Mitsubishi Electric MELSEC FX2N-2LC User Manual

USER’S MANUAL
FX2N-2LC Temperature Control Block
FX2N-2LC Temperature Control Block
Foreword
This manual contains te xt, diag rams and explanations which will guide the reader in the cor­rect installation and operation of the communication facilities of FX series.
Before attempting to install or use the communication facilities of FX series this manual should be read and understood.
If in doubt at an y stage of the installation of t he communication facilities of FX series always consult a professional electrical engineer wh o is qualified and trained to the local and national standards which apply to the installation site.
If in doubt about the operation or use of the communication facilities of FX series please consult the nearest Mitsubisi Electric dis tributor.
This manual is subject to change without notice.
FX2N-2LC Tempereture Control Block
FX
2N
-2LC
Temperature Control Block
USER’S MANUAL
Manual number : JY992D85801 Manual revision : A
Date : January 2000
i
FX2N-2LC Tempereture Control Block
ii
FX2N-2LC Tempereture Control Block
FAX BACK
Mitsubishi has a world wide reputation for its efforts in continually developing and pushing back the frontiers of industrial automation. What is sometimes overlooked by the user is the care and attention to detail that is taken with the documentation. However,to continue this pro­cess of improvement, the comments of the Mitsubishi users are always welcomed. This page has been designed for you,the reader,to fill in your comments and fax them back to us. We look forward to hearing from you.
Fax numbers: Your name....................................................
Mitsubishi Electric.... .....................................................................
America (01) 847-478-2253 Your company..............................................
Australia (02) 638 -7072 .....................................................................
Germany (0 21 02) 4 86-1 12 Your location:................................................
South Africa (0 27) 11 444-0223 .................... .................................................
United Kingdom (01707) 278-695
Please tick the box of your choice
What condition did the manual arrive in? Will you be using a f o lder to store the manual? What do you think to the manual presentation? Are the explanations understandable?
Which explanation was most difficult to understand:..................................................................
....................................................................................................................................................
Are there any diagrams which are not clear?
If so,which:..................................................................................................................................
What do you think to the manual layout?
If there one thing you would li ke to see improved,what is it?............ ............................. .............
....................................................................................................................................................
....................................................................................................................................................
Could you find the information you required easily using the index and/or the contents,if possi-
ble please identify your experience:............................................................................................
....................................................................................................................................................
....................................................................................................................................................
....................................................................................................................................................
....................................................................................................................................................
Good Yes Tidy Yes
Yes
Good
Minor damage
No
Un-friendly
Not too bad
No
Not too bad
Unusable
Unusable
Un-helpful
Do you have any comments in general about the Mitsubishi manuals?.............................. .. .....
....................................................................................................................................................
....................................................................................................................................................
....................................................................................................................................................
....................................................................................................................................................
Thank you for taking the time to fill out this questionnaire. We hope you found both the product and this manual easy to use.
iii
FX2N-2LC Tempereture Control Block
iv
FX2N-2LC Tempereture Control Block
Guidelines for the Safety of the User and Protection of the Temperature control block FX2N-2LC.
This manual provides information for the use of the Temperature control block FX2N-2LC. The manual has been writte n to be use d by trained and compe tent personnel. T he definition of such a person or persons is as follows;
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated w ith this manual should be of a com petent nature, trained and qualified to the loc al and national sta ndards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to auto­mated equipment.
