Mitsubishi iQ-RD77GF32, iQ-RD77GF4, iQ-RD77MS4, iQ-RD77MS8, iQ-RD77MS16 User Manual

...
MELSEC iQ-R Simple Motion Module User's Manual (Startup)
-RD77MS2 -RD77GF4
-RD77MS4 -RD77GF8
-RD77MS8 -RD77GF16
-RD77MS16 -RD77GF32

SAFETY PRECAUTIONS

WARNING
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
(Read these precautions before using this product.)
the product correctly.
The precautions given in this manual are concerned with this product only. Refer to the MELSEC iQ-R Module Configuration
Manual for a description of the PLC system safety precautions.
In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION".
Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious
consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
[Design Precautions]
WARNING
Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller. Failure to do so may result in an accident due to an incorrect output or malfunction. (1) Emergency stop circuits, protection circuits, and protective interlock circuits for conflicting
operations (such as forward/reverse rotations or upper/lower limit positioning) must be configured external to the programmable controller.
(2) When the programmable controller detects an abnormal condition, it stops the operation and all
outputs are:
• Turned off if the overcurrent or overvoltage protection of the power supply module is activated.
• Held or turned off according to the parameter setting if the self-diagnostic function of the CPU module detects an error such as a watchdog timer error.
(3) All outputs may be turned on if an error occurs in a part, such as an I/O control part, where the
CPU module cannot detect any error. To ensure safety operation in such a case, provide a safety mechanism or a fail-safe circuit external to the programmable controller. For a fail-safe circuit example, refer to "General Safety Requirements" in the MELSEC iQ-R Module Configuration Manual.
(4) Outputs may remain on or off due to a failure of a component such as a relay and transistor in an
output circuit. Configure an external circuit for monitoring output signals that could cause a serious accident.
In an output circuit, when a load current exceeding the rated current or an overcurrent caused by a load short-circuit flows for a long time, it may cause smoke and fire. To prevent this, configure an external safety circuit, such as a fuse.
Configure a circuit so that the programmable controller is turned on first and then the external power supply. If the external power supply is turned on first, an accident may occur due to an incorrect output or malfunction.
For the operating status of each station after a communication failure, refer to manuals relevant to the network. Incorrect output or malfunction due to a communication failure may result in an accident.
1
[Design Precautions]
WARNING
When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding. Improper operation may damage machines or cause accidents.
Especially, when a remote programmable controller is controlled by an external device, immediate action cannot be taken if a problem occurs in the programmable controller due to a communication failure. To prevent this, configure an interlock circuit in the program, and determine corrective actions to be taken between the external device and CPU module in case of a communication failure.
Do not write any data to the "system area" and "write-protect area" of the buffer memory in the module. Also, do not use any "use prohibited" signals as an output signal from the CPU module to each module. Doing so may cause malfunction of the programmable controller system. For the "system area", "write-protect area", and the "use prohibited" signals, refer to the user's manual for the module used.
If a communication cable is disconnected, the network may be unstable, resulting in a communication failure of multiple stations. Configure an interlock circuit in the program to ensure that the entire system will always operate safely even if communications fail. Failure to do so may result in an accident due to an incorrect output or malfunction.
To maintain the safety of the programmable controller system against unauthorized access from external devices via the network, take appropriate measures. To maintain the safety against unauthorized access via the Internet, take measures such as installing a firewall.
Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller. Failure to do so may result in an accident due to an incorrect output or malfunction. (1) Machine home position return is controlled by two kinds of data: a home position return direction
and a home position return speed. Deceleration starts when the proximity dog signal turns on. If an incorrect home position return direction is set, motion control may continue without deceleration. To prevent machine damage caused by this, configure an interlock circuit external to the programmable controller.
(2) When the module detects an error, the motion slows down and stops or the motion rapidly stops,
depending on the stop group setting in parameter. Set the parameter to meet the specifications of a positioning control system. In addition, set the home position return parameter and positioning data within the specified setting range.
(3) Outputs may remain on or off, or become undefined due to a failure of a component such as an
insulation element and transistor in an output circuit, where the module cannot detect any error. In a system that the incorrect output could cause a serious accident, configure an external circuit for monitoring output signals.
If safety standards (ex., robot safety rules, etc.,) apply to the system using the module, servo amplifier and servomotor, make sure that the safety standards are satisfied.
Construct a safety circuit externally of the module or servo amplifier if the abnormal operation of the module or servo amplifier differs from the safety directive operation in the system.
2
[Design Precautions]
WARNING
Do not remove the SSCNET cable while turning on the control circuit power supply of the module and servo amplifier. Do not see directly the light generated from SSCNET connector of the module or servo amplifier and the end of SSCNET cable. When the light gets into eyes, you may feel something wrong with eyes. (The light source of SSCNET complies with class1 defined in JISC6802 or IEC60825-1.)
[Design Precautions]
CAUTION
Do not install the control lines or communication cables together with the main circuit lines or power cables. Keep a distance of 100 mm or more between them. Failure to do so may result in malfunction due to noise.
During control of an inductive load such as a lamp, heater, or solenoid valve, a large current (approximately ten times greater than normal) may flow when the output is turned from off to on. Therefore, use a module that has a sufficient current rating.
After the CPU module is powered on or is reset, the time taken to enter the RUN status varies depending on the system configuration, parameter settings, and/or program size. Design circuits so that the entire system will always operate safely, regardless of the time.
Do not power off the programmable controller or reset the CPU module while the settings are being written. Doing so will make the data in the flash ROM and SD memory card undefined. The values need to be set in the buffer memory and written to the flash ROM and SD memory card again. Doing so also may cause malfunction or failure of the module.
When changing the operating status of the CPU module from external devices (such as the remote RUN/STOP functions), select "Do Not Open by Program" for "Opening Method" of "Module Parameter". If "Open by Program" is selected, an execution of the remote STOP function causes the communication line to close. Consequently, the CPU module cannot reopen the line, and external devices cannot execute the remote RUN function.
[Installation Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
3
[Installation Precautions]
CAUTION
Use the programmable controller in an environment that meets the general specifications in the Safety Guidelines included with the base unit. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To mount a module, place the concave part(s) located at the bottom onto the guide(s) of the base unit, and push in the module until the hook(s) located at the top snaps into place. Incorrect interconnection may cause malfunction, failure, or drop of the module.
To mount a module with no module fixing hook, place the concave part(s) located at the bottom onto the guide(s) of the base unit, push in the module, and fix it with screw(s). Incorrect interconnection may cause malfunction, failure, or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the module with a screw.
Tighten the screws within the specified torque range. Undertightening can cause drop of the screw, short circuit, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
When using an extension cable, connect it to the extension cable connector of the base unit securely. Check the connection for looseness. Poor contact may cause malfunction.
When using an SD memory card, fully insert it into the SD memory card slot. Check that it is inserted completely. Poor contact may cause malfunction.
Securely insert an extended SRAM cassette into the cassette connector of the CPU module. After insertion, close the cassette cover and check that the cassette is inserted completely. Poor contact may cause malfunction.
Do not directly touch any conductive parts and electronic components of the module, SD memory card, extended SRAM cassette, or connector. Doing so can cause malfunction or failure of the module.
[Wiring Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before installation and wiring. Failure to do so may result in electric shock or cause the module to fail or malfunction.
After installation and wiring, attach a blank cover module (RG60) to each empty slot and an included extension connector protective cover to the unused extension cable connector before powering on the system for operation. Failure to do so may result in electric shock.
