(Be sure to read these instructions before using the product.)
Before using this product, read this manual and the relevant manuals introduced in this manual carefully
and handle the product correctly with full attention to safety.
The precautions given in this manual are concerned with this product. For the safety precautions of the
programmable controller system, please read the user's manual of the CPU module to use.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
DANGER
CAUTION
Note that the failure to observe ! CAUTION level instructions may also lead to serious results
according to the circumstances.
Be sure to observe the precautions of both levels to ensure personal safety.
Please keep this manual in accessible place and be sure to forward it to the end user.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in minor or moderate injury or property damage.
[Design Precautions]
!
DANGER
• When a communication error has occurred in data link, data in the master module are
maintained.
Establish an interlock circuit in the sequence program using communication status information
so that the safety will be ensured.
!
CAUTION
• Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other.
They should be installed 100mm (3.9inch) or more from each other.
Not doing so could result in noise that would cause erroneous operation.
• Do not write data to "Reserved area" of remote I/O areas or remote devices.
Doing so may cause malfunctions of the product.
A - 1 A - 1
[Installation Precautions]
!
CAUTION
• Use each product in an environment as specified in the "general specification" in this manual.
Using the programmable controller outside the range of the general specifications may result in
electric shock, fire or malfunction, or may damage or degrade the product.
• Securely fix the product with DIN rails or module mounting screws.
Failure to do so may cause a fall or malfunctions of the product.
• Do not touch the conducted area or electric parts of the product.
Doing so may cause product malfunctioning or breakdowns.
[Wiring Precautions]
!
CAUTION
• For application to the CC-Link/LT, use cables specified by the CC-Link Partner Association.
Otherwise, performance of the CC-Link/LT cannot be guaranteed. Also, wire a network properly
in accordance with the specifications given in Chapter 3.
If not, normal data transmission cannot be guaranteed.
• Be sure to shut off all phases of the external power supply used by the system before installation
or wiring.
Not doing so can cause the product to be damaged or malfunction.
• Always ground the FG terminal to the protective ground conductor.
Not doing so can cause a malfunction.
• Make sure of the rated voltage and pin-outs of the product for proper wiring.
Connecting power source of improper rated voltage or faulty wiring may cause a fire or failure.
• Ensure that no foreign matter such as chips and wire-offcuts enter the product.
Foreign matter can cause a fire, failure or malfunction.
A - 2 A - 2
[Wiring Precautions]
!
CAUTION
• Always secure the communication cable connected to the product by running it in a conduit or
clamping it.
Not doing so can cause damage to the product and/or cable due to the dangling, motion,
careless pulling, etc. of the cable or cause a malfunction due to a faulty connection of the cable.
• When disconnecting the communication cable connected to the product, do not pull it by holding
its cable part.
When disconnecting the cable with connector, hold the connector of the product's connection
part.
Disconnect the terminal block connection cable after loosening the terminal block screws.
Pulling the cable connected to the product can cause a malfunction or damage to the product
and/or cable.
[Starting and Maintenance Precautions]
!
CAUTION
• Do not touch pins while the product is energized. Doing so may cause malfunctions.
• Be sure to shut off all phases of the external power supply used by the system before cleaning.
• Do not disassemble or modify the product.
Doing so may cause failure, malfunctions, injury or fire.
• Do not drop the product or give it hard impact since its case is made of resin. Doing so can
damage the product.
• Be sure to shut off all phases of the external power supply used by the system before mounting
or dismounting the product to or from the panel.
Not doing so can cause the product to fail or malfunction.
• Mounting/removing the terminal block is limited to 50 times after using a product.
(IEC61131-2-compliant)
• Before handling the module, always touch grounded metal, etc. to discharge static electricity
from the human body.
Failure to do so can cause the module to fail or malfunction.
[Disposal Precautions]
!
CAUTION
• When disposing of this product, treat it as industrial waste.
A - 3 A - 3
REVISIONS
* The manual number is given on the bottom left of the back cover.
Correction
Compliance with the EMC Directive and Low Voltage Directive,
Section 2.3, 3.3.2, 3.4.5
May, 2008 SH(NA)-080362E-F
Correction
Manuals, Compliance with the EMC Directive and Low Voltage Directive,
Generic Terms and Abbreviations,
Section 2.2, 3.7.1, 3.8.1, 3.9, 4.5.2, 4.6, 4.7.1, 6.2, 6.6.6
Japanese Manual Version SH-080361-F
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
Thank you for purchasing the MELSEC-A series programmable controller. Before using the product, read
this manual carefully to fully understand the functions and the performance of the programmable controller.
Please forward a copy of this manual to the end user.
1.2 Features ................................................................................................................................................... 1- 2
2.3 Precautions for System Configuration..................................................................................................... 2- 3
2.4 Parts Sold Separately .............................................................................................................................. 2- 7
3. SPECIFICATIONS 3- 1 to 3-28
3.1 General Specifications ............................................................................................................................. 3- 1
3.7.6 Data of faulty station (2 occupied stations: Address RWrn+1, common to 4 and 8 occupied stations
(4 occupied stations
3.7.7 Remote I/O error data (2 occupied stations: Address RWrn+2, common to 4 and 8 occupied stations
(4 occupied stations
3.7.8 Data of remote station connection (2 occupied stations: Address RWrn+3, common to 4 and
8 occupied stations (4 occupied stations
3.7.9 Setting data (2 occupied stations: Address RWrn+4, common to 4 and 8 occupied stations
(4 occupied stations
3.8 Data Link Processing Time...................................................................................................................... 3-26
3.8.1 CC-Link link scan time ...................................................................................................................... 3-26
3.8.2 CC-Link/LT link scan time ................................................................................................................. 3-26
3.9 Transmission Delay Time ........................................................................................................................ 3-27
4.1 Procedure Up to Data Link ...................................................................................................................... 4- 1
4.2 Mounting and Installation ......................................................................................................................... 4- 3
4.3 Part Names and Settings .........................................................................................................................4- 4
4.4 Facing Direction of the Module Installation ............................................................................................. 4- 7
4.5 Connecting Modules by CC-Link/LT Side Cables................................................................................... 4- 8
4.5.1 How to connect dedicated flat cable connector ............................................................................... 4- 9
4.5.2 How to connect VCTF or high flexible cable connector................................................................... 4-11
4.5.3 Mixture of different kinds of cables ...................................................................................................4-14
The following manuals are also relevant to this product.
You can order them as necessary.
Relevant Manuals
Manual Name
Control & Communication System Master/Local Module User's Manual
type AJ61BT11/A1SJ61BT11
Describes the system configuration, performance specifications, functions, handling, wiring and
troubleshooting of the AJ61BT11 and A1SJ61BT11. (Sold separately)
Control & Communication System Master/Local Module User's Manual
type AJ61QBT11/A1SJ61QBT11
Describes the system configuration, performance specifications, functions, handling, wiring and
troubleshooting of the AJ61QBT11 and A1SJ61QBT11. (Sold separately)
Manual Number
(Model Code)
IB-66721
(13J872)
IB-66722
(13J873)
Control & Communication System Master/Local Module User's Manual type QJ61BT11N
Describes the system configuration, performance specifications, functions, handling, wiring and
troubleshooting of the QJ61BT11N. (Sold separately)
Type A80BDE-J61BT11 Control & Communication Link System Master/Local Interface
Board User's Manual (For SW4DNF-CCLINK-B)
Describes the system configuration, performance specifications, handling, wiring and troubleshooting of
the A80BDE-J61BT11. (Sold separately)
Type Q80BD-J61BT11N Control & Communication Link System Master/Local Interface
Board User's Manual (For SW1DNC-CCBD2-B)
Describes the system configuration, performance specifications, handling, wiring and troubleshooting of
the A80BDE-J61BT11. (Sold separately)
SH-080394E
(13JR64)
IB-0800175
(13JR28)
SH-080527ENG
(13JR77)
Compliance with the EMC Directive and Low Voltage Directive
(1) For programmable controller system
To configure a system meeting the requirements of the EMC and Low Voltage
Directives when incorporating the Mitsubishi programmable controller (EMC and
Low Voltage Directives compliant) into other machinery or equipment, refer to the
"EMC AND LOW VOLTAGE DIRECTIVES" chapter of the User's Manual for the
CPU module used.
The CE mark, indicating compliance with the EMC and Low Voltage Directives, is
printed on the rating plate of the programmable controller.
(2) For the product
For the compliance of this product with the EMC and Low Voltage Directives,
refer to the "CC-Link module" section in the "EMC AND LOW VOLTAGE
DIRECTIVES" chapter of the User's Manual for the CPU module used.
A - 8 A - 8
Generic Terms and Abbreviations
Unless otherwise specified, this manual uses the following generic terms and abbreviations.
Generic Term/Abbreviation Description
AJ65SBT-CLB Abbreviation for AJ65SBT-CLB CC-Link - CC-Link/LT bridge module.
Generic product name for the product types SWnD5C-GPPW-E, SWnD5C-GPPW-EA,
GX Developer
Master module
Remote I/O module
Remote device module
Remote module Generic term for remote I/O module and remote device module.
Remote I/O station
Remote device station
Remote station Generic term for remote I/O station and remote device station.
Intelligent device station
Dedicated power supply
Power supply adapter
RX
RY
RWw
RWr
SWnD5C-GPPW-EV and SWnD5C-GPPW-EVA.
(n indicates any of Versions 0 to 7)
Station that controls data link system.
One master station is required for each system.
Remote module that handles bit unit data only. (Performs input and output with external
devices.)
Remote module that handles bit unit and word unit data only. (Performs input and
output with external devices, and analog data conversion.)
Remote station that handles bit unit data only. (Performs input and output with external
devices.)
Remote station that handles bit unit and word unit data only. (Performs input and output
with external devices, and analog data conversion.)
Station that can perform transient transmission, such as the AJ65BT-R2N (including
local stations).
Module connected for power supply to CC-Link/LT system. At least one dedicated
power supply or power supply adapter is required for a system.
Remote input (for CC-Link)
Information input in bit unit from the remote station to the master station. (Represented
as RX)
Remote output (for CC-Link)
Information output in bit unit from the master station to the remote station.
(Represented as RY)
Remote register (Write area for CC-Link)
Information output in 16-bit unit from the master station to the remote device station.
(Represented as RWw)
Remote register (Read area for CC-Link)
Information input in 16-bit unit from the remote device station to the master station.
This manual provides the specifications, part names, setting, etc. of the AJ65SBT-CLB
CC-Link - CC-Link/LT bridge module (hereafter referred to as the AJ65SBT-CLB) that
is designated to be used as a remote device station in a CC-Link system.
The AJ65SBT-CLB includes the bridge function to establish a connection between CCLink and CC-Link/LT.
Using the AJ65SBT-CLB connects the remote I/O of CC-Link/LT to a CC-Link system.
Any of the A series, QnA series and Q series can be used to configure a system,
realizing a compact wire-saving system.
AJ65SBT-CLBRemote I/O stationRemote I/O station
Terminating resistor
Power supply adapter
CC-Link side
CC-Link/LT side
Partner company's
product
General power supply
24 V DC
Terminating resistor
Remote station
CL1Y4-T1B2
CL2AD4-B
Y0
Remote station
1 - 1 1 - 1
1 OVERVIEW
MELSEC-A
1.2 Features
The AJ65SBT-CLB has the following features.
(1) Seamless connection of two networks
The AJ65SBT-CLB is a bridge module that can connect CC-Link and CC-Link/LT
seamlessly.
Using RX and RY (bit devices), one bridge module can control up to 224 points
(448 points when both inputs and outputs are used).
(2) Confirmation of communication status of CC-Link/LT remote
stations
The data link statuses and I/O errors of CC-Link/LT remote stations can be
confirmed from the PLC CPU of the CC-Link master station.
(3) Configuration of CC-Link/LT using A, QnA ser ies
A CC-Link/LT system can be configured using the MELSEC-A, QnA series via
CC-Link.
(4) Wire saving and easy installation
The one-touch connectors ensure easy installation by using as the CC-Link side
communication connectors.
(5) Compact size
The AJ65SBT-CLB has the same size as the AJ65SBTB1-8 compact remote
I/O module.
(Width 87.0 (3.43)
Either of screws or DIN rail can be used to mount the module to a control panel.
height 49.0 (1.93) depth 40.0 (1.57) mm (inch))
1
1 - 2 1 - 2
A
2 SYSTEM CONFIGURATION
2 SYSTEM CONFIGURATION
2.1 Overall Configuration
MELSEC-
This section explains a system including the AJ65SBT-CLB.
For the transmission specifications, station-to-station distance, overall cable distance
2
(maximum transmission distance), etc. of CC-Link, refer to the user's manual of the
master module.
Refer to Section 3.3 for the wiring specifications.
Master
station
Remote I/O station
Intelligent
device station
CC-Link side
CC-Link/LT side
AJ65SBT-CLB
C
L
1
P
A
D
Remote stationRemote stationRemote station
C
L
2
8
Y
-
T
P
1
B
2
Y
0
C
L
2
8
Y
-
T
P
1
B
2
Y
0
1
Power
supply
adapter
General
power
supply
Item Specifications Remarks
Transmission speed 2.5 Mbps 625 kbps 156kbps
Station-to-station distance Not limited
Max. no. of modules per drop line 8 modules
Length of trunk line 35 m 100 m 500 m
T-branch interval Not limited
Max. length of drop line 4 m 16 m 60 m Max. cable length for one branch line
Overall length of drop lines 15 m 50 m 200 m Total length of all drop lines
T-branch
connection
Master station
Table 2.1 Network Wiring Specifications
Cable length between terminating resistors.
Length of
Length of trunk line (Drop line not included)
Interval length of T-branch
drop lines not included
*3
Terminating
resistor
Length
of
drop
Power
line
supply
adapter
Length of drop line
*2
*1
Remote
station
Remote
station
Distance
between stations
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Trunk line
Drop line
*3
Terminating
resistor
Remote
station
1: The length of the drop line includes the length of 2. (The max. length of drop line and overall
length of drop lines include the length of
2.)
3: Refer to Section 4.5.4 for the terminating resistor mounting method.
2 - 1 2 - 1
A
2 SYSTEM CONFIGURATION
MELSEC-
POINT
(1) The connection order of remote stations is not relevant to the station numbers.
