Mitsubishi HWE05060 Service Manual

Page 1
SERVICE MANUAL
<indoor unit> Service ref.
Models
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
TM
1. REFERENCE MANUAL ····························· 2
2. SAFETY PRECAUTION ···························· 3
3. PART NAMES AND FUNCTIONS ············· 7
4. SPECIFICATION ······································· 9
6. OUTLINES & DIMENSIONS ···················· 12
7. WIRING DIAGRAM ·································· 13
8. REFRIGERANT SYSTEM DIAGRAM ······ 14
9. TROUBLESHOOTING ···························· 15
10
. DISASSEMBLY INSTRUCTIONS ············ 27
11
. PARTS LIST ············································· 29
12
. OPTIONAL PARTS ·································· 33
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
ON/OFF
TEMP.
Series PEAD
R407C/R410A
2005
NOTE:
• This manual describes only service data of the indoor units.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Page 2
2
REFERENCE MANUAL
1
Service Ref.
PUHZ-RP35/50/60/71/100/125/140VHA PUHZ-RP100/125/140YHA
PUHZ-RP71/100/125/140VHA-A
PUHZ-RP200/250YHA
PUHZ-RP200/250YHA-A
PU(H)-P·VGAA.UK PU(H)-P·YGAA.UK
SUZ-KA·VA.TH
Service Manual No.
OC334
OC337
OC338
OC339
OC336
OC322
1-1. OUTDOOR UNIT’S SERVICE MANUAL
Series (Outdoor unit)
PUHZ-RP·VHA(-A) PUHZ-RP·YHA(-A)
PU(H)-P·VGAA.UK PU(H)-P·YGAA.UK
Manual No.
OCS01
OCS02
1-2. TECHNICAL DATA BOOK
Page 3
3
SAFETY PRECAUTION
2
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
· R407C cylinder are available on the market has a syphon pipe.
· Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release the refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[1] Cautions for service
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Cautions for units utilising refrigerant R407C
CAUTIONS RELATED TO NEW REFRIGERANT
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Use ESTER , ETHER or HAB as the lubricant to coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Gravimeter
Unit
Page 4
4
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a or R407C.
5 Adapter for reverse flow check. ·Attach on vacuum pump.
6 Refrigerant charge base.
7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
Page 5
5
<Cautions for units utilizing refrigerant R410A>
CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the following. á For RP4 be sure to perform pipe replacement operation
before test run.
á Use flare nut as provided with this product.
Use a newly flared pipe.
áAvoid using thin pipes. For the detail, please refer to the
outdoor unit service manual No. OC294.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige- rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
If no reverse flow check valve is used, vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera- nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools (for R410A)
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur which is hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Contamination inside refrigerant piping can cause deterio- ration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com- pressor.
If large amount of mineral oil enter, that can cause deterio- ration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the system with the specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
Ensure that the cylinder for R410A is syphon type. Charging should be performed with the syphon cylinder type stood vertically. (Refrigerant must be charged from liquid phase.)
Page 6
6
Gravimeter
Unit
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Specifications
1
Gauge manifold • Only for R410A
• Use the existing fitting
specifications
.(UNF1/2)
• Use high-tension side pressure of 5.3MPa·G or over.
2
Charge hose • Only for R410A
• Use pressure performance of 5.09MPa·G or over.
3
Electronic scale
4
Gas leak detector • Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check • Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder • Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8
Refrigerant recovery equipment
Page 7
7
PART NAMES AND FUNCTIONS
3
Indoor Unit
Air intake (sucks the air from inside the room into the unit)
Air outlet
A
Page 8
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature. The room temperature display range is 8–39°C. The display flashes if the temperature is less than 8 °C or 39 °C or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is station­ary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
8
Remote controller
Display
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Built-in temperature sensor
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if the feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
Page 9
9
Service Ref. Power supply
Input kW Running current
1
1
1
1
A
Starting current A External finish Heat exchanger
Fan
Fan (drive) × No.