4
[Wiring Precautions]
CAUTION
Individually ground the FG and LG terminals of the programmable controller with a ground resistance of 100 ohms or less. Failure to do so may result in electric shock or malfunction.
Use a solderless terminal with an insulation sleeve for terminal block wiring. Note that up to two solderless terminals can be connected per terminal block.
Use applicable solderless terminals and tighten them within the specified torque range. If any spade solderless terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
Check the rated voltage and signal layout before wiring to the module, and connect the cables correctly. Connecting a power supply with a different voltage rating or incorrect wiring may cause fire or failure.
Connectors for external devices must be crimped or pressed with the tool specified by the manufacturer, or must be correctly soldered. Incomplete connections may cause short circuit, fire, or malfunction.
Securely connect the connector to the module. Poor contact may cause malfunction.
Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100 mm or more between them. Failure to do so may result in malfunction due to noise.
When an overcurrent caused by an error of an external device or a failure of a module flows for a long time, it may cause smoke and fire. To prevent this, configure an external safety circuit, such as a fuse.
Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or cables or malfunction due to poor contact. Do not clamp the extension cables with the jacket stripped. Doing so may change the characteristics of the cables, resulting in malfunction.
When disconnecting the communication cable or power cable from the module, do not pull the cable by the cable part. For the cable connected to the terminal block, loosen the terminal screws. Pulling the cable connected to the module may result in malfunction or damage to the module or cable.
Check the interface type and correctly connect the cable. Incorrect wiring (connecting the cable to an incorrect interface) may cause failure of the module and external device.
Tighten the terminal screws or connector screws within the specified torque range. Undertightening can cause drop of the screw, short circuit, fire, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, fire, or malfunction.
Tighten the terminal block mounting screws, terminal screws, and module fixing screws within each specified torque range. Undertightening of the terminal block mounting screws and terminal screws can cause short circuit, fire, or malfunction. Overtightening of them can damage the screw and/or module, resulting in drop, short circuit, or malfunction. Undertightening of the module fixing screws can cause drop of the screw. Overtightening of them can damage the screw and/or module, resulting in drop.
When disconnecting the cable from the module, do not pull the cable by the cable part. For the cable with connector, hold the connector part of the cable. For the cable connected to the terminal block, loosen the terminal screw. Pulling the cable connected to the module may result in malfunction or damage to the module or cable.
5
[Wiring Precautions]
CAUTION
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction.
A protective film is attached to the top of the module to prevent foreign matter, such as wire chips, from entering the module during wiring. Do not remove the film during wiring. Remove it for heat dissipation before system operation.
Programmable controllers must be installed in control panels. Connect the main power supply to the power supply module in the control panel through a relay terminal block. Wiring and replacement of a power supply module must be performed by qualified maintenance personnel with knowledge of protection against electric shock. For wiring, refer to the MELSEC iQ-R Module Configuration Manual.
For Ethernet cables to be used in the system, select the ones that meet the specifications in this manual. If not, normal data transmission is not guaranteed.
[Startup and Maintenance Precautions]
WARNING
Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction.
Correctly connect the battery connector. Do not charge, disassemble, heat, short-circuit, solder, or
throw the battery into the fire. Also, do not expose it to liquid or strong shock. Doing so will cause the battery to produce heat, explode, ignite, or leak, resulting in injury and fire.
Shut off the external power supply (all phases) used in the system before cleaning the module or retightening the terminal screws, connector screws, or module fixing screws. Failure to do so may result in electric shock.
[Startup and Maintenance Precautions]
CAUTION
When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding. Improper operation may damage machines or cause accidents.
Especially, when a remote programmable controller is controlled by an external device, immediate action cannot be taken if a problem occurs in the programmable controller due to a communication failure. To prevent this, configure an interlock circuit in the program, and determine corrective actions to be taken between the external device and CPU module in case of a communication failure.
Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone
System) more than 25 cm away in all directions from the programmable controller. Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may cause the module to fail or malfunction.
6
[Startup and Maintenance Precautions]
CAUTION
Tighten the screws within the specified torque range. Undertightening can cause drop of the component or wire, short circuit, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
After the first use of the product, do not mount/remove the module to/from the base unit, and the terminal block to/from the module, and do not insert/remove the extended SRAM cassette to/from the CPU module more than 50 times (IEC 61131-2 compliant) respectively. Exceeding the limit may cause malfunction.
After the first use of the product, do not insert/remove the SD memory card to/from the CPU module more than 500 times. Exceeding the limit may cause malfunction.
Do not touch the metal terminals on the back side of the SD memory card. Doing so may cause malfunction or failure of the module.
Do not touch the integrated circuits on the circuit board of an extended SRAM cassette. Doing so may cause malfunction or failure of the module.
Do not drop or apply shock to the battery to be installed in the module. Doing so may damage the battery, causing the battery fluid to leak inside the battery. If the battery is dropped or any shock is applied to it, dispose of it without using.
Startup and maintenance of a control panel must be performed by qualified maintenance personnel with knowledge of protection against electric shock. Lock the control panel so that only qualified maintenance personnel can operate it.
Before handling the module, touch a conducting object such as a grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or malfunction.
Before testing the operation, set a low speed value for the speed limit parameter so that the operation can be stopped immediately upon occurrence of a hazardous condition.
Confirm and adjust the program and each parameter before operation. Unpredictable movements may occur depending on the machine.
When using the absolute position system function, on starting up, and when the module or absolute position motor has been replaced, always perform a home position return.
Before starting the operation, confirm the brake function.
Do not perform a megger test (insulation resistance measurement) during inspection.
After maintenance and inspections are completed, confirm that the position detection of the absolute
position detection function is correct.
Lock the control panel and prevent access to those who are not certified to handle or install electric equipment.
7
[Operating Precautions]
CAUTION
When changing data and operating status, and modifying program of the running programmable controller from an external device such as a personal computer connected to an intelligent function module, read relevant manuals carefully and ensure the safety before operation. Incorrect change or modification may cause system malfunction, damage to the machines, or accidents.
Do not power off the programmable controller or reset the CPU module while the setting values in the buffer memory are being written to the flash ROM in the module. Doing so will make the data in the flash ROM and SD memory card undefined. The values need to be set in the buffer memory and written to the flash ROM and SD memory card again. Doing so also may cause malfunction or failure of the module.
Note that when the reference axis speed is specified for interpolation operation, the speed of the partner axis (2nd, 3rd, or 4th axis) may exceed the speed limit value.
Do not go near the machine during test operations or during operations such as teaching. Doing so may lead to injuries.
[Disposal Precautions]
CAUTION
When disposing of this product, treat it as industrial waste.
When disposing of batteries, separate them from other wastes according to the local regulations. For
details on battery regulations in EU member states, refer to the MELSEC iQ-R Module Configuration Manual.
[Transportation Precautions]
CAUTION
When transporting lithium batteries, follow the transportation regulations. For details on the regulated models, refer to the MELSEC iQ-R Module Configuration Manual.
The halogens (such as fluorine, chlorine, bromine, and iodine), which are contained in a fumigant used for disinfection and pest control of wood packaging materials, may cause failure of the product. Prevent the entry of fumigant residues into the product or consider other methods (such as heat treatment) instead of fumigation. The disinfection and pest control measures must be applied to unprocessed raw wood.
8

