[6] BC controller service instruction ............................................ 208
0 LED display .................................................................................. 211
[1] LED Monitor Display .............................................................. 211
Page 4
Safety Precautions
Symbols used in the text
Warning:
Failure to follow all instructions may result in serious personal injury or death.
Caution:
Failure to follow all instructions may result in personal injury or damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Beware of electric shock (This symbol is displayed on the main unit label.) <Color : Yellow>
Warning : Carefully read the labels affixed to the main unit.
Before installing the unit, be sure to carefully read all of the following safety precautions.
These precautions provide important information regarding safety. Be sure to follow them to ensure safety.
After reading this handbook, hand it over to those who will be using the unit.
The user of the unit should keep this manual at hand and make it available to those who will be performing
repairs or relocating the unit.
Also, make it available to the new user when the user changes hands.
Be sure to carefully follow each step in this
handbook when installing the unit.
• Improper installation may result in water leak,
electric shock, smoke or fire.
Securely attach the terminal cover (panel) on the
unit.
• If installed improperly, dust and/or water may enter
the unit and present a risk of electric shock, smoke,
or fire.
Only use Refrigerant R410A as indicated on the
unit when installing or relocating the unit.
• The use of any other refrigerant or an introduction of
air into the unit circuit may cause the unit to run an
abnormal cycle and cause the unit to burst.
Do not make any changes or modifications to the
unit. In case of problems, consult the dealer.
•If repairs are not made properly, the unit may leak
water and present a risk of electric shock, or it may
produce smoke or cause fire.
Have all electrical work performed by a licensed
electrician according to the local regulations and
the instructions given in this manual. Secure a
circuit designated exclusively to the unit.
• Improper installation or a lack of circuit capacity may
cause the unit to malfunction or present a risk of
electric shock, smoke, and fire.
Have the unit professionally installed.
• Improper installation by an unqualified person may
result in water leak, electric shock, or fire.
Only use specified cables for wiring. Securely
connect each cable, and make sure that the cables
are not straining the terminals.
• Cables not connected securely and properly may
generate heat and cause fire.
Place the unit on a stable, level surface that
withstands the weight of the unit to prevent the
unit from tipping over or falling causing injury as a
result.
Take necessary safety measures against typhoons
and earthquakes to prevent the unit from falling
over.
- 1 -
Page 5
When relocating the air conditioner, consult the
dealer or a specialist.
• Improper installation may result in water leak,
electric shock, or fire.
• Consult the dealer for necessary measures to take.
After completing the service work, check for a
refrigerant gas leak.
• If leaked gas refrigerant is exposed to a heart
source such as fan heater, stove, and electric grill,
noxious gases may form.
In the event of a refrigerant gas leak, provide
adequate ventilation to the room.
• If leaked refrigerant gas is exposed to a heat source,
noxious gases may form.
With All-Fresh type air conditioners, outdoor air
may be directly blown into the room upon thermo
off. Take this into consideration when installing the
unit.
• Direct exposure to outdoor air may present a health
hazard, and it may also cause food items to
deteriorate.
When installing the unit in a small room, safeguard
against hypoxia that results from leaked refrigerant
reaching the threshold level.
Precautions for Handling Units for Use with R410A
Caution
Warning : Carefully read the labels affixed to the main unit.
Do not try to defeat the safety features of the
devices, and do not change the settings.
• Defeating the safety features on the unit such as the
pressure switch and temperature switch or using
parts other than those specified by Mitsubishi
Electric may result in fire or explosion.
Use refrigerant pipes made of C1220 phosphorus
deoxidized copper categorized under H3000
(Copper and Copper Alloy Seamless Pipes and
Tubes), a standard set by JIS. Keep the inner and
outer surfaces of the pipes clean and free of
contaminants such as sulfur, oxides, dust/dirt,
shaving particles, oils, and moisture.
• Contaminants inside the refrigerant piping will cause
the refrigerant oil to deteriorate.
Do not use the following tools that have been used
with the conventional refrigerants.Prepare tools
that are for exclusive use with R410A.
(Gauge manifold, charging hose, gas leak detector,
reverse-flow check valve, refrigerant charge base,
vacuum gauge, and refrigerant recovery
equipment.)
• If refrigerant and /or refrigerant oil left on these tools
are mixed in with R410A, or if water is mixed with
R410A, it will cause the refrigerant to deteriorate.
• Since R410A does not contain chlorine, gas-leak
detectors for conventional refrigerators will not work.
Only use specified parts.
• Have the unit professionally installed.
Improper installation may cause water leak, electric
shock, smoke, or fire.
Use a vacuum pump with a reverse-flow-check
valve.
• If other types of valves are used, the vacuum pump
oil will flow back into the refrigerant cycle and cause
the refrigerator oil to deteriorate.
Do not use the existing refrigerant piping
• The old refrigerant and refrigerator oil in the existing
piping contain a large amount of chlorine, which will
cause the refrigerator oil in the new unit to
deteriorate.
• R410A is a high-pressure refrigerant, and the use of
the existing piping may result in bursting.
- 2 -
Page 6
Before Installing the Unit
Warning
Caution
Store the piping to be used during installation
indoors, and keep both ends of the piping sealed
until immediately before brazing. (Keep elbows and
other joints wrapped in plastic.)
• If dust, dirt, or water enters the refrigerant cycle, it
may cause the oil in the unit to deteriorate or may
cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or
alkylbenzene to coat flares and flange connections.
• A large amount of mineral oil will cause the
refrigerating machine oil to deteriorate.
Do not use a charging cylinder.
• The use of charging cylinder will change the
composition of the refrigerant and lead to power
loss.
Exercise special care when handling the tools.
• An introduction of foreign objects such as dust, dirt,
or water into the refrigerant cycle will cause the
refrigerating machine oil to deteriorate.
Only use R410A refrigerant.
• The use of refrigerants containing chlorine (i.e. R22)
will cause the refrigerant to deteriorate.
Use liquid refrigerant to charge the system.
• Charging the unit with gas refrigerant will cause the
refrigerant in the cylinder to change its composition
and will lead to a drop in performance.
Do not install the unit in a place where there is a
possibility of flammable gas leak.
• Leaked gas accumulated around the unit may start a
fire.
Do not use the unit to preserve food, animals,
plants, artifacts, or for other special purposes.
• The unit is not designed to provide adequate
conditions to preserve the quality of these items.
When installing the unit in a hospital, take
necessary measures against noise.
• High-frequency medical equipment may interfere
with the normal operation of the air conditioning unit
or the air conditioning unit may interfere with the
normal operation of the medical equipment.
Do not use the unit in an unusual environment.
• The use of the unit in the presence of a large
amount of oil, steam, acid, alkaline solvents, or
special types of sprays may lead to a remarkable
drop in performance and/or malfunction and
presents a risk of electric shock, smoke, or fire.
• The presence of organic solvents, corroded gas
(such as ammonia, sulfur compounds, and acid)
may cause gas or water leak.
Do not place the unit on or over things that may
not get wet.
• When humidity level exceeds 80% or when the
drainage system is clogged, indoor units may drip
water.
• Installation of a centralized drainage system for the
outdoor unit may also need to be considered to
prevent water drips from the outdoor units.
- 3 -
Page 7
Before Installing (Relocating) the Unit or Performing Electric Work
Caution
Warning
Do not spray water on the air conditioners or
immerse the air conditioners in water.
• Water on the unit presents a risk of electric shock.
Install a breaker for current leakage at the power
source to avoid the risk of electric shock.
• Without a breaker for current leakage, there is a risk
of electric shock, smoke, or fire.
Use wires that are specified in the installation
manual.
• The use of other types of wires presents a risk of
electrical current leak, electric shock, smoke, or fire.
Periodically check the platform on which the unit is
placed for damage to prevent the unit from falling.
• If the unit is left on a damaged platform, it may
topple over, causing injury.
Ground the unit.
• Do not connect the grounding on the unit to gas
pipes, water pipes, lightning rods, or the grounding
terminals of telephones. Improper grounding
presents a risk of electric shock, smoke, fire, or the
noise caused by improper grounding may cause the
unit to malfunction.
Use breakers and fuses (electrical current breaker,
remote switch <switch + Type-B fuse>, molded
case circuit breaker) with a proper current
capacity.
• The use of large-capacity fuses, steel wire, or
copper wire may damage the unit or cause smoke or
fire.
When installing draining pipes, follow the
instructions in the manual, and make sure that they
properly drain water so as to avoid dew
condensation.
• If not installed properly, they may cause water leaks
and damage the furnishings.
Make sure the wires are not subject to tension.
• If the wires are too taut, they may break or generate
heat and/or smoke and cause fire.
Exercise caution when transporting products.
• Do not try to move equipments over 20kg (approx.
44 lbs.) alone.
• Do not use the PP bands used on some packages
for transportation.
• Wear protective gloves to avoid injury caused by
touching the fins on the heat exchanger with bare
hands.
• When using a suspension bolt to transport the heatsource unit, use a four-point suspension. A threepoint suspension does not provide adequate stability
and presents a risk of accidents.
Properly dispose of the packing materials.
• Things such as nails and wood pieces may be
included in the package. Dispose of them properly to
prevent injury.
• Plastic bags present a choking hazard to children.
Tear up the plastic bags before disposing of them to
prevent accidents.
When installing or relocating the unit, make sure
that no substance other than the specified
refrigerant(R410A) enters the refrigerant circuit.
• Any presence of foreign substance such as air can
cause abnormal pressure rise or explosion.
- 4 -
Page 8
Before the Test Run
Caution
Turn on the unit at least 12 hours before the test
run.
• Keep the unit on throughout the season.
Turning the unit off during the season may cause
problems.
Do not turn off the power immediately after
stopping the unit.
• Allow for at least five minutes before turning off the
unit; otherwise, the unit may leak water or
experience other problems.
Do not operate the unit without panels and safety
guards in their proper places.
• They are there to keep the users from injury from
accidentally touching rotating, high-temperature, or
high-voltage parts.
Do not touch the refrigerant pipes with bare hands
during and immediately after operation.
• Depending on the state of the refrigerant in the
system, certain parts of the unit such as the pipes
and compressor may become very cold or hot and
may subject the person to frost bites or burning.
Do not operate switches with wet hands to avoid
electric shock.
Do not operate the unit without air filters.
• Dust particles in the air may clog the system and
cause malfunction.
- 5 -
Page 9
- 6 -
¡¡
Read Before Servicing
[1] Items to Be Checked
1. Verify the type of refrigerant used by the unit to be serviced.
Refrigerant Type : R410A
2. Check the symptom exhibited by the unit to be serviced.
Look in this service handbook for symptoms relating to the refrigerant cycle.
3. Be sure to carefully read the Safety Precautions at the beginning of this document.
4. Prepare necessary tools: Prepare tools exclusive for use with each refrigerant type.
Refer to P7 for more information.
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be
moved or replaced.
• Use pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and
free of contaminants such as sulfur, oxides, dust/dirt, shaving particles, oils, and moisture.
• Contaminants inside the refrigerant piping will cause the refrigerant oil to deteriorate.
6. If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas
hydrofluoric acid may form. Keep workplace well ventilated.
CAUTION
1. Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
2. Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to
deteriorate.
Page 10
- 7 -
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
[Necessary tools for use with R410A (Adaptability of tools that are for use with R22 and R407C)]
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Refrigerant charging
Connecting the unit to piping
5.09MPa on the High-pressure side.
Hose diameter larger than the conventional ones.
Write down the refrigerant type.
Pink in color at the top of the cylinder.
Hose diameter larger than the conventional ones.
Use Type-2 Flare nuts.
(That are in compliance with JIS B 8607).
2. Tools and materials that may be used with R410A with some restrictions
Tools/MaterialsNotesUse
Gas leak detector
Vacuum Pump
Flare Tool
Refrigerant Recovery Equipment
Detection of gas leaks
Vacuum drying
Flare machining of piping
Recovery of refrigerant
The ones for HFC type refrigerant may be used.
May be used if a reverse flow check adaptor is
attached.
Changes have been made in the flare machining
dimension. Refer to the next page.
May be used if designed for use with R410A.
3. Tools and materials that are used with R22 or R407C that can also be used with R410A
Tools/MaterialsNotesUse
Vacuum Pump with a Check valve
Bender
Torque Wrench
Pipe Cutter
Welder and Nitrogen Cylinder
Refrigerant Charging Meter
Vacuum Gauze
Stronger than type-O pipes of the same radial thickness.
- 8 -
[3] Piping Materials
NOOK
New PipingExisting Piping
Do not use the existing piping!
<Types of copper pipe>
• The distinction between type-O and type-1/2H pipes is made based on the strength of the pipes themselves.
•Type-O pipes are soft and can easily be bent with hands.
•Type-1/2H pipes are considerably stronger than type-O pipes of the same radial thickness.
Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R401A is higher than that of the units for use with R22, use
pipes with at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
Maximum Operation PressureApplicable Refrigerants
3.45 MPa
4.30 MPa
R22, R407C etc.
R410A
<Types of Copper Pipes (Reference)>
✻ Use pipes that meet the local standards.
Type-O pipes
Type-1/2H or
H pipes
Size(mm) Size(inch)Radial Thickness(mm)Type
ø 6.35
ø 9.52
ø 12.7
ø 15.88
ø 19.05
ø 22.2
ø 25.4
ø 28.58
ø 31.75
1/4”
3/8”
1/2”
5/8”
3/4”
7/8”
1”
1 1/8”
1 1/4”
0.8t
0.8t
0.8t
1.0t
1.0t
1.0t
1.0t
1.0t
1.1t
<Piping Materials/Radial Thickness>
✻ Although it was possible to use type-O for pipes with a size of up to ø19.05 (3/4”) with conventional refriger-
ants, use type-1/2H pipes for units that use R410A. (Type-O pipes may be used if the pipe size is
ø19.05 and
the radial thickness is 1.2t.)
✻ The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local
standards.
Page 12
- 9 -
“Radial thickness” and “Refrigerant Types” are indicated on the insulation material on the piping materials for the
new refrigerant.
Indication of the radial thickness (mm)Indication of the refrigerant type
<Example of the symbols indicated on the insulation material>
The type of piping materials can also be found on the package.
<Example of a label found on the package>
~08-2~
Appears every 1 m
2 : common to type 1 and type 2
Refrigerant Type : R22,R407C,R410A
Bore diameter and radial thickness of the copper piping : 9.52✕0.8, 15.88✕1.0
<Indication of the radial thickness and refrigerant type on the piping materials>
The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to
increase air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the
pipe between 1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.
Flare Machining Dimension(mm)
External dimension
of pipes
Size
Dimension A
R410A
ø 6.35
ø 9.52
ø 12.7
ø 15.88
ø 19.05
1/4”
3/8”
1/2”
5/8”
3/4”
9.1
13.2
16.6
19.7
24.0
R22
9.0
13.0
16.2
19.4
23.3
Dimension A
<Flare Machining (type-O and OL only)>
Type-2 flare nuts instead of type-1 s are used to increase the strength. The size of some of the flare nuts have
also been changed.
Flare nut dimension(mm)
External dimension
of pipes
Size
Dimension B
R410A(Type2)
ø 6.35
ø 9.52
ø 12.7
ø 15.88
ø 19.05
1/4”
3/8”
1/2”
5/8”
3/4”
17.0
22.0
26.0
29.0
36.0
R22(Type1)
17.0
22.0
24.0
27.0
36.0
Dimension B
<Flare Nut>
✻ The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local
standards.
Page 13
Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse)
Storing them outdoors may cause dirt, waste, or water to infiltrate.
Both ends of the pipes should be sealed until immediately before brazing.
Wrap elbows and T’s in plastic bags for storage.
✻
The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water
infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be
stored with more care than with the conventional refrigerant pipes.
OK
OK
NO
NO
- 10 -
[4] Storage of Piping Material
1. Storage location
2. Pipe sealing before storage
Page 14
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
•Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
•Do not use oils other than ester oil, ether oil or alkylbenzene.
- 11 -
[5] Piping Machining
Page 15
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,
etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not usedWhen non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (BCuP-3) which requires no flux when brazing between copper pipes or between a copper pipe
and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if
water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
•Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When
applying non-oxide brazing, use nitrogen.
- 12 -
[6] Brazing
Page 16
No changes from the conventional method. Note that a refrigerant leakage detector for R22 or R407C cannot detect
R410A leakage.
Halide torchR22 or R407C leakage detector
Items to be strictly observed :
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment’s airtightness, taking
temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R410A.
3. Ensure that R410A is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R410A gas will lead the composition of the remaining refrigerant in the cylinder to change and this
refrigerant can then not be used.
Note :
•A leakage detector for R410A is sold commercially and it should be purchased.
1. Vacuum pump with check valve
A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant
circuit when the vacuum pump power is turned off (power failure).
It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump
Use a pump which reaches 65Pa or below after 5 minutes of operation.
In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the
vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge
Use a vacuum gauge that can measure up to 650Pa. Do not use a general gauge manifold since it cannot measure a
vacuum of 650Pa.
4. Evacuating time
•Evacuate the equipment for 1 hour after 650Pa has been reached.
•After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped
In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the
charge hose to drawn in air before stopping operation.
The same operating procedure should be used when using a vacuum pump with a check valve.
1. Vacuum pump with reverse-flow check valve (Photo 1)
To prevent vacuum pump oil from flowing back into the refrigerant circuit upon turning off the vacuum pump’s power
source, use a vacuum pump equipped with a reverse flow check valve.
A check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photos 1 and 2)
Use a vacuum pump that shows a vacuum degree of 65Pa or less after 5 minutes of operation. Use a pump well-
maintained with an appropriate lubricant.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 650Pa and measures at intervals of 130Pa. (A recommended
vacuum gauge is shown in Photo 2.)
Do not use a vacuum gauge that does not register a vacuum degree of 650Pa.
4. Evacuation time
• After the vacuum gauge has registered the vacuum degree of 650Pa, evacuate for 1 hour. (A thorough vacuum drying
removes moisture in the pipes.)
•Verify that the vacuum degree has not risen by more than 130Pa 1 hour after evacuation. A rise by less than 130Pa is
acceptable.
• If it has exceeded by more than 130Pa, conduct vacuuming following the instructions in the “6. Special vacuum drying”
section.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by
loosening the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
• When 650Pa or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has
penetrated the system or that there is a leak. When water infiltration is suspected, vacuum with nitrogen gas.
After breaking the vacuum, pressurize the system with nitrogen gas to a degree of 0.05MPa, and conduct an evacuation
again. Repeat it until 650Pa or lower degree of vacuum is attained or the vacuum pressure rise will be lost.
• Only use nitrogen gas for vacuum breaking. (Use of oxygen may cause an explosion.)
Photo 1 15010HPhoto 2 14010
- 14 -
[9]Vacuum Drying
Page 18
R410A must be in a liquid state when charging.
For a cylinder with a syphon attachedFor a cylinder without a syphon attached
Cylinder color identificationR407C-GrayCharged with liquid refrigerant
R410A-Pink
Reasons :
1.
Note :
•In the case of a cylinder with a syphon, liquid R410A is charged without turning the cylinder up side down. Check the
type of cylinder before charging.
Cylin-
der
Cylin-
der
Valve
Val ve
Liquid
Liquid
R410A is a pseudo-azeotropic refrigerant (boiling point R32 = -52˚C, R125 = -49˚C) and can roughly be handled
in the same way as R22; however, be sure to fill the refrigerant from the liquid side, for doing so from the gas
side will somewhat change the composition of the refrigerant in the cylinder.
When refrigerant leaks, additional refrigerant may be charged. (Add the refrigerant from the liquid side.)
✻Refer to 9-[5].
