Thank you for purchasing the Mitsubishi CNC.
This instruction manual describes the handling and caution points for using this CNC.
Incorrect handling may lead to unforeseen accidents, so always read this instruction
manual thoroughly to ensure correct usage.
Make sure that this instruction manual is delivered to the end user.
Precautions for safety
Please read this instruction manual and auxiliary documents before starting
installation, operation, maintenance or inspection to ensure correct usage.
Thoroughly understand the device, safety information and precautions before starting
operation.
The safety precautions in this instruction manual are ranked as "DANGER" and
"CAUTION".
DANGER
When a dangerous situation may occur if handling is
mistaken
leading to fatal or major injuries.
CAUTION
When a dangerous situation may occur if handling is
mistaken
leading to medium or minor injuries, or physical damage.
Note that some items described as CAUTION may lead to major results
depending on the situation. In any case, important information that must be
observed is described.
The signs indicating prohibited and mandatory items are described below.
This sign indicates that the item is prohibited (must not be
carried out). For example, is used to indicate "Fire
Prohibited".
This sign indicates that the item is mandatory (must be carried
out). For example, is used to indicate grounding.
After reading this instruction manual, keep it in a safe place for future reference.
In this manual, this mark indicates important matters the operator
POINT
should be aware of when using the CNC.
I
For Safe Use
1. Electric shock prevention
Wait at least 10 minutes after turning the power OFF, check the voltage between L1-L2-L3
and L11-L12 terminals with a tester, etc., before starting wiring or inspections.
Failure to observe this could lead to electric shocks.
Ground the servo amplifier and servomotor with Class 3 grounding or higher.
Wiring and inspection work must be done by a qualified technician.
Wire the servo amplifier and servomotor after installation. Failure to observe this could lead
to electric shocks.
Do not touch the switches with wet hands. Failure to observe this could lead to electric
shocks.
Do not damage, apply forcible stress, place heavy items or engage the cable. Failure to
observe this could lead to electric shocks.
DANGER
2. Fire prevention
Install the servo amplifier, servomotor and regenerative resistor on noncombustible material.
Direct installation on combustible material or near combustible materials could lead to fires.
Following the instructions in this manual, always install no-fuse breakers and contactors on
the servo amplifier power input. Select the correct no-fuse breakers and contactors using this
manual as a reference. Incorrect selection could lead to fires.
Shut off the main circuit power at the contactors to emergency stop when an alarm occurs.
CAUTION
II
3. Injury prevention
CAUTION
Do not apply a voltage other than that specified in Instruction Manual on each terminal.
Failure to observe this item could lead to ruptures or damage, etc.
Do not mistake the terminal connections. Failure to observe this item could lead to ruptures
or damage, etc.
Do not mistake the polarity(+ ,–) . Failure to observe this item could lead to ruptures or
damage, etc.
Do not touch the servo amplifier fins, regenerative resistor or servomotor, etc., while the
power is turned ON or immediately after turning the power OFF. Some parts are heated to
high temperatures, and touching these could lead to burns.
4. Various precuations
Observe the following precautions. Incorrect handling of the unit could lead to faults, injuries and
electric shocks, etc.
(1) Transportation and installation
Correctly transport the product according to its weight.
Do not stack the products above the tolerable number.
Do not hold the cables, axis or detector when transporting the servomotor.
Follow this Instruction Manual and install the unit in a place where the weight can be borne.
Do not get on top of or place heavy objects on the unit.
Always observe the installation directions.
Do not install or run a servo amplifier or servomotor that is damaged or missing parts.
Do not let conductive objects such as screws or metal chips, etc., or combustible materials
such as oil enter the servo amplifier or servomotor.
The servo amplifier and servomotor are precision devices, so do not drop them or apply
strong impacts to them.
CAUTION
III
CAUTION
Store and use the units under the following environment conditions.
Environment
Ambient
temperature
Ambient humidity
Storage temperature
Storage humidity
Atmosphere
Altitude 1000m or less above sea level
Vibration
(with no dew condensation)
HS-RF
HS-SF
(1kW or less)
HS-SF
(2.0kW or
less)
HS-MF
Servomotor Interface unit
0°C to +40°C
(with no freezing)
80% RH or less
–15°C to +65°C
(with no freezing)
90% RH or less (with no dew condensation)
Indoors (Where unit is not subject to direct sunlight)
With no corrosive gas, combustible gas, oil mist or dust.
X: 9.8m/sec2 (1G)
Y: Y: 24.5m/sec2
(2.5G) or less
X: 19.6m/sec2 (2G)
Y: 49m/sec2 (5G) or
less
X: 19.6m/sec2 (2G)
Y: 19.6m/sec2 (2G)
or less
Conditions
0°C to +55°C
(with no freezing)
90%RH or less
(with no dew condensation)
–20°C to +65°C
(with no freezing)
5.9m/sec2 (0.6G) or less
Securely fix the servomotor to the machine. Insufficient fixing could lead to the
servomotor deviating during operation.
Never touch the rotary sections of the servomotor during operations. Install a cover, etc.,
on the shaft.
When coupling to a servomotor shaft end, do not apply an impact by hammering, etc.
The detector could be damaged.
Do not apply a load exceeding the tolerable load onto the servomotor shaft. The shaft
could break.
When storing for a long time, please contact your dealer.
IV
(2) Wiring
Correctly and securely perform the wiring. Failure to do so could lead to runaway of the
servomotor.
(3) Trial operation and adjustment
Check and adjust each parameter before starting operation. Failure to do so could lead to
unforeseen operation of the machine.
Do not make remarkable adjustments and changes as the operation could become unstable.
CAUTION
CAUTION
(4) Usage methods
Install an external emergency stop circuit so that the operation can be stopped and power
shut off immediately.
Unqualified persons must not disassemble or repair the unit.
Never make modifications.
Reduce magnetic interference by installing a noise filter. The electronic devices used near
the servo amplifier could be affected by magnetic noise. Install a line noise filter, etc., when
there is an influence from magnetic interference.
Always use the servomotor and servo amplifier with the designated combination.
The servomotor's magnetic brakes are for holding purposes. Do not use them for normal
braking.
There may be cases when holding is not possible due to the magnetic brake's life or the
machine construction (when ball screw and servomotor are coupled via a timing belt, etc.).
Install a stop device to ensure safety on the machine side.
CAUTION
V
(5) Troubleshooting
CAUTION
If a hazardous situation is predicted during stop or product trouble, use a servomotor with
magnetic brakes or install an external brake mechanism.
Use a double circuit configuration
that allows the operation circuit for
the magnetic brakes to be operated
even by the external emergency
stop signal.
If an alarm occurs, remove the
cause and secure the safety before
resetting the alarm.
Never go near the machine after restoring the power after a failure, as the machine could
start suddenly.
(Design the machine so that personal safety can be ensured even if the machine starts
suddenly.)
Control in the intelligent
servomotor.
Servomotor
(6) Maintenance, inspection and part replacement
Magnetic
brake
Shut off with CNC brake
control PLC output.
EMG
24VDC
The capacity of the electrolytic capacitor will drop due to deterioration. To prevent secondary
damage due to failures, replacing this part every ten years when used under a normal
environment is recommended. Contact the nearest dealer for repair and replacement of
parts.
(7) Disposal
Treat this unit as general industrial waste.
(8) General precautions
CAUTION
CAUTION
CAUTION
The drawings given in this Specifications and Maintenance Instruction Manual show the
covers and safety partitions, etc., removed to provide a clearer explanation. Always return
the covers or partitions to their respective places before starting operation, and always follow
the instructions given in this manual.
VI
Compliance to European EC Directives
1. European EC Directives
The European EC Directives were issued to unify Standards within the EU Community and to smooth
the distribution of products of which the safety is guaranteed. In the EU Community, the attachment
of a CE mark (CE marking) to the product being sold is mandatory to indicate that the basic safety
conditions of the Machine Directives (issued Jan. 1995), EMC Directives (issued Jan. 1996) and the
Low-voltage Directives (issued Jan. 1997) are satisfied. The machines and devices in which the servo
is assembled are a target for CE marking.
The servo is a component designed not to function as a single unit but to be used with a combination
of machines and devices. Thus, it is not subject to the EMC Directives, and instead the machines and
devices in which the servo is assembled are targeted.
This servo complies with the Standards related to the Low-voltage Directives in order to make CE
marking of the assembled machines and devices easier. The EMC INSTALLATION GUIDELINES (IB
(NA) 67303) which explain the servo amplifier installation method and control panel manufacturing
method, etc., has been prepared to make compliance to the EMC Directives easier. Contact
Mitsubishi or your dealer for more information.
2. Cautions of compliance
Use the standard servo amplifier and EN Standards compliance part (some standard models are
compliant) for the servomotor. In addition to the items described in this instruction manual, observe
the items described below.
(1) Environment
The servo amplifier must be used within an environment having a Pollution Class of 2 or more as
stipulated in the IEC664. For this, install the servo amplifier in a control panel having a structure
(IP54) into which water, oil, carbon and dust cannot enter.
(2) Power supply
1) The servo amplifier must be used with the overvoltage category II conditions stipulated in
IEC664. For this, prepare a reinforced insulated transformer that is IEC or EN Standards
complying at the power input section.
2) When supplying the control signal input/output power supply from an external source, use a
24 VDC power supply of which the input and output have been reinforced insulated.
(3) Installation
1) To prevent electric shocks, always connect the servo amplifier protective earth (PE) terminal
(terminal with mark) to the protective earth (PE) on the control panel.
2) When connecting the earthing wire to the protective earth (PE) terminal, do not tighten the
wire terminals together. Always connect one wire to one terminal.
PE terminalPE terminal
(4) Wiring
1) Always use crimp terminals with insulation tubes so that the wires connected to the servo
amplifier terminal block do not contact the neighboring terminals.
Crimp terminal
Insulation tube
Wire
VIII
(5) Peripheral devices
1) Use a no-fuse breaker and magnetic contactor that comply with the EN/IEC Standards
described in Chapter 7 Peripheral Devices.
2) The wires sizes must follow the conditions below. When using other conditions, follow Table 5
of EN60204 and the Appendix C.
• Ambient temperature: 40°C
• Sheath: PVC (polyvinyl chloride)
• Install on wall or open table tray
(6) Servomotor
Contact Mitsubishi for the outline dimensions, connector signal array and detector cable.
(7) Others
Refer to the EMC INSTALLATION GUIDELINES (IB (NA) 67303) for other EMC Directive
1-3 Inspection at purchase ............................................................................... 1-3
1-3-1 Explanation of type ............................................................................. 1-3
1–1
Chapter 1 Introduction
1-1 Intelligent servomotor outline
The Mitsubishi intelligent servomotor is an integrated motor, encoder and amplifier, and has the
following features.
• Space saving
The amplifier does not need to be stored in the power distribution panel, so the machine, power
distribution panel and heat exchanger can be downsized.
• Wire saving
Only one wire is used between the NC and motor. (The signal and 200VAC input are wired with
the same cable.)
• Flexible
As an option axis can be added without changing the power distribution panel, variations can be
easily added to the machine.
• High-speed
As the power distribution panel does not require space, the servo can easily be used for
hydraulic and pneumatic devices.
1-2 Limits and special notes for intelligent servomotor
1-2-1 Precautions for selecting the intelligent servomotor
(1) The intelligent servomotor does not have the regenerative resistor option (the regenerative
resistor capacity cannot be increased.). Make sure that the regenerative energy is less than the
tolerable regenerative capacity. Use the standalone HA/HC Series motor and
MDS-B-V1/V2/SVJ2 Series servo amplifier for applications having a high regenerative energy
due to a high positioning frequency or large load inertia, etc.
(2) The HS-MF23 type does not have a regenerative resistor. There may be limits to the working
rotation speed depending on the load inertia. Avoid using in applications generating continuous
regeneration, such as with a vertical axis.
1-2-2 Precautions for use
(1) IP65 is recommended for the engagement of the HS-RF∗∗/SF∗∗ type connector. Make sure that
water or oil, etc., does not come in contact in the disengaged state.
(2) Connect the HS-MF type relay connector in a relay box having a structure (IP54) that prevents
the entry of water, oil and dust, etc. Fix the enclosed cable to the motor.
(3) A contact that released the brakes when the servo turns ON is built-in. The brakes will not be
released just by inputting the 24V power from an external source. If the brakes need to be
released when assembling the machine, etc., refer to section 6-4. Wiring a motor with brakes.
1-2-3 Miscellaneous
(1) When the motor shaft is turned by hand, it may seem heavier than other servomotors, or may
seem tight. This is caused because of the dynamic brakes in the built-in amplifier, and is not a
fault.
1–2
Chapter 1 Introduction
1-3 Inspection at purchase
Open the package, and read the rating nameplate to confirm that the servo amplifier and servomotor
are as ordered.
1-3-1 Explanation of type
(1) Amplifier + motor integrated type
HS - oo ¡¡oooo - So
Motor Series RF : Medium capacity, low inertia
SF : Medium capacity, medium inertia
MF : Small capacity, ultra-low inertia
(1) HS-MF, HS-RF Series (Low-inertia, small capacity/low-inertia, medium capacity)
Type HS-MF23 HS-RF43 HS-RF73
Short-time
characteristics
Continuous
characteristics
Maximum torque (N·m) 1.92 3.18 5.97
Rated rotation speed (r/min) 3000
Maximum rotation speed (r/min) 3000
Moment of inertia J (×10-4kg·m2) 0.089 0.8 1.5
Detector resolution/method 8,000/absolute value 100,000/absolute value
Power
supply
Control method Sine wave PWM control, current control method
Dynamic brakes Built-in
Recommended load moment of inertia
(Protection applies for connector section when engaged)
170 to 253VAC 50/60Hz
±5%
Note 1: The rated output and rated rotation speed are the guaranteed values in the 200 to 230VAC 50/60Hz range. The torque-speed
Note 2: Make sure that the acceleration/deceleration torque is within 80% of the maximum output torque.
Note 3: Make sure that the continuous effective load torque is within 80% of the motor rated torque.
Note 4: With the HS-MF23, if the recommended load moment of inertia rate is exceeded, an overvoltage alarm may occur because of
Note 5: Magnetic brakes are prepared for the 0.4KW and larger capacities. The HS-MF23 does not have brake specifications.
line diagram indicates the characteristics when 200VAC is input. Note that the high-speed characteristics will drop when the
power voltage drops.
the speed and deceleration torque. (Refer to Chapter 11.)
2–2
2-2 Torque characteristics
3.0
[HS-MF23]
Chapter 2 Specifications
4.0
[HS-RF43]
8.0
[HS-RF73]
3.0
2.0
Intermittent
operation range
Torque[N・m]
1.0
Short-time operation range
Continuous
operation range
0
0
100020003000
Motor speed[r/min
]
2.0
Torque[N・m]
1.0
[HS-SF52]
10
Intermittent
operation range
5
Torque[N・m]
Short-time operation range
Continuous
operation range
0
0
10002000
Motor speed[r/min
]
10
Torque[N・m]
Intermittent
operation range
Short-time operation range
Continuous
operation range
0
0
10002000
Motor speed[r/min
[HS-SF53]
Intermittent
operation range
5
Short-time operation range
Continuous operation
range
0
0
100020003000
Motor speed[r/min
3000
]
]
6.0
Intermittent
operation range
4.0
Torque[N・m]
Short-time operation range
2.0
0
0
Motor speed[r/min
20
10
Torque[N・m]
Short-time operation range
0
01000
Motor speed[r/min
Continuous
operation range
10002000
[HS-SF102]
Intermittent
operation range
Continuous
operation range
3000
]
2000
]
[HS-SF103]
20
10
Torque[N・m]
Short-time operation range
0
0
Intermittent
operation range
Continuous operation
range
100020003000
Motor speed[r/min
]
40
20
Torque[N・m]
0
01000
[HS-SF202]
Intermittent
operation range
Short-time operation range
Continuous
operation range
Motor speed[r/min
]
2000
2–3
Chapter 2 Specifications
60
±5
2-3 Outline dimension drawings
2-3-1 HS-MF23
640±30
56.5
18
108
178
4
2.5
Cross-section
4
Φ11h6
A-A
2-3-2 HS-RF43/73
Φ27
101
82
118
93
With oil seal
0
-0.03
5
54.3
108.00
Cross-section
A-A
Connector
JL04V-2A28-11PE
L
10
3
With oil seal
25
7
3
45°
16304
A
Φ50h7
A
A
φ 70
23.3
100
173.5
75
LL
18
Changed dimensions
Model L LL
HS-RF43 400W 86 204
HS-RF43B 400W with brakes In planning stages
HS-RF73 750W 104 222
HS-RF73B 750W with brakes In planning stages
2–4
A
φ16.000
A
Taper
1/10
28
φ22
φ
115
135
φ
45
゚
4-φ9
□
100
φ95h7
A
12
2-3-3 HS-SF52/53/102/103
96
216
Changed dimensions
Model L LL
HS-SF53/52 500W 87 232
HS-SF53/52B 500W with brakes 119 270
HS-SF103/102 1kW 112 257
HS-SF103/102B 1kW with brakes 144 295
2-3-4 HS-SF202
Chapter 2 Specifications
145L
5
L
Cross section
A-A
70
LL
0
-0.03
23.3
5
4.25
4.3
12
3
φ 165
25
A
φ16.000
22
φ
A
A
Taper
1/10
18
2812
58
110h7
φ 145
130
□130
45°
79
45°
119
70
18
3
75
0
+0.010
φ35
264
0
-0.025
φ114.3
φ
200
φ
LL
230
□
176
Changed dimensions
Model L LL
HS-SF202 2kW 116 270
HS-SF202B 2kW with brakes In planning stages
The servo amplifier has an electronic thermal relay to protect the servomotor and servo amplifier
from overloads. The operation characteristics of the electronic thermal relay when standard
parameters (SV021=60, SV022=150) are set shown below.
