mitsubishi HS Specification Manual

NG)
INTELLIGENT SERVOMOTOR
HS Series
Specifications and Instruction Manual
Introduction
Thank you for purchasing the Mitsubishi CNC. This instruction manual describes the handling and caution points for using this CNC. Incorrect handling may lead to unforeseen accidents, so always read this instruction manual thoroughly to ensure correct usage. Make sure that this instruction manual is delivered to the end user.
Precautions for safety
Please read this instruction manual and auxiliary documents before starting installation, operation, maintenance or inspection to ensure correct usage. Thoroughly understand the device, safety information and precautions before starting operation.
The safety precautions in this instruction manual are ranked as "DANGER" and "CAUTION".
DANGER
When a dangerous situation may occur if handling is mistaken leading to fatal or major injuries.
CAUTION
When a dangerous situation may occur if handling is mistaken leading to medium or minor injuries, or physical damage.
Note that some items described as CAUTION may lead to major results depending on the situation. In any case, important information that must be
observed is described. The signs indicating prohibited and mandatory items are described below.
This sign indicates that the item is prohibited (must not be carried out). For example, is used to indicate "Fire
Prohibited".
This sign indicates that the item is mandatory (must be carried out). For example, is used to indicate grounding.
After reading this instruction manual, keep it in a safe place for future reference.
In this manual, this mark indicates important matters the operator
POINT
should be aware of when using the CNC.
I
For Safe Use
1. Electric shock prevention
Wait at least 10 minutes after turning the power OFF, check the voltage between L1-L2-L3 and L11-L12 terminals with a tester, etc., before starting wiring or inspections. Failure to observe this could lead to electric shocks.
Ground the servo amplifier and servomotor with Class 3 grounding or higher.
Wiring and inspection work must be done by a qualified technician.
Wire the servo amplifier and servomotor after installation. Failure to observe this could lead to electric shocks.
Do not touch the switches with wet hands. Failure to observe this could lead to electric shocks.
Do not damage, apply forcible stress, place heavy items or engage the cable. Failure to observe this could lead to electric shocks.
DANGER
2. Fire prevention
Install the servo amplifier, servomotor and regenerative resistor on noncombustible material. Direct installation on combustible material or near combustible materials could lead to fires.
Following the instructions in this manual, always install no-fuse breakers and contactors on the servo amplifier power input. Select the correct no-fuse breakers and contactors using this manual as a reference. Incorrect selection could lead to fires.
Shut off the main circuit power at the contactors to emergency stop when an alarm occurs.
CAUTION
II
3. Injury prevention
CAUTION
Do not apply a voltage other than that specified in Instruction Manual on each terminal. Failure to observe this item could lead to ruptures or damage, etc.
Do not mistake the terminal connections. Failure to observe this item could lead to ruptures or damage, etc.
Do not mistake the polarity(+ ,–) . Failure to observe this item could lead to ruptures or damage, etc.
Do not touch the servo amplifier fins, regenerative resistor or servomotor, etc., while the power is turned ON or immediately after turning the power OFF. Some parts are heated to high temperatures, and touching these could lead to burns.
4. Various precuations
Observe the following precautions. Incorrect handling of the unit could lead to faults, injuries and electric shocks, etc.
(1) Transportation and installation
Correctly transport the product according to its weight. Do not stack the products above the tolerable number. Do not hold the cables, axis or detector when transporting the servomotor. Follow this Instruction Manual and install the unit in a place where the weight can be borne. Do not get on top of or place heavy objects on the unit. Always observe the installation directions. Do not install or run a servo amplifier or servomotor that is damaged or missing parts. Do not let conductive objects such as screws or metal chips, etc., or combustible materials
such as oil enter the servo amplifier or servomotor. The servo amplifier and servomotor are precision devices, so do not drop them or apply
strong impacts to them.
CAUTION
III
CAUTION
Store and use the units under the following environment conditions.
Environment
Ambient temperature
Ambient humidity
Storage temperature Storage humidity Atmosphere Altitude 1000m or less above sea level
Vibration
(with no dew condensation)
HS-RF HS-SF (1kW or less)
HS-SF (2.0kW or less)
HS-MF
Servomotor Interface unit
0°C to +40°C
(with no freezing)
80% RH or less
–15°C to +65°C
(with no freezing)
90% RH or less (with no dew condensation)
Indoors (Where unit is not subject to direct sunlight)
With no corrosive gas, combustible gas, oil mist or dust.
X: 9.8m/sec2 (1G) Y: Y: 24.5m/sec2
(2.5G) or less X: 19.6m/sec2 (2G) Y: 49m/sec2 (5G) or
less X: 19.6m/sec2 (2G) Y: 19.6m/sec2 (2G)
or less
Conditions
0°C to +55°C
(with no freezing)
90%RH or less
(with no dew condensation)
–20°C to +65°C
(with no freezing)
5.9m/sec2 (0.6G) or less
Securely fix the servomotor to the machine. Insufficient fixing could lead to the servomotor deviating during operation.
Never touch the rotary sections of the servomotor during operations. Install a cover, etc., on the shaft.
When coupling to a servomotor shaft end, do not apply an impact by hammering, etc. The detector could be damaged.
Do not apply a load exceeding the tolerable load onto the servomotor shaft. The shaft could break.
When storing for a long time, please contact your dealer.
IV
(2) Wiring
Correctly and securely perform the wiring. Failure to do so could lead to runaway of the servomotor.
(3) Trial operation and adjustment
Check and adjust each parameter before starting operation. Failure to do so could lead to unforeseen operation of the machine.
Do not make remarkable adjustments and changes as the operation could become unstable.
CAUTION
CAUTION
(4) Usage methods
Install an external emergency stop circuit so that the operation can be stopped and power shut off immediately.
Unqualified persons must not disassemble or repair the unit.
Never make modifications.
Reduce magnetic interference by installing a noise filter. The electronic devices used near the servo amplifier could be affected by magnetic noise. Install a line noise filter, etc., when there is an influence from magnetic interference.
Always use the servomotor and servo amplifier with the designated combination. The servomotor's magnetic brakes are for holding purposes. Do not use them for normal
braking. There may be cases when holding is not possible due to the magnetic brake's life or the
machine construction (when ball screw and servomotor are coupled via a timing belt, etc.). Install a stop device to ensure safety on the machine side.
CAUTION
V
(5) Troubleshooting
CAUTION
If a hazardous situation is predicted during stop or product trouble, use a servomotor with magnetic brakes or install an external brake mechanism.
Use a double circuit configuration that allows the operation circuit for the magnetic brakes to be operated even by the external emergency stop signal. If an alarm occurs, remove the cause and secure the safety before resetting the alarm.
Never go near the machine after restoring the power after a failure, as the machine could start suddenly. (Design the machine so that personal safety can be ensured even if the machine starts suddenly.)
Control in the intelligent servomotor.
Servomotor
(6) Maintenance, inspection and part replacement
Magnetic brake
Shut off with CNC brake control PLC output.
EMG
24VDC
The capacity of the electrolytic capacitor will drop due to deterioration. To prevent secondary damage due to failures, replacing this part every ten years when used under a normal environment is recommended. Contact the nearest dealer for repair and replacement of parts.
(7) Disposal
Treat this unit as general industrial waste.
(8) General precautions
CAUTION
CAUTION
CAUTION
The drawings given in this Specifications and Maintenance Instruction Manual show the covers and safety partitions, etc., removed to provide a clearer explanation. Always return the covers or partitions to their respective places before starting operation, and always follow the instructions given in this manual.
VI
Compliance to European EC Directives
1. European EC Directives
The European EC Directives were issued to unify Standards within the EU Community and to smooth the distribution of products of which the safety is guaranteed. In the EU Community, the attachment of a CE mark (CE marking) to the product being sold is mandatory to indicate that the basic safety conditions of the Machine Directives (issued Jan. 1995), EMC Directives (issued Jan. 1996) and the Low-voltage Directives (issued Jan. 1997) are satisfied. The machines and devices in which the servo is assembled are a target for CE marking. The servo is a component designed not to function as a single unit but to be used with a combination of machines and devices. Thus, it is not subject to the EMC Directives, and instead the machines and devices in which the servo is assembled are targeted. This servo complies with the Standards related to the Low-voltage Directives in order to make CE marking of the assembled machines and devices easier. The EMC INSTALLATION GUIDELINES (IB (NA) 67303) which explain the servo amplifier installation method and control panel manufacturing method, etc., has been prepared to make compliance to the EMC Directives easier. Contact Mitsubishi or your dealer for more information.
2. Cautions of compliance
Use the standard servo amplifier and EN Standards compliance part (some standard models are compliant) for the servomotor. In addition to the items described in this instruction manual, observe the items described below.
(1) Environment
The servo amplifier must be used within an environment having a Pollution Class of 2 or more as
stipulated in the IEC664. For this, install the servo amplifier in a control panel having a structure (IP54) into which water, oil, carbon and dust cannot enter.
(2) Power supply
1) The servo amplifier must be used with the overvoltage category II conditions stipulated in IEC664. For this, prepare a reinforced insulated transformer that is IEC or EN Standards complying at the power input section.
2) When supplying the control signal input/output power supply from an external source, use a 24 VDC power supply of which the input and output have been reinforced insulated.
(3) Installation
1) To prevent electric shocks, always connect the servo amplifier protective earth (PE) terminal (terminal with mark) to the protective earth (PE) on the control panel.
2) When connecting the earthing wire to the protective earth (PE) terminal, do not tighten the wire terminals together. Always connect one wire to one terminal.
PE terminal PE terminal
(4) Wiring
1) Always use crimp terminals with insulation tubes so that the wires connected to the servo amplifier terminal block do not contact the neighboring terminals.
Crimp terminal
Insulation tube Wire
VIII
(5) Peripheral devices
1) Use a no-fuse breaker and magnetic contactor that comply with the EN/IEC Standards described in Chapter 7 Peripheral Devices.
2) The wires sizes must follow the conditions below. When using other conditions, follow Table 5 of EN60204 and the Appendix C.
Ambient temperature: 40°C
Sheath: PVC (polyvinyl chloride)
Install on wall or open table tray
(6) Servomotor
Contact Mitsubishi for the outline dimensions, connector signal array and detector cable.
(7) Others
Refer to the EMC INSTALLATION GUIDELINES (IB (NA) 67303) for other EMC Directive
measures related to the servo amplifier.
VIII

Contents

Chapter 1 Introduction
1-1 Intelligent servomotor outline.............................................................................. 1-2
1-2 Limits and special notes for intelligent servomotor........................................... 1-2
1-2-2 Precautions for selecting the intelligent servomotor ..................................... 1-2
1-2-2 Precautions for use....................................................................................... 1-2
1-2-3 Miscellaneous............................................................................................... 1-2
1-3 Inspection at purchase......................................................................................... 1-3
1-3-1 Explanation of type....................................................................................... 1-3
Chapter 2 Specifications
2-1 Standard specifications ....................................................................................... 2-2
2-2 Torque characteristics......................................................................................... 2-3
2-3 Outline dimension drawings................................................................................ 2-4
2-3-1 HS-MF23 ...................................................................................................... 2-4
2-3-2 HS-RF43/73.................................................................................................. 2-4
2-3-3 HS-SF52/53/102/103.................................................................................... 2-5
2-3-4 HS-SF202..................................................................................................... 2-5
Chapter 3 Characteristics
3-1 Overload protection characteristics.................................................................... 3-2
3-2 Magnetic brake characteristics ........................................................................... 3-3
3-2-1 Motor with magnetic brakes.......................................................................... 3-3
3-2-2 Magnetic brake characteristics ..................................................................... 3-4
3-2-3 Magnetic brake power supply....................................................................... 3-4
3-3 Dynamic brake characteristics............................................................................ 3-5
3-3-1 Deceleration torque...................................................................................... 3-5
3-3-2 Coasting amount .......................................................................................... 3-6
Chapter 4 Peripheral Devices
4-1 Dedicated options................................................................................................. 4-2
4-1-1 I/F unit........................................................................................................... 4-2
4-1-2 Battery option for absolute position system.................................................. 4-6
4-1-3 Cables and connectors................................................................................. 4-7
4-1-4 Cable clamp fitting........................................................................................ 4-11
4-2 Peripheral devices................................................................................................ 4-12
4-2-1 Selection of wire........................................................................................... 4-12
4-2-2 Selection of no-fuse breakers....................................................................... 4-12
4-2-3 Selection of contactor................................................................................... 4-13
4-2-4 Circuit protector............................................................................................ 4-14
Chapter 5 Installation
5-1 Installation of servomotor.................................................................................... 5-3
5-1-1 Environmental conditions............................................................................ 5-3
5-1-2 Cautions for mounting load (prevention of impact on shaft)......................... 5-3
5-1-3 Installation direction .................................................................................... 5-3
5-1-4 Tolerable load of axis ................................................................................... 5-4
5-1-5 Oil and waterproofing measures................................................................... 5-4
5-1-6 Cable stress.................................................................................................. 5-5
i
5-2 Installation of interface unit................................................................................. 5-6
5-2-1 Environmental conditions.............................................................................. 5-6
5-2-2 Installation direction...................................................................................... 5-6
5-2-3 Prevention of entering of foreign matter....................................................... 5-6
5-3 Noise measures.................................................................................................... 5-7
Chapter 6 Wiring
6-1 System connection diagram................................................................................ 6-3
6-2 Connector ............................................................................................................. 6-4
6-2-1 Connector signal layout................................................................................ 6-4
6-2-2 Signal name.................................................................................................. 6-5
6-3 Connection of power supply................................................................................ 6-6
6-3-1 Example of connection for controlling magnetic switch (MC)
with MDS-B-CV/CR....................................................................................... 6-6
6-3-2 Example of connection for controlling magnetic switch with
external sequence circuit.............................................................................. 6-8
6-3-3 Wiring of contactors (MC)............................................................................. 6-8
6-3-4 Surge absorber............................................................................................. 6-9
6-4 Wiring the motor with brakes............................................................................... 6-9
6-4-1 Connection example..................................................................................... 6-9
6-4-2 Manually releasing the magnetic brakes....................................................... 6-10
6-5 Connection with the NC ....................................................................................... 6-11
6-5-1 Connection system....................................................................................... 6-11
Chapter 7 Setup
7-1 Setting the initial parameters............................................................................... 7-2
7-1-1 Servo specification parameters .................................................................... 7-2
7-1-2 Limitations to electronic gear setting value................................................... 7-2
7-1-3 Parameters set according to feedrate........................................................... 7-3
7-1-4 Parameters set according to machine load inertia........................................ 7-3
7-1-5 Standard parameter list according to motor.................................................. 7-4
Chapter 8 Adjustment
8-1 Measurement of adjustment data........................................................................ 8-2
8-1-1 D/A output specifications.............................................................................. 8-2
8-1-2 Setting the output data................................................................................. 8-2
8-1-3 Setting the output scale................................................................................ 8-3
8-1-4 Setting the offset amount ............................................................................. 8-3
8-1-5 Clamp function.............................................................................................. 8-3
8-1-6 Filter function................................................................................................ 8-3
8-2 Gain adjustment ................................................................................................... 8-4
8-2-1 Current loop gain.......................................................................................... 8-4
8-2-2 Speed loop gain............................................................................................ 8-4
8-2-3 Position loop gain......................................................................................... 8-6
8-3 Characteristics improvement............................................................................... 8-8
8-3-1 Optimal adjustment of cycle time.................................................................. 8-8
8-3-2 Vibration suppression measures................................................................... 8-10
8-3-3 Improving the cutting surface precision ........................................................ 8-12
8-3-4 Improvement of protrusion at quadrant changeover..................................... 8-15
8-3-5 Improvement of overshooting....................................................................... 8-19
ii
8-3-6 Improvement of characteristics during acceleration/deceleration ................. 8-21
8-4 Setting for emergency stop ................................................................................. 8-24
8-4-1 Deceleration control...................................................................................... 8-24
8-4-2 Vertical axis drop prevention control............................................................. 8-26
8-5 Collision detection .............................................................................................. 8-27
8-6 Parameter list........................................................................................................ 8-30
Chapter 9 Inspections
9-1 Inspections............................................................................................................ 9-2
9-2 Life parts............................................................................................................... 9-2
9-3 Replacing the unit................................................................................................. 9-3
9-3-1 HS-MF23** type............................................................................................ 9-3
9-3-2 HS-FR43/73, HS-SF52/53/102/103 type ...................................................... 9-3
9-3-3 HS-SF202 type............................................................................................. 9-4
Chapter 10 Troubleshooting
10-1 Points of caution and confirmation................................................................... 10-2
10-2 Troubleshooting at start up............................................................................... 10-2
10-3 Protective functions list ..................................................................................... 10-3
10-3-1 Alarm............................................................................................................ 10-3
10-3-2 Warnings list................................................................................................. 10-7
10-3-3 Alarm and warning deceleration method and reset method.......................... 10-8
Chapter 11 Selection
11-1 Outline ................................................................................................................. 11-2
11-1-1 Servomotor................................................................................................... 11-2
11-1-2 Regeneration methods................................................................................. 11-3
11-2 Selection of servomotor series.......................................................................... 11-4
11-2-1 Motor series characteristics.......................................................................... 11-4
11-2-2 Servomotor precision.................................................................................... 11-4
11-3 Selection of servomotor capacity...................................................................... 11-6
11-3-1 Load inertia ratio........................................................................................... 11-6
11-3-2 Short time characteristics.............................................................................. 11-6
11-3-3 Continuous characteristics............................................................................ 11-7
11-4 Selection of regenerative resistor..................................................................... 11-9
11-4-1 Limits for HS-MF23....................................................................................... 11-9
11-4-2 Approximate calculation of positioning frequency......................................... 11-9
11-4-3 Calculation of regenerative energy............................................................... 11-9
11-4-4 Calculation of positioning frequency............................................................. 11-11
11-5 Motor shaft conversion load torque.................................................................. 11-12
11-6 Expressions for load inertia calculation ........................................................... 11-13
iii

Chapter 1 Introduction

1-1 Intelligent servomotor outline.................................................................... 1-2
1-2 Limits and special notes for intelligent servomotor................................ 1-2
1-2-2 Precautions for selecting the intelligent servomotor........................... 1-2
1-2-2 Precautions for use............................................................................. 1-2
1-2-3 Miscellaneous ..................................................................................... 1-2
1-3 Inspection at purchase ............................................................................... 1-3
1-3-1 Explanation of type ............................................................................. 1-3
1–1
Chapter 1 Introduction
1-1 Intelligent servomotor outline
The Mitsubishi intelligent servomotor is an integrated motor, encoder and amplifier, and has the following features.
Space saving The amplifier does not need to be stored in the power distribution panel, so the machine, power distribution panel and heat exchanger can be downsized.
Wire saving Only one wire is used between the NC and motor. (The signal and 200VAC input are wired with the same cable.)
Flexible As an option axis can be added without changing the power distribution panel, variations can be easily added to the machine.
High-speed As the power distribution panel does not require space, the servo can easily be used for hydraulic and pneumatic devices.
1-2 Limits and special notes for intelligent servomotor
1-2-1 Precautions for selecting the intelligent servomotor
(1) The intelligent servomotor does not have the regenerative resistor option (the regenerative
resistor capacity cannot be increased.). Make sure that the regenerative energy is less than the tolerable regenerative capacity. Use the standalone HA/HC Series motor and MDS-B-V1/V2/SVJ2 Series servo amplifier for applications having a high regenerative energy due to a high positioning frequency or large load inertia, etc.
(2) The HS-MF23 type does not have a regenerative resistor. There may be limits to the working
rotation speed depending on the load inertia. Avoid using in applications generating continuous regeneration, such as with a vertical axis.
1-2-2 Precautions for use
(1) IP65 is recommended for the engagement of the HS-RF∗∗/SF∗∗ type connector. Make sure that
water or oil, etc., does not come in contact in the disengaged state.
(2) Connect the HS-MF type relay connector in a relay box having a structure (IP54) that prevents
the entry of water, oil and dust, etc. Fix the enclosed cable to the motor.
(3) A contact that released the brakes when the servo turns ON is built-in. The brakes will not be
released just by inputting the 24V power from an external source. If the brakes need to be released when assembling the machine, etc., refer to section 6-4. Wiring a motor with brakes.
1-2-3 Miscellaneous
(1) When the motor shaft is turned by hand, it may seem heavier than other servomotors, or may
seem tight. This is caused because of the dynamic brakes in the built-in amplifier, and is not a fault.
1–2
Chapter 1 Introduction
1-3 Inspection at purchase
Open the package, and read the rating nameplate to confirm that the servo amplifier and servomotor are as ordered.
1-3-1 Explanation of type
(1) Amplifier + motor integrated type
HS - oo ¡¡o o o o - So
Motor Series RF : Medium capacity, low inertia SF : Medium capacity, medium inertia MF : Small capacity, ultra-low inertia
Intelligent servomotor
¡¡: Short-time rated output (W/100) · o : Rotation speed (rpm/1000) 103: 1kW·3000r/min 202: 2kW·2000r/min 73: 0.75kW·3000r/min 102: 1kW·2000r/min 53: 0.5kW·3000r/min 52: 0.5kW·2000r/min 43: 0.4kW·3000r/min 23: 200W·3000r/min
Amplifier type EX: With amplifier/encoder for NC
Motor option B: Brakes provided Blank: No brakes
(2) Part types for separable amplifier and motor
1) Motor/encoder unit type
MDS - B - ISV ¡¡ o o
Intelligent servomotor amplifier/encoder
Amplifier type EX: With amplifier/encoder for NC
Short-time rated output (W/100) 20: 2kW 05: 0.5kW 10: 1kW 04: 0.4kW 07: 0.75kW
Amplifier/encoder special symbol (Cable length, etc.)
2) Motor only type
HS - oo ¡¡o o - so
Motor Series RF : Medium capacity, low inertia SF : Medium capacity, medium inertia
Intelligent servomotor
Motor option B: Brakes provided Blank: No brakes
¡¡: Short-time rated output (W/100) · o : Rotation speed (rpm/1000) 103: 1kW·3000r/min 202: 2kW·2000r/min 73: 0.75kW·3000r/min 102: 1kW·2000r/min 53: 0.5kW·3000r/min 52: 0.5kW·2000r/min 43: 0.4kW·3000r/min
Motor special symbol (Not provided with standard product)
Motor special symbol (Not provided with standard product)
Amplifier/encoder special symbol (Cable length, etc.)
Explanation of rating nameplate
1–3
Chapter 1 Introduction
Motor section type
Type
Amplifier/encoder section type and rated i nput/output
Current version
Serial No.
MITSUBISHI
TYPE
MOTORHS‑SF202 DRIVEUNITMDS‑B‑ISV‑20EX RATEDINPUT *3AC200‑230V50/60Hz 10.0A RATEDOUTPUT3AC11.0A
S/W BND516W000A7H/WVER.* SERIAL#XXXXXXXXXXX DATE00/01
MITSUBISHIELECTRICCORPORATIONJAPAN
*   X X  X  X  X X   X  X  X  X  X   *
INTELLIGENTSERVO
HS-SF202EX
1–4

