Thank you for choosing this Mitsubishi Inverter.
This Instruction Manual is intended for users who "just want to run the inverter".
If you are going to utilize functions and performance, refer to the FR-A701 Series Instruction Manual (Applied) [IB0600337ENG]. The Instruction Manual (Applied) is separately available from where you purchased the inverter or
your Mitsubishi sales representative.
7.4Installation of the heatsink portion outside the enclosure for use................................ 194
701
1
2
3
4
5
6
7
This Instruction Manual (Basic) provides handling information and precautions for use of the equipment.
Please forward this Instruction Manual (Basic) to the end user.
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the
inverter until you have read through the Instruction Manual
and appended documents carefully and can use the
equipment correctly. Do not use this product until you have
a full knowledge of the equipment, safety information and
instructions.
In this Instruction Manual, the safety instruction levels are
classified into "WARNING" and "CAUTION".
WARNING
CAUTION
CAUTION
The level may even lead to a serious
consequence according to conditions. Both instruction
levels must be followed because these are important to
personal safety.
Incorrect handling may cause
hazardous conditions, resulting in
death or severe injury.
Incorrect handling may cause
hazardous conditions, resulting in
medium or slight injury, or may cause
only material damage.
1. Electric Shock Prevention
WARNING
z While power is ON or when the inverter is running, do not
open the front cover. Otherwise you may get an electric
shock.
z Do not run the inverter with the front cover or wiring cover
removed. Otherwise you may access the exposed highvoltage terminals or the charging part of the circuitry and
get an electric shock.
z Even if power is OFF, do not remove the front cover
except for wiring or periodic inspection. You may
accidentally touch the charged inverter circuits and get an
electric shock.
z Before wiring or inspection, power must be switched OFF.
To confirm that, LED indication of the operation panel
must be checked. (It must be OFF.) Any person who is
involved in wiring or inspection shall wait for at least 10
minutes after the power supply has been switched OFF
and check that there are no residual voltage using a tester
or the like. The capacitor is charged with high voltage for
some time after power OFF, and it is dangerous.
z
This inverter must be earthed (grounded). Earthing
(grounding) must conform to the requirements of national
and local safety regulations and electrical code (NEC section
250, IEC 536 class 1 and other applicable standards).
A neutral-point earthed (grounded) power supply for 400V
class inverter in compliance with EN standard must be used.
z Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work.
z The inverter must be installed before wiring. Otherwise
you may get an electric shock or be injured.
z Setting dial and key operations must be performed with
dry hands to prevent an electric shock.
z Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise you may get an
electric shock.
z Do not change the cooling fan while power is ON. It is
dangerous to change the cooling fan while power is ON.
z Do not touch the printed circuit board or handle the
cables with wet hands. Otherwise you may get an electric
shock.
z When measuring the main circuit capacitor capacity, the
DC voltage is applied to the motor for 1s at powering OFF.
Never touch the motor terminal, etc. right after powering
OFF to prevent an electric shock.
2. Fire Prevention
CAUTION
z Inverter must be installed on a nonflammable wall without
holes (so that nobody touches the inverter heatsink on the
rear side, etc.). Mounting it to or near flammable material
can cause a fire.
z If the inverter has become faulty, the inverter power must
be switched OFF. A continuous flow of large current could
cause a fire.
3.Injury Prevention
CAUTION
z The voltage applied to each terminal must be the ones
specified in the Instruction Manual. Otherwise burst,
damage, etc. may occur.
z The cables must be connected to the correct terminals.
Otherwise burst, damage, etc. may occur.
z Polarity must be correct. Otherwise burst, damage, etc.
may occur.
z While power is ON or for some time after power-OFF, do
not touch the inverter as they will be extremely hot. Doing
so can cause burns.
4. Additional Instructions
Also the following points must be noted to prevent an
accidental failure, injury, electric shock, etc.
(1) Transportation and Mounting
CAUTION
z The product must be transported in correct method that
corresponds to the weight. Failure to do so may lead to
injuries.
z Do not stack the boxes containing inverters higher than
the number recommended.
z The product must be installed to the position where
withstands the weight of the product according to the
information in the Instruction Manual.
z Do not install or operate the inverter if it is damaged or
has parts missing.
z When carrying the inverter, do not hold it by the front
cover or setting dial; it may fall off or fail.
z Do not stand or rest heavy objects on the product.
z The inverter mounting orientation must be correct.
z Foreign conductive objects must be prevented from
entering the inverter. That includes screws and metal
fragments or other flammable substance such as oil.
z As the inverter is a precision instrument, do not drop or
subject it to impact.
z The inverter must be used under the following
environment. Otherwise the inverter may be damaged.
