Mitsubishi HWE05260 TECHNICAL MANUAL

AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS
Series : PEH,PUH
HEAT PUMP
: Model
PEH-5,6,8,10,12,16,20MYC PUH-5,6,8,10,12MYG
DATA BOOK
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for
correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.
For installation, conduct the work correctly by following the Installation Manual.
Improper installation may cause a fire, electrical shock or water leakage.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual.
The units should be powered by dedicated power lines. Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electrical shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the falling down of the unit.
The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish. The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressure rise or explosion.
If the unit is loosely mounted, it may fall, and cause injury.
Never repair the unit, remodel or transfer it to another site by yourself.
If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
Ventilate the room if refrigerant leaks during Installation.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
Use only optional parts authorised by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Erroneous handling may induce serious injury depending on the situation.
Warning
Warning
Caution
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Beware of electric shock. <Color: yellow>
Warning:
Carefully read the labels affixed to the unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
• Install the unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for strong winds and earthquakes and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury.
• Always use an filter and other accessories specified by Mitsubishi Elec­tric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
• Do not touch the heat exchanger fins and metal edges.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
• Have all electric work done by a licensed electrician according to “Elec­tric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water ma y enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R22) speci­fied on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.
• Pay a special attention to the place, such as a basement, etc. where re­frigeration gas can stay, since refrigeration is heavier than the air.
• The appliance is not intended for use by young children or infirm per­sons without supervision.
• Young children should be supervised to ensure that they do not play with the appliance.
• Never operate in open phase condition. Control box may be broken.
1.2. Before Installation
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi­tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective drainage work together with the outdoor unit, as required.
1.3. Before Installation (moved) - electrical
work
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• The reverse phase of L lines (L
1, L2, L3) can be detected (Error cord: 4103),
but the reverse phase of L lines and N line can be not be detected.
- Some electric parts should be damaged when power is supplied under the
miss wiring.
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
• Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
• Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands f or a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
PUH-OOMYG
1PEH
5HP 8HP 10HP 12HP
PEH-OOMYC
1No. of outdoor units
No. of outdoor units
Wired remote controller
Accessory (PAR-21MAA)
111 No1 5 8 10 12 No2
6HP
5HPCapacity 8HP 10HP 12HP
5 8 10 12
6HP
6
5 8 10 126
1
-----
6
16HP 20HP
PEH-OOMYC
Model
Model
Model 16 20
22
No1
Connected
outdoor unit
Connected
outdoor unit
810
No2 8 10
Capacity
Capacity
Air inlet : Return the indoor unit.
Filter : Air filter is not provided with in the unit.
However, simple filter is available as optional part to remove visible dust and dirt. If air purification is one of the conditions required for use, consult with your dealer.
Air outlet: Blows the cooled / warmed air into the room.
Air inlet
Filter
Air outlet
[Function selection flowchart]
[1] Stop the air conditioner to start remote controller function selection mode.
[2] Select from item1. → [3] Select from item2. → [4] Make the setting. (Details
are specified in item3)
[5] Setting completed. → [6] Change the display to the normal one. (End)
Function selection
<Wired remote controller type> (1) Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language (CHANGE LANGUAGE)
2.Function limit (FUNCTION SELECTION)
3.Mode selection (MODE SELECTION)
4.Display change (DISP MODE SETTING)
Item 3 (Setting content)
Display in multiple languages is possible.
Setting the range of operation limit (operation lock)
Setting the use or non-use of automatic operation mode
Setting the temperature adjustable range (maximum, minimum)
Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
Setting the use or non-use of clock function
Setting the timer type
Contact number display in case of error
Setting the telephone number
Setting the temperature unit (
˚C or ˚F) to display
Setting the use or non-use of the display of indoor (suction) air temperature
Setting the use or non-use of the display of Cooling or Heating displa y during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) (LOCKING FUNCTION”) (2) Use of automatic mode setting (SELECT AUTO MODE) (3) Temperature range limit setting (LIMIT TEMP FUNCTION) (1) Remote controller main/sub setting (CONTROLLER MAIN/SUB”)
(2) Use of clock setting (CLOCK) (3) Timer function setting (WEEKL Y TIMER) (4) Contact number setting for error situation (CALL.”)
(1) Temperature display
˚C/˚
F setting (TEMP MODE ˚C/˚F )
(2)
Suction air temperature display setting (ROOM TEMP DISP SELECT”) (3)
Automatic cooling/heating display setting (A UT O MODE DISP C/H”)
(Hold down the E button and press the D button for two seconds.) *The display cannot be changed during the unit function
selection, the test run and the self diagnosis.
(Hold down the E button and press the D button for two seconds.)
* The remote controller records the
setting that is made in this way.
Press the G button.
See [4]-1
Item 3
(Setting content)
Item 1
Remote Controller Function Selection Mode
Item 2
Mode selection
(MODE
SELECTION)
Normal display (Display when the air condition is not running)
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
F
G
C
D
B
I
A
H
E
Change Language
(CHANGE LANGUAGE)
Function limit
(FUNCTION
SELECTION)
Display change
(DISP MODE
SETTING)
NOTE Timer operation stops when the display for remote controller function selection is changed to the normal one.
Press the G button.
Press the E button.
Press the E button.
Press the E button.
Press the E button.
Press the G button.
Press the G button.
