•This manual contains t ext, diagrams and explanations which will guide the reader in the corre ct installation
and operation of the FX1S Series Programmable Controllers. It should be read and understood before
attempting to install or use the unit.
•Further inform ation can be found in the FX Series Programming Manual II.
•If in doubt at any stage of the installation of an FX1S Ser ies Pro grammable Controller always consult a professional electrical engineer who is qualified and trained to the local and national standards which apply to
the installation site.
•If in doubt about the op eration or use of FX1S Series Pr ogrammable Controller please consult th e nearest
Mitsubisi Electric distributor.
•This manual is subject to change without notice.
Page 3
FX1S Series Programmable Controllers
FX
Series Programmable Controllers
1S
Hardware Manual
Manual number :JY992D83901
Manual revision :B
Date:April 2000
Page 4
FX1S Series Programmable Controllers
Guidelines for the Safety of the User and Protection of the FX1S.
This manual provides inform ation for the use o f the FX1S. The manual has been wr itte n to be
used by trained and co mpetent pe rsonnel. The definit ion of su ch a pers on or perso ns is as
follows:
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated w ith this manual, shoul d be of a competent
nature, trained and qualified to the local and national standards required to fulfill that
role. These engineers should be fully aware of all aspects of safety with regards to
automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained in the use and maintenance of the completed pr oduct. This
includes being completely familiar with all associated documentation for said product. All
maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment should be trained to use that product in a safe
and coordinate d manner i n complia nce to esta blished safety practices. The op erators
should also be familiar with documentation which is connected with the actual operation
of the completed equipment.
Note :
The term ‘completed equipment’ refers to a third party constructed device which
contains or uses the product associated with this manual.
ii
Page 5
FX1S Series Programmable Controllers
Note’s on the Symbology Used in this Manual
At various times through out this manual cer tain symbols will be used to highlight points of
information which are intended to ensure the users personal safety and protect the integrity of
equipment. Whenever any of the following symbols are encountered its associat ed note must
be read and understood. Each of the symbols used will now be listed with a brief description of
its meaning.
Hardware Warnings
1) Indicates that the identified danger
2) Indicates that the identified danger could
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.
5) Indicates a special point which the us er of the associate software element should
be aware.
6) Indicates a point of interest or further explanation.
WILL
cause physical and property damage.
POSSIBLY
cause physical and property
iii
Page 6
FX1S Series Programmable Controllers
•Under no circumstances will Mitsubishi Electr ic be liable responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
•All examples and diagrams sho wn in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for
actual use of the product based on these illustrative examples.
•Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
iv
Page 7
FX1S Series Programmable ControllersTable of Contents
Table of Contents
Guideline .......................................................................................................................... ii
7.8Device List .....................................................................................................7-11
vii
Page 10
FX2NC Series Programmable ControllersContents.
viii
Page 11
FX1S Series Programmable ControllerIntroduction 1
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 12
Introduction 1FX1S Series Programmable Controller
Page 13
FX1S Series Programmable ControllerIntroduction 1
1.Introduction
This manual covers the hardware installation instructions for the FX1S Series Programmable
Logic Controller.
Table 1.1 : Relay Output Units
MODEL
INPUTOUTPUT
QTYTYPEQTYTYPE
POWER
SUPPLY
DIMENSIONS
mm (inches)
MASS
(WEIGHT)
kg (lbs)
FX1S-10MR-ES/UL6
FX1S-14MR-ES/UL86
FX1S-20MR-ES/UL128
FX1S-30MR-ES/UL1614
24V DC
Sink /
Source
Table 1.2 : Transistor Output Units
INPUTOUTPUT
MODEL
FX1S-10MT-ESS/UL6
FX1S-14MT-ESS/UL86
FX1S-20MT-ESS/UL128
FX1S-30MT-ESS/UL1614
QTYTYPEQTYTYPE
24V DC
Sink /
Source
4
4
Relay
Transistor
(Source)
85 - 264
VAC
POWER
SUPPLY
85 - 264
VAC
60
(2.4)
75
(3.0)
100
(3.9)
60
(2.4)
75
(3.0)
100
(3.9)
90
(3.5)75(3.0)
DIMENSIONS
mm (inches)
90
(3.5)75(3.0)
0.3 (0.66)
0.4
(0.88)
0.45
(0.99)
MASS
(WEIGHT)
kg (lbs)
0.3
(0.66)
0.4
(0.88)
0.45
(0.99)
1-1
Page 14
FX1S Series Programmable ControllerIntroduction 1
Figure 1.1: FX1S Outline Drawing
DINRail
The distance between the ver tical center lines is 8mm (0.31”) le ss than the width of th e unit
Please see previous page for each model’s width measurement.
