•This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
attempting to install or use the unit.
-32DP-IF Profibus-DP Interface Unit. It should be read and understood before
2N
•For operation and setting of FX
Further information can be found in the FX
-32DP-IF Profibus-DP Interface Unit, refer to FX2N-32DP-IF User’s Manual.
2N
Series Hardware Manual, manuals for special function blocks
2N
and Profibus-DP master programmable controllers.
•If in doubt at any stage during the installation of the FX
-32DP-IF Profibus-DP Interface Unit always consult
2N
a professional electrical engineer who is qualified and trained to the local and national standards.
•If in doubt about operation or use of the FX
-32DP-IF Profibus-DP Interface Unit please consult the nearest
2N
Mitsubishi Electric distributor.
•This manual is subject to change without notice.
FX2N-32DP-IF Profibus-DP Interface Unit
FX
2N
-32DP-IF Profibus-DP
Interface Unit
Hardware Manual
Manual number: JY992D77101
Manual revision: E
Date: November 2008
FX2N-32DP-IF Profibus-DP Interface Unit
ii
FX2N-32DP-IF Profibus-DP Interface Unit
Guidelines for the Safety of the User and Protection of the FX2N-32DP-IF
Profibus-DP Interface Unit.
This manual provides information for the use of the FX2N-32DP-IF Profibus-DP Interface Unit.
The manual has been written to be used by trained and competent personnel. The definition of
such a person or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual, should be of a competent
nature, trained and qualified to the local and national standards required to fulfill that
role. These engineers should be fully aware of all aspects of safety with regards to
automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained in the use and maintenance of the completed product. This
includes being completely familiar with all associated documentation for said product. All
maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment should be trained to use that product in a safe
and coordinated manner in compliance to established safety practices. The operators
should also be familiar with documentation which is connected with the actual operation
of the completed equipment.
Note :
The term ‘completed equipment’ refers to a third party constructed device which
contains or uses the product associated with this manual.
iii
FX2N-32DP-IF Profibus-DP Interface Unit
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of
information which are intended to ensure the users personal safety and protect the integrity of
the equipment. Whenever any of the following symbols are encountered its associated note
must be read and understood. Each of the symbols used will now be listed with a brief
description of its meaning.
Hardware Warnings
1) Indicates that the identified danger
2) Indicates that the identified danger could
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.
5) Indicates a special point which the user of the associate software element should
be aware.
6) Indicates a point of interest or further explanation.
WILL
cause physical and property damage.
POSSIBLY
cause physical and property
iv
FX2N-32DP-IF Profibus-DP Interface Unit
•Under no circumstances will Mitsubishi Electric be liable responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
•All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
•Please contact a Mitsubishi distributor for more information concerning applications in life
critical situations or high reliability.
5.2Check the Status of the LEDs of the 32DP-IF ..................................................... 5-2
Appendix A
Further Information Manual Lists.............................................................. A-1
Appendix B
Update History of FX
-32DP-IF and GSD File ....................................... B-1
2N
viii
FX2N-32DP-IF Profibus-DP Interface Unit
1.Introduction
The FX2N-32DP-IF(-D) Profibus-DP Interface Unit (called “32DP-IF” hereinafter) can be used
2N
to connect FX
an existing Profibus-DP network.
The 32DP-IF provides an intelligent slave function for decentralized control applications. Digital
and analog data from a Profibus-DP master CPU (called “DP-master” hereinafter) can be sent
and received to/from any of the supported I/O blocks and special function blocks.
1.1Features of the 32DP-IF
Using the 32DP-IF the FX2N/FX0N series extension units/blocks and special function units/
blocks can exchange data with any DP-master.
•Up to 256 I/O points and/or up to 8 special function blocks can be connected to the 32DP-IF.
/FX0N series extension units/blocks and special function units/blocks directly to
Introduction 1
However, adjust total control I/O points to 256 or less. See section 1.3.
•The slave address of the 32DP-IF is adjusted by DIP switches. See chapter 4.
•The 32DP-IF can be connected to a Profibus-DP network via a standard 9-pin D-SUB connector
and a shielded twisted pair cable complying with EN50170. Optional glassfiber adapters are
supported by the 32DP-IF and are available from other vendors.
See chapter 2.