See [4]-2. (1)
See [4]-2. (2)
See [4]-2. (3)
See [4]-3. (1)
See [4]-3. (2)
See [4]-3. (3)
See [4]-3. (4)
See [4]-4. (1)
See [4]-4. (2)
See [4]-4. (3)
Dot display
The language that is selected in CHANGE LANGUAGE mode appears on this display. English is set in this manual.
Press the D button.
Press the D button.
Press the D button.
Operation function limit setting (LOCKING FUNCTION)
Press the G button.
Temperature range limit setting (LIMIT TEMP FUNCTION)
Use of automatic mode setting (SELECT AUTO MODE)
Temperature display ˚C/˚F setting (TEMP MODE ˚C/˚F)
Press the G button.
Automatic cooling/heating display setting (AUTO MODE DISP C/H)
Suction air temperature display setting (ROOM TEMP DISP SELECT)
Remote controller main/sub setting (CONTROLLER MAIN/SUB)
Press the G button.
Timer function setting (WEEKL Y TIMER)
Use of clock setting (CLOCK)
Contact number setting for error situation (CALL.”)
Notes Remedies
Since air conditioners use microcomputer inside, the small amount of noise interference is come from the power supply, transmission line and air conditioning units. When air conditioners are installed near the equipment, which uses subtle electric signals (eg. wireless microphones, medical equipment), malfunctions may occur among the equipment due to noise interference. When air conditioners are installed near the equipment that discharge strong noise (Electrical discharge machine), malfunctions may occur among air conditioners. If these cases are concerned, refer to the following.
Place the equipment, which is easy to get influenced by noise interference (eg. recivers of wireless microphones, antennas) far from the air conditioners. Separate the power supply of the equipment which discharges strong noise from the air conditioners' power supply. Install transmission line, power supply line, and air conditioner apart from each other.
Notes Remedies
When outdoor air temperature is low (6
˚CWB or lower), the outdoor unit capacity may drop due to the frost on the heat exchanger, and the defrost operation may start. (This is normal.)
The longer it takes to defrost due to over cooled gas pipes (due to too much frost on the heat exchanger, or outdoor unit exposed directly to outdoor air), the longer it takes for the outdoor unit to return to the normal operation. (It takes maximum 10~20 minutes.)
Estimate the load, according to the capacity correction described in the section [1. The characteristics of cooling/heating capacity] in [3Product data].
Take the following correction factors into account when calculating heating capacity requirement: temperature, piping length, and defrosting.
Take appropriate measures against wind and snow. (Refer to Chapter 4-1.)
Notes Remedies
The noise level, which is described in the outdoor unit specification is measured in an anechoic room. Therefore, the environment and sound echo at the installation site must be taken into account.
Do not install outdoor units next to each other in the residential areas. If outdoor unit noise is concerned, please ask us for installation environment.
Cooling
TOTAL INPUT TOTAL RUN CURRENT
COMPRESSOR INPUT RUN CURRENT STARTING CURRENT O/D FAN INPUT RUN CURRENT STARTING CURRENT I/D FAN INPUT RUN CURRENT STARTING CURRENT
PEH-5,6 220-240V
PEH-8,10 PUH-5~10 380-415V
VOLT ITEM
kW
A
kW
A A
kW
A A
kW
A A
5.45
10.8
4.42
8.12
65.5
0.23
0.58
1.5
0.80
3.7
6.4
PEH-5MYC
PUH-5MYG
6.19
11.0
5.16
8.32
74.0
0.23
0.58
1.5
0.80
3.7
6.4
PEH-6MYC PUH-6MYG
7.81
14.6
6.45
11.94
95.0
0.46
1.16
3.0
0.90
1.5 5
PEH-8MYC PUH-8MYG
9.80
18.1
8.44
15.44
125.0
0.46
1.16
3.0
0.90
1.5 5
PEH-10MYC
PUH-10MYG
TOTAL INPUT TOTAL RUN CURRENT
COMPRESSOR INPUT RUN CURRENT STARTING CURRENT O/D FAN INPUT RUN CURRENT STARTING CURRENT I/D FAN INPUT RUN CURRENT STARTING CURRENT
PEH-12~20 PUH-8~12 380-415V
VOLT ITEM
kW
A
kW
A A
kW
A A
kW
A A
10.80
19.5
9.01
16.04
118.0
0.46
1.16
3.0
1.33
2.3 9
PEH-12MYC
PUH-12MYG
15.12
29.4
12.9
23.88
106.9
0.92
2.32
4.2
1.30
3.2
8.5
PEH-16MYC
PUH-8MYG X 2
20.27
38.3
16.88
30.88
140.4
0.92
2.32
4.2
2.47
5.1 10
PEH-20MYC
PUH-10MYG X 2
Heating
TOTAL INPUT TOTAL RUN CURRENT
COMPRESSOR INPUT RUN CURRENT STARTING CURRENT O/D FAN INPUT RUN CURRENT STARTING CURRENT I/D FAN INPUT RUN CURRENT STARTING CURRENT
PEH-5,6 220-240V
PEH-8,10 PUH-5~10 380-415V