- 15 -
[10] Changing Refrigerant
[11] Remedies to be taken in case of a refrigerant leak
Page 19
Composition (wt%)
Type of refrigerant
Chloride
Safety Class
Molecular Weight
Boiling Point
Steam Pressure (25
˚C,MPa)(gauge)
Saturated Steam Density (25
˚C,kg/m3)
Flammability
Ozone Depletion Coefficient (ODP)✻1
Global Warming Coefficient (GWP)✻2
Refrigerant charging method
Addition of refrigerant in case of a leak
R410A
R32/R125
(50/50)
Simulated azeotropic
refrigerant
Not contained
A1/A1
72.6
-51.4
1.557
64.0
Non-flammable
0
1730
Liquid charging
Possible
R407C
R32/R125/R134a
(23/25/52)
Non-azeotropic
refrigerant
Not contained
A1/A1
86.2
-43.6
0.9177
42.5
Non-flammable
0
1530
Liquid charging
Possible
New Refrigerant
(HFC system)
Conventional Refrigerant
(HCFC system)
R22
R22
(100)
Single refrigerant
Contained
A1
86.5
-40.8
0.94
44.4
Non-flammable
0.055
1700
Gas charging
Possible
✻1: When CFC11 is used as a reference ✻2: When CO
2 is used as a reference
- 16 -
[12] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and a chemically stable non-flammable refrigerant.
However, because the specific gravity of steam is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia. Also, leaked refrigerant exposed directly to an
open flame will generate noxious gasses. Use the unit in a well-ventilated room.
R410A
MPa
0.30
0.70
1.34
2.31
3.73
4.17
-20
0
20
40
60
65
R407C
MPa
0.18
0.47
0.94
1.44
2.44
2.75
R22
MPa
0.14
0.40
0.81
1.44
2.33
2.60
Pressure (gauge)
Temperature (
˚C)
3. Pressure Characteristics
The pressure in the units that use R410A is 1.6 times as great as that in the units that use R22.
2. Refrigerant Composition
Because R410A is a simulated azeotropic refrigerant, it can be handled in almost the same manner as a single
refrigerant such as R22. However, if the refrigerant is removed in the vapor phase, the composition of the refriger
ant in the cylinder will somewhat change.
Remove the refrigerant in the liquid phase. Additional refrigerant may be added in case of a refrigerant leak.
Page 20
- 17 -
RefrigerantRefrigerating machine oil
R22
R407C
R410A
Mineral oil
Ester oil
Ester oil
[13] Notes on Refrigerating Machine Oil
1. Refrigerating Machine Oil in the HFC Refrigerant System
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 refrigerant system.
Please note that the ester oil sealed in the unit is not the same as commercially available ester oil.
CauseSymptom
Clogged expansion valve and capillary
Poor cooling performance
Compressor overheat
Poor motor insulation
Motor burning
Coppering of the orbiting part
Locking
Burning in the orbiting part
Burning in the orbiting part
Expansion valve and capillary clogging
Poor cooling performance
Compressor overheat
Burning in the orbiting part
Effects on the refrigeration cycle
Sludge formation
Generation of acid
Oxidization
Oil degradation
Water infiltration
Air infiltration
Infiltration
of
contaminants
Dust, dirt
Mineral oil
etc.
Expansion valve and capillary freeze
Hydrolysis
Oxidization
Adhesion to expansion valve and capillary
Infiltration of contaminants into the compressor
Sludge formation and adhesion
Oil degradation
2. Effects of the ✻Contaminants in the System
Refrigerating machine oil used in the HFC system must be handled more carefully than conventional mineral oils.
The table below shows the effects of air, moisture, and contaminants in the refrigerating machine oil on the refrigeration cycle.
✻ “ Contaminants ” is defined as moisture, air, process oil, dust/dirt, the wrong types of refrigerant and refrigerat-
ing machine oil.
<The Effects of Air, Moisture, and Contaminants in the Refrigerating Machine Oil on the Refrigeration Cycle.>
Page 21
OKNO
➀ Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
➁ Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power source wiring so
that it is not influenced by electric noise from power source wiring. (Do not insert transmission line and power source wire
in the same conduit.)
➂ Be sure to provide designated grounding work to heat source unit.
➃ Give some allowance to wiring for electrical part box of indoor and heat source unit, because the box is sometimes rem-
oved at the time of service work.
➄ Never connect 380~415V(220~240V) power source to terminal block of transmission line.If connected,electrical parts
will be burnt out
➅ Use 2-core shield cable for transmission line. If transmission lines of different systems are wired with the same multiple-
core cable, the resultant poor transmitting and receiving will cause erroneous operations.
Heat
source
unit
Heat
source
unit
Indoor unit
Remote
BC controller
controller
2-core cable
2-core cable
Remote
controller
Indoor unit
Multiple-
core cable
BC controller
Type of cable
Cable diameter
Remarks
Sheathed 2-core cable (unshielded)
CVV
0.3
~ 1.25mm
2
(0.75 ~ 1.25mm2) ✻1
✻ The BC controller is connected to WR2 and R2 systems.
More than 1.25mm
2
Shielding wire (2-core)
CVVS,CPEVS or MVVS
When 10m is exceeded, use cables with
the same specification as transmission cables.
CVVS,MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS: PE insulated PVC jacketed shielded communication cable
CVV: PV insulated PVC sheathed control cable
—
✻
1 Connected with simple remote controller.
- 18 -
™™
Restrictions
[1] Electrical Work & M-NET control
1. Attention
2. Types of control cable
Page 22
00
00
101
Main
00
201
201
201
202
000
247
Address (1)setting varies depending on the system configuration. See “[3] Examples of system connection”
section for details.
Unit or controller
Address
Setting method
setting range
Indoor unitMain/sub units
Lossnay
M-NET
remote
controller
Main remote controller
Sub remote controller
MA remote controller
Outdoor (Heat source) unit
System
controller
Group remote controller
System remote controller
ON/OFF remote controller
Schedule timer (for M-NET)
Centralized controller
(Note 5)
LM adapter
0, 01~50
(Note 1)
101~150
151~200
(Note 2)
0, 51~100
(Note 1, 3, 4)
52~100
(Note 3, 4)
201~250
201~250
201~250
201~250
0, 201~250
201~250
Notes:
Factory
setting
Type and method of switch setting
Switch setting vary depending on the system configuration. Make sure to read “[3] Examples of system connection”
before conducting electrical work. Turn off the power before setting the switch. Operating the switch while the unit is
being powered will not change the setting, and the unit will not properly function.
1. Address setting is not required for a single refrigerant system (with a few exception).
2. When setting M-NET remote controller address to “200,” make it “00.”
3. When setting the heat source unit and outdoor auxiliary unit address to “100,” make it “50.”
4. When an address in a system overlapped with the heat source unit or BC controller (Main) address of other refrigerant system,
choose an another address within the set range that is not in use (with a few exceptions).
5. When controlling the K-control units;
(1) A K-transmission converter (Model name: PAC-SC25KA) is required. To set the address for the K-transmission converter,
set it to the lowest address of the K-control unit to be controlled + 200.
(2) Set the address of the system controller (G-50A) to “0.” The K-control unit can only be controlled by the system controller
with the address “0.”
(3) To control both K-control unit and M-NET model unit, make the address of the K-control unit larger than that of the indoor
unit of M-NET model.
Group-register on the system controller so that the group No. and the lowest address of the K-controlled indoor units
belonging to the group will be identical.
6. BC controller is found only in the R2 and WR2 systems.
Use the address that equals the sum of the smallest indoor
unit address in the same refrigerant system and 50.
Use the address that equals the sum of the smallest
address of the indoor unit out of all the indoor units
that are connected to the BC controller and 50.
When a sub BC controller is connected, the automatic
start up function will not be available.
Auxiliary
units
BC controller (Sub)
Use the address that equals the sum of the address of the
heat source unit in the same refrigerant system and 1.
BC controller (Main)
Choose any number within the range of addresses shown left.
However when using with the upper SC setting, or wishing to
control the k-control units, set to “0.”
Assign the smallest address to the indoor unit to
become the main unit within the same group, and
then use sequential numbers to assign an address
to all the indoor units in the group. (Note 5)
If applicable, set the sub BC controllers in an R2
system in the following order:
(1)
Indoor unit to be connected to the main BC controller
(2)
Indoor unit to be connected to No.1 sub BC controller
(3)
Indoor unit to be connected to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
Assign any unused address after setting all indoor units.
Set to the lowest address of the indoor main unit
within the same group + 150.
Set to the lowest No. of the group to be controlled + “200.”
Set to the lowest No. of the group desired to be controlled + “200.”
Choose any number within the range of addresses shown left.
Choose any number within the range of ad-dresses shown left.
Choose any number within the range of addresses shown left.
Set to the lowest address of the indoor main unit
within the same group + 100.
No address setting required. (When operating with 2 remote controllers,
the main/sub selector switch must be set.
- 19 -
[2] Types of Switch Setting and Address Setting
1. Switch setting
2. Address setting
Page 23
Setting the power supply selecting connector for outdoor unit (Heat source unit)
(Factory setting: CN41 is connected.)
(2)
Settings for the centralized control switch on the outdoor (heat source) unit
(Factory setting: SW2-1 set to “OFF”)
(3)
Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
(6)
Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 “OFF.”)
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7)
_
n/a
n/a
applicable
applicable//n/a
applicable//n/a
applicable//n/a
With connection to
the indoor-outdoor
transmission line
With connection to
the transmission
line for centralized
control
_
_
_
Indoor unit port switch setting (R2/WR2 series (Factory Setting: “0”))
Make the settings for the port switch that corresponds to the connected BC (Main/Sub) controller.
When more than two ports are used, make the setting on the port with a smaller port number.
The total capacity and the number of connectable indoor units per port is 90 and below, and 3 respectively.
(4)
Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to “OFF”.)
1To use the built-in sensor on the remote controller, set the SW1-1 to ON.
✻Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
✻When using the built-in sensor on the remote controller, install the remote controller where room temperature can
be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models (PEFY-P, M-E-F, PFFY-P, RM-E-F) is ON.
2When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
✻When using an optional temperature sensor, install it where room temperature can be detected.
(5)
Operation of the indoor unit when the operation is resumed after the unit was stoppedFunction
Setting (SW1) (Note 4)
Power ON/OFF by the plug (Note 1, 2, 3)
Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power off (power failure).
9
OFF
ON
OFF
10
ON
OFF
OFF
System
configuration
Single-refrigerant
system
Connection with the
system controller
Power supply
unit for transmission
lines
Grouping
operation of
different
Unnecessary
Unnecessary (Note 2)
()
applicable
The setting of the power supply selecting
connector
Use CN41 as is.
(Factory setting)
Use CN41 as is.
(Factory setting)
Multiplerefrigerant
system
System configuration
Switch setting for centralized control (SW2-1)
Connection with the system controller : n/a
Connection with the system controller : applicable (Note 1)
Leave it to OFF.(Factory setting)
ON
(Note 1) The total number of connectible units in the refrigerant system will be limited. Refer to DATA BOOK.
(Note 2) The need for a power supply unit for transmission lines depends on the system configuration. Refer to DATA BOOK.
(Note 3) When connecting a system controller to the transmission line for centralized control or performing a group operation of units in
different refrigerant systems, the replacement of male power supply switch connector (CN41) must be performed only on one
of the heat source units in the system.
(If a model between 34 and 50 HP is included in the system, replace the connector on that unit.)
(Note 1) Do not cut off power to the outdoor (Heat source) unit.
Cutting off the power supply to the outdoor (Heat source) unit will cut off the power supply to the crankcase heater and may
cause the compressor to malfunction when the unit is put back into operation.
(Note 2) Not applicable to units with a built-in drain pump or humidifier
(Note 3) Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant circuits
will be turned on or off by the plug.
(Note 4) Requires that the dipswitch settings for all the units in the group be made.
(Note 1) When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
Disconnect the male connector from the female
power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.
(Note 3)
Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor (Heat source)
unit whose CN41 was replaced with CN40 to
the earth terminal ( ) on the electric box.
Automatic restoration
after power failure
Power supplied
from outdoor
(Heat source) unit
- 20 -
Page 24
- 21 -
Various types of control using input-output signal connector on the heat source unit (Connection options)(8)
NO
OK
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
(Wrong)
(Correct)
100%
100%
→
→
0%
75%
→
→
50%
50%
Demand control
steps
■CN51
Remote controller board
Controller board on
Heat source unit
Relay circuit
Adapter
CN51
X
Y
X
Y
Maximum allowable wiring length = 10 m
L1 : Error indicator lamp/freeze prevention output
L2 : Compressor operation display lamp
X,Y : Relay (For 12V DC coil rating 0.9 W or below)
L1
L2
Field-installed
■CN3D
Remote controller board
Controller board on
Heat source unit
Relay circuit
Adapter
CN3D
X
Y
X
Y
1
2
3
5
4
3
Maximum allowable wiring length = 10 m
SW1 : Night mode command or step command
SW2 : Compressor ON/OFF command
X,Y
:
Relay (Contact Minimum applied load 12V DC 1 mA)
X :
Relay (Contact rating 219~240V AC 1 A)
52P :
Contactor for pump
SW1
SW2
Field-installed
■TB8
Heat source unit
TB8
3
4
Shortcircuit
jumper
wire
63PW
With connection to pump interlock circuit
Remove the jumper wire when pump interlock circuit signal
connection is made to 3 or 4 of TB8.
(Note 1) The night mode function is enabled when Dip SW 4-7 is set to OFF.
When Dip SW4-7 are set to ON, step demand control is possible, using different configurations of night mode
input and Compressor ON/OFF input settings.
(Note 2) Error status output function on the heat source unit is enabled when Dip SW3-3 is set to OFF.
When Dip SW3-3 is set to ON, signal is output when heat source unit is stopped and water temperature (TH6) goes below 5˚C.
(Note 3) Operation-ON signal is output while the compressor is in operation if Dip SW2-7 is set to OFF.
If Dip SW2-7 is set to OFF, signal is output while receiving cooling or heating operation signal from the remote
controller.
(Signal output is continued even if the compressor comes to a stop due to Thermo OFF.)
FunctionUsage
Signal
type
Terminal
Compressor ON/OFF (level)
Operation status of
the compressor
Error status or freeze
prevention output (Note 2)
Night mode or
step demand (level) (Note 1)
CN3D
TB8
TB8
CN51
Input
Output
Prohibiting cooling/heating operation (thermo OFF) by an external input to the heat
source unit.
✻Can be used as a demand control function for each refrigerant system.
How to extract signals from the heat source unit.
✻Can be used as an operation status display device.
✻Can be used for an interlock operation with external devices.
Performs a low-noise-level operation of the outdoor unit by an external input to the
heat source unit. (The unit can perform a night mode operation under the following
conditions: Outdoor air temperature below 30˚C during cooling operation/Outdoor
air temperature above 3˚C during heating operation.
Pump interlock
signal input (level)
Forces the heat source unit to stop by receiving a contact signal from the pump
interlock circuit.
Operation-ON signal
(Note 3)
Note the following steps to be taken when using the STEP DEMAND
(Example) When witching from 100% to 50%
To tal length (0.3 ~ 1.25mm2)
m1200m
m2 + m3200m
m4 + m5200m
Control wiring example
Group
Prohibited itemsAllowable length
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. When the total number of indoor units exceeds 26 units Including that above Type 200, a transmission booster is required. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the transmission booster.
4. In the case when start/stop input (CN32, CN51, CN41) is used
by indoor group operation, the “Automatic address set-up”
can not be employed. Please refer to 1. (2) “ Manual address
set-up.”
5. For the connection of LOSSNAY with more than 2 units in a
single refrigerant system, refer to the following “Connection
of 2 LOSSNAY units in refrigerant system.”
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
Group
LC
≤
≤
≤
≤
≤
✻1BC and BS are found only in the R2 and WR2 systems.
When connected to the BS, indoor-outdoor automatic
address start up function will not be available.
00
OC
BC
✻
1
✻
1
00
00
TB02
BS
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
- 22 -
[3]Examples of system connection
1. System using MA remote controller
(1) In the case of single refrigerant system (Automatic address set-up)
Page 26
Wiring method • Address setting method
a. Indoor/outdoor transmission line
❉ When the transmission line is long or noise sources are located near the unit, recommend to use shielded wire.
Connection of shielded wire:
For the earth of shielded wire, apply jumper wiring connection between the earth screw of OC and the S-terminal of
IC terminal block (TB5).
b. Centralized control transmission line
Connection is not required.
c. MA remote controller wiring
Connect the 1, 2 terminals of MA remote controller wiring terminal block (TB15) on IC to the terminal block of MA
remote controller (MA). (with non-polarity two wires)
❉ MA remote controller can be connected to A-type indoor unit or later.
For 2-remote controller operation:
To employ 2-remote controller operation, connect 1, 2 terminals of the terminal block (TB15) on IC to the terminal
block of two MA remote controllers.
❉ Set the main/sub selector switch of one MA remote controller to the sub remote controller. (For the setting method,
see the installation manual of MA remote controller.)
For indoor group operation:
For the group operation of IC, connect 1, 2 terminals of the terminal block (TB15) on all ICs within the same group,
and connect 1, 2 terminals of the terminal block (TB15) on another IC to the terminals of MA remote controller.
(with non-polarity two wires)
❉ To operate the indoor units with different function in the same group, refer to 1. (2).
d. LOSSNAY connection
❉ Linked and registered automatically with all indoor units within a refrigerant system.
❉ Please refer to the 1. (2) “Manual address set-up,” when interlocking partial indoor units with Lossnay, using
Lossnay alone without interlocking, interlocking indoor units and Lossnay for over 16 units within a refrigerant
system, or connecting LOSSNAY for over 2 units in a refrigerant system.
e. Switch setting
Address setting is not required.
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
Main unitIC
Not required
Not required
–
00
1Indoor unit
Sub unitIC
2LOSSNAYLCNot required–
3
MA remote
Main uni
BC controller
tMANot required–
Main
controller
Sub unitMASub unit
4
Outdoor (Heat source) unit OC
–
5
Auxiliary
units
BC
• Refer to 1. (2)
• Branch number setting is required by
R2 and WR2 systems.
to operate indoor units
with different function in the same
group.
Set with main/sub
selector switch.
00
00
Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor (heat
source) unit (OC), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC
controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor
unit. (with non-polarity two wires)
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on IC to the indoor/outdoor
transmission terminal block (TB5) on LOSSNAY (LC). (with non-polarity two wires)
- 23 -
Page 27
L2L1
OC
TB3
TB7TB02
TB02
IC
TB5TB
15
12
01
IC
TB5TB
15
12
02
A1 B2
MA
A1 B2
MA
TB5
05
IC
TB5
12
TB
15
IC
TB5TB
15
12
0403
TB5
06
A1 B2
MA
L11
L3L4
L12L13
a. Indoor/outdoor transmission line
The same as 1. (1)
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
The same as 1. (1)
Control wiring example
Group
Prohibited itemsAllowable length
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. When the total number of indoor units exceeds 26 units including that above Type 200, a transmission booster is required. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the transmission booster.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
✻
1.
BC and BS are found only in the R2 and WR2 systems.
51
52
53
BC✻1
BS
✻1
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
- 24 -
1. System using MA remote controller
(2) In the case of single refrigerant system connecting 2 or more LOSSNAY units (Manual address set-up)
Page 28
- 25 -
1Indoor unit
2LOSSNAY
3
MA remote
controlle
4Outdoor (Heat source) unit
r
Main unit
Sub unit
Main unit
BC Controller
(sub)
BC Controller
(main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Wiring method • Address setting method
a. Indoor/outdoor transmission line
Connection of shielded wire:
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
For 2-remote controller operation:
For indoor group operation:
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
d. LOSSNAY connection
❉ The interlocking registration of the indoor unit and Lossnay from the remote controller is required. (For the regis-
tration method, see the installation manual of remote controllers.)
e. Switch setting
Address setting is required as listed below.
