Mitsubishi HWE05030 Service Manual

Models
PQRY-P200, P250YGM-A PQRY-P400, P500YSGM-A CMB-P104, P105, P106, P108, P1010, P1013, P1016V-G CMB-P108, P1010, P1013, P1016V-GA CMB-P104, P108V-GB PQHY-P200, P250YGM-A PQHY-P400, P500YSGM-A
Service Handbook
AIR CONDITIONERS CITY MULTI
Service Handbook PQRY-P200, P250YGM-A
PQRY-P400, P500YSGM-A CMB-P104, P105, P106, P108, P1010, P1013, P1016V-G CMB-P108, P1010, P1013, P1016V-GA CMB-P104, P108V-GB PQHY-P200, P250YGM-A PQHY-P400, P500YSGM-A
Issued in Oct. 2005 HWE05030 Printed in Japan
New publication effective Oct. 2005.
Specifications subject to change without notice.
Service Handbook PQRY-P200, P250, P400, P500Y(S)GM-A
Contents
1 Read Before Servicing ................................................................ 6
[1] Items to Be Checked .............................................................. 6
[2] Necessary Tools and Materials .............................................. 7
[3] Piping Materials ...................................................................... 8
[4] Storage of Piping Material ...................................................... 10
[5] Piping Machining .................................................................... 11
[6] Brazing.................................................................................... 12
[7]
Airtightness Test
...................................................................... 13
[8] Vacuuming .............................................................................. 13
[9] Vacuum Drying........................................................................ 14
[10] Changing Refrigerant.............................................................. 15
[11] Remedies to be taken in case of a refrigerant leak................ 15
[12]
Characteristics of the Conventional and the New Refrigerants
.. 16
[13] Notes on Refrigerating Machine Oil........................................ 17
2 Restrictions .................................................................................. 18
[1] Electrical Work & M-NET control ............................................ 18
[2] Types of Switch Setting and Address Setting ........................ 19
[3] Examples of system connection ............................................ 22
[4] Restrictions on Refrigerant Piping Length.............................. 38
3 Components of the Heat source Unit .......................................... 52
[1] Appearance of the Components and Refrigerant Circuit........ 52
[2] Control Box ............................................................................ 57
[3] Circuit Board .......................................................................... 59
[4] BC controller (inside the panel) .............................................. 63
[5] BC control box ........................................................................ 66
[6] BC controller board ................................................................ 66
4 Remote Controller ........................................................................ 68
[1]
Functions and Specifications of MA and ME Remote Controllers
.... 68
[2] Group Setting and Interlocking Settings that are Made on
an ME Remote Controller...................................................... 69
[3]
Interlocking Setting via the MA Remote Controller
........................ 73
[4] Switching to the built-in Thermo on the remote controller ...... 76
5 Electrical Wiring Diagram ............................................................ 77
[1] PQRY-P200, P250YGM-A, PQRY-P400, P500YSGM-A ........ 77
[2] CMB-P104V-G ........................................................................ 78
[3] CMB-P105, 106V-G ................................................................ 79
[4] CMB-P108, 1010V-G .............................................................. 80
[5] CMB-P1013, 1016V-G ............................................................ 81
[6] CMB-P104V-GB...................................................................... 82
[7] CMB-P108V-GB...................................................................... 83
[8] CMB-P108, 1010V-GA............................................................ 84
[9] CMB-P1013, 1016V-GA.......................................................... 85
[10]Power Dispatching Extension Unit for the Transmission
Lines...................................................................................... 86
6 Refrigerant Circuit ........................................................................ 87
[1] Refrigerant Circuit Diagram .................................................... 87
[2] Functions of Principal Parts.................................................... 93
[3] BC controller .......................................................................... 95
7 Control.......................................................................................... 97
[1] Dip Switch Functions and Their Factory Settings .................. 97
[2] Controlling the Heat source Unit ............................................ 102
[3] Operation Flow Chart ............................................................ 114
8 Test Run ...................................................................................... 120
[1] Check Items before Test Run.................................................. 120
[2] Test Run Method .................................................................... 120
[3] Operating Characteristics and Refrigerant Amount................ 121
[4] Adjustment and Judgment of Refrigerant Amount ................ 121
[5] Refrigerant Volume Adjustment Mode Operation .................. 124
[6] Symptoms that do not Signify Problems ................................ 128
[7]
Standard Operation Data (Reference Data)
.............................. 129
9 Troubleshooting............................................................................ 133
[1] Check Code List .................................................................... 133
[2] Responding to Error Display on the Remote Controller ........ 135
[3] Investigation of Transmission Wave Shape/Noise .................. 170
[4] Troubleshooting of Principal Parts .......................................... 173
[5] Refrigerant Leak .................................................................... 204
[6] BC controller service instruction ............................................ 208
0 LED display .................................................................................. 211
[1] LED Monitor Display .............................................................. 211
Safety Precautions
Symbols used in the text
Warning:
Failure to follow all instructions may result in serious personal injury or death.
Caution:
Failure to follow all instructions may result in personal injury or damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Beware of electric shock (This symbol is displayed on the main unit label.) <Color : Yellow>
Warning : Carefully read the labels affixed to the main unit.
Before installing the unit, be sure to carefully read all of the following safety precautions.
These precautions provide important information regarding safety. Be sure to follow them to ensure safety.
After reading this handbook, hand it over to those who will be using the unit. The user of the unit should keep this manual at hand and make it available to those who will be performing repairs or relocating the unit. Also, make it available to the new user when the user changes hands.
Be sure to carefully follow each step in this handbook when installing the unit.
Improper installation may result in water leak,
electric shock, smoke or fire.
Securely attach the terminal cover (panel) on the unit.
If installed improperly, dust and/or water may enter
the unit and present a risk of electric shock, smoke, or fire.
Only use Refrigerant R410A as indicated on the unit when installing or relocating the unit.
The use of any other refrigerant or an introduction of
air into the unit circuit may cause the unit to run an abnormal cycle and cause the unit to burst.
Do not make any changes or modifications to the unit. In case of problems, consult the dealer.
If repairs are not made properly, the unit may leak
water and present a risk of electric shock, or it may produce smoke or cause fire.
Have all electrical work performed by a licensed electrician according to the local regulations and the instructions given in this manual. Secure a circuit designated exclusively to the unit.
Improper installation or a lack of circuit capacity may
cause the unit to malfunction or present a risk of electric shock, smoke, and fire.
Have the unit professionally installed.
