Before installing the unit, thoroughly read the following safety precautions.
Observe these safety precautions for your safety.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference.
Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services.
When the user changes, make sure that the new user receives this manual.
Ask your dealer or a qualified technician to install the
unit.
Improper installation by the user may result in water leakage, electric shock, smoke, and/or fire.
Properly install the unit on a surface that can withstand the weight of the unit.
Unit installed on an unstable surface may fall and cause injury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the
cable.
Improperly connected or fixed cables may produce heat
and start a fire.
Take appropriate safety measures against strong
winds and earthquakes to prevent the unit from falling.
If the unit is not installed properly, the unit may fall and
cause serious injury to the person or damage to the unit.
Do not make any modifications or alterations to the
unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock,
smoke, and/or fire.
In the event of a refrigerant leak, thoroughly ventilate
the room.
If refrigerant gas leaks and comes in contact with an open
flame, poisonous gases will be produced.
When installing the All-Fresh type units, take it into
consideration that the outside air may be discharged
directly into the room when the thermo is turned off.
Direct exposure to outdoor air may have an adverse effect
on health. It may also result in food spoilage.
Properly install the unit according to the instructions
in the installation manual.
Improper installation may result in water leakage, electric
shock, smoke, and/or fire.
Have all electrical work performed by an authorized
electrician according to the local regulations and instructions in this manual, and a dedicated circuit must
be used.
Insufficient capacity of the power supply circuit or improper
installation may result in malfunctions of the unit, electric
shock, smoke, and/or fire.
To reduce the risk of injury, do not sit, stand, or place
objects on the unit.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.
HWE09060GB
ii
Page 3
WARNING
Securely attach the terminal block cover (panel) to the
unit.
If the terminal block cover (panel) is not installed properly,
dust and/or water may infiltrate and pose a risk of electric
shock, smoke, and/or fire.
After completing the service work, check for a gas
leak.
If leaked refrigerant is exposed to a heat source, such as a
fan heater, stove, or electric grill, poisonous gases may be
produced.
Only use the type of refrigerant that is indicated on the
unit when installing or reinstalling the unit.
Infiltration of any other type of refrigerant or air into the unit
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode.
When installing the unit in a small room, exercise caution and take measures against leaked refrigerant
reaching the limiting concentration.
Consult your dealer with any questions regarding limiting
concentrations and for precautionary measures before installing the unit. Leaked refrigerant gas exceeding the limiting concentration causes oxygen deficiency.
Consult your dealer or a specialist when moving or reinstalling the unit.
Improper installation may result in water leakage, electric
shock, and/or fire.
To reduce the risk of injury, wear protective gear, such
as gloves and safety goggles.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature
switch by defeating the safety features of these devices, or
the use of accessories other than the ones that are recommended by MITSUBISHI may result in smoke, fire, and/or
explosion.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper installation by the user may result in water leakage, electric
shock, smoke, and/or fire.
Control box houses high-voltage parts.
When opening or closing the front panel of the control box,
do not let it come into contact with any of the internal components. Before inspecting the inside of the control box,
turn off the power, keep the unit off for at least 10 minutes,
and confirm that the voltage between FT-P and FT-N on
INV Board has dropped to DC20V or less. (It takes about
10 minutes to discharge electricity after the power supply is
turned off.)
Hold the front panel up when opening it to keep it from
falling forward.
HWE09060GB
ii
Page 4
CAUTION
Precautions for handling units for use with R410A
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re-
sidual refrigerant and refrigerating machine oil in the existing piping may cause the refrigerating machine oil in the
new unit to deteriorate.
R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Use refrigerant pipes made of phosphorus deoxidized
copper. Keep the inner and outer surfaces of the pipes
clean and free of such contaminants as sulfur, oxides,
dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes
may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both
ends of the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate or
cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the refrigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and
may result in performance loss.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow
check valve is used, the vacuum pump oil may flow into the
refrigerant cycle and cause the refrigerating machine oil to
deteriorate.
Prepare tools for exclusive use with R410A. Do not use
the following tools if they have been used with the conventional refrigerant (gauge manifold, charging hose,
gas leak detector, reverse-flow check valve, refrigerant
charge base, vacuum gauge, and refrigerant recovery
equipment.).
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the refrigerating machine oil to deteriorate.
Infiltration of water may cause the refrigerating machine
oil to deteriorate.
Gas leak detectors for conventional refrigerants will not
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use
with R410A.
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate.
Only use refrigerant R410A.
The use of other types of refrigerant that contain chlorine
(i.e. R22) may cause the refrigerating machine oil to deteriorate.
HWE09060GB
iiiiii
Page 5
Before installing the unit
WARNING
Do not install the unit where a gas leak may occur.
If gaseous refrigerant leaks and piles up around the unit, it
may be ignited.
Do not use the unit to keep food items, animals, plants,
artifacts, or for other special purposes.
The unit is not designed to preserve food products.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical
sprays are used frequently. Doing so may lead to a remarkable drop in performance, electric shock, malfunctions, smoke, and/or fire.
The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas
leakage or water leakage.
When installing the unit in a hospital, take appropriate
measures to reduce noise interference.
High-frequency medical equipment may interfere with the
normal operation of the air conditioner or vice versa.
Do not install the unit on or over things that cannot get
wet.
When the humidity level exceeds 80% or if the drainage
system is clogged, the indoor unit may drip water. Drain water is also discharged from the outdoor unit. Install a centralized drainage system if necessary.
HWE09060GB
iv
Page 6
CAUTION
Before installing the unit (moving and reinstalling the unit) and performing
electrical work
Properly ground the unit.
Do not connect the grounding wire to a gas pipe, water pipe,
lightning rod, or grounding wire from a telephone pole. Improper grounding may result in electric shock, smoke, fire,
and/or malfunction due to noise interference.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in
excessive heat, smoke, and/or fire.
Install an earth leakage breaker to avoid the risk of
electric shock.
Failure to install an earth leakage breaker may result in
electric shock, smoke, and/or fire.
Use the kind of power supply wires that are specified
in the installation manual.
The use of wrong kind of power supply wires may result in
current leak, electric shock, and/or fire.
Use breakers and fuses (current breaker, remote
switch <switch + Type-B fuse>, moulded case circuit
breaker) with the proper current capacity.
The use of wrong capacity fuses, steel wires, or copper
wires may result in malfunctions, smoke, and/or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged platform, it may fall and
cause injury.
Properly install the drain pipes according to the instructions in the installation manual. Keep them insulated to avoid dew condensation.
Improper plumbing work may result in water leakage and
damage to the furnishings.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
alone.
Do not carry the product by the PP bands that are used on
some products.
Do not touch the heat exchanger fins. They are sharp and
dangerous.
When lifting the unit with a crane, secure all four corners
to prevent the unit from falling.
Properly dispose of the packing materials.
Nails and wood pieces in the package may pose a risk of
injury.
Plastic bags may pose a risk of choking hazard to chil-
dren. Tear plastic bags into pieces before disposing of
them.
Do not spray water on the air conditioner or immerse
the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to
protect your hands from metal parts and high-temperature parts.
HWE09060GB
vv
Page 7
Before the test run
CAUTION
Turn on the unit at least 12 hours before the test run.
Keep the unit turned on throughout the season. If the unit is
turned off in the middle of a season, it may result in malfunctions.
To avoid the risk of electric shock or malfunction of the
unit, do not operate switches with wet hands.
Do not touch the refrigerant pipes with bare hands during and immediately after operation.
During or immediately after operation, certain parts of the
unit such as pipes and compressor may be either very cold
or hot, depending on the state of the refrigerant in the unit
at the time. To reduce the risk of frost bites and burns, do
not touch these parts with bare hands.
Do not operate the unit without panels and safety
guards.
Rotating, high-temperature, or high-voltage parts on the unit
pose a risk of burns and/or electric shock.
Do not turn off the power immediately after stopping
the operation.
Keep the unit on for at least five minutes before turning off
the power to prevent water leakage or malfunction.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause malfunctions.
