This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the F940WGOT-TWD-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the
F940WGOT Series.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use that product in a safe and
co-ordinated manner in compliance to established safety practices.
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
Note:
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
2) Indicates that the identified danger could
cause physical and property damage.
WILL
POSSIBLY
cause physical and property
damage.
•Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
•All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.
•Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Associated Manuals
Manual NameManual NumberDescription
F940WGOT Series
|
(F940GOT-TWD)
Installation Manual
GOT-F900
~
OPERATION MANUAL
(describes GT Designer2)
GOT-F900 Series
~
Operation Manual
GOT-F900 Series
~
Hardware Manual
(connection diagram)
GT Designer2 Version1
|
Operating Manual
GT Designer2 Version1
|
Reference Manual
GT Designer
|
Operating Manual
FX-PCS-DU/WIN-E
|
SOFTWARE MANUAL
JY997D93901
JY997D09101
(separate volume)
JY992D94701
(separate volume)
JY992D94801
(separate volume)
(PDF files on CDROM included with
product)
(PDF files on CDROM included with
product)
Included with the
screen creation
software
JY992D68301
(included with the
screen creation
software)
Describes the specifications, wiring, and
installation of F940WGOT Series graphic
operation terminal. (hardware)
Describes the operation and use of the GOTF900 Series graphic operation terminals and GT
Designer2.
Describes the operation and use of the GOTF900 Series graphic operation terminals, GT
Designer and FX-PCS-DU/WIN-E.
Describes wiring and installation of the GOTF900 Series graphic operation terminals.
Describes the operation of GT Designer2
(SW*D5C-GTD2-E) and data transfer to the
GOT-900 Series.
Describes the specifications and setting of object
functions in GT Designer2 (SW*D5C-GTD2-E).
Describes the operation of GT Designer
(SW*D5C-GOTR-PACKE) and data transfer to
the GOT-900 Series. (Refer to the help file)
Describes the operation of FX-PCS-DU/WIN-E
screen creation software.
Page 2
Manual NameManual NumberDescription
50(1.96")
23(0.91")
205(8.07")
g)
5(0.20")orless
70.6(2.78)
h)
f)
10(0.39")
d)
10(0.39")
34.5(1.35")
23(0.91")
23(0.91")
34.5(1.35")
e)
143(5.63")
133(5.24")
c)
24VDC
F9GT-40FMB
User’s Manual
~
Indispensable manual
|
Either manual is necessary.
Refer if necessary, please.
JY992D98601
This manual contains explanations for installation
and operating procedures of the F9GT-40FMB
data transfer adapter.
Refer to the Programming manual (ΙΙ) or relevant hardware manuals for details concerning the applicable
PLC.
1. Introduction
The F940WGOT series (hereafter called “GOT”) is to be
mounted on the face of a control panel or operations panel, and
connected to the programming port (CPU port) or the
communication port (communication port) of a PLC.
Various devices can be monitored and PLC data changed
through the GOT screens. Several display screens are built-in to
the GOT, and additional personalized screens can be created by
the user.
1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs
as well as a host of third party manufactured units. Further
information can be found in GOT-F900 Series Hardware
Manual.
2) PLC user programs can be downloaded, uploaded and monitored using programming software GXDeveloper or FX-PCS/WIN-E on a personal computer via the GOT. Further information can be found
in GOT-F900 Series Operation Manual.
3) Display screens are created using the following software:
Software NameVersion
GT Designer2
SWD5C-GTD2-E
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
SW5-F edition of SW5D5C-GOTR-PACKE (version 5.05F) or later
GOT-F900 Series (for Windows) screen creation software.
SW0PC-FXDU/WIN-E version 2.50 or later
1.1 Product Lists
Production NameDescription
F940WGOT-TWD-E Graphic operation terminal main unit
Communication cable (GOT ↔ CPU port in FX
2NC
FX
FX-50DU-CAB0
FX-50DU-CAB0/EN
FX-50DU-CAB0-**M
FX-40DU-CAB
FX-40DU-CAB-**M
QC30R2
FX-232CAB-1Data exchange cable (GOT ↔ Personal computer <9-pin D-sub>)
PM-20BLBattery for Alarm history, sampling and current time data retention.