CONDITIONS OF USE FOR THE PRODUCT

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.
9

INTRODUCTION

Thank you for purchasing the Mitsubishi Electric MELSEC iQ-R series programmable controllers.
This manual describes the specifications, procedures before operation and wiring of the relevant products listed below. Before
using this product, please read this manual and the relevant manuals carefully and develop familiarity with the functions and
performance of the MELSEC iQ-R series programmable controller to handle the product correctly.
When applying the program examples provided in this manual to an actual system, ensure the applicability and confirm that it
will not cause system control problems.
Please make sure that the end users read this manual.
Relevant products
RD77MS2, RD77MS4, RD77MS8, RD77MS16
RD77GF4, RD77GF8, RD77GF16, RD77GF32
Symbols used in this manual are shown below.
A serial No. is inserted in the "**" mark.
• [Pr.**]: Symbols indicating positioning parameter or home position return parameter items
• [Da.**]: Symbols indicating positioning data or block start data items
• [Md.**]: Symbols indicating monitor data items
• [Cd.**]: Symbols indicating control data items
• [RD77MS]: Symbols indicating that it corresponds to only RD77MS
• [RD77GF]: Symbols indicating that it corresponds to only RD77GF

COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES

Method of ensuring compliance
To ensure that Mitsubishi programmable controllers maintain EMC and Low Voltage Directives when incorporated into other
machinery or equipment, certain measures may be necessary. Please refer to one of the following manuals.
MELSEC iQ-R Module Configuration ManualSafety Guidelines (This manual is included with the base unit.)
The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives.
Additional measures
To ensure that this product maintains EMC and Low Voltage Directives, please refer to one of the following manuals.
MELSEC iQ-R Module Configuration ManualSafety Guidelines (This manual is included with the base unit.)
10

CONTENTS

SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
CONDITIONS OF USE FOR THE PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
RELEVANT MANUALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
TERMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
PERIPHERALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
CHAPTER 1 PART NAMES 18
1.1 LED Display Specifications of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.2 LED Display Specifications of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CHAPTER 2 SPECIFICATIONS 22
2.1 Performance Specifications of the RD77MS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.2 Performance Specifications of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3 Specifications of Interfaces with External Devices of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Electrical specifications of input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
2.4 External Circuit Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
CHAPTER 3 FUNCTION LIST 31
3.1 Control Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Main functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Sub functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Common functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.2 Combination of Main Functions and Sub Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.3 List of RD77GF Network Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Function list of CC-Link IE Field Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
CHAPTER 4 PROCEDURES BEFORE OPERATIONS 45
4.1 Procedures before Operation of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2 Procedures before Operation of the RD77GF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
CHAPTER 5 NETWORK CONFIGURATION OF RD77GF 49
CONTENTS
5.1 CC-Link IE Field Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
5.2 Precautions for System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
CHAPTER 6 WIRING 54
6.1 Wiring of the RD77MS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
6.2 External Input Connection Connector of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Signal layout for external input connection connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
List of input signal details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Interface internal circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.3 Wiring of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
CHAPTER 7 OPERATION EXAMPLES 68
11
7.1 Operation Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
7.2 Communication Examples of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
APPENDICES 88
Appendix 1 Component List of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Reference product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Appendix 2 Component List of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Reference product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Recommended product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Appendix 3 Connection with External Devices of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
External input signal cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Appendix 4 External Dimensions of the RD77MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Appendix 5 External Dimensions of the RD77GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
INDEX 108
REVISIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
TRADEMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
12