If overload operation over the electronic thermal relay protection curve shown below is carried out,
overload 1 (alarm 50) will occur. If the maximum current is commanded at 95% or higher
continuously for one second or more due to a machine collision, etc., overload 2 (alarm 51) will occur.
1000.0
100.0
10.0
Operation time [sec]
1.0
0.1
0.1
050100150200250300350400
When stopped
Motor load rate [%]
When rotating
maximum capacity
Fig. 3-1 Overload protection characteristics
3–2
Chapter 3 Characteristics
3-2 Magnetic brake characteristics
1. The axis will not be mechanically held even when the dynamic brakes are
used. If the machine could drop when the power fails, use a servomotor
with magnetic brakes or provide an external brake mechanism as holding
means to prevent dropping.
2. The magnetic brakes are used for holding, and must not be used for normal
braking. There may be cases when holding is not possible due to the life or
CAUTION
machine structure (when ball screw and servomotor are coupled with a
timing belt, etc.). Provide a stop device on the machine side to ensure
safety. When releasing the brakes, always confirm that the servo is ON
first. Sequence control considering this condition is possible if the amplifier
motor brake control signal (MBR) is used.
3. When operating the brakes, always turn the servo OFF (or ready OFF).
4. When the vertical axis drop prevention function is used, the drop of the
vertical axis during an emergency stop can be suppressed to the minimum.
3-2-1 Motor with magnetic brakes
(1) Types
The motor with magnetic brakes is set for each motor. The "B" following the standard motor type
indicates the motor with brakes.
(2) Applications
When this type of motor is used for the vertical feed axis in a machining center, etc., slipping and
dropping of the spindle head can be prevented even when the hydraulic balancer's hydraulic
pressure reaches zero when the power turns OFF. When used with a robot, deviation of the
posture when the power is turned OFF can be prevented.
When used for the feed axis of a grinding machine, a double safety measures is formed with the
deceleration stop (dynamic brake stop), and the risks of colliding with the grinding stone and
scattering can be prevented.
This motor cannot be used for purposes other than holding and braking during a power failure
(emergency stop). (This cannot be used for normal deceleration, etc.)
(3) Features
1) The magnetic brakes use a DC excitation method, thus:
• The brake mechanism is simple and the reliability is high.
• There is no need to change the brake tap between 50 Hz and 60 Hz.
• There is no rush current when the excitation occurs, and shock does not occur.
• The brake section is not larger than the motor section.
2) The magnetic brakes are built into the motor, and the installation dimensions are the same as
the motor without brakes.
3–3
Chapter 3 Characteristics
3-2-2 Magnetic brake characteristics
HS-RF Series HA-SF Series
Item
Type (Note 1) Spring braking type safety brakes
Rated voltage 24VDC
Rated current at 20°C (A)
Excitation coil resistance at 20°C (Ω)
Capacity (W) 9.9 19.2 19.2
Attraction current (A) 0.20 0.25 0.25
Dropping current (A) 0.12 0.085 0.08
Static friction torque (N·m) 2.4 6.8 8.5
Moment of inertia (Note 2) J (×10–4kg·m2) 0.26 0.35 2.0
Release delay time (sec) (Note 3) 0.03 0.03 0.03
Tolerable braking work amount
(J)
Brake play at motor axis (deg.) 0.1 to 0.9 0.2 to 0.6 0.2 to 0.6
Brake life (Note 4)
Per braking 64 400 400
Per hour 640 4000 4000
20,000 times with 32 (J)
43B
73B
0.41 0.8 0.8
58 30 30
braking amount
per braking
53B 52B
103B 102B
20,000 times with 200 (J)
braking amount
per braking
20,000 times with 200 (J)
202B
braking amount
per braking
Notes:
1. There is no manual release mechanism. Refer to section "6-4-2 Manually releasing the magnetic brakes".
2. These are the values added to the servomotor without brakes.
3. This is the value for 20°C at the initial attraction gap.
4. The brake gap will widen through brake lining wear caused by braking. However, the gap cannot be
adjusted. Thus, the brake life is reached when adjustments are required.
5. A leakage flux will be generated at the shaft end of the servomotor with magnetic brakes.
6. When operating in low speed regions, the sound of loose brake lining may be heard. However, this is not a
problem in terms of function.
7. The brake characteristics for the HS-RF Series and HS-SF202 are the planned values.
3-2-3 Magnetic brake power supply
(1) Brake excitation power supply
1) Prepare a brake excitation power supply that can accurately ensure the attraction current in
consideration of the voltage fluctuation and excitation coil temperature.
2) The brake terminal polarity is random. Make sure not to mistake the terminals with other
circuits.
(2) Brake excitation circuit
<Cautions>
• Provide sufficient DC cut off capacity at the contact.
• Always use a serge absorber.
3–4
Chapter 3 Characteristics
3-2 Dynamic brake characteristics
When an emergency stop occurs such as that due to a servo alarm detection, the motor will stop with
the deceleration control at the standard setting. However, by setting the servo parameter (SV017:
SPEC), the dynamic brake stop can be selected. If a servo alarm that cannot control the motor occurs,
the dynamic brakes stop the servomotor regardless of the parameter setting.
3-3-1 Deceleration torque
The dynamic brakes use the motor as a generator, and obtains the deceleration torque by consuming
that energy with the dynamic brake resistance. The characteristics of this deceleration torque have a
maximum deceleration torque (Tdp) regarding the motor speed as shown in the following drawing.
The torque for each motor is shown in the following table.
dp
T
Deceleration
torque
dp
0
N
Motor speed
Fig. 3-2 Deceleration torque characteristics of a dynamic brake stop
Table 3-1 Max. deceleration torque of a dynamic brake stop
The motor coasting amount when stopped by a dynamic brake can be approximated using the
following expression.
CMAX =
No
60
CMAX : Maximum motor coasting amount (turn)
No : Initial motor speed (r/min)
JM : Motor inertia (kg·cm2)
JL : Motor shaft conversion load inertia (kg·cm2)
te : Brake drive relay delay time (sec) (Normally, 0.03sec)
A : Coefficient A (Refer to the table below)
B : Coefficient B (Refer to the table below)
Always wait at least 10 minutes after turning the power OFF, and check the
DANGER
voltage with a tester, etc., before connecting the option or peripheral device.
Failure to observe this could lead to electric shocks.
CAUTION
Use the designated peripheral device and options. Failure to observe this
could lead to faults or fires.
4-1 Dedicated options
4-1-1 I/F unit
Name Intelligent servomotor I/F unit
Type HS-IF-6
Maximum number of connected
axes
Input power voltage AC200 to 230V 50/60Hz
Functions
Miscellaneous Surge absorber, radio noise filter, internal 5V power
Ambient temperature 0°C to +55°C (with no freezing)
Ambient humidity 90% RH or less (with no dew condensation)
Environ-me
nt
conditions
Outline dimensions H: 300 × W: 80 × D: 80 (refer to following drawings)
Storage temperature –20°C to +65°C (with no freezing)
Storage humidity 90% RH or less (with no dew condensation)
Atmosphere Indoors (not subject to direct sunlight). No corrosive gases, flammable gases, oil mist or dust
Altitude 1000m or below sea level
Vibration 5.9m/sec2 or less
(The total number of connected axes follows the NC unit specifications)
Serial bus interface between NC and intelligent servomotor
200VAC branching to main circuit and control power circuit
(1) Outline drawing
Maximum 6 intelligent servomotor axes
300
285
2-M3 screw
For grounding
plate installation
80
80
4–2
Chapter 4 Option and Peripheral Devices
インテリジェントサーボ
左より第1軸、第2軸、・・・
(2) Explanation of each part
CN1B
CN1B
Servo/spindle drive
サーボ・主軸ドライブ
CN1A
CN1A
From NC
NCより
CN11
CN11
Intelligent servomotor 1st axis
インテリジェントサーボモータ第1軸
CN12
CN12
Intelligent servomotor 2nd axis
インテリジェントサーボモータ第2軸
CN13
CN13
Intelligent servomotor 3rd axis
インテリジェントサーボモータ第3軸
Alarm display LED
アラーム表示LED
1st axis, 2nd axis, to 6th axis,
CN1B connection axis from
第6軸、CN1B接続軸
left.
SW7
SW7
Servo monitor D/A output
サーボモニタD/A出力
changeover switch
切替スイッチ
Always set to ON (left) when
starting up.
立ち上げ時は必ずON(左)として下さい。
SW1 to SW3
SW1〜SW3
Usage/non-usage setting
各々CN11〜CN13の
switch for CN11 to CN13.
使用/未使用設定スイッチ
Set switch to right for
connected axis, and to left for
接続軸はスイッチを右へ未
disconnected axis.
接続軸は左として下さい。
CN14
CN14
Intelligent servomotor 4th axis
インテリジェントサーボモータ第4軸
CN15
CN15
Intelligent servomotor 5th axis
インテリジェントサーボモータ第5軸
CN16
CN16
Intelligent servomotor 6th axis
インテリジェントサーボモータ第6軸
L1 L2 L3
L1L2 L3
L11 L12
L11 L12
PE
PE
SW4 to SW6
SW4〜SW6
Usage/non-usage setting
各々CN11〜CN13の
switch for CN11 to CN13.
使用/未使用設定スイッチ
Set switch to right for
connected axis, and to left for
接続軸はスイッチを右へ未
disconnected axis.
接続軸は左として下さい。
TE1 to TE6
TE1〜TE6
Intelligent servomotor terminal
block.
モータ用端子台
* The drawing shows the state
with the terminal block cover
*図は端子台カバーを
removed.
はずしたときのものです
TE7
TE7
200VAC
AC200V
Input terminal block
入力端子台
4–3
Chapter 4 Option and Peripheral Devices
(3) Signal wire connection and switch settings
1) Connector connection
Connect the cable from the NC unit to CN1A. The servo/spindle drive other than the
intelligent servomotor is connected to CN1B. If there is no servo/spindle drive, connect the
battery unit or terminator.
The intelligent servomotor axis No. is set according to the I/F unit connector connection site.
Connect to the correct connector.
2) Switch setting
Set the setting switches SW1 to SW6 according to whether CN11 to CN16 are used or not.
SW7 is the servo monitor D/A output changeover switch, so normally set it to the left position.
Set it to the right when using the D/A output function. Note that when the power is turned ON,
this switch must be set to the left or the "Amplifier Not Mounted" alarm will occur.
(4) Power supply connection
1) Explanation of terminal block
Connect the 200VAC power to TE7.
The intelligent servomotor's power wires are connected to TE1 to TE6. The TE1 to TE6
connection order is random, but connect from TE6 in order from the motor with the larger
capacity.
The connections are L1, L2, L3 (main power), L11, L12 (control circuit power), and PE from
the left on each terminal block.
2) Wire end treatment
Single wire : Peel the wire sheath and use the wire.
Peeling length
Stranded wire : Peel the wire sheath and twist the core wires before
using. Take care to prevent short-circuiting with the
A
neighboring poles caused by fine wire strands.
Do not solder onto the core wires as a contact fault could occur.
(Wire size: 0.25 to 2.5mm2)
Wire size
Single wire Stranded wire
Peeling length
A (mm)
TE7 0.2 to 6mm2 0.2 to 4mm2 8
TE1 to TE6 0.2 to 1.5mm2 0.2 to 1.5mm2 10
3) Connection method
TEL7 (200VAC power supply) TE1 to 6 (intelligent servomotor)
Insert the wire, and tighten the terminal with a flat-tip
screwdriver. The tightening torque is 0.5 to 0.6Nm.
Insert the wire while pressing the terminal block lever. The
wire will be fixed when the lever is released.
4–4
Chapter 4 Option and Peripheral Devices
4) Total capacity of connected motors
The total capacity of the motors that can be
connected to the HS-IF-6 main power terminal
block is 6kW or less. If the total motor capacity
exceeds 6kW, wire with a standalone terminal
block.
HS motor
Terminal block
(5) D/A output measurement methods
1) Remove the upper cover from the I/F uni t.
2) Connect a measuring instrument to the I/F unit check pin.
Refer to the drawing on the right
for the connection sections.
3) When observing the waveform,
turn the I/F unit's servo monitor
#1 1st axis display
#2 2nd axis display
#3 3rd axis display
#4 4th axis display
D/A output changeover switch to
OFF (right).
4) Select the data to be measured
with the parameters. (Refer to
section "8-1. Measuring the
#7 CN1B connection axis display
#6 6th axis display
#5 5th axis display
Servo monitor D/A output
changeover switch
adjustment data".)
CAUTION
Always turn the DIP
switch ON before turning
the power ON. Do not
connect a measuring
instrument having a low
input impedance when
turning the power ON.
The "Amplifier Not
Mounted" alarm will
occur.
D/A output grounding
terminal
4th axis D/A output
terminal
(6) Alarm display LED
6th axis D/A output
terminal
The alarm display LED holds the state
of each axis alarm when an alarm or
emergency stop occurs.
Use this to pinpoint the cause when an
emergency stop state occurs due to a cable or amplifier fault.
The display of each LED will change as shown below.
#1 #2 #3 #4 #5 #6 #7
When 200VAC is turned ON Not set Not set Not set Not set Not set Not set Not set
After NC starts Not ON Not ON Not ON Not ON Not ON Not ON Not ON
Emergency stop occurrence from NC side Not ON Not ON Not ON Not ON Not ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 1st axis ON Not ON Not ON Not ON Not ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 2nd axis Not ON ON Not ON Not ON Not ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 3rd axis Not ON Not ON ON Not ON Not ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 4th axis Not ON Not ON Not ON ON Not ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 5th axis Not ON Not ON Not ON Not ON ON Not ON Not ON
Emergency stop occurrence from intelligent servomotor 6th axis Not ON Not ON Not ON Not ON Not ON ON Not ON
4–5
HS-IF-6
Alarm display LED
1st axis D/A output
terminal
2nd axis D/A output
terminal
3rd axis D/A output
terminal
5th axis D/A output
terminal
Chapter 4 Option and Peripheral Devices
Emergency stop occurrence from servo/spindle connected to CN1B Not ON Not ON Not ON Not ON Not ON Not ON ON
4–6
Chapter 4 Option and Peripheral Devices
4-1-2 Battery option for absolute position system
A battery or battery unit must be provided for the absolute position system.
Battery option specifications
Item Battery unit
Type MDS-A-BT2 MDS-A-BT4 MDS-A-BT6 MDS-A-BT8
No. of backup axes 2 axes 4 axes 6 axes 7 axes
Battery continuous back up time Approx. 12,000 hours
Battery useful life 7 years from date of unit manufacture
Data save time during battery
replacement
Back up time from battery warning
to alarm occurrence
The battery life will be greatly affected by the ambient temperature. The above
data shows the theoretic values for when the ambient temperature of the
CAUTION
battery is 25°C. If the ambient temperature rises, generally the back up time
and useful life will be shorter.
<Outline dimension drawing>
MDS-A-BT2
MDS-A-BT4
MDS-A-BT6
MDS-A-BT8
HS-MF : 2 hours at time of delivery, 1 hour after 5 years
HS-RF, -SF : 20 hours at time of delivery, 10 hour after 5 years
Approx. 100 hours
ø6 Use an M5 screw for the installation.
3 5
3 4
1 45
1 35
1 5
9
R30
1 5
3 0
1 00
<Connection>
Instead of the terminator, connect the battery unit to the final drive unit with the
amplifier-amplifier bus cable.
1 60
Unit (mm)
4–7
Chapter 4 Option and Peripheral Devices
4-1-3 Cables and connectors
(1) Cable list
Part name Type Descriptions
Communication cable for
CNC unit - Amplifier
Amplifier - Amplifier
For I/F unit
Terminator connector A-TM
For HS-MF between
intelligent servomotor and
I/F unit
For
intelligent
servo-moto
r
For HS-RF and HS-SF
between intelligent
servomotor and I/F unit
178289-3
(Housing for power supply)
178289-6 (Housing for signal)
1-917511-5
(Contact for L1, L2, PE)
1-175217-5
(Contact for L11, L12, signal)
Servomotor side connector
(Japan Aviation)
JI04V-6A28-11SE-EB (Straight)
or
JI04V-8A28-11SE-EB (Angle)
JL04-2428CK (Clamp)
brown
blue
black
Motor side
A
E
B
F
D
H
C
G
X
T
I
W
R
J
K
L
M
N
L12
U
4–8
Chapter 4 Option and Peripheral Devices
(3) Usage cables
The following cables are available as the compound cables for both signals and power supply.
(1) Part name: MIX20C(30/-SV,40/,7/36/0.08)-V
Maker: Oki Electric Cable Co., Ltd.
(2) Part name: MIX19C(19,30,150/0.08)-V
Maker: Oki Electric Cable Co., Ltd.
This connector is not an
option. It is integrated with
the cable.
