Mitsubishi Electric Melsec Q, Melsec QJ71PB92V, Melsec QJ71PB92U, Melsec QJ71PB92SY, Melsec QJ71PB92E User Manual

PROFIBUS-DP Master Module User's Manual
-QJ71PB92V

SAFETY PRECAUTIONS

WARNING
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable controller system, refer to the user’s manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION"
Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious consequences. Observe the precautions of both levels because they are important for personal and system safety. Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
[Design Precautions]
WARNING
When a communication error occurs on PROFIBUS-DP, the status of the faulty station is as shown below. Create an interlock circuit in the sequence program using the communication status information to ensure the system operates safely (Input X1, buffer memory 5A20 An erroneous output or malfunction may cause accidents. (1) The QJ71PB92V holds the input data before the communication failure. (2) When the QJ71PB92V has gone down, the output status of each DP-Slave is dependent on the
QJ71PB92V parameter setting on GX Configurator-DP.
(3) When a DP-Slave has gone down, the output status of the other DP-Slaves is dependent on the
QJ71PB92V parameter setting on GX Configurator-DP.
Do not output the "use prohibited" signal as the output signal to an intelligent function module from the programmable controller CPU. Doing so may cause malfunction of the programmable controller system.
H to 5B19H (23072 to 23321)).
A - 1
[Design Precautions]
WARNING
When a stop error has occurred to the CPU module, the communication status varies depending on the error time output mode setting of GX Works2 as shown below. Set the communication status for when a stop error has occurred to the CPU module according to the system specifications. Note that, if the QJ71PB92V is mounted to a redundant system, it operates as described in (1) below regardless of the setting. (1) When "Error time output mode" is set to "Hold"
(a) Since the communication with the DP-Slave is continued, values at the time of the CPU
module stop error occurrence are held as the output data sent to the DP-Slave from the QJ71PB92V.
(b) Input data received from DP-Slaves are updated into the buffer memory of the QJ71PB92V.
(2) When "Error time output mode" is set to "Clear"
(a) Communications with DP-Slaves are interrupted, and output data are not sent. (b) Input data received from DP-Slaves are held in the buffer memory of the QJ71PB92V.
When the QJ71PB92V is mounted in a redundant system, set the watchdog timer for DP-Slaves so that the calculation formula shown in Section 4.8 (5) is satisfied. If the formula is not satisfied, a watchdog timer error occurs in DP-Slaves during system switching.
CAUTION
Do not install PROFIBUS cables together with the main circuit or power lines or bring them close to each other. Keep a distance of 100mm (3.94 inches) or more between them. Failure to do so may result in malfunction due to noise.
A - 2
[Installation Precautions]
CAUTION
Use the programmable controller in an environment that meets the general specifications in the user's manual for the CPU module used. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To mount the module, while pressing the module mounting lever located in the lower part of the module, fully insert the module fixing projection(s) into the hole(s) in the base unit and press the module until it snaps into place. Incorrect mounting may cause malfunction, failure or drop of the module. When using the programmable controller in an environment of frequent vibrations, fix the module with a screw.
Tighten the screw within the specified torque range. Undertightening can cause drop of the screw, short circuit or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may result in damage to the product.
Do not directly touch any conductive parts and electronic components of the module. Doing so can cause malfunction or failure of the module.
A - 3
[Wiring Precautions]
WARNING
Be sure to shut off all phases of the external power supply used by the system before wiring PROFIBUS cables. Failure to do so may cause the module to fail or malfunction.
CAUTION
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction.
Be sure to place the PROFIBUS cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or cables or malfunction due to poor contact.
When disconnecting the PROFIBUS cable, do not pull it by holding the cable part. Be sure to hold its connector which is plugged into the module. Pulling the cable with it connected to the module may damage the module and/or cable, or cause malfunctions due to poor contact of the cable.
A protective film is attached to the top of the module to prevent foreign matter, such as wire chips, from entering the module during wiring. Do not remove the film during wiring. Remove it for heat dissipation before system operation.
A - 4
[Startup and Maintenance Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before cleaning the module or retightening the connector screws or module fixing screws. Failure to do so may result in electric shock or cause the module to fail or malfunction. Undertightening can cause drop of the screw, short circuit or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
CAUTION
Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone System) more than 25cm (9.85 inches) away in all directions from the programmable controller. Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may cause the module to fail or malfunction.
After the first use of the product, do not mount/remove the module to/from the base unit more than 50 times (IEC 61131-2 compliant). Exceeding the limit may cause malfunction.
Before handling the module, touch a grounded metal object to discharge the static electricity from the
human body. Failure to do so may cause the module to fail or malfunction.
[Disposal Precautions]
CAUTION
When disposing of this product, treat is as an industrial waste.
A - 5

CONDITIONS OF USE FOR THE PRODUCT

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above restrictions, Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.
A - 6