Improper installation by an unqualified person may
result in water leak, electric shock, or fire.
Only use specified cables for wiring. Securely connect each cable, and make sure that the cables are not straining the terminals.
Cables not connected securely and properly may
generate heat and cause fire.
Place the unit on a stable, level surface that withstands the weight of the unit to prevent the unit from tipping over or falling causing injury as a result.
Take necessary safety measures against typhoons and earthquakes to prevent the unit from falling over.
- 1 -
When relocating the air conditioner, consult the dealer or a specialist.
Improper installation may result in water leak,
electric shock, or fire.
Consult the dealer for necessary measures to take.
After completing the service work, check for a refrigerant gas leak.
If leaked gas refrigerant is exposed to a heart
source such as fan heater, stove, and electric grill, noxious gases may form.
In the event of a refrigerant gas leak, provide adequate ventilation to the room.
If leaked refrigerant gas is exposed to a heat source,
noxious gases may form.
With All-Fresh type air conditioners, outdoor air may be directly blown into the room upon thermo off. Take this into consideration when installing the unit.
Direct exposure to outdoor air may present a health
hazard, and it may also cause food items to deteriorate.
When installing the unit in a small room, safeguard against hypoxia that results from leaked refrigerant reaching the threshold level.
Precautions for Handling Units for Use with R410A
Caution
Warning : Carefully read the labels affixed to the main unit.
Do not try to defeat the safety features of the devices, and do not change the settings.
Defeating the safety features on the unit such as the
pressure switch and temperature switch or using parts other than those specified by Mitsubishi Electric may result in fire or explosion.
Use refrigerant pipes made of C1220 phosphorus deoxidized copper categorized under H3000 (Copper and Copper Alloy Seamless Pipes and Tubes), a standard set by JIS. Keep the inner and outer surfaces of the pipes clean and free of contaminants such as sulfur, oxides, dust/dirt, shaving particles, oils, and moisture.
Contaminants inside the refrigerant piping will cause
the refrigerant oil to deteriorate.
Do not use the following tools that have been used with the conventional refrigerants.Prepare tools that are for exclusive use with R410A. (Gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.)
If refrigerant and /or refrigerant oil left on these tools
are mixed in with R410A, or if water is mixed with R410A, it will cause the refrigerant to deteriorate.
Since R410A does not contain chlorine, gas-leak
detectors for conventional refrigerators will not work.
Only use specified parts.
Have the unit professionally installed.
Improper installation may cause water leak, electric shock, smoke, or fire.
Use a vacuum pump with a reverse-flow-check valve.
If other types of valves are used, the vacuum pump
oil will flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Do not use the existing refrigerant piping
The old refrigerant and refrigerator oil in the existing
piping contain a large amount of chlorine, which will cause the refrigerator oil in the new unit to deteriorate.
R410A is a high-pressure refrigerant, and the use of
the existing piping may result in bursting.
- 2 -
Before Installing the Unit
Warning
Caution
Store the piping to be used during installation indoors, and keep both ends of the piping sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
If dust, dirt, or water enters the refrigerant cycle, it
may cause the oil in the unit to deteriorate or may cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flange connections.
A large amount of mineral oil will cause the
refrigerating machine oil to deteriorate.
Do not use a charging cylinder.
The use of charging cylinder will change the
composition of the refrigerant and lead to power loss.
Exercise special care when handling the tools.
An introduction of foreign objects such as dust, dirt,
or water into the refrigerant cycle will cause the refrigerating machine oil to deteriorate.
Only use R410A refrigerant.
The use of refrigerants containing chlorine (i.e. R22)
will cause the refrigerant to deteriorate.
Use liquid refrigerant to charge the system.
Charging the unit with gas refrigerant will cause the
refrigerant in the cylinder to change its composition and will lead to a drop in performance.
Do not install the unit in a place where there is a possibility of flammable gas leak.
Leaked gas accumulated around the unit may start a
fire.
Do not use the unit to preserve food, animals, plants, artifacts, or for other special purposes.
The unit is not designed to provide adequate
conditions to preserve the quality of these items.
When installing the unit in a hospital, take necessary measures against noise.
High-frequency medical equipment may interfere
with the normal operation of the air conditioning unit or the air conditioning unit may interfere with the normal operation of the medical equipment.
Do not use the unit in an unusual environment.
The use of the unit in the presence of a large
amount of oil, steam, acid, alkaline solvents, or special types of sprays may lead to a remarkable drop in performance and/or malfunction and presents a risk of electric shock, smoke, or fire.
The presence of organic solvents, corroded gas
(such as ammonia, sulfur compounds, and acid) may cause gas or water leak.
Do not place the unit on or over things that may not get wet.
When humidity level exceeds 80% or when the
drainage system is clogged, indoor units may drip water.
Installation of a centralized drainage system for the
outdoor unit may also need to be considered to prevent water drips from the outdoor units.
- 3 -
Before Installing (Relocating) the Unit or Performing Electric Work
Caution
Warning
Do not spray water on the air conditioners or immerse the air conditioners in water.
Water on the unit presents a risk of electric shock.
Install a breaker for current leakage at the power source to avoid the risk of electric shock.
Without a breaker for current leakage, there is a risk
of electric shock, smoke, or fire.
Use wires that are specified in the installation manual.
The use of other types of wires presents a risk of
electrical current leak, electric shock, smoke, or fire.
Periodically check the platform on which the unit is placed for damage to prevent the unit from falling.
If the unit is left on a damaged platform, it may
topple over, causing injury.
Ground the unit.
Do not connect the grounding on the unit to gas
pipes, water pipes, lightning rods, or the grounding terminals of telephones. Improper grounding presents a risk of electric shock, smoke, fire, or the noise caused by improper grounding may cause the unit to malfunction.
Use breakers and fuses (electrical current breaker, remote switch <switch + Type-B fuse>, molded case circuit breaker) with a proper current capacity.
The use of large-capacity fuses, steel wire, or
copper wire may damage the unit or cause smoke or fire.
When installing draining pipes, follow the instructions in the manual, and make sure that they properly drain water so as to avoid dew condensation.
If not installed properly, they may cause water leaks
and damage the furnishings.
Make sure the wires are not subject to tension.
If the wires are too taut, they may break or generate
heat and/or smoke and cause fire.
Exercise caution when transporting products.
• Do not try to move equipments over 20kg (approx. 44 lbs.) alone.
• Do not use the PP bands used on some packages for transportation.