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
• Set
•
•
the lowest address within
a same group to the indoor unit
desired to be the main unit.
[Main unit +1, +2, +3, .... ]
Set any address after setting al
5
Auxiliary
units
BS
BC
Set with main/sub selector switch.
l
indoor units.
–
00
00
Main
00
•When operating indoor
units with different function
within a same group, assign the indoor unit with the
most plenty of function to
the main unit.
• Set the address not to be
overlapped with the indoor
unit address.
The lowest address of indoor unit
within refrigerant system + 50
The address of the indoor unit
connected to the sub BC controller must be larger than that
of the indoor unit connected to
the main BC controller.
If applicable, set the sub BC
controllers in an R2 system in
the following order:
(1)
Indoor unit to be connected
to the main BC controller
(2)
Indoor unit to be connected
to No.1 sub BC controller
(3)
Indoor unit to be connected
to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
•
Use the address that equals the
sum of the smallest indoor unit
address out of all the indoor
units that are connected to the
sub BC controller and 50.
Outdoor (Heat source) unit
address +1
Requires a branch-number setting.
Set to the main unit address within a same group in serial order
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on the indoor unit (IC) to the terminal
block (TB5) on Lossnay (LC). (with non-polarity two wires)
• To set the address to “100,”
set it to “50”.
• If the address of main BC
controller overlaps with the
address of the outdoor
(heat source) unit or the
sub BC controller, use an
unused address within the
setting range.
• The use of a sub BC controller requires a main BC
controller.
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the indoor unit connected to different outdoor (heat source) units.
4. Replacement of the power supply selecting connector (CN41)
on the outdoor (heat source) unit should be done only on one
outdoor (heat source) unit.
5. Grounding of S-terminal of the centralized control terminal
block (TB7) on outdoor (heat source) unit should be done
only on one outdoor (heat source) unit.
6. When the total number of indoor units exceeds 26 units including that above Type 200, a transmission booster is required. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the transmission booster.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
≤
≤
≤
NO
✻1.BC and BS are found only in the R2 and WR2 systems.
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
51
52
53
55
54
Connect
OC
OC
Leave CN41
as it is.
CN41→CN40
Replace
TB02
TB02
TB02
TB7TB3
TB7TB3
BC✻1
BC
✻1
BS
✻1
1. System using MA remote controller
(3) In the case of different refrigerant grouping operation
Page 30
- 27 -
Wiring method • Address setting method
a. Indoor/outdoor transmission line
❉
Make sure to use shielded wire.
Connecting of shielded wire:
The same as 1. (1)
b. Centralized control transmission line
Apply jumper wiring between M1, M2 terminals of centralized control transmission line terminal blocks (TB7) on
each OC. For one OC only, replace the power selecting connector (CN41) with (CN40).
❉ Make sure to use shielded wire.
Connecting of shielded wire:
Apply jumper wiring to connect the shielded earth to S-terminal of the terminal block (TB7) on each OC. Connect Sterminal of the terminal block (TB7) on the one OC with (CN40) replaced to the earth screw ( ) of the electrical parts box.
c. MA remote controller wiringThe same as 1. (1)
For 2-remote controller operation:The same as 1. (1)
For indoor unit group operation:The same as 1. (2)
d. LOSSNAY connectionThe same as 1. (2)
e. Switch setting
Address setting is required as follows.
Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor (heat
source) unit (OC), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC
controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor
unit. (with non-polarity two wires)
1Indoor unit
2LOSSNAY
3
MA remote
controlle
4Outdoor (Heat source) unit
r
Main unit
Sub unit
Main uni
t
BC Controller
(sub)
BC Controller
(main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
• Set
•
•
the lowest address within
a same group to the indoor unit
desired to be the main unit.
[Main unit +1, +2, +3, .... ]
Set any address after setting al
5
Auxiliary
units
BS
BC
Set with main/sub selector switch.
l
indoor units.
–
00
00
Main
00
•When operating indoor
units with different function
within a same group, assign the indoor unit with the
most plenty of function to
the main unit.
• Set the address not to be
overlapped with the indoor
unit address.
The lowest address of indoor unit
within refrigerant system + 50
The address of the indoor unit
connected to the sub BC controller must be larger than that
of the indoor unit connected to
the main BC controller.
If applicable, set the sub BC
controllers in an R2 system in
the following order:
(1)
Indoor unit to be connected
to the main BC controller
(2)
Indoor unit to be connected
to No.1 sub BC controller
(3)
Indoor unit to be connected
to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
•
Use the address that equals the
sum of the smallest indoor unit
address out of all the indoor
units that are connected to the
sub BC controller and 50.
Outdoor (Heat source) unit
address +1
Requires a branch-number setting.
Set to the main unit address within a same group in serial order
• To set the address to “100,”
set it to “50”.
• If the address of main BC
controller overlaps with
the address of the outdoor
(heat source) unit or the
sub BC controller, use an
unused address within the
setting range.
• The use of a sub BC controller requires a main BC
controller.
Page 31
- 28 -
IC
TB5 TB
15
12
01
IC
TB5 TB
15
12
07
A1 B2
MA
A1 B2
MA
TB5
05
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0403
TB5
06
A1 B2
MA
L3L2L1L4
L23L22L21L24
L31
L32
NO
a. Indoor/outdoor transmission line
The same as 1. (3)
b. Centralized control transmission line
Farthest length via outdoor (heat source) unit
(1.25m m2 or more)
L32 + L31 + L1 + L2 + L3 + L4500m
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the indoor unit connected to different outdoor (heat source) units.
6. When the total number of indoor units exceeds 26 units Including that above Type 200, a transmission booster is re-
quired. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the transmission booster.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
Notes:
1. Leave SW2-1 as “OFF” when connecting LM adapter only.
2. LM adapter requires the power source of 1-phase AC 230V.
Note 2
System controller
≤
≤
≤
4. Replacement of the power supply selecting connector (CN41)
on the outdoor (heat source) unit should be done only on
one outdoor (heat source) unit.
5. Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor (heat source)
unit only.
✻1.BC and BS are found only in the R2 and WR2 systems.
NO
TB02TB7TB3
Note 1
Note 1
CN41→CN40 Replace
SW2-1 OFF→ON
51
53
54
52
57
Connect
OC
OC
TB7TB02
TB02
TB3
Leave CN41 as it is.
SW2-1 OFF→ON
BC✻1
BC
✻1
BS
✻1
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
1. System using MA remote controller
(4) In the case of connecting system controller to centralized control transmission line
Page 32
- 29 -
Wiring method • Address setting method
a. Indoor/outdoor transmission line
Connection of shielded wire:
The same as 1. (3)
The same as 1. (1)
c. MA remote controller wiring
For 2-remote controller operation:
For indoor group operation:
The same as 1. (1)
The same as 1. (1)
The same as 1. (1)
d. LOSSNAY connection
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on (IC) to the terminal block (TB5) on
the indoor/outdoor transmission line terminal block (TB5) on Lossnay (LC). (with non-polarity two wires)
❉ The interlocking registration of the indoor unit and LOSSNAY from the system controller is required. (For the
registration method, see the installation manual of the system remote controllers.) When connecting ON/OFF
remote controller and LM adaptor only, the interlocking registration from the remote controller is required.
e. Switch setting
Address setting is required as listed below.
b. Centralized control transmission line
Apply jumper wiring between M1, M2 terminals of centralized control transmission line terminal blocks (TB7) on
each OC. On one OC only, replace the power selecting connector (CN41) with (CN40). Set the centralized control
switch (SW2-1) on the main board of all outdoor (heat source) units to “ON.”
❉ Make sure to use shielded wire.
Connection of shielded wire:
Apply jumper wiring to connect the shielded earth to S-terminal of the terminal block (TB7) on each OC. Connect
S-terminal of the terminal block (TB7) on one OC with (CN40) connected to the earth screw ( ) of the electrical parts box.
1Indoor unit
2LOSSNAY
3
MA remote
controlle
4Outdoor (Heat source) unit
r
Main unit
Sub unit
Main uni
t
BC Controller
(sub)
BC Controller
(main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
• Set
•
•
the lowest address within
a same group to the indoor unit
desired to be the main unit.
[Main unit +1, +2, +3, .... ]
Set any address after setting al
5
Auxiliary
units
BS
BC
Set with main/sub selector switch.
l
indoor units.
–
00
00
Main
00
•When operating indoor
units with different function
within a same group, assign the indoor unit with the
most plenty of function to
the main unit.
• Set the address not to be
overlapped with the indoor
unit address.
The lowest address of indoor unit
within refrigerant system + 50
The address of the indoor unit
connected to the sub BC controller must be larger than that
of the indoor unit connected to
the main BC controller.
If applicable, set the sub BC
controllers in an R2 system in
the following order:
(1)
Indoor unit to be connected
to the main BC controller
(2)
Indoor unit to be connected
to No.1 sub BC controller
(3)
Indoor unit to be connected
to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
•
Use the address that equals the
sum of the smallest indoor unit
address out of all the indoor
units that are connected to the
sub BC controller and 50.
Outdoor (Heat source) unit
address +1
Requires a branch-number setting.
Set to the main unit address within a same group in serial order
• To set the address to “100,”
set it to “50”.
• If the address of main BC
controller overlaps with
the address of the outdoor
(heat source) unit or the
sub BC controller, use an
unused address within the
setting range.
• The use of a sub BC controller requires a main BC
controller.
Page 33
NO
Control wiring example
Prohibited itemsAllowable length
Connection to the BC controller
Numbers in the squares indicate pipe-end
connection number.
– Example to use shielded wire –
System controller
Note 2
Note 1
IC
TB5 TB
15
12
01
IC
TB5 TB
15
12
02
IC
TB5 TB
15
12
04
IC
TB5 TB
15
12
06
A1 B2
MA
A1 B2
MA
A1 B2
MA
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0503
GroupGroup
GroupGroup
L2
L22
L3
IC
TB5 TB
15
12
07
IC
TB5 TB
15
12
08
A1 B2
MA
Group
L6L5L7
IC
TB5 TB
15
12
09
IC
TB5 TB
15
12
10
A1 B2
MA
Group
L26L27
L4
L23L24L25
A1 B2
MA
L31
L32
S
M1M2
S
M1M2SM1M2
S
M1M2
S
M1M2
S
M1M2SM1M2
S
M1M2
S
M1M2SM1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2SM1M2
S
M1M2
S
M1M2
S
M1M2SM1M2
S
M1M2
M1M2
OC
TB3
TB7
51
BC
BC
TB02
5257
OC
TB3
TB7
53
TB02
BS
TB02
BS
TB02
L1
L21
CN41→CN40 Replace
SW2-1 OFF→ON
Leave CN41 as it is.
SW2-1 OFF→ON
112122212
57
112443234
5459
IC
TB5 TB
15
12
11
IC
TB5 TB
15
12
12
A1 B2
MA
Group
L9L10
61
BS
TB02
1212
L8
Connect
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the indoor unit connected to different outdoor (heat source) units.
6. When the total number of indoor units exceeds 26 units Including that above Type 200, a transmission booster is required. When the transmission booster is used, BC and BS
cannot be connected to TB3 (indoor unit side) on the transmission booster.
4. Replacement of the power supply selecting connector (CN41)
on the outdoor (heat source) unit should be done only on one
outdoor (heat source) unit.
5. Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor (heat source)
unit only.
Notes:
1. Leave SW2-1 as “OFF” when connecting LM adapter only.
2. LM adapter requires the power source of 1-phase AC 230V.
Connecting (multiple) BC controllers in R2 and WR2 systems (with the system controller connected to the transmission lines for centralized control)
Page 34
1Indoor unit
2LOSSNAY
3
MA remote
controller
Outdoor (Heat source) unit
4
Main unit
Sub unit
Main unit
BC Controller
(sub)
BC Controller
(main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Sub unit
Wiring method • Address setting method
a. Indoor/outdoor transmission line
Connection of shielded wire:The same as 1. (1)
Connection of shielded wireThe same as 1. (4)
b. Centralized control transmission line
The same as 1. (4)
c. MA remote controller wiringThe same as 1. (1)
For 2-remote controller operation:The same as 1. (1)
For indoor group operation:
The same as 1. (1)
d. LOSSNAY connectionThe same as 1. (4)
e. Switch settingAddress setting is required as listed below.
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
[Main unit +1, +2, +3, .... ]
5
Auxiliary
units
BS
BC
Set with main/sub selector switch.
–
00
00
Main
00
• Assign the smallest address
within the group to the indoor
unit to become the main unit.
• The address of the indoor unit
connected to the sub BC controller must be larger than that
of the indoor unit connected to
the main BC controller.
• If applicable, set the sub BC
controllers in an R2 system in
the following order:
(1)
Indoor unit to be connected
to the main BC controller
(2)
Indoor unit to be connected
to No.1 sub BC controller
(3)
Indoor unit to be connected
to No.2 sub BC controller
Set the address so that (1) < (2) < (3)
• To set the address to “100,”
set it to “50”.
• If the address of main BC
controller overlaps with
the address of the outdoor
(heat source) unit or the
sub BC controller, use an
unused address within the
setting range.
• The use of a sub BC controller requires a main BC
controller.
•
Using the system controller,
make the same indoor group
setting that was made with
the MA remote controller.
• Set the address not to be
overlapped with the indoor
unit address.
• R2 and WR2 types require
a branch number setting.
Use the address that equals the
sum of the smallest indoor unit
address out of all the indoor
units that are connected to the
sub BC controller and 50.
The lowest address of indoor unit
within refrigerant system + 50
Outdoor (Heat source) unit
address +1
Set to the main unit address within a same group in serial order
Connect terminals M1 and M2 of the indoor-outdoor transmission line terminal block (TB3) on the outdoor (heat
source) unit (OC) to the terminals M1 and M2 of the indoor-outdoor transmission terminal block (TB02) of the main
BC controller (BC) and the sub BC controller (BS) and terminals M1 and M2 of the indoor-outdoor transmission terminal block (TB5) on each indoor unit (IC).
❉ Make sure to use shielded wire.
1. M-NET and MA remote controllers can not be connected together to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the indoor unit connected to different outdoor (heat source) units.
4. Replacement of the power supply selecting connector (CN41)
on the outdoor (heat source) unit should be done only on one
outdoor (heat source) unit.
5. Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor (heat source)
unit only.
6. The system controller connectable to the indoor/outdoor transmission line counts for 3 sets maximum. While G-50 counts
for only 1 set
7. When the total number of indoor units exceeds 26 sets, th e
system controller may not be connected to the indoor/outdoor transmission line.
8. When the total number indoor units exceed 18 sets and they
includes Type 200 or above, the system controller may not
be connected to the indoor/outdoor transmission line.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
Note 1
System controller
Note 1. LM adaptor may not be connected to indoor/outdoor transmission line.
≤
≤
≤
≤
≤
✻1.BC and BS are found only in the R2 and WR2 systems.
NO
OC
TB3
TB7
51
✻1 BC
TB02
52
OC
TB3
TB7
53
✻1 BC
TB02
54
TB02
57
✻1 BS
Connect
CN41→CN40 Replace
SW2-1 OFF→ON
Leave CN41 as it is.
SW2-1 OFF→ON
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
1. System using MA remote controller
(6) In the case of connecting system controller to indoor/outdoor transmission line (excluding LM adaptor)
Page 36
- 33 -
Wiring method • Address setting method
a. Indoor/outdoor transmission line
❉ Make sure to use shielded wire.
Connection of shielded wire:
For the grounding of shielded wire, apply jumper wiring between the grounding screw of OC, S-terminal of the
terminal block (TB3), and S-terminal of the system controller.
b. Centralized control transmission line
Apply jumper wiring between M1, M2 terminals of centralized control transmission line terminal blocks (TB7) on
each OC. On one OC only, replace the power selecting connector (CN41) with (CN40). Set the centralized control
switch (SW2-1) on the main board of all outdoor (heat source) units to “ON.”
❉ Make sure to use shielded wire.
Connection of shielded wire:
Apply jumper wiring to connect the shielded earth to S-terminal of the terminal block (TB7) on each OC. Connect Sterminal of the terminal block (TB7) on one OC with (CN40) connected to the earth screw ( ) of the electrical parts box.
c. MA remote controller wiring
The same as 1. (1)
For 2-remote controller operation:
The same as 1. (1)
For indoor unit group operation:
The same as 1. (2)
d. LOSSNAY connection
Apply jumper wiring to connect M1, M2 terminals of the terminal block (TB5) on (IC) to the terminal block (TB5) on
the indoor/outdoor transmission line terminal block (TB5) on Lossnay (LC). (with non-polarity two wires)
❉ The interlocking registration of the indoor unit and Lossnay is required from the system controller. (For the
registration method, see the instruction manual of system controller.)
To connect ON/OFF remote controller only, interlocking registration from the remote controller is required.
e. Switch settingAddress setting is required as follows.
Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor (heat
source) unit (OC), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC
controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor
unit. (with non-polarity two wires)
1Indoor unit
2LOSSNAY
3
MA remote
controlle
4Outdoor (Heat source) unit
r
Main unit
Sub unit
Main uni
t
BC Controller
(sub)
BC Controller
(main)
Sub unit
IC
LC
MA
OC
MA
01 ~ 50
01 ~ 50
Not required
52 ~ 100
51 ~ 100
Not required
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
Set any address after setting all
indoor units.
5
Auxiliary
units
BS
BC
Set with main/sub selector switch.
–
00
00
Main
00
The lowest address of indoor unit
within refrigerant system + 50
• Set the lowest address within a
same group to the indoor unit
desired to be the main unit.
• The address of the indoor unit
connected to the sub BC
controller must be larger than that
of the indoor unit connected to
the main BC controller.
• If applicable, set the sub BC
controllers in an R2 system in the
following order:
(1) Indoor unit to be connected to
the main BC controller
(2) Indoor unit to be connected to
No.1 sub BC controller
(3) Indoor unit to be connected to
No.2 sub BC controller
Set the address so that (1) < (2) < (3)
Set to the main unit address within a
same group in serial order
[Main unit +1, +2, +3,....]
Use the address that equals the
sum of the smallest indoor unit address out of all the indoor units that
are connected to the sub BC controller and 50.
Outdoor (Heat source) unit
address +1
• When operating indoor units
with different function within a
same group, as-sign the
indoor unit with the most
plenty of function to the main
unit.
• Requires a branch-number
setting.
• Set the address not to be
overlapped with the indoor
unit address.
• To set the address to “100,”
set it to “50”.
• If the address of main BC con-
troller overlaps with the address of the outdoor (heat
source) unit or the sub BC controller, use an unused address within the setting range.
• The use of a sub BC controller
requires a main BC controller.
Page 37
- 34 -
IC
TB5 TB
15
12
01
101
103
102
IC
TB5 TB
15
12
07
A1 B2
RC
A1 B2
RC
TB5
05
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0403
TB5
06
A1 B2
RC
L3L4
L23L24
L2L1
L22L21
L31
L32
NO
Control wiring example
Group
Prohibited itemsAllowable length
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
Note 2
System controller
✻1.BC and BS are found only in the R2 and WR2 systems.
1. A group of indoor units cannot be connected to both M-NET
remote controller and MA remote controllers.
2. No more than 2 M-NET remote controllers can be connected
to a group of indoor units.
3. Do not connect the TB5’s (Terminal block) of the indoor
units that are connected to different outdoor (heat source)
units.
4. Replace CN41 (power supply switch connector on outdoor
(heat source) units) on only one of the outdoor (heat source)
units.
5. Ground the S terminal of TB7 on only one of the outdoor
(heat source) units.
