This manual describes the part names, dimensions, installation, cabling and
specifications for the product. This manual is extracted from MELSEC iQ-F
FX5U User's Manual (Hardware). Refer to MELSEC iQ-F FX5U User's Manual
(Hardware) for more details. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in the handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration: Ethernet is a trademark of Xerox Corporation. MODBUS is a
registered trademark of Schneider Electric SA. Phillips is a registered trademark of
Phillips Screw Company. The company name and the product name to be described
in this manual are the registered trademarks or trademarks of each company.
Effective December 2017
Specifications are subject to change without notice.
Safety Precaution (Read these precautions before use.)
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
This manual classifies the safety precautions into two categories:
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
and .
STARTUP AND
MAINTENANCE
PRECAUTIONS
Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
Before cleaning or retightening terminals, cut off all phases of t he power supply
externally. Failure to do so in the power ON status may cause electric shock.
Before modifying the program in operation, forcing output, running or stopping
the PLC, read through this manual carefully, and ensure complete safety.
An operation error may damage the machinery or cause accidents.
Do not change the program in the PLC from two or more peripheral equipment
devices at the same time. (i.e. from an engineering tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
Use the battery for memory backup in conformance to the MELSEC iQ-F
FX5U User's Manual (Hardware).
- U se the battery for the specified purpose only.
- C onnect the battery correctly.
- D o not charge, disassemble, heat, put in fire, short-circuit, connect
reversely, weld, swallow or burn the battery, or apply excessive forces
(vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or expose to direct sunlight.
- D o not expose to water, bring near fire or touch liquid leakage or other
contents directly.
- When replacing the battery, make sure to use our specified prod uct (FX3U-32BL).
- W hen a battery error occurs ("BAT" LED is lit in red), follow the
description in MELSEC iQ-F FX5U User's Manual (Hardware).
Incorrect handling of the battery may cause heat excessive generation,
bursting, ignition, liquid leakage or deformation, and lead to inj ury,
failures and malfunction of facilities and other equipment.
2014 MITSUBISHI ELECTRIC CORPORATION
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in minor or moderate injury or
property damage.
STARTUP AND
MAINTENANCE
PRECAUTIONS
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
Turn off the power to the PLC before connecting or disconnecting
extension cable.
Failure to do so may cause equipment failures or malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- P eripheral devices, expansion board, expansion adapter, and
connector conversion adapter
- Extension modules, bus conversion module, and battery
Do not use the chemicals for cleaning.
If there is the possibility of touching the PLC inside a control panel in
maintenance, make sure to discharge to avoid the influence of static
electricity.
DISPOSAL PRECAUTIONS
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
When disposing of batteries, separate them from other waste according to
local regulations.
(For details on the Battery Directive in EU countries, refer to the MELSEC
iQ-F FX5U User's Manual (Hardware).)
TRANSPORTATION
PRECAUTIONS
When transporting the PLC with the optional battery, turn on the
before shipment, confirm that the battery mode is set using a parameter and
the BAT LED is OFF, and check the battery life.
If the PLC is transported with the BAT LED ON or the battery exhausted,
the battery-backed data may be unstable during transportation.
The PLC is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications (Section 2.1)by
using dedicated packaging boxes and shock-absorbing palettes. Failure to
do so may cause failures in the PLC.
After transportation, verify operation of the PLC and check for damage of
the mounting part, etc.
When transporting lithium batteries, follow required transportation regulations.
(For details on the regulated products, refer to the MELSEC iQ-F FX5U
User's Manual (Hardware).)
any
PLC
Associated manuals
For the necessary product manuals or documents, consult with your local
Mitsubishi Electric representative.
Associated manuals
FX5U CPU module comes with this document (hardware manual).
For a detailed explanation of the FX5U CPU module hardware and information
on instructions for PLC programming and intelligent function module, refer to
the relevant documents.
specifications, procedures before
operation, and troubleshooting of
the FX5 CPU module.
Explains FX5U CPU module
specification details for I/O, wiring,
installation, and maintenance.
Explains the N:N network, MELSEC
Communication protocol, inverter
communication, and non-protocol
communication.
Explains the MODBUS serial
communication.
Functions for communication via
built-in Ethernet port
Certification of UL, cUL standards
Please consult with Mitsubishi Electric for information on UL, cUL standard
practices and the corresponding types of equipment.
Compliance with EC directive (CE Marking)
This product complies with EC directive, however, this document does not guarantee
that a mechanical system including this product will comply with EC directive.
Compliance to EMC directive and LVD directive of the entire mechanical
system should be checked by the user/manufacturer. For more details please
contact the local Mitsubishi Electric sales site.