REVISIONS

Additions
Section number changes
Change of a term
Additions
Section number changes
Additions
Modifications
* The manual number is given on the bottom left of the back cover.
Print Date * Manual Number Revision
Aug., 2005 SH (NA)-080572ENG-A First edition
Jun., 2006 SH (NA)-080572ENG-B
May, 2007 SH (NA)-080572ENG-C • Rewritten to include the QJ71PB92D-compatible function.
Modifications
SAFETY PRECAUTIONS, GLOSSARY, Section 1.1, 2.1, 2.2.1, 2.4, 3.1 to
3.5, Chapter 4, Section 4.1.1, 4.1.3, 4.2.1 to 4.2.3, 4.5, 4.6, 5.3, 5.4, 6.1 to
6.3, 6.5, 6.6.4, Chapter 7 to Section 7.1.3, 9.4, Appendix 2
Section 2.3 , 3.5.3, 4.7, 4.8, 5.2.2, 6.7, 7.7, 7.9, 8.1, 9.3, 9.4.1 to 9.4.6,
Appendix 1
Section 5.2 5.2.1, Section 7.7 7.8, Section 8.1 to 8.2 Section 8.2 to
Section 8.3, Appendix 1 to Appendix 2 Appendix 2 to Appendix 3
• Modified for descriptions of GX Configurator-DP Version 7.02C.
"PLC" was changed to "programmable controller".
Modifications
SAFETY PRECAUTIONS, ABOUT THE GENERIC TERMS AND
ABBREVIATIONS, ABOUT MANUALS, GLOSSARY, Chapter 1, Section 1.1,
2.1, 2.4, 3.5.1, 4.5, 4.6, 5.3, 6.1, 6.3 to 6.7, Chapter 7, Section 8.1 to 8.3,
Chapter 9 to Section 9.1, 9.3, 9.5.1 to 9.5.6, Appendix 1 to 2.3
Section 4.9, 9.2
Section 9.2 to 9.5 9.3 to 9.6
Dec., 2011 SH (NA)-080572ENG-D • Revision related to the support of GX Configurator-DP Version 7.07H
Modifications
SAFETY PRECAUTIONS, COMPLIANCE WITH EMC AND LOW VOLTAGE
DIRECTIVES, ABOUT THE GENERIC TERMS AND ABBREVIATIONS,
Section 2.1, 2.3.1, 3.3.1, 3.3.2, 3.4.4 to 3.4.6, 3.4.13, 4.1.3, 4.4, 4.5, 4.8, 4.9,
5.4, 5.5.1, Chapter 6, Section 6.2 to 6.5, Section 6.6.1 to 6.6.4, Chapter 7,
Section 7.1, 7.1.1, 7.1.2, 7.9.1, 8.1, 9.2, Appendix 2.2, WARRANTY
CONDITIONS OF USE FOR THE PRODUCT, MANUAL ORGANIZATION,
Section 2.3.3
Jun., 2015 SH (NA)-080572ENG-E
ABOUT THE GENERIC TERMS AND ABBREVIATIONS, Section 2.1, 3.1,
3.4.10, 4.9, 5.4, 7.4.3, 6.6.4, 9.1, 9.2, 9.3, 9.5.2, 9.5.3, 9.5.4, 9.5.5, 9.5.6, 9.6,
Appendix 2.1
A - 7
Print Date * Manual Number Revision
Modifications
Section number changes
Sep. 2018 SH (NA)-080572ENG-F
Related Manuals, Chapter 1, Section 1.1, 2.1, 2.4, Chapter 4, Section 4.6,
4.8, 5.3.1, 5.3.2, Chapter 6, Section 6.6.1, 6.6.2, 6.6.3, 6.7, 7.1, 7.8.1, 7.9.1,
9.1, 9.2, 9.4.2, 9.4.3, 9.5
Appendix 3 Appendix 1
Japanese Manual Version SH-080571-I
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
© 2005 MITSUBISHI ELECTRIC CORPORATION
A - 8

INTRODUCTION

Thank you for purchasing the Mitsubishi Electric programmable controller, MELSEC-Q series. Please read this manual carefully before use to develop familiarity with the functions and performance, and use it correctly.