Surrounding
air
temperature
Ambient
humidity
Storage
temperature
Atmosphere
Environment
Altitude/
vibration
∗1 Temperature applicable for a short time, e.g. in transit.
-10°C to +50°C (non-freezing)
90%RH or less (non-condensing)
-20°C to +65°C *1
Indoors (free from corrosive gas, flammable gas,
oil mist, dust and dirt)
Maximum 1,000m above sea level for standard
operation.
2
or less at 10 to 55Hz (directions of X, Y, Z
5.9m/s
axes)
(2) Wiring
CAUTION
z Do not install a power factor correction capacitor or surge
suppressor/capacitor type filter on the inverter output
side. These devices on the inverter output side may be
overheated or burn out.
z The connection orientation of the output cables U, V, W to
the motor affects the rotation direction of the motor.
A-1
(3) Trial run
CAUTION
z Before starting operation, each parameter must be
confirmed and adjusted. A failure to do so may cause
some machines to make unexpected motions.
(4) Usage
WARNING
z Any person must stay away from the equipment when the
retry function is set as it will restart suddenly after trip.
z Since pressing key may not stop output depending
on the function setting status, separate circuit and switch
that make an emergency stop (power OFF, mechanical
brake operation for emergency stop, etc.) must be
provided.
z OFF status of the start signal must be confirmed before
resetting the inverter fault. Resetting inverter alarm with
the start signal ON restarts the motor suddenly.
z
The inverter must be used for three-phase induction motors.
Connection of any other electrical equipment to the
inverter output may damage the equipment.
z Performing pre-excitation (LX signal and X13 signal)
under torque control (Real sensorless vector control) may
start the motor running at a low speed even when the start
command (STF or STR) is not input. The motor may also
run at a low speed when the speed limit value = 0 with a
start command input. It must be confirmed that the motor
running will not cause any safety problem before
performing pre-excitation.
z Do not modify the equipment.
z
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the product.
(5) Emergency stop
CAUTION
z A safety backup such as an emergency brake must be
provided to prevent hazardous condition to the machine
and equipment in case of inverter failure.
z When the breaker on the inverter input side trips, the
wiring must be checked for fault (short circuit), and
internal parts of the inverter for a damage, etc. The cause
of the trip must be identified and removed before turning
ON the power of the breaker.
z When any protective function is activated, appropriate
corrective action must be taken, and the inverter must be
reset before resuming operation.
(6) Maintenance, inspection and parts replacement
CAUTION
z Do not carry out a megger (insulation resistance) test on
the control circuit of the inverter. It will cause a failure.
(7) Disposal
CAUTION
z The inverter must be treated as industrial waste.
General instruction
Many of the diagrams and drawings in this Instruction
Manual (Basic) show the inverter without a cover or partially
open for explanation. Never operate the inverter in this
manner. The cover must be always reinstalled and the
instruction in this Instruction Manual (Basic) must be
followed when operating the inverter.
CAUTION
z The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is
recommended to install both an external thermal and PTC
thermistor for overheat protection.
z Do not use a magnetic contactor on the inverter input for
frequent starting/stopping of the inverter. Otherwise the
life of the inverter decreases.
z The effect of electromagnetic interference must be
reduced by using a noise filter or by other means.
Otherwise nearby electronic equipment may be affected.
z When driving a 400V class motor by the inverter, the
motor must be an insulation-enhanced motor or measures
must be taken to suppress surge voltage. Surge voltage
attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.
z When parameter clear or all parameter clear is performed,
the required parameters must be set again before starting
operations because all parameters return to the initial value.
z The inverter can be easily set for high-speed operation.
Before changing its setting, the performances of the
motor and machine must be fully examined.
z Stop status cannot be hold by the inverter's brake
function. In addition to the inverter’s brake function, a
holding device must be installed to ensure safety.
z Before running an inverter which had been stored for a long
period, inspection and test operation must be performed.
z For prevention of damage due to static electricity, nearby
metal must be touched before touching this product to
eliminate static electricity from your body.