Fan motor output kW
Airflow (Lo-Hi)
m
3
/min <CFM>
External static pressure Pa Booster heater kW Operation control & Thermostat
Noise level (Lo-Hi)
dB (A)
Unit drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg (lbs)
Notes 1. Above data based on indicated voltage
Indoor Unit: Single phase 230V 50Hz Outdoor Unit: Single phase 230V 50Hz/3 phase 400V 50Hz
INDOOR UNIT
Weight
5/35/50Pa at 220V
10/50/70Pa at 230V
20/60/75Pa at 240V
Service Ref. Power supply
Input kW
Running current
1
1
1
1
A
Starting current A External finish Heat exchanger
Fan
Fan (drive) × No.
Fan motor output kW
Airflow (Lo-Hi)
m
3
/min <CFM>
External static pressure Pa Booster heater kW Operation control & Thermostat
Noise level (Lo-Hi)
dB (A)
Unit drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg (lbs)
INDOOR UNIT
Weight
5/35/50Pa at 220V
10/50/70Pa at 230V
20/60/75Pa at 240V
Service Ref. Power supply
Input kW
Running current
1
1
1
1
A
Starting current A External finish Heat exchanger
Fan
Fan (drive) × No.
Fan motor output kW
Airflow (Lo-Hi)
m
3
/min <CFM>
External static pressure Pa Booster heater kW Operation control & Thermostat
Noise level (Lo-Hi)
dB (A)
Unit drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg (lbs)
INDOOR UNIT
Weight
5/35/50Pa at 220V
10/50/70Pa at 230V
20/60/75Pa at 240V
Single phase, 50Hz, 220-240V
0.18
0.80
1.03
Galvanized sheets
Plate fin coil
Centrifugal (direct) × 2
0.10
16.5-21<582-741>
16-20<565-706> at 220V/5Pa, 230V/10Pa, 240V/20Pa
5/35/50Pa at 220V, 10/50/70Pa at 230V, 20/60/75Pa at 240V
Built in remote controller
32-36/33-39/34-41
33-37/35-40/36-42
35-39/37-42/37-43
32 (1-1/4)
1171 (46-1/8)
740 (29-1/8)
275 (10-13/16)
42 (93)
PEAD-RP60GA
Single phase, 50Hz, 220-240V
0.21
0.94
1.21
Galvanized sheets
Plate fin coil
Centrifugal (direct) × 2
0.10
20-25<706-883>
19-24<671-847> at 220V/5Pa, 230V/10Pa, 240V/20Pa
5/35/50Pa at 220V, 10/50/70Pa at 230V, 20/60/75Pa at 240V
Built in remote controller
34-37/35-40/36-42
35-38/37-41/37-43
37-40/38-42/38-43
32 (1-1/4)
1171 (46-1/8)
740 (29-1/8)
275 (10-13/16)
42 (93)
PEAD-RP71GA
Single phase, 50Hz, 220-240V
0.28
1.25
1.61
Galvanized sheets
Plate fin coil
Centrifugal (direct) × 2
0.16
26.5-33<935-1165>
25.5-32<900-1130> at 220V/5Pa, 230V/10Pa, 240V/20Pa
5/35/50Pa at 220V, 10/50/70Pa at 230V, 20/60/75Pa at 240V
Built in remote controller
38-42/40-45/40-46
40-43/42-45/42-46
42-45/43-46/43-47
32 (1-1/4)
1411 (55-9/16)
740 (29-1/8)
275 (10-13/16)
50 (111)
PEAD-RP100GA
SPECIFICATION
4
Page 10
10
14 15 16 17 18 19 20 21 22 23 24 25 26 27
14 15 16 17 18 19 20 21 22 23 24 25 26 27
14 15 16 17 18 19 20 21 22 23 24 25 26 27
0
10
20
30
40
50
60
70
80
90
100
110
Upper limit
120
130
Airflow rate (m3/min) Airflow rate (m3/min)
Fan performance <220V>
Extemal static pressure (Pa)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
Extemal static pressure (Pa)
Fan performance <230V>
Corrected air flow
