Mitsubishi FR-EPN Instruction Manual

MITSUBISHI INVERTER Instruction Manual
FR-EPN
Communications
Option Unit
DeviceNet is a registered trademark of Open DeviceNet Vendor Association (ODVA). DeviceNetManager is a trademark of Allen-Bradley Company, Inc.
iii
Warning symbols
For you own safety, please pay special attention to instructions containing the following symbol:
This warning symbol indicates the presence of dangerous voltage. It informs you of high volta ge conditions, situation and locations that may cause death or serious injury if you do not follow precautions.
NOTES
inform you of situations or conditions which will damage machinery or cause additional motor­operation downtime if you do not take suggested steps to correct or address such situations or conditions.
iv
Thank you for choosing this option unit for the Mitsubishi FREQROL transistorized frequency inverters. Please read this manual carefully before using.
DeviceNet Communications Option Unit (FR-EPN) This option allows the inverter to be connected to a network adhering to the
DeviceNet communications protocol. Some important features are highlighted belo w.
Data rates of 125K baud, 250K baud, and 500K baud are selectable.
Up to 64 stations supported on a single network.
Ability to add or remove stations without disrupting network operation.
Network access to all inverter parameters, Start/Stop commands, and
monitor data.
v
Table of Contents
1. STRUCTURE 1
2. INSTALLATION 2
2.1. PRE-I
NSTALLATION CHECKS
2
2.2. I
NSTALLATION PROCEDURE
2
2.3. C
ONNECTION TO NETWORK
7
2.4. LED S
TATUS INDICATOR
7
3. GETTING STARTED 10
3.1. B
AUD RATE
10
3.2. N
ET MODE AND PARAMETER SETUP
10
3.3. C
ONNECTION AND DISCONNECTION
11
4. OPERATION 12
4.1. O
PERATION MODES
12
4.2. O
PERATION MODE SELECTION
12
4.3. F
UNCTIONS AVAILABLE IN OPERATION MODES
13
4.4. I
NPUT FROM DEVICENET TO INVERTER
13
4.5. O
UTPUT FROM INVERTER TO DEVICENET
14
4.6. O
PERATION ON ALARM OCCURRENCE
15
4.7. I
NVERTER RESET
16
5. FR-EPN SPECIFIC PARAMETERS 17
5.1. PR.118 17
5.2. O
THER OPTION-SPECIFIC PARAMETERS
18
vi
6. OBJECT MAP 20
6.1. I
DENTITY OBJECT
- C
LASS 0X
01 20
6.2. D
EVICENET OBJECT
- C
LASS 0X
03 21
6.3. I/O A
SSEMBLIES OBJECT CLASS
04 21
6.4. D
EVICENET CONNECTION OBJECT CLASS 0X
05 22
6.5. M
OTOR DATA OBJECT
- C
LASS 0X
28 25
6.6. C
ONTROL SUPERVISOR
- C
LASS 0X
29 26
6.7. AC D
RIVE CLASS 0X
2A 27
6.8. A200E E
XTENDED CLASS 0X
66 31
7. ELECTRONIC DATA SHEET 36
8. PARAMETERS 37
9. SPECIFICATIONS 48
STRUCTURE
- 1 -
1. STRUCTURE
FR-EPN
Node Address
SW2
x1
SW1
x10
MNS
193 mm.
44 mm.
V+ CAN+ SHLD
CAN-
V-
Connector
DeviceNet Connector
Station
Number
Switches
Status LED
Mounting
Hole
(2 places)
25 mm.
v
Front View Right Side View
INSTALLATION
- 2 -
2. INSTALLATION
Remove the inverter cover and install the option unit using the following procedure:
2.1. Pre-Installation Checks
(1) Check the inverter type. This option unit may only be used with the FREQROL-A100E and A200E
series inverters and must not be used with any other series (e. g. A100, A200, Z and F series). These models have a different option connector to prevent connecting by mistake; however, if the user forces the connector, the inverter may be damaged.
(2) Make sure that the inverter input power is off. The inverter may be damaged if the option unit is installed with the input
power on. The inverter executes an initialization procedure at power on that includes checking the option port. Adding the option later causes a hardware conflict which may damage the inverter or option unit and result in the alarm “E. CPU”.
(3) Ensure that the following accessories are supplied with the option unit:
Instruction Manual
Mounting Screws M3 x 14
2.2. Installation Procedure
(1) Snugly insert the connector of the option unit into the connector of the
inverter.