A-2
— CONTENTS —
1OUTLINE1
1.1Product checking and parts identification .............................................................. 1
1.2Inverter and peripheral devices..............................................................................2
7.3.2Dedicated motor outline dimension drawings ........................................................................ 190
7.4Installation of the heatsink portion outside the enclosure for use ...................... 194
7.4.1Protrusion of heatsink ............................................................................................................ 194
APPENDICES 196
Appendix 1 Main differences and compatibilities with the FR-A700 series ................. 196
Appendix 2 Instructions for compliance with the EU Directives (400V class only)..... 197
Appendix 3 Instructions for UL and cUL Compliance................................................. 199
Appendix 4 Control mode-based parameter (function) correspondence
table and instruction code list ................................................................... 201
<Abbreviations>
DU: Operation panel (FR-DU07)
PU: Operation panel (FR-DU07) and parameter unit (FR-PU04, FR-PU07)
Inverter: Mitsubishi inverter FR-A701 series
FR-A701: Mitsubishi inverter FR-A701 series
Pr.: Parameter Number (Number assigned to function)
PU operation: Operation using the PU (FR-DU07/FR-PU04/FR-PU07)
External operation: Operation using the control circuit signals
Combined operation: Combined operation using the PU (FR-DU07/FR-PU04/FR-PU07) and external operation
Standard motor: SF-JR
Constant-torque motor: SF-HRCA
Vector dedicated motor: SF-V5RU
<Trademarks>
ONWORKS
L
DeviceNet is a registered trademark of ODVA (Open DeviceNet Vender Association, Inc.).
Company and product names herein are the trademarks and registered trademarks of their respective owners.
REMARKS
⋅ For differences and compatibility between the FR-A701 series and FR-A700 series, refer to page 196.
®
is registered trademarks of Echelon Corporation in the U.S.A. and other countries.
IV
Product checking and parts identification
1OUTLINE
1.1Product checking and parts identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to
ensure that the product agrees with your order and the inverter is intact.
• Inverter Model
--
FR
A721
5.5
K
Cooling fan
(Refer to page 175)
Symbol
A721
Front cover
(Refer to page 4)
Operation panel
(FR-DU07)
Power lamp
Lit when the control circuit
(R1/L11, S1/L21) is supplied
with power.
Alarm lamp
Lit when the inverter is
in the alarm status
(major fault).
Capacity plate
Capacity plate
Voltage Class
Three-phase 200V class
Three-phase 400V classA741
(Refer to page 48)
FR-A721-5.5K
Inverter Model
Indicate inverter
capacity (kW)
Serial number
• Accessory
· Eyebolt for hanging the inverter
CapacityEyebolt sizeQuantity
11K , 1 5 KM82
18.5K to 30KM102
37K to 55KM122
* The 5.5K and 7.5K are not provided with eyebolts.
(Refer to page 175)
USB connector
(Refer to page 337)
PU connector
(Refer to page 22)
RS-485 terminals
(Refer to page 26)
Connector for plug-in
option connection
(Refer to the Instruction Manual
of options.)
There are three connection
connectors and they are called
connector 1, connector 2, and
connector 3 from the top.
Voltage/current input switch
(Refer to page 12)
AU/PTC switchover switch
(Refer to Chapter 4 of the
Instruction Manual (Applied).)
Control circuit
terminal block
Main circuit
terminal block
(Refer to page 20)
Charge lamp
Lit when power is supplied
to the main circuit
Fan blockFan cover
(Refer to page 175)
(Refer to page 13)
Rating plate
Inverter Model
Applied motor
Output rating
Serial number
1
OUTLINE
(Refer to page 13)
Rating plate
FR-A721-5.5K
capacity
Input rating
REMARKS
For removal and reinstallation of covers, refer to page 4.
Harmonic suppression guideline (when inverters are used in Japan)
All models of general-purpose inverters used by specific consumers are covered by "Harmonic suppression guideline for consumers
who receive high voltage or special high voltage". (For details, refer to page 39 .)
1
Inverter and peripheral devices
1.2Inverter and peripheral devices
Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
(Refer to page 182)
Moulded case circuit breaker (MCCB) or
earth leakage circuit breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the inverter
at power on.
(Refer to page 3)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
(Refer to page 3)
USB connector
A personal computer and an inverter
can be connected with a
USB (Ver1. 1) cable.