• Wear protective gloves to avoid injury caused by touching the fins on the heat exchanger with bare hands.
• When using a suspension bolt to transport the heat­source unit, use a four-point suspension. A three­point suspension does not provide adequate stability and presents a risk of accidents.
Properly dispose of the packing materials.
• Things such as nails and wood pieces may be included in the package. Dispose of them properly to prevent injury.
• Plastic bags present a choking hazard to children. Tear up the plastic bags before disposing of them to prevent accidents.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant(R410A) enters the refrigerant circuit.
• Any presence of foreign substance such as air can cause abnormal pressure rise or explosion.
- 4 -
Before the Test Run
Caution
Turn on the unit at least 12 hours before the test run.
• Keep the unit on throughout the season. Turning the unit off during the season may cause problems.
Do not turn off the power immediately after stopping the unit.
• Allow for at least five minutes before turning off the unit; otherwise, the unit may leak water or experience other problems.
Do not operate the unit without panels and safety guards in their proper places.
• They are there to keep the users from injury from accidentally touching rotating, high-temperature, or high-voltage parts.
Do not touch the refrigerant pipes with bare hands during and immediately after operation.
• Depending on the state of the refrigerant in the system, certain parts of the unit such as the pipes and compressor may become very cold or hot and may subject the person to frost bites or burning.
Do not operate switches with wet hands to avoid electric shock.
Do not operate the unit without air filters.
• Dust particles in the air may clog the system and cause malfunction.
- 5 -
- 6 -
¡¡
Read Before Servicing
[1] Items to Be Checked
1. Verify the type of refrigerant used by the unit to be serviced.
Refrigerant Type : R410A
2. Check the symptom exhibited by the unit to be serviced.
Look in this service handbook for symptoms relating to the refrigerant cycle.
3. Be sure to carefully read the Safety Precautions at the beginning of this document.
4. Prepare necessary tools: Prepare tools exclusive for use with each refrigerant type.
Refer to P7 for more information.
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
• Use pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and
free of contaminants such as sulfur, oxides, dust/dirt, shaving particles, oils, and moisture.
• Contaminants inside the refrigerant piping will cause the refrigerant oil to deteriorate.
6. If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may form. Keep workplace well ventilated.
CAUTION
1. Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
2. Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate.
- 7 -
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
[Necessary tools for use with R410A (Adaptability of tools that are for use with R22 and R407C)]
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/Materials NotesUse
Gauge Manifold Charging Hose Refrigerant Recovery Equipment Refrigerant Cylinder
Refrigerant Cylinder Charging Port Flare Nut
Evacuating, refrigerant charging Evacuating, refrigerant charging Refrigerant recovery Refrigerant charging
Refrigerant charging Connecting the unit to piping
5.09MPa on the High-pressure side. Hose diameter larger than the conventional ones.
Write down the refrigerant type. Pink in color at the top of the cylinder. Hose diameter larger than the conventional ones. Use Type-2 Flare nuts. (That are in compliance with JIS B 8607).
2. Tools and materials that may be used with R410A with some restrictions
Tools/Materials NotesUse
Gas leak detector Vacuum Pump
Flare Tool
Refrigerant Recovery Equipment
Detection of gas leaks Vacuum drying
Flare machining of piping
Recovery of refrigerant
The ones for HFC type refrigerant may be used. May be used if a reverse flow check adaptor is attached. Changes have been made in the flare machining dimension. Refer to the next page. May be used if designed for use with R410A.
3. Tools and materials that are used with R22 or R407C that can also be used with R410A
Tools/Materials NotesUse
Vacuum Pump with a Check valve Bender Torque Wrench
Pipe Cutter Welder and Nitrogen Cylinder Refrigerant Charging Meter Vacuum Gauze
Vacuum drying Bending pipes Tightening flare nuts
Cutting pipes Welding pipes Refrigerant charging Checking vacuum degree
Only ø 12.70 (1/2”) and ø 15.88 (5/8”) have a larger flare machining dimension.
4. Tools and materials that must not be used with R410A
Tools/Materials NotesUse
Charging Cylinder Refrigerant Charging Must not be used with R410A-type units.
Tools for R410A must be handled with special care; keep moisture and dust from entering the cycle.
Type-O pipes Soft copper pipes (annealed copper pipes)
They can be bent easily with hands.
Type-1/2H pipes Hard copper pipes (straight pipes)
Stronger than type-O pipes of the same radial thickness.
- 8 -
[3] Piping Materials
NOOK
New Piping Existing Piping
Do not use the existing piping!
<Types of copper pipe>
• The distinction between type-O and type-1/2H pipes is made based on the strength of the pipes themselves.
•Type-O pipes are soft and can easily be bent with hands.
•Type-1/2H pipes are considerably stronger than type-O pipes of the same radial thickness.
Use pipes made of phosphorus deoxidized copper. Since the operation pressure of the units that use R401A is higher than that of the units for use with R22, use pipes with at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7 mm or less may not be used.)
Maximum Operation Pressure Applicable Refrigerants
3.45 MPa
4.30 MPa
R22, R407C etc. R410A
<Types of Copper Pipes (Reference)>
Use pipes that meet the local standards.
Type-O pipes
Type-1/2H or
H pipes
Size(mm) Size(inch) Radial Thickness(mm) Type
ø 6.35 ø 9.52
ø 12.7 ø 15.88 ø 19.05
ø 22.2
ø 25.4 ø 28.58 ø 31.75
1/4” 3/8” 1/2” 5/8” 3/4” 7/8”
1” 1 1/8” 1 1/4”
0.8t
0.8t
0.8t
1.0t
1.0t
1.0t
1.0t
1.0t
1.1t
<Piping Materials/Radial Thickness>
Although it was possible to use type-O for pipes with a size of up to ø19.05 (3/4”) with conventional refriger-
ants, use type-1/2H pipes for units that use R410A. (Type-O pipes may be used if the pipe size is
ø19.05 and
the radial thickness is 1.2t.)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local
standards.
- 9 -
“Radial thickness” and “Refrigerant Types” are indicated on the insulation material on the piping materials for the new refrigerant.
Indication of the radial thickness (mm) Indication of the refrigerant type
Radial thickness Symbols
0.8
1.0
08 10
Refrigerant type Symbol Type1 R22, R407C Type2 R410A
1 2
<Example of the symbols indicated on the insulation material>
The type of piping materials can also be found on the package. <Example of a label found on the package>
~08-2~
Appears every 1 m
2 : common to type 1 and type 2 Refrigerant Type : R22,R407C,R410A Bore diameter and radial thickness of the copper piping : 9.520.8, 15.881.0
<Indication of the radial thickness and refrigerant type on the piping materials>
The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between 1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.