1-2
Page 15
FX1S Series Programmable ControllerIntroduction 1
1.1Model na me
FX1S-14MT-ESS/UL
A)
B)
C)
Table 1.3 : Model Table
F)
E)
D)
A)PLC type : FX
B)Total number of I / O channels
C)
D)
Unit type
MMPU - main unit
Output type
RRelay
TTransistor
1S
Features
Omit AC, Japanese specification
D24V DC Japanese specification
DS24V DC World specification
E)
DSS 24V DC World specification, DC source transistor
ESAC Power Supply World specification
ESS
F)
AC Power Supply World speci fication , DC sourc e
transistor
UA1 AC Power Supply, AC inputs
ULCE,UL registered product
1-3
Page 16
FX1S Series Programmable ControllerIntroduction 1
1.2World Specification
Table 1.4 : World / Japanese Specifications
Input
Sink / Source
World spec models : SINK / SOURCE
Japanese models : ALWAYS SINK
Outputs
Transistor
World spec models : ALWAYS SOURCE
Japanese models : ALWAYS SINK
1.3Serial Numbers
SERIAL NO.: 9 X 3267
1)
e.g.
9=1999
0=2000
Table 1.5 : Notes on Serial Numbers
1)
2)
3)
Production year
Production month
Production serial number
BFX1N Memory Cassette or Display Unit
CFX
DFX0N Network Adaptors
EProgramming Cables
FProgramming Software
GHMI Devices, F900 GOT and FX-DU Series
HDedicated Programming Tools
Expansion Boards
1N
Table 1.7 : Connection Ports
Memory Port
1
Extension Board Port
2
Programming Port
3
1-6
Page 19
FX1S Series Programmable ControllerIntroduction 1
1.4.2Rules for Expansion
The FX1S Series can:
•Use one expansion unit or board per square B, C, and G concurrently.
•The FX1S can supply 400mA at 24V DC.
The FX1S cannot:
-Be expanded by the use of Special Funcion Blocks.
-Supply a 5V DC service supply.
-Use FX
-Use the FX
1N
-422-BD + FX-2PIF.
1N
-5DM and the FX-10DM concurrently.
-Use more than one FX-10DM at the same time. For example, the configuration
FX-10DM + (FX
1N
1.5EEProm Backup Data
FX1S existing data will be kept for 5 minutes during power down before the data is lost.
The capacitor b acked memor y wi ll retai n programs for 10 days and th e capaci tor req uires 30
minutes to recharge upon powerup.
-422-BD + FX-10DM) is not allowed.
1-7
Page 20
FX1S Series Programmable ControllerIntroduction 1
1-8
Page 21
FX1S Series Programmable Controllers
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 22
FX1S Series Programmable Controllers
Page 23
FX1S Series Programmable ControllersTerminal layouts 2
S/S
X1
NX0X4X6
FX1S-20MR-ES/UL
X5X7
0VY0Y1Y2Y3
X3
X2
24V
COM0 COM1COM3 COM4COM2
L
X11 X13
X10 X12
Y5Y6Y7
Y4
S/SS/S
N
S/S
X2X4
FX1S-30MR-ES/UL
X3X5
0V
Y0Y1Y2Y4
X1
X0
24V
COM0 COM1
Y3Y5
COM2
L
X7X11X6X13 X15
X12X10X14 X16
X17
Y6
Y7Y11
Y10
Y14Y12
Y13
COM4
Y15
COM3
S/SX1
NX0X4
FX1S-10MR-ES/UL
X5
0V
Y0Y1Y2Y3
X3
X2
24V
COM0 COM1COM3COM2
L
S/SX1
NX0X4X6
FX1S-14MR-ES/UL
X5X7
0V
Y0Y1Y2Y4
X3
X2
24V
COM0 COM1
Y3Y5
COM2
L
2.Terminal layouts
The following selection of terminal layouts are taken from the FX1S product range.
