Indicates that incorrect handling may cause hazardous conditions, resulting in
death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in
minor or moderate injury or property damage.
(Read these precautions before use.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full
attention to safety in order to handle the product correctly.
This manual classifies the safety precautions into two categories: [WARNING] and [CAUTION].
Depending on the circumstances, procedures indicated by [CAUTION] may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be read whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
WARNING
● Make sure to set up the following safety circuits outside the PLC to ensure safe system operation
even during external power supply problems or PLC failure. Otherwise, malfunctions may cause
serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a protection circuit, an interlock
circuit for opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to
prevent damage to the equipment at the upper and lower positioning limits.)
- Note that when the CPU module detects an error, such as a watchdog timer error, during self-
diagnosis, all outputs are turned off. Also, when an error that cannot be detected by the CPU
module occurs in an input/output control block, output control may be disabled. External circuits
and mechanisms should be designed to ensure safe machinery operation in such a case.
- Note that when an error occurs in a relay, transistor or triac of an output circuit, the output might
stay on or off. For output signals that may lead to serious accidents, external circuits and
mechanisms should be designed to ensure safe machinery operation in such a case.
● Construct an interlock circuit in the program so that the whole system always operates on the safe
side before executing the control (for data change) of the PLC in operation.
Read the manual thoroughly and ensure complete safety before executing other controls (for program
change, parameter change, forcible output and operation status change) of the PLC in operation.
Otherwise, the machine may be damaged and accidents may occur due to erroneous operations.
● In an output circuit, when a load current exceeding the current rating or an overcurrent caused by a
load short-circuit flows for a long time, it may cause smoke and fire. To prevent this, configure an
external safety circuit, such as a fuse.
● For the operating status of each station after a communication failure of the network, refer to relevant
manuals for the network. Incorrect output or malfunction may result in an accident.
● To maintain the safety of the programmable controller system against unauthorized access from
external devices via the network, take appropriate measures. To maintain the safety against
unauthorized access via the Internet, take measures such as installing a firewall.
1
Page 4
[DESIGN PRECAUTIONS]
CAUTION
● When an inductive load such as a lamp, heater, or solenoid valve is controlled, a large current
(approximately ten times greater than normal) may flow when the output is turned from off to on. Take
proper measures so that the flowing current does not exceed the value corresponding to the
maximum load specification of the resistance load.
● After the CPU module is powered on or is reset, the time taken to enter the RUN status varies
depending on the system configuration, parameter settings, and/or program size.
Design circuits so that the entire system will always operate safely, regardless of this variation in time.
● Simultaneously turn on and off the power supplies of the CPU module and extension modules.
● If a long-time power failure or an abnormal voltage drop occurs, the PLC stops, and output is turned
off. When the power supply is restored, it will automatically restart (when the RUN/STOP/RESET
switch is on RUN side).
[INSTALLATION PRECAUTIONS]
WARNING
● Make sure to cut off all phases of the power supply externally before attempting installation or wiring
work. Failure to do so may cause electric shock or damage to the product.
● Use the product within the generic environment specifications described in Page 20 Generic
Specifications of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt
air, Cl
condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage
may occur.
, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature,
2
2
Page 5
[INSTALLATION PRECAUTIONS]
CAUTION
● Do not touch the conductive parts of the product directly. Doing so may cause device failures or
malfunctions.
● When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the
ventilation slits of the PLC. Failure to do so may cause fire, equipment failures or malfunctions.
● For product supplied together with a dust proof sheet, the sheet should be affixed to the ventilation
slits before the installation and wiring work to prevent foreign objects such as cutting and wiring
debris.
However, when the installation work is completed, make sure to remove the sheet to provide
adequate ventilation. Failure to do so may cause fire, equipment failures or malfunctions.
● Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the
PC board, thereby causing nonconformities.
● Install the product securely using a DIN rail.
● Connect the expansion adapter securely to their designated connectors. Loose connections may
cause malfunctions.
● Work carefully when using a screwdriver such as installation of the product. Failure to do so may
cause damage to the product or accidents.
● Connect the extension cables, peripheral device cables, input/output cables and battery connecting
cable securely to their designated connectors. Loose connections may cause malfunctions.
● When using an SD memory card, insert it into the SD memory card slot. Check that it is inserted
completely. Poor contact may cause malfunction.
● Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so
may cause equipment failures or malfunctions.
-Peripheral devices, expansion adapter, and connector conversion adapter
-Extension modules, bus conversion module and connector conversion module
-Battery
3
Page 6
[WIRING PRECAUTIONS]
WARNING
● Make sure to cut off all phases of the power supply externally before attempting installation or wiring
work. Failure to do so may cause electric shock or damage to the product.
● Make sure to attach the terminal cover, provided as an accessory, before turning on the power or
initiating operation after installation or wiring work. Failure to do so may cause electric shock.
● The temperature rating of the cable should be 80 or more.
It may differ depending on the extension devices. For details, refer to the user's manual of the
extension devices.
● Make sure to wire the screw terminal block in accordance with the following precautions. Failure to do
so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
-The disposal size of the cable end should follow the dimensions described in the manual.
-Tightening torque should follow the specifications in the manual.
-Tighten the screws using a Phillips-head screwdriver No. 2 (shaft diameter 6 mm or less). Make
sure that the screwdriver does not touch the partition part of the terminal block.
● Make sure to properly wire to the terminal block (European type) in accordance with the following
precautions. Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
breakage, malfunctions, or damage to the product.
-The disposal size of the cable end should follow the dimensions described in the manual.
-Tightening torque should follow the specifications in the manual.
-Twist the ends of stranded wires and make sure that there are no loose wires.
-Do not solder-plate the electric wire ends.
-Do not connect more than the specified number of wires or electric wires of unspecified size.
-Affix the electric wires so that neither the terminal block nor the connected parts are directly
stressed.
[WIRING PRECAUTIONS]
CAUTION
● Perform class D grounding (grounding resistance: 100 Ω or less) of the grounding terminal on the
2
CPU module and extension modules with a wire 2 mm
Do not use common grounding with heavy electrical systems (refer to Page 81 Grounding).
● Connect the power supply wiring to the dedicated terminals described in this manual. If an AC power
supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out.
● Do not wire vacant terminals externally. Doing so may damage the product.
● Install module so that excessive force will not be applied to terminal blocks, power connectors, I/O
connectors, communication connectors, or communication cables. Failure to do so may result in wire
damage/breakage or PLC failure.
or thicker.
4
Page 7
CAUTION
● Make sure to observe the following precautions in order to prevent any damage to the machinery or
accidents due to malfunction of the PLC caused by abnormal data written to the PLC due to the
effects of noise.
-Do not bundle the power line, control line and communication cables together with or lay them
close to the main circuit, high-voltage line, load line or power line. As a guideline, lay the power
line, control line and communication cables at least 100 mm away from the main circuit, highvoltage line, load line or power line.
-Ground the shield of the shielded wire or shielded cable at one point on the PLC. However, do not
use common grounding with heavy electrical systems.
-Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
[STARTUP AND MAINTENANCE PRECAUTIONS]
WARNING
● Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or
malfunctions.
● Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to
do so in the power ON status may cause electric shock.
● Before modifying the program in operation, forcible output, running or stopping the PLC, read through
this manual carefully, and ensure complete safety. An operation error may damage the machinery or
cause accidents.
● Do not change the program in the PLC from two or more peripheral equipment devices at the same
time. (i.e. from an engineering tool and a GOT) Doing so may cause destruction or malfunction of the
PLC program.
● Use the battery for memory backup in conformance to this manual.
-Use the battery for the specified purpose only.
-Connect the battery correctly.
-Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or
burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery.
-Do not store or use the battery at high temperatures or expose to direct sunlight.
-Do not expose to water, bring near fire or touch liquid leakage or other contents directly.
Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid
leakage or deformation, and lead to injury, fire or failures and malfunction of facilities and other
equipment.
5
Page 8
[STARTUP AND MAINTENANCE PRECAUTIONS]
CAUTION
● Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
● After the first use of the SD memory card, do not insert/remove the memory card more than 500 times.
500 times or more may cause malfunction.
● Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do
so may cause equipment failures or malfunctions.
● Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so
may cause equipment failures or malfunctions.
-Peripheral devices, expansion adapter and connector conversion adapter
-Extension modules, bus conversion module, and connector conversion module
-Battery
[OPERATION PRECAUTIONS]
CAUTION
● Construct an interlock circuit in the program so that the whole system always operates on the safe
side before executing control (for data change) of the PLC in operation. Read the manual thoroughly
and ensure complete safety before executing other controls (for program change, parameter change,
forcible output and operation status change) of the PLC in operation. Otherwise, the machine may be
damaged and accidents may occur by erroneous operations.
[DISPOSAL PRECAUTIONS]
CAUTION
● Please contact a certified electronic waste disposal company for the environmentally safe recycling
and disposal of your device.
● When disposing of batteries, separate them from other waste according to local regulations. (For
details on the Battery Directive in EU countries, refer to Page 175 Handling of Batteries and
Devices with Built-in Batteries in EU Member States.)
6
Page 9
[TRANSPORTATION PRECAUTIONS]
CAUTION
● When transporting the PLC with the optional battery, turn on the PLC before shipment, confirm that
the battery mode is set using a parameter and the BAT LED is OFF, and check the battery life. If the
PLC is transported with the BAT LED ON or the battery exhausted, the battery-backed data may be
unstable during transportation.
● The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in
the general specifications (Page 20 Generic Specifications) by using dedicated packaging boxes
and shock-absorbing palettes. Failure to do so may cause failures in the PLC. After transportation,
verify operation of the PLC and check for damage of the mounting part, etc.
● When transporting lithium batteries, follow required transportation regulations. (For details on the
regulated products, refer to Page 175 Handling of Batteries and Devices with Built-in Batteries in
EU Member States.)
● When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are
used for disinfecting and protecting wooden packaging from insects, they cause malfunction when
entering our products. Please take necessary precautions to ensure that remaining materials from
fumigant do not enter our product, or treat packaging with methods other than fumigation (heat
method). Additionally, disinfect and protect wood from insects before packing products.
INTRODUCTION
This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and
operation of the FX5UC Programmable Controllers and should be read and understood before attempting to install or use the
module.
Always forward it to the end user.
Regarding use of this product
• This product has been manufactured as a general-purpose part for general industries, and has not been designed or
manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger
movement vehicles, consult Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product where major
accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
Note
• If in doubt at any stage during the installation of the product, always consult a professional electrical engineer who is
qualified and trained in the local and national standards. If in doubt about the operation or use, please consult the nearest
Mitsubishi Electric representative.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference, please use it after
confirming the function and safety of the equipment and system. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed, without a notice, for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you notice a doubtful
point, an error, etc., please contact the nearest Mitsubishi Electric representative. When doing so, please provide the
Lit: Can be used or cannot be removed.
Flashing: In preparation
Off: Not inserted or can be removed.
1 OUTLINE
1.1 Part Names
17
Page 20
No.NameDescription
[1]
[2]
[3]
[4]
[5]
[9]Output connectorConnector for connecting output signal cables.
[10]DIN rail mounting hookHook for mounting a CPU module on a DIN rail of DIN46277 (35 mm wide).
[11]SD memory card disable switchSwitch for disabling access to the SD memory card when the card is to be removed.
[12]SD memory card slotSlot for inserting an SD memory card.
[13]RUN/STOP/RESET switchSwitch for operating the CPU module. (Page 121 Methods of running, stopping, and resetting)
RUN: Runs the program
STOP: Stops the program
RESET: Resets the CPU module (hold the switch on the RESET side for approximately 1 second.)
Side
Left side/right side
No.NameDescription
[1]Expansion adapter connector coverCover for protecting the expansion adapter connector.
[2]Subsequent extension connector coverCover for protecting the subsequent extension connector.
[3]DIN rail mounting grooveThe module can be installed on a DIN46277 rail (35 mm wide).
[4]NameplateThe product model name, manufacturer's serial number, power supply specifications, and MAC
[5]Genuine product certification labelGenuine product certification label to prevent counterfeiting
address are shown.
Products that do not have the genuine product certification label or nameplate are not covered by the
warranty.
18
1 OUTLINE
1.1 Part Names
Page 21
Bottom side
[3]
[2]
[1]
No.NameDescription
[1]Battery coverCover for protecting the battery connecting connector.
[2]Power connector for CPU moduleConnector for connecting power cables.
[3]RS-485 terminal resistor selector switchSwitch for switching terminal resistance for built-in RS-485 communication.
Use a tool such as a screwdriver to operate the RS-485 terminal resistance selector switch. Make sure that
the tip of a tool does not damage the switch or case.
1
1 OUTLINE
1.1 Part Names
19
Page 22
2SPECIFICATIONS
The CPU module specifications are explained below.
2.1Generic Specifications
ItemSpecifications
Operating ambient temperature
Storage ambient temperature-25 to 75, non-freezing
Operating ambient humidity5 to 95%RH, non-condensation
Storage ambient humidity5 to 95%RH, non-condensation
Vibration resistance
Shock resistance
Noise durabilityBy noise simulator at noise voltage of 1000 Vp-p, noise width of 1 μs and period of 30 to 100 Hz
GroundingClass D grounding (grounding resistance: 100 Ω or less) <Common grounding with a heavy electrical system is not
Working atmosphereFree from corrosive or flammable gas and excessive conductive dust
Operating altitude
Installation locationInside a control panel
Overvoltage category
Pollution degree
Equipment classClass 2
*1 The simultaneous ON ratio of available PLC inputs or outputs changes with respect to the ambient temperature, refer to Page 24
Input/Output Derating Curve.
*2 The operating ambient temperature is 0 to 55 for products manufactured before June 2016. For details on Intelligent function
modules, refer to manuals of each product.
*3 In the case where operating ambient temperature is lower than 0, the specifications are different from the above description. For
details, refer to Page 139 Precautions for operating ambient temperature.