RELEVANT MANUALS

Manual name [manual number] Description Available form
MELSEC iQ-R Simple Motion Module User's Manual (Startup) [IB-0300245ENG] (This manual)
MELSEC iQ-R Simple Motion Module User's Manual (Application) [IB-0300247ENG]
MELSEC iQ-R Simple Motion Module User's Manual (Advanced Synchronous Control) [IB-0300249ENG]
MELSEC iQ-R Simple Motion Module User's Manual (Network) [IB-0300307ENG]
This manual does not include detailed information on the followings:
• General specifications
• Available CPU modules and the number of mountable modules
• Installation
For details, refer to the following. MELSEC iQ-R Module Configuration Manual
This manual does not include information on the module function blocks.For details, refer to the Function Block Reference for
the module used.
Specifications, procedures before operation, system configuration, wiring, and operation examples of the Simple Motion module
Functions, input/output signals, buffer memory, parameter settings, programming, and troubleshooting of the Simple Motion module
Functions and programming for the synchronous control of the Simple Motion module
Functions, parameter settings, troubleshooting, and buffer memory of CC-Link IE Field Network
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
e-Manual refers to the Mitsubishi Electric FA electronic book manuals that can be browsed using a dedicated
tool.
e-Manual has the following features:
• Required information can be cross-searched in multiple manuals.
• Other manuals can be accessed from the links in the manual.
• The hardware specifications of each part can be found from the product figures.
• Pages that users often browse can be bookmarked.
• Sample programs can be copied to an engineering tool.
13

TERMS

Unless otherwise specified, this manual uses the following terms.
Term Description
2-axis module A generic term for RD77MS2
4-axis module A generic term for RD77MS4 and RD77GF4
8-axis module A generic term for RD77MS8 and RD77GF8
16-axis module A generic term for RD77MS16 and RD77GF16
32-axis module A generic term for RD77GF32
Axis Another term for a servo amplifier
Buffer memory A memory in an intelligent function module, where data (such as setting values and monitoring values) are stored. When
CC-Link IE Field Network A high-speed and large-capacity open field network that is based on Ethernet (1000BASE-T)
CPU module The abbreviation for the MELSEC iQ-R series CPU module
CPU module (built-in Ethernet port part)
Cyclic transmission A function by which data are periodically exchanged among stations on the network using link devices
Data link A generic term for cyclic transmission and transient transmission
Dedicated instruction An instruction for using functions of the module
Device A device (X, Y, M, D, or others) in a CPU module
Disconnection A process of stopping data link if a data link error occurs
Engineering tool A generic term for GX Works2, GX Works3, and MR Configurator2
Ethernet device A generic term for the devices supporting IP communication (such as personal computers)
Global label A label that is enabled for all program data when creating multiple program data in the project. There are two types of
GX Works2 The product name of the software package for the MELSEC programmable controllers
GX Works3
Intelligent device station A station that exchanges I/O signals (bit data) and I/O data (word data) with another station by cyclic transmission. This
Intelligent function module A MELSEC iQ-R series module that has functions other than input and output, such as an A/D converter module and D/
Label A label that represents a device in a given character string
Link device A device (RX, RY, RWr, or RWw) in a module on CC-Link IE Field Network
Link refresh Automatic data transfer between a link device of the Simple Motion module and a device in a CPU module
Link scan (link scan time) Time required for all the stations on the network to transmit data. The link scan time depends on data volume and the
Link special register (SW) Word data that indicates the operating status and data link status of a module on CC-Link IE Field Network
Link special relay (SB) Bit data that indicates the operating status and data link status of a module on CC-Link IE Field Network
Local station A station that performs cyclic transmission and transient transmission with the master station and other local stations
Master station A station that controls the entire network. This station can perform cyclic transmission and transient transmission with all
Master/local module A generic term for the following modules when the CC-Link IE Field Network function is used:
Module label A label that represents one of memory areas (I/O signals and buffer memory areas) specific to each module in a given
MR Configurator2 The product name of the setup software for the servo amplifier
MR-J3(W)-B MR-J3-_B_(-RJ)/MR-J3W-_B Servo amplifier series
MR-J4(W)-B MR-J4-_B_(-RJ)/MR-J4W_-_B Servo amplifier series
MR-J4-B-RJ MR-J4-_B_-RJ Servo amplifier series
MR-J4-GF MR-J4-_GF_(-RJ) Servo amplifier series
MR-JE-B(F) MR-JE-_B/MR-JE-_BF Servo amplifier series
using the CPU module, the memory is indicated for storing data (such as setting values and monitored values) of the Ethernet function and data used for data communication of the multiple CPU function.
A built-in Ethernet port part of the CPU module (CPU part for the RnENCPU) (MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup))
global labels: module label that is automatically generated by GX Works2 and GX Works3 and label that can be created for the any of the specified devices.
station responds to a transient transmission request from another station and also issues a transient transmission request to another station.
A converter module
number of transient transmission requests.
stations. Only one master station can be used in a network.
• RJ71GF11-T2
• RJ71EN71
• RnENCPU
character string. GX Works2 and GX Works3 automatically generate this label, which can be used as a global label.
14
Ter m Description
Network module A generic term for the following modules:
RAS The abbreviation for Reliability, Availability, and Serviceability. This term refers to usability of automated equipment.
RD77GF Another term for the MELSEC iQ-R series Simple Motion module (compatible with CC-Link IE Field Network)
RD77MS Another term for the MELSEC iQ-R series Simple Motion module (compatible with SSCNET/H)
Relay station A station that includes two or more network modules. Data are passed through this station to stations on other networks
Remote device station A station that exchanges I/O signals (bit data) and I/O data (word data) with another station by cyclic transmission. This
Remote I/O station A station that exchanges I/O signals (bit data) with the master station by cyclic transmission
Remote input (RX) Bit data input from a slave station to the master station (For some areas in a local station, data are input in the opposite
Remote output (RY) Bit data output from the master station to a slave station (For some areas in a local station, data are output in the
Remote register (RWr) Word data input from a slave station to the master station (For some areas in a local station, data are input in the
Remote register (RWw) Word data output from the master station to a slave station (For some areas in a local station, data are output in the
Reserved station A station reserved for future use. This station is not actually connected, but counted as a connected station.
Return A process of restarting data link when a station recovers from an error
RnENCPU A generic term for the R04ENCPU, R08ENCPU, R16ENCPU, R32ENCPU, and R120ENCPU
Safety communications A function to exchange safety data between safety stations on the same network
Safety connection A connection established for safety communications
Safety CPU A generic term for the R08SFCPU, R16SFCPU, R32SFCPU, and R120SFCPU
Safety data Data exchanged through safety communications
Safety station A generic term for a station that performs safety communications and standard communications
Servo amplifier A generic term for a drive unit
Simple Motion module The abbreviation for the MELSEC iQ-R series Simple Motion module
Slave station A generic term for a local station, remote I/O station, remote device station, and intelligent device station
SSCNET
SSCNET/H
Transient transmission A function of communication with another station, which is used when requested by a dedicated instruction or the
*1
*1
• Ethernet interface module
• CC-Link IE Controller Network module
• Module on CC-Link IE Field Network
• MELSECNET/H network module
• MELSECNET/10 network module
• RnENCPU (network part)
station responds to a transient transmission request from another station.
direction.)
opposite direction.)
opposite direction.)
opposite direction.)
Unless specified in particular, indicates the motor driver unit of the sequential command method which is controlled by the Simple Motion module (belonging to own station).
High speed synchronous communication network between RD77MS and servo amplifier
engineering tool
*1 SSCNET: Servo System Controller NETwork
15

