Thank you for choosing this Mitsubishi Inverter.
This Instruction Manual is intended for users who "just want to run the inverter".
If you are going to utilize functions and performance, refer to the FR-A701 Series Instruction Manual (applied) [IB0600337ENG]. The Instruction Manual (applied) is separately available from where you purchased the inverter or
your Mitsubishi sales representative.
7.4Installation of the heatsink portion outside the enclosure for use................................ 187
701
1
2
3
4
5
6
7
This instruction manual (Basic) provides handling information and precautions for use of the equipment.
Please forward this instruction manual (Basic) to the end user.
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the inverter until you
have read through this instruction manual (Basic) and appended documents
carefully and can use the equipment correctly. Do not use the inverter until
you have a full knowledge of the equipment, safety information and
instructions. In this instruction manual (Basic), the safety instruction levels
are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that even the level may lead to a serious consequence
according to conditions. Please follow strictly the instructions of both levels
because they are important to personnel safety.
1. Electric Shock Prevention
• While power is on or when the inverter is running, do not open the front cover.
Otherwise you may get an electric shock.
• Do not run the inverter with the front cover or wiring cover removed.
Otherwise, you may access the exposed high-voltage terminals or the charging
part of the circuitry and get an electric shock.
• Even if power is off, do not remove the front cover except for wiring or periodic
inspection.You may access the charged inverter circuits and get an electric shock.
• Before starting wiring or inspection, check to make sure that the operation panel
indicator is off, wait for at least 10 minutes after the power supply has been
switched off, and check that there are no residual voltage using a tester or the
like. The capacitor is charged with high voltage for some time after power off and
it is dangerous.
• This inverter must be earthed (grounded). Earthing (Grounding) must conform to
the requirements of national and local safety regulations and electrical codes.
(NEC section 250, IEC 536 class 1 and other applicable standards)
Use a neutral-point earthed (grounded) power supply for 400V class inverter in
compliance with EN standard.
• Any person who is involved in the wiring or inspection of this equipment should
be fully competent to do the work.
• Always install the inverter before wiring. Otherwise, you may get an electric shock
or be injured.
• Perform setting dial and key operations with dry hands to prevent an electric
shock. Otherwise you may get an electric shock.
• Do not subject the cables to scratches, excessive stress, heavy loads or
pinching. Otherwise you may get an electric shock.
• Do not replace the cooling fan while power is on. It is dangerous to replace the
cooling fan while power is on.
Do not touch the printed circuit board with wet hands. You may get an electric shock.
•
• When measuring the main circuit capacitor capacity, the DC voltage is applied to
the motor for 1s at powering off. Never touch the motor terminal, etc. right after
powering off to prevent an electric shock.
2. Fire Prevention
• Install the inverter on a nonflammable wall without holes (so that nobody can
touch the inverter heatsink on the rear side, etc.).
Mounting it to or near combustible material can cause a fire.
• If the inverter has become faulty, switch off the inverter power.
A continuous flow of large current could cause a fire.
3. Injury Prevention
• Apply only the voltage specified in the instruction manual to each terminal.
Otherwise, burst, damage, etc. may occur.
• Ensure that the cables are connected to the correct terminals. Otherwise, burst,
damage, etc. may occur.
• Always make sure that polarity is correct to prevent damage, etc. Otherwise,
burst, damage, etc. may occur.
• While power is on or for some time after power-off, do not touch the inverter as it
is hot and you may get burnt.
4. Additional Instructions
Also note the following points to prevent an accidental failure, injury, electric
shock, etc.
(1) Transportation and installation
• When carrying products, use correct lifting gear to prevent injury.
• Do not stack the inverter boxes higher than the number recommended.
• Ensure that installation position and material can withstand the weight of the
inverter. Install according to the information in the instruction manual.
• Do not install or operate the inverter if it is damaged or has parts missing. This can
result in breakdowns.
• When carrying the inverter, do not hold it by the front cover or setting dial; it may
fall off or fail.
• Do not stand or rest heavy objects on the product.
• Check the inverter mounting orientation is correct.
• Prevent other conductive bodies such as screws and metal fragments or other
flammable substance such as oil from entering the inverter.
• As the inverter is a precision instrument, do not drop or subject it to impact.
• Use the inverter under the following environmental conditions. Otherwise, the
inverter may be damaged.
Surrounding air temperature -10°C to +50°C (non-freezing)
Ambient humidity90% RH or less (non-condensing)
Storage temperature-20°C to +65°C
Atmosphere
Altitude, vibration
Environment
*1 Temperature applicable for a short time, e.g. in transit.
Assumes that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Assumes that incorrect handling may cause
hazardous conditions, resulting in medium or slight
injury, or may cause physical damage only.
CAUTION
WARNING
CAUTION
CAUTION
CAUTION
Indoors (free from corrosive gas,
flammable gas, oil mist, dust and dirt)
Maximum 1000m above sea level for
standard operation. 5.9m/s
*1
2
or less
(3) Test operation and adjustment
• Before starting operation, confirm and adjust the parameters. A failure to do so
may cause some machines to make unexpected motions.
(4) Operation
• When you have chosen the retry function, stay away from the equipment as it
will restart suddenly after an alarm stop.
• Since pressing key may not stop output depending on the function setting
status (refer to page 109), provide a circuit and switch separately to make an
emergency stop (power off, mechanical brake operation for emergency stop,
etc).
• Make sure that the start signal is off before resetting the inverter alarm. A failure
to do so may restart the motor suddenly.
• The load used should be a three-phase induction motor only. Connection of any
other electrical equipment to the inverter output may damage the inverter as well as
equipment.