VOLT ITEM
kW
A
kW
A A
kW
A A
kW
A A
4.67
9.1
3.64
6.42
65.5
0.23
0.58
1.5
0.8
3.7
6.4
PEH-5MYC
PUH-5MYG
5.22
9.9
4.19
7.22
74.0
0.23
0.58
1.5
0.8
3.7
6.4
PEH-6MYC PUH-6MYG
7.03
13.4
5.67
10.74
95.0
0.46
1.16 3
0.9
1.5 5
PEH-8MYC PUH-8MYG
9.12
16.8
7.76
14.14
125.0
0.46
1.16 3
0.9
1.5 5
PEH-10MYC
PUH-10MYG
TOTAL INPUT TOTAL RUN CURRENT
COMPRESSOR INPUT RUN CURRENT STARTING CURRENT O/D FAN INPUT RUN CURRENT STARTING CURRENT I/D FAN INPUT RUN CURRENT STARTING CURRENT
PEH-12~20 PUH-8~12 380-415V
VOLT ITEM
kW
A
kW
A A
kW
A A
kW
A A
9.71
17.7
7.92
14.24
118.0
0.46
1.16 3
1.33
2.3 9
PEH-12MYC
PUH-12MYG
13.56
27.0
11.34
21.48
105.7
0.92
2.32
4.16
1.3
3.2
8.5
PEH-16MYC
PUH-8MYG X 2
18.91
35.7
15.52
28.28
139.1
0.92
2.32
4.16
2.47
5.1 10
PEH-20MYC
PUH-10MYG X 2
PEH-8 Fan Performance Curve
(Pa)
250
200
150
100
External Static Pressure
50
Recommended range
o
Hi
B
A
0
40.0 50.0 60.0 70.06980.0 90.0
Air flow
(CMM)
Indoor
DB
˚C
Indoor
WB
˚C
T/I
kW
8.24
Q
40
Outdoor DB
˚C
kW
20.624 17
PEH-8MYC
input Capacity
0.9
1.0
1.01
1.1
45 50 55 60 65 7069
Air flow rate (m
3
/min)
Capacity/ input factor
<Accessory>
·Conduit mouting plate (Painted the same color as the unit body) a)ø27····················································1pc. b)ø34····················································1pc.
·Tapping screw 412·······························4pcs.
·Connection pipe······································1pc.
Note 1.It is possible to change to ø27 or ø34 by selecting the conduit mounting plate a,b.
Air inlet
Air outlet
Top view
4-1020 Holes <For mounting anchor bolt M8>
[Field supply]
Air inlet
Note 1 ø40 Hole <For the power supply wiring>
<For the indoor unit connection wiring>
ø27 Hole
Refrigerant pipe ø15.88(5/8 flare)
Refrigerant pipe ø28.6 (1-1/8 flange)
Connection pipe (Accessory)
Knock out hole Pressure gauge (For option)
Front view Right side viewLeft side view
58515 15
54734 34
615
108.51230
1447 9
108.5
152 55
97
100115
65
10
103
1480
<Accessory>
·Conduit mouting plate (Painted the same color as the unit body) a) ø27····················································1pc. b) ø34····················································1pc.
·Tapping screw 412································4pcs.
·Connection pipe·······································1pc.
Note 1.It is possible to change to ø27 or ø34 by selecting the conduit mounting plate a,b.
615
547 3434
585 1515
Air inlet
Air outlet
Top view
4-1020 Holes <For mounting anchor bolt M8> [Field supply]
108.5830108.5
91047
Air inlet
Right side viewFront view
1480
Knock out hole Pressure gauge (For option)
10
103
Connection pipe (Accessory)
Refrigerant pipe PUH-8MYG :
ø
25.4 (1 flange)
PUH-10MYG :
ø
28.6 (1-1/8 flange)
Refrigerant pipe ø15.88(5/8 flare)
Left side view
ø27 Hole <For the indoor unit connection wiring>
Note 1 ø40 Hole <For the power supply wiring>
55152
97
100115
65
Rubber bush <Remote controller wiring>
Rubber bush <Outdoor unit connection wiring>
Rubber bush <Power supply wiring>
75
55
12970
Return air sensor
A
A
4- 12 Holes
Drain R1
Top view
Control box
Return air duct flange
Supply air duct flange
<For hanging bolt M10> [Field supply]
22- 3.1 Holes
24- 3 Holes
Refrigerant pipe
15.88 (5/8 braze)
Refrigerant pipe
25.4 (1 braze)
<Accessory> .
Pipe cover.......................................... 2pcs.
(For dew condensation prevention of local piping and unit connection.)
.
Remote controller............................... 1pcs.
Return air
Left side view
Supply air
Front view
42
124 34
131
530
50
9525011
7x130(=910)
10
130
130
45
45
31 31
1102
200
10
8x130(=1040)
1300
20
199
100
40
20
462
144
1284
400
155 1000 105
40 1260 40
1340
1400
56539
22330
145
89
35
130
130
35
634
262 73
10
54 10
376
2510010025
Rubber bush <Remote controller wiring>
Rubber bush <Outdoor unit connection wiring>
Rubber bush <Power supply wiring>
75
55
70 129
A
A
4- 12 Holes
Drain R1
Top view
Control box
22- 3.1 Holes
<For hanging bolt M10> [Field supply]
Return air duct flange
Supply air duct flange
26- 3 Holes
Left side view
Supply air
Return air
Front view
Return air sensor
<Accessory> .
Pipe cover..........................................2pcs.
(For dew condensation prevention of .
Remote controller.............................. 1pcs.
local piping and unit connection.)
