Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Indicates that incorrect handling may cause hazardous conditions, resulting in
death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in
medium or slight personal injury or physical damage.
Depending on the circumstances, procedures indicated by may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.
1. DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the service power supply for sensors varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line.
As a guideline, lay the control line at least 100mm(3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog input adaptor or
special analog extension block at one point on the PLC.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog output adaptor
or special analog extension block at one point on the analog device side.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to the power connectors or terminal blocks.
Failure to do so may result in wire damage/breakage or PLC failure.
(1)
Safety Precautions
(Read these precautions before use.)
2. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
•
- Tightening torque should be between 0.22 to 0.25 N
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
m.
3. STARTUP AND MAINTENANCE PRECAUTIONS
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electrical shock or malfunctions.
• Before cleaning or retightening terminals, cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
• Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual
and the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
• Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from
a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric distributor.
• Turn off the power to the PLC before connecting or disconnecting any extension cable.
Failure to do so may cause equipment failures or malfunctions.
• Turn of the power to the PLC before attaching or detaching the peripheral devices, expansion boards, special
adapters, and extension blocks.
Failure to do so may cause equipment failures or malfunctions.
(2)
FX3G/FX3U/FX
FX3G/FX3U/FX3UC Series Programmable
Controllers
User's Manual [Analog Control Edition]
3UC
PLC User's Manual - Analog Control Edition
Manual numberJY997D16701
Manual revisionF
Date11/2008
Foreword
This manual describes the "analog" function of the MELSEC-F FX Series programmable controllers and
should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
• This manual provides information for the use of the FX3U Series Programmable Controllers. The manual
has been written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
Note: the term 'completed equipment' refers to a third party constructed device which contains or uses
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult the nearest Mitsubishi Electric distributor.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
distributor.
3UC
PLC User's Manual - Analog Control Edition
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
the product associated with this manual
Registration
•Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
Warranty...................................................................................................................................... i
Revised History ......................................................................................................................... ii
17
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Table of Contents
MEMO
18
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
1.Introduction
1 Introduction
1.1 Outline and Features of Analog Control
A
Common Items
This manual describes the analog products for the FX3G/FX3U/FX3UC Series PLC.
This chapter describes the analog control methods and applications.
1.1Outline and Features of Analog Control
For the FX Series, there are 3 types of analog control: Voltage/Current input, Voltage/Current output, and
Temperature Sensor input.
It is important to select products that are optimum for the purpose of use.
FX
3UC
FX3U Series PLCFX3G Series PLC
Voltage/current input
control type
•
3U
-4AD
FX
•
3UC
-4AD
FX
•
3
U
-4AD-ADP
FX
•
3G
-2AD-BD
FX
→ Refer to Subsection
1.1.1.
Voltage/current
output control type
•FX
•
•
→ Refer to Subsection
Series PLC
3U
-4DA
FX3U-4DA-ADP
FX
3G
-1DA-BD
1.1.2.
Temperature sensor
input control type
•FX
3U
-4AD-PT-ADP
3U
-4AD-PTW-ADP
•FX
•FX
3U
-4AD-PNK-ADP
•
FX
3U
-4AD-TC-ADP•
3U
→ Refer to Subsection
1.1.3.
B
FX
3UC
-4AD
C
D
E
F
FX
3U
-4AD
FX
3U
-4AD-ADP
FX
3G
-2AD-BD
FX
3U
-4DA
FX
3U
-4DA-ADP
Flowmeter,
pressure sensor, etc.
In addition to the above applications, the FX
Inverter, etc.
3U/FX3UC/FX3G Series PLC can be used for various purposes.
Input the voltage/current signal from a flowmeter, pressure sensor, etc. to the PLC to monitor the condition of
the workpiece or equipment.
Voltage or
current
Output the current or voltage
data from the flux rate or the
pressure.
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
3UC Series Analog input products
FX
•FX
3UC-4AD
Analog input
special function
block, special
adapter,
expansion board
A/D conversion
data
Configuration Drawings of Analog Products."
→ For detailed description, refer to Section B.
1 Introduction
1.1 Outline and Features of Analog Control
1.1 Outline and Features of Analog Control
FX
3U
/FX
3
UC
Check the flux rate using
the PLC.
/FX
Series PLC
3
G
3U Series Analog input products
FX
•FX
3U-4AD
→ For detailed description, refer to Section B.
•FX
3U-4AD-ADP
→ For detailed description, refer to Section C.
3G Series Analog input products
FX
•FX
3G-2AD-BD
→ For detailed description, refer to Section D.
