Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in minor or moderate injury or property damage.
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention
to safety to handle the product correctly.
The precautions given in this manual are concerned with this product only. For the safety precautions of the
programmable controller system, refer to the user’s manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: "WARNING" and "CAUTION"
Under some circumstances, failure to observe the precautions given under "CAUTION" may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.
[Design Precautions]
WARNING
When a communication error occurs on PROFIBUS-DP, the status of the faulty station is as shown
below.
Create an interlock circuit in the sequence program using the communication status information to
ensure the system operates safely (Input X1, buffer memory 5A20
An erroneous output or malfunction may cause accidents.
(1) The QJ71PB92V holds the input data before the communication failure.
(2) When the QJ71PB92V has gone down, the output status of each DP-Slave is dependent on the
QJ71PB92V parameter setting on GX Configurator-DP.
(3) When a DP-Slave has gone down, the output status of the other DP-Slaves is dependent on the
QJ71PB92V parameter setting on GX Configurator-DP.
Do not output the "use prohibited" signal as the output signal to an intelligent function module from
the programmable controller CPU.
Doing so may cause malfunction of the programmable controller system.
H to 5B19H (23072 to 23321)).
A - 1
[Design Precautions]
WARNING
When a stop error has occurred to the CPU module, the communication status varies depending on
the error time output mode setting of GX Works2 as shown below.
Set the communication status for when a stop error has occurred to the CPU module according to
the system specifications.
Note that, if the QJ71PB92V is mounted to a redundant system, it operates as described in (1) below
regardless of the setting.
(1) When "Error time output mode" is set to "Hold"
(a) Since the communication with the DP-Slave is continued, values at the time of the CPU
module stop error occurrence are held as the output data sent to the DP-Slave from the
QJ71PB92V.
(b) Input data received from DP-Slaves are updated into the buffer memory of the QJ71PB92V.
(2) When "Error time output mode" is set to "Clear"
(a) Communications with DP-Slaves are interrupted, and output data are not sent.
(b) Input data received from DP-Slaves are held in the buffer memory of the QJ71PB92V.
When the QJ71PB92V is mounted in a redundant system, set the watchdog timer for DP-Slaves so
that the calculation formula shown in Section 4.8 (5) is satisfied.
If the formula is not satisfied, a watchdog timer error occurs in DP-Slaves during system switching.
CAUTION
Do not install PROFIBUS cables together with the main circuit or power lines or bring them close to
each other.
Keep a distance of 100mm (3.94 inches) or more between them.
Failure to do so may result in malfunction due to noise.
A - 2
[Installation Precautions]
CAUTION
Use the programmable controller in an environment that meets the general specifications in the
user's manual for the CPU module used.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the
product.
To mount the module, while pressing the module mounting lever located in the lower part of the
module, fully insert the module fixing projection(s) into the hole(s) in the base unit and press the
module until it snaps into place.
Incorrect mounting may cause malfunction, failure or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the module
with a screw.
Tighten the screw within the specified torque range.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the
module.
Failure to do so may result in damage to the product.
Do not directly touch any conductive parts and electronic components of the module.
Doing so can cause malfunction or failure of the module.
A - 3
[Wiring Precautions]
WARNING
Be sure to shut off all phases of the external power supply used by the system before wiring
PROFIBUS cables.
Failure to do so may cause the module to fail or malfunction.
CAUTION
Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
Be sure to place the PROFIBUS cables in a duct or clamp them.
If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or
cables or malfunction due to poor contact.
When disconnecting the PROFIBUS cable, do not pull it by holding the cable part.
Be sure to hold its connector which is plugged into the module.
Pulling the cable with it connected to the module may damage the module and/or cable, or cause
malfunctions due to poor contact of the cable.
A protective film is attached to the top of the module to prevent foreign matter, such as wire chips,
from entering the module during wiring.
Do not remove the film during wiring.
Remove it for heat dissipation before system operation.
A - 4
[Startup and Maintenance Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before cleaning the module or
retightening the connector screws or module fixing screws.
Failure to do so may result in electric shock or cause the module to fail or malfunction.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
CAUTION
Do not disassemble or modify the modules.
Doing so may cause failure, malfunction, injury, or a fire.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone
System) more than 25cm (9.85 inches) away in all directions from the programmable controller.
Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the
module.
Failure to do so may cause the module to fail or malfunction.
After the first use of the product, do not mount/remove the module to/from the base unit more than
50 times (IEC 61131-2 compliant).
Exceeding the limit may cause malfunction.
Before handling the module, touch a grounded metal object to discharge the static electricity from the
human body.
Failure to do so may cause the module to fail or malfunction.
[Disposal Precautions]
CAUTION
When disposing of this product, treat is as an industrial waste.
A - 5
CONDITIONS OF USE FOR THE PRODUCT
(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above restrictions, Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.
A - 6
REVISIONS
Additions
Section number changes
Change of a term
Additions
Section number changes
Additions
Modifications
* The manual number is given on the bottom left of the back cover.
Print Date* Manual NumberRevision
Aug., 2005SH (NA)-080572ENG-AFirst edition
Jun., 2006SH (NA)-080572ENG-B
May, 2007SH (NA)-080572ENG-C• Rewritten to include the QJ71PB92D-compatible function.
Modifications
SAFETY PRECAUTIONS, GLOSSARY, Section 1.1, 2.1, 2.2.1, 2.4, 3.1 to
3.5, Chapter 4, Section 4.1.1, 4.1.3, 4.2.1 to 4.2.3, 4.5, 4.6, 5.3, 5.4, 6.1 to
Thank you for purchasing the Mitsubishi Electric programmable controller, MELSEC-Q series.
Please read this manual carefully before use to develop familiarity with the functions and performance, and use
it correctly.
INTRODUCTION............................................................................................................................................... A - 9
CONTENTS ...................................................................................................................................................... A - 9
MANUALS....................................................................................................................................................... A - 13
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES...................................................................A - 13
MANUAL ORGANIZATION............................................................................................................................. A - 14
ABOUT THE GENERIC TERMS AND ABBREVIATIONS ..............................................................................A - 15
PACKING LIST ...............................................................................................................................................A - 17
3.2 Function List ................................................................................................................................... 3 - 3
3.3Input/Output Signals to/from Programmable Controller CPU .......................................................... 3 - 4
3.3.1List of I/O signals ...................................................................................................................... 3 - 4
3.3.2Details of I/O signals................................................................................................................. 3 - 6
The manuals related to this product are listed below.
Please place an order as needed.
Manual name
GX Configurator-DP Version7 Operating Manual
Explains the overview, installation method, and operating method of GX Configurator-DP Version 7.
(Sold separately)
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES
(1) Method of ensuring compliance
To ensure that Mitsubishi Electric programmable controllers maintain EMC and Low
Voltage Directives when incorporated into other machinery or equipment, certain
measures may be necessary. Please refer to one of the following manuals
• QCPU User's Manual (Hardware Design, Maintenance and Inspection)
• Safety Guidelines
(This manual is included with the CPU module or base unit.)
The CE mark on the side of the programmable controller indicates compliance with
EMC and Low Voltage Directives.
(2) Additional measures
No additional measures are necessary for the compliance of this product with EMC
and Low Voltage Directives.
Manual number
(model code)
SH-080579ENG
(13JU54)
A - 13
MANUAL ORGANIZATION
In this manual, pages are organized and the symbols are used as shown below.
The following illustration is for explanation purpose only, and should not be referred to as
an actual documentation.
Chapter index
The chapter of the current page is
highlighted.
Reference
A reference in this manual or a
reference manual is followed by .
A - 14
Section title
The section of the current page is
shown.
• Description of a redundant system
Unless otherwise specified, a redundant system in this manual is a system
where QJ71PB92Vs are mounted on main base units.
When the QJ71PB92V is mounted on an extension base unit in a redundant
system, the module operates in the same way as used in a single CPU
system. However, there are some restrictions. For the restrictions, refer to the
following.
( User's manual for the redundant system for the CPU module used)
ABOUT THE GENERIC TERMS AND ABBREVIATIONS
Unless otherwise specified, this manual uses the following generic terms and
abbreviations to describe the Type QJ71PB92V PROFIBUS-DP Master Module.
General term/AbbreviationDescription
QJ71PB92VAbbreviation for the QJ71PB92V PROFIBUS-DP Master module
PROFIBUS-DPAbbreviation of PROFIBUS-DP network
MELSECNET/HAbbreviation of MELSECNET/H network system
Generic term for the Q00JCPU, Q00CPU, Q00UJCPU, Q00UCPU, Q01CPU, Q01UCPU,
QCPU
CPU module
Redundant CPUGeneric term for the Q12PRHCPU and Q25PRHCPU
GX Works2The product name of the software package for the MELSEC programmable controllers
GX Configurator-DP
BBLKRDAbbreviation for G. BBLKRD
BBLKWRAbbreviation for G. BBLKWR
Generic term of the product model SWnD5C-PROFID-E. ("n" means version 7 or later.)
A - 15
GLOSSARY
This part explains the glossary used in this manual.
Ter mDescription
A basic version of PROFIBUS-DP.
The following functions are executable:
PROFIBUS-DPV0
PROFIBUS-DPV1
PROFIBUS-DPV2
Class 1A device exchanging I/O data with a DP-Slaves. (QJ71PB92V, QJ71PB92D, etc)
DP-Master
DP-SlaveA device that exchanges I/O data with a DP-Master (Class 1). (such as the QJ71PB93D)
RepeaterA device used to connect different segments of PROFIBUS-DP
Bus terminatorA terminating resistor that is connected to either end of each segment on PROFIBUS-DP
Configuration tool
GSD file
FDL address
Bus parameter
Master parameter
Slave parameter
I/O CONFIGURATION
DATA
I/O data exchangeThis function allows I/O data exchange between a DP-Master (Class 1) and DP-Slaves.
Global control
Diagnostic information
Extended diagnostic error
information
Class 2
• I/O data exchange
• Diagnostic information notification
etc.
A PROFIBUS-DP version for which the following functions have been added to the basic
functionality of PROFIBUS-DPV0.
• Acyclic communication
• Alarm function
etc.
A PROFIBUS-DP version for which the following functions have been added to the
PROFIBUS-DPV1 functionality
• Time stamping
etc.
A device that communicates with DP-Slaves and checks their FDL address settings and/or
operation states
The DP-Master (Class 2) is used as a DP-Master for supervising the network, which can start,
maintain, and diagnose the system.
Software used to set bus parameters, slave parameters, etc. and to write them to a DP-Master
(GX Configurator-DP, etc.)
An electronic file that contains parameters of a DP-Slave
The GSD file is used to set up the slave parameters on GX Configurator-DP.
The numbers assigned to a DP-Master and DP-Slaves
The FDL address is set within the range from 0 to 125.
The parameter used for the communication setting of PROFIBUS-DP
The bus parameter is set up on the GX Configurator-DP.
The parameter used for the settings (FDL address, transmission speed, etc.) of the
QJ71PB92V
The master parameter is set up on the GX Configurator-DP.
The parameter for a DP-Slave, which is set on the DP-Master.
The slave parameter is set up on the GX Configurator-DP.
The setting items are described on the GSD File.
Information on I/O configuration of a DP-Slave
This function enables synchronization command transmission for I/O data from a DP-Master
(Class 1) to DP-Slaves.
Diagnostic information of PROFIBUS-DP, which is detected by a DP-Master or notified by a
DP-Slave
Diagnostic information specific to each DP-Slave
Each of DP-Slaves notifies of it to the DP-Master when an error is detected.
(To the next page)
A - 16
Ter mDescription
Bus cycle time
Ident No.
UTC
Time masterA master station that can send a request for time control. (QJ71PB92V, etc.)
System AThe system to which the system-A connector of the tracking cable is connected.
System BThe system to which the system-B connector of the tracking cable is connected.
Control systemThe system that is controlling the redundant system and performing network communication
Standby systemThe system for backup in the redundant system
New control system
New standby system
QJ71PB92D-compatible
function
QJ71PB92D The QJ71PB92D type PROFIBUS-DP interface module
PROFIBUS-DP processing time for the DP-Master to perform cyclic communication with each
DP-Slave
A specific number for each module that is connected to PROFIBUS-DP
Ident No. is described in a GSD file of each module.
The UTC is based on the UTC, which stands for Coordinated Universal Time.
In order to adjust the time gap with the GMT (Greenwich Mean Time), the "leap second" has
been added.
The system changed from the standby system status to the control system status due to system
switching
The system changed from the control system status to the standby system status due to system
switching
The function used to replace the QJ71PB92D with the QJ71PB92V
The QJ71PB92V type PROFIBUS-DP master module has this function.
PACKING LIST
The following indicates the packing list of the QJ71PB92V.
This manual explains the specifications, functions, procedures before system operation,
and troubleshooting for the QJ71PB92V PROFIBUS-DP master module (hereinafter
referred to as "QJ71PB92V").
The QJ71PB92V is used for connecting MELSEC-Q Series programmable controllers to
PROFIBUS-DP.
The QJ71PB92V operates as a DP-Master (Class 1) on PROFIBUS-DP networks.
Figure 1.1 PROFIBUS-DP Using QJ71PB92V (Continued)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
1 - 2
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
1
OVERVIEW
1.1 Features
The following describes the features of the QJ71PB92V.
(1) DP-Master (Class 1) on PROFIBUS-DP
The QJ71PB92V complies with IEC 61158, and operates as a DP-Master (Class 1) on
PROFIBUS-DP systems.
(a) Up to 125 DP-Slaves are connectable
*1
Up to 125 DP-Slaves
exchange of I/O data up to 8192 bytes. (Section 4.1.1)
* 1 Up to 124 DP-Slaves when QJ71PB92Vs are mounted on main base units in a redundant system
(b) Diagnostic information can be easily acquired
Diagnostic or extended diagnostic information of an error occurred on a DP-Slave
during I/O data exchange can be easily acquired using the buffer memory and I/O
signals. (Section 4.1.2)
can be connected to a single QJ71PB92V, enabling
(c) Supporting the global control function
By sending services (SYNC, UNSYNC, FREEZE, UNFREEZE) to each DP-Slave
in a group, synchronous control of DP-Slave I/O data is available. (Section
4.1.3)
Table1.1 Descriptions of Services
Service NameDescription
This service is for synchronizing the output status of DP-Slaves.
SYNC
UNSYNCThis service is for ending the SYNC mode.
FREEZE
UNFREEZEThis service is for ending the FREEZE service.
(d) Supporting PROFIBUS-DPV1 and PROFIBUS-DPV2
PROFIBUS-DPV1 and PROFIBUS-DPV2, which are extended versions of
PROFIBUS-DP, are supported
The QJ71PB92V supports the following:
In the SYNC mode, the output status of a DP-Slave is refreshed
each time it receives the SYNC service.
While no SYNC service is received, the output status is held.
This service is for synchronizing the input status of DP-Slaves.
In the FREEZE mode, the input status of a DP-Slave is refreshed
each time it receives the FREEZE service.
While no FREEZE service is received, the input status is held.
1 - 3
1) PROFIBUS-DPV1
• Acyclic communication with DP-Slaves (Section 4.2.1)
• Alarm acquisition (Section 4.2.2)
2) PROFIBUS-DPV2
• Time control function on DP-Slaves (Section 4.3.1)
1.1 Features
1
OVERVIEW
(2) I/O data consistency
(3) Easy parameter setup
Using the automatic refresh setting in GX Configurator-DP or dedicated instructions
(BBLKRD/BBLKWR) ensures data consistency when reading/writing I/O data from the
QJ71PB92V buffer memory. (Section 4.5)
Use of GX Configurator-DP enables bus parameters, master parameters, slave
parameters, and various other parameters to be easily set up. (CHAPTER 6)
1
OVERVIEW
2
(4) Swapping of I/O data
The upper and lower bytes can be reversed (swapped) in word units when I/O data is
sent or received.
This simplifies programming as you no longer need to create a program for swapping
the upper and lower bytes on the QJ71PB92V or DP-Slave. (Section 4.4)
(5) Mountable on MELSECNET/H remote I/O station
The QJ71PB92V can be mounted on a MELSECNET/H remote I/O station.
This allows you to install the QJ71PB92V at a remote site away from the QCPU.
(Section 7.8)
(6) Output status setting for the case of a CPU stop error (Stop/Continue of
I/O data exchange)
For the case of a CPU stop error on a QCPU or remote I/O station where the
QJ71PB92V is mounted, whether to stop or continue I/O data exchange with DP-
Slaves can be specified. (Section 4.6)
(7) Changing DP-Slave setting to reserved station status temporarily
Without modifying the slave parameter in GX Configurator-DP, the station type of DP-
Slaves can be changed to "Reserved station" temporarily. (Section 4.7)
Since there is no need to change slave parameters, changing a DP-Slave setting to a
reserved station is easy.