•An FX-20P-E or personal computer can be used to monitor the status of the 32DP-IF and the
data exchanged with the Profibus network. For operating instructions of the FX-20P-E or
personal computer, refer to their respective operation manuals. For device numbers and
explanation, refer to the FX
b) Power supply terminals (screw terminal: M3.5 (0.14"))
2N
FX
FX
-32DP-IF (AC power supply type): L, N and grounding terminal
2N
-32DP-IF-D (DC power supply type): 24+, 24- and grounding terminal
c) Direct mounting hole (2-φ4.5 (0.18"))
d) 24 V DC power terminal (screw terminal: M3.5 (0.14"))
2N
FX
-32DP-IF-D does not have this terminal.
e) RUN/STOP switch:When this switch is in the RUN position, the 32DP-IF will exchange
data with extension units/blocks and special function blocks. If this
switch is in the STOP position, the 32DP-IF will exchange only input
data with extension units/blocks.
f)Communication port for FX-20P-E or personal computer
g) POWER LED:ON when power is supplied.
h) RUN LED:ON when 32DP-IF is exchanging data with extension units/blocks
and special function blocks.
i)BF LED:ON when a communication error is detected (No data exchange).
j)DIA LED:ON when diagnostic data is detected.
k) Hook for DIN rail mounting
l)DIP switches for slave address of this unit
m)Extension port
n) Groove for DIN rail mounting (DIN rail width: 35 mm (1.38"))
Extension I/O units/blocks and
special function blocks *
3
Slave or
DP-master *
1
Slave or
DP-master *
FX2N-32DP-IF Profibus-DP
interface unit *
DP-master
1
2
*1 The units at each end of the Profibus-DP network must have a terminating resistor. This
will either be in the master, slave unit or in the Profibus connector.
*2 For connecting a monitoring tool, refer to subsection 1.3.1
*3 For connecting units/blocks, refer to subsection 1.3.2.
Caution
The parameter data of the 32DP-IF must be set correctly in the DP-master, if the parameter
data is not correct, the operation of the module may be affected.
For parameter of 32DP-IF, refer to FX
An FX-20P-E or personal computer can be used to monitor the 32DP-IF and the data
exchanged with the Profibus. For operating instructions of the FX-20P-E or personal computer,
refer to their respective operation manuals. For device numbers and explanation, refer to the
2N
FX
-32DP-IF User’s Manual.
Connecting cable is same as FX
2N
MPU.
Table 1.2:Connected Programming Tools
Monitoring ToolsDescription
FX-20P-E
Personal Computer
(MELSEC MEDOC PLUS)
Device monitor
Note;
For monitoring the 32DP-IF with a personal computer the PLC setting must be adjusted as
for the FX series PLC type.
Further information for the Configuration Rules can be found in FX
2N
-32DP-IF User’s Manual.
1) Total I/O points on the system ≤ 256 points
The following (a ~ c) I/O points must be a total of 256 points or less.
For I/O point allocation for each extension unit/block and each special function unit/block,
refer to FX
2N
-32DP-IF User’s Manual.
a) Count I/O points for the extension units/blocks (including additional occupied points).
b) Count the occupation I/O points for special function units/blocks.
A 32DP-IF can connect a Maximum of 8 special function blocks.
2N
c) Count I/O points for FX
-32ASI-M’s active slaves.
2) Supply 24V DC (total internal and service power supply) and 5V DC to the extnsion I/O
blocks and special function units/blocks from the 32DP-IF or exteniosn I/O units.
If 24V DC and 5V DC is not supplied to both special function blocks and extension I/O
blocks, the hardware configuration will need to be changed.
For power consumption, refer to FX
2N
-32DP-IF User’s Manual.
3) Total exchange data length ≤ 200 bytes
(or DP master’s maximum exchange data length if ≤ 200 bytes)
The following (a, b) exchange data must be a total of 200 bytes (or DP master’s maximum
exchange data length if ≤ 200 bytes) or less.
For exchange data length, refer to FX
2N
-32DP-IF User’s Manual.
a) Total exchange data for extension I/O units/blocks.
b) Total exchange data for special function units/blocks.
4) Total user parameter length ≤ 193 bytes
(or DP master’s maximum user parameter length if ≤ 193 bytes)
The user parameter length must be a total of 193 bytes (or DP master’s maximum exchange
data length if ≤ 193 bytes) or less.
For user parameter length, refer to FX
To prevent a rise in temperature, mount the units to the back walls. Never mount them to the
floor, ceiling or side wall of an enclosure.