Flare Machining Dimension(mm)
External dimension of pipes
Size
Dimension A
R410A
ø 6.35 ø 9.52
ø 12.7 ø 15.88 ø 19.05
1/4” 3/8” 1/2” 5/8” 3/4”
9.1
13.2
16.6
19.7
24.0
R22
9.0
13.0
16.2
19.4
23.3
Dimension A
<Flare Machining (type-O and OL only)>
Type-2 flare nuts instead of type-1 s are used to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimension(mm)
External dimension of pipes
Size
Dimension B
R410A(Type2)
ø 6.35
ø 9.52
ø 12.7 ø 15.88 ø 19.05
1/4” 3/8” 1/2” 5/8” 3/4”
17.0
22.0
26.0
29.0
36.0
R22(Type1)
17.0
22.0
24.0
27.0
36.0
Dimension B
<Flare Nut>
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local
standards.
Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate.
Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and T’s in plastic bags for storage.
The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be stored with more care than with the conventional refrigerant pipes.
OK
OK
NO
NO
- 10 -
[4] Storage of Piping Material
1. Storage location
2. Pipe sealing before storage
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.
- 11 -
[5] Piping Machining
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (BCuP-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When applying non-oxide brazing, use nitrogen.
- 12 -
[6] Brazing
No changes from the conventional method. Note that a refrigerant leakage detector for R22 or R407C cannot detect R410A leakage.
Halide torch R22 or R407C leakage detector
Items to be strictly observed :
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment’s airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R410A.
3. Ensure that R410A is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R410A gas will lead the composition of the remaining refrigerant in the cylinder to change and this refrigerant can then not be used.
Note :
•A leakage detector for R410A is sold commercially and it should be purchased.
1. Vacuum pump with check valve A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 65Pa or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 650Pa. Do not use a general gauge manifold since it cannot measure a vacuum of 650Pa.
4. Evacuating time
•Evacuate the equipment for 1 hour after 650Pa has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the charge hose to drawn in air before stopping operation. The same operating procedure should be used when using a vacuum pump with a check valve.
NO
NO
- 13 -
[7] Airtightness Test
[8] Vacuuming
Recommended vacuum gauge : ROBINAIR 14010 Thermistor Vacuum Gauge
1. Vacuum pump with reverse-flow check valve (Photo 1)
To prevent vacuum pump oil from flowing back into the refrigerant circuit upon turning off the vacuum pump’s power
source, use a vacuum pump equipped with a reverse flow check valve.
A check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photos 1 and 2)
Use a vacuum pump that shows a vacuum degree of 65Pa or less after 5 minutes of operation. Use a pump well-
maintained with an appropriate lubricant.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 650Pa and measures at intervals of 130Pa. (A recommended
vacuum gauge is shown in Photo 2.)
Do not use a vacuum gauge that does not register a vacuum degree of 650Pa.
4. Evacuation time
• After the vacuum gauge has registered the vacuum degree of 650Pa, evacuate for 1 hour. (A thorough vacuum drying
removes moisture in the pipes.)
•Verify that the vacuum degree has not risen by more than 130Pa 1 hour after evacuation. A rise by less than 130Pa is
acceptable.
• If it has exceeded by more than 130Pa, conduct vacuuming following the instructions in the “6. Special vacuum drying”
section.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by
loosening the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
• When 650Pa or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has
penetrated the system or that there is a leak. When water infiltration is suspected, vacuum with nitrogen gas.
After breaking the vacuum, pressurize the system with nitrogen gas to a degree of 0.05MPa, and conduct an evacuation
again. Repeat it until 650Pa or lower degree of vacuum is attained or the vacuum pressure rise will be lost.
• Only use nitrogen gas for vacuum breaking. (Use of oxygen may cause an explosion.)
Photo 1 15010H Photo 2 14010
- 14 -
[9] Vacuum Drying
R410A must be in a liquid state when charging.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Reasons :
1.
Note :
In the case of a cylinder with a syphon, liquid R410A is charged without turning the cylinder up side down. Check the type of cylinder before charging.
Cylin-
der
Cylin-
der
Valve
Val ve
Liquid
Liquid
R410A is a pseudo-azeotropic refrigerant (boiling point R32 = -52˚C, R125 = -49˚C) and can roughly be handled in the same way as R22; however, be sure to fill the refrigerant from the liquid side, for doing so from the gas side will somewhat change the composition of the refrigerant in the cylinder.
When refrigerant leaks, additional refrigerant may be charged. (Add the refrigerant from the liquid side.) Refer to 9-[5].
- 15 -
[10] Changing Refrigerant
[11] Remedies to be taken in case of a refrigerant leak
Composition (wt%) Type of refrigerant
Chloride Safety Class Molecular Weight Boiling Point Steam Pressure (25
˚C,MPa)(gauge)
Saturated Steam Density (25
˚C,kg/m3) Flammability Ozone Depletion Coefficient (ODP)1 Global Warming Coefficient (GWP)2 Refrigerant charging method Addition of refrigerant in case of a leak
R410A
R32/R125
(50/50)
Simulated azeotropic
refrigerant
Not contained
A1/A1
72.6
-51.4
1.557
64.0
Non-flammable
0
1730
Liquid charging
Possible
R407C
R32/R125/R134a
(23/25/52)
Non-azeotropic
refrigerant
Not contained
A1/A1
86.2
-43.6
0.9177
42.5
Non-flammable
0
1530
Liquid charging
Possible
New Refrigerant
(HFC system)
Conventional Refrigerant
(HCFC system)
R22 R22
(100)
Single refrigerant
Contained
A1
86.5
-40.8
0.94
44.4
Non-flammable
0.055 1700
Gas charging
Possible
1: When CFC11 is used as a reference 2: When CO
2 is used as a reference
- 16 -
[12] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and a chemically stable non-flammable refrigerant. However, because the specific gravity of steam is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia. Also, leaked refrigerant exposed directly to an open flame will generate noxious gasses. Use the unit in a well-ventilated room.
R410A
MPa
0.30
0.70
1.34
2.31
3.73
4.17
-20 0 20 40 60 65
R407C
MPa
0.18
0.47
0.94
1.44
2.44
2.75
R22
MPa
0.14
0.40
0.81
1.44
2.33
2.60
Pressure (gauge)
Temperature (
˚C)
3. Pressure Characteristics
The pressure in the units that use R410A is 1.6 times as great as that in the units that use R22.