b) Any commissioning or service engineer must be of a competent nature, tr ained and qual-
ified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely f amili ar with all ass ociated docume ntation for the said product. All maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment should be trained to use that product in a safe
and coordinated manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected with the actual operation of the completed equipment.
Note :
Note: the term ‘completed equipment’ refers to a third party constructed device which contains or uses the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times through out this manual cer tain s ymbols will be used to highlight p oints of information which are intended to ensure the users personal safety and protect the integrity of equipment. Whenever any of the following symbols are encountered its associated note must be read and understood. Each of the symbols used will no w be lis ted with a brief description of its meaning.
Hardware Warnings
1) Indicates that the identified danger
2) Indicates that the identified danger could
WILL
cause physical and property damage.
POSSIBLY
cause physical and proper ty
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.
5) Indicates a special point which the user of the associate software element should be aware of.
6) Indicates a point of interest or further explanation.
v
FX2N-2LC Tempereture Control Block
Under no circumstances will Mitsubishi Electric be liable responsible for any consequential damage that may arise as a result of the installation or use of this equipment.
All examples and diagr ams show n in this manual are int ended only as an aid to understand­ing the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustra tive examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.
vi
FX2N-2LC Temperature Control Block
1. Introduction ...........................................................................................1-1
1.1 Outline of product ................................................................................................ 1-2
2. Product Configuration ...................................................... ............ .........2 -1
2.1 Outside d ime nsion........ .. ... ..................................................................................2-1
2.2 Name of each part...............................................................................................2-1
2.3 Status ind ic a t io n ..................................................................................................2-2
2.4 Installation method .............................................................................................. 2-3
2.5 Connection to PC Main Unit................ ........................................................ ........2-4
3. Specifications........................................................................................3-1
3.1 Environm en tal specifica tion s........ .. .. ................................................................... 3-1
3.2 Power supp ly specificati o n s .. .. ... .........................................................................3-1
3.3 Performance specifications .................................................................................3-2
3.4 Input specifications...................................................................... ...................... ..3-3
3.5 Input range............................................................ ..............................................3-4
3.6 Output specifications...........................................................................................3-5
Contents
4. Wiring....................................................................................................4-1
4.1 Wiring ..................................................................................................................4-2
5. Introduction of Functions.......................................................................5-1
5.1 PID control...........................................................................................................5-1
5.1.1 Easy PID control with two degrees of freedom..........................................................5-1
5.1.2 Overshoot prevention function.... ....... ...... ............................................. .....................5-2
5.2 Two-position control ............................................................................................ 5-3
5.3 Auto tuning fu n c tio n...................... .......................................................................5-4
5.3.1 AT (auto tuning)......................................................................................................... 5-4
5.3.2 AT bias ...................................................................................................................... 5-5
5.4 Auto / manual......................................................................................................5-6
5.4.1 Auto mode and manual mode ...................................................................................5-6
5.4.2 Balance-less, bump-less function..............................................................................5-7
5.5 Heater disconnection detection function...................................................... ........5-8
5.6 Loop breaking alarm function (LBA)....................................................................5-9
6. Alarm................................................................................ .....................6-1