Note: All layouts are diagr ammatic only and are intended to aid the creation of wiring diagrams.
2.1Relay Output Controllers
Figure 2.1: Terminal Layouts, Relay Outputs
2-1
Page 24
FX1S Series Programmable ControllersTerminal layouts 2
S/S
X1
NX0X4
FX1S-10MT-ESS/UL
X5
0V
Y0Y1Y2Y3
X3
X2
24+ +V0 +V1+V3+V2
L
S/S
X1
NX0X4X6
FX1S-14MT-ESS/UL
X5X7
0V
Y0Y1Y2Y4
X3
X2
24+
+V0+V1
Y3Y5
+V2
L
S/SS/S
N
S/S
X2X4
FX1S-30MT-ESS/UL
X3X5
V0
Y0Y1Y2Y4
X1
X0
24+ +V0 +V1Y3Y5+V2
L
X7X11X6X13 X15
X12X10X14 X16
X17
Y6
Y7Y11
Y10
Y14Y12
Y13+V4Y15
+V3
S/SX1
NX0X4X6
FX1S-20MT-ESS/UL
X5X7
0V
Y0Y1Y2Y3
X3
X2
24+ +V0 +V1+V3 +V4+V2
L
X11 X13
X10 X12
Y5Y6Y7
Y4
2.2Transistor Output Controllers
Figure 2.2: Terminal Layouts, Transistor Output
2-2
Page 25
FX1S Series Programmable Controllers
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 26
FX1S Series Programmable Controllers
Page 27
FX1S Series Programmable ControllersInstallation Notes 3
3.Installation Notes
The installation of FX1S products has been design ed to be safe and easy. When the products
associated with this manual are used as a system or individually, they must be installed in a
suitable enclosure. The enclosure should be selec ted and install ed in accordance to the local
and national standards.
3-1
Page 28
FX1S Series Programmable ControllersInstallation Notes 3
3.1Product Outline
Figure 3.1: Features of the FX1S PLC
Table 3.1 : Feature Table
1
Direct Mounting Holes (4.5 mm Diameter)
7
DIN Rail Mounting Clip
2
Input Terminals (24V DC)
3
Output Terminals
4
Input LED Status Indicators
5
Output LED Status Indicators
6
PLC Status Indicators(POWER, RUN, ERROR)
8
Top Cover
Optional Equipment port (Memory Cassette, FX1N-
9
232, 422, 485, 8AV, and CNV BDs, FX
10
Programming Port
Analog Trim Pots, D8 030 read f rom VR1, the top trim
11
pot. D8031 read from VR2, the bottom trim pot.
12
Run/Stop Switch
1N
-5DM
3-2
Page 29
FX1S Series Programmable ControllersInstallation Notes 3
3.2FX1S RUN/STOP Control
RUN or STOP of the FX1S can be controlled by:
The RUN/STOP switch mounted next to the programming port.
n
A standard input (X0 to X17) defined by the system parameters.
o
Remotely from a personal computer or other programming peripheral.
p
Note
:The FX
1S
RUN/STOP switch works in parallel with the RUN-input terminal. Please
refer to Table 3.2.
1S
During remote operation the FX
RUN/STOP status is determined by the most recently
operated control.
E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal
computer, the PLC can only be restarted with the RUN/STOP switch by first moving the
switch to STOP and then back to RUN.