High(50Pa)
High(35Pa)
High(10Pa)
High(50Pa)
High(70Pa)
High(5Pa)
Low
0
10
20
30
40
50
60
70
80
90
100
110
Upper limit
120
130
17
0.8
0.85
0.95
1.05
1.1
0.9
1
18 19 20 21 22 23 24 25 26 27 28
Airflow rate (m3/min)
Airflow (m
3
/min)
Fan performance <240V>
Extemal static pressure (Pa)
High(75Pa)
High(60Pa)
High(20Pa)
Low
Low
Upper limit
Correction factor
Cooling capacity
Heating capacity
PEAD-RP71GA
10
PEAD-RP60GA
12
0
10
20
30
40
50
60
70
80
90
100
110
Upper limit
120
130
13 14 15 16 17 18 19 20 21 22 23
Airflow rate (m3/min)
12 13 14 15 16 17 18 19 20 21 22 23
Airflow rate (m3/min)
Fan performance <220V>
Extemal static pressure (Pa)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
Extemal static pressure (Pa)
Fan performance <230V>
Corrected air flow
High(50Pa)
High(35Pa)
High(10Pa)
High(50Pa)
High(70Pa)
High(5Pa)
Low
12
0
10
20
30
40
50
60
70
80
90
100
110
120
130
13 14 15 16 17 18 19 20 21 22 23
14
0.8
0.85
0.95
1.05
1.1
0.9
1
15
Heating capacity
Cooling capacity
16 17 18 19 20 21 22 23 24 25
Airflow rate (m3/min)
Airflow (m
3
/min)
Fan performance <240V>
Extemal static pressure (Pa)
High(75Pa)
High(60Pa)
High(20Pa)
Low
Low
Upper limit
Upper limit
Correction factor
5
FAN PERFORMANCE AND CORRECTED AIR FLOW
Page 11
1111
PEAD-RP100GA
Fan performance <220V>
160 150 140
Upper limit
130 120 110 100
90 80 70 60 50 40 30 20 10
Extemal static pressure (Pa)
0
Low
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
Airflow rate (m3/min) Airflow rate (m3/min)
Fan performance <240V>
160 150 140
Upper limit
130 120 110 100
90 80 70 60 50 40 30 20 10
Extemal static pressure (Pa)
0
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
Low
Airflow rate (m3/min)
High(50Pa)
High(35Pa)
High(5Pa)
High(75Pa)
High(60Pa)
High(20Pa)
Fan performance <230V>
160 150 140
Upper limit
130 120 110 100
90 80 70 60 50 40 30 20 10
Extemal static pressure (Pa)
0
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
Low
Corrected air flow
1.1
1.05
Heating capacity
1
0.95
0.9
Correction factor
0.85
0.8 25
26 27 28 29 30 31 32 33 34 35 36 37
Airflow (m
High(10Pa)
Cooling capacity
3
/min)
High(70Pa)
High(50Pa)
Page 12
12
2. REMOTE CONTROLLER
6
OUTLINES & DIMENSIONS
1. INDOOR UNIT
PEAD-RP60, 71, 100GA
Air outlet
Air outlet
Air inlet
Refrigerant piping flare connection(liquid øH copper tube):HP Refrigerant piping flare connection(gas øJ copper tube):LP Electrical parts box Terminal bed : Power source Terminal bed : Remote control Filter Drain pan (R1 External thread: ø34)(;Fixable to opposition side.)
NOTE: IT IS NECESSARY TO REMOVE THE CEILING PARTS OR TO KEEP THE MAINTENANCE HOLE OF
OVER UNIT SIZE WHEN YOU HAVE A MAINTENANCE OR SERVICE THE FOLLOWING PARTS. SERVICE: MOTOR,SIROCCO FAN,HEAT EXCHANGER,DRAIN PAN (EXCHANGE) FILTER(IN CASE OF INDOOR UNIT HAVE INLET DUCT.) MAINTENANCE: HEAT EXCHANGER,DRAIN PAN(SURFACE WASHING) (WASHING) FILTER(IN CASE OF INDOOR UNIT HAVE INLET DUCT.)