(2) The remote station numbers are not necessarily consecutive. (Empty station
number does not cause data link failure.)
2.2 Applicable System
This section explains the applicable master modules and the precautions for system
configuration.
(1) The following table indicates the applicable master modules.
Model Name
Q series QJ61BT11N, QJ61BT11
QnA series AJ61QBT11, A1SJ61QBT11
A series AJ61BT11, A1SJ61BT11
FX series FX2N-16CCL-M
PCI board Q80BD-J61BT11N, A80BD-J61BT11
Others CC-Link partner maker's master module
2.2.1 Applicable software package
The FX series can be used within the range of:
FX
1N, FX1NC 128 points
FX
2N, FX2NC 256 points
in the whole system.
2
To carry out CC-Link / CC-link/LT diagnostics, GX Developer of Version 8.00A or later
is required.
2 - 2 2 - 2
A
2 SYSTEM CONFIGURATION
2.3 Precautions for System Configuration
(1) Arrangement of AJ65SBT-CLB
(a) CC-Link side
The AJ65SBT-CLB can be placed in any position as the remote device
station of the CC-Link system.
(b) CC-Link/LT side
Since T-branch connection can be made, the AJ65SBT-CLB can
apparently be placed midway through the trunk line. Note that the length of
Master
station
the trunk line is defined as the length between two terminating resistors.
Remote
I/O station
CC-Link side
CC-Link/LT side
AJ65SBT-CLB
Terminating resistor
Remote
device station
*3
MELSEC-
Remote
I/O station
Length of drop line
*2*2*2
Remote
station
Remote
station
Remote
station
Remote
station
*3
Terminating
resistor
Length of drop line
Length
of
drop
line
Length of trunk line
Power
supply
adapter
*2
*1
Remote
station
Remote
station
Distance
between stations
Remote
station
Remote
station
*1
Remote
station
Remote
station
Trunk line
Drop line
1 The length of drop line includes the length of 2. (The max. length of drop line and overall
length of drop lines include the length of 2.)
3 Refer to Section 4.5.4 for the terminating resistor mounting method.
(2) Number of CC-Link/LT side drop line branch stages
In the CC-Link/LT system, branch the drop line up to two stages.
The drop line cannot be branched to three or more stages.
Remote
station
Remote
station
Third drop line branch stage: cannot be wired.
Remote
station
Trunk line
Drop line
2 - 3 2 - 3
A
2 SYSTEM CONFIGURATION
(3) Mounting condition for CC-Link/LT dedicated power supply or
power supply adaptor
The mounting conditions for a dedicated power supply or power supply adapter
for the CC-Link/LT vary depending on the devices to be connected and the wiring
length.
Refer to the User’s Manual of the dedicated power supply or power supply adapter for
the conditions.
POINT
Always connect the dedicated power supply or power supply adapter to the trunk
line. (Connection to branch lines is not allowed.)
(4) Prevention of incorrect input/output from remote I/O module of CC-
Link/LT
To prevent incorrect input/output from remote I/O modules, design the system
while paying full attention to the following.
(a) When power is ON or OFF
Power ON the remote I/O module (Power on the dedicated power supply or
power supply adapter) before starting the data link.
Also, stop the data link before powering OFF the remote I/O module
(Powering off the dedicated power supply or power supply adapter).
MELSEC-
Data link start
Data link stop
Master module
(Data link status)
Remote I/O module
(Power status)
Executed
Stopped
ON
OFF
2 - 4 2 - 4
A
2 SYSTEM CONFIGURATION
(b) Instantaneous power failure of remote I/O module
When instantaneous power failure occurs in the power source (24V DC) for
the remote I/O module, incorrect data may be input.
1) Causes of incorrect input due to instantaneous power failure
Remote I/O module
(Power for module and
external power supply for input)
MELSEC-
The hardware of the remote I/O module converts the supplied power of
24V DC into 5V DC inside the module and uses it for its own operation.
When instantaneous power failure occurs in the remote I/O module,
the following,
(Time until 5V DC is turned OFF inside the remote I/O module)
>(Response time from ON to OFF of the input ), is established.
Therefore, when the devices are refreshed within the time shown as
(1), data will be incorrectly input. (Especially, when the input response
time is set to the high-speed response type)
1)
Remote I/O module
(Inside 5V DC)
Input (Xn)
Externally powering off for
input, turns input (Xn) OFF
after response time from ON to
OFF of Input unit.
Externally powering off for
input, turns input (Xn) ON
after response time from OFF
to ON of input module.
2 - 5 2 - 5
A
2 SYSTEM CONFIGURATION
2) Preventive measure against incorrect input
MELSEC-
Install wiring so that the power is supplied from the same power
source to the power supply module, stabilized power supply and
external power supply for AC input.
Remote I/O module
Remote I/O module
External
supply
power
for input
External
supply
power
for input
DC input
AC input
AJ65SBT-CLB
Stabilized
power supply
Stabilized
power supply
AJ65SBT-CLB
Stabilized
power supply
24VDC
24VDC
24VDC
Power supply
adapter
Power supply
adapter
2 - 6 2 - 6
A
2 SYSTEM CONFIGURATION
2.4 Parts Sold Separately
The plugs for AJ65SBT-CLB are sold separately.
One-touch
connector plug for
communication
1, 2
Online connector for
communication
One-touch connector
plug with terminating
resistor
(including 1)
3
Please purchase them as necessary.
Mitsubishi model
name
A6CON-L5P
A6CON-LJ5P
A6CON-TR11 ⎯
Part model name
(manufacturer)
35505-6000-
BOM GF (3M)
35720-L200-B00
AK (3M)
1 Mitsubishi's A6CON- 5P includes 10 plugs.
2 Once insulation-displaced, the one-touch connector plugs cannot be reused.
3 Mitsubishi's A6CON- J5P includes 5 plugs.
Specifications
communication line
0.5 (AWG#20)
shielded cable (drain wire)
0.5 (AWG#20)
⎯⎯⎯⎯
One-touch connector plug with
terminating resister attached
for communication (110Ω)
MELSEC-
2.2 to 3.0
Red
⎯⎯⎯
Color of
the cover
REMARK
• As following table indicates, the optional plugs/connectors are compatible with the
connectors for this module.
Connector for this Module Optional Parts
One-touch connector for
communication
• One-touch connector plug for communication
• Online connector for communication
• One-touch connector plug with terminating resistor
• Cables, connectors and terminating resistors on the CC-Link/LT side
For inquiries about the cables, connectors and/or terminating resistors on the CCLink/LT side, access the home page of the CC-Link Partner Association on the
Internet at http://www.cc-link.org/
.
2 - 7 2 - 7
A
2 SYSTEM CONFIGURATION
MEMO
MELSEC-
2 - 8 2 - 8
A
3 SPECIFICATIONS
3 SPECIFICATIONS
MELSEC-
3.1 General Specifications
Operating ambient
temperature
3
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
Shock resistance
Operating ambience No corrosive gases
Operating altitude 2000m (6562ft.) max.
Installation location Inside control panel
Overvoltage
category 1
Pollution degree 2 2 max.
Item Specifications
This chapter provides the specifications of the AJ65SBT-CLB.
Table 3.1 General specifications
0 to 55°C
-25 to 75°C
5 to 95%RH, non-condensing
5 to 95%RH, non-condensing
Frequency Acceleration Amplitude Sweep count
Conforming
to
JIS B 3502,
IEC 61131-2
Conforming to JIS B 3502, IEC 61131-2 (147 m/s
Under
intermittent
vibration
Under
continuous
vibration
10 to 57Hz ———
57 to 150Hz
10 to 57Hz ———
57 to 150Hz
9.8m/s2
4.9m/s2
II max.
2
, 3 times in each of 3 directions X, Y, Z)
0.075mm
(0.003inch)
———
0.035mm
(0.001inch)
———
10 times each in
X, Y, Z directions
(for 80 min.)
1 : This indicates the section of the power supply to which the equipment is assumed to be connected
between the public electrical power distribution network and the machinery within premises. Category II
applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
2 : This index indicates the degree to which conductive material is generated in terms of the environment
where the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs but temporary conductivity may be produced
due to condensation.
3 : Do not use or store the programmable controller under pressure higher than the atmospheric pressure of
altitude 0m.
Doing so can cause a malfunction.
When using the programmable controller under pressure, please contact your sales representative.
3 - 1 3 - 1
A
3 SPECIFICATIONS
MELSEC-
3.2 Performance Specifications
The following table provides the performance specifications of the AJ65SBT-CLB.
Table
3.2 Performance specifications
Item Specifications
Station type Remote device station
CC-Link Version Ver.1.10
2 stations
Number of
occupied
stations
CC-Link side
AJ65SBT-CLB connection position No restrictions
External connection system
4-point mode 8-point mode 16-point mode
Control
CC-Link/LT side
Communication specifications
Module mounting screw
Module mounting direction
24V DC power
Common
supply
Level of protection IP2X
Weight 0.09kg
1 Performance of the CC-Link/LT cannot be guaranteed for use of cables other than the dedicated flat cables, VCTF
cables and high flexible cables.
2 Supplied by the dedicated power supply or power supply adaptor of CC-Link/LT.
3 For VCTF cable specifications, see Table 3.3.
4 Use the dedicated flat cables and high flexible cables accredited by the CC-Link Partner Association. (Refer to Section
2.4.)
4 stations
8 stations
(4 occupied stations
modules)
Maximum number of link points
Number in parentheses assumes
use of the same I/O addresses
Number of link points per station
Number in parentheses assumes
specifications
use of the same I/O addresses
Transmission speed 2.5Mbps/625kbps/156kbps
Communication system BITR system (Broadcastpolling Interval Timed Response)
Transmission path format T-branch system
Error control system CRC
Number of connected modules 56 modules
Remote station number 1 to 56
AJ65SBT-CLB connection position Connected at the end of the trunk line
RAS functions
Connection cable 1
Voltage 24V DC externally supplied (20.4V DC to 26.4V DC, ripples within 5%)
2
Current consumption 0.075A (When 24V DC)
Start-time current 0.165A (When 24V DC)
2
64 points each for RX and RY (16 points are used in the system)
8 points each for RWr and RWw
128 points each for RX and RY (16 points are used in the system)
16 points each for RWr and RWw
256 points each for RX and RY (32 points are used in the system)
32 points each for RWr and RWw
One-touch connector for communication [transmission circuit] (5-pin,
insulation displacement type connector plug is sold separately)
<Sold separately> Online connector for communication: A6CON-LJ5P
224 points (448 points)
4 points
(8 points)
Network diagnostics, internal loopback diagnostics, slave station
separation, automatic return to system
M4
Tightening torque range 78 to 108N
DIN rail can also be used for mounting.
Can be mounted in any of six orientations.
(No restrictions on mounting directions)
4
cm
3
3 - 2 3 - 2
A
3 SPECIFICATIONS
Table 3.3 VCTF cable specifications (Extract from JIS C 3306)
MELSEC-
Type No. of cores
Vinyl cabtyre,
Round cord
Nominal cross-
sectional area
4 0.75mm
Conductor
Composition
No. of wires/wire diameter
2
30/0.18mm 1.1mm
Outside
diameter
Insulator
thickness
0.6mm 1.0mm
Sheath
thickness
3.3 Network Wiring Specifications
3.3.1 CC-Link network wiring specifications
For the network wiring specifications of CC-Link, refer to the user's manual of the
master module.
3.3.2 CC-Link/LT network wiring specifications
Master
station
CC-Link side
CC-Link/LT side
T-branch
connection
Terminating
1 The length of drop line includes the length of 2. (The max. length of drop line and overall
length of drop lines include the length of
3 Refer to Section 4.5.4 for the terminating resistor mounting method.
3 - 3 3 - 3
The following indicates the network wiring specifications of CC-Link/LT.
Item Specifications Remarks
Transmission speed 2.5 Mbps 625 kbps156 kbps
Distance between stations Not limited
Max. no. of connectable
modules per drop line
8 modules
Cable length between
Length of trunk line 35 m 100 m 500 m
terminating resistors. Length
of drop lines not included
T-branch interval Not limited
Max. length of drop line 4 m 16 m 60 m
Max. cable length per branch
line
Overall length of drop lines 15 m 50 m 200 m Total length of all drop lines
device station
*1
Length
of
drop
line
Remote
Length of trunk line (Drop line not included)
*2
Distance
between stations
Remote
station
Remote
Remote
station
Remote
I/O station
station
Interval length of T-branch
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Trunk line
Drop line
AJ65SBT-CLB
resistor
Remote
I/O station
Length
of
drop
*3
line
Power
supply
adapter
2.)
Terminating
resistor
Conductor
resistance
(20
)
25.1
Ω/km
*3
A
3 SPECIFICATIONS
MELSEC-
POINT
When connecting multiple lines with dedicated connectors to form one trunk line,
the number of connections must be 10 or less.
Line
Master station
connection
Terminating
resistor
Power
supply
adapter
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Remote
station
Terminating
resistor
3 - 4 3 - 4
A
3 SPECIFICATIONS
3.4 Concept of Remote Input/Output
This section explains the I/O signals for the AJ65SBT-CLB module.
Example: The following provides an example of setting the AJ65SBT-CLB to 2
occupied stations and 4-point mode.
Master
station
Station 1
1 station
occupied
Station 2
2 stations
occupied
Station 3
1 station
occupied
MELSEC-
CC-Link side
CC-Link/LT side
CC-Link master station
Station 1
Station 2
Station 3
AJ65SBT-CLB
Remote input
RX0F to RX00
RX1F to RX10
RX2F to RX20
RX3F to RX30
RX4F to RX40
RX5F to RX50
RX6F to RX60
RX7F to RX70
to
RX7FF to RX7F0
Section 3.5.1 to Section 3.5.3
Station 1
4 input
points
CL1X4-D1B2 CL2X8-D1B2
1 station
2 station
1 station
Station 2
8 input
points
AJ65SBT-CLB
RX2F to RX20
RX3F to RX30
RX4F to RX40
RX5F to RX50
Station 4
2 output
points
CL1Y2-T1D2S
48 points
System area,
16 points
Station 3
4 output
points
CL1Y4-T1B2
CC-Link/LT side
1) 4 points
2) 8 points
3) 4 points
4) 2 points
Empty,2 points
5) 16 points
Station 5
16 input
points
CL2X16-D1M1V
1 station
2 stations
1 station
1 station
4 stations
Section 3.5.4
3 - 5 3 - 5
A
3 SPECIFICATIONS
3.5 Remote I/O Signals for CC-Link Master Module
This section explains the I/O signals of the AJ65SBT-CLB for the CC-Link master
module.