22.0
39.0
23.8
33.3
14.0
12.7
[Unit: mm]
11.5
20.9
42.0
33.0
29.7
4–9
Chapter 4 Option and Peripheral Devices
10 or
Conduit installation
10 or more
(spanner catching width)
Screw
(Effective screw
(Spanner catching width)
Screw
(Clamp range)
Bushing
Screw
For intelligent servomotor HS-RF/HS-SF
Single block
Maker: Japan Aviation
Type: JL04V-6A28-11SE
[Unit: mm]
Positioning key
Screw
Straight plug
Maker: Japan Aviation
Type: JL04V-6A28-11SE-EB
Angle plug
Maker: Japan Aviation
Type: JL04V-8A28-11SE-EB
[Unit: mm]
[Unit: mm]
Positioning key
Positioning key
dimensions
(Effective screw length)
less
1-7/46-18UNEF-2A
Cable clamp
Maker: Japan Aviation
Type: JL04V-2428CK (17)
Applicable cable diameter:
ø15 to ø18
1-7/16-18UNEF-2A
length)
[Unit: mm]
1-7/16-18UNEF-2B
4–10
Chapter 4 Option and Peripheral Devices
Connector for intelligent servomotor HS-MF
Maker: Japan AMP
<Type>
For power supply
6-pole receptacle/housing: 178289-3
Contact: 1-917511-5 (L1, L2, PE)
1-175217-5 (L11, L12)
For signal
12-pole receptacle/housing: 178289-6
Contact: 1-175217-5
No. of
poles
6 178289-3 24.36 16.70
12 178289-6 35.09 28.35
Type
Dimension
A B
[Unit: mm]
Row A
5.08
3.81
Circuit number 1
A
16.3
Row B
Row B
22.8
Row A
B
11.63
(5) Communication cable assembly
Assemble the cable as shown in the following drawing, with the cable shield wire securely
connected to the ground plate of the connector.
Cor e wire
Shield (external conductor)
Sheath
Core wi re
Shiel d
(external conductor)
Sheath
Ground plate
When folding back the shield, fold back the shield over an area covered with vinyl tape or copper
tape, and seat onto the fitting surface of the plate screw section so that the shield wire and
grounding plate securely contact without play.
CAUTION
Take care not to mistake the connection when manufacturing the cable.
Failure to observe this could lead to faults, runaway or fire.
4–12
Chapter 4 Option and Peripheral Devices
4-1-4 Cable clamp fitting
Use the following types of grounding plate and cable clamp fitting to strengthen the noise resistance
of the communication cable. The grounding plate can be installed onto the terminal block cover of the
I/F unit (HS-IF-6). Peel part of the cable sheath as shown in the drawing to expose the shield sheath,
and press that section against the grounding plate with the cable clamp fitting.
Grounding plate
Grounding plate (E) outline
70
24
17.5
Cable clamp
fitting A, B
Grounding bar
Shield sheath
Cable clamp fitting outline
6
2-φ5 hole
Installation hole
35
30
10MAX L
622
56
3
M4 screw *
11
* Always wire the grounding wire from the grounding plate to the
cabinet grounding plate.
4–13
L
Fitting A 70
Fitting B 45
24
Chapter 4 Option and Peripheral Devices
4-2 Peripheral devices
4-2-1 Selection of wire
Select the interface unit L1, L2, L3 and grounding wires from the following wire sizes according to the
total capacity of the connected motors.
Total motor capacity 1kW or less 2.5kW or less 6kW or less 9kW or less 12kW or less
(Note) The total capacity of the motors connected to the interface unit must be 6kW or less. If the
total motor capacity exceeds 6kW, wire with a standalone terminal block.
4-2-2 Selection of no-fuse breakers
Use the following table to obtain the NFB (no-fuse breaker) rated current from the total rated capacity
(SVJ2 total output capacity) of the motor driving the SVJ2 servo amplifier to be connected to the NFB
to be selected, and select the no-fuse breaker.
When the MDS-B-SPJ2 spindle amplifier or converter unit will share no-fuse breakers, select from the
total NFB rated current of each SVJ2 total output capacity and SPJ2 spindle amplifier or convertor
unit. However, separate the SVJ2 servo amplifier no-fuse breaker from the others, and select the
NF60 type (60A) or smaller capacity dedicated for SVJ2 servo amplifiers if the total NFB rated current
exceeds 60A.
NFB rated current table
Intelligent servomotor
SVJ2 total output capacity
NFB rated current 10A20A 30A 40A 50A 60A
MDS-B-SPJ2-02
MDS-B-SPJ2
Converter unit
NFB rated current 10A20A 30A 40A 50A
NFB rated current 10A20A 30A 40A 50A 60A
Recommended NFB
(Mitsubishi Electric Corp.:
Option part)
Special order part: This part is not handled by the NC Dept. Marketing Section or dealer.
(Example 1)
MDS-B-SPJ2-04
MDS-B-SPJ2-075
MDS-B-SPJ2-15
MDS-A-CR-10
MDS-A-CR-15
The NFB is selected for the MDS-B-SVJ2-10 with three HS-SF102 axes and one
MDS-B-SPJ2-75 axis connected.
1.5kW or less 3.5kW or less 7kW or less 10kW or less 13kW or less 16kW or less
Because there are 1kW × 3 = 3kW on the intelligent servomotor side, 20A is selected
from the table for the NFB rated current.
40A is selected from the table for the SPJ2-75 rated current.
Therefore, the total rated current is 60A, and the NF60-CP3P60A is selected.
(Example 2)
The NFB is selected for the MDS-B-SVJ2-20 with two HS-SF202 axes and one
MDS-B-CR-90 connected.
Because there are 2kW × 2 = 4kW on the intelligent servomotor side, 30A is selected
from the table for the NFB rated current.
50A is selected from the table for the MDS-B-CV-90 rated current.
Therefore, the total rated current is 80A. The NFB is separated from converter unit,
and the NF30-CS3P30A is selected for the SVJ2. (Refer to the "MDS-A/B Series
Specifications Manual" for details on selecting the converter NFB.)
4–14
Chapter 4 Option and Peripheral Devices
Install independent no-fuse breakers and contactors as the SVJ2 main circuit
power supply if the total current capacity exceeds 60A when the power supply
is shared between the converter and a large capacity SPJ2 spindle amplifier.
DANGER
No-fuse breakers may not operate for short-circuits in small capacity amplifiers
if they are shared with a large capacity unit, and this could cause fires. Select
a capacity of NF60 or less for the intelligent servomotor and SVJ2 servo
amplifier.
4-2-3 Selection of contactor
Select the contactor based on section "(1) Selection from rush current" when the system connected to
the contactor to be selected is intelligent servomotor, an MDS-B-SVJ2 servo amplifier and 3.7kW or
less MDS-B-SPJ2 spindle amplifier.
When a converter unit or 5.5kW or more MDS-B-SPJ2 spindle amplifier is included, calculate both
the capacities in sections "(1) Selection from rush current" and "(2) Selection from input current", and
select the larger of the two capacities.
(1) Selection from rush current
Use the following table to select the contactors so the total rush current for each unit does not
Special order part: This part is not handled by the NC Dept. Marketing Section or dealer.
< Selection only from rush current >
exceed the closed circuit current amount.
Rush current table
Intelligent servomotor
Rush current 45A100A
MDS-B-SVJ2
Rush current 45A50A 70A 100A
MDS-B-SPJ2
Rush current 45A50A 100A 15A
Converter unit
Rush current 15A40A
HS-RF43, HS-RF73
HS-SF52, HS-SF53
MDS-B-SVJ2-01
MDS-B-SVJ2-03
MDS-B-SVJ2-04
MDS-B-SPJ2-02
MDS-B-SPJ2-04
MDS-A-CR-10 to MDS-A-CR-90
MDS-A/B-CV-37 to MDS-A/B-CV-75
MDS-B-SVJ2-06 MDS-B-SVJ2-07
MDS-B-SPJ2-075
HS-MF23
HS-SF102, HS-SF103
HS-SF202
MDS-B-SPJ2-15
MDS-B-SPJ2-22
MDS-B-SPJ2-37
MDS-A/B-CV-110
Contactor selection table 1
Contactor closed current
capacity
(Total rush current)
Recommended contactor
(Mitsubishi Electric Corp.:
Option part)
110A 200A 220A 300A 400A 550A 650A 850A
S-N10
AC200V
S-N18
AC200V
S-N20
AC200V
S-N25
AC200V
S-N35
AC200V
S-K50
AC200V
(Example 1)
The contactor is selected for the MDS-B-SVJ2-10 with three HS-SF102 axes and one
MDS-B-SPJ2-37 axis connected.
(JS-SF102 × 4 axes input current) + (MDS-B-CV-55 input current) = 30A + 30A = 60A
Therefore, S-N35 200VAC.
From these, the S-K50 200VAC is selected as having the larger of the two capacities.
4-2-4 Circuit protector
MDS-A/B-CV-75
MDS-A-CR-75
S-N25
AC200V
MDS-A-CR-90
MDS-A/B-CV-110
S-N35
AC200V
When installing a circuit protector dedicated for the control power input, use a circuit protector with
inertial delay to prevent malfunctioning in respect to the rush current generated when the power is
turned ON. The size and conductivity time of the rush current fluctuate according to the power supply
impedance and potential.
Recommended circuit
Servo amplifier Rush current
Intelligent servomotor 70 to 130A 0.5 to 1msec Rated current 0.2A per axis
Conductivity
time
protector
(Mitsubishi Electric
Corp.: Option part)
Special order part: This part is not handled by the NC
Department Marketing Section or dealer.
CP30-BA type with
medium-speed inertial delay
4–17
Chapter 5 Installation
5-1 Installation of servomotor.......................................................................... 5-3
1. Install the unit on noncombustible material. Direct installation on
combustible material or near combustible materials could lead to fires.
2. Follow this Instruction Manual and install the unit in a place where the
weight can be borne.
3. Do not get on top of or place heavy objects on the unit.
Failure to observe this could lead to injuries.
4. Always use the unit within the designated environment conditions.
5. Do not let conductive objects such as screws or metal chips, etc., or
combustible materials such as oil enter the servo amplifier or servomotor.
6. Do not block the servo amplifier intake and outtake ports. Doing so could
lead to failure.
7. The servo amplifier and servomotor are precision devices, so do not drop
them or apply strong impacts to them.
8. Do not install or run a servo amplifier or servomotor that is damaged or
missing parts.
9. When storing for a long time, please contact your dealer.
5–2
Chapter 5 Installation
5-1 Installation of servomotor
1. Do not hold the cables, axis or detector when transp orting the servomotor.
Failure to observe this could lead to faults or injuries.
2. Securely fix the servomotor to the machine. Insufficient fixing could lead to
the servomotor deviating during operation. Failure to observe this could
lead to injuries.
CAUTION
5-1-1 Environmental conditions
Environment Conditions
Ambient temperature
Ambient humidity 80% RH or less (with no dew condensation)
Storage temperature
Storage humidity 90% RH or less (with no dew condensation)
Atmosphere
Altitude 1000m or less above sea level
Vibration
5-1-2 Cautions for mounting load (prevention of impact on shaft)
3. When coupling to a servomotor shaft end, do not apply an impact by
hammering, etc. The detector could be damaged.
4. Never touch the rotary sections of the servomotor during operations. Install
a cover, etc., on the shaft.
5. Do not apply a load exceeding the tolerable load onto the servomotor shaft.
The shaft could break.
0°C to +40°C (with no freezing)
–20°C to +65°C (with no freezing)
• Indoors (Where unit is not subject to direct sunlight)
• With no corrosive gas or combustible gas.
• With no oil mist or dust
HS-MF X, Y: 19.6m/s2 (2G) or less
HS-RF
HS-SF 1kW or less
HS-SF 2kW
X: 9.8m/s2 (1G) or less
Y: 24.5m/s2 (2.5G) or less
X: 19.6m/s2 (2G) or less
Y: 49m/s2 (5G) or less
Servomotor
X
Y
Acceleration
(1) When using the servomotor with key way, use the
screw hole at the end of the shaft to mount the pulley
onto the shaft. To install, first place the double-end
stud into the shaft screw holes, contact the coupling
Serv omotor
Double-end stud
end surface against the washer, and press in as if
tightening with a nut. When the shaft does not have a
key way, use a frictional coupling, etc.
(2) When removing the pulley, use a pulley remover,
and make sure not to apply an impact on the shaft.
(3) Install a protective cover on the rotary sections such
Pulley
Nut
Washer
as the pulley installed on the shaft to ensure safety.
(4) The direction of the detector installation on the
servomotor cannot be changed.
Never hammer the end of the shaft
CAUTION
during assembly.
5-1-3 Installation direction
There are no restrictions on the installation direction. Installation in any direction is possible, but as a
standard the servomotor is installed so that the motor power supply wire and detector cable cannon
plugs (lead-in wires) face downward. When the servomotor is not installed in the standard direction,
refer to section "5-1-5 Oil and waterproofing measures" and take the appropriate measures.
The brake plates may make a sliding sound when a servomotor with magnetic brake is installed with
the shaft facing upward, but this is not a fault.
5–3
Chapter 5 Installation
5-1-4 Tolerable load of axis
(1) Using the flexible coupling, set the axis core deviation to less than the tolerable radial load of the
axis.
(2) When using a pulley, sprocket and timing belt, select so that the loads are within the tolerable
radial load.
(3) A rigid coupling must not be used as it will apply an excessive bending load on the axis to break.
Caution: The symbols in the table follow the drawing below.
L : Length from flange isntallation surface to center of load weight [mm]
1. When coupling with a ball screw, etc., use a flexible coupling, and keep the
shaft core deviation to below the tolerable radial load.
2. When installing the pulleys or gears on the motor shaft, the radial load will
increase as the diameter of these parts decreases. Consider this when
designing the machine.
3. When using a timing belt, adjust so that the radial load (double the tension)
CAUTION
generated from the tension is less than the values given above.
4. In a machine having a thrust load, such as a worm gear, provide a separate
bearing on the machine side so that the a load exceeding the tolerable
thrust load is not applied on the motor.
5. Do not use a rigid coupling as an excessive bending load will be applied on
the shaft and could cause the shaft to break.
5-1-5 Oil and waterproofing measures
L
Radial load
Thrust load
(1) The servomotor does not have a precise water or oil-proof structure. The type (IP class) following
the IEC standards is indicated as the intelligent servomotor's protection type. These standards are
the short-time performance standards, so make sure that the motor surface is not subject to fluids
and that fluids do not accumulate. If cutting oil, etc., could enter, always provide a protective
cover. Always consider the cover seams, edges, shapes and dimensions. Note that the IP class
does not indicate the corrosion resistance level.
(2) When a gear box is installed on the servomotor, make sure that
the oil level height from the center of the shaft is higher than the
values given below. Open a breathing hole on the gear box so
that the inner pressure does not rise.
Servomotor Oil level (mm)
HS-MF23 12
HS-RF43, 73, -SF103 20
HS-SF202 25
Oil level
Gear
Lip
Servomotor
Oil seal
5–4
Chapter 5 Installation
(3) When installing the servomotor horizontally, set the power cable and detector cable to face
downward.
When installing vertically or on an inclination, provide a cable trap.
Cable trap
(4) Do not use the unit with the cable submerged in oil or water. (Refer to lower left drawing)
(5) When installing on the top of the shaft end, make sure that oil from the gear box, etc., does not
enter the servomotor.
Cover
Gear
Lubricating oil
Servomotor
Oil or water pool
Servomotor
<Fault> Capillary tube phenomenon
(6) Connect the HS-MF23 relay connector in a relay box having a structure (IP54) that prevents water,
oil and dust, etc., from entering. Fix the enclosed cable to the motor, and also fix the enclosed
cable to the motor.
5-1-6 Cable stress
(1) Sufficiently consider the cable clamping method so that bending stress and the stress from the
cable's own weight is not applied on the cable connection.
(2) In applications where the servomotor moves, make sure that excessive stress is not applied on
the cable.
Select the cable bending radius from the required bending life and wire type.
Fix the detector cable and power cable enclosed with the servomotor.
(3) Make sure that the cable sheathes will not be cut by sharp cutting chips, worn by contacting the
machine corners, or stepped on by workers or vehicles.
5–5
Chapter 5 Installation
5-2 Installation of interface unit
5-2-1 Environmental conditions
Environment Conditions
Ambient temperature
Ambient humidity 90% RH or less (with no dew condensation)
Storage temperature
Storage humidity 90% RH or less (with no dew condensation)
Atmosphere Indoors (Where unit is not subject to direct sunlight)
Altitude 1000m or less above sea level
Vibration 5.9m/sec2 (0.6G) or less
5-2-2 Installation direction
Install so that the front of the interface unit is visible and the terminal block comes to the bottom.
5-2-3 Prevention of entering of foreign matter
0°C to +55°C (with no freezing)
–20°C to +65°C (with no freezing)
With no corrosive gas, combustible gas, oil mist or dust
Treat the cabinet with the following items.
• Make sure that the cable inlet is dust and oil proof by using packing, etc.
• Make sure that the external air does not enter inside by using head radiating holes, etc.
• Close all clearances.
• Securely install door packing.
• If there is a rear cover, always apply packing.
• Oil will tend to accumulate on the top. Take special measures such as oil-proofing the top so that
oil does not enter the cabinet from the screw holds.
• After installing each unit, avoid machining in the periphery. If cutting chips, etc., stick onto the
electronic parts, trouble may occur.
5–6
Chapter 5 Installation
from servo amplifier
from servo amplifier
power supply wire
servomotor
power supply wire
leakage current
5-3 Noise measures
Noise includes that which enters the servo amplifier from an external source and causes the servo
amplifier to malfunction, and that which is radiated from the servo amplifier or motor and causes the
peripheral devices or amplifier itself to malfunction. The servo amplifier output is a source of noise as
the DC voltage is switched at a high frequency. If the peripheral devices or amplifier malfunction
because of the noise, measures must be taken to suppressed this noise. These measures differ
according to the propagation path of the noise.
