Hardware Manual
Manual Number JY997D53401
Revision F
Date December 2017
This manual describes the part names, dimensions, installation, cabling and specifications for the product. This manual is extracted from MELSEC iQ-F FX5U User's Manual (Hardware). Refer to MELSEC iQ-F FX5U User's Manual (Hardware) for more details. Before use, read this manual and manuals of relevant products fully to acquire proficiency in the handling and operating the product. Make sure to learn all the product information, safety information, and precautions. And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
Registration: Ethernet is a trademark of Xerox Corporation. MODBUS is a registered trademark of Schneider Electric SA. Phillips is a registered trademark of Phillips Screw Company. The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company.
Effective December 2017 Specifications are subject to change without notice.

Safety Precaution (Read these precautions before use.)

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. This manual classifies the safety precautions into two categories:
Depending on the circumstances, procedures indicated by may also cause severe injury. It is important to follow all precautions for personal safety.
and .
STARTUP AND MAINTENANCE PRECAUTIONS
Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions. Before cleaning or retightening terminals, cut off all phases of t he power supply
externally. Failure to do so in the power ON status may cause electric shock.
Before modifying the program in operation, forcing output, running or stopping the PLC, read through this manual carefully, and ensure complete safety. An operation error may damage the machinery or cause accidents. Do not change the program in the PLC from two or more peripheral equipment
devices at the same time. (i.e. from an engineering tool and a GOT) Doing so may cause destruction or malfunction of the PLC program. Use the battery for memory backup in conformance to the MELSEC iQ-F
FX5U User's Manual (Hardware).
- U se the battery for the specified purpose only.
- C onnect the battery correctly.
- D o not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or expose to direct sunlight.
- D o not expose to water, bring near fire or touch liquid leakage or other contents directly.
- When replacing the battery, make sure to use our specified prod uct (FX3U-32BL).
- W hen a battery error occurs ("BAT" LED is lit in red), follow the description in MELSEC iQ-F FX5U User's Manual (Hardware).
Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or deformation, and lead to inj ury, failures and malfunction of facilities and other equipment.
2014 MITSUBISHI ELECTRIC CORPORATION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
STARTUP AND MAINTENANCE PRECAUTIONS
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric representative. Turn off the power to the PLC before connecting or disconnecting
extension cable. Failure to do so may cause equipment failures or malfunctions. Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- P eripheral devices, expansion board, expansion adapter, and connector conversion adapter
- Extension modules, bus conversion module, and battery
Do not use the chemicals for cleaning.If there is the possibility of touching the PLC inside a control panel in
maintenance, make sure to discharge to avoid the influence of static electricity.
DISPOSAL PRECAUTIONS
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
When disposing of batteries, separate them from other waste according to
local regulations. (For details on the Battery Directive in EU countries, refer to the MELSEC iQ-F FX5U User's Manual (Hardware).)
TRANSPORTATION PRECAUTIONS
When transporting the PLC with the optional battery, turn on the
before shipment, confirm that the battery mode is set using a parameter and the BAT LED is OFF, and check the battery life. If the PLC is transported with the BAT LED ON or the battery exhausted, the battery-backed data may be unstable during transportation.
The PLC is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications (Section 2.1) by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the PLC. After transportation, verify operation of the PLC and check for damage of the mounting part, etc. When transporting lithium batteries, follow required transportation regulations.
(For details on the regulated products, refer to the MELSEC iQ-F FX5U User's Manual (Hardware).)
any
PLC

Associated manuals

For the necessary product manuals or documents, consult with your local Mitsubishi Electric representative.
Associated manuals
FX5U CPU module comes with this document (hardware manual). For a detailed explanation of the FX5U CPU module hardware and information on instructions for PLC programming and intelligent function module, refer to the relevant documents.
Manual name Manual No. Description
MELSEC iQ-F FX5 User's Manual (Startup)
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5 User's Manual (Serial Communication)
MELSEC iQ-F FX5 User's Manual (MODBUS Communication)
MELSEC iQ-F FX5 User's Manual
fire or
(Ethernet Communication)
How to obtain manuals
Explains performance
JY997D58201
JY997D55301
JY997D55901
JY997D56101
JY997D56201
specifications, procedures before operation, and troubleshooting of the FX5 CPU module.
Explains FX5U CPU module specification details for I/O, wiring, installation, and maintenance.
Explains the N:N network, MELSEC Communication protocol, inverter communication, and non-protocol communication.
Explains the MODBUS serial communication.
Functions for communication via built-in Ethernet port

Certification of UL, cUL standards

Please consult with Mitsubishi Electric for information on UL, cUL standard practices and the corresponding types of equipment.