*4 When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are sudden
temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a
fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent condensation.
*5 The criterion is shown in IEC61131-2.
*6 When the system has equipment which specification values are lower than above mentioned vibration resistance specification values,
the vibration resistance specification of the whole system is corresponding to the lower specification.
*7 For grounding, refer to Page 81 Grounding.
*8 The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
*9 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises. Category applies to equipment for which electrical power is supplied from
fixed facilities. The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
*10 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used. Pollution
level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.
*5*6
*5
*8
*9
*10
*1
-20 to 55, non-freezing
FrequencyAccelerationHalf amplitudeSweep count
Installed on DIN
rail
147 m/, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
*7
allowed.>
0 to 2000 m
or less
2 or less
*2*3
*4
5 to 8.4 Hz1.75 mm10 times each in X, Y, Z directions
8.4 to 150 Hz4.9 m/
(80 min in each direction)
Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltages between each terminal and
the CPU module ground terminal.
■ CPU module, I/O module
Between terminalsDielectric withstand voltage Insulation resistanceRemarks
Between power supply terminal (24 V DC) and ground terminal500 V AC for one minute10 MΩ or higher by 500 V DC
Between input terminal (24 V DC) and ground terminal
Between output terminal (transistor) and ground terminal
Between output terminal (relay) and ground terminal1.5 kV AC for one minuteI/O module only
20
2 SPECIFICATIONS
2.1 Generic Specifications
insulation resistance tester
Page 23
■Expansion adapter
1 scan time
Power failure
detection time
SD8008
5 ms
Approx.
2 ms
DC power supply
SM8000:
SM8007:
SM8008:
RUN monitor
Momentary
power failure
detection
Power failure
detected
For information concerning the dielectric withstand voltage and insulation resistance of each expansion adapter, refer to
manuals of each expansion adapter.
■Intelligent function module
For information concerning dielectric withstand voltage and insulation resistance of each intelligent function module, refer to
manuals of each intelligent function module.
2.2Power Supply Specifications
The CPU module power supply specifications are explained below.
For the consumption current of each extension module, refer to Page 31 PRODUCT LIST or manuals of each extension
module.
DC power supply
ItemSpecifications
Power supply voltage24 V DC
Voltage fluctuation range+20%, -15%
Allowable instantaneous power failure timeOperation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse125 V, 3.15 A Time-lag fuse
Rush currentFX5UC-32MT/35 A max. 0.5 ms or less/24 V DC
FX5UC-64MT/
FX5UC-96MT/
Power consumption
24 V DC power supply capacity500 mA
5 V DC power supply capacity720 mA
*1 This item shows value when only the CPU module is used.
The value in [] is the value in the maximum configuration connectable to the CPU module. (The value does not include the external 24 V
DC power supply of extension devices)
*1
FX5UC-32MT/5 W/24 V DC [30 W/24 V DC +20%, -15%]
FX5UC-64MT/8 W/24 V DC [33 W/24 V DC +20%, -15%]
FX5UC-96MT/11 W/24 V DC [36 W/24 V DC +20%, -15%]
40 A max. 0.5 ms or less/24 V DC
2
The following shows the power failure detection time of the FX5UC CPU module.
2.2 Power Supply Specifications
2 SPECIFICATIONS
21
Page 24
2.3Input Specifications
The CPU module input specifications are explained below.
24 V DC input (sink/source)
Input numbers in the table indicate the CPU module umbers.
ItemSpecifications
No. of input pointsFX5UC-32MT/16 points
FX5UC-64MT/32 points
FX5UC-96MT/48 points
Connection typeConnector
Input typeFX5UC-MT/DSink
FX5UC-MT/DSSSink/source
Input signal voltage24 V DC +20%, -15%
Input signal currentX0 to X175.3 mA/24 V DC
X20 and
subsequent
Input impedanceX0 to X174.3 kΩ
X20 and
subsequent
ON input sensitivity currentX0 to X173.5 mA or more
X20 and
subsequent
OFF input sensitivity current1.5 mA or less
Input
response
frequency
Pulse
waveform
FX5UC-32MT/X0 to X5200 kHz
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-32MT/X6 to X1710 kHz
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-64MT/,
FX5UC-96MT/
Wave form
X0 to X7
X10 to X17
X20 and
subsequent
4.0 mA/24 V DC
5.6 kΩ
3.0 mA or more
When capturing pulses of a response frequency of 50 to 200 kHz, refer to Page 88 When a
high-speed pulse is captured.
0.1±0.05 kHz
T1T1
Input
response
time
(H/W filter
delay)
Input response time
(Digital filter setting value)
2 SPECIFICATIONS
22
2.3 Input Specifications
T1 (pulse width)T2 (rise/fall time)
FX5UC-32MT/X0 to X52.5 μs or more1.25 μs or less
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-32MT/X6 to X1750 μs or more25 μs or less
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-32MT/
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-32MT/X6 to X17ON: 30 μs or less
FX5UC-64MT/,
FX5UC-96MT/
FX5UC-64MT/,
FX5UC-96MT/
X0 to X7
X10 to X17
X0 to X5ON: 2.5 μs or
X0 to X7
X10 to X17
X20 and
subsequent
OFF: 2.5 μs or less
OFF: 50 μs or less
ON: 50 μs or less
OFF: 150 μs or less
None, 10 μs, 50 μs, 0.1 ms, 0.2 ms, 0.4 ms, 0.6 ms, 1 ms, 5 ms, 10 ms (initial value), 20 ms, 70 ms
When using this product in an environment with much noise, set the digital filter.
less
T2T2
Page 25
ItemSpecifications
X
COM
24 V DC
Fuse
*1: Input impedance
*1
Photocoupler
X
COM0
Photocoupler
24 V DC
Fuse
*1: Input impedance
*1
Input signal formatFX5UC-MT/DNo-voltage contact input
NPN open collector transistor
FX5UC-MT/DSSNo-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
Input circuit insulationPhoto-coupler insulation
Indication of input operationLED is lit when input is on (DISP switch: IN)
The CPU module output specifications are explained below.
Transistor output
ItemOutput specifications
No. of output pointsFX5UC-32MT/16 points
FX5UC-64MT/32 points
FX5UC-96MT/48 points
Connection typeConnector
Output typeFX5UC-MT/DTransistor/sink output
FX5UC-MT/DSSTransistor/source output
External power supply5 to 30 V DC
Max. loadY0 to Y30.3 A/pointThe total load current per common terminal should be the following value.
Y4 and subsequent0.1 A/point
Open circuit leakage current0.1 mA or less/30 V DC
Voltage drop when ONY0 to Y31.0 V or less
Y4 and subsequent1.5 V or less
Response timeY0 to Y32.5 μs or less/10 mA or more (5 to 24 V DC)
Y4 and subsequent0.2 ms or less/100 mA (24 V DC)
Insulation of circuitPhoto-coupler insulation
Indication of output operationLED is lit when output is on (DISP switch: OUT)
Output circuit configuration
• 8 output points/common terminal: 0.8 A or less
For details of the common, refer to Page 29 Terminal Layout.
*1
*1 When two common terminals are connected outside the CPU module, resistance load is 1.6A or less.
2.5Input/Output Derating Curve
The derating curve below shows the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient
temperature. Use the PLC within the simultaneous input or output ON ratio range shown in the figure.
24
2 SPECIFICATIONS
2.4 Output Specifications
Page 27
2.6Performance Specifications
ItemSpecifications
Control systemStored-program repetitive operation
Input/output control systemRefresh system
(Direct access input/output allowed by specification of direct access input/output [DX, DY])
Programming
specifications
Operation
specifications
Command
processing time
Memory
capacity
Flash memory (Flash ROM) write countMaximum 20000 times
File storage
capacity
Clock functionDisplay dataYear, month, day, hour, minute, second, day of week (leap year automatic detection)
Power failure
retention
(clock data
No. of input/
output points
Power failure
retention
(device)
*1 Interrupt from the intelligent function module and high-speed pulse input/output module.
*2 The value listed above indicates the number of files stored in the root folder.
*3 Clock data is retained using the power accumulated in a large-capacity capacitor incorporated into the PLC. When voltage of the large-
capacity capacitor drops, clock data is no longer accurately retained. The retention period of a fully charged capacitor (electricity is
conducted across the PLC for at least 30 minutes) is 10 days (ambient temperature: 25). How long the capacitor can hold the data
depends on the operating ambient temperature. When the operating ambient temperature is high, the holding period is short.
*4 It is possible to back up all devices in device (high-speed) area. When a battery is used, it is also possible to back up devices in device
(standard) area.
Programming languageLadder diagram (LD), structured text (ST), function block diagram/ladder diagram (FBD/LD)
Programming extension functionFunction block (FB), function (FUN), label programming (local/global)
Constant scan0.2 to 2000 ms (can be set in 0.1 ms increments)
Fixed cycle interrupt1 to 60000 ms (can be set in 1 ms increments)
Timer performance specifications100 ms, 10 ms, 1 ms
Data memory
P: No. of program files
FB: No. of FB files
SD Memory CardNZ1MEM-2GBSD: 511
PrecisionDifferences per month ±45 sec./25 (TYP)
Retention methodLarge-capacity capacitor
Retention time10 days (Ambient temperature: 25)
*3
)
(1) No. of input/output points256 points or less
(2) No. of remote I/O points384 points or less
Total No. of points of (1) and (2)512 points or less
Power failure retention capacityMaximum 12 k word
(128 kbytes, flash memory)
P: 32, FB: 16
*2
NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD: 65534
*4
*2
2
*1
2 SPECIFICATIONS
2.6 Performance Specifications
25
Page 28
Number of device points
ItemBase Max. number of points
No. of user device points Input relay (X)81024 pointsThe total number of X and Y assigned to input/output points is up
Output relay (Y)81024 points
Internal relay (M)1032768 points (can be changed with parameter)
Latch relay (L)1032768 points (can be changed with parameter)
Link relay (B)1632768 points (can be changed with parameter)
Annunciator (F)1032768 points (can be changed with parameter)
Link special relay (SB)1632768 points (can be changed with parameter)
Step relay (S)104096 points (fixed)
Timer systemTimer (T)101024 points (can be changed with parameter)
Accumulation
timer system
Accumulation
timer (ST)
101024 points (can be changed with parameter)
Counter systemCounter (C)101024 points (can be changed with parameter)
Long counter (LC) 101024 points (can be changed with parameter)
Data register (D)108000 points (can be changed with parameter)
Link register (W)1632768 points (can be changed with parameter)
Link special register (SW)1632768 points (can be changed with parameter)
No. of system device
points
Special relay (SM)1010000 points (fixed)
Special register (SD)1012000 points (fixed)
Module access deviceIntelligent function module device1065536 points (designated by U\G)
No. of index register
points
Index register (Z)
*2
Long index register (LZ)
*2
1024 points
1012 points
No. of file register points File register (R)1032768 points (can be changed with parameter)
No. of nesting pointsNesting (N)1015 points (fixed)
No. of pointer pointsPointer (P)104096 points
Interrupt pointer (I)10178 points (fixed)
OthersDecimal constant
(K)
Signed16 bits: -32768 to +32767, 32 bits: -2147483648 to +2147483647
Unsigned16 bits: 0 to 65535, 32 bits: 0 to 4294967295
Hexadecimal constant (H)16 bits: 0 to FFFF, 32 bits: 0 to FFFFFFFF
Real constant (E) Single precisionE-3.40282347+38 to E-1.17549435-38, 0, E1.17549435-38 to E3.40282347+38
Character stringShift-JIS code: Max. 255 single-byte characters (256 including NULL)
*1 Can be changed with parameters within the capacity range of the CPU built-in memory.
*2 Total of the index register (Z) and long index register (LZ) is maximum 24 words.
to 256 points.
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
26
2 SPECIFICATIONS
2.6 Performance Specifications
Page 29
2.7Communication Specifications
The built-in Ethernet and built-in RS-485 communication specifications are as explained below.
Built-in Ethernet communication
For details of built-in Ethernet communication, refer to the following.
Communication modeFull-duplex (FDX)/ Half-duplex (HDX)
InterfaceRJ45 connector
Transmission methodBase band
Maximum segment length (The distance between hub
and node)
Cascade connection100BASE-TXMax. 2 stages
10BASE-TMax. 4 stages
Protocol typeCC-Link IE field network Basic
Number of simultaneously open connections allowedTotal of 8 connections
*1
Hub
Insulation methodPulse transformer insulation
IP address
Cable used
*5
*6
For 100BASE-TX
connection
For 10BASE-T
connection
100 m
*2
*2
MELSOFT connection
SLMP (3E frame)
Socket communication
Predefined protocol support
FTP server
*3*4
(Up to 8 external devices can access one CPU module at the same time.)
Hubs with 100BASE-TX or 10BASE-T ports can be used.
Initial value: 192.168.3.250
Ethernet standard-compatible cable, category 5 or higher (STP cable)
Ethernet standard-compatible cable, category 3 or higher (STP cable)
2
*1
*1 IEEE802.3x flow control is not supported.
*2 Number of stages that can be connected when a repeater hub is used. When a switching hub is used, check the specifications of the
switching hub used.
*3 The first device for MELSOFT connection is not included in the number of connections. (The second and the following devices are
included.)
*4 The CC-Link IE field network Basic and FTP server are not included in the number of connections.
*5 If the first octet is 0 or 127, a parameter error (2222H) will occur. (Example: 0.0.0.0, 127.0.0.0, etc.)
*6 A straight cable can be used. If a personal computer or GOT and CPU module are directly connected a cross cable can be used.
2 SPECIFICATIONS
2.7 Communication Specifications
27
Page 30
Built-in RS-485 communication
90
W
89.1
74
Unit: mm
For details of built-in RS-485 communication, refer to the following.
The following shows the system configuration equipment of the FX5UC.