3.5.1 Remote I/O signal list when 2 stations are occupied
MELSEC-
Signal Direction: AJ65SBT-CLB master module Signal Direction: Master module AJ65SBT-CLB
Remote input (RX) Name Remote output (RY) Name
RXn0
to
RX(n 2)F
RX(n+3)0
to
3)9
RX(n
RX(n 3)A Error status flag
RX(n 3)B Remote READY
RX(n 3)C
RX(n 3)D
RX(n 3)E
RX(n 3)F
Out of 64 points, 16 points are used as a system area.
RYn0
Used by CC-Link/LT remote
Use prohibited
Use prohibited
to
RY(n 2)F
3)0
RY(n
to
3)F
RY(n
Used by CC-Link/LT remote
Use prohibited
POINT
The prohibited devices are used by the system and therefore cannot be used by
the user.
If data is written to the buffer memory area corresponding to the prohibited device
or to the device specified for auto refresh, the functions of the AJ65SBT-CLB
cannot be guaranteed.
3 - 6 3 - 6
A
3 SPECIFICATIONS
3.5.2 Remote I/O signal list when 4 stations are occupied
MELSEC-
Signal Direction: AJ65SBT-CLB Master module Signal Direction: Master module AJ65SBT-CLB
Remote input (RX) Name Remote output (RY) Name
RXn0
to
6)F
RX(n
RX(n 7)0
to
RX(n 7)9
RX(n 7)A Error status flag
RX(n 7)B Remote READY
RX(n 7)C
RX(n 7)D
RX(n 7)E
RX(n 7)F
Out of 128 points, 16 points are used as a system area.
RYn0
Used by CC-Link/LT remote
Use prohibited
Use prohibited
to
RY(n 6)F
RY(n
7)0
to
RY(n 7)F
Used by CC-Link/LT remote
Use prohibited
POINT
The prohibited devices are used by the system and therefore cannot be used by
the user.
If data is written to the buffer memory area corresponding to the prohibited device
or to the device specified for auto refresh, the functions of the AJ65SBT-CLB
cannot be guaranteed.
3 - 7 3 - 7
A
3 SPECIFICATIONS
MELSEC-
3.5.3 Remote I/O signal list when 8 stations are occupied (4 occupied stations 2 modules)
Out of 256 points, 32 points are used as a system area.
When 8 stations (4 occupied stations
Signal Direction: AJ65SBT-CLB Master module Signal Direction: Master module AJ65SBT-CLB
Remote input (RX) Name Remote output (RY) Name
RXn0
to
RX(n 6)F
RX(n 7)0
to
7)9
RX(n
RX(n 7)A Error status flag
RX(n 7)B Remote READY
RX(n 7)C
RX(n 7)D
RX(n 7)E
RX(n 7)F
RX(n 8)0
to
RX(n E)F
RX(n F)0
to
F)9
RX(n
RX(n F)A Error status flag
RX(n F)B Remote READY
RX(n F)C
RX(n F)D
RX(n F)E
RX(n F)F
occupying modules are placed in series.
Used by CC-Link/LT remote
Use prohibited
Use prohibited
Used by CC-Link/LT remote
Use prohibited
Use prohibited
POINT
• The prohibited devices are used by the system and therefore cannot be used by
the user.
If data is written to the buffer memory area corresponding to the prohibited device
or to the device specified for auto refresh, the functions of the AJ65SBT-CLB
cannot be guaranteed.
• Set the station data as two modules that occupy four remote device stations.
• The same data is stored into "RXn
2 modules) are occupied, two 4-station
RYn0
to
RY(n 6)F
7)0
RY(n
to
7)F
RY(n
RY(n 8)0
to
RY(n E)F
F)0
RY(n
to
F)F
RY(n
Used by CC-Link/LT remote
Use prohibited
Used by CC-Link/LT remote
Use prohibited
7A, RXn 7B" and "RXn FA, RXn FB".
3 - 8 3 - 8
A
3 SPECIFICATIONS
3.5.4 Details of remote I/O signals
This section explains the assignment and functions of the CC/Link remote
inputs/outputs.
(1) Remote I/O signal list for 4-point mode setting
CC-Link
RXnF to RXn0 Station number 4 Station number 3 Station number 2 Station number 1
RX(n 2)F to RX(n 2)0 Station number 12 Station number 11 Station number 10 Station number 9
RX(n 3)F to RX(n 3)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 4 Station number 3 Station number 2 Station number 1
RY(n 2)F to RY(n 2)0 Station number 12 Station number 11 Station number 10 Station number 9
RY(n 3)F to RY(n 3)0 Use prohibited
CC-Link
RXnF to RXn0 Station number 4 Station number 3 Station number 2 Station number 1
RX(n 6)F to RX(n 6)0 Station number 28 Station number 27 Station number 26 Station number 25
RX(n 7)F to RX(n 7)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 4 Station number 3 Station number 2 Station number 1
RY(n 6)F to RY(n 6)0 Station number 28 Station number 27 Station number 26 Station number 25
RY(n 7)F to RY(n 7)0 Use prohibited
(a) The following table lists the I/O signals for 2 occupied station setting
F E D C B A 9 8 7 6 5 4 3 2 1 0
to to
F E D C B A 9 8 7 6 5 4 3 2 1 0
to to
(b) The following table lists the I/O signals for 4 occupied station setting
F E D C B A 9 8 7 6 5 4 3 2 1 0
to to
F E D C B A 9 8 7 6 5 4 3 2 1 0
to to
MELSEC-
Remote input (X) of CC-Link/LT Remote input (RX) of
Remote output (Y) of CC-Link/LT Remote output (RY) of
Remote input (X) of CC-Link/LT Remote input (RX) of
Remote output (Y) of CC-Link/LT Remote output (RY) of
3 - 9 3 - 9
A
3 SPECIFICATIONS
CC-Link
RXnF to RXn0 Station number 4 Station number 3 Station number 2 Station number 1
to to
RX(n 6)F to RX(n 6)0 Station number 28 Station number 27 Station number 26 Station number 25
RX(n 7)F to RX(n 7)0 Use prohibited
RX(n 8)F to RX(n 8)0 Station number 32 Station number 31 Station number 30 Station number 29
to to
RX(n E)F to RX(n E)0 Station number 56 Station number 55 Station number 54 Station number 53
RX(n F)F to RX(n F)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 4 Station number 3 Station number 2 Station number 1
to to
RY(n 6)F to RY(n 6)0 Station number 28 Station number 27 Station number 26 Station number 25
RY(n 7)F to RY(n 7)0 Use prohibited
RY(n 8)F to RY(n 8)0 Station number 32 Station number 31 Station number 30 Station number 29
to to
RY(n E)F to RY(n E)0 Station number 56 Station number 55 Station number 54 Station number 53
RY(n F)F to RY(n F)0 Use prohibited
MELSEC-
(c) The following table lists the I/O signals for 8 occupied station (4 occupied
stations
2 modules) setting
Remote input (X) of CC-Link/LT Remote input (RX) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
Remote output (Y) of CC-Link/LT Remote output (RY) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
3 - 10 3 - 10
A
3 SPECIFICATIONS
(2) Remote I/O signal list for 8-point mode setting
CC-Link
RXnF to RXn0 Station number 2 Station number 1
to to
RX(n 2)F to RX(n 2)0 Station number 6 Station number 5
RX(n 3)F to RX(n 3)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 2 Station number 1
to to
RY(n 2)F to RY(n 2)0 Station number 6 Station number 5
RY(n 3)F to RY(n 3)0 Use prohibited
CC-Link
RXnF to RXn0 Station number 2 Station number 1
to to
RX(n 6)F to RX(n 6)0 Station number 14 Station number 13
RX(n 7)F to RX(n 7)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 2 Station number 1
to to
RY(n 6)F to RY(n 6)0 Station number 14 Station number 13
RY(n 7)F to RY(n 7)0 Use prohibited
MELSEC-
(a) The following table lists the I/O signals for 2 occupied station setting
Remote input (X) of CC-Link/LT Remote input (RX) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
Remote output (Y) of CC-Link/LT Remote output (RY) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
(b) The following table lists the I/O signals for 4 occupied station setting
Remote input (X) of CC-Link/LT Remote input (RX) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
Remote output (Y) of CC-Link/LT Remote output (RY) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
3 - 11 3 - 11
A
3 SPECIFICATIONS
CC-Link
RXnF to RXn0 Station number 2 Station number 1
to to
RX(n 6)F to RX(n 6)0 Station number 14 Station number 13
RX(n 7)F to RX(n 7)0 Use prohibited
RX(n 8)F to RX(n 8)0 Station number 16 Station number 15
to to
RX(n E)F to RX(n E)0 Station number 28 Station number 27
RX(n F)F to RX(n F)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 2 Station number 1
to to
RY(n 6)F to RY(n 6)0 Station number 14 Station number 13
RY(n 7)F to RY(n 7)0 Use prohibited
RY(n 8)F to RY(n 8)0 Station number 16 Station number 15
to to
RY(n E)F to RY(n E)0 Station number 28 Station number 27
RY(n F)F to RY(n F)0 Use prohibited
MELSEC-
(c) The following table lists the I/O signals for 8 occupied station (4 occupied
stations
F E D C B A 9 8 7 6 5 4 3 2 1 0
F E D C B A 9 8 7 6 5 4 3 2 1 0
2 modules) setting
Remote input (X) of CC-Link/LT Remote input (RX) of
Remote output (Y) of CC-Link/LT Remote output (RY) of
3 - 12 3 - 12
A
3 SPECIFICATIONS
(3) Remote I/O signal list for 16-point mode setting
CC-Link
RXnF to RXn0 Station number 1
to to
RX(n 2)F to RX(n 2)0 Station number 3
RX(n 3)F to RX(n 3)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 1
to to
RY(n 2)F to RY(n 2)0 Station number 3
RY(n 3)F to RY(n 3)0 Use prohibited
CC-Link
RXnF to RXn0 Station number 1
to to
RX(n 6)F to RX(n 6)0 Station number 7
RX(n 7)F to RX(n 7)0 Use prohibited
CC-Link
RYnF to RYn0 Station number 1
to to
RY(n 6)F to RY(n 6)0 Station number 7
RY(n 7)F to RY(n 7)0 Use prohibited
MELSEC-
(a) The following table lists the I/O signals for 2 occupied station setting
Remote input (X) of CC-Link/LT Remote input (RX) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
Remote output (Y) of CC-Link/LT Remote output (RY) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
(b) The following table lists the I/O signals for 4 occupied station setting
Remote input (X) of CC-Link/LT Remote input (RX) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
Remote output (Y) of CC-Link/LT Remote output (RY) of
F E D C B A 9 8 7 6 5 4 3 2 1 0
3 - 13 3 - 13
A
3 SPECIFICATIONS
(c) The following table lists the I/O signals for 8 occupied station (4 occupied
CC-Link
RXnFRXn0
to to
RX(n6)FRX(n6)0
RX(n7)FRX(n7)0
RX(n8)FRX(n8)0
to to
RX(nE)FRX(nE)0
RX(nF)FRX(nF)0
CC-Link
RYnFRYn0
to to
RY(n6)FRY(n6)0
RY(n7)FRY(n7)0
RY(n8)FRY(n8)0
to to
RY(nE)FRY(nE)0
RY(nF)FRY(nF)0
stations
F E D C B A 9 8 7 6 5 4 3 2 1 0
F E D C B A 9 8 7 6 5 4 3 2 1 0
2 modules) setting
Remote input (X) of CC-Link/LT Remote input (RX) of
Station number 1
Station number 7
Use prohibited
Station number 8
Station number 14
Use prohibited
Remote input (Y) of CC-Link/LT Remote input (RY) of
Station number 1
Station number 7
Use prohibited
Station number 8
Station number 14
Use prohibited
Device No. Signal Name Description
RX(n 3)A 1 Error status flag
RX(n 3)B 2 Remote READY
(4) Functions of remote I/O signals
Turns on when a remote I/O error occurs on CC-Link/LT side or when all
stations or remote stations become faulty. Automatically turns off upon
recovery from the error.
Turns on during normal operation.
Turns off in the CC-Link/LT side self-loopback test mode or when a switch
error occurs on a CC-Link/LT side.
1: When 4 stations are occupied RX(n 7)A
When 8 stations are occupied RX(n 7)A, RX(n F)A
2: When 4 stations are occupied RX(n 7)B
When 8 stations are occupied RX(n
7)B, RX(n F)B
MELSEC-
3 - 14 3 - 14
A
3 SPECIFICATIONS
MELSEC-
3.6 Concept of the Number of Control Points (Point Mode Setting for CC-Link/LT and
Number of Occupied Stations Setting for CC-Link)
This section explains the concept of the settings required for system configuration, i.e.,
point mode setting and number of occupied stations setting.
The point mode setting sets the number of points that can be controlled for each
occupied remote station in the CC-Link/LT.
The point mode has three different modes: 4-point mode, 8-point mode, and 16-point
mode. If the number of occupied stations is the same, the number of remote stations that
can be controlled in the CC-Link/LT changes depending on the setting of the point mode.
Note that, when connecting a remote device station to the CC-Link/LT system, set the
16-point mode in the point mode setting for the CC-Link/LT.
3.6.1 Setting number of occupied stations
This section explains a simple setting method of the point mode setting and number of
occupied stations setting.
As the point mode, use the 4-point mode. According to the number of I/O points of the
Number of Remote
Station I/O Points
48 points or less 2 stations
49 to 112 points 4 stations
113 to 224 points
remote station, refer to the following table and set the number of occupied stations.
POINT
Number of Occupied Stations Setting
of AJ65SBT-CLB
8 stations
(4 occupied stations
2 modules)
Point Mode Setting of
AJ65SBT-CLB
4-point mode
Since the default setting is the 8-point mode, change it to the 4-point mode.
3.6.2 Setting point mode
This section explains the point mode setting and the application method for number of
occupied stations setting.