7. Buffer Memory (BFM) ...........................................................................7-1
7.1 Buffer memo ry lis t ... ............................................................................................. 7-1
7.2 Details of buffer memories................................................................................... 7-4
7.2.1 BFM #0: Flag.............................................................................................................7-4
7.2.2 BFM #1 (CH1) and BFM #2 (CH2): Event.................................................................7-5
7.2.3 BFM #3 (CH1) and BFM #4 (CH2): Measured value (PV) ........................................7-7
7.2.4 BFM #5 (CH1) and BFM #6 (CH2): Control output value (MV) .................................7-7
7.2.5 BFM #7 (CH1) and BFM #8 (CH2): Heater current measured value.........................7-7
7.2.6 BFM #9: Default setting command............................................................................7-7
7.2.7 BFM #10: Error reset command ................................................................................7-7
7.2.8 BFM #11: Control start/stop changeover...................................................................7-7
7.2.9 BFM #12 (CH1) and BFM #21 (CH2) : Set value (SV)..............................................7-8
vii
FX2N-2LC Temperature Control Block
7.2.10 BFM #13 to BFM #16 (CH1) and BFM #22 to BFM #25 (CH2):
Alarm 1/2/3/4 set value..............................................................................................7-8
7.2.11 BFM #17 (CH1) and BFM #26 (CH2): Heater disconnection alarm set value...........7-8
7.2.12 BFM #18 (CH1) and BFM #27 (CH2) : Auto/manual mode changeover ...................7-8
7.2.13 BFM #19 (CH1) and BFM #28 (CH2): Manual output set value................................7-9
7.2.14 BFM #20 (CH1) and BFM #29 (CH2): Auto tuning ex ecu tio n com man d..... ..............7-9
7.2.15 BCM#30: Unit type code............................................................................................7-9
7.2.16 BFM #32 (CH1) and BFM #51 (CH2): Operation mode ............................................7-9
7.2.17 BFM #33 (CH1) and BFM #52 (CH2): Proportional band (P)....................................7-9
7.2.18 BFM #34 (CH1) and BFM #53 (CH2): Integral time (I)............................................ 7-10
7.2.19 BFM #35 (CH1) and BFM #54 (CH2): Derivative time (D) ......................................7-10
7.2.20 BFM #36 (CH1) and BFM #55 (CH2): Control response parameter .......................7-11
7.2.21 BFM #37 (CH1) and BFM #56 (CH2): Output limiter upper limit
BFM #38 (CH1) and BFM #57 (CH2): Output limiter lower limit..............................7-12
7.2.22 BFM #39 (CH1) and BFM #58 (CH2): Output change ratio limiter..........................7-13
7.2.23 BFM #40 (CH1) and BFM #59 (CH2): Sensor correction value setting (PV bias)...7-14
7.2.24 BFM #41 (CH1) and BFM #60 (CH2): Adjustment sensitivity (dead zone) setting..7-15
7.2.25 BFM #42 (CH1) and BFM #61 (CH2): Control output cycle setting.........................7-15
7.2.26 BFM #43 (CH1) and BFM #62 (CH2): Primary delay digital filter setting ................7-16
7.2.27 BFM #44 (CH1) and BFM #63 (CH2): Setting change ratio limiter..........................7-17
7.2.28 BFM #45 (CH1) and BFM #64 (CH2): AT (auto tuning) bias...................................7-18
7.2.29 BFM #46 (CH1) and BFM #65 (CH2): Normal/reverse operation selection ............7-18
7.2.30 BFM #47 (CH1) and BFM #66 (CH2): Setting limiter upper limit
BFM #48 (CH1) and BFM #67 (CH2): Setting limiter lower limit .............................7-19
7.2.31 BFM #49 (CH1) and BFM #68 (CH2): Loop breaking alarm judgement time..........7-20
7.2.32 In BFM #50, set the loop breaking alarm dead zone of CH1.
In BFM #69, set the loop breaking alarm dead zone of CH2...................................7-21
7.2.33 BFM #70 (CH1) and BFM #71 (CH2): Input type selection .....................................7-22
7.2.34 BFM #72 to BFM #75: Alarm mode setting .............................................................7-23
7.2.35 BFM #76: Alarm 1/2/3/4 dead zone setting .............................................................7-25
7.2.36 BFM #77: Number of times of alarm 1/2/3/4 delay..................................................7-26
7.2.37 BFM #78: Number of times of heater disconnection alarm delay............................7-26
7.2.38 BFM #79: Temperature rise completion range setting ............................................ 7-27
7.2.39 BFM #80: Temperature rise completion soak time..................................................7-27
7.2.40 BFM #81: CT monitor method changeover .............................................................7-28
7.2.41 BFM #82: Set value range error address ................................................................7-28
7.2.42 BFM #83: Set value backup command....................................................................7-29
Contents
8. Program Example ........................................................................ .........8-1
8.1 Program example ................................................................................................ 8-2
9. Diagnostic .............................................................................................9-1
viii
FX2N-2LC Temperature Control Block
Introduction 1
1 Introduction
2 Product Configuration
3 Specifications
4 Wiring
5 Introduction of Functions
6Alarm
1
7 Buffer Memory (BFM)
8 Program Example
9 Diagnostic
FX2N-2LC Temperature Control Block
Introduction 1
FX2N-2LC Temperature Control Block