Compliance with EC directive (CE Marking)

This product complies with EC directive, however, this document does not guarantee that a mechanical system including this product will comply with EC directive. Compliance to EMC directive and LVD directive of the entire mechanical system should be checked by the user/manufacturer. For more details please contact the local Mitsubishi Electric sales site. For the caution for compliance with the EC directive, refer to MELSEC iQ-F FX5U User's Manual (Hardware).

Incorporated Items

Check if the following product and items are included in the package:
CPU module
FX5U-MR/ES, FX5U-MT/ES, FX5U-MT/ESS, FX5U-MR/DS, FX5U-MT/DS, FX5U-MT/DSS (: 32, 64, 80)
I/O module
FX5-EX/ES, FX5-EYR/ES, FX5-EYT/ES, FX5-EYT/ESS (: 8, 16)
FX5-32ER/ES, FX5-32ET/ES, FX5-32ET/ESS, FX5-32ER/DS, FX5-32ET/DS, FX5-32ET/DSS
Product 1 module
Dust proof protection sheet 1 sheet
Manuals [Japanese /English] 1 manual
Manuals [Chinese] 1 manual
Product 1 module
Dust proof protection sheet 1 sheet
Product 1 module
Dust proof protection sheet 1 sheet
Extension cable 1 cable
Included Items

1. Outline

1.1 Part names

[2] [3]
[6]
[5]
[4]
[3] [2] [1]
No. Name
[1] DIN rail mounting hooks
[2] Expansion adapter connecting hooks
[3] Terminal block covers
[4] Built-in Ethernet communication connector (with cover)
[5] Top cover
Operation status display LEDs
PWR Green On while the PLC is powered.
*1
Red Lit/flashing when an error occurs.
ERR
[6]
P.RUN Green On while the PLC is running.
BAT Red Lit when the battery voltage drops.
CARD Green Lit when the SD memory card is inserted.
[7]
[8] [9] [6]
[10]
No. Name
RD Green
SD Green
[6]
SD/RD Green
[7] Expansion board connector cover
[8] Input display LEDs (Green)
[9] Extension connector cover
[10] O utput display LEDs (Green)
*1 When powered on in the factory default state, ERR LED starts flashing
because there is no program. For details, refer to the following manual.
With cover open
Lit when data is received through communication via built-in RS-485.
Lit when data is sent through communication via built-in RS-485.
Lit when data is sent or received through communication via built-in Ethernet.
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
[8]
[7] [6]
[5]
[4]
[3]
[2]
[1]
[8]
No. Name
[1] Built-in RS-485 communication terminal block
[2] RS-485 terminal resister selector switch
[3] RUN/STOP/RESET switch
[4] SD memory card disable switch
[5] Built-in analog I/O terminal block
Terminal names
[6]
shows a function grounding terminal.
[7] SD memory card slot
[8] Terminal block mounting screws
[9] Expansion board connector
[10] Extension connector
[11] Battery holder
[12] Battery connector
No. Name
[1] Expansion adapter connector cover
[2]
Genuine product certification label
Nameplate
*1
[3]
[4] DIN rail mounting groove
*1 Products that do not have the genuine product certification label or
nameplate are not covered by the warranty.
*1
[9]
[10]
[11]
[12]
Page 2

1.2 External dimensions and weight

FX5-16EX
FX5-232ADP
FX5-16EYT
A
A
50 mm
A
A
A
FX5U
CPU module
2
A
A2
22
2-4.5-diam mounting holes (FX5U-32M) 4-4.5-diam mounting holes (FX5U-64M, FX5U-80M) FX5U-32M do not have the (*)-marked mounting holes.
*
80
90
*
22
Model name W: mm
FX5U-32M 150 123 Approx. 0.7
FX5U-64M 220 193 Approx. 1.0
FX5U-80M 285 258 Approx. 1.2
Outer paint color Body: Munsell 0.6B7.6/0.2
W1
W
Mounting hole pitches
W1: mm
Mounting hole pitches
MASS (Weight): kg