2. Refrigerant Composition
Because R410A is a simulated azeotropic refrigerant, it can be handled in almost the same manner as a single refrigerant such as R22. However, if the refrigerant is removed in the vapor phase, the composition of the refriger ant in the cylinder will somewhat change. Remove the refrigerant in the liquid phase. Additional refrigerant may be added in case of a refrigerant leak.
- 17 -
Refrigerant Refrigerating machine oil
R22 R407C R410A
Mineral oil
Ester oil Ester oil
[13] Notes on Refrigerating Machine Oil
1. Refrigerating Machine Oil in the HFC Refrigerant System
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 refrigerant system. Please note that the ester oil sealed in the unit is not the same as commercially available ester oil.
Cause Symptom
Clogged expansion valve and capillary Poor cooling performance Compressor overheat Poor motor insulation Motor burning Coppering of the orbiting part Locking Burning in the orbiting part
Expansion valve/capillary Poor cooling performance Drier clogging Compressor overheat
Burning in the orbiting part Expansion valve and capillary clogging Poor cooling performance Compressor overheat Burning in the orbiting part
Effects on the refrigeration cycle
Sludge formation Generation of acid Oxidization Oil degradation
Water infiltration
Air infiltration
Infiltration
of
contaminants
Dust, dirt
Mineral oil etc.
Expansion valve and capillary freeze
Hydrolysis
Oxidization
Adhesion to expansion valve and capillary
Infiltration of contaminants into the compressor
Sludge formation and adhesion
Oil degradation
2. Effects of the Contaminants in the System
Refrigerating machine oil used in the HFC system must be handled more carefully than conventional mineral oils. The table below shows the effects of air, moisture, and contaminants in the refrigerating machine oil on the refrig­eration cycle.
“ Contaminants ” is defined as moisture, air, process oil, dust/dirt, the wrong types of refrigerant and refrigerat-
ing machine oil.
<The Effects of Air, Moisture, and Contaminants in the Refrigerating Machine Oil on the Refrigeration Cycle.>
OK NO
Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power source wiring so
that it is not influenced by electric noise from power source wiring. (Do not insert transmission line and power source wire in the same conduit.)
Be sure to provide designated grounding work to heat source unit.Give some allowance to wiring for electrical part box of indoor and heat source unit, because the box is sometimes rem-
oved at the time of service work.
Never connect 380~415V(220~240V) power source to terminal block of transmission line.If connected,electrical parts
will be burnt out
Use 2-core shield cable for transmission line. If transmission lines of different systems are wired with the same multiple-
core cable, the resultant poor transmitting and receiving will cause erroneous operations.
Heat
source
unit
Heat
source
unit
Indoor unit
Remote
BC controller
controller
2-core cable
2-core cable
Remote
controller
Indoor unit
Multiple-
core cable
BC controller
Type of cable
Cable diameter
Remarks
Sheathed 2-core cable (unshielded) CVV
0.3
~ 1.25mm
2
(0.75 ~ 1.25mm2) 1
The BC controller is connected to WR2 and R2 systems.
More than 1.25mm
2
Shielding wire (2-core) CVVS,CPEVS or MVVS
When 10m is exceeded, use cables with the same specification as transmission cables.
0.3 ~ 1.25mm
2
(0.75 ~ 1.25mm2) 1
Max length : 200m
Transmission cables M-NET Remote controller cables MA Remote controller cables
CVVS,MVVS : PVC insulated PVC jacketed shielded control cable CPEVS : PE insulated PVC jacketed shielded communication cable CVV : PV insulated PVC sheathed control cable
1 Connected with simple remote controller.
- 18 -
Restrictions
[1] Electrical Work & M-NET control
1. Attention
2. Types of control cable
00
00
101
Main
00
201
201
201
202
000
247
Address (1) setting varies depending on the system configuration. See “[3] Examples of system connection” section for details.
Unit or controller
Address
Setting method
setting range
Indoor unit Main/sub units
Lossnay
M-NET remote controller
Main remote controller
Sub remote controller
MA remote controller
Outdoor (Heat source) unit
System controller
Group remote controller
System remote controller
ON/OFF remote controller
Schedule timer (for M-NET)
Centralized controller (Note 5)
LM adapter
0, 01~50
(Note 1)
101~150
151~200
(Note 2)
0, 51~100
(Note 1, 3, 4)
52~100
(Note 3, 4)
201~250
201~250
201~250
201~250
0, 201~250
201~250
Notes:
Factory
setting
Type and method of switch setting
Switch setting vary depending on the system configuration. Make sure to read “[3] Examples of system connection” before conducting electrical work. Turn off the power before setting the switch. Operating the switch while the unit is being powered will not change the setting, and the unit will not properly function.
1. Address setting is not required for a single refrigerant system (with a few exception).
2. When setting M-NET remote controller address to “200,” make it “00.”
3. When setting the heat source unit and outdoor auxiliary unit address to “100,” make it “50.”
4. When an address in a system overlapped with the heat source unit or BC controller (Main) address of other refrigerant system, choose an another address within the set range that is not in use (with a few exceptions).
5. When controlling the K-control units; (1) A K-transmission converter (Model name: PAC-SC25KA) is required. To set the address for the K-transmission converter,
set it to the lowest address of the K-control unit to be controlled + 200.
(2) Set the address of the system controller (G-50A) to “0.” The K-control unit can only be controlled by the system controller
with the address “0.”
(3) To control both K-control unit and M-NET model unit, make the address of the K-control unit larger than that of the indoor
unit of M-NET model. Group-register on the system controller so that the group No. and the lowest address of the K-controlled indoor units belonging to the group will be identical.
6. BC controller is found only in the R2 and WR2 systems.
Use the address that equals the sum of the smallest indoor unit address in the same refrigerant system and 50.
Use the address that equals the sum of the smallest address of the indoor unit out of all the indoor units that are connected to the BC controller and 50. When a sub BC controller is connected, the automatic start up function will not be available.
Auxiliary units
BC controller (Sub)
Use the address that equals the sum of the address of the heat source unit in the same refrigerant system and 1.
BC controller (Main)
Choose any number within the range of addresses shown left. However when using with the upper SC setting, or wishing to control the k-control units, set to “0.”