Refrigerant pipe
15.88 (5/8 braze)
Refrigerant pipe
28.6 (1-1/8 braze)
42
124
131
50 530
34
130
9525011
10
66
1302
1484
7x130(=910)
130
45
45
200
20
100
20
199
40
1500
462
66 9X130(=1170)
10
25 100 100 25
10 10
1540
40146040
255 205
376
1000
1600
73262
400
39 565
54
634
35130
89
145
144
330 22
130
35
1
C11
1
C12
3
1
C21
3
C22
1
MF2 MF3
TB6
UVWN
C14
SV1
CH 63H1 63L
21S4
X1
3
6 1
6
1 3 5 7
F10
F20
F30
CNOUT1
CNOUT2
1
6
5
11
3
3
1
35
CNIN
CNFC2
CNFAN
F.C. BOARD
CNPOW
3
1
F2
5
1
F03
LED1
SW4
1
OFF
ON
4
SW3
OFF
ON
1
2
SW5
OFF
ON
1
SW1
6
6
OFF
ON
1
SW2
TH2
CN51
CN28CNS3
CNFG
CN81
63H2
3
CN20
TR
313
CN53
CNMNT CN2
1212
CN312CN4CN40
1
L1
L2 L3
N
N
52C
51C
CN3N
CN27
CN24
CN3S
CNVMNT
CN3D
1
3
L1 L2 L3
3
1
CN34
DC power supply
Transmission Circuit
F02
F04
CNFC1
X05
X02
X04
X01
X03
MC
CN23
1 3
CN22
CN21
3
5
3
CN26
3
CN25
CN52
1
52C
52C
1
2
1
TH1
F1
1
3
F01
1
1
1
7
PE
51C
X1
OUT OUT
IN
IN
N.F.BOARD
Blue
Black
White
Red
Black
White
Red
Green/Yellow
TO INDOOR UNIT CONNECTING WIRES (*2) (POLER)
S3S2S1
MAIN BOARD
INDOOR UNIT
OUTDOOR UNIT CONTROL BOX
(*1)(*1)
TB8
TB3
TB1
POWER SUPPLY 3N~PE 380/400/415V 50HZ
PUH-12MYG : 60A
CIRCUIT BREAKER PUH-8MYG : 50A
(FIELD SUPPLY) PUH-10MYG : 50A
OUTDOOR UNIT
TR TRANSFORMER
FAN MOTOR (OUTDOOR)MF2,MF3
SYMBOL NAME F1,F2 FUSE (15A 250VAC CLASS T) 51C 52C 63L 63H1 63H2 MC COMPRESSOR MOTOR
LIQUID PIPE TEMP
OVER CURRENT RELAY (COMPRESSOR)
21S4 SV1 CH TB1,3,6,8 TH1 TH2
MAGNETIC CONTACTOR (COMPRESSOR) PRESSURE SWITCH (LOW PRESSURE)
4-WAY VALVE
X1 AUXILIARY RELAY
SOLENOID VALVE CRANK CASE HEATER (COMPRESSOR) TERMINAL BLOCK
PRESSURE SWITCH (HIGH PRESSURE) PRESSURE SWITCH (FOR CONTROL)
THERMISTOR
DISCHARGE TEMP
F01-F04
FUSE (6.3A 250VAC CLASS F)
X01-X05
LED1
SW1-5 SWITCH
AUXILIARY RELAY
LED (FOR SERVICE)
OUTDOOR MAIN BOARD
N.F.BOARD
F10-F30
FUSE (6.3A 250VAC CLASS F)
Caution,
1.To protect compressor from abnormal current, over current relays is installed. Therefore, do not change factory set value of over current relays.
6. mark is connector.
Note:1.The dotted lines show field wiring.
2.Color of earth wire is yellow and green twisting.
3.Specification subject to change without notice.
4.This motor(*1) includes auto reset type internal thermostat.
5.Indoor and outdoor connecting wires (*2) are made with polarities, make sure matching wiring and terminal.
OUTDOOR UNIT
C14
TR TRANSFORMER
FAN MOTOR (OUTDOOR)MF2
SYMBOL NAME F1,F2 FUSE (15A 250VAC CLASS T) 51C 52C 63L 63H1 63H2 MC COMPRESSOR MOTOR
LIQUID PIPE TEMP
OVER CURRENT RELAY (COMPRESSOR)
21S4 SV1 CH TB1,3 TH1 TH2
MAGNETIC CONTACTOR (COMPRESSOR) PRESSURE SWITCH (LOW PRESSURE)
4-WAY VALVE SOLENOID VALVE CRANK CASE HEATER (COMPRESSOR) TERMINAL BLOCK
PRESSURE SWITCH (HIGH PRESSURE) PRESSURE SWITCH (FOR CONTROL)
THERMISTOR
DISCHARGE TEMP
1
C11
1
C12
3
MF2
3 1
CN51
CN81
63H2
1
2
F01-F04
FUSE (6.3A 250VAC CLASS F)
X01-X05
LED1
SW1-5 SWITCH
AUXILIARY RELAY
LED (FOR SERVICE)
OUTDOOR MAIN BOARD
SV1
CH
63H1
63L
21S4
1
6
1 3 5 7
F10
F20
F30
CNOUT1
CNOUT2
1
6
5
11
3
3
1
35
CNIN
CNFC2
CNFAN
F.C. BOARD
CNPOW
3
1
F2
5
1
F03
LED1
SW4
1
OFF
ON
4
SW3
OFF
ON
1
2
SW5
OFF
ON
OFF
ON
1
SW1
661
SW2
TH2
CN28
CNS3
CNFG
CN20
TR
313
CN53
CNMNT
CN2
121
2
CN3
1
2
CN4CN40
1
L1
L2 L3
N
N
52C
51C
CN3N
CN27
CN24
CN3S
CNVMNT
CN3D
1
3
L1 L2 L3
3
1
CN34
DC power supply
Transmission Circuit
F02
F04
CNFC1
X05
X02
X04
X01
X03
MC
CN23
1 3
CN22
CN21
3
5
3
CN26
3
CN25
CN52
1
52C
52C
1
TH1
F1
F01
1
1
7
PE
51C
N.F.BOARD
Blue
Black
White
Red
Black
White
Red
Green/Yellow
TO INDOOR UNIT CONNECTING WIRES (*2) (POLER)
S3S2S1
MAIN BOARD
N.F.BOARD
F10-F30
FUSE (6.3A 250VAC CLASS F)
INDOOR UNIT
OUTDOOR UNIT CONTROL BOX
(*1)
TB3
TB1
POWER SUPPLY 3N~PE 380/400/415V 50HZ
CIRCUIT BREAKER PUH-5MYG : 30A
(FIELD SUPPLY) PUH-6MYG : 30A
Caution,
1.To protect compressor from abnormal current, over current relays is installed. Therefore, do not change factory set value of over current relays.