Chapter 2 Specifications

2-1 Standard specifications............................................................................. 2-2
2-2 Torque characteristics............................................................................... 2-3
2-3 Outline dimension drawings ..................................................................... 2-4
2-3-1 HS-MF23............................................................................................ 2-4
2-3-2 HS-RF43/73....................................................................................... 2-4
2-3-3 HS-SF52/53/102/103 ......................................................................... 2-5
2-3-4 HS-SF202 .......................................................................................... 2-5
2–1
Chapter 2 Specifications
2-1 Standard specifications
(1) HS-MF, HS-RF Series (Low-inertia, small capacity/low-inertia, medium capacity)
Type HS-MF23 HS-RF43 HS-RF73
Short-time characteristics
Continuous characteristics
Maximum torque (N·m) 1.92 3.18 5.97 Rated rotation speed (r/min) 3000 Maximum rotation speed (r/min) 3000 Moment of inertia J (×10-4kg·m2) 0.089 0.8 1.5 Detector resolution/method 8,000/absolute value 100,000/absolute value
Power supply
Control method Sine wave PWM control, current control method Dynamic brakes Built-in Recommended load moment of inertia
rate Environment conditions Follows section 3-1-1 Environment conditions
Structure
Rated output (kW) 0.2/15min 0.4/30min 0.75/30min Rated torque (N·m) 0.64 1.27 2.39 Rated output (kW) 0.15 0.32 0.6 Rated torque (N·m) 0.48 1.02 1.91
Voltage/frequency 3-phase 200VAC to 230VAC 50/60Hz (HS-MF23 is single-phase) Tolerable voltage fluctuation 170 to 253VAC Tolerable frequency
fluctuation Power facility capacity (kVA) 0.5 0.9 1.3
4-fold or less when using cutting axis, 10-fold or less when using peripheral axis
Fully closed self-cooling: Protective structure IP65 (Excluding MF23 connector. Protection
applies for all connectors when engaged to machine.)
±5%
(2) HS-SF Series (medium-inertia, medium-capacity)
Type HS-SF52 HS-SF53 HS-SF102 HS-SF103 HS-SF202
Short-time characteristics
Continuous characteristics
Maximum torque (N·m) 11.8 8.82 21.6 16.7 41.7 Rated rotation speed (r/min) 2000 3000 2000 3000 2000 Maximum rotation speed (r/min) 2000 3000 2000 3000 2000 Moment of inertia J (×10-4kg·m2) 6.6 6.6 13.6 13.6 42.5 Detector resolution/method 100,000/absolute value
Power supply
Control method Sine wave PWM control, current control method Dynamic brakes Built-in Recommended load moment of inertia
rate Environment conditions Follows section 3-1-1 Environment conditions
Structure
Rated output (kW) 0.5/30min 0.5/30min 1.0/30min 1.0/30min 2.0/30min Rated torque (N·m) 2.39 1.59 4.78 3.18 9.55 Rated output (kW) 0.4 0.4 0.75 0.75 1.5 Rated torque (N·m) 1.91 1.27 3.58 2.39 7.16
Voltage/frequency 3-phase 200VAC to 230VAC 50/60Hz Tolerable voltage
fluctuation Tolerable frequency
fluctuation Power facility capacity
(kVA)
1.0 1.0 1.7 1.7 3.5
4-fold or less when using cutting axis, 10-fold or less when using peripheral axis
Fully closed self-cooling: Protective structure IP65
(Protection applies for connector section when engaged)
170 to 253VAC 50/60Hz
±5%
Note 1: The rated output and rated rotation speed are the guaranteed values in the 200 to 230VAC 50/60Hz range. The torque-speed
Note 2: Make sure that the acceleration/deceleration torque is within 80% of the maximum output torque. Note 3: Make sure that the continuous effective load torque is within 80% of the motor rated torque. Note 4: With the HS-MF23, if the recommended load moment of inertia rate is exceeded, an overvoltage alarm may occur because of
Note 5: Magnetic brakes are prepared for the 0.4KW and larger capacities. The HS-MF23 does not have brake specifications.
line diagram indicates the characteristics when 200VAC is input. Note that the high-speed characteristics will drop when the power voltage drops.
the speed and deceleration torque. (Refer to Chapter 11.)
2–2
2-2 Torque characteristics
3.0
[HS-MF23]
Chapter 2 Specifications
4.0
[HS-RF43]
8.0
[HS-RF73]
3.0
2.0
Intermittent operation range
TorqueNm
1.0
Short-time operation range
Continuous operation range
0
0
1000 2000 3000
Motor speed[r/min
2.0
TorqueNm
1.0
[HS-SF52]
10
Intermittent operation range
5
TorqueNm
Short-time operation range
Continuous operation range
0
0
1000 2000
Motor speed[r/min
10
TorqueNm
Intermittent operation range
Short-time operation range
Continuous operation range
0
0
1000 2000
Motor speed[r/min
[HS-SF53]
Intermittent operation range
5
Short-time operation range
Continuous operation range
0
0
1000 2000 3000
Motor speed[r/min
3000
6.0
Intermittent operation range
4.0
TorqueNm
Short-time operation range
2.0
0
0
Motor speed[r/min
20
10
TorqueNm
Short-time operation range
0
0 1000
Motor speed[r/min
Continuous operation range
1000 2000
[HS-SF102]
Intermittent operation range
Continuous operation range
3000
2000
[HS-SF103]
20
10
TorqueNm
Short-time operation range
0
0
Intermittent operation range
Continuous operation range
1000 2000 3000
Motor speed[r/min
40
20
TorqueNm
0
0 1000
[HS-SF202]
Intermittent operation range
Short-time operation range
Continuous operation range
Motor speed[r/min
2000
2–3
Chapter 2 Specifications
60
±5
2-3 Outline dimension drawings
2-3-1 HS-MF23
640±30
56.5 18
108
178
4
2.5
Cross-section
4
Φ11h6
A-A
2-3-2 HS-RF43/73
Φ27
101
82
118
93
With oil seal
0
-0.03
5
54.3
108.00
Cross-section
A-A
Connector
JL04V-2A28-11PE
L
10
3
With oil seal
25
7
3
45°
16304
A
Φ50h7
A
A
φ 70
23.3
100
173.5
75
LL
18
Changed dimensions Model L LL
HS-RF43 400W 86 204 HS-RF43B 400W with brakes In planning stages HS-RF73 750W 104 222 HS-RF73B 750W with brakes In planning stages
2–4
A
φ16.000
A
Taper 1/10
28
φ22
φ
115
135
φ
45
4-φ9
100
φ95h7
A
12
2-3-3 HS-SF52/53/102/103
96
216
Changed dimensions Model L LL
HS-SF53/52 500W 87 232 HS-SF53/52B 500W with brakes 119 270 HS-SF103/102 1kW 112 257 HS-SF103/102B 1kW with brakes 144 295
2-3-4 HS-SF202
Chapter 2 Specifications
145 L
5
L
Cross section
A-A
70
LL
0
-0.03
23.3
5
4.25
4.3
12
3
φ 165
25
A
φ16.000
22
φ
A
A
Taper
1/10
18
28 12
58
110h7
φ 145
130
130
45°
79
45°
119
70
18
3
75
0
+0.010
φ35
264
0
-0.025
φ114.3
φ
200
φ
LL
230
176
Changed dimensions Model L LL
HS-SF202 2kW 116 270 HS-SF202B 2kW with brakes In planning stages
2–5

Chapter 3 Characteristics

3-1 Overload protection characteristics.......................................................... 3-2
3-2 Magnetic brake characteristics.................................................................. 3-3
3-2-1 Motor with magnetic brakes................................................................ 3-3
3-2-2 Magnetic brake characteristics ........................................................... 3-4
3-2-3 Magnetic brake power supply............................................................. 3-4
3-3 Dynamic brake characteristics................................................................... 3-5
3-3-1 Deceleration torque............................................................................. 3-5
3-3-2 Coasting amount................................................................................. 3-6
3–1
Chapter 3 Characteristics
95% of amplifier or motor
3-1 Overload protection characteristics
The servo amplifier has an electronic thermal relay to protect the servomotor and servo amplifier from overloads. The operation characteristics of the electronic thermal relay when standard parameters (SV021=60, SV022=150) are set shown below. If overload operation over the electronic thermal relay protection curve shown below is carried out, overload 1 (alarm 50) will occur. If the maximum current is commanded at 95% or higher continuously for one second or more due to a machine collision, etc., overload 2 (alarm 51) will occur.
1000.0
100.0
10.0
Operation time [sec]
1.0
0.1
0.1
0 50 100 150 200 250 300 350 400
When stopped
Motor load rate [%]
When rotating
maximum capacity
Fig. 3-1 Overload protection characteristics
3–2
Chapter 3 Characteristics
3-2 Magnetic brake characteristics
1. The axis will not be mechanically held even when the dynamic brakes are used. If the machine could drop when the power fails, use a servomotor with magnetic brakes or provide an external brake mechanism as holding means to prevent dropping.
2. The magnetic brakes are used for holding, and must not be used for normal braking. There may be cases when holding is not possible due to the life or
CAUTION
machine structure (when ball screw and servomotor are coupled with a timing belt, etc.). Provide a stop device on the machine side to ensure safety. When releasing the brakes, always confirm that the servo is ON first. Sequence control considering this condition is possible if the amplifier motor brake control signal (MBR) is used.
3. When operating the brakes, always turn the servo OFF (or ready OFF).
4. When the vertical axis drop prevention function is used, the drop of the vertical axis during an emergency stop can be suppressed to the minimum.
3-2-1 Motor with magnetic brakes
(1) Types
The motor with magnetic brakes is set for each motor. The "B" following the standard motor type indicates the motor with brakes.
(2) Applications
When this type of motor is used for the vertical feed axis in a machining center, etc., slipping and dropping of the spindle head can be prevented even when the hydraulic balancer's hydraulic pressure reaches zero when the power turns OFF. When used with a robot, deviation of the posture when the power is turned OFF can be prevented. When used for the feed axis of a grinding machine, a double safety measures is formed with the deceleration stop (dynamic brake stop), and the risks of colliding with the grinding stone and scattering can be prevented. This motor cannot be used for purposes other than holding and braking during a power failure (emergency stop). (This cannot be used for normal deceleration, etc.)
(3) Features
1) The magnetic brakes use a DC excitation method, thus:
• The brake mechanism is simple and the reliability is high.
• There is no need to change the brake tap between 50 Hz and 60 Hz.
• There is no rush current when the excitation occurs, and shock does not occur.
• The brake section is not larger than the motor section.
2) The magnetic brakes are built into the motor, and the installation dimensions are the same as the motor without brakes.
3–3
Chapter 3 Characteristics
3-2-2 Magnetic brake characteristics
HS-RF Series HA-SF Series
Item
Type (Note 1) Spring braking type safety brakes Rated voltage 24VDC Rated current at 20°C (A) Excitation coil resistance at 20°C () Capacity (W) 9.9 19.2 19.2 Attraction current (A) 0.20 0.25 0.25 Dropping current (A) 0.12 0.085 0.08 Static friction torque (N·m) 2.4 6.8 8.5 Moment of inertia (Note 2) J (×10–4kg·m2) 0.26 0.35 2.0 Release delay time (sec) (Note 3) 0.03 0.03 0.03 Tolerable braking work amount
(J) Brake play at motor axis (deg.) 0.1 to 0.9 0.2 to 0.6 0.2 to 0.6
Brake life (Note 4)
Per braking 64 400 400 Per hour 640 4000 4000
20,000 times with 32 (J)
43B 73B
0.41 0.8 0.8 58 30 30
braking amount
per braking
53B 52B 103B 102B
20,000 times with 200 (J)
braking amount
per braking
20,000 times with 200 (J)
202B
braking amount
per braking
Notes:
1. There is no manual release mechanism. Refer to section "6-4-2 Manually releasing the magnetic brakes".
2. These are the values added to the servomotor without brakes.
3. This is the value for 20°C at the initial attraction gap.
4. The brake gap will widen through brake lining wear caused by braking. However, the gap cannot be adjusted. Thus, the brake life is reached when adjustments are required.
5. A leakage flux will be generated at the shaft end of the servomotor with magnetic brakes.
6. When operating in low speed regions, the sound of loose brake lining may be heard. However, this is not a problem in terms of function.
7. The brake characteristics for the HS-RF Series and HS-SF202 are the planned values.
3-2-3 Magnetic brake power supply
(1) Brake excitation power supply
1) Prepare a brake excitation power supply that can accurately ensure the attraction current in consideration of the voltage fluctuation and excitation coil temperature.
2) The brake terminal polarity is random. Make sure not to mistake the terminals with other circuits.
(2) Brake excitation circuit
<Cautions>
Provide sufficient DC cut off capacity at the contact.
Always use a serge absorber.
3–4
Chapter 3 Characteristics
3-2 Dynamic brake characteristics
When an emergency stop occurs such as that due to a servo alarm detection, the motor will stop with the deceleration control at the standard setting. However, by setting the servo parameter (SV017: SPEC), the dynamic brake stop can be selected. If a servo alarm that cannot control the motor occurs, the dynamic brakes stop the servomotor regardless of the parameter setting.
3-3-1 Deceleration torque
The dynamic brakes use the motor as a generator, and obtains the deceleration torque by consuming that energy with the dynamic brake resistance. The characteristics of this deceleration torque have a maximum deceleration torque (Tdp) regarding the motor speed as shown in the following drawing. The torque for each motor is shown in the following table.
dp
T
Deceleration torque
dp
0
N
Motor speed
Fig. 3-2 Deceleration torque characteristics of a dynamic brake stop
Table 3-1 Max. deceleration torque of a dynamic brake stop
Motor type
HS-MF23 0.64 0.40 465 HS-SF52 2.39 2.40 496 HS-RF43 HS-SF53 1.59 2.54 472 HS-RF73 3.18 3.67 582 HS-SF102 4.78 11.19 884 HS-SF103 3.18 10.72 1045 HS-SF202 9.55 10.56 457
Rated torque
(N·m)
Tdp (N•m) Ndp (r/min) Motor type
Rated torque
(N·m)
Tdp (N•m) Ndp (r/min)
3–5
Chapter 3 Characteristics
t
OFF
3-3-2 Coasting amount
The motor coasting amount when stopped by a dynamic brake can be approximated using the following expression.
CMAX =
No 60
CMAX : Maximum motor coasting amount (turn) No : Initial motor speed (r/min) JM : Motor inertia (kg·cm2) JL : Motor shaft conversion load inertia (kg·cm2) te : Brake drive relay delay time (sec) (Normally, 0.03sec) A : Coefficient A (Refer to the table below) B : Coefficient B (Refer to the table below)
Emergency stop (EMG)
Motor brake control output
Motor brake actual operation
Table 3-2 Coasting amount calculation coefficients
Motor
type
HS-MF23 0.088 1.38 × 10 HS-RF43 0.8 2.04 × 10 HS-RF73 1.5 2.04 × 10
JM
(kg·cm2)
· te + ( 1 +
Motor speed
Initial speed: No
Fig. 3-3 Dynamic brake braking diagram
A B Motor type
–11
0.90 × 10–5 HS-SF52 6.6 16.13 × 10
–11
2.07 × 10–5 HS-SF53 6.6 15.99 × 10
–11
2.07 × 10–5 HS-SF102 13.6 4.00 × 10
L
J
) · (A · No3 + B · No)
M
J
OFF
OFF
e
HS-SF103 13.6 3.53 × 10 HS-SF202 42.5 25.60 × 10
Coasting amount
JM
(kg·cm2)
Time
A B
–11
11.93 × 10–5
–11
10.71 × 10–5
–11
9.38 × 10–5
–11
11.58 × 10–5
–11
16.07 × 10–5
3–6