CONTENTS

SAFETY PRECAUTIONS .................................................................................................................................A - 1
CONDITIONS OF USE FOR THE PRODUCT.................................................................................................. A - 6
REVISIONS.......................................................................................................................................................A - 7
INTRODUCTION............................................................................................................................................... A - 9
CONTENTS ...................................................................................................................................................... A - 9
MANUALS....................................................................................................................................................... A - 13
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES...................................................................A - 13
MANUAL ORGANIZATION............................................................................................................................. A - 14
ABOUT THE GENERIC TERMS AND ABBREVIATIONS ..............................................................................A - 15
GLOSSARY ....................................................................................................................................................A - 16
PACKING LIST ...............................................................................................................................................A - 17
CHAPTER1 OVERVIEW 1 - 1 to 1 - 5
1.1 Features........................................................................................................................................... 1 - 3
CHAPTER2 SYSTEM CONFIGURATION 2 - 1 to 2 - 17
2.1 Applicable System .......................................................................................................................... 2 - 1
2.1.1 Precautions for use on MELSECNET/H remote I/O stations.................................................... 2 - 4
2.2 PROFIBUS-DP Network Configuration............................................................................................2 - 5
2.2.1 Basic configuration of the PROFIBUS-DP network .................................................................. 2 - 5
2.2.2 PROFIBUS-DP network configuration examples ..................................................................... 2 - 6
2.3 Redundant System Configuration (Redundant CPUs Only) ............................................................ 2 - 8
2.3.1 PROFIBUS-DP network configuration...................................................................................... 2 - 8
2.3.2 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on main base units)
................................................................................................................................................ 2 - 10
2.3.3 PROFIBUS-DP network configuration examples (QJ71PB92Vs mounted on extension base units)
................................................................................................................................................ 2 - 15
2.4 Checking the Function Version and Serial No. .............................................................................. 2 - 16
CHAPTER3 SPECIFICATIONS 3 - 1 to 3 - 68
3.1 Performance Specifications ............................................................................................................. 3 - 1
3.2 Function List ................................................................................................................................... 3 - 3
3.3 Input/Output Signals to/from Programmable Controller CPU .......................................................... 3 - 4
3.3.1 List of I/O signals ...................................................................................................................... 3 - 4
3.3.2 Details of I/O signals................................................................................................................. 3 - 6
3.4 Buffer Memory ............................................................................................................................... 3 - 17
A - 9
3.4.1 Buffer memory list................................................................................................................... 3 - 17
3.4.2 Local station information area................................................................................................. 3 - 21
3.4.3 Operation mode change area .................................................................................................3 - 23
3.4.4 I/O data exchange area .......................................................................................................... 3 - 24
3.4.5 Slave status area .................................................................................................................... 3 - 29
3.4.6 Diagnostic information area .................................................................................................... 3 - 36
3.4.7 Extended diagnostic information read area ............................................................................ 3 - 43
3.4.8 Bus cycle time area ................................................................................................................ 3 - 44
3.4.9 Global control area ................................................................................................................. 3 - 45
3.4.10 Acyclic communication area ................................................................................................... 3 - 47
3.4.11 Alarm area .............................................................................................................................. 3 - 51
3.4.12 Time control area.................................................................................................................... 3 - 51
3.4.13 Temporary slave reservation area ..........................................................................................3 - 52
3.4.14 Redundant system area.......................................................................................................... 3 - 54
3.5 Processing Time ............................................................................................................................ 3 - 59
3.5.1 Bus cycle time......................................................................................................................... 3 - 59
3.5.2 Transmission delay time......................................................................................................... 3 - 63
3.5.3 System switching time in redundant system........................................................................... 3 - 65
CHAPTER4 FUNCTIONS 4 - 1 to 4 - 44
4.1 PROFIBUS-DPV0 Functions ........................................................................................................... 4 - 2
4.1.1 I/O data exchange .................................................................................................................... 4 - 2
4.1.2 Acquisition of diagnostic and/or extended diagnostic information ............................................ 4 - 4
4.1.3 Global control function .............................................................................................................. 4 - 7
4.2 PROFIBUS-DPV1 Functions ......................................................................................................... 4 - 11
4.2.1 Acyclic communication with DP-Slaves .................................................................................. 4 - 11
4.2.2 Alarm acquisition .................................................................................................................... 4 - 14
4.3 PROFIBUS-DPV2 Functions ......................................................................................................... 4 - 16
4.3.1 Time control over DP-Slaves .................................................................................................. 4 - 16
4.4 Data Swap Function ...................................................................................................................... 4 - 18
4.5 Data Consistency Function ............................................................................................................ 4 - 20
4.6 Output Status Setting for the Case of a CPU Stop Error ............................................................... 4 - 23
4.7 Temporary slave reservation function............................................................................................ 4 - 26
4.8 Redundant system support function .............................................................................................. 4 - 28
4.9 QJ71PB92D-Compatible Function................................................................................................. 4 - 38
CHAPTER5 SETTINGS AND PROCEDURES BEFORE SYSTEM OPERATION
5 - 1 to 5 - 12
5.1 Implementation and Installation ....................................................................................................... 5 - 1
5.1.1 Handling precautions ................................................................................................................ 5 - 1
5.2 Procedures Before System Operation ............................................................................................. 5 - 2
5.2.1 In the case of the single CPU system.......................................................................................5 - 2
5.2.2 In the case of the redundant system......................................................................................... 5 - 3
5.3 Part Names and Settings ................................................................................................................. 5 - 5
5.4 Self-diagnostics ............................................................................................................................... 5 - 7
A - 10
5.5 Wiring............................................................................................................................................... 5 - 9
5.5.1 PROFIBUS cable wiring ........................................................................................................... 5 - 9
5.5.2 Wiring precautions .................................................................................................................. 5 - 12
CHAPTER6 PARAMETER SETTING 6 - 1 to 6 - 24
6.1 Parameter Setting Procedure .......................................................................................................... 6 - 1
6.2 Operation Mode Setting ................................................................................................................... 6 - 4
6.3 Master Parameters .......................................................................................................................... 6 - 6
6.4 Bus Parameters ............................................................................................................................... 6 - 8
6.5 Slave Parameters .......................................................................................................................... 6 - 10
6.6 Automatic Refresh Parameters...................................................................................................... 6 - 14
6.6.1 Automatic refresh parameter setup procedure ....................................................................... 6 - 14
6.6.2 Automatic Refresh Settings .................................................................................................... 6 - 16
6.6.3 Writing Automatic Refresh Parameters .................................................................................. 6 - 19
6.6.4 Number of set automatic refresh parameters ......................................................................... 6 - 20
6.7 Parameter Setting by GX Works2.................................................................................................. 6 - 23
CHAPTER7 PROGRAMMING 7 - 1 to 7 - 86
7.1 I/O Data Exchange Program Examples...........................................................................................7 - 3
7.1.1 Program examples using automatic refresh ............................................................................. 7 - 7
7.1.2 Program example using dedicated instructions ...................................................................... 7 - 10
7.1.3 Program example using the MOV instruction ......................................................................... 7 - 12
7.2 Program Example for Acquisition of Extended Diagnostic Error Information ................................ 7 - 13
7.3 Program Example for Global Control Function .............................................................................. 7 - 14
7.4 Program Example for Acyclic Communication with DP-Slaves ..................................................... 7 - 15
7.4.1 READ services (Class1_SERVICE, Class2_SERVICE) ........................................................ 7 - 17
7.4.2 WRITE services (Class1_SERVICE, Class2_SERVICE) ....................................................... 7 - 20
7.4.3 INITIATE service (Class2_SERVICE) .................................................................................... 7 - 23
7.4.4 ABORT service (Class2_SERVICE)....................................................................................... 7 - 27
7.4.5 Program example ................................................................................................................... 7 - 29
7.5 Program Example for Alarm Acquisition ........................................................................................7 - 31
7.5.1 Alarm read request (without ACK) .......................................................................................... 7 - 32
7.5.2 Alarm ACK request ................................................................................................................. 7 - 36
7.5.3 Alarm read request (with ACK) ............................................................................................... 7 - 41
7.5.4 Program example ................................................................................................................... 7 - 47
7.6 Program Example for Time Control over DP-Slaves ..................................................................... 7 - 49
7.6.1 Time data read request .......................................................................................................... 7 - 50
7.6.2 Time data write request (UTC format) .................................................................................... 7 - 52
7.6.3 Time data write request .......................................................................................................... 7 - 54
7.6.4 Program example ................................................................................................................... 7 - 56
7.7 Program Example for Temporary Slave Reservation .................................................................... 7 - 58
7.8 Program Example When Mounting the QJ71PB92V on a MELSECNET/H Remote I/O Network
....................................................................................................................................................... 7 - 59
7.8.1 Program example for the I/O data exchange function (When mounted on a remote I/O station)
................................................................................................................................................ 7 - 59
A - 11
7.8.2 Other precautions ................................................................................................................... 7 - 66
7.9 Program Examples for Use in the Redundant System .................................................................. 7 - 67
7.9.1 I/O Data Exchange Program Examples.................................................................................. 7 - 71
7.9.2 Program example for acquisition of extended diagnostic error information............................ 7 - 81
7.9.3 Program example for global control function .......................................................................... 7 - 82
7.9.4 Program example for acyclic communication with DP-Slaves ................................................ 7 - 83
7.9.5 Program example for alarm acquisition .................................................................................. 7 - 84
7.9.6 Program example for time control over DP-Slaves................................................................. 7 - 84
7.9.7 Program example for temporary slave reservation................................................................. 7 - 86
CHAPTER8 DEDICATED INSTRUCTIONS 8 - 1 to 8 - 7
8.1 Precautions for Dedicated Instructions ............................................................................................ 8 - 2
8.2 G. BBLKRD...................................................................................................................................... 8 - 4
8.3 G. BBLKWR ..................................................................................................................................... 8 - 6
CHAPTER9 TROUBLESHOOTING 9 - 1 to 9 - 30
9.1 Error Check Using the LEDs and Corrective Actions ...................................................................... 9 - 2
9.2 When Parameters cannot be Written from GX Configurator-DP ..................................................... 9 - 4
9.3 When Communication with DP-Slaves Is Not Possible ................................................................... 9 - 6
9.4 Troubleshooting in the Redundant System......................................................................................9 - 8
9.4.1 When output data turn OFF or momentarily OFF in system switching ..................................... 9 - 8
9.4.2 When the FAULT LED of the QJ71PB92V in the new control system is ON............................ 9 - 9
9.4.3 Maintenance of the QJ71PB92V in the standby system......................................................... 9 - 10
9.5 Error Codes ................................................................................................................................... 9 - 13
9.5.1 Error codes E200H to E2FFH (Error codes generated when reading extended diagnostic
information)............................................................................................................................. 9 - 14
9.5.2 Error codes E300H to E3FFH (Error codes generated when switching operation mode) ...... 9 - 15
9.5.3 Error codes E400H to E4FFH (Error codes generated during acyclic communication).......... 9 - 16
9.5.4 Error codes E500H to E5FFH (Error codes generated when reading alarms) ....................... 9 - 21
9.5.5 Error codes E600H to E6FFH (Error codes generated when executing time control) ............ 9 - 24
9.5.6 Error codes F100H to FBFFH (Local diagnostic information of the QJ71PB92V) .................. 9 - 25
9.6 How to Return the QJ71PB92V to Its Factory-set Conditions ....................................................... 9 - 28
APPENDICES APPX - 1 to APPX - 2
Appendix 1 External Dimensions.......................................................................................................APPX- 1
INDEX INDEX - 1 to INDEX - 2
A - 12