6. mark is connector.
Note:1.The dotted lines show field wiring.
2.Color of earth wire is yellow and green twisting.
3.Specification subject to change without notice.
4.This motor(*1) includes auto reset type internal thermostat.
5.Indoor and outdoor connecting wires (*2) are made with polarities, make sure matching wiring and terminal.
(No.2)
INDOOR
CONTROLLER BOARD
(No.1)
REMOTE CONTROLLER
BOARD
POWER BOARD
INDOOR
INDOOR POWER BOARD
(No.1)
(No.1)
(No.2)
INDOOR
CONTROLLER BOARD
(No.2)
TO OUTDOOR UNIT CONNECTING WIRES (POLAR)
TO OUTDOOR UNIT CONNECTING WIRES (POLAR)
C5 C6 C7
POWER SUPPLY 3N~PE 380/400/415V 50Hz
CIRCUIT BREAKER (FIELD SUPPLY) PEH-16,20MYC:15A
RED
WHITE
BLACK
RED
S2 S3
S1
OUTDOOR UNIT
TB3
TB8
OUT OUT IN IN
IN
IN
OUT
OUT
TB8
C02
1
2
3
4123
(*1)SW2
OFF
ON
5
4123
(*1)SW2
OFF
ON
5
TAB1
TAB1
FAN
CNDK
3
1
1573
X4 X5 X6
12345
SW1
OFF
ON
SWE
OFF
ON
CN20
CN21
CN41
CN29
1 2 3 4
1 2
1 2
2
1
CN2D
CN90
CN22
CN2L
CND
CN32
CN31
CN51
12345
FUSE
ZNR
3
1
3
11
2
DC13.1V
LED1 LED2 LED3
2
1
2
1
2
1
2
1
3
3
6
5
4
9
8
7
3
1 2
CN3C
3
1
CNSK
2
1
CN2S
DC
13.1V
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
FAN
CNDK
CND
CN32
CN31
CN51
12345
FUSE
ZNR
3
1
3
1
3
11
2
DC13.1V
1573
X4 X5 X6
LED1 LED2 LED3
2
1
2
1
2
1
2
1
3
3
6
5
4
9
8
7
3
1 2
CN3C
12345
SW1
OFF
ON
SWE
OFF
ON
CN20
CN21
CN41
CN29
1 2 3 4
1 2
1 2
2
1
FB11
PE
BLACK
WHITE
RED
52F
S1
4
1 2
OUTDOOR UNIT
TB3
S1 S2 S3
INDOOR UNIT CONTROL BOX
REMOTE CONTROLLER
S2 S3
TB5
TB6
MF1
TB2
LCD
N
L3
L2
L1
52F
X1
X1
X2
BLUE
RED
FB21
S1 S2 S3
X2
TH1-1 TH2-1 TH5-1
TH5-2
TH2-2
TH1-2
TB4-2
TB4-1
C01
1 2 3
49F
C01
5
FB12
FB22
51F
51F
CR
X4 X5 X6
X4 X5 X6
ZNR5~7
DSR
DSA
C5
SNB BOARD 1
SNB BOARD 2
Caution,
1.To protect fan motor from abnormal current,over current relays is installed. Therefore, do not change factory set value of over current relays.
7. mark is connector.
Note:1.The dotted lines show field wiring.
2.Color of earth wire is yellow and green twisting.
3.Specification subject to change without notice.
NOISE KILLER
CAPACITOR
C5~C7
SNB BOARD 1
ZNR5~7
VARISTOR
DSA,DSR
ARRESTER
C5
CAPACITOR
NOISE KILLER
SNB BOARD 2
AUXILIARY RELAYX4-6
MF1 51F
49F
TB2,4-1,4-2,5
TH1-1,1-2 TH2-1,2-2
FAN MOTOR (INDOOR) OVER CURRENT RELAY (INDOOR FAN MOTOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR) TERMINAL BLOCK
THERMISTOR
INDOOR UNIT
REMOTE CONTROLLER
FUSE FUSE (T6.3AL250V) ZNR VARISTOR
SW2 SWE LED1 LED (POWER SUPPLY) LED2 LED (POWER SUPPLY<REMOTE CONTROLLER>) LED3 LED (TRANSMISSION<INDOOR·OUTDOOR>)
4.Indoor and outdoor connecting wires are made with polarities,make sure matching wiring and terminal.