• Performing pre-excitation (LX signal and X13 signal) under torque control (real
sensorless vector control) may start the motor running at a low speed even
when the start command (STF or STR) is not input. The motor may run also at a
low speed when the speed limit value = 0 with a start command input. Perform
pre-excitation after making sure that there will be no problem in safety if the
motor runs.
• Do not modify the equipment.
• Do not perform parts removal which is not instructed in this manual. Doing so
may lead to fault or damage of the inverter.
• The electronic thermal relay function does not guarantee protection of the motor
from overheating. It is recommended to install both an external thermal and PTC
thermistor for overheat protection.
• Do not use a magnetic contactor on the inverter input for frequent starting/
stopping of the inverter. Otherwise, the life of the inverter decreases.
• Use a noise filter to reduce the effect of electromagnetic interference. Otherwise
nearby electronic equipment may be affected.
• When a 400V class motor is inverter-driven, please use an insulation-enhanced
motor or measures taken to suppress surge voltages. Surge voltages
attributable to the wiring constants may occur at the motor terminals,
deteriorating the insulation of the motor.
• When parameter clear or all clear is performed, reset the required parameters
before starting operations. Each parameter returns to the initial value.
• The inverter can be easily set for high-speed operation. Before changing its
setting, fully examine the performances of the motor and machine.
• In addition to the inverter's holding function, install a holding device to ensure
safety.
• Before running an inverter which had been stored for a long period, always
perform inspection and test operation.
• For prevention of damage due to static electricity, touch nearby metal before
touching this product to eliminate static electricity from your body.
(5) Emergency stop
• Provide a safety backup such as an emergency brake which will prevent the
machine and equipment from hazardous conditions if the inverter fails.
• When the breaker on the inverter input side trips, check for the wiring fault (short
circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip,
then remove the cause and power on the breaker.
• When the protective function is activated, take the corresponding corrective
action, then reset the inverter, and resume operation.
CAUTION
WARNING
CAUTION
CAUTION
(6) Maintenance, inspection and parts replacement
CAUTION
• Do not carry out a megger (insulation resistance) test on the control circuit of the
inverter. It will cause a failure.
(7) Disposing of the inverter
CAUTION
• Treat as industrial waste.
General instructions
Many of the diagrams and drawings in this instruction manual show the inverter
without a cover, or partially open. Never run the inverter in this status. Always
replace the cover and follow this instruction manual when operating the
inverter.
(2) Wiring
• Do not install a power factor correction capacitor or surge suppressor/radio
noise filter (capacitor type filter) on the inverter output side. The device on the
inverter output side may be overheated or burn out.
• The connection orientation of the output cables U, V, W to the motor will affect
the direction of rotation of the motor.
CAUTION
A-1
— CONTENTS —
1OUTLINE1
1.1Product checking and parts identification .............................................................. 1
1.2Inverter and peripheral devices.............................................................................. 2
7.3.2Dedicated motor outline dimension drawings ........................................................................ 183
7.4Installation of the heatsink portion outside the enclosure for use ......................187
7.4.1Protrusion of heatsink............................................................................................................ 187
APPENDICES 189
Appendix 1 Main differences and compatibilities with the FR-A700 series ................. 189
Appendix 2 Instructions for UL and cUL Compliance ................................................. 190
Appendix 3 Control mode-based parameter (function) correspondence
table and instruction code list ................................................................... 192
CONTENTS
<Abbreviations>
DU: Operation panel (FR-DU07)
PU: Operation panel(FR-DU07) and parameter unit (FR-PU04, FR-PU07)
Inverter: Mitsubishi inverter FR-A701 series
FR-A701: Mitsubishi inverter FR-A701 series
Pr.: Parameter Number
PU operation: Operation using the PU (FR-DU07/FR-PU04/FR-PU07).
External operation: Operation using the control circuit signals
Combined operation: Combined operation using the PU (FR-DU07/FR-PU04/FR-PU07) and external operation
Standard motor: SF-JR
Constant-torque motor: SF-HRCA
Vector dedicated motor: SF-V5RU
<Trademarks>
ONWORKS
L
DeviceNet is a registered trademark of ODVA (Open DeviceNet Vender Association, Inc.).
Company and product names herein are the trademarks and registered trademarks of their respective owners.
REMARKS
⋅ For differences and compatibility between the FR-A701 series and FR-A700 series, refer to page 189.
®
is registered trademarks of Echelon Corporation in the U.S.A. and other countries.
IV
MEMO
Product checking and parts identification
1OUTLINE
1.1Product checking and parts identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to
ensure that the product agrees with your order and the inverter is intact.
• Inverter Type
--
FR
A721
5.5
K
Cooling fan
(Refer to page 167)
Symbol
A721
Front cover
(Refer to page 4)
Operation panel
(FR-DU07)
Power lamp
Lit when the control circuit
(R1/L11, S1/L21) is supplied
with power.
Alarm lamp
Lit when the inverter is
in the alarm status
(major fault).
Capacity plate
Capacity plate
Voltage Class
Three-phase 200V class
Three-phase 400V classA741
(Refer to page 48)
FR-A721-5.5K
Inverter type
Indicate inverter
capacity (kW)
Serial number
• Accessory
· Eyebolt for hanging the inverter
CapacityEyebolt sizeNumber
11K , 1 5 KM82
18.5K to 30KM102
37K to 55KM122
* The 5.5K and 7.5K are not provided with eyebolts.
(Refer to page 167)
PU connector
(Refer to page 22)
RS-485 terminals
(Refer to page 27)
Connector for plug-in
option connection
(Refer to the instruction manual
of options.)