Figure 2.1: Mounting Location
Mounting and Wiring 2
> 50 mm
(1.97")
> 50 mm
(1.97")
FX2N-32DP-IF
-4DA
2N
FX
> 50 mm
(1.97")
-4AD
2N
FX
-16EX
2N
-ES/UL
FX
-16EYT
2N
-ESS/UL
FX
> 50 mm
(1.97")
2-1
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.2: Mounting Arrangement
2-2
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.1.2Mounting
Mounting method for the 32DP-IF is DIN rail mounting or direct wall mounting.
1) DIN Rail Mounting
-Align the upper side of the DIN rail mounting groove of the 32DP-IF with a DIN rail*1 (c),
and push it on the DIN rail(d). See Figure 2.3.
-When removing the 32DP-IF from the DIN rail, the hook for DIN rail is pulled (e), and the
32DP-IF is removed (f). See Figure 2.4.
Figure 2.3: Attach to DIN Rail
2-3
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.4: Remove from DIN Rail
*1 Uses DIN 46277 <35mm (1.38")>
2) Direct Mounting to Back Walls
The 32DP-IF can be mounted with M4 screws by using the direct mounting holes.
An interval space between each unit of 1 ~ 2 mm is necessary.
For mounting hole position of 32DP-IF, refer to section 1.2. Further information about extension I/O units/blocks can be found in the FX
2N
Hardware Manual. Further information about
special function units/blocks can be found in each manual.
2-4
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.2Caution for Wiring
1) Do not lay signal cable near to either high voltage power cabling or cabinet housing along
the same trunking duct. Effects of noise or surge induction may occur. Keep signal cables of
more than 100 mm (3.94") from these power cables.
2) Ground the shield wire or the shield of a cable at one point on the module. Do not, however,
ground at the same point as high voltage lines.
3) Cut off all phases of power source before installation or performing wiring work in order to
avoid electric shock or damage to the product.
4) Replace the provided terminal cover before supplying power and operating the unit after
installation or wiring work, in order to avoid electric shock.
5) To connect the 32DP-IF to a Profibus-DP network should be used only the Profibus
connectors and shielded twisted-pair cable complying with EN50170.
6) The power supply of the extension units/blocks and the special function units/blocks should
be starting-up at the same time or earlier than it with 32DP-IF.
7) DO NOT use the “●” terminal of the 32DP-IF.
8) “24+” and “24-” terminal are not reversible.
If “24+” and “24-” terminal are reversed, the units/block may be serious damaged.
2-5
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
9) The terminal tightening torque is 0.5 to 0.8 N•m. Tighten securely to avoid malfunction.
10)The terminal screws of FX
0N
FX
, FX2N Series extension I/O units/blocks and special function units/blocks are M3
2N
-32DP-IF is M3.5 (0.14"). However, the terminal screws of the
(0.12"). The crimp style terminal (see drawing) suitable for use with these screws should be
fitted to the cable for wiring.
When installing 1 or 2 crimp terminal to a terminal, see each explanation below. However, 3
crimp terminals or more cannot be installed to a single terminal.
2-6
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
a) Handle the crimp terminal of the following size as and when 1 wire is used per terminal.
Refer to Figure 3.3 for installation instructions.
Figure 2.5: Crimp Terminal for M3.5 Screws
φ
3.7 (0.15")
6.8 mm (0.27" )
or less
Figure 2.6: Crimp Terminal for M3 Screws
φ
3.2 (0.13")
6.2 mm (0.24" )
or less
Figure 2.7: Installing 1 wire Per Terminal
Terminal screw
Terminal
Crimp terminal
6.8 mm (0.27")
or less
6.2 mm (0.24")
or less
φ
3.7 (0.15")
φ
3.2 (0.13")
2-7
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
b) Handle the crimp terminal of the following size as and when 2 wires are used per
terminal. Refer to Figure 3.6 for installation instructions.
Figure 2.8: Crimp Terminal for M3.5 Screws
3.7 (0.15")
φ
6.8 mm (0.27" )
or less
6.0 mm or more6.0 mm or more
Figure 2.9: Crimp Terminal for M3 Screws
φ
3.2 (0.13")
6.2 mm (0.24" )
or less
6.3 mm or more
Figure 2.10:Installing 2 Wires Per Terminal
Terminal screw
Crimp terminal
6.8 mm (0.27")
or less
6.2 mm (0.24")
or less
3.7 (0.15")
φ
φ
3.2 (0.13")
6.3 mm or more
Terminal
2-8
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.3Power Supply
Further information for the extension unit’s wiring can be found in the FX2N Series Hardware
Manual. Further information for special function units/blocks can be found in their respective
manual. For wiring of grounding, refer to Section 2.4.
