Mitsubishi FX1N Series, FX1N-60MR, FX1N-40MR, FX1N-40MT, FX1N-60MT Hardware Manual

...
FX1N JAPANESE SPECIFICATION UNITS
HARDWARE MANU AL
JY997D07901A
This manual conta ins safety infor mation, assoc iated manua l listing s, specific ations and ter minal layouts and wiring for Japanese specification FX
PLC main units. For complete operation , mounting and programming ins truction s please refer to th e FX1N HANDY MANUAL (JY992D87501 JAPANESE ONLY) and PROGRAMMING MANUAL. These manuals should be read and understood before attempting to install or use the unit.
Guidelines for the Safety of the User and Protection of the FX1N PLC
This manual has been wr itten to be used by trained and competent personnel. The definition of such a person or persons is as follows:
a) Any engineer who i s responsible fo r the planni ng, design and construction of automatic equipm ent using the
product associated with this manual, should be of a competent nature, tr ained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
b) Any commissioning or service engi neer must be of a compete nt nature, trained an d qualified to the local and
national standards. These engineers should also be trained in the use and maintenance of the complete product. This includes being completely familiar with all associa ted documentation for the said product. All maintenance should be carried out in accordance with established safety practices
c) All operators of th e completed equipment should be trai ned to use that product in a safe and co-ordin ated
manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected to the actual operation of the completed equipment
Note:
The term ‘completed equipment’ refers to a third par ty constructed device which contains or us es the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger could
POSSIBLY
cause physical and property damage.
2) Indicates a point of further interest or further explanation.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubish i Electr ic will accep t no respo nsibility for actual us e of the productbased on these illustrative exam ples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific applic ation.
Further Information Manual Lists
The following manuals are recomm ende d as essen tial reference m ater ial for the corr ect operat ion of an FX
1N
series Programmable Controller
Manual name Manual No. Description
FX1N HANDY MA NUAL
JY992D87501
(JAPANESE ONLY)
Describes contents related to hardware of world specification FX
series PLCs such as
specifications, wiring and installation.
FX1S, FX1N, FX2N, FX
2NC
PROGRAMMING MANUAL
JY992D62001
(JAPANESE ONLY)
Programming manual for FX
1S
, FX1N, FX2N and
FX
2NC
series Programmable Logic Controllers
1. Introduction
This manual covers basic hardware details for th e FX1N Series Programmable Logic Controller.
1.1 World Specification
MODEL
INPUT OUTPUT
POWER SUPPLY
QTY TYPE QTY TYPE
FX1N-24MR
14
(16)
24V DC
SINK
10
(16)
Relay
100-240
VAC
+10%
-15%
50/60Hz
FX
-24MT
Transistor
FX
-40MR
24 16
Relay
FX
-40MT
Transistor
FX1N-60MR
36
(40)
24
Relay
FX
-60MT
Transistor
FX1N-24MR-D
14
(16)
24V DC
SINK
10
(16)
Relay
12V DC
-15% to
24V DC
+20%
FX
-24MT-D
Transistor
FX1N-40MR-D
24 16
Relay
FX1N-40MT-D
Transistor
FX
-60MR-D
36
(40)
24
Relay
FX
-60MT-D
Transistor
Input - Sink/Source
World Spec models: SINK/SOURCE. Japanese models: ALWAYS SINK
Output - Transisto r
World Spec models: ALWAYS SOURCE . Japanese models: ALWAYS SINK
2. Specifications
The installation of FX1N products has been designed to be safe and easy. When t he products assoc iated with this manual are used as a system or individually, they must be installed in a suitable enclosure. The enclosure should be selected and installed in accordance to the local and national standards.
Item Description
Operating Temperature 0 to 55 °C (32 to 131 °F) Storage Temperature -20 to 70 °C (-4 to 158 °F) Operating Humidity 35 to 85% Relative Humidity, No condensation storage Humidity 35 to 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.75 mm Half Amplitude 57 - 150 Hz: 9.8 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Vibration Resistance
- DIN rail Mounting
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude 57 -150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock Resistance
Conforms to IEC 68-2-27: 147m/s2 Acceleration, Action Time: 11ms
3 times in eac h direction X, Y, and Z Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise s imulator Dielectric Withstand
Voltage
AC unit = 1500 V AC > 1 min, tested between all points, terminals and ground
DC unit = 500 V AC > 1 min, tested between all points, terminals and ground. Insulation Resistance 5 MΩ > at 500 V DC, tested between all points, terminals and ground
Grounding
Grounding resistance 100 or less
Use a cable of at least 0.2mm
2
(AWG24) to ground equipment. Note that ground cable must not be connected to the s ame ground as power circuits. Grounding is recommended but if a proper ground cann ot be provided, the PLC will operate correctly without.