There are three connection
connectors and they are called
CON. 1, CON. 2, and CON. 3
from above.
Voltage/current input switch
(Refer to page 12)
AU/PTC switchover switch
(Refer to chapter 4 of the
instruction manual (applied).)
Control circuit
terminal block
Main circuit
terminal block
(Refer to page 20)
(Refer to page 13)
Charge lamp
Lit when power is supplied
to the main circuit
Fan blockFan cover
(Refer to page 167)
(Refer to page 13)
Rating plate
Inverter type
Applied motor
capacity
Input rating
Output rating
Serial number
1
OUTLINE
Rating plate
FR-A721-5.5K
REMARKS
For removal and reinstallation of covers, refer to page 4.
Harmonic suppression guideline (when inverters are used in Japan)
All models of general-purpose inverters used by specific consumers are covered by "Harmonic suppression guideline for consumers
who receive high voltage or special high voltage". (For details, refer to page 39 .)
1
Inverter and peripheral devices
1.2Inverter and peripheral devices
Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
(Refer to page 174)
Moulded case circuit breaker (MCCB) or
earth leakage circuit breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the inverter
at power on.
(Refer to page 3)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
(Refer to page 3)
Inverter (FR-A701)
The life of the inverter is influenced by surrounding air temperature. The surrounding air
temperature should be as low as possible within the permissible range. This must be noted
especially when the inverter is installed in an enclosure. (Refer to page 6)
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept
fully away from the main circuit to protect them from noise.(Refer to page 12)
Noise filter
(FR-BLF)
Install a noise filter to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about 1MHz to 10MHz.
When more wires are passed through, a more
effective result can be obtained. The total number of
wires passed through should be 4T or more.
Capacitor type filter
(FR-BIF)
Reduces the radio noise.
Devices connected to the output
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the output
side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the motor and inverter.
R/L1 S/L2 T/L3
Earth
(Ground)
UWV
Earth (Ground)
Noise filter (FR-BLF)
Install a noise filter to reduce
the electromagnetic noise
generated from the inverter.
Effective in the range from
about 1MHz to 10MHz. A wire
should be wound four turns at
a maximum.
Motor
CAUTION
·
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side. This will cause the
inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them.
· This inverter has a built-in AC reactor (FR-HAL) and a circuit type specified in Harmonic suppression guideline in Japan is threephase bridge (capacitor smoothed) and with reactor (AC side). (Refer to page 39) Do not use an AC reactor (FR-HAL) of a standalone option except following purpose. (Note that overload protection of the converter may operate when a thyristor load is
connected in the power supply system. To prevent this, always install an optional stand-alone AC reactor (FR-HAL).) A DC
reactor (FR-HEL) can not be connected to the inverter.
· Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, connecting a capacitor type filter will reduce electromagnetic
wave interference.
· Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
2
Inverter and peripheral devices
1.2.1Peripheral devices
Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor Output
*1
(kW)
5.5FR-A721-5.5K50AF 40AS-N20, N21
7.5FR-A721-7.5K50AF 50AS-N25
11FR-A721-11K100AF 75AS-N35
15FR-A721-15K100AF 100AS-N50
18.5FR-A721-18.5K225AF 125AS-N50
22FR-A721-22K225AF 150AS-N65
30FR-A721-30K225AF 175AS-N80
37FR-A721-37K225AF 225AS-N125
45FR-A721-45K400AF 300AS-N150
55FR-A721-55K400AF 350AS-N180
400V class
Motor Output
*1
(kW)
5.5FR-A741-5.5K30AF 20AS-N11, N12
7.5FR-A741-7.5K30AF 30AS-N20
11FR-A741-11K50AF 40AS-N20
15FR-A741-15K50AF 50AS-N20
18.5FR-A741-18.5K100AF 60AS-N25
22FR-A741-22K100AF 75AS-N25
30FR-A741-30K100AF 100AS-N50
37FR-A741-37K225AF 125AS-N50
45FR-A741-45K225AF 150AS-N65
55FR-A741-55K225AF 175AS-N80
*1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC/400VAC 50Hz.
*2 Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the appropriate UL and cUL listed class RK5, class T
type fuse or UL489 molded case circuit breaker (MCCB).
(Refer to page 190.)
*3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC
with class AC-3 rated current for the motor rated current.
Applicable Inverter TypeBreaker Selection*2Input Side Magnetic Contactor*3
Applicable Inverter TypeBreaker Selection*2Input Side Magnetic Contactor*3
MCCBINV
MCCBINV
IM
IM
1
OUTLINE
REMARKS
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
3
Method of removal and reinstallation of
the front cover
1.3Method of removal and reinstallation of the front cover
•Removal of the operation panel
1) Loosen the two screws on the operation panel.
(These screws cannot be removed.)
When reinstalling the operation panel, insert it straight to reinstall securely and tighten the fixed screws of the
operation panel.
2) Push the left and right hooks of the operation panel
and pull the operation panel toward you to remove.
•Removal of the front cover
1) Remove installation screws on the front cover
1 to remove the front cover 1.
Front cover 1
3) Pull the front cover 2 toward you to remove by pushing an installation hook on the right side
using left fixed hooks as supports.
2) Loosen the installation screws of the
front cover 2.
Front cover 2
Installation hook
4
•Reinstallation of the front cover
1) Insert the two fixed hooks on the left side of the
front cover 2 into the sockets of the inverter.