5.Emergency operation If a trouble occurs with either the remote controller or the indoor microcom­ puter and no other trouble exists, emergency operation for cooling or heating can be performed by changing the setting of switch (SWE) "ON" on the indoor controller board.
TH5-1,5-2
SWITCH(MODEL SELECTION)SW1 SWITCH(CAPACITY CORD) SWITCH(EMERGENCY OPERATION)
CR SURGE KILLER
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)52F
OUTDOOR UNIT
ROOM TEMP LIQUID PIPE TEMP COND/EVA TEMP
TERMINAL BLOCK
TERMINAL BLOCK
FERRITE COREFB11,FB12
6.SW2(*1) shows PEH-20MYC setting. (2 places) In case of PEH-16MYC setting is shown as below.
FB21,FB22
BOARD
CONTROLLER
INDOOR
NAME
NAME
SYMBOL
TB3,TB8
SYMBOL
TB6
X1,2 AUXILIARY RELAY
NAMESYMBOL
5
ON OFF
(*1)SW2
3214
Cooling Capacity (Standard Air Flow) ; PEH-5MYC
Outdoor DB˚C
Indoor Indoor Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF Q SHC SHF T/I
DB
˚C WB˚C kW kW kW kW kW kW kW kW kW kW kW kW kW kW
15 13.9 9.6 0.69 4.55 13.4 9.4 0.70 4.85 12.8 9.1 0.71 5.20 12.0 8.7 0.73 11.0 8.3 0.75 6.10
16 14.3 8.8 0.62 4.60 13.7 8.5 0.62 4.90 13.1 8.3 0.63 5.25 12.4 7.9 0.64 11.6 7.6 0.66 6.15
17 14.8 8.0 0.54 4.65 14.1 7.7 0.55 4.95 13.6 7.5 0.55 5.30 12.9 7.2 0.56 12.1 6.9 0.57 6.20
15 13.9 11.1 0.80 4.55 13.4 10.9 0.81 4.85 12.8 10.6 0.83 5.20 12.0 10.2 0.85 11.0 9.8 0.89 6.10
16 14.3 10.3 0.72 4.60 13.7 10.0 0.73 4.90 13.1 9.8 0.75 5.25 12.4 9.4 0.76 11.6 9.1 0.78 6.15
17 14.8 9.5 0.64 4.65 14.1 9.2 0.65 4.95 13.6 9.0 0.66 5.30 12.9 8.7 0.67 12.1 8.4 0.69 6.20
18 15.2 8.7 0.57 4.70 14.6 8.5 0.58 5.00 14.0 8.2 0.59 5.35 13.4 8.0 0.60 12.6 7.6 0.60 6.30
19 15.8 8.0 0.51 4.75 15.2 7.7 0.51 5.10 14.6 7.5 0.51 5.45 13.9 7.2 0.52 13.1 6.9 0.53 6.35
16 14.3 11.8 0.83 4.60 13.7 11.5 0.84 4.90 13.1 11.3 0.86 5.25 12.4 10.9 0.88 11.6 10.6 0.91 6.15
17 14.8 11.0 0.74 4.65 14.1 10.7 0.76 4.95 13.6 10.5 0.77 5.30 12.9 10.2 0.79 12.1 9.9 0.82 6.20
18 15.2 10.2 0.67 4.70 14.6 10.0 0.68 5.00 14.0 9.7 0.69 5.35 13.4 9.5 0.71 12.6 9.1 0.72 6.30
19 15.8 9.5 0.60 4.75 15.2 9.2 0.61 5.10 14.6 9.0 0.62 5.45 13.9 8.7 0.63 13.1 8.4 0.64 6.35
20 16.4 8.7 0.53 4.80 15.8 8.5 0.54 5.20 15.2 8.2 0.54 5.55 14.5 8.0 0.55 13.7 7.7 0.56 6.40
21 16.9 7.9 0.47 4.85 16.3 7.7 0.47 5.25 15.8 7.5 0.47 5.60 15.1 7.2 0.48 14.3 6.9 0.48 6.45
18 15.2 11.7 0.77 4.70 14.6 11.5 0.79 5.00 14.0 11.2 0.80 5.35 13.4 10.9 0.81 12.6 10.6 0.84 6.30
19 15.8 11.0 0.70 4.75 15.2 10.7 0.70 5.10 14.6 10.5 0.72 5.45 13.9 10.2 0.73 13.1 9.9 0.76 6.35
20 16.4 10.2 0.62 4.80 15.8 10.0 0.63 5.20 15.2 9.7 0.64 5.55 14.5 9.5 0.66 13.7 9.1 0.66 6.40
21 16.9 9.4 0.56 4.85 16.3 9.2 0.56 5.25 15.8 9.0 0.57 5.60 15.1 8.7 0.58 14.3 8.4 0.59 6.45
22 17.4 8.6 0.49 4.90 16.9 8.4 0.50 5.25 16.4 8.2 0.50 5.60 15.7 8.0 0.51 14.9 7.7 0.52 6.55