Item Description
Industrial automation
Elincom
Group
EuropeanUnion: www.elinco.eu Russia: www.elinc.ru
1N
PLC
1N
HANDY
1. Introduction
This manual covers basic hardware details for th e FX1N Series Programmable Logic Controller.
INPUT OUTPUT
QTY TYPE QTY TYPE
14
(16)
24 16
36
(40)
14
(16)
24 16
36
(40)
FX FX FX FX FX FX FX FX FX FX FX FX
MODEL
-24MR
-24MT
-40MR
-40MT
-60MR
-60MT
-24MR-D
-24MT-D
-40MR-D
-40MT-D
-60MR-D
-60MT-D
1.1 World Specification
Input - Sink/Source Output - Transisto r
World Spec models: SINK/SOURCE. Japanese models: ALWAYS SINK World Spec models: ALWAYS SOURCE . Japanese models: ALWAYS SINK
24V DC
SINK
24V DC
SINK
10
(16)
24
10
(16)
24
Relay
Transistor
Relay
Transistor
Relay
Transistor
Relay
Transistor
Relay
Transistor
Relay
Transistor
POWER SUPPLY
100-240
VAC
+10%
-15%
50/60Hz
12V DC
-15% to
24V DC
+20%
DIMENSIONS
mm (inches)
90
(3.6)
90
130
(3.5)
(5.2)
175
(7.0)
90
(3.6)
90
130
(3.5)
(5.2)
175
(7.0)
75
(3.0)
75
(3.0)
WEIGHT
kg (lbs)
0.45
(0.99)
0.65
(1.44)
0.80
(1.77)
0.45
(0.99)
0.65
(1.44)
0.80
(1.77)
2.1 Power Specifications
AC Powered Units FX
Power Supply 100-240V AC +10% -15%, 50-60 Hz Max. allowable momentary power failure 10ms; If less than 10ms, PLC continues operation Fuse (size) rating 250V 1A 250V 3.15A (3A)
In-rush current Power Consumption *1 30W 32W 35W
*1 Includes the input current (7 or 5 mA per point)
DC Powered Units FX
Power S upply 24V DC + 20% - 12V DC -15% (28.8 ~ 10.2 V DC) Max. allowable momentary power failure 5ms; If less than 5ms, PLC continues operation Fuse (size) rating 125V 3.15A (3A)
In-rush current
Power Consumption
2.2 Input Specifications
Input voltage 24V DC Input current 24V DC, 7mA 24V DC, 5mA 24V DC, 5mA
!
Input switching current
Response time 10ms Variable response time 0-15ms --- Circuit isolation Photocoupler Operation indication LED is lit
OFF ON ! OFF <1.5mA
2. Specifications
The installation of FX1N products has been designed to be safe and easy. When t he products assoc iated with this manual are used as a system or individually, they must be installed in a suitable enclosure. The enclosure should be selected and installed in accordance to the local and national standards.
Item Description
Operating Temperature 0 to 55 °C (32 to 131 °F) Storage Temperature -20 to 70 °C (-4 to 158 °F) Operating Humidity 35 to 85% Relative Humidity, No condensation storage Humidity 35 to 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
Item Description
Vibration Resistance
- DIN rail Mounting
Shock Resistance
1S
, FX1N, FX2N and
Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise s imulator Dielectric Withstand
Voltage Insulation Resistance 5 MΩ > at 500 V DC, tested between all points, terminals and ground
Grounding
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.75 mm Half Amplitude 57 - 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude 57 -150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction) Conforms to IEC 68-2-27: 147m/s
2
Acceleration, Action Time: 11ms
3 times in eac h direction X, Y, and Z
AC unit = 1500 V AC > 1 min, tested between all points, terminals and ground DC unit = 500 V AC > 1 min, tested between all points, terminals and ground.
Grounding resistance 100 Ω or less Use a cable of at least 0.2mm
2
(AWG24) to ground equipment. Note that ground cable must not be connected to the s ame ground as power circuits. Grounding is recommended but if a proper ground cann ot be provided, the PLC will operate correctly without.
2.3 Output Specifica tions
Description Relay Output Transistor Output
Switched voltages (resistive load) Rated current / N points
(resistive load) Max. Inductive load 80VA, 120/240V AC 12W/24V DC
Max. lamp l oad (tungsten load)
Minimum load
OFF
ON
ON
!