For the caution for compliance with the EC directive, refer to MELSEC iQ-F
FX5U User's Manual (Hardware).
Incorporated Items
Check if the following product and items are included in the package:
[4] Built-in Ethernet communication connector (with cover)
[5] Top cover
Operation status display LEDs
PWR Green On while the PLC is powered.
*1
Red Lit/flashing when an error occurs.
ERR
[6]
P.RUN Green On while the PLC is running.
BATRed Lit when the battery voltage drops.
CARD Green Lit when the SD memory card is inserted.
[7]
[8]
[9]
[6]
[10]
No.Name
RDGreen
SDGreen
[6]
SD/RD Green
[7] Expansion board connector cover
[8] Input display LEDs (Green)
[9] Extension connector cover
[10] O utput display LEDs (Green)
*1 When powered on in the factory default state, ERR LED starts flashing
because there is no program. For details, refer to the following manual.
With cover open
Lit when data is received through communication via
built-in RS-485.
Lit when data is sent through communication via
built-in RS-485.
Lit when data is sent or received through
communication via built-in Ethernet.
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
[8]
[7]
[6]
[5]
[4]
[3]
[2]
[1]
[8]
No.Name
[1] Built-in RS-485 communication terminal block
[2] RS-485 terminal resister selector switch
[3] RUN/STOP/RESET switch
[4] SD memory card disable switch
[5] Built-in analog I/O terminal block
Terminal names
[6]
shows a function grounding terminal.
[7] SD memory card slot
[8] Terminal block mounting screws
[9] Expansion board connector
[10] Extension connector
[11] Battery holder
[12] Battery connector
No.Name
[1] Expansion adapter connector cover
[2]
Genuine product certification label
Nameplate
*1
[3]
[4] DIN rail mounting groove
*1 Products that do not have the genuine product certification label or
nameplate are not covered by the warranty.
*1
[9]
[10]
[11]
[12]
Page 2
1.2 External dimensions and weight
FX5-16EX
FX5-232ADP
FX5-16EYT
A
A
50 mm
A
A
A
FX5U
CPU module
2
A
A2
22
2-4.5-diam mounting holes (FX5U-32M)
4-4.5-diam mounting holes (FX5U-64M, FX5U-80M)
FX5U-32M do not have the (*)-marked mounting holes.
*
80
90
*
22
Model nameW: mm
FX5U-32M150123Approx. 0.7
FX5U-64M220193Approx. 1.0
FX5U-80M285258Approx. 1.2
Outer paint color Body: Munsell 0.6B7.6/0.2
W1
W
Mounting
hole
pitches
W1: mm
Mounting hole pitches
MASS (Weight): kg
2. Installation (general specifications)
As for installation of the I/O modules, expansion adapters and expansion
boards, refer to MELSEC iQ-F FX5U User's Manual (Hardware).
INSTALLATION
PRECAUTIONS
Use the product within the generic environment specifications described in
section 2.1 of this manual. Never use the product in areas with exces sive
dust, oily smoke, conductive dusts, c orrosive gas (salt air, Cl
or NO2), flammable gas, vibration or impacts, or expose it to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
INSTALLATION
PRECAUTIONS
Do not touch the conductive parts of the product directly. Doing so may
cause device failures or malfunctions.
When drilling screw holes or wiring, make sure that cutting and wiring
debris do not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
For the product supplied together with a dust proof sheet, the sheet should
be affixed to the ventilation slits before installation and wiring work to
prevent foreign objects such as cutting and wiring debris. However, when
the installation work is completed, make sure to remove the sheet to
provide adequate ventilation.
Failure to do so may cause fire, equipment failures or malfunctions.
Install the product on a fla t surface. If the mounting s urface is rough, undue
force will be applied to the PC board, thereby causing nonconformities.
Install the product securely using a DIN rail or mounting screws.
Connect the extension cables, peripheral device cables, input/ output cables
and battery connecting cable securely to t heir designated connectors.
Loose connections may cause malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- P eripheral devices, expansion board, expansion adapter, and
connector conversion adapter
- Extension modules, bus conversion module, and battery
2.1 Generic specifications
ItemSpecification
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
-20 to 55 (-4 to 131 ), non-freezing
*1
-25 to 75 (-13 to 167 ), non-freezing
5 to 95%RH, non-condensing
5 to 95%RH, non-condensing
*3
83
*2
Unit: mm
8
2, H2S, SO2
ItemSpecification
Vibration
*4*5
resistance
Shock
*4
resistance
Noise durability
Dielectric
withstand voltage
Insulation
*6
resistance
Grounding
Working
atmosphere
Operating altitude
Installation location
Overvoltage category
Pollution degree
*1 The simul taneous ON ratio of available PLC inputs or outputs changes with
respect to the ambient temperature. In the ca se where operating ambient
temperature is lower than 0
description. Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
*2 The operating ambient temperature is 0 to 55 (32 to 131) for
products manufactured before June 2016. For intelligent function
modules, refer to the manual for each product.