3.1Overall Configuration
3
*1 The extension connector of the extension power supply module can use either connector connection or cable connection.
*2 Use this to connect a module (extension cable type) located distantly or on a second stage. The connector conversion adapter (FX5-
When using connector connection, an extension connector type module can be connected.
CNV-BC) is required when the connection destination is a module of extension cable type (except for extension power supply module).
When also using a bus conversion module in the same system, connect the powered input/output module directly after the extended
extension cable.
3 PRODUCT LIST
3.1 Overall Configuration
31
Page 34
3.2CPU Module
FX5UCM
Power supply, input/output type: Connection on connector
• T/DSS: DC power supply/24 V DC (sink/source) input/Transistor (source) output
• T/D: DC power supply/24 V DC (sink) input/Transistor (sink) output
CPU moduleTotal number of
input/output points
Model name
The CPU module incorporates a CPU, memory, input/output terminals, and power supply.
24 V DC sink and source input type
ModelNo. of input/output pointsInput typeOutput
Total No.
of points
FX5UC-32MT/D32 points16 points16 points24 V DC
FX5UC-32MT/DSS24 V DC
FX5UC-64MT/D64 points32 points32 points24 V DC
FX5UC-64MT/DSS24 V DC
FX5UC-96MT/D96 points48 points48 points24 V DC
FX5UC-96MT/DSS24 V DC
No. of input
points
No. of output
points
(sink)
(sink/source)
(sink)
(sink/source)
(sink)
(sink/source)
type
Transistor
(sink)
Transistor
(source)
Transistor
(sink)
Transistor
(source)
Transistor
(sink)
Transistor
(source)
The model name of the CPU module can be checked on the nameplate on the right side. After extension
devices are connected, the nameplate cannot be seen. Check the model name in the following places.
• T/D: 24 V DC (sink) input/Transistor (sink) output
• T/DSS: 24 V DC (sink/source) input/Transistor (source) output
• R/ES: 24 V DC (sink/source) input/relay output
• T/ES: 24 V DC (sink/source) input/transistor (sink) output
• T/ESS: 24 V DC (sink/source) input/transistor (source) output
Powered input/output module
• R/DS: DC power supply/24 V DC (sink/source) input/relay output
• T/DS: DC power supply/24 V DC (sink/source) input/transistor (sink) output
• T/DSS: DC power supply/24 V DC (sink/source) input/transistor (source) output
High-speed pulse input/output module
• T/ES-H: 24 V DC (sink/source) input/Transistor (sink) output
• T/ESS-H: 24 V DC (sink/source) input/Transistor (source) output
Input/output
extension
Total number of
input/output points
Connection type
• No symbol:
Terminal block
• C: Connector
Extension modules are used to expand inputs/outputs, functions, and others.
The two connection types, extension connector type and extension cable type, are provided for extension modules.
•
Extension connector type
•
Extension cable type
FX5-CNV-IFC or FX5-C1PS-5V is required to use modules of extension cable type.
I/O module
I/O modules are used to expand inputs/outputs.
For details, refer to Page 140 I/O Module.
Pullout tab
3
Extension cable
3.3 Extension Module
3 PRODUCT LIST
33
Page 36
Input module
Input modules are used to expand inputs.
■Extension connector type
ModelNumber of input/output pointsInput typeOutput
Total No.
of points
FX5-C16EX/D16 points16 points24 V DC
FX5-C16EX/DS24 V DC
FX5-C32EX/D32 points32 points24 V DC
FX5-C32EX/DS24 V DC
No. of
input
points
No. of
output
points
(sink)
(sink/source)
(sink)
(sink/source)
type
Connector100 mA65 mA
Connector120 mA130 mA
■Extension cable type
ModelNumber of input/output pointsInput typeOutput
Total No.
of points
FX5-8EX/ES8 points8 points24 V DC
FX5-16EX/ES16 points16 points100 mA(85 mA)
No. of
input
points
No. of
output
points
(sink/source)
type
Terminal
Connection
type
Connection
type
block
Current consumption
5 V DC
power
supply
24 V DC
power
supply
External 24 V DC
power supply
(24 V DC power
supply for input
circuits)
Current consumption
5 V DC power
supply
75 mA(50 mA)
24 V DC power
supply
*1
*1
*1 Since external power supply is used for input circuit in FX5UC CPU module systems, power supply from CPU module or extension
power supply module is not included.
Output module
Output modules are used to expand outputs.
■Extension connector type
ModelNumber of input/output pointsInput typeOutput
Total No.
of points
FX5-C16EYT/D16 points16 pointsTransistor
FX5-C16EYT/DSSTransistor
FX5-C32EYT/D32 points32 pointsTransistor
FX5-C32EYT/DSSTransistor
No. of
input
points
No. of
output
points
type
(sink)
(source)
(sink)
(source)
Connection
type
Connector100 mA100 mA
Connector120 mA200 mA
Current consumption
5 V DC power
supply
24 V DC power
supply
34
3 PRODUCT LIST
3.3 Extension Module
Page 37
■Extension cable type
ModelNumber of input/output pointsInput typeOutput
Total No.
of points
FX5-8EYR/ES8 points8 pointsRelayTerminal
FX5-8EYT/ESTransistor
FX5-8EYT/ESSTransistor
FX5-16EYR/ES16 points16 pointsRelayTerminal
FX5-16EYT/ESTransistor
FX5-16EYT/ESSTransistor
No. of
input
points
No. of
output
points
type
(sink)
(source)
(sink)
(source)
Connection
type
block
block
Input/output module
Input/output modules are used to expand inputs/outputs.
■Extension connector type
ModelNumber of input/output pointsInput typeOutput
Total No.
of points
FX5-C32ET/D32 points16 points16 points24 V DC
FX5-C32ET/DSS24 V DC
No. of
input
points
No. of
output
points
(sink)
(sink/source)
type
Transistor
(sink)
Transistor
(source)
Connection
type
Connector120 mA100 mA65 mA
Current consumption
5 V DC power
supply
75 mA75 mA
100 mA125 mA
24 V DC power
supply
Current consumption
5 V DC
power
supply
24 V DC
power
supply
External 24 V DC
power supply
(24 V DC power
supply for input
circuits)
3
■Extension cable type
ModelNo. of input/output pointsInput typeOutput
Total No.
of points
FX5-16ER/ES16 points8 points8 points24 V DC
FX5-16ET/ESTransistor
FX5-16ET/ESSTransistor
No. of
input
points
No. of
output
points
(sink/source)
type
RelayTerminal100 mA125 mA
(sink)
(source)
Connection
type
Current consumption
5 V DC power
supply
Powered input/output module
The powered input/output module includes a power supply and is used to expand input/output
ModelNo. of input/output pointsInput typeOutput
Total No.
of points
FX5-32ER/DS32 points16 points16 points24 V DC
FX5-32ET/DSTransistor
FX5-32ET/DSSTransistor
No. of
input
points
No. of
output
points
(Sink/source)
type
RelayTerminal
(sink)
(source)
Connection
type
block
Power supply capacity
5 V DC power
supply
965 mA310 mA
24 V DC power
supply
24 V DC power
supply
3 PRODUCT LIST
3.3 Extension Module
35
Page 38
High-speed pulse input/output module
The high-speed pulse input/output module is a product for extending the high-speed input/output.
ModelNo. of input/output pointsInput typeOutput
Total No.
of points
FX5-16ET/ES-H*116 points8 points8 points24 V DC
FX5-16ET/ESS-H
*1
No. of
input
points
No. of
output
points
(Sink/source)
type
Transistor
(sink)
Transistor
(source)
*1 For supported versions, refer to Page 176 Added and Changed Functions.
*2 External power supply is used for input circuit in FX5UC CPU module systems. This value is the current consumed internally.
Connection
type
Terminal
block
Current consumption
5 V DC power
supply
100 mA125 mA
24 V DC power
supply
(82 mA
Intelligent function module
Intelligent function modules, such as simple motion modules, have functions other than input/output.
For details, refer to manuals of each module.
FX5 intelligent function module
The following FX5 intelligent function module can be used in FX5UC systems using connector conversion modules.
For the connector conversion modules to be connected, refer to Page 38 Connector conversion module.
■Analog
ModelFunctionNo. of occupied
input/output
points
*1
FX5-8AD
FX5-4LC
*1
8-ch voltage input/current input/thermocouple
input/resistance thermometer input
4-ch temperature control (thermocouple/
resistance thermometer/micro voltage)
4-point current sensor input
4-point transistor output
8 points40 mA100 mA
8 points140 mA25 mA
Current consumption
5 V DC power
supply
24 V DC
power supply
External 24 V DC
power supply
*2
)
■Positioning
ModelFunctionNo. of occupied
input/output
points
FX5-20PG-P
*1
Pulse output for 2-axis control (transistor)8 points 120 mA
Current consumption
5 V DC power
supply
24 V DC
power supply
External 24 V DC
power supply
■Simple motion
ModelFunctionNo. of occupied
input/output
points
FX5-40SSC-S4-axis control (compatible with SSCNET /H)8 points 250 mA
*1
FX5-80SSC-S
8-axis control (compatible with SSCNET /H)8 points 250 mA
Current consumption
5 V DC power
supply
24 V DC
power supply
External 24 V DC
power supply
36
3 PRODUCT LIST
3.3 Extension Module
Page 39
■Network
ModelFunctionNo. of occupied
input/output
points
FX5-CCLIEF
FX5-CCL-MS
FX5-ASL-M
*1 For supported versions, refer to Page 176 Added and Changed Functions.
*2 When using with the master station, the number of remote I/O points is added. For details, refer to Page 48 Calculation of the
*3 This value does not include supply current to slave modules. For details, refer to MELSEC iQ-F FX5 User's Manual (ASLINK).
*4 Note that the warranty for this model differs from the ones for other PLCs. For details, refer to MELSEC iQ-F FX5 User's Manual
*1
*1*4
number of remote I/O points.
(ASLINK).
Intelligent device station for CC-Link IE Field
network
*1
Master station/intelligent device station for CCLink (Ver. 2.00 and Ver.1.10 compatible)
Master for AnyWireASLINK8 points200 mA100 mA
8 points10 mA230 mA
*2
8 points
Current consumption
5 V DC power
supply
100 mA
24 V DC
power supply
External 24 V DC
power supply
*3
FX3 intelligent function module
The following FX3 intelligent functions modules can be used in FX5UC systems by using bus conversion modules.
For the bus conversion modules to be connected, refer to Page 39 Bus conversion module.
To use the modules, refer to Page 43 Bus conversion module.
■Analog
ModelFunctionNo. of occupied
input/output
points
FX3U-4AD4-ch voltage/current input8 points110 mA90 mA
FX3U-4DA4-ch voltage/current output120 mA160 mA
FX3U-4LC4-ch temperature control (thermocouple/
resistance thermometer/micro voltage)
4-point current sensor input
4-point transistor output
Current consumption
5 V DC power
supply
160 mA50 mA
24 V DC
power supply
External 24 V DC
power supply
3
■Positioning
ModelFunctionNo. of occupied
input/output
points
FX3U-1PGPulse output for independent 1-axis control8 points150 mA40 mA
Current consumption
5 V DC power
supply
24 V DC
power supply
External 24 V DC
power supply
■High-speed counter
ModelFunctionNo. of occupied
input/output
points
FX3U-2HC2-ch high-speed counter8 points245 mA
Current consumption
5 V DC power supply24 V DC power supply
3 PRODUCT LIST
3.3 Extension Module
37
Page 40
■Network
Precautions
ModelFunctionNo. of occupied
input/output
points
FX3U-16CCL-MMaster station for CC-Link (compatible with Ver.
2.00 and Ver. 1.10)
FX3U-64CCLIntelligent device station for CC-Link8 points 220 mA
*4
FX3U-128ASL-M
*1 Number of remote I/O points is added. For details, refer to Page 48 Calculation of the number of remote I/O points.
*2 The number of input/output points set by the rotary switch is added. For details, refer to FX3U-128ASL-M User's Manual.
*3 This value does not include supply current to slave modules. For details, refer to FX3U-128ASL-M User's Manual.
*4 Note that the warranty for this model differs from the ones for other PLCs. For details, refer to FX3U-128ASL-M User's Manual.
Master for AnyWireASLINK8 points
8 points
*1
*2
• Some FX3 intelligent function modules are not supported. For details, refer to the user's manual for each product.
• When using the network module of the FX3 intelligent function module, set the parameter in the program.
• The bus speed for accessing the FX3 intelligent function module is the FX3 speed.
Current consumption
5 V DC power
supply
240 mA
130 mA100 mA
24 V DC
power supply
External 24 V DC
power supply
*3
Extension power supply module
The extension power supply module is an added power supply if the built-in power supply of the CPU module is insufficient.
For details on the specifications of the extension power supply module, refer to MELSEC iQ-F FX5-C1PS-5V Hardware
Manual.
ModelFunctionNo. of occupied
input/output
points
FX5-C1PS-5VExtension power supply1200 mA
Power supply capacity
5 V DC power supply24 V DC power supply
*1
625 mA
*1
*1 If the ambient temperature exceeds 40, use the extension power supply module at the following current values within the derating
range.
Derating curve
Output current [mA]
1200
800
625
400
24 V DC
5 V DC
Ambient
5540
temperature []
Connector conversion module
Connector conversion modules are used to connect FX5 extension module (extension cable type) in FX5UC systems.
ModelFunctionNo. of occupied
input/output
points
FX5-CNV-IFCConnector conversion from CPU module or
extension modules (extension connector type)
Current consumption
5 V DC power supply24 V DC power supply
38
3 PRODUCT LIST
3.3 Extension Module
Page 41
Bus conversion module
Bus conversion modules are used to connect FX3 intelligent functions modules in FX5UC systems. For details of the
specifications of each bus conversion module, refer to the hardware manual of each product.