Assign the smallest address to the indoor unit to become the main unit within the same group, and then use sequential numbers to assign an address to all the indoor units in the group. (Note 5) If applicable, set the sub BC controllers in an R2 system in the following order:
(1)
Indoor unit to be connected to the main BC controller
(2)
Indoor unit to be connected to No.1 sub BC controller
(3)
Indoor unit to be connected to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
Assign any unused address after setting all indoor units.
Set to the lowest address of the indoor main unit within the same group + 150.
Set to the lowest No. of the group to be controlled + “200.”
Set to the lowest No. of the group desired to be controlled + “200.”
Choose any number within the range of addresses shown left.
Choose any number within the range of ad-dresses shown left.
Choose any number within the range of addresses shown left.
Set to the lowest address of the indoor main unit within the same group + 100.
No address setting required. (When operating with 2 remote controllers, the main/sub selector switch must be set.
- 19 -
[2] Types of Switch Setting and Address Setting
1. Switch setting
2. Address setting
Setting the power supply selecting connector for outdoor unit (Heat source unit) (Factory setting: CN41 is connected.)
(2)
Settings for the centralized control switch on the outdoor (heat source) unit (Factory setting: SW2-1 set to “OFF”)
(3)
Various start-stop controls (Indoor unit settings) Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
(6)
Miscellaneous settings Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 “OFF.”) When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7)
_
n/a
n/a
applicable
applicable//n/a
applicable//n/a
applicable//n/a
With connection to the indoor-outdoor transmission line
With connection to the transmission line for centralized control
_
_
_
Indoor unit port switch setting (R2/WR2 series (Factory Setting: “0”)) Make the settings for the port switch that corresponds to the connected BC (Main/Sub) controller. When more than two ports are used, make the setting on the port with a smaller port number. The total capacity and the number of connectable indoor units per port is 90 and below, and 3 respectively.
(4)
Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to “OFF”.)
1To use the built-in sensor on the remote controller, set the SW1-1 to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can
be detected. (Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models (PEFY-P, M-E-F, PFFY-P, RM-E-F) is ON.
2When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
When using an optional temperature sensor, install it where room temperature can be detected.
(5)
Operation of the indoor unit when the operation is resumed after the unit was stoppedFunction
Setting (SW1) (Note 4)
Power ON/OFF by the plug (Note 1, 2, 3)
Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes) Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes) Indoor unit will remain stopped regardless of its operation status before power off (power failure).
9
OFF
ON
OFF
10
ON
OFF
OFF
System configuration
Single-refrigerant system
Connection with the system controller
Power supply unit for transmission lines
Grouping operation of different
Unnecessary
Unnecessary (Note 2)
()
applicable
The setting of the power supply selecting connector
Use CN41 as is. (Factory setting)
Use CN41 as is. (Factory setting)
Multiple­refrigerant system
System configuration
Switch setting for centralized control (SW2-1)
Connection with the system controller : n/a
Connection with the system controller : applicable (Note 1)
Leave it to OFF.(Factory setting)
ON
(Note 1) The total number of connectible units in the refrigerant system will be limited. Refer to DATA BOOK. (Note 2) The need for a power supply unit for transmission lines depends on the system configuration. Refer to DATA BOOK. (Note 3) When connecting a system controller to the transmission line for centralized control or performing a group operation of units in
different refrigerant systems, the replacement of male power supply switch connector (CN41) must be performed only on one of the heat source units in the system.
(If a model between 34 and 50 HP is included in the system, replace the connector on that unit.)
(Note 1) Do not cut off power to the outdoor (Heat source) unit.
Cutting off the power supply to the outdoor (Heat source) unit will cut off the power supply to the crankcase heater and may
cause the compressor to malfunction when the unit is put back into operation. (Note 2) Not applicable to units with a built-in drain pump or humidifier (Note 3) Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant circuits
will be turned on or off by the plug. (Note 4) Requires that the dipswitch settings for all the units in the group be made.
(Note 1) When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
Disconnect the male connector from the female power supply switch connector (CN41) and con­nect it to the female power supply switch con­nector (CN40) on only one of the outdoor units. (Note 3) Connect the S (shielded) terminal on the termi­nal block (TB7) on the outdoor (Heat source) unit whose CN41 was replaced with CN40 to the earth terminal ( ) on the electric box.
Automatic restoration after power failure
Power supplied from outdoor (Heat source) unit
- 20 -
- 21 -
Various types of control using input-output signal connector on the heat source unit (Connection options)(8)
NO OK
If the step listed as the wrong example above is taken, thermo may go off. The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does not necessarily correspond with the capacity.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
Demand control
steps
CN51
Remote controller board
Controller board on Heat source unit
Relay circuit
Adapter
CN51
X Y
X
Y
Maximum allowable wiring length = 10 m
L1 : Error indicator lamp/freeze prevention output L2 : Compressor operation display lamp X,Y : Relay (For 12V DC coil rating 0.9 W or below)
L1
L2
Field-installed
CN3D
Remote controller board
Controller board on Heat source unit
Relay circuit
Adapter
CN3D
X
Y
X
Y
1 2
3
5 4
3
Maximum allowable wiring length = 10 m
SW1 : Night mode command or step command SW2 : Compressor ON/OFF command X,Y
:
Relay (Contact Minimum applied load 12V DC 1 mA)
X :
Relay (Contact rating 219~240V AC 1 A)
52P :
Contactor for pump
SW1
SW2
Field-installed
TB8
Heat source unit
TB8
3
4
Short­circuit jumper wire
63PW
With connection to pump interlock circuit
Remove the jumper wire when pump interlock circuit signal connection is made to 3 or 4 of TB8.
63PW:Pressure switch (Contact: Minimum applied load 5 mA)
TB8
Heat source unit
TB8
1
2
Terminals
X
52P
Lamp power supply
SW4-7:OFF (Compressor ON/OFF, Night mode)
Open
Short
Compressor ON/OFF
CN3D 1-3P
OFF
ON
SW4-7:ON (Step demand)
Open
Short
Night mode
CN3D 1-2P
CN3D 1-2P
ON
OFF
Open
Short
Open
CN3D 1-3P
0%
75%
Short
50%
100%
(No demand)
(Note 1) The night mode function is enabled when Dip SW 4-7 is set to OFF.
When Dip SW4-7 are set to ON, step demand control is possible, using different configurations of night mode input and Compressor ON/OFF input settings.
(Note 2) Error status output function on the heat source unit is enabled when Dip SW3-3 is set to OFF.