F9WGT-40PSCTransparent protection sheet for F940WGOT (5 pieces)
F9GT-40FMBData transfer adapter (Flash memory built in)
series PLC)
The connector on the GOT side is wired straight through.
Cable length is 3m (9' 10").
Communication cable (GOT ↔ CPU port in FX
2NC
FX
series PLC)
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
Communication cable (GOT ↔ CPU port in FX
2NC
FX
series PLC)
The connector on the GOT side is wired straight through.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),
30M: 30m (98' 5")
Communication cable (GOT ↔ CPU port in FX, FX
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
Communication cable (GOT ↔ CPU port in FX, FX
The connector on the GOT side is wired straight through.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")
Communication cable (GOT ↔ CPU port in Q series PLC)
The connector on the GOT side wired straight through. Cable length is 3m (9' 10").
P L C
P r o g r a m m i n g
p o r t
G O T
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
2C
, A or QnA series PLC)
2C
, A or QnA series PLC)
Caution
During abnormal communication (including cable breakages) ages when monitor within the
GOT, communication between the GOT and programmable controller CPU is interrupted. It is
impossible to operate switches or devices in the PLC through the GOT.
Communication and normal operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction.
Page 3
Note;
5 0 ( 1 . 9 6 " )
2 3 ( 0 . 9 1 " )
2 0 5 ( 8 . 0 7 " )
g )
5 ( 0 . 2 0 " ) o r l e s s
7 0 . 6 ( 2 . 7 8 )
h )
f )
1 0 ( 0 . 3 9 " )
d )
1 0 ( 0 . 3 9 " )
3 4 . 5 ( 1 . 3 5 " )
2 3 ( 0 . 9 1 " )
2 3 ( 0 . 9 1 " )
3 4 . 5 ( 1 . 3 5 " )
e )
1 4 3 ( 5 . 6 3 " )
1 3 3 ( 5 . 2 4 " )
c )
2 4V D C
•Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep
a safe distance of more than 100 mm from these wires.
•Operate touch switches on the display screen by hand.
DO NOT use excessive force, or attempt operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen.
1.2 Dimensions and Each Part Name
Dimensions: mm (inches)MASS (Weight): 1 kg (2.2 lbs)
Dielectric Withstand Voltage 500 V AC > 1 min, tested between power terminals and ground
Insulation Resistance5 MΩ > at 500 V DC, tested between power terminals and ground
GroundGrounding resistance 100 Ω or less. (Class D)
ProtectionIP 65F
Horizontal mounting: 0 ~ 50 °C (32 ~ 122 °F)
Vertical and flat mounting: 0 ~ 40 °C (32 ~ 104 °F)
Must be free of lamp black, corrosive gas, flammable gas, or excessive
amount of electroconductive dust particles and must be no direct
sunlight. (Same as for saving)
10 ~ 57 Hz: 0.075 mm Half Amplitude
57 ~ 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
10 ~ 57 Hz: 0.035 mm Half Amplitude
57 ~ 150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
2
147m/s
Acceleration,
2
Acceleration
3 times in each direction X, Y, and Z
Page 4
HEAD OFFICEHIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPAN
2.2 Power Supply Specifications
b)
a)
c)
b)
a)
ItemsSpecifications
Power Supply Voltage24V DC, +10% -15%
Power Supply Ripple200 mV or less
Ratings: 650 mA at 24V DC
Current Consumption
750 mA at 24V DC or less when power supply is turned ON
400 mA at 24 V DC when backlight is turned OFF
FuseFuse built-in GOT (impossible to change)
Max. Allowable Momentary
Power Supply Failure period
1 ms; If less than 1 ms, the GOT will continue operation. If 1 ms or
more, the GOT will shut down.
BatteryBuilt-in, PM-20BL type lithium battery. (Approximately 5 years life)
•Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is
impossible to completely avoid this symptom, as the liquid crystal display comprises of a great
number of display elements.
Flickers may be observed depending on the display color.
Please note that these dots appear due to its characteristic and are not caused by product defect.
•When the same screen is displayed for a long time, an incidental color or partial discoloration is
generated on the screen due to heat damage, and it may not disappear.