2. Installation (general specifications)

As for installation of the I/O modules, expansion adapters and expansion boards, refer to MELSEC iQ-F FX5U User's Manual (Hardware).
INSTALLATION PRECAUTIONS
Use the product within the generic environment specifications described in
section 2.1 of this manual. Never use the product in areas with exces sive dust, oily smoke, conductive dusts, c orrosive gas (salt air, Cl or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
INSTALLATION PRECAUTIONS
Do not touch the conductive parts of the product directly. Doing so may
cause device failures or malfunctions.
When drilling screw holes or wiring, make sure that cutting and wiring
debris do not enter the ventilation slits of the PLC. Failure to do so may cause fire, equipment failures or malfunctions.
For the product supplied together with a dust proof sheet, the sheet should
be affixed to the ventilation slits before installation and wiring work to prevent foreign objects such as cutting and wiring debris. However, when the installation work is completed, make sure to remove the sheet to provide adequate ventilation. Failure to do so may cause fire, equipment failures or malfunctions. Install the product on a fla t surface. If the mounting s urface is rough, undue
force will be applied to the PC board, thereby causing nonconformities.
Install the product securely using a DIN rail or mounting screws.
Connect the extension cables, peripheral device cables, input/ output cables
and battery connecting cable securely to t heir designated connectors. Loose connections may cause malfunctions. Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- P eripheral devices, expansion board, expansion adapter, and connector conversion adapter
- Extension modules, bus conversion module, and battery

2.1 Generic specifications

Item Specification
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
-20 to 55 (-4 to 131 ), non-freezing
*1
-25 to 75 (-13 to 167 ), non-freezing
5 to 95%RH, non-condensing
5 to 95%RH, non-condensing
*3
83
*2
Unit: mm
8
2, H2S, SO2
Item Specification
Vibration
*4*5
resistance
Shock
*4
resistance
Noise durability
Dielectric withstand voltage
Insulation
*6
resistance
Grounding
Working atmosphere
Operating altitude
Installation location
Overvoltage category
Pollution degree
*1 The simul taneous ON ratio of available PLC inputs or outputs changes with
respect to the ambient temperature. In the ca se where operating ambient temperature is lower than 0 description. Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
*2 The operating ambient temperature is 0 to 55 (32 to 131) for
products manufactured before June 2016. For intelligent function modules, refer to the manual for each product.
*3 When used in a low-temperature environment, use in an environment
with no sudden temperature changes. If there are sudden temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to
prevent condensation. *4 The criterion is shown in IEC61131-2. *5 When the system has equipment which spec ification values are lower
than above mentioned vibration resistance specificat ion values, the
vibration resistance specification of the whole system is corresponding to
the lower specification. *6 Dielectric withstand voltage and insulation resistance are shown in the
following table.
CPU modules, I/O modules
Between power supply terminal (AC power) and ground terminal
Between power supply terminal (DC power) and ground terminal
Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal
Between output terminal (relay) and ground terminal
Between output terminal (transistor) and ground terminal
Expansion boards, expansion adapters, intelligent function module
Between terminal of expansion board and ground terminal
Between terminal of expansion adapter and ground terminal
Intelligent function module Each manual
For dielectric withstand voltage test and insulation resistance test of each
product, refer to the following manual.
*7 For grounding, refer to Section 3.3.
*8
*10
*11
Term ina l
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Frequency
Acceleration
(Hz)
5 to 8.4
Installed on DIN rail
8.4 to 150
5 to 8.4
Installed directly
8.4 to 150
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
By noise simulator of 1000 Vp-p noise voltage, 1 μs noise width and 30 to 100 Hz noise frequency
1.5 kV AC for 1 minute or 500
*6
V AC for 1 minute
10 M or higher by 500 V DC insulation resistance tester
Class D grounding (Grounding resistance: 100 or less) <Common grounding with a heavy electrical system is
not allowed.>
Free from corrosive or flammable gas and excessive conductive dusts
0 to 2000 m
Inside a control panel
II or less
2 or less
*7
, the specifications are different from the above
Half amplitude
(m/s2)
1.75
4.9
3.5
9.8
Between each terminal and ground terminal
*9
Dielectric
strength
1.5 kV AC for 1 minute
500 V AC for
1 minute
500 V AC for
1 minute
1.5 kV AC for
1 minute
500 V AC for
1 minute
Not allowed Not allowed
500 V AC for
1 minute
Sweep
(mm)
10 times each in X, Y, Z directions (80 min in each direction)
Insulation resistance
10 M or higher by 500 V DC insulation resistance tester
10 M or higher by 500 V DC insulation resistance tester
10 M or higher by 500 V DC insulation resistance tester
count
*8 The PLC cannot be used at a pressure higher than the atmospheric
pressure to avoid damage.
*9 The programmable controller is assumed to be installed in an
environment equivalent to indoor.
*10 This indicates the section of the power supply to which the equipment is
assumed to be connected bet ween the public electri cal power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*11T his index indicates the degree to which conductive material is generated
in the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.

2.2 Installation location

Install the PLC in an environment conforming to the generic specifications (Section 2.1), installation precautions.
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides of the CPU module. If you intend to add extension devices in the future, keep necessary spaces on the left and right sides.