When Dip SW3-3 is set to ON, signal is output when heat source unit is stopped and water temperature (TH6) goes be­low 5˚C.
(Note 3) Operation-ON signal is output while the compressor is in operation if Dip SW2-7 is set to OFF.
If Dip SW2-7 is set to OFF, signal is output while receiving cooling or heating operation signal from the remote controller. (Signal output is continued even if the compressor comes to a stop due to Thermo OFF.)
FunctionUsage
Signal
type
Terminal
Compressor ON/OFF (level)
Operation status of the compressor
Error status or freeze prevention output (Note 2)
Night mode or step demand (level) (Note 1)
CN3D
TB8
TB8
CN51
Input
Output
Prohibiting cooling/heating operation (thermo OFF) by an external input to the heat source unit.
Can be used as a demand control function for each refrigerant system.
How to extract signals from the heat source unit.
Can be used as an operation status display device.Can be used for an interlock operation with external devices.
Performs a low-noise-level operation of the outdoor unit by an external input to the heat source unit. (The unit can perform a night mode operation under the following conditions: Outdoor air temperature below 30˚C during cooling operation/Outdoor air temperature above 3˚C during heating operation.
Pump interlock signal input (level)
Forces the heat source unit to stop by receiving a contact signal from the pump interlock circuit.
Operation-ON signal (Note 3)
Note the following steps to be taken when using the STEP DEMAND (Example) When witching from 100% to 50%
IC
TB5TB02TB7 TB3 TB
15
12
00
IC
TB5 TB
15
12
00
A1 B2
MA
A1 B2
MARC
TB5
00
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0000
IC
TB5 TB
15
12
00
A1 B2
MA
A1 B2
MA
A1 B2
MA
MA
m1
L11
m2
L3 L4
L12 L13
m3
m5
m4
NO
NO
NO
L2L1
A1 B2
A1 B2
a. Indoor/outdoor transmission line
Farthest length (1.25mm2 or more) L1 + L2 + L3 + L4 200m L1 + L2 + L11 + L12 + L13 200m
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
To tal length (0.3 ~ 1.25mm2) m1 200m m2 + m3 200m m4 + m5 200m
Control wiring example
Group
Prohibited items Allowable length
1. M-NET and MA remote controllers can not be connected to­gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected to the indoor unit within the same group.
3. When the total number of indoor units exceeds 26 units In­cluding that above Type 200, a transmission booster is re­quired. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the trans­mission booster.
4. In the case when start/stop input (CN32, CN51, CN41) is used by indoor group operation, the “Automatic address set-up” can not be employed. Please refer to 1. (2) “ Manual address set-up.”
5. For the connection of LOSSNAY with more than 2 units in a single refrigerant system, refer to the following “Connection of 2 LOSSNAY units in refrigerant system.”
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
Group
LC
✻1BC and BS are found only in the R2 and WR2 systems.
When connected to the BS, indoor-outdoor automatic address start up function will not be available.
00
OC
BC
1
1
00
00
TB02
BS
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
- 22 -
[3] Examples of system connection
1. System using MA remote controller
(1) In the case of single refrigerant system (Automatic address set-up)
Wiring methodAddress setting method
a. Indoor/outdoor transmission line
When the transmission line is long or noise sources are located near the unit, recommend to use shielded wire.
Connection of shielded wire:
For the earth of shielded wire, apply jumper wiring connection between the earth screw of OC and the S-terminal of
IC terminal block (TB5).
b. Centralized control transmission line
Connection is not required.
c. MA remote controller wiring
Connect the 1, 2 terminals of MA remote controller wiring terminal block (TB15) on IC to the terminal block of MA
remote controller (MA). (with non-polarity two wires)
MA remote controller can be connected to A-type indoor unit or later.
For 2-remote controller operation:
To employ 2-remote controller operation, connect 1, 2 terminals of the terminal block (TB15) on IC to the terminal
block of two MA remote controllers.
Set the main/sub selector switch of one MA remote controller to the sub remote controller. (For the setting method,
see the installation manual of MA remote controller.)
For indoor group operation:
For the group operation of IC, connect 1, 2 terminals of the terminal block (TB15) on all ICs within the same group,
and connect 1, 2 terminals of the terminal block (TB15) on another IC to the terminals of MA remote controller.
(with non-polarity two wires)
To operate the indoor units with different function in the same group, refer to 1. (2).
d. LOSSNAY connection
Linked and registered automatically with all indoor units within a refrigerant system.
Please refer to the 1. (2) “Manual address set-up,” when interlocking partial indoor units with Lossnay, using
Lossnay alone without interlocking, interlocking indoor units and Lossnay for over 16 units within a refrigerant
system, or connecting LOSSNAY for over 2 units in a refrigerant system.
e. Switch setting
Address setting is not required.
Order
Unit or controller
Address
Setting method Caution
Factory
setting range
setting
Main unit IC
Not required
Not required
00
1 Indoor unit
Sub unit IC
2 LOSSNAY LC Not required
3
MA remote
Main uni
BC controller
tMANot required
Main
controller
Sub unit MA Sub unit
4
Outdoor (Heat source) unit OC
5
Auxiliary units
BC
• Refer to 1. (2)
• Branch number setting is required by R2 and WR2 systems.
to operate indoor units with different function in the same group.
Set with main/sub selector switch.
00
00
Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor (heat source) unit (OC), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor unit. (with non-polarity two wires)
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on IC to the indoor/outdoor transmission terminal block (TB5) on LOSSNAY (LC). (with non-polarity two wires)
- 23 -
L2L1
OC
TB3
TB7 TB02
TB02
IC
TB5 TB
15
12
01
IC
TB5 TB
15
12
02
A1 B2
MA
A1 B2
MA
TB5
05
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0403
TB5
06
A1 B2
MA
L11
L3 L4
L12 L13
a. Indoor/outdoor transmission line
The same as 1. (1)
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
The same as 1. (1)
Control wiring example
Group
Prohibited items Allowable length
1. M-NET and MA remote controllers can not be connected to­gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected to the indoor unit within the same group.
3. When the total number of indoor units exceeds 26 units in­cluding that above Type 200, a transmission booster is re­quired. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the trans­mission booster.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
1.
BC and BS are found only in the R2 and WR2 systems.