•Using the GOT Backlight OFF function can prolong the life of the backlight.
For details on the Backlight OFF function, refer to the following.
GOT-F900 Series OPERATION MANUAL/GOT-F900 Series OPERATION MANUAL [GT Designer2
Version]
0.324 mm (0.013") Horizontal × 0.375 mm (0.015") Vertical.
[Actual character size ratio 1:1.16]
50,000 hours or more
(Operating temperature: 25 °C / 77°F)
50,000 hours or more
(Operating temperature: 25 °C / 77°F)
User screen: 500 screens or less
System screen: Allocated screens No. 1001-1030.
3. Installation
Note;
•Do not mount the GOT in an environment that contains dust, soot corrosive or conducive
dust, corrosive or flammable gas, or expose the unit to high temperatures, dew
condensation, direct sunlight, rain wind or impact and vibration.
If the GOT is used in such a place, electrical shock, fire, malfunction, damages or
deterioration may caused.
•Never drop cutting chips or electric wire chips into the ventilation window of the GOT
when drilling screw holes or performing wiring. Such chips may cause fire, failure or
malfunction.
•Turn off the power before securely connecting any cables. Poor connection may cause
malfunction.
The GOT is designed to be mounted in a panel. Install it using the following procedure:
1) Preparing the panel surface.
On the panel surface, cut a rectangular mounting slot of the
dimensions shown on the right.
At this time, space of 10 mm is required at each of the top and the
bottom of the slot, inside the panel for metal fixtures as shown in
“4) Dimensions required inside the panel for installation”.
U n i t : m m ( i n c h e s )
S l o t t o b e c u t o n p a n e l
+ 1 ( + 0 . 0 4 " )
2 0 6 ( 8 . 1 1 " )
0
+ 1 ( + 0 . 0 4 " )
0
( 4 . 8 8 " )
1 2 4
Page 5
HEAD OFFICEHIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPAN
Note
b )
a )
c )
b )
a )
•Make sure that the thickness of the panel surface is no more than 5 mm (0.20").
2) Inserting the GOT into the panel surface
Attach the packing seal to the GOT, and insert the GOT from
the front face of the panel surface.
a) Packing seal
b) GOT
c) Mounting slot
3) Fixing the GOT
Put hooks of the mounting brackets (supplied) in to the
mounting holes of the GOT. Tighten mounting bolts (also
supplied) until the GOT is securely fixed.
Fix mounting bolts in all four positions, above and below the
GOT.
a) Clamping bolt
b) Mounting bracket
Note:
Make sure to tighten the clamping bolts with a torque of 0.3 ~ 0.5 Nm.
4) Dimensions required inside the panel
for installation.
When installing the GOT, make sure
that the inner dimensions shown on the
right are available.
a) PLC connection cable
b) Packing seal
4. Power Supply Wiring
Caution:
Cut OFF all external phases of power source, before installation or wiring to avoid electric
shock or serious damage to the product.
Note:
•Wire the power supply using electric wires of 0.75 mm2 or more so that voltage drop will
not occur. Use M3 size crimp style terminals. Securely tighten crimp-style terminals with a
torque of 0.5 ~ 0.8 Nm so that errors can be avoided.
•Insure correct termination of the DC power source, incorrect connection may result in unit
failure serious damage to the GOT.
•Attach a 2 A fuse to the 24V DC power supply.
•Perform Class D (100Ω or less) grounding with an electric wire of at least 1.25 mm
Never perform common grounding of the GOT and a strong power system.
Note
•Use an external power supply to provide 24V DC.
(The service power supply of the programmable controller cannot be used.)
•Even if instantaneous power interruption of less than 1 ms occurs, the GOT continues to
operate. When power interruption for a considerable period of time or voltage drop occurs,
the GOT stops its operation. However, when the power supply is recovered, the GOT
automatically restarts its operation. (The screen displayed just after recovery is
determined by the working environment originally set.)
Grounding resistance
100Ω or less (class D)
"
2 2 5 ( 8 . 8 6 " )
1 4 3 ( 5 . 6 3 " )
a )
5 ( 0 . 2 0 " ) o r l e s s
24V DC external
power supply
7 0 . 6 ( 2 . 7 8
)
b )
2
.