MANUALS

Related Manuals
The manuals related to this product are listed below. Please place an order as needed.
Manual name
GX Configurator-DP Version7 Operating Manual
Explains the overview, installation method, and operating method of GX Configurator-DP Version 7.
(Sold separately)

COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES

(1) Method of ensuring compliance
To ensure that Mitsubishi Electric programmable controllers maintain EMC and Low Voltage Directives when incorporated into other machinery or equipment, certain measures may be necessary. Please refer to one of the following manuals
• QCPU User's Manual (Hardware Design, Maintenance and Inspection)
• Safety Guidelines (This manual is included with the CPU module or base unit.) The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives.
(2) Additional measures
No additional measures are necessary for the compliance of this product with EMC and Low Voltage Directives.
Manual number
(model code)
SH-080579ENG
(13JU54)
A - 13

MANUAL ORGANIZATION

In this manual, pages are organized and the symbols are used as shown below. The following illustration is for explanation purpose only, and should not be referred to as an actual documentation.
Chapter index
The chapter of the current page is highlighted.
Reference
A reference in this manual or a
reference manual is followed by .
A - 14
Section title
The section of the current page is shown.
• Description of a redundant system Unless otherwise specified, a redundant system in this manual is a system where QJ71PB92Vs are mounted on main base units.
When the QJ71PB92V is mounted on an extension base unit in a redundant system, the module operates in the same way as used in a single CPU system. However, there are some restrictions. For the restrictions, refer to the following.
( User's manual for the redundant system for the CPU module used)

