Limiter
•CH
Sensor Adjustment(NonSensitive)Setting
•CH
AT Bias
•CH
Unused Channel Setting
•Transistor ON Time Output Delay Monitor Setting
•Operation Level Resolution Change
•Temperaure Rise Complete Range Setting
•Temperature Rise Complete Sock Time Setting
Reference
section
Section 5.4
(2) The initially set data are registered to the PLC CPU parameters, and when the PLC CPU is set
to the RUN mode, they are written to the temperature control module automatically.
(1) Set the automatically refreshed temperature control module buffer memory channel-by-channel.
Automatic refresh
•Data Write Error Code
•CH
Measured Temperature Value(PV)
•CH
Operation Level(MV)
•CH
Target Value Setting(SV)
•CH
Transistor Output Flag
•CH
Occurred Warning Content
•CH
Warning Setting Value1
(2) The values stored in the temperature control module buffer memory where automatic refresh
setting was made are automatically read when the END instruction of the PLC CPU is executed.
Warning Setting Value2
•CH
•CH
Warning Setting Value3
•CH
Warning Setting Value4
•CH
Heater Down Warning Setting
•CH
Measured Heater Current Value
•CH
Operation Level
•CH
Temperature Rise Decision Flag
5 - 1 5 - 1
Section 5.5
5 UTILITY PACKAGE (GX Configur ator-TC)
MELSEC-Q
FunctionDescription
Monitors and tests the buffer memory and I/O signals for the temperature control module.
you can use the auto tuning function.
•Write Data Error Code
•CH
Decimal Point Place
•CH
Measured Temperature Value(PV)
•CH
Operation Level(MV)
•CH
Target Value Setting(SV)
•CH
Transistor Output Flag
•CH
ON Delay Output
•X00:Module Ready Flag
•X01:Setting/Operation Mode Status
•X02:Write Error Flag
•X03:Hardware Error Flag
•X04:CH1 Auto Tuning Status
•X05:CH2 Auto Tuning Status
•X06:CH3 Auto Tuning Status
•X07:CH4 Auto Tuning Status
2
•X08:E
PROM Write Completion Flag
•X09: Default Value Write Completion Flag
2
•X0A:E
PROM Write Fail Flag
•X0B:Setting Change Completion Flag
•X0C:CH1 Warning Occurred Flag
•X0D:CH2 Warning Occurred Flag
•X0E:CH3 Warning Occurred Flag
•X0F:CH4 Warning Occurred Flag
•Y01:Setting/Operation Mode Instruction
Monitor/test
•Y02:Error Reset Instruction
•Y04:CH1 Auto Tuning Instruction
•Y05:CH2 Auto Tuning Instruction
•Y06:CH3 Auto Tuning Instruction
•Y07:CH4 Auto Tuning Instruction
2
•Y08:E
PROM Backup Instr u ction
•Y09:Default Setting Registry Instruction
•Y0B:Setting Change Instruction
•Y0C:CH1 PID Calculation Compulsory
•Y0D:CH2 PID Calculation Compulsory
•Y0E:CH3 PID Calculation Compulsory
•Y0F:CH4 PID Calculation Compulsory
•CH
Proportion(P) Setting
•CH
Integral Time(I) Setting
•CH
Differential Time(D) Setting
•CH
E2PROM PID Constant Read Instruction
•CH
E2PROM PID Constant Read
Completion Flag
•CH
Output Control Cycle Setting
•CH
Control Response Parameter
•CH
Stop Mode Setting
•PID Continue Flag
•CH
Stop Mode Setting
•PID Continue Flag
•CH
Temperature Value (PV) Upper Limit
Cross Warning
•CH
Temperature Value (PV) Lower Limit
Cross Warning
•CH
Warning1
•CH
Warning2
•CH
Warning3
•CH
Warning4
•CH
Heater Down Warning
•CH
Loop Down Warning
•CH
OFF Time Abnormal Current Warning
•CH
Warning1 Mode Setting
•CH
Warning Setting Value1
•CH
Warning2 Mode Setting
•CH
Warning Setting Value2
•CH
Warning3 Mode Setting
•CH
Warning Setting Value3
•CH
Warning4 Mode Setting
•CH
Warning Setting Value4
•Warning Non Sensitive Zone Setting
•Warning Delay Count
•CH
Loop Down Detect Decision Time
•CH
Loop Down Detect Dead Band
•CH
Heater Down Warning
•Heater Down/OFF Time Abnormal Current
Detect Delay Count
•Heater Down Correction Function Select
•CT Monitor Format Change
•CT
Measured Hea ter Curr ent V alue
•CT
Channel Layout Setting
•CT
CT Select
•CT
Standard Heater Current Value
•CH
Operation Level
•Operation Level Resolution Change
•CH
Temperature Rise Decision Flag
•Temperature Rise Complete Range Setting
•Temperature Rise Complete Sock Time Setting
•CH
Input Range
•CH
Upper Limit Setting Limiter
•CH
Lower Limit Setting Limiter
•CH
Forward/Reverse Operation Setting
•CH
Change Rate Limiter Setting
•CH
Sensor Correction Value Setting
•CH
Temporary Delay Digital Filter Setting