3) Fix the front cover 2 with the installation screws.4) Fix the front cover 1 with the installation
Method of removal and reinstallation of
the front cover
2) Using the fixed hooks as supports, securely press the
front cover 2 against the inverter.
(Although installation can be done with the operation
panel mounted, make sure that a connector is
securely fixed.)
Front cover 2Front cover 2
screws.
Front cover 2
Front cover 1
REMARKS
· For the 55K, the front cover 1 is separated into two parts.
CAUTION
1. Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.
2. The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter. Before
reinstalling the front cover, check the serial numbers to ensure that the cover removed is reinstalled to the inverter from where
it was removed.
1
OUTLINE
5
Installation of the inverter and enclosure
design
1.4Installation of the inverter and enclosure design
When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the
environment of an operating place, and others must be fully considered to determine the enclosure structure, size and
equipment layout. The inverter unit uses many semiconductor devices. To ensure higher reliability and long period of
operation, operate the inverter in the ambient environment that completely satisfies the equipment specifications.
1.4.1Inverter installation environment
The inverter consists of precision mechanical and electronic parts. Never install or handle it in any of the following
conditions as doing so could cause an operation fault or failure.
Direct sunlight
Vertical mounting
(When installing two or
more inverters, install
them in parallel.)
Vibration (5.9m/s2 or more)
Transportation by
holding the front cover
High temperature,
high humidity
Oil mist, flammable
gas, corrosive gas,
fluff, dust, etc.
Horizontal placement
Mounting to
combustible material
As the inverter installation environment should satisfiy the standard specifications indicated in the following table,
operation in any place that does not meet these conditions not only deteriorates the performance and life of the
inverter, but also causes a failure. Refer to the following points and take adequate measures.
Environmental standard specifications of inverter
ItemDescription
Surrounding air
temperature
Ambient humidity90% RH maximum (non-condensing)
AtmosphereFree from corrosive and explosive gases, dust and dirt
Maximum Altitude1,000m or less
Vibration
-10°C to +50°C (non-freezing)
2
or less
5.9m/s
6
Installation of the inverter and enclosure
design
(1) Temperature
The permissible surrounding air temperature of the inverter is between -10°C and +50°C. Always operate the inverter
within this temperature range. Operation outside this range will considerably shorten the service lives of the
semiconductors, parts, capacitors and others. Take the following measures so that the surrounding air temperature of
the inverter falls within the specified range.
1)Measures against high temperature
• Use a forced ventilation system or similar cooling system. (Refer to page 9.)
• Install the enclosure in an air-conditioned electrical chamber.
• Block direct sunlight.
• Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.
• Ventilate the area around the enclosure well.
2)Measures against low temperature
• Provide a space heater in the enclosure.
• Do not power off the inverter. (Keep the start signal of the inverter off.)
3)Sudden temperature changes
• Select an installation place where temperature does not change suddenly.
• Avoid installing the inverter near the air outlet of an air conditioner.
• If temperature changes are caused by opening/closing of a door, install the inverter away from the door.
(2) Humidity
Normally operate the inverter within the 45 to 90% range of the ambient humidity. Too high humidity will pose problems
of reduced insulation and metal corrosion. On the other hand, too low humidity may produce a spatial electrical
breakdown. The insulation distance specified in JEM1103 "Control Equipment Insulator" is defined as humidity 45 to
85%.
1)Measures against high humidity
• Make the enclosure enclosed, and provide it with a hygroscopic agent.
• Take dry air into the enclosure from outside.
• Provide a space heater in the enclosure.
2)Measures against low humidity
What is important in fitting or inspection of the unit in this status is to discharge your body (static electricity)
beforehand and keep your body from contact with the parts and patterns, besides blowing air of proper humidity into
the enclosure from outside.
3)Measures against condensation
Condensation may occur if frequent operation stops change the in-enclosure temperature suddenly or if the outsideair temperature changes suddenly.
Condensation causes such faults as reduced insulation and corrosion.
• Take the measures against high humidity in 1).
• Do not power off the inverter. (Keep the start signal of the inverter off.)
1
OUTLINE
(3) Dust, dirt, oil mist
Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due
to moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged filter.
In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated
insulation and short circuit in a short time.
Since oil mist will cause similar conditions, it is necessary to take adequate measures.
Countermeasures
• Place in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 9.)
• Purge air.
Pump clean air from outside to make the in-enclosure pressure higher than the outside-air pressure.
7
Installation of the inverter and enclosure
design
(4) Corrosive gas, salt damage
If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and parts will corrode or
the relays and switches will result in poor contact.
In such places, take the measures given in Section (3).
(5) Explosive, flammable gases
As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure.
In places where explosion may be caused by explosive gas, dust or dirt, an enclosure cannot be used unless it
structurally complies with the guidelines and has passed the specified tests. This makes the enclosure itself expensive
(including the test charges).
The best way is to avoid installation in such places and install the inverter in a non-hazardous place.
(6) Highland
Use the inverter at the altitude of within 1000m.
If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate
dielectric strength.
(7) Vibration, impact
The vibration resistance of the inverter is up to 5.9m/s2 at 10 to 55Hz frequency and 1mm amplitude.
Vibration or impact, if less than the specified value, applied for a long time may make the mechanism loose or cause
poor contact to the connectors.
Especially when impact is imposed repeatedly, caution must be taken as the part pins are likely to break.
Countermeasures
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from sources of vibration.
8
Installation of the inverter and enclosure
design
1.4.2Cooling system types for inverter enclosure
From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps,
resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature
lower than the permissible temperatures of the in-enclosure equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method.
