Thank you for choosing this Mitsubishi Inverter plug-in option. This Instruction Manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum. Please forward this manual to the end user.
This section is specifically about
safety matters
Do not attempt to install, operate, maintain or inspect this product until you have read through this Instruction Manual and appended documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Incorrect handling may cause
WARNING
CAUTION
The level may even lead to a serious consequence according to conditions. Both instruction levels must be followed because these are important to personal safety.
CAUTION
hazardous conditions, resulting in death or severe injury.
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.

SAFETY INSTRUCTIONS

1. Electric Shock Prevention
WARNING
While power is ON or when the inverter is running, do not
open the front cover. You may get an electric shock.
Do not run the inverter with the front cover or wiring cover
removed. Otherwise, you may access the exposed high­voltage terminals and charging part and get an electric shock.
Even if power is OFF, do not remove the front cover except
for wiring or periodic inspection. You may accidentally touch the charged inverter circuits and get an electric shock.
Before wiring or inspection, power must be switched OFF. To
confirm that, LED indication of the operation panel must be checked. (It must be OFF.) Any person who is involved in wiring or inspection shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous.
Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work.
The plug-in option must be installed before wiring. Otherwise,
you may get an electric shock or be injured.
Do not touch the plug-in option or handle the cables with wet
hands. Otherwise you may get an electric shock.
Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise you may get an electric shock.
A-1
2. Injury Prevention
3) Usage
CAUTION
The voltage applied to each terminal must be the ones
specified in the Instruction Manual. Otherwise burst, damage, etc. may occur.
The cables must be connected to the correct terminals.
Otherwise burst, damage, etc. may occur.
Polarity must be correct. Otherwise burst, damage, etc. may
occur.
While power is ON or for some time after power-OFF, do not
touch the inverter as they will be extremely hot. Doing so can cause burns.
3. Additional Instructions
Also the following points must be noted to prevent an accidental failure, injury, electric shock, etc.
1) Transportation and mounting
CAUTION
Do not install or operate the plug-in option if it is damaged or
has parts missing.
Do not stand or rest heavy objects on the product.
The mounting orientation must be correct.
Foreign conductive objects must be prevented from entering
the inverter. That includes screws and metal fragments or other flammable substances such as oil.
2) Trial run
CAUTION
Before starting operation, each parameter must be confirmed
and adjusted. A failure to do so may cause some machines to make unexpected motions.
WARNING
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the inverter.
CAUTION
When parameter clear or all parameter clear is performed, the required parameters must be set again before starting operations because all parameters return to the initial value.
Static electricity in your body must be discharged before you
touch the product. Otherwise the product may be damaged.
4) Maintenance, inspection and parts replacement
CAUTION
Do not test the equipment with a megger (measure insulation
resistance).
5) Disposal
CAUTION
This inverter plug-in option must be treated as industrial
waste.
6) General instruction
Many of the diagrams and drawings in this Instruction Manual show the inverter without a cover or partially open for explanation. Never operate the inverter in this manner. The cover must be reinstalled and Instruction manual of the inverter must be followed when operating the inverter.
A-2
— CONTENTS —
1 PRE-OPERATION INSTRUCTIONS 1
1.1 Inverter Model ....................................................................................................................................1
1.2 Unpacking and Product Confirmation .............................................................................................2
1.2.1 Product confirmation.......................................................................................................................................2
1.3 Parts ....................................................................................................................................................3
1.4 Specifications.....................................................................................................................................4
2 INSTALLATION AND WIRING 5
2.1 Pre-Installation Instructions .............................................................................................................5
2.2 Installation Procedure .......................................................................................................................6
2.3 Wiring..................................................................................................................................................8
3 PARAMETER LIST 11
4 HIGH-SPEED ANALOG OUTPUT 12
4.1 Wiring Example ................................................................................................................................12
4.2 Terminals ..........................................................................................................................................13
4.3 Calibration procedure......................................................................................................................14
4.3.1 Calibration of voltmeter.................................................................................................................................14
4.3.2 Monitor setting..............................................................................................................................................17
4.3.3 Scale setting.................................................................................................................................................21
4.3.4 High-speed analog output filter setting.........................................................................................................21
4.4 Instructions ......................................................................................................................................22
I
5 DIGITAL OUTPUT 23
5.1 Terminals ..........................................................................................................................................23
5.2 Output Signal List ............................................................................................................................24
II