2-9
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.3.1AC Power Supply Type: FX2N-32DP-IF
When wiring a 32DP-IF and extension I/O units/blocks, the connection method is identical to a
2N
FX
FX
•Supply both FX
series PLC. Further information can be found in the FX2N-32DP-IF User’s Manual and
2N
Series Hardware Manual.
2N
-32DP-IF and extension I/O units from the same AC power source.
•Connect “COM” terminal on the 32DP-IF to the “0V” terminal on the extension unit.
•For ground wiring, refer to Section 2.4.
2-10
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.11:AC Power Supply Type: FX2N-32DP-IF
Grounding Ref. Section 2.4
100~
240V
AC
L
N
Emegency
MC*1Start
stop
MC
MCMC
Fuse
Service power supply
Switch
X
C
2
L NL N
4
+
O
M
S
S
Extension
I/O Block
FX
-32DP-IF
2N
(Source
Input)
X
0
/
0
0
0
0
1
Extension I/O Unit
<AC Power
Supply Type>
(Source Input
Relay Output)
Service power supply
Switch
X0X
0
V
S
S
/
1
Y
C
O
M
1
Y
0
0
0
0
0
1
2
4
+
Power supply for AC loads
*1 Magnetic contact safety circuit
Power supply for AC loads
2-11
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.3.2DC Power Supply Type: FX2N-32DP-IF-D
When wiring a 32DP-IF and extension I/O units/blocks, the connection method is identical to a
2N
FX
FX
series PLC. Further information can be found in the FX2N-32DP-IF User’s Manual and
2N
Series Hardware Manual.
•Supply both FX2N-32DP-IF-D and extension I/O units/blocks from the same DC power source.
•For ground wiring, refer to Section 2.4.
2-12
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.12:DC Power Supply Type: FX2N-32DP-IF-D
24V
DC
Fuse
Emegency
MC*1Start
stop
MC
MCMC
Grounding Ref. Section 2.4
2
4
+
2
*2*2
4
-
S
S
X
0
/
0
0
Extension
2N
FX
-32DP-IF-D
I/O Block
(Source
Input)
Switch
X
0
0
1
2
4
V
0
V
S
S
Extension I/O Unit
<DC Power
Supply Type>
(Source Input
Relay Output)
Switch
X0X
/
C
O
M
1
1
Y
0
0
0
Y
0
0
1
Power supply for DC loads
*1 Magnetic contact safety circuit
*2 DO NOT connect wire to this terminal.
Power supply for AC loads
2-13
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
2.4Profibus-DP Network
To connect the 32DP-IF to a Profibus-DP network should be used only the Profibus connectors
and shielded twisted-pair cable complying with EN50170.
Please use terminating resistors and Profibus connectors as shown in the DP-master manual
and Profibus connector manual.
The 32DP-IF does not have a terminating resistance built-in.
Note: Noise Prevention
For noise prevention please attach at least 50mm (1.97”) of the shielded twisted-pair cable
along the grounding plate to which the ground terminal is connected.
2-14
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.13:Connect to Profibus-DP Network
32DP-IF
L(24+)
N(24-)
c
d
e
f
Table 2.1:Connect to Profibus-DP Network
Ref.Description
①Power source for 32DP-IF (Refer to section 3.2)
②Grounding terminal in 32DP-IF
③Profibus connector (Refer to Figure 3.10)
④Grounding plate
gh
i
⑤
For noise Prevention please attach at least 50mm (1.97”)
cable along the grounding plate to which the ground terminal is connected.
⑥Grounding resistance of 100Ω or less
⑦Shielded twisted-pair cable complying with EN50170 to Profibus-DP network
of the shielded
twisted-pair
2-15
FX2N-32DP-IF Profibus-DP Interface UnitMounting and Wiring 2
Figure 2.14:Profibus Connection
Shielded twisted-pair cable to
Profibus-DP network
2N
FX
-32DP-IF Profibus-DP
Interface Unit
2.5Wiring for Connecting to Extension Blocks/Units and Special Function Blocks
Further information can be found in FX2N-32DP-IF User’s Manual, FX2N Hardware Manual and
each manual for using special function unit/block.