SETTINGS AND
3
4
5
6
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
1.1 Features
1 - 4
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
1
OVERVIEW
(8) Redundant system can be constructed
(a) Redundancy is available for the QJ71PB92V.
By mounting the QJ71PB92V together with a redundant CPU, a redundant
system can be constructed.
Even if the QJ71PB92V detects an error, the control and standby systems are
switched each other continuing communications. (Section 4.8)
(b) System switching is available when an error occurs in the QJ71PB92V or in
communication with a DP-Slave.
The systems can be switched when an error occurs in the QJ71PB92V or in
communication with a DP-Slave.
• When the QJ71PB92V detects a critical error
Bus terminator
• When the QJ71PB92V detects a communication error of a DP-Slave
Control system
New standby system
Control system
New standby system
Error in
QJ71PB92V
Standby system
New control system
Continues communication
System switching
Tracking cable
ST1PSD
ST1H-PB
RELEASE
RESET
PROFIBUS I/F
ST1PDD
RUN
ERR
RUN ERR
RUN ERR
RUN
ERR
RUN ERR RUN ERR
SYS
11 21
11 21
.
AUX
AUX
DP-Slave (QJ71PB93D)DP-Slave (ST1H-PB)
Figure 1.2 When the QJ71PB92V detects a critical error
Standby system
Continues communication
New control system
Bus terminator
1 - 5
System switching
Tracking cable
Bus terminatorBus terminator
Communication
failure
Figure 1.3 When the QJ71PB92V detects a communication error of a DP-Slave
1.1 Features
2
Remark
POINT
SYSTEM CONFIGURATION
CHAPTER2 SYSTEM CONFIGURATION
This chapter explains the system configuration of the QJ71PB92V.
1
OVERVIEW
2.1 Applicable System
This section describes applicable systems.
(1) Mountable modules, No. of mountable modules, and mountable base
unit
(a) When mounting to CPU module
For the mountable CPU modules, No. of mountable modules, and mountable
base unit of the QJ71PB92V, refer to the following manual.
User's manual of the CPU module used (Hardware Design, Maintenance and
Inspection)
When using a C Controller module, refer to the user's manual for a C Controller
module.
(1) The number of mountable modules is restricted depending on the automatic
refresh setting on the QJ71PB92V. ( Section 6.6.4)
For details, refer to Section 6.6.4.
(2) To utilize the data consistency function and dedicated instructions, use a
QCPU whose first 5 digits of the serial No. is "02092" or later.
SETTINGS AND
2
3
4
5
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
2.1 Applicable System
2 - 1
6
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
2
Remark
SYSTEM CONFIGURATION
(b) When mounting to remote I/O station of MELSECNET/H
The following shows the mountable network modules, No. of mountable modules,
and mountable base unit of the QJ71PB92V module.
Power shortage may occur depending on the combination with other mounted
modules or the number of mounted modules.
When mounting modules, pay attention to the power supply capacity.
When the power shortage occurs, review the combination of modules to be
mounted.
Table2.1 When mounting to remote I/O station of MELSECNET/H
Mountable network
module
QJ72LP25-25
QJ72LP25G
QJ72LP25GE
QJ72BR15
No. of mountable
modules
Up to 64
Mountable base unit
*1
Main base unit of
remote I/O station
Extension base unit
of remote I/O station
*2
: Mountable, : Not mountable
* 1 Limited to the range of the number of I/O points in the network module.
* 2 Mountable on any I/O slot of the mountable base unit.
The Basic model QCPU cannot create the MELSECNET/H remote I/O network.
2 - 2
2.1 Applicable System
2
SYSTEM CONFIGURATION
(2) Supported software packages
The following shows the compatibility between software packages and the system
using the QJ71PB92V.
GX Developer or GX Works2: For setting QCPU parameters and creating sequence
programs (required)
GX Configurator-DP: Configuration software for the QJ71PB92V (required)
Table2.2 Supported software packages
1
OVERVIEW
2
System
Q00J/Q00/Q01CPU
Q02/Q02H/Q06H/
Q12H/Q25HCPU
Q02PH/Q06PHCPU
Q12PH/Q25PHCPU
Q12PRH/Q25PRHCPU Redundant systemVersion 8.17T or later
Q00UJCPUSingle CPU system
Q00U/
Q01UCPU
Q02UCPU
Q03UD/Q04UDH/
Q06UDHCPU
Q10UDH/Q20UDHCPU
Q13UDH/Q26UDHCPU
Q03UDV/Q04UDV/
Q06UDV/Q13UDV/
Q26UDVCPU
Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/
Q26UDEHCPU
Q10UDEH/
Q20UDEHCPU
Q50UDEH/
Q100UDEHCPU
When the CPU is mounted on a MELSECNET/H
remote I/O station
Single CPU systemVersion 7 or later
Multiple CPU systemVersion 8 or laterVersion 1.14Q or later
Single CPU systemVersion 4 or laterVersion 1.11M or later
Multiple CPU systemVersion 6 or laterVersion 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU systemVersion 1.14Q or later
Single CPU system
Multiple CPU system
GX Developer
Version 8.68W or later Version 7.04E or later
Version 7.10L or laterVersion 7.00A or later
Version 8.76E or laterVersion 7.04E or later
Version 8.48A or later
Version 8.76E or laterVersion 7.04E or later
Version 8.62Q or laterVersion 7.03D or later
Not availableVersion 7.09K or laterVersion 1.95Z or later
Version 8.68W or later Version 7.03D or later
Version 8.76E or laterVersion 7.04E or later
Not availableVersion 7.07H or laterVersion 1.25B or later
Version 6 or laterVersion 7.00A or laterVersion 1.34L or later
Software version
GX Configurator-DP
Version 7.00A or later
Version 7.00A or later
Version 7.03D or later
Version 7.02C or later
*1
*3
GX Works2
Version 1.11M or later
Version 1.86Q or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
*2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
SYSTEM OPERATION
6
PARAMETER SETTING
7
* 1 The operation mode of the QJ71PB92V cannot be changed using GX Configurator-DP Version
7.03D or later.
Change the mode using Operation mode change request area (Un\G2255).
* 2 For how to use GX Configurator-DP and GX Works2 together, refer to the GX Configurator-DP
Version7 Operating Manual.
* 3 To mount the QJ71PB92V on an extension base unit, use GX Configurator-DP Version 7.03D or
later.
2.1 Applicable System
2 - 3
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
2
SYSTEM CONFIGURATION
2.1.1 Precautions for use on MELSECNET/H remote I/O stations
The following are the precautions when using the QJ71PB92V on MELSECNET/H remote
I/O stations.
(1) Automatic refresh
Automatic refresh is not available when the QJ71PB92V is mounted on a
MELSECNET/H remote I/O station.
To use the automatic refresh, mount the QJ71PB92V on a remote master station
(QCPU).
(2) Dedicated instructions (BBLKWR, BBLKRD)
Dedicated instructions (BBLKWR, BBLKRD) cannot be used when the QJ71PB92V is
mounted on a MELSECNET/H remote I/O station.
To use dedicated instructions, mount the QJ71PB92V on a remote master station
(QCPU).
(3) QJ71PB92V parameter setup
To set QJ71PB92V parameters, connect GX Configurator-DP to a remote I/O station.
QJ71PB92V parameters cannot be set via a remote master station.
2 - 4
2.1 Applicable System
2.1.1 Precautions for use on MELSECNET/H remote I/O stations
2
SYSTEM CONFIGURATION
2.2 PROFIBUS-DP Network Configuration
1
2.2.1 Basic configuration of the PROFIBUS-DP network
This section explains the basic PROFIBUS-DP configuration for using the QJ71PB92V as
a DP-Master (Class 1).
(1) System equipment
The following table shows the equipment required for the PROFIBUS-DP system.
Table2.3 System Equipment
System EquipmentDescription
DP-Master (Class 1)QJ71PB92V
Configuration toolGX Configurator-DP Version 7.00A or later
DP-SlaveSuch as the QJ71PB93D
RepeaterRequired when 32 or more DP-Slaves are connected
PROFIBUS cable
Bus terminator
(2) Network configuration
In the PROFIBUS-DP system configuration, the following conditions must be
satisfied:
(a) Number of connectable modules in an entire network (When repeaters are used)
*1
DP-Master
* 1 Including the QJ71PB92V
+ DP-Slaves 126
Section 5.5.1
2
3
4
5
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
(b) Number of connectable modules per segment
*1
DP-Master
* 1 Including the QJ71PB92V
* 2 A repeater is counted for both segments.
(c) Max. no. of repeaters
Up to 3 repeaters can be used for communication between the QJ71PB92V and
any DP-Slave.
(d) Number of connectable DP-Slaves per QJ71PB92V
Up to 125 DP-Slaves can be connected to a single QJ71PB92V.
(e) Multi-master system
When a communication chip of ASPC2 STEP C mode or equivalent is used, the
DP-Master cannot be connected to the PROFIBUS-DP in which the QJ71PB92V
is included.
To use a DP-Master with such a communication chip, configure another network.
For the communication chip currently used, consult its manufacturer.
+ DP-Slaves + repeaters *2 32
SETTINGS AND
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
2.2 PROFIBUS-DP Network Configuration
2.2.1 Basic configuration of the PROFIBUS-DP network
2 - 5
DEDICATED
INSTRUCTIONS
2
r
DP-Master (Class 1) (FDL address 0)
Bus terminatorBus terminator
Repeater 1
Segment 1
Segment 2
: Connection points counted
as number of modules
QCPU
QJ71
PB92V
Power
supply
module
DP-Slave
(FDL address 2)
DP-Slave
(FDL address 1)
DP-Slave
(FDL address 30)
DP-Slave
(FDL address 32)
DP-Slave
(FDL address 31)
DP-Slave : 30 modules
DP-Slave : 31 modules
DP-Slave
(FDL address 61)
*1
SYSTEM CONFIGURATION
2.2.2 PROFIBUS-DP network configuration examples
(1) Maximum configuration with no repeater connected
DP-Master (QJ71PB92V): 1
DP-Slaves: 31
DP-Master (Class 1) (FDL address 0)
Power
supply
module
Bus terminatorBus terminato
DP-Slave
(FDL address 1)
Figure 2.1 Maximum Configuration With No Repeater Connected
* 1 When using redundant CPUs, configure the network as shown in Section 2.3.
QCPU
*1
QJ71
PB92V
DP-Slave
(FDL address 2)
DP-Slave : 31 modules
: Connection points counted
as number of modules
Segment 1
(FDL address 31)
(2) Maximum configuration with a repeater connected
* 1 When using redundant CPUs, configure the network as shown in Section 2.3.
Figure 2.3 When 125 DP-Slaves are connected
(4) When multiple DP-Masters are connected (Multi-master system)
More than one DP-Master with different FDL addresses can be connected to the
same network.
SETTINGS AND
4
5
6
7
8
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
2.2 PROFIBUS-DP Network Configuration
2.2.2 PROFIBUS-DP network configuration examples
2 - 7
DEDICATED
INSTRUCTIONS
2
SYSTEM CONFIGURATION
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.1 PROFIBUS-DP network configuration
This section explains configuration of a redundant PROFIBUS-DP system in which the
QJ71PB92Vs are mounted.
For the redundant system using the QJ71PB92V, refer to Section 4.8.
(1) System equipment
The following table shows the equipment required for the redundant PROFIBUS-DP
system.
Table2.4 System Equipment
System EquipmentDescription
DP-Master (Class 1)
Configuration tool
DP-SlaveRedundant or non-redundant DP-Slave (such as the QJ71PB93D)
RepeaterRequired when 32 or more DP-Slaves are connected
PROFIBUS cable
Bus terminator
QJ71PB92V, function version D or later (Section 2.4)
GX Configurator-DP Version 7.00A or later
(To mount the QJ71PB92V on an extension base unit, use GX
Configurator-DP Version 7.03D or later.)
Section 5.5.1
2 - 8
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.1 PROFIBUS-DP network configuration
2
<
SYSTEM CONFIGURATION
(2) Network configuration
To use the QJ71PB92V in a redundant PROFIBUS-DP system configuration, the
following conditions must be met:
(a) Mounting the QJ71PB92V on a main base unit
1) Number of connectable modules in an entire network (When repeaters are
used)
Control system QJ71PB92V + Standby system QJ71PB92V + DP-Slaves
* 1 * 2
126
* 1 Up to 124 DP-Slaves are connectable.
* 2 A redundant DP-Slave may have two FDL addresses (for control and standby systems).
If all of the DP-Slaves are this type, the number of connectable DP-Slaves is 62.
2) Number of connectable modules per segment
Control system QJ71PB92V + Standby system QJ71PB92V + DP-Slaves +
* 1
<
Repeaters
* 1 A repeater are counted for both segments.
3) Max. no. of repeaters
Up to 3 repeaters can be used for communication between the QJ71PB92V
and any DP-Slave.
32
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
4) Number of connectable DP-Slaves per QJ71PB92V
Up to 124 DP-Slaves can be connected to a single QJ71PB92V.
(b) Mounting the QJ71PB92V on an extension base unit
The conditions of when the QJ71PB92V is mounted on an extension base unit are
the same as those of when the module is used in a single CPU system or multiple
CPU system. (Section 2.2.1)
SETTINGS AND
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
8
DEDICATED
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.1 PROFIBUS-DP network configuration
2 - 9
INSTRUCTIONS
2
r
SYSTEM CONFIGURATION
2.3.2 PROFIBUS-DP network configuration examples (QJ71PB92Vs
mounted on main base units)
(1) When using only non-redundant DP-Slaves
(a) Maximum Configuration With No Repeater Connected
DP-Master (QJ71PB92V): 2
DP-Slave: 30
: Connection points counted
as number of modules
Control system
DP-Master (Class 1)
(FDL address 0)
Standby system
DP-Master (Class 1)
(FDL address 1)
Power
supply
module
Bus terminator Bus terminato
Figure 2.4 Maximum Configuration with No Repeater Connected (Non-Redundant DP-Slaves Only)
Redundant
CPU
DP-Slave
(FDL address 2)
QJ71
PB92V
Tracking cable
DP-Slave
(FDL address 3)
DP-Slave : 30 modules
Power
supply
module
Segment 1
Redundant
CPU
(FDL address 31)
QJ71
PB92V
DP-Slave
2 - 10
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.2 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on main base units)
2
DP-Slave
(FDL address 2)
DP-Slave
(FDL address 3)
DP-Slave
(FDL address 30)
Bus terminatorBus terminator
Repeater 1
DP-Slave
(FDL address 31)
DP-Slave
(FDL address 32)
DP-Slave
(FDL address 61)
DP-Slave : 29 modules
Segment 1
Segment 2
DP-Slave : 31 modules
Tracking cable
Power
supply
module
Redundant
CPU
QJ71
PB92V
DP-Master (Class 1)
(FDL address 0)
: Connection points counted
as number of modules
Control system
Standby system
DP-Master (Class 1)
(FDL address 1)
Power
supply
module
Redundant
CPU
QJ71
PB92V
SYSTEM CONFIGURATION
(b) Maximum configuration with a repeater connected
DP-Master (QJ71PB92V): 2
DP-Slave: 60
Repeater: 1
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 2.5 Maximum Configuration with a Repeater Connected (Non-Redundant DP-Slaves Only)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
2.3.2 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on main base units)
2.3 Redundant System Configuration (Redundant CPUs Only)
Figure 2.8 When Using Redundant and Non-Redundant DP-Slaves
DP-Master (Class 1)
(FDL address 0)
Redundant
CPU
DP-Slave
DP-Slave
(FDL address 31)
QJ71
PB92V
Tracking cable
DP-Slave
(FDL address 3)
DP-Slave : 29 modules
DP-Slave
(FDL address 32)
DP-Slave : 30 modules
Standby system
Power
supply
module
Segment 1
Segment 2
DP-Master (Class 1)
(FDL address 1)
Redundant
DP-Slave
(FDL address 30)
DP-Slave
(FDL address 60)
CPU
QJ71
PB92V
Repeater 1-2
2 - 14
Using repeaters, redundant DP-Slaves and non-redundant ones must be
separately connected to different segments.
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.2 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on main base units)
2
SYSTEM CONFIGURATION
1
2.3.3 PROFIBUS-DP network configuration examples (QJ71PB92Vs
mounted on extension base units)
The network configuration examples of when the QJ71PB92V is mounted on an extension
base unit are the same as those of when the module is used in a single CPU system or
multiple CPU system. (Section 2.2.2)
For precautions on when the QJ71PB92V is mounted on an extension base unit, refer to
the following.