Figure 3.2: RUN/STOP Input Wiring Diagram
Table3.2: Run Status Table
➁
RUN
n
RUN/STOP
SWITCH
99
X2S/S0V 24VX0X1
9
o
RUN INPUT
TERMINAL
9
FX1S MPU
STATUS
RUN
RUN
STOP
RUN
3-3
Page 30
FX1S Series Programmable ControllersInstallation Notes 3
3.3General Specifications
Table 3.3: General Specifications
ItemDescription
Operating Temperature0 to 55 °C (32 to 131 °F)
Storage Temperature-20 to 70 °C (-4 to 158 °F)
Operating Humidity35 to 85% Relative Humidity, No condensation
storage Humidity35 to 90% Relative Humidity, No condensation
Dielectric Withstand Voltage1500 V AC > 1 min , tested between all p oints, terminals and ground
Insulation Resistance5 MΩ > at 500 V DC, tested between power terminals and ground
GroundClass 3 (100 Ω or less)
Conforms to IEC 68-2-6; 10 - 57 Hz: 0. 075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to IEC 68-2-6; 10 - 57 Hz: 0. 035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
2
Conforms to IEC 68-2-27: 147m/s
3 times in each direction X, Y, and Z
Acceleration, Action Time: 11 ms
2
Acceleration
2
Acceleration
3-4
Page 31
FX1S Series Programmable ControllersInstallation Notes 3
3.4PLC Mounting Arrangements
To prevent a rise in temperature, mount the units to walls. Never mount them to the floor or
ceiling of an enclosure.
Caution
•Units should mot be installed in areas subject to the following conditions: excessive or
conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular
impact shocks or excessive vibration.
•Take special care not to allow debr is to fall inside the unit during installation e.g. cut
wires, shavings etc. Once installation is complete remove the protective paper band: to
prevent overheating.
Figure 3.3: PLC Mounting Diagram
A
FX
1S
CPU
A
A
> 50mm(1.97 inches)
AA
3-5
Page 32
FX1S Series Programmable ControllersInstallation Notes 3
3.5DIN Rail Mounting
Units can be snap mounted to 35mm DIN rail (DIN EN 50022). To release pull the spring
loaded clips away from the rail and slide the unit off and up.
3.6Termination of Screw Terminals
Cables term inating at a s crew termin al of an FX2N and FX0N product should be fitted with
insulated crimp ter minals, see example shown. Terminals screws should be tightened to
between 0.5 to 0.8 N‚m. Screw terminals must be secured to prevent a loose connection from
causing a malfunction.
Figure 3.4 : Terminal Crimp Diagram
Max.
6.2mm
0.24 in
Max.
6.2mm
0.24 in
To suit M3 (0.12in)
screw terminals
3-6
Page 33
FX1S Series Programmable Controllers
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 34
FX1S Series Programmable Controllers
Page 35
FX1S Series Programmable ControllersPower Supply 4
4.Power Supply
4.1Wiring Techniques
The wiring of FX1S products has been designed to be safe and easy. If during the installation of
these product or associated products concer n is felt, please contact a professional electrician
who is trained to the local and national standards applicable to the installation site.
4.2Wiring Cautions
• Do not run input signals in the same multicore cable as output signals or allow them to
share the same wire.
• Do not lay I/O signal cables next to power cables or allow them to share the same trunking
duct. Low voltage cables should be reliably separated or insulated with regard t o high voltage cabling.
•Where I/O signal lines are used over an extended distance consideration for voltage drop
and noise interference should be made.
4.3Power Supply
When wiring AC supplies the “Live” cable should be connected to the “L” terminal and the
“Neutral” cable should be connected to the “N” terminal. Do NOT connect the “Live” wire to the
“N” terminal, the user might receive a dangerous shock on powerup.
4-1
Page 36
FX1S Series Programmable ControllersPower Supply 4
4.4Power Supply Characteristics
Table 4.1 : Power Requirements
FX1S-10MFX1S-14MFX1S-20MFX1S-30M
P ower supply100 ~ 240V AC +10%, -15%, 50-60Hz
Max. allowable momentary
power failure period
Fuse (size) rating250V 1.0A 5φ×20mm (0.2×0.79 inc h es)
In-rush current
Power consumption *119W19W20W21W
*1 Includes the input current (5 or 7mA per point).
10ms; if less than 10ms, the PLC will continue operation.