*3 When used in a low-temperature environment, use in an environment
with no sudden temperature changes. If there are sudden temperature
changes because of opening/closing of the control panel or other
reasons, condensation may occur, which may cause a fire, fault, or
malfunction. Furthermore, use an air conditioner in dehumidifier mode to
prevent condensation.
*4 The criterion is shown in IEC61131-2.
*5 When the system has equipment which spec ification values are lower
than above mentioned vibration resistance specificat ion values, the
vibration resistance specification of the whole system is corresponding to
the lower specification.
*6 Dielectric withstand voltage and insulation resistance are shown in the
following table.
CPU modules, I/O modules
Between power supply terminal
(AC power) and ground terminal
Between power supply terminal
(DC power) and ground terminal
Between 24 V DC service power supply
connected to input terminal (24 V DC) and
ground terminal
Between output terminal (relay) and
ground terminal
Between output terminal (transistor) and
ground terminal
Expansion boards, expansion adapters, intelligent function module
Between terminal of expansion board and
ground terminal
Between terminal of expansion adapter
and ground terminal
Intelligent function moduleEach manual
For dielectric withstand voltage test and insulation resistance test of each
product, refer to the following manual.
*7 For grounding, refer to Section 3.3.
*8
*10
*11
Term ina l
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Frequency
Acceleration
(Hz)
5 to 8.4
Installed
on DIN rail
8.4 to 150
5 to 8.4
Installed
directly
8.4 to 150
147 m/s2 Acceleration, Action time: 11 ms,
3 times by half-sine pulse in each direction X, Y, and Z
By noise simulator of 1000 Vp-p noise voltage, 1 μs noise
width and 30 to 100 Hz noise frequency
1.5 kV AC for 1 minute or 500
*6
V AC for 1 minute
10 M or higher by 500 V DC
insulation resistance tester
Class D grounding (Grounding resistance: 100 or less)
<Common grounding with a heavy electrical system is
not allowed.>
Free from corrosive or flammable gas and excessive
conductive dusts
0 to 2000 m
Inside a control panel
II or less
2 or less
*7
, the specifications are different from the above
Half amplitude
(m/s2)
1.75
4.9
3.5
9.8
Between each terminal
and ground terminal
*9
Dielectric
strength
1.5 kV AC for
1 minute
500 V AC for
1 minute
500 V AC for
1 minute
1.5 kV AC for
1 minute
500 V AC for
1 minute
Not allowedNot allowed
500 V AC for
1 minute
Sweep
(mm)
10 times each
in X, Y, Z
directions (80
min in each
direction)
Insulation
resistance
10 M or higher
by 500 V DC
insulation
resistance tester
10 M or higher
by 500 V DC
insulation
resistance tester
10 M or higher by
500 V DC insulation
resistance tester
count
*8 The PLC cannot be used at a pressure higher than the atmospheric
pressure to avoid damage.
*9 The programmable controller is assumed to be installed in an
environment equivalent to indoor.
*10 This indicates the section of the power supply to which the equipment is
assumed to be connected bet ween the public electri cal power distribution
network and the machinery within premises. Category II applies to
equipment for which electrical power is supplied from fixed facilities. The
surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*11T his index indicates the degree to which conductive material is generated
in the environment in which the equipment is used. Pollution level 2 is
when only non-conductive pollution occurs. Temporary conductivity
caused by condensation must be expected occasionally.
2.2 Installation location
Install the PLC in an environment conforming to the generic specifications
(Section 2.1), installation precautions.
Installation location in enclosure
Space in enclosure
Extension devices can be connected
on the left and right sides of the CPU
module.
If you intend to add extension
devices in the future, keep
necessary spaces on the left and
right sides.
2.2.1 Affixing the dust proof sheet
The dust proof sheet should be affixed to the ventilation port before beginning
the installation and wiring work.
Be sure to remove the dust proof sheet when the installation and wiring work is
completed.
2.3 Procedures for installing to and detaching from DIN rail
The products can be installed on a DIN46277 rail [35 mm wide]. This section
explains the installations of the CPU modules.
2.3.1 Installation
1) Connect the expansion boards and expansion ada pters to the CPU module.