Chapter 4 Peripheral Devices

4-1 Dedicated options....................................................................................... 4-2
4-1-1 I/F unit................................................................................................. 4-2
4-1-2 Battery option for absolute position system........................................ 4-6
4-1-3 Cables and connectors....................................................................... 4-7
4-1-4 Cable clamp fitting .............................................................................. 4-11
4-2 Peripheral devices....................................................................................... 4-12
4-2-1 Selection of wire.................................................................................. 4-12
4-2-2 Selection of no-fuse breakers............................................................. 4-12
4-2-3 Selection of contactor ......................................................................... 4-13
4-2-4 Circuit protector................................................................................... 4-14
4–1
Chapter 4 Option and Peripheral Devices
Always wait at least 10 minutes after turning the power OFF, and check the
DANGER
voltage with a tester, etc., before connecting the option or peripheral device. Failure to observe this could lead to electric shocks.
CAUTION
Use the designated peripheral device and options. Failure to observe this could lead to faults or fires.
4-1 Dedicated options
4-1-1 I/F unit
Name Intelligent servomotor I/F unit
Type HS-IF-6 Maximum number of connected
axes Input power voltage AC200 to 230V 50/60Hz
Functions Miscellaneous Surge absorber, radio noise filter, internal 5V power
Ambient temperature 0°C to +55°C (with no freezing) Ambient humidity 90% RH or less (with no dew condensation)
Environ-me nt conditions
Outline dimensions H: 300 × W: 80 × D: 80 (refer to following drawings)
Storage temperature –20°C to +65°C (with no freezing) Storage humidity 90% RH or less (with no dew condensation) Atmosphere Indoors (not subject to direct sunlight). No corrosive gases, flammable gases, oil mist or dust Altitude 1000m or below sea level Vibration 5.9m/sec2 or less
(The total number of connected axes follows the NC unit specifications)
Serial bus interface between NC and intelligent servomotor
200VAC branching to main circuit and control power circuit
(1) Outline drawing
Maximum 6 intelligent servomotor axes
300
285
2-M3 screw
For grounding plate installation
80
80
4–2
Chapter 4 Option and Peripheral Devices
インテリジェントサーボ
左より第1軸、第2軸、・・・
(2) Explanation of each part
CN1B
CN1B
Servo/spindle drive
サーボ・主軸ドライブ
CN1A
CN1A
From NC
NCより
CN11
CN11 Intelligent servomotor 1st axis
インテリジェントサーボモータ第1軸
CN12
CN12 Intelligent servomotor 2nd axis
インテリジェントサーボモータ第2軸
CN13
CN13
Intelligent servomotor 3rd axis
インテリジェントサーボモータ第3軸
Alarm display LED
アラーム表示LED
1st axis, 2nd axis, to 6th axis, CN1B connection axis from
第6軸、CN1B接続軸
left.
SW7
SW7
Servo monitor D/A output
サーボモニタD/A出力
changeover switch
切替スイッチ
Always set to ON (left) when starting up.
立ち上げ時は必ずON (左)として下さい。
SW1 to SW3
SW1〜SW3
Usage/non-usage setting
各々CN11〜CN13の
switch for CN11 to CN13.
使用/未使用設定スイッチ
Set switch to right for connected axis, and to left for
接続軸はスイッチを右へ未
disconnected axis.
接続軸は左として下さい。
CN14
CN14
Intelligent servomotor 4th axis
インテリジェントサーボモータ第4軸
CN15
CN15 Intelligent servomotor 5th axis
インテリジェントサーボモータ第5軸
CN16
CN16 Intelligent servomotor 6th axis
インテリジェントサーボモータ第6軸
L1 L2 L3
L1 L2 L3
L11 L12
L11 L12
PE
PE
SW4 to SW6
SW4〜SW6
Usage/non-usage setting
各々CN11〜CN13の
switch for CN11 to CN13.
使用/未使用設定スイッチ
Set switch to right for connected axis, and to left for
接続軸はスイッチを右へ未
disconnected axis.
接続軸は左として下さい。
TE1 to TE6
TE1〜TE6
Intelligent servomotor terminal block.
モータ用端子台
* The drawing shows the state
with the terminal block cover
*図は端子台カバーを
removed.
はずしたときのもので
TE7
TE7
200VAC
AC200V
Input terminal block
入力端子台
4–3
Chapter 4 Option and Peripheral Devices
(3) Signal wire connection and switch settings
1) Connector connection
Connect the cable from the NC unit to CN1A. The servo/spindle drive other than the
intelligent servomotor is connected to CN1B. If there is no servo/spindle drive, connect the battery unit or terminator.
The intelligent servomotor axis No. is set according to the I/F unit connector connection site.
Connect to the correct connector.
2) Switch setting
Set the setting switches SW1 to SW6 according to whether CN11 to CN16 are used or not.
SW7 is the servo monitor D/A output changeover switch, so normally set it to the left position. Set it to the right when using the D/A output function. Note that when the power is turned ON, this switch must be set to the left or the "Amplifier Not Mounted" alarm will occur.
(4) Power supply connection
1) Explanation of terminal block
Connect the 200VAC power to TE7. The intelligent servomotor's power wires are connected to TE1 to TE6. The TE1 to TE6
connection order is random, but connect from TE6 in order from the motor with the larger capacity.
The connections are L1, L2, L3 (main power), L11, L12 (control circuit power), and PE from
the left on each terminal block.
2) Wire end treatment
Single wire : Peel the wire sheath and use the wire.
Peeling length
Stranded wire : Peel the wire sheath and twist the core wires before using. Take care to prevent short-circuiting with the
A
neighboring poles caused by fine wire strands. Do not solder onto the core wires as a contact fault could occur. (Wire size: 0.25 to 2.5mm2)
Wire size Single wire Stranded wire
Peeling length
A (mm)
TE7 0.2 to 6mm2 0.2 to 4mm2 8 TE1 to TE6 0.2 to 1.5mm2 0.2 to 1.5mm2 10
3) Connection method
TEL7 (200VAC power supply) TE1 to 6 (intelligent servomotor)
Insert the wire, and tighten the terminal with a flat-tip screwdriver. The tightening torque is 0.5 to 0.6Nm.
Insert the wire while pressing the terminal block lever. The wire will be fixed when the lever is released.
4–4
Chapter 4 Option and Peripheral Devices
4) Total capacity of connected motors
The total capacity of the motors that can be connected to the HS-IF-6 main power terminal block is 6kW or less. If the total motor capacity exceeds 6kW, wire with a standalone terminal block.
HS motor
Terminal block
(5) D/A output measurement methods
1) Remove the upper cover from the I/F uni t.
2) Connect a measuring instrument to the I/F unit check pin.
Refer to the drawing on the right
for the connection sections.
3) When observing the waveform,
turn the I/F unit's servo monitor
#1 1st axis display
#2 2nd axis display
#3 3rd axis display
#4 4th axis display
D/A output changeover switch to OFF (right).
4) Select the data to be measured
with the parameters. (Refer to section "8-1. Measuring the
#7 CN1B connection axis display
#6 6th axis display
#5 5th axis display
Servo monitor D/A output changeover switch
adjustment data".)
CAUTION
Always turn the DIP switch ON before turning the power ON. Do not connect a measuring instrument having a low input impedance when turning the power ON. The "Amplifier Not Mounted" alarm will occur.
D/A output grounding terminal
4th axis D/A output terminal
(6) Alarm display LED
6th axis D/A output terminal
The alarm display LED holds the state of each axis alarm when an alarm or emergency stop occurs. Use this to pinpoint the cause when an emergency stop state occurs due to a cable or amplifier fault. The display of each LED will change as shown below.
#1 #2 #3 #4 #5 #6 #7
When 200VAC is turned ON Not set Not set Not set Not set Not set Not set Not set After NC starts Not ON Not ON Not ON Not ON Not ON Not ON Not ON Emergency stop occurrence from NC side Not ON Not ON Not ON Not ON Not ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 1st axis ON Not ON Not ON Not ON Not ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 2nd axis Not ON ON Not ON Not ON Not ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 3rd axis Not ON Not ON ON Not ON Not ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 4th axis Not ON Not ON Not ON ON Not ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 5th axis Not ON Not ON Not ON Not ON ON Not ON Not ON Emergency stop occurrence from intelligent servomotor 6th axis Not ON Not ON Not ON Not ON Not ON ON Not ON
4–5
HS-IF-6
Alarm display LED
1st axis D/A output terminal
2nd axis D/A output terminal
3rd axis D/A output terminal
5th axis D/A output terminal
Chapter 4 Option and Peripheral Devices
Emergency stop occurrence from servo/spindle connected to CN1B Not ON Not ON Not ON Not ON Not ON Not ON ON
4–6
Chapter 4 Option and Peripheral Devices
4-1-2 Battery option for absolute position system
A battery or battery unit must be provided for the absolute position system.
Battery option specifications
Item Battery unit
Type MDS-A-BT2 MDS-A-BT4 MDS-A-BT6 MDS-A-BT8 No. of backup axes 2 axes 4 axes 6 axes 7 axes Battery continuous back up time Approx. 12,000 hours Battery useful life 7 years from date of unit manufacture
Data save time during battery replacement
Back up time from battery warning to alarm occurrence
The battery life will be greatly affected by the ambient temperature. The above data shows the theoretic values for when the ambient temperature of the
CAUTION
battery is 25°C. If the ambient temperature rises, generally the back up time and useful life will be shorter.
<Outline dimension drawing>
MDS-A-BT2 MDS-A-BT4 MDS-A-BT6 MDS-A-BT8
HS-MF : 2 hours at time of delivery, 1 hour after 5 years HS-RF, -SF : 20 hours at time of delivery, 10 hour after 5 years
Approx. 100 hours
ø6 Use an M5 screw for the installation.
3 5
3 4
1 45
1 35
1 5
9
R30
1 5
3 0
1 00
<Connection>
Instead of the terminator, connect the battery unit to the final drive unit with the amplifier-amplifier bus cable.
1 60
Unit (mm)
4–7
Chapter 4 Option and Peripheral Devices
4-1-3 Cables and connectors
(1) Cable list
Part name Type Descriptions
Communication cable for CNC unit - Amplifier Amplifier - Amplifier
For I/F unit
Terminator connector A-TM
For HS-MF between intelligent servomotor and I/F unit
For intelligent servo-moto r
For HS-RF and HS-SF between intelligent servomotor and I/F unit
(2) Cable wiring diagram
For MS-MF For HS-RF/SF
I/F unit (power distribution panel)
Signal
side
name
TXD TXD* RXD RXD* ALM ALM* EMG EMG* MON LG BAT
SD
L1
L2
PE
L11
L12
2
12
4
14
3
13
7
17
8 5 9
Plate
brown
blue
green/yellow
gray
white
SH21 Length:
0.35, 0.5, 0.7, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 6, 7, 8, 9, 10, 15, 20, 30m
HSMF-CABL-o-oM
HSSFo-CABL-o-oM
Axis No. Blank: No display 1: 1st axis : 6: 6th axis
Motor side connector 2: Straight 3: Right angle
Length (m)
Length (m) Axis No. Blank: No display 1: 1st axis : 6: 6th axis
Motor side
A1 B1 A2 B2 A4 B4 A3 B3 A6 B5 A5
B6 A1
B1
B2
A3
B3
Servo amplifier side connector (Sumitomo 3M) 10120-6000EL (Connector) 10320-3210-000 (Shell kit)
I/F unit side connector (Sumitomo 3M) 10120-3000VE (Connector) 10320-52A0-008 (Shell kit)
I/F unit side connector (Sumitomo 3M) 10120-3000VE (Connector) 10320-52A0-008 (Shell kit)
I/F unit (power distribution panel)
Signal
side
name
TXD TXD* RXD RXD* ALM ALM* EMG EMG* MON LG BAT
SD
BR RG
L1
L2
L3
PE
L11
2
12
4
14
3
13
7
17
8 5 9
Plate
yellow/green
Servo amplifier side connector (Sumitomo 3M) 10120-6000EL (Connector) 10320-3210-000 (Shell kit)
Servomotor side connector (Japan AMP)
178289-3 (Housing for power supply) 178289-6 (Housing for signal) 1-917511-5 (Contact for L1, L2, PE) 1-175217-5 (Contact for L11, L12, signal)
Servomotor side connector (Japan Aviation)
JI04V-6A28-11SE-EB (Straight) or JI04V-8A28-11SE-EB (Angle) JL04-2428CK (Clamp)
brown
blue
black
Motor side
A E B F D H C G X T I
W R
J
K
L
M
N
L12
U
4–8
Chapter 4 Option and Peripheral Devices
(3) Usage cables
The following cables are available as the compound cables for both signals and power supply.
(1) Part name: MIX20C(30/-SV,40/,7/36/0.08)-V Maker: Oki Electric Cable Co., Ltd. (2) Part name: MIX19C(19,30,150/0.08)-V Maker: Oki Electric Cable Co., Ltd.
Use the (1) cable for a capacity of 1kW or more.
(4) Connector outline drawing
For IF unit
Maker: Sumitomo 3M (Ltd.) <Type> Connector: 10120-3000VE Shell kit: 10320-52F0-008
[Unit: mm]
12.0
10.0
Maker: Sumitomo 3M (Ltd.) <Type> Connector: 10120-6000EL Shell kit: 10320-3210-000
This connector is not an option. It is integrated with the cable.
22.0
39.0
23.8
33.3
14.0
12.7
[Unit: mm]
11.5
20.9
42.0
33.0
29.7
4–9
Chapter 4 Option and Peripheral Devices
10 or
Conduit installation
10 or more
(spanner catching width)
Screw
(Effective screw
(Spanner catching width)
Screw (Clamp range)
Bushing
Screw
For intelligent servomotor HS-RF/HS-SF
Single block Maker: Japan Aviation Type: JL04V-6A28-11SE
[Unit: mm]
Positioning key
Screw
Straight plug Maker: Japan Aviation Type: JL04V-6A28-11SE-EB
Angle plug Maker: Japan Aviation Type: JL04V-8A28-11SE-EB
[Unit: mm]
[Unit: mm]
Positioning key
Positioning key
dimensions
(Effective screw length)
less
1-7/46-18UNEF-2A
Cable clamp Maker: Japan Aviation Type: JL04V-2428CK (17)
Applicable cable diameter: ø15 to ø18
1-7/16-18UNEF-2A
length)
[Unit: mm]
1-7/16-18UNEF-2B
4–10
Chapter 4 Option and Peripheral Devices
Connector for intelligent servomotor HS-MF
Maker: Japan AMP <Type> For power supply 6-pole receptacle/housing: 178289-3 Contact: 1-917511-5 (L1, L2, PE) 1-175217-5 (L11, L12)
For signal 12-pole receptacle/housing: 178289-6 Contact: 1-175217-5
No. of poles
6 178289-3 24.36 16.70
12 178289-6 35.09 28.35
Type
Dimension
A B
[Unit: mm]
Row A
5.08
3.81
Circuit number 1
A
16.3
Row B
Row B
22.8
Row A
B
11.63
(5) Communication cable assembly
Assemble the cable as shown in the following drawing, with the cable shield wire securely
connected to the ground plate of the connector.
Cor e wire
Shield (external conductor)
Sheath
Core wi re
Shiel d (external conductor)
Sheath
Ground plate
When folding back the shield, fold back the shield over an area covered with vinyl tape or copper tape, and seat onto the fitting surface of the plate screw section so that the shield wire and grounding plate securely contact without play.
CAUTION
Take care not to mistake the connection when manufacturing the cable. Failure to observe this could lead to faults, runaway or fire.
4–12
Chapter 4 Option and Peripheral Devices
4-1-4 Cable clamp fitting
Use the following types of grounding plate and cable clamp fitting to strengthen the noise resistance of the communication cable. The grounding plate can be installed onto the terminal block cover of the I/F unit (HS-IF-6). Peel part of the cable sheath as shown in the drawing to expose the shield sheath, and press that section against the grounding plate with the cable clamp fitting.
Grounding plate
Grounding plate (E) outline
70 24
17.5
Cable clamp
fitting A, B
Grounding bar
Shield sheath
Cable clamp fitting outline
6
2-φ5 hole
Installation hole
35
30
10MAX L
6 22
56
3
M4 screw *
11
* Always wire the grounding wire from the grounding plate to the
cabinet grounding plate.
4–13
L
Fitting A 70 Fitting B 45
24
Chapter 4 Option and Peripheral Devices
4-2 Peripheral devices
4-2-1 Selection of wire
Select the interface unit L1, L2, L3 and grounding wires from the following wire sizes according to the total capacity of the connected motors.
Total motor capacity 1kW or less 2.5kW or less 6kW or less 9kW or less 12kW or less
Wire size (mm2) IV1.25SQ IV2SQ IV3.5SQ IV5.5SQ IV8SQ
(Note) The total capacity of the motors connected to the interface unit must be 6kW or less. If the
total motor capacity exceeds 6kW, wire with a standalone terminal block.
4-2-2 Selection of no-fuse breakers
Use the following table to obtain the NFB (no-fuse breaker) rated current from the total rated capacity (SVJ2 total output capacity) of the motor driving the SVJ2 servo amplifier to be connected to the NFB to be selected, and select the no-fuse breaker. When the MDS-B-SPJ2 spindle amplifier or converter unit will share no-fuse breakers, select from the total NFB rated current of each SVJ2 total output capacity and SPJ2 spindle amplifier or convertor unit. However, separate the SVJ2 servo amplifier no-fuse breaker from the others, and select the NF60 type (60A) or smaller capacity dedicated for SVJ2 servo amplifiers if the total NFB rated current exceeds 60A.
NFB rated current table
Intelligent servomotor SVJ2 total output capacity
NFB rated current 10A 20A 30A 40A 50A 60A
MDS-B-SPJ2-02
MDS-B-SPJ2
Converter unit
NFB rated current 10A 20A 30A 40A 50A
NFB rated current 10A 20A 30A 40A 50A 60A Recommended NFB
(Mitsubishi Electric Corp.: Option part)
Special order part: This part is not handled by the NC Dept. Marketing Section or dealer.
(Example 1)
MDS-B-SPJ2-04 MDS-B-SPJ2-075 MDS-B-SPJ2-15
MDS-A-CR-10 MDS-A-CR-15
The NFB is selected for the MDS-B-SVJ2-10 with three HS-SF102 axes and one MDS-B-SPJ2-75 axis connected.
1.5kW or less 3.5kW or less 7kW or less 10kW or less 13kW or less 16kW or less
MDS-B-SPJ2-22 MDS-B-SPJ2-37
MDS-A/B-CV-37 MDS-A-CR-22 MDS-A-CR-37
MDS-B-SPJ2-55 MDS-B-SPJ2-75 MDS-B-SPJ2-110
MDS-A/B-CV-55 MDS-A-CR-55
MDS-A/B-CV-75 MDS-A-CR-75
MDS-A-CR-90 MDS-A/B-CV-110
No-fuse breaker selection table
NF30-CS3P10A NF30-CS3P20A NF30-CS3P30A NF50-CP3P40A NF50-CP3P50A NF60-CP3P60
A
Because there are 1kW × 3 = 3kW on the intelligent servomotor side, 20A is selected from the table for the NFB rated current. 40A is selected from the table for the SPJ2-75 rated current. Therefore, the total rated current is 60A, and the NF60-CP3P60A is selected.
(Example 2)
The NFB is selected for the MDS-B-SVJ2-20 with two HS-SF202 axes and one MDS-B-CR-90 connected.
Because there are 2kW × 2 = 4kW on the intelligent servomotor side, 30A is selected from the table for the NFB rated current. 50A is selected from the table for the MDS-B-CV-90 rated current. Therefore, the total rated current is 80A. The NFB is separated from converter unit, and the NF30-CS3P30A is selected for the SVJ2. (Refer to the "MDS-A/B Series Specifications Manual" for details on selecting the converter NFB.)
4–14
Chapter 4 Option and Peripheral Devices
Install independent no-fuse breakers and contactors as the SVJ2 main circuit power supply if the total current capacity exceeds 60A when the power supply is shared between the converter and a large capacity SPJ2 spindle amplifier.
DANGER
No-fuse breakers may not operate for short-circuits in small capacity amplifiers if they are shared with a large capacity unit, and this could cause fires. Select a capacity of NF60 or less for the intelligent servomotor and SVJ2 servo amplifier.
4-2-3 Selection of contactor
Select the contactor based on section "(1) Selection from rush current" when the system connected to the contactor to be selected is intelligent servomotor, an MDS-B-SVJ2 servo amplifier and 3.7kW or less MDS-B-SPJ2 spindle amplifier. When a converter unit or 5.5kW or more MDS-B-SPJ2 spindle amplifier is included, calculate both the capacities in sections "(1) Selection from rush current" and "(2) Selection from input current", and select the larger of the two capacities.
(1) Selection from rush current
Use the following table to select the contactors so the total rush current for each unit does not
Special order part: This part is not handled by the NC Dept. Marketing Section or dealer.
< Selection only from rush current >
exceed the closed circuit current amount.
Rush current table
Intelligent servomotor
Rush current 45A 100A
MDS-B-SVJ2
Rush current 45A 50A 70A 100A
MDS-B-SPJ2
Rush current 45A 50A 100A 15A
Converter unit
Rush current 15A 40A
HS-RF43, HS-RF73 HS-SF52, HS-SF53
MDS-B-SVJ2-01 MDS-B-SVJ2-03 MDS-B-SVJ2-04
MDS-B-SPJ2-02 MDS-B-SPJ2-04
MDS-A-CR-10 to MDS-A-CR-90
MDS-A/B-CV-37 to MDS-A/B-CV-75
MDS-B-SVJ2-06 MDS-B-SVJ2-07
MDS-B-SPJ2-075
HS-MF23 HS-SF102, HS-SF103 HS-SF202
MDS-B-SPJ2-15 MDS-B-SPJ2-22 MDS-B-SPJ2-37
MDS-A/B-CV-110
Contactor selection table 1
Contactor closed current capacity (Total rush current)
Recommended contactor (Mitsubishi Electric Corp.: Option part)
110A 200A 220A 300A 400A 550A 650A 850A
S-N10
AC200V
S-N18
AC200V
S-N20
AC200V
S-N25
AC200V
S-N35
AC200V
S-K50
AC200V
(Example 1)
The contactor is selected for the MDS-B-SVJ2-10 with three HS-SF102 axes and one MDS-B-SPJ2-37 axis connected.
(HS-SF102 × 3 axes rush current) + (SPJ2-37 × 1 axis rush current) = 3 × 100A + 1 × 100A = 400A Therefore, S-N35 200VAC is selected.
MDS-B-SVJ2-10 MDS-B-SVJ2-20
MDS-B-SPJ2-55 MDS-B-SPJ2-75
MDS-B-SPJ2-110
S-K65
AC200V
S-K80
AC200V
4–15
Chapter 4 Option and Peripheral Devices
(2) Selection from input current
Use the following table to select the contactors so the total input current for each unit does not exceed the rated continuity current.
Input current table
Intelligent servomotor
MDS-B-SVJ2 total output
capacity
Input current 10A 20A 30A 40A 50A 60A
1.5kW or less 3.5kW or less 7kW or less 10kW or less 13kW or less 16kW or less
MDS-B-SPJ2-02
MDS-B-SPJ2
Input current 10A 20A 30A 40A 50A
MDS-B-SPJ2-04
MDS-B-SPJ2-075
MDS-B-SPJ2-15
MDS-B-SPJ2-22 MDS-B-SPJ2-37
MDS-B-SPJ2-55 MDS-B-SPJ2-75 MDS-B-SPJ2-110
Converter unit
Input current 10A 20A 30A 40A 50A
MDS-A-CR-10 MDS-A-CR-15
MDS-A/B-CV-37
MDS-A-CR-22 MDS-A-CR-37
MDS-A/B-CV-55
MDS-A-CR-55
Contactor selection table 2
Contactor rated continuity current (Total input current)
Recommended contactor (Mitsubishi Electric Corp.: Option part)
Special order part: This part is not handled by the NC Dept. Marketing Section or dealer.
(Example 2)
20A 32A 50A 60A
S-N10
AC200V
S-N20
AC200V
The contactor is selected for the MDS-B-SVJ2-10 with four HS-SF102 axes and one MDS-B-CV-55 connected.
< Selection from rush current >
(HS-SF102 × 4 axes rush current) + (MDS-B-CV-55 rush current) = 4 × 100A + 15A = 415A Therefore, S-K50 200VAC.
< Selection from input current >
(JS-SF102 × 4 axes input current) + (MDS-B-CV-55 input current) = 30A + 30A = 60A Therefore, S-N35 200VAC. From these, the S-K50 200VAC is selected as having the larger of the two capacities.
4-2-4 Circuit protector
MDS-A/B-CV-75
MDS-A-CR-75
S-N25
AC200V
MDS-A-CR-90
MDS-A/B-CV-110
S-N35
AC200V
When installing a circuit protector dedicated for the control power input, use a circuit protector with inertial delay to prevent malfunctioning in respect to the rush current generated when the power is turned ON. The size and conductivity time of the rush current fluctuate according to the power supply impedance and potential.
Recommended circuit
Servo amplifier Rush current
Intelligent servomotor 70 to 130A 0.5 to 1msec Rated current 0.2A per axis
Conductivity
time
protector
(Mitsubishi Electric
Corp.: Option part)
Special order part: This part is not handled by the NC Department Marketing Section or dealer.
CP30-BA type with
medium-speed inertial delay
4–17