Other Series Analog input products
2NC-4AD• FX2N-4AD• FX2N-5A
•FX
•FX
2N-8AD• FX2N-2AD• FX0N-3A
→ For a detailed description of the other analog input
products, refer to the corresponding manuals.
A-2
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
1.1.2Analog output control
Output the voltage/current signal from the PLC to an inverter, etc. to control the inverter frequency, etc.
1 Introduction
1.1 Outline and Features of Analog Control
A
Common Items
3U
/FX
3
FX
UC
Output the frequency data
from the PLC.
Series PLC/FX
3
G
D/A conversion
data
Analog output
special function
block, special
adapter,
expansion board
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
Configuration Drawings of Analog Products."
Analog output products for FX
3U Series
•FX3U-4DA
→ For detailed description, refer to Section E.
•FX
3U-4DA-ADP
→ For detailed description, refer to Section F.
Analog output products for FX
•FX
3G-1DA-BD
3G Series
→ For detailed description, refer to Section G.
Other Series Analog output products
2NC-4DA• FX2N-2DA• FX0N-3A
•FX
•FX
2N-4DA• FX2N-5A
→ For a detailed description of the other analog output
products, refer to the corresponding manuals.
Voltage or
current
The frequency will be
changed depending on
the input voltage/current.
Inverter, etc.
B
FX
3UC
-4AD
C
D
E
F
FX
3U
-4AD
FX
3U
-4AD-ADP
FX
3G
-2AD-BD
FX
3U
-4DA
FX
3U
-4DA-ADP
G
H
-ADP
-ADP
J
-ADP
FX
3G
-1DA-BD
FX
3U
-4AD-PT
I
FX
3U
-4AD-PTW
FX
3U
-4AD-PNK
A-3
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
1.1.3Temperature sensor input control
Use the PLC to check the workpiece/machine temperature measured with a thermocouple or platinum
resistance thermometer sensor.
1 Introduction
1.1 Outline and Features of Analog Control
1.1 Outline and Features of Analog Control
Temperature data
(Analog data)
Measure the
temperature of the
equipment.
Temperature
sensor input,
special function
block or special
adapter
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
3U Series Temperature sensor input products
FX
•FX
3U-4AD-PT-ADP
•FX
3U-4AD-PTW-ADP
•FX
3U-4AD-PNK-ADP
•FX
3U-4AD-TC-ADP
Other Series Temperature sensor input products
2N-8AD• FX2N-2LC
•FX
•FX
2N-4AD-TC• FX2N-4AD-PT
→ For a detailed description of the other temperature sensor input products, refer to the
Temperature data
(Digital value)
Configuration Drawings of Analog Products."
→ For detailed description, refer to Section H.
→ For detailed description, refer to Section I.
→ For detailed description, refer to Section J.
→ For detailed description, refer to Section K.
FX3U/FX
3
UC
3
Check the temperature
using the PLC.
corresponding manuals.
Series PLC/FX
G
A-4
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
2.Description of Analog Products
2.1Types of Analog Products
Analog input/output products are required to perform analog control using the FX Series PLC.
There are 2 types of input/output products: the expansion board, special adapter and the special function
block.
Subsequent subsections explain differences among analog products.
2.1.1Expansion board
The analog expansion board uses PLC devices to send/receive data to/from the PLC.
2 Description of Analog Products
2.1 Types of Analog Products
A
B
FX
3UC
-4AD
C
Common Items
FX
3U
-4AD
FX
3U
-4AD-ADP
1. FX3G Series PLC
• Connect analog expansion boards to option connectors of an FX3G PLC.
• Up to 2
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
*1.Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*1
analog expansion boards can be connected.
PLC
Analog
expansion board
When two analog expansion boards are connected to the 40-point or 60-point type main unit, analog
special adapters are not available in the main unit.
Edition.
D
E
F
G
FX
3G
-2AD-BD
FX
3U
-4DA
FX
3U
-4DA-ADP
FX
3G
-1DA-BD
A-5
H
-ADP
-ADP
-ADP
J
FX
3U
-4AD-PT
I
FX
3U
-4AD-PTW
FX
3U
-4AD-PNK
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
2.1.2Special adapter
The analog special adapter uses PLC devices to send/receive data to/from the PLC.
1. FX3U Series PLC
• Connect the special adapter(s) to the left side of the FX3U Series PLC.
• An expansion board is needed to connect the special adapter(s).
• Up to 4 analog special adapters can be connected.