1. Introduction

Cautions on design
Install a saf et y circui t outs ide the PLC or the temper at ure cont rol block FX2N-2LC so that the entire system conservatively operates even if an abnormality occurs in the external power supply or a failure occurs in the PLC or the FX If a safety circuit is installed inside the PLC, malfu nction and erroneous output may cause accidents.
1) Make sure to const ruct an emergency stop circuit, protection circui t or interlock circuit to prevent damages of a machine, etc. outside the PLC or the FX
2N
-2LC.
2N
Introduction 1
1
-2LC.
2) If the PLC or the FX
-2LC detects an abnormality such as a watch dog timer error or
2N
input value error by the self-diagnosis function or when an abnormality occurs in the I/O control area, etc. which cannot be detected by the CPU in the PLC, output control may be disabled. Design external circuits and structure so that the entire system conservatively operates in such cases.
3) If a failure occurs in a relay, transistor, TRIAC, etc. in an output unit of the FX
2N
the PLC, outputs may keep ON or OFF. For output sig nals whic h ma y lead t o se v er e accidents , design e xt ernal circuits and struc­ture so that the entire system conservatively operates.
Cautions on installation
Use the unit in the environment for the general specifications described in the manual. Nev er use the unit in a place with dusts , soot, conducti ve dusts , corrosive gas or flamma­ble gas, place exposed to high temperature, dew condensation or rain and wi nd or place exposed to vibration or impact. If the unit is used in such a place, electrical shock, fire, malfunction, damages in the unit or deterioration of the unit ma y be caused.
Never drop cutting chips or electric wire chips into the ventilation window of the FX 2LC while drilling screw holes or wiring cables. Such chips may cause fire, failure or malfunction.
-2LC or
-
2N
After finishing installation, remove a dust preventing sheet adhered on the ventilation window of the PC and the FX
2N
-2LC.
If the sheet remains attached, fire, failure or malfunction may be caused.
Securely connect cables such as extension cables and memory cassettes to specified connectors. Imperfect contact may cause malfunction.
Caution on disposal
When disposing of the unit, treat it as industrial waste.
1-1
FX2N-2LC Temperature Control Block

1.1 Outline of product

The temperature control block FX2N-2LC (hereafter referred to as "temperature control block" or "FX output points is a special block to read temperature signals from thermocouples and platinum resistance thermometer bulbs, and pe rform PID output control. Connect the FX
1) As input sensors, two thermocouples, two platinum resistance thermometer bulbs or one
-2LC") equipped with two temperature input points and two transistor (open collector)
2N
-2LC to the FX
2N
thermocouple and one platinum resistance thermometer bulb are available.
2N/2NC
Introduction 1
Series PC.
2) Data can be written and read using FROM/TO instructions when the FX to the FX (The FX
2N
Series PC.
2N/2NC
-2LC performs arithmetic operation for PID control and output control. You do not
-2LC is connected
2N
have t o creat e sequence programs for PID operation.)
3) Disconnection of heaters can be detected by current detection (CT).
4) The proportional band, the integral time and the derivative time can be easily set by auto tuning.
5) Channels are isolated against each other.
1-2
FX2N-2LC Temperature Control Block
Product Configuration 2
1 Introduction
2 Product Configuration 2
3 Specifications
4 Wiring
5 Introduction of Functions
6Alarm
7 Buffer Memory (BFM)
8 Program Example
9 Diagnostic
FX2N-2LC Temperature Control Block
Product Configuration 2
FX2N-2LC Temperature Control Block

2. Product Configuration

2.1 Outside dimension

4
Extension cable
24+
24- O
Connector for next step extension cable
Product Configuration 2
2
FX2N-2LC
Mounting hole
φ
2-
45
55

2.2 Name of each part

24+
24- O
POWER
24V
OUT1
OUT2
DIN rail
90
80 ±0.5
(mounting dimension)
Status indicator LED
DIN rail (width: 35 mm) mounting groove
87
Unit: mm Mass: kg Outer color: Munsell 0.08GY / 7.64 / 0.81
Terminal block
24+ COM
24-
OUT1OUT2
POWER
FX2N-2LC
24V
OUT1
OUT2
:PC connection cable
:Screw mounting hole
:Status indicator LED
:DIN rail mounting g roove (DIN rail width: 35 mm)
:DIN rail mounting hook
:Connector for next step ex tension cable
CT
CH1 CH2
CT FG
PTA
PTB
TC+
PTB
TC-
CT
CT FG
PTA
PTB
TC+
PTB
TC-
2-1
FX2N-2LC Temperature Control Block