Air inlet
In case of rear inlet
In case of bottom inlet
3
64
261
3.5
271.53.5
D
120XE=F
120 86
15
48
Opposition side
7
66
78
A
2XG-ø2.9
2XG-ø2.8
6
7
6 5 4 1 2
Access door
33
260
86.5
120
10010018
236.6
236.614
296
2X3-ø2.9
2X2-ø3
162
130 16
19.5
Service space:550 or more
179
250~350
450
450
39
100~200
86
15
609.6 (Lifting bolt pitch)
75
15
15.5
C(Lifting bolt pitch)
46
20
680
100
D
D
100
30
237
18
120
120XE=F
86
B
15
30
39
120xE=F
15
2
1
3 4 5 6 7
Setting at shipment
J
HGFEDCBAModel
Outdoor unit(MUZ,SUZ);6.35 Other outdoor unit;9.52
84071012105010901125
RP60
R410A Outdoor unit;15.88 R407C Outdoor unit;19.05
1365 1330 1290 1252 9 1080
1125 1090 1050 1012 7 840
8
10
8
15.88
15.88
9.52
9.52
RP100
RP71

     




Page 13
13
7
WIRING DIAGRAM
TO MA-REMOTE CONTROLLER DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1
ZNR
<A>
FUSE
N
L
S1 S2
12
21
12
S3
TO CND
TO OUTDOOR UNIT
TO CN3C
P.B.
I.B.
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR. OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
POWER SUPPLY ~(1PHASE) 230V 50Hz
Capacity cord switch
Model selection switch
SW2SW1
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
ON OFF
12345
ON OFF
12345
ON OFF
12345
COND./EVA. TEMP. THERMISTOR (0
°C/15K,25°C/5.4K DETECT)
PIPE TEMP. THERMISTOR/LIQUID (0
°C/15K,25°C/5.4K DETECT)
INTAKE AIR TEMP.THERMISTOR (0
°C/15K,25°C/5.4K DETECT)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAMENAME
SYMBOLSYMBOL
NAME
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
X1
Y L W
O R N
X6X5X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B L U
B
L
U
B L U
B L U
(BLK)
(WHT)
(RED)
(BLU)
B L K
W H T
BLK
WHT
(WHT)
(BLU)
B R N
BRN
O R N
ORN YLW
(BLU)(RED)(ORN)
(RED)
(WHT)
B L K
W H
T
B L K
W
H T
(WHT)
(WHT)
O R G
B L K
B L U
B L K
Y L W
Y L W
G R Y
??A
54321
OFF
ON
100GA
71GA
60GA
MODELS
*
(FACTORY SHIPMENT)
240V230V220V
20Pa
60Pa
75Pa
10Pa
50Pa
70Pa50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2 1
TB5
TB4
S3
S1
S2
2 1
CNP
1331
31
13
CNSK
2
1
CN2S
643521
MF
C
1
2
CN24
3
21
12
3
1
2
121
2
TH5TH2
TH1
LED1 LED2 LED3
1
2
CN2D
CN3C
31
CND CNDK
137
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789
4
321
54321
INSIDE SECTION OF CONTROL BOX
NOTE 1.SINCE THE OUTDOOR SIDE ELECTRIC WIRING MAY CHANGE BE SURE
TO CHECK THE OUTDOOR UNIT ELECTRIC WIRING FOR SERVICING.
2.INDOOR AND OUTDOOR CONNECTING WIRES ARE MADE WITH POLARITIES, MAKE WIRING MATCHING TERMINAL NUMBERS(S1,S2,S3).
3.SYMBOLS USED IN WIRING DIAGRAM ABOVE ARE,
:CONNECTOR, :TERMINAL.
4.THE WIRING BETWEEN MA-REMOTE CONTROLLER AND TB5 IS INCLUDED IN THE PACKAGE.
