MELSEC iQ-F FX5-CCLIEF
Hardware Manual
Manual Number JY997D63901
Revision B
Date July 2017
This manual describes the part names, dimensions, installation, and
specifications of the product. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration: Ethernet is a trademark of Xerox Corporation. Phillips is a registered
trademark of Phillips Screw Company.
The company name and the product name to be described in this manual are the
registered trademarks or trademarks of each company.
Effective July 2017
Specifications are subject to change without notice.
Safety Precautions
This manual classifies the safety precautions into two categories:
Depending on the circumstances, procedures indicated by may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manual
How to obtain manuals
For the necessary product manuals or documents, consult with your local
Mitsubishi Electric representative.
and .
Manual name Manual No. Description
MELSEC iQ-F FX5
User's Manual
(CC-Link IE)
MELSEC iQ-F FX5U
User's Manual
(Hardware)
MELSEC iQ-F FX5UC
User's Manual
(Hardware)
MELSEC iQ-F FX5
Programming Manual
(Instructions, Standard
Functions/Function
Blocks)
2016 MITSUBISHI ELECTRIC CORPORATION
(Read these precautions before use.)
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in minor or moderate injury or
property damage.
JY997D64201
JY997D55301
JY997D61401
JY997D55801
Describes the functions of the
CC-Link IE Field network module.
Explains FX5U CPU module
specification details for I/O, wiring,
installation, and maintenance.
Explains FX5UC CPU module
specification details for I/O, wiring,
installation, and maintenance.
Describes specifications of
instructions and functions that can
be used in programs.
Applicable standards
FX5-CCLIEF comply with the EC Directive (EMC Directive) and UL standards (UL,
cUL). Further information can be found in the following manual.
Regarding the standards that relate to the CPU module, please refer to either the
product catalog or consult with your local Mitsubishi Electric representative.
Attention
This product is designed for use in industrial applications.
1. Outline
FX5-CCLIEF intelligent device station for CC-Link IE Field network (hereinafter
referred to as FX5-CCLIEF) is an intelligent function module for connecting to a CCLink IE Field network as an intelligent device station.
1.1 Incorporated Items
Check that the following product and items are included in the package:
Product
Included Items
FX5-CCLIEF intelligent device station for CC-Link IE Field network
FX2NC-100MPCB power cable: (1 m, three wire)
Dust proof protection sheet (1 sheet)
Hardware manual (This manual)
MELSEC iQ-F FX5 User's Manual (CC-Link IE)
1.2 External Dimensions, Part Names
[4] [5]
2-4.5 Mounting holes
[3]
[2]
[1]
16
[11]
[12]
[1] Modular jack for P2 (RJ-45) (with cap)
[2] Modular jack for P1 (RJ-45) (with cap)
[3] Extension cable
[4] Dot matrix LED
[5] Direct mounting hole: 2 holes of
[6] Operation status display LEDs
[7] Extension connector (for next module)
[8] Name plate
[9] DIN rail mounting groove (DIN rail: DIN 46277, 35 mm wide)
[10] DIN rail mounting hook
[11] Pullout tab
[12] Power connector
[6]
90
[7]
80 (Mounting hole pitch)
50
MASS (Weight): Approx. 0.3 kg
Outer painting color: Munsell 0.6B7.6/0.2
4.5 (mounting screw: M4 screw)
[8]
8320
8
Unit: mm
[9]
[10]
1.3 Indications of LEDs
LED display LED color Status Indication
*1
D LINK
L ERR Red
POWER Green
RUN Green
ERROR
P1
P2
Dot matrix LED Orange -
*1 The LED is always off in offline mode.
Green
SD Green
RD Green
*1
Red
L ER Red
LINK Green
L ER Red
LINK Green
Data link (cyclic transmission being
On
performed)
Flashing Data link (cyclic transmission stopped)
Off Data link not performed (disconnection)
On Data being sent
Off Data not being sent
On Data being received
Off Data not being received
On Error data are received
Off Normal data are received
On Power on
Off Power off
On Normal operation
Off Error
Minor error
On
(Major error when the RUN LED turns off)
Moderate error
Flashing
(Major error when the RUN LED turns off)
Off Normal operation
On Error data are received
Off Normal data are received
On Link-up
Off Link-down
On Error data are received
Off Normal data are received
On Link-up
Off Link-down
Displays the station number set in the
module and the module communication
test result.
2. Installation
INSTALLATION
PRECAUTIONS
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Use the product within the generic environment specifications described in
the User's Manual (Hardware) for the CPU module to be used.
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock , fire, malfunctions,
deterioration or damage may occur.
INSTALLATION
PRECAUTIONS
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
The dust proof sheet should be affixed to the ventilation slits before
installation and wiring work to block foreign objects such as cutting and wiring
debris. However, when the installation work is completed, make sure to
remove the sheet to provide adequate ventilation.
Failure to do so may cause fire, equipment failures or malfunctions.
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
Install the product securely using a DIN rail or mounting screws.
Connect the extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
For further information on mounting, refer to the following manual.
2, H2S, SO2 or NO2), flammable gas,
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
3. Wiring
WIRING PRECAUTIONS
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
Securely connect the connector to the module. Poor contact may cause
malfunction.
Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to malfunction of the PLC caused
by abnormal data written to the PLC due to the effects of noise:
- D o not bundle the power line and communication cables together with or
lay them close to the main circuit, high-voltage line, load line or power line.