If 10ms or more, the PLC will shut down
100V AC - Max. 15A for 5ms
200V AC - Max. 25A for 5ms
4-2
Page 37
FX1S Series Programmable ControllersPower Supply 4
Figure 4.1: Example Wiring
FX1S Series
AC/DC
Converter
24+
24-
u
L
v
24V
0V
P ower supply 100 ~ 240V AC +10% -15%
n
50 - 60 Hz
Circuit protector or Fuse
85-264V AC
50/60 Hz
t
N
n
➓
MC
MC
q
p
PL
r
MCMC
s
o
s
o
Emergency stop
p
Power supply switch
q
Power ON pilot indicator
r
P ower supply for loads
s
Grounding resistor 100Ω or less (class3)
t
Fuse
u
Main unit
v
Breaker
w
4-3
Page 38
FX1S Series Programmable ControllersPower Supply 4
4.5Earthing / Grounding
Use a cable at least 0.2mm2 (AWG24) to ground equipment. Ground resistance must be
less than 100Ω (class 3). Note that the ground cable must not be connected to the same
ground as the power circuits. Grounding is recommended but if a proper ground cannot be
provided the PC will still operate correctly without being grounded.
4-4
Page 39
FX1S Series Programmable Controllers
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 40
FX1S Series Programmable Controllers
Page 41
FX1S Series Programmable ControllersInputs 5
5.Inputs
5.124V DC Input Specifications
Table 5.1: FX1S Input Specifications
FX1S Main Unit
ÆÆÆÆ
X0
X7X10
Input voltage24V DC +/- 10%
Input current
Input switching
current
Response time10msec (default)
Variable response time
Circuit isolationPhotocoupler
Operation indicationLED is lit
OFF Æ ON>4.5mA>3.5mA
ON Æ OFF<1.5mA
24V DC,
7mA
0 - 15msec for X000-X017 via use
the FX
digital filter.
1S
ÆÆÆÆ
24V DC, 5mA
X17
5-1
Page 42
FX1S Series Programmable ControllersInputs 5
24V0VS/SX0X1X2
NPN
FX1S-**MT-ESS/UL
➊
➌
➍
➎
FX1S-Sink
5.1.1Typical wiring
Figure 5.1: Input Wiring
FX1S-Source
➋
PNP
24V0VS/SX0X1X2
➊
FX1S-**MT-ESS/UL
124V DC Service Supply
2PNP Sensor
3NPN Sensor
4Input Device Contact
5FX1S Controller Main Body
➍
➎
5-2
Page 43
FX1S Series Programmable ControllersInputs 5
5.1.2Input Circuit Connection
Figure 5.2: Input Circuit Diagrams (Source/Sink)
Source (-ve S/S)
Sink (+ve S/S)
24V
24V DC
X
S/S
0V
5.1.3Diodes and Inputs Connected in Series
Figure 5.3: Diode Connection Diagram
24V
X
S/S
0V
24V
24V DC
X
S/S
0V
Vdrop across the diode Max. 4V
No more than 2 LEDs should be connected in series.
5-3
Page 44
FX1S Series Programmable ControllersInputs 5
5.1.4Resistors and Inputs Connected in Parallel
1S
Parallel resistance Rp: FX
= 15kΩ. If resistance Rp is less than the stated value, then add the
Rb value using the Equation 1 calculation.
Alternatively; Current leakage: FX
1S
= 1.5mA. If the current leakage is greater than the stated
value, then add the Rb value using the equation 2 calculation.
2A/1 point, 8A/COM0.5A/1 point, 0.8A/COM
80VA, See table 6.2 for more
details
100W (1.17A/85V A C, 0.4A/
250V AC)
When supply voltage < 5V
DC allow at least 2mA flo w
10ms<0.2ms (100mA/24V DC); <5µs (Y0,Y1 only)
10ms<0.2ms (100mA/24V DC); <5µs (Y0,Y1 only)
By RelayPhotoCoupler
----------------0.1mA/30V DC
LED is lit when coil is energized
12W/24V DC
0.9W/24V DC
------------------
6-1
Page 48
FX1S Series Programmable ControllersOutputs 6
6.1Relay Output Example
Figure 6.1: Typical Relay Wiring Diagram
Do not use this terminal
nnnn
Fuse
oooo
Surge absorbing Diode.