PLCGOT
24V DC
Fuse (2A)
Page 6
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
5. Expansion Module (F9GT-40FMB)
F9GT-40FMB has a built-in flash memory and can transfer screen data when installed in the GOT.
(When installed in the OS earlier than version 1.40, screen display is not available while transferring data
from F9GT-40FMB to the GOT.)
For the use methods and specifications, refer to the manual for F9GT-40FMB.
6. Maintenance
Cautions:
•Correctly connect the battery for memory backup. Never charge, disassemble, heat, burn
or short-circuit the battery. If the battery is handled in such a way, or fire may be caused.
•Always power OFF and remove the GOT from the panel before starting replacement of
the battery. If this is not the case, electrical shock may be sustained.
•Never disassemble or modify the GOT. Disassembly or modification may cause failure,
malfunction or fire. For repair, please, contact a service representative.
Note:
Turn off the power, before connecting/disconnecting cables.
Connecting/disconnecting cables while the power is turned on will cause failure or
malfunction.
When repairing the backlight and liquid crystal screen, please, contact a service representative.
6.1 Battery Replacement
When the battery voltage drops, a control device (system information) set by the screen design software
turns ON. The control device interlocks with an auxiliary relay in the PLC. It is recommended to provide a
lamp while utilizing the output of the PLC so that voltage drop can be monitored outside the GOT.
For details of control devices, refer to the GOT-F900 Series Operation Manual.
Note:
For approximately one month after the control device (system information) for battery voltage
drop turns ON, the battery will back up the alarm history, sampling and the current time. When
the control device turns ON, replace the battery (PM-20BL) as soon as possible.
The screen data is stored in the flash memory, therefore, data will remain even after severe
battery voltage loss.
6.1.1 Replacement Procedure
1) Turn off the power to the GOT and remove the battery holder
cover.
2) Remove the existing battery from the battery holder, and
disconnect.
3) Within 30 seconds, connect a new battery.
4) Insert the new battery into the battery holder, and attach the
cover.
P M - 2 0 B L
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
opportunity loss or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For the detailed warranty, refer to the GOT-F900 Series HARDWARE MANUAL [CONNECTION].
Manual number : JY992D93901
Manual revision: E
Date: Sep. 2008
Page 7
F940WGOT Series (F940WGOT-TWD)
5 0 ( 1 . 9 6 " )
2 3 ( 0 . 9 1 " )
2 0 5 ( 8 . 0 7 " )
g )
5 ( 0 . 2 0 " ) o r l e s s
7 0 . 6 ( 2 . 7 8 )
h )
f )
1 0 ( 0 . 3 9 " )
d )
1 0 ( 0 . 3 9 " )
3 4 . 5 ( 1 . 3 5 " )
2 3 ( 0 . 9 1 " )
2 3 ( 0 . 9 1 " )
3 4 . 5 ( 1 . 3 5 " )
e )
1 4 3 ( 5 . 6 3 " )
1 3 3 ( 5 . 2 4 " )
c )
2 4V D C
Installation Manual
JY992D93901E
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the F940WGOT-TWD-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the
F940WGOT Series.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use that product in a safe and
co-ordinated manner in compliance to established safety practices.
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
Note:
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
2) Indicates that the identified danger could
damage.
•Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
•All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.
•Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Associated Manuals
Manual NameManual NumberDescription
F940WGOT Series
|
(F940GOT-TWD)
Installation Manual
GOT-F900
~
OPERATION MANUAL
(describes GT Designer2)
GOT-F900 Series
~
Operation Manual
GOT-F900 Series
~
Hardware Manual
(connection diagram)
GT Designer2 Version1
|
Operating Manual
GT Designer2 Version1
|
Reference Manual
GT Designer
|
Operating Manual
FX-PCS-DU/WIN-E
|
SOFTWARE MANUAL
JY997D93901
JY997D09101
(separate volume)
JY992D94701
(separate volume)
JY992D94801
(separate volume)
(PDF files on CDROM included with
product)
(PDF files on CDROM included with
product)
Included with the
screen creation
software
JY992D68301
(included with the
screen creation
software)
cause physical and property damage.