(IN CASE OF CONNECT THE REPLACEMENT WIRING)
*External static pressure
PEAD-RP60, 71, 100GA
Page 14
14
8
REFRIGERANT SYSTEM DIAGRAM
PEAD-RP60, 71, 100GA
Indoor unit
Indoor heat exchanger
Thermistor TH5 (Cond./Eva. temperature)
Strainer
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant GAS pipe connection
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature (Liquid)
Distributor with strainer
Refrigerant LIQUID pipe connection
Page 15
15
9
TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check the contents below before investigating details.
9-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (9-2).
Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (9-3).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (9-3). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
Page 16
16
9-2. SELF-DIAGNOSIS ACTION TABLE
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P1
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90: or more Open: -40: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
13 Check resistance value of thermistor. 0: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 9-6. Tu rn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Tu rn the power off, and on again to operate after check.
P2
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90: or more Open: -40: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90: or more or -40: or
less.
5 Defective indoor controller board.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 9-6. Turn the power on and check restart after insert­ing connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
Tu rn the power off, and on again to operate after check.
P4
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Tu rn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or room temperature is short/open temperature.
• During drain pomp operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.
0: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 9-6. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Tu rn the power off, and on again to operate after check.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pomp is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pomp
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from lead wire.
• Clogged filter is causing wave of drain.
4 Defective indoor controller board.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 9-6.
Tu rn the power off, and on again to operate after check.
Page 17
17
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evap­orator> temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode. <Frost prevention mode> If pipe <liquid or condenser-evaporator> temperature is 2: or below when 16 minutes has passed after compressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe <liquid or condenser/evaporator> temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
2 Overheating protection (Heating mode)
The units is in six-minute resume prevention mode if pipe <condenser / evaporator> temperature is detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again within 10 minutes after six-minute resume prevention mode.
P8
1 Slight temperature difference
between indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe <condenser / evaporator> temperature thermistor
5 Stop valve is not opened
completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 9-6.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's
winding. Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 9-6.
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid or condenser/evapo­rator pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 deg ] (TH-TH1) TH: Lower temperature between: liquid
pipe temperature (TH2) and con­denser/evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode> When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrost­ing mode is over)
Heating range : 3 deg [ (TH5-TH1)
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room temperature display on remote controller and outdoor controller circuit board. Pipe <liquid or condenser / evaporator> temperature display is indicated by setting SW2 of outdoor controller circuit board as follows.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
Conduct temperature check with outdoor controller circuit board after connecting ‘A-Control Service Tool(PAC-SK52ST)’.
(
)
Page 18
18
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P9
Abnormality of pipe temperature ther­mistor / Condenser-Evaporator (TH5)
1 The unit is in three-minute resume pro-
tection mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within three min­utes. (The unit returns to normal opera­tion, if it has normally reset.)
2 Constantly detected during cooling, dry-
ing, and heating operation (except defrosting) Short: 90: or more Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Temperature of thermistor is
90: or more or -40: or less caused by defective refrigerant circuit.
5 Defective indoor controller
board.
13 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board. Refer to 9-6. Tu rn the power on and check restart after inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with outdoor controller circuit board. If pipe <condenser / evaporator> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with outdoor control circuit board. If there is exclusive difference with actual pipe <condenser / evaporator> temperature replace indoor controller board. There is no abnormality if none of above comes within the unit. Tu rn the power off and on again to operate.
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Check wiring of remote controller.
•Total wiring length: max.500m (Do not use cablex 3 or more)
• The number of connecting indoor units: max.16units
• The number of connecting remote con­troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller. c) When “RC E3” is displayed, d) When “ERC 00-06” is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem.
Put the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board. b)When “RC NG”is displayed, replace
remote controller. c)When “RC E3”or “ERC 00-66”is displayed,
noise may be causing abnormality.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote controller.
1 Tw o remote controller are set
as “main.”
(In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address.
4 Defective transmitting receiving
circuit of remote controller.
5 Defective transmitting receiving
circuit of indoor controller board.
6 Noise has entered into trans-
mission wire of remote con­troller.
In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service tool (PAC-SK52ST).
(
)
Page 19
19
E6
1 Contact failure, short circuit or,
mis-wiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Check LED display on the outdoor control cir-
cuit board. (Connect A-control service tool, PA C-SK52ST.) Refer to EA-EC item if LED displays EA-EC.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or outdoor unit.