As a guideline, lay the power line, control line and communication cables
at least 100 mm away from the main circuit, high-voltage line, load line or
power line.

3.1 Connector to be used and cable
3.1.1 Pin configuration
The pin configuration of the RJ-45 connector is as follows:
Pin No.
1
8
3.1.2 Cables to be used
Use Ethernet cable that meets the following standards.
Ethernet cable Typ e
Double shielded, STP
Straight cable
3.1.3 Power supply connector
For further information on the power supply wiring and power cable, refer to the
following manual.
3.2 Grounding
Ground the PLC as stated below.
Perform class D grounding. (Grounding resistance: 100 or less)
Ground the PLC independently if possible.
If the PLC cannot be grounded independently, perform the "Shared grounding"
shown below.
For details, refer to the following manual.
Other
PLC
equipment
Independent grounding
(Best condition)
Bring the grounding point close to the PLC as much as possible so that the
ground cable can be shortened.
Signal Contents
1 TP0+ Data 0 send and receive (+ side)
2 TP0- Data 0 send and receive (- side)
3 TP1+ Data 1 send and receive (+ side)
4 TP2+ Data 2 send and receive (+ side)
5 TP2- Data 2 send and receive (- side)
6 TP1- Data 1 send and receive (- side)
7 TP3+ Data 3 send and receive (+ side)
8 TP3- Data 3 send and receive (- side)
IEEE802.3 (1000BASE-T)
ANSI/TIA/EIA-568-B (Category 5e)
MELSEC iQ-F FX5 User's Manual (CC-Link IE)
(Green)
( Black)
( Red )
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Other
PLC
equipment
Shared grounding
(Good condition)
Other
PLC
equipment
Common grounding
(Not allowed)
4. Specification
DESIGN
PRECAUTIONS
Make sure to set up the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs. reverse
rotation), and an interlock circuit (to prevent damage to the equipment at the
upper and lower positioning limits).
- Note that when the CPU module detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the CPU module occurs in an input/output control block,
output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
For the operating status of each station after a communication failure, refer to
manuals relevant to the network . Incorrect output or malfunctio n due to a
communication failure may result in an accident.
Construct an interlock circuit in the program so that the whole system always
operates on the safe side before ex ecuting the control (for data change) of the
PLC in operation. Read the manual thoroughly and ensure complete safety before
executing other controls (for program change, parameter change, forcible output
and operation status change) of the PLC in operation. Otherwise, the machine
may be damaged and accidents may occur due to erroneous operations.
Especially, when a remote programmable controller is controlled by an external
device, immediate action cannot be taken if a problem occurs in the
programmable controller due to a communication failure. To prevent this,
configure an interlock circuit in the program, and determine corrective actions to
be taken between the external device and CPU module in case of a
communication failure.
If a communication cable is disconnected, the network may be unstable, resulting
in a communication failure of multiple stations. Configure an interlock circuit in the
program to ensure that the en tire system will always op erate safely even if
communications fail. Failure to do so may result in an accident due to an incorrect
output or malfunction.
To maintain the safety of the programmable controller system against
unauthorized access from external devices via the network, take appropriate
measures. To maintain the safety against unauthorized access via the Internet,
take measures such as installing a firewall.
DESIGN
PRECAUTIONS
Simultaneously turn on and off the power supplies of the CPU module and
extension modules.
STARTUP AND
MAINTENANCE
PRECAUTIONS
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION
PRECAUTIONS
The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product. After transportation, verify
operation of the product and check for damage of the mounting part, etc.
4.1 Applicable CPU module
Model name Applicability
FX5U CPU module Ver. 1.030 or later
FX5UC CPU module
*1 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-CCLIEF to the
FX5UC CPU module.
4.2 General Specifications
The items other than the following are equivalent to those of the CPU module.
For the general specification, refer to the following manual.
Items Specifications
Dielectric withstand
voltage
Insulation
resistance
*1
Ver. 1.030 or later
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
500 V AC for 1 minute
10 M or higher by 500 V DC
insulation resistance tester
Between all terminals an d
ground terminal
4.3 Power Supply Specifications
Items Specifications
Power supply voltage 24 V DC +20%, -15%
External
power
supply
Internal
power
supply
Allowable instantaneous
power failure time
Current consumption 230 mA
Power supply voltage 5 V DC
Current consumption 10 mA
Operation continues when the
instantaneous power failure is shorter than
1 ms.
4.4 Performance Specifications
Items Specifications
Station type Intelligent device station
Station number 1 to 120 (sets by parameter or program)
Communication speed 1 Gbps
Network topology
Maximum station-to-station
distance
Cascade connection Max. 20 stages
Communication method Token passing
Maximum number
*1
of link points
Number of occupied I/O points 8 points
*1 The maximum number of link points that a master station can assign to one FX5-
CCLIEF unit.
*2 256 points (512 bytes) when the mode of the master station is online (High-
Speed Mode).
Line topology, star topology (coexistence of line
topology and star topology is also possible), and ring
topology
100 m
(conforms to ANSI/TIA/EIA-568-B (Category 5e))
RX 384 points, 48 bytes
RY 384 points, 48 bytes
RWr
1024 points, 2048 bytes
RWw
1024 points, 2048 bytes
*2
*2
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the grat is warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
Loss in opport unity, lost profits inc urred to the user by Failures of Mitsubishi p roducts.
(2)
(3)
Special damages and secondary damages w hether foreseeable or not, compensa tion for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.