User's manual for the redundant system for the CPU module used
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
2.3 Redundant System Configuration (Redundant CPUs Only)
2.3.3 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on extension base units)
2 - 15
DEDICATED
INSTRUCTIONS
2
SYSTEM CONFIGURATION
2.4 Checking the Function Version and Serial No.
This section explains how to check the function version and serial No. of the QJ71PB92V.
(1) Checking the "Rating plate" on the side of the module
The serial No. and function version of the module are printed in the SERIAL section of
the rating plate.
Figure 2.9 Rating Plate
Serial number (first 5 digits)
Function version
Relevant regulation
standards
(2) Checking through GX Works2
The following explains how to check the serial No. and function version of the module
through GX Works2.
The serial No. and function version are displayed on the "Product information list" or
"Module's Detailed Information" window of GX Works2.
The procedure for checking the serial No. and function version on the "Product
information list" window is shown below.
Start Procedure
To display the window for checking the serial number and function version, select
[Diagnostics] [System monitor] and click the button in GX
Works2.
Product inf. list
2 - 16
Figure 2.10 Product Information List
2.4 Checking the Function Version and Serial No.
2
POINT
SYSTEM CONFIGURATION
[Serial No., Ver., Product No.]
• The serial No. of the module is displayed in the "Serial No." column.
• The function version of the module is displayed in the "Ver." column.
• The serial No. (Product No.) shown on the rating plate is displayed in the
"Product No." column.
Note that "-" is displayed in the "Product No." column for the QJ71PB92V since
this module is not supporting Product No. display.
* 1 The Product No. is displayed in the column only when the Universal model QCPU is used.
1
*1
OVERVIEW
2
The serial No. shown on the rating plate may not match with the one displayed on
Product information list of GX Works2.
• The serial No. on the rating plate indicates the management information
of the product.
• The serial No. displayed on Product inf. list of GX Works2 indicates the
functional information of the product.
The functional information of the product is updated when a new function
is added.
SETTINGS AND
3
4
5
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
2.4 Checking the Function Version and Serial No.
2 - 17
6
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
CHAPTER3 SPECIFICATIONS
This chapter explains the performance and transmission specifications of the QJ71PB92V.
For general specifications, refer to the user's manual (hardware design, maintenance and
inspection) for the CPU module used.
3.1 Performance Specifications
The performance specifications of the QJ71PB92V are given below.
Table3.1 Performance Specifications
ItemSpecifications
PROFIBUS-DP station typeDP-Master (Class 1)
Transmission specifications
Electrical standard/
characteristics
Medium
Network topologyBus topology (Tree topology when repeaters are used)
Data link method• Between DP-Master and DP-Slave: Polling method
Encoding methodNRZ
Transmission speed
Transmission distance
Max. No. of repeaters3 repeaters
Number of connectable
modules
(Per segment)
Number of connectable
modules
(Per network)
Max. No. of DP-Slaves
(Per QJ71PB92V)
I/O data
size
Number of writes to flash
ROM
No. of occupied I/O points32 (I/O assignment: 32 intelligent points)
Internal current consumption
(5VDC)
External dimensions98(3.86 in.) (H) x 27.4(1.08 in.) (W) x 90(3.54 in.) (D) [mm]
Weight0.13 kg
Input dataMax. 8192 bytes (Max. 244 bytes per DP-Slave)
Output data Max. 8192 bytes (Max. 244 bytes per DP-Slave)
EIA-RS485 compliant
Shielded twisted pair cable (Section 5.5.1)
*1
9.6 kbps to 12 Mbps ((1) in this section)
Differs depending on the transmission speed((1) in this section)
32 per segment (including repeater(s))
126 per network (total of DP-Masters and DP-Slaves (Section 2.2))
*2
125 per QJ71PB92V (Section 2.2)
Max. 100000 times
0.57 A
3 - 1
* 1 The transmission speed is controlled within 0.2%. (Compliant with IEC 61158-2)
* 2 Up to 124 DP-Slaves when QJ71PB92Vs are mounted on main base units in a redundant system
(Section 2.3)
3.1 Performance Specifications
3
Max. transmission distance [m/network] =
(Number of repeaters + 1) x Transmission distance [m/segment]
SPECIFICATIONS
(1) Transmission distance
Transmission SpeedTransmission Distance
9.6 kbps
93.75 kbps
187.5 kbps1000 m (3281 ft.)/segment4000 m (13123 ft.)/network
500 kbps400 m (1312 ft.)/segment1600 m (5249 ft.)/network
1.5 Mbps200 m (656 ft.)/segment800 m (2625 ft.)/network
3 Mbps
12 Mbps
* 1 The max. transmission distance in the table above is based on the case where 3 repeaters are
used.
The calculation formula for the transmission distance extended using a repeater(s) is:
Table3.2 Transmission Distance
1200 m (3937 ft.)/segment4800 m (15748 ft.)/network19.2 kbps
100 m (328 ft.)/segment400 m (1312 ft.)/network6 Mbps
Max. Transmission Distance when
Repeater is Used
*1
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.1 Performance Specifications
3 - 2
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
3.2 Function List
FunctionDescription
PROFIBUS-DPV0
I/O data exchange
Acquisition of
diagnostic and
extended diagnostic
information
Global control function
PROFIBUS-DPV1
Acyclic communication
with DP-Slaves
Alarm acquisition
PROFIBUS-DPV2
Time control over DP-
Slaves
Data swap function
Data consistency function
Output status setting for the
case of a CPU stop error
Temporary slave
reservation function
Redundant system support
function
QJ71PB92D-compatible
function
The following table summarizes a list of QJ71PB92V functions.
Table3.3 Function List
Up to 125 DP-Slaves can be connected to a single QJ71PB92V, enabling the I/O data
exchange of max. 8192 bytes.
Note that when QJ71PB92Vs are mounted on main base units in a redundant system,
up to 124 DP-Slaves can be connected.
Diagnostic or extended diagnostic information of an error occurred on a DP-Slaves
during I/O data exchange can be easily acquired using the buffer memory and I/O
signals.
By sending services (SYNC, UNSYNC, FREEZE, UNFREEZE) to each DP-Slave in a
group, synchronous control of DP-Slave I/O data is available.
This function allows data reading/writing to DP-Slaves at any specific timing
independently of I/O data exchange.
This function enables acquisition of up to 8 alarms or status information data that have
been generated on any DP-Slave.
This function allows the QJ71PB92V to operate as the time master and set the time of
each DP-Slave.
This function swaps the upper and lower bytes in word units when I/O data is sent and
received.
When I/O data from DP-Slaves are read from or written to the buffer memory, this
function prevents the I/O data from being separated and incorrectly mixed.
• Automatic refresh setting (GX Configurator-DP)
• Dedicated instructions (BBLKRD and BBLKWR instructions)
This function sets whether to stop or continue I/O data exchange with DP-Slaves when a
CPU stop error occurs on a QCPU or remote I/O station where the QJ71PB92V is
mounted.
When the QJ71PB92V is mounted to a redundant system, I/O data exchange with DP-
Slaves is continued regardless of the setting until systems A and B go down.
Without modifying the slave parameter in GX Configurator-DP, this function allows the
DP-Slave type to be changed to "Reserved station" temporarily.
When the control system CPU or the QJ71PB92V detects an error, the control and
standby systems are switched each other to continue communications.
This function is used to replace the QJ71PB92D with the QJ71PB92V.
When the QJ71PB92D has failed, replace it with the QJ71PB92V using the
QJ71PB92D-compatible function.
Reference
Section
Section 4.1.1
Section 4.1.2
Section 4.1.3
Section 4.2.1
Section 4.2.2
Section 4.3.1
Section 4.4
Section 4.5
Section 4.6
Section 4.7
Section 4.8
Section 4.9
3 - 3
3.2 Function List
3
SPECIFICATIONS
3.3 Input/Output Signals to/from Programmable Controller CPU
This section explains the input/output signals of the QJ71PB92V.
3.3.1 List of I/O signals
The following I/O signal assignment is based on the case where the start I/O No. of the
QJ71PB92V is "0000" (installed to slot 0 of the main base unit).
Device X represents input signals from the QJ71PB92V to the QCPU. Device Y represents
output signals from the QCPU to the QJ71PB92V.
The following shows the I/O signals to/from the QCPU.
Table3.4 List of I/O Signals
Signal Direction: QJ71PB92V QCPUSignal Direction: QCPU QJ71PB92V
Device No.Signal NameDevice No.Signal Name
X00Data exchange start completed signalY00Data exchange start request signal
X01Diagnostic information detection signalY01
X02Diagnostic information area cleared signalY02Diagnostic information area clear request signal
X03Use prohibitedY03Use prohibited
X04Global control completed signalY04Global control request signal
X05Global control failed signalY05Use prohibited
X06
X07
X08Y08
X09Y09
X0AY0A
X0BY0B
X0CData consistency requesting signalY0CData consistency start request signal
X0D
X0EY0E
X0FY0F
X10Operation mode signalY10
X11Operation mode change completed signalY11Operation mode change request signal
X12
X13Y13
X14Y14
X15Y15
X16Y16
X17Y17
X18Alarm read response signalY18Alarm read request signal
X19Time control start response signalY19Time control start request signal
Extended diagnostic information read response
signal
Use prohibited
Use prohibited
Use prohibited
Y06
Y07
Y0DRestart request signal
Y12
Diagnostic information detection reset request
signal
Extended diagnostic information read request
signal
Use prohibited
Use prohibited
Use prohibited
SETTINGS AND
1
2
3
4
5
6
7
SYSTEM
PROCEDURES BEFORE
OVERVIEW
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.1 List of I/O signals
(To the next page)
3 - 4
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
POINT
Remark
SPECIFICATIONS
Table3.4 List of I/O Signals (Continued)
Signal Direction: QJ71PB92V QCPUSignal Direction: QCPU QJ71PB92V
Device No.Signal NameDevice No.Signal Name
X1AUse prohibitedY1A
X1BCommunication READY signalY1B
X1CUse prohibitedY1C
X1DModule READY signalY1D
X1EUse prohibitedY1E
X1FWatchdog timer error signalY1F
Among the I/O signals for the QCPU, do not output (turn ON) the signals indicated
as "Use prohibited."
If any of the "Use prohibited" signals is output, the programmable controller
system may malfunction.
Use prohibited
For how to use the output signals to continue or reexecute respective functions in
event of system switching in the redundant system, refer to Section 7.9.
3 - 5
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.1 List of I/O signals
3
SPECIFICATIONS
3.3.2 Details of I/O signals
(1) Data exchange start request signal (Y00), data exchange start completed
signal (X00)
(a) Turn ON the Data exchange start request signal (Y00) to start I/O data exchange.
(b) When I/O data exchange is started after turning ON the Data exchange start
request signal (Y00), the Data exchange start completed signal (X00) turns ON.
The Data exchange start completed signal (X00) turns OFF in any of the following
cases:
• When the Data exchange start request signal (Y00) is turned OFF
• When an error causing stop of I/O data exchange occurs
• When parameters are currently being written to the QJ71PB92V from GX
Configurator-DP
• When the operation mode of the QJ71PB92V has been changed
• When a communication error has occurred on a DP-Slave. (Only when the
master parameter, "Error action flag" is checked)
Data exchange start
request signal (Y00)
Data exchange start request
Data exchange start
completed
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Data exchange start
completed signal (X00)
I/O data exchange
stopped
Figure 3.1 Data Exchange Start Request Signal (Y00), Data Exchange Start Completed Signal (X00)
(c) Use these signals as interlock signals when reading/writing I/O data.
(d) Write the initial values of the output data to the buffer memory before turning ON
the Data exchange start request signal (Y00).
(e) Turning OFF the Data exchange start request signal (Y00) clears the information
in the following areas.
The information in the other buffer memory areas is held.
• Slave status area (Normal communication detection) (Un\G23040 to
Un\G23047)
• Slave status area (Diagnostic information detection) (Un\G23056 to
Un\G23064)
Exchanging I/O data I/O data exchange
stopped
SETTINGS AND
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 6
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
(2) Diagnostic information detection reset request signal (Y01), Diagnostic
information detection signal (X01)
(a) The Diagnostic information detection signal (X01) turns ON when a
communication error is detected after the time preset in Diagnostic information
non-notification time setting area (Un\G2084) has elapsed.
The following processing is performed at the same time that the Diagnostic
information detection signal (X01) turns ON:
• The RSP ERR. LED turns ON.
• The diagnostic information is stored in the Diagnostic information area (for
mode 3) (Un\G23072 to Un\G23321).
The extended diagnostic information is stored in the Extended diagnostic
information area (for mode 3) (Un\G23328 to Un\G23454).
• The corresponding bit in the Slave status area (Diagnostic information
detection) (Un\G23056 to Un\G23064) of the station that sent the diagnostic
information turns ON.
• The error information of the QJ71PB92V is stored in the Local station error
information area (Un\G23071).
(b) Turning ON the Diagnostic information detection reset request signal (Y01) turns
OFF the Diagnostic information detection signal (X01).
The following processing is performed at the same time that the Diagnostic
information detection signal (X01) turns OFF:
• The RSP ERR. LED turns OFF.
• The corresponding bit in the slave status area (Diagnostic information
detection) (Un\G23056 to Un\G23064) of the station that sent the diagnostic
information turns ON.
(c) When new diagnostics information is generated while the Diagnostic information
detection reset request signal (Y01) is ON, the behavior is as follows:
• The Diagnostic information detection signal (X01) does not turn ON.
• The RSP ERR. LED does not turn ON.
• The corresponding bit in the Slave status area (Diagnostic information
detection) (Un\G23056 to Un\G23064) of the station that sent the diagnostic
information does not turn ON.
(d) After the Diagnostic information detection signal (X01) turns OFF, take actions for
the error cause and turn OFF the Diagnostic information detection reset request
signal (Y01).
3 - 7
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3
Remark
SPECIFICATIONS
(e) After the Diagnostic information detection signal (X01) is turned OFF, the
QJ71PB92V checks for diagnostic information again.
If any diagnostic information has been generated, the Diagnostic information
detection signal (X01) turns ON, and processing at (a) is performed.
1
OVERVIEW
Diagnostic information
Diagnostic information detection
reset request signal (Y01)
Diagnostic information
detection signal (X01)
Reads diagnostic, extended
diagnostic or local station error
information from buffer memory.
Diagnostic information area (for mode 3) (Un\G23072 to Un\G23321)
1
Extended diagnostic information area (for mode 3) (Un\G23328 to Un\G23454)
Local station error information area (Un\G23071)
Figure 3.2 Diagnostic Information Detection Reset Request Signal (Y01), Diagnostic Information
detection reset
Error detection
1
Detection Signal (X01)
MOV/FROM
instruction
Turning ON the Diagnostic information detection reset request signal (Y01) does
not clear the information shown below.
To clear the following information, turn ON the Diagnostic information area clear
request signal (Y02).
• Diagnostic information area (for mode 3) (Un\G23072 to Un\G23321)
• Extended diagnostic information area (for mode 3) (Un\G23328 to Un\G23454)
• Local station error information area (Un\G23071)
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 8
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
SPECIFICATIONS
(3) Diagnostic information area clear request signal (Y02), Diagnostic
information area cleared signal (X02)
(a) Turn ON the Diagnostic information area clear request signal (Y02) when clearing
the following information:
• Diagnostic information area (for mode 3) (Un\G23072 to Un\G23321)
• Extended diagnostic information area (for mode 3) (Un\G23328 to
Un\G23454)
• Local station error information area (Un\G23071)
(b) When the Diagnostic information area clear request signal (Y02) is turned ON,
and the processing at (a) is completed, the Diagnostic information area cleared
signal (X02) turns ON.
(c) When new diagnostics information is generated while the Diagnostic information
area clear request signal (Y02) is ON, the following information stays cleared. (No
diagnostic, extended diagnostic or local station error information is stored.)
• Diagnostic information area (for mode 3) (Un\G23072 to Un\G23321)
• Extended diagnostic information area (for mode 3) (Un\G23328 to
Un\G23454)
• Local station error information area (Un\G23071)
(d) After the Diagnostic information area cleared signal (X02) has turned ON, turn
OFF the Diagnostic information area clear request signal (Y02).
(e) Taking corrective actions for the error and turning OFF the Diagnostic information
area clear request signal (Y02) turns OFF the Diagnostic information area cleared
signal (X02).
(f) After the Diagnostic information area clear request signal (Y02) is turned OFF, the
QJ71PB92V checks for diagnostic information again.
