MELSEC iQ-F FX5-20PG-
Hardware Manual
Manual Number JY997D74101
Revision B
Date October 2018
This manual describes the part names, dimensions, installation, and
specifications of the product. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration:
The company name and the product name to be described in this manual are the
registered trademarks or trademarks of each company.
Effective October 2018
Specifications are subject to change without notice.
Safety Precautions
This manual classifies the safety precautions into two categories:
Depending on the circumstances, procedures indicated by may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manual
How to obtain manuals
For the necessary product manuals or documents, consult with your local
Mitsubishi Electric representative.
Applicable standards
FX5-20PG- complies with the EC Directive (EMC Directive) and UL standards
(UL, cUL). Further information can be found in the following manual.
Regarding the standards that relate to the CPU module, please refer to either the
product catalog or consult with your local Mitsubishi Electric representative.
Attention
This product is designed for use in industrial applications.
and .
Manual name Manual No. Description
MELSEC iQ-F FX5
User's Manual
(Positioning Control
- Intelligent function
module)
MELSEC iQ-F FX5U
User's Manual
(Hardware)
MELSEC iQ-F FX5UC
User's Manual
(Hardware)
© 2017 MITSUBISHI ELECTRIC CORPORATION
(Read these precautions before use.)
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in minor or moderate injury or
property damage.
SH-081805ENG Explains positioning module.
JY997D55301
JY997D61401
(Positioning Control - Intelligent function module)
Explains FX5U CPU module
specification details for I/O, wiring,
installation, and maintenance.
Explains FX5UC CPU module
specification details for I/O, wiring,
installation, and maintenance.
→ MELSEC iQ-F FX5 User's Manual
1. Outline
FX5-20PG- 2-axis pulse train positioning module (hereinafter referred to as FX520PG-) is an intelligent function module for high speed, high precision positioning
with servo motors or stepping motors via drive units.
1.1 Incorporated Items
Check that the following product and items are included in the package:
Product FX5-20PG- 2 axis pulse train positioning module
FX2NC-100MPCB power cable: (1 m, three wire)
Included Items
Dust proof protection sheet (1 sheet)
Hardware manual [Japanese /English] (This manual)
Hardware manual [Chinese]
1.2 External Dimensions, Part Names
[4]
[1]
16
[11]
2-4.5 Mounting holes
50
[12]
[5]
[6]
[7]
80 (Mounting hole pitch)
AX1
POWER
AX2
RUN
ERROR
AX1
POWER
AX2
RUN
ERROR
AX1
POWER
AX2
RUN
ERROR
AX1
POWER
AX2
RUN
ERROR
AX1
POWER
AX2
RUN
ERROR
90
MASS (Weight): Approx. 0.2 kg
Outer painting color: Munsell 0.6B7.6/0.2
*1
[3]
[2]
[1] Connector for external devic es
[2] Extension cabl e
[3] Differential driver common terminal
[4] Direct mounting hole: 2 ho les of φ4.5 (mounting screw: M4 screw)
[5] Axis displa y LED (AX1, AX2)
[6] Operation status displ ay LEDs
[7] Extension conne ctor (for next module)
[8] Name plate
[9] DIN rail mounting groove (DIN rail: DIN 46277, 35 mm wide)
[10] DIN rail mounting hook
[11] Pullout tab
[12] Power connector
*1 FX5-20PG-D only
1.3 Indications of LEDs
: OFF, : ON, : Flashing (Flashing interval ON: 200 ms/OFF: 200 ms)
FX5-20PG- status LED display Indication
Power OFF
Normal operation
(RUN LED is ON,
ERROR LED is OFF)
Operation failure
[8]
Power OFF
Axes stopped
Axes on standby
Axes in operation
Minor error
Moderate error
Unit: mm
[9]
[10]
8
83
FX5-20PG- status LED display Indication
Operation failure
1.4 Signal Layouts
The signal layout of the FX5-20PG- connector for external devices is as follows:
1.4.1 40-pin connectors
B20
B19
B18
B17
B16
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
*1 The signal layouts of FX5-20PG-D are as follows.