23 17.9 7.8 0.44 4.95 17.4 7.6 0.44 5.30 16.9 7.4 0.44 5.65 16.3 7.2 0.44 15.5 6.9 0.45 6.65
19 15.8 12.5 0.79 4.75 15.2 12.2 0.80 5.10 14.6 12.0 0.82 5.45 13.9 11.7 0.84 13.1 11.3 0.86 6.35
20 16.4 11.7 0.71 4.80 15.8 11.5 0.73 5.20 15.2 11.2 0.74 5.55 14.5 10.9 0.75 13.7 10.6 0.77 6.40
21 16.9 10.9 0.64 4.85 16.3 10.7 0.66 5.25 15.8 10.5 0.66 5.60 15.1 10.2 0.68 14.3 9.9 0.69 6.45
22 17.4 10.1 0.58 4.90 16.9 9.9 0.59 5.25 16.4 9.7 0.59 5.60 15.7 9.4 0.60 14.9 9.2 0.62 6.55
23 17.9 9.3 0.52 4.95 17.4 9.1 0.52 5.30 16.9 8.9 0.53 5.65 16.3 8.7 0.53 15.5 8.4 0.54 6.65
24 18.4 8.4 0.46 5.00 17.9 8.3 0.46 5.35 17.5 8.1 0.46 5.70 16.9 7.9 0.47 16.1 7.6 0.47 6.70
20 16.4 13.2 0.80 4.80 15.8 12.9 0.82 5.20 15.2 12.7 0.84 5.55 14.5 12.4 0.86 13.7 12.1 0.88 6.40
21 16.9 12.4 0.73 4.85 16.3 12.1 0.74 5.25 15.8 11.9 0.75 5.60 15.1 11.7 0.77 14.3 11.4 0.80 6.45
22 17.4 11.5 0.66 4.90 16.9 11.4 0.67 5.25 16.4 11.2 0.68 5.60 15.7 10.9 0.69 14.9 10.6 0.71 6.55
23 17.9 10.7 0.60 4.95 17.4 10.5 0.60 5.30 16.9 10.4 0.62 5.65 16.3 10.2 0.63 15.5 9.9 0.64 6.65
24 18.4 9.9 0.54 5.00 17.9 9.7 0.54 5.35 17.5 9.6 0.55 5.70 16.9 9.4 0.56 16.1 9.1 0.57 6.70
46.0
20
25.0 30.0 35.0 40.0
22
24
26
28
30
T/I
kW
5.60
5.70
5.75
5.60
5.70
5.75
5.80
5.85
5.70
5.75
5.80
5.85
5.95
6.00
5.80
5.85
5.95
6.00
6.05
6.10
5.85
5.95
6.00
6.05
6.10
6.15
5.95
6.00
6.05
6.10
6.15
Cooling Capacity (Standard Air Flow) ; PEH-6MYC
Outdoor DB˚C
Indoor Indoor Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF T/I Q SHC SHF T/I
DB
˚C WB˚C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
15 18.3 12.4 0.68 4.60 18.3 12.4 0.68 4.54 18.2 12.3 0.68 4.54 17.9 12.2 0.68 4.60 17.5 12.0 0.69 4.66 17.1 11.8 0.69 4.88
16 18.9 11.4 0.60 4.60 18.8 11.4 0.61 4.60 18.7 11.3 0.60 4.60 18.4 11.2 0.61 4.66 18.0 11.0 0.61 4.71 17.6 10.8 0.61 4.94
17 19.4 10.4 0.54 4.66 19.3 10.4 0.54 4.66 19.3 10.4 0.54 4.60 18.9 10.2 0.54 4.71 18.5 10.0 0.54 4.77 18.1 9.8 0.54 5.00
15 18.4 14.3 0.78 4.60 18.3 14.3 0.78 4.54 18.2 14.2 0.78 4.54 17.9 14.1 0.79 4.60 17.5 13.9 0.79 4.66 17.1 13.7 0.80 4.88
16 18.9 13.3 0.70 4.60 18.8 13.2 0.70 4.60 18.7 13.2 0.71 4.60 18.4 13.1 0.71 4.66 18.0 12.9 0.72 4.71 17.6 12.7 0.72 4.94
17 19.4 12.3 0.63 4.66 19.3 12.2 0.63 4.66 19.3 12.2 0.63 4.60 18.9 12.0 0.63 4.71 18.5 11.9 0.64 4.77 18.1 11.7 0.65 5.00
18 19.9 11.2 0.56 4.66 19.9 11.2 0.56 4.66 19.7 11.2 0.57 4.66 19.4 11.0 0.57 4.77 19.1 10.9 0.57 4.83 18.7 10.7 0.57 5.11
19 20.7 10.3 0.50 4.77 20.5 10.3 0.50 4.71 20.5 10.3 0.50 4.71 20.1 10.1 0.50 4.83 19.7 9.9 0.50 4.88 19.3 9.8 0.51 5.17
16 18.9 15.1 0.80 4.60 18.8 15.1 0.80 4.60 18.7 15.0 0.80 4.60 18.4 14.9 0.81 4.66 18.0 14.7 0.82 4.71 17.6 14.5 0.82 4.94