If any diagnostic information has been generated, the diagnostic information,
extended diagnostic information and/or local station error information is stored in
the buffer memory.
Diagnostic information area
clear request signal (Y02)
Diagnostic information area
cleared signal (X02)
Figure 3.3 Diagnostic Information Area Clear Request Signal (Y02), Diagnostic Information Area Cleared
Clear request
Clear completed
Signal (X02)
3 - 9
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3
SPECIFICATIONS
1
(4) Global control request signal (Y04), Global control completed signal
(X04)
(a) Turn ON the Global control request signal (Y04) when executing the global
control.
(b) When the Global control request signal (Y04) is turned ON, and global control
processing is completed, the Global control completed signal (X04) turns ON.
(c) After the Global control completed signal (X04) has turned ON, turn OFF the
Global control request signal (Y04).
(d) Turning OFF the Global control request signal (Y04) turns OFF the Global control
completed signal (X04).
(e) Turn ON the Global control request signal (Y04) while the Data exchange start
completed signal (X00) is ON.
If the Global control request signal (Y04) is turned ON with the Data exchange
start completed signal (X00) OFF, both of the Global control completed signal
(X04) and Global control failed signal (X05) turn ON.
Data exchange start completed
signal (X00)
Output data is written.
1
Writing of
output data
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Global control request signal (Y04)
Global control completed signal (X04)
Output data area (for mode 3) (Un\G14336 to Un\G18431)
1
Figure 3.4 Global Control Request Signal (Y04), Global Control Completed Signal (X04)
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 10
DEDICATED
INSTRUCTIONS
3
Remark
Global control request
Global control completed
Global control failed
Global control request signal (Y04)
Global control completed signal (X04)
Global control failed signal (X05)
SPECIFICATIONS
(5) Global control failed signal (X05)
(a) If the Global control request signal (Y04) is turned ON while the Data exchange
start completed signal (X00) is OFF, both the Global control completed signal
(X04) and Global control failed signal (X05) turn ON.
(b) The ON status of the Global control failed signal (X05) means that the global
control has failed.
Remedy the cause of the error, and execute the global control again.
(c) Turning OFF the Global control request signal (Y04) turns OFF the Global control
failed signal (X05).
Figure 3.5 Global Control Failed Signal (X05)
For details on the global control, refer to Section 4.1.3.
3 - 11
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3
Remark
Extended diagnostic information
read completed
Extended diagnostic
information read request
Extended diagnostic
information read request
signal (Y06)
Extended diagnostic
information read response
signal (X06)
SPECIFICATIONS
1
(6) Extended diagnostic information read request signal (Y06), Extended
diagnostic information read response signal (X06)
(a) Turn ON the Extended diagnostic information read request signal (Y06) when
reading the extended diagnostic information of the FDL address specified in the
Extended diagnostic information read request area (Un\G23456).
(b) Turning ON the Extended diagnostic information read request signal (Y06) clears
the information of the Extended diagnostic information read response area
(Un\G23457 to Un\G23583).
(c) When the Extended diagnostic information read request signal (Y06) is turned
ON, and reading of the extended diagnostic information of the specified FDL
address is completed, the Extended diagnostic information read response signal
(X06) turns ON.
(d) After the Extended diagnostic information read response signal (X06) has turned
ON, turn OFF the Extended diagnostic information read request signal (Y06).
(e) Turning OFF the Extended diagnostic information read request signal (Y06) turns
OFF the Extended diagnostic information read response signal (X06).
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Figure 3.6 Extended Diagnostic Information Read Request Signal (Y06), Extended Diagnostic Information
Read Response Signal (X06)
For details on acquisition of extended diagnostics information, refer to Section
4.1.2.
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 12
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
(7) Data consistency start request signal (Y0C), Data consistency
requesting signal (X0C)
(a) The Data consistency start request signal (Y0C) is used to enable the data
consistency function for dedicated instructions.
Table3.5 Data Consistency Start Request Signal (Y0C)
ON/OFF StatusDescription
Enables read/write executed by dedicated instructions.
ON
OFF
Turning ON the Data consistency start request signal
(Y0C) turns ON the Data consistency requesting
signal (X0C).
Disables read/write executed by dedicated
instructions.
Turning OFF the Data consistency start request signal
(Y0C) turns OFF the Data consistency requesting
signal (X0C), and the BBLKRD and BBLKWR
instructions are not executed.
(b) Use the Data consistency start request signal (Y0C) and Data consistency
requesting signal (X0C) as interlock signals for dedicated instructions.
(c) When using the data consistency function (automatic refresh) by the GX
Configurator-DP, turn OFF the Data consistency start request signal (Y0C).
Data consistency
Data consistency start
request signal (Y0C)
Data consistency
requesting signal (X0C)
Figure 3.7 Data Consistency Start Request Signal (Y0C), Data Consistency Requesting Signal (X0C)
start request
Data consistency
function enabled
(8) Restart request signal (Y0D)
(a) If the QJ71PB92V has gone down for some reason (the FAULT LED: ON, the
module READY signal (X1D): OFF), turning the Restart request signal (Y0D) OFF,
ON and OFF again restarts the QJ71PB92V.
(b) After the QJ71PB92V is restarted, the status is the same as the one after:
• The programmable controller is turned OFF and back ON again.
• The QCPU is reset.
3 - 13
(9) Operation mode signal (X10)
This signal indicates whether or not the current operation mode is Communication
mode (mode 3).
Table3.6 Operation Mode Signal (X10)
ON/OFF StatusDescription
ONOther than Communication mode (mode 3)
OFFCommunication mode (mode 3)
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3
POINT
Operation mode change request signal : Y11
Operation mode change completed signal : X11
MOV/FROM
instruction
Set an operation mode in
"Operation mode change
request area".
Check the result in "Operation
mode change result area" and
"Current operation mode".
Data exchange start request signal : Y00
Operation mode change result
MOV/TO
instruction
Operation mode change result area (Un\G2256)
SPECIFICATIONS
1
(10) Operation mode change request signal (Y11), Operation mode change
completed signal (X11)
(a) Turn ON the Operation mode change request signal (Y11) when changing the
operation mode to the one set in the Operation mode change request area
(Un\G2255).
The operation mode can be changed without resetting the QCPU.
(b) Turning ON the Operation mode change request signal (Y11) clears the
information of the Operation mode change result area (Un\G2256).
(c) The Operation mode change completed signal (X11) turns ON when the operation
mode is changed, and the result of the change is stored to the Operation mode
change result area (Un\G2256).
(d) Make sure that A300
change result area (Un\G2256), and turn OFF the Operation mode change
request signal (Y11).
(e) Turning OFF the Operation mode change request signal (Y11) turns OFF the
Operation mode change completed signal (X11).
H (Normally completed) is stored in the Operation mode
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Figure 3.8 Operation mode change request signal (Y11), Operation mode change completed signal (X11)
(1) Do not turn the power OFF or reset the QCPU during the operation mode
registration to the flash ROM by turning ON the Operation mode change
request signal (Y11).
Turn the power OFF or reset the QCPU after the Operation mode change
completed signal (X11) has turned ON.
If the power is turned OFF or the QCPU is reset by mistake, register the
operation mode to the flash ROM again.
(2) If the redundant CPU is in the Backup mode, the operation mode of the
QJ71PB92V cannot be changed.
An error code is stored in the Operation mode change result area
(Un\G2256). (Section 9.5.2)
The operation mode of the QJ71PB92V must be changed when the
redundant CPU is in Separate or Debug mode. (User's manual for the
redundant system for the CPU module used)
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 14
DEDICATED
INSTRUCTIONS
3
Remark
SPECIFICATIONS
(11) Alarm read request signal (Y18), Alarm read response signal (X18)
(a) Turn ON the Alarm read request signal (Y18) when reading alarms on the
specified DP-Slave according to the information set in the Alarm request area
(Un\G26432 to Un\G26434).
(b) Turning ON the Alarm read request signal (Y18) clears the information in the
Alarm response area (Un\G26446 to Un\G26768).
Note, however, that the information in the following areas are not cleared when
the alarm ACK request (request code: 1501
Buffer Memory Address
DEC (HEX)
26449 to 26484
(6751
26489 to 26524
(6779
26529 to 26564
(67A1
26569 to 26604
(67C9
26609 to 26644
(67F1
26649 to 26684
(6819
26689 to 26724
(6841
26729 to 26764
(6869
H) is executed:
Table3.7 Areas Not Cleared At Alarm ACK Request Execution
Description
H to 6774H)
H to 679CH)
H to 67C4H)
H to 67ECH)
H to 6814H)
H to 683CH)
H to 6864H)
H to 688CH)
Area to which alarm data of alarm data No.1 is stored
Area to which alarm data of alarm data No.2 is stored
Area to which alarm data of alarm data No.3 is stored
Area to which alarm data of alarm data No.4 is stored
Area to which alarm data of alarm data No.5 is stored
Area to which alarm data of alarm data No.6 is stored
Area to which alarm data of alarm data No.7 is stored
Area to which alarm data of alarm data No.8 is stored
(c) The Alarm read response signal (X18) turns ON when alarms on the specified
DP-Slave are read, and the execution result is stored to the Alarm response area
(Un\G26446 to Un\G26768).
(d) Read the alarm information from the Alarm response area (Un\G26446 to
Un\G26768), and turn OFF the Alarm read request signal (Y18).
(e) Turning OFF the Alarm read request signal (Y18) turns OFF, the Alarm read
response signal (X18).
For details on acquisition of alarms, refer to Section 4.2.2.
3 - 15
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3
Remark
SPECIFICATIONS
1
(12) Time control start request signal (Y19), Time control start response
signal (X19)
(a) Turn ON the Time control start request signal (Y19) when executing the time
control over DP-Slaves according to the information set in the Time control setting
request area (Un\G26784 to Un\G26792).
(b) Turning ON the Time control start request signal (Y19) clears the information in
the Time control setting response area (Un\G26800 to Un\G26812).
(c) The Time control start response signal (X19) turns ON when the time control over
DP-Slaves is executed, and the execution result is stored in the Time control
setting response area (Un\G26800 to Un\G26812).
(d) Read the execution result from the Time control setting response area
(Un\G26800 to Un\G26812), and turn OFF the Time control start request signal
(Y19).
(e) Turning OFF the Time control start request signal (Y19) turns OFF the Time
control start response signal (X19).
For details on time control over DP-Slaves, refer to Section 4.3.1.
(13) Communication READY signal (X1B)
(a) The Communication READY signal (X1B) turns ON when the Module READY
signal (X1D) turns ON and I/O data exchange is ready to be started. (The signal
turns ON only in the Communication mode (mode 3).)
2
3
4
5
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
(b) The signal turns OFF when an error disabling I/O data exchange occurs on the
QJ71PB92V.
(c) Use the signal as an interlock signal for when turning ON the Data exchange start
request signal (Y00).
(14) Module READY signal (X1D)
(a) This signal turns ON when the QJ71PB92V is started up. (This signal turns ON
regardless of the operation mode.)
(b) While the QJ71PB92V is not ready, this signal is OFF.
(15) Watchdog timer error signal (X1F)
(a) This signal turns ON when a watchdog timer error occurs on the QJ71PB92V.
(b) The Watchdog timer error signal (X1F) does not turn OFF until:
• The programmable controller is turned OFF and back ON again, or
• The QCPU is reset.
3.3 Input/Output Signals to/from Programmable Controller CPU
3.3.2 Details of I/O signals
3 - 16
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
SPECIFICATIONS
3.4 Buffer Memory
This section explains the buffer memories of the QJ71PB92V.
3.4.1 Buffer memory list
The following shows a list of the buffer memories that are used for transferring data
between the QJ71PB92V and the QCPU.
Address
DEC (HEX)
0 to 2079
(0
H to 81FH)
2080
(820
H)
2081
(821
H)
2082 to 2083
(822
H to 823H)
2084
(824
H)
2085
(825
H)
2086 to 2253
(826
H to 8CDH)
2254
(8CE
H)
2255
(8CF
H)
2256
(8D0
H)
2257
(8D1
H)
2258
(8D2
H)
2259
(8D3
H)
2260 to 2262
(8D4
H to 8D6H)
2263
(8D7
H)
2264
(8D8
H)
System area (Use prohibited)
Diagnostic information invalid
setting area
Global control area
System area (Use prohibited)
Diagnostic information nonnotification time setting area
Current diagnostic information
non-notification time area
System area (Use prohibited)
Current operation mode area
Operation mode change request
area
Operation mode change result
area
Local FDL address display area
Offline test status area
Flash ROM storage mode
System area (Use prohibited)
Control master FDL address
display area
Standby master FDL address
display area
Table3.8 Buffer Memory List
NameDescription
Values for masking (invalidating) diagnostic
information from DP-Slaves are set in this
area.
The global control function to be executed is
set in this area.
This area is used to set the time during which
no diagnostic information is notified after
communication start.
This area stores the time (remaining time)
during which no diagnostic information is
notified after communication start.
This area stores data of the currently operating
mode.
When executing the operation mode change
request, a desired operation mode is set in this
area.
This area stores the execution result of the
operation mode change request.
This area stores the FDL address of the local
station.
This area stores the details or result of the selfdiagnostic test.
This area stores the operation mode currently
stored in the flash ROM.
This area stores the FDL address of the
control system QJ71PB92V when it is used in
a redundant system.
This area stores the FDL address of the
standby system QJ71PB92V when it is used in
a redundant system.
Initial
value
02B9
0001
FFFE
FFFF
FFFF
Read/
Write
HR/W
0R/W
20R/W
0R
HR
HR/W
0R
HR
0R
HR
*2R
*2R
*1
Reference
Section
Section
3.4.6
Section
3.4.9
Section
3.4.6
Section
3.4.6
Section
3.4.2
Section
3.4.3
Section
3.4.3
Section
3.4.2
Section
3.4.2
Section
3.4.2
Section
3.4.14
Section
3.4.14
3 - 17
* 1 This indicates whether or not read/write is possible from the sequence program.
R: Read only, R/W: Read/write executable
* 2 The initial value varies depending on the QCPU installed with the QJ71PB92V or the parameter.
(Section 3.4.14)
(To the next page)
3.4 Buffer Memory
3.4.1 Buffer memory list
3
SPECIFICATIONS
Address
DEC (HEX)
2265 to 2271
(8D9
H to 8DFH)
2272
(8E0
2273
(8E1
2274
(8E2
2275 to 6143
(8E3
H to 17FFH)
6144 to 10239
(1800
H to 27FFH)
10240 to 14335
(2800
H to 37FFH)
14336 to 18431
(3800
H to 47FFH)
18432 to 22527
(4800
H to 57FFH)
22528 to 22777
(5800
H to 58F9H)
22778 to 22783
(58FA
H to 58FFH)
22784 to 22908
(5900
H to 597CH)
22909 to 22911
(597D
H to 597FH)
22912 to 23036
(5980
H to 59FCH)
23037 to 23039
(59FD
H to 59FFH)
23040 to 23047
(5A00
H to 5A07H)
23048 to 23055
(5A08
H to 5A0FH)
23056 to 23064
(5A10
H to 5A18H)
23065 to 23070
(5A19
H to 5A1EH)
23071
(5A1FH)
23072 to 23321
(5A20
H to 5B19H)
1
Table3.8 Buffer Memory List (Continued)
NameDescription
System area (Use prohibited)
H)
H)
H)
Current bus cycle timeThis area stores the current bus cycle time.0R
Min. bus cycle time
Max. bus cycle time
System area (Use prohibited)
Input data area (for mode 3)
System area (Use prohibited)
Output data area (for mode 3)
System area (Use prohibited)
Address information area
(for mode 3)
System area (Use prohibited)
Input data start address area
(for mode 3)
System area (Use prohibited)
Output data start address area
(for mode 3)
System area (Use prohibited)
Slave status area (Normal
communication detection)
Slave status area (Reserved
station setting status)
Slave status area (Diagnostic
information detection)
System area (Use prohibited)
Local station error information
area
Diagnostic information area
(for mode 3)
* 1 This indicates whether or not read/write is possible from the sequence program.
R: Read only, R/W: Read/write executable
This area stores the minimum value of the bus
cycle time.
This area stores the maximum value of the bus
cycle time.
In Communication mode (mode 3), this area is
used to store the input data received from each
DP-Slave.
In Communication mode (mode 3), this area is
used to set the output data to be sent to each
DP-Slave.
In Communication mode (mode 3), this area is
used to store the FDL address of each DP-
Slave and I/O data length.
In Communication mode (mode 3), this area is
used to store the start address (buffer memory
address) of the input data of each DP-Slave.
In Communication mode (mode 3), this area is
used to store the start address (buffer memory
address) of the output data of each DP-Slave.