ModelFunctionNo. of occupied
input/output
points
FX5-CNV-BUSCBus conversion from CPU module or extension
modules (extension connector type)
FX5-CNV-BUSBus conversion from extension modules
(extension cable type) or FX5 intelligent function
modules
8 points150 mA
8 points150 mA
Current consumption
5 V DC power supply24 V DC power supply
3.4Expansion Adapter
Expansion adapters are used to expand functions and are connected on the left side of the CPU module.
For details of the specifications of each expansion adapter, refer to the hardware manual of each product.
ModelFunctionNo. of occupied
input/output
points
FX5-4AD-ADP4-CH voltage/current input10 mA20 mA
FX5-4DA-ADP4-CH voltage/current output10 mA160 mA
*1 For supported versions, refer to Page 176 Added and Changed Functions.
3.5Extended Extension Cable and Connector
Conversion Adapter
Extended Extension Cable
Use this to install the FX5 extension module (extension cable type) at a remote location. When the connection destination is
a module of extension cable type (except for extension power supply module), always use the connector conversion adapter
(FX5-CNV-BC).
ModelFunction
FX5-30ECDistance between modules (0.30 m)
FX5-65ECDistance between modules (0.65 m)
Connector Conversion Adapter
Adapter for connecting extended extension cable and module of extension cable type (except for extension power supply
module).
ModelFunction
FX5-CNV-BCConnector conversion adapter for connecting extended extension cable and module of extension cable type (except for extension
power supply module).
3 PRODUCT LIST
3.4 Expansion Adapter
39
Page 42
3.6Terminal Module
For details of the terminal modules, refer to Page 160 Terminal Module.
ModelFunctionNo. of occupied
input/output
points
FX-16E-TBDirectly connected to the I/O connector of a
FX-32E-TB112 mA/16 points
FX-16EX-A1-TB100 V AC input type48 mA
FX-16EYR-TBRelay output type80 mA
FX-16EYT-TBTransistor output type (sink output)11 2 mA
FX-16EYS-TBTriac output type112 mA
FX-16E-TB/ULDirectly connected to the I/O connector of a
FX-32E-TB/UL112 mA/16 points
FX-16EYR-ES-TB/ULRelay output type80 mA
FX-16EYT-ES-TB/ULTransistor output type (sink output)112 mA
FX-16EYT-ESS-TB/ULTransistor output type (source output)112 m A
FX-16EYS-ES-TB/ULTriac output type112 m A
PLC.
PLC.
112 mA
112 mA
Current consumption
5 V DC power
supply
24 V DC
power supply
External 24 V DC
power supply
3.7SD Memory Card
For details of the SD memory card, refer to Page 158 SD Memory Card.
ModelFunction
NZ1MEM-2GBSDSD memory card (Mitsubishi product)
NZ1MEM-4GBSD
NZ1MEM-8GBSD
NZ1MEM-16GBSD
L1MEM-2GBSD
L1MEM-4GBSD
3.8Battery
For details of the battery, refer to Page 123 Battery.
ModelFunction
FX3U-32BLBattery
3.9Communication Cable
Use a communication cable to connect a PLC with a personal computer by RS-232C communication.
ModelFunction
FX-232CAB-1FX5-232ADP⇔Personal computer
3.10Engineering Tool
For design and programming of FX5UC systems, use GX Works3.
For the operation method, refer to the GX Works3 Operating Manual.
ModelFunction
GX Works3MELSEC PLC software package
40
3 PRODUCT LIST
3.6 Terminal Module
Page 43
4SYSTEM CONFIGURATION
Ex.
FX3U-16CCL-M
Module No. 5
FX3U-4DA
Module No. 4
FX3U-4AD
Module No. 3
FX3 extension module
CC-Link slave station
FX5 extension module
FX3 extension module
FX5-C1PS-5V
FX5-CNV-IFC
X0 to X17
FX5UC-32MT/D
I/O moduleI/O moduleExtension power
supply module
Y0 to Y17
-
Y20 to Y57
FX5-C32EYT/DFX5-232ADP
Configuration of a whole system
CPU module
Expansion
adapter
X20 to X57
-
FX5-C32EX/D
Remote I/ORemote I/O
FX5-C32ET/D
Y60 to Y77
X60 to X77
Input/output
module
Connector
conversion
module
Intelligent
module
Intelligent
module
Intelligent
module
Expansion
adapter
Output
module
Input
module
FX5 extension module
FX5-40SSC-S
Module No. 1
FX5-CNV-BUS
Module No. 2
I/O module
Intelligent module
I/O module
Extended
extension
cable
Y100 to Y117
FX5-16EYR/ES
X100 to X117
X120 X137
Y120 Y137
-
FX5-16EX/ES
Simple motion
module
Powered
input/output module
Bus
conversion
module
Output
module
Input
module
FX5-32ER/DS
FX5 extension
module
Configuration of a whole system
The configuration of an entire system is shown below as an example.
For assignment of the module numbers for extension module, refer to Page 63 Module number of Extension modules.
4
4 SYSTEM CONFIGURATION
41
Page 44
4.1Rules of System Configuration
Ex.
CPU module
Up to
2 modules
Up to
1 module
Up to
1 module
Expansion
adapter
(Communi-
cation)
Up to
4 modules
Expansion
adapter
(Analog)
Connector
conversion
module
Bus
conversion
module
Up to 16 modules
*1
Up to
6 modules
Input
module,
Output
module
Up to
2 modules
Up to
12 modules
Up to
10 modules
Extension
power
supply
module
Input
module,
Output
module
Input
module,
Output
module
FX5
intelligent
module
FX3
intelligent
module
Up to 8 modules
Power is supplied from the CPU module.
Power is supplied from the
extension power supply module.
Input
module
*1
,
Output
module
CPU module
Expansion
adapter
Input
module
*1
,
Output
module
Extension
power
supply
module
Bus
conversion
module
Input
module
*1
,
Output
module
FX3
intelligent
module
The system configuration must meet the following four requirements.
Number of connected extension devices
The number of extension devices that can be connected to a single system of FX5UC CPU modules is limited.
For details, refer to Page 44 Limitations on the Number of Connected Extension Devices.
*1 Extension power supply module and connector conversion module are not included in the number of connected extension devices.
Number of input/output points
With the FX5UC CPU modules, a total of up to 512 points or less including the number of input/output points of extension
devices (max. 256 points) and number of remote I/O points (max. 384 points) can be controlled.
For details on the number of input/output points, refer to Page 47 Limitation on the Number of Input/Output Points.
Current consumption
The power to the extension devices is supplied from a CPU module, powered input/output module or extension power supply
module.
The number of extension devices that can be connected must be determined from the power supply capacity of the CPU
module or extension power supply module.
For details on the current consumption, refer to Page 50 Limitation on Current Consumption.
*1 The power to the input circuit of the input module is supplied from the external power supply.
42
4 SYSTEM CONFIGURATION
4.1 Rules of System Configuration
Page 45
Limitations when using extension devices
■Modules of extension cable type
FX5-CNV-IFC or FX5-C1PS-5V is required to use modules of extension connector type.
■Limitations on high-speed pulse input/output module
Up to four high-speed pulse input/output modules can be connected in a system.
■Bus conversion module
• A bus conversion module is required to use FX3 extension module. FX3 extension modules can be connected to the right
side of the bus conversion module only.
• For limitations on the number of connected extension devices, refer to Page 46 Connection to the bus conversion
module (connection with FX3 extension devices).
■Limitations on intelligent function modules
Note that some intelligent function modules have limitations on the number of modules, order and combination in which they
are added for each individual module.
ModelLimitation
FX5-CCLIEFOnly one module may be connected per system.
FX5-CCL-MSOne module can be connected to the system for each station type.
• Master station: 1
• Intelligent device station: 1
When using the FX5-CCL-MS as the master station, it cannot be used together with the FX3U-16CCL-M.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together with the FX3U-64CCL.
FX5-ASL-MOnly one module may be connected per system.
Use together with the FX3U-128ASL-M is not possible.
FX3U-2HCUp to two modules connectable per system.
Connect a module of this type immediately after the bus conversion module.
FX3U-16CCL-MOnly one module may be connected per system.
When using the FX5-CCL-MS as the master station, it cannot be used together with the FX5-CCL-MS.
FX3U-64CCLOnly one module may be connected per system.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together with the FX5-CCL-MS.
FX3U-128ASL-MOnly one module may be connected per system.
Use together with the FX5-ASL-M is not possible.
4
■Using the extended extension cable
• The connector conversion adapter is required when the extended extension cable connection destination is a module of
extension cable type (except for extension power supply module).
• When connecting a bus conversion module in the same system, connect the powered input/output module directly after the
extended extension cable.
• This cannot be used with the FX3 extension module.
Count the total number of input/output points of the CPU module and I/O modules.
To obtain the total number of input/output points, count the input points (X0 and more) and output points (Y0 and more) of the
CPU module and I/O modules.
For details of the number of input/output points by models, refer to the following.
Page 32 CPU Module
Page 33 I/O module
Number of occupied input/output points of intelligent function modules
Count the number of occupied input/output points of intelligent function modules.
The number of occupied input/output points per module is 8.
For details on the number of occupied input/output points by models, refer to Page 36 Intelligent function module.
Calculation of the number of remote I/O points
If the master module of the network is used, calculate the number of remote I/O points connected on the network.
The total number of remote I/O points must not exceed 384 points.
The maximum number of remote I/O points differs according to type of the network.
• When CC-Link IE field network Basic is used, remote I/O points that are used in CC-Link IE field network Basic are
occupied, and then remote I/O points of the intelligent function module are occupied.
• When using CC-Link master (FX3U-16CCL-M) and AnyWireASLINK master (FX3U-128ASL-M) together, connect FX3U-
128ASL-M on the left side. In the FX5UC CPU module, FX3U-16CCL-M parameters are set up by PLC program and will
occupy up to 256 remote I/O points. Therefore, the remote I/O points of FX3U-128ASL-M that is connected to the right side
may be less than 128 points when FX3U-16CCL-M is connected to the left side.
When input/output points are 160 points, FX3U-16CCL-M is connected to the left side of FX3U-128ASL-M, and 256 points of
remote I/O points to be used with FX3U-16CCL-M are occupied: 512 points - 160 points - 256 points = 96 points
Remote I/O points that can be used with FX3U-128ASL-M are 96 points or less.
When input/output points are 160 points, FX3U-16CCL-M is connected to the right side of FX3U-128ASL-M, and the total
number of remote I/O points to be used with FX3U-128ASL-M is 128 points: 512 points - 160 points - 128 points = 224 points
Remote I/O points that can be used with FX3U-16CCL-M are 224 points or less.
48
4 SYSTEM CONFIGURATION
4.3 Limitation on the Number of Input/Output Points
Page 51
CC-Link IE field network Basic remote I/O
384 points
Actually used CC-Link IE field network Basic remote I/O points
stations
The total number of number of
occupied stations
64 points
=
(a)
64 points
Maximum number of CC-Link IE field
network Basic remote I/O points
(a) CC-Link IE field network
Basic remote I/O points
≥
384 points
Actually used CC-Link remote I/O points
station
=
(b)
×32 points
• FX5-CCL-MS (master station)
256 points
• FX3U-16CCL-M
Maximum number of
CC-Link remote I/O points
(b) CC-Link remote
I/O points
The total number of the remote I/O
stations × 32 points
≥
384 points
AnyWireASLINK remote I/O
(c)points
• FX5-ASL-M
128 points
• FX3U-128ASL-M
Maximum number of
AnyWireASLINK remote I/O
points
(c) Number of remote I/O points assigned to
AnyWireASLINK master
Remote I/O points that are used in CC-Link IE field network Basic are calculated as "number of occupied stations × 64 points”.
CC-Link remote I/O
The number of remote I/O points to be used in CC-Link are calculated as "number of remote I/O stations × 32 points".
Even if using less than 32 remote I/O points, calculate as "number of remote I/O stations × 32 points."
AnyWireASLINK remote I/O
The number of I/O points set below is assigned to the remote I/O to be used with AnyWireASLINK.
• FX5-ASL-M: Set with the engineering tool parameters.
• FX3U-128ASL-M: Set with the rotary switch on the FX3U-128ASL-M main body.
For details, refer to the following manuals.
MELSEC iQ-F FX5 User's Manual (ASLINK)
FX3U-128ASL-M User's Manual
4
4.3 Limitation on the Number of Input/Output Points
4 SYSTEM CONFIGURATION
49
Page 52
4.4Limitation on Current Consumption
Power supply from the CPU module
CPU module
Input
module
Bus
conversion
module
Connector
conversion
module
Expansion
adapter
Output
module
Ex.
FX5
intelligent
module
Input
module
FX3
intelligent
module
Ex.
Ex.
Ex.
Power required for expansion adapters and extension modules is supplied from the CPU module, powered input/output
module or extension power supply module. The number of extension devices that can be connected must be determined from
the capacity of the power supply.
Power supply check from the CPU module (current consumption
calculation)
Check if power can be supplied to extension devices with the power supply capacity of the CPU module.
Calculate following the procedure below.
1. Check the power supply capacity of the CPU module used.
(Page 32 CPU Module)
TypeModelPower supply capacity
5 V DC power supply24 V DC power supply
CPU moduleFX5UC-32MT/D720 mA500 mA
2. Check the current consumption of extension devices.
(Page 33 Extension Module)
TypeModelCurrent consumption
5 V DC power supply24 V DC power supply
Expansion adapterFX5-232ADP30 mA30 mA
Output moduleFX5-C32EYT/D120 mA200 mA
Input moduleFX5-C32EX/D120 mA
Connector conversion moduleFX5-CNV-IFC
Simple motion moduleFX5-40SSC-S
Input moduleFX5-16EX/ES100 mA
Bus conversion moduleFX5-CNV-BUS150 mA
Analog inputFX3U-4AD110 mA
3. Calculate the total current consumption of each power supply.
Power supply typeTotal current consumption
5 V DC power supply630 mA
24 V DC power supply230 mA
50
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
Page 53
4. Check if expansion to the CPU module is permitted.
mAmA
CPU module
Total number of
extension devices
Current consumption
5 V DC
power supply capacity
mA
0 mA
Calculation result
630 mA720 mA90 mA
Ex.