2) Push out all DIN rail
mounting hooks (right
fig. A)
3) Fit the upper edge of the DIN rail
mounting groove (right fig. B) onto the
DIN rail.
4) Lock the DIN rail mounting hooks (below fig. C) w hile pressing the PLC
against the DIN rail.
2.4 Procedures for installing directly (with M4 screws)
The product can be installed directly on the panel (with screws).
This section explains the installation of the CPU modules.
2.4.1 Mounting hole pitches
Refer to the External Dimensions (Section 1.2) for the product's mounting hole
pitch information.
For the affixing procedure, refer to the instructions
B
C
C
4
4
on the dust proof sheet.
2.4.2 Installation
The FX5U-32M is used as the CPU
module in this example.
1) Make mounting holes in the
mounting surface referring to the
external dimensions diagram.
2) Fit the CPU module (right fig. A)
based on the holes, and secure it
with M4 screws (right fig. B). (In the
case of FX5U-64M/80M, there
are four screw holes.)
B
A
B
3. Specifications and examples of external wiring
As for the details of the power supply wiring and input/output wiring, refer to
MELSEC iQ-F FX5U User's Manual (Hardware).
DESIGN PRECAUTIONS
Make sure to set up the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a
protection circuit, an interlock circuit for opposite movements (such as
normal vs. reverse rotation), and an interlock circuit (to prevent
damage to the equipment at the upper and lower positioning limits).
- Note that w hen the CPU module detects an error, such as a watchdog
timer error, during self-diagnosis, all outputs are turned off. Also, when
an error that cannot be detected by the CPU module occurs in an input/
output control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
- Note t hat the output current of the 24 V DC service power supply varies
depending on the model and the absence/presence of extension
modules. If an overload occurs, the voltage automatically drops, inputs
in the PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
- Note that w hen an error occurs in a relay or transistor of an output
circuit, the output might stay on or off.
For output signals that may lead to serious accidents, external circuits
and mechanisms should be designed to ensure safe machinery
operation in such a case.
Construct an interlock circuit in the program s o that the whole system always
operates on the safe side before executing the control (for data change) of the
PLC in operation . Read the manual thoroughly and ensure complete s afety
before executing other controls (for program change, parameter change,
forcible output and operation status change) of the PLC in operation.
Otherwise, the machine may be damaged and accidents may o ccur due to
erroneous operations.
DESIGN PRECAUTIONS
Simultaneously turn on and off the power supplies of the CPU module and
extension modules.
WIRING PRECAUTIONS
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, provided as an accessory, before
turning on the power or initiating operation after installation or wiring work.
Failure to do so may cause electric shock.
The temperature rating of the cable should be 80 or more.
Make sure to wire the screw terminal block in ac cordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a shortcircuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifica tions in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft
diameter 6 mm or less). Make sure that the screwdriver does not touch
the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a shortcircuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifica tions in the manual.
- Twist the ends of stranded wires and make sure that there are no loose wires.
- Do not sol der-plate the electric wire ends.
- Do not con nect more than the specified number of wires or electric
wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the
connected parts are directly stressed.
Page 3
WIRING PRECAUTIONS
5 mm
Perform class D grounding (grounding resistance: 100 or less) of the grounding
terminal on the CPU module and extension modules with a wire 2 mm
Do not use common grounding with heavy ele ctrical systems (refer to
section 3.3).
Connect the power supply wiring to the dedicated terminals described in
this manual. If an AC power supply is co nnected to a DC input/output
terminal or DC power supply terminal, the PLC will burn out.
Do not wire vacant terminals externally. Doing so may damage the product.
Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to malfunction of the PLC
caused by abnormal data written to the PLC due to the effects of noise.
- D o not bundle the power line, control line and communication cables
together with or lay them close to the main circuit, high-voltage line,
load line or power line. As a guideline, lay the power line, control line
and communication cables at least 100 mm away from the main circuit,
high-voltage line, load line or power line.
- Ground the shield of the shielded wire or shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical systems.
Ground the shield of the analog input/output cable at one point on the
signal receiving side.
However, do not use common grounding with heavy electrical systems.
3.1 Cable end treatment and tightening torque
3.1.1 Screw type terminal block
For the terminals of FX5U CPU module and I/O module, M3 screws are used.
The electric wire ends should be treated as shown below.
Tighten the screws to a torque of 0.5 to 0.8 Nm.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
When one wire is connected to one terminal
3.2
6.2 mm or less
Terminal
screw
Solderless
terminal
2
or thicker.