(1) If the number of occupied stations is set the same, the number of controllable remote
stations changes depending on the point mode setting, as the following table shows.
2 Occupied
Stations
4 Occupied
Stations
(4 occupied stations 2 modules)
8 Occupied Stations
(2) If the remote module is the same, the number of occupied stations changes due
to the point mode.
For example, if a 16-point module is used, the occupied station number changes
from 4 occupied stations to 2 occupied stations to 1 occupied station when the point
mode changes from the 4-point mode to the 8-point mode to the 16-point mode.
A
3 SPECIFICATIONS
(3) As the point mode, it is recommended to use the 4-point mode that has the least
Master
station
Station 1
2 stations
occupied
MELSEC-
number of empty points.
Example: In the case of one 2-point remote station, five 4-point remote stations,
one 8-point remote station and one 16-point remote station
Station 2
1 station
occupied
Station 3
1 station
occupied
CC-Link side
CC-Link/LT side
4-point mode
(4 points/station)
Number of occupied
stations: 2 stations
(maximum 48 points)
Total number of
stations: 12 stations
X/Y0
1) 4 points
2) 8 points
3) 4 points
X/Y10
4) 2 points
Empty, 2 points
5)16 points
X/Y20
X/Y23
6) 4 points
7) 4 points
8) 4 points
Use
prohibited
16 points
AJ65SBT-CLB
Station 1
4 input
points
Station 2
8 input
points
Station 3
4 output
points
CL1X4-D1B2 CL2X8-D1B2CL1Y4-T1B2
Station 4
2 output
points
CL1Y2-T1D2SCL1XY8-DT1B2CL1Y4-T1B2
8-point mode
(8 points/station)
Number of occupied
stations: 4 stations
(maximum 112 points)
Total number of
stations: 9 stations
1 station
X/Y0
2 station
1 station
X/Y10
1 station
4 station
X/Y20
1 station
1 station
1 station
X/Y30
1) 4 points
Empty, 4 points
2) 8 points
3) 4 points
Empty, 4 points
4) 2 points
Empty, 6 points
5)
16 points
6) 4 points
Empty, 4 points
7) 4 points
Empty, 4 points
8) 4 points
Empty, 4 points
1 station
1 station
1 station
1 station
2 station
1 station
1 station
1 station
16-point mode
(16 points/station)
Number of occupied
stations: 4 stations
(maximum 112 points)
Total number of
stations: 8 stations
X/Y0
1) 4 points
Empty,12points
X/Y10
2) 8 points
Empty, 8 points
X/Y20
3) 4 points
Empty,12points
X/Y30
4) 2 points
Empty,14points
X/Y40
5)
16 points
Station 6
4 input/output
1 station
1 station
1 station
1 station
1 station
Station 5
16 input
points
CL2X16-D1M1VCL1Y4-T1B2
Station 8
4 output
points
points
16-point mode (4 points/station)
Number of occupied stations: 8 stations
(4 occupied stations 2 stations)
(maximum 224 points)
Total number of stations: 8 stations
X/Y0
X/Y10
1) 4 points
Empty,12points
X/Y80
1 station
X/Y90
1) 4 points
Empty,12points
2) 8 points
1 station
Empty, 8 points
X/Y20
3) 4 points
1 station
1 station
Empty,96points
1 station
X/Y30
X/Y40
Empty,12points
4) 2 points
Empty,14points
5)
16 points
Station 7
4 output
points
1 station
X/Y50
X/Y60
X/Y70
6) 4 points
Empty,12points
7) 4 points
Empty,12points
Use
prohibited
16 points
First module
1 station
1 station
Use
prohibited
16 points
Second module
Empty,48points
Use
prohibited
16 points
X/Y50
X/Y60
X/Y70
6) 4 points
Empty,12points
7) 4 points
Empty,12points
8) 4 points
Empty,12points
1 station
1 station
1station
When 4 occupied stations and 16-point mode are selected in
the above system, Station 8 cannot be set. (When the 16-point
mode has been set for 4 occupied stations, only up to 7 stations can be set.)
Set 8 occupied stations (4 occupied stations 2 modules) as shown above,
or change the point mode setting to the 4-point mode or 8-point mode.
3 - 16 3 - 16
A
3 SPECIFICATIONS
(4) The assignment of the I/O numbers is explained below using the assignment
Station
No.
Model NameInputOutput
(2 stations occupied)
MELSEC-
sheet in the Appendices. It is an example where the number of occupied stations
is 2 and the point mode setting is the 4-point mode as shown in the configuration
of the Section (3).
Station
No.
Model NameInputOutput
(4 stations occupied)
3 - 17 3 - 17
A
3 SPECIFICATIONS
3.7 Remote Registers
The AJ65SBT-CLB has the remote registers to make data communication with the
master module.
This section explains the assignment and data structure of the remote registers of the
AJ65SBT-CLB.
3.7.1 Assignment of remote registers
MELSEC-
The following tables indicate the assignment of the remote registers.
(1) RWw
Address Remote Register Definition Initial value Reference
RWwn Last station number setting 0 Sec. 3.7.2
RWwn 1 Data link stop/restart instructions 0 Sec. 3.7.3
RWwn 2 Error status flag clear 0 Sec. 3.7.4
RWwn 3
to
RWwn
F
n: Address assigned to the master station in station number setting.
Use prohibited
(2) RWr
(a) When 2 stations are occupied
Address Remote Register Definition Reference
RWrn Data of operating statuses Sec. 3.7.5
RWrn 1 Data of faulty station : Station number 1 to 12 Sec. 3.7.6
RWrn 2 Remote I/O error data :Station number 1 to 12 Sec. 3.7.7
RWrn 3 Data of remote station connection Sec. 3.7.8
RWrn 4 Setting data Sec. 3.7.9
RWrn 5
to
RWrn
7
n: Address assigned to the master station in station number setting.
Use prohibited
(b) When 4 stations are occupied
Address Remote Register Definition Reference
RWrn Data of operating states Sec. 3.7.5
RWrn 1
RWrn 2
RWrn 3
RWrn 4
RWrn 5
RWrn 6
RWrn 7 Setting data Sec. 3.7.9
RWrn 8
to
RWrn
F
Data of faulty station : Station number 1 to 28 Sec. 3.7.6
Remote I/O error data :Station number 1 to 28 Sec. 3.7.7
Data of remote station connection Sec. 3.7.8
Use prohibited
n: Address assigned to the master station in station number setting.
3 - 18 3 - 18
A
3 SPECIFICATIONS
MELSEC-
(c) When 8 stations (4 occupied stations 2 modules) are
occupied
First module
Address Remote Register Definition Reference
RWrn Data of operating statuses Sec. 3.7.5
RWrn 1
RWrn 2
RWrn 3
4
RWrn
RWrn 5
RWrn 6
RWrn 7 Setting data Sec. 3.7.9
RWrn 8
to
F
RWrn
Second module
Address Remote Register Definition Reference
RWr(n 1) Data of operating states Sec. 3.7.5
RWr(n 1) 1
RWr(n 1) 2
RWr(n 1) 3
RWr(n 1) 4
RWr(n 1) 5
RWr(n 1) 6
RWr(n 1) 7 Setting data Sec. 3.7.9
RWr(n 1) 8
to
RWr(n
POINT
1) F
The prohibited remote register areas are used by the system and therefore cannot
be used by the user.
If data is written to the buffer memory area corresponding to the prohibited remote
register area or to the device specified for auto refresh, the functions of the
AJ65SBT-CLB cannot be guaranteed.
Data of faulty station : Station number 1 to 32 Sec. 3.7.6
Remote I/O error data : Station number 1 to 32 Sec. 3.7.7
Data of remote station connection Sec. 3.7.8
Use prohibited
Data of faulty station : Station number 33 to 56 Sec. 3.7.6
Remote I/O error data : Station number 33 to 56 Sec. 3.7.7
Data of remote station connection Sec. 3.7.8
Use prohibited
n: Address assigned to the master station in station number setting.
3 - 19 3 - 19
A
3 SPECIFICATIONS
MELSEC-
3.7.2 Last station number setting (common to 2, 4 and 8 occupied stations (4 occupied
stations 2 modules): Address RWwn)
The setting status of the last station number is stored.
Bit Name Description Initial value
b0 to b7 Empty Fixed at 0
Set the last station number for a data link.
This eliminates the processing of data link
to the non-connected stations, reducing the
link refresh time.
If the value is set beyond the number of
connectable stations (refer to Section
b8 to b13
b14, b15 Empty Fixed at 0
Last station number
setting
3.6.2), the setting will be ignored.
<Setting range>
2 occupied stations: Station 1 to 12
4 occupied stations: Station 1 to 28
8 occupied stations (4 occupied stations
If the value of 0 or more than 56 is set, a
data link is performed with the number of
stations within the setting range.
2 modules): Station 1 to 56
0
3.7.3 Data link stop/restart instructions (common to 2, 4 and 8 occupied stations (4 occupied
stations 2 modules): Address RWwn+1)
Data link stop and restart are controlled. When a data link stop and a data link restart
are requested simultaneously, the data link stop has higher priority.
Bit Name Description Initial value
b0 Data link stop
b1 to b14 Empty Fixed at 0
b15 Data link restart
0 : Data link stop not requested
1 : Data link stop requested
0 : Data link restart not requested
1 : Data link restart requested
0
0
3.7.4 Error status flag clear (common to 2, 4 and 8 occupied stations (4 occupied stations
2 modules): Address RWwn+2)
Error of station outside control range is cleared.
Bit Name Description Initial value
b0 to b2 Empty Fixed at 0
Error of station
b3
b4 to b15 Empty Fixed at 0
outside control range
clear
0 : Clear not requested
1 : Clear requested
0
3 - 20 3 - 20
A
3 SPECIFICATIONS
MELSEC-
3.7.5 Data of operating statuses (common to 2, 4 and 8 occupied stations (4 occupied
stations 2 modules): Address RWrn)
Bit Name Description
b0 Data link status
b1 Initial communication status
b2 to b7 Empty Fixed at 0
b8 Data link failure
b9 All stations failed
b10 Remote I/O error
b11 Error of station outside control range
b12 Point mode setting error
b13 Transmission speed setting error
b14 Switching during operation
b15 Hardware failure
The CC-Link/LT side operating status is stored.
0: Data link stopped
1: Data link being executed
0: Initial communication not completed
1: Initial communication completed
0: Data link normal
1: One or more faulty station in data link identified
0: One or more normal data link station identified
1: All stations are faulty
0: No remote I/O error
1: One or more faulty remote I/O station
0: No error
1: Remote station(s) set to the station number higher than the last
of refresh range
0: Normal
1: Point mode switch set outside valid range
0: Normal
1: Transmission rate setting switch set outside valid range
0: No switching
1: Switching identified
0: Normal
1: Failure identified by self-loopback test
3 - 21 3 - 21
A
3 SPECIFICATIONS
MELSEC-
3.7.6 Data of faulty station (2 occupied stations: Address RWrn 1, common to 4 and 8
(first module: 1 to 32 stations, second module: 33 to 56 stations)
Station
Station
Station
Station
Station 9 Station 8 Station 7 Station 6 Station 5 Station 4 Station 3 Station 2 Station
14
13
12
11
10
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
30
29
28
27
26
25
24
23
22
21
20
19
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
46
45
44
43
42
41
40
39
38
37
36
35
Station
Station
Station
Station
Station
Station
56
55
54
53
52
51
0: Normal
1: Data link error
Station
18
Station
34
Station
50
1
Station
17
Station
33
Station
49
3 - 22 3 - 22
A
3 SPECIFICATIONS
MELSEC-
3.7.7 Remote I/O error data (2 occupied stations: Address RWrn 2, common to 4 and 8
occupied stations (4 occupied stations 2 modules): Address RWrn 3, RWrn 4)
The remote I/O error occurrence statuses of the CC-Link/LT remote stations during
data link are stored.
For the error definition, refer to the manual of the corresponding CC-Link/LT remote
station.
• When 2 stations are occupied, the remote I/O errors of CC-Link/LT are stored into
RWrn
• When 4 or 8 stations (4 occupied stations
I/O errors of CC-Link/LT are stored into RWrn
3.7.8 Data of remote station connection (2 occupied stations: Address RWrn 3, common to
4 and 8 occupied stations (4 occupied stations 2 modules): Address RWrn 5,
RWrn 6)
The CC-Link/LT remote stations connected on the line are detected, and the
connection statuses of the remote stations are stored.
Note that if any remote station is disconnected from the system, the corresponding bit
does not turn off (turn to 0) after the connections of the CC-Link/LT remote stations
have been detected.
• When 2 stations are occupied, the data of remote station connection of CC-Link/LT
is stored into RWrn
• When 4 or 8 stations (4 occupied stations
3.
2 modules) are occupied, the data of
remote station connection of CC-Link/LT is stored into RWrn 5, RWrn 6.
(first module: 1 to 32 stations, second module: 33 to 56 stations)
Station
Station
Station
Station
Station 9 Station 8 Station 7 Station 6 Station 5 Station 4 Station 3 Station 2 Station
14
13
12
11
10
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
30
29
28
27
26
25
24
23
22
21
20
19
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
Station
46
45
44
43
42
41
40
39
38
37
36
35
Station
Station
Station
Station
Station
Station
56
55
54
53
52
51
0: Remote station not connected
1: Remote station connected
Station
18
Station
34
Station
50
1
Station
17
Station
33
Station
49
3 - 24 3 - 24
A
3 SPECIFICATIONS
MELSEC-
3.7.9 Setting data (2 occupied stations: Address RWrn+4, common to 4 and 8 occupied
stations (4 occupied stations 2 modules): Address RWrn 7)
The setting statuses of the switches for occupied station number setting, transmission
speed setting, point mode setting, test mode and data link last station number are
stored.
• When 2 stations are occupied, the setting data of CC-Link/LT are stored into
RWrn+4.