(1) General measures for noise
Avoid wiring the servo amplifier's power supply wire and signal wires in parallel or in a bundled
state. Always use separate wiring. Use a twisted pair shield wire for the detector cable, the
control signal wires for the bus cable, etc., and for the control power supply wire. Securely ground
the shield.
Use one-point grounding for the servo amplifier and motor.
(2) Measures against noise entering from external source and causing servo amplifier to
malfunction
If a device generating noise is installed near the servo amplifier, and the servo amplifier could
malfunction, take the following measures.
Install a surge killer on devices (magnetic contactor, relay, etc.) that generate high levels of
noise.
Install a data line filter on the control signal wire.
Ground the detector cable shield with a cable clamp.
(3) Measures against noise radiated from the servo amplifier and causing peripheral devices
to malfunction
The types of propagation paths of the noise generated from the servo amplifier and the noise
measures for each propagation path are shown below.
Noise generated
Airborne
propagation noise
Magnetic
induction noise
Static induction
noise
Cable
propagation noise
and ⑤
Noise directly radiated
Noise radiated from
Noise radiated from
Noise propagated over
Noise lead in from
grounding wire by
Path ①
Path ② Path ④
Path ③ Path ⑥
Path ⑦
Path ⑧
5–7
⑦
Chapter 5 Installation
⑤
⑦
②
②
Noise
propaga-tion
① ② ③
④ ⑤ ⑥
path
⑦
⑧
Instrument
Receiver
①
③
Servomotor
Servo
amplif ier
④
SM
⑥
Sensor
power
supply
Sensor
⑧
Measures
When devices such as instruments, receivers or sensors, which handle minute
signals and are easily affected by noise, or the signal wire of these devices, are
stored in the same panel as the servo amplifier and the wiring is close, the device
could malfunction due to airborne propagation of the noise. In this case, take the
following measures.
(1) Install devices easily affected as far away from the servo amplifier as
possible.
(2) Lay the signals wires easily affected as far away from the input wire with the
servo amplifier.
(3) Avoid parallel wiring or bundled wiring of the signal wire and power wire.
(4) Insert a line noise filter on the input/output wire or a radio noise filter on the
input to suppress noise radiated from the wires.
(5) Use a shield wire for the signal wire and power wire, or place in separate
metal ducts.
If the signal wire is laid in parallel to the power wire, or if it is bundled with the
power wire, the noise could be propagated to the signal wire and cause
malfunction because of the magnetic induction noise or static induction noise. In
this case, take the following measures.
(1) Install devices easily affected as far away from the servo amplifier as
possible.
(2) Lay the signals wires easily affected as far away from the input wire with the
servo amplifier.
(3) Avoid parallel wiring or bundled wiring of the signal wire and power wire.
(4) Use a shield wire for the signal wire and power wire, or place in separate
metal ducts.
If the power supply for the peripheral devices is connected to the power supply in
the same system as the servo amplifier, the noise generated from the servo
amplifier could back flow over the power supply wire and cause the devices to
malfunction. In this case, take the following measures.
(1) Install a radio noise filter on the servo amplifier's power wire.
(2) Install a line noise filter on the servo amplifier's power wire.
If a closed loop is structured by the peripheral device and servo amplifier's
grounding wires, the leakage current could penetrate and cause the devices to
malfunction. In this case, change the device grounding methods and the
grounding place.
5–8
Chapter 6 Wiring
6-1 System connection diagram........................................................................ 6-3
6-4 Wiring the motor with brakes...................................................................... 6-9
6-4-1 Connection example ............................................................................. 6-9
6-4-2 Manually releasing the magnetic brakes .............................................. 6-10
6-5 Connection with the NC............................................................................... 6-11
6-5-1 Connection system ............................................................................... 6-11
6–1
Chapter 6 Wiring
DANGER
Wait at least 10 minutes after turning the power OFF and check the voltage
servomotor with Class 3 grounding
CAUTION
). Failure to observe this item could lead
1. Wiring work must be done by a qualified technician.
2.
with a tester, etc., before starting wiring. Failure to observe this could lead
to electric shocks.
3. Securely ground the servo amplifier and
or higher.
4. Wire the servo amplifier and servomotor after installation. Failure to
observe this could lead to electric shocks.
5. Do not damage, apply forcible stress, place heavy items or engage the
cable. Failure to observe this could lead to electric shocks.
1. Correctly and securely perform the wiring. Failure to do so could lead to
runaway of the servomotor.
2. Do not mistake the terminal connections.
Failure to observe this item could lead to ruptures or damage, etc.
3. Do not mistake the polarity ( + , –
to ruptures or damage, etc.
4. Electronic devices used near the servo amplifier may receive magnetic
obstruction. Reduce the effect of magnetic obstacles by installing a noise
filter, etc.
5. Do not modify this unit.
6–2
6-1 System connection diagram
reactor
3ø200VAC L1, L2,
I/F unit HS-IF-6
I/Fユニット HS-IF-6
MELDASCNC
DC24V
24VDC
ブレーキ回路
Brake circuit
Chapter 6 Wiring
サーボ
Servo
MDS-
MDS-
B-
B-V1,V2
B-AL
ACリア
AC
クトル
主軸
Spindle
MDS-
MDS-
B-SP
B-SP
パワーサ
Power
プライ
supply
MDS-
MDSB-CV
B-CV
MC
Battery unit
バッテリーユニット
A-BT
A-BT
MC relay
MC用リレー
主回路電源用
L3 for main circuit
power
3φAC200VL1,L2,L3,
200VAC L11, L12 for
制御回路電源用AC200V
control circuit power
L11,L12
インテリジェント
Intelligent servomotor
サーボモータ
Note)
1) Keep the cable length to within 30m.
2) This is a motor with magnetic brakes. The power connected to the magnetic brake does not
have a polarity.
3) Securely connect the shield wire to the plate (grounding plate) in the connector.
4) When using as an absolute connector, connect MDS-A-BTo.
NF
6–3
6-2 Connector
Never connect the power wire to the signal terminal or the signal wire to the
CAUTION
DANGER
6-2-1 Connector signal layout
(1) HS-RFxxE, HS-SFxxE
U
L12
V
Open
W
BR
X
MON
power terminal. There is a risk of electric shock. Failure to observe this can
also cause damage or faults with the NC unit or devices connected to the NC.
Apply only the designated voltage to each terminal. Failure to observe this
could lead to damage or faults.
Main circuit power supply input terminal
Connect 3-phase 200 to 230VAC, 50/60Hz.
Control circuit power supply input terminal
Connect 1-phase 200 to 230VAC, 50/60Hz.
Grounding terminal
Connect and ground with the servomotor grounding terminal.
For NC connection
Connect the 24VDC for the magnetic brakes. (Only when
brakes are provided.)
The power supply polarity is irrelevant.
6–5
Chapter 6 Wiring
6-3 Connection of power supply
1. Keep the power voltage and capacity within the controller's specification
range. Failure to observe this could lead to damage or faults.
2. For safety purposes, always instal l a no-fuse breaker or earth leakage
breaker, and shut off when an error occurs or before inspecting. A large
CAUTION
6-3-1 Example of connection for controlling magnetic switch (MC) with MDS-B-CV/CR
The following connection example applies when the power supply unit MDS-B-CV/CVE/CR is
provided in the system.
The magnetic switch can also be controlled by the MDS-B-SVJ2/SPJ2. Refer to the respective unit's
specification manual for details.
(1) When sharing a power supply unit and power supply
rush current flows when the power is turned ON. Refer to Chapter 6 and
select the no-fuse breaker or earth leakage breaker.
3. For safety purposes, install a magnetic switch that shuts off when an error
occurs. If the converter unit MDS-B-CV is provided in the system, use the
converter's magnetic switch control function. The magnetic switch can be
directly driven by the MDS-B-CV.
MC
3-phase
200VAC
24VDC
External
emergency
stop
NFB
Mitsubishi
CNC
PE
L1
L2
L3
L11
L12
AC reactor B-AL
Intelligent
servomotor
I/F unit
Power supply
unit
MDS-B-CV/CR
PE
L1
L2
L3
L11
L12
MC1
L+
L−
Terminator
Servo/spindle
drive unit
MDS-B-Vx/SP
PE
L11
L12
L+
L−
1. The MDS-B-CV is a power supply regenerative type converter; an AC
reactor is required in the power supply line.
Connect the intelligent servomotor main circuit power supply on the power
CAUTION
supply side of the AC reactor.
2. A no-fuse breaker and contactor cannot be shared when the rated current of
the no-fuse breaker exceeds 60A.
6–6
Chapter 6 Wiring
(2) When not sharing a converter and power supply
If the rated current exceeds 60A by the selection of the no-fuse breaker when the converter and
power supply are shared, install the no-fuse breakers and contactors separate from the converter
unit.
3-phase
200VAC
NFB1
NFB2
MC1
MC2
AC reactor B-AL
PE
L1
L2
L3
L11
L12
Intelligent
servomotor
Power supply
unit
MDS-B-CV/CR
PE
L1
L2
L3
L11
L12
MC1
L+
L−
Terminator
Servo/spindle
drive unit
MDS-B-Vx/SP
PE
L11
L12
L+
L−
24VDC
External
emergency
stop
DANGER
Mitsubishi
CNC
I/F unit
Install independent no-fuse breakers as the intelligent servomotor power
supply if the total current capacity exceeds 60A when the converter and power
supply are shared.
No-fuse breakers may not operate for short-circuits in small capacity amplifiers
if they are shared with a large capacity unit, and this could cause fires. For the
intelligent servomotor, use an NF60 type or lower capacity breaker.
(Refer to section 4.)
6–7
Chapter 6 Wiring
emergency stop signal. If the input power is cut off during deceleration control,
(Order of priority of the contactor drive method)
6-3-2 Example of connection for controlling magnetic switch with external sequence circuit
Relay
Prepare a sequence that
cuts off with the alarm.
3-phase
200VAC
24VDC
External
emergency
stop
External
emergency stop
NFB
Mitsubishi
CNC
MC
PE
L1
L2
L3
L11
L12
Intelligent
servomotor
I/F unit
Terminator
PE
L1
L2
L3
L11
L12
Class 3 grounding
or higher
Intelligent
servomotor
6-3-3 Wiring of contactors (MC)
A contactor (magnetic contactor) is inserted in the main circuit power supply input (L1, L2, L3) of
servo amplifier, and the power supply input is shut off when an emergency stop or servo alarm
occurs.
When an emergency stop or servo alarm occurs, the servo amplifier stops the motor using
deceleration control or a dynamic brake. The contactors cannot be shut off during deceleration control,
because the regeneration energy (MDS-B-CV Series) is returned to the power supply, and the power
supply for deceleration must be held. Therefore, the CNC controls the contactors. The CNC confirms
that all axes are stopped, or confirms the dynamic brake operation. Then it outputs a shutoff
command for amplifiers that drive contactors.
When actually driving the contactor, it is driven by the amplifier of the axis having the longest
deceleration time constant in consideration of the communication from the NC being cut off.
Generally, when a converter (MDS-B-CV/CVE/CR) is provided, the contact is driven by the converter.
When a spindle amplifier is provided, the contactor is driven by the spindle amplifier, and when the
servo amplifier (MDS-B-SVJ2) is provided, the contact is driven by the servo amplifier.
Give consideration to the above, and examine the contactor drive method in the following order of
priority.
1. Using the contactor control output (MC1) of the converter unit.
2. Driven by spindle amplifier (MDS-B-SPJ2 in this case).
3. Driving from the servo amplifier (MDS-B-SVJ2) of the vertical axis (unbalanced axis).
4. Driving from the servo amplifier (MDS-B-SVJ2) having the longest deceleration time constant.
5. Driven by external sequence (only for intelligent servomotor.)
Directly cut off the contact with an external sequence only when using the
CAUTION
intelligent servomotor. In this case, cut off the power supply with a delay longer
than the servo's acceleration/deceleration time constant in respect to the
6–8
Chapter 6 Wiring
the undervoltage alarm could occur or the deceleration control may be
prevented.
6–9
Chapter 6 Wiring
6-3-4 Surge absorber
As protection against surge voltage caused by lightning, etc., the surge absorber and radio noise filter
shown below are built into the intelligent servomotor's I/F unit MDS-B-HSIF (refer to Chapter 6) and
the MDS-B-CV AC reactor B-ALxx. When not using these simultaneously, install a surge absorber
and filter on the input power supply as shown below. Refer to the following table and select the surge
absorber.
L1
VAR1
L2
VAR2VAR3
L3
C1
C2C3
C4
C5
C6
PE
VAR4
Symbol Type Maker Rating
VAR1 to
VAR3
TNR23G471K
VAR4 DSAZR2-302M Mitsubishi Materials Corp.
C1 to C3 AL-U2E224K
C4 to C6 DE7120F332MVA-1KC
MARCON ELECTRONICS
CO., LTD.
SHIZUKI ELECTRONIC
CO., INC.
Murata Manufacturing Co.,
Ltd.
Varistor voltage 423 to 517V
DC discharge start voltage
2400 to 3600V
250VAC 0.22µF
2500VAC 3300pF
6-4 Wiring the motor with brakes
1. No mechanical guarantee is provided even when the dynamic brakes are
used. If the machine could drop during a power failure, use a motor with
magnetic brakes or provide an external brake mechanism to prevent
dropping.
2. The magnetic brakes are used for holding, and must not be used for normal
braking. There may be cases when holding is not possible due to the life
CAUTION
6-4-1 Connection example
and machine structure (when ball screw and servomotor axis are connected
via a timing belt, etc.). Provide a stopping device to ensure safety on the
machine side.
3. The magnetic brakes of the motor with magnetic brakes are controlled in
the intelligent servomotor. However, provide a double circuit configuration
so that these brakes will operate even with the external emergency stop
signal.
BR
RG
Amplifier
Servomotor
RA
Magnetic brakes
Cut off with emergency stop signal.
EMG
24VDC
1) The brakes are safety brakes, and will operate when the power (24VDC) is turned OFF.
6–10
Chapter 6 Wiring
2) Prepare a brake excitation power supply that ensures a secure attraction current.
3) The brake terminal polarity is random, but must not be mistaken with other circuits.
6–11
Chapter 6 Wiring
6-4-2 Manually releasing the magnetic brakes
The intelligent servomotor has a relay for controlling the brakes in the amplifier, so the brakes cannot
be released even if power is supplied to the 24V power terminal (BR, RG) for the cannon plug brakes.
Release the brakes with the following method when the brakes need to be released for handling when
assembling, adjusting or servicing the machine.
(1) Method 1
Remove the amplifier section and input the 24V power to the motor brakes. There is no polarity.
Refer to section "9-3. Replacing the unit" for details on removing and installing the amplifier
section.
The amplifier terminal is a connector, so prepare the following connector beforehand.
Enter the brake release mode by changing the MON signal, normally used for the axis No.
selection, several times.
1) Prepare the circuit operation box shown with the dotted line below, and connect with the
intelligent servomotor as shown in the drawing.
2) Open SW1 and SW2.
3) Input 200VAC to the LL1 and LL2 terminals. → The LED will turn ON.
4) Turn SW1 ON. → The LED will flicker.
5) Turn SW2 ON. → The LED will turn OFF.
6) Turn SW2 OFF. → The LED will turn ON, and the relay in the
amplifier will turn ON.
7) Input 24VDC to the BR and RG terminals. → The brakes will be released.
8) Thereafter, when SW2 is turned ON the brakes will be applied, and when turned OFF, the
brakes will be released.
Intelligent
servomotor
Control
power
Control
circuit
RA
*
Operation box
330Ω
L11
L12
BR
RG
ALM
ALM
MON
LG
All other pins are open.
NFB
SW2SW1
680Ω
LED
For OFF at
emergency
For status
indication
200VAC
24VDC
6–12
6-5 Connection with the NC
6-5-1 Connection system
I/F unit
CN1ACN1B
Mitsubishi
CNC
CON1 to CON4
Chapter 6 Wiring
Terminator or battery unit when
there is no other drive unit
MDS-B Series servo/spindle drive unit
Terminator or battery
unit
Intelligent servomotor
(1) Refer to "Chapter 6 Peripheral devices" for details on connecting and setting the I/F unit.
(2) The I/F unit's CON1 to CON4 (intelligent servo connection connectors) can be connected to any
connector.
(3) If the MDS-B Series servo/spindle drive unit is connected as shown above, connect the I/F unit
between the CNC and servo spindle drive. Other drive units cannot be connected between the
CNC and I/F unit.
I/F unit
Mitsubishi
CNC
MDS-B Series servo/spindle drive unit
An I/F unit cannot be connected
behind the servo/spindle drive unit.
Intelligent servomotor
(4) There may be cases when the I/F unit (PCB) is manufactured by the machine maker. In this case,
contact the machine maker for details on connecting and setting the I/F unit.
6–13
Chapter 7 Setup
7-1 Setting the initial parameters..................................................................... 7-2
7-1-2 Limitations to electronic gear setting value......................................... 7-2
7-1-3 Parameters set according to feedrate................................................. 7-3
7-1-4 Parameters set according to machine load inertia.............................. 7-3
7-1-5 Standard parameter list according to motor........................................ 7-4
7–1
Chapter 7 Setup
7-1 Setting the initial parameters
The servo parameters must be set to start up the servo drive system.
The servo parameters are input from the CNC. The input method will differ according to the CNC, so
refer to the Instruction Manual provided with each CNC.
7-1-1 Servo specification parameters
The servo specification parameters are determined according to the machine specifications and servo
system specifications.
No. Abbrev. Parameter name Explanation
SV017 SPEC Servo specifications This is a HEX setting parameter. Set this as follows according to the servo
SV025 MTYP Motor type Set the motor type.