HWE09060GB
vi
Page 8
CONTENTS
I Read Before Servicing
[1] Read Before Servicing.............................................................................................................. 3
[2] Necessary Tools and Materials ................................................................................................ 4
[10] Remedies to be taken in case of a Refrigerant Leak ....................................................... 12
[11] Characteristics of the Conventional and the New Refrigerants ....................................... 13
[12] Notes on Refrigerating Machine Oil ................................................................................. 14
HWE09060GB
- 1 -
Page 11
- 2 -
Page 12
[ I Read Before Servicing ]
CAUTION
I Read Before Servicing
[1] Read Before Servicing
1. Check the type of refrigerant used in the system to be serviced.
Refrigerant Type
PFAV series: R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas
hydrofluoric acid may form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE09060GB
- 3 -
Page 13
[ I Read Before Servicing ]
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/MaterialsUseNotes
Gauge ManifoldEvacuation and refrigerant chargingHigher than 5.09MPa[738psi] on the
high-pressure side
Charging HoseEvacuation and refrigerant chargingThe hose diameter is larger than the
conventional model.
Refrigerant Recovery CylinderRefrigerant recovery
Refrigerant CylinderRefrigerant chargingThe refrigerant type is indicated. The
cylinder is pink.
Charging Port on the Refrigerant Cylinder Refrigerant chargingThe charge port diameter is larger
than that of the current port.
Flare NutConnection of the unit with the pipesUse Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
Tools/MaterialsUseNotes
Gas Leak DetectorGas leak detectionThe ones for use with HFC refrigerant
may be used.
Vacuum PumpVacuum dryingMay be used if a check valve adapter
is attached.
Flare ToolFlare processingFlare processing dimensions for the
piping in the system using the new refrigerant differ from those of R22. Refer to I [3] Piping Materials.
Refrigerant Recovery EquipmentRefrigerant recoveryMay be used if compatible with
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/MaterialsUseNotes
Vacuum Pump with a Check ValveVacuum drying
BenderBending pipes
Torque WrenchTightening flare nutsOnly the flare processing dimensions
for pipes that have a diameter of
ø12.70 (1/2") and ø15.88 (5/8") have
been changed.
Pipe CutterCutting pipes
Welder and Nitrogen CylinderWelding pipes
Refrigerant Charging MeterRefrigerant charging
Vacuum GaugeVacuum level check
HWE09060GB
- 4 -
Page 14
[ I Read Before Servicing ]
4. Tools and materials that must not be used with R410A
Tools/MaterialsUseNotes
Charging CylinderRefrigerant chargingProhibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
Tools recommended for replacing parts for changing the indoor unit static air pressure
When replacing a motor or pulley, work can be performed easier by using tools of dimensions close to the following specifications.
Extension bar
13
18
Ratchet handle/9.5mm [3/8"]
36
10.5
75
17
27.5
190
HWE09060GB
- 5 -
Page 15
[ I Read Before Servicing ]
[3] Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed)Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn)Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
at the same radial thickness.
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
O-materials (Annealed) can easily be bent with hands.
1/2H-materials (Drawn) are considerably stronger than O-material (Annealed) at the same thickness.
2. Types of copper pipes
Maximum working pressureRefrigerant type
3.45 MPa [500psi]R22, R407C etc.
4.30 MPa [624psi]R410A etc.
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper.
The operation pressure of the units that use R410A is higher than that of the units that use R22.
Use pipes that have at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
Pipe size (mm[in])Radial thickness (mm)Type
ø6.35[1/4"]0.8t
ø9.52[3/8"]0.8t
ø12.7[1/2"]0.8t
ø15.88[5/8"]1.0t
ø19.05[3/4"]1.0t
ø22.2[7/8"]1.0t
ø25.4[1"]1.0t
ø28.58[1-1/8"]1.0t
ø31.75[1-1/4"]1.1t
ø34.93[1-3/8"]1.1t
ø41.28[1-5/8"]1.2t
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn)
unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE09060GB
- 6 -
Page 16
[ I Read Before Servicing ]
Dimension A
Dimension B
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in])
A dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]9.19.0
ø9.52[3/8"]13.213.0
ø12.7[1/2"]16.616.2
ø15.88[5/8"]19.719.4
ø19.05[3/4"]24.023.3
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in])
B dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]17.017.0
ø9.52[3/8"]22.022.0
ø12.7[1/2"]26.024.0
ø15.88[5/8"]29.027.0
ø19.05[3/4"]36.036.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
HWE09060GB
- 7 -
Page 17
[ I Read Before Servicing ]
[4] Storage of Piping
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse)
If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
Both ends of the pipes should be sealed until just before brazing.
Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not
handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to
deteriorate and cause a compressor failure.
[5] Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil.
Use only ester oil, ether oil, and alkylbenzene.
HWE09060GB
- 8 -
Page 18
[ I Read Before Servicing ]
[6] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide
scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of oxidized solder for brazingUse of non-oxidized solder for brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use non-oxidized solder.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
HWE09060GB
- 9 -
Page 19
[ I Read Before Servicing ]
[7] Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)
Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an
HFC(R410A) leak.
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum
pump with a reverse-flow check valve.
A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly
to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not
be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recommended vacuum gauge is shown in Photo2.)
Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening
the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE09060GB
- 11 -
Page 21
[ I Read Before Servicing ]
[9] Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink.Refrigerant charging in the liquid state
ValveValve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the
liquid state.)
Refer to "X [5] Refrigerant Leak."(page 208)
HWE09060GB
- 12 -
Page 22
[ I Read Before Servicing ]
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a confined area.
New Refrigerant (HFC type)Conventional Refriger-
ant (HCFC type)
R410AR407CR22
R32/R125R32/R125/R134aR22
Composition (wt%)(50/50)(23/25/52)(100)
Type of RefrigerantPseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
ChlorideNot includedNot includedIncluded
Safety ClassA1/A1A1/A1A1
Molecular Weight72.686.286.5
Boiling Point (°C/°F)-51.4/-60.5-43.6/-46.4-40.8/-41.4
Steam Pressure
1.557/2260.9177/1330.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.042.544.4
FlammabilityNonflammableNonflammableNonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
Refrigerant Charging MethodRefrigerant charging in
Replenishment of Refrigerant after a Refrigerant
*1
*2
000.055
173015301700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
AvailableAvailableAvailable
Leak
*1 When CFC11 is used as a reference
*2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410AR407CR22
MPa/psiMPa/psiMPa/psi
-20/-40.30/440.18/260.14/20
0/320.70/1020.47/680.40/58
20/681.34/1940.94/1360.81/117
40/1042.31/3351.44/2091.44/209
60/1403.73/5412.44/3542.33/338
65/1494.17/6052.75/3992.60/377
HWE09060GB
- 13 -
Page 23
[ I Read Before Servicing ]
[12] Notes on Refrigerating Machine Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system.
Note that the ester oil used in the system has properties that are different from commercially available ester oil.
RefrigerantRefrigerating machine oil
R22 Mineral oil
R407CEster oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out.
The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
CauseSymptomsEffects on the refrigerant cycle
Water infiltrationFrozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes
Poor cooling performance
Compressor overheat
Motor insulation failure
Burnt motor
Coppering of the orbiting scroll
Lock
Burn-in on the orbiting scroll
Hydrolysis
Sludge formation and adhesion
Acid generation
Oxidization
Oil degradation
Air infiltrationOxidization
Adhesion to expansion valve and capillary
tubes
Clogged expansion valve, capillary tubes, and
drier
Poor cooling performance
Infiltration of
contaminants
Dust, dirt
Infiltration of contaminants into the compressor
Compressor overheat
Burn-in on the orbiting scroll
Sludge formation and adhesionClogged expansion valve and capillary tubes
Mineral oil
etc.