6. Transmission line booster is necessary when the total
number of connected indoor units exceeds 20 (19 with 1 BC
and 18 with 1 BC and BS each). When the transmission
booster is used, BC and BS cannot be connected to TB3
(indoor unit side) on the transmission booster.
7. Transmission line booster is necessary if the system
includes indoor units of 200 or higher and the total number
of indoor units exceeds 16 (15 with 1 BC and 14 with 1 BC
and BS each).
a. Indoor/outdoor transmission line
b. Centralized control transmission line
c. M-NET remote controller wiring
The same as 2. (1)
The same as 1. (4)
The same as 1. (3)
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
NO
OC
TB3
TB7
51
✻1 BC
TB02
52
OC
TB3
TB7
53
✻1 BC
TB02
54
TB02
57
✻1 BS
Connect
Note1
Note1
Notes:
1. Leave SW2-1 as “OFF” when connecting LM adapter only.
2. LM adapter requires the power source of 1-phase AC 230V.
CN41→CN40 Replace
SW2-1 OFF→ON
Leave CN41 as it is.
SW2-1 OFF→ON
2. System Using the M-NET Remote Controller
(1) System with the system controller connected to the transmission lines for centralized control
Page 38
- 35 -
BC Controller
(sub)
BC Controller
(main)
52 ~ 100
5
Auxiliary
units
BS
BC
00
Use the address that equals the
sum of the smallest indoor unit address out of all the indoor units that
are connected to the sub BC controller and 50.
Outdoor (Heat source) unit
address +1
a. Indoor/outdoor transmission line
Connection of shielded wire:
b. Centralized control transmission line
c. M-NET remote controller wiring
The same as 1. (3)
For 2-remote controller operation:
The same as 1. (1)
Connection of shielded wire:
The same as 1. (4)
The same as 1. (4)
For a 2-remote-controller operation, connect each of the terminals M1 and M2 of the IC terminal block to the two
RC terminal blocks respectively.
Indoor unit group operation
To operate IC’s as a group, connect the M1, M2 terminals of the terminal block on the main IC in the group with
the RC terminal block (with non-polar two wires)
❉M-NET remote controller can be connected at any point on the indoor/outdoor transmission line.
❉To run a group operation of indoor units that have different functions, select the unit with the greatest number
of functions as the main unit.
The same as 1. (4)
For indoor unit group operation:
d. LOSSNAY connection
M-NET remote controller wiring
Connect each of the M1 and M2 terminals of TB5 (indoor/outdoor transmission line terminal block) on the IC to
the terminals on the M-NET remote controller.
e. Switch settingAddress setting is required as follows.
1Indoor unit
2LOSSNAY
3
M-NET
remote
controller
4Outdoor (Heat source) unit
Main unit
Sub unit
Main unit
Sub unit
IC
OC
LC
RC
RC
01 ~ 50
01 ~ 50
51 ~ 100
101 ~ 150
151 ~ 200
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
00
00
101
00
Starting with the number main unit
address +1, assign a sequential
number to each of the rest of the
indoor units.
After all indoor units have received
an address, use any remaining
number and assign it to the Lossnay
unit. units.
The smallest indoor unit address in
the same refrigerant system +50
The address of the main unit in the
same group +100
The address of the main unit in the
same group +150
• Assign the smallest address within
the group to the indoor unit to
become the main unit.
• Assign a larger address to the
indoor unit that is connected to the
R2-type sub BC controller than the
one assigned to the indoor unit
connected to the main BC
controller.
• If applicable, set the sub BC con-
trollers in an R2 system in the following order:
(1) Indoor unit to be connected to
the main BC controller
(2) Indoor unit to be connected to
No.1 sub BC controller
(3) Indoor unit to be connected to
No.2 sub BC controller
Set the address so that (1) < (2) < (3)
• Make the initial setting of the
indoor unit group setting with
the system controller
(MELANS).
• Branch numbers must be set
for systems with R2 and WR2.
• The Lossnay address must not
overlap with the indoor unit
address.
• 100’ s digit does not need to be
set.
• Set the address to “ 00 ” when
setting it to “ 200 ”.
• Set the address to “ 50 ” when
setting it to “ 100 ”.
Wiring method • Address setting method
• To set the address to “100,” set
it to “50”.
• If the address of main BC controller overlaps with the address of the outdoor (heat
source) unit or the sub BC controller, use an unused address
within the setting range.
• The use of a sub BC controller
requires a main BC controller.
Page 39
- 36 -
IC
TB5 TB
15
12
01
IC
TB5 TB
15
12
02
IC
TB5 TB
15
12
07
104
IC
TB5 TB
15
12
06
A1 B2
MA
A1 B2
RC
A1 B2
MA
IC
TB5
12
TB
15
IC
TB5 TB
15
12
0503
L2L1
L22L21
L3L4
L23L24
105
A1 B2
RC
L31
L32
NO
a. Indoor/outdoor transmission line
The same as 1. (3)
b. Centralized control transmission line
The same as 1. (4)
c-1. MA remote controller wiring
The same as 1. (1)
c-2. M-NET remote controller wiring
The same as 2. (1)
Control wiring example
Group
Prohibited itemsAllowable length
1. Make sure to connect the system controller.
2. M-NET and MA remote controllers can not be connected together to the indoor unit within a same group.
3. M-NET remote controller of 3 units or more can not be connected to the indoor unit within a same group.
6.
7.
8. When the total number of indoor units exceeds 20 sets, transmission line booster is required. When the transmission
booster is used, BC and BS cannot be connected to TB3
(indoor unit side) on the transmission booster.
9. When the total number of indoor units exceed 16 sets and
they include Type 200 or above, the transmission line booster
is required.
– Example to use shielded wire –
Group
Group
Note 2
System controller
Notes:
1. Leave SW2-1 as “OFF” when connecting LM adapter only.
2. LM adapter requires the power source of 1-phase AC 230V.
Note1
Note1
Group
Replacement of the power supply selecting connector (CN41)
on the outdoor (heat source) unit should be done only on one
outdoor (heat source) unit.
Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor (heat source)
unit only.
CN41→CN40 Replace
SW2-1 OFF→ON
Leave CN41 as it is.
SW2-1 OFF→ON
4. MA remote controller of 3 units or more can not be connected
to the indoor unit within a same group.
5. Do not connect together the terminal blocks (TB5) of the indoor unit connected to different outdoor (heat source) units.
OC
TB3
TB7
51
✻2 BC
TB02
52
OC
TB3
TB7
53
✻2 BC
TB02
54
TB02
57
✻2 BS
NO
Connect
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2M1M2
3. System where MA remote controller and M-NET remote controller coexist
Page 40
- 37 -
Indoor
unit
MA
remote
controller
Indoor
unit
M-NET
remote
controller
Wiring method • Address setting method
a. Indoor/outdoor transmission lineThe same as 1. (3)
Connection of shielded wire:The same as 1. (1)
b. Centralized control transmission lineThe same as 1. (4)
Connection of shielded wire:The same as 1. (4)
c-1. MA remote controller wiring, For 2-remote controller operation: , For indoor unit group operation:
The same as 1. (1)
c-2. M-NET remote controller, For 2-remote controller operation: , For indoor unit group operation:
The same as 2. (1)
d. Lossnay connectionThe same as 1. (4)
e. Switch settingAddress setting is required as follows.
Operation
with MA
remote
controller
Operation
with M-NET
remote
ontroller
Lossnay
Outdoor (Heat source) unit
IC
MA
MA
IC
RC
RC
LC
OC
01 ~ 50
Not
required
Sub remote
controller
01 ~ 50
101 ~ 150
151 ~ 200
01 ~ 50
51 ~ 100
52 ~ 100
Order
Unit or controller
Address
Setting methodCaution
Factory
setting range
setting
–
00
Main
00
101
00
00
00
Main
unit
Sub
unit
Main
unit
Sub
unit
Main
unit
Sub
unit
Main
unit
Sub
unit
1
2
3
4
BC Controller
(sub)
BC Controller
(main)
5
Auxiliary
units
BS
BC
• To set the address to “100,” set it
to “50”.
• If the address of main BC controller overlaps with the address of
the outdoor (heat source) unit or
the sub BC controller, use an unused address within the setting
range.
• The use of a sub BC controller requires a main BC controller
Use the address that equals the
sum of the smallest indoor unit address out of all the indoor units that
are connected to the sub BC controller and 50.
Outdoor (Heat source) unit
address +1
• Set the lowest address within a
same group to the indoor unit
desired to be the main unit.
• Assign a larger address to the
indoor unit that is connected to the
R2-type sub BC controller than the
one assigned to the indoor unit
connected to the main BC
controller.
• If applicable, set the sub BC con-
trollers in an R2 system in the following order:
(1) Indoor unit to be connected to
the main BC controller
(2) Indoor unit to be connected to
No.1 sub BC controller
(3) Indoor unit to be connected to
No.2 sub BC controller
Set the address so that (1) < (2) < (3)
• After setting the address of the
indoor unit to be operated with MA
controller, set the lowest address
among the same group to the
indoor unit desired to be the main
unit.
• Assign a larger address to the
indoor unit that is connected to the
R2-type sub BC controller than the
one assigned to the indoor unit
connected to the main BC
controller.
• Set lower address than that of
the indoor unit connected to
M-NET remote controller.
• Initially set the same setting
detail as that of indoor unit group
executed in the wiring of MA
remote controller with system
controller.
• Branch numbers must be set for
systems with R2 and WR2.
• Initially set the same setting
detail as that of indoor unit group
with system controller.
• Branch numbers must be set for
a system with R2.
• 100 digits are not required to set.
• When setting the address as
“200,” make it “00.”
• When setting the address to
“100,” make it “50.”
• Set so that not duplicating with
the indoor unit addresses.
Set to the main unit address within
a same group in serial order.
[Main unit +1, +2, +3,
....]
Set to the main unit address within
a same group in serial order.
[Main unit +1, +2, +3,
....]
Main unit address inside a same
group + 100
After setting all indoor units, set any
address.
The lowest address of indoor unit
within refrigerant system + 50
Main unit address inside a same
group + 150
Set by using the main/sub selector
switch
Page 41
- 38 -
For the piping connection, the end branching system is applied where the end of refrigerant piping from the heat source
unit is branched and connected to each indoor unit. As the piping connection method, the indoor unit is applied with flare
connection, heat source unit gas piping is flange connection, and liquid piping is flare connection. For the branching,
brazed connection is applied.
Warning
Be careful not to leak refrigerant gas (R410A) near a fire. Refrigerant gas if touched a fire of gas oven and the like will
be decomposed to generate poisonous gas leading to gas-poisoning. Do not conduct welding work in a closed room.
Run a gas leak test after completing refrigerant piping work.
Do not use a charging cylinder.
• Using a charging cylinder may cause the refrigerant to
deteriorate.
Do not use existing refrigerant piping.
• The old refrigerant and refrigerator oil in the existing piping
contains a large amount of chlorine which may cause the
refrigerantor oil of the new unit to deteriorate.
Store the piping to be used during installation indoors
and keep both ends of the piping sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
• If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Caution
Caution
Caution
Do not use a refrigerant other than that indicated on
the equipment at installation or movement.
•Mixing of different refrigerant or air makes the refrigeration cycle
abnormal causing breakage and the like.
Warning
Caution
Use refrigerant piping phosphorus deoxidized copper. In addition, be sure that the inner and outer surface of the pipes are clean and free of hazardous
sulphur, oxides, dust/dirt, shaving particles, oils,
moisture, or any other contaminant.
• Contaminants on the inside of the refrigerant piping may cause
the refrigerant residual oil to deteriorate.
Caution
Use liquid refrigerant to fill the system.
• If gas refrigerant is used to seal the system, the composition of
the refrigerant in the cylinder will change and performance may
drop.
[4]Restrictions on Refrigerant Piping Length
Page 42
- 39 -
B
A
a
b
c
d
e
400
350
300
250
200
30 40 50 60 70 80 90 100 110
70
60
40
30
50
10
20
0
051015
Note 1: Use the figures in the parentheses if the capacity of the connected indoor units is P200 type or above.
Note 2: Refer to the graph below for restrictions on refrigerant piping length when the total piping length exceeds 300 m.
Note 3: Refer to the graph below for restrictions on refrigerant piping length when the piping length between the BC
controller and the farthest indoor unit exceeds 40 m. (except P250-type indoor units)
Note 4: When indoor units of P200 type or above are connected, neither branch joints nor branch headers can be used.
Note 5: Do not connect P200- or P250-type indoor units and other types of indoor units at the same pipe end connection.
[16 branches or less (the use of only the main BC controller or standard BC controller)]
BC controller
Indoor unit
Indoor unit
Heat
source
unit
Indoor unit
Indoor unitIndoor unit
110 m or less
40 m or less
(P141~P250 types: 2-line merge)
• Restrictions on piping length
Total piping length (m)
Piping length between main BC controller
and farthest indoor unit (m)
• Height difference and branch piping length between
BC controller and indoor unit. (A)
Distance between heat source unit and
BC controller (m)
Height difference between main BC controller and
farthest indoor unit (m)
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
Junction
pipe
(option)
Branch pipe (for Y-series)
CMY-Y102S-G
H = 50 m or less (outdoor unit above)
H’ = 40 m or less (outdoor unit below)
h1 = 15 m or less
h2 = 15 m or less
Total piping length
A + B + a + b + c + d + e
Piping length
Farthest piping length
Between heat source unit - BC controller
Height difference
Between BC controller and indoor unit
Between indoor unit and BC controller
Between indoor units
Between indoor unit
and heat source unit
Heat source unit above
Heat source unit below
300 m less (Note 2)
A + e
150 m or less
(175 m equivalent length or less)
A110 m or less
e40 m or less (Note 3)
H50 m or less
H’40 m or less
h115 m or less (10 m or less) (Note 1)
h215 m or less (10 m or less) (Note 1)
ItemPiping sectionsAllowable value
1. Line-branch method
■PQRY-P200,P250YGM-A
Page 43
B
A
a
b
c
d
e
400
350
300
250
200
30 40 50 60 70 80 90 100 110
70
60
40
30
50
10
20
0
051015
Note:
A system with more than 16 branching requires 2 to 3 BC controllers (main/sub) and 3 pipes between BC controllers.
Note 1: Refer to the graph below for restrictions on refrigerant piping when the total piping length exceeds 300 m.
Note 2: Refer to the graph below for restrictions on refrigerant piping length when the piping length between the BC
controller and the farthest indoor unit exceeds 40 m. (except P250-type indoor units)
Note 3: Use the figures in the parentheses if the capacity of the connected indoor units is P200 type or above.
Note 4: When indoor units of type P200 or above are connected, neither branch joints nor branch headers can be used.
Note 5: When 2 sub BC controllers are connected, include them in the figures in the table above.
Note 6: When 2 sub BC controllers are connected, connect them in parallel.
C
Note 6
f
g
h3
h4
[Systems that requires more than 16 pipe-end connections or with multiple BC controllers
(with a use of both main and sub controllers)]
BC controller (main)
Indoor unit
Indoor unit
Indoor unit
Indoor unitIndoor unit
BC controller
(sub)
110 m or less
40 m or less
<With more than 16 branching>
(P141~P250 types: 2-line merge)
• Restrictions on piping length
Total piping length (m)
Piping length between main BC controller
and farthest indoor unit (m)
• Height difference and branch piping length between
BC controller and indoor unit. (A)
Distance between heat source unit and
BC controller (m)
Height difference between main BC controller and
farthest indoor unit (m)
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
Junction
pipe
(option)
Branch pipe (for Y-series)
CMY-Y102S-G
H = 50 m or less (outdoor unit above)
H’ = 40 m or less (outdoor unit below)
h1 = 15 m or less
h2 = 15 m or less
Total piping length
A + B + C + a + b + c + d + e + f + g
Piping length
Farthest piping length
Between heat source unit - BC controller
Height difference
Between BC controller and indoor unit
Between indoor unit and BC controller
Between indoor units
Between indoor unit
and heat source unit
Heat source unit above
Heat source unit below
300 m less
A + C + g or A + e
150 m or less
(175 m equivalent length or less)
A110 m or less
e or C + g40 m or less (Note 2)
Between main BC controller and sub BC controller
h315 m or less
H50 m or less
H’40 m or less
h115 m or less (10 m or less) (Note 3)
h215 m or less (10 m or less) (Note 3)
Between indoor (main BC controller) and
indoor (sub BC controller) units
h4
15 m or less (10 m or less)
(Notes 3 and 5)
Indoor unitIndoor unit
ItemPiping sectionsAllowable value
Heat
source
unit
- 40 -
■PQRY-P200,P250YGM-A
Page 44
B
A
D
a
b
c
d
e
400
350
300
250
200
30 40 50 60 70 80 90 100 110
70
60
40
30
50
10
20
0
051015
Note 1: Use the figures in the parentheses if the capacity of the connected indoor units is P200 type or above.
Note 2: Refer to the graph below for restrictions on refrigerant piping length when the total piping length exceeds 300 m.
Note 3: Refer to the graph below for restrictions on refrigerant piping length when the piping length between the BC
controller and the farthest indoor unit exceeds 40 m. (except P250-type indoor units)
Note 4: When indoor units of P200 type or above are connected, neither branch joints nor branch headers can be used.
Note 5: Use optional extension wire for water-source unit to leave a space between the compressor unit and the heat
exchanger.
Note 6: The piping length between the compressor unit and the heat exchanger unit must be 10m or less.
[16 branches or less (the use of only the main BC controller or standard BC controller)]
BC controller
Indoor unit
Indoor unit
Heat
exchanger
unit
(Heat source unit)
Compre-
ssor
unit
Indoor unit
Indoor unitIndoor unit
110 m or less
40 m or less
(P141~P250 types: 2-line merge)
• Restrictions on piping length
Total piping length (m)
Piping length between main BC controller
and farthest indoor unit (m)
• Height difference and branch piping length between
BC controller and indoor unit. (A)
Distance between heat source unit and
BC controller (m)
Height difference between main BC controller and
farthest indoor unit (m)
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
Junction
pipe
(option)
Branch pipe (for Y-series)
CMY-Y102S-G
H = 50 m or less (Compressor unit above)
H’ = 40 m or less (Compressor unit below)
h1 = 15 m or less
h2 = 15 m or less
h3 h3’
Piping lengthHeight difference
Total piping length
Farthest piping length
Between Compressor unit - BC controller
Between BC controller and indoor unit
Between indoor unit and BC controller
Between indoor units
Compressor unit above
Compressor unit below
A + D + e
A + D110 m or less
40 m or less (Note 3)
50 m or less
40 m or less
15 m or less (10 m or less) (Note 1)
15 m or less (10 m or less) (Note 1)
Compressor unit above
Compressor unit below
0 m
10 m or less
300 m or less (Note 2)
150 m or less
(175 m equivalent length or less)
e
Between Compressor unit and Heat exchanger unit
10 m or less (Note 5, Note 6)
D
H
H’
h1
h2
h3
h3’
Piping sectionsAllowable value
Item
A + B + D + a + b + c + d + e
Between Compressor unit
and Heat exchanger unit
Between indoor unit
and Compressor unit
■PQRY-P400,P500YSGM-A
- 41 -
Page 45
B
a
b
c
d
e
400
350
300
250
200
30 40 50 60 70 80 90 100 110
70
60
40
30
50
10
20
0
051015
Note:
A system with more than 16 branching requires 2 to 3 BC controllers (main/sub) and 3 pipes between BC controllers.
Note 1: Refer to the graph below for restrictions on refrigerant piping when the total piping length exceeds 300 m.