2.3 Status indication

Table 2.1:
LED name Indication Description
POWER
24V
OUT1
OUT2
Lit (green) 5 V power is supplied from PC main unit. Extinguished 5 V power is not supplied from PC main unit. Lit (red) 24 V power is supplied from outside. Extinguished 24 V power is not supplied from outside. Lit (red) OUT1 output is ON. Extinguished OUT1 output is OFF. Lit (red) OUT2 output is ON. Extinguished OUT2 output is OFF.
Product Configuration 2
2-2
FX2N-2LC Temperature Control Block

2.4 Installation method

Product Configuration 2
The FX2N-2LC can be installed on the right side of an FX2N/
Series extension unit or another extension block.
2NC
The FX
-2LC can be attached with a DIN rail DIN46277 ( wid th: 35 mm) or directl y attached to
2N
Series PLC ba sic unit, FX2N/
2NC
a panel surface with scr ews (M4).
Installation on DIN rail Align the upper side of the DIN rail mounting groove of the FX DIN46277 (width: 35 mm) (①), and push the FX When removing the FX remove the FX
-2LC (④).
2N
-2LC, pull out downward the DIN rail mounting hook (③), then
2N
-2LC on the DIN rail (②).
2N
-2LC with a DIN rail
2N
When attaching to DIN rail When removing from DIN rail
2
Direct installation on panel surface Screw-tighten the FX mounting holes provided on the left side of the FX
-2LC with M4 screws to a panel surface using two (upper and lower)
2N
-2LC.
2N
Assure the interval of 1 to 2 mm between a unit or block installed on the left side of the FX
-2LC.
2N
Cautions on installation
Use the unit in the environment for the general specifications described in the manual.
Nev er use the unit in a place with dusts , soot, conducti ve dusts , corrosive gas or flamma­ble gas, place exposed to high temperature, dew condensation or rain and wi nd or place exposed to vibration or impact. If the unit is used in such a place, electrical shock, fire, malfunction, damages in the unit or deterioration of the unit ma y be caused.
Never drop cutting chips or electric wire chips into the ventilation window of the FX
2LC while drilling screw holes or wiring cables. Such chips may cause fire, failure or malfunction.
After finishing installation, remove a dust preventing sheet adhered on the ventilation
window of the PC and the FX If the sheet remains attached, fire, failure or malfunction may be caused.
2N
-2LC.
2N
-
Securely connect cables such as extension cables and memory cassettes to specified
connectors. Imperfect contact may cause malfunction.
2-3
FX2N-2LC Temperature Control Block