1) Cooling by natural heat dissipation from the enclosure surface (Totally enclosed type)
2) Cooling by heat sink (Aluminum heatsink, etc.)
3) Cooling by ventilation (Forced ventilation type, pipe ventilation type)
4) Cooling by heat exchanger or cooler (Heat pipe, cooler, etc.)
Cooling SystemEnclosure StructureComment
Natural
cooling
Forced
cooling
Natural ventilation
(Enclosed, open type)
Natural ventilation (Totally
enclosed type)
Heatsink cooling
Forced ventilation
Heat pipeTotally enclosed type for enclosure downsizing.
Heatsink
INV
INV
INV
INV
Heat
pipe
INV
Low in cost and generally used, but the enclosure size
increases as the inverter capacity increases. For
relatively small capacities.
Being a totally enclosed type, the most appropriate for
hostile environment having dust, dirt, oil mist, etc. The
enclosure size increases depending on the inverter
capacity.
Having restrictions on the heatsink mounting position
and area, and designed for relative small capacities.
For general indoor installation. Appropriate for enclosure
downsizing and cost reduction, and often used.
1
OUTLINE
9
Installation of the inverter and enclosure
design
1.4.3Inverter placement
(1) Installation of the Inverter
Installation on the enclosure
CAUTION
⋅ When encasing multiple inverters, install them in parallel as a cooling measure.
⋅ Install the inverter vertically.
Vertical
Refer to the clearances below.
(2) Clearances around the inverter
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
Surrounding air temperature and humidity
Measurement
position
Inverter
5cm
Measurement
position
5cm
5cm
Temperature: -10°C to 50°C
Ambient humidity: 90% RH
5cm
or more
10cm or more
5cm
or more
10cm or more
maximum
Leave enough clearances and take
cooling measures.
REMARKS
For replacing the cooling fan, 30cm of space is necessary in front of the inverter. Refer to page 167 for fan replacement.
Clearances (side)Clearances (front)
5cm
Inverter
or
more
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
10
Installation of the inverter and enclosure
design
(4) Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter
should be heat resistant.
(5) Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown in the figure
below (a). When it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides
since heat from the bottom inverters can increase the temperatures in the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter higher
than the permissible value by providing ventilation and increasing the enclosure size.
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When intalling a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow. (Air
passes through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
InverterInverter
1
OUTLINE
<Good example><Bad example>
Placement of ventilation fan and inverter
11
Terminal connection diagram
2WIRING
2.1Terminal connection diagram
Sink logic
Main circuit terminal
Control circuit terminal
MCCB
MC
*6*6
R/L1
Earth
S/L2
T/L3
R1/L11
S1/L21
Main circuit
Control circuit
STF
STR
STOP
RH
RM
RL
JOG
*2
RT
MRS
RES
*3
AU
AU
PTC
CS
SD
PC
10E(+10V)
10(+5V)
2
5
1
4
Option connector 1
Option connector 2
Option connector 3
SOURCE
*4
Voltage/current
input switch
ON
OFF
0 to 5VDC
0 to 10VDC
0 to 20mADC
(Initial value)
selected
(Analog common)
±
10VDC
0 to
0 to ±5VDC
selected
4 to 20mADC
0 to 5VDC
0 to 10VDC
selected
SINK
2
4
*4
(Initial value)
*4
(Initial value)
*4
Three-phase AC
power supply
Jumper
*1. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to chapter 4 of the instruction
manual (applied))
Forward
rotation
start
Reverse
rotation
start
Start self-
holding selection
High speed
Multi-speed
selection
*2. JOG terminal can be used
as pulse train input terminal.
Use Pr. 291 to select
JOG/pulse.
Middle
speed
Low speed
Jog mode
Second function selection
*3. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
Output stop
Reset
after instantaneous
power failure
Contact input common
24VDC power supply
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
*
Terminal input specifications
4.
can be changed by analog
input specifications
switchover (Pr. 73, Pr. 267).
Set the voltage/current input
switch in the OFF position to
select voltage input (0 to 5V/0
to10V) and ON to select
current input (4 to 20mA).
(Refer to chapter 4 of the
instruction manual (applied))
*5
3
Ω
1
Auxiliary
input
Terminal
4 input
(Current
input)
2
(+)
(+)
(-)
(-)
Connector
for plug-in option
connection
*5
. It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
*1
(Ground)
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire
of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
N/-P/+
C1
B1
A1
C2
B2
A2
RUN
SU
IPF
OL
FU
SE
PU
connector
USB
connector
FM
*9
SD
AM
TXD+
TXD-
RXD+
RXD-
SG
Terminating
VCC
resistor
U
V
W
*6. Do not connect any options to P/+ and
N/-.
Relay output 1
(Fault output)
Terminal functions
vary with the output
terminal assignment
(Pr. 195, Pr. 196)
(Refer to chapter 4 of the
instruction manual
(applied))
Relay output 2
Open collector output
Running
Up to frequency
Instantaneous
power failure
Overload
Terminal functions
vary with the output
terminal assignment
(Pr. 190 to Pr. 194)
(Refer to chapter 4 of the
instruction manual
(applied))
Frequency detection
Open collector output common
Sink
/source common
*
7. It is not necessary when
calibrating the indicator
from the operation panel.
*9
. Because the FR Configurator has not
worked with the FR-A701 series, a USB
connector can not be used.
*8
5
Calibration
resistor *7
+
-
(+)
Analog signal output
(0 to 10VDC)
(-)
RS-485 terminals
Data transmission
Data reception
GND
(Permissible load
5V
current 100mA)
Motor
IM
Earth (Ground)
Relay output
*8. FM terminal can be
used for pulse train
output of open
collector output
using Pr.291.