Chapter 5 Installation

5-1 Installation of servomotor.......................................................................... 5-3
5-1-1 Environmental conditions.................................................................... 5-3
5-1-2 Cautions for mounting load (prevention of impact on shaft) ............... 5-3
5-1-3 Installation direction .......................................................................... 5-3
5-1-4 Tolerable load of axis.......................................................................... 5-4
5-1-5 Oil and waterproofing measures......................................................... 5-4
5-1-6 Cable stress........................................................................................ 5-5
5-2 Installation of interface unit ....................................................................... 5-6
5-2-1 Environmental conditions.................................................................... 5-6
5-2-2 Installation direction............................................................................ 5-6
5-2-3 Prevention of entering of foreign matter.............................................. 5-6
5-3 Noise measures........................................................................................... 5-7
5–1
Chapter 5 Installation
CAUTION
1. Install the unit on noncombustible material. Direct installation on combustible material or near combustible materials could lead to fires.
2. Follow this Instruction Manual and install the unit in a place where the weight can be borne.
3. Do not get on top of or place heavy objects on the unit.
Failure to observe this could lead to injuries.
4. Always use the unit within the designated environment conditions.
5. Do not let conductive objects such as screws or metal chips, etc., or combustible materials such as oil enter the servo amplifier or servomotor.
6. Do not block the servo amplifier intake and outtake ports. Doing so could lead to failure.
7. The servo amplifier and servomotor are precision devices, so do not drop them or apply strong impacts to them.
8. Do not install or run a servo amplifier or servomotor that is damaged or missing parts.
9. When storing for a long time, please contact your dealer.
5–2
Chapter 5 Installation
5-1 Installation of servomotor
1. Do not hold the cables, axis or detector when transp orting the servomotor. Failure to observe this could lead to faults or injuries.
2. Securely fix the servomotor to the machine. Insufficient fixing could lead to the servomotor deviating during operation. Failure to observe this could lead to injuries.
CAUTION
5-1-1 Environmental conditions
Environment Conditions
Ambient temperature Ambient humidity 80% RH or less (with no dew condensation) Storage temperature Storage humidity 90% RH or less (with no dew condensation)
Atmosphere
Altitude 1000m or less above sea level
Vibration
5-1-2 Cautions for mounting load (prevention of impact on shaft)
3. When coupling to a servomotor shaft end, do not apply an impact by hammering, etc. The detector could be damaged.
4. Never touch the rotary sections of the servomotor during operations. Install a cover, etc., on the shaft.
5. Do not apply a load exceeding the tolerable load onto the servomotor shaft. The shaft could break.
0°C to +40°C (with no freezing)
–20°C to +65°C (with no freezing)
Indoors (Where unit is not subject to direct sunlight)
With no corrosive gas or combustible gas.
With no oil mist or dust
HS-MF X, Y: 19.6m/s2 (2G) or less HS-RF
HS-SF 1kW or less HS-SF 2kW
X: 9.8m/s2 (1G) or less Y: 24.5m/s2 (2.5G) or less
X: 19.6m/s2 (2G) or less Y: 49m/s2 (5G) or less
Servomotor
X
Y
Acceleration
(1) When using the servomotor with key way, use the
screw hole at the end of the shaft to mount the pulley onto the shaft. To install, first place the double-end stud into the shaft screw holes, contact the coupling
Serv omotor
Double-end stud
end surface against the washer, and press in as if tightening with a nut. When the shaft does not have a key way, use a frictional coupling, etc.
(2) When removing the pulley, use a pulley remover,
and make sure not to apply an impact on the shaft.
(3) Install a protective cover on the rotary sections such
Pulley
Nut
Washer
as the pulley installed on the shaft to ensure safety.
(4) The direction of the detector installation on the
servomotor cannot be changed.
Never hammer the end of the shaft
CAUTION
during assembly.
5-1-3 Installation direction
There are no restrictions on the installation direction. Installation in any direction is possible, but as a standard the servomotor is installed so that the motor power supply wire and detector cable cannon plugs (lead-in wires) face downward. When the servomotor is not installed in the standard direction, refer to section "5-1-5 Oil and waterproofing measures" and take the appropriate measures. The brake plates may make a sliding sound when a servomotor with magnetic brake is installed with the shaft facing upward, but this is not a fault.
5–3
Chapter 5 Installation
5-1-4 Tolerable load of axis
(1) Using the flexible coupling, set the axis core deviation to less than the tolerable radial load of the
axis.
(2) When using a pulley, sprocket and timing belt, select so that the loads are within the tolerable
radial load.
(3) A rigid coupling must not be used as it will apply an excessive bending load on the axis to break.
Servomotor Tolerable radial load Tolerable thrust load
HS-MF23 88N L=25 59N HS-RF43/73 392N L=58 196N HS-SF52/53/102/103 392N L=58 196N HS-SF202 2058N L=79 980N
Caution: The symbols in the table follow the drawing below.
L : Length from flange isntallation surface to center of load weight [mm]
1. When coupling with a ball screw, etc., use a flexible coupling, and keep the shaft core deviation to below the tolerable radial load.
2. When installing the pulleys or gears on the motor shaft, the radial load will increase as the diameter of these parts decreases. Consider this when designing the machine.
3. When using a timing belt, adjust so that the radial load (double the tension)
CAUTION
generated from the tension is less than the values given above.
4. In a machine having a thrust load, such as a worm gear, provide a separate bearing on the machine side so that the a load exceeding the tolerable thrust load is not applied on the motor.
5. Do not use a rigid coupling as an excessive bending load will be applied on the shaft and could cause the shaft to break.
5-1-5 Oil and waterproofing measures
L
Radial load
Thrust load
(1) The servomotor does not have a precise water or oil-proof structure. The type (IP class) following
the IEC standards is indicated as the intelligent servomotor's protection type. These standards are the short-time performance standards, so make sure that the motor surface is not subject to fluids and that fluids do not accumulate. If cutting oil, etc., could enter, always provide a protective cover. Always consider the cover seams, edges, shapes and dimensions. Note that the IP class does not indicate the corrosion resistance level.
(2) When a gear box is installed on the servomotor, make sure that
the oil level height from the center of the shaft is higher than the values given below. Open a breathing hole on the gear box so that the inner pressure does not rise.
Servomotor Oil level (mm)
HS-MF23 12 HS-RF43, 73, -SF103 20 HS-SF202 25
Oil level
Gear
Lip
Servomotor
Oil seal
5–4
Chapter 5 Installation
(3) When installing the servomotor horizontally, set the power cable and detector cable to face
downward.
When installing vertically or on an inclination, provide a cable trap.
Cable trap
(4) Do not use the unit with the cable submerged in oil or water. (Refer to lower left drawing) (5) When installing on the top of the shaft end, make sure that oil from the gear box, etc., does not
enter the servomotor.
Cover
Gear
Lubricating oil
Servo­motor
Oil or water pool
Servomotor
<Fault> Capillary tube phenomenon
(6) Connect the HS-MF23 relay connector in a relay box having a structure (IP54) that prevents water,
oil and dust, etc., from entering. Fix the enclosed cable to the motor, and also fix the enclosed cable to the motor.
5-1-6 Cable stress
(1) Sufficiently consider the cable clamping method so that bending stress and the stress from the
cable's own weight is not applied on the cable connection.
(2) In applications where the servomotor moves, make sure that excessive stress is not applied on
the cable. Select the cable bending radius from the required bending life and wire type. Fix the detector cable and power cable enclosed with the servomotor. (3) Make sure that the cable sheathes will not be cut by sharp cutting chips, worn by contacting the
machine corners, or stepped on by workers or vehicles.
5–5
Chapter 5 Installation
5-2 Installation of interface unit
5-2-1 Environmental conditions
Environment Conditions
Ambient temperature Ambient humidity 90% RH or less (with no dew condensation) Storage temperature Storage humidity 90% RH or less (with no dew condensation) Atmosphere Indoors (Where unit is not subject to direct sunlight)
Altitude 1000m or less above sea level Vibration 5.9m/sec2 (0.6G) or less
5-2-2 Installation direction
Install so that the front of the interface unit is visible and the terminal block comes to the bottom.
5-2-3 Prevention of entering of foreign matter
0°C to +55°C (with no freezing)
–20°C to +65°C (with no freezing)
With no corrosive gas, combustible gas, oil mist or dust
Treat the cabinet with the following items.
Make sure that the cable inlet is dust and oil proof by using packing, etc.
Make sure that the external air does not enter inside by using head radiating holes, etc.
Close all clearances.
Securely install door packing.
If there is a rear cover, always apply packing.
Oil will tend to accumulate on the top. Take special measures such as oil-proofing the top so that
oil does not enter the cabinet from the screw holds.
After installing each unit, avoid machining in the periphery. If cutting chips, etc., stick onto the electronic parts, trouble may occur.
5–6
Chapter 5 Installation
from servo amplifier
from servo amplifier
power supply wire
servomotor
power supply wire
leakage current
5-3 Noise measures
Noise includes that which enters the servo amplifier from an external source and causes the servo amplifier to malfunction, and that which is radiated from the servo amplifier or motor and causes the peripheral devices or amplifier itself to malfunction. The servo amplifier output is a source of noise as the DC voltage is switched at a high frequency. If the peripheral devices or amplifier malfunction because of the noise, measures must be taken to suppressed this noise. These measures differ according to the propagation path of the noise.
(1) General measures for noise
Avoid wiring the servo amplifier's power supply wire and signal wires in parallel or in a bundled state. Always use separate wiring. Use a twisted pair shield wire for the detector cable, the control signal wires for the bus cable, etc., and for the control power supply wire. Securely ground the shield. Use one-point grounding for the servo amplifier and motor.
(2) Measures against noise entering from external source and causing servo amplifier to
malfunction
If a device generating noise is installed near the servo amplifier, and the servo amplifier could malfunction, take the following measures. Install a surge killer on devices (magnetic contactor, relay, etc.) that generate high levels of noise. Install a data line filter on the control signal wire. Ground the detector cable shield with a cable clamp.
(3) Measures against noise radiated from the servo amplifier and causing peripheral devices
to malfunction
The types of propagation paths of the noise generated from the servo amplifier and the noise measures for each propagation path are shown below.
Noise generated
Airborne propagation noise
Magnetic induction noise
Static induction noise
Cable propagation noise
and
Noise directly radiated
Noise radiated from
Noise radiated from
Noise propagated over
Noise lead in from grounding wire by
Path
Path Path
Path Path
Path
Path
5–7
Chapter 5 Installation
Noise
propaga-tion
① ② ③
④ ⑤ ⑥
path
Instru­ment
Receiver
Servomotor
Servo amplif ier
SM
Sensor
power
supply
Sensor
Measures
When devices such as instruments, receivers or sensors, which handle minute signals and are easily affected by noise, or the signal wire of these devices, are stored in the same panel as the servo amplifier and the wiring is close, the device could malfunction due to airborne propagation of the noise. In this case, take the following measures.
(1) Install devices easily affected as far away from the servo amplifier as
possible.
(2) Lay the signals wires easily affected as far away from the input wire with the
servo amplifier. (3) Avoid parallel wiring or bundled wiring of the signal wire and power wire. (4) Insert a line noise filter on the input/output wire or a radio noise filter on the
input to suppress noise radiated from the wires. (5) Use a shield wire for the signal wire and power wire, or place in separate
metal ducts.
If the signal wire is laid in parallel to the power wire, or if it is bundled with the power wire, the noise could be propagated to the signal wire and cause malfunction because of the magnetic induction noise or static induction noise. In this case, take the following measures.
(1) Install devices easily affected as far away from the servo amplifier as
possible. (2) Lay the signals wires easily affected as far away from the input wire with the
servo amplifier. (3) Avoid parallel wiring or bundled wiring of the signal wire and power wire. (4) Use a shield wire for the signal wire and power wire, or place in separate
metal ducts.
If the power supply for the peripheral devices is connected to the power supply in the same system as the servo amplifier, the noise generated from the servo amplifier could back flow over the power supply wire and cause the devices to malfunction. In this case, take the following measures.
(1) Install a radio noise filter on the servo amplifier's power wire. (2) Install a line noise filter on the servo amplifier's power wire.
If a closed loop is structured by the peripheral device and servo amplifier's grounding wires, the leakage current could penetrate and cause the devices to malfunction. In this case, change the device grounding methods and the grounding place.
5–8