Pin No.
For further information on signal, refer to the following manual.
MELSEC iQ-F FX5 User's Manual (Positioning Control - Intelligent function module)
→
1.4.2 Differential driver common terminal (FX5-20PG-D only)
AX1
POWER
AX2
RUN
ERROR
Axis 2 (AX2)
Pin No.
A20
B20
A19
B19
A18
B18
A17
B17
A16
B16
A15
B15
A14
B14
A13
B13
A12
B12
A11
B11
A10
B10
A9
B9
A8
B8
A7
B7
A6
B6
A5
B5
A4
B4
A3
B3
A2
B2
A1
B1
Axis 2 (AX2)
Signal
B18 PULSE R- A18 PULSE R-
B17 PULSE R+ A17 PULSE R+
B16 PULSE F- A16 PULSE F-
B15 PULSE F+ A15 PULSE F+
Differential driver
common terminal
Error (Initial not completed)
Axis 1 (AX1)
Signal
PULSER B-
PULSER A-
PULSE COM*1A18
PULSE R
PULSE COM*1A16
PULSE F
CLRCOM
CLEAR
RDYCOM
READY
PG0COM
PG05
PG024
COM
COM
CHG
STOP
DOG
RLS
FLS
Pin No.
A20
PULSER B+
A19
PULSER A+
A17
A15
A14
A13
A12
A11
A10
PULSE COM
PULSE R
PULSE COM
PULSE F
A9
A8
A7
A6
A5
A4
A3
A2
A1
*1
*1
Axis 1 (AX1)
Pin No.
Signal
PLS COM (Differential driver common)
Signal
CLRCOM
CLEAR
RDYCOM
READY
PG0COM
PG05
PG024
COM
COM
CHG
STOP
DOG
RLS
FLS
Signal
2. Installation
INSTALLATION
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Use the product within the generic environment specifications described in the
User's Manual (Hardware) for the CPU module to be used.
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl
impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
INSTALLATION
PRECAUTIONS
• Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
• When drilling screw holes or wiring, make sure that cutting and wiring debris do
not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
2, H2S, SO2 or NO2), flammable gas, vibration or
INSTALLATION
PRECAUTIONS
• The dust proof sheet should be affixed to the ventilation slits before
installation and wiring work to block foreign objects such as cutting and
wiring debris. However, when the inst allation work is complete d, make sure
to remove the sheet to provide adequate ventilation.
Failure to do so may cause fire, equipment failures or malfunctions.
• Install the product on a flat surface. If the mounting surface is rough, undue
force will be applied to the PC board, thereby causing nonconformities.
• Install the product securely using a DIN rail or mounting screws.
• Connect the extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
For further information on mounting, refer to the following manual.
*1
*1
3. Wiring
*1
WIRING PRECAUTIONS
*1
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• The temperature rating of the cable should be 80 or more.
• Make sure to properly wire to the spring clamp terminal block in accordance
with the following precautions.
Failure to do so may cause electric shock, equipment failu res, a shortcircuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end shoul d follow the dimensions described
in the manual.
- Twist the ends of stranded wires and make sure that there are no loose
wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
WIRING PRECAUTIONS
• Securely connect the connector to the module. Poor contact may cause
malfunction.
• Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to malfunction of the PLC caused
by abnormal data written to the PLC due to the effects of noise:
- Do not bundle the power line and communication cables together with or
lay them close to the main circuit, high-voltage line, load line or power line.
As a guideline, lay the power line, control line and communication cables
at least 100 mm away from the main circuit, high-voltage line, load line or
power line.
3.1 Applicable Connector
Use the following 40 pin connectors.