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale
12
2.2Main circuit terminal specifications
2.2.1Specification of main circuit terminal
Main circuit terminal specifications
Terminal
Symbol
R/L1,
S/L2,
T/L3
U, V, WInverter outputConnect a three-phase squirrel-cage motor.
R1/L11,
S1/L21
P/+, N/-DC terminalDo not connect any options.
Terminal N a meDescription
AC power inputConnect to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers from terminals R/L1-R1/
L11 and S/L2-S1/L21 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
Power supply for
control circuit
Earth (Ground)
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
Power supply capacity for the 15K or less is 90VA and for the 18.5K or
more is 100VA.
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
2
WIRING
13
Main circuit terminal specifications
2.2.2Terminal arrangement of the main circuit terminal, power supply and the motor
wiring.
200V class
FR-A721-5.5K, 7.5KFR-A721-11K, 15K
R1/L11 S1/L21
Screw size
(M4)
Screw size (M5)
R/L1 S/L2 T/L3
N/-
Charge lamp
Jumper
Screw size (11K: M5, 15K: M6)
P/+
IM
Power supply
FR-A721-18.5K to 45KFR-A721-55K
Motor
Power supply
Screw size (M4)
R1/L11 S1/L21
Charge
lamp
Jumper
Screw size
R/L1 S/L2 T/L3
(M4)
R1/L11 S1/L21
Charge lamp
Jumper
N/-P/+
IM
Motor
Screw size (M4)
R1/L11 S1/L21
Charge
lamp
Jumper
Screw size
(18.5K/22K/30K: M8, 37K/45K: M10)
R/L1 S/L2
Power supply
T/L3
IM
Motor
Screw size
(18.5K/22K/30K: M6,
37K/45K: M8)
N/-
P/+
Screw size (M12)
R/L1 S/L2 T/L3
Power supply
IM
Motor
N/-
Screw size (M8)
P/+
14
400V class
FR-A741-5.5K, 7.5KFR-A741-11K, 15K
Screw size (M4)
R1/L11
S1/L21
Charge lamp
Jumper
Screw size (M4)
Main circuit terminal specifications
S1/L21
R1/L11
Screw size (M4)
Charge lamp
Jumper
P/+
R/L1 S/L2 T/L3
N/-
IM
Power supply
FR-A741-18.5K to 45KFR-A741-55K
Screw size (18.5K to 30K : M6,
Motor
Screw size (M4)
S1/L21
R1/L11
37K/45K : M8)
Charge lamp
Jumper
Screw size (M5)
R/L1 S/L2 T/L3
Power supply
IM
Motor
S1/L21
R1/L11
P/+
N/-
Screw size (M4)
Charge lamp
Jumper
2
WIRING
R/L1 S/L2 T/L3
Power supply
IM
Motor
N/-
P/+
R/L1 S/L2 T/L3
Screw size (M8)
N/-
P/+
IM
Power supply
CAUTION
· The power supply cables must be connected to R/L1, S/L2, T/L3. (Phase sequence needs not to be matched.) Never connect
the power cable to the U, V, W of the inverter. Doing so will damage the inverter.
· Connect the motor to U, V, W. At this time, turning on the forward rotation switch (signal) rotates the motor in the
counterclockwise direction when viewed from the motor shaft.
Motor
15
Main circuit terminal specifications
2.2.3Cables and wiring length
(1) Applied cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor
torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
*1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of
75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
*2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the
surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the United States.)
*3 For the 15K or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the 18.5K or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C.
Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for earthing (grounding) of the 18.5K or more is indicated in ( ).
*1The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of
Assumes that the surrounding air temperature is
*2For the 45K or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of
Assumes that the surrounding air temperature is
For the 55K, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of
the surrounding air temperature is
(Selection example for use mainly in the United States.)
*3For the 45K or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes
that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 55K, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. Assumes that
the ambient temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
40°C
50°C
or less and the wiring distance is 20m or less.
40°C
or less and the wiring distance is 20m or less.
or less and wiring is performed in an enclosure.
.
.
16
The line voltage drop can be calculated by the following formula:
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Notes on earthing (grounding)
z Always earth (ground) the motor and inverter.
1)Purpose of earthing (grounding)
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before
use.
An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to
manufacture an insulating material that can shut off a leakage current completely, and actually, a slight current flow
into the case. The purpose of earthing (grounding) the case of an electrical apparatus is to prevent operator from
getting an electric shock from this leakage current when touching it.
To avoid the influence of external noises, this earthing (grounding) is important to audio equipment, sensors,
computers and other apparatuses that handle low-level signals or operate very fast.
2)Earthing (grounding) methods and earthing (grounding) work
As described previously, earthing (grounding) is roughly classified into an electrical shock prevention type and a
noise-affected malfunction prevention type. Therefore, these two types should be discriminated clearly, and the
following work must be done to prevent the leakage current having the inverter's high frequency components from
entering the malfunction prevention type earthing (grounding):
(a) Where possible, use independent earthing (grounding) for the inverter. If independent earthing (grounding) (I)
is impossible, use joint earthing (grounding) (II) where the inverter is connected with the other equipment at an
earthing (grounding) point. Joint earthing (grounding) as in (III) must be avoided as the inverter is connected
with the other equipment by a common earth (ground) cable.
Also a leakage current including many high frequency components flows in the earth (ground) cables of the
inverter and inverter-driven motor. Therefore, they must use the independent earthing (grounding) method and
be separated from the earthing (grounding) of equipment sensitive to the aforementioned noises.