This area stores the communication status of
each DP-Slave.
This area stores the reserved or temporary
slave reservation setting of each DP-Slave.
This area stores the diagnostic information
generation status of each DP-Slave.
This area stores the error information of the
local station (QJ71PB92V).
In Communication mode (mode 3), this area is
used to store the diagnostic information of the
error occurred on each DP-Slave during
communication.
Initial
value
FFFF
Read/
Write*
0R
0R
0R
0R/W
HR
0R
0R
0R
0R
0R
0R
0R
Reference
1
(To the next page)
Section
Section
3.4.8
Section
3.4.8
Section
3.4.8
Section
3.4.4
Section
3.4.4
Section
3.4.4
Section
3.4.4
Section
3.4.4
Section
3.4.5
Section
3.4.5
Section
3.4.5
Section
3.4.2
Section
3.4.6
SETTINGS AND
2
3
4
5
6
7
8
SYSTEM
PROCEDURES BEFORE
OVERVIEW
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.4 Buffer Memory
3.4.1 Buffer memory list
3 - 18
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
Address
DEC (HEX)
23322 to 23327
(5B1A
H to 5B1FH)
23328 to 23454
(5B20
H to 5B9EH)
23455
(5B9F
23456
(5BA0
23457 to 23583
(5BA1
H to 5C1FH)
23584 to 23591
(5C20
H to 5C27H)
23592 to 23599
(5C28
H to 5C2FH)
23600 to 23607
(5C30
H to 5C37H)
23608 to 23615
(5C38
H to 5C3FH)
23616 to 23647
(5C40
H to 5C5FH)
23648 to 23656
(5C60
H to 5C68H)
23657 to 23663
(5C69
H to 5C6FH)
23664 to 23672
(5C70
H to 5C78H)
23673 to 23807
(5C79
H to 5CFFH)
23808
(5D00
23809 to 24832
(5D01
H to 6100H)
24833 to 25119
(6101
H to 621FH)
25120
(6220
25121 to 26144
(6221
H to 6620H)
NameDescription
System area (Use prohibited)
Extended diagnostic information
area (for mode 3)
System area (Use prohibited)
H)
Extended diagnostic information
H)
read request area
Extended diagnostic information
read response area
Parameter setting status area
(Active station)
Parameter setting status area
(Reserved station)
Temporary slave reservation
status area
Temporary slave reservation
request area
System area (Use prohibited)
System switching condition
setting area (Disconnected
station detection)
System area (Use prohibited)
System switching condition
setting result area (Disconnected
station detection)
System area (Use prohibited)
Acyclic communication request
H)
execution instruction area
Acyclic communication request
area
System area (Use prohibited)
Acyclic communication request
H)
result area
Acyclic communication response
area
* 1 This indicates whether or not read/write is possible from the sequence program.
Table3.8 Buffer Memory List (Continued)
In Communication mode (mode 3), this area is
used to store the extended diagnostic
information of the error occurred on each DP-
Slave during communication.
This area is used to set the FDL address of the
station from which the extended diagnostic
information is read.
This area stores the execution result of the
extended diagnostic information read request.
This area stores data of the DP-Slaves that are
set to Normal DP-Slave by the slave
parameters.
This area stores data of the DP-Slaves that are
set to Reserved station by the slave
parameters.
This area stores data of the DP-Slaves that are
set to Temporary slave reservation by the
temporary slave reservation function.
This area is used to set DP-Slaves to
Temporary slave reservation using the
temporary slave reservation function.
When the QJ71PB92V is mounted on a
redundant system, this area is used to set the
switching target DP-Slaves.
When the QJ71PB92V is mounted on a
redundant system, this area stores the
switching target DP-Slaves.
This area is used to set which request is to be
executed in acyclic communications.
This area is used to set the request data for
acyclic communications.
This area stores the request acceptance status
and execution completion status in acyclic
communications.
This area stores the execution result of acyclic
communication.
R: Read only, R/W: Read/write executable
Initial
value
Read/
Write
0R
FFFF
HR/W
0R
0R
0R
0R
0R/W
0R/W
0R
0R/W
0R/W
0R
0R
(To the next page)
*1
Reference
Section
Section
3.4.6
Section
3.4.7
Section
3.4.7
Section
3.4.5
Section
3.4.5
Section
3.4.5
Section
3.4.13
Section
3.4.14
Section
3.4.14
Section
3.4.10
Section
3.4.10
Section
3.4.10
Section
3.4.10
3 - 19
3.4 Buffer Memory
3.4.1 Buffer memory list
3
POINT
SPECIFICATIONS
Address
DEC (HEX)
26145 to 26415
(6621
H to 672FH)
26416 to 26424
(6730
H to 6738H)
26425 to 26431
(6739
H to 673FH)
26432 to 26434
(6740
H to 6742H)
26435 to 26445
(6743
H to 674DH)
26446 to 26768
(674E
H to 6890H)
26769 to 26783
(6891
H to 689FH)
26784 to 26792
(68A0
H to 68A8H)
26793 to 26799
(68A9
H to 68AFH)
26800 to 26812
(68B0
H to 68BCH)
26813 to 32767
(68BD
H to 7FFFH)
Table3.8 Buffer Memory List (Continued)
NameDescription
System area (Use prohibited)
Slave status area
(Alarm detection)
System area (Use prohibited)
Alarm request area
System area (Use prohibited)
Alarm response area
System area (Use prohibited)
Time control setting request area
System area (Use prohibited)
Time control setting response
area
System area (Use prohibited)
* 1 This indicates whether or not read/write is possible from the sequence program.
R : Read only, RW : Read/write executable
This area stores the alarm status of each DP-
Slave.
This area is used to set the request data for
alarm acquisition.
This area stores the execution result of alarm
acquisition.
This area is used to set the request data for
time control.
This area stores the execution result of time
control.
Initial
value
Read/
*1
Write
0R
0R/W
0R
0R/W
0R
Reference
Section
Section
3.4.5
Section
3.4.11
Section
3.4.11
Section
3.4.12
Section
3.4.12
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Do not write any data to "System area (Use prohibited)".
Doing so may cause the programmable controller system to malfunction.
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.4 Buffer Memory
3.4.1 Buffer memory list
3 - 20
DEDICATED
INSTRUCTIONS
3
POINT
SPECIFICATIONS
3.4.2 Local station information area
The information of the local station (QJ71PB92V) is stored in this area.
(1) Local station error information area (Un\G23071)
This area stores the error information of the local station (QJ71PB92V).
Table3.9 Local Station Error Information Area (Un\G23071)
Stored ValueDescription
0000HNormal
Other than 0000H
The information in the Local station error information area (Un\G23071) is not
cleared even if the problem occurred on the QJ71PB92V has been solved.
To clear the Local station error information area (Un\G23071), turn ON the
Diagnostic information area clear request signal (Y02).
Error (Error code ( Section 9.5.6 ))
(2) Current operation mode area (Un\G2254)
This area stores the current operation mode value.
Table3.10 Current Operation Mode Area (Un\G2254)
Stored ValueDescription
0001HParameter setting mode
0002HSelf-diagnostic mode
0003HCommunication mode (mode 3)
0009HFlash ROM initialization mode
0101H
0103H
* 1 Operation mode currently registered to flash ROM
Parameter setting mode
Communication mode (mode 3)
*1
*1
(3) Flash ROM storage mode (Un\G2259)
This area stores the operation mode currently stored to flash ROM.
Table3.11 Flash ROM Storage Mode (Un\G2259)
Stored ValueDescription
0101HParameter setting mode
0103HCommunication mode (mode 3)
FFFFHNot registered (No operation mode has been registered to the flash ROM.)
3 - 21
3.4 Buffer Memory
3.4.2 Local station information area
3
SPECIFICATIONS
1
(4) Local FDL address display area (Un\G2257)
The FDL address of the local station is stored.
Table3.12 Local FDL Address Display Area (Un\G2257)
Stored ValueDescription
0000H to 007DH
(0 to 125)
FFFFHParameter not set
* 1 When the QJ71PB92V is mounted on a redundant system, the following address is stored.
When it is in the control system: Control master FDL address
When it is in the standby system: Standby master FDL address
The FDL address of the local station
*1
(5) Offline test status area (Un\G2258)
The self-diagnostics test details or test result is stored in this area.
For details on the self-diagnostics test, refer to Section 5.4.
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SETTINGS AND
5
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.4 Buffer Memory
3.4.2 Local station information area
3 - 22
DEDICATED
INSTRUCTIONS
3
POINT
SPECIFICATIONS
3.4.3 Operation mode change area
This area is used to change the operation mode of the local station (QJ71PB92V).
For changing the operation mode, refer to Section 6.2.
(1) Operation mode change request area (Un\G2255)
For execution of the operation mode change request, set a desired operation mode.
(Initial value: FFFE
The initial value (FFFE
If the Operation mode change request signal (Y11) is turned ON with the initial value
stored in the Operation mode change request area (Un\G2255), E300
Operation mode change result area (Un\G2256) and the operation mode is not
changed.
Set ValueDescription
FFFFH
H)
H) is used for malfunction prevention.
Table3.13 Operation Mode Change Request Area (Un\G2255)
0001HThe mode is changed to Parameter setting mode.
0002HThe mode is changed to Self-diagnostics mode.
0003HThe mode is changed to Communication mode (mode 3).
0009HThe mode is changed to Flash ROM initialization mode.
The mode is changed to Parameter setting mode.
0101H
0103H
The Parameter setting mode is registered to the flash ROM at the same
time as the operation mode change.
The mode is changed to Communication mode (mode 3).
The Communication mode (mode 3) is registered to the flash ROM at the
same time as the operation mode change.
The mode is changed to Parameter setting mode.
The mode registered to the flash ROM is deleted at the same time as the
operation mode change.
H is stored in the
3 - 23
If the redundant CPU is in the Backup mode, the operation mode of the
QJ71PB92V cannot be changed.
An error code is stored in the Operation mode change result area (Un\G2256).
(Section 9.5.2)
The operation mode of the QJ71PB92V must be changed when the redundant
CPU is in Separate or Debug mode. (User's manual for the redundant
system for the CPU module used)
(2) Operation mode change result area (Un\G2256)
This area stores the execution result of the operation mode change request.
Table3.14 Operation Mode Change Result Area (Un\G2256)
Stored ValueDescription
A300HNormally completed
Other than A300H
3.4 Buffer Memory
3.4.3 Operation mode change area
Failed (Error code (Section 9.5.2))
3
POINT
SPECIFICATIONS
1
3.4.4 I/O data exchange area
This area is used for the I/O data exchange function.
OVERVIEW
(1) Data are assigned to the I/O data exchange area in the order of parameters
set in GX Configurator-DP (in the order of FDL addresses).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/OMapping" of GX Configurator-DP.
Order of assignment
(2) When parameters have been modified (deletion or addition of DP-Slave(s))
on GX Configurator-DP, the buffer memory is reassigned.
After modifying parameters, review the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (Section 6.5)
*1
(3) Input data of a DP-Slave
stored in the Input data area of the QJ71PB92V.
Data stored before the fault are held in the relevant Input data area for the
DP-Slave.
, which has failed in I/O data exchange, are not
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
* 1 DP-Slave corresponding to the bit that is turned OFF in the Slave status area (Normal
communication detection) (Un\G23040 to Un\G23047)
3.4 Buffer Memory
3.4.4 I/O data exchange area
3 - 24
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
POINT
b0b7b8b15
2nd byte of 1st module1st byte of 1st module
4th byte of 1st module3rd byte of 1st module
22nd byte of 1st module 21st byte of 1st module
23rd byte of 1st module
2nd byte of 2nd module 1st byte of 2nd module
4th byte of 2nd module
3rd byte of 2nd module
6th byte of 2nd module
5th byte of 2nd module
7th byte of 2nd module
00
H
00
H
Input data of 1st module
(Input data length:
23 bytes)
Input data of 2nd module
(Input data length:
7 bytes)
Input data of n-th module
6144(1800
H
)
6156(180C
H
)
6157(180D
H
)
6160(1810
H
)
10239(27FF
H
)
6156(180C
H
)
6155(180BH)
6144(1800
H
)
6145(1801
H
)
6160(1810
H
)
6157(180D
H
)
6158(180E
H
)
6159(180F
H
)
Address
DEC (HEX)
to
to
to
SPECIFICATIONS
(1) Input data area (for mode 3) (Un\G6144 to Un\G10239)
When the operation mode is Communication mode (mode 3), input data from DPSlaves are stored in this area.
(a) Data length setting
The data length (unit: byte) for each station is variable and assigned based on the
slave parameter ("Slave Modules" window) set using GX Configurator-DP.
For the DP-Slave that has a fixed data length, the slave parameter setting will be
ignored.
(b) Data length range
The maximum data length per module is 244 bytes, and the total data length for all
DP-Slaves can be set up to 8192 bytes.
When the data length is an odd number of bytes, 00
The input data of the next station is assigned starting from the next buffer memory
address.
H is stored to the final high byte.
3 - 25
Figure 3.9 Example of Input Data Assignment (1st module: 23 bytes, 2nd module: 7 bytes)
If a DP-Slave with no input data is assigned, its space in the input data area is
taken over by the next station with input data, as shown below.
Each DP-Slave setting
1st module
2nd module
3rd module
4th module
5th module
Input data : Set
Input data : None
Input data : Set
Input data : Set (Data length: 0)
Input data : Set
3.4 Buffer Memory
3.4.4 I/O data exchange area
Assignment result in Input data area of QJ71PB92V
6144(1800
H)
Because of no input data setting for 2nd
and 4th modules, no area is assigned for them
Input data of 1st module
Input data of 3rd module
Input data of 5th module
3
POINT
1st module
2nd module
3rd module
4th module
Output data of 1st module
Output data of 3rd module
5th module
Output data of 5th module
14336(3800
H)
Output data : Set
Output data : Set
Output data : Set
Each DP-Slave setting Assignment result in Output data area of QJ71PB92V
Because of no output data setting for 2nd
and 4th modules, no area is assigned for them
Output data : None
Output data : Set (Data length: 0)
SPECIFICATIONS
(2) Output data area (for mode 3) (Un\G14336 to Un\G18431)
When the operation mode is Communication mode (mode 3), output data to DPSlaves are set.
(a) Data length setting
The data length (unit: byte) for each station is variable and assigned based on the
slave parameter ("Slave Modules" window) set using GX Configurator-DP.
For the DP-Slave that has a fixed data length, the slave parameter setting will be
ignored.
1
OVERVIEW
2
Address
DEC (HEX)
14336(3800H)
to
14348(380CH
14349(380DH)
to
14352(3810H)
to
18431(47FFH)
Figure 3.10 Example of Output Data Assignment (1st module: 23 bytes, 2nd module: 7 bytes)
(b) Data length range
The maximum data length per module is 244 bytes, and the total data length for all
DP-Slaves can be set up to 8192 bytes.
When the data length is an odd number of bytes, the final high byte is occupied.
Set 00
H to the final high byte.
The output data of the next station is assigned starting from the next buffer address.
Output data of 1st module
(Output data length:
23 bytes)
)
Output data of 2nd module
(Output data length:
7 bytes)
Output data of n-th module
14336(3800H)
14337(3801
14347(380B
14348(380C
14349(380D
14350(380E
14351(380F
14352(3810
2nd byte of 1st module1st byte of 1st module
H
)
4th byte of 1st module3rd byte of 1st module
H
)
22nd byte of 1st module 21st byte of 1st module
H
)
H
)
2nd byte of 2nd module 1st byte of 2nd module
H
)
4th byte of 2nd module
H
)
6th byte of 2nd module
H
)
00
00
H
H
23rd byte of 1st module
3rd byte of 2nd module
5th byte of 2nd module
7th byte of 2nd module
SYSTEM
CONFIGURATION
3
b0b7b8b15
SPECIFICATIONS
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
SYSTEM OPERATION
6
If a DP-Slave with no output data is assigned, its space in the output data area is
taken over by the next station with output data, as shown below.
3.4 Buffer Memory
3.4.4 I/O data exchange area
3 - 26
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
(3) Address information area (for mode 3) (Un\G22528 to Un\G22777)
When the operation mode is Communication mode (mode 3), the FDL address and
I/O data length of each DP-Slave are stored in this area.
Information of 125 modules is stored in the Address information area (for mode 3) in
the same order for each module.
Information for reserved or temporary slave reservation is also stored.