ABOUT THE GENERIC TERMS AND ABBREVIATIONS

Unless otherwise specified, this manual uses the following generic terms and abbreviations to describe the Type QJ71PB92V PROFIBUS-DP Master Module.
General term/Abbreviation Description
QJ71PB92V Abbreviation for the QJ71PB92V PROFIBUS-DP Master module PROFIBUS-DP Abbreviation of PROFIBUS-DP network MELSECNET/H Abbreviation of MELSECNET/H network system
Generic term for the Q00JCPU, Q00CPU, Q00UJCPU, Q00UCPU, Q01CPU, Q01UCPU,
QCPU
CPU module
Redundant CPU Generic term for the Q12PRHCPU and Q25PRHCPU GX Works2 The product name of the software package for the MELSEC programmable controllers
GX Configurator-DP
BBLKRD Abbreviation for G. BBLKRD BBLKWR Abbreviation for G. BBLKWR
Q02CPU, Q02HCPU, Q02PHCPU, Q02UCPU, Q03UDCPU, Q03UDVCPU, Q03UDECPU,
Q04UDHCPU, Q04UDVCPU, Q04UDEHCPU, Q06HCPU, Q06PHCPU, Q06UDHCPU,
Q06UDVCPU, Q06UDEHCPU, Q10UDHCPU, Q10UDEHCPU, Q12HCPU, Q12PHCPU,
Q12PRHCPU, Q13UDHCPU, Q13UDVCPU, Q13UDEHCPU, Q20UDHCPU,
Q20UDEHCPU, Q25HCPU, Q25PHCPU, Q25PRHCPU, Q26UDHCPU, Q26UDVCPU,
Q26UDEHCPU, Q50UDEHCPU, and Q100UDEHCPU
Configuration tool for QJ71PB92V
Generic term of the product model SWnD5C-PROFID-E. ("n" means version 7 or later.)
A - 15

GLOSSARY

This part explains the glossary used in this manual.
Ter m Description
A basic version of PROFIBUS-DP.
The following functions are executable:
PROFIBUS-DPV0
PROFIBUS-DPV1
PROFIBUS-DPV2
Class 1 A device exchanging I/O data with a DP-Slaves. (QJ71PB92V, QJ71PB92D, etc)
DP-Master
DP-Slave A device that exchanges I/O data with a DP-Master (Class 1). (such as the QJ71PB93D) Repeater A device used to connect different segments of PROFIBUS-DP Bus terminator A terminating resistor that is connected to either end of each segment on PROFIBUS-DP
Configuration tool
GSD file
FDL address
Bus parameter
Master parameter
Slave parameter
I/O CONFIGURATION
DATA I/O data exchange This function allows I/O data exchange between a DP-Master (Class 1) and DP-Slaves.
Global control
Diagnostic information
Extended diagnostic error
information
Class 2
• I/O data exchange
• Diagnostic information notification
etc. A PROFIBUS-DP version for which the following functions have been added to the basic
functionality of PROFIBUS-DPV0.
• Acyclic communication
• Alarm function
etc. A PROFIBUS-DP version for which the following functions have been added to the
PROFIBUS-DPV1 functionality
• Time stamping
etc.
A device that communicates with DP-Slaves and checks their FDL address settings and/or
operation states
The DP-Master (Class 2) is used as a DP-Master for supervising the network, which can start,
maintain, and diagnose the system.
Software used to set bus parameters, slave parameters, etc. and to write them to a DP-Master
(GX Configurator-DP, etc.) An electronic file that contains parameters of a DP-Slave
The GSD file is used to set up the slave parameters on GX Configurator-DP. The numbers assigned to a DP-Master and DP-Slaves
The FDL address is set within the range from 0 to 125. The parameter used for the communication setting of PROFIBUS-DP
The bus parameter is set up on the GX Configurator-DP. The parameter used for the settings (FDL address, transmission speed, etc.) of the
QJ71PB92V
The master parameter is set up on the GX Configurator-DP. The parameter for a DP-Slave, which is set on the DP-Master.
The slave parameter is set up on the GX Configurator-DP.
The setting items are described on the GSD File.
Information on I/O configuration of a DP-Slave
This function enables synchronization command transmission for I/O data from a DP-Master
(Class 1) to DP-Slaves. Diagnostic information of PROFIBUS-DP, which is detected by a DP-Master or notified by a
DP-Slave Diagnostic information specific to each DP-Slave
Each of DP-Slaves notifies of it to the DP-Master when an error is detected.
(To the next page)
A - 16
Ter m Description
Bus cycle time
Ident No.
UTC
Time master A master station that can send a request for time control. (QJ71PB92V, etc.) System A The system to which the system-A connector of the tracking cable is connected. System B The system to which the system-B connector of the tracking cable is connected. Control system The system that is controlling the redundant system and performing network communication Standby system The system for backup in the redundant system
New control system
New standby system
QJ71PB92D-compatible
function
QJ71PB92D The QJ71PB92D type PROFIBUS-DP interface module
PROFIBUS-DP processing time for the DP-Master to perform cyclic communication with each
DP-Slave A specific number for each module that is connected to PROFIBUS-DP
Ident No. is described in a GSD file of each module. The UTC is based on the UTC, which stands for Coordinated Universal Time.
In order to adjust the time gap with the GMT (Greenwich Mean Time), the "leap second" has
been added.
The system changed from the standby system status to the control system status due to system
switching The system changed from the control system status to the standby system status due to system
switching The function used to replace the QJ71PB92D with the QJ71PB92V
The QJ71PB92V type PROFIBUS-DP master module has this function.