• When 4 or 8 stations (4 occupied stations
data of CC-Link/LT are stored into RWrn
Bit Name Description
Setting statuses of the CC-Link side switches SW1, SW2
b0 to b1
b2 to b3
b4 to b5 Point mode setting
b6 Test mode
b7 Not used
b8 to b13
b14 to b15 Not used
Number of occupied
stations
Transmission speed
setting
Data link last station
number
for operation setting
00: 2 occupied stations 01: 4 occupied stations,
10: 8 occupied stations (4 occupied stations
11: Setting prohibited
Setting statuses of the CC-Link side switches SW8, SW9,
SW10 for operation setting
00: 156kbps 01: 625kbps
10: 2.5Mbps 11: Setting prohibited
Setting statuses of the CC-Link side switches SW4, SW5
for operation setting
00: 8-point mode 01: 4-point mode,
10: 16-point mode 11: Setting prohibited
Setting status of the CC-Link side switch SW3 for operation
setting
0: Under usual conditions
1: At self-loopback test execution time
The last station number of the remote station that can
perform a data link is stored.
0: Switch OFF
1: Switch ON
POINT
• The values of this remote register change depending on the occupied station
number setting, point mode setting and last station number setting.
• If any CC-Link/LT remote station connected has a station number setting greater
than the value of the data link last station number, an error of station outside
control range occurs.
2 modules) are occupied, the setting
7.
2 modules)
3 - 25 3 - 25
A
3 SPECIFICATIONS
3.8 Data Link Processing Time
The CC-Link side data link and CC-Link/LT side data link operate asynchronously.
3.8.1 CC-Link link scan time
Refer to the user's manual of the master module.
3.8.2 CC-Link/LT link scan time
This section explains the CC-Link/LT link scan time.
[Link scan time (LS)]
LS = a + (b
a: Constant
b: Constant
c: Constant
N: Last station number
Transmission speed 2.5 Mbps 625 kbps 156 kbps
a 22 88 353
4-point mode 46 41 37
b
8-point mode 56 51 47
16-point mode 76 71 67
c 0.4 1.6 6.4
(2.5Mbps when 8 stations (4 occupied stations 2 modules) are occupied)
N) c [ s]
Link scan time
MELSEC-
2.5
2.0
(ms)Link scan time
1.5
1.0
0.5
0
0
16-point mode
8-point mode
4-point mode
142856
Number of
stations
3 - 26 3 - 26
A
3 SPECIFICATIONS
3.9 Transmission Delay Time
Transmission delay time is indicated below.
• For input
Indicates the time from when a signal is input to the remote station until the device
(X) of the CPU turns on (off).
• For output
Indicates the time from when the device (Y) of the CPU turns on (on) until the output
of the remote station turns on (off).
The transmission delay time can be calculated by the following expression.
Transmission delay time
transmission delay time"
(1) CC-Link side transmission delay time
This is the time taken until a signal is transmitted between the master station and
remote I/O station, which is indicated in the user's manual of the master module.
Note that the response time of the remote I/O station should be ignored.
(2) CC-Link/LT side transmission delay time
(a) AJ65SBT-CLB remote station (input)
(b) AJ65SBT-CLB remote station (output)
(Example) When the CC-Link master station sequence program scan time is
MELSEC-
"CC-Link side transmission delay time" "CC-Link/LT side
[Calculation expression]
remote station input response time [ms]
LS
LS : Link scan time (refer to Section 3.8)
[Calculation expression]
2 remote station input response time [ms]
LS
LS : Link scan time (refer to Section 3.8)
10ms, the CC-Link link scan time is 2.5ms, the CC-Link/LT remote I/O
station input response time is 1.5ms, the CC-Link/LT transmission
speed is 2.5Mbps, the number of stations is 28, and the point mode
setting is the 4-point mode
1) For input
CC-Link side : 10
CC-Link/LT side : 22
0.54 15.54 [ms]
15
2) For output
CC-Link side : 10
CC-Link/LT side : (22
17.5
1.08 18.58 [ms]
2.5 2 15 [ms]
(46 28)
2.5 3 17.5 [ms]
(46 28) 0.4) 2 1.08 [ms]
0.4
0.54 [ms]
3 - 27 3 - 27
A
3 SPECIFICATIONS
MEMO
MELSEC-
3 - 28 3 - 28
A
4 PROCEDURE UP TO DATA LINK
4 PROCEDURE UP TO DATA LINK
MELSEC-
4.1 Procedure Up to Data Link
This chapter provides the procedure from AJ65SBT-CLB mounting to data link start.
The following flowchart indicates the procedure to start the data link of the system
using the AJ65SBT-CLB.
Mount the AJ65SBT-CLB to the control panel or device.
4
Start
Set the switches, etc. of the AJ65SBT-CLB.
(1) CC-Link side
Station number
Transmission speed
Number of occupied stations
(2) CC-Link/LT side
Point mode setting
Transmission speed
Self-loopback test setting
Connect the modules on the CC-Link/LT side with
dedicated flat cables. Connect terminating resistors
to the ends of the trunk line.
Refer to Section 4.2
Refer to Section 4.3
Connect the dedicated power supply or power
supply adaptor of CC-Link/LT.
Check prior to power-on
Confirm the power supply voltage (24V DC) to be
input to the power supply adaptor.
Check that the RUN/STOP switch of the PLC CPU
is in the "STOP" position.
Check for overlapping remote station numbers.
Power on CC-Link/LT.
Confirm that the PW LED of the AJ65SBT-CLB turns on.
To the next page
4 - 1 4 - 1
A
4 PROCEDURE UP TO DATA LINK
MELSEC-
Continued from the previous page
Power on the CC-Link side.
Start a data link on the CC-Link side.
Make operation checks with the LEDs.
(1) Check the CC-Link side operation.
When data link is normal: L RUN turns on.
When data link is abnormal: L ERR. turns on.
(2) CC-Link/LT side operation check
When data link is normal: L RUN turns on.
When data link is abnormal: L ERR. turns on.
When switch setting is outside range: ERR
turns on.
Confirm the connection status of each module.
Check the remote station connection data.
Perform CC-Link / CC-Link/LT diagnostics to
make operation check.
4
Programming
End
POINT
(1) If the station number of a CC-Link/LT remote station is duplicated, the station
may malfunction (false input/output).
(2) Depending on the combination of the point mode setting and the number of I/O
points for the CC-Link/LT remote station used, multiple station numbers may be
assigned.
Carefully check if the station number of the remote station of 8 or more I/O
points is not duplicated with the number of the next station.
(3) When any of the operation setting switches of the AJ65SBT-CLB or the
CC-Link/LT remote station has been changed with the system power ON, be
sure to turn OFF and then ON the power of the entire CC-Link/LT system.
4 - 2 4 - 2
A
4 PROCEDURE UP TO DATA LINK
4.2 Mounting and Installation
4.2.1 Handling precautions
This section explains the precautions for handling the AJ65SBT-CLB.
Do not touch the terminals while the module is energized. Doing so may cause
!
CAUTION
malfunctions.
Be careful not to let foreign matter such as dust or wire chips get inside the module.
This may cause a fire, failure or malfunctions.
Do not disassemble or modify the module.
Doing so may cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the module directly.
Doing so may cause a malfunction or failure of the module.
Since the case of the module is made of resin, do not drop it or give it a shock.
Doing so may damage the module.
Tighten the terminal screws within the specified torque range.
Loose tightening may cause a short circuit or malfunction.
Overtightening may cause a short circuit or malfunction due to damage to the screws
or module.
When disposing of this product, handle it as industrial waste.
Use the module in the environment specified in this manual.
Failure to do so may cause an electric shock, fire, malfunction, or damage to or
deterioration of the product.
Securely fix the module with DIN rails or mounting screws, and securely tighten it
within the specified torque range of the mounting screws.
Loose tightening may cause a drop or malfunction.
Overtightening may cause a drop or malfunction due to damage to the screws or
module.
Be sure to shut off all phases of the external power supply used by the system
before mounting or dismounting the product to or from the panel. Failure to do so
may cause a failure or malfunctions of the module.
Before handling the module, always touch grounded metal, etc. to discharge static
electricity from the human body.
Failure to do so can cause the module to fail or malfunction.
(1) Tighten the module mounting screws within the following ranges.
Screw Location Tightening Torque Range
Module mounting screw (M4 screw) 78 to 108N cm
FG terminal block terminal screw (M3 screw) 42 to 58N cm
(2) A protective film is attached on the module’s surface for the purpose of scratch
prevention during transportation.
Prior to use, be sure to remove it.
(3) Mount a DIN rail while paying full attention to the following points.
(a) Applicable DIN rail model name (compliant to IEC 60715)
TH35-7.5Fe
TH35-7.5A1
(b) DIN rail mounting screw interval
The pitch of 200mm or less should be ensured for screwing.
(4) When mounting the AJ65SBT-CLB to a DIN rail, push the centerline of the DIN
rail hook at the module bottom with your finger until it clicks.
MELSEC-
4 - 3 4 - 3
A
4 PROCEDURE UP TO DATA LINK
4.3 Part Names and Settings
This section explains the part names, LED displays, and setting methods of switch, etc
for the AJ65SBT-CLB.
1)
Diagram 1
MELSEC-
A
J65SBT-CLB
(FG)
6)
CC-Link/LTCC-LinkCC-LinkCC-Link/LT
ERR.LERR.RUNLLRUNERR.PW L
3)
STATION NO.
ON
5)
BRATE
456789 1245267123103
TST
MODE
CC-Link/LTCC-Link
4)
Number Name Description
Shows the module status as the LED on/off.
LED name Description
CC-Link side CC-Link/LT side
PW
1) LED display
On: Module normal
Off: Module fault or not supplied with power
On: Data link communication normal
Off: Data link communication off (time-
L RUN
out)
NC
BRATENOS
112121241248102040
8
2)
<During normal operation>
On: Data link being executed
Off: Data link stopped
<In self-loopback test mode>
On: Self-loopback test completed.
Off: Self-loopback test failed
4 - 4 4 - 4
A
4 PROCEDURE UP TO DATA LINK
Number Name Description
Shows the module status as the LED on/off.
LED name Description
On: CC-Link side switch setting error
Data link communication fault error
Flicker: CC-Link side switch setting is
changed during operation.
L ERR.
1) LED display
ERR.
Off: No error
MELSEC-
<During normal operation>
On: Data link error station (detected)
Station outside control range
detected
Flicker: Data link error stations (all
stations)
Off: No error
<In self-loopback test mode>
On: Self-loopback test failed
Off: Self-loopback test completed
Setting error detection
On: CC-Link/LT side switch setting
error
Flicker: CC-Link/LT side switch
setting is changed during
operation.
Off: No error
4 - 5 4 - 5
A
4 PROCEDURE UP TO DATA LINK
MELSEC-
Diagram 1
CC-Link
STATION NO.
NOSBRATE
CC-Link/LT
TST
MODE
BRATE
NC
112121241248102040
4567891245267123103
ON
12345678910
1234 678
5
8
: The case silkscreen No. corresponds
to switch silkscreen No.
Switch silkscreen No.
Case silkscreen No.
Number Name Description
Use the switches in STATION NO. "10", "20" and "40" to set the tens of the station number.
Use the switches in STATION NO. "1", "2", "4" and "8" to set the units of the station number.
Tens Units
Station
Number
Station number
setting switches
(CC-Link side)
STATION NO.
2)
Transmission
speed setting
switches
(CC-Link side)
B RATE
Number of
occupied stations
setting switches
(CC-Link side)
NOS: Numbers of
Occupied stations
1 OFF OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF OFF ON ON
10 OFF OFF ON OFF OFF OFF OFF
11 OFF OFF ON OFF OFF OFF ON
63 ON ON OFF OFF OFF ON ON
The factory settings are all OFF.
The station number can be set within the range 1 to 63 when two stations are occupied, 1 to
61 when four stations are occupied, or 1 to 57 when eight stations (four occupied stations
two modules) are occupied.
Setting a value other than the above will result in a setting error. (The "L ERR." LED on the
CC-Link side is lit.)
Setting Switches
0
1 OFF OFF ON 625 kbps
2 OFF ON OFF 2.5 Mbps
3 OFF ON ON 5.0 Mbps
4 ON OFF OFF 10 Mbps
Setting a value other than the above will result in a setting error. (The "L ERR." LED on the
CC-Link side is lit.)
Setting Switches
0
1 OFF ON 4 stations
Setting a value other than the above will result in a setting error. (The "L ERR." LED on the
CC-Link side is lit.)
Setting
Value
(factory-set)
Setting
Value
(factory-set)
2 ON OFF
40 20 10 8 4 2 1
4 2 1
OFF OFF OFF 156 kbps
2 1
OFF OFF 2 stations
Transmission Speed
Number of occupied stations
8 stations
(four occupied stations two
modules)
4 - 6 4 - 6
A
4 PROCEDURE UP TO DATA LINK
MELSEC-
Number Name Description
Self-loopback test
setting switch
(CC-Link/LT side)
TST
Point mode setting
switches (CC-Link/LT
side)
MODE
2)
Transmission speed
setting switches
(CC-Link/LT side)
B RATE
One-touch connector
3)
for communication
CC-Link/LT Interface
4)
connector
5) DIN rail hook Used to mount the module to the DIN rail.
6) FG terminal Ground terminal
OFF: Normal operation mode (factory-set)
ON: Self-loopback test mode
Setting Switches
0
1 OFF ON 4 points
2 ON OFF 16 points
Setting a value other than the above will result in a setting error. (The "L ERR." LED on the
CC-Link/LT side is lit.)
Setting Switches
0
1 OFF ON 625 kbps
2 ON OFF 2.5 Mbps
Setting a value other than the above will result in a setting error. (The "L ERR." LED on the
CC-Link/LT side is lit.)
A one-touch connector for communication line connection.
Connect two optional one-touch connector plugs for communication to the two connector.
Connector for CC-Link/LT communication line connection.
Setting
Value
(factory-set)
Setting
Value
(factory-set)
2 1
Points
OFF OFF 8 points
Transmission Speed
2 1
OFF OFF 156 kbps
4.4 Facing Direction of the Module Installation
The AJ65SBT-CLB can be mounted in any of six orientations with a DIN rail or module
When installing to the side of the board
mounting screws. (There are no restrictions on the mounting orientations.)
When installing
on top of the board
When installing
at the bottom of the board
4 - 7 4 - 7
A
4 PROCEDURE UP TO DATA LINK
4.5 Connecting Modules by CC-Link/LT Side Cables
This section explains the connection method using the cables designed for CCLink/LT:
(1) The cables can be connected regardless of the order of the station number.
(2) Be sure to set the QJ61CL12 at the end of the trunk line. The terminating
resistor close to the QJ61CL12 should be connected within 20 cm from the
QJ61CL12.