Note 2: Refer to the graph below for restrictions on refrigerant piping length when the piping length between the BC controller
and the farthest indoor unit exceeds 40 m. (except P250-type indoor units)
Note 3: Use the figures in the parentheses if the capacity of the connected indoor units is P200 type or above.
Note 4: When indoor units of type P200 or above are connected, neither branch joints nor branch headers can be used.
Note 5: When 2 sub BC controllers are connected, include them in the figures in the table above.
Note 6: When 2 sub BC controllers are connected, connect them in parallel.
Note 7: Use optional extension wire for water-source unit to leave a space between the compressor unit and the heat exchanger.
Note 8: The piping length between the compressor unit and the heat exchanger unit must be 10m or less.
C
Note 6
f
g
h4
h5
A
D
[Systems that requires more than 16 pipe-end connections or with multiple BC controllers
(with a use of both main and sub controllers)]
BC controller (main)
Indoor unit
Indoor unit
Indoor unit
Indoor unitIndoor unit
BC controller
(sub)
40 m or less
<With more than 16 branching>
(P141~P250 types: 2-line merge)
• Restrictions on piping length
Total piping length (m)
Piping length between main BC controller
and farthest indoor unit (m)
• Height difference and branch piping length between BC controller and indoor unit. (A)
Distance between heat source unit and
BC controller (m)
Height difference between main BC controller and
farthest indoor unit (m)
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
Junction
pipe
(option)
Branch pipe (for Y-series)
CMY-Y102S-G
H = 50 m or less (Copressor unit above)
H’ = 40 m or less (Copressor unit below)
h1 = 15 m or less
h2 = 15 m or less
Indoor unitIndoor unit
Heat
exchanger
unit
(Heat source unit)
Compre-
ssor
unit
110 m or less
h3’h3
Piping lengthHeight difference
Total piping length
Farthest piping length
Between Compressor unit - BC controller
Between BC controller and indoor unit
Between indoor unit and BC controller
Between indoor units
Between main BC controller and sub BC controller
Compressor unit above
Compressor unit below
A + C + D + g or A + e
e or C + g
A + D
110 m or less
40 m or less (Note 2)
Between Compressor unit and Heat exchanger unit
D
10 m or less (Note 7, Note 8)
50 m or less
40 m or less
15 m or less (10 m or less) (Note 3)
15 m or less (10 m or less) (Note 3)
15 m or less
15 m or less (10 m or less)
(Note 3 and 5)
Compressor unit above
Compressor unit below
0 m
10 m or less
300 m or less
150 m or less
(175 m equivalent length or less)
H
H’
h1
h2
h3
h3’
h5
h4
Piping sectionsAllowable value
Item
A + B + C + D + a + b + c + d + e + f + g
Between Compressor unit
and Heat exchanger unit
Between indoor unit
and Compressor unit
Between indoor unit (main BC controller) and
indoor unit (sub BC controller)
■PQRY-P400,P500YSGM-A
- 42 -
Page 46
L
H
A
A
BCD
a
b
c
d
h
e
1
5
23 4
1 Line branching system
ItemPiping sectionAllowable value
To tal piping lengthA + B + C + D + a + b + c + d +eLess than 300m
LengthFarthest piping length (L)A + B + C + D + e
Farthest piping length after first branch ( )B + C + D + eLess than 40m
Upper heat source unitHLess than 50m
Height
Indoor
– Heat source
Lower heat source unitH’Less than 40m
difference
Indoor – IndoorhLess than 15m
Note: The total model names downstream in the table below
represent that viewed from A-point in the above figure.
First branch
Indoor
IndoorIndoorIndoor
To downstream unit
Indoor
Less than 150m
L
H
A
a
b
c
d
h
e
f
Heat
source
unit
Heat
source
unit
6
345
1 2
2 Header branching system
Note: The branch piping can not be branched again after header branching.
First branch
Cap
ItemPiping sectionAllowable value
To tal piping lengthA + a + b + c + d + e + fLess than 300m
LengthFarthest piping length (L) A + fLess than 150m
Farthest piping length after first branch ( )fLess than 40m
Height
Upper heat source unitHLess than 50m
Indoor
– Heat source
Lower heat source unitLess than 40m
difference
Indoor – IndoorhLess than 15m
Indoor Indoor
Indoor Indoor Indoor
Indoor
H’
- 43 -
■PQHY-P200,P250YGM-A
Page 47
L
H
A
A
B
C
a
b
c
d
h
e
1
2
345
H
3 Mixed line and header branching system
Note: The total model names downstream in the table below
represent that viewed from A-point in the above figure.
Note: The branch piping can not be branched
again after header branching.
First branch
(Branch joint)
Branch joint
Indoor
Branch header
Cap
To downstream unit
ItemPiping sectionAllowable value
To tal piping lengthA + B + C + a + b + c + d + eLess than 300m
LengthFarthest piping length (L)A + B + bLess than 150m
Farthest piping length after first branch ( )B + bLess than 40m
Upper heat source unitLess than 50m
Height
Indoor
– Heat source
Lower heat source unitLess than 40m
difference
Indoor – IndoorhLess than 15m
IndoorIndoorIndoor
Indoor
H’
Heat
source
unit
- 44 -
Page 48
L
H
A
A
BCD
a
b
c
d
h
e
1
5
23 4
1 Line branching system
ItemPiping sectionAllowable value
To tal piping length
A + B + C + D + E + a + b + c + d +e
Less than 300m
LengthFarthest piping length (L)A + B + C + D + E + e
Farthest piping length after first branch ( )B + C + D + eLess than 40m
Upper Compressor unitHLess than 50m
Height
Indoor
– Compressor unit
Lower Compressor unitH’Less than 40m
difference
Indoor – IndoorhLess than 15m
Upper Compressor unith2Less than 0m
Compressor unit
–
Heat exchanger unit
Lower Compressor unith2’Less than 10m
Upper Compressor unith2Less than 0m
Compressor unit
–
Heat exchanger unit
Lower Compressor unith2’Less than 15m
Note: The total model names downstream in the table below
represent that viewed from A-point in the above figure.
First branch
Indoor
IndoorIndoorIndoor
To downstream unit
Indoor
Less than 150m
L
H
A
a
b
c
d
h
e
f
E
E
Heat
exchanger
unit
(Heat source unit)
Compre-
ssor
unit
h2
Heat
exchanger
unit
(Heat source unit)
Compre-
ssor
unit
h2
6
345
1 2
2 Header branching system
Note: The branch piping can not be branched again after
header branching.
First branch
Cap
ItemPiping sectionAllowable value
To tal piping lengthA + a + b + c + d + e + fLess than 300m
LengthFarthest piping length (L) A + fLess than 150m
Farthest piping length after first branch ( )fLess than 40m
Height
Upper Compressor unitHLess than 50m
Indoor
– Compressor unit
Lower Compressor unitLess than 40m
difference
Indoor – IndoorhLess than 15m
Indoor Indoor
Indoor Indoor Indoor
Indoor
H’
- 45 -
■PQHY-P400,P500YSGM-A
Page 49
L
H
A
A
B
C
a
b
c
d
h
e
Upper Compressor unith2Less than 0m
Compressor unit
–
Heat exchanger unit
Lower Compressor unith2’Less than 15m
1
2
345
H
3 Mixed line and header branching system
Note: The total model names downstream in the table below
represent that viewed from A-point in the above figure.
Note: The branch piping can not be branched
again after header branching.
First branch
(Branch joint)
Branch joint
Indoor
Branch header
Cap
To downstream unit
ItemPiping sectionAllowable value
To tal piping lengthA + B + C + a + b + c + d + eLess than 300m
LengthFarthest piping length (L)A + B + bLess than 150m
Farthest piping length after first branch ( )B + bLess than 40m
Upper Compressor unitLess than 50m
Height
Indoor
– Compressor unit
Lower Compressor unitLess than 40m
difference
Indoor – IndoorhLess than 15m
IndoorIndoorIndoor
Indoor
H’
E
Heat
exchanger
unit
(Heat source unit)
Compre-
ssor
unit
h2
- 46 -
Page 50
Note 1: Heat source units and BC controllers are supplied with flanges with a short copper pipe as a part used to
connect to the low pressure pipe.
✻ When 2 sub controllers are connected, determine the pipe size on the main side based
on the total capacity of the indoor units that are connected to the 2 sub controllers, and
determine the pipe size on the sub controller side based on the total capacity of the
units that are connected.
Note 2: Use pipes that are specified in the section “Read Before Servicing: [3] Piping Materials.”
1Between heat source unit and BC controller (Part A)
2Between BC controller and indoor unit (Parts a, b, c, d, and e)
3Between main BC controller and sub BC controller (Part C)
4Compressor unit and Heat exchanger unit (Part D)
Item
Refrigerant piping
size
High pressure
pipe
Low pressure
pipe
High pressure
pipe
Low pressure
pipe
Heat source unit
ø 28.58 (Brazed)ø 22.2 (Brazed)ø 19.05 (Brazed)
ø 22.2 (Brazed)ø 19.05 (Brazed)ø 15.88 (Brazed)
ø 28.58ø 22.2ø 19.05
ø 22.2ø 19.05ø 15.88
PQRY-P500
YSGM-A
PQRY-P400
YSGM-A
PQRY-P250
YGM-A
PQRY-P200
YGM-A
End connection
of heat source unit
and BC controller
Item
Refrigerant piping
size
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Indoor unit
ø 22.2ø 15.88ø 12.7
ø 9.52ø 6.35
ø 22.2ø 15.88
ø 19.05
ø 19.05ø 12.7
ø 9.52ø 6.35
250200
63, 71, 80, 100
125, 140
20, 25, 32
40, 50
End connection
of indoor unit
(Flare connection
for all unit types)
Item
Refrigerant piping
size
(Use brazing for
all units.)
Low-pressure
Liquid pipe
Liquid pipe
High-pressure
Gas pipe
Indoor unit
ø 28.58ø 19.05ø 22.2
ø 19.05ø 15.88
ø 12.7ø 9.52
P301~P350P201~P300~P200
Refrigerant pipe
size
Heat source unit
Bypass pipe
Low-pressure
pipe
High-pressure
pipe
ø 28.58
ø 19.05
ø 9.52
PQRY-P500
YSGM-A
PQRY-P400
YSGM-A
PQRY-P250
YGM-A
PQRY-P200
YGM-A
- 47 -
2. Refrigerant piping size
<PQRY>
Page 51
A(mm)
B, C, D(mm)
a, b, c, d, e(mm)
Downstream unit model total
The 1st branch of P450 ~ P650
Branch kit model
CMY-Y102S-G
CMY-Y102L-G
CMY-Y202-G
Outdoor model
P200
P250
Liquid pipe
ø9.52
*1 ø9.52
Gas pipe
ø19.05
P400ø12.7ø28.58
P500ø15.88ø28.58
ø22.2
Total cap aci ty of indoor units
~ 140
141 ~ 200
201 ~ 300
301 ~ 400
401 ~ 650
Liquid pipe
ø9.52
ø9.52
ø9.52
ø12.7
ø15.88
Gas pipe
ø15.88
ø19.05
ø22.2
ø28.58
ø28.58
Model number
20,25,32,40,50
63,71,80,100,125,140
200
250
Liquid pipe
ø6.35
ø9.52
ø9.52
ø9.52
Gas pipe
ø12.7
ø15.88
ø19.05
ø22.2
4-Branching header
(Downstream unit
model total 200)
CMY-Y104-G
8-Branching header
(Downstream unit
model total 400)
CMY-Y108-G
10-Branching header
Downstream unit
model total 650)
CMY-Y1010-G
*1 ø12.7 for over 90m
~ 200
201 ~ 400
401 ~ 650
- 48 -
<PQHY>
Page 52
1 Total capacity of connectable indoor units: P140 or below (P250 or below when a junction pipe is used)
2 The number of connectable indoor units: 3 max.
3 Branch pipe: Use Type CMY-Y102S-G (option)
4 Selection of refrigerant piping (pipe size of the A and B in the figure above): Use the total capacity of the
downstream indoor units to determine the proper pipe size, using the table below as a reference.
Use an optional junction pipe kit and merge the 2
joints
Use the reducer that is supplied with the BC
controller
(1) BC controller (standard model) end connection piping size
[P200,P250 types]
Note: Use the flare nut provided with the BC controller
Liquid pipe side: 3/8F
(flare)
Gas pipe side: 5/8F
(flare)
Liquid pipe side: 3/8F
(flare)
Gas pipe side: 5/8F
(flare)
Provided with a thermal
insulation cover
Liquid pipe side:
ø 6.35 ID
Gas pipe side:
ø 12.7 ID
Liquid pipe side:
ø 9.52 ID
Gas pipe side:
ø 19.05 ID
(ø 22.2 with reducer)
Total capacity of the indoor units
P140 or belowø 15.88ø 9.52
P141~P200ø 19.05ø 9.52
P201~P250
(❈) With reducer
ø 22.2 (❈)ø 9.52
Gas pipeLiquid pipe
To heat source unit
✻1
Reduce
(supplied)
✻1: To connect P20-P50 type indoor units
✻3: To connect multiple indoor units to a branch joint (or to a junction pipe)
✻2: To connect P200 or P250 type indoor units
(or when the total capacity of the indoor units
exceeds P141)
The size of the branch end connection on the BC controller is designed to fit P50-P140 type indoor units.
To connect other types of indoor units, perform the following procedures.
✻2
Junction
pipe kit
(Type: CMYR160-J)
(option)
Branch pipe
(Type: CMY-Y102S-G)(option)
✻3
Maximum of 3 units per branch joint
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
End connection:
brazed connection
BC controller
Item
Heat
source
unit side
Indoor unit side
High-pressure side
(liquid side)
Low-pressure side
(gas side)
Piping sections
ø 15.88
(Brazed)
ø 19.05
(Brazed)
ø 22.2
(Brazed)
ø 19.05
(Brazed)
ø 9.52
(Flare)
ø 15.88
(Flare)
✻ BC controllers (standard model) can only be connected to P200,P250
heat source units.
PQRY-P200YGM-A
PQRY-P250YGM-A
70
234
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unitIndoor unit
P50 type
or below
P63-P140
types
P200-P250
types
BA
- 49 -
3. Connecting the BC controllers
<PQRY>
Page 53
The size of the branch end connection on the BC controller is designed to fit P63-P140 type indoor units.
To connect other types of indoor units, perform the following procedures.
✻1: To connect P20-P50 type indoor units, use the reducer that is supplied with the BC controller
✻2: To connect P200 or P250 type indoor units (or when the total capacity of the indoor units exceeds P141),
use an optional junction pipe kit (Type: CMY-R160-J) and merge the 2 joints.
✻3: To connect multiple indoor units to a branch joint (or to a junction pipe)
• Total capacity of connectable indoor units : P140 or below (P250 or below when a junction pipe is used)
• The number of connectable indoor units
: 3 max.
• Selection of refrigerant piping (pipe size of the A and B in the figure above)
: Use the total capacity of the downstream indoor units to determine the proper pipe size, using the
table below as a reference.
(2) BC controller (main) end connection piping size
Total capacity of the indoor units
P140 or belowø 15.88ø 9.52
P141~P200ø 19.05ø 9.52
P201~P250
(❈) With reducer
ø 22.2 (❈)ø 9.52
Gas pipeLiquid pipe
To heat source unit
✻1
Reducer
(supplied)
✻2
Junction pipe kit
(Type: CMY-R160-J)
(option)
Branch pipe (Type: CMY-Y102S-G)
(For CITY MULTI Y series, option)
Maximum of 3 units per branch joint.
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
End connection:
brazed connection
Main BC controller
Item
High-pressure side
(liquid side)
Low-pressure side
(gas side)
Piping sections
ø 19.05
(Brazed)
ø 22.2
(Brazed)
ø 28.58
(Brazed)
ø 15.88
(Brazed)
ø 19.05
(Brazed)
ø 22.2
(Brazed)
ø 9.52
(Flare)
ø 15.88
(Flare)
PQRY-P250YGM-A
PQRY-P200YGM-A
PQRY-P400YSGM-A
PQRY-P500YSGM-A
Heat
source
unit side
Indoor unit side
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unitIndoor unit
P50 type
or below
P63-P140
types
P200-P250
types
BA
- 50 -
Page 54
The size of the branch end connection on the BC controller is designed to fit P63-P140 type indoor units.
To connect other types of indoor units, perform the following procedures.
✻1: To connect P20-P50 type indoor units, use the reducer that is supplied with the BC controller
✻2: To connect P200 or P250 type indoor units (or when the total capacity of the indoor units exceeds P141),
use an optional junction pipe kit (Type: CMY-R160-J) and merge the 2 joints.
✻3: To connect multiple indoor units to a branch joint (or to a junction pipe)
• Total capacity of connectable indoor units : P140 or below (P250 or below when a junction pipe is used)
• The number of connectable indoor units : 3 max.
• Selection of refrigerant piping (pipe size of the A and B in the figure above) :
Use the total capacity of the downstream indoor units to determine the proper pipe size, using the
table below as a reference.
(3) BC controller (sub) end connection piping size
Total capacity of the indoor units
P140 or belowø 15.88ø 9.52
P141~P200ø 19.05ø 9.52
P201~P250
(❈) With reducer
ø 22.2 (❈)ø 9.52
Gas pipeLiquid pipe
Main BC controller
✻1
Reducer
(supplied)
✻2
Junction pipe kit
(Type: CMY-R160-J)
(option)
Branch pipe (Type: CMY-Y102S-G)
(For CITY MULTI Y series, option)
Maximum of 3 units per branch joint.
Total capacity of P140 or less
(All units connected to the same
branch joint must be in the same mode.)