PACKING LIST

The following indicates the packing list of the QJ71PB92V.
Model Product name Quantity
QJ71PB92V QJ71PB92V PROFIBUS-DP master module 1
A - 17
1
RESET
RELEASE
PROFIBUS I/F
ST1H-PB
.
RUN
AUX
ERR
ST1PSD
SYS
RUN ERR
11 21
RUN ERR
11 21
RUN
AUX
ERR
ST1PDD
RUN ERR RUN ERR
DP-Master (Class 1)(QJ71PB92V)
DP-Slave (QJ71PB93D) DP-Slave ( MELSEC-ST system) DP-Slave
Bus terminator
Bus terminator
Single CPU system
RESET
RELEASE
PROFIBUS I/F
ST1H-PB
.
RUN
AUX
ERR
ST1PSD
SYS
RUN ERR
11 21
RUN ERR
11 21
RUN
AUX
ERR
ST1PDD
RUN ERR RUN ERR
DP-Slave
(QJ71PB93D)
DP-Slave
(MELSEC-ST System)
DP-Slave
Bus terminator
Bus terminator
Tracking cable
Control system Standby system
Redundant CPU (Q25PRHCPU)
DP-Master (Class 1) (QJ71PB92V)
Redundant system
OVERVIEW

CHAPTER1 OVERVIEW

This manual explains the specifications, functions, procedures before system operation, and troubleshooting for the QJ71PB92V PROFIBUS-DP master module (hereinafter referred to as "QJ71PB92V"). The QJ71PB92V is used for connecting MELSEC-Q Series programmable controllers to PROFIBUS-DP. The QJ71PB92V operates as a DP-Master (Class 1) on PROFIBUS-DP networks.
1 - 1
Figure 1.1 PROFIBUS-DP Using QJ71PB92V
1
RESET
RELEASE
PROFIBUS I/F
ST1H-PB
.
RUN
AUX
ERR
ST1PSD
SYS
RUN ERR
11 21
RUN ERR
11 21
RUN
AUX
ERR
ST1PDD
RUN ERR RUN ERR
DP-Slave (QJ71PB93D) DP-Slave ( MELSEC-ST System) DP-Slave
Bus terminator
Bus terminator
(
QJ72LP25-25
)
MELSECNET/H
Remote I/O network
Remote master station (QJ71LP21-25)
MELSECNET/H remote I/O network
DP-Master (Class 1)(QJ71PB92V)
Remote I/O station
OVERVIEW
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 1.1 PROFIBUS-DP Using QJ71PB92V (Continued)
SETTINGS AND
4
5
6
7
PROCEDURES BEFORE
FUNCTIONS
SYSTEM OPERATION
PARAMETER SETTING
1 - 2
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
1
OVERVIEW

1.1 Features

The following describes the features of the QJ71PB92V.
(1) DP-Master (Class 1) on PROFIBUS-DP
The QJ71PB92V complies with IEC 61158, and operates as a DP-Master (Class 1) on PROFIBUS-DP systems.
(a) Up to 125 DP-Slaves are connectable
*1
Up to 125 DP-Slaves
exchange of I/O data up to 8192 bytes. ( Section 4.1.1)
* 1 Up to 124 DP-Slaves when QJ71PB92Vs are mounted on main base units in a redundant system
(b) Diagnostic information can be easily acquired
Diagnostic or extended diagnostic information of an error occurred on a DP-Slave during I/O data exchange can be easily acquired using the buffer memory and I/O
signals. ( Section 4.1.2)
can be connected to a single QJ71PB92V, enabling
(c) Supporting the global control function
By sending services (SYNC, UNSYNC, FREEZE, UNFREEZE) to each DP-Slave
in a group, synchronous control of DP-Slave I/O data is available. ( Section
4.1.3)
Table1.1 Descriptions of Services
Service Name Description
This service is for synchronizing the output status of DP-Slaves.
SYNC
UNSYNC This service is for ending the SYNC mode.
FREEZE
UNFREEZE This service is for ending the FREEZE service.
(d) Supporting PROFIBUS-DPV1 and PROFIBUS-DPV2
PROFIBUS-DPV1 and PROFIBUS-DPV2, which are extended versions of PROFIBUS-DP, are supported The QJ71PB92V supports the following:
In the SYNC mode, the output status of a DP-Slave is refreshed
each time it receives the SYNC service.
While no SYNC service is received, the output status is held.
This service is for synchronizing the input status of DP-Slaves.
In the FREEZE mode, the input status of a DP-Slave is refreshed
each time it receives the FREEZE service.
While no FREEZE service is received, the input status is held.
1 - 3
1) PROFIBUS-DPV1
• Acyclic communication with DP-Slaves ( Section 4.2.1)
• Alarm acquisition ( Section 4.2.2)
2) PROFIBUS-DPV2
• Time control function on DP-Slaves ( Section 4.3.1)
1.1 Features
1
OVERVIEW
(2) I/O data consistency
(3) Easy parameter setup
Using the automatic refresh setting in GX Configurator-DP or dedicated instructions (BBLKRD/BBLKWR) ensures data consistency when reading/writing I/O data from the
QJ71PB92V buffer memory. ( Section 4.5)
Use of GX Configurator-DP enables bus parameters, master parameters, slave
parameters, and various other parameters to be easily set up. ( CHAPTER 6)
1
OVERVIEW
2
(4) Swapping of I/O data
The upper and lower bytes can be reversed (swapped) in word units when I/O data is sent or received. This simplifies programming as you no longer need to create a program for swapping
the upper and lower bytes on the QJ71PB92V or DP-Slave. ( Section 4.4)
(5) Mountable on MELSECNET/H remote I/O station
The QJ71PB92V can be mounted on a MELSECNET/H remote I/O station. This allows you to install the QJ71PB92V at a remote site away from the QCPU.
( Section 7.8)
(6) Output status setting for the case of a CPU stop error (Stop/Continue of
I/O data exchange)
For the case of a CPU stop error on a QCPU or remote I/O station where the QJ71PB92V is mounted, whether to stop or continue I/O data exchange with DP-
Slaves can be specified. ( Section 4.6)
(7) Changing DP-Slave setting to reserved station status temporarily
Without modifying the slave parameter in GX Configurator-DP, the station type of DP-
Slaves can be changed to "Reserved station" temporarily. ( Section 4.7) Since there is no need to change slave parameters, changing a DP-Slave setting to a reserved station is easy.
SETTINGS AND
3
4
5
6
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
1.1 Features
1 - 4
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
1
OVERVIEW
(8) Redundant system can be constructed
(a) Redundancy is available for the QJ71PB92V.
By mounting the QJ71PB92V together with a redundant CPU, a redundant system can be constructed. Even if the QJ71PB92V detects an error, the control and standby systems are
switched each other continuing communications. ( Section 4.8)
(b) System switching is available when an error occurs in the QJ71PB92V or in
communication with a DP-Slave. The systems can be switched when an error occurs in the QJ71PB92V or in communication with a DP-Slave.
• When the QJ71PB92V detects a critical error
Bus terminator
• When the QJ71PB92V detects a communication error of a DP-Slave
Control system
New standby system
Control system
New standby system
Error in
QJ71PB92V
Standby system
New control system
Continues communication
System switching
Tracking cable
ST1PSD
ST1H-PB
RELEASE
RESET
PROFIBUS I/F
ST1PDD
RUN
ERR
RUN ERR
RUN ERR
RUN
ERR
RUN ERR RUN ERR
SYS
11 21
11 21
.
AUX
AUX
DP-Slave (QJ71PB93D) DP-Slave (ST1H-PB)
Figure 1.2 When the QJ71PB92V detects a critical error
Standby system
Continues communication
New control system
Bus terminator
1 - 5
System switching
Tracking cable
Bus terminator Bus terminator
Communication
failure
Figure 1.3 When the QJ71PB92V detects a communication error of a DP-Slave
1.1 Features
2
Remark
POINT
SYSTEM CONFIGURATION