2.2.1 Affixing the dust proof sheet

The dust proof sheet should be affixed to the ventilation port before beginning the installation and wiring work.
Be sure to remove the dust proof sheet when the installation and wiring work is completed.

2.3 Procedures for installing to and detaching from DIN rail

The products can be installed on a DIN46277 rail [35 mm wide]. This section explains the installations of the CPU modules.

2.3.1 Installation

1) Connect the expansion boards and expansion ada pters to the CPU module.
2) Push out all DIN rail mounting hooks (right fig. A)
3) Fit the upper edge of the DIN rail mounting groove (right fig. B) onto the DIN rail.
4) Lock the DIN rail mounting hooks (below fig. C) w hile pressing the PLC against the DIN rail.

2.4 Procedures for installing directly (with M4 screws)

The product can be installed directly on the panel (with screws). This section explains the installation of the CPU modules.

2.4.1 Mounting hole pitches

Refer to the External Dimensions (Section 1.2) for the product's mounting hole pitch information.
For the affixing procedure, refer to the instructions
B
C
C
4
4
on the dust proof sheet.

2.4.2 Installation

The FX5U-32M is used as the CPU module in this example.
1) Make mounting holes in the mounting surface referring to the external dimensions diagram.
2) Fit the CPU module (right fig. A) based on the holes, and secure it with M4 screws (right fig. B). (In the case of FX5U-64M/80M, there are four screw holes.)
B
A
B

3. Specifications and examples of external wiring

As for the details of the power supply wiring and input/output wiring, refer to MELSEC iQ-F FX5U User's Manual (Hardware).
DESIGN PRECAUTIONS
Make sure to set up the following safety circuits outside the PLC to ensure safe system operation even during external power supply problems or PLC failure. Otherwise, malfunctions may cause serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a protection circuit, an interlock circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
- Note that w hen the CPU module detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the CPU module occurs in an input/ output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
- Note t hat the output current of the 24 V DC service power supply varies depending on the model and the absence/presence of extension modules. If an overload occurs, the voltage automatically drops, inputs in the PLC are disabled, and all outputs are turned off. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
- Note that w hen an error occurs in a relay or transistor of an output circuit, the output might stay on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
Construct an interlock circuit in the program s o that the whole system always operates on the safe side before executing the control (for data change) of the PLC in operation . Read the manual thoroughly and ensure complete s afety before executing other controls (for program change, parameter change, forcible output and operation status change) of the PLC in operation. Otherwise, the machine may be damaged and accidents may o ccur due to erroneous operations.
DESIGN PRECAUTIONS
Simultaneously turn on and off the power supplies of the CPU module and
extension modules.
WIRING PRECAUTIONS
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, provided as an accessory, before
turning on the power or initiating operation after installation or wiring work. Failure to do so may cause electric shock.
The temperature rating of the cable should be 80 or more.Make sure to wire the screw terminal block in ac cordance with the
following precautions. Failure to do so may cause electric shock, equipment failures, a short­circuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifica tions in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6 mm or less). Make sure that the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short­circuit, wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifica tions in the manual.
- Twist the ends of stranded wires and make sure that there are no loose wires.
- Do not sol der-plate the electric wire ends.
- Do not con nect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
Page 3
WIRING PRECAUTIONS
5 mm
Perform class D grounding (grounding resistance: 100  or less) of the grounding terminal on the CPU module and extension modules with a wire 2 mm
Do not use common grounding with heavy ele ctrical systems (refer to section 3.3).
Connect the power supply wiring to the dedicated terminals described in
this manual. If an AC power supply is co nnected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
Do not wire vacant terminals externally. Doing so may damage the product.
Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to malfunction of the PLC caused by abnormal data written to the PLC due to the effects of noise.
- D o not bundle the power line, control line and communication cables together with or lay them close to the main circuit, high-voltage line, load line or power line. As a guideline, lay the power line, control line and communication cables at least 100 mm away from the main circuit, high-voltage line, load line or power line.
- Ground the shield of the shielded wire or shielded cable at one point on the PLC. However, do not use common grounding with heavy electrical systems.
Ground the shield of the analog input/output cable at one point on the
signal receiving side. However, do not use common grounding with heavy electrical systems.