Typ e Model
Soldering type
connector
(straight type)
Crimping type
connector
(straight type)
Soldering type
connector
(dual purpose
(straight/oblique)
type)
*1 Use wire with a sheath outside diameter of 1.3 mm or less when the 40 pins
are used. Select appropriate cables according to the current value used.
→ MELSEC iQ-F FX5U User's Manual (Hardware)
→ MELSEC iQ-F FX5UC User's Manual (Hardware)
Suitable wiring
Size Typ e Material
0.088 to
2
0.3 mm
*1
A6CON1
A6CON2
A6CON4
*1
(AWG28
to 22)
0.088 to
0.24 mm
(AWG28
to 24)
0.088 to
0.3 mm
(AWG28
to 22)
2
Strand
wire
2
3.2 Differential Driver Common Terminal
3.2.1 Suitable wiring
No. of wire per terminal One wire
Single wire, Strand wire
(Material: Copper wire)
Wire
Ferrules with insulation sleeve
size
Ferrules without insulation sleeve
Temperature rating 80 or more
AWG24 to 16 (0.2 to 1.5 mm
AWG23 to 19 (0.25 to 0.75 mm
AWG23 to 16 (0.25 to 1.5mm2)
Copper
wire
Temperature
rating
80 or
more
2
)
2
)

3.2.2 Wire end treatment
Strip the cable about 10 mm from the tip to connect a wire ferrule at the stripped
area. Failure to do so may result in electric shock or short circuit between adjacent
terminals because the conductive part. If the wire strip length is too short, it may
result in the poor contact to the spring clamp terminal part.
When using a wire ferrule with an insulating sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, otherwise the wire cannot
be inserted easily
- Strand wire/single wire
10 mm
Check the shape of the wire insertion opening with the following chart, and use
the smaller wire ferrule than the described size. Also, insert the wire with care so
that the wire ferrule is in proper orientation. Failure to do so may cause the bite of
the terminal and the damage of the terminal block.
The following table shows wire ferrules and tools for wire ferrules compatible.
Shape of the wire
insertion opening
2.4 mm
1.5 mm
The following table shows wire ferrules and its associated tools compatible with
the terminal block. The shape of the wire ferrule differs depending on the crimp
tool to be used, use the reference product. If the product other than referenced
products is used, the wire ferrule cannot be removed. Sufficiently confirm that the
wire ferrule can be removed before use.
<Reference product>
Manufacturer Sleeve Ferrules model
PHOENIX
CONTACT
GmbH & Co. KG
3.2.3 Connecting a cable
• When ferrules with insulation sleeve are used
Insert a wire with the ferrule with insulation sleeve into the wire insertion
opening and push the wire.
• When stranded wires and solid wires are used
Push the open/close button of the terminal block with a flathead screwdriver.
While pushing the open/close button, insert the wire into the ins ertion opening
until the wire reaches the back, and then release the open/close button.
Then, pull the wire lightly and check that it is clamped securely.
<Reference>
3.2.4 Disconnection of the cable
Push the open/close button of the wire to be disconnected with a flathead
screwdriver. Pull out the wire with the open/close button pushed.
3.3 Power Connector
For further information on the power supply wiring and power cable, refer to the
following manual.
Manufacturer Model
PHOENIX CONTACT GmbH & Co. KG SZS 0.4×2.5 VDE
- Ferrule with insulation sleeve
Insulation sleeve
2 to 2.8 mm
Sectional shape of a wire ferrule
Terminal
block
When using a tool of the reference
product, the sectional shape becomes
a trapezoid close to a rectangle.