Check all the units in case of twin triple indoor unit system.
2-4 Tu rn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
Other indoor controller board may have
defective in case of twin triple indoor unit system.
E7
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.
1 Defective transmitting receiving
circuit of indoor controller board
2 Noise has entered into power
supply.
3 Noise has entered into outdoor
control wire.
1-3 Tu rn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for six minutes after putting the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for three minutes.
3 Consider the unit abnormal under the
following condition: When two or more indoor units are connected to one outdoor unit, indoor controller board cannot receive a signal for three minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals.
Error Code
Meaning of error code and detection method
Cause
Countermeasure
Fb
Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board.
1 Replace indoor controller board.
E1
or
E2
Abnormality of remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1 Defective remote controller.
1 Replace remote controller.
Page 20
20
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board.
4 Defective indoor power board.
9-3. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
Cause
Countermeasure
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board.
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board.
5 Defective indoor controller board.
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L
3, N).
• When AC 220~240V is not detected. Check the power wiring to outdoor unit and the breaker.
• When AC 220~240V is detected. —Check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected. Check the fuse on outdoor controller circuit board. Check the wiring connection.
• When AC 220~240V is detected. —Check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected. Check indoor/outdoor unit connecting wire for mis-wiring.
• When AC 220~240V is detected. —Check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 9-6-1.
• When no voltage is output. Check the wiring connection.
• When output voltage is between DC12.5V and DC13.7V. —Check 5 (below).
5 Check the wiring connection between
indoor controller board and indoor power board. Check the fuse on indoor controller board. If no problems are found, indoor controller board is defective.
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant address “0”.)
1 Reconfirm the setting of refrigerant
address for outdoor unit
Set the refrigerant address to “0”. (For grouping control system under which 2 or more outdoor units are connected, set one of the units to “0”.) Set refrigerant address using SW1 (3-6) on outdoor controller circuit board.
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected. Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method of connecting the connectors. Connect the connector correctly refer­ring to installation manual of an optional kit.
• When there is no problem in the method of connecting the connectors.
-Check 3 (below).
3 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
• When AC220~240V is detected.
-Check 4 (below).
4 Check voltage output from CN2S on
indoor power board.
• When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
• When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor controller board is defective.
Page 21
21
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How to check the parts”.)
• Check for breaking of wire or connec­tion failure of connector.
• Check “Up/down vane setting”. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena
Cause
Countermeasure
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units whose refrigerant address is 0.
3 Short-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units
are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the short-cut of remote controller wires.
• When LED2 is lit, connect remote controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board.
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced, replace wireless remote controller board.
Page 22
22
9-4. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occurs, emergency operation starts as the indoor controller board switch (SWE) is set to ON. During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation (2) Drain-up machine operation
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation. (4) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit. (5) After completing the emergency operation, return the switch setting, etc. in former state. (6) Since vane does not work at emergency operation, position the vane manually and slowly.
Page 23
23
9-5. HOW TO CHECK THE PARTS
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Par ts name Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester (winding temp. 20°C).