Poor cooling performance
Compressor overheat
Oil degradationBurn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE09060GB
- 14 -
Page 24
II Restrictions
[1] System configuration ....................................................................................................... 17
[2] Types and Maximum allowable Length of Cables ........................................................... 17
[3] Switch Settings and Address Settings ............................................................................. 19
[4] Sample System Connection............................................................................................. 25
[5] An Example of a System to which an MA Remote Controller is connected..................... 26
[6] Restrictions on Pipe Length ............................................................................................. 34
HWE09060GB
- 15 -
Page 25
- 16 -
Page 26
[ II Restrictions ]
TB3TB7TB3TB
7
TB3TB7TB3TB
7
TB3TB7TB3TB
7
TB3TB7TB3TB
7
Outdoor unit
Indoor unit
Remote Controller
2-core shielded cable
Outdoor unit
multiple-core cable
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
2-core shielded cable
Indoor unit
Remote Controller
II Restrictions
[1] System configuration
1. Unit combination
The table below shows a list of outdoor units that are compatible with the indoor unit described in this manual.
(1) Standard type combination
Indoor unit model nameOutdoor unit model name
PFAV-P250VM-EPUHY-P250YHM-A
PFAV-P500VM-EPUHY-P500YSHM-A
PFAV-P750VM-EPUHY-P750YSHM-A
(2) Fresh Air Intake type combination
Indoor unit model nameOutdoor unit model name
PFAV-P300VM-E-FPUHY-P250YHM-A
PFAV-P600VM-E-FPUHY-P500YSHM-A
PFAV-P900VM-E-FPUHY-P750YSHM-A
1) Do not connect the PFAV series indoor units and other types of indoor units together to an outdoor unit.
[2] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this manual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference.
(Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic components on the terminal block.
6) Use 2-core shielded cables as transmission cables.
Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
(2) Control wiring
Different types of control wiring are used for different systems.
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line.
Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce
noise interference.
HWE09060GB
- 17 -
Page 27
[ II Restrictions ]
1) M-NET transmission line
Facility
type
TypeShielded cable CVVS, CPEVS, MVVS
Cable type
Number of
cores
Cable sizeLarger than 1.25mm2 [AWG16]
Maximum transmission
line distance between the
outdoor unit and the farthest indoor unit
Maximum transmission
line distance for centralized control and Indoor/
outdoor transmission line
(Maximum line distance
via outdoor unit)
All facility types
2-core cable
200 m [656ft] max.
500 m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
HWE09060GB
- 18 -
Page 28
[ II Restrictions ]
2) Remote controller wiring
MA remote controller
*1
TypeCVV
Number of
cores
Cable type
Cable size
2-core cable
0.3 to 1.25mm
2
[AWG22 to 16] *2
(0.75 to 1.25mm2 )
[AWG18 to 16] *3
Maximum overall line
length
200 m [656ft] max.
*1 MA remote controller refers to MA remote controller (PAR-21MAA), MA simple remote controller, and wireless re-
mote controller.
*2 The use of cables that are smaller than 0.75mm2 (AWG18) is recommended for easy handling.
*3 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1. Switch setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected " before performing wiring work.
Set the switches while the power is turned off.
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not
function properly.
Units on which to set the switchesSymbolUnits to which the power must be shut off
Indoor unitMain/sub unitICOutdoor units
MA remote controllerMain/sub remote
MAIndoor units
*2
and Indoor units
controller
Outdoor unit
*1
OC,OSOutdoor units
*2
*1. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity
from large to small (if two or more units have the same capacity, in the order of address from small to large).
*2. Turn off the power to all the outdoor units in the same refrigerant circuit.
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controllerAddress setting
Setting methodFacto-
range
Indoor unitMain/sub unit01 to 50
*1
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
*2
MA remote controllerNo address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
Outdoor unit51 to 100
*1
Assign an address that equals the address of the indoor unit in the same refrigerant circuit plus 50. The
System controller Group remote
controller
System remote
controller
ON/OFF remote controller
Schedule timer
(compatible
outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
201 to 250Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the
range listed on the left to each unit.
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the
range listed on the left to each unit.
*3
with M-NET)
Central controller
G(B)-50A
000,
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit. The address must
be set to "000" to control the K-control unit.
LM adapter201 to 250Assign an arbitrary but unique address within the
range listed on the left to each unit.
ry set-
ting
00
Main
00
201
202
000
247
*1. To set the outdoor unit address to "100," set the rotary switches to "50."
*2. Some indoor units have 2 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1.
*3. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity
from large to small (if two or more units have the same capacity, in the order of address from small to large).
HWE09060GB
- 20 -
Page 30
[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
System configuration
Connection to
the system controller
Power supply unit
for transmission
lines
Group operation
of units in a system with multiple
Power supply switch connector connection
outdoor units
System with
one outdoor unit
System with
multiple outdoor
units
___Leave CN41 as it is
(Factory setting)
Not connected_Not grouped
GroupedDisconnect the male connector from the fe-
With connection
to the indoor
unit system
With connection
to the centralized control
system
Not requiredGrouped/not
grouped
Not required
(Powered from the
*1
Grouped/not
grouped
outdoor unit)
Required *
1
Grouped/not
grouped
male power supply switch connector (CN41)
and connect it to the female power supply
switch connector (CN40) on only one of the
outdoor units.
*Connect the S (shielded) terminal on the ter-
minal block (TB7) on the outdoor unit whose
CN41 was replaced with CN40 to the
ground terminal ( ) on the electric box.
Leave CN41 as it is
(Factory setting)
*2
*1 The need for a power supply unit for transmission lines depends on the system configuration.
*2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
System configurationCentralized control switch settings *
1
Connection to the system controller Not connectedLeave it to OFF. (Factory setting)
Connection to the system controller Connected *
2
ON
*1 Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
2) To activate the temperature sensor supplied with the Fresh Air Intake model unit, set the SW1-1 to "OFF" and SW3-8 to "ON."
Install the sensor where the room temperature can be detected.
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
*2
Function
Power ON/OFF by
the plug
*1
Automatic restoration
after power failure
Operation of the indoor unit when the operation is resumed after the unit was
stopped
Indoor unit will go into operation regardless of its operation status before power
off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power
Setting (SW1)
910
OFFON
ONOFF
OFFOFF
off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
crankcase heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Requires that the dipswitch settings for all the units in the group be made.
HWE09060GB
- 21 -
Page 31
[ II Restrictions ]
CAUTION
(6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
TypeUsageFunction
Input Prohibiting cooling/heating operation (thermo OFF) by an external
DEMAND (level)CN3D
input to the outdoor unit.
*It can be used as the DEMAND control device for each system.
Performs a low level noise operation of the outdoor unit by an external input to the outdoor unit.
Low-noise mode
*3*4
(level)
Terminal
to be
*1
used
*2
Option
Adapter for
external input
(PACSC36NA-E)
* It can be used as the silent operation device for each refrigerant
system.
Forces the outdoor unit to perform a fan operation by receiving signals from the snow sensor.
*5
Snow sensor signal
input (level)
CN3S
Cooling/heating operation can be changed by an external input.Auto-changeoverCN3N
Out-
How to extract signals from the outdoor unit
put
*It can be used as an operation status display device.
*It can be used for an interlock operation with external devices.
Operation status of
the compressor
Error status
*6
CN51Adapter for
external output
(PACSC37SA-E)
*1. For detailed drawing, refer to "Example of wiring connection".
*2. For details, refer to (1) through (4) on the next page.
*3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of
on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2
or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.
*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri-
ority mode.
When SW5-5 is set to ON: The Low-noise mode always remains effective.
When SW5-5 is set to OFF: The Low-noise mode is cancelled when certain outside temperature or pressure criteria are
met, and the unit goes into normal operation (capacity priority mode).
Low-noise mode is effectiveCapacity priority mode becomes effective
CoolingHeatingCoolingHeating
TH7 < 30°C [86°F]
and
63HS1 < 32kg/cm
2
TH7 > 3°C [37°F]
and
63LS > 4.6kg/cm
TH7 > 35°C [95°F]
2
or
63HS1 > 35kg/cm
2
TH7 < 0°C [32°F]
or
63LS < 3.9kg/cm
2
*5. When multiple outdoor units exist in one refrigerant circuit system, settings on every outdoor unit (signal input) are re-
quired.
*6. When multiple outdoor units exist in one refrigerant circuit, take out signals from the outdoor unit (OC).
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.
Snow sensor : The outdoor fan runs when X is closed
in stop mode or thermostat mode.