(Refer to page 27)
Inverter (FR-A701)
The life of the inverter is
influenced by surrounding air
temperature. The surrounding
air temperature should be as low
as possible within the
permissible range. This must be
noted especially when the
inverter is installed in an
enclosure. (Refer to page 6)
Wrong wiring might lead to
damage of the inverter. The
control signal lines must be kept
fully away from the main circuit
to protect them from noise.(Refer
to page 12)
EMC filter (ferrite core)
(FR-BLF)
Install a noise filter to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about 1MHz to 10MHz.
When more wires are passed through, a more
effective result can be obtained. The total number of
wires passed through should be 4T or more.
EMC filter (capacitor)
(FR-BIF)
Reduces the radio noise.
Devices connected to the output
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the output
side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the motor and inverter.
: Install these options as required.
R/L1 S/L2 T/L3
Earth
(Ground)
UWV
Earth (Ground)
EMC filter (ferrite core)
(FR-BLF)
Install a noise filter to
reduce the
electromagnetic noise
generated from the
inverter.
Effective in the range
from about 1MHz to
10MHz. A wire should be
wound four turns at a
maximum.
Motor
CAUTION
·
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side. This will cause the
inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them.
· This inverter has a built-in AC reactor (FR-HAL) and a circuit type specified in Harmonic suppression guideline in Japan is threephase bridge (capacitor smoothed) and with reactor (AC side). (Refer to page 39) Do not use an AC reactor (FR-HAL) of a standalone option except following purpose. (Note that overload protection of the converter may operate when a thyristor load is
connected in the power supply system. To prevent this, always install an optional stand-alone AC reactor (FR-HAL).) A DC
reactor (FR-HEL) can not be connected to the inverter.
· Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, connecting a capacitor type filter will reduce electromagnetic
wave interference.
· Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
2
Inverter and peripheral devices
1.2.1Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor Output
(kW)
*1
5.5FR-A721-5.5K40AS-N20, N21
7.5FR-A721-7.5K50AS-N25
11FR-A721-11K75AS-N35
15FR-A721-15K100AS-N50
18.5FR-A721-18.5K125AS-N50
22FR-A721-22K150AS-N65
30FR-A721-30K175AS-N80
37FR-A721-37K225AS-N125
45FR-A721-45K300AS-N150
55FR-A721-55K350AS-N180
400V class
Motor Output
(kW)
*1
5.5FR-A741-5.5K20AS-N11, N12
7.5FR-A741-7.5K30AS-N20, N21
11FR-A741-11K40AS-N20, N21
15FR-A741-15K50AS-N20, N21
18.5FR-A741-18.5K60AS-N25
22FR-A741-22K75AS-N25
30FR-A741-30K100AS-N50
37FR-A741-37K125AS-N50
45FR-A741-45K150AS-N65
55FR-A741-55K175AS-N80
*1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC/400VAC 50Hz.
*2 Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed Class RK5 or Class T
type fuse or UL 489 molded case circuit breaker (MCCB) that is suitable for branch circuit protection.
(Refer to page 199.)
*3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC
with class AC-3 rated current for the motor rated current.
Applicable Inverter ModelBreaker Selection*2Input Side Magnetic Contactor*3
Applicable Inverter ModelBreaker Selection*2Input Side Magnetic Contactor*3
MCCBINV
MCCBINV
IM
IM
1
OUTLINE
CAUTION
· When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable according to the motor output.
· When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
3
Method of removal and reinstallation of
the front cover
1.3Method of removal and reinstallation of the front cover
•Removal of the operation panel
1) Loosen the two screws on the operation panel.
(These screws cannot be removed.)
When reinstalling the operation panel, insert it straight to reinstall securely and tighten the fixed screws of the
operation panel.
2) Push the left and right hooks of the operation panel
and pull the operation panel toward you to remove.
•Removal of the front cover
1) Remove installation screws on the front cover
1 to remove the front cover 1.
Front cover 1
3) Pull the front cover 2 toward you to remove by pushing an installation hook on the right side
using left fixed hooks as supports.
2) Loosen the installation screws of the
front cover 2.
Front cover 2
Installation hook
4
•Reinstallation of the front cover
1) Insert the two fixed hooks on the left side of the
front cover 2 into the sockets of the inverter.
3) Fix the front cover 2 with the installation screws.4) Fix the front cover 1 with the installation
Method of removal and reinstallation of
the front cover
2) Using the fixed hooks as supports, securely press the
front cover 2 against the inverter.