End connection:
brazed connection
Sub BC controller
Item
BC
controller
side
High-pressure side
(liquid side)
Low-pressure side
(gas side)
Piping sections
ø 19.05
(Brazed)
ø 15.88
(Brazed)
ø 22.2
(Brazed)
ø 19.05
(Brazed)
ø 28.58
(Brazed)
Liquid side
ø 9.52
(Brazed)
ø 12.7
(Brazed)
Total capacity of indoor units
connected to applicable BC controller
P200 type and below
P201-P300 types
P301 types and above
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unitIndoor unit
P50 type
or below
P63-P140
types
P200-P250
types
BA
- 51 -
Page 55
4-way valve
Accumulator
Compressor
Solenoid valve block
Check valve block
Heat exchanger
Sub box
Control box
Solenoid
valve
(SV7a~7c)
- 52 -
££
Components of the Heat source Unit
[1] Appearance of the Components and Refrigerant Circuit
< PQRY-P200, P250 >
Page 56
4-way valve
Accumulator
Compressor
Solenoid valve block
Check valve block
Heat exchanger
Sub box
Control box
Subcool coil
< PQHY-P200, P250 >
- 53 -
Page 57
Accumulator
Sub box
Control box
Compressor
Relay cable connector
(Compressor unit Heat exchanger unit)
Relay cable connector
(Compressor unit Heat exchanger unit)
- 55 -
< PQRY-P400, P500 (Heat exchanger unit) >
Page 59
- 56 -
Solenoid valve
(SV7a~7c)
Subcool coil
4-way valve
Check valve block 2
Check valve block 1
Solenoid valve block 2
Solenoid valve block 1
Heat exchanger
Relay cable connector
(Compressor unit Heat exchanger unit)
< PQHY-P400, P500 (Heat exchanger unit) >
Page 60
- 57 -
Power supply terminal
block (TB1)
Main board
Tr ansmission line
terminal block
for centralized control
(TB7)
Indoor/outdoor
transmission
terminal block
(TB3)
INV board
Choke coil
(L1, L2)
Filter board
DCL (back)
Noise filter
Tr ansmission line
terminal block
for centralized control
(TB7)
Indoor/outdoor
transmission terminal block
(TB3)
Rush current
protection resistor
(R11, R12)
Electromagnetic contactor
(52C1)
Smoothing capacitor
(C11, C12)
Gate amp board
(G/A board)
Diode stack (DS)
Power supply
terminal block
(TB1)
ACCT-U ACCT-WIPM DCCT
[2] Control Box
[ Appearance ]
[ Under the circuit board cover ]
Page 61
Pump interlock input
Operation-ON signal output terminal block
(TB8)
Relay board
- 58 -
[ Sub box ]
Page 62
- 59 -
CNVCC1
Controlled
source input
1–2
DC30V
1–3
DC30V
4–5
DC7V
4–6
DC12V
7–8
DC7V
CNRS3BLD2
CNAC3
Power output
3
L1
1
L2
CN20
Power input
5
L1
CN21
Power input
3
L2
1
N
LD1
Service LED
SW5SW4 SW3SW2SWU2SWU1 SW1
CNLVB
CNLVC
CN3S
CN63PW
CN3D
CN3N
CNRS3ACNS1 CNS2 CN40CN41
CNRT1
CNOUT1
CN52C
Control for
52C1
CN51
3–4
Compressor
ON/OFF
3–5
Trouble
CN38
[3] Circuit Board
1. Main board
Page 63
- 60 -
CNVCC1
Power supply
1–2
DC30V
1–3
DC30V
4–5
DC7V
4–6
DC12V
7–8
DC7V
CN15V2
Power supply
for IPM control
F02CNVDC
SW1
SW2
CN52C
CNFANCNRS1CNRS2
Serial
transmission
for MAIN board
CNCT2
CNAC2
Power input
5
L2
3
N
1
G
CNTH
CNCT
CNDR2
2. INV board
Page 64
- 61 -
CNFGCNL2CNL1
CNOUT
Controlled
source output
CNIN
Controlled
source input
3. Filter board
CNDR1
CN15V1
CNDC1CNDC2
CNIPM1
4. G/A board
Page 65
CN81
Solenoid valve output
for unit control (200V)
CNAC4
Power input
4
R-phase
1
S-phase
CN83
1
-
3
5
-
7
CNPW
1 - 2 Pump interlock signal output
to main circuit board
CNOUT2
Relay drive input from
main circuit board
Operation-ON signal output
Pump interlock input
- 62 -
5. Relay board (Heat source unit)
Page 66
- 63 -
Gas pipe
(indoor unit side)
Liquid pipe
(indoor unit side)
LEV3
SVM2
PS1
PS3
LEV2
TH11
LEV1
LEV2PS3SVM1
PS1
LEV1LEV3
TH15
TH16TH12
TH11
SVM2
SVM1
High-pressure side (Heat source unit side)
✻ No SVM2 on G type
[4] BC controller (inside the panel)
< CMB-PV-G(A) >
[ Front (CMB-P1016V-G(A) is shown in the picture) ]
< CMB-P1016V-G >
Page 67
- 64 -
Gas-liquid separator
Tube-in-tube heat exchanger
Gas-liquid separator
Tube-in-tube heat exchanger
[ Rear view (CMB-P1016V-G(A) is shown in the picture) ]
< CMB-P1016V-G >
< CMB-P1016V-GA >
Page 68
- 65 -
LEV3aTH25
TH22
< CMB-PV-GB>
[ Front view (CMB-P104V-GB is shown in the picture) ]
[ Rear view (CMB-P104V-GB is shown in the picture) ]
Page 69
- 66 -
BC controller board
Relay board
Te r minal block
for power supply
Te r minal block
for transmission
Tr ansformer
SW1SW2
SW4
SW5
[5] BC control box
[ BC controller control box (CMB-P1016V-GA is shown in the picture) ]
[6] BC controller board
[ BC controller board ]
Page 70
- 67 -
[ Relay board (RELAY 4 board) ]
[ Relay board (RELAY 10 board) ]
Page 71
- 68 -
Function/specification
Remote controller address setting
Not requiredRequired
Indoor/outdoor unit address
setting
Not required (required only by a system
with one outdoor unit)(Note 3)
Required
Wiring methodNon-polar 2 wires
✻
Daisy-chain the indoor units with non-polar
2 wires when running a group operation.
Non-polar 2 wires
Installation location of
remote controller
Connectable to any indoor unit in the
group
Connectible at any point on the
indoor/outdoor transmission line
Interlocking with the
ventilation unit
Each indoor unit can individually be
interlocked with a ventilation unit.
(Registered on the remote controller in
the same group)
Each indoor unit can individually be
interlocked with a ventilation unit.
(Registered on the remote controller)
Making group changes
(Note 1) MA remote controller includes MA remote controllers, MA compact remote controllers, and wireless remote controllers.
(Note 2) M-NET remote controller includes ME remote controllers and compact remote controllers.
(Note 3) Depending on the system configuration, even a single refrigerant system may require an address setting.
(Note 4) Either an MA remote controller or an M-NET remote controller can be connected to a group of multiple-refrigerant systems
or when a system controller is connected.
(Note 1) M-NET remote controllers and MA remote controllers cannot both be connected to the same group of indoor units.
(Note 2) A system controller must be connected to a system that has both MA remote controllers and M-NET remote controllers.
MA remote controller wires between
indoor units require rewiring.
Indoor unit and remote controller
addresses must be changed, or the
registration information must be changed
using MELANS.
< A system using an MA remote controller >< System using an M-NET remote controller >
• Low chances of system expansion and grouping
changes are expected.
• Grouping (floor plan) has been decided at the
time of installation.
• High chances of centralized installation of remote
controllers, system expansion, and grouping changes.
• Grouping (floor plan) has not been decided at the
time of installation.
• Direct connection of the remote controller to the
Lossnay inside the heater-humidifier.
M-NET (ME) remote controller (Notes 1, 2)
MA remote controller
Outdoor unit
Indoor unitM-NET remote controller
Outdoor unit
Indoor unit
M-NET transmission line
(indoor/outdoor transmission line)
M-NET transmission line
(indoor/outdoor transmission line)
GroupGroupGroupGroup
¢¢
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected
on the indoor/outdoor transmission line, and MA remote controller, which is connected to
each indoor unit.
1. Comparison of Functions and Specifications of MA and ME Remote Controllers
2. Selecting the Best Type of Remote Controller
Select either the MA remote controller or the M-NET remote controller to take full advantage of a given system.
The following information is provided as a reference for selection.
Page 72
- 69 -
>
y]
door u
address
w
address
w
/
g
g
.
g
n
]
gs
:
g
bu
s
]
s
.
A
Select the unit address.
3
[SET TEMP. ( ) or ( )] to advance or go back
C
r
.
r
e
5
>
)
)
steps and above.
go to section (2) Address Search.
go to section (2) Address Search.
.
Press again to go back to the Group Setting window as shown
under step .
6
G
Both the indoor unit address and
interlocked unit address will be
.
y.
g
button [SET TEMP. ( ) or ( )] to advance or go back through
y
8
C
OSS
u
s.
- Press button [TEST] while both the indoor unit address and
OSS
d
g.
y
.
y)
y
pp
y.
y.
(
d
address does no
a
)
;
p
.
[
Blinking display of HO ]
G
C
TIMER SET
ON/O
CHECKTEST
CLOCK
ON
[2] Group Setting and Interlocking Settings that are Made on an ME Remote Controller
1. Group setting/interlocking setting
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the
outdoor unit address.
indoor
(A) Group settin
and search and deletion of re
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of re
[Operation Procedures
(1) Address settin
s...........Registration of the indoor units to be controlled with the remote controller,
istered information
istered informatio
Bring up either one of the following displays on the remote controller
normal display, which appears when the unit is stopped. The display window must
look like one of the two fi
ures below to proceed to the next step.
[Normal displa
(B) Interlock Settings(A) Group Settings
tton
hown below
Indoor unit address display window
nit
In
display windo
Bring up the address of the indoor unit and the address of the
LOSSNAY to be interlocked on the displa
- Select the address of the indoor unit to be registered by pressin
display.
- Select the address of the LOSSNAY unit to be interlocked b
- If registration is successfully completed, unit type will appea
on the display as shown in the figure below
- If the selected address does not have a corresponding indoo
unit, an error message will appear on the display. Check th
address, and try again.
Interlocked unit
display windo
FF
window
displayed together
To search for an address,
<Successful completion of registration
Unit type (Indoor unit in this case
<Deletion error
corresponding unit.
To register the addresses for multiple indoor units, repeat
To search for an address,
Make the settings to interlock L
NAY units with indoor
nit
the address of the L
NAY units to be interlocke
are displayed to enter the interlock settin
LOSSNAY address in the indoor unit address displa
address display window
If registration is successfully
completed, the two displa
shown on the left will a
alternatel
(Displayed alternatel
will blink on the displa
Indicates that the selecte
corresponding unit.
NOTE : Interlock all the indoor units in the group with the
LOSSNAY units
not o
erate
otherwise, the LOSSNAY units will
s as
ear
t have
Page 73
- 70 -
>
d>
(C) To return to the normal displa
y
(2)
h
searc
address o
door u
been entered
o
the remote controller, follow steps and .
gs
e
(
)
s
e
.
[
.
section (3) Address Deletion.
y)
,
go to section (3) Address Deletion .
y.
(The display method is the same as the one in step .)
ess
ed
OSS
t
ess
er
t
OSS
y
y.
y
.
h
proceed as follows:
y.
g
button [TIMER SET ( ) or ( )] to advance or go back
.
,
go to section (2) Address Search.
(3)
n
.
.
Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the
g
.
g.
y)
Bring up the Group Setting window.
- Each pressing of button [TIMER ] will bring up the address of a
.
When all the group settings and interlock settings are made, take the
Address searc
To
h for the
f in
nits that have
To search for an address
int
(A) To search group settin
registered indoor unit and its unit type on the display
<Entry found
Unit typ
Indoor unit in this case
<No entries foun
- When only one unit address is registered, the same addres
will remain on the display regardless of how many times th
button is pressed
To delete an address, go to
TIMER ]
(B) Interlock setting searc
the displa
- Select the address of the indoor unit to be searched by pressin
through the interlocked addresses
LOSSNAY can be searched in the same manner by bringing up
the LOSSNAY address in the Interlocked unit address displa
L
NAY and indoor unit that is interlocked with it will be
displa
ed alternatel
Addr
L
of an interlock
NAY uni
(Displayed alternatel
Bring up the address of another registered unit on the
displa
window
unit.
To go back to the normal display,
Addr
of anoth
interlocked uni
(Displayed alternatel
To delete an address
Address deletio
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings
The interlock settings between units can be deleted by deleting the interlock settings
display window. To delete an address, the address must first be bought up on the display.
Delete the re
istered indoor unit address or the interlock setting between units
display to delete the interlock settin
Page 74
- 71 -
(A) To delete group settin
gs
gs
>
.
e
p
.
y)
>
.
r
.
.
gs
y
r
gs
s
Y
y
will appear in
p
.
2. Remote controller functions selection via the ME remote controller
The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode.
.
.
E
y]
seconds.
n
n
)
e
.
g
m
temperature. In this case, AUTO COOL or AUTO HEAT will appear on the remote controller display.
This setting can be changed so that only AUTO will appear on the display.
pypygp)
ed.
ude A
ed.
controller function selection modes
g
)Oper
e
a
r
)
e
ST
T
CLOCKONOFF
(B) To delete interlock settin
<Successful completion of deletion
will be displayed in the room temperature display window
(Displayed alternatel
- If a transmission error occurs, the selected setting will not b
deleted, and the display will appear as shown below.
In this case, re
eat the steps above
<Deletion error
will be displayed in the room temperature display window
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controlle
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller
et the address as shown below
(A) To make group settin
Interlocked unit address display window...Remote controller address
Indoor unit address displa
window...........The address of the indoor unit to be controlled with the remote controlle
(B) To make interlock settin
Interlocked unit address display window...LOSSNAY addres
Indoor unit address display window..........The address of the indoor unit to be interlocked with the LOSSNA
If deletion is successfull
completed,
window. In this case, repeat the
ste
s above
In the remote controller function selection mode, the settings for three types of functions can be made or changed as necessary.
When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the roo
2) Room temperature display selection mode (Display or non-display of room temperature
Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on th
remote controller
By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved
NOT
On the PAR-F27MEA-F model, automatic operation mode cannot be selected while the unit is in the narrowed preset temperature range mode
Only the lower limit can be set for cooling/dry mode, and upper limit for heating mode.
TIMER SE
N/OFF
HECKTE
mode settin
*
ange limit mode (AO
selection mod
mode displ
Set temperature range limit mode (cool/d
ange limit mode (Heat
[Normal displa
for two
*
Skip A mode select
*
Incl
mode select
butto
butto
Room temperature displa selection mod
Page 75
- 72 -
OST
CK
[Operation Procedures
]
y).
de.
Press button [TIMER SET ( ) or ( )] in this
)
)
e
.
pressing and holding buttons [CHECK] and [MODE] simultaneously for 2 seconds.
D
UN
OST
D
UN
E
OST
E
OST
E
E
UN
OST
OR
E
OST
n
.
e.
)
A
A
F
lights
displa
s
ed.
ude A
ed.
A
ed.
ab
.
A
r
e
)
r
28
)
:
)
o
)
7
1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal
displa
under the remote controller function selection mo
Skip
mode setting (when you want to skip
F
or (] bttons are pressed in this state the
witch
[Time selection ( or (] btto
Skip
mode select
When
Incl
mode select
mode can be selected using the mode selection btton
utton and automatic opertion is not possibl
utton, A mode is skipped.
ENTRALLY CONTROLLE
DEFR
TEST R
ENTRALLY CONTROLLE
TAND BY
DEFR
NOT AVAILABL
TEST R
Room temperature display selection mode (Display or non-display of room temperature
INSID
TAND BY
DEFR
TAND BY
DEFR
INSID
HECK MOD
TEST R
Narrowed preset temperature range mode (The range of preset temperature can be changed.
1)Temperature range setting for the cooling/dry mod
i
TAND BY
DEFR
HE
TAND BY
DEFR
range for the heating operation
il
mode temper
Lower limit tempe
[Upper limit temperature adjustment range]
*
Mid temper
ture indoor units ha a loer limit temperature of 1
Medium temperature range indoor unit
ENSA
INSID
Medium temperature range indoor unit
mode opertion
ange fr
ture
tur
and []
.
(*2
(Can be adjusted as l
er limit temperture.
Page 76
- 73 -
]
OSS
OSS
>
.
.
.
g
.
.
The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
r
.
searc
.
.
[3] Interlocking Setting via the MA Remote Controller
1. Lossnay interlocking setting (Make this setting only when necessary)
Make this setting only when necessary
*When an upper controller is connected, make the settings on the upper controller
NOTE : To perform an interlocked operation with LOSSNAY units, interlock all the indoor units in the group with the LOSSNAY units
Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to
search and delete re
In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30
[Operation Procedures
istered information
<Indoor unit address and indoor unit> <L
articular LOSSNAY unit
Go to step. Deletion Procedures to delete any LOSSNAY settings
- Registration erro
NAY address and L
NAY
2. Search Procedures to
h for a
Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit
Page 77
- 74 -
door u
address>
< 2. Search Procedures
>
The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
a
.
If the deletion fails
<In
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller
t is connected to the indoor unit
th
nit
2. Search Procedures. ), and bring up the result of the search for both the
Page 78
- 75 -
2. Remote controller function selection via the MA remote controller
1
)
2
b
[4]-1
gy
gy
de
gy
n
pped)
n
ock
b
.
b
.Press
e
.
ess
e
b
.
b
tton.
b
.
)
)
)
)
)
)
)
)
)
)
b
.
ess
e
b
.
ess
e
b
.
ess
e
btton.
b
.
ess
e
b
.
E
.
CK
R
ST
F
y
guage.
h
n
.
.
]
[1] Stop the air conditioner to start the remote controller function selection mode. [2] Select from category 1. [3] Select from category 2.
[4] Make the setting. [5] Setting completed [6] Go back to the normal display (Finish)
n
ck
n
)
)
yg
)
.
t
e
)
b
g
.
n
e
.
r
ode
)
p
y.
)
g
.
)
/SUB
)
g (
)
1) Remote controller functio
The settings for the following remote controller functions can be changed in the remote controller function selection mode
Change the settings as necessary
Category
1.Language selectio
2.Function lo
.Mode selectio
4.Display mode
1
2
3
Function selection flowchart
Category
MENUN/OF
Multi-language display is supported
Sets the type of locking to put into effec
Enables or disables automatic operation mod
Sets the adjustable temperature range (maximum, minimum
ets the remote controller as main or su
*
When two remote controllers are connected to the same
Enables or disables clock functio
Sets the timer typ
Contact number can be set to appear in case of error
Sets the telephone numbe
tomatic m
Category 3 (Setting content
Dot displa
Messages are displayed in the
selected lan
All examples in this manual are
iven in Englis
N/OFF
HE
TE
LEA
roup, one controller must be set as sub
Normal display (Display that appears
when the air condition is sto
for two seconds.
*The display cannot be changed during function selection,
test run, and self-dia
Language selectio
tton
Function l
tton.
Pr
th
tton
Mode selectio
Display mode
tton
th
btton
tton
button simultaneously for two seconds.
*The settings that are made according to
this
rocedure are stored in the remote
Pr
th
controller memor
nosis
Remote controller function
lection mo
Remote controller main/sub setting (NTROLLER MAIN
Pr
th
Suction air temperature display settin
tton
tton
See
See [4]-2. (1
tton
See [4]-2. (2
See [4]-2. (3
Pr
th
tton
See [4]-3. (1
See [4]-3. (2
See [4]-3. (3
See [4]-3. (4
Pr
th
tton
See [4]-4. (1
See [4]-4. (2
See [4]-4. (3
NOT
Timer operation stops when the display is changed from remote controller function selection to normal display
Page 79
- 76 -
[4] Switching to the built-in Thermo on the remote controller
1. Selecting the position of temperature detection by the indoor unit
(Factory setting: SW1-1 “OFF” )
To use the built-in sensor in the remote controller, set the SW1-1 on the indoor unit to ON.
✻ Some remote controllers are not equipped with a built-in sensor. Use the built-in sensor on the indoor unit
instead.
✻ When using the built-in sensor on the remote controller, install the remote controller where room tempera-
ture can be detected.
n
ON
.
.
e
.
[Setting details
]
n
g
g.
g
)
o1
ed.
.
.
c
.
p
.
F
p
.
ge.
COO
:
.
.
.
.
g
g
.
.
ge
9
pp
)
g
:
d
ed
:
.
:
sabled.
:
sabled.
g
r
.
y
.
s
.
n
C
g)
F: Temperature is displayed in F.
g
n
g
.
.
yed.
g
[4] -1. Language selectio
The language that appears on the dot display can be selected from amon
the followin
(1) Function lock settin
n
no2All buttons are lock
OFF (Initial setting): No buttons are locked
* To enable locking from the normal display, press and hold the
on the normal display after the above setting is made
(2) Automatic mode display selectio
When the remote controller is connected to a unit with an automati
operation mode, the following settings can be made
Automatic mode is displayed when the
o
F
After this setting is made, the temperature can be changed within the set
ran
LIMIT TEMP
The temperature range for the cooling/dry mode can be changed
The temperature range for the heating mode can be changed
L MODE
eration mode is selected
: Automatic mode is not displayed when the
eration mode is selected
o
4] -3. Mode selectio
(1) Remote controller main/sub settin
Main:Designates the controller as the main controller
Sub:Designates the controller as the sub controller
lock function is enabled
OFFlock function is disabled
(3) Timer function settin
(Select one of the following.