Address
DEC (HEX)
22528(5800H)
22529(5801
22530(5802
22531(5803
to
22776(58F8H)
22777(58F9
FDL address of 1st module
H)
I/O data length of 1st module
FDL address of 2nd module
H)
I/O data length of 2nd module
H)
FDL address of 125th module
I/O data length of 125th module
H)
Figure 3.11 Address Information Area (for mode 3) (Un\G22528 to Un\G22777)
* 1 The difference between 00H and FFH is as follows:
00
FF
The FDL address of the 1st module is stored. (Initial value: FFFFH)
22528(5800H)
22529(5801
H means that input or output data are assigned with the data length set to 0.
H shows that assigned input or output data do not exist.
0000H to 007DH (0 to 125): FDL address
FFFFH : No FDL address assigned
The input data length of the 1st
module is stored. (Initial value:
FF
H) *1
H)
00
H to F4H : Input data
FF
H : Input data not assigned
length
(unit: byte)
The output data length of the 1st
module is stored. (Initial value:
FF
H) *1
00
00H to F4H : Output data
FF
H
H : Output data not assigned
b0b7b8b15
length
(unit: byte)
3 - 27
3.4 Buffer Memory
3.4.4 I/O data exchange area
3
22784(5900H)
1800H to 27FFH : Input data start address
: Input data not assigned
b0b15
Input data start address of 1st module
Input data start address of 2nd module
Input data start address of 125th module
FFFFH
The start address (buffer memory address) of the
input data of the 1st module is stored. (Initial value:
FFFF
H
)
22785(5901H)
22908(597C
H)
22528(5800
H)
Address
DEC (HEX)
to
22912(5980H)
3800H to 47FFH: Output data start address
: Output data not assigned
b0b15
Output data start address of 1st module
Output data start address of 2nd module
Output data start address of 125th module
FFFF
H
The start address (buffer memory address) of the
output data of the 1st module is stored.
(Initial value: FFFF
H
)
22913(5981H)
22036(59FC
H
)
22912(5980
H
)
Address
DEC (HEX)
to
SPECIFICATIONS
(4) Input data start address area (for mode 3) (Un\G22784 to Un\G22908)
When the operation mode is Communication mode (mode 3), the start address (buffer
memory address) for each DP-Slave's input data is stored in this area.
Creating a sequence program utilizing the Input data start address area (for mode 3)
(Un\G22784 to Un\G22908) allows address specification of the Input data area
without consideration of the input points for each DP-Slave.
Information of 125 modules is stored in the Input data start address area (for mode 3)
in the same order for each module.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 3.12 Input Data Start Address Area (for mode 3) (Un\G22784 to Un\G22908)
(5) Output data start address area (for mode 3) (Un\G22912 to Un\G23036)
When the operation mode is Communication mode (mode 3), the start address (buffer
memory address) for each DP-Slave's output data is stored in this area.
Creating a sequence program utilizing the Output data start address area (for mode 3)
(Un\G22912 to Un\G23036) allows address specification of the Output data area
without consideration of the output points for each DP-Slave.
Information of 125 modules is stored in the Output data start address area (for mode
3) in the same order for each module.
Figure 3.13 Output Data Start Address Area (for mode 3) (Un\G22912 to Un\G23036)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.4 Buffer Memory
3.4.4 I/O data exchange area
PROGRAMMING
8
DEDICATED
INSTRUCTIONS
3 - 28
3
POINT
SPECIFICATIONS
3.4.5 Slave status area
This area stores the operation status of each DP-Slave.
(1) The corresponding bits of the Slave status area are assigned in order of the
parameters set in GX Configurator-DP (in order of the FDL address).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/OMapping" of GX Configurator-DP.
Order of assignment
(2) When parameters have been modified (deletion or addition of DP-Slave(s))
on GX Configurator-DP, the buffer memory is reassigned.
After modifying parameters, review the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (Section 6.5)
3 - 29
3.4 Buffer Memory
3.4.5 Slave status area
3
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123 12211311412111 5116117118119120
44454348424633344135363738394047
108109107112106110979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
1 Bits b15 to b13 of address 23047 (5A07H) are fixed to 0.
Each bit indicates
the n-th DP-Slave.
1
11
23040(5A00
H
)
23041(5A01
H
)
23043(5A03
H
)
23044(5A04
H
)
23047(5A07
H
)
23046(5A06
H
)
23045(5A05
H
)
23042(5A02
H
)
Address
DEC (HEX)
SPECIFICATIONS
(1) Slave status area (Normal communication detection) (Un\G23040 to
Un\G23047)
The communication status of each DP-Slave is stored in this area. (Initial value:
0000
H)
When the Data exchange start request signal (Y00) is turned OFF, all the information
of the Slave status area (Normal communication detection) (Un\G23040 to
Un\G23047) is cleared.
0: I/O data communication error, or no communication (including reserved, temporary
slave reservation and/or not-configured stations)
1: Exchanging I/O data
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 3.14 Slave Status Area (Normal communication detection) (Un\G23040 to Un\G23047)
Turning ON the Data exchange start request signal (Y00) updates the information in
the Slave status area (Normal communication detection) (Un\G23040 to Un\G23047),
turning ON (1) the bits of the DP-Slave currently exchanging I/O data.
Data exchange start
request signal
Slave status area
(Normal communication detection)
Figure 3.15 Operation in Slave Status Area (Normal communication detection) (When I/O data exchange
When an I/O data communication error occurs on a DP-Slave, the corresponding bit
turns OFF (0), and it turns ON (1) again when normal status is restored.
Data exchange start
request signal
Slave status area
(Normal communication detection)
Figure 3.16 Operation in Slave Status Area (Normal communication detection) (When I/O data exchange
3.4 Buffer Memory
3.4.5 Slave status area
(Y00)
OFF
(Y00)
OFF
OFF
OFF
I/O data exchange
error occurred
ON
ON
is normal)
ON
ON
error occurred)
Restored from I/O
data exchange error
3 - 30
SETTINGS AND
4
5
6
7
8
DEDICATED
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123 122113114121115116117118119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
23049(5A09H)
23054(5A0EH)
23052(5A0CH)
23048(5A08H)
23053(5A0DH)
23051(5A0BH)
23050(5A0AH)
23055(5A0FH)
1 Bits b15 to b13 of address 23055 (5A0FH) are fixed to 0.
Results stored in Slave status area (Reserved station setting status) (Un\G23048 to Un\G23055)
SPECIFICATIONS
(2) Slave status area (Reserved station setting status) (Un\G23048 to
Un\G23055)
This area stores the reserved or temporary slave reservation setting of each DPSlave. (Initial value: 0000
0: Normal DP-Slave or not-configured station
1: Reserved or temporary slave reservation
H)
Figure 3.17 Slave Status Area (Reserved station setting status) (Un\G23048 to Un\G23055)
When the Data exchange start completed signal (X00) is turned ON, the data in the Slave
status area (Reserved station setting status) (Un\G23048 to Un\G23055) are updated.
The following is an example.
Figure 3.18 An Example in Slave Status Area (Reserved Station Setting Status)
3 - 31
3.4 Buffer Memory
3.4.5 Slave status area
3
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123112211311412111 511611 7118119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
1 Bits b15 to b13 of address 23064 (5A18H) are fixed to 0.
23057(5A11
H)
Each bit indicates
the n-th DP-Slave.
23058(5A12H)
23059(5A13H)
23060(5A14H)
23061(5A15H)
23062(5A16
H
)
23063(5A17H)
23064(5A18H)
11
Address
DEC(HEX)
SPECIFICATIONS
(3) Slave status area (Diagnostic information detection) (Un\G23056 to
Un\G23064)
The information on diagnostic status of each DP-Slave is stored in this area.
When the Data exchange start request signal (Y00) is turned OFF, all the information
of the Slave status area (Diagnostic information detection) (Un\G23056 to
Un\G23064) is cleared.
(a) All stations' diagnostic status (Un\G23056)
This area stores the diagnostic information detection status of all DP-Slaves.
(Initial value: 0000
If diagnostic information is detected in any one of the stations in Each station's
diagnostic status (Un\G23057 to Un\G23064), 1 is stored in All stations' diagnostic
status (Un\G23056).
0: All DP-Slaves normal
1: Diagnostic error information detected
H)
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(b) Each station's diagnostic status (Un\G23057 to Un\G23064)
This area stores the diagnostic information detection status of each DP-Slave.
(Initial value: 0000
H)
0: Normal (including reserved, temporary slave reservation and/or not-configured
stations)
1: Diagnostic information detected
Figure 3.19 Each Station's Diagnostic Status (Un\G23057 to Un\G23064)
SETTINGS AND
4
5
6
PROCEDURES BEFORE
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.4 Buffer Memory
3.4.5 Slave status area
3 - 32
7
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
Address
DEC(HEX)
23584(5C20
H)
23585(5C21
H)
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123*112211311 4121115116117118119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
23588(5C24
H)
23587(5C23
H)
23586(5C22
H)
23589(5C25
H)
23590(5C26
H)
23591(5C27
H)
*1 The bits, b15 to b13 of address 23591 (5C27
H) are fixed to 0.
Each bit represents
the n-th DP-Slave
*1 *1
Address
DEC(HEX)
23592(5C28
H)
23593(5C29
H)
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123*112211311 412111511 611711 8119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
23596(5C2C
H)
23595(5C2B
H)
23594(5C2A
H)
23597(5C2D
H)
23598(5C2E
H)
23599(5C2F
H)
*1 The bits, b15 to b13 of address 23599 (5C2F
H) are fixed to 0.
Each bit represents
the n-th DP-Slave
*1 *1
SPECIFICATIONS
(4) Parameter setting status area (Active station) (Un\G23584 to Un\G23591)
This area stores data of the DP-Slaves that are set to Normal DP-Slave by the slave
parameters. (Initial value: 0000
The set data are stored when the Communication READY signal (X1B) turns ON.
0: Reserved or not-configured station
1: Normal DP-Slave
H)
Figure 3.20 Parameter setting status area (Active station) (Un\G23584 to Un\G23591)
(5) Parameter setting status area (Reserved station) (Un\G23592 to
Un\G23599)
This area stores data of the DP-Slaves that are set to Reserved station by the slave
parameters. (Initial value: 0000
The set data are stored when the Communication READY signal (X1B) turns ON.
0: Normal DP-Slave or not-configured station
1: Reserved station
H)
Figure 3.21 Parameter setting status area (Reserved station) (Un\G23592 to Un\G23599)
3 - 33
3.4 Buffer Memory
3.4.5 Slave status area
3
Address
DEC(HEX)
23600(5C30
H)
23601(5C31
H)
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123*112211311 412111511 611711 8119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
23604(5C34
H)
23603(5C33
H)
23602(5C32
H)
23605(5C35
H)
23606(5C36
H)
23607(5C37
H)
*1 The bits, b15 to b13 of address 23607 (5C37
H) are fixed to 0
Each bit represents
the n-th DP-Slave
*1 *1
SPECIFICATIONS
(6) Temporary slave reservation status area (Un\G23600 to Un\G23607)
This area stores data of the DP-Slaves that are set to temporary slave reservation by
the temporary slave reservation function. (Initial value: 0000
The setting is stored when the Data exchange start completed signal (X00) turns ON.
(Section 3.4.13)
0: Normal DP-Slave, reserved or not-configured station
1: Temporary slave reservation
H)
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 3.22 Temporary slave reservation status area (Un\G23600 to Un\G23607)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.4 Buffer Memory
3.4.5 Slave status area
3 - 34
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124125123 122113114121115116117118119120111
44454348424633344135363738394047
108109107112106110979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
26417(6731
H
)
Each bit indicates
the n-th DP-Slave.
26418(6732
H
)
26419(6733
H
)
26420(6734
H
)
26421(6735
H
)
26422(6736
H
)
26423(6737
H
)
26424(6738
H
)
1 Bits b15 to b13 of address 26424 (6738H) are fixed to 0.
Address
DEC (HEX)
SPECIFICATIONS
(7) Slave status area (Alarm detection) (Un\G26416 to Un\G26424)
The information on alarm status of each DP-Slave is stored in this area.
(a) All stations' alarm status (Un\G26416)
This area stores the alarm detection status of all DP-Slaves. (Initial value: 0000
If an alarm is detected in any one of the stations in Each station's alarm status
(Un\G26417 to Un\G26424), 1 is stored in All stations' alarm status (Un\G26416).
0: No alarm in all DP-Slaves
1: Alarm detected
(b) Each station's alarm status (Un\G26417 to Un\G26424)
This area stores the alarm detection status of each DP-Slave. (Initial value:
0000
If an alarm is detected in any one of the stations and the corresponding bit turns
ON (1) in Each station's alarm status (Un\G26417 to Un\G26424), the RSP
ERR.LED turns ON.
H)
H)
0: No alarm (including reserved, temporary slave reservation, not-configured and/
or non-alarm-ready stations)
1: Alarm generated
Figure 3.23 Each Station's Alarm Status (Un\G26417 to Un\G26424)
3 - 35
3.4 Buffer Memory
3.4.5 Slave status area
3
POINT
Remark
SPECIFICATIONS
1
3.4.6 Diagnostic information area
This area stores diagnostic information settings and actual diagnostic information.
OVERVIEW
(1) Diagnostic information non-notification time setting area (Un\G2084)
The time during which no diagnostic information is notified after communication start
(after Data exchange start completed signal (X00) turns ON) is set in this area. (Initial
value: 20 seconds)
Table3.15 Diagnostic Information Non-notification Time Setting Area (Un\G2084)
Set ValueDescription
0 to 65535
This setting prevents temporary error detection. (e.g. when turning ON a DP-Slave
after turning ON the QJ71PB92V)
When diagnostic information is generated within the time duration set by this setting,
the conditions are as follows:
• The Diagnostic information detection signal (X01) does not turn ON.
• The RSP ERR. LED does not turn ON.
• No error code and detailed data is stored in the Diagnostic information area (for
mode 3) (Un\G2307 to Un\G23321) and/or Extended diagnostic information area
(for mode 3) (Un\G23328 to Un\G23454).
• The bit corresponding to the station that sent the diagnostic information does not
turn ON in the Slave status area (Diagnostic information detection) (Un\G23056
to Un\G23064).
Set the time during which diagnostic information is not notified.
(Unit: seconds)
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Set a value into the Diagnostic information non-notification time setting area
(Un\G2084) when the Data exchange start request signal (Y00) is OFF.
Values set with the Data exchange start request signal (Y00) ON are ignored.
The time (remaining time) during which no diagnostic information is notified after
communication start (after Data exchange start completed signal (X00) turns ON)
can be checked in the Current diagnostic information non-notification time area
(Un\G2085).
3.4 Buffer Memory
3.4.6 Diagnostic information area
3 - 36
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
SPECIFICATIONS
(2) Current diagnostic information non-notification time area (Un\G2085)
This area stores the remaining time during which no diagnostic information is notified
after communication start (after Data exchange start completed signal (X00) turns
ON). (initial value: 0 seconds)
The non-notification time is set in the Diagnostic information non-notification time
setting area (Un\G2084).
When the time set in the Diagnostic information non-notification time setting area
(Un\G2084) has elapsed after communication start (after Data exchange start completed
signal (X00) turns ON), the value in the Current diagnostic information non-notification
time area (Un\G2085) becomes 0.
While communication is stopped (Data exchange start request signal (Y00): OFF), the
remaining time is held until the Data exchange start request signal (Y00) is turned ON
again.
Table3.16 Current diagnostic Information Non-notification Time Area (Un\G2085)
Stored ValueDescription
A countdown time (remaining time), during which no diagnostic information
0 to 65535
is notified, is stored. (Unit: seconds)
No diagnostic information is notified until the value reaches 0.
3 - 37
3.4 Buffer Memory
3.4.6 Diagnostic information area
3
POINT
bitDescription
Initial
value
b15
b0Parameter transmission request from the DP-Slave
Diagnostic information read requestb1
Fixed to 0b2
b3The DP-Slave is monitored by the watchdog timer.
b4DP-Slave entered FREEZE mode.
b5DP-Slave entered SYNC mode.
b60 (Reserved)
b7
b8Unable to exchange I/O data with DP-Slaves.
b9The DP-Slave is not ready to exchange I/O data.
b10
b11Extended diagnostic information exists.
b12The function requested by the DP-Master is not supported.
Illegal response from DP-Slaveb13
b14Illegal parameter(s) sent from the DP-Master
Controlled by another DP-Master
1
0
0
1
1
1
0
1
0
1
0
0
0
0
0
0
b15 to b0
See below.
2080(820
H)
The parameter (No. of I/O bytes) received from the DP-Master
does not match that of the DP-Slave.
Excluded from I/O data exchange according to the parameter settings
Address
DEC (HEX)
SPECIFICATIONS
(3) Diagnostic information invalid setting area (Un\G2080)
Setting some values to this area can mask (invalidate) any data of the diagnostic
information that is sent from a DP-Slave during communication. (Initial value: 02B9
0: Validates the diagnostic information.