OFF
!
Response time (approx.)
Circuit isolation By Relay PhotoCoupler Open circuit current leakage ---------------- 0.1mA/30V DC Operation indication LED is lit when coil is energized
100W (1.17A/85V AC, 0.4A/
3. Installation Notes
The installation of FX1N products has been designed to be safe and easy. If during the installation of these products or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.
1N
FX
Main PLC units can be either directly or DIN rail mou nted. For details of either met hod, and
installation guidelines please refer to the FX
Mounting Cautions
• Units should not be installed in areas subject to the following conditions: excessive or con- ductive dust, corrosive or flammable gas, moisture or rain, exc essive heat, regular impact shocks or excessive vibrat ion.
• Take special care not to allow debris to fall inside the unit during installation e.g. cut wires, shavings etc. Once installation is complete remove the protective paper band, to prevent overheating.
DIMENSIONS
mm (inches)
WEIGHT
kg (lbs)
90
(3.6)
90
(3.5)
75
(3.0)
0.45
(0.99)
130
(5.2)
0.65
(1.44)
175
(7.0)
0.80
(1.77)
90
(3.6)
90
(3.5)
75
(3.0)
0.45
(0.99)
130
(5.2)
0.65
(1.44)
175
(7.0)
0.80
(1.77)
Acceleration
Acceleration
2.1 Power Specifications
*1 Includes the input current (7 or 5 mA per point)
2.2 Input Specifications
AC Powered Units FX1N-24M FX1N-40M FX1N-60M
Power Supply 100-240V AC +10% -15%, 50-60 Hz Max. allowable momentary power failure 10ms; If less than 10ms, PLC continues operation Fuse (size) rating 250V 1A 250V 3.15A (3A)
In-rush current
100V AC - Max. 30A for 5ms 200V AC - Max. 50A for 5ms
Power Consumption *1 30W 32W 35W
DC Powered Units FX1N-24M FX1N-40M FX1N-60M
Power S upply 24V DC + 20% - 12V DC -15% (28.8 ~ 10.2 V DC) Max. allowable momentary power failure 5ms; If less than 5ms, PLC continues operation Fuse (size) rating 125V 3.15A (3A)
In-rush current
24V DC - Max. 25A for 1ms
12V DC - Max. 22A for 0.3ms
Power Consumption
15W 18W 20W
FX1N Main unit
FX0N, FX2N Extension
block
X0
!!!!
X7 X10
!!!!
Input voltage 24V DC ±10% Input current 24V DC, 7mA 24V DC, 5mA 24V DC, 5mA
Input switching current
OFF ! ON >4.5mA >3.5mA >3.5mA
ON ! OFF <1.5mA Response time 10ms Variable response time 0-15ms --­Circuit isolation Photocoupler Operation indication LED is lit
2.3 Output Specifica tions
Description Relay Output Transistor Output
Switched voltages (resistive load)
240V AC, ≤ 30V DC 5-30V DC
Rated current / N points (resistive load)
2A/1 point, 8A/COM 0.5A/1 point, 0.8A/COM Max. Inductive load 80VA, 120/240V AC 12W/24V DC Max. lamp l oad (tungsten load)
100W (1.17A/85V AC, 0.4A/
250V AC)
1.5W/24V DC
Minimum load
When supply voltage < 5V
DC allow at least 2mA flow
------------------
Response time (approx.)
OFF
!
ON
10ms < 0.2ms; < 5µs (Y0,Y1 only)
ON
!
OFF
10ms < 0.2ms (I > 0.2A); <5µs (Y0,Y1 only) Circuit isolation By Relay PhotoCoupler Open circuit current leakage ---------------- 0.1mA/30V DC Operation indication LED is lit when coil is energized
3. Installation Notes
The installation of FX1N products has been designed to be safe and easy. If during the installation of these products or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.
FX
1N
Main PLC units can be either directly or DIN rail mou nted. For details of either met hod, and
installation guidelines please refer to the FX
1N
HANDY MANUAL JY992D87501 (JAPANESE ONLY).
Mounting Cautions
• Units should not be installed in areas subject to the following conditions: excessive or con­ductive dust, corrosive or flammable gas, moisture or rain, exc essive heat, regular impact shocks or excessive vibrat ion.
• Take special care not to allow debris to fall inside the unit during installation e.g. cut wires, shavings etc. Once installation is complete remove the protective paper band, to prevent overheating.
Loading...