X
CN3S
Preparations
in the field
Maximum cable
length is 10m
Adapter
2
Outdoor unit
control board
2
3
1
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Relay circuit
(3) CN3N
2. Optional part : PAC-SC36NA-E or field supply.
Preparations
in the field
OFF
CoolingONHeating
Normal
Y
OFF
ON
X
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay
CN3N
X
Y
Relay circuit
Adapter
2
Outdoor unit
control board
Maximum cable
length is 10m
1
2
3
Example of wiring connection
(4) CN3D
Relay circuit
Adapter
X
Y
Preparations
in the field
Maximum cable
length is 10m
X : Low-noise mode
Y : Compressor ON/OFF
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
2
1
2
3
Outdoor unit
control board
CN3D
Relay circuit
Preparations
in the field
X : Low-noise mode
X : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Low-noise mode : The noise level is reduced by controlling the maximum
Outdoor unit
1
2
2
control board
CN3D
Adapter
X
3
Maximum cable
length is 10m
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
fan frequency and maximum compressor frequency.
HWE09060GB
- 23 -
Page 33
[ II Restrictions ]
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
Demand control
steps
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
1) SW4-4: OFF (Compressor ON/OFF, Low-noise mode)
CN3D 1-3PCompressor ON/OFF
OpenCompressor ON
Short-circuitCompressor OFF
*1
CN3D 1-2PLow-noise mode
*2
OpenOFF
Short-circuitON
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON, this function cannot be used.
*2. This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on
the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
CN3D 1-2P
CN3D 1-3POpenShort-circuit
Open100% (No DEMAND)75%
Short-circuit0% (Compressor OFF)50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
*4. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*5. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
(*4, *5)
HWE09060GB
- 24 -
Page 34
[ II Restrictions ]
[4] Sample System Connection
Examples of typical system connection are shown.
Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System
configuration
System with one out-
1.
door unit
Grouping of units in a
2.
system with multiple
outdoor units
System with one out-
3.
door unit
Connection to the system controller
NO
NO
With connection to transmission line
for centralized control
Address start up for in-
door and outdoor units
Manual
address setup
Manual
address setup
Manual
address setup
Notes
HWE09060GB
- 25 -
Page 35
[ II Restrictions ]
IC
TB5
M1 M2
S
TB
15
12
01
AB
MA (main body)
IC
TB5
M1 M2
S 12
TB
15
02
AB
MA (sold separately)
AB
MA (main body)
Main
Sub
Group
Group
AB
MA
m1
m3
m2
L1
OC
TB3
TB7
M1 M2
M1 M 2
S
51
OC
TB3
TB7
M1 M2
M1 M2
S
52
[5] An Example of a System to which an MA Remote Controller is connected
1. Single-outdoor-unit system (manual IC/OC address setup)
(1) Sample control cable wiring configuration
(2) Cautions
1) Do not connect terminal blocks TB5 on the indoor units
that are connected to an outdoor unit in a different refrigerant circuit with each other.
2) No more than two MA remote controllers can be connected to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Maximum cable distance (1.25 mm
2
[AWG16] min.)
L1≤200m [656ft]
2) Transmission cable for the centralized control system
No connection is required.
3) MA remote controller wiring
2
Total cable length (0.3 to 1.25mm
[AWG22 to 16])
m1≤200m [656ft]
m2+m3≤200m [656ft]
- 26 -
GBHWE09060
Page 36
[ II Restrictions ]
(4) Wiring method
1) Indoor-outdoor transmission cable
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission cable (TB3) on the outdoor unit (OC) and of the terminal block for indoor-outdoor transmission cable (TB5) on the indoor unit (IC).
(Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Connect the ground terminal ( ) of OC to the S terminal
of TB5 on IC with the shielded cable.
2) Transmission cable for the centralized control system
No connection is required.
(5) Address setting method
Address
Unit or controller
setting
range
1Indoor unitMain con-
IC01 to 50Assign the lowest address
troller
Sub controller
3) MA remote controller wiring
Required when operation with two remote controllers or
group operation is performed.
When two remote controllers are connected to the
system
When two remote controllers are connected to the system, connect terminals 1 and 2 on the terminal block for
MA remote controller cable (TB15) on the indoor unit (IC)
to the terminal block on the MA remote controller (sold
separately). (Non-polarized two-wire)
Set the Main/Sub setting of the MA remote controller
(sold separately) connected to the indoor unit to Sub.
Refer to the Instruction Manual for the MA remote controller for the setting method. The main MA remote controller is built in on the indoor unit.
4) Switch setting
Address setting is required as follows.
Setting methodNotes
To perform a group opto the main indoor unit in
the group.
Assign sequential numbers starting with the address of the main unit in
the same group.
[main unit +1, +2, +3…]
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
Factory
setting
00
2MA remote
controller
Main remote con-
MANo settings
required
-Main
troller
Sub remote
controller
MASub re-
mote controller
3Outdoor unit OCOS51 to 100Assign an address that
Settings to be made in the
remote controller function
selection mode
equals the address of the
indoor unit in the same re-
To set the address to
"100," set the switch to
"50."
frigerant circuit plus 50.
Assign sequential addresses to the outdoor
units in the same refrigerant circuit.
The outdoor units are automatically designated as
OC and OS. (Note)
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
00
HWE09060GB
27- 27 -
Page 37
[ II Restrictions ]
IC
MA(Main)
TB5-1
M1 M2
S
01
TB15
12
AB
MA(Sub)
AB
MA
* Applicable to the
P750 and P900-F
models.
02*
OC
TB3
M1 M2
51
M1 M2
52
TB7
M1 M2
S
TB3
TB7
M1 M2
S
L1
L2
m1
m2
AB
2. Single-refrigerant-circuit system
(1) Sample control cable wiring configuration
(2) Cautions
1) Assign sequential addresses to the indoor unit.
2) No more than two MA remote controllers can be connected to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
2) Transmission cable for the centralized control system
No connection is required.
3) MA remote controller wiring
Total cable length (0.3 to 1.25mm
2
[AWG22 to 16])
m1 +m2 ≤ 200m [656ft]
- 28 -
GBHWE09060
Page 38
[ II Restrictions ]
(4) Wiring method
1) Indoor-outdoor transmission cable
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission cable (TB3) on the outdoor units (OC and OS) (Note1) and of the terminal block
for indoor-outdoor transmission cable (TB5) on the indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Connect the ground terminal of OC to the S terminal
of TB5 on IC with the shielded cable.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
2) Transmission cable for the centralized control system
No connection is required.
(5) Address setting method
Address
Unit or controller
setting
range
1Indoor unitMain con-
IC01 to 50To be set to an arbitrary
troller
3) MA remote controller wiring
Required when operation with two remote controllers or
group operation is performed.
When two remote controllers are connected to the
system
When two remote controllers are connected to the system, connect terminals 1 and 2 on the terminal block for
MA remote controller cable (TB15) on the indoor unit (IC)
to the terminal block on the MA remote controller (sold
separately). (Non-polarized two-wire)
Set the Main/Sub setting of the MA remote controller
(sold separately) connected to the indoor unit to Sub.
The main MA remote controller is built in on the indoor
unit.
4) Switch setting
Address setting is required as follows.
Setting methodNotes
address within the range
on the left.
Factory
setting
00
Sub controller*
Assign an address that
equals the address of the
main unit +1.
2MA remote
controller
Main remote con-
MANo settings
required
-Main
troller
Sub remote
controller
MASub re-
mote controller
3Outdoor unitOCOS51 to 100Assign an address that
Settings to be made in the
remote controller function
selection mode
equals the address of the
indoor unit in the same re-
To set the address to
"100," set the switch to
"50."
frigerant circuit plus 50.
Assign sequential addresses to the outdoor
units in the same refrigerant circuit.
The outdoor units are automatically designated as
OC and OS. (Note)
∗Applicable to the P750 and P900-F models.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
00
HWE09060GB
29- 29 -
Page 39
[ II Restrictions ]
m1
m2m3
M1
M2M1M2
M1
M2
M1
M2
M1M2M1
M2SS12
Leave the power jumper
as it is on CN41.
Leave the power jumper
as it is on CN41.