1: Invalidates the diagnostic information.
1
H)
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
Figure 3.24 Diagnostic Information Invalid Setting Area (Un\G2080)
Even if diagnostic information corresponding to each bit is generated on a DP-Slave,
it is not recognized as diagnostic information, and the status of the QJ71PB92V is as
follows:
• The Diagnostic information detection signal (X01) does not turn ON.
• The RSP ERR. LED does not turn ON.
• No error code and detailed data is stored in the Diagnostic information area (for
mode 3) (Un\G2307 to Un\G23321) and/or Extended diagnostic information area
(for mode 3) (Un\G23328 to Un\G23454).
• The bit corresponding to the station that sent the diagnostic information does not
turn ON in the Slave status area (Diagnostic information detection) (Un\G23056
to Un\G23064).
Set values into the Diagnostic information invalid setting area (Un\G2080) when
the Data exchange start request signal (Y00) is OFF.
Values set with the Data exchange start request signal (Y00) ON are ignored.
3.4 Buffer Memory
3.4.6 Diagnostic information area
3 - 38
SETTINGS AND
4
5
6
7
8
DEDICATED
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
Diagnostic information
area of 1st module
: Other extended diagnostic
information exists.
: No other extended
diagnostic information
exists.
The FDL address of the 1st
module is stored.
: Normal : Normal
b0b7b8b15
23072(5A20H)
23073(5A21H)
23074(5A22H)
23075(5A23H)
23320(5B18H)
23321(5B19H)
23072(5A20H)
23073(5A21H)
Diagnostic information
area of 2nd module
Diagnostic information
area of 125th module
The status 3 information (Whether
or not any extended diagnostic
information other than the one sent
this time is stored in the DP-Slave)
of the 1st module is stored.
(Initial value: 00
H)
00
H
(Initial value: 00H)
In the normal status, 00
H is stored.
00
H
Other than 00H :
00
H
80H
00H to 7DH (0 to 125): FDL address
The status 2 information of the 1st
module is stored.
(Initial value: 00
H)
The status 1 information of the 1st
module is stored.
(Initial value: 00
H)
Other than 00
H :
Address
DEC(HEX)
to
(b)
(b)
SPECIFICATIONS
(4) Diagnostic information area (for mode 3) (Un\G23072 to Un\G23321)
(a) This area stores the diagnostic information generated on DP-Slaves during
communication.
Information of 125 modules is stored in Diagnostic information area (for mode 3)
in the same order for each module.
3 - 39
Figure 3.25 Diagnostic Information Area (for mode 3) (Un\G23072 to Un\G23321)
3.4 Buffer Memory
3.4.6 Diagnostic information area
3
POINT
SPECIFICATIONS
(1) Data are assigned to the Diagnostic information area (for mode 3) in the order
of the parameters set in GX Configurator-DP (in the order of FDL addresses).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/OMapping" of GX Configurator-DP.
Order of assignment
(2) When parameters have been modified (deletion or addition of DP-Slave(s))
on GX Configurator-DP, the buffer memory is reassigned.
After modifying parameters, review the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (Section 6.5)
(3) The information in Diagnostic information area (for mode 3) (Un\G23072 to
Un\G23321) is not cleared even if the problem occurred on the DP-Slave has
been solved.
To clear the information in Diagnostic information area (for mode 3)
(Un\G23072 to Un\G23321), turn ON the Diagnostic information area clear
request signal (Y02).
1
2
3
4
5
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
3.4 Buffer Memory
3.4.6 Diagnostic information area
3 - 40
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
SPECIFICATIONS
(b) Information of status 1 and 2
The diagnostic information generated on DP-Slaves is stored to status 1 and 2,
and corresponding bits turn ON (1).
I/O data exchange between a DP-Master and DP-Slaves is continued even if any
of the following errors occurs.
The following table lists the meaning of each bit, actions to be taken, and the
station where the diagnostic information is detected.
Table3.17 Diagnostic Information
ItemBitDescriptionActionDetected in
(1) When I/O data exchange is started
Normally operating (This occurs every time I/O
Status 2
Status 1
Requesting transmission of parameters from DP-
b0
Slave
b1Diagnostic information read requestCheck the DP-Slave status.DP-Slave
b20 (Fixed)
b3The DP-Slave is monitored by the watchdog timer.Normally operatingDP-Slave
The parameter (No. of I/O bytes) received from the
b10
DP-Master does not match that of the DP-Slave.
b11 There is some extended diagnostic information.Check the DP-Slave status.DP-Master
The function requested by the DP-Master is not
b12
supported.
b13 Illegal response from DP-SlaveCheck the DP-Slave or network status.DP-Master
b14 Illegal parameter(s) sent from the DP-MasterCheck the parameters.DP-Slave
b15 Controlled by another DP-Master.
data exchange is started.)
(2) While I/O data are exchanged
Check the DP-Slave status and
communication line.
(1) When I/O data exchange is stopped
Normally operating(This occurs every time I/O
data exchange is stopped.)
(2) While I/O data are exchanged
Check if any parameter has been changed
from the DP-Master (Class 2) on the network.
Check the DP-Slave status and communication
line.
Check the parameters.
(1) When I/O data exchange is started
Normally operating (This occurs every time I/O
data exchange is started.)
(2) While I/O data are exchanged
Check the DP-Slave status and
communication line.
Check the slave parameters.DP-Slave
Check if the DP-Slave supports the global control
function or not.
Verify the DP-Slave specifications.
Check if more than one DP-Master are
communicating with the same DP-Slave.
Check the parameters.
DP-Slave
DP-Master
DP-Master
DP-Slave
DP-Slave
DP-Master
3 - 41
3.4 Buffer Memory
3.4.6 Diagnostic information area
3
POINT
23332(5B24H)
23329(5B21
H)
23454(5B9E
H)
23333(5B25
H)
23331(5B23
H)
80H : Other extended diagnostic information
exists.
The latest FDL address of the DP-Master is stored.
00
H to 7DH (0 to 125) : FDL address
23330(5B22H)
The latest information of status 1 is stored.
(Initial value : 00
H)
00
H : Normal
b0b7b8b15
The latest ident No. of the DP-Slave is stored. (Initial value : 0000H)
23328(5B20H)
0000
H to 007DH (0 to 125) : FDL address
The FDL address of the DP-Slave that notified of the latest extended diagnostic information in addresses
23329 to 23454 (5B21
H to 5B9EH), is stored. (Initial value: 0000H)
The data size of the latest extended diagnostic information in addresses 23330 to 23454 (5B22
H to 5B9EH)
is stored. (Initial value : 0000
H)
0006
H to 00F4H : Data size of extended diagnostic information (unit: byte)
The latest information of status 2 is stored.
(Initial value : 00
H)
00
H : Normal
Other than 00
H :
Other than 00
H :
(Initial value : 00
H)
For the DP-Slave that has not started I/O data
exchange, FF
H is stored.
The latest status 3 information (Whether or not any
extended diagnostic information other than the one
sent this time is stored in the DP-Slave) is stored.
(Initial value : 00
H)
00
H : No other extended diagnostic information
exists.
The latest extended diagnostic information (max. 244 bytes) is stored. (Initial value : 0000
H)
Address
DEC(HEX)
to
This section(4)(b)
This section(4)(b)
SPECIFICATIONS
(5) Extended diagnostic information area (for mode 3) (Un\G23328 to
Un\G23454)
This area stores the latest extended diagnostic information occurred during
communication.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 3.26 Extended Diagnostic Information Area (for mode 3) (Un\G23328 to Un\G23454)
(1) The information in Extended diagnostic information area (for mode 3)
(Un\G23328 to Un\G23454) is not cleared even if corrective action is taken for
the relevant error that has occurred on a DP-Slave.
To clear the information in Extended diagnostic information area (for mode 3)
(Un\G23328 to Un\G23454), turn ON the Diagnostic information area clear
request signal (Y02).
(2) When b11 of the Diagnostic information invalid setting area (Un\G2080) is set
to ON (1), information is not stored in the Extended diagnostic information
area (for mode 3) (Un\G23328 to Un\G23454).
3.4 Buffer Memory
3.4.6 Diagnostic information area
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
SYSTEM OPERATION
6
PARAMETER SETTING
7
PROGRAMMING
8
DEDICATED
INSTRUCTIONS
3 - 42
3
23461(5BA5H)
23458(5BA2
H)
23583(5C1F
H)
23462(5BA6
H)
23460(5BA4
H)
80H : Other extended diagnostic information
exists.
The FDL address of the DP-Master is stored.
(Initial value: 00
H)
For the DP-Slave that has not started I/O data
exchange, FF
H is stored.
00
H to 7DH (0 to 125) : FDL address
23459(5BA3H)
The information of status 1 is stored.
(Initial value: 00
H)
00
H : Normal
b0b7b8b15
The ident No. of the DP-Slave is stored. (Initial value : 0000H)
23457(5BA1H)
Other than A200
H : Failed (Error code )
The read result is stored. (Initial value : 0000
H)
The data size of the extended diagnostic information in addresses 23459 to 23583 (5BA3
H to 5C1FH) is stored.
(Initial value : 0000
H)
0006
H to 00F4H : Data size of extended diagnostic information (unit : byte)
The latest information of status 2 is stored.
(Initial value : 00
H)
00
H : Normal
Other than 00
H :
Other than 00
H :
The status 3 information (Whether or not any
extended diagnostic information other than the one
sent this time is stored in the DP-Slave) is stored.
(Initial value : 00
H)
00
H : No other extended diagnostic information
exists.
The extended diagnostic information (max. 244 bytes) is stored. (Initial value : 0000
H)
A200H : Normally completed
Address
DEC (HEX)
to
Section 9.5.1
Section 3.4.6 (4) (b)
Section 3.4.6 (4) (b)
SPECIFICATIONS
3.4.7 Extended diagnostic information read area
This area is used to read the extended diagnostic information from DP-Slaves.
(1) Extended diagnostic information read request area (Un\G23456)
Set the FDL address of the DP-Slave whose extended diagnostic information is to be
read. (Initial value: FFFF
Table3.18 Extended Diagnostic Information Read Request Area (Un\G23456)
Set ValueDescription
0000H to 007DH
(0 to 125)
By setting the FDL address is set in the Extended diagnostic information read request
area (Un\G23456) and turning ON the Extended diagnostic information read request
signal (Y06), the extended diagnostic information is stored in the Extended diagnostic
information read response area (Un\G23457 to Un\G23583).
H)
Set the FDL address of the DP-Slave.
(2) Extended diagnostic information read response area (Un\G23457 to
Un\G23583)
The execution result of the extended diagnostic information read request is stored in
this area.
If the request failed, the values in address 23458 to 23583(5BA2
H.
0
Figure 3.27 Extended Diagnostic Information Read Response Area (Un\G23457 to Un\G23583)
H to 5C1FH) become
3 - 43
3.4 Buffer Memory
3.4.7 Extended diagnostic information read area
3
SPECIFICATIONS
1
3.4.8 Bus cycle time area
This area stores the bus cycle time.
OVERVIEW
(1) Current bus cycle time (Un\G2272)
The current bus cycle time is stored in this area. (Unit: 1ms)
(2) Min. bus cycle time (Un\G2273)
The minimum value of the bus cycle time is stored in this area. (Unit: 1ms)
(3) Max. bus cycle time (Un\G2274)
The maximum value of the bus cycle time is stored in this area. (Unit: 1ms)
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
3.4 Buffer Memory
3.4.8 Bus cycle time area
3 - 44
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
bit
DescriptionInitial value
b15
b0Unused (Fixed to 0)
Unused (Fixed to 0)
Unused (Fixed to 0)
Unused (Fixed to 0)
b1
UNFREEZE (Retention of the actual input data is
disabled.)
b2
b3FREEZE (Actual input data is held and read.)
b4
UNSYNC (Retention of the actual input data is
disabled.)
b5SYNC (Actual output data is written and held.)
b6
b7
b8Executed on DP-Slaves in group 1
Executed on DP-Slaves in group 3
Executed on DP-Slaves in group 2
Executed on DP-Slaves in group 4
Executed on DP-Slaves in group 5
Executed on DP-Slaves in group 6
Executed on DP-Slaves in group 7
Executed on DP-Slaves in group 8
b9
b10
b11
b12
b13
b14
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
b15 to b0
See below.2081(821
H)
See (b).
See (c).
Reference Section
Address
DEC(HEX)
(c)
(b)
SPECIFICATIONS
3.4.9 Global control area
This area is used for the global control function.
(1) Global control area (Un\G2081)
(a) Set the global control function to be executed.
Specify the global control service to be sent by bits b5 to b2 in the Global control
area, and set the target group No. by bits b15 to b8. (Initial value: 0000
0: Not execute
1: Execute
H)
3 - 45
3.4 Buffer Memory
3.4.9 Global control area
Figure 3.28 Global Control Area (Un\G2081)
3
Remark
SPECIFICATIONS
(b) Setting global control services (b5 to b2)
The following service combinations are not executable at the same time.
• SYNC and UNSYNC (If both services are attempted concurrently, UNSYNC
• FREEZE and UNFREEZE (If both services are attempted concurrently,
The following shows the services and their set values for b5 to b2.
1) Setting for execution of the SYNC and UNSYNC services
* 1 When 1 is set to this bit, it is handled as an invalid value. (The operation is the same as when the
value is set to 0.)
only is enabled.)
UNFREEZE only is enabled.)
Table3.19 SYNC/UNSYNC Settings (b5, b4)
Service to be Executed
SYNC10
UNSYNC
Set Value
b5b4
* 1
0
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
1
2) Setting for execution of the FREEZE and UNFREEZE services
Table3.20 FREEZE/UNFREEZE Settings (b3, b2)
Service to be Executed
FREEZE10
UNFREEZE
* 1 When 1 is set to this bit, it is handled as an invalid value. (The operation is the same as when the
value is set to 0.)
Set Value
b3b2
* 1
0
(c) Setting the target group No. (b15 to b8)
Multiple group Nos. can be set for the target group No.
When 0s are set to all of b8 to b15, the set global control service is sent to all DPSlaves (including DP-Slaves for which group No. is not set).
For details on the global control, refer to Section 4.1.3.
SPECIFICATIONS
4
1
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
SYSTEM OPERATION
6
PARAMETER SETTING
3.4 Buffer Memory
3.4.9 Global control area
3 - 46
7
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
23809(5D01H)
23936(5D80
H)
23937(5D81
H)
24064(5E00
H)
24065(5E01
H)
24192(5E80
H)
24193(5E81
H)
24320(5F00
H)
24321(5F01
H)
24448(5F80
H)
24449(5F81
H)
24576(6000
H)
24577(6001
H)
24705(6081
H)
24832(6100
H)
24704(6080
H)
Request instruction No.1 area (Data size: 128 words)
Request instruction No.2 area (Data size: 128 words)
Request instruction No.3 area (Data size: 128 words)
Request instruction No.4 area (Data size: 128 words)
Request instruction No.5 area (Data size: 128 words)
Request instruction No.6 area (Data size: 128 words)
Request instruction No.7 area (Data size: 128 words)
Request instruction No.8 area (Data size: 128 words)
Address
DEC (HEX)
to
to
to
to
to
to
to
to
SPECIFICATIONS
3.4.10 Acyclic communication area
The area is used for acyclic communications.
(1) Acyclic communication request area (Un\G23809 to Un\G24832)
Set the request instruction of acyclic communication in this area. (Initial value: 0000H)
Up to eight request instructions can be set.
For the format for request instructions, refer to Section 7.4.
Figure 3.29 Acyclic Communication Request Area (Un\G23809 to Un\G24832)
3 - 47
3.4 Buffer Memory
3.4.10 Acyclic communication area
3
BitDescriptionInitial value
b0Execution instruction of request instruction No.1
Execution instruction of request instruction No.2
Execution instruction of request instruction No.3
Execution instruction of request instruction No.4
Execution instruction of request instruction No.5
Execution instruction of request instruction No.6
Execution instruction of request instruction No.7
Execution instruction of request instruction No.8
b1
b2
b3
b4
b5
b6
b7
0
0
0
0
0
0
0
0
See below.23808(5D00
H)
b7 to b0b15 to b8
00H (Fixed)
Address
DEC (HEX)
SPECIFICATIONS
(2) Acyclic communication request execution instruction area (Un\G23808)
Set the execution instruction for acyclic communication in this area.