In a tall building, it will be a good policy to use the noise malfunction prevention type earthing (grounding) with
steel frames and carry out electric shock prevention type earthing (grounding) in the independent earthing
(grounding) method.
(b) This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national
and local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable
standards).
Use a neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard.
(c) Use the thickest possible earth (ground) cable. The earth
indicated in the table on the previous page.
(d) The grounding point should be as near as possible to the inverter, and the ground wire length should be as
short as possible.
(e) Run the earth (ground) cable as far away as possible from the I/O wiring of equipment sensitive to noises and
run them in parallel in the minimum distance.
(ground) cable should be of not less than the size
The overall wiring length for connection of a single motor or multiple motors should be within 500m.
(The wiring length should be 100m maximum for vector control.)
Total wiring length
500m or less
300m
300m
300m + 300m = 600m
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at
the motor terminals, deteriorating the insulation of the motor.
Refer to page 42 for measures against deteriorated insulation.
CAUTION
· Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the
wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or fault
of the equipment connected on the inverter output side. If fast response current limit function malfunctions, disable this function.
(For Pr. 156 Stall prevention operation selection, refer to chapter 4 of the instruction manual (applied).)
For explanation of surge voltage suppression filter (FR-ASF-H), refer to the manual of each option.
· Do not perform vector control with a surge voltage suppression filter (FR-ASF-H) connected.
(4) Cable size of the control circuit power supply (terminal R1/L11, S1/L21)
· Terminal screw size: M4
· Cable size: 0.75mm
· Tightening torque: 1.5N·m
2
to 2mm
2
18
Main circuit terminal specifications
2.2.4When connecting the control circuit and the main circuit separately
to the power supply (separate power)
<Connection diagram>When fault occurs, opening of the electromagnetic contactor (MC) on the
MC
Remove the jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
Inverter
inverter power supply side results in power loss in the control circuit,
disabling the fault output signal retention. Terminals R1/L11 and S1/L21 are
provided to hold a fault signal. In this case, connect the power supply
terminals R1/L11 and S1/L21 of the control circuit to the primary side of the
MC.
1)Remove the upper screws.
2)Remove the lower screws.
3)Pull the jumper toward you to
remove.
4)
Connect the separate power supply
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
Never connect
the power cable to
the terminals in the lower stand.
Doing so will damage the inverter.
R1/
L11
T/L3
S/L2
R/L1
MC
Main power supply
Power supply
terminal block for
the control circuit
S1/
L21
Power supply
terminal block
for the control circuit
FR-A721-5.5K to 15K
FR-A741-5.5K to 15K
3)
Power supply terminal block
for the control circuit
R1/L11
1)
2)
4)
FR-A721-18.5K to 55K
FR-A741-18.5K to 55K
S1/L21
2
CAUTION
· Do not turn off the control power (terminals R1/L11 and S1/L21) with the main circuit power (R/L1, S/L2, T/L3) on. Doing so may
damage the inverter. Make up a circuit which will switch off the main circuit power supply terminals R/L1, S/L2, T/L3 when the
control circuit power supply terminals R1/L11, S1/L21 are switched off.
· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying power
from other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
primary side of the MC.
· When separate power is supplied from R1/L11 and S1/L21, the power capacity necessary for the 15K or less is 90VA, for the
18.5K or more is 100VA.
· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and a fault output will not be held.
WIRING
19
Control circuit specifications
2.3Control circuit specifications
2.3.1Control circuit terminals
indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to chapter 4 of
the instruction manual (applied).)
(1) Input signals
Terminal
Symbol
Type
STF
STR
STOP
RH,
RM, RL
JOG
RT
MRSOutput stop
RESReset
AU
Contact input
CS
SD
PC
Ter min al
Name
Forward
rotation start
Reverse
rotation start
Star t selfholding
selection
Multi-speed
selection
Jog mode
selection
Pulse train
input
Second
function
selection
Terminal 4
input
selection
PTC input
Selection of
automatic
restart after
instantaneous
power failure
Contact input
common (sink)
(initial setting)
External
transistor
common
(source)
24VDC power
supply
common
External
transistor
common (sink)
(initial setting)
Contact input
common
(source)
24VDC power
supply
Description
Turn on the STF signal to start forward
rotation and turn it off to stop.
Turn on the STR signal to start reverse
rotation and turn it off to stop.
Turn on the STOP signal to self-hold the start signal.*2
Multi-speed can be selected according to the combination of RH,
RM and RL signals.
Turn on the JOG signal to select Jog operation (initial setting) and
turn on the start signal (STF or STR) to start Jog operation.
JOG terminal can be used as pulse train input terminal. To use as
pulse train input terminal, the Pr. 291 setting needs to be changed.
(maximum input pulse: 100
Turn on the RT signal to select second function.
When the second function such as "second torque boost" and
"second V/F (base frequency)" are set, turning on the RT signal
selects these functions.
Turn on the MRS signal (20ms or more) to stop the inverter output.
Use to shut off the inverter output when stopping the motor by
electromagnetic brake.
Used to reset fault output provided when fault occurs.
Turn on the RES signal for more than 0.1s, then turn it off.
Initial setting is for reset always. By setting Pr. 75, reset can be set
to enabled only at fault occurrence. Recover about 1s after reset
is cancelled.
Terminal 4 is made valid only when the AU signal is turned on. (The
frequency setting signal can be set between 4 and 20mADC.)
Turning the AU signal on makes terminal 2 (voltage input) invalid.
AU terminal is used as PTC input terminal (thermal protection of
the motor). When using it as PTC input terminal, set the AU/PTC
switch to PTC.