CHAPTER2 SYSTEM CONFIGURATION

This chapter explains the system configuration of the QJ71PB92V.
1
OVERVIEW

2.1 Applicable System

This section describes applicable systems.
(1) Mountable modules, No. of mountable modules, and mountable base
unit
(a) When mounting to CPU module
For the mountable CPU modules, No. of mountable modules, and mountable base unit of the QJ71PB92V, refer to the following manual. User's manual of the CPU module used (Hardware Design, Maintenance and Inspection)
When using a C Controller module, refer to the user's manual for a C Controller module.
(1) The number of mountable modules is restricted depending on the automatic
refresh setting on the QJ71PB92V. ( Section 6.6.4) For details, refer to Section 6.6.4.
(2) To utilize the data consistency function and dedicated instructions, use a
QCPU whose first 5 digits of the serial No. is "02092" or later.
SETTINGS AND
2
3
4
5
SYSTEM
PROCEDURES BEFORE
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
SYSTEM OPERATION
2.1 Applicable System
2 - 1
6
7
8
PARAMETER SETTING
PROGRAMMING
DEDICATED
INSTRUCTIONS
2
Remark
SYSTEM CONFIGURATION
(b) When mounting to remote I/O station of MELSECNET/H
The following shows the mountable network modules, No. of mountable modules, and mountable base unit of the QJ71PB92V module. Power shortage may occur depending on the combination with other mounted modules or the number of mounted modules. When mounting modules, pay attention to the power supply capacity. When the power shortage occurs, review the combination of modules to be mounted.
Table2.1 When mounting to remote I/O station of MELSECNET/H
Mountable network
module
QJ72LP25-25
QJ72LP25G
QJ72LP25GE
QJ72BR15
No. of mountable
modules
Up to 64
Mountable base unit
*1
Main base unit of
remote I/O station
Extension base unit
of remote I/O station
*2
: Mountable, : Not mountable
* 1 Limited to the range of the number of I/O points in the network module. * 2 Mountable on any I/O slot of the mountable base unit.
The Basic model QCPU cannot create the MELSECNET/H remote I/O network.
2 - 2
2.1 Applicable System
2
SYSTEM CONFIGURATION
(2) Supported software packages
The following shows the compatibility between software packages and the system using the QJ71PB92V. GX Developer or GX Works2: For setting QCPU parameters and creating sequence programs (required)
GX Configurator-DP: Configuration software for the QJ71PB92V (required)
Table2.2 Supported software packages
1
OVERVIEW
2
System
Q00J/Q00/Q01CPU
Q02/Q02H/Q06H/
Q12H/Q25HCPU
Q02PH/Q06PHCPU
Q12PH/Q25PHCPU
Q12PRH/Q25PRHCPU Redundant system Version 8.17T or later
Q00UJCPU Single CPU system
Q00U/
Q01UCPU
Q02UCPU
Q03UD/Q04UDH/
Q06UDHCPU
Q10UDH/Q20UDHCPU
Q13UDH/Q26UDHCPU
Q03UDV/Q04UDV/
Q06UDV/Q13UDV/
Q26UDVCPU
Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/
Q26UDEHCPU
Q10UDEH/
Q20UDEHCPU
Q50UDEH/
Q100UDEHCPU
When the CPU is mounted on a MELSECNET/H
remote I/O station
Single CPU system Version 7 or later
Multiple CPU system Version 8 or later Version 1.14Q or later
Single CPU system Version 4 or later Version 1.11M or later
Multiple CPU system Version 6 or later Version 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system
GX Developer
Version 8.68W or later Version 7.04E or later
Version 7.10L or later Version 7.00A or later
Version 8.76E or later Version 7.04E or later
Version 8.48A or later
Version 8.76E or later Version 7.04E or later
Version 8.62Q or later Version 7.03D or later
Not available Version 7.09K or later Version 1.95Z or later
Version 8.68W or later Version 7.03D or later
Version 8.76E or later Version 7.04E or later
Not available Version 7.07H or later Version 1.25B or later
Version 6 or later Version 7.00A or later Version 1.34L or later
Software version
GX Configurator-DP
Version 7.00A or later
Version 7.00A or later
Version 7.03D or later
Version 7.02C or later
*1
*3
GX Works2
Version 1.11M or later
Version 1.86Q or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
*2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
SYSTEM OPERATION
6
PARAMETER SETTING
7
* 1 The operation mode of the QJ71PB92V cannot be changed using GX Configurator-DP Version
7.03D or later. Change the mode using Operation mode change request area (Un\G2255).
* 2 For how to use GX Configurator-DP and GX Works2 together, refer to the GX Configurator-DP
Version7 Operating Manual.
* 3 To mount the QJ71PB92V on an extension base unit, use GX Configurator-DP Version 7.03D or
later.
2.1 Applicable System
2 - 3
8
PROGRAMMING
DEDICATED
INSTRUCTIONS
2
SYSTEM CONFIGURATION