=-
mAmA
CPU module
Total number of
extension devices
Current consumption
mA
0 mA
Calculation result
230 mA500 mA270 mA
24 V DC
power supply capacity
Ex.
=-
• 5 V DC power supply
• 24 V DC power supply
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the CPU module.
Reconfigure the system, adding extension power supply modules.
4
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
51
Page 54
Power supply check from the powered input/output module
CPU module
Expansion
adapters
Output
module
Connector
conversion
module
Input
module
Output
module
Input
module
FX5
Intelligent
module
FX3
Intelligent
module
Powered
input/
output
module
Power supply from powered input/output module
Bus
conversion
module
Ex.
Ex.
Ex.
(current consumption calculation)
If 5 V DC and 24 V DC power supplies of the CPU module are insufficient and system cannot be extended, add a powered
input/output module.
Check if power can be supplied to extension modules with the power supply capacity of the powered input/output module.
Calculate following the procedure below.
1. Check the power supply capacity of the powered input/output module.
(Page 35 Powered input/output module)
TypeModelPower supply capacity
5 V DC power supply24 V DC power supply
Powered input/output moduleFX5-32ER/DS965 mA310 mA
2. Check the current consumption of the extension module.
(Page 33 I/O module)
(Page 36 Intelligent function module)
TypeModelCurrent consumption
5 V DC power supply24 V DC power supply
Input moduleFX5-16EX/ES100 mA85 mA
Output moduleFX5-16EYR/ES100 mA125 mA
Simple motion moduleFX5-40SSC-S
Bus conversion moduleFX5-CNV-BUS150 mA
Analog inputFX3U-4AD110 mA
3. Calculate the total current consumption of each power supply.
Power supply typeTotal current consumption
5 V DC power supply460 mA
24 V DC power supply210 mA
52
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
Page 55
4. Check if expansion to the extension power supply module is permitted.
mA
-
mA
Powered input/output
module
Current consumption
mA
≥
0 mA
=
Calculation result
Ex.
460 mA965 mA505 mA
Capacity of 5 V DC
power supply
Total of current
consumed by extension
module
mA
-
mA
Powered input/output
module
Current consumption
mA
≥
0 mA
=
Calculation result
Ex.
210 mA310 mA100 mA
Capacity of 24 V DC
power supply
Total of current
consumed by extension
module
Power supply from extension power supply module
CPU module
Bus
conversion
module
Connector
conversion
module
FX5
Intelligent
module
FX3
Intelligent
module
Extension
power
supply
module
Expansion
adapters
Output
module
Output
module
Input
module
Ex.
Ex.
• 5 V DC power supply
• 24 V DC power supply
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the CPU module.
Reconfigure the system, adding powered input/output module.
Power supply check from extension power supply module
(current consumption calculation)
If 5 V DC and 24 V DC power supply of the CPU module is insufficient and cannot be extended, add an extension power
supply module.
Check if power can be supplied to extension modules with the power supply capacity of the extension power supply module.
4
Calculate following the procedure below.
1. Check the power supply capacity of the extension power supply module used.
(Page 38 Extension power supply module)
TypeModelPower supply capacity
Extension power supply moduleFX5-C1PS-5V1200 mA625 mA
5 V DC power supply24 V DC power supply
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
53
Page 56
If the ambient temperature exceeds 40, use the extension power supply module at the following current
Ex.
Ex.
mAmA
Total number of
extension devices
mA
0 mA
Extension power
supply module
5 V DC
power supply capacity
Current consumptionCalculation result
480 mA1200 mA720 mA
Ex.
-
≥=
mAmA
Total number of
extension devices
mA
0 mA
Extension power
supply module
24 V DC
power supply capacity
Current consumptionCalculation result
200 mA625 mA425 mA
Ex.
-
≥=
values within the derating range.
Derating curve
Output current [mA]
1200
800
625
400
24 V DC
5 V DC
Ambient
5540
temperature []
2. Check the current consumption of extension devices.
(Page 33 Extension Module)
TypeModelCurrent consumption
5 V DC power supply24 V DC power supply
Output moduleFX5-C32EYT/D120 mA200 mA
Connector conversion moduleFX5-CNV-IFC
Simple motion moduleFX5-40SSC-S
Input moduleFX5-16EX/ES100 mA
Bus conversion moduleFX5-CNV-BUS150 mA
Analog inputFX3U-4AD110 mA
3. Calculate the total current consumption of each power supply.
Power supply typeTotal current consumption
5 V DC power supply480 mA
24 V DC power supply200 mA
4. Check if expansion to the extension power supply module is permitted.
• 5 V DC power supply
• 24 V DC power supply
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the extension
power supply module.
Reconfigure the system, adding extension power supply modules.
54
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
Page 57
4.5Rules of System Configuration and Examples of
FX5-C16EYT/D
FX5-C16EYT/D
FX5-C16EX/D
FX5UC-32MT/D
FX5-232ADP
FX5-485ADP
FX5-CNV-BUS
FX5-40SSC-S
FX5-CNV-IFC
FX3U-1PG
FX3U-4AD
FX3U-128ASL-M
FX3U-4LC
FX3U-64CCL
CC-Link
FX5-C16EYT/D
To CC-Link
master station
The number of transmission points
setting for AnyWireASLINK
64 points
Remote I/O
station
Remote I/O
station
Remote I/O
station
Reconfiguration
The rules of system configuration are explained below referring to a sample system configuration using expansion adapter, I/
O module, and intelligent function module.
System configuration example
The following system configuration is under consideration.
4
Check of limitation on the number of modules
Check if the sample system configuration is within the connectable-module range.
■Number of connected expansion adapters
(Page 44 Number of connected expansion adapters)
TypeNo. of modules used LimitationsJudgment
Expansion adapter (Communication)2Up to 2OK
■Number of connected extension modules
• Number of modules connected on whole system
(Page 44 Overall system limitation)
TypeNo. of modules used LimitationsJudgment
Extension module11
(Connector conversion
module is excluded.)
Connector conversion module1Only 1OK
Bus conversion module1Only 1OK
• Number of modules connected to the CPU module
(Page 45 Connection to the CPU module)
TypeNo. of modules used LimitationsJudgment
Total No. of I/O modules, intelligent function modules, and bus conversion modules 11Up to 12OK
Total No. of intelligent function module and bus conversion modules7Up to 8OK
• Number of modules connected to the bus conversion module
(Page 46 Connection to the bus conversion module (connection with FX3 extension devices))
TypeNo. of modules used LimitationsJudgment
Total No. of intelligent function modules5Up to 6OK
Up to 16
(Extension power supply modules, connector
conversion module are excluded.)
OK
4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
55
Page 58
Check on limitations when using extension devices
+
96 points
≤
56 points
256 points
Number of input/output points
152 points
Calculation result
=
OK
Number of
input/output points
Number of occupied
input/output points
Max. number of
input/output points
Check the use of the extension devices.
■Use of the module of extension cable type
(Page 43 Modules of extension cable type)
LimitationsJudgement
When using the extension cable type module, FX5-CNV-IFC or FX5-C1PS-5V should be connected.OK
■Use of the bus conversion module
(Page 43 Bus conversion module)
LimitationsJudgment
FX3 extension modules are connected on the right side of the bus conversion module.OK
FX5 extension modules are connected on the left side of the bus conversion module.OK
■Connection of intelligent function modules
(Page 43 Limitations on intelligent function modules)
ModelLimitationsJudgment
FX3U-128ASL-MOnly one module may be connected to the system.
Use together with the FX5-ASL-M is not possible.
FX3U-64CCLOnly one module may be connected to the system.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together
with the FX5-CCL-MS.
OK
OK
Check of limitation on the number of input/output points
Check if the number of input/output points of the sample system configuration is within the limit range.
■Number of input/output points
(Page 47 Calculation of the number of input/output points)
4.5 Rules of System Configuration and Examples of Reconfiguration
Page 63
■Number of remote I/O points
≤ 384 points
Remote I/O points
64 points
OK
Maximum number of
Remote I/O points
≤
152 points
512 points
Number of input/output points
+
Remote I/O points
64 points
Total number of input/output points
=
216 points
Calculation result
OK
Max. number of
input/output points
350 mA
-
720 mA
CPU module
Current consumption
370 mA
=
Calculation result
OK
Capacity of 5 V DC
power supply
Total of current
consumed by extension
module
260 mA
-
500 mA
CPU module
Current consumption
240 mA
=
Calculation result
OK
Capacity of 24 V DC
power supply
Total of current
consumed by extension
module
(Page 48 Calculation of the number of remote I/O points)
NetworkNo. of remote I/O points
AnyWireASLINK64 points
■Total number of I/O points and remote I/O points
(Page 47 Limitation on the Number of Input/Output Points)
Check of limitation on current consumption
Check if power required for extension devices can be supplied from the CPU module and extension power supply module.
4
■ Check of power supply from the CPU module
(Page 50 Power supply check from the CPU module (current consumption calculation))
Power supply capacity of the CPU module
TypeModelPower supply capacity
5 V DC power supply24 V DC power supply
CPU moduleFX5UC-32MT/D720 mA500 mA
Current consumption of extension devices
TypeModelCurrent consumption
5 V DC power supply24 V DC power supply
Expansion adapterFX5-232ADP30 mA30 mA
Expansion adapterFX5-485ADP20 mA30 mA
Input moduleFX5-C16EX/D100 mA
Output moduleFX5-C16EYT/D100 mA100 mA
Output moduleFX5-C16EYT/D100 mA100 mA
4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
61
Page 64
■ Check of power supply from the extension power supply module
800 mA
-
1200 mA
Current consumption
400 mA
=
Calculation result
OK
Capacity of 5 V DC
power supply
Extension power
supply module
Total of current
consumed by extension
module
100 mA
-
625 mA
Current consumption
525 mA
=
Calculation result
OK
Capacity of 24 V DC
power supply
Extension power
supply module
Total of current
consumed by extension
module
(Page 53 Power supply check from extension power supply module (current consumption calculation))
Power supply capacity of the extension power supply module
TypeModelPower supply capacity
5 V DC power supply24 V DC power supply
Extension power supply moduleFX5-C1PS-5V1200 mA625 mA
Current consumption of extension devices
TypeModelCurrent consumption
5 V DC power supply24 V DC power supply
Output moduleFX5-C16EYT/D100 mA100 mA
Connector conversion moduleFX5-CNV-IFC
Simple motion moduleFX5-40SSC-S
Bus conversion moduleFX5-CNV-BUS150 mA
Pulse output moduleFX3U-1PG150 mA
Analog input moduleFX3U-4AD110 mA
Temperature controller moduleFX3U-4LC160 mA
AnyWireASLINK master moduleFX3U-128ASL-M130 mA
CC-Link intelligent device moduleFX3U-64CCL
Result check
The reconfigured system is acceptable because the number of extension devices, consumption capacity of 5 V DC and 24 V
DC power supply, and number of input/output points are all within the limit range.
62
4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
Page 65
4.6Numbers and Assignment in System
Ex.
No. 2
Module No.
No. 3
Expansion
adapter
FX5-232ADP
Input module
FX5-C32EX/D
Input module
FX5-C32EYT/D
CPU module
FX5UC-32MT/D
Bus conversion
module
FX5-CNV-BUSC
No. 1
Intelligent
module
FX3U-1PG
Intelligent
module
FX3U-4AD
Input/output numbers and module numbers in an FX5UC system are explained.
Module input/output number
The input/output numbers are octal numbers. Input is assigned to "X" and output to "Y."
Input/output numbers are used for communication of ON/OFF data between I/O modules and the CPU module.
• Input/output numbers (X/Y) are octal.
Input/output numbers (X/Y) are automatically assigned as shown below.
X0 to X7, X10 to X17, X20 to X27, ... X70 to X77, X100 to X107, ...
Y0 to Y7, Y10 to Y17, Y20 to Y27, ... Y70 to Y77, Y100 to Y107, ...
• Numbers for added I/O module
To an added I/O module, input numbers and output numbers following the input numbers and output numbers given to the
preceding device are assigned. The last digit of the assigned numbers must begin with 0.
Module number of Extension modules
The CPU module automatically assigns numbers (1 to 16) to intelligent function modules or bus conversion module as module
numbers in order of distance from the CPU module.
• Intelligent function modules or bus conversion module connected to the CPU module
Module numbers are assigned to intelligent function modules in order of distance from the CPU module: No. 1 to No. 16.
• Products to which module numbers are not assigned
Module numbers are not assigned to the following extension devices.
• I/O moduleFX5-C32EX/D, FX5-C32EYT/D, etc.
• Expansion adapterFX5-232ADP, FX5-485ADP, etc.
• Connector conversion moduleFX5-CNV-IFC
• Connector conversion adapterFX5-CNV-BC
• Extension power supply module FX5-C1PS-5V
4
4.6 Numbers and Assignment in System
4 SYSTEM CONFIGURATION
63
Page 66
5INSTALLATION
FX5-C32EX/D
FX5-232ADP
FX5-C32EYT/D
A
A
50 mm
A
A
A
FX5UC
CPU
module
5.1Installation Location
Use the PLC under the environmental conditions complying with the generic specifications (Page 20 Generic
Specifications).
Installation location in enclosure
To prevent temperature rise, do not mount the PLC on the floor or ceiling, or in the vertical direction. Always mount the PLC
horizontally on the wall as shown in the following figure.
Spaces in enclosure
Extension devices can be connected on the left and right sides of the CPU module of the PLC. Keep a space of at least 50
mm between the module main body and other devices and structure.