WEEKLY TIMER (Initial setting)
AUTO OFF TIMER
IMPLE TIMER
TIMER MODE OFF
i
(4) Technical assistance contact number settin
CALL OFF: The set contact numbers are not displayed in an erro
situation
CALL**** *** ****: The set contact numbers are displayed in an
CALL_: Contact numbers can be entered when the displa
appears as shown on the left
Setting the contact number
To set the contact numbers, follow the following procedures
Auto off timer function is enabl
Simple timer function is enabled
Timer function is di
rror situation
Weekly timer function is enable
The temperature range for the automatic mode can be changed
OFF (Initial setting): The temperature range is not set
When any setting other than OFF is selected, the temperature range
for cooling, heating, and automatic mode is also made. The range
settin
will not take effect if the temperature range has not been set
settin
tton
To switch between the upper limit setting and the lower limit setting, press
Settable ran
Heating mode
Automatic mode Lower limit: 1
U
Mr. Slim units, Free-plan units, and medium temperature range units
er limit: 28 ~ 19
[4] -4. Display mode change
1) Temperature unit selectio
(Initial settin
(2) Suction air temperature display settin
ON: Suction air temperature is displayed.
OFF: Suction air temperature is not displa
(3) Automatic cooling/heating display settin
Page 80
- 77 -
∞∞
Electrical Wiring Diagram
[1] PQRY,PQHY-P200, P250YGM-A, P400, P500YSGM-A
✻1
+
-
~
~
~
+
+
“ ✻5 ” is on the Heat exchanger unit side for P400/500 type.
✻1
✻4
✻2
✻2
✻2
✻3
HEATCOOL
Auto change over:ON
Auto change over:OFF
CN3N 1-3P
CN3N 1-2P
SHORT
OPEN
OPENSHORT
✻5
✻5
✻5
✻4.Auto change over(CN3N 1-2P,1-3P):PQHY only
✻2
✻1
✻2✻2
trouble signal
water freeze signalON
OFF
SW3-3 CN51 3-5P
Bypass outlet temp.detect
at sub-coolcoil
TH8
✻3,✻5
LEV2
Electronic expansion valve
(Heat exchanger for inverter)
PQHY-P400/P500YSGM-A
PQHY-P200/P250YGM-A
✻3
:exist X:not exist
Freeze prevention sensor
TH9
Liquid outlet temp.detect
at sub-coolcoil
TH7
Pipe temp.detect
TH5
✻3
✻1.Function according to switch operation.
(SW4-7:CN3D 1-2P,and CN3D 1-3P,
SW3-3:CN51 3-5P)
✻2Model name
Z20
63LS
63HS
LEV1
Electronic expansion valve
(Sub-cool coil bypass)
Solenoid valve
(Heat exchanger capacity control)
SV7a,b,c
Solenoid valve
(Heat exchanger capacity control)
SV5a,b
<Symbol explanation>
SymbolName
AC Current SensorACCT
DC Current Sensor
DC reactor
(Power factor improvement)
Magnetic contactor
(Inverter main circuit)
Fan motor (Radiator panel)
Case heater(Compressor)
4-way valve
Solenoid valve
(Discharge-suction bypass)
Solenoid valve
(Heat exchanger capacity control)
Thermistor
Discharge pipe temp. detect
Outlet temp.detect of
heat exchanger for inverter.
Radiator panel temp. detect
High pressure switch
High pressure sensor
Low pressure sensor
Choke coil(Transmission)
Function device
Earth terminal
MF1
CH11
21S4a
SV4a,b,c,d
TH11
TH6
L1,L2
Water temp.detect
L1,L2
DCL
DCCT
63H
52C
THHS1
THINV
SV1
PQRY-P400/P500YSGM-A
<Difference of appliance>
PQRY-P200/P250YGM-A
NOTE:The broken lines indicate field wiring.
Compressor
ON/OFF
SHORTOPEN
OPEN
SHORT
CN3D 1-2P
CN3D 1-3P
100%
0%
75%
50%
CN3D
1-3P
OPEN
SHORTSHORT
OPEN
CN3D
1-2P
NIGHT
MODE
OFF
ON
SW4-7:ON (STEP DEMAND)
OFF
ON
SW4-7:OFF (Compressor ON/OFF
and NIGHT MODE)
Auto change over
HEAT COOL
321
CN3N
blue
234
5
687
1
CN102B
6
543
2
CN101B
1
11
10
9
8
7
CN101B
12
CN104B
6 5 4 3 2 1
4 3 2 18 7 6 5
10
9
12 11
CN103A
569
10
13
2
10
13
956
2
7
532
753
2
R23R22
CNTYP5
CNH
CNTYP4
CN01
CNL
black
3 2 13 2 12 13 2 12 1
red
white
black
1 2 31 2 3
63HS
63LS
TH11
black
white
red
CN101A
7
8
9
10
11
12
CN103B
CN104A
12 1110
98 7 6 5 2 14 3
6 5 4 3 2 1
CN102A
CN101A
876
54321
54321
6
63PW
12345
6
Refer to the service handbook
about the switch operations.
210
SWU3
SWU1
Address setting
SWU2
1010
1
10
1
10
1
10
Control circuit board
1
1
SW5
OFFOFF ONOFF ON
OFF OFF ON
ON
ON
LD1
SW4
SW3 SW2 SW1
Function setting
Maintenance
setting
LD2
4 3 2 1
PE
TH8TH9
Unit ON/OFF
Sub box
CNLVB
red
6 5 4 3 2 1
LEV1
detection
circuit
X11
TH7 TH5
L1L2L3
N
L1L2L3
N
9
SV
7a
SV
7b
SV
7c
Pump interlock
1
8
1
8
1
8
12345
detection
circuit
X23
X22
X21
X25
TB8
(Terminal Block)
432
1
CN81
CN83
SV
4b
SV
4a
CN06
yellow
))
CN63PW
blue
123
4
123
4
CNPW
blue
1
2 1
THINV
2 1
CN09
green
L1L2L3
N
detection
circuit
red
white
blue
white
X01
Function setting
SV
5a
21S
4a
SV
5b
SV
4c
SV
4d
SV1
52C
shield
X04
1
9
1
1414
1
9
1
Compressor ON/OFF
NIGHT MODE
or STEP DEMAND
123
CNAC3
black
LEV2
6 5 4 3 2 1
CNLVC
yellow
63H
INDOOR/OUTDOOR
TRANSMISSION LINE
CNOUT1
yellow
4 3 2 1
RELAY-BOARD
CNAC4
765432 1
CNOUT2
yellow
123 45
6
1
7
CNRS3B
Compressor ON/OFF
Water freeze signal or
trouble signal
CNVCC1
CN51
CN3D
321
12V
CN52C
yellow
CN38
green
CN36
CN35
red
CN33
X02
CN32
X01
X09
X08
X03
CNS2
blue
CNS1
blue
CH11
123
Z20
123
123
123
12345
6
9
2 1
8 7 6 5
TH6
CN02
CNTYP1
red
CN20
CN21
blue
F01
250VAC
6.3A T
F02
250VAC
6.3A T
1 2 34 5
1 2 3
TB1
(Terminal Block)
Power source
3N ~
380/400/415V
50/60Hz
black
red
52C
DCL
C2
red
1 2 3 4
DS
(Diode stack)
DCCT
white
black
432
1
CNDC2
N
IPM
P
C4
MC
Gate amp board
ACCT
-W
V
ACCT
ACCT-U
X52
U V W
C1
R4
R3
R1
R2
ACNF
(Noise Filter)
E
FILTER BOARD
1
CNFG
blue
1 2
1 2
L1L2
1 2
CNL1CNL2
CNOUT
green
CNIN
blue
C5
ZNR4
12345
6
X05
CN34
red
X07
X06
CN15V1
CNDC1
black
CNDR1
123
4
1 8
CNVCC1
1 2 3 4 5
CNAC2
MF1
CNFAN
red
SW2SW1
1 4
1 6
ON
OFF
ON
OFF
LED1 operation
LED2 error
321
CNFG
blue
1
2
CNCT2
blue
432
1
123
4
CNTH
green
1 2
THHS1
1 7
1 2 3 4
CNCT
CNRS1
Power circuit board
CNDC2
black
CN15V2
CNDR2
TB3
(Terminal Block)
M1M2SM2M1
TB7
(Terminal Block)
1 2 3
1 2
shield
F02
700VDC
2A T
red
white
black
blue
detection
circuit
red
white
black
blue
red
black
Motor
(Compressor)
F01
250VAC
2A T
U
W
CENTRAL CONTROL
TRANSMISSION LINE
Inverter controller box
Page 81
- 78 -
[2] CMB-P104V-G
CONT.B
Pressure sensor
TR
TH11,12,15,16
LEV1,3
PS1,3
SymbolName
Transformer
Thermistor sensor
Expansion valve
SV1
~4A,B,C Solenoid valve
TB01
Terminal block
(for power source)
TB02
Terminal block
(for Transmission)
T1
~4Terminal
F01
Fuse AC250V 6.3A F
Solenoid valveSVM1
TR
TB02
CN26
3
1
CN12
1
53
CN05
6
54
3
2
1
CONT.B
1
2
CN02
3
CNP1
123
CNP3
211234567
8
4
3
2
1
12321
CN03
CN13
CN10
CN11
CN07
TH11
TH12
TH15
TH16
PS1
PS3
6
54
3
2
1
TB01
LEV3LEV1
S(SHIELD)
M2
M1
220V
~240V20V~22V
L
123
4
10
9
8
423
10
214
3
SV3A
SV3B
SV2B
SV3C
SV2C
SV2A
243
756
4
3
2
123
4
1
234
234
9
8
7
6
5
SV1C
SV1A
SV1B
7
5
3
1
7
5
3
1
7
5
3
1
X2
X1
X30
X4
X3
X31
X6
X5
X32
CN27(Red)
CN28(Blue)
1
1
1
1
234
13
12
11
16
15
14
13
12
11
SV4B
SV4C
SV4A
151614
1
234
1
7
5
3
1
X8
X7
X33
CN29(Green)
SVM1
123
1
2
3
1
3
CN36(Green)
X21
N
ZNR01
ZNR02
CNTR
(Red)
2
2
PE
3
1
3
1
T2
T3
T1
T4
PE
TO NEXT INDOOR UNIT
PULL BOX
FUSE(16A)
BREAKER(16A)
POWER SUPPLY
~220V-240V
50Hz/60Hz
Indoor/outdoor
Transmission Line
ON
OFF
1
SW5
OFF
8
SW4
ON
1
8
BC controller
Circuit
board
SW2 SW1
110
F01
250VAC
6.3A F
(Black)
(Red)
(Yellow)
(Red)
(Yellow)
DSA
Note:1.TB02 is transmission terminal block.
Never connect power line to it.
2.The initial set values of switch on
CONT.B are as follows.
SW1:0
SW2:0
Symbol explanation
Page 82
- 79 -
[3] CMB-P105, 106V-G
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~6
TB02
TB01
CONT.B
Circuit
board
BC
controller
Te r minal block
(for Transmission)
Solenoid valve
Solenoid valve
Te r minal block
(for power source)
Pressure sensor
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~6A,B,C
SVM1
TR
TH11,12,15,16
LEV1,3
PS1,3
Note: 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on
CONT.B are as follows.
SW1:0
SW2:0
F01
250VAC
6.3A F
CMB-P106V-G ONLY
101
SW1SW2
(Black)
(Red)
(Yellow)(Red)
DSA
(Red)
(Yellow)
8
1
ON
SW4
8
OFF
SW5
1
OFF
ON
T5
T4
T6
T1
T3
T2
1
3
1
322
Indoor/outdoor
Tr ansmission line
PE
PE
50Hz/60Hz
~ 220V-240V
POWER SUPPLY
BREAKER(16A)
FUSE(16A)
PULL BOX
TO NEXT INDOOR UNIT
CN31(Yellow)
CN30(Black)
X35
X11
X12
X34
X9
X10
X33
X7
X8
135
7
135
7
135
1
4
3
2
1
4
3
2
1
4
3
2
1
SV6B
SV6A
SV6C
123
4
1
234
3
4
324
1
2
1
141615
SV4A
SV4C
SV5B
SV4B
SV5C
SV5A
111213
141516
111213
4
3
2
1
1
1
1
X32
X5
X6
X31
X3
X4
X30
X1
X2
135
7
135
7
135
7
SV1B
SV1A
SV1C
567
8
9
4
3
2
4
3
2
1
4
3
2
1
234
657
342
SV2A
SV2C
SV3C
SV2B
SV3B
SV3A
3
4
1
2
10
324
8910
4
3
2
1
20V~22V220V~240V
LEV1LEV3
TB01
123456
PS3
PS1
TH16
TH15
TH12
TH11
CN11
CN10
CN13
CN03
12321
123
4
8
7
6
5
4
3
2
1
1
2
CNP3
321
CNP1
3
CN02
2
1
CONT.B
123456
351
CN12
1
CNTR
3
CN26
TR
1
3
2
123
SVM1
3
1
X21
TB02
M2
M1
S(SHIELD)
CN07CN05
ZNR01
CN27(Red)
CN28(Blue)
CN29(Green)
ZNR02
L
N
CN36(Green)
Page 83
- 80 -
[4] CMB-P108, 1010V-G
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~10
TB02
TB01
REL.B
CONT.B
Circuit
board
Relay
BC controller
Te r minal block
(for Transmission)
Solenoid valve
Solenoid valve
Te r minal block
(for power source)
Pressure sensor
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~10A,B,C
SVM1
TR
TH11,12,15,16
LEV1,3
PS1,3
Note:
1. TB02 is transmission
terminal block.
Never connect power
line to it.
2. The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0
SW2 SW1
110
CMB-P1010V-G ONLY
F01
250VAC
6.3A F
(Black)
(Red)
(Yellow)
(Red)
DSA
(Yellow)
81
OFF
ON
SW4
SW5
OFF
ON
81
2
132
3
1
T6
T2
T3
T4
T5
T1
T7T8T9
T10
Indoor/outdoor
Tr ansmission line
50Hz/60Hz
~220V-240V
POWER SUPPLY
BREAKER(16A)FUSE(16A)
PULL BOX
TO NEXT INDOOR UNIT
PE
PE
REL.B
SVM1
32 1
32 1
CNTR
1
3
CN26
CN38
31
531
76543211234567
CN50CN50
PS3
PS1
TR
TH16
TH15
TH12
TH11
CN11
CN10
CN02CN03
12321
123
4
87654
32112
CNP3
321
3
2
1
LEV1LEV3
123456123456
CONT.B
CN52
1
3
CN39
1234567
220V~240V20V~22V
SV6B
SV6A
SV6C
123
4
1
234
33
2
1
2
1
16
15
14
765
13
12
11
10
9
8
16
15
14
765
10
9
8
13
12
11
4
4
4
4
3
3
3
3
2
2
2
2
1
1
1
1
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
234
123
4
234
234
1
1
1
753
1
753
1
753
1
753
1
753
1
7
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10X9X34
X12
X11
X35
142
3
142
3
432
1
SV1C
SV1A
SV1B
123
4
531
X2
X1
X30
1234123412341234
1234123412341234
SV7B
SV8B
SV9B
SV10B
SV7A
SV8A
SV9A
SV10A
SV7C
SV8C
SV9C
SV10C
131415101112978654
4876512 11 10915 14 1316
16
CN35(Blue)
CN32
CN33(Red)
CN34(Black)
X14
X13
X36
X37
X15
X16
X18
X17
X38
X39
X19
X20
573175317531751333
CN12
CN36(Green)
1
3
X21
S(SHIELD)
TB02
M2
M1
CNP1
CN13
CN07
CN05
CN27(Red)
CN28(Blue)
CN29(Green)
CN30(Black)
CN31(Yellow)
N
TB01
L
ZNR02
ZNR01
(Red)
Page 84
- 81 -
[5] CMB-P1013, 1016V-G
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~16
TB02
TB01
REL.B
CONT.B
Circuit
board
Relay
BC controller
Te r minal block
(for Transmission)
Solenoid valve
Solenoid valve
Te r minal block
(for power source)
Pressure sensor
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~16A,B,C
SVM1
TR
TH11,12,15,16
LEV1,3
PS1,3
Note: 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on CONT.B are as follows.
SW1:0
SW2:0
18
81
1
X41
3
135
135
7
135
7
7
5
X49
X50
X46
X47
X48
X44
X40
X43
X42
X45
135
7
135
7
7
X54
X57
X53
X52
X56
X55
X51
124
3
124
3
432
1
432
1
123
4
123
4
123
4
123
4
123
4
123
4
123
4
123
4
123
4
123
4
161514
7
6
51423
13
121110
161514
13
121110
9
8
231
798
654
1
3
123
2
SVM1
1357 1357 1357
X20
X18
X19
X17
X39
X38
X16
X15
X37
X36
X13
X14
331357
432 1432 1432 143 2 1
432 1432 1432 14321
13141510111297865
4
4
876512 11 10915 14 13
16
16
11
11
135
7135713571357135713
5
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10X9X34
X12
X11
X35
1
2
1233
432
1
432
1
123
4
123
4
123
4
123
4
234
123
4
123
4
123
4
123
4
234
161514
765
423
131211
1098
423
161514
131211
10
9
8
765
123
8765432
1
4
1
3
12321
123
4
8765432
112
321
321
123456123456
4
1234567
832
1
31
531
31213
312
1
3
X21
CMB-P1016V-G ONLY
F01
250VAC
6.3A F
SW2 SW1
110
(Black)
(Red)
(Red)
(Yellow)
(Blue)
DSA
ON
OFF
SW5
OFF
SW4
ON
T16
T12
T13
T14
T15
T11
T7T8T9
T10
T6
T2
T3
T4
T5
T1
3
1
3
122
Indoor/outdoor
Tr ansmission line
TO NEXT
50Hz/60Hz
~220V-240V
POWER SUPPLY
BREAKER(16A)FUSE(16A)
PULL BOX
PE
PE
INDOOR UNIT
CN42
SV16C
SV16A
SV16B
SV15C
SV15A
SV15B
SV14B
SV14A
SV14C
SV13B
SV13A
SV13C
SV12B
SV12A
SV12C
SV11C
SV11A
SV11B
REL.B
CN40
CN32
SV10C
SV10A
SV10B
SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7B
SV7A
SV6C
SV6A
SV6B
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
(Yellow)
CN43(Red)
CN41(Green)
CN45(Green)
CN44(Yellow)
20V~22V220V~240V
PS3
PS1
CNTR
CN26
CN38
TR
TH16
TH15
TH12
TH11
CN11
CN10
CN02CN03
CNP3
CNP1
CNOUT4
CNOUT2
CNOUT1
CNOUT3
CN12
CN39
CONT.B
CNVCC2
CNVCC1
LEV3LEV1
CN13
CN05
CN07
(Yellow)(Blue)
(Red)
CN27(Red)
CN28(Blue)
CN29(Green)
CN30(Black)
CN31(Yellow)
CN36(Green)
CN35(Blue)
CN34(Black)
CN33(Red)
S(SHIELD)
TB02
M2
M1
TB01
N
L
ZNR02
ZNR01
Page 85
- 82 -
[6] CMB-P104V-GB
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~4
TB02
TB01
CONT.B
Circuit
board
BC
controller
Te r minal block
(for Transmission)
Solenoid valve
Te r minal block
(for power source)
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~4A,B,C
TR
TH12,15
LEV3
Note: 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on
CONT.B are as follows.