3.2
Applicable
cable
3.2
6.3 mm or more
Terminal
Certification
UL Listed
*1
Terminal
screw
Pressure
bonding tool
YA-1 (J.S.T.
Mfg. Co., Ltd.)
Solderless
terminal
6.2 mm or less
<Reference>
Term ina l
manufacturer
J.S.T. Mfg.
Co., Ltd.
Typ e N o.
FV1.25-B3A AWG22 to 16
FV2-MS3AWG16 to 14
When two wires are connected to one terminal
6.2 mm or less
3.2
6.2 mm or less
<Reference>
Term ina l
manufacturer
J.S.T. Mfg.
Co., Ltd.
*1 To adapt the LVD directive (EN61010-2-201:2013) of the EC
directive, avoid the wiring with two wires to the built-in terminal, and take
an appropriate action such as adding an external terminal.
For the time of compliance with the LVD directive (EN61010-2-201:2013),
refer to MELSEC iQ-F FX5U User's Manual (Hardware).
3.1.2 European type terminal block
1) Wire size
No. of wire
per terminal
Solid wire/Stranded wire
6.3 mm or more
Typ e N o.
Applicable
cable
FV1.25-B3A AWG22 to 16 UL Listed
Terminal
Certification
Pressure
bonding tool
YA-1 (J.S.T.
Mfg. Co., Ltd.)
Wire size
Ferrules with insulating sleeve
1AWG24 to 20AWG24 to 20
2AWG24
2) Treatment of wire ends
Strip the coating of strand wire and twist the cable core before connecting
it, or strip the coating of single wire before connecting it. An alternative
connection is to use a ferrule with insulating sleeve.
When using a wire ferrule with an insulating sleeve, choose a wire with
proper cable sheath referring to the above outside dimen sions, otherwise
the wire cannot be inserted easily.
Tighten the screws to a torque of 0.22 to 0.25 Nm.
Do not tighten terminal screws exceeding with a torque outside the abovementioned range.
Failure to do so may cause equipment failures or malfunctions.
3) Tool
For tightening the terminal, use a
commercially available small
screwdriver having a straight
form that is not widened toward
the end as shown right.
Note:
If the diameter of screwdriver grip is too small, tightening torque may not be
achieved. To achieve the appropriate tightening torque shown in the table
above, use the following screwdriver or appropriate replacement (grip
diameter: approximately 25 mm).
0.4 mm
With
straight tip
2.5 mm
ManufacturerModel names
Phoenix Contact GmbH & Co. KGSZS 0.4×2.5
3.2 Power supply specifications and external wiring
3.2.1 Power supply specifications [CPU module, FX5-32E]
Item
Specification
AC power typeDC power type
Rated voltage100 to 240 V AC24 V DC
Voltage fluctuation range-15%, +10%-30%, +20%
Frequency rating50/60 Hz
Allowable instantaneous
power failure time
FX5U-32M,
Power fuse
FX5-32E
FX5U-64M,
FX5U-80M
FX5U-32M
Rush current
FX5U-64M,
FX5U-80M
FX5-32E
Operation can be
continued upon
occurrence of
instantaneous power
failure for 10 ms or less.
250 V 3.15 A Time-lag Fuse
250 V 5 A Time-lag Fuse
25 A max. 5 ms or less/100 V AC
50 A max. 5 ms or less/200 V AC
30 A max. 5 ms or less/100 V AC
60 A max. 5 ms or less/200 V AC
30 A max. 5 ms or less/100 V AC
65 A max. 5 ms or less/200 V AC
Operation can be
continued upon
occurrence of
instantaneous power
*1
failure for 5 ms or less.
50 A max. 0.5 ms or
less/24 V DC
65 A max. 2.0 ms or
less/24 V DC
50 A max. 0.5 ms or
less/24 V DC
FX5U-32M 30 W30 W
Power
consumption
FX5U-64M 40 W40 W
*2
FX5U-80M 45 W45 W
FX5-32E25 W25 W
FX5U-32M
24 V DC power
supply
capacity
*3
FX5U-64M
FX5U-80M
FX5-32E
5 V DC built-in
power supply
capacity
*1 When the supply voltage is 200 V AC, the time can be change to 10 to
100 ms by editing the user program.
*2 This item shows value when all 2 4 V DC power supplies are used in the
maximum configuration connectable to the CPU module. (The current of
the input circuit is included.)
*3 The AC power type has 24 V DC service power supply, and the DC
power type has 24 V DC built-in power supply. When I/O modules are
connected, they consume current from the power supply.
*4 Capacity of 24 V DC service power supply when serv ice power supply is
used for the input circuit. The value in () is capacity of 24 V DC service
power supply when external power supply is used for the input circuit.
