1. Outline
The RS-422 communication board FX1N-422-BD (hereafter referred to as "422BD") is connected to the FX1S/FX
Series PLC basic unit, and used as a connection port for a programming tool (such as the GOT Series, the ET Series,
programming tool FX-10P/20P or personal computer).
For example, by using the 422BD, two GOT Series units can be connected to the FX1S/FX1N Series PLC, or the GOT
Series unit can be connected to a programming tool (such as F X-10P, FX-20P or personal computer). However, a
programming tool can be connected to only either one between the connector built in the PLC and the connector of
the 422BD.
Only one function expansion board can be connected to one PLC basic unit. Accordingly, the 422BD cannot be used
-485-BD or the FX1N-232-BD.
together with the FX
1N
2. Outside Dimensions and Name of Each Part
Unit: mm
43
➂
➀
➃
➀ Mounting hole (2-φ3.5)
➁
➁ Connector for PLC
➂ Connector for RS-422 equipment (mini-DIN, 8-pin type)
The top face of this connector is higher than the top face of the PLC
panel cover by approximately 3 mm when a cable is not connected, and
38.5
by approximately 50 mm when a cable is connected.
➃ Connector for display module FX
-5DM or memory cassette FX1N-
1N
EEPROM-8L
Accessories: Top cover for board 1
M3 screw to mount board 2
M3 screw to fix top cover 1
1N
1N
-
3. Connectable Models and Cables
Peripheral equipment Cable Current consumption of 5V DC
FX-20P
FX-10P 120mA
Personal computer
(for pr ogramming)
FX-10DM FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP 180mA
F930GOT, F940GOT,
ET-940, F940/943GOT
(handy type)
FX-20P-CAB0 or
(FX-20P-CAB + FX-20P-CADP)
{F2-232CAB (for D-sub, 25-pin type),
F2-232CAB-1 (for D-sub, 9-pin type) or
F2-232CAB-2 (for half-pitch, 14-pin type)}
+ FX-232AW(C) + FX-422CAB0
FX-50DU-CAB0 Not required
FX-40DU-CAB(-10M) (or equivalent cable) + FX- 422AW0 180mA
180mA
220mA

JY992D84101B
DATE : MAY 2000
4. Installation
Make sure to turn off the power before installing the 422BD.
A) Communication board 422BD (function expansion board)
B) Connector for optional equipment
C) M3 screw to fix board (2 pieces) (offered as accessories of board)
D) Top cover for board (offered as an accessory of board)
E) M3 screw to fix top cover (offered as an accessory of board)
Note: This screw cannot be removed.
• Plug the communication board A) in to the connector B).
• Fix the board to the basic unit with two M3 screws C). (Tightening torque: 0.3 to 0.6 Nžm)
• Remove the top c over of the basic unit, a nd a ttach th e top cover f or b oard D) i nstea d.
During attachment, remov e D)’ with a n ipper , e tc. so that the conn ector of the board is e xposed.
• Fix the top cover with the M3 screw E). (Tightening torque: 0.3 to 0.6 Nžm)
-5DM is used also, refer to the handy manual offered with the FX1S/FX1N Series PLC main unit.
• When the FX
• Only one function expansion board is available for one FX
1N
/FX1N Series PLC basic unit. Never stack up two or
1S
more function expansion boards. (Even if they are stacked up, they do not function at all.)
5. Specifications
5.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit. (Refer to the manual of the PLC main unit.)
5.2 Power supply specifications
5V DC, 60 mA is supplied as the power from the PLC.
For the details, refer to the handy manual of the PLC main unit.
5.3 Performance specifications
Transmis sion standard
Maximum transmission distance
External equipment connection meth od
Communication method
Communication procedure
Insulation
In conformance to RS-422
50 m maximum
Mini-DIN, 8- pin sock e t
Half duplex, bi-directional
Protocol for programming tool
Not insulated
D)'
D)
C)
A)
B)
Note)
E)
C)
6. Cautions on Use
1) Do not perform communication setting of D8120 using a peripheral equipment or program. If such setting is
performed, communication with a programming tool or the GOT Series is disabled.
2) Connect a programming tool (such as FX-10P, FX-20P and personal computer) to either one between a connector
built in the PLC and the connector of the 422BD. If a programming tool is connected to the both connector s, the
following may occur:
A program stored in the PLC may not match a program stored in the programming tool. If the program is changed
or the set value of timers or counters are changed in this status, the program may be partially overwritten and the
PLC may malfunction.
7. Troubleshooting
1) Make sure that the connected cables are properly connected.
2) Check connection with the PLC and the POWER LED status on the PLC main unit.
3) Make sure that the communication format is in the initial status (D8120 = K0).
Using periph eral equipmen t, make sure of the co mmunication sett ing in para meters. If n on-procedure (RS
instruction) or a dedicated protocol is selected, clear the setting to "0" using peripheral equipment.
4) Make sure that RS, VRRD and VRSC instructions are not used in the program. If they are used, delete them, turn
off the power of the PLC, then turn it on again.
5) If the special auxiliary relay M8070 or M8071 is ON, set it to OFF using peripheral equipmen t, turn off the pow er of
the PLC, then turn it on again.
For the phone number and the fax number of Technical Consulting in the FA Division within
Corporation an d the M ELSE C-F Fax Information Service, refer to the manual of th e PLC ma in unit.
M Electric