Chapter 6 Wiring

6-1 System connection diagram........................................................................ 6-3
6-2 Connector ..................................................................................................... 6-4
6-2-1 Connector signal layout ........................................................................ 6-4
6-2-2 Signal name.......................................................................................... 6-5
6-3 Connection of power supply....................................................................... 6-6
6-3-1 Example of connection for controlling magnetic switch (MC)
with MDS-B-CV/CR............................................................................... 6-6
6-3-2 Example of connection for controlling magnetic switch with
external sequence circuit ...................................................................... 6-8
6-3-3 Wiring of contactors (MC)..................................................................... 6-8
6-3-4 Surge absorber..................................................................................... 6-9
6-4 Wiring the motor with brakes...................................................................... 6-9
6-4-1 Connection example ............................................................................. 6-9
6-4-2 Manually releasing the magnetic brakes .............................................. 6-10
6-5 Connection with the NC............................................................................... 6-11
6-5-1 Connection system ............................................................................... 6-11
6–1
Chapter 6 Wiring
DANGER
Wait at least 10 minutes after turning the power OFF and check the voltage
servomotor with Class 3 grounding
CAUTION
). Failure to observe this item could lead
1. Wiring work must be done by a qualified technician.
2. with a tester, etc., before starting wiring. Failure to observe this could lead to electric shocks.
3. Securely ground the servo amplifier and or higher.
4. Wire the servo amplifier and servomotor after installation. Failure to observe this could lead to electric shocks.
5. Do not damage, apply forcible stress, place heavy items or engage the cable. Failure to observe this could lead to electric shocks.
1. Correctly and securely perform the wiring. Failure to do so could lead to runaway of the servomotor.
2. Do not mistake the terminal connections.
Failure to observe this item could lead to ruptures or damage, etc.
3. Do not mistake the polarity ( + , – to ruptures or damage, etc.
4. Electronic devices used near the servo amplifier may receive magnetic obstruction. Reduce the effect of magnetic obstacles by installing a noise filter, etc.
5. Do not modify this unit.
6–2
6-1 System connection diagram
reactor
3ø200VAC L1, L2,
I/F unit HS-IF-6
I/Fユニット HS-IF-6
MELDASCNC
DC24V
24VDC
ブレーキ回路
Brake circuit
Chapter 6 Wiring
サーボ
Servo MDS-
MDS-
B-
B- V1,V2
B-AL
ACリア
AC
クトル
主軸
Spindle MDS-
MDS-
B-SP
B-SP
パワーサ
Power
プライ
supply
MDS-
MDS­B-CV
B-CV
MC
Battery unit
バッテリーユニット
A-BT
A-BT
MC relay
MC用リレー
主回路電源用
L3 for main circuit power
3φAC200VL1,L2,L3,
200VAC L11, L12 for
制御回路電源用AC200V
control circuit power
L11,L12
インテリジェント
Intelligent servomotor
サーボモータ
Note)
1) Keep the cable length to within 30m.
2) This is a motor with magnetic brakes. The power connected to the magnetic brake does not have a polarity.
3) Securely connect the shield wire to the plate (grounding plate) in the connector.
4) When using as an absolute connector, connect MDS-A-BTo.
NF
6–3
6-2 Connector
Never connect the power wire to the signal terminal or the signal wire to the
CAUTION
DANGER
6-2-1 Connector signal layout
(1) HS-RFxxE, HS-SFxxE
L12
Open
BR
MON
power terminal. There is a risk of electric shock. Failure to observe this can also cause damage or faults with the NC unit or devices connected to the NC.
Apply only the designated voltage to each terminal. Failure to observe this could lead to damage or faults.
L11
Open
RG
Open
GND
L1
L2
L3
PE
Chapter 6 Wiring
*
TXD
RXD
EMG
ALM
BAT
TXD
RXD
EMG
ALM
(Japan Aviation) Applicable connector: JL04V-28A28-11PE
(2) HS-MF23E
B1 L2
A1 L1
B2 PE
A2 Open
B3
L12
A3
L11
B1
TXD
A1
TXDA2RXDA3EMG
B4
RXD
B4
EMG
B4
ALM
A4
ALMA5BATA6MON
B6
GND
B6 FG
Applicable connector: Power connector : 178964-3 (AMP) Signal connector : 178964-6 (AMP)
6–4
Power supply for
6-2-2 Signal name
Name Signal name Details
L1·L2·L3
L11·L12
PE
Power supply
TXD, TXD*
RXD, RXD* MON
FG EMG, EMG*
Control signal
ALM, ALM* BAT GND
RG
Brake
BR
Main circuit power supply
Control circuit power supply
Protective ground
NC transmission data
NC reception data
Monitor output Ground Emergency stop Alarm Battery Ground
magnetic brakes
Chapter 6 Wiring
Main circuit power supply input terminal Connect 3-phase 200 to 230VAC, 50/60Hz.
Control circuit power supply input terminal Connect 1-phase 200 to 230VAC, 50/60Hz.
Grounding terminal Connect and ground with the servomotor grounding terminal.
For NC connection
Connect the 24VDC for the magnetic brakes. (Only when brakes are provided.) The power supply polarity is irrelevant.
6–5
Chapter 6 Wiring
6-3 Connection of power supply
1. Keep the power voltage and capacity within the controller's specification range. Failure to observe this could lead to damage or faults.
2. For safety purposes, always instal l a no-fuse breaker or earth leakage breaker, and shut off when an error occurs or before inspecting. A large
CAUTION
6-3-1 Example of connection for controlling magnetic switch (MC) with MDS-B-CV/CR
The following connection example applies when the power supply unit MDS-B-CV/CVE/CR is provided in the system. The magnetic switch can also be controlled by the MDS-B-SVJ2/SPJ2. Refer to the respective unit's specification manual for details.
(1) When sharing a power supply unit and power supply
rush current flows when the power is turned ON. Refer to Chapter 6 and select the no-fuse breaker or earth leakage breaker.
3. For safety purposes, install a magnetic switch that shuts off when an error occurs. If the converter unit MDS-B-CV is provided in the system, use the converter's magnetic switch control function. The magnetic switch can be directly driven by the MDS-B-CV.
MC
3-phase 200VAC
24VDC
External emergency stop
NFB
Mitsubishi
CNC
PE L1 L2 L3
L11 L12
AC reactor B-AL
Intelligent
servomotor
I/F unit
Power supply unit MDS-B-CV/CR
PE L1 L2 L3
L11 L12 MC1
L+ L−
Terminator
Servo/spindle drive unit MDS-B-Vx/SP
PE
L11 L12
L+ L−
1. The MDS-B-CV is a power supply regenerative type converter; an AC reactor is required in the power supply line.
Connect the intelligent servomotor main circuit power supply on the power
CAUTION
supply side of the AC reactor.
2. A no-fuse breaker and contactor cannot be shared when the rated current of the no-fuse breaker exceeds 60A.
6–6
Chapter 6 Wiring
(2) When not sharing a converter and power supply
If the rated current exceeds 60A by the selection of the no-fuse breaker when the converter and power supply are shared, install the no-fuse breakers and contactors separate from the converter unit.
3-phase
200VAC
NFB1
NFB2
MC1
MC2
AC reactor B-AL
PE L1 L2 L3
L11 L12
Intelligent
servomotor
Power supply unit MDS-B-CV/CR
PE L1 L2 L3
L11 L12 MC1
L+ L−
Terminator
Servo/spindle drive unit MDS-B-Vx/SP
PE
L11 L12
L+ L−
24VDC
External emergency stop
DANGER
Mitsubishi
CNC
I/F unit
Install independent no-fuse breakers as the intelligent servomotor power supply if the total current capacity exceeds 60A when the converter and power supply are shared. No-fuse breakers may not operate for short-circuits in small capacity amplifiers if they are shared with a large capacity unit, and this could cause fires. For the intelligent servomotor, use an NF60 type or lower capacity breaker. (Refer to section 4.)
6–7
Chapter 6 Wiring
emergency stop signal. If the input power is cut off during deceleration control,
(Order of priority of the contactor drive method)
6-3-2 Example of connection for controlling magnetic switch with external sequence circuit
Relay Prepare a sequence that cuts off with the alarm.
3-phase
200VAC
24VDC
External emergency stop
External emergency stop
NFB
Mitsubishi
CNC
MC
PE L1 L2 L3
L11 L12
Intelligent
servomotor
I/F unit
Terminator
PE L1 L2 L3
L11 L12
Class 3 grounding
or higher
Intelligent
servomotor
6-3-3 Wiring of contactors (MC)
A contactor (magnetic contactor) is inserted in the main circuit power supply input (L1, L2, L3) of servo amplifier, and the power supply input is shut off when an emergency stop or servo alarm occurs. When an emergency stop or servo alarm occurs, the servo amplifier stops the motor using deceleration control or a dynamic brake. The contactors cannot be shut off during deceleration control, because the regeneration energy (MDS-B-CV Series) is returned to the power supply, and the power supply for deceleration must be held. Therefore, the CNC controls the contactors. The CNC confirms that all axes are stopped, or confirms the dynamic brake operation. Then it outputs a shutoff command for amplifiers that drive contactors. When actually driving the contactor, it is driven by the amplifier of the axis having the longest deceleration time constant in consideration of the communication from the NC being cut off. Generally, when a converter (MDS-B-CV/CVE/CR) is provided, the contact is driven by the converter. When a spindle amplifier is provided, the contactor is driven by the spindle amplifier, and when the servo amplifier (MDS-B-SVJ2) is provided, the contact is driven by the servo amplifier. Give consideration to the above, and examine the contactor drive method in the following order of priority.
1. Using the contactor control output (MC1) of the converter unit.
2. Driven by spindle amplifier (MDS-B-SPJ2 in this case).
3. Driving from the servo amplifier (MDS-B-SVJ2) of the vertical axis (unbalanced axis).
4. Driving from the servo amplifier (MDS-B-SVJ2) having the longest deceleration time constant.
5. Driven by external sequence (only for intelligent servomotor.)
Directly cut off the contact with an external sequence only when using the
CAUTION
intelligent servomotor. In this case, cut off the power supply with a delay longer than the servo's acceleration/deceleration time constant in respect to the
6–8
Chapter 6 Wiring
the undervoltage alarm could occur or the deceleration control may be prevented.
6–9
Chapter 6 Wiring
6-3-4 Surge absorber
As protection against surge voltage caused by lightning, etc., the surge absorber and radio noise filter shown below are built into the intelligent servomotor's I/F unit MDS-B-HSIF (refer to Chapter 6) and the MDS-B-CV AC reactor B-ALxx. When not using these simultaneously, install a surge absorber and filter on the input power supply as shown below. Refer to the following table and select the surge absorber.
L1
VAR1
L2
VAR2 VAR3
L3
C1
C2 C3
C4
C5
C6
PE
VAR4
Symbol Type Maker Rating
VAR1 to VAR3
TNR23G471K
VAR4 DSAZR2-302M Mitsubishi Materials Corp.
C1 to C3 AL-U2E224K
C4 to C6 DE7120F332MVA-1KC
MARCON ELECTRONICS CO., LTD.
SHIZUKI ELECTRONIC CO., INC.
Murata Manufacturing Co., Ltd.
Varistor voltage 423 to 517V DC discharge start voltage
2400 to 3600V 250VAC 0.22µF
2500VAC 3300pF
6-4 Wiring the motor with brakes
1. No mechanical guarantee is provided even when the dynamic brakes are used. If the machine could drop during a power failure, use a motor with magnetic brakes or provide an external brake mechanism to prevent dropping.
2. The magnetic brakes are used for holding, and must not be used for normal braking. There may be cases when holding is not possible due to the life
CAUTION
6-4-1 Connection example
and machine structure (when ball screw and servomotor axis are connected via a timing belt, etc.). Provide a stopping device to ensure safety on the machine side.
3. The magnetic brakes of the motor with magnetic brakes are controlled in the intelligent servomotor. However, provide a double circuit configuration so that these brakes will operate even with the external emergency stop signal.
BR
RG
Amplifier
Servomotor
RA
Magnetic brakes
Cut off with emergency stop signal.
EMG
24VDC
1) The brakes are safety brakes, and will operate when the power (24VDC) is turned OFF. 6–10
Chapter 6 Wiring
2) Prepare a brake excitation power supply that ensures a secure attraction current.
3) The brake terminal polarity is random, but must not be mistaken with other circuits.
6–11
Chapter 6 Wiring
6-4-2 Manually releasing the magnetic brakes
The intelligent servomotor has a relay for controlling the brakes in the amplifier, so the brakes cannot be released even if power is supplied to the 24V power terminal (BR, RG) for the cannon plug brakes. Release the brakes with the following method when the brakes need to be released for handling when assembling, adjusting or servicing the machine.
(1) Method 1
Remove the amplifier section and input the 24V power to the motor brakes. There is no polarity. Refer to section "9-3. Replacing the unit" for details on removing and installing the amplifier section. The amplifier terminal is a connector, so prepare the following connector beforehand.
Plug housing : SMP-02V-BC Socket contact : BHF-001T-0.8BS (J.S.T. Mfg Co., Ltd.)
(2) Method 2
Enter the brake release mode by changing the MON signal, normally used for the axis No. selection, several times.
1) Prepare the circuit operation box shown with the dotted line below, and connect with the intelligent servomotor as shown in the drawing.
2) Open SW1 and SW2.
3) Input 200VAC to the LL1 and LL2 terminals. The LED will turn ON.
4) Turn SW1 ON. The LED will flicker.
5) Turn SW2 ON. The LED will turn OFF.
6) Turn SW2 OFF. The LED will turn ON, and the relay in the
amplifier will turn ON.
7) Input 24VDC to the BR and RG terminals. The brakes will be released.
8) Thereafter, when SW2 is turned ON the brakes will be applied, and when turned OFF, the brakes will be released.
Intelligent servomotor
Control
power
Control
circuit
RA
*
Operation box
330
L11 L12 BR RG
ALM
ALM MON
LG
All other pins are open.
NFB
SW2 SW1
680
LED
For OFF at emergency
For status indication
200VAC
24VDC
6–12
6-5 Connection with the NC
6-5-1 Connection system
I/F unit
CN1A CN1B
Mitsubishi
CNC
CON1 to CON4
Chapter 6 Wiring
Terminator or battery unit when there is no other drive unit
MDS-B Series servo/spindle drive unit
Terminator or battery unit
Intelligent servomotor
(1) Refer to "Chapter 6 Peripheral devices" for details on connecting and setting the I/F unit. (2) The I/F unit's CON1 to CON4 (intelligent servo connection connectors) can be connected to any
connector.
(3) If the MDS-B Series servo/spindle drive unit is connected as shown above, connect the I/F unit
between the CNC and servo spindle drive. Other drive units cannot be connected between the CNC and I/F unit.
I/F unit
Mitsubishi
CNC
MDS-B Series servo/spindle drive unit
An I/F unit cannot be connected behind the servo/spindle drive unit.
Intelligent servomotor
(4) There may be cases when the I/F unit (PCB) is manufactured by the machine maker. In this case,
contact the machine maker for details on connecting and setting the I/F unit.
6–13

Chapter 7 Setup

7-1 Setting the initial parameters..................................................................... 7-2
7-1-1 Servo specification parameters........................................................... 7-2
7-1-2 Limitations to electronic gear setting value......................................... 7-2
7-1-3 Parameters set according to feedrate................................................. 7-3
7-1-4 Parameters set according to machine load inertia.............................. 7-3
7-1-5 Standard parameter list according to motor........................................ 7-4
7–1
Chapter 7 Setup
7-1 Setting the initial parameters
The servo parameters must be set to start up the servo drive system. The servo parameters are input from the CNC. The input method will differ according to the CNC, so refer to the Instruction Manual provided with each CNC.
7-1-1 Servo specification parameters
The servo specification parameters are determined according to the machine specifications and servo system specifications.
No. Abbrev. Parameter name Explanation
SV017 SPEC Servo specifications This is a HEX setting parameter. Set this as follows according to the servo
SV025 MTYP Motor type Set the motor type.
SV036 PTYP Regenerative resistor type Set 1000 as a standard. SV027 SSF1 Special servo function
selection 1
SV033 SSF2 Special servo function
selection 2 SV001 PC1 Motor side gear ratio SV002 PC2 Machine side gear ratio SV018 PIT Ball screw pitch Set the ball screw pitch with an mm unit. Set 360 for a rotary axis. SV019 RNG1 Position detector resolution SV020 RNG2 Speed detector resolution SV003 PGN1 Position loop gain Set 33 as a standard.
specifications.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
abs dmk
bit Meaning when "0" is set. Meaning when "1" is set.
0 dmk 7 abs Incremental control Absolute position control
Set all bits other than those above to 0.
Refer to the standard parameter list for each motor for the settings.
Set 4000 as a standard.
Set 0000 as a standard.
Set the motor side gear ratio in PC1 and the machine side gear ratio in PC2. When using a rotary axis, set the total deceleration (acceleration) ratio.
Set the motor detector resolution with a kp/rev unit for both settings. Refer to the standard parameters for each motor for the settings.
Deceleration control stop (Standard)
Dynamic brake stop selection
7-1-2 Limitations to electronic gear setting value
The servo amplifier has internal electronic gears. The command value from the NC is converted into a detector resolution unit to carry out position control. The electronic gears are single gear ratios calculated from multiple parameters as shown below. However, each value (ELG1, ELG2) must be less than 32767. If the value overflows, the initial parameter error (alarm 37) or error parameter No. 101 (2301 with M50/M64 Series NC) will be output. If an alarm occurs, the mechanical specifications and electrical specifications must be revised so that the electronic gears are within the specifications range.
Reduced fraction of
ELG1 ELG2
=
PC2 × RANG
PC1 × PIT × IUNIT
(reduced fraction)
RANG = RNG1 = RNG2 IUNIT = 2/NC command unit (µm) 1µm : IUNIT = 2, 0.1µm: IUNIT = 20
When the above is calculated, the following conditions must be satisfied.
ELG1 32767 ELG2 32767
If the electronic gears in the amplifier overflow, the alarm 37 or error
POINT
parameter No. 101 (2301 with M50/M64 series NC) will be output.
7–2
Chapter 7 Setup
Load inertia scale (total load inertia/motor inertia)
40 0
80 60
Load inertia scale (total load inertia/motor inertia)
20 0 50 40 30
Load inertia scale (total load inertia/motor inertia)
7-1-3 Parameters set according to feedrate
The following parameters are determined according to each axis' feedrate.
No. Abbrev. Parameter name Explanation
SV023 OD1 Excessive error detection
width at servo ON SV026 OD2 Excessive error detection
width at servo OFF
A protective function will activate if the error between the position command and position feedback is excessive. If the machine load is heavy and problems occur with the standard settings, gradually increase the setting value.
<Calculation of standard setting value> OD1 = OD2 =
Rapid traverse rate (mm/min) 60 × PGN1
÷ 2 (mm)
7-1-4 Parameters set according to machine load inertia
The following parameters are set according to the machine's inertia.
No. Abbrev. Parameter name Explanation
SV005 VGN1 Speed loop gain. Refer to the comparison graph with the load inertia scale for the standard setting
SV008 VIA Speed loop leading
compensation
HS-MF
value. Set 1364 as a standard. Set 1900 as a standard for the SHG control.
If the load inertia is large and is in the standard VIA change region, set the value in the comparison graph regardless of whether normal control or SHG control is used.
Motor single unit
100
HS-RF
Standard VIA change region
Standard VGN1
Standard VGN1
10
600
500
400
300
200
100
1
HC-SF
0
3 7
5 9
Standard VIA change region
HC-SF52 HC-SF102
HC-SF202
HC-SF53, HC-SF103
VIA
11
Standard VGN1
VIA
1500
1000
500
20
11
VIA
1500
1000
500
HC-RF43 HC-RF73
VIA
1
3 7
5 9
7–3
Chapter 7 Setup
7-1-5 Standard parameter list according to motor
Set the parameters other than 7-2-1 to 7-2-4 to the standard parameters.
Motor type
No. Abbrev. Parameter name
SV001 PC1 Motor side gear ratio SV002 PC2 Machine side gear ratio SV003 PGN1 Position loop gain 1 33 SV004 PGN2 Position loop gain 2 0 SV005 VGN1 Speed loop gain Refer to "7-1-4 Parameters set according to machine load inertia" SV006 0 SV007 0 SV008 VIA Speed loop leading compensation 1364
SV009 IQA
SV010 IDA SV011 IQG Current loop Q axis gain 400 384 384 512 256 384 256 384
SV012 IDG Current loop D axis gain 400 384 384 512 256 384 256 384 SV013 ILMT Current limit value 400 300 300 700 700 600 700 500
SV014 ILMTsp SV015 FFC Acceleration feed forward gain 0
SV016 LMC1 Lost motion compensation 1 0 SV017 SPEC Servo specifications Refer to "7-1-1 Servo specification parameters"
SV018 PIT Ball screw pitch SV019 RNG1 Position detector resolution 8 100
SV020 RNG2 Speed detector resolution 8 100 SV021 OLT Overload time constant 60 SV022 OLL Overload detection level 150
SV023 OD1 SV024 INP In-position width 50
SV025 MTYP Motor type 229E 22E0 22E1 22B0 22C0 22B1 22C1 22B3 SV026 OD2 SV027 SSF1 Special servo function selection 1 4000
SV028
to 035
SV036 PTYP Regenerative resistor type 1000 SV037
to 046
SV047 EC Inductive voltage compensation gain 70 SV048 EMGrt Vertical axis drop prevention time 0
SV049 SV050
PGN1sp
to 064
Current loop Q axis leading compensation
Current loop D axis leading compensation
Current limit value during special operation
Excessive error detection width during servo ON
Excessive error detection width during servo OFF
Compensation function for special
functions
Compensation function for special
functions
Position loop gain during spindle synchronization 1
Compensation function for special
functions
MF23 RF43 RF73 SF52 SF53 SF102 SF103 SF202
Set the motor side gear ratio in PC1 and the machine side gear ratio in PC2. When using a rotary axis, set the total deceleration (acceleration) ratio.
4096 8192 8192 8192 4096 8192 4096 4096
4096 8192 8192 8192 4096 8192 4096 4096
400 250 250 700 700 600 700 500
Set the ball screw pitch with an mm unit.
Set 360 for a rotary axis.
Refer to "7-1-3 Parameters set according to feedrate"
Refer to "7-1-3 Parameters set according to feedrate"
0
0
15
0
7–4