pppp
External Mechanical
qqqq
Interlock
Emergency Stop
r
Noise suppressor 0.1µF
capacitor + 100-120
s
resistorContactor
Valve
t
➎
➒
➋
COM0
➌
COM1COM2
Y0Y1Y2Y3
MC2MC1
➐
➋
➍
MC1MC2
➎
➊
Y4Y5
➏
➑
➓
Incandescent Lamp
u
DC Power Supply
v
Ω
AC Power Supply
w
6-2
Page 49
FX1S Series Programmable ControllersOutputs 6
6.1.1Reliability Tests
The test results in Table 6.2 were gathered fro m a 1 sec ON/OFF t est cycle. Please note that
the over current induced by in-rush greatly reduces the relay contacts service life. The rated lif e
for an inductive AC load such as a contactor or solenoid valve is 500,000 operations at 20VA.
Table 6.2: Relay Life Cycle Data
Description20VA35VA80VA
Load capacity
Life of contact (cycles)3,000,0001,000,000200,000
Example load (Mitsubishi contactor)S-K10 ~ S-K95S-K100 ~ S-K150S-K180,S-K400
0.2A/100VAC
0.1A/200VAC
0.35A/100V AC
0.17A/240V AC
0.8A/100V AC
0.4A/240V AC
6.1.2Response Times
OFF times increase as the load current decreases.
For improved response times use a 'dummy' resistor, see Figure 6.2. If a response time of 0.2
msec or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal
line has a current greater than 60mA/24V DC.
Figure 6.2: Dummy load
10 to 100mA
+V
Y
Dummy loadLoad
5 to 24V
6-3
Page 50
FX1S Series Programmable ControllersOutputs 6
6.1.3Transistor Output Examples
Figure 6.3: Transistor Output Wiring Diagram
Do not use this terminal
nnnn
Emergency Stop
oooo
Fuse
pppp
External Mechanical
qqqq
Interlock
Output Terminal Y0
r
Output Terminal Y1
s
DC Power Supply
t
➐
➋
➍➏➎
+V0Y0Y1Y2Y3+V1+V2Y4Y5
MC1MC2
MC2MC1
➌
➌
➊➍
Figure 6.4: Japanese Model Transistor Output
➐
➋
COM0
➌
➌
➍➏➎
COM1COM2
Y0Y1Y2Y3
MC1MC2
MC2MC1
➊➍
Y4Y5
6-4
Page 51
FX1S Series Programmable ControllersOutputs 6
6.2Applying safe loads
Ensure all loads are applied to the same side of each PLC output, see previous figures.
Loads which should NEVER simultaneously operate (e.g. direction control of a motor),
because of a safety critical situation, should not rely on the PLC's sequencing alone.
Mechanical interlocks MUST be fitted to all safety critical circuits. (See preceding figure.)
6-5
Page 52
FX1S Series Programmable ControllersOutputs 6
6-6
Page 53
FX1S Series Programmable Controllers
1Introduction
2Terminal Layouts
3Installation Notes
4Power Supply
5Inputs
6Outputs
7Diagnostics
Page 54
FX1S Series Programmable Controllers
Page 55
FX1S Series Programmable ControllersDiagnostics 7
7.Diagnostics
7.1Preliminary Checks
POWER
RUN
ERROR
POWER
RUN
ERROR
POWER
RUN
ERROR
Check po wer supply, ground and I/O cables are wired correc tly.
Turn the power supply on. Check the power LED is lit. Down load a small
test progra m into the PLC. Verify the program to en sure it has been written
to the PLC correctly. Using the programming device forcibly turn ON/OFF
each output. Check t he output LEDs for operation.
Put the PLC into R UN. Chec k the R UN LED is lit. Chec k the pre viously down
loaded program works correc tly. Once all checks a re complete tak e the PLC
out of run and turn OFF the power supply.
During this testing stage take extreme care not to touch any live or hazardous parts.
7-1
Page 56
FX1S Series Programmable ControllersDiagnostics 7
PLCM/CPLCM/CPLCM/C
998
7.1.1ERROR LED ON (CPU ERROR)
POWER
RUN
ERROR
A
B
Remedy
Reset PLC.