*5 The value in [] is capacity of 24 V DC power supply in the case where
operating ambient temperature is lower than 0.
*6 The value in () is capacity of power supply when the supply voltage is
16.8-19.2 V DC.
FX5U-32M 900 mA
FX5U-64M,
FX5U-80M
*7
FX5-32E965 mA
400 mA (480 mA)
[300 mA (380 mA)]
600 mA (740 mA)
[300 mA (440 mA)]
600 mA (770 mA)
[300 mA (470 mA)]
250 mA (310 mA)
1100 mA
*4
480 mA (360 mA*6)
*4*5
*4
740 mA (530 mA*6)
*4*5
*4
770 mA (560 mA*6)
*4*5
*4
310 mA
900 mA (775 mA
1100 mA (975 mA
*7 Power is supplied to I/O modules, intelligent function modules, ex pansion
adapters and expansion boards.
The following manual shows further information.
3.2.2 Example of external wiring [AC power type]
100 to 240 V AC power is supplied to the CPU module and FX5-32E. For the
details of wiring work, refer to Section 3.1.
Refer to MELSEC iQ-F FX5U User’s Manual (Hardware).
100 to 240 V AC
Breaker
Power on
Emer-
MC
DC
power
supply
gency
MCMC
24 V DC
PL
[1]
L
*
N
*
Class D grounding
See section 3.3 for
details.
[1]: CPU module, FX5-32E
3.2.3 Example of external wiring [DC power type]
24 V DC power is supplied to the CPU module and FX5-32E. For the details
of wiring work, refer to Section 3.1.
MC
Fuse
DCAC
Power supply for loads connected
to CPU module output terminals
Input signal
current
ON input
sensitivity
current
OFF input sensitivity current1.5 mA or less
Input response time
Input signal form
(Input sensor form)
Input operation displayLED on panel turns on when input.
3.4.2 Examples of input wiring [AC power type] (when 24 V DC
Circuit protector
Power on
Emer-
MC
gency
3.4.3 Examples of input wiring [DC power type]
PL
[1]
Fuse
MC
*
MCMC
*
Class D grounding
See section 3.3 for details.
[1]: CPU module, FX5-32E
3.3 Grounding
Ground the PLC as stated below.
Perform class D grounding. (Grounding resistance: 100 or less)
Ground the PLC independently if possible.
*6
)
*6
)
If it cannot be grounded independently, ground it jointly as shown below.
Other
PLC
equipment
Independent grounding
(Best condition)
Use ground wires thicker than AWG14 (2 mm
Bring the grounding point close to the PLC as much as possible so that the
ground cable can be shortened.
3.4 Input specifications and external wiring
3.4.1 Input specifications (24 V DC input type)
ItemSpecification
Input signal voltage24 V DC 20%, -15%
X0 to X174.3 k
Input
impedance
CPU
module
X20 and
subsequent
FX5 I/O module5.6 k
Power supply for loads connected
to CPU module output terminals
Other
PLC
equipment
Shared grounding
(Good condition)
Common grounding
2
).
5.6 k
PLC
equipment
(Not allowed)
Other
3.5 Relay output specifications and external wiring
3.5.1 Relay output specifications
External power supply
ItemSpecification
X0 to X175.3 mA/24 V DC
CPU
X20 and
module
subsequent
4.0 mA/24 V DC
FX5 I/O module4.0 mA/24 V DC
X0 to X173.5 mA or more
CPU
X20 and
module
subsequent
3.0 mA or more
FX5 I/O module3.0 mA or more
Refer to MELSEC iQ-F FX5U
User's Manual (Hardware)
Sink input
Source input
No-voltage contact input NPN
open collector transistor
No-voltage contact input PNP
open collector transistor
service power supply is used)
1. Sink input type 2. Source input type
[1][1]
S/S
0V
24V
X0
X1
X2
X3
L
N
Fuse
*
100 to 240 V AC
3-wire type
sensor
S/S
0V
24V
X0
X1
X2
X3
L
N
Fuse
*
100 to 240 V AC
[2][2]
S/S
X0
*
Class D grounding
See section 3.3 for details.
[1]: CPU module, FX5-32E [2]: Input module
1. Sink input type 2. Source input type
[1][1]
*
S/S
X0
X1
X2
X3
[2]
S/S
X0
*
Class D grounding
See section 3.3 for details.