Chapter 8 Adjustment

8-1 Measurement of adjustment data .............................................................. 8-2
8-1-1 D/A output specifications .................................................................... 8-2
8-1-2 Setting the output data........................................................................ 8-2
8-1-3 Setting the output scale ...................................................................... 8-3
8-1-4 Setting the offset amount.................................................................... 8-3
8-1-5 Clamp function.................................................................................... 8-3
8-1-6 Filter function...................................................................................... 8-3
8-2 Gain adjustment .......................................................................................... 8-4
8-2-1 Current loop gain................................................................................ 8-4
8-2-2 Speed loop gain.................................................................................. 8-4
8-2-3 Position loop gain ............................................................................... 8-6
8-3 Characteristics improvement..................................................................... 8-8
8-3-1 Optimal adjustment of cycle time ........................................................ 8-8
8-3-2 Vibration suppression measures......................................................... 8-10
8-3-3 Improving the cutting surface precision .............................................. 8-12
8-3-4 Improvement of protrusion at quadrant changeover........................... 8-15
8-3-5 Improvement of overshooting.............................................................. 8-19
8-3-6 Improvement of characteristics during acceleration/deceleration....... 8-21
8-4 Setting for emergency stop........................................................................ 8-24
8-4-1 Deceleration control............................................................................ 8-24
8-4-2 Vertical axis drop prevention control................................................... 8-26
8-5 Collision detection .................................................................................... 8-27
8-6 Parameter list............................................................................................... 8-30
5–1
Chapter 8 Adjustment
8-1 Measurement of adjustment data
The intelligent servomotor has a function to D/A output the various control data. To adjust the servo and set the servo parameters that match the machine, it is necessary to use the D/A output and measure the internal status of the servo. Measure using a hi-coder, synchroscope, etc.
8-1-1 D/A output specifications
<Output specifications>
No. of channels : 1ch. Output cycle : 888µsec (min. value) Output precision : 8bit Output voltage range : 0V to 2.5V to 5V Output pins : On intelligent servo I/F unit Output scale setting : ±1/256 to ±128 times Output resistance : 1k
<Output function>
Offset amount adjustment function
Output clamp function
Low path filter function
<Measurement method>
Connect the measuring instrument to the I/F unit check pin. When observing the waveform, turn the I/F unit DIP switch OFF. Note that the DIP switch must be turned ON when the power is turned ON. Do not connect a measuring instrument having a low input impedance when turning the power ON.
8-1-2 Setting the output data
No. Abbrev. Parameter name Explanation
SV061 DA1NO D/A output channel 1 data No. Input the No. of the data to be output to each D/A output channel.
No.
10 11 Position droop 4 mm/V 3.55 msec 12 13 14 15 16 3.55 msec 17 3.55 msec 18 3.55 msec
19
20
Output data Standard output unit
0 0 V test output For offset amount adjustment 1 Speed feedback 2000rpm/1V 2 Current feedback Rated current/0.5V 3 Speed command 2000rpm/1V 4 Current command Rated current/0.5V 5 V-phase current value 40A/V 6 W-phase current value 40A/V
Estimated disturbance
7
torque 8 9
Position droop(×10) 400 µm/V
Position droop(×100) 40 µm/V
Feedrate (F∆T)
Feedrate (F∆T×10)
q axis current
cumulative value
d axis current
cumulative value
Rated current/0.5V
40000 (mm/min)/V
4000 (mm/min)/V
888 µsec
Output cycle
888 µsec 888 µsec 888 µsec 888 µsec 888 µsec 888 µsec
888 µsec
3.55 msec
3.55 msec 888 µsec 888 µsec
888 µsec
No. Output data Standard output unit
21 Motor load level 100%/1.25V 113.7 msec 22 Amplifier load level 100%/1.25V 113.7 msec
Regenerative load
23
level 24 PN bus wire voltage 200V/V (1/200) 25 Speed cumulative item 26 Cycle counter 0–125V 27 3.55 msec 28 29 3.55 msec 30 3.55 msec 31
to
99
100 5 V test output
Saw-tooth wave test
101
output
Rectangular wave test
102
output
103
Setting prohibited
100%/1.25V 910.2 msec
1.25 to 3.75V
Cycle 113.7 msec
2.5 to 3.75V
Cycle 227.5 msec
Output cycle
888 µsec 888 µsec 888 µsec
888 µsec
888 µsec
8–2
Chapter 8 Adjustment
When overflow is set
0
-10V
5V
Time
When clamp is set
Time
8-1-3 Setting the output scale
This is set when an output is to made with a unit other than the standard output unit.
(Example 1) When SV061= 5, SV063 = 2560
The V-phase current value will be output with 4A/V unit to D/A output ch. 1.
(Example 2) When SV063 = 11, SV064 = 128
The position droop will be output with a 8mm/V unit to the D/A output ch. 2.
No. Abbrev. Parameter name Explanation Setting range
SV063 DA1MPY D/A output channel 1
output scale
SV064 DA2MPY D/A output channel 2
output scale
When "0" is set, the output will be made with the standard output unit. To change the output unit, set a value other than 0. The scale is set with a 1/256 unit. When 256 is set, the unit will be the
same as the standard output unit.
–32768 to 32767
8-1-4 Setting the offset amount
This is used when the zero level of the output voltage is to be finely adjusted. The output scale when the data No. is 0 will be the offset amount. After setting the offset, set the data No. to a value other than 0, and do not set it to 0 again. The offset value will be reset when the amplifier power is turned OFF. (The value is not reset when the NC power is turned OFF.)
No. Abbrev. Parameter name Explanation Setting range
SV061 DA1NO D/A output channel 1
data No.
SV063 DA1MPY D/A output channel 1
offset amount
Set "0". 0 to 102
The amount can be set with the output precision unit. Observe the output value and set so that the output value is 0 V.
–10 to 10
8-1-5 Clamp function
This is used when the output value such as the position droop exceeds the output range and over flows.
Position droop
5V
-10V
0
D/A output range
8-1-6 Filter function
A low path filter with a cutoff frequency of 140 Hz can be set.
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit Meaning when "0" is set. Meaning when "1" is set.
selection 3
Set the clamp function and filter function with the following parameter.
daf2 daf1 dac2 dac1
4 dac1 ch. 1 Overflow setting ch. 1 Clamp setting 5 dac2 ch. 2 Overflow setting ch. 2 Clamp setting 6 daf1 ch. 1 No filter ch. 1 Filter operation 7 daf2 ch. 2 No filter ch. 2 Filter operation
mon
8–3
Chapter 8 Adjustment
the VGN1 setting value is raised, the subsequent servo adjustment becomes
8-2 Gain adjustment
8-2-1 Current loop gain
No. Abbrev. Parameter name Explanation Setting range
SV009 IQA q axis leading compensation 1 to 20480 SV010 IDA d axis leading compensation 1 to 20480 SV011 IQG q axis gain 1 to 2560 SV012 IDG d axis gain
8-2-2 Speed loop gain
(1) Setting the speed loop gain
The speed loop gain (SV005: VGN1) is an important parameter for determining the responsiveness of the servo control. During servo adjustment, the highest extent that this value can be set to becomes important. The setting value has a large influence on the machine cutting precision and cycle time. To adjust the VGN1 value, first obtain the standard VGN1 to judge how much VGN1 is required for the machine load inertia. The standard VGN1 is the value that corresponds to the size of the machine load inertia shown in the graph in section 7-1-3. If the load inertia is not clear, estimate it using the following procedure.
1) Set the VGN1 of a level where acceleration/deceleration operation is possible. (Set a slightly lower value so resonance does not occur.)
2) Set SV037 = 100, SV043 = 600, and SV044 = 0 in the servo parameters. Carry out a return operation within the range where the axis can operate smoothly. At this time, set the acceleration/deceleration time constant so the acceleration/deceleration torque equals or exceeds (is 100% or higher than) the stall (rated) torque.
3) Observe the estimated disturbance using the D/A output, and increase the SV037 value until the disturbance torque during acceleration/deceleration becomes smaller (cannot be observed).
(The unbalance torque is observed as an estimated disturbance torque in the vertical and
slanted axes, so ignore this amount or set the torque offset (SV032) and adjust. The friction torque is also observed in the same way for axes having a large amount of friction, but this should be ignored. Refer to section "8-3-3 (4) Disturbance observer" for details.)
4) The SV037 setting where the disturbance torque becomes the smallest during the estimated acceleration/deceleration is the machine's total load inertia magnification including the motor inertia. Obtain the standard VGN1 from the graph in section 7-1-3 based on this value.
<When machine resonance does not occur at the standard VGN1>
Set the standard VGN1. Use the standard value if no problem (such as machine resonance) occurs. If sufficient cutting precision cannot be obtained at the standard VGN1, do not raise the VGN1 further above the standard value. Instead, use the disturbance observer and adjust. Basically, there is no need to set a value higher than the standard value in VGN1.
<When machine resonance occurs at the standard VGN1>
Machine resonance is occurring if the shaft makes abnormal sounds when operating or stopping, and a fine vibration can be felt when the machine is touched while stopped. Machine resonance occurs because the servo control responsiveness includes the machine resonance points. (Speed control resonance points occur, for example, at parts close to the motor such as ball screws.) Machine resonance can be suppressed by lowering VGN1 and the servo control responsiveness, but the cutting precision and cycle time are sacrificed. Thus, set a vibration suppression filter and suppress the machine resonance (Refer to section "8-3-2 Vibration suppression measures"), and set a value as close as possible to the standard VGN1. If the machine resonance cannot be sufficiently eliminated even by using a vibration suppression filter, then lower the VGN1.
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain Set this according to the motor inertia size.
The final VGN1 setting value should be 70 to 80% of the largest value at which
POINT
machine resonance does not occur. If the vibration suppression functions are used to suppress the resonance and
This setting is determined by the motor's electrical characteristics. Set the standard parameters for all parameters. (These are used for maker adjustments.)
1 to 2560
1 to 999
If vibration occurs, adjust by lower the setting by 20% to 30% at a time.
8–4
Chapter 8 Adjustment
more favorable.
8–5
Chapter 8 Adjustment
(2) Setting the speed loop leading compensation
The speed loop leading compensation (SV008: VIA) determines the characteristics of the speed loop mainly at low frequency regions. 1364 is set as a standard, and 1900 is set as a standard during SHG control. The standard value may drop as shown in the graph in section 7-1-3 in respect to loads with a large inertia. When the VGN1 is set lower than the standard value because the load inertia is large or because machine resonance occurred, the speed loop control band is lowered. If the standard value is set in the leading compensation in this status, the leading compensation control itself will induce vibration. In concrete terms, a vibration of 10 to 20Hz could be caused during acceleration/deceleration and stopping, and the position droop waveform could be disturbed when accelerating to a constant speed and when stopped. (Refer to the following graphs.) This vibration cannot be suppressed by the vibration suppression functions. Lower the VIA in increments of 100 from the standard setting value. Set a value where vibration does not occur and the position droop waveform converges smoothly. Because lowering the VIA causes a drop in the position control's trackability, the vibration suppression is improved even when a disturbance observer is used without lowering the VIA. (Be careful of machine resonance occurrence at this time.)
Speed FB
0
D/A output range
Position droop
0
Vibration waveform with leading compensation control
Time
Time
0
0
Adjusted position droop waveform
If VIA is lowered, the position droop waveform becomes smooth and overshooting does not occur. However, because the trackability regarding the position commands becomes worse, that amount of positioning time and precision are sacrificed. VIA must be kept high (set the standard value) to guarantee precision, especially in high-speed contour cutting (generally F = 1000 or higher). In other words, a large enough value must be set in VGN1 so that the VIA does not need to be lowered in machines aimed at high-speed precision. When adjusting, the cutting precision will be better if adjustment is carried out to a degree where overshooting does not occur and a high VIA is maintained, without pursuing position droop smoothness. If there are no vibration or overshooting problems, the high-speed contour cutting precision can be further improved by setting the VIA higher than the standard value. In this case, adjust by raising the VIA in increments of 100 from the standard value. Setting a higher VIA improves the trackability regarding position commands in machines for which cycle time is important, and the time to when the position droop converges on the in-position width is shortened. It is easier to adjust the VIA to improve precision and cycle time if a large value (a value near the standard value) can be set in VGN1, or if VGN1 can be raised equivalently using the disturbance observer.
No. Abbrev. Parameter name Explanation Setting range
SV008 VIA Speed loop leading
compensation
1364 is set as a standard. 1900 is set as a standard during SHG control. Adjust in increments of approx. 100. Raise the VIA and adjust to improve the contour tracking precision in high-speed cutting. If the position droop vibrates (10 to 20Hz), lower the VIA and adjust.
1 to 9999
Time
Time
8–6
Chapter 8 Adjustment
POINT
Position droop vibration of 10Hz or less is not leading compensation control vibration. The position loop gain must be adjusted.
8–7
Chapter 8 Adjustment
8-2-3 Position loop gain
(1) Setting the position loop gain
The position loop gain (SV003:PGN1) is a parameter that determines the trackability to the command position. 33 is set as a standard. Set the same position loop gain value between interpolation axes. When PGN1 is raised, the settling time will be shortened, but a speed loop that has a responsiveness that can track the position loop gain with increased response will be required. If the speed loop responsiveness is insufficient, several Hz of vibration or overshooting will occur during acceleration/deceleration. Vibration or overshooting will also occur when VGN1 is smaller than the standard value during VIA adjustment, but the vibration that occurs in the position loop is generally 10Hz or less. (The VIA vibration that occurs is 10 to 20Hz.) When the position control includes machine resonance points (Position control machine resonance points occur at the machine end parts, etc.) because of insufficient machine rigidity, the machine will vibrate during positioning, etc. In either case, lower PGN1 and adjust so vibration does not occur. If the machine also vibrates due to machine backlash when the motor stops, the vibration can be suppressed by lowering the PGN1 and smoothly stopping. If SHG control is used, an equivalently high position loop gain can be maintained while suppressing these vibrations. To adjust the SHG control, gradually raise the gain from a setting where 1/2 of a normal control PGN1 where vibration did not occur was set in PGN1. If the PGN1 setting value is more than 1/2 of the normal control PGN1 when SHG control is used, there is an improvement effect in position control. (Note that for the settling time the improvement effect is
SV003 PGN1 Position loop gain 1 Set 33 as a standard. If PGN1 is increased, the settling time will be
SV004 PGN2 Position loop gain 2 Set 0. (For SHG control) 0 to 999 SV057 SHGC SHG control gain Set 0. (For SHG control) 0 to 999
at 1/ 2 or more.)
No. Abbrev. Parameter name Explanation Setting range
1 to 200
shortened, but a sufficient speed loop response will be required.
CAUTION
Always set the same value3 for position loop gain between interpolation axes.
(2) Setting the position loop gain for spindle synchronous control
During spindle synchronous control (synchronous tapping control, etc.), there are three sets of position loop gain parameters besides the normal control.
No. Abbrev. Parameter name Explanation Setting range
SV049 PGN1sp Position loop gain 1
during spindle synchronization
SV050 PGN2sp Position loop gain 2
during spindle synchronization
SV058 SHGCsp SHG control gain
during spindle synchronization
Set 15 as a standard. 1 to 200
Set 0 as a standard. (For SHG control)
Set 0 as a standard. (For SHG control)
Set the same parameter as the position loop gain for the spindle synchronous control.
0 to 999
0 to 999
Always set the same value for the position loop gain between the spindle and
CAUTION
servo synchronous axes.
8–8
Chapter 8 Adjustment
3
(3) SHG control (option function)
If the position loop gain is increased or feed forward control (CNC function ) is used to shorten the settling time or increase the precision, the machine system may vibrate easily. SHG control changes the position loop to a high-gain by stably compensating the servo system position loop through a delay. This allows the settling time to be reduced and a high precision to be achieved.
(Feature 1) When the SHG control is set, even if PGN1 is set to the same value as the
conventional gain, the position loop gain will be doubled.
(Feature 2) The SHG control response is smoother than conventional position control during
acceleration/deceleration, so the gain can be increased further with SHG control compared to the conventional position control.
(Feature 3) With SHG control, a high gain is achieved so a high precision can be obtained during
contour control.
The following drawing shows an example of the improvement in roundness
characteristics with SHG control.
50.0
0.0
-50.0
-50.0
F=3000mm/minERROR=5.0µm/div)
0.0
Shape error characteristics
During SHG control, PGN1, PGN2 and SHGC are set with the following ratio.
PGN1 : PGN2 : SHGC = 1 :
8
: 6
1) : Commanded path
2) : SHG control (PGN1=47)
3) : Conventional control (PGN1=33)
<Effect>
50.0
Control method
SHG control Conventional
control
Roundness error (µm)
2.5
22.5
During SHG control even if the PGN1 setting value is the same, the actual position loop gain will be higher, so the speed loop must have a sufficient response. If the speed loop response is low, vibration or overshooting could occur during acceleration/deceleration in the same manner as conventional control. If the speed loop gain has been lowered because machine resonance occurs, lower the position loop gain and adjust.
No. Abbrev. Parameter name
SV003 (SV049)
SV004 (SV050)
SV057 (SV058)
SV008 VIA Speed loop leading
SV015 FFC Acceleration feed
PGN1 (PGN1sp)
PGN2 (PGN2sp)
SHGC (SHGCsp)
Position loop gain 1
Position loop gain 2
SHG control gain
compensation
forward gain
The SHG control is an optional function. If the option is not set in the CNC, the
CAUTION
alarm 37 or warning E4, Error Parameter No. 104 (2304 for M50/M64 Series CNC) will be output.
Setting
ratio
1 23 26 33 38 47
8/3 62 70 86 102 125
6 140 160 187 225 281
Set 1900 as a standard for SHG control. 1 to 9999
Set 100 as a standard for SHG control. 0 to 999
Setting example Explanation Setting range
Always set a combination of the three parameters.
1 to 200
0 to 999
0 to 999
8–9
Chapter 8 Adjustment
8-3 Characteristics improvement
8-3-1 Optimal adjustment of cycle time
The following items must be adjusted to adjust the cycle time. Refer to the Instruction Manuals provided with each CNC for the acceleration/deceleration pattern.
1) Rapid traverse rate (rapid) : This will affect the maximum speed during positioning.
2) Clamp speed (clamp) : This will affect the maximum speed during cutting.
3) Acceleration/deceleration time : Set the time to reach the feedrate. constant (G0t∗, G1t)
4) In-position width (SV024) : This will affect each block's movement command end time.
5) Position loop gain (SV003) : This will affect each block's movement command settling time.
(1) Adjusting the rapid traverse rate
To adjust the rapid traverse, the CNC axis specification parameter rapid traverse rate (rapid) and acceleration/deceleration time constant (G0t) are adjusted. The rapid traverse rate is set so that the motor speed matches the machine specifications in the range below the maximum speed in the motor specifications. For the acceleration/deceleration time constants, carry out rapid traverse reciprocation operation, and set so that the maximum current command value at acceleration/deceleration is within the range shown below. (Only when the rapid traverse rate is below the rated speed.) Set the same value as the adjusted acceleration/deceleration time constant in the servo parameter's deceleration control time constant (SV056: EMGt). (When deceleration control is set.) For motors in which the maximum speed is greater than the rated speed, the output torque is particularly restricted in the region at or above the rated speed. When adjusting, watch the current FB waveform during acceleration/deceleration, and adjust so that the torque is within the specified range. Be careful, as insufficient torque can easily occur when the amplifier input voltage is low (170 to 190V), and an excessive error can easily occur during acceleration/deceleration.
HS-MF Series HS-RF Series HS-SF Series
Motor type
HS-MF23 280 to 320% HS-RF43 200 to 240% HS-SF52 420 to 470% HS-RF73 200 to 240% HS-SF53 420 to 470% HS-SF102 440 to 500% HS-SF103 500 to 560% HS-SF202 420 to 470%
Max. current
command value
Motor type
Max. current
command value
Motor type
Max. current
command value
(2) Adjusting the cutting rate
To adjust the cutting rate, the CNC axis specification parameter clamp speed (clamp) and acceleration/deceleration time constant (G1t) are adjusted. The in-position width at this time must be set to the same value as actual cutting.
• Determining the clamp rate and adjusting the acceleration/deceleration time constant
(Features) The maximum cutting rate (clamp speed) can be determined freely. (Adjustment) Carry out cutting feed reciprocation operation with no dwell at the maximum
cutting rate and adjust the acceleration/deceleration time constant so that the maximum current command value during acceleration/deceleration is within the range shown below.
• Setting the step acceleration/deceleration and adjusting the clamp speed (Features) The acceleration/deceleration time constant is determined with the position
loop in the servo, so the acceleration/deceleration F⊿T can be reduced.
(Adjustment) Set 1 (step) for the acceleration/deceleration time constant and carry out
cutting feed reciprocation operation with no dwell. Adjust the cutting feed rate so that the maximum current command value during acceleration/deceleration is within the range shown below, and then set the value in the clamp speed.
8–10
Chapter 8 Adjustment
3
6
60 × G0tL × PGN1
10
0
0
F
G0tL
<Maximum current command value>
For the maximum current command value during acceleration/deceleration, the maximum current command value (MAXcmd) for one second is output to MAX current 1 and MAX current 2 on the CNC servo monitor screen and observed. The meaning of the display for MAX current 1 and MAX current 2 will differ according to the parameter settings.
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit Monitor Meaning when 0 is set Meaning when 1 is set
0 mon
selection 3
(3) Adjusting the in-position width
Because there is a response delay in the servomotor drive due to position loop control, a "settling time" is also required for the motor to actually stop after the command speed from the CNC reaches 0. The movement command in the next block is generally started after it is confirmed that the machine has entered the "in-position width" range set for the machine. The in-position width is effective even when the standard servo parameters are set. However, it may follow the CNC parameters, so refer to the CNC Instruction Manual for the setting.
No. Abbrev. Parameter name Unit Explanation Setting range
SV024 INP In-position detection
width
The in-position width setting and confirmation availability depend on the CNC
POINT
parameters
(4) Adjusting the settling time
The settling time is the time required for the position droop to enter the in-position width after the feed command (F⊿T) from the CNC reaches 0. The settling time can be shortened by raising the position loop gain or using SHG control. However, a sufficient response (sufficiently large VNG1 setting) for the speed loop is required to carry out stable control. The settling time during normal control when the CNC is set to linear acceleration/ deceleration can be calculated using the following equation. During SHG control, estimate the settling time by multiplying PGN1 by 2.