WILL
POSSIBLY
cause physical and property
Describes the specifications, wiring, and
installation of F940WGOT Series graphic
operation terminal. (hardware)
Describes the operation and use of the GOTF900 Series graphic operation terminals and GT
Designer2.
Describes the operation and use of the GOTF900 Series graphic operation terminals, GT
Designer and FX-PCS-DU/WIN-E.
Describes wiring and installation of the GOTF900 Series graphic operation terminals.
Describes the operation of GT Designer2
(SW*D5C-GTD2-E) and data transfer to the
GOT-900 Series.
Describes the specifications and setting of object
functions in GT Designer2 (SW*D5C-GTD2-E).
Describes the operation of GT Designer
(SW*D5C-GOTR-PACKE) and data transfer to
the GOT-900 Series. (Refer to the help file)
Describes the operation of FX-PCS-DU/WIN-E
screen creation software.
Manual NameManual NumberDescription
F9GT-40FMB
User’s Manual
~
Indispensable manual
|
Either manual is necessary.
Refer if necessary, please.
JY992D98601
This manual contains explanations for installation
and operating procedures of the F9GT-40FMB
data transfer adapter.
Refer to the Programming manual (ΙΙ) or relevant hardware manuals for details concerning the applicable
PLC.
1. Introduction
The F940WGOT series (hereafter called “GOT”) is to be
mounted on the face of a control panel or operations panel, and
connected to the programming port (CPU port) or the
communication port (communication port) of a PLC.
Various devices can be monitored and PLC data changed
through the GOT screens. Several display screens are built-in to
the GOT, and additional personalized screens can be created by
the user.
1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs
as well as a host of third party manufactured units. Further
information can be found in GOT-F900 Series Hardware
Manual.
2) PLC user programs can be downloaded, uploaded and monitored using programming software GXDeveloper or FX-PCS/WIN-E on a personal computer via the GOT. Further information can be found
in GOT-F900 Series Operation Manual.
3) Display screens are created using the following software:
Software NameVersion
GT Designer2
SWD5C-GTD2-E
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
SW5-F edition of SW5D5C-GOTR-PACKE (version 5.05F) or later
GOT-F900 Series (for Windows) screen creation software.
SW0PC-FXDU/WIN-E version 2.50 or later
1.1 Product Lists
Production NameDescription
F940WGOT-TWD-E Graphic operation terminal main unit
Communication cable (GOT ↔ CPU port in FX
2NC
FX
FX-50DU-CAB0
series PLC)
The connector on the GOT side is wired straight through.
Cable length is 3m (9' 10").
Communication cable (GOT ↔ CPU port in FX
2NC
FX
FX-50DU-CAB0/EN
series PLC)
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
Communication cable (GOT ↔ CPU port in FX
2NC
FX
series PLC)
FX-50DU-CAB0-**M
The connector on the GOT side is wired straight through.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),
30M: 30m (98' 5")
Communication cable (GOT ↔ CPU port in FX, FX
FX-40DU-CAB
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
Communication cable (GOT ↔ CPU port in FX, FX
FX-40DU-CAB-**M
The connector on the GOT side is wired straight through.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")
QC30R2
Communication cable (GOT ↔ CPU port in Q series PLC)
The connector on the GOT side wired straight through. Cable length is 3m (9' 10").
FX-232CAB-1Data exchange cable (GOT ↔ Personal computer <9-pin D-sub>)
PM-20BLBattery for Alarm history, sampling and current time data retention.
F9WGT-40PSCTransparent protection sheet for F940WGOT (5 pieces)
F9GT-40FMBData transfer adapter (Flash memory built in)
Caution
During abnormal communication (including cable breakages) ages when monitor within the
GOT, communication between the GOT and programmable controller CPU is interrupted. It is
impossible to operate switches or devices in the PLC through the GOT.
Communication and normal operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction.
P L C
P r o g r a m m i n g
p o r t
G O T
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
0
, FX0S, FX1S, FX0N, FX1N, FX2N or
2C
, A or QnA series PLC)
2C
, A or QnA series PLC)
Note;
•Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep
a safe distance of more than 100 mm from these wires.