MA (main body)
Sub
MA (main body)
Main
Group
L1
L2
TB3
TB7
51
OC
IC
01
TB15
TB5
A
B
A
B
OC
TB3
TB7
52
IC
02
TB15
TB5
3. Group operation of the indoor units connected to different outdoor units
(1) Sample control cable wiring configuration
(2) Cautions
1) Assign sequential addresses to the indoor unit.
2) Do not connect the terminal blocks (TB5) of the indoor
units that are connected to different outdoor units with
each other.
3) No more than two MA remote controllers can be connected to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
When a relay connector for MA remote controller cable is
removed from the indoor unit, the unit can be in the same
state as when MA remote controller is removed from the
unit.
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Same as section [5] 1.
2) Transmission cable for the centralized control system
Same as section [5] 1.
3) MA remote controller wiring
2
Total cable length (0.3 to 1.25mm
[AWG22 to 16])
m1+m2+m3 ≤ 200m [656ft]
- 30 -
GBHWE09060
Page 40
[ II Restrictions ]
(4) Wiring method
1) Indoor-outdoor transmission cable
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission cable (TB7) on the outdoor unit (OC) and of the terminal block for indoor-outdoor transmission cable (TB5) on the indoor unit (IC).
(Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Same as section [5] 1.
2) Transmission cable for the centralized control system
Same as section [5] 1.
3) MA remote controller wiring
To perform a group operation of the indoor units con-
nected to different outdoor units, set one of the MA remote controllers to Sub.
Same as section [5] 1.
(5) Address setting method
Address
Unit or controller
setting
range
1Indoor unitMain con-
IC01 to 50Assign the lowest ad-
troller
Sub controller
When two remote controllers are connected to the
system
Same as section [5] 1.
Group operation of indoor units
To perform a group operation of indoor units, connect the
terminals 1 and 2 of the terminal block (TB15) on the indoor units with each other. (Non-polarized two-wire)
Set the Main/Sub setting of one of the indoor unit remote
controllers to Sub.
Designate the indoor unit in the group with the greatest
number of functions as the main unit.
4) Switch setting
Address setting is required as follows.
Setting methodNotes
To perform a group
dress to the main indoor
unit in the group.
Assign sequential numbers starting with the address of the main unit in
the same group.[main
unit +1, +2, +3…]
operation of indoor
units that feature dif-
ferent functions, des-
ignate the indoor unit
in the group with the
greatest number of
functions as the main
unit.
Factory
setting
00
2MA remote
controller
Main remote con-
MANo settings
required
-Main
troller
Sub remote
controller
MASub remote
controller
Settings to be made in the
remote controller function
selection mode
3Outdoor unitOC
OS
51 to 100Assign an address that
equals the address of the
indoor unit in the same re-
To set the address to
"100," set the switch
to "50."
frigerant circuit plus 50.
Assign sequential addresses to the outdoor
units in the same refrigerant circuit.The outdoor
units are automatically
designated as OC and
OS. (Note)
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
00
HWE09060GB
31- 31 -
Page 41
[ II Restrictions ]
IC
TB5 TB
15
12
01
AB
IC
TB5
12
TB
15
02
AB
Group
Group
Note 1 When only the LM adapter is connected, leave DIP SW2-1 to OFF as it is.
Note 2 LM adapter operates on a single-phase 200 VAC power supply.
L1
L2
OC
TB3
TB7
SS
SS
51
OC
TB3
TB7
52
ABS
L31
L32
Note 2 and 3
Note 1
Leave the power jumper as
it is on CN41.
SW2-1 OFF→ON
To be connected
Move the power jumper from
CN41 to CN40.
SW2-1 OFF→ON
MA (main body)
MA (main body)
System controller
M1
M2
M1
M2
M1
M2
M1 M2M1 M2M1 M2
4. An example of a system in which a system controller is connected to the transmission cable for the centralized control system and the power is supplied from the outdoor unit
(1) Sample control cable wiring configuration
(2) Cautions
1) No more than two MA remote controllers can be connected to a group of indoor units.
2) Do not connect the terminal blocks (TB5) of the indoor
units that are connected to different outdoor units with
each other.
3) The replacement of the power jumper connector from
CN41 to CN40 must be performed on only one outdoor
unit in the system.
4) Connect the S (shield) terminal of the terminal block for
centralized control system connection (TB7) on the outdoor unit whose power jumper was moved from CN41 to
CN40 to the ground terminal of the unit.
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Same as section [5] 1.
2) Transmission cable for the centralized control system
3) MA remote controller wiring
Same as section [5] 1.
- 32 -
GBHWE09060
Page 42
[ II Restrictions ]
(4) Wiring method
1) Indoor-outdoor transmission cable
Same as section [5] 2.
Shielded cable connection
Same as section [5] 1.
2) Transmission cable for the centralized control system
Daisy-chain terminals M1 and M2 of the terminal block
for centralized control system connection (TB7) on OCs
and terminals A and B of the system controller on OCs.
(non-polarized two-wire)
Move the power jumper on the control board from CN41
to CN40 on only one of the outdoor units. Set the centralized control switch (DIP SW2-1) of the control board on
all outdoor units to ON.
Only use shielded cables.
(5) Address setting method
Unit or controller
1Indoor unitMain con-
IC01 to 50Assign the lowest
Address set-
ting range
troller
Sub controller
2MA remote
controller
Main remote con-
MANo settings
required
troller
Sub remote con-
MASub remote
controller
troller
3Outdoor unitOC
51 to 100Assign an address
OS
Shielded cable connection
Daisy-chain the S terminals of the terminal block (TB7)
and of the system controller on the outdoor units with the
shielded cable. Connect the S (shield) terminal of the terminal block (TB7) on the outdoor unit whose power jumper was moved from CN41 to CN40 to the ground terminal
( ) of the control box.
3) MA remote controller wiring
Same as section [5] 1.
When two remote controllers are connected to the
system
Same as section [5] 1.
Group operation of indoor units
Same as section [5] 1.
4) Switch setting
Address setting is required as follows.
Setting methodNotes
To perform a group operaaddress to the main
indoor unit in the
group.
Assign sequential
numbers starting
tion of indoor units that fea-
ture different functions,
designate the indoor unit
with the most functions in
the group as the main unit.
with the address of
the main unit in the
same group.
[main unit +1, +2,
+3…]
-Make the same indoor unit
group settings with the system controller as the ones
Settings to be made
in the remote con-
that were made with the MA
remote controller.
troller function selection mode
To set the address to "100,"
that equals the ad-
set the switch to "50."
dress of the indoor
unit in the same refrigerant circuit plus
50.
Assign sequential
addresses to the
outdoor units in the
same refrigerant circuit.
The outdoor units
are automatically
designated as OC
and OS. (Note)
Factory
setting
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
HWE09060GB
33- 33 -
Page 43
[ II Restrictions ]
Note1. "-"
Note2. If the A/C system is designed to use cooling mode under outdoor temperature 0°C, H’<=15m.
Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
IU : Indoor unit , OU : Outdoor unit
L1
A
OU
H (OU above IU)
H' (OU under IU)
Bent equivalent length "M"
M (m/bent [ft./bent])Outdoor Model
PUHY-P250YHM0.42 [1.38]
IU
Piping length(m [ft.])
Max. length
Piping in the figureItem
Max. equivalent length
A
Height between OU and IU (OU above IU)
Height between OU and IU (OU under IU)
Indoor Unit size Pipe(Gas)Pipe(Liquid)
P250 ø22.20 [7/8"]ø9.52 [3/8"]
Indoor unit piping size selection rule
P300-F *2ø22.20 [7/8"]ø9.52 [3/8"]
*2. "-F" indicates Fresh air intake type
[6] Restrictions on Pipe Length
P250 model
HWE09060GB
- 34 -
Page 44
[ II Restrictions ]
Outdoor Twinning Kit
CMY-Y100VBK2
Note1. "-"
Note2. If the A/C system is designed to use cooling mode under outdoor temperature 0°C, H’<=15m.
Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
H (OU above IU)
H' (OU under IU)
h2
T
A
L1
S
IU : Indoor unit , OU : Outdoor unit
2m
To indoor unit
To indoor unit
To indoor unit
2mTo indoor unit
Trap (gas
pipe only)
Upward
incline
Downward
incline
Install the pipes from the outdoor unit to the branch
joint with a downward incline.