If you intend to add extension devices, keep necessary spaces on the left and right sides.
Configuration without extended extension cable
64
5 INSTALLATION
5.1 Installation Location
Page 67
Configuration in 2 stages with extended extension cable
Another
equipment
Powered
input/output
module
FX5- 40SSC -S
FX5-40SSC-S
Extended
extension cable
• FX5-30EC
• FX5-65EC
Another
equipment
FX5UC CPU
module
FX5-C16EX
FX5-C16EYT
FX5-CNV-IFC
FX5-C16EYT
FX5-232ADP
≥50mm
FX5-CNV-BC
FX5-16EX
Another
equipment
Extension module
A
50 mmA
A
FX5UC
CPU
module
For product dimensions or manual for
various products, refer to Appendix
4. I/O Module.
Expansion
adapter
Input
module
Output
module
Input
module
Output
module
≥50mm
FX5UC
CPU module
Intelligent
module
Connector
conversion
module
For product dimensions or manual for various products,
refer to App 4 I/O Module.
For product dimensions or manual for various
products, refer to App 4 I/O Module.
Input
module
Output
module
Powered
input/output
module
Intelligent
module
Input
module
Output
module
Expansion
adapters
Extended
extension cable
•
FX5-30EC(30cm)
•
FX5-65EC(65cm)
Extension module
Layout in enclosure
The PLC components can be laid out in one stage or in two stages, upper and lower. The connecting procedures in each case
are explained below.
Keep a space of at least 50 mm between the module main body or other devices and structure.
5
Configuration in 1-stage layout
Configuration in 2-stage layout
5 INSTALLATION
5.1 Installation Location
65
Page 68
5.2Examination for Installing Method in Enclosure
DIN rail
FX5-16EYTFX5-16EX
2 mm
FX5-CNV-IFCFX5-C32EX
FX5UC-32MT/D
• FX5-30EC
FX5-CNV-BC
*1
(+ indicates an M4 screw.)
2mm
FX5-16EX
FX5-40SSC-S
DIN rail
Extended extension cable
• FX5-65EC
2mm
FX5-16EX
FX5-40SSC-S
(+ indicates an M4 screw.)
FX5UC-32MT/D
DIN rail
Extended extension cable
• FX5-30EC
• FX5-65EC
FX5-CNV-BC
*1
FX5-CNV-IFC
FX5-C32EX
Examine the installation location of PLC considering the environmental conditions (Page 20 Generic Specifications).
When extension cables are used for the connection, install the products keeping a space of about 2 mm
between them.
Installing on DIN rail
• The PLC can be installed on a DIN46277 rail (35 mm wide).
• The PLC can be easily moved and removed.
• The PLC installation height is the same as the DIN rail.
For details on the procedures for installing on and detaching from DIN rail, refer to Page 67 Procedures for Installing on
and Detaching from DIN Rail.
■Example of installation
*1 FX5-CNV-BC can only be installed directly.
Example of combination of installation on DIN rail and direct installation
• The CPU module side can be installed on the DIN rail, and the extension modules extended by the extended extension
cable can be directly installed.
• The PLC can be installed on a 35 mm wide DIN46277 rail.
• The PLC can be easily moved and removed.
• The PLC installation height is the same as the DIN rail.
• The PLC can be installed directly in the enclosure with M4 screws.
For details on the procedures for installing on and detaching from DIN rail, refer to Page 67 Procedures for Installing on
and Detaching from DIN Rail. For mounting hole pitch, refer to Page 69 Removal of CPU module.
■Example of installation
*1 FX5-CNV-BC can only be installed directly.
66
5 INSTALLATION
5.2 Examination for Installing Method in Enclosure
Page 69
5.3Procedures for Installing on and Detaching from
1
A
A
1
B
C
3
DIN Rail
The CPU module can be installed on a DIN46277 rail (35 mm wide).
Preparation for installation
Connecting extension devices
Some extension devices must be mounted on the CPU module before the module is installed in the enclosure.
• Connect expansion adapters or extension modules (extension connector type) on the CPU module before mounting the
PLC in the enclosure.
• Mount extension modules (extension cable type) or terminal modules in the enclosure after mounting the CPU module in
the enclosure.
• Mount (replace) a battery before mounting the CPU module.
Affixing the dust proof sheet
The dust proof sheet should be affixed to the ventilation slits before beginning the installation and wiring work.
For the affixing procedure, refer to the instructions on the dust proof sheet.
Always remove the dust proof sheet when the installation and wiring work is completed.
Installation of CPU module
5
Connect expansion adapters or extension modules (extension connector type) on the CPU module before mounting the PLC
in the enclosure.
For the connection method of the expansion adapters, refer to Page 71 Connecting method A - connection of an
expansion adapter.
For the connection method of the extension modules (extension connector type), refer to Page 72 Connecting method B
- connection of an extension module (extension connector type).
1. Push out all DIN rail mounting hooks (A in the following figure).
2. Fit the upper edge of the DIN rail mounting groove (B in the following figure) onto the DIN rail.
3. Lock the DIN rail mounting hooks (C in the following figure) while pressing the PLC against the DIN rail.
5.3 Procedures for Installing on and Detaching from DIN Rail
5 INSTALLATION
67
Page 70
Installation of extension modules (extension cable type)
Back side
A
1
1. Push out the DIN rail mounting hook (A in the right figure) of the
extension module (extension cable type).
2. Fit the upper edge of the DIN rail mounting groove (B in the right
figure) onto the DIN rail.
3. Push the product against the DIN rail.
B
4. Lock the DIN rail mounting hooks while pressing the product
against the DIN rail.
3
5. Connect the extension cable. For the connecting procedure of the extension cables, refer to Page 71 Connecting
Methods for CPU Module and Extension Devices.
Installation of terminal modules
1. Turn off all the power supplies connected to the CPU module,
extension modules, or terminal modules.
2. Fit the upper edge of the DIN rail mounting groove (A in the right
figure) onto the DIN rail.
3. Push the product against the DIN rail.
A
3
Removal of CPU module
1. Remove the connection cables including power cables and I/O
cables.
2. Insert the tip of a flathead screwdriver into the hole of the DIN rail
mounting hook (B in the right figure). This step also applies for
the DIN rail mounting hooks of the expansion adapters or
extension modules (connector type).
3. Move the flathead screwdriver as shown in the right figure to
draw out the DIN rail mounting hooks of all devices.
4. Remove the product from the DIN rail (C in the right figure).
5. Push in the DIN rail mounting hooks (D in the right figure).
68
5 INSTALLATION
5.3 Procedures for Installing on and Detaching from DIN Rail
C
B
D
2
5
4
3
Page 71
5.4Procedures for Installing Directly (with M4 Screws)
A
2020
80
90
W
B
55
80
90
C
88
80
90
The product can be installed directly in the enclosure (with screws).
Position the holes so that there is a gap of about 2 mm between the products.
Hole pitches for direct mounting
The product mounting hole pitches are shown below.
For pitch that varies depending on the product, refer to the table.
For the mounting hole dimensions of intelligent function modules, refer to user's manuals of each product.
Unit: mm
FX5-CNV-BUSRefer to the figure shown to the left.
5 INSTALLATION
5.4 Procedures for Installing Directly (with M4 Screws)
69
Page 72
Hole pitches when extension module connected
Ex.
A
C
80
Unit: mm
2
*1
2
*1
FX5-16EX/ES
FX5-CNV-BUS
FX3U-1PG
3014
Rear panel
2
A
Rear panel
*1 The gap between products is 2 mm.
Installation of extension module (extension cable type)
1. Make mounting holes on the mounting surface
according to the external dimensions diagram.
2. Push in the DIN rail mounting hook (A in the right figure)
of the extension module (extension cable type). If the
DIN rail mounting hook is not pushed in, the screw hole
is covered, and the extension module cannot be
mounted. (This procedure may not be required,
depending on the model.)
3. Fit the extension module (extension cable type) (B in the
right figure) to the holes, and secure it with M4 screws
(C in the right figure).
C
B
C
70
5 INSTALLATION
5.4 Procedures for Installing Directly (with M4 Screws)
Page 73
5.5Connecting Methods for CPU Module and
Connecting
method B
Expansion adapter
Connecting
method A
Connecting
method C
Connecting
method D
FX5 extension
module (extension
connector type)
Connector
conversion
module
FX5UC CPU
module
FX5 extension
module (extension
cable type)
Connecting
method F
Bus
conversion
module
FX3
extension module
Connecting
method D
Connecting
method E
FX5 extension
module (extension
connector type)
Extended
extension
cable
Connector
conversion
adapter
B
2
2
1
B
A
B
4
3
3
3
4
B
C
Extension Devices
This section explains the connection methods for extension devices.
Connection of extension devices
The connection method varies depending on the combination of products, i.e., the CPU module, expansion adapters, and
extension modules.
The connecting methods are explained with the following configuration example.
Connecting method A - connection of an expansion adapter
5
This subsection explains how to connect the expansion adapter to the CPU module.
1. Remove expansion adapter connector cover (A in the right
figure).
2. Slide the hook for coupling the expansion adapter of the CPU
module (B in the right figure).
3. Connect the expansion adapter to the CPU module as shown in
the right figure.
4. Slide the hook for coupling the expansion adapter of the CPU
module (B in the right figure) to fix the expansion adapter (C in
the right figure).
5.5 Connecting Methods for CPU Module and Extension Devices
5 INSTALLATION
71
Page 74
Connecting method B - connection of an extension module
A
44
44
3
3
3
A
C
(extension connector type)
This subsection explains how to connect the extension module (extension connector type).
1. Slide the hook for coupling the extension module (A in the right
figure) of the existing module (left side).
2. Remove the subsequent extension connector cover (B in the
right figure).
3. Connect an extension module as shown in the right figure.
4. Slide the hook for coupling the extension module (A in the right
figure) of the existing module to fix the extension module (C in
the right figure).
A
B
A
Extension connector of extension power supply module can use either extension cable type or the extension
connector type.
72
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
Page 75
Connecting method C - connection of a connector conversion
Precautions
A
C
D
31
B
module (extension connector type) or the extension power
supply module and an extension module (extension cable type)
This subsection explains how to connect the extension module (extension cable type) to the connector conversion module
(extension connector type) or the extension power supply module.
1. Remove the top cover (B in the right figure) of the existing
module (left side) (A in the right figure). (Only extension power
supply module.)
2. Connect the extension cable (C in the right figure) of the module
to be connected (right side) to the existing module (left side) (A in
the right figure).
3. Fit the top cover (B in the right figure). (Only extension power
supply module.)
4. Draw out the pullout tab (D in the right figure) of the extension
cable on the right side of the top cover. (Only extension power
supply module.)
Extension connector of extension power supply module can use either extension cable type or the extension
connector type.
5
Cautions on mounting and removing extension cables
• Make sure that the pullout tab of extension cables do not touch the conductive parts of the module.
• When removing the extension cable, pull the pullout tab of the extension cable straight up.
Connecting method D - connection between extension modules
(extension cable type)
This subsection explains how to connect extension modules (extension cable type).
1. Remove the top cover (B in the right figure) of the existing
module (left side) (A in the right figure).
2. Connect the extension cable (C in the right figure) of the module
to be connected (right side) to the existing module (left side) (A in
the right figure).
3. Fit the top cover (B in the right figure).
4. Draw out the pullout tab (D in the right figure) of the extension
cable on the right side of the top cover.
Cautions on mounting and removing extension cables
• Make sure that the pullout tab of extension cables do not touch the conductive parts of the module.
• When removing the extension cable, pull the pullout tab of the extension cable straight up.
B
D
31
C
A
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
73
Page 76
Connecting method E - connection of extended extension cable
B
A
A
A
A
1
1
4
4
3
2
C
E
F
D
E
G
A
and connector conversion adapter
This subsection explains the procedures for connecting an extended extension cable and FX5-CNV-BC to the extension cable
of the FX5 extension module.
1. Separate the case of FX5-CNV-BC into two pairs as shown
right figure. To separate the case, use a precision flathead
screwdriver. Slightly insert the tip of the screwdriver into part
A shown in the right figure, and the hook (B in the right
figure) will come off (4 places).
2. Connect the extended extension cable on the upstream side
(C in the right figure).
3. Connect the extension cable on the downstream side (D in
the right figure).
4. Pull the tab (E in the right figure) outside, fit the upper cover
(F in the right figure) and the lower cover (G in the right
figure), and press down the upper cover until it is hooked.
Connecting method F - connection of a bus conversion module
and an FX3 intelligent function module
This subsection explains how to connect the FX3 extension module to the bus conversion module.
1. Connect the extension cable (A in the right figure) from the FX3
extension module to the subsequent extension connector of the
bus conversion module.
This illustration is FX5-CNV-BUSC. When FX5-CNV-BUS is used,
connect the extension cable to the bus conversion module in the
same way.
74
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
Page 77
Connection of power cables
Precautions
3: Ground (Green)
1: (Red)
FX5UC CPU module,
FX5-C1PS-5V
The following shows the pin numbers of the power connectors.
2: (Black)
1: (Red)
2: (Black)
CPU module
Input module (extension connector type)
Output module (extension connector type)
Input/output module (extension connector type)
Resin cover
Since the lower connector is covered with a resin cover at
shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover
wiring to a subsequent extension module is performed.
FX5-CEX/D,
FX5-C32ET/D
Crossover wiring between input
extension blocks
Green: Ground
Black:
Red:
Red:
Black:
Power cable connection of the CPU module, extension power supply module and I/O
modules
The power must be supplied to the FX5UC CPU module, FX5-C1PS-5V, FX5-CEX/D, and FX5-C32ET/D.
Use the power cable for CPU modules to supply the power to the FX5UC CPU module and FX5-C1PS-5V.
To supply the power to FX5-CEX/D and FX5-C32ET/D, use two power connectors (upper and lower) on each module for
crossover wiring.