•Operate touch switches on the display screen by hand.
DO NOT use excessive force, or attempt operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen.
1.2 Dimensions and Each Part Name
Dimensions: mm (inches)MASS (Weight): 1 kg (2.2 lbs)
Dielectric Withstand Voltage 500 V AC > 1 min, tested between power terminals and ground
Insulation Resistance5 MΩ > at 500 V DC, tested between power terminals and ground
GroundGrounding resistance 100 Ω or less. (Class D)
ProtectionIP 65F
Horizontal mounting: 0 ~ 50 °C (32 ~ 122 °F)
Vertical and flat mounting: 0 ~ 40 °C (32 ~ 104 °F)
Must be free of lamp black, corrosive gas, flammable gas, or excessive
amount of electroconductive dust particles and must be no direct
sunlight. (Same as for saving)
10 ~ 57 Hz: 0.075 mm Half Amplitude
57 ~ 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
10 ~ 57 Hz: 0.035 mm Half Amplitude
57 ~ 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
2
147m/s
Acceleration,
3 times in each direction X, Y, and Z
Page 8
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
2.2 Power Supply Specifications
b )
a )
c )
b )
a )
ItemsSpecifications
Power Supply Voltage24V DC, +10% -15%
Power Supply Ripple200 mV or less
Ratings: 650 mA at 24V DC
Current Consumption
750 mA at 24V DC or less when power supply is turned ON
400 mA at 24 V DC when backlight is turned OFF
FuseFuse built-in GOT (impossible to change)
Max. Allowable Momentary
Power Supply Failure period
1 ms; If less than 1 ms, the GOT will continue operation. If 1 ms or
more, the GOT will shut down.
BatteryBuilt-in, PM-20BL type lithium battery. (Approximately 5 years life)
User screen: 500 screens or less
System screen: Allocated screens No. 1001-1030.
User MemoryFlash memory 1MB (built-in)
•Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is
impossible to completely avoid this symptom, as the liquid crystal display comprises of a great
number of display elements.
Flickers may be observed depending on the display color.
Please note that these dots appear due to its characteristic and are not caused by product defect.
•When the same screen is displayed for a long time, an incidental color or partial discoloration is
generated on the screen due to heat damage, and it may not disappear.
•Using the GOT Backlight OFF function can prolong the life of the backlight.
For details on the Backlight OFF function, refer to the following.
GOT-F900 Series OPERATION MANUAL/GOT-F900 Series OPERATION MANUAL [GT Designer2
Version]
3. Installation
Note;
•Do not mount the GOT in an environment that contains dust, soot corrosive or conducive
dust, corrosive or flammable gas, or expose the unit to high temperatures, dew
condensation, direct sunlight, rain wind or impact and vibration.
If the GOT is used in such a place, electrical shock, fire, malfunction, damages or
deterioration may caused.
•Never drop cutting chips or electric wire chips into the ventilation window of the GOT
when drilling screw holes or performing wiring. Such chips may cause fire, failure or
malfunction.
•Turn off the power before securely connecting any cables. Poor connection may cause
malfunction.
The GOT is designed to be mounted in a panel. Install it using the following procedure:
1) Preparing the panel surface.
On the panel surface, cut a rectangular mounting slot of the
dimensions shown on the right.
At this time, space of 10 mm is required at each of the top and the
bottom of the slot, inside the panel for metal fixtures as shown in
“4) Dimensions required inside the panel for installation”.
S l o t t o b e c u t o n p a n e l
2 0 6 ( 8 . 1 1 " )
U n i t : m m ( i n c h e s )
+ 1 ( + 0 . 0 4 " )
0
Note
•Make sure that the thickness of the panel surface is no more than 5 mm (0.20").
5. Expansion Module (F9GT-40FMB)
F9GT-40FMB has a built-in flash memory and can transfer screen data when installed in the GOT.
2) Inserting the GOT into the panel surface
Attach the packing seal to the GOT, and insert the GOT from
the front face of the panel surface.
a) Packing seal
(When installed in the OS earlier than version 1.40, screen display is not available while transferring data
from F9GT-40FMB to the GOT.)