When a bit is turned ON (1), the request instruction corresponding to the bit is
executed. (Initial value: 0000
H)
1
OVERVIEW
0: Not execute
1: Execute
Figure 3.30 Acyclic Communication Request Execution Instruction Area (Un\G23808)
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
3.4 Buffer Memory
3.4.10 Acyclic communication area
3 - 48
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
0
0
0
0
0
0
0
0
b15
b14
b13
b12
b11
b10
b9
Completion status of request instruction No.8
Completion status of request instruction No.7
Completion status of request instruction No.6
Completion status of request instruction No.5
Completion status of request instruction No.4
Completion status of request instruction No.3
Completion status of request instruction No.2
Completion status of request instruction No.1
b8
Initial valueDescription
Bit
0
0
0
0
0
0
0
0
Acceptance status of request instruction No.8
Acceptance status of request instruction No.7
Acceptance status of request instruction No.6
Acceptance status of request instruction No.5
Acceptance status of request instruction No.4
Acceptance status of request instruction No.3
Acceptance status of request instruction No.2
Acceptance status of request instruction No.1
Initial valueDescription
b7
b6
b5
b4
b3
b2
b1
b0
Bit
totob15b0b8 b7
AddressDEC
(HEX)
25120(6220
H)
1) The request acceptance status is stored.
0: Not accepted
1: Acceptance completed
2) The request completed status is stored.
0: Not executed or in execution
1: Execution completed
See 1) below.See 2) below.
SPECIFICATIONS
(3) Acyclic communication request result area (Un\G25120)
This area stores the request acceptance status and request execution completion
status of acyclic communication.
3 - 49
3.4 Buffer Memory
3.4.10 Acyclic communication area
Figure 3.31 Acyclic Communication Request Result Area (Un\G25120)
3
25121(6221H)
25248(62A0
H)
25633(6421H)
25760(64A0
H)
25889(6521
H)
26016(65A0
H)
25761(64A1
H)
25888(6520
H)
26017(65A1
H)
26144(6620
H)
25505(63A1
H)
25632(6420
H)
25377(6321
H)
25504(63A0
H)
25249(62A1
H)
25376(6320
H)
Response area for request instruction
No.1 (Data size: 128 words)
Response area for request instruction
No.2 (Data size: 128 words)
Response area for request instruction
No.3 (Data size: 128 words)
Response area for request instruction
No.4 (Data size: 128 words)
Response area for request instruction
No.5 (Data size: 128 words)
Response area for request instruction
No.6 (Data size: 128 words)
Response area for request instruction
No.7 (Data size: 128 words)
Response area for request instruction
No.8 (Data size: 128 words)
Address
DEC(HEX)
to
to
to
to
to
to
to
to
SPECIFICATIONS
(4) Acyclic communication response area (Un\G25121 to Un\G26144)
The execution result of acyclic communication is stored in this area. (Initial value:
H)
0000
For the response format for the execution result, refer to Section 7.4.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
4
FUNCTIONS
5
Figure 3.32 Acyclic Communication Response Area (Un\G25121 to Un\G26144)
3.4 Buffer Memory
3.4.10 Acyclic communication area
3 - 50
SETTINGS AND
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
SPECIFICATIONS
3.4.11 Alarm area
This area is used for the alarm acquisition.
(1) Alarm request area (Un\G26432 to Un\G26434)
Set request data for alarm acquisition in this area. (Initial value: 0000H)
For the request format, refer to Section 7.5.
(2) Alarm response area (Un\G26446 to Un\G26768)
The execution result of alarm acquisition is stored in this area. (Initial value: 0000H)
For the response format for the execution result, refer to Section 7.5.
3.4.12 Time control area
This area is used for the time control.
(1) Time control setting request area (Un\G26784 to Un\G26792)
Set request data for the time control setting in this area. (Initial value: 0000H)
For the request format, refer to Section 7.6.
(2) Time control setting response area (Un\G26800 to Un\G26812)
The execution result of the time control setting is stored in this area. (Initial value:
H)
0000
For the response format for the execution result, refer to Section 7.6.
3 - 51
3.4 Buffer Memory
3.4.11 Alarm area
3
POINT
SPECIFICATIONS
1
3.4.13 Temporary slave reservation area
This area is used for the temporary slave reservation function.
OVERVIEW
(1) The corresponding bits of the Temporary slave reservation area are assigned
in order of the parameters set in GX Configurator-DP (in order of the FDL
address).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/OMapping" of GX Configurator-DP.
Order of assignment
(2) When parameters have been modified (deletion or addition of DP-Slave(s)) in
GX Configurator-DP, the order of the assigned DP-Slaves is changed.
After modifying parameters, check the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (Section 6.5)
2
3
4
5
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Address
DEC(HEX)
23608(5C38
23609(5C39
23610(5C3A
23611(5C3B
23612(5C3C
23613(5C3D
23614(5C3E
23615(5C3F
(1) Temporary slave reservation request area (Un\G23608 to Un\G23615)
This area is used to set DP-Slaves to Temporary slave reservation using the
temporary slave reservation function. (Initial value: 0000
0: Not specify the DP-Slave to Temporary slave reservation
1: Specify the DP-Slave to Temporary slave reservation
b15 b14 b13 b12 b11 b10 b9 b8 b7
H)
H)
H)
H)
H)
H)
H)
H)
*1 *1 *1
*1 The bits, b15 to b13 of address 23615 (5C3F
Figure 3.33 Temporary slave reservation request area (Un\G23608 to Un\G23615)
12131116101412934567815
28292732263017182519202122232431
44454348424633344135363738394047
60615964586249505751525354555663
76777580747865667367686970717279
92939196909481828983848586878895
10810910711210611 0979810599100101102103104111
124125123 12211311412111 511611 711811 9120
b6 b5 b4 b3 b2 b1 b0
H) are fixed to 0.
H)
Each bit represents
the n-th DP-Slave
SETTINGS AND
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
3.4 Buffer Memory
3.4.13 Temporary slave reservation area
3 - 52
DEDICATED
INSTRUCTIONS
3
POINT
SPECIFICATIONS
When the Data exchange start request signal (Y00) is turned ON, the DP-Slaves
specified in the Temporary slave reservation request area (Un\G23608 to Un\G23615)
become temporary slave reservation.
Temporary slave reservation
request area
(Un\G23608 to Un\G23615)
Data exchange start request signal (Y00)
Data exchange start completed signal (X00)
Slave status area
(Reserved station setting status)
(Un\G23048 to Un\G23055)
and
Temporary slave reservation
status area
(Un\G23600 to Un\G23607)
Figure 3.34 Operation in Temporary Slave Reservation Request Area
OFF
OFF
Specifies temporary slave reservation(s)
ON
Executes
temporary slave
reservation
Stores status data
(1) Set values in the Temporary slave reservation request area (Un\G23608 to
Un\G23615) while the Data exchange start request signal (Y00) is OFF.
Values set with the Data exchange start request signal (Y00) ON are ignored.
(2) Normal DP-Slaves can be changed to Temporary slave reservations.
Changing Reserved stations (DP-Slaves set as reserved stations with slave
parameters) to Normal DP-Slave status is not allowed.
For the temporary slave reservation function, refer to Section 4.7.
ON
3 - 53
3.4 Buffer Memory
3.4.13 Temporary slave reservation area
3
POINT
Order of assignment
SPECIFICATIONS
3.4.14 Redundant system area
This area is used for the redundant system support function.
For details on the redundant system support function, refer to Section 4.8.
(1) The corresponding bits of the Redundant system area are assigned in order
of the parameters set in GX Configurator-DP (in order of the FDL address).
The actual order of assignment can be checked in Address information area
(for mode 3) (Un\G22528 to Un\G22777) or in "Documentation of I/OMapping" of GX Configurator-DP.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
(2) When parameters have been modified (deletion or addition of DP-Slave(s)) in
GX Configurator-DP, the order of the assigned DP-Slaves is changed.
After modifying parameters, check the sequence program.
If some DP-Slaves are expected to be connected to the network in the future,
setting them as Reserved stations in the parameter setting eliminates the
need to check the sequence program. (Section 6.5)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
3.4 Buffer Memory
3.4.14 Redundant system area
3 - 54
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
SPECIFICATIONS
(1) Control master FDL address display area (Un\G2263)
This area stores the FDL address of the control system QJ71PB92V when it is used in
a redundant system.
The FDL address is stored when the Communication READY signal (X1B) turns ON.
The FDL addresses for the control system are set in GX Configurator-DP.
(Section 6.3)
Table3.21 Control Master FDL Address Display Area (Un\G2263)
Set ValueDescription
0000H to 007DH
(0 to 125)
FFFFH
The FDL address of the QJ71PB92V in the control system
• Parameter not registered
• The QJ71PB92V is not mounted to a redundant system.
(2) Standby master FDL address display area (Un\G2264)
This area stores the FDL address of the standby system QJ71PB92V when it is used
in a redundant system.
The FDL address is stored when the Communication READY signal (X1B) turns ON.
The FDL addresses for the standby system are set in the Intelligent function module
switch setting of GX Works2. (Section 6.7)
Table3.22 Standby Master FDL Address Display Area (Un\G2264)
Set ValueDescription
0000H to 007DH
(0 to 125)
FFFFH
The FDL address of the QJ71PB92V in the standby system
• Parameter not registered
• The QJ71PB92V is not mounted to a redundant system.
3 - 55
3.4 Buffer Memory
3.4.14 Redundant system area
3
Data exchange start request signal (Y00)
OFF
ON
OFF
Specifies system switching condition
Data exchange start completed signal (X00)
System switching condition setting area
(Disconnected station detection)
(Un
\
G23648 to Un\G23656)
ON
Settings
system switching
condition
System switching condition setting result area
(Disconnected station detection)
(Un\G23664 to Un\G23672)
Stores result data
SPECIFICATIONS
(3) System switching condition setting area (Disconnected station
detection) (Un\G23648 to Un\G23656)
When the QJ71PB92V is mounted on a redundant system, this area is used to set the
switching target DP-Slaves. (Initial value: 0000
H)
1
OVERVIEW
Address
DEC(HEX)
23649(5C61
23650(5C62
23651(5C63
23652(5C64
23653(5C65
23654(5C66
23655(5C67
23656(5C68H)
(a) System switching condition (Un\G23648)
Set AND or OR as a condition for the setting in the System switching DP-Slave
specification (Un\G23649 to Un\G23656).
0: OR condition(If a communication error occurs on any of the specified DP-
Slaves, the systems are switched.)
1: AND condition (If a communication error occurs on all of the specified DP-
Slaves, the systems are switched.)
(b) System switching DP-Slave specification (Un\G23649 to Un\G23656)
Set the target DP-Slaves for the system switching. (Initial value: 0000
0: Not system switching target
1: System switching target
b15 b14 b13 b12 b11 b10 b9 b8 b7
H)
H)
H)
H)
H)
H)
H)
*1 *1 *1
*1 The bits, b15 to b12 of address 23656 (5C68
Figure 3.35 System switching DP-Slave specification (Un\G23649 to Un\G23656)
12131116101412934567815
28292732263017182519202122232431
44454348424633344135363738394047
60615964586249505751525354555663
76777580747865667367686970717279
92939196909481828983848586878895
108109107112106110979810599100101102103104111
124 123*112211311412111 511611711 8119120
b6 b5 b4 b3 b2 b1 b0
H) are fixed to 0.
By turning ON the Data exchange start request signal (Y00), the DP-Slaves
specified in the System switching condition setting area (Disconnected station
detection) (Un\G23648 to Un\G23656) become the target for system switching.
H)
Each bit represents
the n-th DP-Slave
SETTINGS AND
2
3
4
5
6
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
Figure 3.36 Operation in System Switching Condition Setting Area (Disconnected station detection)
3.4 Buffer Memory
3.4.14 Redundant system area
3 - 56
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
3
POINT
SPECIFICATIONS
System switching is performed when an error occurs in communication with a DPSlave, which is specified in the System switching condition setting area
(Disconnected station detection) (Un\G23648 to Un\G23656).
(1) Set values into the System switching condition setting area (Disconnected
station detection) (Un\G23648 to Un\G23656) when the Data exchange start
request signal (Y00) is OFF.
Values set with the Data exchange start request signal (Y00) ON are ignored.
(2) With a communication error identified in a system switching target DP-Slave
after system switching, no system switching is performed even if a
communication error occurs in another DP-Slave.
To perform system switching again, restore all of the switching target DP-
Slaves
The DP-Slave status can be confirmed in the Slave status area (Normal
communication detection) (Un\G23040 to Un\G23047). (Section 3.4.5)
* 1 It is any of all the DP-Slaves that are specified in the System switching DP-Slave specification area
(Un\G23649 to Un\G23656).
*1
to normal condition.
*1
Control system
New standby system
Power
supply
module
Bus terminator
Communication
Power
supply
module
Redundant
CPU
DP-Slave
(FDL address 2)
failure
Redundant
CPU
QJ71
PB92V
QJ71
PB92V
Executes system
switching
Tracking cable
DP-Slave
(FDL address 3)
No system
switching
Tracking cable
Standby system
New control system
Power
supply
module
Before recovery of the
switching target DP-Slave, an
error occurred at another DPSlave.
New control systemNew standby system
Power
supply
module
Redundant
CPU
DP-Slave
(FDL address 4)
Redundant
CPU
QJ71
PB92V
QJ71
PB92V
3 - 57
Bus terminator
DP-Slave
(FDL address 2)
Communication
failure
3.4 Buffer Memory
3.4.14 Redundant system area
DP-Slave
(FDL address 3)
DP-Slave
(FDL address 4)
Communication
failure
3
POINT
Address
DEC(HEX)
23665(5C71
H)
23666(5C72
H)
b15 b14 b13 b12 b11 b10 b9 b8 b7
12131116101412934567815
124 123
*
1
12211311 412111511 611711 8119120
44454348424633344135363738394047
10810910711210611 0979810599100101102103104111
92939196909481828983848586878895
76777580747865667367686970717279
28292732263017182519202122232431
60615964586249505751525354555663
b6 b5 b4 b3 b2 b1 b0
23669(5C75
H)
23668(5C74
H)
23667(5C73
H)
23670(5C76
H)
23671(5C77
H)
*1 The bits, b15 to b12 of address 23672 (5C78
H) are fixed to 0.
Each bit represents
the n-th DP-Slave
23672(5C78H)
*1 *1 *1
SPECIFICATIONS
1
(4) System switching condition setting result area (Disconnected station
detection) (Un\G23664 to Un\G23672)
(a) System switching condition setting result (Un\G23664)
The results of the setting in the System switching condition (Un\G23648) are
stored.
0: OR condition
1: AND condition
(b) System switching DP-Slave specification result (Un\G23665 to Un\G23672)
The results of the setting in the System switching DP-Slave specification
(Un\G23649 to Un\G23656) are stored.
0: Not system switching target
1: System switching target
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
Figure 3.37 System Switching DP-Slave Specification Result (Un\G23665 to Un\G23672)
In either of the following cases, check the System switching condition setting
(Un\G23648) again.
• A value other than 0 and 1 is stored in the System switching condition
setting result area (Un\G23664).
• Although setting is made in the System switching DP-Slave specification
area (Un\G23649 to Un\G23656), data in the System switching DP-Slave
specification result area (Un\G23665 to Un\G23672) are all 0s.
3.4 Buffer Memory
3.4.14 Redundant system area
3 - 58
SETTINGS AND
5
6
7
8
DEDICATED
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
INSTRUCTIONS
3
Time
Buffer memory
Internal buffer
DP-Slave 1
Treq(1)
Max_Tsdr(1)
LrPt(1)Pt(2)Pt(3)
Tsdi(M)Tsdi(M)
MSI(Min. Slave Interval) *1
Total of Treq, Max_Tsdr and Tres *1
Tres(1)
Treq(2)
Max_Tsdr(2)
Tres(2)
Treq(3)
Max_Tsdr(3)
Tres(3)
QJ71PB92V
Tsdi(M)
DP-Slave 2
DP-Slave 3
*2
SPECIFICATIONS
3.5 Processing Time
This section explains the bus cycle time and transmission delay time.
3.5.1 Bus cycle time
(1) When a single DP-Master is used
Figure 3.38 Bus Cycle Time (DP-Master: 1, DP-Slave: 3)
* 1 "MSI (Minimum polling cycle)" or "Total of Treq, Max_Tsdr and Tres", whichever is greater is Bc
(Bus cycle time). ((1) (a) in this section)
* 2 If "MSI (Minimum polling cycle)" is greater than "Total of Treq, Max_Tsdr and Tres", the
QJ71PB92V transfers data from the internal buffer to the buffer memory within the "MSI (Minimum
polling cycle)".
3 - 59
3.5 Processing Time
3.5.1 Bus cycle time
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.