The display data for the maximum current value on the servo monitor is determined with the following parameter.
MAX current 1
MAX current 2
Set 50 as a standard.
µm
Set the precision required for the machine.
Maximum current command value after power is turned ON
Maximum current com-mand value for one second
daf2 daf1 dac2 dac1
Maximum current command value for one second
Maximum current FB value for one second
FT
Position droop
Settling time
In-position width
0 to 32767
Time
In-position
mon
Settling time (msec) =
10
PGN1
×
ln
F × 10
INP
× 1 exp
2
PGN1 × G0tL
3
PGN1 : Position loop gain1 (SV003) (rad/sec) F : Rapid traverse rate (mm/min) G0tL : Rapid traverse linear acceleration/ deceleration time constant (msec)
8–11
Chapter 8 Adjustment
INP : In-position width (SV024) (µm)
Speed command (r/min)
Current command (Stall %)
Example of speed/current command waveform during acceleration/deceleration
(Reference) The rapid traverse acceleration/deceleration time setting value G0tL for when linear
acceleration/deceleration is set is calculated with the following expression.
G0tL =
(JL + JM) × No
95.5 × (0.8 × T
3000
-3000 200
-200
0
Time
0
Time
MAX
– TL)
6000 ( PGN1 × K)
(msec)
2
NO : Motor reach speed (r/min) JL : Motor shaft conversion load inertia (kg·cm2) JM : Motor inertia (kg·cm2) T
: Motor max. torque (N·m)
MAX
TL : Motor shaft conversion load (friction, unbalance) torque (N·m) PGN1 : Position loop gain 1 (rad/sec) K : "1" during normal control, "2" during SHG control
8-3-2 Vibration suppression measures
If vibration (machine resonance) occurs, it can be suppressed by lowering the speed loop gain (VGN1). However, cutting precision and cycle time will be sacrificed. (Refer to "8-2-2 Speed loop gain".) Thus, try to maintain the VGN1 as high as possible, and suppress the vibration using the vibration suppression functions. If the VGN1 is lowered and adjusted because vibration cannot be sufficiently suppressed with the vibration suppression functions, adjust the entire gain (including the position loop gain) again.
<Examples of vibration occurrence>
• A fine vibration is felt when the machine is touched, or a groaning sound is heard.
• Vibration or noise occurs during rapid traverse.
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain
POINT
Suppress the vibration using the vibration suppression functions, and maintain the speed loop gain (SV005: VGN1) as high as possible. (The standard value is the upper limit.)
Set according to the load inertia size. If machine resonance occurs, adjust by lowering in increments of 20 to 30%. The setting value is 70 to 80% of the value where resonance does not occur.
1 to 999
8–12
Chapter 8 Adjustment
(1) Machine resonance suppression filter (Notch filter)
The resonance elimination filter will function at the set frequency. Use the D/A output function to output the current feedback and measure the resonance frequency. Note that the resonance frequency that can be measured is 0 to 500 Hz.
<Setting method>
1. Set the resonance frequency in the machine resonance suppression filter frequency (SV038: FHz).
2. If the machine starts to vibrate at another frequency, raise (make shallower) the notch filter depth compensation value (SV033: SSF2.nfd), and adjust to the optimum value at which the resonance can be eliminated.
3. When the vibration cannot be completely eliminated, use another vibration suppression control (jitter compensation).
No. Abbrev. Parameter name Explanation Setting range
SV038 FHz Notch filter frequency Set the resonance frequency to be suppressed. (Valid at 72 or
SV033 SSF2 Special servo function
selection 2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 nfd
bit Descriptions
0~3 nfd
more). Set 0 when the filter is not to be used.
The notch filter depth compensation is set with the following parameters.
Set the filter depth for the notch filter.
Deeper Shallower Setting value 0 2 4 6 8 A C E Depth (dB) −18.1 −12.0 −8.5 −6.0 −4.1 −2.5 −1.2
(2) Jitter compensation
The load inertia becomes extremely small if the motor position enters the machine backlash when the motor is stopped. Because this means that an extremely large VGN1 is set for the load inertia, vibration may occur. Jitter compensation is the suppression of vibration occurring when the motor stops by ignoring the backlash amount of speed feedback pulses when the speed feedback polarity changes. Increase the number of ignored pulses by one pulse at a time, and set a value at which the vibration can be suppressed. (Because the position feedback is controlled normally, there is no worry of positional deviation.) When an axis that does not vibrate is set, vibration could be induced, so take care.
No. Abbrev. Parameter name Explanation
SV027 SSF1 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
aflt zrn2 ovs2 ovs1 lmc2 lmc1 vfct2 vfct1
4 vfct1 5 vfct2
selection 1
Set the jitter compensation with the following parameter.
bit
No jitter
compensation
0 1 0 1 0 0 1 1
One pulse
compensation
Two pulse
compensation
Jitter compensation vibration suppression is only effective when the motor is
POINT
stopped.
0 to 3000
Three pulse
compensation
8–13
Chapter 8 Adjustment
Frictional
Unbalance
Cutting
8-3-3 Improving the cutting surface precision
If the cutting surface precision or roundness is poor, improvements can be made by increasing the speed loop gain (VGN1, VIA) or by using the disturbance observer function.
<Examples of faults>
• The surface precision in the 45° direction of a taper or arc is poor.
• The load fluctuation during cutting is large, causing vibration or surface precision defects to occur.
Adjust by raising the speed loop gain equivalently to improve cutting surface
POINT
(1) Adjusting the speed loop gain (VGN1)
If the speed loop gain is increased, the cutting surface precision will be improved but the machine will resonate easily. The final VGN1 setting should be approx. 70 to 80% of the maximum value where resonance does not occur. (Refer to "8-2-2 (1) Setting the speed loop gain")
(2) Adjusting the speed loop leading compensation (VIA)
The VIA has a large influence on the position trackability, particularly during high-speed cutting (generally F1000 or more). Raising the setting value improves the position trackability, and the contour precision during cutting can be improved. For high-speed high-precision cutting machines, adjust so that a value equal to or higher than the standard value can be set. When VIA is set lower than the standard value and set to a value differing between interpolation axes, the roundness may worsen (the circle may distort). This is due to differences occurring in the position trackability between interpolation axes. The distortion can be improved by matching the VIA with the smaller of the values. Note that because the position trackability is not improved, the surface precision will not be improved. (Refer to "8-2-2 (2) Setting the speed loop leading compensation")
precision, even if the measures differ. In this case, it is important how much the machine resonance can be controlled, so adjust making sufficient use of vibration suppression functions.
Y
X
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain Increase the value by 20 to 30% at a time.
SV008 VIA Speed loop leading
compensation
If the machine starts resonating, lower the value by 20 to 30% at a time. The setting value should be 70 to 80% of the value where resonance does not occur.
1364 is set as a standard. 1900 is set as a standard during SHG control. Adjust in increments of approx. 100. Raise the VIA and adjust to improve the contour tracking precision in high-speed cutting. If the position droop vibrates (10 to 20Hz), lower the VIA and adjust.
1 to 999
1 to 9999
(3) Voltage non-sensitive zone (Td) compensation
With the PWM control of the inverter, a dead time
direction
Motor torque
(non-energized time) is set to prevent short-circuits caused by simultaneous energizing of the P side and N side transistors having the same phase. The
torque
dead time has a non-sensitive zone for particularly low voltage commands. Thus, when feeding with a low speed and a low torque, the control may be unstable. When an unbalanced axis is lowering, the frictional torque and unbalance torque, and the frictional torque and deceleration torque before the quadrant changes during circle cutting, are balanced. The motor output torque will be approximately zero, and the control accuracy may drop. In this case, the
Deceleration torque =
frictional torque
Lowering
For unbalance torque For circle cutting
torque
control accuracy can be improved by using the voltage non-sensitive band compensation. Note
8–14
0
Balanced
Chapter 8 Adjustment
order
fine
Current command after
Current command
that this may cause vibration to increased while the motor is running.
No. Abbrev. Parameter name Explanation Setting range
SV030 IVC Voltage non-sensitive
band compensation
(4) Fine torque compensation
There may be cases when not much torque is generated during low speed feed, or when the wear torque and unbalance torque during lowering an unbalance axis or the wear torque and deceleration torque before a quadrant torque changeover during circular cutting are unbalanced. These can cause the motor output torque to be approximately zero and the control accuracy to drop. In this case, the control accuracy can be improved by using fine torque compensation. Note that this may cause vibration during motor operation to increase.
SV030 TDCG Voltage non-sensitive
SV040 LMCT Lost motion
SV045 TRUB Collision detection
compensation
band compensation/ fine torque compensation Cx
compensation non-sensitive band/ torque compensation Cy
function frictional torque/fine torque compensation B1
Cy (sv040)
B1 (sv045)
Set the standard value 20. Note that the vibration could increase during motor operation.
Set the fine torque compensation amount Cx in the high-
Stall %
(rated
current %)
8 bits. Normally, 0 is set. Set 255 to use this function.
µm / Set the fine torque compensation Cy in the high-order 8 bits.
Normally, 0 is set. Set 255 to use this function.
To use fine torque compensation, set approx. 10 to 30 in the high-order 8 bits.
/
Current (rated %) for Cx, Cy, B1 setting value 256
MF23 22.5% SF53 24.9%
Cx
(sv030)
before compensation
RF43 13.8% SF102 26.6% RF73 20.1% SF103 30.1% SF52 24.9% SF202 24.8%
0 to 200
–32768
32767
–32768
32767
–32768
32767
to
to
to
8–15
(4) Disturbance observer
Jm
JL : Too low
JL : Too high
JL : Optimum
0
The disturbance observer can reduce the effect caused by disturbance, frictional resistance or torsion vibration during cutting by estimating the disturbance torque and compensating it. It also is effective in suppressing the vibration caused by speed leading compensation control.
<Setting method>
1) Adjust VGN1 to the value where vibration does not occur, and then lower it 10 to 20%.
2) Set the load inertia scale (SV037:JL) with a percentage in respect to the motor inertia of the total load inertia.
3) Set the observer filter band (observer pole) in the disturbance observer 1 (SV043:OBS1), and estimate the high frequency disturbance to suppress the vibration. Set 600 as a standard.
4) Set the observer gain in disturbance observer 2 (SV044:OBS2). The disturbance observer will function here for the first time. Set 100 first, and if vibration does not occur, increase the setting by 50 at a time to increase the observer effect.
5) If vibration occurs, lower OBS1 by 50 at a time. The vibration can be eliminated by lowering OBS2, but the effect of the disturbance observer can be maintained by keeping OBS2 set to a high value.
<Adjustment method>
If the load inertia is not clearly known, estimate it with the following method.
1) With the unbalance axis, set the torque offset (SV032:TOF). (Refer to "8-3-4 (2) Unbalance torque compensation")
2) Set JL = 100, OBS1 = 600, and OBS2 = 0, and carry out a return operation within the range where the axis can operate smoothly. At this time, set the acceleration/deceleration time constant so the acceleration/deceleration torque equals or exceeds (is 100% or higher than) the stall (rated) torque.
3) Observe the estimated disturbance torque using the D/A output, and increase JL until the disturbance torque during acceleration/deceleration becomes small (cannot be observed).
Even when the torque offset is set and JL is an appropriate value, the friction torque amount
remains in the estimated disturbance torque of axes having a large amount of friction. As shown in the graphs below, judge the setting value for JL having only the friction torque remaining as the machine load inertia magnification.
Speed command
0
Estimated disturbance torque
Chapter 8 Adjustment
0
Time
Friction torque
0 0
0
Time
Time
SV037 JL Load inertia scale %
SV043 OBS1 Disturbance observer 1 rad/sec
SV044 OBS2 Disturbance observer 2 %
No. Abbrev. Parameter name Unit Explanation Setting range
Set the load inertia that includes the motor in respect to the motor inertia. (When the motor is a single unit, set 100%)
JL = Set the observer filter band (observer pole).
Set 600 as a standard, and lower the setting by 50 at a time if vibration occurs.
Set the observer gain. Set 100 to 300 as a standard, and lower the setting if vibration occurs.
Jl + Jm
Jm : Motor inertia Jl : Machine inertia
0 to 5000
0 to 1000
0 to 1000
1. When the observer gain is set to zero (OBS2 = 0), the estimated disturbance torque can be output to the D/A output even if the disturbance observer is not functioning.
POINT
2. Parts of the machine that do not move smoothly can be presumed to be the disturbance.
3. When the disturbance observer has been started, the lost motion compensation must be readjusted.
8–16
Chapter 8 Adjustment
Cutting
8-3-4 Improvement of protrusion at quadrant changeover
The response delay (caused by non-sensitive band from friction, torsion, expansion/contraction, backlash, etc.) caused when the machine advance direction reverses is compensated with the lost motion compensation function. With this, the protrusions that occur with the quadrant changeover in the DDB measurement method, or the streaks that occur when the quadrant changes during circular cutting can be improved.
direction
Circle cutting path before compensation Circle cutting path after compensation
(1) Lost motion compensation (LMC)
The lost motion compensation compensates the response delay during the reversal by adding the torque command set with the parameters when the speed direction changes. There are two methods for lost motion compensation. With the intelligent servomotor, type 2 is used as a standard. (The explanation for type 1 method is omitted because it is interchangeable with the old method.)
<Setting method>
1) Set the special servo function selection 1 (SSF1) bit 9. (The LMC type 2 will start).
2) Set the compensation amount with a stall % (rated current % for the general -purpose motor) unit in the lost motion compensation 1 (LMC1). The LMC1 setting value will be used for compensation in the positive and negative directions when LMC2 is 0.
3) If the compensation amount is to be changed in the direction to be compensated, set LMC2. The compensation direction setting will be as shown below with the CW/CCW setting. If only one direction is to be compensated, set the side not to be compensated as –1.
Compensation
point
A X axis: LMC2 X axis: LMC1 B Y axis: LMC1 Y axis: LMC2 C X axis: LMC1 X axis: LMC2 D Y axis: LMC2 Y axis: LMC1
CW CCW
No. Abbrev. Parameter name Explanation
SV027 SSF1 The lost motion compensation starts with the following parameter.
aflt zrn2 ovs2 ovs1 lmc2 lmc1 vfct2 vfct1
bit No LMC LMC type 1 LMC type 2
No. Abbrev.
SV016 LMC1 Lost motion
SV041 LMC2 Lost motion
Special servo function selection 1
Parameter
name
compensation 1
compensation 2
Stall % (rated current %)
Stall % (rated current %)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Unit Explanation Setting range
While measuring the quadrant protrusion amount, adjust with a 5% unit. The ± direction setting value will be applied when LMC2 is set to
0. Set 0 as a standard.
Set this when the compensation amount is to be changed
Compensation
The X axis command direc-
C
tion changes from – to +.
8 lmc1 9 lmc2
8–18
The Y axis command direc-
D
+Y
-X
-Y
0 1 0 1 0 0 1 1
tion changes from + to –.
The X axis command direc-
A
tion changes from + to –.
+X
The Y axis command direc-
B
tion changes from – to +.
Setting
prohibited.
–1 to 200
–1 to 200
Chapter 8 Adjustment
2
and the adaptive filter cannot be simultaneously started. A parameter error
according to the direction.
<Adjustment method>
First confirm whether the axis to be compensated is an unbalance axis (vertical axis, slant axis). If it is an unbalance axis, carry out the adjustment after performing step "(2) Unbalance torque compensation". Next, measure the frictional torque. Carry out reciprocation operation (approx. F1000) with the axis to be compensated and measure the load current % when fed at a constant speed on the CNC servo monitor screen. The frictional torque of the machine at this time is expressed with the following expression.
Frictional torque =
The standard setting value for the lost motion compensation 1 (LMC1) is double the frictional torque above.
(Example)
Assume that the load current % was 25% in the + direction and –15% in the – direction when JOG feed was carried out at approx. F1000. The frictional torque is as shown below, so 20% × 2 = 40% is set for LMC1. (Compensated in both directions with LMC2 set to 0.) With this setting, 40% compensation will be carried out when the command reverses from the + direction to the – direction, and when the command reverses from the – direction to the + direction.
LMC1 = 20% × 2 = 40% (Compensated in both directions with LMC2 set to 0.)
For the final adjustment, measure the CNC sampling measurement (DBB measurement) or while carrying out actual cutting. If the compensation amount is insufficient, increase LMC1 or LMC2 by 5% at a time. Note that if the setting is too high, biting may occur.
Compensation 0 Optimum Too high
1. When either parameter SV016: LMC1 or SV041: LMC2 is set to 0, the same
2. To compensate in only one direction, set -1 in the parameter (LMC1 or
3. The value set based on the friction torque is the standard value for LMC
POINT
4. When the disturbance observer has been started, the observer
5. Once LMC compensation type 1 is started, the overshooting compensation
(+ feed load current %) – (– feed load current %)
25 – (–15) 2
= 20%
amount of compensation is carried out in both the positive and negative direction with the setting value of the other parameter (the parameter not set to
0). LMC2) for the direction in which compensation is prohibited. compensation. The optimum compensation value changes with the cutting
conditions (cutting speed, cutting radius, blade type, workpiece material, etc.). Be sure to ultimately make test cuts matching the target cutting and determine the compensation amount.
compensation will also be effective on quadrant protrusions, so the optimum compensation amount of the lost motion compensation will drop. Note that the quadrant protrusions cannot be completely compensated with only the disturbance observer.
8–19
will occur.
Chapter 8 Adjustment
8–20
(2) Unbalance torque compensation
After
If the load torque differs in the positive and negative directions such as with a vertical axis or slant axis, the torque offset (TOF) is set to carry out accurate lost motion compensation.
<Setting method>
Measure the unbalance torque. Carry out reciprocation operation (approx. F1000) with the axis to be compensated and measure the load current % when fed at a constant speed on the CNC servo monitor screen. The unbalance torque at this time is expressed with the following expression.
Unbalance torque =
(+ feed load current %) – (– feed load current %) 2
The unbalance torque value above is set for the torque offset (TOF). If there is a difference in the protrusion amount according to the direction, make an adjustment with LMC2. Do not adjust with TOF.
(Example)
Assume that the load current % was 40% in the + direction and 20% in the – direction when JOG feed was carried out at approx. F1000. The unbalance torque is as shown below, so 30% is set for TOF.
Chapter 8 Adjustment
−40 + (−20) 2
= −30%
No. Abbrev. Parameter name Unit Explanation Setting range
SV032 TOF Torque offset Stall % (rated
current %)
Set this when carrying out lost motion compensation. Set the unbalance torque amount.
–100 to 100
Even when TOF is set, the torque output characteristics of the motor and load
POINT
current display of the CNC servo monitor will not change. Both the LMC compensation and collision detection function are affected.
(3) Adjusting the lost motion compensation timing
If the speed loop gain has been lowered from the standard setting value because the machine rigidity is low or because machine resonance occurs easily, or when cutting at high speeds, the quadrant protrusion may appear later than the quadrant changeover point on the servo control. In this case, suppress the quadrant protrusion by setting the lost motion compensation timing (SV039: LMCD) to delay the LMC compensation.
<Adjustment method>
If a delay occurs in the quadrant protrusion in the circle or arc cutting as shown below in respect to the cutting direction when CNC sampling measurement (DDB measurement) or actual cutting is carried out, and the compensation appears before the protrusion position, set the lost motion compensation timing (SV039:LMCD). While measuring the arc path, increase LMCD by 10 msec at a time, to find the timing that the protrusion and compensation position match.
compensation
Cutting direction
Before timing delay compensation After timing delay compensation
8–21
Chapter 8 Adjustment
No. Abbrev. Parameter name Unit Explanation Setting range
SV039 LMCD Lost motion
compensation timing
When the LMCD is gradually raised, a two-peaked contour may occur at the motor FB position DBB measurement. However, due to the influence of the cutter diameter in cutting such as end milling, the actual cutting surface becomes smooth. Because satisfactory cutting can be achieved even if this two-peaked contour occurs, consider the point where the protrusion becomes the smallest and finest possible without over compensating (bite-in) as the optimum setting.
Cutter center path
Cutter diameter
Actual cutting surface
Cutting direction
(4) Adjusting for feed forward control
In LMC compensation, a model position considering the position loop gain is calculated based on the position command sent from the CNC, and compensation is carried out when the feed changes to that direction. When the CNC carries out feed forward (fwd) control, overshooting equivalent to the operation fraction unit occurs in the position commands, and the timing of the model position direction change may be mistaken. As a result, the LMC compensation timing may deviate, or compensation may be carried out twice. If feed forward control is carried out and the compensation does not operate correctly, adjust with the non-sensitive band (SV040: LMCT) during feed forward control. In this non-sensitive band control, overshooting of a set width or less is ignored. The model position direction change point is correctly recognized, and the LMC compensation is correctly executed. This parameter is meaningless when feed forward control is not being carried out.
<Adjustment method>
If the compensation timing deviates during feed forward control, increase the LMCT setting by 1µm at a time. Note that 2µm are set even when the LMCT is set to 0.
No. Abbrev. Parameter name Unit Explanation Setting range
SV040 LMCT Non-sensitive band
during feed forward control
Setting of the non-sensitive band (SV040: LMCT) during feed forward control
POINT
is effective for improving overshooting compensation mis-operation during feed forward control.
Set this when the lost motion compensation timing does not
msec
match. Adjust while increasing the value by 10 at a time.
Quadrant changeover point
This setting is valid only during feed forward control.
µm
2 µm is set when this is set to 0. Adjust by increasing the value by 1 µm at a time.
Point of LMC compensation execution
0 to 2000
0 to 100
8–22
Chapter 8 Adjustment
0
0
Overshoot
0
0
Overshoot
8-3-5 Improvement of overshooting
The phenomenon when the machine position goes past or exceeds the command during feed stopping is called overshooting. Overshooting is compensated by overshooting compensation (OVS compensation). The phenomenon when the machine position exceeds the command during feed stopping is called overshooting. Overshooting occurs due to the following two causes.
1. Machine system torsion: Overshooting will occur mainly during rapid traverse settling
2. Machine system friction: Overshooting will occur mainly during one pulse feed Either phenomenon can be confirmed by measuring the position droop.
Speed FB
Position droop
Time
1. Overshooting during rapid traverse settling 2. Overshooting during pulse feed
(1) Overshooting compensation (OVS compensation)
In OVS compensation, the overshooting is suppressed by subtracting the torque command set in the parameters when the motor stops. OVS compensation has a compensation effect for the overshooting during either rapid traverse settling or pulse feed. Note that there is no compensation if the next feed command has been issued before the motor positioning (stop). (Therefore, there is no compensation during circle cutting.) There is also no compensation when the CNC is carrying out feed forward control.