For the use methods and specifications, refer to the manual for F9GT-40FMB.
6. Maintenance
b) GOT
c) Mounting slot
Cautions:
•Correctly connect the battery for memory backup. Never charge, disassemble, heat, burn
or short-circuit the battery. If the battery is handled in such a way, or fire may be caused.
•Always power OFF and remove the GOT from the panel before starting replacement of
3) Fixing the GOT
Put hooks of the mounting brackets (supplied) in to the
mounting holes of the GOT. Tighten mounting bolts (also
supplied) until the GOT is securely fixed.
Fix mounting bolts in all four positions, above and below the
GOT.
a) Clamping bolt
b) Mounting bracket
Note:
Make sure to tighten the clamping bolts with a torque of 0.3 ~ 0.5 Nm.
When repairing the backlight and liquid crystal screen, please, contact a service representative.
6.1 Battery Replacement
When the battery voltage drops, a control device (system information) set by the screen design software
the battery. If this is not the case, electrical shock may be sustained.
•Never disassemble or modify the GOT. Disassembly or modification may cause failure,
malfunction or fire. For repair, please, contact a service representative.
Note:
Turn off the power, before connecting/disconnecting cables.
Connecting/disconnecting cables while the power is turned on will cause failure or
malfunction.
turns ON. The control device interlocks with an auxiliary relay in the PLC. It is recommended to provide a
lamp while utilizing the output of the PLC so that voltage drop can be monitored outside the GOT.
For details of control devices, refer to the GOT-F900 Series Operation Manual.
4) Dimensions required inside the panel
for installation.
When installing the GOT, make sure
that the inner dimensions shown on the
right are available.
a) PLC connection cable
b) Packing seal
"
2 2 5 ( 8 . 8 6 " )
1 4 3 ( 5 . 6 3 " )
a )
5 ( 0 . 2 0 " ) o r l e s s
7 0 . 6 ( 2 . 7 8
)
6.1.1 Replacement Procedure
b )
Note:
For approximately one month after the control device (system information) for battery voltage
drop turns ON, the battery will back up the alarm history, sampling and the current time. When
the control device turns ON, replace the battery (PM-20BL) as soon as possible.
The screen data is stored in the flash memory, therefore, data will remain even after severe
battery voltage loss.
1) Turn off the power to the GOT and remove the battery holder
cover.
2) Remove the existing battery from the battery holder, and
disconnect.
4. Power Supply Wiring
Caution:
3) Within 30 seconds, connect a new battery.
4) Insert the new battery into the battery holder, and attach the
cover.
Cut OFF all external phases of power source, before installation or wiring to avoid electric
shock or serious damage to the product.
P M - 2 0 B L
Note:
•Wire the power supply using electric wires of 0.75 mm2 or more so that voltage drop will
not occur. Use M3 size crimp style terminals. Securely tighten crimp-style terminals with a
torque of 0.5 ~ 0.8 Nm so that errors can be avoided.
•Insure correct termination of the DC power source, incorrect connection may result in unit
failure serious damage to the GOT.
•Attach a 2 A fuse to the 24V DC power supply.
•Perform Class D (100Ω or less) grounding with an electric wire of at least 1.25 mm
2
.
Never perform common grounding of the GOT and a strong power system.
Note
•Use an external power supply to provide 24V DC.
(The service power supply of the programmable controller cannot be used.)
•Even if instantaneous power interruption of less than 1 ms occurs, the GOT continues to
operate. When power interruption for a considerable period of time or voltage drop occurs,
the GOT stops its operation. However, when the power supply is recovered, the GOT
automatically restarts its operation. (The screen displayed just after recovery is
determined by the working environment originally set.)
+ 1 ( + 0 . 0 4 " )
0
( 4 . 8 8 " )
1 2 4
Grounding resistance
100Ω or less (class D)
24V DC external
power supply
Fuse (2A)
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
opportunity loss or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For the detailed warranty, refer to the GOT-F900 Series HARDWARE MANUAL [CONNECTION].
Manual number : JY992D93901
Manual revision: E
Date: Sep. 2008
24V DC
PLCGOT
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.