• When using the high-speed input/output special adapter(s), be sure to connect the high-speed input/output
special adapter(s) first, and then connect the analog special adapter(s).
Analog special adapters
FX3U-4AD-ADP
FX3U-4AD-ADP
FX3U-4AD-ADP
FX3U-4AD-ADP
POWER
PO ER
POWER
2 Description of Analog Products
2.1 Types of Analog Products
2.1 Types of Analog Products
High-speed
input/output
special adapters
WPOWER
Expansion board
RDA
RD
RDB
SDA
SD
SDB
SG
FX3U-***-BD
PLC
Up to 4 Analog adapters can be connected.
"***" represents "422", "232",
"485", "CNV", or "USB."
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
2. FX3UC (D, DSS) Series PLC
• Connect the special adapter(s) to the left side of the FX3UC (D, DSS) Series PLC.
• Up to 4 analog special adapters can be connected.
Analog special adapters
FX3U-4AD-ADP
POWER
PO ER
POWER
WPOWER
FX3U-4AD-ADP
FX3U-4AD-ADP
FX3U-4AD-ADP
Up to 4 Analog adapters can be connected.
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
PLC
Edition.
Edition.
A-6
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
3. FX3UC-32MT-LT(-2) PLC
• Connect the special adapter(s) to the left side of the FX3UC-32MT-LT(-2) PLC.
• An expansion board is needed to connect the special adapter(s).
• Up to 4 analog special adapters can be connected.
Analog special adapters
FX3U-4AD-ADP
FX3U-4AD-ADP
POWER
2 Description of Analog Products
2.1 Types of Analog Products
A
Common Items
Expansion board
FX3U-4AD-ADP
FX3U-4AD-ADP
PO ER
POWER
WPOWER
RDA
RD
RDB
SDA
SD
SDB
SG
PLC
B
FX
3UC
-4AD
FX
3U
-4AD
FX3U-***-BD
Up to 4 Analog adapters can be connected.
"***" represents "422", "232", "485", "CNV", or "USB."
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
4. FX3G Series PLC
• Connect the special adapter(s) to the left side of the FX3G Series PLC.
• A connector conversion board is needed to connect the special adapter(s).
• Up to 2
*1.Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*1
analog special adapters can be connected.
Analog
Connector conversion adapter
PLC
special adapters
3G
-CNV-ADP
FX
Up to 2 Analog adapters can be connected.
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
When two analog expansion boards are connected to the 40-point or 60-point type main unit, analog
special adapters are not available in the main unit.
C
D
E
F
G
FX
3U
-4AD-ADP
FX
3G
-2AD-BD
FX
3U
-4DA
FX
3U
-4DA-ADP
FX
3G
-1DA-BD
A-7
H
-ADP
-ADP
-ADP
J
FX
3U
-4AD-PT
I
FX
3U
-4AD-PTW
FX
3U
-4AD-PNK
FX3G/FX3U/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
2.1.3Special function block
The special function block uses buffer memory (BFM) to send/receive data to/from the PLC.
1. FX3U Series PLC
• Connect the special function block(s) to the right side of the FX3U Series PLC.
• Up to 8 special function blocks can be connected.
PLCAnalog special function block
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
2. FX3UC Series PLC
• Connect the special function block(s) to the right side of the FX3UC Series PLC.
• In some cases, FX
PLC
*1
special function blocks can be connected.
• Up to 8
2NC-CNV-IF or FX3UC-1PS-5V may be needed for connection.
FX
3UC
or FX
special function block
2NC
Analog
3U
, FX
2N
and FX
for FX
Up to 8 special function units/blocks can be
connected (excluding the special adapters).
FX
FX
3UC
2NC
-1PS-5V
or
-CNV-IF
FX
0N
3U
, FX2N or FX0N Analog
special function block
2 Description of Analog Products
2.1 Types of Analog Products
2.1 Types of Analog Products
Up to 8*1 special function units/blocks can be connected (excluding the special adapters).
*1.Up to 7 special function units/blocks can be connected to the FX
3UC-32MT-LT(-2) PLC.
Select either FX3UC-1PS-5V or FX2NC-CNV-IF considering the current components consumption.
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
3. FX3G Series PLC
• Connect the special function block(s) to the right side of the FX3G Series PLC.
• Up to 8 special function blocks can be connected.
PLCAnalog special function block
Up to 8 special func tion units/blocks can be
connected (excluding t he special adapters ).
→ For a detailed description of the system configuration, refer to the PLC User's Manual - Hardware Edition.
for FX