PERIPHERALS

RD77MS4
ERRRUN
AX
3
4
2
1
AX
SSCNET
µ
cable
External input signal cable
Synchronous encoder via servo amplifier: Q171ENC-W8 (Up to 4 modules via MR-J4-B-RJ), etc.
RD77MS
• Upper stroke limit
• Lower stroke limit
• Proximity dog
External input signals of servo amplifier
Manual pulse generator/ Incremental synchronous encoder × 1
Assigning the external input signals for 20 points to any of the following signals.
External command signal/Switching
signal
Upper stroke limit
Lower stroke limit
• Proximity dog
signal
Stop signal
Forced stop input (24 V DC)
Servo motor
Servo motor
Servo motor
MR-J4(W)-B servo amplifier MR-J3(W)-B servo amplifier MR-JE-B(F) servo amplifier Optical hub unit MR-MV200 Inverter FR-A700 series/FR-A800 series Stepping motor driver AlphaStep/5-phase manufactured by ORIENTAL MOTOR Co., Ltd. Servo driver VC´ series/VPH series manufactured by CKD NIKKI DENSO CO., LTD.
IAI electric actuator controller manufactured by IAI Corporation
RD77MS2: Up to 2 axes RD77MS4: Up to 4 axes RD77MS8: Up to 8 axes RD77MS16: Up to 16 axes
The following figure shows the peripherals when the RD77MS is used.
16
• The external input signal cannot be used depending on the connected device. Confirm the specification of
the connected device.
• When using RD77MS2, the external input signals that can be assigned are for 10 points.
The following figure shows the peripherals when the RD77GF is used.
RD77GF4
ERRRUN
AX1-4 D LINK SD/RD
L ERR
L ER
LINK
RD77GF4: Up to 4 axes RD77GF8: Up to 8 axes RD77GF16: Up to 16 axes RD77GF32: Up to 32 axes
MR-J4-GF servo amplifier (Motion mode)
Servo motor
Servo motor
Servo motor
MR-J4-GF
servo amplifier
(I/O mode)
Servo motor
Another brand
drive unit
Remote I/OLocal station
CC-Link IE Field Network cable
RD77GF
Switching hub
• Upper stroke limit
• Lower stroke limit
• Proximity dog
External input signals of servo amplifier
Synchronous encoder via servo amplifier: Q171ENC-W8 (via MR-J4-_GF_-RJ)
• The external input signal cannot be used depending on the connected device. Confirm the specification of
the connected device.
17
1 PART NAMES
RD77MS16
ERRRUN
AX1-16
RD77MS8
ERRRUN
AX1-8
RD77MS4
ERRRUN
AX
3
4
2
1
AX
RD77MS2
ERRRUN
2
1
AX
(6)
(4)
(5)
(1)
(2)
(3)
(2)
(3)
(1)
(4)
(6)
(5)
(6)
(5)
(4)
(2)
(3)
(1)
(3)
(2)
(3)
(1)
(4)
(6)
(5)
RD77MS2 RD77MS4 RD77MS8 RD77MS16
This chapter describes the part names of the Simple Motion module.
No. Name Description
(1) RUN LED For details, refer to the following.
(2) ERR LED
(3) Axis display LED
(4) External input connection connector Connects to a mechanical system input, manual pulse generator/incremental synchronous encoder, or
(5) SSCNET cable connector Connects to a servo amplifier.
(6) Serial No. marking Shows the serial No. printed on the rating plate.
Page 20 LED Display Specifications of the RD77MS
forced stop input. For the signal layout, refer to the following. Page 26 Specifications of Interfaces with External Devices of the RD77MS
18