(2) Securely fix the option unit to the inverter at the top and bottom with the
mounting screws. If the screw holes in the option unit do not line up with the inverter mounting holes, check that the connectors have been fitted correctly.
- 3 -
Warning! Hazardous voltage present. Always isolate the power from the inverter, and wait 5 minutes to ensure the charge lamp has gone out before inserting or removing this option unit, or touching the terminals.
INSTALLATION
- 4 -
(3) Make a drop cable out of DeviceNet thin cable long enough to extend
from the inverter to the network trunk cable. Remember that the maximum length of this cable by the DeviceNet standard is 10 feet. On one end of the cable, install a connector compatible with the trunk cable and leave free wires on the other end. See figures below.
To FR-EPN
To Network Trunk
Cable
DeviceNet thin cable
DeviceNet Drop Cable with
Sealed Connector
1.5 in.
0.25 in.
Signal Wire
Signal Color
+V Red CAN + White Shield Orange CAN - Blue
-V Black
- 5 -
IBM Compatible
Stub containing
terminating
resistor
Trunk Cable
Drop
Cable
(4) Strip the insulation and shielding on the free wire end of the drop cable
back about 1.5 inches to expose the four colored signal wires and the silver shield wire. Strip the insulation on the signal wires back about 1/4 inch and tin the leads with solder. Tin the end of the shield wire also to prevent it from fraying. Some pre-made cables have this step already completed.
(5) Route the cable neatly through the wiring space along with any other
wires connected to inverter terminals so that when the front cover is reinstalled, the cables to the inverter control circuit terminals and option terminals are not caught between the inverter and inverter cover.
(6) Install the signal wires into the DeviceNet terminal block paying close
attention to match the colors of the wires with the colored label on the cover. Insertion of a screwdriver into the upper holes of the terminal block opens the clamps in the lower holes to allow wire insertion. A flathead screwdriver of 3 mm maximum width works best. Removal of the screwdriver then closes the clamps on the wire. These clamps grip the wire very tightly and the user should not be able to pull the wires back out if they are installed correctly .
INSTALLATION
- 6 -
Note:
The correct method for opening the clamps on the DeviceNet terminal block is simply to insert the screwdriver straight into the unlocking hole. It does not involve inserting the screwdriver and then using a lever action to open the clamps. The increase in screwdriver thickness further up the shaft opens the clamps as the screwdriver is inserted. Do not attempt with an improperly sized screwdriver. See figure below.
FR-EPN
Node Address
SW2
x1
SW1
x10
V+
CAN+
SHLD
CAN-
V-
RED WHITE GREY
BLUE
BLACK
DeviceNet
Cable
Wire Color
Wire terminal
Actuator
Insert driver into Actuator
to open Wire terminal
- 7 -
2.3. Connection To Network
(1) Upon completion of the installation procedure, the inverter should be at
rest with the power off. The option unit is mounted in the inverter with the drop cable connected to the terminal block, but unconnected to the network trunk cable. Set the node address on the two switches to a number between 0 and 63. SW1 is the tens digit and SW2 is the ones digit. Ensure that the number chosen is not already being used by another station on the network including a master station. Any number out of the range of 0 to 63 is changed to address 63 by the option unit software.
Note:
The state of the Node Address switches are sampled once at power on. Changing the Node Address later on will have no effect and the software will keep the number read at power on. Turn power off, readjust the switches, and turn power back on to change the node address.
(2) It is now safe to apply power to the inverter and run it in PU or external
mode provided that any external inverter control cables not associated with DeviceNet are installed correctly. If the trunk connector is a DeviceNet sanctioned pluggable or sealed connector, the connection to the active network can be made at any time whether inverter power is on or off. The option unit automatically detects when the connection is made. If connecting to the network with free wires, power to the network and inverter should be shut off as a safety measure in case two or more signal wires are accidentally shorted together.