SW1:0
SW2:0
SW2 SW1
110
F01
250VAC
6.3A F
(Yellow)
(Red)
(Yellow)
DSA
ON
OFF
1
SW5
OFF
8
SW4
ON
1
8
T2
T3
T1
T4
Indoor/outdoor
Tr ansmission Line
PULL BOX
TO NEXT INDOOR UNIT
50Hz/60Hz
220V~240V
POWER SUPPLY
BREAKER(16A)
FUSE(16A)
PE
PE
TR
CN26
3
1
CN12
153
CONT.B
CN02
211234567
8
4
3
2
1
12321
CN10
CN11
TH12
TH15
654321
LEV3
220V~240V20V~22V
123
4
10
9
8
423
10
214
3
SV3A
SV3B
SV2B
SV3C
SV2C
SV2A
243
756
4
3
2
1
234
1
234
234
9
8
7
6
5
SV1C
SV1A
SV1B
7
5
3
1
7
5
3
1
7
5
3
1
X2
X1
X30
X4
X3
X31
X6
X5
X32
1
1
1
1
2
3
4
13
12
11
16
15
14
13
12
11
SV4B
SV4C
SV4A
151614
1
2
3
4
1
7
5
3
1
X8
X7
X33
TB02
S(SHIELD)
M2
M1
CN03
CN13
TB01
N
L
CN07
(Red)
CNTR
CN27(Red)
CN28(Blue)
CN29(Green)
ZNR01ZNR02
Page 86
- 83 -
[7] CMB-P108V-GB
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~8
TB02
TB01
REL.B
CONT.B
Circuit
board
Relay
BC controller
Te r minal block
(for Transmission)
Solenoid valve
Te r minal block
(for power source)
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~8A,B,C
TR
TH12,15
LEV3
Note:
1. TB02 is transmission
terminal block.
Never connect power
line to it.
2. The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0
SW2 SW1
110
(Red)
(Yellow)
DSA
F01
250VAC
6.3A F
81
OFF
ON
SW4
SW5
OFF
ON
81
T6
T2
T3
T4
T5
T1
T7T8
Indoor/outdoor
Tr ansmission line
PE
TO NEXT INDOOR UNIT
PULL BOX
FUSE(16A)BREAKER(16A)
POWER SUPPLY
~220V-240V
50Hz/60Hz
PE
REL.B
CNTR
1
3
CN26
CN38
31
531
7654321
CN50
TR
TH15
TH12
CN11
CN10
CN02CN03
12321
123
4
8765432
112
LEV3
123456
CONT.B
CN52
1
3
CN39
1234567
220V~240V20V~22V
SV6B
SV6A
SV6C
123
4
123
4
33
2
1
2
1
16
15
14
765
13
12
11
10
9
8
16
15
14
765
10
9
8
13
12
11
4
4
4
4
3
3
3
3
2
2
2
2
1
1
1
1
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
234
123
4
234
234
1
1
1
7
531
7
531
7
531
7
531
7
531
7
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10X9X34
X12
X11
X35
142
3
142
3
432
1
SV1C
SV1A
SV1B
123
4
531
X2
X1
X30
12341234
12341234
SV7B
SV8B
SV7A
SV8A
SV7C
SV8C
131415101112978654
4876512 11 10915 14 1316
16
CN32
X14
X13
X36
X37
X15
X16
X18
X17
X38
X39
X19
X20
573175317531751333
CN12
TB02
S(SHIELD)
M2
M1
(Red)
CN13
CN07
ZNR01ZNR02
N
L
TB01
CN27(Red)
CN28(Blue)
CN29(Green)
CN30(Black)
CN35(Blue)
CN34(Black)
CN33(Red)
CN31(Yellow)
Page 87
- 84 -
[8] CMB-P108, 1010V-GA
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~10
TB02
TB01
REL.B
CONT.B
Circuit
board
Relay
BC controller
Te r minal block
(for Transmission)
Solenoid valve
Solenoid valve
Te r minal block
(for power source)
Pressure sensor
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~10A,B,C
SVM1,2
TR
TH11,12,15,16
LEV1~3
PS1,3
Note:
1. TB02 is transmission
terminal block.
Never connect power
line to it.
2. The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0
CMB-P1010V-GA ONLY
F01
250VAC
6.3A F
10 1
SW1SW2
(Black)
(Red)
(Yellow)(Red)(Blue)
DSA
18
ON
OFF
SW5
SW4
ON
OFF
18
T10
T9T8T7
T1
T5
T4
T3
T2
T6
1
3
231
2
Indoor/outdoor
Tr ansmission line
PE
PE
TO NEXT INDOOR UNIT
FUSE(16A)
PULL BOX
BREAKER(16A)
POWER SUPPLY
~220V-240V
50Hz/60Hz
SVM2
SVM1
32 1
321
3214
4321
3331571357157175
X20
X19
X39
X38
X17
X18
X16
X15
X37
X36
X13
X14
CN32
16
16131415910111256784
45687912 11 1015 14 13
SV10C
SV9C
SV8C
SV7C
SV10A
SV9A
SV8A
SV7A
SV10B
SV9B
SV8B
SV7B
432 1 43 2 1 43 2 1 43 2 1
432 1 43 2 1 43 2 1 43 21
7654321
CN52
REL.B
CN39
CN35(Blue)
CN34(Black)
CN33(Red)
1
3
1
3
1
3
CN46(Yellow)
X21
X60
X30
X1
X2
135
432
1
SV1B
SV1A
SV1C
123
4
324
1
X35
X11
X12
X34
X9
X10
X33
X7
X8
X32
X5
X6
X31
X3
X4
713571357135713571357
1
1
1
432
432
432
1
432
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
8
9
10
111213
567
141516
123
324
1
8
9
10
111213
567
141516
123
432
1
432
1
SV6C
SV6A
SV6B
20V~22V220V~240V
CONT.B
654321654321
LEV3LEV1
123
123
CNP3
211234567
8
432
1
12321
CN02
CN10
CN11
TH11
TH12
TH15
TH16
TR
PS1
PS3
CN50
7654321
135
CN12
13
CN38
CN26
3
1
654321
LEV2
CNP1
CN13
CN07CN05CN06
S(SHIELD)
TB02
M2
M1
ZNR02
ZNR01
CNTR
(Red)
CN27(Red)
CN28(Blue)
CN29(Green)
CN31(Yellow)
CN30(Black)
CN36(Green)
L
N
TB01
CN03
(Yellow)
Page 88
- 85 -
[9] CMB-P1013, 1016V-GA
Symbol explanation
Fuse AC250V 6.3A F
F01
Te r minalT1
~16
TB02
TB01
REL.B
CONT.B
Circuit
board
Relay
BC controller
Te r minal block
(for Transmission)
Solenoid valve
Solenoid valve
Te r minal block
(for power source)
Pressure sensor
Expansion valve
Thermistor sensor
Tr ansformer
NameSymbol
SV1
~16A,B,C
SVM1,2
TR
TH11,12,15,16
LEV1~3
PS1,3
Note: 1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on CONT.B are as follows.
SW1:0
SW2:0
F01
250VAC
6.3A F
(Red)
CMB-P1016V-GA ONLY
SW2 SW1
110
(Black)
(Red)
(Yellow)
(Blue)
DSA
(Blue)
18
ON
OFF
SW5
OFF
8
SW4
ON
1
PE
PE
50Hz/60Hz
~220V-240V
POWER SUPPLY
TO NEXT
INDOOR UNIT
BREAKER(16A)FUSE(16A)
PULL BOX
T16
T12
T13
T14
T15
T11
T7T8T9
T10
T6
T2
T3
T4
T5
T1
3
1
3
1
2
2
Indoor/outdoor
Tr ansmission line
X60
CN46(Yellow)
133
CNOUT4
CNOUT2
4
1234567
832
1
CN12
531
TB01
L
N
LEV1
123456
CN05
2
113
2
2
3
SVM1
SVM2
1
3
135
135
7
135
7
7
5
X49
X50
X48
135
7
135
7
7
X54
X57
X53
X52
X56
X55
X51
1
243
4
3
1
432
1
SV16C
SV16A
SV16B
123
4
123
4
123
4
123
4
123
4
123
4
123
4
123
4
123
4
SV15C
SV15A
SV15B
SV14B
SV14A
SV14C
SV13B
SV13A
SV13C
SV12B
SV12A
SV12C
123
4
161514
7
6
51423
13
121110
9
8
1
243
161514
7
6
51423
13
121110
9
8
SV11C
SV11A
SV11B
REL.B
CN43(Red)
CN44(Yellow)
CN45(Green)
X21
CN36(Green)
1
13571357 1357
X20
X18
X19
X17
X39
X38
X16
X15
X37
X36
X13
X14
331357
CN32
432 1432 1432 1432 1
432 143 21432 143 21
131415101112978654
4876 512 11 10915 14 13
16
16
SV10C
SV10A
SV10B
SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7B
SV7A
1
1
11
135
7
135
71357135713571357
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10X9X34
X12
X11
X35
CN26
CN27(Red)
CN28(Blue)
CN29(Green)
CN30(Black)
CN31(Yellow)
1
2
1233
432
1
432
1
SV6C
SV6A
SV6B
123
4
123
4
123
4
123
4
234
123
4
123
4
123
4
123
4
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
234
161514
765
423
13
12
11
10
9
8
423
161514
13
12
11
10
9
8
765
SV1C
SV1A
SV1B
X41
CN42
X46
X47
X44
X40
X43
X42
X45
20V~22V220V~240V
PS3
PS1
123
8765432
1
4
1
3
CN38
TR
TH16
TH15
TH12
TH11
CN11
CN10
CN02
12321
123
12345612345
6
4
8765432
112
CNP3
321
321
31
CNOUT1
CNOUT3
31
CN39
CONT.B
213
CNVCC2
312
LEV3
S(SHIELD)
TB02
M2
M1
CN03
(Yellow)
CNVCC1
(Blue)
CNP1
CN13
CN07
LEV2
CN06
ZNR02ZNR01
CN35(Blue)
CN33(Red)
CN34(Black)
(Yellow)
CN40
CN41(Green)
(Red)
CNTR
Page 89
- 86 -
Terminal
block
CN1
DSA1ZNR1
S.A.B.
3
2
1
M-NET TRANSMISSION
LINE
(OUTDOOR UNIT SIDE)
M-NET TRANSMISSION
LINE
ADDITIONAL INDOOR
UNIT SIDE
Breaker (3A)
Power source
220-240V~/N
50/60Hz
NF
ZNR2
E
3
4
2
1
L
AC250V
2A F
TB1
PE
N
BOX BODY
BOX BODY
BOX BODY
S.P.S.
L
CN2
CN1
BOX BODY
12
3
4
21
2
1
TB3
TB2
S
B
A
A
B
S
2
1
2
1
CN2
CN4
CN3
C.B.
CN1
( )
1
2
3
45
M-NET transmission line
(Outdoor unit side)
M-NET transmission line
(Additional indoor unit side)
Surge Absorber
DSA1
Varistor
ZNR1,2
Choke coil(Transmission)
L
Earth terminal
Noise Filter
Surge absorber board
Switching Power Supply
Circuit board
Fuse
NAMESYMBOL
SYMBOL EXPLANATION
Power source
TB3
TB2
TB1
F
NF
S.A.B.
S.P.S.
C.B.
[10] Power Dispatching Extension Unit for the Transmission Lines
Page 90
High pressure
sensor
CJ1
Oil
sepa-
rator
TH11
CJ2
SV1
SV7c
CP1
BV2
Accumulator
High pressure switch
4-way valve
ST6
ST1
Low pressure sensor
ST10
ST11
BV1
CV8a
CV10a
CV9a
CV5a
CV4a
CV2a
CV3a
CV6a
CV7a
TH6
SV4b
SV4c
SV4d
Orifice
ST14
ST15ST16
Check Valve Block 1
Solenoid Valve Block 1
SV7b
CV11
SV7a
10HP
only
THINV
LEV2
ST13
Air heat exchanger
ST5
TH9
Water
circulating
Water heat exchanger
(Double coil type)
Compre-
ssor
SV4a
- 87 -
§§
Refrigerant Circuit
[1] Refrigerant Circuit Diagram
< PQRY-P200, P250YGM-A >
Page 91
High pressure sensor
CJ1
TH11
CJ2
SV1
CP1
BV2
Accumulator
4-way valve
ST6
ST1
ST10
ST11
BV1
CV8a
CV10a
CV9a
CV5a
CV4a
CV2a
CV3a
CV6a
CV7a
TH6
SV4a
SV4b
SV4c
SV4d
ST14
ST15
ST16
SV7c
Check Valve Block 1
Solenoid Valve Block 1
Solenoid Valve
Block 2
SV7b
CV11
SV7a
THINV
LEV2
ST13
Air heat exchanger
CV3b
CV2b
CV5b
CV6b
CV4b
SV5a
SV5b
CV7b
BV3
BV4
BV5
ST22
ST23
ST18
ST19
TH9
Check Valve Block 2
Oil
sepa-
rator
Compre-
ssor
Low
pressure
sensor
Water heat exchanger
(Double coil type)
Water
circulating
20HP
only
20HP
only
Orifice
Main Unit
Sub Unit (Heat exchanger)
High
pressure
switch
CV12
- 88 -
< PQRY-P400, P500YSGM-A >
Page 92
Check Valves Block 1Y
High pressure
sensor
CJ1
TH11
CJ2
SV1
SV7c
CP1
BV2
Accumulator
High pressure switch
4 way valve
ST6
ST1
63LS
ST10
ST11
BV1
CV8a
CV10a
CV9a
CV4a
CV3a
CV6a
CV7a
TH6
SV4b
SV4c
SV4d
ST14ST15ST16
Solenoid Valves Block 1
SV7b
CV11
SV7a
THINV
LEV2
ST13
Air heat exchanger
TH7 ST2
LEV1
ST8
TH5
TH8
ST5
TH9
SV4a
Oil
sepa-
rator
Compre-
ssor
10HP
only
Orifice
Water
circulating
Water heat exchanger
(Double coil type)
- 89 -
< PQHY-P200, P250YGM-A >
Page 93
Check Valves Block 1Y
Check Valves Block 2Y
High pressure sensor
High
pressure
switch
CJ1
TH11
CJ2
SV1
CP1
4 way valve
ST6
ST10
ST11
CV8a
CV10a
CV9a
CV4a
CV3a
CV6a
CV7a
TH6
SV4a
SV4b
SV4c
SV4d
Orifice
ST14ST15ST16
Solenoid Valves Block 1
SV7b
CV11
SV7a
THINV
LEV2
ST13
Compressor Unit
Sub Unit (Heat exchanger)
Solenoid Valves
Block 2
ST18
CV6b
CV3b
CV4b
SV5a SV5b
CV7b
BV3
BV4
BV5
ST1
BV1
TH7
LEV1
ST8
TH5
BV2
ST2
TH8
ST22
SV7c
ST23
ST19
TH9
20HP
only
20HP
only
Oil
sepa-
rator
Compre-
ssor
Air heat exchanger
Accumulator
Low
pressure
sensor
Water
circulating
Water heat exchanger
(Double coil type)
CV12
- 90 -
< PQHY-P400, P500YSGM-A >
Page 94
- 91 -
< CMB-P104,105,106,108,1010,1013,1016V-G >
< CMB-P104,108V-GB >
TH15
TH12
LEV3
LEV1
TH16
PS1 PS3
TH11
SVM1
HIC-B
Gas/Liquid
Separator
Solenoid
valve Block
Check
valve Block
TH25
TH22
LEV3a
CP
Solenoid
valve Block
Check
valve Block
Page 95
- 92 -
< CMB-P108,1010,1013,1016V-GA >
TH15
TH12
LEV3
LEV1
TH16
PS1
PS3
TH11
Solenoid
valve Block
SVM1
SVM2
Gas pipe
(high pressure side)
Gas/Liquid
Separator
LEV2
Liquid pipe
Check
valve Block
Gas pipe
(low pressure side)
Page 96
NameNotesFunctionSpecificationCheck method
Symbol
(function)
1
273+t
Compressor
High
-pressure
sensor
Pressure
switch
Thermistor
MC1
63HS
R120=7.465kΩ
R25/120=4057
Rt =
7.465exp{4057( - )}
Resistance value
check
Resistance value
check
1
393
1
273+t
R0=15kΩ
R0/80=3460
Rt =
15exp{3460( - )}
1
273
Pressure
0~4.15MPa
Vout 0.5~3.5V
0.071V/0.098MPa
Pressure [MPa]
=1.38✕Vout[V]-0.69
Gnd (Black)
Vout (White)
Vcc (DC5V) (red)
Connector
63HS
1
123
2
3
Adjusts the volume of circulating refrigerant by controlling the operating
frequency with the operating pressure.
Low-pressure shell scroll type
Winding resistance
20˚C : 0.583Ω
63H1
TH11
(Discharge)
TH9
(Outlet water
temperature)
THINV
THHS
Inverter
heat sink
temperature
Heat sink
1 Detects high pressure
2 Protects high pressure
1 Detects discharge temperature
2 Protects high pressure
Freeze prevention of water-source
heat exchanger
TH6
(Inlet water
temperature)
TH5
(Piping
temperature)
Detects inlet water temperature
1 Detects the temperature at the
inverter cooler’s heat exchanger
outlet.
2 Controls the LEV2 opening angle
Controls inverter cooling fan, using
THHS temperature.
Supplies refrigerant to indoor units in
cooling operation
Supplies refrigerant to indoor units in
heating operation
Supplies refrigerant to indoor units in
cooling operation
SV A
SV
B
SV
C
3. GB type
Page 100
- 97 -
SW4
SW5
1
2
3
4
1
2
3
4
5
5
6
6
7
7
8
8
9
9
–
Pump down operation
Heating Tcm
–
–
–
–
Night mode/Step demandNight modeDemand functionBefore power on
–
–
SW3
1
2
3
4
5
6
7
8
9
10
10
10
Not connected to the
centralized control
Ordinary control
Ordinary control
–
–
–
SW3-2 invalid
Stops all ICs
–
–
Ordinary control
49˚C
–
–
–
–
–
Before power on
Before power on
Before power on
Anytime after power on (When switched
from OFF to ON)
Anytime after power on
(Except during initial start up mode/becomes
ineffective 2 hours after compressor start up)
–
–
–
Anytime after power on
After power on and when SW3-1 is on.
–
After power on and while compressor is stopped
Anytime after power on
–
–
–
–
–
–
Switch Function
Function according to switch settingSwitch setting timing
OFFONOFFON
SWU
SW2
1~2
1
2
3
4
5
6
7
8
9
10
Unit address setting
Centralized control switch
Deletion of connection
information
Deletion of error history
Refrigerant amount
adjustment
–
–
–
Test run: valid/invalid
Test run: ON/OFF
Set to 00 or 51-100 with the dial switch
Anytime after power on
SW1
1~10
For self-diagnosis/operation
monitoring
Refer to the LED monitor display on the outdoor unit board
Connected to the centralized
control
Deletion
Deletion of IC/OC error
history
Storage of IC/OC error
history
Refrigerant amount
adjustment mode
–
–
–
–
–
–
–
SW3-2 valid
Test runs all ICs
–
Pump down operation
53˚C
–
––––
–
––––
–
––––
––––
––––
–
––––
–
–
––––
––––
––––
––––
––––
––––
––––
––––
––––
––––
Note: All are set to OFF at factory shipment
At all times
At all times
At all times
Normal
Water heat exchanger
freeze prevention signal
Normal
Disregard trouble
Heat source unit abnormal
output
Freeze prevention operation*
Disregard pump interlock
trouble.
CN51-3,5 Output switching
Freeze prevention operation
At all timesThe relay closes during
compressor operation.
The relay closes during
reception of the cooling or the
heating operation signal from
the controller.
(Note: It is output even if the
thermostat is OFF
(when the compressor is
stopped).)
Operation ON signal
output switching
Relay contact output
TB8-1,2
¶¶
Control
[1] Dip Switch Functions and Their Factory Settings
1. Heat source unit
(1) Main board
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.