(Refer to the thermistor)
Room temperature thermistor (TH1)
Pipe temperature thermistor (TH2)
Condenser/Evaporator temperature thermistor (TH5)
Fan motor (MF)
Normal
4.3k"~9.6k"
Motor terminal
Orange-Gray
Orange-Black
Black-Blue
Blue-Yellow
Yellow-Red
Orange-Red
Protector
OPEN
CLOSE
RP60,71
145±5°C
94±15°C
RP100
135±5°C
86±15°C
RP60, 71
35.0"
10.3"
5.87"
6.97"
21.4"
-
RP100
35.2"
2.63"
3.00"
7.01"
-
50.7"
Abnormal
Open or short
Normal
Abnormal
Open or short





 
   
 :
 
"
<Thermistor Characteristic graph>
Room temperature thermistor(TH1) Pipe temperature thermistor(TH2) Condenser/evaporator temperature thermistor(TH5)
Thermistor R
0=15k" ±3%
Fixed number of B=3480k" ±2%
Rt=15exp { 3480( ) }
0: 15k" 10: 9.6k" 20: 6.3k" 25: 5.2k" 30: 4.3k" 40: 3.0k"
Thermistor for lower temperature
1
273+t
1
273
Page 24
24
9-6.TEST POINT DIAGRAM
9-6-1. Power board PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
CNSK Connect to the indoor controller board (CNDK) Between
11
to 33220-240V AC
CN2S Connect to the indoor controller board (CN2D) Between
11
to
33
12.6-13.7V DC (Pin11(+))
Page 25
25
9-6-2. Indoor controller board PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
FAN Fan motor output
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2) (220~240V AC)
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
FUSE (6.3A 250V)
CND Power supply input (220~240V AC)
SWE Emergency operation
SW2 Capacity setting
SW1 Model setting
CN2L Connector (LOSSNAY)
CN51 Centrally control
CN6V Vane motor output (MV)
CN90 Connect to the wireless remote controller board (CNB)
CN31 Drain sensor (DS)
CN29 Condenser/evaporator temperature thermistor (TH5)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN22 Remote controller connecting wire (10.4~14.6V DC)
LED3 Tr ansmission (Indoor/outdoor)
LED2 Power supply (R.B)
LED1 Power supply (I.B)
CN2D Connector to the indoor power board (CN2S) (12.5~13.7V DC)
CN3C Tr ansmission (Indoor/outdoor) (0~24V DC)
}
}
Non polarity
+
+
CN41 Connector (HA terminal-A)
Page 26
26
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model
settings
Capacity settings
Pair number setting with wireless remote controller
For service board
Remarks
SW2
J41 J42
Unit type setting
JP1
Indoor controller board type setting
JP3
0 1 2
3 ~ 9
Wireless remote controller setting
Control PCB setting
J41 J42
<Settings at time of factory shipment> Wireless remote controller: 0 Control PCB: (for both J41 and J42) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper line is disco­nnected.)
There is no jumper (JP1) because these models have the cond./eva. temperature thermistor (TH5).
(Marks in the table below) Jumper wire ( : Short : Open)
Without TH5
With TH5
Model
JP1
Factory shipment
Service parts
Indoor controller board type
JP3
12345
ON
OFF
Service board
MODELS
1 2 3 4 5
1 2 3 4 5
PEAD-RP60GA
ON OFF
PEAD-RP71GA
1 2 3 4 5
ON OFF
PEAD-RP100GA
ON OFF
9-7. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board. SW1 and SW2 are equipped only for service parts. Model setting and capacity setting are memorized in the nonvolatile memory of the control p.c. board of the unit.
Page 27
27
10
DISASSEMBLY INSTRUCTIONS
Figure1.
1. Removing the fan motor
1. Remove the screws that fix the bottom plate A,
and remove it.
2. Removing the drain pan as follows: (1) Remove the screws that fix the drain pan.
(2) Slide the drain pan in the direction
1, Figure1
and unhook the drain pan catches.
(3) Slide the drain pan in the direction
2, Figure1
and unhook the 2 catches on the other side of the drain pipe.
3. Remove the screws that fix the bottom plate assem-
bly, and remove it.
4. Disconnect the fan motor connector from the con-
troller box.
5. Remove the sirocco fan setting screw and the motor fixture setting screw to remove the motor fixture. Remove the other motor fixture as well, and then remove the fan motor. (Figure 2)
6. Remove the 8 screws that fix fan housing.
 
   
    

1
2
 
A
 
 
  
   
Page 28
28
Figure2.
Fan base
Sirocco fan
Motor
Housing
assembly
Piece
Bush
Piece
Motor base
Leg
Bush
Sirocco fan
Housing assembly
Page 29
29
11
PARTS LIST
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
EXTERNAL PARTS
10.11
1.2
8.9
3.4
5.6.7
Part No. Part Name Drawing No.
No.