(Although installation can be done with the operation
panel mounted, make sure that a connector is
securely fixed.)
Front cover 2Front cover 2
screws.
Front cover 2
Front cover 1
REMARKS
· For the 55K, the front cover 1 is separated into two parts.
CAUTION
1. Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.
2. The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter. Before
reinstalling the front cover, check the serial numbers to ensure that the cover removed is reinstalled to the inverter from where
it was removed.
1
OUTLINE
5
Installation of the inverter and enclosure
design
1.4Installation of the inverter and enclosure design
When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the
environment of an operating place, and others must be fully considered to determine the enclosure structure, size and
equipment layout. The inverter unit uses many semiconductor devices. To ensure higher reliability and long period of
operation, operate the inverter in the ambient environment that completely satisfies the equipment specifications.
1.4.1Inverter installation environment
The inverter consists of precision mechanical and electronic parts. Never install or handle it in any of the following
conditions as doing so could cause an operation fault or failure.
Vibration (5.9m/s2 or more
Direct sunlight
at 10 to 55Hz (directions of
X, Y, Z axes))
High temperature,
high humidity
Horizontal placement
Vertical mounting
(When installing two or
more inverters, install
them in parallel.)
Transportation by
holding the front cover
Oil mist, flammable
gas, corrosive gas,
fluff, dust, etc.
Mounting to
combustible material
As the inverter installation environment should satisfy the standard specifications indicated in the following table,
operation in any place that does not meet these conditions not only deteriorates the performance and life of the
inverter, but also causes a failure. Refer to the following points and take adequate measures.
Environmental standard specifications of inverter
ItemDescription
Surrounding air
temperature
Ambient humidity90% RH maximum (non-condensing)
AtmosphereFree from corrosive and explosive gases, dust and dirt
Maximum Altitude1,000m or less
Vibration
-10°C to +50°C (non-freezing)
2
5.9m/s
or less at 10 to 55Hz (directions of X, Y, Z axes)
6
Installation of the inverter and enclosure
design
(1) Temperature
The permissible surrounding air temperature of the inverter is between -10°C and +50°C. Always operate the inverter
within this temperature range. Operation outside this range will considerably shorten the service lives of the
semiconductors, parts, capacitors and others. Take the following measures so that the surrounding air temperature of
the inverter falls within the specified range.
1) Measures against high temperature
• Use a forced ventilation system or similar cooling system. (Refer to page 9.)
• Install the enclosure in an air-conditioned electrical chamber.
• Block direct sunlight.
• Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.
• Ventilate the area around the enclosure well.
2) Measures against low temperature
• Provide a space heater in the enclosure.
• Do not power off the inverter. (Keep the start signal of the inverter off.)
3) Sudden temperature changes
• Select an installation place where temperature does not change suddenly.
• Avoid installing the inverter near the air outlet of an air conditioner.
• If temperature changes are caused by opening/closing of a door, install the inverter away from the door.
(2) Humidity
Normally operate the inverter within the 45 to 90% range of the ambient humidity. Too high humidity will pose problems
of reduced insulation and metal corrosion. On the other hand, too low humidity may produce a spatial electrical
breakdown. The insulation distance specified in JEM1103 "Control Equipment Insulator" is defined as humidity 45 to
85%.
1) Measures against high humidity
• Make the enclosure enclosed, and provide it with a hygroscopic agent.
• Take dry air into the enclosure from outside.
• Provide a space heater in the enclosure.
2) Measures against low humidity
What is important in fitting or inspection of the unit in this status is to discharge your body (static electricity)
beforehand and keep your body from contact with the parts and patterns, besides blowing air of proper humidity into
the enclosure from outside.
3) Measures against condensation
Condensation may occur if frequent operation stops change the in-enclosure temperature suddenly or if the outsideair temperature changes suddenly.
Condensation causes such faults as reduced insulation and corrosion.
• Take the measures against high humidity in 1).
• Do not power off the inverter. (Keep the start signal of the inverter off.)
1
OUTLINE
(3) Dust, dirt, oil mist
Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due
to moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged filter.
In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated
insulation and short circuit in a short time.
Since oil mist will cause similar conditions, it is necessary to take adequate measures.
Countermeasures
• Place in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 9.)
• Purge air.
Pump clean air from outside to make the in-enclosure pressure higher than the outside-air pressure.