•CH
Upper Limit Output Limiter
•CH
Lower Limit Output Limiter
•CH
Output Change Lev el Limit er
•CH
Sensor Adjustment(NonSensitive)
•CH
AT Bias
•CH
Unused Channel Sett ing
•Transistor ON Time Outpu t Delay Monit or Se tting
•CH
MAN Mode Switch Completion Flag
•CH
AUTO/MAN M ode Chan ge
•CH
MAN Output Setting
•Auto Tuning
Reference
section
5
Section 5.6
5 - 2 5 - 2
5 UTILITY PACKAGE (GX Configur ator-TC)
5.2 Installing and Uninstalling the Utility Package
See "Method of installing the MELSOFT Series" attached with the utility package
regarding the install and uninstall operation for the utility package.
5.2.1 User precautions
The following explains the precautions on using the Utility package:
(1) Important safety information
Since the utility is add-in software for GX Developer, make sure to read "Safety
Precautions" and the basic operating procedures in the GX Developer Operating
Manual.
(2) About installation
GX Configurator-TC is an add-in software package for GX Developer Version 4
or later products. Therefore, install GX Configurator-TC in a personal computer in
which GX Developer Version 4 or later product has been installed.
MELSEC-Q
(3) About display screen errors while usi ng the intel lig ent function
module utility
There may be cases in which the screen will not properly display while the
intelligent function module utility is being used, due to a lack of system resources.
If this occurs, close the intelligent function module utility first, and then close GX
Developer (program, comments, etc.) and other applications. Next, restart GX
Developer and the intelligent function module utility.
(4) To start the intelligent function module utility
(a) In GX Developer, select "QCPU (Q mode)" for the PLC series and specify the
project. If anything other than "QCPU (Q mode)" is selected for the PLC
series, or if no pro je ct i s spe ci fie d, th e i ntellig ent function module utility will not
start.
(b) Multiple intelligent function module utilities can be started.
However, the [Open file]/[Save file] parameter operations of the intelligent
function module can only be performed by a single intelligent function
module utility. Other intelligent function module utilities can perform the
[Monitor/test] operation only.
(5) How to switch screens when two or more intel l igent function
module utilities are started
When two or more intelligent function module utility screens cannot be displayed
side by side, use the task bar to display the desired intelligent function module
utility screen on top of other screens.
5 - 3 5 - 3
5 UTILITY PACKAGE (GX Configur ator-TC)
(6) About the number of parameters that ca n be set i n GX
Configurator-TC
The number of parameters that can be set by the GX Configurator for an
intelligent function module installed in the CPU module and in a remote I/O
station of the MELSECNET/H network system is limited.
For example, if multiple intelligent function modules are installed in a remote I/O
station, set the GX Configurator so that the number of parameter settings of all
the intelligent function modules does not exceed the maximum number of
parameter settings.The total number of parameter settings is calculated
separately for the initial setting and for the automatic refresh setting.
The number of parameter settings that can be set for one module in the GX
Configurator-TC is as shown below.
Object ModuleInitial settingAutomatic refresh setting
Q64TCTT/Q64TCRT20 (Fixed)45 (Maximum number of settings)
Q64TCTTBW/Q64TCRTBW20 (Fixed)57 (Maximum number of settings)
Example) Counting the number of parameter settings in the automatic refresh
setting
The number of settings in this one line is
counted as one setting.
The number of settings is not counted by columns.
Add up all the setting items in this setting screen,
then add them to the total for the other intelligent
function modules to get a grand total.
5 - 4 5 - 4
5 UTILITY PACKAGE (GX Configur ator-TC)
MELSEC-Q
5.2.2 Operating environment
The operating environment of the personal computer where the GX Configurator-TC is
used is explained.