If the length of pipe between the branch joint and outdoor
unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
OK
NO
OU
OU
IU
max
Bent equivalent length "M"
M (m/bent [ft./bent])Outdoor Model
PUHY-P500YSHM0.50 [1.64]
PUHY-P750YSHM0.70 [2.29]
Piping length(m [ft.])
Max. length
Piping in the figureItem
Max. equivalent length
S+A
Height between OU and IU (OU above IU)
Height between OU and IU (OU above IU)
[1] Outdoor Unit Components and Refrigerant Circuit .......................................................... 39
[2] Control Box of the Outdoor Unit....................................................................................... 41
[3] Outdoor Unit Circuit Board............................................................................................... 42
HWE09060GB
- 37 -
Page 47
- 38 -
Page 48
[ III Outdoor Unit Components ]
Fan
Control
Box
Fan guard
Fin guard
Front panel
Heat exchanger
III Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit
1. Outdoor unit components
(1) PUHY-P250, P350, P400YHM-A
HWE09060GB
- 39 -
Page 49
[ III Outdoor Unit Components ]
High pressure sensor(63HS1)
Liquid side valve
High-pressure switch(63H1)
Compressor cover
Accumulator
Compressor
Oil separator
Check valve
High pressure check joint
Low pressure sensor(63LS)
4-way valve(21S4a)
4-way valve(21S4b)
Low pressure check joint
Linear Expansion
Valve(LEV1)
Subcool coil
Linear Expansion Valve(LEV2a,2b)
Solenoid valve (SV1a)
Solenoid valve (SV9)
Gas side valve
Solenoid valve(SV5b)
Check valve
High pressure check joint
Low pressure sensor(63LS)
4-way valve(21S4a)
4-way valve(21S4b)
4-way valve(21S4c)
Low pressure check joint
Linear Expansion
Valve(LEV1)
Subcool coil
Linear Expansion Valve(LEV2a,2b)
High pressure sensor(63HS1)
High-pressure switch(63H1)
Compressor cover
Accumulator
Compressor
Oil separator
Solenoid valve (SV1a)
Solenoid valve (SV9)
Solenoid valve(SV5b)
Solenoid valve(SV5c)
Gas side valve
Liquid side valve
2. Refrigerant circuit
(1) PUHY-P250YHM-A
(2) PUHY-P350 and P400YHM-A
HWE09060GB
- 40 -
Page 50
[ III Outdoor Unit Components ]
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of
the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes,
and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
(It takes about 10 minutes to discharge electricity after the power supply is turned off.)
Control board
DC reactor (DCL)
Electromagnetic relay(72C)
Noise filter
Note.1
INV board
Fan board
Rush current protection resistor
(R1,R5) Note.2
Terminal block for transmission
line (TB3, TB7)
M-NET board
Terminal block for power supply
L1,L2,L3,N,
(TB1)
Capacitor(C100)
[2] Control Box of the Outdoor Unit
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
HWE09060GB
- 41 -
Page 51
[ III Outdoor Unit Components ]
CN332
Output 18VDC
GND
(
Fan board
)
LED2
Lit during normal
CPU operation
CN72
72C
driving output
Serial communication signal input
GND (
INV board)
Output 17VDC
CN801
Pressure switch
connection
CN4
GND
Serial communication signal output
LEV
driving output
LED1
Service LED
SWU1,2
Address switch
SW1-5
Dip
switch
Sensor
input
CNVCC2
Output 12VDC
Output 5VDC
GND
CNIT
Output 12VDC
GND
Output 5VDC
Power supply detection input
Power supply ON/OFF signal output
CNS2
Transmission line input/output
for centralized control system (30VDC)
CN41
Power supply for
centralized control OFF
CN40
Power supply for
centralized control ON
CN102
Indoor/outdoor transmission line input/output (30VDC)
Power supply input for centralized control system (30VDC)
External signal input (contact input)
F01
Fuse
250V AC/3.15A
CNAC
L1
N
LED3
Lit
when powered
LED3
Lit
when powered
Actuator
driving output
Output 12VDC
Compressor
ON/OFF output
Error output
CN51
CNAC2
L1
N
CNDC
Bus voltage input
P
N
CN2
[3] Outdoor Unit Circuit Board
1. Outdoor unit control board
HWE09060GB
- 42 -
Page 52
[ III Outdoor Unit Components ]
2. M-NET board
Grounding
CN04
Bus voltage input
P
N
CNS2
Transmission line input/output for
CN102
Power supply output for centralized control system
Indoor/outdoor transmission line input/output
Grounding
Grounding
TB3
Indoor/outdoor
transmission block
centralized control system
Ground terminal for
transmission line
CNIT
12VDC input
GND
5VDC input
Power supply detection output
Power supply ON/OFF
signal input
TB7
Terminal block for
transmission line for
centralized control
LED1
Power supply for
indoor
transmission line
TP1,2
Check pins for
indoor/outdoor
transmission line
HWE09060GB
- 43 -
Page 53
[ III Outdoor Unit Components ]
3. INV board
Bus voltage check
terminal (P)
Note
IGBT
(Rear)
CN1
Bus voltage output
N
P
Bus voltage check
terminal (N)
Note 1
SC-L1
Input(L1)
SC-L2
Input(L2)
SC-P1
SC-P2
Bus voltage Input(P)
Rectifier diode output (P)
CN6
Open: No-load operation setting
LED1
Lit: Inverter in normal operation
Blink: Inverter error
Short-circuited: Normal setting
CN5V
GND
5VDC output
RSH1
Overcurrent detection
resistor
CN4
GND
CNTYP Inverter
board type
SC-V
Inverter output(V)
SC-W
Inverter output(W)
SC-U
Inverter output(U)
(INV Board)
Serial communication
signal output
CN2
S
erial communication
signal output
GND
17VDC input
SC-L3
Input(L3)
CT22
Current sensor(W)
CT3
Current sensor(L3)
CT12
Current sensor(U)
C30 C37
Smoothing capacitor
1) Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
It takes about 10 minutes to discharge electricity after the power supply is turned off.
HWE09060GB
- 44 -
Page 54
[ III Outdoor Unit Components ]
4. Fan board
CNVDC
Bus voltage input
N
P
CNINV
Inverter output
W
V
U
R630,R631
Overcurrent detection
resistor
DIP IPM Rear
CN18V
Input 18VDC
GND
LED3
Lit during normal
CPU operation
CN4
GND
Serial communication signal output
CN5
GND(Control board)
Serial communication signal output
CN21
Serial communication signal output
GND(INV board)
Input 17VDC
CN22
GND(INV board)
Input 5VDC
Serial communication signal input
GND(INV board)
Output 17VDC
THBOX
Thermistor
(Control box internal temperature
detection)
LED1
Inverter in normal operation
LED2
Inverter error
HWE09060GB
- 45 -
Page 55
[ III Outdoor Unit Components ]
CN4
Output
(Rectified L2-N current)
P
N
CN5
Output
(Rectified L2-N current)
P
N
TB21
Input/output(L1)
TB22
Input/output(L2)
TB23
Input/output(L3)
TB24
Input(N)
CN1B
Input
L3
L2
CN1A
Input
N
L1
Grounding
F1,F2,F3,F4
Fuse
250VAC 6.3A
CN3
Output
L1
N
Grounding
CN2
Surge absorber circuit
Surge absorber circuit
Short circuit
Short circuit
Use the following procedure to replace the pulley and motor of the PFAV-P500VM-E.
1. Replacement Procedure
(1) Attaching the fan pulley set and electric motor pulley set
1)
Remove the front lower and upper panels (2 screws for each).
2) Loosen the electric motor base securing bolts and electric
motor base slide bolt, and then remove the V belt. See Figures 1 and 2.
3) Loosen the set screws of the pulleys, and then remove the
fan pulley.
* Depending on the diameter of the pulley, the electric motor
may need to be slid towards the back side.
4) Slide the electric motor base towards the front.
5) Attach the replacement pulleys and V belt.