1
S70 071 669
2
S70 072 669
S70 061 669
3
4
S70 062 669
5
S70 K01 480
S70 K02 480
6
7
S70 K03 480
8
S70 061 529
9
S70 071 529
10
S70 061 500
11
S70 071 500
Bottom plate 1 ass’y
H.EX. General ass’y
Filter
W652372Z05Bottom plate 2
W652372Z07Bottom plate 2
W902770G01
W902770G02Bottom plate 1 ass’y
W274422G06H.EX. General ass’y
W274422G04
W274422G05H.EX. General ass’y
W906341G01Drain pan ass’y
W906341G02Drain pan ass’y
W652374G04
W652374G03Filter
PEAD-
RP60GA
1
1
1
1
1
Qt’y/set
PEAD-
RP71GA
1
1
1
1
1
PEAD-
RP100GA
1
1
1
1
1
Spec.
Page 30
30
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
7
8
2
1
2
1.16
5.6
5.6
9.10
11.12
17.18
8
7
3.4
13.14.15
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Part No. Part Name Drawing No.
Qt’y/set
R02F328H09 2
2
22
2
2
2
2
2
2
22
11
1
1
1
1
2
1
11
1
1
1
11
1
R02F328G84
W491760H02
W126471G01
W903428G02
P714913X01
P412291X01
R02G131H07
P412292X01
W353715H01
W634069Z02
W902771Z03
with a nut
Piece
Piece
Bush
W902772G08Fan base ass’y
W902772G07Fan base ass’y
Sirocco fan
Housing ass’y
Motor
Leg
Capacitor 6
W241060H03Motor support
P714914X01Motor
Capacitor 8
Attachment
Motor base
Motor base
P412209X01Capacitor 4
R31F676H01
S70 507 131
S70 507 132
S70 768 105
S70 Y05 114
S70 980 110
S70 Y02 220
S70 510 255
S70 883 130
S70 610 255
S70 652 131
S70 090 130
S70 031 130
S70 710 677
S70 610 677
S70 090 130
S70 Y03 220
S70 710 255
S70 755 105 Bush
PEAD-
RP60GA
PEAD-
RP71GA
PEAD-
RP100GA
Page 31
31
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
CONTROL BOX PARTS
4
7
5
3
6
Earth post
2
1
Part No. Part Name Drawing No.
No.
1
S70 979 717
S70 435 717
2
S70 K06 313
3
4
S70 KW3 202
5
S70 KW2 202
6
S70 KW1 202
7
S70 K70 310
8
9
10
Terminal bed
Terminal bed
Power Board
Thermistor
Thermistor
Thermistor
Controller Board
P436110X01
BA73S950H02
RG00B435F08
W905588G01
W906303G02
W906303G01
RG00D008B02
PEAD-
RP60GA
1
1
Qt’y/set
PEAD-
RP71GA
PEAD-
RP100GA
111
111
111
111
111
11
11
Spec.
< TB4 >
< TB5 >
PWB
<TH1> RED
< TH2 > WHITE
<
TH5 > BLACK
I.B
Page 32
32
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
ELECTRICAL PARTS
1
TEMP.
ON/OFF
No. Part No. Part Name Drawing No.
1
2
S70 030 305
Remote controllerS70 KW1 713
Remote controller cable
P972122X01
W873334G05
Qt’y/set
PEAD-
PEAD-
PEAD-
RP100GA
RP71GA
RP60GA
111
111
Spec.
MA Remo-con
10 m
Page 33
33
1. REMOTE SENSOR
2. REMOTE OPERATION ADAPTER
3. REMOTE ON/OFF ADAPTER
4. INSULATION KIT
12
OPTIONAL PARTS
Part No. PAC-SE41TS-E
PEAD-RP60,71,100GAApplied model
Part No. PAC-SF40RM-E
PEAD-RP60,71,100GAApplied model
Part No. PAC-SE55RA-E
PEAD-RP60,71,100GAApplied model
Part No. PAC-SK010DK
PEAD-RP60,71,100GAApplied model
Page 34
HWE05060 Issued in Aug. 2005 Printed in Japan
New publication, effective Aug. 2005. Specifications subject to change without notice.
TM
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Loading...