SV036 PTYP Regenerative resistor type Set 1000 as a standard.
SV027 SSF1 Special servo function
selection 1
SV033 SSF2 Special servo function
selection 2
SV001 PC1 Motor side gear ratio
SV002 PC2 Machine side gear ratio
SV018 PIT Ball screw pitch Set the ball screw pitch with an mm unit. Set 360 for a rotary axis.
SV019 RNG1 Position detector resolution
SV020 RNG2 Speed detector resolution
SV003 PGN1 Position loop gain Set 33 as a standard.
specifications.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
abs dmk
bit Meaning when "0" is set. Meaning when "1" is set.
0 dmk
7 abs Incremental control Absolute position control
Set all bits other than those above to 0.
Refer to the standard parameter list for each motor for the settings.
Set 4000 as a standard.
Set 0000 as a standard.
Set the motor side gear ratio in PC1 and the machine side gear ratio in PC2.
When using a rotary axis, set the total deceleration (acceleration) ratio.
Set the motor detector resolution with a kp/rev unit for both settings.
Refer to the standard parameters for each motor for the settings.
Deceleration control stop
(Standard)
Dynamic brake stop selection
7-1-2 Limitations to electronic gear setting value
The servo amplifier has internal electronic gears. The command value from the NC is converted into
a detector resolution unit to carry out position control. The electronic gears are single gear ratios
calculated from multiple parameters as shown below. However, each value (ELG1, ELG2) must be
less than 32767.
If the value overflows, the initial parameter error (alarm 37) or error parameter No. 101 (2301 with
M50/M64 Series NC) will be output.
If an alarm occurs, the mechanical specifications and electrical specifications must be revised so that
the electronic gears are within the specifications range.
Reduced fraction of
ELG1
ELG2
=
PC2 × RANG
PC1 × PIT × IUNIT
(reduced fraction)
RANG = RNG1 = RNG2
IUNIT = 2/NC command unit (µm)
1µm : IUNIT = 2, 0.1µm: IUNIT = 20
When the above is calculated, the following conditions must be satisfied.
ELG1 ≤ 32767
ELG2 ≤ 32767
If the electronic gears in the amplifier overflow, the alarm 37 or error
POINT
parameter No. 101 (2301 with M50/M64 series NC) will be output.
The following parameters are determined according to each axis' feedrate.
No. Abbrev. Parameter name Explanation
SV023 OD1 Excessive error detection
width at servo ON
SV026 OD2 Excessive error detection
width at servo OFF
A protective function will activate if the error between the position command and
position feedback is excessive. If the machine load is heavy and problems occur
with the standard settings, gradually increase the setting value.
<Calculation of standard setting value>
OD1 = OD2 =
Rapid traverse rate (mm/min)
60 × PGN1
÷ 2 (mm)
7-1-4 Parameters set according to machine load inertia
The following parameters are set according to the machine's inertia.
No. Abbrev. Parameter name Explanation
SV005 VGN1 Speed loop gain. Refer to the comparison graph with the load inertia scale for the standard setting
SV008 VIA Speed loop leading
compensation
<HS-MF>
value.
Set 1364 as a standard. Set 1900 as a standard for the SHG control.
If the load inertia is large and is in the standard VIA change region, set the value in
the comparison graph regardless of whether normal control or SHG control is used.
Motor single unit
100
<HS-RF>
Standard VIA change region
Standard
VGN1
Standard
VGN1
10
600
500
400
300
200
100
1
<HC-SF>
0
3 7
5 9
Standard VIA change region
HC-SF52
HC-SF102
HC-SF202
HC-SF53, HC-SF103
VIA
11
Standard
VGN1
VIA
1500
1000
500
20
11
VIA
1500
1000
500
HC-RF43
HC-RF73
VIA
1
3 7
5 9
7–3
Chapter 7 Setup
7-1-5 Standard parameter list according to motor
Set the parameters other than 7-2-1 to 7-2-4 to the standard parameters.
Motor type
No. Abbrev. Parameter name
SV001 PC1 Motor side gear ratio
SV002 PC2 Machine side gear ratio
SV003 PGN1 Position loop gain 1 33
SV004 PGN2 Position loop gain 2 0
SV005 VGN1 Speed loop gain Refer to "7-1-4 Parameters set according to machine load inertia"
SV006 – – 0
SV007 – – 0
SV008 VIA Speed loop leading compensation 1364
SV009 IQA
SV010 IDA
SV011 IQG Current loop Q axis gain 400 384 384 512 256 384 256 384
SV012 IDG Current loop D axis gain 400 384 384 512 256 384 256 384
SV013 ILMT Current limit value 400 300 300 700 700 600 700 500
SV014 ILMTsp
SV015 FFC Acceleration feed forward gain 0
SV016 LMC1 Lost motion compensation 1 0
SV017 SPEC Servo specifications Refer to "7-1-1 Servo specification parameters"
SV025 MTYP Motor type 229E 22E0 22E1 22B0 22C0 22B1 22C1 22B3
SV026 OD2
SV027 SSF1 Special servo function selection 1 4000
SV028
to 035
SV036 PTYP Regenerative resistor type 1000
SV037
to 046
SV047 EC Inductive voltage compensation gain 70
SV048 EMGrt Vertical axis drop prevention time 0
SV049
SV050
PGN1sp
to 064
Current loop Q axis leading
compensation
Current loop D axis leading
compensation
Current limit value during special
operation
Excessive error detection width during
servo ON
Excessive error detection width during
servo OFF
Compensation function for special
–
functions
Compensation function for special
–
functions
Position loop gain during spindle
synchronization 1
Compensation function for special
–
functions
MF23 RF43 RF73 SF52 SF53 SF102 SF103 SF202
Set the motor side gear ratio in PC1 and the machine side gear ratio in PC2.
When using a rotary axis, set the total deceleration (acceleration) ratio.
4096 8192 8192 8192 4096 8192 4096 4096
4096 8192 8192 8192 4096 8192 4096 4096
400 250 250 700 700 600 700 500
Set the ball screw pitch with an mm unit.
Set 360 for a rotary axis.
Refer to "7-1-3 Parameters set according to feedrate"
Refer to "7-1-3 Parameters set according to feedrate"
0
0
15
0
7–4
Chapter 8 Adjustment
8-1 Measurement of adjustment data .............................................................. 8-2
The intelligent servomotor has a function to D/A output the various control data. To adjust the servo
and set the servo parameters that match the machine, it is necessary to use the D/A output and
measure the internal status of the servo. Measure using a hi-coder, synchroscope, etc.
8-1-1 D/A output specifications
<Output specifications>
No. of channels : 1ch.
Output cycle : 888µsec (min. value)
Output precision : 8bit
Output voltage range : 0V to 2.5V to 5V
Output pins : On intelligent servo I/F unit
Output scale setting : ±1/256 to ±128 times
Output resistance : 1kΩ
<Output function>
• Offset amount adjustment function
• Output clamp function
• Low path filter function
<Measurement method>
Connect the measuring instrument to the I/F unit check pin. When observing the waveform, turn the
I/F unit DIP switch OFF.
Note that the DIP switch must be turned ON when the power is turned ON. Do not connect a
measuring instrument having a low input impedance when turning the power ON.
8-1-2 Setting the output data
No. Abbrev. Parameter name Explanation
SV061 DA1NO D/A output channel 1 data No. Input the No. of the data to be output to each D/A output channel.
0 0 V test output For offset amount adjustment
1 Speed feedback 2000rpm/1V
2 Current feedback Rated current/0.5V
3 Speed command 2000rpm/1V
4 Current command Rated current/0.5V
5 V-phase current value 40A/V
6 W-phase current value 40A/V
This is set when an output is to made with a unit other than the standard output unit.
(Example 1) When SV061= 5, SV063 = 2560
The V-phase current value will be output with 4A/V unit to D/A output ch. 1.
(Example 2) When SV063 = 11, SV064 = 128
The position droop will be output with a 8mm/V unit to the D/A output ch. 2.
No. Abbrev. Parameter name Explanation Setting range
SV063 DA1MPY D/A output channel 1
output scale
SV064 DA2MPY D/A output channel 2
output scale
When "0" is set, the output will be made with the standard output unit.
To change the output unit, set a value other than 0.
The scale is set with a 1/256 unit. When 256 is set, the unit will be the
same as the standard output unit.
–32768 to 32767
8-1-4 Setting the offset amount
This is used when the zero level of the output voltage is to be finely adjusted. The output scale when
the data No. is 0 will be the offset amount. After setting the offset, set the data No. to a value other
than 0, and do not set it to 0 again. The offset value will be reset when the amplifier power is turned
OFF. (The value is not reset when the NC power is turned OFF.)
No. Abbrev. Parameter name Explanation Setting range
SV061 DA1NO D/A output channel 1
data No.
SV063 DA1MPY D/A output channel 1
offset amount
Set "0". 0 to 102
The amount can be set with the output precision unit. Observe the output
value and set so that the output value is 0 V.
–10 to 10
8-1-5 Clamp function
This is used when the output value such as the position droop exceeds the output range and over
flows.
Position
droop
5V
-10V
0
D/A output
range
8-1-6 Filter function
A low path filter with a cutoff frequency of 140 Hz can be set.
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bitMeaning when "0" is set. Meaning when "1" is set.
selection 3
Set the clamp function and filter function with the following parameter.
the VGN1 setting value is raised, the subsequent servo adjustment becomes
8-2 Gain adjustment
8-2-1 Current loop gain
No. Abbrev. Parameter name Explanation Setting range
SV009 IQA q axis leading compensation 1 to 20480
SV010 IDA d axis leading compensation 1 to 20480
SV011 IQG q axis gain 1 to 2560
SV012 IDG d axis gain
8-2-2 Speed loop gain
(1) Setting the speed loop gain
The speed loop gain (SV005: VGN1) is an important parameter for determining the
responsiveness of the servo control. During servo adjustment, the highest extent that this value
can be set to becomes important. The setting value has a large influence on the machine cutting
precision and cycle time.
To adjust the VGN1 value, first obtain the standard VGN1 to judge how much VGN1 is required
for the machine load inertia.
The standard VGN1 is the value that corresponds to the size of the machine load inertia shown in
the graph in section 7-1-3. If the load inertia is not clear, estimate it using the following
procedure.
1) Set the VGN1 of a level where acceleration/deceleration operation is possible. (Set a
slightly lower value so resonance does not occur.)
2) Set SV037 = 100, SV043 = 600, and SV044 = 0 in the servo parameters. Carry out a return
operation within the range where the axis can operate smoothly. At this time, set the
acceleration/deceleration time constant so the acceleration/deceleration torque equals or
exceeds (is 100% or higher than) the stall (rated) torque.
3) Observe the estimated disturbance using the D/A output, and increase the SV037 value until the
disturbance torque during acceleration/deceleration becomes smaller (cannot be observed).
(The unbalance torque is observed as an estimated disturbance torque in the vertical and
slanted axes, so ignore this amount or set the torque offset (SV032) and adjust. The friction
torque is also observed in the same way for axes having a large amount of friction, but this
should be ignored. Refer to section "8-3-3 (4) Disturbance observer" for details.)
4) The SV037 setting where the disturbance torque becomes the smallest during the
estimated acceleration/deceleration is the machine's total load inertia magnification
including the motor inertia. Obtain the standard VGN1 from the graph in section 7-1-3
based on this value.
<When machine resonance does not occur at the standard VGN1>
Set the standard VGN1. Use the standard value if no problem (such as machine resonance)
occurs. If sufficient cutting precision cannot be obtained at the standard VGN1, do not raise the
VGN1 further above the standard value. Instead, use the disturbance observer and adjust.
Basically, there is no need to set a value higher than the standard value in VGN1.
<When machine resonance occurs at the standard VGN1>
Machine resonance is occurring if the shaft makes abnormal sounds when operating or stopping,
and a fine vibration can be felt when the machine is touched while stopped. Machine resonance
occurs because the servo control responsiveness includes the machine resonance points.
(Speed control resonance points occur, for example, at parts close to the motor such as ball
screws.) Machine resonance can be suppressed by lowering VGN1 and the servo control
responsiveness, but the cutting precision and cycle time are sacrificed. Thus, set a vibration
suppression filter and suppress the machine resonance (Refer to section "8-3-2 Vibration
suppression measures"), and set a value as close as possible to the standard VGN1. If the
machine resonance cannot be sufficiently eliminated even by using a vibration suppression filter,
then lower the VGN1.
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain Set this according to the motor inertia size.
The final VGN1 setting value should be 70 to 80% of the largest value at which
POINT
machine resonance does not occur.
If the vibration suppression functions are used to suppress the resonance and
This setting is determined by the motor's electrical characteristics.
Set the standard parameters for all parameters.
(These are used for maker adjustments.)
1 to 2560
1 to 999
If vibration occurs, adjust by lower the setting by 20% to 30% at a time.
8–4
Chapter 8 Adjustment
more favorable.
8–5
Chapter 8 Adjustment
(2) Setting the speed loop leading compensation
The speed loop leading compensation (SV008: VIA) determines the characteristics of the speed
loop mainly at low frequency regions. 1364 is set as a standard, and 1900 is set as a standard
during SHG control. The standard value may drop as shown in the graph in section 7-1-3 in
respect to loads with a large inertia.
When the VGN1 is set lower than the standard value because the load inertia is large or because
machine resonance occurred, the speed loop control band is lowered. If the standard value is set
in the leading compensation in this status, the leading compensation control itself will induce
vibration. In concrete terms, a vibration of 10 to 20Hz could be caused during
acceleration/deceleration and stopping, and the position droop waveform could be disturbed
when accelerating to a constant speed and when stopped. (Refer to the following graphs.)
This vibration cannot be suppressed by the vibration suppression functions. Lower the VIA in
increments of 100 from the standard setting value. Set a value where vibration does not occur
and the position droop waveform converges smoothly. Because lowering the VIA causes a drop
in the position control's trackability, the vibration suppression is improved even when a
disturbance observer is used without lowering the VIA. (Be careful of machine resonance
occurrence at this time.)
Speed FB
0
D/A output range
Position
droop
0
Vibration waveform with leading
compensation control
Time
Time
0
0
Adjusted position droop waveform
If VIA is lowered, the position droop waveform becomes smooth and overshooting does not occur.
However, because the trackability regarding the position commands becomes worse, that amount
of positioning time and precision are sacrificed. VIA must be kept high (set the standard value) to
guarantee precision, especially in high-speed contour cutting (generally F = 1000 or higher). In
other words, a large enough value must be set in VGN1 so that the VIA does not need to be
lowered in machines aimed at high-speed precision. When adjusting, the cutting precision will be
better if adjustment is carried out to a degree where overshooting does not occur and a high VIA
is maintained, without pursuing position droop smoothness.
If there are no vibration or overshooting problems, the high-speed contour cutting precision can
be further improved by setting the VIA higher than the standard value. In this case, adjust by
raising the VIA in increments of 100 from the standard value.
Setting a higher VIA improves the trackability regarding position commands in machines for
which cycle time is important, and the time to when the position droop converges on the
in-position width is shortened.
It is easier to adjust the VIA to improve precision and cycle time if a large value (a value near the
standard value) can be set in VGN1, or if VGN1 can be raised equivalently using the disturbance
observer.
No. Abbrev. Parameter name Explanation Setting range
SV008 VIA Speed loop leading
compensation
1364 is set as a standard. 1900 is set as a standard during SHG control.
Adjust in increments of approx. 100.
Raise the VIA and adjust to improve the contour tracking precision in
high-speed cutting. If the position droop vibrates (10 to 20Hz), lower the
VIA and adjust.
1 to 9999
Time
Time
8–6
Chapter 8 Adjustment
POINT
Position droop vibration of 10Hz or less is not leading compensation control
vibration. The position loop gain must be adjusted.
8–7
Chapter 8 Adjustment
8-2-3 Position loop gain
(1) Setting the position loop gain
The position loop gain (SV003:PGN1) is a parameter that determines the trackability to the
command position. 33 is set as a standard. Set the same position loop gain value between
interpolation axes.
When PGN1 is raised, the settling time will be shortened, but a speed loop that has a
responsiveness that can track the position loop gain with increased response will be required. If
the speed loop responsiveness is insufficient, several Hz of vibration or overshooting will occur
during acceleration/deceleration. Vibration or overshooting will also occur when VGN1 is smaller
than the standard value during VIA adjustment, but the vibration that occurs in the position loop
is generally 10Hz or less. (The VIA vibration that occurs is 10 to 20Hz.) When the position control
includes machine resonance points (Position control machine resonance points occur at the
machine end parts, etc.) because of insufficient machine rigidity, the machine will vibrate during
positioning, etc. In either case, lower PGN1 and adjust so vibration does not occur.
If the machine also vibrates due to machine backlash when the motor stops, the vibration can be
suppressed by lowering the PGN1 and smoothly stopping.
If SHG control is used, an equivalently high position loop gain can be maintained while
suppressing these vibrations. To adjust the SHG control, gradually raise the gain from a setting
where 1/2 of a normal control PGN1 where vibration did not occur was set in PGN1. If the PGN1
setting value is more than 1/2 of the normal control PGN1 when SHG control is used, there is an
improvement effect in position control. (Note that for the settling time the improvement effect is
SV003 PGN1 Position loop gain 1 Set 33 as a standard. If PGN1 is increased, the settling time will be
SV004 PGN2 Position loop gain 2 Set 0. (For SHG control) 0 to 999
SV057 SHGC SHG control gain Set 0. (For SHG control) 0 to 999
at 1/ 2 or more.)