ItemPeripheral devices
Installation (Add-in) destination
Computer main unitPersonal computer on which Windows® operates.
CPU
Required memory
Hard disk
free space
Display
Operating system
For installation65 MB or more
For operation10 MB or more
1
Add-in to GX Developer Version 4 (English version) or later
Refer to the following table "Used operating system and performance req uired for
personal computer".
800 600 dot or more resolution
Microsoft
Microsoft® Windows® 98 Operating System (English version)
Microsoft
Microsoft® Windows NT® Workstation Operating System Version 4.0 (English version)
Microsoft® Windows® 2000 Professional Operating System (English version)
Microsoft
Microsoft® Windows® XP Home Edition Operating System (English version)
®
Windows® 95 Operating System (English version)
®
Windows® Millennium Edition Operating System (English version)
®
Windows® XP Professional Operating System (English version)
3
1: Install the GX Configurator-TC in GX Developer Version 4 or higher in the same language.
GX Developer (English version) and GX Configurator-TC (Japanese version) cannot be used in
combination, and GX Developer (Japanese version) and GX Configurator-TC (English version) cannot be
used in configuration.
2: GX Configurator-TC cannot be used as an add-in with GX Developer Version 3 or earlier versions.
3: Setting fonts Size of WindowsR for "Large Fonts" may cause the text to extend off screen. Therefore,
choose "Small Fonts".
2
Used operating system and performance required for personal computer
Operating system
Windows® 95Pentium® 133MHz or more32MB or more
Windows® 98Pentium® 133MHz or more32MB or more
Windows® MePentium® 150MHz or more32MB or more
Windows NT® Workstation 4.0Pentium® 133MHz or more32MB or more
Windows® 2000 ProfessionalPentium® 133MHz or more64MB or more
Windows® XP
Professional
Windows® XP
Home Edition
"XP compatibility
mode" and "Fast User
Switching" are not
supported.
Pentium
Pentium
Performance Required for Personal Computer
CPURequired memory
®
300MHz or more128MB or more
®
300MHz or more128MB or more
5 - 5 5 - 5
5 UTILITY PACKAGE (GX Configur ator-TC)
5.3 Explanation of Utility Package Operations
5.3.1 How to perform common utility package operations
(1) Available control keys
Special keys that can be used during operations of the utility package and their
application s are shown in the table below.
Name of keyApplication
Esc
Tab
Ctrl
Delete
Back
space
Cancels a newly entered value when entering data in a cell.
Closes the window.
Moves between controls in the window.
Uses together with the mouse when multiple cells are sele cted
in the Test selected.
Deletes the character where the cursor is positioned.
When a cell is selected, clears all of the setting content s.
Deletes the character where the cursor is positioned.
MELSEC-Q
Page
Up
Page
Down
Enter
Moves the cursor.
Moves the cursor one page up.
Moves the cursor one page down.
Confirms the value entered in the cell.
(2) Data to be created with the utility package
The data and files shown below that are created with the utility package are also
used by GX Developer operations. Figure 5.1 shows which operation uses which
data or file.
<Intelligent module parameters>
(a) This data is created with the auto refresh setting, and stored in the intelligent
module parameter file of the project to be created using GX Developer.
Project
Program
Parameters
(b) Steps 1) to 3) shown in Figure 5.1 are performed using the following
2) Operating on the intelligent module parameter setting module selection
screen of the utility.
[File]
[Open file] / [Save file]
5 - 6 5 - 6
5 UTILITY PACKAGE (GX Configur ator-TC)
3) Operating using GX Developer.
[Online]
[Read from PLC] / [Write to PLC] "Intelligent module
parameter"
Or, operate on the intelligent module parameter setting module selection
screen of the utility.
[Online]
[Read from PLC] / [Write to PLC]
<Text file>
(a) A text file can be created by performing the initial setting or auto refresh
setting, or selecting Make text file
can be utilized to create user documents.
(b) Text files can be saved to any di recto ry.
However, a path (folder where the file is to be saved) cannot be created
during Make text file
the file using Windows
MELSEC-Q
on the monitor/test screen. Text files
operation, so create a folder in advance for saving
®
Explorer.
QCPU
Q25HCPU
A
MODE.
RUN.
ERR.
USER.
BAT.
BOOT.