(3) Connect terminating resistors to the both ends of the trunk line of CC-Link/LT.
POINT
Calculate the number of required connectors referring to the following example.
Example) When using a dedicated flat cable as a trunk line and VCTF cables as
AJ65SBT
-CLB
drop lines
MELSEC-
1)
2)3)
Power supply
adapter
General
power supply
(24V DC)
6)7)
Remote
module
8)
9)
4)
5)
2
Remote
module
Trunk line (Dedicated flat cable)
Drop line (Dedicated flat cable)
Drop lin e (VCTF c able)
10)11)
3
4
(1)
(2)
Remote
module
5
Remote
module
6
Remote
module
VCTF cable connector
Dedicated flat cable connector
Terminating resistor (CL9-TERM)
12)
13) 14) 15)
16)
Remote
module
Remote
module
Module
with cable
17)
71
8
18)
20cm or less
Remote
module
Commercially
available terminal
19)
The number of required connectors can be obtained as follows:
1) Dedicated flat cable connectors (No. of ): 19
2) VCTF cable connectors (No. of
): 8
3) Terminal blocks (No. of ): 2
4) Terminating resistors (No. of
): 2
4 - 8 4 - 8
A
4 PROCEDURE UP TO DATA LINK
4.5.1 How to connect dedicated flat cable connector
This section explains the connection method of the connector for the dedicated flat
cable.
1) Correctly place the dedicated flat cable
in the cover. (Check that the position
of the orange part is correct.)
Orange
2) Close the cover so that the flat cable
will be held between both sides of the
cover.
Orange
MELSEC-
3) Assemble the cover with the body and
pressure-weld them using pliers or
similar device.
Orange
Note 1) This setting position is wrong.
Orange
(b) T-Branch Processing
5) Cut 2 portions of the edge of the cover
with nippers and remove the edge.
Cut
Note 2) If the orange part is seen through
the guide hole in the front cover,
the wiring is not correct. Open
the cover and perform the
previous step again.
Orange
6) Set the cover at the point where
T-branch is to be set.
Orange
4) Check that all of four latches are
engaged. Pressure-welding is
completed.
Orange
7) Execute pressure-welding as
instructed in step 3 to 4.
Orange
4 - 10 4 - 10
A
4 PROCEDURE UP TO DATA LINK
4.5.2 How to connect VCTF or high flexible cable connector
This section describes how to connect the VCTF cable connector or high flexible cable
connector.
(1) Components
The components are shown below.
MELSEC-
For VCTF cable connection: Green
For high flexible cable connection:
Yellow green
Component 2: Body (Aqua)Component 1: Cover
Component 3:
VCTF cable/High flexible cable
Red
White
Black
Green
n
e
e
r
G
k
c
a
l
B
e
t
i
h
W
d
e
R
r
e
v
o
C
e
d
i
s
n
i
Cable colors and
relevant signals
Signal name
+24V
DA
DB
24G
Cable color
Red
White
Black
Green
4 - 11 4 - 11
A
4 PROCEDURE UP TO DATA LINK
(2) Operating steps
The operating steps are shown below.
(a) Processing Cable End
1) Place each wire of the VCTF cable
or high flexible cable so that its wire
color matches the color inside the
cover.
d
e
R
e
t
i
h
W
k
c
a
l
n
e
B
e
r
G
2) Close the cover so that the wires
are properly fitted. When the
wiring is correct, the green cable
can be viewed through the hole.
If a red, white or black cable is
viewed through the hole, open
the cover and correct the wiring.
Incorrect wiring may cause failure
of the module.
MELSEC-
3) Assemble the cover with the body
and press-fit them with pliers.
4) Verify that 4 latches are engaged.
Press-fitting is complete.
m
c
4
Green: Correct wiring
Red, white or black: Incorrect wiring
5)-1 When using a terminal block for T-branching
When connecting VCTF cables or high flexible cables to the terminal block, cable colors must be
matched for each terminal.
VCTF cable/
High flexible cable
DADB24G+24V
VCTF cable/
High flexible cable
VCTF cable/
High flexible cable
Red
White
Black
Green
Note) When connecting a dedicated flat cable to the terminal block
(e.g. in a case where a VCTF cable is used for the trunk line
and dedicated flat cables for drop lines), each of "+24V",
"DA", "DB" and "24G" printed on the dedicated flat cable
must match the color of the VCTF or high flexible cable as
shown in the right table.
Split the dedicated flat cable into discrete "+24V", "DA", "DB"
and "24G" cables.
Dedicated flat
cable
+24V Red
DA White
DB Black
24G Green
VCTF cable/High
flexible cable
4 - 12 4 - 12
A
4 PROCEDURE UP TO DATA LINK
MELSEC-
5)-2 When using a connector for T-branching
After removing the sheath 7cm or more, make a T-branch wiring with a connector in the same way as
the T-branch method for the dedicated flat cable.
VCTF cable/High flexible cable (Trunk line)
VCTF cable/
High flexible cable(Drop line)
Connector for VCTF cable/
High flexible cable
Connector for VCTF cable/
High flexible cable
(c) T-Branching procedure (Trunk line: Dedicated flat cable, Drop
line: VCTF cable/High flexible cable)
6) Make a T-branch wiring with the connector in the same way as the T-branch method for the dedicated flat
cable.
Dedicated flat cable (Trunk line)
Connector for dedicated flat cable
(d) Processing procedure for VCTF cable/High flexible cable
7) Cut off the 2 portions of the covers
edge with nippers and remove the
edge.
Cut
VCTF cable/
High flexible cable(Drop line)
Connector for VCTF cable/
High flexible cable
connector (Connecting terminating resistor)
8) Place the cover at the point
where the terminating resistor
is to be connected.
9) Follow the step (a) 3) and 4)
and execute press-fitting.
4 - 13 4 - 13
A
4 PROCEDURE UP TO DATA LINK
(3) Precautions for use of high flexible cables
Wire the high flexible cable in a way to prevent from applying load to the high
flexible cable connection even when the cable moves.
4.5.3 Mixture of different kinds of cables
This section describes mixture of different kinds of cables.
(1) Trunk line
Mixture of different kinds of cables is not allowed.
(2) Drop line
(a) Mixture of different kinds of cables is allowed.
(b) Using more than one kind of cables for the same drop line is not allowed.
(See Fig. 4.1.)
When using a module with cable (e.g. CL1Y2-T1D2S), however, dissimilar
cables can be connected if the dedicated flat cable of the module is 20cm
long or less. (See Fig. 4.2.)
[Example]
MELSEC-
Remote
module
Remote
module
Remote
module
Trunk line (VCTF cable)
Drop line (Dedicated flat cable)
Drop line (VCTF cable)
Remote
module
Module with cable
20cm or less
Remote
module
Trunk line (VCTF cable)
Drop line (Dedicated flat cable)
Drop line (VCTF cable)
Fig. 4.1 Fig. 4.2
4 - 14 4 - 14
A
4 PROCEDURE UP TO DATA LINK
(3) System configuration example for using dedicated flat cable as
trunk line
AJ65SBT
-CLB
MELSEC-
AJ65SBT
-CLB
Power supply
adapter
Remote
module
General
power supply
(24V DC)
Trunk line (Dedicated flat cable)
Drop line (Dedicated flat cable)
Drop line (VCTF cable/High flexible cable)
Remote
module
(4) System configuration example for using VCTF cable as trunk line
Connecting terminating resistor on AJ65SBT-CLB side
Terminating resistor (CL9-TERM)
Install
VCTF cable
connector
(For AJ65SBT-CLB)
VCTF cable
connector*
(For terminating resist or)
Remote
module
Remote
module
Remote
module
VCTF/high frexible cable connector
Dedicated flat cable connector
Terminating resistor (CL9-TERM)
VCTF cable
Remote
module
Remote
module
Module
with cable
20cm or less
Remote
module
Commercially
available terminal
* For the processing procedure for the VCTF cable connector
(for the terminating resistor), refer to Section 4.5.2.
Remote
module
Remote
module
Module
with cable
20cm or less
Remote
module
Commercially
available terminal
Power supply
adapter
Remote
module
General
power supply
(24V DC)
Trunk line (VCTF cable)
Drop line (Dedicated flat cable)
Drop line (VCTF cable/High flexible cable)
Remote
module
Remote
module
Remote
module
Remote
module
VCTF/high frexible cable connector
Dedicated flat cable connector
Terminating resistor (CL9-TERM)
4 - 15 4 - 15
A
4 PROCEDURE UP TO DATA LINK
(5) System configuration example for using high flexible cable as trunk
line
Connecting terminating resistor on AJ65SBT-CLB side
Terminating resistor (CL9-TERM)
MELSEC-
AJ65SBT
-CLB
High flexible
cable connector
(For AJ65SBT-CLB)
* For processing procedure for the high flexible cable connector*
(for terminating resistor), refer to Section 4.5.2.
Power supply
adapter
Remote
General
power supply
(24V DC)
Trunk line (High flexible cable)
Drop line (Dedicated flat cable)
Drop line (VCTF cable/High flexible cable)
module
High flexible
cable connector*
(For terminating resistor)
Remote
module
Install
High flexible
cable
Remote
module
Remote
module
Remote
module
VCTF/high frexible cable connector
Dedicated flat cable connector
Terminating resistor (CL9-TERM)
Remote
module
Remote
module
Module
with cable
20cm or less
Remote
module
Commercially
available terminal
4 - 16 4 - 16
A
r
4 PROCEDURE UP TO DATA LINK
4.5.4 Mounting terminating resistors
Use the CL9-TERM (Gray) for the terminating resistor.
For the system configuration using the dedicated flat cables only, the CL9-RYVK
(Black) can be also used. Note that the same type must be used for both ends of the
trunk line.
(1) Mounting terminating resistor to AJ65SBT-CLB side
Mount the terminating resistor to the AJ65SBT-CLB side as shown below.
Note that it should be placed within 20 cm from the AJ65SBT-CLB.
MELSEC-
Within 20cm
AJ65SBT-CLB
Terminating resisto
(2) Mounting terminating resistor to another end of trunk line
Mount the terminating resistor to the opposite end to the AJ65SBT-CLB side as
shown below.
Terminating resistor
4 - 17 4 - 17
A
4 PROCEDURE UP TO DATA LINK
4.6 CC-Link Side Connection
This section explains the wiring the CC-Link dedicated cables that connect the
AJ65SBT-CLB and master module.
MELSEC-
4 - 18 4 - 18
A
4 PROCEDURE UP TO DATA LINK
4.6.1 Connection of the CC-Link dedicated cables
Connect the CC-Link dedicated cable between the AJ65SBT-CLB and master module
as shown below.
For this module, use the Ver. 1.10-compatible CC-Link dedicated cable (FANC110SBH,CS-110,FA-CBL200PSBH).You cannot use the Ver. 1.10-compatible
CC-Link dedicated cables, CC-Link dedicated cables or CC-Link dedicated, highperformance cables of other than the above models.
The shield wire of the CC-Link dedicated cable should be connected to "SLD" in
each module, and both ends should be grounded through "FG".
"SLD" and "FG" are connected inside the module.
Online connector
for communication
(Blue)
(White)
(Yellow)
(Blue)
(White)
(Yellow)
SLD
SLD
1
2
3
4
5
1
2
3
4
5
CONA
1
2
3
4
5
CONB
1
2
3
4
5
DA
DB
DG
NC
SLD
DA
DB
DG
NC
SLD
One-touch connector plug
with terminating resistor
5432 1
4321
5
A6CON-TR11
Online connector
for communication
(Blue)
(White)
(Yellow)
Terminating
SLD
1
2
3
4
5
1
2
3
4
5
resistor
(A6CON-TR11)
CONA
1
2
3
4
5
CONB
1
2
3
4
5
DA
DB
DG
NC
SLD
DA
DB
DG
NC
SLD
FG
4 - 19 4 - 19
A
(
)
A
4 PROCEDURE UP TO DATA LINK
4.7 Wiring the One-Touch Connector Plug
This section describes wiring the one-touch connector plug.
Refer to section 2.4 for more information on the models and specifications of the onetouch connector plugs which comply to the AJ65SBT-CLB.
m
m
1
Plug cover
Metal contact
DA (Blue)
DB (White)
DG (Yellow)
Drain wire (AWG20)
s
s
e
l
r
o
Pliers
Plug body
Cut the shield wire, aluminum tape and braid.
Stretch the drain wire and twist it from the base.
3cm in length, 7 times or more
Metal contacts
Metal contacts
MELSEC-
1) Check the connector.
Check that the plug cover is attached to the plug body.
Note: Do not push the plug cover into the plug body.
Once pressed, the plug cannot be used any more.
2) Processing for communication cable
Strip the cable 3cm or more and perform the processing
indicated at left.
If the electric wire lengths are not even, trim their ends
with a nipper to the same length so as to insert them
neatly into a connector.
3) Insert the cable.
Lift the end of the plug cover and insert the cable until it
almost reaches the plug body (within 1mm from the
other end of the plug cover).
Insufficient cable insertion may cause improper press
fitting.
Note: When inserting the cable, prevent the cable from
sticking out from the plug cover end.
4) Set the plug cover.
fter inserting the cable, put down the plug cover so that
its face is horizontal to the plug surface, allowing the
metal contacts to be fitted into the plug cover.
5) Press the center part of the plug cover.
Using pliers, press the center part of the plug cover
vertically and strongly.
For the one-touch connectors, use adjustable pliers so
that their jaws can be widely opened.
(To the next page)
4 - 20 4 - 20
A
4 PROCEDURE UP TO DATA LINK
(From the previous page)
Pliers
Latches
[Correct example]
0.2mm or less
[Wrong example]
[Correct example]
[Wrong example]
MELSEC-
6) Press both ends of the plug cover
After pressing the center part of the plug cover, press both
ends of the plug cover where latches are located.
Verify that the latches engage with the plug body.
7) Check the press-fit condition (viewing from the wiring side).
Viewing from the wiring side, check that the plug surface is
flash with the plug cover.
The difference between the plug cover and the plug
surface must be 0.2mm or less.
Note: The condition where the plug cover is tilted as
shown in [Wrong example] or protrudes from the
plug surface 0.2mm or more is an improper press-fit
condition.