2.5 Connection to PC Main Unit

Connect the FX2N-2LC to the PC main unit with an extension cabl e. FX
-2LC units are treated as special blocks of the PLC, and the special block No. 0 to 7 is
2N
automatically assigned to each FX (These unit Nos. are used in FROM/TO instructions.) One FX For the details of I/O assignment in the PC, refer to the manual of the FX
-2LC unit occupies eight I/O points in the PC main unit.
2N
Product Configuration 2
-2LC unit from the one nearest to the PLC basic unit.
2N
Series PC.
2N/2NC
FX2N-32MR
(X000 to X017)
X3X2X1
FX2N-32MR
Y4Y5Y6
Y10
COM3
X10 X14 X16
X7
IN
OUT
Y12
Y11
Y13Y1Y2Y3
14 171510 12 13
Y14
COM X4
LX13X15
24+N
(Y000 to Y017)
72456130
1611
72456130
1611 1514 1710 12 13
Y15
FX2N-4AD
POWER
RUN
BATT.V
PROG.E
CPU.E
FX2N-4AD
Special
block
No. 0
POWER
A/D
24V
FX2N-2LC
POWER
FX2N-2LC
24V
OUT1
OUT2
Special
block No. 1
(X020 to X037)
(Y020 to Y037)
( ) indicates the I/O No. assignment in the PC main unit.
Up to eight FX units can be connected to the FX
When connecting the FX
-2LC units can be connected to the FX2N Series PC. Up to four FX2N-2LC
2N
Series PC.
2NC
-2LC unit to the FX
2N
Series PC, the interface FX
2NC
required. (When connecting the FX
-2LC unit to the FX2N Series PC, the interface FX
2N
not required.)
FX2N-32MR
X0
X6 X0 X2 X4 X6
COM X4
24+N
X3X2X1
FX2N-32ER
X5
X7
IN
01234567
OUT
76543210
72456130
72456130
Y4Y5Y6
COM4COM2Y4Y5Y6Y7 COM3Y0Y1Y2Y3COM1Y0Y1Y2Y3
L X1X3X5X7
POWER
Y7
FX2N-2LC
POWER
FX2N-2LC
24V
OUT1
OUT2
Special
block
No.2
-CNV-IF is
2NC
-CNV-IF is
2NC
For extension, an extension cable FX rately are required. Only one FX
-65EC can be used per system.
0N
-65EC (650 mm) and the FX
0N
-CNV-BC sold sepa-
2NC
2-4
FX2N-2LC Temperature Control Block
Specifications 3
1 Introduction
2 Product Configur ation
3 Specifications 3
4 Wiring
5 Introduction of Functions
6Alarm
7 Buffer Memory (BFM)
8 Program Example
9 Diagnostic
FX2N-2LC Temperature Control Block
Specifications 3
FX2N-2LC Temperature Control Block

3. Specifications

3.1 Environmental specifications

Table 3.1:
Item Specifications
Withstand voltage
500 VAC for 1 minute (between analog input terminal and grounding ter­minal)
Specifications 3
Other environmental specifications are equivalent to those for the PC main unit. (Refer to the manual of the PC main unit.)

3.2 Power supply specifications

Table 3.2:
Item Specifications
Driving power supply 24 VDC (-15% to +10%), input from driving power supply terminal Power supply for communi-
cation Current consumption 24 VDC, 55 mA and 5 VDC, 70 mA
Insulation method
Number of occupied I/O points
5 VDC (supplied from inside of PC main unit)
Analog input area and PC are insulated by photocoupler. Power supply and analog input ar e insula ted by DC/DC converter. (Channels are not insulated each other.)
8 points in total (including input points and output points)
3
3-1
FX2N-2LC Temperature Control Block

3.3 Performance specifications

Table 3.3:
Item Description
Control method Control operation period 500 ms
Set temperature range Equivalent to input range (Refer to 7.2.33) Heater disconnection detection
Operation mode
Self-diagnosis function Memory Built-in EEPROM (Number of times of overwrite: 100,000 times)
POWER
24V
Status indication
OUT1
OUT2
Lit (green) 5 V power is supplied from PC main unit. Extinguished 5 V power is not supplied from PC main unit. Lit (red) 24 V power is supplied from outside. Extinguished 24 V power is not supplied from outside. Lit (red) OUT1 output is ON. Extinguished OUT1 output is OFF. Lit (red) OUT2 output is ON. Extinguished OUT2 output is OFF.
Specifications 3
Two-position control, PID control (with auto tuning function), PI control
Alarm is detected in accordance with setting of buffer memory. (Variable within range from 0.0 to 100.0 A.).
0: Measured value monitor 1: Measured value monitor + Temperature alarm 2: Measured value monitor + Temperature alarm + Control (Selected by buffer memory)
Adjustment data and input value are checked by watch dog timer. When abnormality is detected, transistor output turns off.
3-2
FX2N-2LC Temperature Control Block