1 PRE-OPERATION INSTRUCTIONS

1.1 Inverter Model

The inverter model numbers of 55K and 75K stated in this Instruction Manual differ according to -NA, -EC,
-CH(T) versions. Refer to the following correspondence table for each inverter model. (Refer to the
Instruction Manual of each inverter for the inverter model.)
For example, "for the 75K or higher" indicates "for the FR-A740-01440-NA or higher" in the case of FR­A740 of NA version.
NA EC CH
FR-A720-55K FR-A720-02150-NA ⎯⎯
FR-A720-75K FR-A720-02880-NA ⎯⎯
FR-A740-55K
FR-A740-75K
FR-A740-01100-NA (FR-A760-00840-NA)
FR-A740-01440-NA (FR-A760-01040-NA)
FR-A740-01800-EC FR-A740-55K-CHT
FR-A740-02160-EC FR-A740-75K-CHT
1
1
PRE-OPERATION INSTRUCTIONS

1.2 Unpacking and Product Confirmation

Take the plug-in option out of the package, check the product name, and confirm that the product is as you ordered and intact. This product is a plug-in option for the FR-A700 series manufactured in December 2011 or later.
Check the SERIAL number specified on the inverter rating plate or package.
SERIAL number check
z
Refer to Instruction manual of the inverter for the location of the rating plate.
Rating plate example
Symbol Year Month Control number
The SERIAL consists of one symbol, two characters indicating production year and month, and six characters indicating control number. The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December).
1 Z {{{{{{
SERIAL

1.2.1 Product confirmation

Check the enclosed items.
Plug-in option
......................................... 1
Mounting screw (M3 × 6mm)
.............. 2 (Refer to page 6.)
Hex-head screw for option mounting (5.5mm)
...............1 (Refer to page 6.)
5.5mm
2

1.3 Parts

PRE-OPERATION INSTRUCTIONS
Terminal block
Mounting hole
Front view
Switch for manufacturer setting
Do not change from initially-
set status (OFF: ).
Terminal layout
5 5 5 5 5 5
DD3
SW1
DA2 DA3 DA4 DA5 DD0 DD1 DD2
Mounting
hole
N O
SW1
Rear view
Connector
Connect to the inverter
Mounting hole
option slot
(Refer to page 6)
1
3
PRE-OPERATION INSTRUCTIONS

1.4 Specifications

(1) Output signals
High-speed analog output (across the terminal 5’s and the terminals DA2 to DA5), 0VDC to ±10VDC (12-bit output resolution) Digital output (across the terminal 5’s and the terminals DD0 to DD3), 3V to 6V for HI, 0V to 2V for LOW
(2) Output accuracy (reference value)
±10% of the full-scale output value. Depends on the output signal type.
(3) Meters used
DC voltmeter Full-scale ±10V (internal impedance 10kΩ or more) Wiring length Maximum 30m
4

2 INSTALLATION AND WIRING

2.1 Pre-Installation Instructions

Make sure that the input power of the inverter is off.
CAUTION
With input power on, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged.
Static electricity in your body must be discharged before you touch the product. Otherwise the product may be damaged.
2
5
INSTALLATION AND WIRING

2.2 Installation Procedure

1)Remove the inverter front cover.
1)
Screw hole for option mounting
Inverter side option connector
3)
Screw hole for option mounting (on earth plate)
Hex-head screw for option mounting
REMARKS
• Remove a plug-in option after removing two screws on both left and right sides. (When the plug-in option is mounted in the connector 3, it is easier to remove the plug-in option after removing a control circuit terminal block.)
2)
4) Mounting
screws
2)Mount the hex-head screw for option mounting into the inverter screw hole (on earth plate). (size 5.5mm, tightening torque 0.56Nm to 0.75N⋅m)
3)Securely fit the connector of the plug-in option to the inverter connector along the guides.
4)Securely fix the both right and left sides of the plug-in option to the inverter with the accessory mounting screws. (Tightening torque 0.33Nm to
0.40Nm) If the screw holes do not line­up, the connector may not have been plugged snugly. Check for loose plugging.