<Setting and adjustment methods>
1) Set the special servo function selection 1 (SV027:SSF1) bit 10. (OVS compensation will start.)
2) Observe the position droop waveform using the D/A output, and increase the overshoot
compensation 1 (SV031: OVS1) value 1% at a time. Set the smallest value where the overshooting does not occur. If SV042:OVS2 is 0, the overshooting will be compensated in both the forward/reverse directions with the OVS1 setting value.
3) If the compensat ion amount is to be changed in the direction to be compensated, set the +
direction compensation value in OVS1 and the – direction compensation value in OVS2. If only one direction is to be compensated, set the side not to be compensated as –1. The compensation direction setting will be as reversed with the CNC parameter CW/CCW setting.
In OVS compensation, there is no compensation in the following cases.
1. There is no compensation if the next feed command has been issu ed
POINT
before the motor positioning (stop). (There is no compensation in circle cutting.)
2. There is no compensation when the CNC is carrying out feed forward (fwd) control.
Position command
Position droop
Time
8–23
Overshooting compensation type 1
No. Abbrev. Parameter name Explanation
SV027 SSF1 The overshooting compensation starts with the following parameter.
aft zrn2 ovs1 lmc2 lmc1 vfct2 vfct1
bit Meaning when "0" is set. Meaning when "1" is set. 10 ovs1
No. Abbrev. Parameter name Unit Explanation Setting range
SV031 OVS1 Overshooting
SV042 OVS2 Overshooting
POINT
Special servo function selection 1
compensation 1
compensation 2
Stall % (rated current %)
Stall % (rated current %)
1. When either parameter SV031: OVS1 or SV042: OVS2 is set to 0, the same amount of compensation is carried out in both the positive and negative direction, using the setting value of the other parameter (the parameter not set to 0).
2. To compensate in only one direction, set -1 in the parameter (OVS1 or OVS2) for the direction in which compensation is prohibited.
3. For contour cutting, the projection at the arc end point is compensated with OVS compensation. LMC compensation is carried out at the arc starting point.
Chapter 8 Adjustment
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Overshooting compensation type 1 stop
Increase the value by 1% at a time, and find the value where overshooting does not occur. When OVS2 is set to 0, the setting value will be applied in both the ± directions.
Set 0 as a standard. Set this when the compensation amount is to be changed according to the direction.
OVS compensation
Cutting direction
start
–1 to 100
–1 to 100
LMC compensation
8–24
Chapter 8 Adjustment
-200
-200
Time Time
Time Time
8-3-6 Improvement of characteristics during acceleration/deceleration
(1) SHG control (option function)
Because SHG control has a smoother response than conventional position controls, the acceleration/deceleration torque (current FB) has more ideal output characteristics (A constant torque is output during acceleration/deceleration.) The peak torque is kept low by the same acceleration/deceleration time constant, enabling the time constant to be shortened. Refer to item "(3) SHG control" in section "8-2-3 Position loop gain" for details on setting SHG control.
3000
Speed command (r/min.)
-3000 200
Current FB (stall %)
3000
Speed command (r/min.)
-3000 200
Current FB (stall %)
No. Abbrev. Parameter name
SV003
(SV049)
SV004
(SV050)
SV057
(SV058)
SV008 VIA
SV015 FFC
PGN1
(PGN1sp)
PGN2
(PGN2sp)
SHGC
(SHGCsp)
Position loop gain 1 1 23 26 33 38 47 1 to 200
Position loop gain 2 8/3 62 70 86 102 125 0 to 999
SHG control gain 6 140 160 187 225 281 Speed loop leading
compensation Acceleration feed
forward gain
0
0
Acceleration/deceleration characteristics during conventional control
0
0
Acceleration/deceleration characteristics during SHG control
Setting
ratio
Set 1900 as a standard value during SHG control. 1 to 9999
Set 100 as a standard value during SHG control. 0 to 999
Setting example Explanation Setting range
Always set a combination of 3 parameters.
0 to 999
8–25
(2) Acceleration feed forward
60 40 20
60 40 20
Vibration may occur at 10 to 20 Hz during acceleration/deceleration when a short time constant of 30 msec or less is applied, and a position loop gain (PGN1) higher than the general standard value or SHG control is used. This is because the torque is insufficient when starting or when starting deceleration, and can be resolved by setting the acceleration feed forward gain (SV015:FFC). This is also effective in reducing the peak current (torque). While measuring the current command waveform, increase FFC by 50 to 100 at a time and set the value where vibration does not occur.
Chapter 8 Adjustment
Current command (Stall %)
200
100
0
200
100
0
0
Timemsec
80
100
0
Timemsec
80
No FFC setting With FFC setting
Acceleration feed forward gain means that the speed loop gain during acceleration/deceleration is raised equivalently. Thus, the torque (current command) required during acceleration/deceleration starts sooner. The synchronization precision will improve if the FFC of the delayed side axis is raised between axes for which high-precision synchronous control (such as synchronous tap control and superimposition control).
No. Abbrev. Parameter name Unit Explanation Setting range
SV015 FFC Acceleration feed
forward gain
A 10 10 50 50 Standard value
% The standard setting value is 0. To improve the
acceleration/deceleration characteristics, increase the value by approx. A given below. During SHG control, use the standard setting values given below.
Motor MF23 RF43/73
for SHG control
10 10 100 100
SF52/53/
102/103
SF202
1 to 999
100
POINT
during SHG control.
8–26
Overshooting occurs easily when a value above the standard value is set
Chapter 8 Adjustment
0
-200
compensation
With inductive
(3) Inductive voltage compensation
The current loop response is improved by compensating the back electromotive force element induced by the motor rotation. This improved the current command efficiency, and allows the acceleration/deceleration time constant to the shortened.
<Adjustment method>
1) Set 1 in "mon" of the special servo function selection 3 (SV034: SSF3) bit 0, and output the current command and current FB to the servo monitor.
2) While accelerating/decelerating at rapid traverse, adjust the inductive voltage compensation gain (SV047:EC) so that the current FB peak is a few % smaller than the current command peak.
3000
Speed command (r/min)
-3000 200
No inductive voltage
Time
Current command (stall %)
0
voltage compensation
Time
Inductive voltage compensation
To adjust the inductive voltage compensation, output 1 second of the maximum current command value and 1 second of the maximum current FB value to MAX current 1 and MAX current 2 on the CNC servo monitor screen and observe. Change over and display "mon" of the special servo function selection 3 (SV034: SSF3).
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit Monitor Meaning when 0 is set Meaning when 1 is set
0 mon
No. Abbrev. Parameter name Unit Explanation Setting range
SV047 EC
selection 3
Inductive voltage compensation gain
The display data for the maximum current value on the servo monitor is determined with the following parameter.
daf1 dac1
MAX current 1
MAX current 2
Set 100% as a standard. Lower the gain if the current FB peak
%
exceeds the current command peak.
Maximum current command value after power is turned ON
Maximum current com-mand value for one second
Maximum current command value for one second
Maximum current FB value for one second
mon
0 to 200
If the current FB peak is larger than the current command peak, overcompensation or overcurrent (alarm 3A) could occur easily. Note that
POINT
when using with a large load inertia, or when using over the rated rotation speed with a motor set to rated rotation speed < maximum rotation speed, overcompensation could occur easily.
8–27
Chapter 8 Adjustment
EMGt
Constant inclination deceleration
Time
Dynamic brakes activate at 60 r/min or less
8-4 Setting for emergency stop
The emergency stop referred to here indicates the following states.
1) When the external emergency stop was input (including other axis alarms)
2) When the CNC power down was detected
3) When a servo alarm was detected
8-4-1 Deceleration control
This intelligent servomotor servo amplifier decelerates the motor according to the set time constant in the ready ON state even when an emergency stop occurs, and activates the dynamic brakes after stopping and turning ready OFF. This series of controls is called deceleration control. In the intelligent servomotor, deceleration control is the standard method of stopping during an emergency stop.
<Features>
1) When the load inertia is large, deceleration and stop are possible with a short time constant using the dynamic brakes. (Stopping is possible with a basically normal acceleration/ deceleration time constant.)
2) When used in a transfer line, etc., stopping with little shock is possible by setting a long time constant.
(1) Setting the deceleration control time constant
The time to stopping from the rapid traverse rate (rapid: axis specification parameter) is set in the deceleration control time constant (SV056: EMGt). A position loop step stop is carried out when 0 is set. When linear (straight line) acceleration/deceleration is selected for the rapid traverse, the same value as the acceleration/deceleration time constant (G0tL) becomes the standard value. When another acceleration/deceleration pattern is selected, set the rapid traverse to linear acceleration/deceleration. Adjust to the optimum acceleration/deceleration time constant, and set that value as the standard value.
<Operation>
When an emergency stop occurs, the motor will decelerate at the same inclination from each speed, and will change to the dynamic brakes at 60 r/min or less. If the power fails, etc., the dynamic brakes will be applied during the deceleration control. When the motor brakes are controlled with amplifier output while using an unbalanced axis, the motor brake control output operates simultaneously with the changeover to the dynamic brakes.
RAPID
Motor speed
Dynamic brakes
Motor brake control output (MBR)
OFF ON
OFF ON
Emergency stop occurrence
No. Abbrev. Parameter name Unit Explanation Setting range
SV056 EMGt Deceleration control
time constant
Set the time to stop from rapid traverse rate (rapid).
msec
Set the same value as the rapid traverse acceleration/deceleration time constant (G0tL) as a standard.
0 to 5000
1. The deceleration will not be controlled when a servo alarm that uses the dynamic brake stopping method occurs. Stopping is by the dynamic brake method regardless of the parameter setting.
POINT
2. When a power failure occurs, the stopping method may change over to a dynamic brake stop during deceleration control if the deceleration time constant is set comparatively long. This is because of low bus voltage in the amplifier.
8–24
CAUTION
PGN1 × 60
2
60
rapid × 1000
Time
(2) Dynamic brake stop
When an emergency stop occurs, it is possible to have the machine stop from the beginning using a dynamic brake without controlling the deceleration. Set bit 0 in the servo specifications (SV017: SPEC) to select a dynamic brake stop. In a dynamic brake stop, the dynamic brakes operate at the same time the emergency stop occurs, and the motor brake output also operates at the same time.
Chapter 8 Adjustment
If the deceleration control time constant (EMGt) is set longer than the acceleration/deceleration time constant, the overtravel point (stroke end point) may be exceeded. A collision may be caused on the machine end, so be careful.
Emergency stop occurrence
Motor speed
Dynamic brakes
Motor brake control output (MBR)
OFF
ON
OFF
ON
No. Abbrev. Parameter name Explanation
SV017 SPEC Servo specifications Set the dynamic brake stop with the following parameter.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 abs vdir mc dmk
bit Meaning when "0" is set. Meaning when "1" is set. 0 dmk Deceleration control stop Dynamic brake stop
If a dynamic brake stop is selected, the software does not participate at all in
POINT
CAUTION
the motor stop control after an emergency stop occurs.
When a dynamic brake stop is selected, in general the coasting distance during an emergency stop will be comparatively longer, so be careful.
(3) Deceleration control stop distance
If stopping with deceleration control during an emergency stop, the stop distance L
DEC
approximately calculated with the following expression. However, the value will be higher than the following expression if the current is limited during deceleration. Refer to section "3-3-2 Coasting amount" for the stop distance using dynamic brakes.
L
DEC
=
F
+
1
×
F
×
F × EMGt
(mm)
can be
F : Feedrate during emergency stopped (mm/min) rapid : Rapid traverse rate (mm/min) PGN1 : Position loop gain 1 (SV003) (rad/sec) EMGt : Deceleration control time constant (SV056) (msec)
8–25
Chapter 8 Adjustment
mum
Brake activation delay
Time
8-4-2 Vertical axis drop prevention control
The vertical axis drop prevention control is a function that prevents the vertical axis from dropping due to a delay in the brake operation when an emergency stop occurs. The servo ready OFF will be delayed by the time set in the parameter from when the emergency stop occurs. Thus, the no-control time until the brakes activate can be eliminated.
<Setting and adjustment methods>
Set the time to delay the ready OFF in the vertical axis drop prevention time (SV048:EMGrt). Read the current position on the CNC screen, and apply the emergency stop. Set the minimum delay time where the axis does not drop.
Motor speed
Emergency stop occurrence
Deceleration control
Dynamic brakes
Motor brake control output (MBR)
Motor brake actual operation
Servo ready (READY)
OFF ON
OFF ON
OFF ON
ON OFF
EMGrt
No. Abbrev. Parameter name Unit Explanation Setting range
SV048 EMGrt Vertical axis drop
prevention time
Input the time to delay the ready OFF when an emergency stop
msec
occurs. Increase the setting by 100 msec at a time and set the mini value where the axis does not drop.
0 to 2000
1. This control will not function if the dynamic brake stop is selected with the servo specifications (SV017: SPEC).
2. This control will not function if an alarm for which the dynamic brakes are
POINT
set as the stopping method occurs in an axis where vertical axis drop prevention control is being carried out.
3. A drop amount of several µm to 10µm will remain due to the brake play.
CAUTION
1. Do not set a vertical axis drop prevention time longer than required. The servo control and brakes could collide causing an overload alarm or amplifier damage. There is no problem if the duplicate time is within 100msec.
2. During a power failure, vertical axis drop prevention cont rol (including deceleration control) exceeding 100msec cannot be guaranteed. The control will change to the dynamic brakes.
8–26
Chapter 8 Adjustment
0
SV032)
SV060)
G1 feed (cutting feed)
G0 feed (rapid traverse)
SV060×clG1
8-5 Collision detection
The purpose of the collision detection function is to quickly detect a collision and decelerate to a stop. This suppresses the excessive torque generated to the machine tool, and suppresses the occurrence of an abnormality. Impact during a collision cannot be prevented even when the collision detection function is used, so this function does not guarantee that the machine will not break and does not guarantee the machine accuracy after a collision. Thus, the conventional caution is required to prevent machine collisions from occurring.
(1) Collision detection method 1
The required torque is calculated from the position command issued from the NC. The disturbance torque is calculated from the difference with the actual torque. When this disturbance torque exceeds the collision detection level set with the parameters, the axis will decelerate to a stop with at 80% of the motor's maximum torque. After decelerating to a stop, the alarm 58 or 59 will occur, and the system will stop. The collision detection level for rapid traverse (G0) is set with TLMT: SVC060. The collision detection level for cutting feed (G1) is set to 0 to 7-fold (SV053.clG1) based on the collision detection level for rapid traverse. If 0 is set for clG1, the collision detection method 1 will not function during cutting feed. If 0 is set for TLMT: SV060, all collision detections (method 1 and method 2) will not function.
Estimated torque (stall %)
Speed command (r/min)
3000
-3000
200
100
-100
-200
0
G0 collision detection level
Alarm detection range for collision detection method 1
(2) Collision detection method 2
When the current command reaches the motor's maximum current, the axis will decelerate to a stop with at 80% of the motor's maximum torque. After decelerating to a stop, the alarm 5A will occur, and the system will stop. If the acceleration/deceleration time constant is short and incorrect detections are made easily during normal operation, increase the acceleration/deceleration time constant and adjust so that the current during acceleration is not saturated (so that the maximum current is not reached). If the acceleration/deceleration time constant cannot be increased, set parameter SV035.bit11: SSF4.cl2n to 1 to ignore the collision detection method 2.
The collision detection function does not guarantee safety or machine
CAUTION
accuracy during a collision. Thus, the conventional caution is required to prevent machine collisions from occurring.
Collision detection method 1 detection range (Alarm 58/59)
G0 collision detection level
Collision
For rapid traverse (for G0 feed)
For cutting feed (for G1 feed)
detec-tion level
setting parameter
SV060 Alarm 58
SV060×clG1
(SV035)
Frictional torque
(SV045)
Unbalance torque
Detection
Alarm 59
alarm
8–27
<Setting and adjustment methods>
1. Validate the extended function. (Set sv035: SSF4, bit7 (eram) to 1.)
2. Confirm that SHG control is being used. The collision detection function is valid only during SHG control.
3. Measure the unbalance torque, and set in the torque offset (SV03: TOF). Refer to the section "8-3-4 (2) Unbalance torque compensation" for details on measuring the unbalance torque.
4. Measure the frictional torque, and set in the frictional torque (SV045: TRUB). Refer to the section "8-3-4-(1) Lost motion compensation" for details on measuring the frictional torque.
5. Set the estimated torque gain (SV059: TCNV) with the following method. Set sv035: SSF5, bit 15 (clt) for the axis to be adjusted to 1. Repeatedly move the axis to be adjusted in both directions at the maximum rapid traverse rate. Observe the MPOF display value on the NC unit's [I/F Diagnosis/Servo Monitor] screen, and continue operation until the display value stabilizes. Once the display value stabilizes, set that value as the estimated torque gain (SV059: TCNV).
6. If the acceleration/deceleration time is short and the current is easily saturated, set SV035.bit15(cl2n) to 1, and ignore the collision detection method 2.
7. Set the collision detection level.
Feed Detection level setting Explanation
G0 SV060
G1 SV060×clG1 (SV035)
1. The SHG control must be validated to use the collision detection function or to carry out load inertia measurement operation.
2. When measuring the estimated torque gain, if the unbalance torque (SV032) and frictional torque (SV045) setting values are changed, the
POINT
measurement results will change. The unbalance torque and frictional torque must be set as accurately as possible to carry out accurate measurement.
3. Set the detection level with an allowance to avoid incorrect detections.
4. When SV060 is set to 0, all collision detection functions will be invalidated.
Chapter 8 Adjustment
First set SV060: TLEV = 100, and carry out no-load operation at the maximum rapid traverse feed rate. If an alarm does not occur, lower the setting by 10, and if an alarm occurs, raise the setting by 20. Set a value that is 1.5 times the limit value where the alarm does not occur. If SV034.mon is set to 7, the maximum disturbance torque will appear on the NC servo monitor, so adjust using this value as a reference.
The detection level for G1 is set as an integer-fold of the G0 detection level. Calculate the maximum cutting load, and adjust the SV035.clG1 setting value so that the detection level is larger than the maximum cutting load.
8–28
Chapter 8 Adjustment
ue) is displayed
No. Abbrev. Parameter name Explanation
SV035 SSF4 The following parameters are used for the collision detection.
clt clG1 cl2n clet eram
bit Meaning when "0" is set. Meaning when "1" is set. 7 eram Extended function invalid Extended function invalid
10 clet During normal use
11 cl2n Collision detection method 2 valid
15 clt During normal use
SV032 TOF Torque offset Stall % (rated
SV045 TRUB Frictional torque Stall % (rated
SV059 TCNV Torque estimated gain (load
SV060 TLMT G0 collision detection level Stall % (rated
Special servo function selection 4
inertia rate)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The latest two-second estimated disturbance torque peak value (3.5ms average val at MPOF on the Servo Monitor screen.
Collision detection method 2 invalid
12
to
14
current %)
current %)
current %)
Set the collision detection level for collision detection method 1, cutting (G1) feed.
clG1
The G1 collision detection level is SV060 × clG1. When clG1 is set to 0, the collision detection method 1 will not function during cutting feed.
The value to be set in TCNV is calculated and displayed at MPOF on the Servo Monitor screen.
Set the unbalance torque amount. –100 to 100
Set the frictional torque for using the collision detection function.
Set the torque estimated gain for using the collision
detection function. If acceleration/deceleration operation is carried out with SV035.clt set to 1 and SV060 set to 0, the estimated torque gain will be displayed on the NC Monitor screen.
Set the collision detection level of method 1 G0 feed when using the collision detection function. When 0 is set, all collision detection functions will not function.
0 to 100
0 to 5000
0 to 200
8–29
Chapter 8 Adjustment
speed
8-6 Parameter list
No. Abbrev. Parameter name Unit Explanation
SV001 PC1 Motor side gear ratio 1 to 32767 SV002 PC2 SV003 PGN1 Position loop gain 1 rad/sec SV004 PGN2 Position loop gain 2 rad/sec
SV005 VGN1 Speed loop gain
SV006 Set "0". 0 SV007 Set "0". 0
SV008 VIA
SV009 IQA SV010 IDA
SV011 IQG q axis gain 1 to 2560 SV012 IDG d axis gain
SV013 ILMT Current limit value
SV014 ILMTsp
SV015 FFC
SV016 LMC1
SV017 SPEC Servo specifications
SV018 PIT Ball screw pitch mm SV019 RNG1 SV020 RNG2
Machine side gear ratio
Speed loop leading compensation
q axis leading compensation
d axis leading compensation
Current limit value during special operation
Acceleration feed forward gain
Lost motion compensation 1
Position detector resolution
Speed detector resolution
1 to 20480 1 to 20480
Stall % (rated current %)
Stall % (rated current %)
Stall % (rated current %)
Set "0" in bits with no particular description.
kp/rev 8 to 100 kp/rev
Set the motor side and machine side gear ratio. For the rotary axis, set the total deceleration (acceleration) ratio. Even if the gear ratio is within the setting range, the electronic gears may overflow and cause an alarm.
Set the position loop gain. Set 33 as a standard. When using SHG control, also set PGN2 and SHGC.
Set 0 as a standard. When using SHG control, also set PGN1 and SHGC.
Set this according to the motor inertia size. If motor resonance occurs, lower the value by 20 to 30% at a time. The setting value should be 70 to 80% of the value where resonance does not occur.
Set 1364 as a standard. During SHG control, set 1900 as a standard. Raise this value to improve contour tracking precision in high­cutting. Lower this value when the position droop vibrates. Adjust by 100 at a time.
This setting is determined by the motor's electrical characteristics. Set the standard parameters for all parameters. (These are used for maker adjustments.)
Set the standard parameter value. The maximum torque is determined by the motor specifications.
Set the standard parameter value. Set the limit torque mainly for the stopper.
The standard setting value is 0. For SGH control, set 100.
%
To improve the acceleration/deceleration characteristics, increase the value by 50 to 100 at a time.
The protrusion amount during quadrant changeover is suppressed. Adjust in 5% units. When LMC2 is set to 0, the setting value will apply in both the ± directions.
bit Meaning when "0" is set Meaning when "1" is set
0 dmk 1
2 3 4 5 6 7 abs Incremental control Absolute position control 8
9 10 11 12 mtc 13 14 15
Deceleration controlo stop selection (SVJ2 standard)
Motor table selection according to model Set 0100 for the intelligent servomotor HS Series.
Set the ball screw pitch. Set 360 for the rotary axis. Refer to the CNC Instruction Manual for the inch ball screw.
Set the motor detector resolution for both settings. Refer to the Standard parameter list per motor for the settings.
Dynamic brake stop selection
Setting
range
1 to 32767
1 to 200 0 to 999
1 to 999
1 to 9999
1 to 2560
0 to 500
0 to 500
1 to 999
–1 to 200
1 to 32767
8 to 100
SV001 is a parameter validated when the NC power is turned ON again.
8–30
Loading...