1 PART NAMES

No. Name Description
RD77GF4
ERRRUN
AX1-4
D LINK
SD/RD
L ERR
L ER
LINK
RD77GF8
ERRRUN
AX1-8
D LINK
SD/RD L ERR
L ER
LINK
RD77GF16
ERRRUN
AX1-16
D LINK
SD/RD
L ERR
L ER
LINK
RD77GF32
ERRRUN
AX1-32
D LINK
SD/RD
L ERR
L ER
LINK
RD77GF4 RD77GF8 RD77GF16
(2)
(3) (4)
(8)
(7)
(1)
(5) (6)
(9)
(2)
(3) (4)
(8)
(7)
(1)
(5) (6)
(9)
(2)
(3) (4)
(8)
(7)
(1)
(5) (6)
(9)
RD77GF32
(2)
(3) (4)
(8)
(7)
(1)
(5) (6)
(9)
(1) RUN LED For details, refer to the following.
(2) ERR LED
(3) Axis display LED
(4) D LINK LED
(5) SD/RD LED
(6) L ERR LED
(7) LEDs for CC-Link IE Field connector
(8) Connector for CC-Link IE Field Network
cable
(9) Serial No. marking Shows the serial No. printed on the rating plate.
Page 21 LED Display Specifications of the RD77GF
Connects to a slave station. In the following manual, this connector is referred to as "PORT2", "P2", or "Port 2". MELSEC iQ-R Simple Motion Module User's Manual (Network)
1
1 PART NAMES
19
1.1 LED Display Specifications of the RD77MS
This section lists the LED display specifications of the RD77MS.
: OFF, : ON, : Flashing
Simple Motion module status
Normal operation RUN
Operation failure RUN
Online module change RUN
LED display Description
ERR
RUN ERR
ERR
RUN ERR
ERR
RUN ERR
AX1 AX2 AX3 AX4
AX1-8
AX1-16
AX1 AX2 AX3 AX4
AX1-8
AX1-16
AX1 AX2 AX3 AX4
AX1-8
AX1-16
AX1 AX2 AX3 AX4
AX1-8
AX1-16
AX1 AX2 AX3 AX4
AX1-8
AX1-16
AX1 AX2 AX3 AX4
AX1-8
AX1-16
*1
*1
*2
*2
*3
*3
The axes stopped The axes on standby
The axis in operation
Minor error
Moderate error Watchdog timer error
Module remove selection in operation
Module change in operation
*1 When all axes are stopped or on standby, the AX LED turns OFF. *2 When any of the axes is in operation, the AX LED turns ON. *3 When an error occurs in any of the axes, the AX LED is flashing.
1 PART NAMES
20

1.1 LED Display Specifications of the RD77MS

1.2 LED Display Specifications of the RD77GF
This section lists the LED display specifications of the RD77GF.
Simple Motion module status
Normal operation RUN
Operation failure RUN
LED display Description
*1
ERR
RUN ERR
ERR
RUN ERR
RUN ERR
RUN ERR
AX1-4
*1
AX1-8
AX1-16
AX1-32
AX1-4
AX1-8
AX1-16
AX1-32
AX1-4
AX1-8
AX1-16
AX1-32
AX1-4
AX1-8
AX1-16
AX1-32
AX1-4 Flashing (500 ms interval): A data link faulty station detected
AX1-8
AX1-16
AX1-32
AX1-4 Major error
AX1-8
AX1-16
AX1-32
*1
*1
*2
*2
*2
*2
*3
*3
*3
*3
*4
*4
*4
*4
The axes stopped The axes on standby
The axis in operation
Minor error (related to axis)
Minor error (general)
Flashing (200 ms interval): Moderate error
1
: OFF, : ON, : Flashing
*1 When all axes are stopped or on standby, the AX LED turns OFF. *2 When any of the axes is in operation, the AX LED turns ON. *3 When an error occurs in any of the axes, the AX LED is flashing. *4 The AX LED does not turn OFF when the axis is in operation or a minor error (related to axis) has occurred.
Status LED display Description
Indicates the data link status. D LINK
D LINK
D LINK
Indicates the data sending/receiving status.
Indicates the receive data and line error status.
Indicates the port status. L ER Abnormal data received
Indicates the link status. LINK Link-up
SD/RD Data being sent or received
SD/RD Data not sent nor received
L ERR Abnormal data received
L ERR Normal data received
L ER Normal data received
LINK Link-down
*1
*1
*1
Data link (cyclic transmission being performed)
Data link (cyclic transmission stopped)
Data link not performed (disconnection)
: OFF, : ON, : Flashing
*1 The LED is always OFF in offline mode.
1 PART NAMES

1.2 LED Display Specifications of the RD77GF

21
2 SPECIFICATIONS
This chapter describes the performance specifications of the RD77MS and the RD77GF.
2.1 Performance Specifications of the RD77MS
This section lists the performance specifications of the RD77MS.
Item RD77MS2 RD77MS4 RD77MS8 RD77MS16
Number of controlled axes 2 axes 4 axes 8 axes 16 axes
Operation cycle 0.444 ms/0.888 ms/1.777 ms/3.555 ms
Interpolation function 2-axis linear
interpolation, 2-axis circular interpolation
Control method PTP (Point To Point) control, path control (linear, arc, and helix can be set), speed control, speed-
position switching control, position-speed switching control, speed-torque control
Control unit mm, inch, degree, pulse
Positioning data 600 data/axis (The 101st data to the 600th data can be set only with the engineering tool.)
Execution data backup function Parameters, positioning data, and block start data can be saved on flash ROM. (battery-less backup)
Positioning Positioning system PTP control: Incremental system/absolute system
Speed-position switching control: Incremental system/absolute system Position-speed switching control: Incremental system Path control: Incremental system/absolute system
Positioning range In absolute system
• -214748364.8 to 214748364.7 (m)
• -21474.83648 to 21474.83647 (inch)
• 0 to 359.99999 (degree)
• -2147483648 to 2147483647 (pulse)
In incremental system
• -214748364.8 to 214748364.7 (m)
• -21474.83648 to 21474.83647 (inch)
• -21474.83648 to 21474.83647 (degree)
• -2147483648 to 2147483647 (pulse)
In speed-position switching control (INC mode)/position-speed switching control
• 0 to 214748364.7 (m)
• 0 to 21474.83647 (inch)
• 0 to 21474.83647 (degree)
• 0 to 2147483647 (pulse) In speed-position switching control (ABS mode) 0 to 359.99999 (degree)
Speed command 0.01 to 20000000.00 (mm/min)
0.001 to 2000000.000 (inch/min)
0.001 to 2000000.000 (degree/min) 1 to 1000000000 (pulse/s)
Acceleration/deceleration process Trapezoidal acceleration/deceleration, S-curve acceleration/deceleration
Acceleration/deceleration time 1 to 8388608 (ms) (Four patterns can be set for each of acceleration time and deceleration time.)
Rapid stop deceleration time 1 to 8388608 (ms)
2-, 3-, or 4-axis linear interpolation, 2-axis circular interpolation, 3-axis helical interpolation
*1
*2
22