1) AC Power Supply Type (FX
a) Supply both FX
2N
-32DP-IF and extension I/O units from the same AC power source.
2N
-32DP-IF)
b) Connect “COM” terminal on the FX
units. For extension unit’s wiring, refer to FX
2) DC Power Supply Type FX
2N
Supply both FX
-32DP-IF-D and extension I/O units/blocks from the same DC power
2N
-32DP-IF-D)
source.
2N
-32DP-IF to the “0V” terminal on the extension
2N
Series Hardware Manual.
2-16
FX2N-32DP-IF Profibus-DP Interface Unit
3.Specifications
3.1General Specifications
Table 3.1:General Specifications
ItemDescription
Operating Temperature0 ~ 55°C (32 to 131°F)
Storage Temperature-20 ~ 70°C (-4 to 158°F)
Operating Humidity35 ~ 85% Relative Humidity, No condensation
Storage Humidity35 ~ 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Specifications 3
10 ~ 57Hz: 0.075mm Half Amplitude
2
57 ~ 150Hz: 9.8m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
10 ~ 57Hz: 0.035mm Half Amplitude
57 ~ 150Hz: 4.9m/s
Sweep Count for X, Y, Z: 10 times (80min in each direction)
Acceleration
2
Acceleration
Shock Resistance
Noise Immunity1,000Vp-p, 1microsecond, 30 ~ 100Hz, tested by noise simulator
-32DP-IF1,500V AC > 1 min, tested between all points, terminals and ground
FX
Dielectric
Withstand Voltage
Insulation Resistance
Grounding
Complies withUL508
2N
-32DP-IF-D500V AC > 1 min, tested between all points, terminals and ground
FX
2N
147m/s
3 times in each direction X, Y, and Z
5M
Grounding resistance is 100
2
Acceleration, Action Time: 11ms
Ω
> at 500V DC, tested between all points, terminals and ground
The slave address of 32DP-IF for Profibus network is set by the ON/OFF configuration of DIP
switches. Slave address setting range is 0 ~ 126. When 32DP-IF’s power supply is turned ON,
the slave address is the sum total of these DIP switch values.
Figure 4.1: DIP Switches
64
32
16
8
4
2
Address Setting 4
1
This is the DIP switch value.
ON
This DIP switch is not
OFF
used for the address
setting. Please leave in
the OFF position.
These DIP
switches are OFF.
This DIP switch is ON.
Note:
If the address of 32DP-IF is changed, the 32DP-IF must be turned OFF and ON again in
order to activate the new address.
If slave address of 32DP-IF is set to “22”, the DIP switches are as shown below.
Figure 4.2: Address Setting
8
4
2
64
32
16
1
ON
OFF
4-2
FX2N-32DP-IF Profibus-DP Interface Unit
5.Diagnostics
5.1Preliminary Checks
1) Check “POWER LED”. If this is OFF, please see section 5.2.
2) Check that the slave address is the same at the 32DP-IF and the DP-master configuration.
If the slave address is not the same in the 32DP-IF and in the DP-master, change this
address to match in both modules.
3) Check that the parameter data of 32DP-IF are set correctly in the DP-master.
If the parameter data of the 32DP-IF are not set correctly in the DP-master, communication
over the Profibus-DP network may be affected.
4) Check whether the network wiring and/or the cables for the extension blocks/units are
Diagnostics 5
properly connected to the 32DP-IF.
5) Check that the system configuration rules have not been exceeded, i.e. the number of
special function blocks does not exceed 8 and control I/O of 32DP-IF is 256 or less.
If the 32DP-IF does not seem to operate normally, check the following items.
2N
For error flags, error codes, and device explanation, refer to FX
-32DP-IF User’s Manual.
1) Check the status of the “POWER LED”.
Table 5.1:POWER LED Check
Status
LitPower source is OK.
UnlitPossible AC or DC power failure, check power line and power source.
Description
2) Check the status of the “RUN LED”
Table 5.2:RUN LED Check
Lit
Unlit
Status
The 32DP-IF will exchange data with extension units/blocks and special function
blocks.
The 32DP-IF will exchange only input data with extension units/blocks. Check
position of the RUN/STOP switch. If the switch is in the STOP position, change
to RUN.