3.1 Cable end treatment and tightening torque

3.1.1 Screw type terminal block

For the terminals of FX5U CPU module and I/O module, M3 screws are used. The electric wire ends should be treated as shown below. Tighten the screws to a torque of 0.5 to 0.8 Nm. Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause equipment failures or malfunctions.
When one wire is connected to one terminal
3.2
6.2 mm or less
Terminal screw
Solderless terminal
2
or thicker.
3.2
Applicable
cable
3.2
6.3 mm or more
Terminal
Certification
UL Listed
*1
Terminal screw
Pressure
bonding tool
YA-1 (J.S.T. Mfg. Co., Ltd.)
Solderless terminal
6.2 mm or less
<Reference>
Term ina l
manufacturer
J.S.T. Mfg. Co., Ltd.
Typ e N o.
FV1.25-B3A AWG22 to 16
FV2-MS3 AWG16 to 14
When two wires are connected to one terminal
6.2 mm or less
3.2
6.2 mm or less
<Reference>
Term ina l
manufacturer
J.S.T. Mfg. Co., Ltd.
*1 To adapt the LVD directive (EN61010-2-201:2013) of the EC
directive, avoid the wiring with two wires to the built-in terminal, and take an appropriate action such as adding an external terminal. For the time of compliance with the LVD directive (EN61010-2-201:2013), refer to MELSEC iQ-F FX5U User's Manual (Hardware).

3.1.2 European type terminal block

1) Wire size
No. of wire
per terminal
Solid wire/Stranded wire
6.3 mm or more
Typ e N o.
Applicable
cable
FV1.25-B3A AWG22 to 16 UL Listed
Terminal
Certification
Pressure
bonding tool
YA-1 (J.S.T. Mfg. Co., Ltd.)
Wire size
Ferrules with insulating sleeve
1 AWG24 to 20 AWG24 to 20
2AWG24
2) Treatment of wire ends Strip the coating of strand wire and twist the cable core before connecting it, or strip the coating of single wire before connecting it. An alternative connection is to use a ferrule with insulating sleeve.
Insulating sleeve
Contact area (Crimp area)
6 mm
2 to 2.5 mm
10.5 to 12 mm
Manufacturer Model Caulking tool
Phoenix Contact GmbH & Co. KG AI 0.5-6WH C RIMPFOX 6
When using a wire ferrule with an insulating sleeve, choose a wire with proper cable sheath referring to the above outside dimen sions, otherwise the wire cannot be inserted easily. Tighten the screws to a torque of 0.22 to 0.25 Nm. Do not tighten terminal screws exceeding with a torque outside the above­mentioned range. Failure to do so may cause equipment failures or malfunctions.
3) Tool For tightening the terminal, use a commercially available small screwdriver having a straight form that is not widened toward the end as shown right.
Note:
If the diameter of screwdriver grip is too small, tightening torque may not be achieved. To achieve the appropriate tightening torque shown in the table above, use the following screwdriver or appropriate replacement (grip diameter: approximately 25 mm).
0.4 mm
With straight tip
2.5 mm
Manufacturer Model names
Phoenix Contact GmbH & Co. KG SZS 0.4×2.5

3.2 Power supply specifications and external wiring

3.2.1 Power supply specifications [CPU module, FX5-32E]
Item
Specification
AC power type DC power type
Rated voltage 100 to 240 V AC 24 V DC
Voltage fluctuation range -15%, +10% -30%, +20%
Frequency rating 50/60 Hz
Allowable instantaneous power failure time
FX5U-32M,
Power fuse
FX5-32E
FX5U-64M, FX5U-80M
FX5U-32M
Rush current
FX5U-64M, FX5U-80M
FX5-32E
Operation can be continued upon occurrence of instantaneous power
failure for 10 ms or less.
250 V 3.15 A Time-lag Fuse
250 V 5 A Time-lag Fuse
25 A max. 5 ms or less/100 V AC 50 A max. 5 ms or less/200 V AC
30 A max. 5 ms or less/100 V AC 60 A max. 5 ms or less/200 V AC
30 A max. 5 ms or less/100 V AC 65 A max. 5 ms or less/200 V AC
Operation can be continued upon occurrence of instantaneous power
*1
failure for 5 ms or less.
50 A max. 0.5 ms or less/24 V DC
65 A max. 2.0 ms or less/24 V DC
50 A max. 0.5 ms or less/24 V DC
FX5U-32M30 W 30 W
Power consumption
FX5U-64M40 W 40 W
*2
FX5U-80M45 W 45 W
FX5-32E 25 W 25 W
FX5U-32M
24 V DC power supply
capacity
*3
FX5U-64M
FX5U-80M
FX5-32E
5 V DC built-in power supply
capacity
*1 When the supply voltage is 200 V AC, the time can be change to 10 to
100 ms by editing the user program.
*2 This item shows value when all 2 4 V DC power supplies are used in the
maximum configuration connectable to the CPU module. (The current of the input circuit is included.)
*3 The AC power type has 24 V DC service power supply, and the DC
power type has 24 V DC built-in power supply. When I/O modules are connected, they consume current from the power supply.
*4 Capacity of 24 V DC service power supply when serv ice power supply is
used for the input circuit. The value in () is capacity of 24 V DC service power supply when external power supply is used for the input circuit.
*5 The value in [] is capacity of 24 V DC power supply in the case where
operating ambient temperature is lower than 0.
*6 The value in () is capacity of power supply when the supply voltage is
16.8-19.2 V DC.
FX5U-32M900 mA
FX5U-64M, FX5U-80M
*7
FX5-32E 965 mA
400 mA (480 mA) [300 mA (380 mA)]
600 mA (740 mA) [300 mA (440 mA)]
600 mA (770 mA) [300 mA (470 mA)]
250 mA (310 mA)
1100 mA
*4
480 mA (360 mA*6)
*4*5
*4
740 mA (530 mA*6)
*4*5
*4
770 mA (560 mA*6)
*4*5
*4
310 mA
900 mA (775 mA
1100 mA (975 mA
*7 Power is supplied to I/O modules, intelligent function modules, ex pansion
adapters and expansion boards. The following manual shows further information.