7
Installation of the inverter and enclosure
design
(4) Corrosive gas, salt damage
If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and parts will corrode or
the relays and switches will result in poor contact.
In such places, take the measures given in Section (3).
(5) Explosive, flammable gases
As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure.
In places where explosion may be caused by explosive gas, dust or dirt, an enclosure cannot be used unless it
structurally complies with the guidelines and has passed the specified tests. This makes the enclosure itself expensive
(including the test charges).
The best way is to avoid installation in such places and install the inverter in a non-hazardous place.
(6) Highland
Use the inverter at the altitude of within 1000m.
If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate
dielectric strength.
(7) Vibration, impact
The vibration resistance of the inverter is up to 5.9m/s2 at 10 to 55Hz frequency (directions of X, Y, Z axes) and 1mm
amplitude.
Vibration or impact, if less than the specified value, applied for a long time may make the mechanism loose or cause
poor contact to the connectors.
Especially when impact is imposed repeatedly, caution must be taken as the part pins are likely to break.
Countermeasures
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from sources of vibration.
8
Installation of the inverter and enclosure
design
1.4.2Cooling system types for inverter enclosure
From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps,
resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature
lower than the permissible temperatures of the in-enclosure equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method.
1) Cooling by natural heat dissipation from the enclosure surface (Totally enclosed type)
2) Cooling by heat sink (Aluminum heatsink, etc.)
3) Cooling by ventilation (Forced ventilation type, pipe ventilation type)
4) Cooling by heat exchanger or cooler (Heat pipe, cooler, etc.)
Cooling SystemEnclosure StructureComment
Natural
cooling
Forced
cooling
Natural ventilation
(Enclosed, open type)
Natural ventilation (Totally
enclosed type)
Heatsink cooling
Forced ventilation
Heat pipeTotally enclosed type for enclosure downsizing.
Heatsink
INV
INV
INV
INV
Heat
pipe
INV
Low in cost and generally used, but the enclosure size
increases as the inverter capacity increases. For
relatively small capacities.
Being a totally enclosed type, the most appropriate for
hostile environment having dust, dirt, oil mist, etc. The
enclosure size increases depending on the inverter
capacity.
Having restrictions on the heatsink mounting position
and area, and designed for relative small capacities.
For general indoor installation. Appropriate for enclosure
downsizing and cost reduction, and often used.
1
OUTLINE
9
Installation of the inverter and enclosure
design
1.4.3Inverter placement
(1) Installation of the Inverter
Installation on the enclosure
CAUTION
⋅ When encasing multiple inverters, install them in parallel as a cooling measure.
⋅ Install the inverter vertically.
Vertical
Refer to the clearances below.
(2) Clearances around the inverter
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
Surrounding air temperature and humidity
Measurement
position
Inverter
5cm
Measurement
position
5cm
5cm
Temperature: -10°C to 50°C
Ambient humidity: 90% RH
5cm
or more
10cm or more
5cm
or more
10cm or more
maximum
Leave enough clearances and take
cooling measures.
REMARKS
For replacing the cooling fan, 30cm of space is necessary in front of the inverter. Refer to page 175 for fan replacement.
Clearances (side)Clearances (front)
5cm
Inverter
or
more
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
10
Installation of the inverter and enclosure
design
(4) Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter
should be heat resistant.
(5) Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown in the figure
below (a). When it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides
since heat from the bottom inverters can increase the temperatures in the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter higher
than the permissible value by providing ventilation and increasing the enclosure size.
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow. (Air
passes through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
InverterInverter
1
OUTLINE
<Good example><Bad example>
Placement of ventilation fan and inverter
11
Terminal connection diagram
2WIRING
2.1Terminal connection diagram
Sink logic
Main circuit terminal
Control circuit terminal
MCCB
MC
*6*6
R/L1
Three-phase AC
power supply
Jumper
*1. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to Chapter 4 of the Instruction
Manual (Applied))
Forward
rotation
start
Reverse
rotation
start
Start self-
holding selection
High speed
Multi-speed
selection
*2. JOG terminal can be used
as pulse train input terminal.
Use Pr. 291 to select
JOG/pulse.
Middle
speed
Low speed
Jog operation
Second function selection
*3. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
Output stop
Reset
after instantaneous
power failure
Contact input common
24VDC power supply
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
*
Terminal input specifications
4.
can be changed by analog
input specifications
switchover (Pr. 73, Pr. 267).