6) Set the parallelism of the fan pulley and electric motor pulley
so that the contents of Table 1 and Figure 3 are satisfied.
7) Tighten the set screws. (Torque: 13.5N•m)
Furthermore, coat the set screws with screw lock (procure
locally) to prevent them from coming undone.
(Screw lock: ThreeBond 1332N or the equivalent)
8) Attach the parts in the reverse order of removal.
(2) Attaching the electric motor
When the electric motor is removed, make sure the work is
performed by two people to ensure it is not dropped.
1)
Remove the front lower and upper panels (2 screws for each).
2) Loosen the electric motor base securing bolts and electric
motor base slide bolt, and then remove the V belt. See Figures 1 and 2.
3) Loosen the set screws of the pulleys, and then remove the
fan pulley.
* Depending on the diameter of the pulley, the electric motor
may need to be slid towards the back side.
4) Slide the electric motor base towards the front.
5) Loosen the stopper securing screw of electric motor base as
shown in Figure 4.
6) Remove the electric motor. (4 bolts)
7) Using standard bolts and nuts, replace the electric motor.
8) Attach the other parts in the reverse order of removal.
2. Cautions
State of V-belt tension
1) While the tension per V-belt is at an appropriate deflection
amount: , set the V-belt so that the deflection weight (W)
meet the values specified in Figure 6 and Table 2.
2) After the V-belt becomes used to the pulley (after approximately 24 hours of operation), make sure the belt is not loose,
and if the belt is loose, adjust it to an appropriate tension
as described in Table2. Furthermore, if the belt is new, adjust
to approximately 1.15 times the deflection force (W).
3) After adjusting for initial stretching in 2), readjust the tension
every 2,000 hours. The belt life is over when the belt circumference has stretched by 2% including the initial stretching
of the belt (approximately 1%). (After approximately 5,000
hours of operation.)
3. Tools
When loosening the securing bolts of the electric motor
base, work can be performed easier by using following tools.
Electric motor base securing bolts
Electric motor base slide bolt
Slide towards the front
A
K
K
K
B
2 .giF1 .giF
Fig. 3
Part A
Stopper
Part A Detailed View
Fig. 4
Fig. 4
Fig. 5
Deflection Weight(W)
=0.016 C
C: Center distance(mm)
Fig. 6
Table 1
Parallelism
Pulley
K (min.) Notes
Cast-iron pulley
10 or
less
Offset between the pulleys (B)
equivalent to 3 mm [1/10"] every 1 m [3.2 ft] of the distance
between the axes (A)
Same as indoor LEV
The resistance
value differs
from that of the
indoor LEV.
(Refer to the
section "LEV
Troubleshooti
ng."(page 193
))
Same as indoor LEV
Resistance
check
Continuity
check with a
tester
21S4b P250 -
P400
models
21S4c P350
and
P400
models
HWE09060GB
1) Changeover between heating
and cooling
2) Controls outdoor unit heat exchanger capacity
- 80 -
AC220-240V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 50%
or heating cycle
Page 90
[ VII Refrigerant Circuit ]
1
273+t
R0=15k
R
0/80
=3460
Rt =
15exp{3460( - )}
1
273
2. Indoor Unit
Part
Name
Linear
expansion valve
Thermistor
Symbol
(functions)
Notes Usage Specification Check method
LEV1) Adjusts superheat at the
indoor heat exchanger
outlet during cooling
2) Adjusts subcool at the
heat exchanger outlet of
the indoor unit during
cooling
TH1
(Suction air
Indoor unit control (ThermoON/OFF)
temperature)
TH2
(Liquid pipe
temperature)
1) Indoor unit control (Frost
prevention, Pre-heating
standby)
2) LEV control during heating operation (subcool
detection)
TH3
(Gas pipe
LEV control during cooling operation (superheat detection)
temperature)
TH4
(Outdoor air
Indoor unit control (ThermoON/OFF)
temperature)
DC12V
Opening of stepping motor
driving valve 0-(1400) pulses
[1] Functions and Factory Settings of the Dipswitches
1. Outdoor unit
(1) Control board
Function according to switch settingSwitch setting timing
SwitchFunction
OFFONOFFONOCOS
SWU1-2Unit address settingSet to 00 or 51-100 with the dial switchBefore power onCC
SW1 1-10
1
2
3
For self-diagnosis/
operation monitoring
Centralized control
switch
Deletion of connection information
Deletion of error history SW
Refer to the LED monitor display on the
outdoor unit board.
Without connection
to the centralized
controller
With connection to
the centralized controller
Anytime after power on
Before power on
Normal controlDeletionBefore power on
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
to ON)
After being energized and
4Pump down modeNormal controlPump down mode
while the compressor is
stopped
SW2
5-----6------
Anytime af-
Forced defrost
7
(Note 3)
Normal control
Forced defrost
starts
10 minutes
after compressor
startup
ter power
on (When
switched
from OFF to
ON)
Defrost timer setting
8
(Note 3)
50 minutes90 minutes
Anytime after power on
(When switched from OFF
to ON)
9------
10------
Units that re-
quire switch
setting
Note.2
CC
BB
A-
CC
A-
AA
BB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VIII [2] Controlling the Outdoor Unit" for details.(page 92)
HWE09060GB
- 85 -
Page 95
[ VIII Control ]
SwitchFunction
SW3
Units that re-
Function according to switch settingSwitch setting timing
quire switch
setting
Note.2
OFFONOFFONOCOS
Test run mode: en-
1
abled/disabled
Test run mode: ON/
2
OFF
SW3-2 disabledSW3-2 enabledAnytime after power onA-
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A-
P250
Defrost start temper-
3
ature
-10°C [14°F]
-5°C [23°F]Anytime after power onBB
P350 · P400
-8°C [18°F]
Defrost end temper-
4
ature
P250
10°C [50°F]
P350 · P400
7°C [45°F]
P250
15°C [59°F]
P350 · P400
12°C [54°F]
Anytime after power on
(except during defrost operation)
BB
5-----6------
7-----8------
9Model setting
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energizedCC
10Model setting
High static pressure
60Pa
High static pressure
30Pa
Before being energizedCC
1-----2------
Anytime after being energized (except during ini-
Refrigerant amount
3
adjustment
Normal operation
mode
Refrigerant amount
adjust mode
tial startup mode.
Automatically cancelled
A-
60 minutes after compressor startup)
SW4
Low-noise mode/
4
step demand switching
Low-noise mode
(Note 3)
Step demand mode Before being energizedCC
5------
Cumulative com-
6
pressor operation
time data deletion
Cumulative compressor operation
time data is retained.
Cumulative compressor operation
time data is deleted.
Anytime after power on
(when the unit is turned
on)
CC
7-----8-----9------
10------
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed.
Setting of CN3D is required.(page 24)
HWE09060GB
- 86 -
Page 96
[ VIII Control ]
Units that re-
SwitchFunction
Function according to switch settingSwitch setting timing
quire switch
setting
Note.2
OFFONOFFONOCOS
1
2
Model selection See the table below (Note 4)Before being energizedCC
3
4
SW5
Low-noise mode
5
selection
Capacity priority
mode (Note 3)
Low-noise modeBefore being energizedA-
6-----7Model selection See the table below (Note 4)Before being energizedBB
8-----9------
10------
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) When set to the capacity priority mode and if the following conditions are met, the Low-noise mode will terminate, and the unit
will go back into the normal operation mode.
Cooling: Outside temperature is high or high pressure is high.
Heating: Outside temperature is low or low pressure is low.(page 22)
4) The table below summarizes the factory settings for dipswitches SW5-1 through SW5-4, and SW5-7. The factory setting for
all other dipswitches is OFF.
SW 5
Model
12347
ONONOFFOFFONP250 model
(2) INV board
Functions are switched with the following connector.
ConnectorFunction
Function according to connec-
tor
Setting timing
EnabledDisabledEnabledDisabled
CN6 shortcircuit con-
nector
Enabling/disabling the following error
detection functions;
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
Error detection enabled
Error detection disable
(No load operation is possible.)