3.2.2 Example of external wiring [AC power type]

100 to 240 V AC power is supplied to the CPU module and FX5-32E. For the details of wiring work, refer to Section 3.1.
Refer to MELSEC iQ-F FX5U User’s Manual (Hardware).
100 to 240 V AC
Breaker
Power on
Emer-
MC
DC power supply
gency
MCMC
24 V DC
PL
[1]
L
*
N
*
Class D grounding See section 3.3 for details.
[1]: CPU module, FX5-32E

3.2.3 Example of external wiring [DC power type]

24 V DC power is supplied to the CPU module and FX5-32E. For the details of wiring work, refer to Section 3.1.
MC
Fuse
DC AC
Power supply for loads connected to CPU module output terminals
Input signal current
ON input sensitivity current
OFF input sensitivity current 1.5 mA or less
Input response time
Input signal form (Input sensor form)
Input operation display LED on panel turns on when input.
3.4.2 Examples of input wiring [AC power type] (when 24 V DC
Circuit protector
Power on
Emer-
MC
gency

3.4.3 Examples of input wiring [DC power type]

PL
[1]
Fuse
MC
*
MCMC
*
Class D grounding See section 3.3 for details.
[1]: CPU module, FX5-32E

3.3 Grounding

Ground the PLC as stated below.
Perform class D grounding. (Grounding resistance: 100 or less)Ground the PLC independently if possible.
*6
)
*6
)
If it cannot be grounded independently, ground it jointly as shown below.
Other
PLC
equipment
Independent grounding
(Best condition)
Use ground wires thicker than AWG14 (2 mmBring the grounding point close to the PLC as much as possible so that the
ground cable can be shortened.

3.4 Input specifications and external wiring

3.4.1 Input specifications (24 V DC input type)

Item Specification
Input signal voltage 24 V DC 20%, -15%
X0 to X17 4.3 k
Input impedance
CPU module
X20 and subsequent
FX5 I/O module 5.6 k
Power supply for loads connected to CPU module output terminals
Other
PLC
equipment
Shared grounding
(Good condition)
Common grounding
2
).
5.6 k
PLC
equipment
(Not allowed)
Other

3.5 Relay output specifications and external wiring

3.5.1 Relay output specifications

External power supply
Item Specification
X0 to X17 5.3 mA/24 V DC
CPU
X20 and
module
subsequent
4.0 mA/24 V DC
FX5 I/O module 4.0 mA/24 V DC
X0 to X17 3.5 mA or more
CPU
X20 and
module
subsequent
3.0 mA or more
FX5 I/O module 3.0 mA or more
Refer to MELSEC iQ-F FX5U User's Manual (Hardware)
Sink input
Source input
No-voltage contact input NPN open collector transistor
No-voltage contact input PNP open collector transistor
service power supply is used)
1. Sink input type 2. Source input type [1] [1]
S/S
0V
24V
X0 X1 X2 X3
L
N
Fuse
*
100 to 240 V AC
3-wire type
sensor
S/S
0V
24V
X0 X1 X2 X3
L
N
Fuse
*
100 to 240 V AC
[2] [2]
S/S
X0
*
Class D grounding See section 3.3 for details.
[1]: CPU module, FX5-32E [2]: Input module
1. Sink input type 2. Source input type [1] [1]
*
S/S
X0 X1 X2 X3
[2]
S/S
X0
*
Class D grounding See section 3.3 for details.
[1]: CPU module, FX5-32E [2]: Input module
24 V DC 24 V DC
3-wire type
sensor
Fuse
S/S
X0
*
S/S
X0 X1 X2 X3
[2]
S/S
X0
Item Specification
30 V DC or less 240 V AC or less ("250 V AC or less" CE, UL, cUL compliant item)
3-wire type sensor
Fuse
3-wire type sensor
if not a
Page 4
Item Specification
Max. load
2 A/point
*1
Min. load 5 V DC, 2 mA (reference value)
Open circuit leakage current
Response time
OFFON Approx. 10 ms
Output operation display LED on panel turns on when output.
*1 The total load current of resistance loads per common terminal should be
the following value.
- 4 output points/common terminal : 8 A or less
- 8 output points/common terminal : 8 A or less As for the number of outputs per common terminal, refer to Chapter 4 and the following manual.