2 SPECIFICATIONS

2.1 Performance Specifications of the RD77MS

Item RD77MS2 RD77MS4 RD77MS8 RD77MS16
Starting time*3Operation cycle
External wiring connection system 40-pin connector
Applicable wire size
External input wiring connector A6CON1, A6CON2, A6CON4 (sold separately)
Manual pulse generator/ Incremental synchronous encoder input maximum frequency
Manual pulse generator 1 pulse input magnification 1 to 10000 times
Flash ROM write count Max. 100000 times
Number of occupied I/O points 32 points (I/O assignment: Intelligent function module 32 points)
Internal current consumption (5 V DC) 1.0 A
External dimensions
Mass 0.22 kg 0.23 kg
0.444 ms
Operation cycle
0.888 ms
Operation cycle
1.777 ms
Operation cycle
3.555 ms
When A6CON1 or A6CON4 is used 0.088 to 0.3 mm2 (AWG28 to AWG22) stranded wire
*4
When A6CON2 is used 0.088 to 0.24 mm
Height 106 mm (4.17 inch)
Width 27.8mm (1.09inch)
Depth 110 mm (4.33 inch)
Maximum number of axes: 1 axis
Maximum number of axes: 2 axes
Maximum number of axes: 4 axes
Maximum number of axes: 4 axes
Maximum number of axes: 8 axes
Maximum number of axes: 12 axes
Maximum number of axes: 8 axes
Maximum number of axes: 12 axes
Maximum number of axes: 16 axes
Maximum number of axes: 8 axes
Maximum number of axes: 12 axes
Maximum number of axes: 16 axes
Differential-output type
Open-collector type
0.7 ms
0.7 ms
0.74 ms
1.1 ms
1.32 ms
1.46 ms
1.1 ms
1.46 ms
1.59 ms
0.92 ms
1.12 ms
1.52 ms
Up to 1 Mpulses/s
Up to 200 kpulses/s
2
(AWG28 to AWG24) stranded wire
*1 The speed-position switching control (ABS mode) can be used only when the control unit is "degree". *2 When "Speed control 10 multiplier setting for degree axis function" is valid, the setting range is 0.01 to 20000000.00 (degree/min). *3 Time from accepting the positioning start signal until BUSY signal turns ON. *4 Use cables with outside diameter of 1.3 mm (0.05 inch) or shorter to connect 40 cables to the connector. In addition, consider the
amount of current to be used and select appropriate cables.
2
2 SPECIFICATIONS
2.1 Performance Specifications of the RD77MS
23
2.2 Performance Specifications of the RD77GF
This section lists the performance specifications of the RD77GF.
Item RD77GF4 RD77GF8 RD77GF16 RD77GF32
Number of controlled axes 4 axes 8 axes 16 axes 32 axes
Operation cycle 0.50 ms/1.00 ms/2.00 ms/4.00 ms
Interpolation function 2-, 3-, or 4-axis linear interpolation
2-axis circular interpolation 3-axis helical interpolation
Control method PTP (Point To Point) control, path control (linear, and arc can be set), speed control, speed-position
Control unit mm, inch, degree, pulse
Positioning data 600 data/axis (All the data points can be set with the buffer memory.)
Execution data backup function Parameters, positioning data, and block start data can be saved on flash ROM. (battery-less backup)
Positioning Positioning system PTP control: Incremental system/absolute system
Positioning range In absolute system
Speed command 0.01 to 20000000.00 (mm/min)
Acceleration/deceleration process Trapezoidal acceleration/deceleration, S-curve acceleration/deceleration
Acceleration/deceleration time 1 to 8388608 (ms) (Four patterns can be set for each of acceleration time and deceleration time.)
Rapid stop deceleration time 1 to 8388608 (ms)
Starting time 0.2 ms to 5.0 ms
Manual pulse generator
Flash ROM write count Max. 100000 times
Number of occupied I/O points 32 points (I/O assignment: Intelligent function module 32 points) 64 points (I/O
Internal current consumption (5 V DC) 1.1 A
External dimensions
Mass 0.23 kg
Signal input form Link device
1 pulse input magnification 1 to 10000 times
Height 106 mm (4.17 inch)
Width 27.8 mm (1.09 inch)
Depth 110 mm (4.33 inch)
switching control, position-speed switching control, speed-torque control
Speed-position switching control: Incremental system/absolute system Position-speed switching control: Incremental system Path control: Incremental system/absolute system
• -214748364.8 to 214748364.7 (m)
• -21474.83648 to 21474.83647 (inch)
• 0 to 359.99999 (degree)
• -2147483648 to 2147483647 (pulse) In incremental system
• -214748364.8 to 214748364.7 (m)
• -21474.83648 to 21474.83647 (inch)
• -21474.83648 to 21474.83647 (degree)
• -2147483648 to 2147483647 (pulse) In speed-position switching control (INC mode)/position-speed switching control
• 0 to 214748364.7 (m)
• 0 to 21474.83647 (inch)
• 0 to 21474.83647 (degree)
• 0 to 2147483647 (pulse) In speed-position switching control (ABS mode) 0 to 359.99999 (degree)
0.001 to 2000000.000 (inch/min)
0.001 to 2000000.000 (degree/min) 1 to 1000000000 (pulse/s)
*2
*1
assignment: Intelligent function module 64 points)
*1 The speed-position switching control (ABS mode) can be used only when the control unit is "degree". *2 When "Speed control 10 multiplier setting for degree axis function" is valid, the setting range is 0.01 to 20000000.00 (degree/min).
2 SPECIFICATIONS
24