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
HWE09060GB
- 87 -
Page 97
[ VIII Control ]
P250,P500
ON
OFF
SW1-2
SW1-3
OFF
ON
P750
Factory setting
2. Function of the switch (Indoor unit)
(1) Dipswitches (Standard type)
1) SW1,3, 7, 8
SwitchFunction
Room temperature de-
1
tection position
2
3
Filter sign
Outdoor air intakeDisabledEnabled
4
SW1
Remote display optionFan output Thermo-ON signal
5
Humidifier control
6
7
8
Automatic recovery after
9
10
power failure
Power resetDisabledEnabled
1
Capacity code
Forced Thermo-ONDisabledForced Thermo-ON
Fan operation during de-
frost cycle
Vapor pan humidifierNot availableAvailable
Heat dissipation1 min. (heating only)
Automatic LEV value
conversion function
Negative 4-degree offset
(heating)
SW3
2
3
4
5
6
7
8
9
10
Heater (heating)DisabledEnabled
SW7
1
2
3
4
1
SW8
Forced Thermo-OFF
2
during test run
3
Function according to switch setting
Switch setting
timing
OFFONOFFON
Indoor unit return air
Filter sign100h
SW1-2
SW1-3
During constant heating
---
---
---
Refer to the table on the setting combination with SW2.
Not availableAvailable
---
---
---
---
---
---
---
OFF
OFF
operation
DisabledEnabled
OFFON
Enabled
EnabledDisabled
Built-in sensor on the re-
mote controller
1250hN/A2500h
ON
OFF
OFFONON
During heating opera-
3 min. 5 sec. (regardless
of the operation mode)
Disabled
ON
tion
When the unit is
stopped (remote
controller is
switched off)
Notes
Set these switches to OFF
when SWC is set to ON.
Return air temp. and preset
temp. are fixed.
Set this switch to ON (disabled)
on the floor-standing units.
Factory settings for these
switches depend on the unit
capacity. Refer to section 2).
When this switch is set to ON,
external Thermo signals are
not effective.
To be enabled on the indoor
units in a multiple-refrigerantcircuit system.
1) The setting timings for the dipswitches 1 and 3 is when the units are stopped (remote controller is switched off). Power reset
is not required.
2) The settings in the shaded areas indicate factory settings.
HWE09060GB
- 88 -
Page 98
[ VIII Control ]
SW2SW4
− 50 OFF OFF ON
− 100 ON OFF ON
No.1 100 ON OFF OFF
No.2 50 OFF OFF OFF
ON
OFF
1 2 3 4 5 6 1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6 1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
<Notes on capacity code and model settings>
If the capacity code or model setting has been incorrectly
set (e.g., when replacing the circuit board), both the indoor
and outdoor units need to be power reset.
P250
P500
P750
Model System
Capacity
SW3-2 SW3-9
SW3-10
2) SW2,SW3-2,SW3-9,SW3-10,SW4
HWE09060GB
- 89 -
Page 99
[ VIII Control ]
Filter sign100h
OFF
OFF
SW1-2
SW1-3
ON
OFF
OFFONON
ON
1250hN/A2500h
P300,P600
ON
OFF
SW1-2
SW1-3
OFF
ON
P900
Factory setting
(2) Dipswitches (Fresh Air Intake type)
1) SW1,3,7,8
SwitchFunction
Function according to switch setting
OFFONOFFON
Room temperature detec-
1
tion position
Indoor unit return air
2
3
Filter sign
4---
5Remote display option
SW1
6Humidifier control
Humidifier freezeup pro-
7
tection
8-
Automatic recovery after
9
power failure
Fan output Thermo-ON signal
During constant heating
operation
DisabledEnabled
--
DisabledEnabled
10Power resetDisabledEnabled
1Model settingHeat pumpCooling-only
2Capacity code
Refer to the table on the setting combination with
3Forced Thermo-ONDisabledForced Thermo-ON
Indoor unit fan operation
4
during defrost cycle
OFFON
5Vapor pan humidifierNot availableAvailable
SW3
6Heat dissipation1 min. (heating only)
Automatic LEV value con-
7
8
version function
Negative 4-degree offset
(heating)
Not availableAvailable
Enabled
9---
10---
1Heater (heating)DisabledEnabled
SW7
2
trol indoor temp.
Return air temp.Supply air temp.
Temp. value used to con-
3---
4---
1---
SW8
2--
3-
--
Built-in sensor on the re-
mote controller
During heating opera-
tion
SW2.
3 min. 5 sec. (regardles s
of the operation mode)
Disabled
-
Switch setting
timing
When the unit is
stopped (remote
controller is
switched off)
When indoor and
outdoor units are
switched off
When the unit is
stopped (remote
controller is
switched off)
Notes
When this switch is set to ON,
units are forced to operate in
the heating mode when the
return air dry temperature is at
or below 5°C[41°F].
Set these switches to OFF
when SWC is set to ON.
Return air temp. and preset
temp. are fixed.
Set this switch to ON (disabled) on the floor-standing
models.
Factory settings for these
switches depend on the unit
capacity. Refer to section 2).
When this switch is set to ON,
external Thermo signals are
not effective.
1) The setting timings for the dipswitches 1 and 3 is when the units are stopped (remote controller is switched off). Power reset
2) The settings in the shaded areas indicate factory settings.
HWE09060GB
is not required.
- 90 -
Page 100
[ VIII Control ]
SW2SW4
− 50 OFF OFF ON
− 100 ON OFF ON
No.1 100 ON OFF OFF
No.2 50 OFF OFF OFF
ON
OFF
1 2 3 4 5 6 1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6 1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
<Notes on capacity code and model settings>
If the capacity code or model setting has been incorrectly
set (e.g., when replacing the circuit board), both the indoor
and outdoor units need to be power reset.
P300-F
P600-F
P900-F
Model System
Capacity
SW3-2 SW3-9
SW3-10
Fan operation on the Fresh Air Intake type units
When the return air dry temperature is 5°C [41°F] or below, units may be forced to operate in the heating mode to prevent
humidifier from freezing up and to prevent cold drafts.
The fan will stop when all refrigerant systems are in trouble and during the defrost cycle. Refer to the table below for how to
set the related switches and for the operation patterns.
SpecificationSW
Notes
OFFON
Operation
Forced heating
operation/Fan
operation when
units are in trouble
Forced heating op-
1-7
eration is disabled.
The fan will operate
when the units are
in trouble. (The fan
will stop when the
fan is in trouble or
when there is a
communication er-
Forced heating op-
eration is enabled.
The fan will not op-
erate when the
units are in trouble.
When the return air dry temperature is 5°C [41°F] or
below, units are forced to operate in the heating
mode regardless of the mode setting to prevent
cold drafts.
The units will resume operation in the selected
mode when the return air dry temperature reaches
6°C[43°F].
Regardless of the outside air temperature, the fan
will not operate if there are any problems.
SW
ror.)
Fan operation
during defrost
cycle
SW
The fan will not op-
3-4
erate when the
units in all refriger-
The fan will operate
when the units are
in the defrost cycle.
This switch is set to off to prevent the humidifier
from freezing up and to prevent cold drafts.
ant systems are in
the defrost cycle.
1) The settings in the shaded areas indicate factory settings.
2) Turning on the fan during the defrost cycle will send cold air into the room, delay normal operation from being resumed, and
cause the room temperature to drastically drop. To avoid this, set SW3-4 to OFF.
3) The operating temperature (return air dry temperature) of the fan is 0°C [32°F] or above. If the fan is operated at the outside
temperature below 0°C [32°F], depending on the ambient air conditions, dew condensation may form on the panel surface.
Use caution so that dew drips will not damage the surrounding equipments.
2) SW2,SW3-2,SW3-9,SW3-10,SW4
(3) Address switches
How to set the indoor unit addresses depends on the system. Refer to the Outdoor Unit Installation Manual and other related
documents for how to set the addresses.
Each address consists of two digits.
(Example)
To set the address to "3," set the 1's digit to "3" and leave the 10's digit to "0."
To set the address to "25," set the 1's digit to "5" and the 10's digit to "2."
3. Switch functions <Remote controller>
(1) MA remote controller (PAR-21MAA)
MA remote controller does not have switches. Refer to the Installation Manual for how to make the function settings.
HWE09060GB
- 91 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.