Set the voltage/current input
switch in the OFF position to
select voltage input (0 to 5V/0
to10V) and ON to select
current input (4 to 20mA).
(Refer to Chapter 4 of the
Instruction Manual (Appl ied))
*5
3
Ω
1
Auxiliary
input
Terminal
4 input
(Current
input)
2
(+)
(-)
(+)
(-)
Connector
for plug-in option
connection
*5
. It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
*1
Earth
(Ground)
S/L2
T/L3
R1/L11
S1/L21
Main circuit
Control circuit
STF
STR
STOP
RH
RM
RL
JOG
*2
RT
MRS
RES
*3
AU
AU
PTC
CS
SD
PC
10E(+10V)
10(+5V)
2
5
1
4
Option connector 1
Option connector 2
Option connector 3
SOURCE
*4
Voltage/current
input switch
ON
OFF
0 to 5VDC
0 to 10VDC
0 to 20mADC
(Initial value)
selectable
(Analog common)
±
10VDC
0 to
0 to ±5VDC
selectable
4 to 20mADC
0 to 5VDC
0 to 10VDC
selectable
SINK
2
4
*4
(Initial value)
*4
(Initial value)
*4
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire
of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
N/-P/+
C1
B1
A1
C2
B2
A2
RUN
SU
IPF
OL
FU
SE
PU
connector
USB
connector
FM
SD
AM
TXD+
TXD-
RXD+
RXD-
SG
Terminating
VCC
resistor
U
V
W
*6. Do not connect any options to P/+ and
N/-.
Relay output 1
(Fault output)
Terminal functions
vary with the output
terminal assignment
(Pr. 195, Pr. 196)
(Refer to Chapter 4 of the
Instruction Manual
(Applied))
Relay output 2
Open collector output
Running
Up to frequency
Instantaneous
power failure
Overload
Terminal functions
vary with the output
terminal assignment
(Pr. 190 to Pr. 194)
(Refer to Chapter 4 of the
Instruction Manual
(Applied))
Frequency detection
Open collector output common
/source common
Sink
*
7. It is not necessary when
calibrating the indicator
from the operation panel.
*8
5
Calibration
resistor *7
+
-
(+)
Analog signal output
(0 to 10VDC)
(-)
RS-485 terminals
Data transmission
Data reception
GND
(Permissible load
5V
current 100mA)
Motor
IM
Earth (Ground)
Relay output
*8. FM terminal can be
used for pulse train
output of open
collector output
using Pr.291.
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale
12
2.2Main circuit terminal specifications
2.2.1Specification of main circuit terminal
Main circuit terminal specifications
Termina l
Symbol
R/L1,
S/L2,
T/L3
U, V, WInverter outputConnect a three-phase squirrel-cage motor.
R1/L11,
S1/L21
P/+, N/-DC terminalDo not connect any options.
Termina l N ameDescription
AC power inputConnect to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers from terminals R/L1-R1/
L11 and S/L2-S1/L21 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with the
Power supply for
control circuit
Earth (Ground)
main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power (R/
L1, S/L2, T/L3) is also turned off when the power supply for control circuit
(R1/L11, S1/L21) is off.
The following power supply capacities are required to supply power
separately from R1/L11 and S1/L21:
90VA for 15K or lower, 100VA for 18.5K or higher
For earthing (grounding) the inverter chassis. Must be earthed
(grounded).