17 19.4 14.1 0.73 4.66 19.3 14.1 0.73 4.66 19.3 14.1 0.73 4.60 18.9 13.9 0.74 4.71 18.5 13.7 0.74 4.77 18.1 13.5 0.75 5.00
18 19.9 13.1 0.66 4.66 19.9 13.1 0.66 4.66 19.7 13.0 0.66 4.66 19.4 12.9 0.66 4.77 19.1 12.7 0.66 4.83 18.7 12.6 0.67 5.11
19 20.7 12.2 0.59 4.77 20.5 12.1 0.59 4.71 20.5 12.1 0.59 4.71 20.1 11.9 0.59 4.83 19.7 11.8 0.60 4.88 19.3 11.6 0.60 5.17
20 21.3 11.2 0.53 4.83 21.3 11.2 0.53 4.77 21.1 11.1 0.53 4.77 20.8 11.0 0.53 4.88 20.5 10.8 0.53 4.94 20.1 10.7 0.53 5.22
21 21.9 10.2 0.47 4.94 21.8 10.1 0.46 4.88 21.7 10.1 0.47 4.88 21.4 10.0 0.47 4.94 21.1 9.9 0.47 5.05 20.7 9.7 0.47 5.28
18 19.9 14.9 0.75 4.66 19.9 14.9 0.75 4.66 19.7 14.8 0.75 4.66 19.4 14.7 0.76 4.77 19.1 14.6 0.76 4.83 18.7 14.4 0.77 5.11
19 20.7 14.0 0.68 4.77 20.5 13.9 0.68 4.71 20.5 13.9 0.68 4.71 20.1 13.8 0.69 4.83 19.7 13.6 0.69 4.88 19.3 13.4 0.69 5.17
20 21.3 13.0 0.61 4.83 21.3 13.0 0.61 4.77 21.1 12.9 0.61 4.77 20.8 12.8 0.62 4.88 20.5 12.7 0.62 4.94 20.1 12.5 0.62 5.22
21 21.9 12.0 0.55 4.94 21.8 12.0 0.55 4.88 21.7 11.9 0.55 4.88 21.4 11.8 0.55 4.94 21.1 11.7 0.55 5.05 20.7 11.5 0.56 5.28
22 22.4 10.9 0.49 5.00 22.3 10.9 0.49 5.00 22.2 10.9 0.49 4.94 21.9 10.7 0.49 5.05 21.7 10.7 0.49 5.17 21.3 10.5 0.49 5.34
23 22.9 9.9 0.43 5.11 22.8 9.8 0.43 5.11 22.7 9.8 0.43 5.05 22.5 9.7 0.43 5.17 22.3 9.7 0.43 5.22 21.9 9.5 0.43 5.45
19 20.7 15.8 0.76 4.77 20.5 15.8 0.77 4.71 20.5 15.8 0.77 4.71 20.1 15.6 0.78 4.83 19.7 15.4 0.78 4.88 19.3 15.2 0.79 5.17
20 21.3 14.8 0.69 4.83 21.3 14.8 0.69 4.77 21.1 14.7 0.70 4.77 20.8 14.6 0.70 4.88 20.5 14.5 0.71 4.94 20.1 14.3 0.71 5.22
21 21.9 13.8 0.63 4.94 21.8 13.8 0.63 4.88 21.7 13.7 0.63 4.88 21.4 13.6 0.64 4.94 21.1 13.5 0.64 5.05 20.7 13.3 0.64 5.28
22 22.4 12.8 0.57 5.00 22.3 12.7 0.57 5.00 22.2 12.7 0.57 4.94 21.9 12.6 0.58 5.05 21.7 12.5 0.58 5.17 21.3 12.3 0.58 5.34
23 22.9 11.7 0.51 5.11 22.8 11.6 0.51 5.11 22.7 11.6 0.51 5.05 22.5 11.5 0.51 5.17 22.3 11.5 0.52 5.22 21.9 11.3 0.52 5.45
24 23.5 10.7 0.46 5.22 23.3 10.6 0.45 5.17 23.3 10.6 0.45 5.17 23.1 10.5 0.45 5.22 22.9 10.4 0.45 5.34 22.5 10.3 0.46 5.51
20 21.3 16.6 0.78 4.83 21.3 16.6 0.78 4.77 21.1 16.6 0.79 4.77 20.8 16.4 0.79 4.88 20.5 16.3 0.80 4.94 20.1 16.2 0.81 5.22
21 21.9 15.6 0.71 4.94 21.8 15.6 0.72 4.88 21.7 15.5 0.71 4.88 21.4 15.4 0.72 4.94 21.1 15.3 0.73 5.05 20.7 15.1 0.73 5.28
22 22.4 14.6 0.65 5.00 22.3 14.5 0.65 5.00 22.2 14.5 0.65 4.94 21.9 14.4 0.66 5.05 21.7 14.3 0.66 5.17 21.3 14.1 0.66 5.34
23 22.9 13.5 0.59 5.11 22.8 13.5 0.59 5.11 22.7 13.4 0.59 5.05 22.5 13.3 0.59 5.17 22.3 13.3 0.60 5.22 21.9 13.1 0.60 5.45
24 23.5 12.5 0.53 5.22 23.3 12.4 0.53 5.17 23.3 12.4 0.53 5.17 23.1 12.3 0.53 5.22 22.9 12.2 0.53 5.34 22.5 12.1 0.54 5.51
30
26
28
22
24
15.0 20.0
20
-5.0 0.0 5.0 10.0
Loading...
+ 107 hidden pages