51
52
53
BC✻1
BS
1
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
- 24 -
1. System using MA remote controller
(2) In the case of single refrigerant system connecting 2 or more LOSSNAY units (Manual address set-up)
- 25 -
1 Indoor unit
2 LOSSNAY
3
MA remote controlle
4 Outdoor (Heat source) unit
r
Main unit
Sub unit
Main unit
BC Controller (sub)
BC Controller (main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Wiring methodAddress setting method
a. Indoor/outdoor transmission line
Connection of shielded wire:
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
For 2-remote controller operation:
For indoor group operation:
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
d. LOSSNAY connection
The interlocking registration of the indoor unit and Lossnay from the remote controller is required. (For the regis-
tration method, see the installation manual of remote controllers.)
e. Switch setting
Address setting is required as listed below.
Order
Unit or controller
Address
Setting method Caution
Factory
setting range
setting
• Set
the lowest address within a same group to the indoor unit desired to be the main unit.
[Main unit +1, +2, +3, .... ]
Set any address after setting al
5
Auxiliary units
BS
BC
Set with main/sub selector switch.
l
indoor units.
00
00
Main
00
•When operating indoor units with different function within a same group, as­sign the indoor unit with the most plenty of function to the main unit.
• Set the address not to be overlapped with the indoor unit address.
The lowest address of indoor unit within refrigerant system + 50
The address of the indoor unit connected to the sub BC con­troller must be larger than that of the indoor unit connected to the main BC controller. If applicable, set the sub BC controllers in an R2 system in the following order: (1)
Indoor unit to be connected to the main BC controller
(2)
Indoor unit to be connected to No.1 sub BC controller
(3)
Indoor unit to be connected to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
Use the address that equals the sum of the smallest indoor unit address out of all the indoor units that are connected to the sub BC controller and 50.
Outdoor (Heat source) unit address +1
Requires a branch-num­ber setting.
Set to the main unit address wit­hin a same group in serial order
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on the indoor unit (IC) to the terminal block (TB5) on Lossnay (LC). (with non-polarity two wires)
• To set the address to “100,” set it to “50”.
• If the address of main BC controller overlaps with the address of the outdoor (heat source) unit or the sub BC controller, use an unused address within the setting range.
• The use of a sub BC con­troller requires a main BC controller.
- 26 -
IC
TB5 TB
15
12
01
IC
TB5 TB
15
12
03
A1 B2
MA
A1 B2
MA
TB5
06
IC
TB5
12
TB
15
IC
TB5 TB
15
12 12
0402
IC
TB5 TB15
05
A1 B2
MA
L3 L4
L23 L24
NO
L1 L2
L22L21
L31
m2
m3
a. Indoor/outdoor transmission line
Farthest length (1.25mm
2
or more) L1 + L2 + L3 + L4 200m L21 + L22 + L23 + L24 200m
b. Centralized control transmission line
Farthest length via outdoor (heat source) unit (1.25m
m
2
or more)
L1 + L2 + L3 + L4 + L31 + L21 + L22 + L23 + L24 500m
c. MA remote controller wiring
The same as 1. (1)
Control wiring example
Group
Prohibited items Allowable length
1. M-NET and MA remote controllers can not be connected to­gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the in­door unit connected to different outdoor (heat source) units.
4. Replacement of the power supply selecting connector (CN41) on the outdoor (heat source) unit should be done only on one
outdoor (heat source) unit.
5. Grounding of S-terminal of the centralized control terminal block (TB7) on outdoor (heat source) unit should be done only on one outdoor (heat source) unit.
6. When the total number of indoor units exceeds 26 units in­cluding that above Type 200, a transmission booster is re­quired. When the transmission booster is used, BC and BS cannot be connected to TB3 (indoor unit side) on the trans­mission booster.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
NO
✻1.BC and BS are found only in the R2 and WR2 systems.
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
51
52
53
55
54
Connect
OC
OC
Leave CN41 as it is.
CN41CN40 Replace
TB02
TB02
TB02
TB7 TB3
TB7 TB3
BC✻1
BC
1
BS
1
1. System using MA remote controller
(3) In the case of different refrigerant grouping operation
- 27 -
Wiring methodAddress setting method
a. Indoor/outdoor transmission line
Make sure to use shielded wire.
Connecting of shielded wire:
The same as 1. (1)
b. Centralized control transmission line
Apply jumper wiring between M1, M2 terminals of centralized control transmission line terminal blocks (TB7) on each OC. For one OC only, replace the power selecting connector (CN41) with (CN40).
Make sure to use shielded wire.
Connecting of shielded wire:
Apply jumper wiring to connect the shielded earth to S-terminal of the terminal block (TB7) on each OC. Connect S­terminal of the terminal block (TB7) on the one OC with (CN40) replaced to the earth screw ( ) of the electrical parts box.
c. MA remote controller wiring The same as 1. (1)
For 2-remote controller operation: The same as 1. (1)
For indoor unit group operation: The same as 1. (2)
d. LOSSNAY connection The same as 1. (2)
e. Switch setting
Address setting is required as follows.
Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor (heat source) unit (OC), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor unit. (with non-polarity two wires)
1 Indoor unit
2 LOSSNAY
3
MA remote controlle
4 Outdoor (Heat source) unit
r
Main unit
Sub unit
Main uni
t
BC Controller (sub)
BC Controller (main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Order
Unit or controller
Address
Setting method Caution
Factory
setting range
setting
• Set
the lowest address within a same group to the indoor unit desired to be the main unit.
[Main unit +1, +2, +3, .... ]
Set any address after setting al
5
Auxiliary units
BS
BC
Set with main/sub selector switch.
l
indoor units.
00
00
Main
00
•When operating indoor units with different function within a same group, as­sign the indoor unit with the most plenty of function to the main unit.
• Set the address not to be overlapped with the indoor unit address.
The lowest address of indoor unit within refrigerant system + 50
The address of the indoor unit connected to the sub BC con­troller must be larger than that of the indoor unit connected to the main BC controller. If applicable, set the sub BC controllers in an R2 system in the following order: (1)
Indoor unit to be connected
to the main BC controller
(2)
Indoor unit to be connected
to No.1 sub BC controller
(3)
Indoor unit to be connected
to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
Use the address that equals the sum of the smallest indoor unit address out of all the indoor units that are connected to the sub BC controller and 50.
Outdoor (Heat source) unit address +1
Requires a branch-num­ber setting.
Set to the main unit address wit­hin a same group in serial order
• To set the address to “100,” set it to “50”.
• If the address of main BC controller overlaps with the address of the outdoor (heat source) unit or the sub BC controller, use an unused address within the setting range.
• The use of a sub BC con­troller requires a main BC controller.
Loading...
+ 208 hidden pages