Press the plug cover securely with pliers until it looks
like [Correct example] condition illustrated on the left.
8) Check the press-fit condition (viewing from the top).
Viewing from the top, check that there is no clearance
between the plug body and plug cover.
Note: Clearance may occur between the plug body and
plug cover when the latches do not engage securely
as shown in [Wrong example].
Press the plug cover firmly with pliers until it looks
like [Correct example] condition illustrated on the left.
Latches
Latch
Clearance
(Wiring completed)
4 - 21 4 - 21
A
4 PROCEDURE UP TO DATA LINK
4.8 Wiring Check
Check the wiring of the CC-Link/LT remote I/O stations and external devices.
After network parameter setting, set "Remote input (RX) refresh device" to
"X400" and "Remote output (RY) refresh device" to "Y400".
(a) Checking the wiring of the input module and external device
1) Turn on the switch, which corresponds to "X400", of the external
device connected to the input module of Station No. 1.
2) Using GX Developer, choose "Online" - "Monitor" - "Device batch", set
"X400" in the "Device" field, and click Monitor Start.
3) When X400 is on, the connection of the input module and external
device is normal.
(b) Checking the wiring of the output module and external device
1) Using GX Developer, choose "Online" - "Debug" - "Device test, set
"Y408" in the "Device" field of "Bit device", and click "Forced ON".
2) If the connection of the output module and external device is normal,
the lamp of the external device corresponding to "Y408" turns on.
4 - 22 4 - 22
A
4 PROCEDURE UP TO DATA LINK
(2) When making refresh with FROM/TO instruction
After network parameter setting, refresh RX/RY to X400/Y400 using the
FROM/TO instruction.
(a) Data link start
The operation in this section is not required when the network parameters
have been set using GX Developer or dedicated instruction.
1) Using GX Developer, choose "Online" - "Debug" - "Device test, set
"Y0" in the "Device" field of "Bit device", and click Forced ON.
2) Using GX Developer, choose "Online" - "Debug" - "Device test, set
"Y6" in the "Device" field of "Bit device", and click "Forced ON".
3) Using GX Developer, choose "Online" - "Monitor" - "Device batch", set
"X6" in the "Device" field, and click Monitor Start.
4) When X6 is on, a data link start has been completed normally.
5) Using GX Developer, choose "Online" - "Debug" - "Device test, set
"Y6" in the "Device" field of "Bit device", and click "Forced ON".
(b) Checking the wiring of the input module and external device
1) Turn on the switch, which corresponds to "X400", of the external
device connected to the input module of Station No. 1.
2) Using GX Developer, choose "Online" - "Monitor" - "Device batch", set
"X400" in the "Device" field, and click Monitor Start.
3) When X400 is on, the connection of the input module and external
device is normal.
(c) Checking the wiring of the output module and external device
1) Using GX Developer, choose "Online" - "Debug" - "Device test, set
"Y408" in the "Device" field of "Bit device", and click "Forced ON".
2) When the connection of the output module and external device is
normal, the lamp of the external device corresponding to "Y408" turns
on.
4.9 Maintenance and Inspection
MELSEC-
There are no special inspection items for the AJ65SBT-CLB module, but follow the
inspection items desribed in the programmable controller CPU User's Manual so that
the system always works in the best condition.
4 - 23 4 - 23
r
5 PROGRAMMING
MELSEC-A
5 PROGRAMMING
This chapter explains the programming of the AJ65SBT-CLB.
When applying any of the program examples introduced in this chapter to the actual
system, verify the applicability and confirm that no problems will occur in the system
control.
Refer to the user's manual of the master module for details of that module, to Section
3.7 for the remote registers, and to the AnSHCPU/AnACPU/AnUCPU/QCPU-A (A
Mode) Programming Manual (Dedicated Instructions) for details of the dedicated
instructions.
5.1 Conditions of Program Examples
The program examples in this chapter are based on the following conditions.
(1) System configuration
PLC CPU
Master station (X0 to X1F/Y0 to Y1F)
I/O (64 input points) (X20 to X5F)
Device X
X400 to X40F
X410 to X41F
X420 to X42F
X430 to X43F
Device Y
Y400 to Y40F
Y410 to Y41F
Y420 to Y42F
Y430 to Y43F
Device D
D200
D201
D202
D203
D204
D205
D206
D207
MELSEC-A
(2) Relation between PLC CPU , CC - Link master stati on, AJ65SBT-
CLB and CC-Link/LT remote I/O stations
CC-Link master station
Address
Address
Remote input (RX)
RX00 to RX0F
E0
H
RX10 to RX1F
H
E1
RX20 to RX2F
H
E2
H
E3
RX30 to RX3F
Remote output (RY)
RY00
160
161
162
163
to
H
RY10
to
H
RY20 to RY2F
H
RY30 to RY3F
H
Remote register (RWw)
RWw0
H
1E0
1E1
1E2
1E3
1E4
1E5
1E6
1E7
RWw1
H
H
RWw2
H
RWw3
RWw4
H
RWw5
H
H
RWw6
RWw7
H
RY0F
RY1F
AJ65SBT-CLB
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
RX20 to RX2F
System
area
RX30 to RX3F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
RY20 to RY2F
System
area
RY30 to RY3F
Remote register (RWw)
RWw0 Last station number
Data link stop/
RWw1
restart instructions
Error status flag
RWw2
clear
RWw3 Use prohibited
RWw4 Use prohibited
RWw5 Use prohibited
RWw6 Use prohibited
RWw7 Use prohibited
CL2X8-D1C3V
(Station No. 1)
Input
X400
X407
to
CL2Y8-TP1C2V
(Station No. 3)
Output
Y408
Y40F
to
Device D
D300
D301
D302
D303
D304
D305
D306
D307
Remote register (RWr)
2E0
2E1
2E2
2E3
2E4
2E5
2E6
2E7
RWr0
H
RWr1
H
RWr2
H
RWr3
H
RWr4
H
RWr5
H
H
RWr6
H
RWr7
Remote register (RWr)
Data of
RWr0
operating statuses
Data of
RWr1
faulty station
Remote I/O error
RWr2
data
Data of remote
RWr3
station connection
RWr4 Setting data
RWr5 Use prohibited
RWr6 Use prohibited
RWr7 Use prohibited
In the program example created with the RRPA instruction (auto refresh parameter
setting) on the ACPU/QCPU (A mode), RWr0 - RWr7 are assigned to D456 to D463.
POINT
Depending on the CPU module, the devices used in the program examples of this
chapter may be unusable. For the valid ranges of the devices, refer to the users'
manual of the CPU module.
For example, when the A1SCPU is used, devices of X100, Y100 and later cannot
be used. Use the devices such as B and M.
5 - 2 5 - 2
5 PROGRAMMING
(3) Devices used by the user
The devices used by the user are indicated below.
Data link stop instruction signal................................................................ X21
Data link restart instruction signal ............................................................ X22
CC-Link side data link error confirmation signal...................................... Y90
CC-Link/LT side remote station connection error confirmation signal.... Y91
CC-Link/LT side data link error confirmation signal................................. Y92
CC-Link/LT side all station fault confirmation signal................................Y93
CC-Link/LT side remote I/O error confirmation signal............................. Y94
CC-Link side data link status read flag.......................................................M0
RLPA instruction execution flag ...............................................................M10
RLPA instruction normally completed flag ...............................................M11
Auto refresh paramet er
setting with dedicated
instruction RRPA
MELSEC-A
Setting of RX head
number
Setting of "X"
Setting of X400
Setting of 64 points
Setting of RY head
number
Setting of "Y"
Setting of Y400
Setting of 64 points
Setting of RW head
number
Setting of "D"
Setting of D200
Setting of 264 points
Setting of SB head
number
Setting of "B"
Setting of B0
Setting of 512 points
Setting of SW head
number
Setting of "W"
Setting of W0
Setting of 512 points
Dedicated instruction
(RRPA)
Head I/O number of
master module
Parameter sto ra g e
head device
5 - 9 5 - 9
5 PROGRAMMING
CC-Link
side data
link status
confirmation
MELSEC-A
Data link status read
AJ65SBT-CLB data link norm al
AJ65SBT-CLB data link abn orm al
CC-Link/LT
side data
link status
confirmation
CC-Link/LT
side error
confirmation
Operation status data read
Remote station connection error
occurrence confirmation
Control starts when remote station
connection status is normal
Data link error occurrence
confirmation
All station fault occurrence
confirmation
Remote I/O error occurrence
confirmation
Control prog r am
Data link stop instruction
Data link restart instruction
Data link stop/restart
instruction write
5 - 10 5 - 10
5 PROGRAMMING
MELSEC-A
5.5 Program Example for Use of ACPU/QCPU ( A Mode) ( FR OM /TO Instructi ons)
The network parameters are set using a sequence program.
(1) Program ex ample
Number of connected
modules: 1
Number of retries: 3 times
Number of modules that return
Network
parameter
setting
to system automatically: 1
Write to master station
Operation specified when CPU
becomes faulty: Continue
Write to master station
Station data of AJ 65SBT-CLB
(remote device station, 2
occupied stations, Station No. 1)
Write to master station
Data link start
Refresh instruction
Data link start according to
parameters in buffer memory
Turns off start request signal at
start-up normal completion.
Parameter status read at
start-up abnormal completion
Turns off start request signal at
start-up abnormal completion.
5 - 11 5 - 11
5 PROGRAMMING
CC-Link side
data link
status
confirmation
CC-Link/LT
side data
link status
confirmation
CC-Link/LT
side error
confirmation
Control program
MELSEC-A
Reads RX00 to RX3F into X400 to
X43F.
Data link status read
AJ65SBT-CLB data link normal
AJ65SBT-CLB data link abnormal
Reads RWr0 to RWr4 into D300 to
D304.
Operation status data read
Remote station connection error
occurrence confirmation
Control starts when remote station
connection status is normal
Data link error occurrence
confirmation
All station fault occurrence
confirmation
Remote I/O error occurrence
confirmation
Data link stop instruction
Data link restart instruction
Data link stop/restart
instruction write
Writes D200 to D202 into RWw0 to
RWw2.
Writes Y400 to Y43F into RY00 to
RY3F.
5 - 12 5 - 12
A
6 TROUBLESHOOTING
MELSEC-
6 TROUBLESHOOTING
This chapter explains troubleshooting.
6.1 Station Status at Error Occurrence
Error Condition
When a communication error occurs
between the CC-Link master station
and AJ65SBT-CLB
When a communication error occurs
between the AJ65SBT-CLB and
CC-Link/LT remote I/O station
The following table indicates the station status at error occurrence.
CC-Link Master Station CC-Link/LT Remote I/O Station
Input
RX
Clear/hold
Clear Continue Continue Clear/hold
1: Depending on the switch setting of the CC-Link master station.
2: Depending on the switch setting of the CC-Link/LT remote I/O station.
Output
RY
1 Continue Continue Clear/hold 2
Input Output
2
6
6 - 1 6 - 1
A
6 TROUBLESHOOTING
6.2 Troubleshooting Flow
MELSEC-
The "ERR." LED of the CC-Link master
station is flickering.
Error occurrence
This section explains error definitions by phenomenon.
Refer to the flowchart in Section 6.3 Troubleshooting when the "ERR."
LED of the CC-Link master station is flickering.
The "PW" LED of the AJ65SBT-CLB has
turned off.
Refer to the flowchart in Section 6.4 Troubleshooting when the "PW"
LED of the AJ65SBT-CLB has turned off.
The CC-Link side "L RUN" LED of the
AJ65SBT-CLB has turned off.
Refer to the flowchart in Section 6.5.1 Troubleshooting when the
CC-Link side "L RUN" LED of the AJ65SBT-CLB has turned off.
The CC-Link side "L ERR." LED of the
AJ65SBT-CLB is flickering.
The CC-Link/LT side "L RUN" LED of the
AJ65SBT-CLB has turned off.
Refer to the flowchart in Section 6.5.2 Troubleshooting when the
CC-Link side "L ERR." LED of the AJ65SBT-CLB is flickering.
Refer to the flowchart in Section 6.6.1 Troubleshooting when the
CC-Link/LT side "L RUN" LED of the AJ65SBT-CLB has turned off.
6
The CC-Link/LT side "L ERR." LED of the
AJ65SBT-CLB has turned on/ is flickering.
The CC-Link/LT side "ERR." LED of the
AJ65SBT-CLB has turned on/is flickering.
Refer to the flowchart in Section 6.6.2 Troubleshooting when the CC-Link/
LT side "L ERR." LED of the AJ65SBT-CLB has turned on/is flickering.
Refer to the flowchart in Section 6.6.3 Troubleshooting when the CC-Link/
LT side "ERR." LED of the AJ65SBT-CLB has turned on/is flickering.
The "PW" LED of the CC-Link/LT remote
I/O station has turned off.
Refer to the flowchart in Section 6.6.4 Troubleshooting when the "PW"
LED of the CC-Link/LT remote I/O station has turned off.
The "L RUN" LED of the CC-Link/LT
remote I/O station has turned off.
The "L ERR." LED of the CC-Link/LT remote
I/O station has turned on/is flickering.
Refer to the flowchart in Section 6.6.5 Troubleshooting when the "L
RUN" LED of the CC-Link/LT remote I/O station has turned off.
Refer to the flowchart in Section 6.6.6 Troubleshooting when the "L ERR."
LED of the CC-Link/LT remote I/O station has turned on/ is flickering.
Input cannot be imported from the
CC-Link/LT remote I/O station.
Output cannot be provided from the
CC-Link/LT remote I/O station.
Refer to the flowchart in Section 6.6.7 Troubleshooting when input
cannot be imported from the CC-Link/LT remote I/O station.
Refer to the flowchart in Section 6.6.8 Troubleshooting when output
cannot be provided from the CC-Link/LT remote I/O station.
6 - 2 6 - 2
A
6 TROUBLESHOOTING
6.3 Troubleshooting when the "ERR" LED on the Master Station is Flashing
The "ERR" LED on the
master station is flickering
MELSEC-
parameter setting consistent
Check the modules in which
SW0098 to SW009B are on.
Is the
with the mounting system
configuration?
YES
Are the
master station
link special registers
SW0080 to SW0083
(other station data
link status)
on?
YES
Are the
master station
link special registers
SW0098 to SW009B
(station overlap
status) on?