[1]: CPU module, FX5-32E [2]: Input module
24 V DC24 V DC
3-wire type
sensor
Fuse
S/S
X0
*
S/S
X0
X1
X2
X3
[2]
S/S
X0
ItemSpecification
30 V DC or less
240 V AC or less ("250 V AC or less"
CE, UL, cUL compliant item)
3-wire type
sensor
Fuse
3-wire type
sensor
if not a
Page 4
ItemSpecification
Max. load
2 A/point
*1
Min. load5 V DC, 2 mA (reference value)
Open circuit leakage current
Response
time
OFFONApprox. 10 ms
Output operation displayLED on panel turns on when output.
*1 The total load current of resistance loads per common terminal should be
the following value.
- 4 output points/common terminal : 8 A or less
- 8 output points/common terminal : 8 A or less
As for the number of outputs per common terminal, refer to
Chapter 4 and the following manual.
3.5.2 Example of relay output wiring
3.6 Transistor output specifications and external wiring
3.6.1 Transistor output specifications
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Load
Fuse
Load
Fuse
100 V AC
24 V DC
Y0
Y1
COM0
Y10
Y11
COM2
CPU module
ItemSpecification
FX5U-MT/S,
FX5-EYT/ES, FX5-32ET/S
Output
form
FX5U-MT/SS,
FX5-EYT/ESS, FX5-32ET/SS
Transistor (Sink)
Transistor (Source)
External power supply5-30 V DC
Max. load
0.5 A/point
*1
Min. load
Open circuit leakage current0.1 mA or less/30 V DC
Y0 to Y31.0 V or less
CPU
Y4 and
ON voltage
module
subsequent
1.5 V or less
I/O module1.5 V or less
Load
Fuse
24 V DC
2.5 s or less/10 mA
or more (5-24 V DC)
0.2 ms or less/200 mA
or more (at 24 V DC)
0.2 ms or less/200 mA
or more (at 24 V DC)
LED on panel turns on
when output.
Y0
Y1
+V0
CPU module
Y0 to Y3
CPU
OFF
ON
module
Y4 and
subsequent
Response
time
I/O module
Output operation display
*1 The total load current of resistance loads per common terminal should be
the following value.
- 4 output point/c ommon terminal: 0.8 A or less
- 8 output point/c ommon terminal: 1.6 A or less
As for the number of outputs per common terminal, refer to Chapter 4 and
the following manual.
3.6.2 External wiring of transistor output
1. External wiring of sink output type 2. External wiring of source output type
Load
Fuse
24 V DC
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Y0
Y1
COM0
CPU module
3.7 Built-in analog input/output specifications and external wiring
As for the details on the built-in analog input/output specifications and external
wiring, refer to the following manual.
3.7.1 Analog input specifications
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
ItemSpecifications
Analog input points2 points (2 channels)
Analog input0-10 V DC (Input resistance: 115.7 k)
Digital output12 bit unsigned binary
Device allocation
Digital output
Input
characteristics
Accuracy (Accuracy for the
full scale of the digital output
value)
value
Maximum
resolution
SD6020 (Input data of ch1)
SD6060 (Input data of ch2)
0 to 4000
2.5 mV
When ambient temperature is 25 5 (77 41°F) Within 0.5% (20 digit)
When ambient temperature is 0 to 55
(32 to 131°F) Within 1.0% (40 digit)
When ambient temperature is -20 to 0
(-4 to 32°F) Within ±1.5% (±60 digit)
*1
*1
*1
Absolute maximum input-0.5 V, +15 V
Insulation method
Occupied points
*1 Digit indicates a digital value.
3.7.2 Analog output specifications
Inside the CPU module and the analog
input circuit are not insulated. Between
input terminals (channels) is not insulated.
0 point (Dose not occupy of input and
output points of the CPU module.)
ItemSpecifications
Analog output points1 point (1 channel)
Digital input12 bit unsigned binary
Analog output
0-10 V DC (Input resistance: 2 k to 1 M)
Device allocationSD6180 (Output setting data of ch1)
Digital input
Output
characteristics
Accuracy*2 (Accuracy for the
full scale of the analog output
value)
value
Maximum
resolution
Insulation method
Occupied points
*1 Digit indicates a digital value.
*2 External load resistance is set to 2 k when shipped from the factory.
Thus, output voltage will increase somewhat if the resistance is set higher
than 2 k. When the resistance is 1 M, output voltage increases
maximum 2%.
3.7.3 Example of analog input
Class D
grounding
See section 3.3 for details.
*1 Use 2-core shielded twisted pair cable for the analog inpu t lines, and
separate the analog input lines from other power lines or inductive lines.
*2 Make sure to short-circuit the "V+" and "V-" terminals when channel is
not used.