GX Developer/
GX Configurator-TC
Project
3)
Disk
Project
1)
AA
2)
B
A: Indicates intelligent module parameters.
B: Indicates the data saved by text file creation.
Personal computer
USB
RS-232
Figure 5.1 correlation diagram for data created using the utility package
5 - 7 5 - 7
5 UTILITY PACKAGE (GX Configur ator-TC)
)
5.3.2 Operation overview
GX Developer screen
[Tools] – [Intelligent function utility] – [Start]
Intelligent module parameter setting
module selection screen
MELSEC-Q
See Section 5.3.3
Initial setting
Initial setting scree n
See Section 5.4
Enter "Start I/O No.", then select
"Package name" and "Module model name".
1
Auto refresh
Auto refresh setting screen
See Section 5.5
5 - 8 5 - 8
5 UTILITY PACKAGE (GX Configur ator-TC)
1)
[Online] – [Monitor/test]
Select monitor/test module screen
MELSEC-Q
Monitor/test
Monitor/test screen
See Section 5.6
Enter "Start I/O No.", then select
"Package name" and "Module model name".
5 - 9 5 - 9
5 UTILITY PACKAGE (GX Configur ator-TC)
5.3.3 Starting the intelligent function utility
[Purpose of operation]
Start the utility from GX Developer, and display the intelligent module parameter
setting module selection screen. The initial setting, auto refresh and select
monitor/test module (selecting the module for which monitoring/testing is to be
performed) screens can be started from this screen.
[Startup procedure]
[Tools] [Intelligent function utility] [Start]
[Setting screen]
MELSEC-Q
[Explanation of items]
(1) How to start each screen
(a) Starting the initial setting
"Start I/O No.
Initial setting
(b) Starting the au to r e fre s h set ti ng
"Start I/O No. "
Auto refresh
(c) Select monitor/test module screen
[Online]
Enter the start I/O No. in hexadecimal.
" "Package name" "Module model name"
"Package name" "Module model na me"
[Monitor/test]
(2) Explanation of the screen command buttons
Delete
Exit
5 - 10 5 - 10
Deletes the initial settings and auto refresh setting for the selected
module.
Ends the intelligent module parameter setting module selection screen.
5 UTILITY PACKAGE (GX Configur ator-TC)
(3) Menu bar
(a) File items
File operations are performed for the intelligent module parameters for the
project opened by GX Developer.
[Open file]: Opens the parameter file.
[Close file]: Closes the parameter file. If changes have been made,
[Save file]: Saves the parameter file.
[Delete file]: Deletes the parameter file.
[Exit]: Ends the intelligent module parameter setting module
(b) Online items
[Monitor/test]: Starts the select monitor/test module screen.
[Read from PLC] : Reads the intelligent module parameters from the CPU
[Write to PLC]: Writes the intelligent module parameters to the CPU
MELSEC-Q
the dialog box asking whether to save the file appears.
selection screen.
module.
module.
POINT
(1) Saving the intelligent modul e parameter files
Since these files cannot be saved using the GX Developer's project save
operation, save the files using the intelligent module parameter setting
module selection screen mentioned above.
(2) Reading and writing the intel l igent modul e par am eters to and
from a PLC using GX Developer.
(a) Once the intelligent module parameters are saved in a file, they can be
read from and written to the PLC.
(b) Set the target PLC CPU using [Online]
Developer.
(c) When mounting the Q64TC on a remote I/O station, use Read from PLC
and Write to PLC of GX Developer.
[Transfer setup] of GX
(3) Checking for the required utility
Start I/O No. is displayed in the Intelligent function module utility setting
screen, but a "
This means that either the required utility is not installed or that the utility
cannot be started from the GX Developer.
Check for the required utility in [Tools] - [Intelligent function utility] - [Utility list
...] in GX Developer, and set it.
" may be displayed fo r the mode l na me.
5 - 11 5 - 11
5 UTILITY PACKAGE (GX Configur ator-TC)
5.4 Initial Settings
[Purpose of operation]
Make initial setting for operating the temperature control module channel-bychannel.
Refer to Section 5.1 for the initial setting parameter types.
Sequence program setting will be made unnecessary by making this initial
setting.
[Startup procedure]
Choose "Start I/O No. " "Package name" "Module model na me"
Initial setting
Enter the start I/O No. in hexadecimal.
[Setting screen]
MELSEC-Q
Control Param e ter SettingWarning Function Setting
1)
5 - 12 5 - 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.