Fault
ERROR
LED ON
Power
OFF ,ON
and trigger
Possible
results
RUN input.
Remedy
LED is lit
Power OFF
Discon-
nect earth/
ground terminal
Possible
results
LED is flashing
Power ON
Remedy
Possible program/scan time error.
Check D8012 for program scan time,
(units 0.2 msec must be less than 0.2
sec, i.e data value <2000).
Has the memory cassette been
LED OFF
installed or removed wh ile the units
has still been powered?
LED is lit
A
B
Check for programming error. Ensure the earth/
ground cable is correctly rewired.
Possible results
D8012 > D8000
7-2
Page 57
FX1S Series Programmable ControllersDiagnostics 7
7.2Common Errors
-Corroded contact points at some point in an I/O line.
-An I/O device has been used outside its specified operating range.
-An input signal occurs in a shorter time period that taken by one program scan.
7.3Maintenance
-Check interior temperature of the panel.
-Check panel air filters if fitted.
-Check for loosening of terminals or mounting facilities (due to vibration).
7-3
Page 58
FX1S Series Programmable ControllersDiagnostics 7
7.4Operation and Error Flags
M8004
(ref. 8004)
M8035
M8036
M8037
M8039
(ref. D8039)
Error occurance
(ON when M8060-7 are ON)
Forced RU N m ode
Forced RU N signal
Forced STOP signal
Constant scan mode
M8061
(ref. D8061)
M8063
(ref. D8063)
M8064
(ref. D8064)
M8065
(ref. D8065, D8069)
M8066
(ref. D8066, D8069)
M8067
(ref. D8067, D8069)
M8068
(ref. D8068)
PC hardware error
Parallel link error
Parameter error
Syntax error
Program (circuit) error
Program execution error
Execution error latch
7-4
Page 59
FX1S Series Programmable ControllersDiagnostics 7
7.5
(default 200msec)
Error Registers
D8000
D8001
D8002
D8003
D8004
D8007
Watchdog timer
PC version
22100 = FX
22 = FX1S, 100 = Version 1.00
Memory capacity
0002=2K steps
Memory type
02H=EEPROM protect switch OFF
0AH=EEPROM protect switch ON
10H=MPU memory
Error flag number
8060=M8060, ( 8060-8068)
Number of momentary power
failures - reset on full power OFF
Version 1.00
1S
7-5
Page 60
FX1S Series Programmable ControllersDiagnostics 7
D8061
D8063
D8064
D8065
D8066
D8067
D8068
D8069
Error code for PLC hardware error
Error code for parallel link fault
Parameter error code
Syntax error code
Program (circuit) error code
Program execut ion error code
Latched step
number of execution error
Step number of er rors associated
No error0000
Parity/overrun/framing error6201
Character error6202
Data sum check error6203
Data format error6204
Command error6205
D8063
Check both power and
communications connections
No error0000
Parity/overrun/framing error6301
Character error6302
Data sum ch ec k e rror6303
Data format error6304
Command error6305
Watchdog timer error6306
7-7
Page 62
FX1S Series Programmable ControllersDiagnostics 7
7.7Instruction List
Table 7.1: Numerically sorted
PROGRAM FLOW
000
010
TRANSFERS, COMP
+-×÷, LOGICS
020
030
SHIFT
DATA OPERATION 1
040
HIGH-SPEED
050
060
HANDY INSTR. 1
FX I/O DEVICES
070
080
FX SER DEVICES
POSITIONING
150
REAL TIME CLOCK
160
220
230
IN-LINE COMPARE
240
0
CJ
CMP
ADD
ZRST
REF
IST
RS
TCMP
≥
LD
OR=
1
CALL
ZCP
SUB
DECO
PRUN
TZCP
OR>
2
SRET
MOV
MUL
ENCO
MTR
ABSD
DSW
ASCI
TADD
AND=
OR<
3
IRET
DIV
HSCS
INCD
HEX
TSUB
AND>
4
EI
INC
SFTR
HSCR
SEGL
CCD
LD=
AND<
≠
OR
5
DI
BMOV
DEC
SFTL
VRRD
ABS
LD>
≤
OR
6
FEND
WAND
SPD
ALT
VRSC
ZRN
TRD
LD<
≠
AND
≥
OR
7
WDT
WOR
PLSY
RAMP
PLSV
TWR
≤
AND
8
FOR
BCD
WXOR
SFWR
PWM
PID
DRVI
≠
LD
≥
AND
9
NEXT
BIN
SFRD
PLSR
DRVA
HOUR
≤
LD
7-8
Page 63
FX1S Series Programmable ControllersDiagnostics 7
Table: 7.2 Alphabetically sorted
Symbol
ABS
ABSD
ADD
A
ALT
AND
ASCI
BCD
BIN
B
BMOV
CALL
CCD
C
CJ
CMP
FNC No.