YES
Are the station
number swi tches
set correctly?
YES
NO
Modification of parameter setting
or mounting system configuration
NO
Master station failure
NO
NO
Set the station number
switches correctly.
Power on again/press the
reset switch.
Check the modules in which
SW0080 to SW0083 are on.
Does
the corresponding bit
indicate the AJ65SBT-
CLB?
NO
Is the power supply on?
YES
YES
NO
Refer to Section 6.4
or later.
Power on.
Check the master side.
Check the slave station side
Corresponding module failure
To the next page
Is the "POWER" LED on?
YES
Is the "RD" LED on?
YES
To the next page
NO
NO
Is the
communication cable
correctly installed?
1
YES
Malfunction of the
corresponding module
Is the
supplied voltage within the
specified range?
YES
Set the supplied voltage
within the specified range .
Corresponding module failure
NO
Wire the communication
cable correctly.
NO
To the next page
6 - 3 6 - 3
A
6 TROUBLESHOOTING
MELSEC-
From the previous pageFrom the previous pageFrom the previous page
Is the "L RUN"
LED on?
YES
Is the "SD" LED
on (flickering)?
YES
The corresponding
module failure
NO
Is the "SD" LED
on (flickering)?
YES
NO
communication cable
The corresponding mo dule
failure (Transmission
speed setting switch)
station number switch correctly
Is the
set (not overlapping with
other stations)?
YES
NO
Is the
transmission speed
setting correct?
YES
Is the
wired correctly?
1
YES
NO
Set the station
number
correctly.
NO
Set the transmission speed
correctly.
Power on again/press the
reset switch.
NO
Wire the communication
cable correctly.
Power on/press the reset
switch.
Power on/press the reset
switch.
Are the
station number switches set
correctly (not overlapping with
other stations)?
YES
The corresponding module
failure (Station number
switch)
The corresponding module
failure (Station number
switch)
NO
Set the station
number
correctly.
Complete
1 : Check for a short, reversed connection, wire breakage, terminating resistor, FG
connection, overall distance and station-to-station distance.
6 - 4 6 - 4
A
6 TROUBLESHOOTING
6.4 Troubleshooting when the "PW" LED of the AJ65SBT-CLB has Turned Off
MELSEC-
"PW" LED of the AJ65SBT-CLB
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem
1: Check for short circuit, inverse connection, cable break or excessive pressure to a cable.
2 : Measure the voltage using the check terminals of the terminating resistors.
turns off
Is power supplied?
YES
Is
supply voltage within
specified range?
YES
NO
NO
Check terminal 24VCheck terminal 24G
Supply power. 1
Make supply voltage within
control range
END
6 - 5 6 - 5
A
6 TROUBLESHOOTING
MELSEC-
6.5 CC-Link Side Troubleshooting
6.5.1 Troubleshooting when the CC-Link side "L RUN" LED of the AJ65SBT-CLB has turned
off
The CC-Link side "L RUN"
LED of the AJ65SBT-CLB has
turned off.
Is the
"SD" LED of the
master station on
(flickering)?
YES
NO
Is the transmission
speed setting correct?
communication cable
wired correctly?
The corresponding module
failure (Transmission speed
setting switch)
YES
Is the
1
YES
NO
Set the transmission speed
Power on/press the reset
switch.
NO
Wire the communication
cable correctly.
Are the
station number switches set
correctly (not overlapping with
other statio ns)?
YES
The corresponding module
failure (Station number
switches)
1 : Check for a short, reversed connection, wire breakage, terminating resistors, FG connection, overall distance and
station-to-station distance.
NO
Set the station number
correctly.
Power on/press the reset
switch.
Complete
6 - 6 6 - 6
A
6 TROUBLESHOOTING
MELSEC-
6.5.2 Troubleshooting when the CC-Link side "L ERR." LED of the AJ65SBT-CLB is
flickering
The CC-Link side "L ERR." LED
of the AJ65SBT-CLB is flickering
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
Check how the LED
is flickering.
Periodically
NO
Return the setting switch to the
previous position.
1 : Check for a short, reversed connection, wire breakage, terminating resistors, FG connection, overall distance and
station-to-station distance.
Has any
setting switch setting been
changed during
operation?
YES
Complete
Not periodically
communication
cable wired correctly?
YES
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
Is the
1
NO
Wire the communication
cable correctly.
6 - 7 6 - 7
A
6 TROUBLESHOOTING
MELSEC-
6.6 CC-Link/LT Side Troubleshooting
6.6.1 Troubleshooting when the CC-Link/LT side "L RUN" LED of the AJ65SBT-CLB has
turned off
The CC-Link/LT side "L RUN"
LED of the AJ65SBT-CLB has
turned off
Is the
test mode switch in the
OFF position?
YES
Is Data link stop ON?
YES(ON)
Turn on Data link restart.1
NO
NO(OFF)
Is CC-Link/LT side
L ERR. on?
NO
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
YES
Check the troubleshooting
when the CC-Link/LT side L
ERR. LED of the AJ65SBTCLB has turned on/is flickering
Complete
1 : When Data link restart and stop are turned on simultaneously,
Data link stop has higher priority.
6 - 8 6 - 8
A
6 TROUBLESHOOTING
MELSEC-
6.6.2 Troubleshooting when the CC-Link/LT side "L ERR." LED of the AJ65SBT-CLB has
turned on/is flickering
The CC-Link/LT side "L ERR."
LED of the AJ65SBT-CLB has
turned on/is flickering
NO
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
Check the remote station that
turned on in faulty station data.
Is all
station fault (RWr)
of the AJ65SBT-
CLB on?
YES
Is
the PW
LED of the CC-Link/
LT remote station
on?
YES
Is
the L RUN
LED of the CC-Link/
LT remote station
on?
YES
Is
the L ERR.
LED of the CC-Link/
LT remote station
off?
YES
Flickering
YES
NO
NO
NO
Is the LED flickering
or on?
On
Is the
test mode switch in the
OFF position?
YES
Are
the remote
stations connected
within the control
range?
YES
Is
faulty station data
(RWr) of the AJ65SBT-
CLB on?
NO
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
Refer to the remote station "PW"
LED troubleshooting.
Refer to the remote station "L
RUN" LED troubleshooting.
Refer to the remote station "L
ERR." LED troubleshooting.
NO
NO
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
Remove the remote station
outside the control range.
Increase number of the occupied
stations.
Reset the last station number
according to the system.
Power off, then on again.
Check the AJ65SBT-CLB
side.
Check the CC-Link/LT
remote station side.
Are there
any problems on
the line?
1
YES
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
1: Check for a short, reversed connection, wire breakage, mixed cables,
terminating resistors, overall distance, drop line distance (overall drop
line length, maximum drop line length) and peripheral environment.
NO
Correct the communication cables.
Complete
6 - 9 6 - 9
A
6 TROUBLESHOOTING
MELSEC-
6.6.3 Troubleshooting when the CC-Link/LT side "ERR." LED of the AJ65SBT-CLB has
turned on/is flickering
The CC-Link/LT side "ERR."
LED of the AJ65SBT-CLB has
turned on/is flickering
Has any
setting switch setting been
changed during
operation?
YES (Changed)
Return the setting switch to the
previous position.
Flickering
NO
(Not changed)
Is the LED
flickering or on?
On
Is the CC-Link/
LT side transmission speed
switch of the AJ65SBT-CLB
set correctly?
YES
Is the CC-
Link/LT side point mode
switch of the AJ65SBT-CLB
set correctly?
YES
Consult your local Mitsubishi service
center or representative, explaining
a detailed description of the problem.
NO
NO
Correct the CC-Link/LT side
point mode setting of the
AJ65SBT-CLB.
Power off, then on again.
Correct the CC-Link/LT side
transmission speed setting of
the AJ65SBT-CLB .
Power off, then on again.
Complete
6 - 10 6 - 10
A
6 TROUBLESHOOTING
MELSEC-
6.6.4 Troubleshooting when the "PW" LED of the CC-Link/LT remote I/O station has turned off
For troubleshooting of the remote device station, refer to the user’s manual for your
remote device station.
The "PW" LED of the CC-Link/LT
remote I/O station has turned off
Is power supplied?
YES
Is the
supply voltage within the
specified range?
2
YES
Consult your local Mitsubishi service center
or representative, explaining a detailed
description of the problem.
1 : Check for a short, reversed connection, wire breakage and insulation
displacement status.
2 : Measure the voltage using the check terminals of the terminating resistors.
Check terminal 24G
NO
NO
Check terminal 24V
Supply power. 1
Change the supply voltage to
within the specified range.
Complete
6 - 11 6 - 11
A
6 TROUBLESHOOTING
MELSEC-
6.6.5 Troubleshooting when the "L RUN" LED of the CC-Link/LT remote I/O station has
turned off
For troubleshooting of the remote device station, refer to the user’s manual for your
remote device station.
The "L RUN" LED of the
CC-Link/LT remote I/O station
has turned off
Has the
transmission speed
setting of the AJ65SBT-CLB
been changed after data
link communication?
NO (Not changed)
Are there any problems
on the line? 1
NO (Without problem)
Is the station number
setting normal? 2
YES
Is the station number
within the controllable range
of the AJ65SBT-CLB? 3
YES (Changed)
Power the system off, then on.
YES (With problem)
Correct the wiring of the
communication cables.
NO
NO
Set the correct station
number. 4
Set the station number to within
the controllable range of the
AJ65SBT-CLB. 4
YES
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
1 : Check for a short, reversed connection, wire breakage, insulation displacement status, terminating resistors, overall distance,
drop line distance (overall drop line length, maximum drop line length) and peripheral environment (noise, etc.).
2 : Note the following.
Any of 0 to 9 should be in the units digit.
The switch should not be mistaken for the output hold setting switch or response speed setting switch.
3 : All station numbers occupied by the host module should be within the controllable range of the AJ65SBT-CLB.
(Refer to Section 3.6.2)
4 : When the station number setting of the remote I/O station has been changed, power the whole system off, then on.
Complete
6 - 12 6 - 12
A
6 TROUBLESHOOTING
MELSEC-
6.6.6 Troubleshooting when the "L ERR." LED of the CC-Link/LT remote I/O station has
turned on/is flickering
For troubleshooting of the remote device station, refer to the user’s manual for your
remote device station.
The "L ERR." LED of the
CC-Link/LT remote I/O station
turned on /is flickering
Has any
setting switch setting
been changed after
power-on?
NO (Not changed)
Are there any
problems on the line? 1
NO (Without problem)
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
1 : Check for a short, reversed connection, wire breakage, insulation displacement status, terminating resistors, overall distance,
drop line distance (overall drop line length, maximum drop line length) and peripheral environment (noise, etc.).
YES (Changed)
Return to the previous setting.
YES (With problem)
Correct the wiring of the
communication cables.
Complete
6 - 13 6 - 13
A
6 TROUBLESHOOTING
MELSEC-
6.6.7 Troubleshooting when input cannot be imported from the CC-Link/LT remote I/O station
For troubleshooting of the remote device station, refer to the user’s manual for your
remote device station.
Input cannot be imported
from the CC-Link/LT remote
I/O station
Is the input
recognized by the
AJ65SBT-CLB?
(Refer to Section 3.7.8)
YES
Is the input LED on?
YES
Is the
wiring check correct?
(Refer to Section 4.8)
NO
NO
NO
Are there any
problems on the line? 1
NO (Without problem)
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
Is the external wiring normal?
YES
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
Review the program,
parameters and/or wiring.
YES (With problem)
NO
Correct the wiring of the
communication cables.
Correct the external wiring.
YES
NO (Not overlapping)
Are the station
numbers overlapping?
YES (Overlapping)
Correct the overlapping
station numbers. 2
Complete
1 : Check for a short, reversed connection, wire breakage, insulation displacement status, terminating resistors, overall distance,
drop line distance (overall drop line length, maximum drop line length) and peripheral environment (noise, etc.).
2 : When the station number setting of the remote I/O station has been changed, power the whole system off, then on.
Consult the local servicing
company, dealer or our
branch office.
6 - 14 6 - 14
A
6 TROUBLESHOOTING
MELSEC-
6.6.8 Troubleshooting when output cannot be provided from the CC-Link/LT remote I/O
station
For troubleshooting of the remote device station, refer to the user’s manual for your
remote device station.
Output cannot be provided
from the CC-Link/LT remote
I/O station
recognized by the AJ65SBT-CLB?
Is the output
(Refer to Section 3.7.8)
YES
Is the output LED on?
YES
Is the external wiring normal?
NO
Correct the external wiring.
NO
NO
YES
Are there any
problems on the line? 1
NO (Without problem)
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
Is the wiring
check correct? (Section 4.8)
YES
Consult your local Mitsubishi
service center or representative,
explaining a detailed description
of the problem.
YES (With problem)
Correct the wiring of the
communication cables.
NO
Review the program,
parameters and/or wiring.
Complete
1 : Check for a short, reversed connection, wire breakage, insulation displacement status, terminating resistors, overall distance,
drop line distance (overall drop line length, maximum drop line length) and peripheral environment (noise, etc.).
6 - 15 6 - 15
A
6 TROUBLESHOOTING
6.7 CC-Link / CC-Link/LT Diagnostics Using GX Developer
After connecting all the modules with connection cables, check the status of each
module to see if data link can be performed.
Data link can also be performed when the master module is mounted on the remote
I/O station of MELSECNET/H.
(1) Line Monitor [Host station]
The data link status, etc. of the AJ65SBT-CLB are monitored.
2) In the "Module No." or "I/O Address" box, specify the master module
connected with the AJ65SBT-CLB for which Line Monitor will be
executed.
3) Check the "CC-Link Bridge" check box. At this time, the station number
of the AJ65SBT-CLB is searched for.
4) In the "Station" box, select the station number of the AJ65SBT-CLB for
which Line Monitor will be executed.
5) Click the Start Monitoring button.
MELSEC-
(b) Monitor items
1) Host Station
Shows that the station being monitored is the AJ65SBT-CLB. (The
AJ65SBT-CLB is displayed as the master station.)
2) Data Link Status
Shows the data link status of the AJ65SBT-CLB.
Start Data linking: Data link start status
Stop Data linking: Data link stop status
Initial comm. incomplete: Initial communication incomplete status
6 - 16 6 - 16
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.