3.5.2 Example of relay output wiring

3.6 Transistor output specifications and external wiring

3.6.1 Transistor output specifications

Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Load
Fuse
Load
Fuse
100 V AC
24 V DC
Y0 Y1
COM0
Y10 Y11
COM2
CPU module
Item Specification
FX5U-MT/S, FX5-EYT/ES, FX5-32ET/S
Output form
FX5U-MT/SS, FX5-EYT/ESS, FX5-32ET/SS
Transistor (Sink)
Transistor (Source)
External power supply 5-30 V DC
Max. load
0.5 A/point
*1
Min. load
Open circuit leakage current 0.1 mA or less/30 V DC
Y0 to Y3 1.0 V or less
CPU
Y4 and
ON voltage
module
subsequent
1.5 V or less
I/O module 1.5 V or less
Load
Fuse
24 V DC
2.5 s or less/10 mA or more (5-24 V DC)
0.2 ms or less/200 mA or more (at 24 V DC)
0.2 ms or less/200 mA or more (at 24 V DC)
LED on panel turns on when output.
Y0
Y1
+V0
CPU module
Y0 to Y3
CPU
OFF ON
module
Y4 and subsequent
Response time
I/O module
Output operation display
*1 The total load current of resistance loads per common terminal should be
the following value.
- 4 output point/c ommon terminal: 0.8 A or less
- 8 output point/c ommon terminal: 1.6 A or less As for the number of outputs per common terminal, refer to Chapter 4 and the following manual.

3.6.2 External wiring of transistor output

1. External wiring of sink output type 2. External wiring of source output type
Load
Fuse
24 V DC
Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Y0
Y1
COM0
CPU module

3.7 Built-in analog input/output specifications and external wiring

As for the details on the built-in analog input/output specifications and external wiring, refer to the following manual.

3.7.1 Analog input specifications

Refer to MELSEC iQ-F FX5U User's Manual (Hardware).
Item Specifications
Analog input points 2 points (2 channels)
Analog input 0-10 V DC (Input resistance: 115.7 k)
Digital output 12 bit unsigned binary
Device allocation
Digital output
Input characteristics
Accuracy (Accuracy for the full scale of the digital output value)
value
Maximum resolution
SD6020 (Input data of ch1) SD6060 (Input data of ch2)
0 to 4000
2.5 mV
When ambient temperature is 25 5 (77 41°F) Within 0.5% (20 digit) When ambient temperature is 0 to 55 (32 to 131°F) Within 1.0% (40 digit) When ambient temperature is -20 to 0 (-4 to 32°F) Within ±1.5% (±60 digit)
*1
*1
*1
Absolute maximum input -0.5 V, +15 V
Insulation method
Occupied points
*1 Digit indicates a digital value.

3.7.2 Analog output specifications

Inside the CPU module and the analog input circuit are not insulated. Between input terminals (channels) is not insulated.
0 point (Dose not occupy of input and output points of the CPU module.)
Item Specifications
Analog output points 1 point (1 channel)
Digital input 12 bit unsigned binary
Analog output
0-10 V DC (Input resistance: 2 k to 1 M)
Device allocation SD6180 (Output setting data of ch1)
Digital input
Output characteristics
Accuracy*2 (Accuracy for the full scale of the analog output value)
value
Maximum resolution
Insulation method
Occupied points
*1 Digit indicates a digital value. *2 External load resistance is set to 2 k when shipped from the factory.
Thus, output voltage will increase somewhat if the resistance is set higher than 2 k. When the resistance is 1 M, output voltage increases maximum 2%.

3.7.3 Example of analog input

Class D grounding
See section 3.3 for details.
*1 Use 2-core shielded twisted pair cable for the analog inpu t lines, and
separate the analog input lines from other power lines or inductive lines.
*2 Make sure to short-circuit the "V+" and "V-" terminals when channel is
not used.