AI 0.25-8 YE 0.25 mm
Ferrules
AI 0.34-8 TQ
with
insulation
insulation
AI 0.5-8 WH 0.5 mm
sleeve
AI 0.75-8 GY 0.75 mm
A 0,25-7 0.25 mm
Ferrules
without
sleeve
A 0,34-7
A 0,5-8 0.5 mm
A 0,75-8 0.75 mm
AI 1.0-8 1.0 mm
AI 1.5-7
(Positioning Control - Intelligent function module)
→ MELSEC iQ-F FX5 User's Manual
14 mm
Suitable
wiring size
0.3, 0.34 mm
0.3, 0.34 mm
1.25, 1.5 mm
Contact area
(Crimp area)
8 mm
2
2
2
2
2
2
2
2
2
2
Crimp tool
CRIMPFOX 6
(Green)
( Black)
( Red )
3.4 Grounding
Ground the PLC as stated below.
• Perform class D grounding. (Grounding resistance: 100 Ω or less)
• Ground the PLC independently if possible.
If the PLC cannot be grounded independently, perform the "Shared grounding"
shown below. For details, refer to the following manual.
→ MELSEC iQ-F FX5U User's Manual (Hardware)
→ MELSEC iQ-F FX5UC User's Manual (Hardware)
Other
PLC
equipment
Independent grounding
(Best condition)
• Bring the grounding point close to the PLC as much as possible so that the ground
cable can be shortened.
Other
PLC
equipment
Shared grounding
(Good condition)
Other
PLC
equipment
Common grounding
(Not allowed)
4. Specification
DESIGN PRECAUTIONS
• Make sure to set up the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
- Most importantly, set up the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs. reverse
rotation), and an interlock circuit (to prevent damage to the equipment at the
upper and lower positioning limits).
- Note that when the CPU module detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the CPU module occurs in an input/output control block,
output control may be disabled. External circuits and mechanisms should be
designed to ensure safe machinery operation in such a case.
- Note that the output current of the 24 V DC service power sup ply varies
depending on the model and the absence/presence of extension modules. If an
overload occurs, the voltage automatically drops, inputs in the PLC are
disabled, and all outputs are turned off. External circuits and mechanisms
should be designed to ensure safe machinery operation in such a case.
- Note that when an error occurs in a relay, transistor or triac of an output circuit,
the output might stay on or off. For output signals that may lead to serious
accidents, external circuits and mechanisms should be designed to ensure
safe machinery operation in such a case.
•
At Forward/Reverse rotation limits, make sure to wire the contacts with NC,
negative-logic. Wiring contacts with NO, posi tive-logic may cause serious accidents.
•
In an output circuit, when a load current exceeding the current rating or an
overcurrent caused by a load short-circuit flows fo r a long time, it may cause smoke
and fire. To prevent this, configure an external safety circuit, such as a fuse.
DESIGN PRECAUTIONS
• Simultaneously turn on and off the power supplies of the CPU module and
extension modules.
STARTUP AND MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it. Doing so may cause damage.
DISPOSAL PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION
PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product. After transportation, verify
operation of the product and check for damage of the mounting part, etc.
4.1 Applicable CPU Module
Model name Applicability
FX5U CPU module Ver. 1.050 or later
FX5UC CPU module
*1 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-20PG-P to the
FX5UC CPU module.
4.2 Applicable Software Package
Software
GX Works3 Ver. 1.035M or later Ver. 1.050C or later
4.3 General Specifications
The items other than the following are equivalent to those of the CPU module.
For the general specification, refer to the following manual.
Items Specifications
Dielectric withstand
voltage
Insulation resistance
*1
Ver. 1.050 or later
FX5-20PG-P FX5-20PG-D
→ MELSEC iQ-F FX5U User's Manual (Hardware)
→ MELSEC iQ-F FX5UC User's Manual (Hardware)
500 V AC for 1 minute
10 MΩ or higher by 500 V DC
insulation resistance tester
Applicability
Between all terminals and
ground terminal
4.4 Power Supply Specifications
Specifications
FX5-20PG-P FX5-20PG-D
External
power
supply
Items
Power supply voltage 24 V DC +20%, -15%
Allowable instantaneous
power failure time
Current consumption 120 mA 165 mA
Operation continues when the instantaneous
power failure is shorter than 5 ms.