When the CS signal is left on, the inverter restarts automatically at
power restoration. Note that restart setting is necessary for this
operation. In the initial setting, a restart is disabled.
(Refer to Pr. 57 Restart coasting time in chapter 4 of
instruction manual (applied).)
Common terminal for contact input terminal (sink logic) and terminal
FM.
When connecting the transistor output (open collector output),
such as a programmable controller, when source logic is
selected, connect the external power supply common for
transistor output to this terminal to prevent a malfunction caused
by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (PC
terminal).
Isolated from terminals 5 and SE.
When connecting the transistor output (open collector output), such
as a programmable controller, when sink logic is selected, connect
the external power supply common for transistor output to this
terminal to prevent a malfunction caused by undesirable currents.
Common terminal for contact input terminal (source logic).
Can be used as 24VDC 0.1A power supply.
k
pulses/s)
When the STF and STR
signals are turned on
simultaneously, the stop
command is given.
the
Rated
Specifications
Input resistance
4.7kΩ
Voltage at opening:
21 to 27VDC
Contacts at shortcircuited: 4 to
6mADC
Input resistance
2kΩ
Contacts at shortcircuited: 8 to
13mADC
Input resistance
4.7kΩ
Voltage at opening:
21 to 27VDC
Contacts at shortcircuited: 4 to
6mADC
--------------------—
Power supply
voltage range 19.2
to 28.8VDC
Permissible load
current 100mA
Refer to
page
88
89
*2
*2
*2
*2
139
93
*2
*2
24
20
Control circuit specifications
Terminal
Symbol
Type
10E
10
2
Terminal
Name
Frequency
setting power
supply
Frequency
setting
(voltage)
Description
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications of terminal 2 when connecting it
to terminal 10E. (Refer to Pr. 73 Analog input selection in chapter 4 of
the instruction manual (applied).)
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes input
and output proportional. Use Pr. 73 to switch from among input 0
to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.
Set the voltage/current input switch in the ON position to select
current input (0 to 20mA).
*1
Rated
Specifications
10VDC
Permissible load
current 10mA
5VDC
Permissible load
current 10mA
Voltage input:
Input resistance
10kΩ ± 1kΩ
Maximum
permissible voltage
20VDC
Current input:
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA makes input and output
proportional. This input signal is valid only when the AU signal is
on (terminal 2 input is invalid).
Frequency
4
Frequency setting
setting
(current)
Use Pr. 267 to switch from among input 4 to 20mA (initial setting),
0 to 5VDC, and 0 to 10VDC.
Set the voltage/current input switch in the OFF position to select
voltage input (0 to 5V/0 to 10V).
*1
(Refer to chapter 4 of the instruction manual (applied).) Use Pr.
858 to switch terminal functions.
Frequency
1
setting
auxiliary
Frequency
5
setting
common
*1 Set Pr. 73, Pr. 267, and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage signal with voltage/current input switch on (current input is selected) or a current signal with switch off (voltage input is
selected) could cause component damage of the inverter or analog circuit of signal output devices.
*2 Refer to chapter 4 of
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use Pr. 73 to switch between the
input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Use Pr. 868 to switch terminal functions.
Common terminal for frequency setting signal (terminal 2, 1 or 4)
and analog output terminal AM. Do not earth (ground).
the instruction manual (applied).
Input resistance
245Ω ± 5Ω
Maximum
permissible current
30mA
Voltage/current
input switch
switch1
switch2
4
Input resistance
10kΩ ± 1kΩ
Maximum
permissible voltage
± 20VDC
--------------------------
2
Refer to
page
*2
86, 91
86, 91
87, 93
*2
2
21
WIRING
Control circuit specifications
(2) Output signals
Terminal
Symbol
Type
A1,
B1,
C1
Relay
A2,
B2,
C2
RUN
SU
OL
Open collector
IPF
FU
SE
FM
Pulse
AM
Analog
Terminal
Name
Description
Rated
Specifications
Refer to
page
1 changeover contact output indicates that the inverter
Relay output 1
(alarm output)
Relay output 21 changeover contact output*2
Inverter
running
Up to
frequency
Overload
warning
Instantaneous
power failure
Frequency
detection
Open collector
output common
For meter
NPN open
collector output
Analog signal
output
protective function has activated and the output stopped.
Abnormal: No conduction across B-C (Across A-C Continuity),
Normal: Across B-C Continuity (No conduction across A-C)
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485 (RS-485)
. Transmission format : Multidrop link
. Communication speed : 4800 to 38400bps
. Overall length: 500m
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed : 300 to 38400bps
Overall length: 500m
22
Description
Refer to
page
26
27
Control circuit specifications
2.3.2Changing the control logic
The input signals are set to sink logic (SINK) when shipped from the factory.
To change the control logic, the jumper connector on the back of the control circuit terminal block must be moved to the
other position.
(The output signals may be used in either the sink or source logic independently of the jumper connector position.)
1)Loosen the two installation screws in both ends of the control circuit terminal block. (These screws cannot be
removed.)
Pull down the terminal block from behind the control circuit terminals.
2)Change the jumper connector set to the sink logic (SINK) on the rear panel of the control circuit terminal block to
source logic (SOURCE).
Jumper connector
3)Using care not to bend the pins of the inverter's control circuit connector, reinstall the control circuit terminal block
and fix it with the mounting screws.
CAUTION
1. Make sure that the control circuit connector is fitted correctly.
2. While power is on, never disconnect the control circuit terminal block.
2
WIRING
23
Loading...
+ 187 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.