No. Abbrev. Parameter name Explanation Setting range
1 to 200
shortened, but a sufficient speed loop response will be required.
CAUTION
Always set the same value3 for position loop gain between interpolation axes.
(2) Setting the position loop gain for spindle synchronous control
During spindle synchronous control (synchronous tapping control, etc.), there are three sets of
position loop gain parameters besides the normal control.
No. Abbrev. Parameter name Explanation Setting range
SV049 PGN1sp Position loop gain 1
during spindle
synchronization
SV050 PGN2sp Position loop gain 2
during spindle
synchronization
SV058 SHGCsp SHG control gain
during spindle
synchronization
Set 15 as a standard. 1 to 200
Set 0 as a standard.
(For SHG control)
Set 0 as a standard.
(For SHG control)
Set the same parameter as the
position loop gain for the spindle
synchronous control.
0 to 999
0 to 999
Always set the same value for the position loop gain between the spindle and
CAUTION
servo synchronous axes.
8–8
Chapter 8 Adjustment
3
(3) SHG control (option function)
If the position loop gain is increased or feed forward control (CNC function ) is used to shorten
the settling time or increase the precision, the machine system may vibrate easily.
SHG control changes the position loop to a high-gain by stably compensating the servo system
position loop through a delay. This allows the settling time to be reduced and a high precision to
be achieved.
(Feature 1) When the SHG control is set, even if PGN1 is set to the same value as the
conventional gain, the position loop gain will be doubled.
(Feature 2) The SHG control response is smoother than conventional position control during
acceleration/deceleration, so the gain can be increased further with SHG control
compared to the conventional position control.
(Feature 3) With SHG control, a high gain is achieved so a high precision can be obtained during
contour control.
The following drawing shows an example of the improvement in roundness
characteristics with SHG control.
50.0
0.0
-50.0
-50.0
(F=3000mm/min,ERROR=5.0µm/div)
0.0
Shape error characteristics
During SHG control, PGN1, PGN2 and SHGC are set with the following ratio.
PGN1 : PGN2 : SHGC = 1 :
8
: 6
1) : Commanded path
2) : SHG control (PGN1=47)
3) : Conventional control (PGN1=33)
<Effect>
50.0
Control
method
SHG control
Conventional
control
Roundness error (µm)
2.5
22.5
During SHG control even if the PGN1 setting value is the same, the actual position loop gain will
be higher, so the speed loop must have a sufficient response. If the speed loop response is low,
vibration or overshooting could occur during acceleration/deceleration in the same manner as
conventional control. If the speed loop gain has been lowered because machine resonance
occurs, lower the position loop gain and adjust.
No. Abbrev. Parameter name
SV003
(SV049)
SV004
(SV050)
SV057
(SV058)
SV008 VIA Speed loop leading
SV015 FFC Acceleration feed
PGN1
(PGN1sp)
PGN2
(PGN2sp)
SHGC
(SHGCsp)
Position loop gain 1
Position loop gain 2
SHG control gain
compensation
forward gain
The SHG control is an optional function. If the option is not set in the CNC, the
CAUTION
alarm 37 or warning E4, Error Parameter No. 104 (2304 for M50/M64 Series
CNC) will be output.
Setting
ratio
1 23 26 33 38 47
8/3 62 70 86 102 125
6 140 160 187 225 281
Set 1900 as a standard for SHG control. 1 to 9999
Set 100 as a standard for SHG control. 0 to 999
Setting example Explanation Setting range
Always set a combination of the
three parameters.
1 to 200
0 to 999
0 to 999
8–9
Chapter 8 Adjustment
8-3 Characteristics improvement
8-3-1 Optimal adjustment of cycle time
The following items must be adjusted to adjust the cycle time. Refer to the Instruction Manuals
provided with each CNC for the acceleration/deceleration pattern.
1) Rapid traverse rate (rapid) : This will affect the maximum speed during positioning.
2) Clamp speed (clamp) : This will affect the maximum speed during cutting.
3) Acceleration/deceleration time : Set the time to reach the feedrate.
constant (G0t∗, G1t∗)
4) In-position width (SV024) : This will affect each block's movement command end time.
5) Position loop gain (SV003) : This will affect each block's movement command settling time.
(1) Adjusting the rapid traverse rate
To adjust the rapid traverse, the CNC axis specification parameter rapid traverse rate (rapid) and
acceleration/deceleration time constant (G0t∗) are adjusted. The rapid traverse rate is set so that
the motor speed matches the machine specifications in the range below the maximum speed in
the motor specifications. For the acceleration/deceleration time constants, carry out rapid
traverse reciprocation operation, and set so that the maximum current command value at
acceleration/deceleration is within the range shown below. (Only when the rapid traverse rate is
below the rated speed.) Set the same value as the adjusted acceleration/deceleration time
constant in the servo parameter's deceleration control time constant (SV056: EMGt). (When
deceleration control is set.)
For motors in which the maximum speed is greater than the rated speed, the output torque is
particularly restricted in the region at or above the rated speed. When adjusting, watch the
current FB waveform during acceleration/deceleration, and adjust so that the torque is within the
specified range. Be careful, as insufficient torque can easily occur when the amplifier input
voltage is low (170 to 190V), and an excessive error can easily occur during
acceleration/deceleration.
HS-MF Series HS-RF Series HS-SF Series
Motor type
HS-MF23 280 to 320% HS-RF43 200 to 240% HS-SF52 420 to 470%
HS-RF73 200 to 240% HS-SF53 420 to 470%
HS-SF102 440 to 500%
HS-SF103 500 to 560%
HS-SF202 420 to 470%
Max. current
command value
Motor type
Max. current
command value
Motor type
Max. current
command value
(2) Adjusting the cutting rate
To adjust the cutting rate, the CNC axis specification parameter clamp speed (clamp) and
acceleration/deceleration time constant (G1t∗) are adjusted. The in-position width at this time
must be set to the same value as actual cutting.
• Determining the clamp rate and adjusting the acceleration/deceleration time constant
(Features) The maximum cutting rate (clamp speed) can be determined freely.
(Adjustment) Carry out cutting feed reciprocation operation with no dwell at the maximum
cutting rate and adjust the acceleration/deceleration time constant so that the
maximum current command value during acceleration/deceleration is within the
range shown below.
• Setting the step acceleration/deceleration and adjusting the clamp speed
(Features) The acceleration/deceleration time constant is determined with the position
loop in the servo, so the acceleration/deceleration F⊿T can be reduced.
(Adjustment) Set 1 (step) for the acceleration/deceleration time constant and carry out
cutting feed reciprocation operation with no dwell. Adjust the cutting feed rate
so that the maximum current command value during acceleration/deceleration
is within the range shown below, and then set the value in the clamp speed.
8–10
Chapter 8 Adjustment
3
6
60 × G0tL × PGN1
10
0
0
F
G0tL
<Maximum current command value>
For the maximum current command value during acceleration/deceleration, the maximum
current command value (MAXcmd) for one second is output to MAX current 1 and MAX current 2
on the CNC servo monitor screen and observed.
The meaning of the display for MAX current 1 and MAX current 2 will differ according to the
parameter settings.
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bitMonitor Meaning when 0 is set Meaning when 1 is set
0 mon
selection 3
(3) Adjusting the in-position width
Because there is a response delay in the servomotor drive due to position loop control, a "settling time"
is also required for the motor to actually stop after the command speed from the CNC reaches 0.
The movement command in the next block is generally started after it is confirmed that the
machine has entered the "in-position width" range set for the machine.
The in-position width is effective even when the standard servo parameters are set. However, it
may follow the CNC parameters, so refer to the CNC Instruction Manual for the setting.
No. Abbrev. Parameter name Unit Explanation Setting range
SV024 INP In-position detection
width
The in-position width setting and confirmation availability depend on the CNC
POINT
parameters
(4) Adjusting the settling time
The settling time is the time required for
the position droop to enter the in-position
width after the feed command (F⊿T) from
the CNC reaches 0.
The settling time can be shortened by
raising the position loop gain or using SHG
control. However, a sufficient response
(sufficiently large VNG1 setting) for the
speed loop is required to carry out stable
control.
The settling time during normal control
when the CNC is set to linear
acceleration/ deceleration can be
calculated using the following equation.
During SHG control, estimate the settling
time by multiplying PGN1 by 2.
The display data for the maximum current value on the servo monitor is determined
with the following parameter.
MAX
current 1
MAX
current 2
Set 50 as a standard.
µm
Set the precision required for the machine.
Maximum current command
value after power is turned
ON
Maximum current
com-mand value for one
second
daf2 daf1 dac2 dac1
Maximum current command
value for one second
Maximum current FB value
for one second
F∆T
Position
droop
Settling time
In-position width
0 to 32767
Time
In-position
mon
Settling time (msec) = −
10
PGN1
×
ln
F × 10
INP
× 1 − exp −
2
PGN1 × G0tL
3
PGN1 : Position loop gain1 (SV003) (rad/sec)
F : Rapid traverse rate (mm/min)
G0tL : Rapid traverse linear acceleration/
deceleration time constant (msec)
8–11
Chapter 8 Adjustment
INP : In-position width (SV024) (µm)
Speed command
(r/min)
Current command
(Stall %)
Example of speed/current command waveform during acceleration/deceleration
(Reference) The rapid traverse acceleration/deceleration time setting value G0tL for when linear
acceleration/deceleration is set is calculated with the following expression.
G0tL =
(JL + JM) × No
95.5 × (0.8 × T
3000
-3000
200
-200
0
Time
0
Time
MAX
– TL)
6000
( PGN1 × K)
(msec) –
2
NO : Motor reach speed (r/min)
JL : Motor shaft conversion load inertia (kg·cm2)
JM : Motor inertia (kg·cm2)
T
: Motor max. torque (N·m)
MAX
TL : Motor shaft conversion load (friction, unbalance) torque (N·m)
PGN1 : Position loop gain 1 (rad/sec)
K : "1" during normal control, "2" during SHG control
8-3-2 Vibration suppression measures
If vibration (machine resonance) occurs, it can be suppressed by lowering the speed loop gain
(VGN1). However, cutting precision and cycle time will be sacrificed. (Refer to "8-2-2 Speed loop
gain".) Thus, try to maintain the VGN1 as high as possible, and suppress the vibration using the
vibration suppression functions.
If the VGN1 is lowered and adjusted because vibration cannot be sufficiently suppressed with the
vibration suppression functions, adjust the entire gain (including the position loop gain) again.
<Examples of vibration occurrence>
• A fine vibration is felt when the machine is touched, or a groaning sound is heard.
• Vibration or noise occurs during rapid traverse.
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain
POINT
Suppress the vibration using the vibration suppression functions, and maintain
the speed loop gain (SV005: VGN1) as high as possible. (The standard value
is the upper limit.)
Set according to the load inertia size.
If machine resonance occurs, adjust by lowering in increments of 20 to
30%.
The setting value is 70 to 80% of the value where resonance does not
occur.
The resonance elimination filter will function at the set frequency. Use the D/A output function to
output the current feedback and measure the resonance frequency. Note that the resonance
frequency that can be measured is 0 to 500 Hz.
<Setting method>
1. Set the resonance frequency in the machine resonance suppression filter frequency (SV038:
FHz).
2. If the machine starts to vibrate at another frequency, raise (make shallower) the notch filter
depth compensation value (SV033: SSF2.nfd), and adjust to the optimum value at which the
resonance can be eliminated.
3. When the vibration cannot be completely eliminated, use another vibration suppression
control (jitter compensation).
No. Abbrev. Parameter name Explanation Setting range
SV038 FHz Notch filter frequency Set the resonance frequency to be suppressed. (Valid at 72 or
The notch filter depth compensation is set with the following parameters.
Set the filter depth for the notch filter.
Deeper ←→ Shallower
Setting value 0 2 4 6 8 A C E
Depth (dB) ∞−18.1−12.0−8.5−6.0−4.1−2.5−1.2
(2) Jitter compensation
The load inertia becomes extremely small if the motor position enters the machine backlash
when the motor is stopped. Because this means that an extremely large VGN1 is set for the load
inertia, vibration may occur.
Jitter compensation is the suppression of vibration occurring when the motor stops by ignoring
the backlash amount of speed feedback pulses when the speed feedback polarity changes.
Increase the number of ignored pulses by one pulse at a time, and set a value at which the
vibration can be suppressed. (Because the position feedback is controlled normally, there is no
worry of positional deviation.)
When an axis that does not vibrate is set, vibration could be induced, so take care.
No. Abbrev. Parameter name Explanation
SV027 SSF1 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
aflt zrn2 ovs2 ovs1 lmc2 lmc1 vfct2 vfct1
4 vfct1
5 vfct2
selection 1
Set the jitter compensation with the following parameter.
bit
No jitter
compensation
0 1 0 1
0 0 1 1
One pulse
compensation
Two pulse
compensation
Jitter compensation vibration suppression is only effective when the motor is
POINT
stopped.
0 to 3000
Three pulse
compensation
8–13
Chapter 8 Adjustment
Frictional
Unbalance
Cutting
8-3-3 Improving the cutting surface precision
If the cutting surface precision or roundness is
poor, improvements can be made by increasing
the speed loop gain (VGN1, VIA) or by using the
disturbance observer function.
<Examples of faults>
• The surface precision in the 45° direction of a
taper or arc is poor.
• The load fluctuation during cutting is large,
causing vibration or surface precision defects
to occur.
Adjust by raising the speed loop gain equivalently to improve cutting surface
POINT
(1) Adjusting the speed loop gain (VGN1)
If the speed loop gain is increased, the cutting surface precision will be improved but the
machine will resonate easily.
The final VGN1 setting should be approx. 70 to 80% of the maximum value where resonance
does not occur. (Refer to "8-2-2 (1) Setting the speed loop gain")
(2) Adjusting the speed loop leading compensation (VIA)
The VIA has a large influence on the position trackability, particularly during high-speed cutting
(generally F1000 or more). Raising the setting value improves the position trackability, and the
contour precision during cutting can be improved. For high-speed high-precision cutting
machines, adjust so that a value equal to or higher than the standard value can be set.
When VIA is set lower than the standard value and set to a value differing between interpolation
axes, the roundness may worsen (the circle may distort). This is due to differences occurring in
the position trackability between interpolation axes. The distortion can be improved by matching
the VIA with the smaller of the values. Note that because the position trackability is not improved,
the surface precision will not be improved. (Refer to "8-2-2 (2) Setting the speed loop leading
compensation")
precision, even if the measures differ. In this case, it is important how much
the machine resonance can be controlled, so adjust making sufficient use of
vibration suppression functions.
Y
X
No. Abbrev. Parameter name Explanation Setting range
SV005 VGN1 Speed loop gain Increase the value by 20 to 30% at a time.
SV008 VIA Speed loop leading
compensation
If the machine starts resonating, lower the value by 20 to 30% at a time.
The setting value should be 70 to 80% of the value where resonance does
not occur.
1364 is set as a standard. 1900 is set as a standard during SHG control.
Adjust in increments of approx. 100.
Raise the VIA and adjust to improve the contour tracking precision in
high-speed cutting. If the position droop vibrates (10 to 20Hz), lower the
VIA and adjust.
1 to 999
1 to 9999
(3) Voltage non-sensitive zone (Td) compensation
With the PWM control of the inverter, a dead time
direction
Motor torque
(non-energized time) is set to prevent short-circuits
caused by simultaneous energizing of the P side
and N side transistors having the same phase. The
torque
dead time has a non-sensitive zone for particularly
low voltage commands. Thus, when feeding with a
low speed and a low torque, the control may be
unstable.
When an unbalanced axis is lowering, the frictional
torque and unbalance torque, and the frictional
torque and deceleration torque before the quadrant
changes during circle cutting, are balanced. The
motor output torque will be approximately zero, and
the control accuracy may drop. In this case, the
Deceleration torque =
frictional torque
Lowering
For unbalance torque For circle cutting
torque
control accuracy can be improved by using the
voltage non-sensitive band compensation. Note
8–14
≒ 0
Balanced
Chapter 8 Adjustment
order
fine
Current command after
Current command
that this may cause vibration to increased while the
motor is running.
No. Abbrev. Parameter name Explanation Setting range
SV030 IVC Voltage non-sensitive
band compensation
(4) Fine torque compensation
There may be cases when not much torque is generated during low speed feed, or when the wear
torque and unbalance torque during lowering an unbalance axis or the wear torque and
deceleration torque before a quadrant torque changeover during circular cutting are unbalanced.
These can cause the motor output torque to be approximately zero and the control accuracy to
drop. In this case, the control accuracy can be improved by using fine torque compensation. Note
that this may cause vibration during motor operation to increase.
The disturbance observer can reduce the effect caused by disturbance, frictional resistance or
torsion vibration during cutting by estimating the disturbance torque and compensating it. It also
is effective in suppressing the vibration caused by speed leading compensation control.
<Setting method>
1) Adjust VGN1 to the value where vibration does not occur, and then lower it 10 to 20%.
2) Set the load inertia scale (SV037:JL) with a percentage in respect to the motor inertia of the
total load inertia.
3) Set the observer filter band (observer pole) in the disturbance observer 1 (SV043:OBS1), and
estimate the high frequency disturbance to suppress the vibration. Set 600 as a standard.
4) Set the observer gain in disturbance observer 2 (SV044:OBS2). The disturbance observer will
function here for the first time. Set 100 first, and if vibration does not occur, increase the
setting by 50 at a time to increase the observer effect.
5) If vibration occurs, lower OBS1 by 50 at a time. The vibration can be eliminated by lowering
OBS2, but the effect of the disturbance observer can be maintained by keeping OBS2 set to a
high value.