FX5-CEX/DS and FX5-C32ET/DSS do not have power connectors. Supply the power to them using input connectors.
5
The following products are provided with power cables.
ClassificationApplicationModelLengthProvided with
APower cable for CPU modules, extension power supply
module
BPower cable for FX5-CEX/D and FX5-C32ET/DFX2NC-100BPCB1 mFX5UC-MT/D
CPower crossover cable for FX5-CEX/D and FX5-C32ET/DFX2NC-10BPCB10.1 mFX5-CEX/D, FX5-C32ET/D
FX2NC-100MPCB1 mFX5UC-MT/D, FX5UC-MT/DSS,
FX5-C1PS-5V
• Wiring FX5-CEX/D or FX5-C32ET/D to a subsequent stage
Since the two power connectors on each module of FX5-CEX/D and FX5-C32ET/D are connected in parallel inside the
module, they have no difference and can be either an inlet port or outlet port for supplying the power. Thus, cables can be
connected to either of the connectors.
However, since the lower connector is covered with a resin cover at shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover wiring to a subsequent module is performed.
(FX5-CEX/DS and FX5-C32ET/DSS do not have power connectors and the power is supplied from using input connectors.
Thus, removing the resin cover is not required.)
To perform crossover wiring, supply the power from the preceding module to the subsequent module. The power cannot be
supplied from the subsequent module to the preceding module.
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
75
Page 78
Removal of power cables
Precautions
a
Example: FX5UC-32MT/D
Push here
with fingers.
Input X
Output Y
Example: FX5UC-32MT/D
Notch
Hold part "a" on the connecter of the power cable with your fingers, and remove the cable in the direction of the arrow.
If the power cable is removed by force, the cable may break.
Connection of I/O cables
I/O connectors
■Cable connection to I/O connectors
I/O connectors conform to MIL-C-83503.
For I/O cables, refer to Page 77 Preparation of I/O connectors and prepare them.
• CPU module, I/O modules (extension connector type)
76
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
Page 79
• Terminal module
I/O cable
Terminal module
■Preparation of I/O connectors
• Suitable connector (commercial item)
Use 20-pin (1-key) sockets conforming to MIL-C-83503.
Check that the sockets do not interfere with peripheral parts including connector covers in advance.
• I/O cables (Mitsubishi option)
I/O cables on which connectors are attached are prepared.
ModelLengthDescriptionTyp e
FX-16E-500CAB-S5 mGeneral-purpose I/O cable• Single wire (Wire color: Red)
• CPU module side: 20-pin connector is attached.
FX-16E-150CAB1.5 mCables for connection of the
FX-16E-300CAB3 m
FX-16E-500CAB5 m
FX-16E-150CAB-R1.5 m• Round multicore cables
FX-16E-300CAB-R3 m
FX-16E-500CAB-R5 m
terminal module and I/O connectors
For the connection with the terminal
module, refer to Page 78
WIRING.
• Flat cables (with tube)
• On both ends, 20-pin connectors are attached.
• On both ends, 20-pin connectors are attached.
5
• Connectors for self-making I/O cables (Mitsubishi option)
Prepare wires and crimp tools by users.
Model and configuration of I/O connectorsSuitable wiring (UL-1061-compliant products are
recommended) and tool
Mitsubishi modelPart description
(Manufactured by DDK Ltd.)
FX2C-I/O-CON for flat cables10 setsCrimp connector FRC2-A020-30SAWG 28 (0.1 mm2)
FX2C-I/O-CON-S for single wires5 setsHousing HU-200S2-001
Crimp contact HU-411S
FX2C-I/O-CON-SA for single wires5 setsHousing HU-200S2-001
Crimp contact HU-411SA
Contact for crimp tools: Fujikura Ltd.
Wire sizeCrimp tool
(Manufactured by DDK Ltd.)
357J-4674D main body
1.27-pitch 20 cores
AWG 22 (0.3 mm
AWG 20 (0.5 mm
357J-4664N attachment
2
)357J-5538
2
)357J-13963
• Certified connectors (commercially available connectors)
Connectors made by DDK Ltd. shown above
5 INSTALLATION
5.5 Connecting Methods for CPU Module and Extension Devices
77
Page 80
6WIRING
6.1Wiring Preparations
Wiring procedure
Before wiring, make sure that the source power supply is off.
1. Prepare the parts for wiring.
Prepare cables and crimp terminals required for wiring. (Page 79 Cable Connecting Procedure)
2. Connect the power cable.
Connect the cable to the power connector.
Provide the protection circuit described in this chapter for the power supply circuit. (Page 82 Power Supply Wiring)
3. Perform class D grounding (grounding resistance: 100 Ω or less) for the ground [] terminal.
Connect the grounded wire to the terminal. (Page 81 Grounding)
4. Wire input [X] terminal.
Connect sensors and switches to the terminals. (Page 84 Input Wiring)
5. Wire output [Y] terminal.
Connect the load to terminals.
(Page 94 Output Wiring)
6. Wire the built-in RS-485 communication terminal blocks and Ethernet communication connectors.
For tightening terminals, use a small, commercially-available screwdriver with a straight tip. The recommended
shape is shown in the figure on the right.
■Precautions
When a precision screwdriver with a small grip is used, the specified tightening torque cannot be obtained. Use
the following screwdriver or equivalent product (grip diameter: 25 mm) to obtain the tightening torque specified
above.
<Reference>
ManufacturerModel
Phoenix Contact GmbH & Co. KGSZS 0.42.5
Screw terminal block
Wire the screw terminal block in accordance with the following specifications.
For information concerning screw terminal blocks for intelligent function modules, refer to User's manual for each intelligent
function module.
Terminal block screw size and tightening torque
ModelTerminal screw sizeTightening torque
I/O module (extension cable type)M30.5 to 0.8 N⋅m
Terminal moduleM3.5
Intelligent function moduleRefer to User's manual for each product.
Do not tighten terminal screws exceeding the specified torque range. Otherwise it may cause equipment failure or
malfunction.
Wire end treatment
Crimp terminal size differs depending on terminal screw size and wiring methods used.
• Use crimp terminals of the following sizes.
■M3 terminal screw
• When a single wire is connected to a single terminal
<Reference>
ManufacturerModelSupported standardCrimp tool
JST Mfg. Co., Ltd.FV1.25-B3AUL ListedYA-1
FV2-MS3
(JST Mfg. Co., Ltd.)
80
6 WIRING
6.2 Cable Connecting Procedure
Page 83
• When two wires are connected to a single terminal
Terminal
φ3.2
6.3 mm
or more
φ3.2
Terminal screw Crimp terminal6.2 mm
or less
6.2 mm
or less
6.3 mm
or more
Terminal
Terminal screw Crimp terminal
6.8 mm
or less
3.7
3.7
6.8 mm
or less
Terminal
3.7
6.0 mm
or more
6.0 mm
or more
3.7
Terminal screwCrimp terminal6.8 mm
or less
6.8 mm
or less
PLCPLCPLC
Other
equipment
Other
equipment
Other
equipment
Independent grounding
(Best condition)
Shared grounding
(Good condition)
Common grounding
(Not allowed)
PLC
CPU
module
Extension
module
Other
equipment
Expansion
adapter
Independent grounding
class D grounding
(grounding resistance: 100 or less)
<Reference>
ManufacturerModelSupported standardCrimp tool
JST Mfg. Co., Ltd.FV1.25-B3AUL ListedYA-1
(JST Mfg. Co., Ltd.)
■M3.5 terminal screw
• When a single wire is connected to a single terminal
6
• When two wires are connected to a single terminal
6.3Grounding
Perform the following.
• Perform class D grounding (Grounding resistance: 100 Ω or less).
• Ground the PLC independently when possible.
• If the PLC cannot be grounded independently, perform the "Shared grounding" shown below.
PLC extension devices (excluding communication adapters)
• Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened.
6 WIRING
6.3 Grounding
81
Page 84
6.4Power Supply Wiring
FX5UC-32MT/D
FX5-C32EX/D
FX5-C32ET/D
FX5-16EX/ES
Class D
grounding
*1
Fuse
MC
MC
PL
Power ON
Emergency
stop
24 V DC
MCMC
FX5-C32EYT/D
Power supply for loads connected
to PLC output terminals
For details of the emergency stop operation,
refer to "DESIGN PRECAUTIONS".
24 V DC24 V DC
Power
connector
Power
crossover
connector
Circuit
protector
*2
*2
*2
FX5-4DA-ADP
*2
S/S
FX5-C1PS-5V
*2
FX5-CNV-IFC
Examples of DC power supply wiring
Provide a 24 V DC power supply to FX5UC CPU module and other modules. Use dedicated connectors to provide the power
supply. (Refer to Page 75 Connection of power cables.)
Power supply wiring example of FX5UC-32MT/D
*1 The grounding resistance should be 100 Ω or less.
*2 Using the same power supply to each module and extension adapters is recommended. When a different power supply is used to them,
turn on the power supply at the same time with the CPU module or earlier than the CPU module. When tuning off the power, confirm the
safety of the system and turn off the CPU module at the same time. Some extension modules may not have power supply terminals.
82
6 WIRING
6.4 Power Supply Wiring
Page 85
Power supply wiring example of FX5UC-32MT/DSS
FX5UC-32MT/DSS
FX5-C32ET/DSS
Class D
grounding
*1
Fuse
MC
PL
Power ON
MC
24 V DC
MCMC
FX5-C32EYT/DSS
Power supply for loads connected
to PLC output terminals
For details of the emergency stop operation,
refer to "DESIGN PRECAUTIONS".
24 V DC24 V DC
Circuit
protector
*2
FX5-C32EX/DS
FX5-4DA-ADP
*2
FX5-16EX/ES
S/S
FX5-C1PS-5V
*2
FX5-CNV-IFC
Emergency
stop
6
*1 The grounding resistance should be 100 Ω or less.
*2 Using the same power supply to each module and extension adapters is recommended. When a different power supply is used to them,
turn on the power supply at the same time with the CPU module or earlier than the CPU module. When tuning off the power, confirm the
safety of the system and turn off the CPU module at the same time. Some extension modules may not have power supply terminals.
6 WIRING
6.4 Power Supply Wiring
83
Page 86
6.5Input Wiring
X
COM0
Photocoupler
*1: Input impedance
*1
Fuse
24 V
DC
The input wiring of the CPU modules, I/O modules, and terminal modules is explained below.
24 V DC input
For input specifications of the CPU modules, refer to Page 22 Input Specifications.
For input specifications of the I/O modules, refer to Page 144 Input specifications.
For input specifications of the terminal modules, refer to Page 161 Input specifications.
Sink and source input
■Differences between the sink input circuit and the source input circuit
• Sink input [-common]
Sink input means a DC input signal with a current flowing from the input (X) terminal. When a device such as a transistor
output type sensor is connected, NPN open collector transistor output can be used.
Circuit example for FX5UC-32MT/DCircuit example for FX5UC-32MT/DSS
Fuse
24 V
DC
Photocoupler
*1
*1: Input impedance
• Source input [+common]
Source input means a DC input signal with a current flowing into the input (X) terminal. When a device such as a
transistor output type sensor is connected, the PNP open collector transistor output can be used.
Circuit example for FX5UC-32MT/DSS
COM
X
Photocoupler
*1
*1: Input impedance
COM0
X
Fuse
24 V
DC
■Switching between sink/source inputs
Sink and source inputs for FX5UC-MT/DSS are switched by changing connection methods; the connection in which the
current flows from the input (X) terminal or the connection in which the current flows into the input (X) terminal.
• Sink input: The connection in which the current flows from the input (X) terminal (Page 90 Sink input wiring)
• Source input: The connection in which the current flows into the input (X) terminal (Page 91 Source input wiring)
84
Inputs (X) of FX5UC-MT/DSS can be set to either sink input or source input. However, sink and source input
modes cannot be mixed.
6 WIRING
6.5 Input Wiring
Page 87
Handling of 24 V DC input
*1 Input impedance
*1
24 V DCFuse
X0
X1
COM
*1 Input impedance
*1
24 V DC
Fuse
COM
X0
X1
*1 Input impedance
*1
24 V DC
Fuse
X0
X1
S/S
*1
X0
X1
S/S
*1 Input impedance
24 V DC
Fuse
■Input terminal
For FX5UC CPU module, input module (extension connector type), and input/output module (extension connector type)
•FX5UC-MT/D, FX5-CEX/D, FX5-C32ET/D
When a no-voltage contact or NPN open collector transistor output is connected between an input (X) terminal and the [COM] terminal and the circuit is
closed, the input (X) turns on.
At this time, the LED corresponding to the DISP switch lights up. (FX5-C16EX/D does not have the DISP switch.)
•FX5UC-MT/DSS, FX5-CEX/DS, FX5-C32ET/DSS
In the sink input, the input (X) is turned on by connecting 24 V DC [+] with
the [COM] terminal, and connecting a no-voltage contact or NPN open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
(FX5-C16EX/DS does not have the DISP switch.)
In the source input, the input (X) is turned on by connecting 24 V DC [-] with
the [COM] terminal, and connecting a no-voltage contact or PNP open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
(FX5-C16EX/DS does not have the DISP switch.)
6
*1
X0
X1
COM
Fuse
*1 Input impedance
24 V DC
• RUN terminal setting
X0 to X17 of a CPU module can be used as RUN input terminals by setting parameters.
MELSEC iQ-F FX5 User's Manual (Application)
For input module (extension cable type), input/output module (extension cable type), powered input/output module, and high-
speed pulse input/output module
• Sink input• Source input
In the sink input, the input (X) is turned on by connecting 24 V DC [+] with
the [S/S] terminal, and connecting a no-voltage contact or NPN open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
In the source input, the input (X) is turned on by connecting 24 V DC [-] with
the [S/S] terminal, and connecting a no-voltage contact or PNP open
collector transistor output between the input terminal and 24 V DC to close
the circuit.