3.4 Input specifications

Table 3.4:
Item Description
Number of input points 2 points
Input type
Measurement precision
Cold contact tempera-
Temperature input
CT input
ture compensation error
Resolution Sampling period 500 mS
Effect of external resis­tance
Input impedance Sensor current Approx. 0.3 mA Allowable input lead wire
resistance Operation when input is
disconnected Operation when input is
short-circuited Number of input points 2 points
Current detector Heater
current measured value
Measurement precision Sampling period 1 second
Thermocou-
ple
Resistance thermome-
ter bulb
When CTL-
12 is used
When CTL-
6 is used
Specifications 3
K, J, R, S, E, T, B, N, PLII, WRe5=26, U, L
Pt100, JPt100
± 0.7 % of range span ± 1 digit (± 0.3 % of range span ± 1 digit when ambient temperature is 23 °C ± 5 °C) However, 0 to 399 °C (0 to 799 °F) in B inputs as well as 0 to 32 °F in PLII and WRe5-26 inputs are outside precision guar­antee range.
Within ± 1.0 °C However, within ± 2.0 °C while input value is -100 to -150 °C within ± 3.0 °C while input value is -150 to -200 °C
0.1 °C (0.1 °F) or 1 °C (1 °F) (Varies depending on input range of used sensors.)
Approx. 0.35 µV/
1 Μ Ω
10 Ω or less
Upscale
Downscale
CTL-12-S36-8 or CTL-6-P-H (manufactured by U.R.D. Co., Ltd.)
0.0 to 100.0 A
0.0 to 30.0 A Larger one between ± 5 % of input value and 2 A
(excluding precision of current detector)
or more
3
3-3
FX2N-2LC Temperature Control Block

3.5 Input range

Table 3.5:
Sensor type K J R S
-200.0 to 200.0 °C
-100.0 to 400.0 °C
Input range
Sensor type E T B N
Input range
-100 to 1300 °C
-100 to 2400 °F
-200.0 to 200.0 °C
-100 to 800 °F
0 to 1000 °C 0 to 1800 °F
-200.0 to 200.0 °C
-100.0 to 400.0 °C
-100.0 to 800.0 °C
-100 to 1200 °C
-100 to 1600 °F
-100 to 2100 °F
-200.0 to 200.0 °C
-200.0 to 400.0 °C 0 to 400.0 °C
-300.0 to 400.0 °F
-300.0 to 700.0 °F
0.0 to 700.0 °F
0 to 1700 °C 0 to 3200 °F
0 to 1800 °C 0 to 3000 °F
Specifications 3
0 to 1700 °C
0 to 3200 °F
0 to 1300 °C
0 to 2300 °F
Sensor type PL II WRe5-26 U L
Input range
Sensor type K J
Input range
0 to 1200 °C 0 to 2300 °F
-50.0 to 150.0 °C
-200.0 to 500.0 °C
-300.0 to 300.0°F
-300 to 900 °F
0 to 2300 °C 0 to 3000 °F
-50.0 to 150.0 °C
-200.0 to 600.0 °C
-300.0 to 300.0°F
-300 to 1100 °F
-200.0 to 600.0 °C
-300.0 to 700.0 °F
0.0 to 900.0 °C 0 to 1600 °F
When B is used, 0 to 399 °C (0 to 799 °F) is outside the precision compensation range.
When PLII is used, 0 to 32 °F is outside the precision compensation range.
When WRe5 to WRe26 are used, 0 to 32 °F is outside the precision compensation range.
3-4
FX2N-2LC Temperature Control Block

3.6 Output specifications

Table 3.6:
Item Description
Number of output points 2 points Output method NPN open collector transistor output Rated load voltage 5 to 24 VDC Maximum load voltage 30 VDC or less Maximum load current 100 mA Leak current in OFF status 0.1 mA or less Maximum voltage drop in ON status 2.5 V (maximum) or 1.0 V (typical) at 100 mA Control output cycle 30 seconds (Variable within range from 1 to 100 seconds)
Specifications 3
3
3-5
FX2N-2LC Temperature Control Block
Specifications 3
3-6
FX2N-2LC Temperature Control Block
Wiring 4
1 Introduction
2 Product Configur ation
3 Specifications
4 Wiring 4
5 Introduction of Functions
6Alarm
7 Buffer Memory (BFM)
8 Program Example
9 Diagnostic
FX2N-2LC Temperature Control Block
Wiring 4
Loading...
+ 70 hidden pages