<Adjustment method>
If the load inertia is not clearly known, estimate it with the following method.
1) With the unbalance axis, set the torque offset (SV032:TOF). (Refer to "8-3-4 (2) Unbalance
torque compensation")
2) Set JL = 100, OBS1 = 600, and OBS2 = 0, and carry out a return operation within the range
where the axis can operate smoothly. At this time, set the acceleration/deceleration time
constant so the acceleration/deceleration torque equals or exceeds (is 100% or higher than)
the stall (rated) torque.
3) Observe the estimated disturbance torque using the D/A output, and increase JL until the
disturbance torque during acceleration/deceleration becomes small (cannot be observed).
Even when the torque offset is set and JL is an appropriate value, the friction torque amount
remains in the estimated disturbance torque of axes having a large amount of friction. As
shown in the graphs below, judge the setting value for JL having only the friction torque
remaining as the machine load inertia magnification.
Speed
command
0
Estimated
disturbance
torque
Chapter 8 Adjustment
0
Time
Friction torque
0 0
0
Time
Time
SV037 JL Load inertia scale %
SV043 OBS1 Disturbance observer 1 rad/sec
SV044 OBS2 Disturbance observer 2 %
No. Abbrev. Parameter name Unit Explanation Setting range
Set the load inertia that includes the motor in respect to the
motor inertia. (When the motor is a single unit, set 100%)
JL =
Set the observer filter band (observer pole).
Set 600 as a standard, and lower the setting by 50 at a time if
vibration occurs.
Set the observer gain.
Set 100 to 300 as a standard, and lower the setting if vibration
occurs.
Jl + Jm
Jm : Motor inertia
Jl : Machine inertia
0 to 5000
0 to 1000
0 to 1000
1. When the observer gain is set to zero (OBS2 = 0), the estimated
disturbance torque can be output to the D/A output even if the disturbance
observer is not functioning.
POINT
2. Parts of the machine that do not move smoothly can be presumed to be the
disturbance.
3. When the disturbance observer has been started, the lost motion
compensation must be readjusted.
8–16
Chapter 8 Adjustment
Cutting
8-3-4 Improvement of protrusion at quadrant changeover
The response delay (caused by non-sensitive band from friction, torsion, expansion/contraction,
backlash, etc.) caused when the machine advance direction reverses is compensated with the lost
motion compensation function.
With this, the protrusions that occur with the quadrant changeover in the DDB measurement method,
or the streaks that occur when the quadrant changes during circular cutting can be improved.
direction
Circle cutting path before compensation Circle cutting path after compensation
(1) Lost motion compensation (LMC)
The lost motion compensation compensates the response delay during the reversal by adding the
torque command set with the parameters when the speed direction changes. There are two
methods for lost motion compensation. With the intelligent servomotor, type 2 is used as a
standard.
(The explanation for type 1 method is omitted because it is interchangeable with the old method.)
<Setting method>
1) Set the special servo function selection 1 (SSF1) bit 9. (The LMC type 2 will start).
2) Set the compensation amount with a stall % (rated current % for the general -purpose motor) unit
in the lost motion compensation 1 (LMC1). The LMC1 setting value will be used for
compensation in the positive and negative directions when LMC2 is 0.
3) If the compensation amount is to be changed in the direction to be compensated, set LMC2. The
compensation direction setting will be as shown below with the CW/CCW setting. If only one
direction is to be compensated, set the side not to be compensated as –1.
Compensation
point
A X axis: LMC2 X axis: LMC1
B Y axis: LMC1 Y axis: LMC2
C X axis: LMC1 X axis: LMC2
D Y axis: LMC2 Y axis: LMC1
CW CCW
No. Abbrev. Parameter name Explanation
SV027 SSF1 The lost motion compensation starts with the following parameter.
aflt zrn2 ovs2 ovs1 lmc2 lmc1 vfct2 vfct1
bitNo LMC LMC type 1 LMC type 2
No. Abbrev.
SV016 LMC1 Lost motion
SV041 LMC2 Lost motion
Special servo function
selection 1
Parameter
name
compensation 1
compensation 2
Stall % (rated
current %)
Stall % (rated
current %)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Unit Explanation Setting range
While measuring the quadrant protrusion amount, adjust with a
5% unit.
The ± direction setting value will be applied when LMC2 is set to
0.
Set 0 as a standard.
Set this when the compensation amount is to be changed
Compensation
The X axis command direc-
C
tion changes from – to +.
8 lmc1
9 lmc2
8–18
The Y axis command direc-
D
+Y
-X
-Y
0 1 0 1
0 0 1 1
tion changes from + to –.
The X axis command direc-
A
tion changes from + to –.
+X
The Y axis command direc-
B
tion changes from – to +.
Setting
prohibited.
–1 to 200
–1 to 200
Chapter 8 Adjustment
2
and the adaptive filter cannot be simultaneously started. A parameter error
according to the direction.
<Adjustment method>
First confirm whether the axis to be compensated is an unbalance axis (vertical axis, slant axis).
If it is an unbalance axis, carry out the adjustment after performing step "(2) Unbalance torque
compensation".
Next, measure the frictional torque. Carry out reciprocation operation (approx. F1000) with the
axis to be compensated and measure the load current % when fed at a constant speed on the
CNC servo monitor screen. The frictional torque of the machine at this time is expressed with the
following expression.
Frictional torque =
The standard setting value for the lost motion compensation 1 (LMC1) is double the frictional
torque above.
(Example)
Assume that the load current % was 25% in the + direction and –15% in the –
direction when JOG feed was carried out at approx. F1000. The frictional torque is as
shown below, so 20% × 2 = 40% is set for LMC1. (Compensated in both directions
with LMC2 set to 0.) With this setting, 40% compensation will be carried out when the
command reverses from the + direction to the – direction, and when the command
reverses from the – direction to the + direction.
LMC1 = 20% × 2 = 40%
(Compensated in both directions with LMC2 set to 0.)
For the final adjustment, measure the CNC sampling measurement (DBB measurement) or while
carrying out actual cutting. If the compensation amount is insufficient, increase LMC1 or LMC2
by 5% at a time. Note that if the setting is too high, biting may occur.
Compensation 0 Optimum Too high
1. When either parameter SV016: LMC1 or SV041: LMC2 is set to 0, the same
2. To compensate in only one direction, set -1 in the parameter (LMC1 or
3. The value set based on the friction torque is the standard value for LMC
POINT
4. When the disturbance observer has been started, the observer
5. Once LMC compensation type 1 is started, the overshooting compensation
(+ feed load current %) – (– feed load current %)
25 – (–15)
2
= 20%
amount of compensation is carried out in both the positive and negative
direction with the setting value of the other parameter (the parameter not set to
0).
LMC2) for the direction in which compensation is prohibited.
compensation. The optimum compensation value changes with the cutting
conditions (cutting speed, cutting radius, blade type, workpiece material,
etc.). Be sure to ultimately make test cuts matching the target cutting and
determine the compensation amount.
compensation will also be effective on quadrant protrusions, so the
optimum compensation amount of the lost motion compensation will drop.
Note that the quadrant protrusions cannot be completely compensated with
only the disturbance observer.
8–19
will occur.
Chapter 8 Adjustment
8–20
(2) Unbalance torque compensation
After
If the load torque differs in the positive and negative directions such as with a vertical axis or
slant axis, the torque offset (TOF) is set to carry out accurate lost motion compensation.
<Setting method>
Measure the unbalance torque. Carry out reciprocation operation (approx. F1000) with the axis to
be compensated and measure the load current % when fed at a constant speed on the CNC
servo monitor screen. The unbalance torque at this time is expressed with the following
expression.
Unbalance torque =
(+ feed load current %) – (– feed load current %)
2
The unbalance torque value above is set for the torque offset (TOF).
If there is a difference in the protrusion amount according to the direction, make an adjustment
with LMC2. Do not adjust with TOF.
(Example)
Assume that the load current % was −40% in the + direction and −20% in the –
direction when JOG feed was carried out at approx. F1000. The unbalance torque is
as shown below, so −30% is set for TOF.
Chapter 8 Adjustment
−40 + (−20)
2
= −30%
No. Abbrev. Parameter name Unit Explanation Setting range
SV032 TOF Torque offset Stall % (rated
current %)
Set this when carrying out lost motion compensation.
Set the unbalance torque amount.
–100 to 100
Even when TOF is set, the torque output characteristics of the motor and load
POINT
current display of the CNC servo monitor will not change. Both the LMC
compensation and collision detection function are affected.
(3) Adjusting the lost motion compensation timing
If the speed loop gain has been lowered from the standard setting value because the machine
rigidity is low or because machine resonance occurs easily, or when cutting at high speeds, the
quadrant protrusion may appear later than the quadrant changeover point on the servo control. In
this case, suppress the quadrant protrusion by setting the lost motion compensation timing
(SV039: LMCD) to delay the LMC compensation.
<Adjustment method>
If a delay occurs in the quadrant protrusion in the circle or arc cutting as shown below in respect
to the cutting direction when CNC sampling measurement (DDB measurement) or actual cutting
is carried out, and the compensation appears before the protrusion position, set the lost motion
compensation timing (SV039:LMCD).
While measuring the arc path, increase LMCD by 10 msec at a time, to find the timing that the
protrusion and compensation position match.
compensation
Cutting
direction
Before timing delay compensation After timing delay compensation
8–21
Chapter 8 Adjustment
No. Abbrev. Parameter name Unit Explanation Setting range
SV039 LMCD Lost motion
compensation timing
When the LMCD is gradually raised, a two-peaked contour may occur at the motor FB position
DBB measurement. However, due to the influence of the cutter diameter in cutting such as end
milling, the actual cutting surface becomes smooth.
Because satisfactory cutting can be achieved even if this two-peaked contour occurs, consider
the point where the protrusion becomes the smallest and finest possible without over
compensating (bite-in) as the optimum setting.
Cutter center path
Cutter diameter
Actual cutting surface
Cutting direction
(4) Adjusting for feed forward control
In LMC compensation, a model position considering the position loop gain is calculated based on
the position command sent from the CNC, and compensation is carried out when the feed
changes to that direction. When the CNC carries out feed forward (fwd) control, overshooting
equivalent to the operation fraction unit occurs in the position commands, and the timing of the
model position direction change may be mistaken. As a result, the LMC compensation timing
may deviate, or compensation may be carried out twice.
If feed forward control is carried out and the compensation does not operate correctly, adjust with
the non-sensitive band (SV040: LMCT) during feed forward control. In this non-sensitive band
control, overshooting of a set width or less is ignored. The model position direction change point
is correctly recognized, and the LMC compensation is correctly executed.
This parameter is meaningless when feed forward control is not being carried out.
<Adjustment method>
If the compensation timing deviates during feed forward control, increase the LMCT setting by
1µm at a time.
Note that 2µm are set even when the LMCT is set to 0.
No. Abbrev. Parameter name Unit Explanation Setting range
SV040 LMCT Non-sensitive band
during feed forward
control
Setting of the non-sensitive band (SV040: LMCT) during feed forward control
POINT
is effective for improving overshooting compensation mis-operation during
feed forward control.
Set this when the lost motion compensation timing does not
msec
match. Adjust while increasing the value by 10 at a time.
Quadrant changeover point
This setting is valid only during feed forward control.
µm
2 µm is set when this is set to 0. Adjust by increasing the value
by 1 µm at a time.
Point of LMC compensation execution
0 to 2000
0 to 100
8–22
Chapter 8 Adjustment
0
0
Overshoot
0
0
Overshoot
8-3-5 Improvement of overshooting
The phenomenon when the machine position goes past or exceeds the command during feed
stopping is called overshooting. Overshooting is compensated by overshooting compensation (OVS
compensation).
The phenomenon when the machine position exceeds the command during feed stopping is called
overshooting. Overshooting occurs due to the following two causes.
1. Machine system torsion: Overshooting will occur mainly during rapid traverse settling
2. Machine system friction: Overshooting will occur mainly during one pulse feed
Either phenomenon can be confirmed by measuring the position droop.
Speed
FB
Position
droop
Time
1. Overshooting during rapid traverse settling 2. Overshooting during pulse feed
(1) Overshooting compensation (OVS compensation)
In OVS compensation, the overshooting is suppressed by subtracting the torque command set in
the parameters when the motor stops.
OVS compensation has a compensation effect for the overshooting during either rapid traverse
settling or pulse feed. Note that there is no compensation if the next feed command has been
issued before the motor positioning (stop). (Therefore, there is no compensation during circle
cutting.) There is also no compensation when the CNC is carrying out feed forward control.
<Setting and adjustment methods>
1) Set the special servo function selection 1 (SV027:SSF1) bit 10. (OVS compensation will start.)
2) Observe the position droop waveform using the D/A output, and increase the overshoot
compensation 1 (SV031: OVS1) value 1% at a time. Set the smallest value where the
overshooting does not occur. If SV042:OVS2 is 0, the overshooting will be compensated in
both the forward/reverse directions with the OVS1 setting value.
3) If the compensat ion amount is to be changed in the direction to be compensated, set the +
direction compensation value in OVS1 and the – direction compensation value in OVS2. If
only one direction is to be compensated, set the side not to be compensated as –1. The
compensation direction setting will be as reversed with the CNC parameter CW/CCW setting.
In OVS compensation, there is no compensation in the following cases.
1. There is no compensation if the next feed command has been issu ed
POINT
before the motor positioning (stop). (There is no compensation in circle
cutting.)
2. There is no compensation when the CNC is carrying out feed forward (fwd)
control.
Position
command
Position
droop
Time
8–23
Overshooting compensation type 1
No. Abbrev. Parameter name Explanation
SV027 SSF1 The overshooting compensation starts with the following parameter.
aft zrn2 ovs1 lmc2 lmc1 vfct2 vfct1
bitMeaning when "0" is set. Meaning when "1" is set. 10 ovs1
No. Abbrev. Parameter name Unit Explanation Setting range
SV031 OVS1 Overshooting
SV042 OVS2 Overshooting
POINT
Special servo function
selection 1
compensation 1
compensation 2
Stall % (rated
current %)
Stall % (rated
current %)
1. When either parameter SV031: OVS1 or SV042: OVS2 is set to 0, the
same amount of compensation is carried out in both the positive and
negative direction, using the setting value of the other parameter (the
parameter not set to 0).
2. To compensate in only one direction, set -1 in the parameter (OVS1 or
OVS2) for the direction in which compensation is prohibited.
3. For contour cutting, the projection at the arc end point is compensated with
OVS compensation. LMC compensation is carried out at the arc starting
point.
Chapter 8 Adjustment
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Overshooting compensation type
1 stop
Increase the value by 1% at a time, and find the value where
overshooting does not occur. When OVS2 is set to 0, the
setting value will be applied in both the ± directions.
Set 0 as a standard.
Set this when the compensation amount is to be changed
according to the direction.
OVS compensation
Cutting direction
start
–1 to 100
–1 to 100
LMC compensation
8–24
Chapter 8 Adjustment
-200
-200
Time Time
Time Time
8-3-6 Improvement of characteristics during acceleration/deceleration
(1) SHG control (option function)
Because SHG control has a smoother response than conventional position controls, the
acceleration/deceleration torque (current FB) has more ideal output characteristics (A constant
torque is output during acceleration/deceleration.) The peak torque is kept low by the same
acceleration/deceleration time constant, enabling the time constant to be shortened.
Refer to item "(3) SHG control" in section "8-2-3 Position loop gain" for details on setting SHG
control.
3000
Speed command
(r/min.)
-3000
200
Current FB
(stall %)
3000
Speed command
(r/min.)
-3000
200
Current FB
(stall %)
No. Abbrev. Parameter name
SV003
(SV049)
SV004
(SV050)
SV057
(SV058)
SV008 VIA
SV015 FFC
PGN1
(PGN1sp)
PGN2
(PGN2sp)
SHGC
(SHGCsp)
Position loop gain 1 1 23 26 33 38 47 1 to 200
Position loop gain 2 8/3 62 70 86 102 125 0 to 999
SHG control gain 6 140 160 187 225 281
Speed loop leading
compensation
Acceleration feed
forward gain
0
0
Acceleration/deceleration characteristics during conventional control
0
0
Acceleration/deceleration characteristics during SHG control
Setting
ratio
Set 1900 as a standard value during SHG control. 1 to 9999
Set 100 as a standard value during SHG control. 0 to 999
Setting example Explanation Setting range
Always set a
combination of 3
parameters.
0 to 999
8–25
(2) Acceleration feed forward
60 40 20
60 40 20
Vibration may occur at 10 to 20 Hz during acceleration/deceleration when a short time constant
of 30 msec or less is applied, and a position loop gain (PGN1) higher than the general standard
value or SHG control is used. This is because the torque is insufficient when starting or when
starting deceleration, and can be resolved by setting the acceleration feed forward gain
(SV015:FFC). This is also effective in reducing the peak current (torque).
While measuring the current command waveform, increase FFC by 50 to 100 at a time and set
the value where vibration does not occur.
Chapter 8 Adjustment
Current
command
(Stall %)
200
100
0
200
100
0
0
Time(msec)
80
100
0
Time(msec)
80
No FFC setting With FFC setting
Acceleration feed forward gain means that the speed loop gain during acceleration/deceleration
is raised equivalently. Thus, the torque (current command) required during
acceleration/deceleration starts sooner. The synchronization precision will improve if the FFC of
the delayed side axis is raised between axes for which high-precision synchronous control (such
as synchronous tap control and superimposition control).