2.1.1 Precautions for use on MELSECNET/H remote I/O stations

The following are the precautions when using the QJ71PB92V on MELSECNET/H remote I/O stations.
(1) Automatic refresh
Automatic refresh is not available when the QJ71PB92V is mounted on a MELSECNET/H remote I/O station. To use the automatic refresh, mount the QJ71PB92V on a remote master station (QCPU).
(2) Dedicated instructions (BBLKWR, BBLKRD)
Dedicated instructions (BBLKWR, BBLKRD) cannot be used when the QJ71PB92V is mounted on a MELSECNET/H remote I/O station. To use dedicated instructions, mount the QJ71PB92V on a remote master station (QCPU).
(3) QJ71PB92V parameter setup
To set QJ71PB92V parameters, connect GX Configurator-DP to a remote I/O station. QJ71PB92V parameters cannot be set via a remote master station.
2 - 4
2.1 Applicable System
2.1.1 Precautions for use on MELSECNET/H remote I/O stations
2
SYSTEM CONFIGURATION

2.2 PROFIBUS-DP Network Configuration

1

2.2.1 Basic configuration of the PROFIBUS-DP network

This section explains the basic PROFIBUS-DP configuration for using the QJ71PB92V as a DP-Master (Class 1).
(1) System equipment
The following table shows the equipment required for the PROFIBUS-DP system.
Table2.3 System Equipment
System Equipment Description
DP-Master (Class 1) QJ71PB92V
Configuration tool GX Configurator-DP Version 7.00A or later
DP-Slave Such as the QJ71PB93D
Repeater Required when 32 or more DP-Slaves are connected
PROFIBUS cable
Bus terminator
(2) Network configuration
In the PROFIBUS-DP system configuration, the following conditions must be satisfied:
(a) Number of connectable modules in an entire network (When repeaters are used)
*1
DP-Master
* 1 Including the QJ71PB92V
+ DP-Slaves 126
Section 5.5.1
2
3
4
5
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
FUNCTIONS
(b) Number of connectable modules per segment
*1
DP-Master
* 1 Including the QJ71PB92V * 2 A repeater is counted for both segments.
(c) Max. no. of repeaters
Up to 3 repeaters can be used for communication between the QJ71PB92V and any DP-Slave.
(d) Number of connectable DP-Slaves per QJ71PB92V
Up to 125 DP-Slaves can be connected to a single QJ71PB92V.
(e) Multi-master system
When a communication chip of ASPC2 STEP C mode or equivalent is used, the DP-Master cannot be connected to the PROFIBUS-DP in which the QJ71PB92V is included. To use a DP-Master with such a communication chip, configure another network. For the communication chip currently used, consult its manufacturer.
+ DP-Slaves + repeaters *2 32
SETTINGS AND
6
7
8
PROCEDURES BEFORE
SYSTEM OPERATION
PARAMETER SETTING
PROGRAMMING
2.2 PROFIBUS-DP Network Configuration
2.2.1 Basic configuration of the PROFIBUS-DP network
2 - 5
DEDICATED
INSTRUCTIONS
2
r
DP-Master (Class 1) (FDL address 0)
Bus terminator Bus terminator
Repeater 1
Segment 1
Segment 2
: Connection points counted as number of modules
QCPU
QJ71 PB92V
Power supply module
DP-Slave
(FDL address 2)
DP-Slave
(FDL address 1)
DP-Slave
(FDL address 30)
DP-Slave
(FDL address 32)
DP-Slave
(FDL address 31)
DP-Slave : 30 modules
DP-Slave : 31 modules
DP-Slave
(FDL address 61)
*1
SYSTEM CONFIGURATION

2.2.2 PROFIBUS-DP network configuration examples

(1) Maximum configuration with no repeater connected
DP-Master (QJ71PB92V): 1 DP-Slaves: 31
DP-Master (Class 1) (FDL address 0)
Power supply module
Bus terminator Bus terminato
DP-Slave
(FDL address 1)
Figure 2.1 Maximum Configuration With No Repeater Connected
* 1 When using redundant CPUs, configure the network as shown in Section 2.3.
QCPU
*1
QJ71 PB92V
DP-Slave
(FDL address 2)
DP-Slave : 31 modules
: Connection points counted as number of modules
Segment 1
(FDL address 31)
(2) Maximum configuration with a repeater connected
DP-Master (QJ71PB92V): 1 DP-Slaves: 61 Repeater: 1
DP-Slave
2 - 6
2.2 PROFIBUS-DP Network Configuration
2.2.2 PROFIBUS-DP network configuration examples
Figure 2.2 Maximum Configuration with a Repeater Connected
* 1 When using redundant CPUs, configure the network as shown in Section 2.3.
Loading...
+ 290 hidden pages