At this time, the LED corresponding to the DISP switch lights up.
6 WIRING
6.5 Input Wiring
85
Page 88
■Input circuit
• Function of an input circuit
The primary and secondary circuits for input are insulated with photocoupler, and the second circuit is provided with a C-
R filter.
The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from input line.
Input has a response delay switching from ON to OFF and OFF to ON, shown in the following table.
ItemSpecifications
Input response time
(H/W filter delay)
• Change of filter time
All input circuits have digital filters, and the input response time shown in the following table can be added by setting
parameters. When using this product in an environment with much noise, set the digital filter.
ItemSpecifications
Input response time
(Digital filter setting value)
For the input signal current and input sensitivity current of the CPU modules, refer to Page 22 Input Specifications.
For the input signal current and input sensitivity current of the I/O modules, refer to Page 144 Input specifications.
■Display of operation
The LED turns ON when the photocoupler is driven.
With CPU module, FX5-C32EX/ or FX5-C32ET/, the LED target is switched with the DISP switch.
• CPU module, FX5-C32ET/: Input (IN)/Output (OUT)
• FX5-C32EX/: Smaller number (F)/Larger number (L)
Precautions for connecting input devices
■In the case of no-voltage contact
Use input devices appropriate for low electric current.
If no-voltage contacts for high current (switches) are used, contact failure may occur.
■In the case of input device with built-in series diode
The voltage drop of the series diode should be the following value or less.
Also make sure that the input current is over the input-sensing level while the switches are on.
Use a two-wire proximity switch whose leakage current, I is 1.5 mA or less when the switch is off.
If the resistance is larger than leakage current, I of 1.5 mA, connect a bleeder resistance Rb (kΩ), obtained by the following
formula as shown in the following figure.
ItemSpecifications
Bleeder resistance Rb (kΩ) FX5UC-32MT/X0 to X57 / (I-1.5) or less
When capturing pulses of a response frequency of 50 to 200 kHz on input X0 to X7 (FX5UC-32M and High-speed pulse
input/output module is X0 to X5) wire the terminals as stated below.
• The wire length should be 5 m or less.
• Use shielded twisted-pair cables for connecting cables. Ground the shield of each shielded cable only on the CPU module
side.
• Connect a 1.5 kΩ (1 W or more) bleeder resistance to the input terminal, so that the sum of the load current of the open
collector transistor output on the mating device and the input current of the CPU module is 20 mA or more.
The above-mentioned restrictions are due to specifications of connecting device (encoder etc.). Please adjust the cable length
and load, for connecting device.
88
6 WIRING
6.5 Input Wiring
Page 91
Input wiring example
FX5UC-32MT/D
FX5-C32EX/D
FX5-16EX/ES
FX5-CNV-IFC
COM
COM
24 V DC
S/S
*1
*2
*3
Fuse
X0
X1
X0
X1
X0
X1
Power
connector
3-wire
sensor
Input
impedance
Input
connector
Power
connector
Input
connector
2-wire
sensor
Input
terminal
Class D
grounding
When a sink-input-dedicated CPU module is used
6
*1 The grounding resistance should be 100 Ω or less.
*2 Handle the power supply circuit properly in accordance with "Power Supply Wiring".
*3 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
6 WIRING
6.5 Input Wiring
89
Page 92
When a CPU module common to sink and source inputs is used
FX5UC-32MT/DSS
FX5-C32EX/DS
COM0
X0
X1
COM0
X0
X1
24 V DC
FX5-16EX/ES
S/S
*1
*2
*3
Fuse
X0
X1
FX5-CNV-IFC
Power
connector
3-wire
sensor
2-wire
sensor
Input
connector
Input
impedance
Input
connector
Input
terminal
Class D
grounding
■Sink input wiring
*1 The grounding resistance should be 100 Ω or less.
*2 Handle the power supply circuit properly in accordance with "Power Supply Wiring".
*3 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
90
6 WIRING
6.5 Input Wiring
Page 93
■Source input wiring
FX5UC-32MT/DSS
COM0
Power
connector
Class D
grounding
Fuse
*2
24 V DC
*1
FX5-C32EX/DS
FX5-CNV-IFC
FX5-16EX/ES
Input
impedance
X0
Input
connector
X1
COM0
X0
X1
Input
connector
S/S
Input terminal
X0
X1
3-wire
sensor
*3
6
2-wire
sensor
*1 The grounding resistance should be 100 Ω or less.
*2 Handle the power supply circuit properly in accordance with "Power Supply Wiring".
*3 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
6 WIRING
6.5 Input Wiring
91
Page 94
Input wiring examples of terminal modules
1
COM
3
45602
713
02456
7
COM
COM
COM
COM
COM
COM
COM
7
6
5
4
3
2
1
0012
3
456
7
24 V DC
0 to 7 (Smaller numbers)0 to 7 (Larger numbers)
Fuse
COM
Input number
of PLC
3-wire
sensor
NPN
Vacant
terminal
1
COM
3
45602
713
02456
7
COM
COM
COM
COM
COM
COM
COM
7
6
5
4
3
2
1
0012
3
456
7
24 V DC
0 to 7 (Smaller numbers)0 to 7 (Larger numbers)
The output wiring of the CPU modules, I/O modules, and terminal modules is explained below.
Transistor output
For output specifications of the CPU modules, refer to Page 24 Output Specifications.
For output specifications of the I/O modules, refer to Page 146 Output specifications.
For output specifications of the terminal modules, refer to Page 162 Output specifications.
Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and terminal
modules.
■Differences in circuit
• Sink output [-common]• Source output [+common]
Output to make load current flow into the output (Y) terminal is called
sink output.
Output to make load current flow out of the output (Y) terminal is
called source output.
*1 The number "0" or "1" is applied in .
Handling of transistor output
■Output terminal
For the CPU module, output module (extension connector type), and input/output module (extension connector type), the
transistor output type is a 8-point common output type.
• Sink output• Source output
The COM (number) terminals that are connected each other inside
the PLC are prepared. For external wiring, connect the COM
(number) terminals outside the PLC to reduce the load per one
COM terminal.
The +V (number) terminals that are connected each other inside the
PLC are prepared. For external wiring, connect the +V (number)
terminals outside the PLC to reduce the load per one +V terminal.
94
6 WIRING
6.6 Output Wiring
Page 97
For the output module (extension cable type), input/output module (extension cable type), powered input/output module and
Load
Fuse
Y0
COM0
Load
Fuse
COM1
Y1
Y4
Y5
DC power
supply
DC power
supply
PLC
Y
COM0
LoadFuse
• Sink output type• Source output type
PLC
Y
+V0
Load
Fuse
Dummy
resistor
Dummy
resistor
COM0
+V0
high-speed pulse input/output module, the transistor output type is a 4-point or 8-point common output type.
• Sink output• Source output
Connect each COM (number) terminal to the minus side of
the load power supply.
The COM terminals are not connected internally.
Connect +V (number) terminal to the plus side of the load
power supply.
The +V terminals are not connected internally.
Fuse
Fuse
Load
DC power
supply
Load
DC power
supply
Y0
Y1
+V0
Y4
Y5
+V1
■External power supply
For driving the load, use a smoothing power supply of 5 to 30 V DC that can output a current two or more times the current
rating of the fuse connected to the load circuit.
■Insulation of circuit
The internal circuit of the PLC and the output transistor are insulated with a photocoupler.
The common blocks are separated from one another.
■Display of operation
The LED turns on and the output transistor turns on when photocouplers are actuated.
With CPU module, FX5-C32EYT/ or FX5-C32ET/, the LED target is switched with the DISP switch.
• CPU module, FX5-C32ET/: Input (IN)/Output (OUT)
• FX5-C32EYT/: Smaller number (F)/Larger number (L)
6
■Response time
Time taken from when the photocoupler of the module is driven (or shut off) to when the transistor is turned on (or off) differs
depending on the output terminal used. For specifications of each module, refer to the following.
For output specifications of the CPU modules, refer to Page 24 Output Specifications.
For output specifications of the I/O modules, refer to Page 146 Output specifications.
For output specifications of the terminal modules, refer to Page 162 Output specifications.
The transistor OFF time is longer under lighter loads. For example, under a load of 24 V DC 40 mA, the
response time is approx. 0.3 ms.
When response performance is required under light loads, provide a dummy resistor as shown below to
increase the load current.
6 WIRING
6.6 Output Wiring
95
Page 98
■Output current
Y
+V0
PLC
Load
Fuse
Source output type
+V0
PLC
Inductive load
Fuse
Source output type
Y
+V0
+V0
Limit of forward
rotation
Limit of reverse
rotation
Forward
rotation
Reverse
rotation
Sink output type
Interlock
PLC output
element
Maximum load differs for each module. For specifications of each module, refer to the following.
For output specifications of the CPU modules, refer to Page 24 Output Specifications.
For output specifications of the I/O modules, refer to Page 146 Output specifications.
For output specifications of the terminal modules, refer to Page 162 Output specifications.
When driving a semiconductor element, carefully check the input voltage characteristics of the applied element.
■Open circuit leakage current
0.1 mA or less.
Wiring precautions
■Protection circuit for load short-circuiting
A short-circuit at a load connected to an output terminal could cause burnout at the output device or the PCB.
To prevent this, a protection fuse should be inserted at the output. Use a load power supply capacity that is at least 2 times
larger than the load current.
Sink output type
Load
Fuse
Y
COM0
COM0
PLC
■Contact protection circuit for inductive loads
When an inductive load is connected, connect a diode (for commutation) in parallel with the load as necessary.
The diode (for commutation) must comply with the following specifications.
Standard
Reverse voltage5 to 10 times the load voltage
Forward currentLoad current or more
Sink output type
Inductive load
Fuse
Y
COM0
COM0
PLC
■Interlock
For loads such as forward/reverse contactors, etc., where a hazardous condition could result if switched ON simultaneously,
an external interlock should be provided for interlocking along with an interlock in the PLC program as shown below.
Source output type
Limit of forward
rotation
Limit of reverse
rotation
Interlock
PLC output
element
Forward
rotation
Reverse
rotation
96
6 WIRING
6.6 Output Wiring
Page 99
Relay output
For output specifications of the I/O modules, refer to Page 146 Output specifications.
For output specifications of the terminal modules, refer to Page 162 Output specifications.
Product life of relay output contacts
The product life of relay contacts varies considerably depending on the load type used.
Note that loads generating reverse electromotive force or rush current may cause poor contact or welding of contacts which
may lead to considerable reduction of the contact product life.
■Inductive load
Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause arc discharge. At
a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger.
The following table shows the standard life of contacts used for inductive loads, such as contactors and solenoid valves.
ModelInductive loadStandard life
FX5-EYR/ES, FX5-32ER/, FX5-16ER/ES20 VA500,000 times
Terminal module35 VA
The following table shows the approximate life of a relay based on the results of our operation life test.
• Test condition: 1 sec. ON/1 sec. OFF
Load capacityContact life
■FX5-EYR/ES, FX5-32ER/, FX5-16ER/ES
20 VA0.2 A/100 V AC3,000,000 times
0.1 A/200 V AC
35 VA0.35 A/100 V AC1,000,000 times
0.17 A/200 V AC
80 VA0.8 A/100 V AC200,000 times
0.4 A/200 V AC
■Terminal module
35 VA0.35 A/100 V AC3,000,000 times
0.17 A/200 V AC
80 VA0.8 A/100 V AC1,000,000 times
0.4 A/200 V AC
120 VA1.2 A/100 V AC200,000 times
0.6 A/200 V AC
The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut
down.
Please refer to the following measures regarding the inductive load.
Page 99 Contact protection circuit for inductive loads
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
6
■Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not
exceed the current corresponding to the maximum specified resistance load.
■Capacitive load
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush current does not
exceed the current corresponding to the maximum specified resistance load.
Capacitive loads such as capacitors may be present in electronic circuit loads including inverters.
■Resistance load
For maximum load specifications of resistance load, refer to the following.
For output specifications of the I/O modules, refer to Page 146 Output specifications.
For output specifications of the terminal modules, refer to Page 162 Output specifications.
6 WIRING
6.6 Output Wiring
97
Page 100
Handling of relay output
PLC
Load
24 V DC
Fuse
Y0
Y1
COM0
Load
100 V AC
Fuse
Y4
Y5
COM1
PLC
COM0
Load
Fuse
Y0
■Output terminal
One common terminal is used for 4 or 8 relay output points.
The common terminal blocks can drive loads of different circuit voltage systems (for example: 100 V AC and 24 V DC).
■External power supply
Use an external power supply of 30 V DC or less or 240 V AC or less (250 V AC or less when the module does not comply
with CE, UL, or cUL standards) for loads.
■Insulation of circuit
The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact.
The common terminal blocks are separated from one another.
■Display of operation
When power is applied to the output relay coil, the LED is lit, and the output contact is turned on.
■Response time
The response time of the output relay from when the power is applied to the coil until the output contact is turned on, and from
when the coil is shut off until the output contact is turned off is approx. 10 ms.
■Output current
At a circuit voltage of 240 V AC or less (250 V AC or less when the module does not comply with CE, UL, or cUL standards),
a resistance load of 2 A per point or an inductive load of 80 VA or less (100 V AC or 200 V AC) can be driven.
For the life of the contact for switching an inductive load, refer to Page 97 Inductive load.
When an inductive load is switched, connect a diode (for commutation) or a surge absorber in parallel with this load.
DC circuitAC circuit
Diode (for commutation)Surge absorber
■Open circuit leakage current
There is no leakage current when the output are OFF.
Wiring precautions
■Protection circuit for load short-circuiting
A short-circuit at a load connected to an output terminal could cause burnout at the output element or the PCB. To prevent
this, a protection fuse should be inserted at the output.
98
6 WIRING
6.6 Output Wiring
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.