2.2 Performance Specifications of the RD77GF

The performance specifications of CC-Link IE Field Network is shown below.
Item RD77GF4 RD77GF8 RD77GF16 RD77GF32
Maximum number of link points per network
Maximum number of link points per station
Safety communications
Inter-module synchronization cycle synchronization communication)
Transient transmission 1: N communication (such as monitor, program upload/download)
Transient transmission capacity 1920 bytes maximum
Maximum number of transient transmissions per link scan
Communication speed 1 Gbps
Network topology Line topology, star topology
Communication cable • Ethernet cable which satisfies 1000BASE-T standard:
Maximum station-to-station distance 100 m (conforms to ANSI/TIA/EIA-568-B (Category 5e))
Overall cable distance Single master
Number of cascade connections 4 levels maximum
Maximum number of connectable stations
Maximum number of networks 239
Communication method Token passing
Master station RX 16K points (16384 points, 2K bytes)
Local station
Maximum number of safety connectable stations per network
Maximum number of safety connections per network
Maximum number of safety connections per station
Maximum number of link points per safety connection
*1
*2
configuration
Single master configuration
RX 16K points (16384 points, 2K bytes)
RY 16K points (16384 points, 2K bytes)
RWr 8K points (8192 points, 16K bytes)
RWw 8K points (8192 points, 16K bytes)
RY 16K points (16384 points, 2K bytes)
RWr 8K points (8192 points, 16K bytes)
RWw 8K points (8192 points, 16K bytes)
RX 2K points (2048 points, 256 bytes)
RY 2K points (2048 points, 256 bytes)
RWr 1K points (1024 points, 2K bytes)
RWw 1K points (1024 points, 2K bytes)
(with
256 points when communication mode is "High-Speed"
256 points when communication mode is "High-Speed"
121 stations
1814 connections
120 connections
8 words (input: 8 words, output: 8 words)
0.50 ms/1.00 ms/2.00 ms/4.00 ms
Dedicated instructions from sequence programs
4
Category 5e or higher, straight cable (double shielded, STP)
• RJ45 connector
Line topology: 12000 m (when 121 stations are connected) Star topology: Depends on the system configuration.
121 stations (master station: 1, slave station: 120)
*3
2
*1 The maximum number of points that a master station can assign to one station. A local station can receive the range assigned to other
stations using the cyclic transmission function. *2 The cycle that each module performs the synchronous control via a network using the synchronous communication function. *3 A switching hub supporting synchronous communication is required for the star topology.
2 SPECIFICATIONS
2.2 Performance Specifications of the RD77GF
25
2.3 Specifications of Interfaces with External Devices
of the RD77MS

Electrical specifications of input signals

External input signal
Specifications of external input signal
Item Specifications
Signal name Input signal (SIN)
Number of input points RD77MS2: 10 points, RD77MS4/RD77MS8/RD77MS16: 20 points
Input method Positive common/Negative common shared
Common terminal arrangement 4 points/common (Common contact: COM)
Isolation method Photocoupler
Rated input voltage 24 V DC
Rated input current (I
Operating voltage range 19.2 to 26.4 V DC (24 V DC+10/-20%, ripple ratio 5% or less)
ON voltage/current 17.5 V DC or more/3.5 mA or more
OFF voltage/current 7 V DC or less/1 mA or less
Input resistance Approx. 6.8 k
Response time OFF ON 1 ms or less
) Approx. 5 mA
IN
ON OFF
Forced stop input
Specifications of forced stop input signal
Item Specifications
Number of input points 1 point
Input method Positive common/Negative common shared
Common terminal arrangement 1 point/common (Common contact: EMI.COM)
Isolation method Photocoupler
Rated input voltage 24 V DC
Rated input current (I
Operating voltage range 19.2 to 26.4 V DC (24 V DC+10/-20%, ripple ratio 5% or less)
ON voltage/current 17.5 V DC or more/3.5 mA or more
OFF voltage/current 7 V DC or less/1 mA or less
Input resistance Approx. 6.8 k
Response time OFF ON 4 ms or less
) Approx. 5 mA
IN
ON OFF
26
2 SPECIFICATIONS

2.3 Specifications of Interfaces with External Devices of the RD77MS

Manual pulse generator/Incremental synchronous encoder input
A-phase
0.5 μs or more
1 μs or more
B-phase
0.25 μs or less
0.25 μs or less
0.5 μs or more
0.25 μs or more
(Note): Duty ratio 50%
A-phase
2.5 μs or more
5 μs or more
B-phase
1.2 μs or less
1.2 μs or less
2.5 μs or more
1.2 μs or more
(Note): Duty ratio 50%
Specifications of manual pulse generator/incremental synchronous encoder
Item Specifications
Signal input form
Differential-output type (26LS31 or equivalent)
*1
Maximum input pulse frequency 1 Mpulses/s (After magnification by 4, up to 4 Mpulses/s)
Pulse width 1 s or more
Leading edge/trailing edge time 0.25 s or less
Phase difference 0.25 s or more
Rated input voltage 5.5 V DC or less
High-voltage 2.0 to 5.25 V DC
Low-voltage 0 to 0.8 V DC
Differential voltage 0.2 V
Cable length Up to 30 m (98.43 ft.)
Example of waveform
A-phase/B-phase (Magnification by 4/Magnification by 2/Magnification by 1), PULSE/SIGN
*2
2
Voltage-output type/Open-collector type (5 V DC)
Maximum input pulse frequency 200 kpulses/s (After magnification by 4, up to 800 kpulses/s)
Pulse width 5 s or more
Leading edge/trailing edge time 1.2 s or less
Phase difference 1.2 s or more
Rated input voltage 5.5 V DC or less
High-voltage 3.0 to 5.25 V DC/2 mA or less
Low-voltage 0 to 1.0 V DC/5 mA or more
Cable length Up to 10 m (32.81 ft.)
Example of waveform
*1 Set the signal input form in "[Pr.24] Manual pulse generator/Incremental synchronous encoder input selection".
*2
2 SPECIFICATIONS
2.3 Specifications of Interfaces with External Devices of the RD77MS
27
[Pr.24] Manual pulse generator/Incremental synchronous encoder input selection
A-phase/B-phase
[Pr.151] Manual pulse generator/Incremental synchronous encoder input logic selection
Positive logic Negative logic
Forward run Reverse run Forward run Reverse run
PULSE/SIGN
*2 Maximum input pulse frequency is magnified by 4, when "A-phase/B-phase Magnification by 4" is set in "[Pr.24] Manual pulse generator/
Incremental synchronous encoder input selection".
Forward run Reverse run
HIGH LOW
Forward run Reverse run
HIGHLOW
28
2 SPECIFICATIONS
2.3 Specifications of Interfaces with External Devices of the RD77MS
Loading...