3.7.4 Example of analog output

*1
*2
Class D grounding
*1 Use 2-core shielded twisted pair cable for the analog output lines, and
separate the analog output lines from other power lines or inductive lines.
*2 Ground the shielded wire at one point on the signal receiving side.
See section 3.3 for details.
0 to 4000
2.5 mV
When ambient temperature is 25 5 (77 41°F) Within 0.5% (20 digit) When ambient temperature is 0 to 55 (32 to 131°F) Within 1.0% (40 digit) When ambient temperature is -20 to 0 (-4 to 32°F) Within ±1.5% (±60 digit)
Inside the CPU module and the analog output circuit are not insulated.
0 point (Dose not occupy any input and output points of the CPU module.)
*1
*2
V+
V-
82.7 k
33 k
*1
ch
V+, ch: represents the channel number
V+
V-
*1
*1

3.7.5 Terminal block layouts

The terminals of the built-in analog input/output are arranged as follows:
Signal Application
V1+ Channel 1 analog input (+)
Analog
V2+ Channel 2 analog input (+)
input
V1+ V2+
V- V+
V-
Analog output
Analog
output
Analog
input
*1 The V- terminals are connected internally.

3.8 Built-in Ethernet communication specifications and external wiring

As for the details on the built-in Ethernet communication spec ifications external wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).

3.8.1 Communication specification

V- Analog input (-)
V+ Analog outp ut (+)
V- Analog output (-)
*1
*1
and
Item Specification
Data transmission speed 100/10 Mbps
Communication mode
Full-duplex (FDX)/Half-duplex (HDX)
*1
Interface RJ45 connector
Transmission method Base band
Maximum segment length (The distance between hub and node)
Cascade connection
100BASE-TX
10BASE-T
Protocol type
Number of simultaneously open connections allowed
*1
Hub
100 m
Max. 2 stages
Max. 4 stages
MELSOFT connection, SLMP (3E frames), Socket communication, Predefined protocol support
Total of 8 for socket communication, MELSOFT connection, SLMP, and Predefined protocol support
Hubs with 100BASE-TX or 10BASE-T ports can be used.
*2
*2
Insulation method Pulse transformer
IP address Initial value: 192.168.3.250
*1 IEEE802.3x flow control is not supported. *2 The value indicates the number of connectable stages when a repeater
hub is used. Contact the manufacturer of the switching hub f or the number of connectable stages when using a switching hub.

3.8.2 Wiring

For the wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Ethernet Communication).

3.8.3 Pin Configuration

The connector of the built-in Ethernet communication are arranged as follows:
Pin No. Signal Contents
1 TXD+ Transmit data (+)
2 TXD- Transmit data (-)
3RXD+
Receive data (+)
4 Not used
5 Not used
81
6 RXD- Receive data (-)
7 Not used
8 Not used
Applicable cable
10BASE-T
100BASE-TX
A straight cable is used. A cross cable can also be used when using direct connection between a personal computer and the FX5U CPU module.
3.9 Built-in RS-485 communication specifications and

3.9.1 Communication specification

Cable conforming to Ethernet standard practice: Category 3 or higher (STP cable)
Cable conforming to Ethernet standard practice: Category 5 or higher (STP cable)
external wiring
Item Specification
Transmission standard In conformance to RS -485/RS-422
Item Specification
Data transmission speed
Communication method
Maximum total extension distance
Protocol type
Max. 115.2 kbps
Full-duplex/Half-duplex
50 m
MELSOFT connection, MELSEC Communication protocol (3C/4C frames), Non-protocol communication, MODBUS RTU, Inverter communication, N:N network, Predefined protocol support
Insulation method No insulation between the PLC.
Terminal resistors Built-in (OPEN/110 /330 )
Connection method European terminal block

3.9.2 Wiring

For the wiring, refer to the following manual.
Refer to MELSEC iQ-F FX5 User's Manual (Serial Communication).
Refer to MELSEC iQ-F FX5 User's Manual (MODBUS Communication).

3.9.3 Terminal block layouts

The terminals of the built-in RS-485 communication are arranged as follows:
SG
Signal name Function
RDARDBSDASDB
RDA
RDB
SDA
SDB
Receive data
Send data
SG Signal ground

4. Terminal block layouts

For details on the terminal block layout, refer to the following manual.
Interpretation of partition
The partition of the output terminals (see following figure) indicates the range of the output connected to the same common.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the grat is warranty term, Mitsubishi shall not be liable for compensation to: (1) Damages caused by any cause found not to be the responsibility of Mitsubishi. (2)
Loss in opport unity, lost profits inc urred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages w hether foreseeable or not, compensa tion for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.