No. Abbrev. Parameter name Unit Explanation Setting range
SV015 FFC Acceleration feed
forward gain
A 10 10 50 50 Standard value
% The standard setting value is 0. To improve the
acceleration/deceleration characteristics, increase the value by
approx. A given below. During SHG control, use the standard
setting values given below.
Motor MF23 RF43/73
for SHG control
10 10 100 100
SF52/53/
102/103
SF202
1 to 999
100
POINT
during SHG control.
8–26
Overshooting occurs easily when a value above the standard value is set
Chapter 8 Adjustment
0
-200
compensation
With inductive
(3) Inductive voltage compensation
The current loop response is improved by compensating the back electromotive force element
induced by the motor rotation. This improved the current command efficiency, and allows the
acceleration/deceleration time constant to the shortened.
<Adjustment method>
1) Set 1 in "mon" of the special servo function selection 3 (SV034: SSF3) bit 0, and output the
current command and current FB to the servo monitor.
2) While accelerating/decelerating at rapid traverse, adjust the inductive voltage compensation
gain (SV047:EC) so that the current FB peak is a few % smaller than the current command
peak.
3000
Speed
command
(r/min)
-3000
200
No inductive voltage
Time
Current
command
(stall %)
0
voltage
compensation
Time
Inductive voltage compensation
To adjust the inductive voltage compensation, output 1 second of the maximum current
command value and 1 second of the maximum current FB value to MAX current 1 and MAX
current 2 on the CNC servo monitor screen and observe.
Change over and display "mon" of the special servo function selection 3 (SV034: SSF3).
No. Abbrev. Parameter name Explanation
SV034 SSF3 Special servo function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bitMonitor Meaning when 0 is set Meaning when 1 is set
0 mon
No. Abbrev. Parameter name Unit Explanation Setting range
SV047 EC
selection 3
Inductive voltage
compensation gain
The display data for the maximum current value on the servo monitor is determined
with the following parameter.
daf1 dac1
MAX
current 1
MAX
current 2
Set 100% as a standard. Lower the gain if the current FB peak
%
exceeds the current command peak.
Maximum current command
value after power is turned
ON
Maximum current
com-mand value for one
second
Maximum current command
value for one second
Maximum current FB value
for one second
mon
0 to 200
If the current FB peak is larger than the current command peak,
overcompensation or overcurrent (alarm 3A) could occur easily. Note that
POINT
when using with a large load inertia, or when using over the rated rotation
speed with a motor set to rated rotation speed < maximum rotation speed,
overcompensation could occur easily.
8–27
Chapter 8 Adjustment
EMGt
Constant inclination deceleration
Time
Dynamic brakes activate at 60 r/min or less
8-4 Setting for emergency stop
The emergency stop referred to here indicates the following states.
1) When the external emergency stop was input (including other axis alarms)
2) When the CNC power down was detected
3) When a servo alarm was detected
8-4-1 Deceleration control
This intelligent servomotor servo amplifier decelerates the motor according to the set time constant in
the ready ON state even when an emergency stop occurs, and activates the dynamic brakes after
stopping and turning ready OFF. This series of controls is called deceleration control. In the intelligent
servomotor, deceleration control is the standard method of stopping during an emergency stop.
<Features>
1) When the load inertia is large, deceleration and stop are possible with a short time constant
using the dynamic brakes. (Stopping is possible with a basically normal acceleration/
deceleration time constant.)
2) When used in a transfer line, etc., stopping with little shock is possible by setting a long time
constant.
(1) Setting the deceleration control time constant
The time to stopping from the rapid traverse rate (rapid: axis specification parameter) is set in the
deceleration control time constant (SV056: EMGt). A position loop step stop is carried out when 0
is set.
When linear (straight line) acceleration/deceleration is selected for the rapid traverse, the same
value as the acceleration/deceleration time constant (G0tL) becomes the standard value. When
another acceleration/deceleration pattern is selected, set the rapid traverse to linear
acceleration/deceleration. Adjust to the optimum acceleration/deceleration time constant, and set
that value as the standard value.
<Operation>
When an emergency stop occurs, the motor will decelerate at the same inclination from each
speed, and will change to the dynamic brakes at 60 r/min or less. If the power fails, etc., the
dynamic brakes will be applied during the deceleration control. When the motor brakes are
controlled with amplifier output while using an unbalanced axis, the motor brake control output
operates simultaneously with the changeover to the dynamic brakes.
RAPID
Motor speed
Dynamic brakes
Motor brake control output (MBR)
OFF
ON
OFF
ON
Emergency stop occurrence
No. Abbrev. Parameter name Unit Explanation Setting range
SV056 EMGt Deceleration control
time constant
Set the time to stop from rapid traverse rate (rapid).
msec
Set the same value as the rapid traverse
acceleration/deceleration time constant (G0tL) as a standard.
0 to 5000
1. The deceleration will not be controlled when a servo alarm that uses the
dynamic brake stopping method occurs. Stopping is by the dynamic brake
method regardless of the parameter setting.
POINT
2. When a power failure occurs, the stopping method may change over to a
dynamic brake stop during deceleration control if the deceleration time
constant is set comparatively long. This is because of low bus voltage in the
amplifier.
8–24
CAUTION
PGN1 × 60
2
60
rapid × 1000
Time
(2) Dynamic brake stop
When an emergency stop occurs, it is possible to have the machine stop from the beginning
using a dynamic brake without controlling the deceleration. Set bit 0 in the servo specifications
(SV017: SPEC) to select a dynamic brake stop.
In a dynamic brake stop, the dynamic brakes operate at the same time the emergency stop
occurs, and the motor brake output also operates at the same time.
Chapter 8 Adjustment
If the deceleration control time constant (EMGt) is set longer than the
acceleration/deceleration time constant, the overtravel point (stroke end point)
may be exceeded.
A collision may be caused on the machine end, so be careful.
Emergency stop occurrence
Motor speed
Dynamic brakes
Motor brake control output (MBR)
OFF
ON
OFF
ON
No. Abbrev. Parameter name Explanation
SV017 SPEC Servo specifications Set the dynamic brake stop with the following parameter.
bitMeaning when "0" is set. Meaning when "1" is set. 0 dmk Deceleration control stop Dynamic brake stop
If a dynamic brake stop is selected, the software does not participate at all in
POINT
CAUTION
the motor stop control after an emergency stop occurs.
When a dynamic brake stop is selected, in general the coasting distance
during an emergency stop will be comparatively longer, so be careful.
(3) Deceleration control stop distance
If stopping with deceleration control during an emergency stop, the stop distance L
DEC
approximately calculated with the following expression. However, the value will be higher than
the following expression if the current is limited during deceleration. Refer to section "3-3-2
Coasting amount" for the stop distance using dynamic brakes.
L
DEC
=
F
+
1
×
F
×
F × EMGt
(mm)
can be
F : Feedrate during emergency stopped (mm/min)
rapid : Rapid traverse rate (mm/min)
PGN1 : Position loop gain 1 (SV003) (rad/sec)
EMGt : Deceleration control time constant (SV056) (msec)
8–25
Chapter 8 Adjustment
mum
Brake activation delay
Time
8-4-2 Vertical axis drop prevention control
The vertical axis drop prevention control is a function that prevents the vertical axis from dropping
due to a delay in the brake operation when an emergency stop occurs. The servo ready OFF will be
delayed by the time set in the parameter from when the emergency stop occurs. Thus, the no-control
time until the brakes activate can be eliminated.
<Setting and adjustment methods>
Set the time to delay the ready OFF in the vertical axis drop prevention time (SV048:EMGrt).
Read the current position on the CNC screen, and apply the emergency stop. Set the minimum
delay time where the axis does not drop.
Motor speed
Emergency stop occurrence
Deceleration control
Dynamic brakes
Motor brake control output (MBR)
Motor brake actual operation
Servo ready (READY)
OFF
ON
OFF
ON
OFF
ON
ON
OFF
EMGrt
No. Abbrev. Parameter name Unit Explanation Setting range
SV048 EMGrt Vertical axis drop
prevention time
Input the time to delay the ready OFF when an emergency stop
msec
occurs.
Increase the setting by 100 msec at a time and set the mini
value where the axis does not drop.
0 to 2000
1. This control will not function if the dynamic brake stop is selected with the
servo specifications (SV017: SPEC).
2. This control will not function if an alarm for which the dynamic brakes are
POINT
set as the stopping method occurs in an axis where vertical axis drop
prevention control is being carried out.
3. A drop amount of several µm to 10µm will remain due to the brake play.
CAUTION
1. Do not set a vertical axis drop prevention time longer than required. The
servo control and brakes could collide causing an overload alarm or
amplifier damage. There is no problem if the duplicate time is within
100msec.
2. During a power failure, vertical axis drop prevention cont rol (including
deceleration control) exceeding 100msec cannot be guaranteed. The
control will change to the dynamic brakes.
8–26
Chapter 8 Adjustment
0
SV032)
SV060)
G1 feed (cutting feed)
G0 feed (rapid traverse)
(SV060×clG1
8-5 Collision detection
The purpose of the collision detection function is to quickly detect a collision and decelerate to a stop.
This suppresses the excessive torque generated to the machine tool, and suppresses the occurrence
of an abnormality. Impact during a collision cannot be prevented even when the collision detection
function is used, so this function does not guarantee that the machine will not break and does not
guarantee the machine accuracy after a collision. Thus, the conventional caution is required to
prevent machine collisions from occurring.
(1) Collision detection method 1
The required torque is calculated from the position
command issued from the NC. The disturbance
torque is calculated from the difference with the
actual torque. When this disturbance torque exceeds
the collision detection level set with the parameters,
the axis will decelerate to a stop with at 80% of the
motor's maximum torque. After decelerating to a
stop, the alarm 58 or 59 will occur, and the system
will stop.
The collision detection level for rapid traverse (G0) is set with TLMT: SVC060. The collision
detection level for cutting feed (G1) is set to 0 to 7-fold (SV053.clG1) based on the collision
detection level for rapid traverse. If 0 is set for clG1, the collision detection method 1 will not
function during cutting feed. If 0 is set for TLMT: SV060, all collision detections (method 1 and
method 2) will not function.
Estimated torque
(stall %)
Speed
command
(r/min)
3000
-3000
200
100
-100
-200
0
G0 collision
detection level
(
Alarm detection range for collision detection method 1
(2) Collision detection method 2
When the current command reaches the motor's maximum current, the axis will decelerate to a
stop with at 80% of the motor's maximum torque. After decelerating to a stop, the alarm 5A will
occur, and the system will stop. If the acceleration/deceleration time constant is short and
incorrect detections are made easily during normal operation, increase the
acceleration/deceleration time constant and adjust so that the current during acceleration is not
saturated (so that the maximum current is not reached).
If the acceleration/deceleration time constant cannot be increased, set parameter SV035.bit11:
SSF4.cl2n to 1 to ignore the collision detection method 2.
The collision detection function does not guarantee safety or machine
CAUTION
accuracy during a collision. Thus, the conventional caution is required to
prevent machine collisions from occurring.
Collision detection method
1 detection range
(Alarm 58/59)
G0 collision
detection level
Collision
For rapid traverse
(for G0 feed)
For cutting feed
(for G1 feed)
detec-tion level
setting parameter
SV060 Alarm 58
SV060×clG1
(SV035)
Frictional torque
(SV045)
Unbalance torque
(
Detection
Alarm 59
alarm
8–27
<Setting and adjustment methods>
1. Validate the extended function. (Set sv035: SSF4, bit7 (eram) to 1.)
2. Confirm that SHG control is being used. The collision detection function is valid only during
SHG control.
3. Measure the unbalance torque, and set in the torque offset (SV03: TOF). Refer to the section
"8-3-4 (2) Unbalance torque compensation" for details on measuring the unbalance torque.
4. Measure the frictional torque, and set in the frictional torque (SV045: TRUB). Refer to the
section "8-3-4-(1) Lost motion compensation" for details on measuring the frictional torque.
5. Set the estimated torque gain (SV059: TCNV) with the following method.
Set sv035: SSF5, bit 15 (clt) for the axis to be adjusted to 1.
Repeatedly move the axis to be adjusted in both directions at the maximum rapid traverse
rate.
Observe the MPOF display value on the NC unit's [I/F Diagnosis/Servo Monitor] screen, and
continue operation until the display value stabilizes.
Once the display value stabilizes, set that value as the estimated torque gain (SV059: TCNV).
6. If the acceleration/deceleration time is short and the current is easily saturated, set
SV035.bit15(cl2n) to 1, and ignore the collision detection method 2.
7. Set the collision detection level.
Feed Detection level setting Explanation
G0 SV060
G1 SV060×clG1 (SV035)
1. The SHG control must be validated to use the collision detection function or
to carry out load inertia measurement operation.
2. When measuring the estimated torque gain, if the unbalance torque
(SV032) and frictional torque (SV045) setting values are changed, the
POINT
measurement results will change. The unbalance torque and frictional
torque must be set as accurately as possible to carry out accurate
measurement.
3. Set the detection level with an allowance to avoid incorrect detections.
4. When SV060 is set to 0, all collision detection functions will be invalidated.
Chapter 8 Adjustment
First set SV060: TLEV = 100, and carry out no-load operation at the
maximum rapid traverse feed rate. If an alarm does not occur, lower the
setting by 10, and if an alarm occurs, raise the setting by 20. Set a value that
is 1.5 times the limit value where the alarm does not occur.
If SV034.mon is set to 7, the maximum disturbance torque will appear on the
NC servo monitor, so adjust using this value as a reference.
The detection level for G1 is set as an integer-fold of the G0 detection level.
Calculate the maximum cutting load, and adjust the SV035.clG1 setting value
so that the detection level is larger than the maximum cutting load.
8–28
Chapter 8 Adjustment
ue) is displayed
No. Abbrev. Parameter name Explanation
SV035 SSF4 The following parameters are used for the collision detection.
clt clG1 cl2n clet eram
bitMeaning when "0" is set. Meaning when "1" is set. 7 eram Extended function invalid Extended function invalid
The latest two-second estimated
disturbance torque peak value
(3.5ms average val
at MPOF on the Servo Monitor
screen.
Collision detection method 2
invalid
12
to
14
current %)
current %)
current %)
Set the collision detection level for collision detection method 1,
cutting (G1) feed.
clG1
The G1 collision detection level is SV060 × clG1.
When clG1 is set to 0, the collision detection method 1 will not
function during cutting feed.
The value to be set in TCNV is
calculated and displayed at MPOF
on the Servo Monitor screen.
Set the unbalance torque amount. –100 to 100
Set the frictional torque for using the collision
detection function.
Set the torque estimated gain for using the collision
detection function.
If acceleration/deceleration operation is carried out
with SV035.clt set to 1 and SV060 set to 0, the
estimated torque gain will be displayed on the NC
Monitor screen.
Set the collision detection level of method 1 G0 feed
when using the collision detection function.
When 0 is set, all collision detection functions will
not function.
0 to 100
0 to 5000
0 to 200
8–29
Chapter 8 Adjustment
speed
8-6 Parameter list
No. Abbrev. Parameter name Unit Explanation
SV001 PC1 Motor side gear ratio 1 to 32767
SV002 PC2
SV003 PGN1 Position loop gain 1 rad/sec
SV004 PGN2 Position loop gain 2 rad/sec
SV005 VGN1 Speed loop gain
SV006 Set "0". 0
SV007 Set "0". 0
SV008 VIA
SV009 IQA
SV010 IDA
SV011 IQG q axis gain 1 to 2560
SV012 IDG d axis gain
SV013 ILMT Current limit value
SV014 ILMTsp
SV015 FFC
SV016 LMC1
SV017 SPEC Servo specifications
SV018 PIT Ball screw pitch mm
SV019 RNG1
SV020 RNG2
Machine side gear
ratio
Speed loop leading
compensation
q axis leading
compensation
d axis leading
compensation
Current limit value
during special
operation
Acceleration feed
forward gain
Lost motion
compensation 1
Position detector
resolution
Speed detector
resolution
1 to 20480
1 to 20480
Stall %
(rated
current %)
Stall %
(rated
current %)
Stall %
(rated
current %)
Set "0" in bits with no particular description.
kp/rev 8 to 100
kp/rev
Set the motor side and machine side gear ratio.
For the rotary axis, set the total deceleration (acceleration) ratio.
Even if the gear ratio is within the setting range, the electronic
gears may overflow and cause an alarm.
Set the position loop gain. Set 33 as a standard.
When using SHG control, also set PGN2 and SHGC.
Set 0 as a standard.
When using SHG control, also set PGN1 and SHGC.
Set this according to the motor inertia size.
If motor resonance occurs, lower the value by 20 to 30% at a time.
The setting value should be 70 to 80% of the value where
resonance does not occur.
Set 1364 as a standard. During SHG control, set 1900 as a
standard.
Raise this value to improve contour tracking precision in highcutting. Lower this value when the position droop vibrates.
Adjust by 100 at a time.
This setting is determined by the motor's electrical characteristics.
Set the standard parameters for all parameters. (These are used
for maker adjustments.)
Set the standard parameter value. The maximum torque is
determined by the motor specifications.
Set the standard parameter value.
Set the limit torque mainly for the stopper.
The standard setting value is 0. For SGH control, set 100.
%
To improve the acceleration/deceleration characteristics, increase
the value by 50 to 100 at a time.
The protrusion amount during quadrant changeover is suppressed.
Adjust in 5% units.
When LMC2 is set to 0, the setting value will apply in both the ±
directions.
bit Meaning when "0" is set Meaning when "1" is set
0 dmk
1
2
3
4
5
6
7 abs Incremental control Absolute position control
8