4.5 Performance Specifications
Items
Number of control axes 2 axes
Pulse output form Transistor Differential driver
Interpolation function 2-axis linear interpolation, 2-axis circular interpolation
Control method
Control unit mm, inch, degree, pulse
Positioning data 600 data/axis
Maximum connection
distance between servos
Number of write
accesses to flash ROM
Number of occupied
I/O points
4.6 Input Specifications
4.6.1 Drive unit READY signal (READY), Stop signal (STOP), Upper limit
signal (FLS), Lower limit signal (RLS)
Items Specifications
Signal voltage 24 V DC
Input current 5 mA
ON current 3.5 mA or more
OFF current 1.7 mA or less
Signal format
Response time 4 ms or less
Insulation of circuit Photo-coupler insulation
Indication of operation
PTP (Point To Point) control, path control (line and arc
can be set), speed control, speed-position switching
control, position-speed switching control
2 m 10 m
100000 times maximum
8 points
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
None (Operation check via buffer memory is possible.)
4.6.2 Zero signal (PG05/PG024)
Items
Signal voltage 5 V DC 24 V DC
Input current 5 mA
ON current 2 mA or more 3 mA or more
OFF current 0.5 mA or less 0.2 mA or less
Signal format NPN open collector transistor
Response time 1 ms or less
Insulation of circuit Photo-coupler insulation
Indication of operation
4.6.3 Manual pulse generator A phase (PULSER A)/ Manual pulse
generator B phase (PULSER B)
Items Specifications
Signal voltage 5 V DC
Input current 14 mA
ON current 2 mA or more
OFF current 0.2 mA or less
Signal format NPN open collector transistor
Response frequency 100 kH z
Insulation of circuit Photo-coupler insulation
Indication of operation
None (Operation check via buffer memory is possible.)
None (Operation check via buffer memory is possible.)
4.6.4 Near-point dog signal (DOG)
Items Specifications
Signal voltage 24 V DC
Input current 5 mA
ON current 3.5 mA or more
OFF current 1.7 mA or less
Specifications
FX5-20PG-P FX5-20PG-D
Specifications
PG05 PG024
Items Specifications
Signal format
Response time 1 ms or less
Insulation of circuit Photo-coupler insulation
Indication of operation
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
None (Operation check via buffer memory is possibl e.)
4.6.5 External command signal (CHG)
Items Specifications
Signal voltage 24 V DC
Input current 5 mA
ON current 2.7 mA or more
OFF current 0.8 mA or less
Signal format
Response time 20 μs
Insulation of circuit Photo-coupler insulation
Indication of operation
4.7 Output Specifications
4.7.1 Deviation counter clear signal (CLEAR)
Items Specifications
Pulse output form Transistor
Signal output time 1 to 65535 ms
Rated load voltage 5 to 24 V DC
Max. load current 100 mA
Output ON voltage 1.5 V or less
Indication of operation
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
None
(Operation check via buffer memory is possible.)
None (Operation check via buffer memory is possibl e.)
4.7.2 Pulse output (PULSE R/ PULSE F) [FX5-20PG-P]
Items Specifications
Pulse output form Transistor
Output form
Output frequency 1 pps to 200 kpps
Rated load voltage 5 to 24 V DC
Max. load current 50 mA
Output ON voltage 1.0 V or less
Indication of operation
4.7.3 Pulse output (PULSE R+/PULSE F+) [FX5-20PG-D]
Specification of a differential driver (equivalent to AM26C31).
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the grat is warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
Loss in opport unity, lost profits inc urred to the user by Failures of Mitsubishi p roducts.
(2)
(3)
Special damages and secondary damages w hether foreseeable or not, compensa tion for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
PULSE/SIGN mode, CW/CCW mode,
A phase/B phase (multiple of 4),
A phase/B phase (multiple of 1)
None (Operation check via buffer memory is possibl e.)
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.