…
155
062
020
066
232-238
082
018
019
015
001
084
000
010
D P
Symbol FNC No. D P
DEC
DECO
DI
D
DIV
DRVA
DRVI
DSW
EI004
E
ENCO042
FEND006
F
FOR008
025
041
005
023
159
158
072
Symbol FNC No. D P
HEX083
H
HSCR054
HSCS053
INC
INCD
INT
I
IRET
IST
…
L
LD
MOV
MTR
M
MUL
NEXT009
N
OR
…
O
024
063
129
003
060
224-230
012
052
022
240-246
7-9
Page 64
FX1S Series Programmable ControllersDiagnostics 7
Symbol
FNC No.
PID
PLSR
PLSV
P
PLSY
PRUN
PWM
RAMP
REF
R
RS080
SEGL074
SFRD039
S
SFTL
SFTR
088
059
157
057
081
058
067
035
034
D P
SymbolFNC No . D P
SFWR
SIN
038
130
SPD056
S
SQR
SRET
048
002
SUB021
TADD
TCMP
162
160
TRD166
T
TSUB163
TWR
TZCP
167
161
Symbol FNC No. D P
VRRD
085
V
VRSC
WAND
WDT
W
WOR
WXOR
ZCP
ZRN
Z
ZRST
086
026
007
027
028
011
156
040
7-10
Page 65
FX1S Series Programmable ControllersDiagnostics 7
7.8Device List
Device TypeDescription
2K steps by FX
Program capacity
Input (X) relay X0 - X17 (16 pts)
Output (Y) relay Y0 - Y15 (14 pts)
General Auxiliary Relays M0-M383 (384 pts)
Auxiliary relay
(512 pnts + 256 pts)
State relay
(128 pts)
Timer
(64 pts)
Latched RelaysM384-M511 (128 pts)
Special functionM8000-M8255 (256 pts)
Initial State RelayS0-S9 (10 pts), same as latched state relay
Latched State RelayS10-S127 (118 pts)
100 msecT0-T62 (63 pts)
10 msec
1 msecT63 (1 pt)
or
2K steps by FX1N-EEPROM-8L
If M8028 is On, T32 - T62 are 10ms timers
internal EEPROM
1S
(X + Y) ≤ 30 pts Max.
(31 pts)
7-11
Page 66
FX1S Series Programmable ControllersDiagnostics 7
Device TypeDescription
General CounterC0-C15 (16 pts)
Counter
(256 pts)
Latched CounterC16-C31 (16 pts)
High Speed CounterC235-C255
General Use RegisterD0-D127 (128 pts)
Latched RegisterD128-D255 (128 pts)
K-32,768 to 32,767-2,147,483,648 to 2,147,483,647
H0 to FFFFH0 to FFFFFFFFH
Float-
0, ±1.175 × 10
-38
to ±3.403 × 10
38
7-12
Page 67
FX1S Series Programmable Controllers
Under no circumstances will MITSUBISHI ELECTRIC be liable or responsible for any consequential damage that
may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. MITSUBISHI ELECTRIC will acce pt no respon sibility for actual use of th e prod uct ba sed o n thes e
illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability
for your specific application.
Page 68
HARDWARE MANUAL
FX1S SERIES PROGRAMMABLE CONTROLLERS
HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX: J24532 CABLE MELCO TOKYO
HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN
JY992D83901B
(MEE0004)
Effective Apr. 2000
Specification are subject
to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.