3.7.4 Example of analog output
*1
*2
Class D grounding
*1 Use 2-core shielded twisted pair cable for the analog output lines, and
separate the analog output lines from other power lines or inductive lines.
*2 Ground the shielded wire at one point on the signal receiving side.
See section 3.3 for details.
0 to 4000
2.5 mV
When ambient temperature is 25 5 (77 41°F) Within 0.5% (20 digit)
When ambient temperature is 0 to 55
(32 to 131°F) Within 1.0% (40 digit)
When ambient temperature is -20 to 0
(-4 to 32°F) Within ±1.5% (±60 digit)
Inside the CPU module and the analog
output circuit are not insulated.
0 point (Dose not occupy any input and
output points of the CPU module.)
*1
*2
V+
V-
82.7 k
33 k
*1
ch
V+, ch: represents the channel number
V+
V-
*1
*1
3.7.5 Terminal block layouts
The terminals of the built-in analog input/output are arranged as follows:
SignalApplication
V1+Channel 1 analog input (+)
Analog
V2+Channel 2 analog input (+)
input
V1+ V2+
V- V+
V-
Analog
output
Analog
output
Analog
input
*1 The V- terminals are connected internally.
3.8 Built-in Ethernet communication specifications and
external wiring
As for the details on the built-in Ethernet communication spec ifications
external wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).
3.8.1 Communication specification
V-Analog input (-)
V+Analog outp ut (+)
V-Analog output (-)
*1
*1
and
ItemSpecification
Data transmission speed100/10 Mbps
Communication mode
Full-duplex (FDX)/Half-duplex (HDX)
*1
InterfaceRJ45 connector
Transmission methodBase band
Maximum segment length (The
distance between hub and node)
Cascade
connection
100BASE-TX
10BASE-T
Protocol type
Number of simultaneously open
connections allowed
*1
Hub
100 m
Max. 2 stages
Max. 4 stages
MELSOFT connection, SLMP (3E frames),
Socket communication, Predefined
protocol support
Total of 8 for socket communication,
MELSOFT connection, SLMP, and
Predefined protocol support
Hubs with 100BASE-TX or 10BASE-T
ports can be used.
*2
*2
Insulation methodPulse transformer
IP addressInitial value: 192.168.3.250
*1 IEEE802.3x flow control is not supported.
*2 The value indicates the number of connectable stages when a repeater
hub is used.
Contact the manufacturer of the switching hub f or the number of
connectable stages when using a switching hub.
3.8.2 Wiring
For the wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).
3.8.3 Pin Configuration
The connector of the built-in Ethernet communication are arranged as follows:
Pin No.SignalContents
1TXD+Transmit data (+)
2TXD-Transmit data (-)
3RXD+
Receive data (+)
4Not used
5Not used
81
6RXD-Receive data (-)
7Not used
8Not used
Applicable cable
10BASE-T
100BASE-TX
A straight cable is used. A cross cable can also be used when using direct
connection between a personal computer and the FX5U CPU module.
3.9 Built-in RS-485 communication specifications and
3.9.1 Communication specification
Cable conforming to Ethernet standard practice:
Category 3 or higher (STP cable)
Cable conforming to Ethernet standard practice:
Category 5 or higher (STP cable)
external wiring
ItemSpecification
Transmission standard In conformance to RS -485/RS-422
ItemSpecification
Data transmission speed
Communication method
Maximum total
extension distance
Protocol type
Max. 115.2 kbps
Full-duplex/Half-duplex
50 m
MELSOFT connection, MELSEC Communication
protocol (3C/4C frames), Non-protocol
communication, MODBUS RTU, Inverter
communication, N:N network, Predefined protocol
support
Insulation methodNo insulation between the PLC.
Terminal resistorsBuilt-in (OPEN/110 /330 )
Connection methodEuropean terminal block
3.9.2 Wiring
For the wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Serial Communication).
Refer to MELSEC iQ-F FX5 User's Manual (MODBUS Communication).
3.9.3 Terminal block layouts
The terminals of the built-in RS-485 communication are arranged as follows:
SG
Signal nameFunction
RDARDBSDASDB
RDA
RDB
SDA
SDB
Receive data
Send data
SGSignal ground
4. Terminal block layouts
For details on the terminal block layout, refer to the following manual.
Interpretation of partition
The partition of the output terminals (see following figure) indicates the range of
the output connected to the same common.
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the grat is warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2)
Loss in opport unity, lost profits inc urred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages w hether foreseeable or not, compensa tion for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Example: FX5U-32MT/ES
Output terminal
Y0
2
Y4
COM0 1COM13
Partition
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.