2.4. LED Status Indicator
(1) After connecting the drop cable to the trunk cable of the active network,
note the condition of the LED labeled MNS on the cover. The option unit uses the Combined Module/Network Status LED scheme proposed in the DeviceNet communications standard. The possible states of this LED are as follows:
INSTALLATION
- 8 -
State of System LED
Condition
Notes
Inverter power off Network Power on
Off Turn inverter power on. Option unit
will then complete duplicate station
number test Network and inverter power on. Connection not yet established by host
Flashing
Green
The option unit has powered up
successfully and determined that its
station number does not conflict
with other stations. However, a host
has not yet established a
communication link. Network and inverter
power on. Connection established by host
Green A master device on the network has
designated the option unit for
communication. LED holds this
state during communication also. Connection Time-Out Flashing
Red
Master designated option unit for
communication (LED Green state),
but then sent no messages within
the time limit set in the expected
packet rate. Check to see that host
station has not been disconnec t ed
from the network. Critical Link failure Red Failed communication device.
Duplicate station number
Network power off.
Cable from option unit to
network not connected or severed.
Option unit is only node on
network.
Network damaged.
Must cycle power to recover
from this fault
Note:
When using complex software in the master, the rate of connections and disconnections may be too fast for the user to follow the network status in detail by simply watching the LED.
- 9 -
(2) Match the condition of the LED with the table above. Most likely, it will
be flashing red or green depending on the software used in the master station. Once a flashing green LED is achieved, the inverter is ready to connect to its host and begin motor control operations through the network.
(3) When inverter power is turned on with the option unit installed, the
option performs a diagnostic self test that can be viewed on the MNS LED. This test is performed even if the option unit is not connected to an active network. When power is turned on, the LED flashes green, then red and finally turns off. The option unit then attempts its duplicate station number test and will start flashing green within a few seconds if successful. If unsuccessful, the LED will go solid red.
(4) At this point, your DeviceNet option unit should be installed and running
properly on your DeviceNet network. Replace the front cover on the inverter paying attention not to cause excess strain on the internal wiring. Your DeviceNet option is now installed. Please read through the rest of this manual for information on the advanced features and detailed operation of this option.
GETTING STARTED
- 10 -
3. GETTING STARTED
3.1. Baud Rate
The baud rate of the FR-EPN is set by the Baud Rate attribute of the DeviceNet class, instance 1 (see section 6.2.3 Class 0x03 Instance Attributes - Instance 1). This setting is also available in Pr.118 (see section
5.1 Pr.118). However, the best way to set it is using a configuration program such as DeviceNetManager software.
To do this, the drive being configured should be set up as the only node on the network aside from the master computer running DeviceNetManager. Performing a parameter all-clear on the drive and cycling power will reset the baud rate to 125 kbps. At this point, DeviceNetManager can be used to configure the baud rate to any of the three possible speeds.
To change the speed manually via the parameter unit, refer to the description of Pr.118.
3.2. Net Mode and Parameter Setup
(1) The inverter must be in Net Mode for motor control operations through
the network. Drive mode is controlled automatically by the FR-EPN option card.
The FR-EPN will attempt to set the drive to Net Mode whenever a DeviceNet connection is made. It will set the drive back to external mode whenever all connections are released. If the drive is running at these times, then the drive will not be set to Net mode, and control cannot be performed via DeviceNet. Monitoring and reading, however, can be performed regardless of the drive mode.
(2) Parameter 81, Motor Pole Count, defaults to four internally even though
9999 is displayed in the parameter unit. This parameter can be modified via the network to control motors other than four pole motors. An incorrect value for parameter 81 results in an incorrect motor speed.
- 11 -
3.3. Connection and Disconnection
(1) The FR-EPN option unit is considered a slave device in the DeviceNet
communications standard. This means that it cannot send messages out on its own and dictate the operations of other devices on the network. A master device establishes a connection to the option unit, sends commands, requests for information, etc., and finally disconnects when communication is completed. The purpose of connection and disconnection is to prevent two master devices from sending motor control commands to the same motor at the same time. It is possible for one master to control the motor while another reads monitor data and parameters.
(2) The option unit operates somewhat independently of the inverter in that
a master may connect or disconnect while the inverter is in PU mode. However, motor control commands from the network will not be recognized unless the connection is made while the inverter is in external mode.
(3) When the master device disconnects from the option unit or the option
unit loses connection due to some fault such as a network power failure, the inverter continues with the last command received until the timeout value is reached. This is set in the expected packet rate of the DeviceNet connection object. For example, the master might send a command to start forward at 60 Hz and then disconnect. The MNS LED will be green during communication and switch to flashing green upon disconnection. The motor will run at 60 Hz until the timeout occurs or the master establishes a new connection and sends different commands.