2
WIRING
13
Main circuit terminal specifications
2.2.2Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
FR-A721-5.5K, 7.5KFR-A721-11K, 15K
R1/L11 S1/L21
Screw size
(M4)
Screw size (M5)
R/L1 S/L2 T/L3
N/-
Charge lamp
Jumper
Screw size (M5 for 11K, M6 for 15K)
P/+
IM
Power supply
FR-A721-18.5K to 45KFR-A721-55K
Motor
Power supply
Screw size (M4)
R1/L11 S1/L21
Charge
lamp
Jumper
Screw size
R/L1 S/L2 T/L3
(M4)
R1/L11 S1/L21
Charge lamp
Jumper
N/-P/+
IM
Motor
Screw size (M4)
R1/L11 S1/L21
Charge
lamp
Jumper
Screw size
(18.5K/22K/30K: M8, 37K/45K: M10)
R/L1 S/L2
Power supply
T/L3
IM
Motor
Screw size
(M6 for 18.5K, 22K and
30K M8 for 37K and 45K)
N/-
P/+
Screw size (M12)
R/L1 S/L2 T/L3
Power supply
IM
Motor
N/-
Screw size (M8)
P/+
14
400V class
FR-A741-5.5K, 7.5KFR-A741-11K, 15K
Screw size (M4)
R1/L11
S1/L21
Charge lamp
Jumper
Screw size (M4)
Main circuit terminal specifications
S1/L21
R1/L11
Screw size (M4)
Charge lamp
Jumper
P/+
R/L1 S/L2 T/L3
N/-
IM
Power supply
FR-A741-18.5K to 45KFR-A741-55K
Screw size (M6 for 18.5K to 30K
M8 for 37K and 45K)
Motor
Screw size (M4)
S1/L21
R1/L11
Charge lamp
Jumper
Screw size (M5)
R/L1 S/L2 T/L3
Power supply
IM
Motor
S1/L21
R1/L11
P/+
N/-
Screw size (M4)
Charge lamp
Jumper
2
WIRING
R/L1 S/L2 T/L3
Power supply
IM
Motor
N/-
P/+
R/L1 S/L2 T/L3
Screw size (M8)
N/-
P/+
IM
Power supply
CAUTION
· The power supply cables must be connected to R/L1, S/L2, T/L3. (Phase sequence needs not to be matched.) Never connect
the power cable to the U, V, W of the inverter. Doing so will damage the inverter.
· Connect the motor to U, V, W. At this time, turning ON the forward rotation switch (signal) rotates the motor in the
counterclockwise direction when viewed from the motor shaft.
Motor
15
Main circuit terminal specifications
2.2.3Cables and wiring length
(1) Applicable cable size
Select the recommended cable size to ensure that a voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor
torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
*1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of
75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
*2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the
surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the United States.)
*3For the 15K or lower, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the 18.5K or higher, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C.
Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
*1The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of
Assumes that the surrounding air temperature is
*2For the 45K or lower, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of
Assumes that the surrounding air temperature is
For the 55K, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of
the surrounding air temperature is
(Selection example for use mainly in the United States.)
*3For the 45K or lower, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes
that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 55K, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. Assumes that
the ambient temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
40°C
50°C
or less and the wiring distance is 20m or less.
40°C
or less and the wiring distance is 20m or less.
or less and wiring is performed in an enclosure.
.
.
16
The line voltage drop can be calculated by the following formula:
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Notes on earthing (grounding)
z Always earth (ground) the motor and inverter.
1)Purpose of earthing (grounding)
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before
use.
An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to
manufacture an insulating material that can shut off a leakage current completely, and actually, a slight current flow
into the case. The purpose of earthing (grounding) the case of an electrical apparatus is to prevent operator from
getting an electric shock from this leakage current when touching it.
To avoid the influence of external noises, this earthing (grounding) is important to audio equipment, sensors,
computers and other apparatuses that handle low-level signals or operate very fast.
2)Earthing (grounding) methods and earthing (grounding) work
As described previously, earthing (grounding) is roughly classified into an electrical shock prevention type and a
noise-affected malfunction prevention type. Therefore, these two types should be discriminated clearly, and the
following work must be done to prevent the leakage current having the inverter's high frequency components from
entering the malfunction prevention type earthing (grounding):
(a) If possible, use (l) independent earthing (grounding) in figure below for the inverter. If independent earthing
(grounding) is not available, use (ll) joint earthing (grounding) in the figure below which the inverter is
connected with the other equipment at an earthing (grounding) point. The (lll) common earthing (grounding)
as in the figure below, which inverter shares a common earth (ground) cable with the other equipment, must
be avoided.
A leakage current including many high frequency components flows in the earth (ground) cables of the
inverter and inverter-driven motor. Therefore, use the independent earthing (grounding) and separated the
earthing (grounding) cable of the inverter from equipments sensitive to EMI.
In a high building, it may be effective to use the EMI prevention type earthing (grounding) connecting to an
iron structure frame, and electric shock prevention type earthing (grounding) with the independent earthing
(grounding) together.
(b) This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national
and local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable
standards).
Use a neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard.
(c) Use the thickest possible earth (ground) cable. The earth
indicated in the table on the previous page.
(d) The grounding point should be as near as possible to the inverter, and the ground wire length should be as
short as possible.
(e) Run the earth (ground) cable as far away as possible from the I/O wiring of equipment sensitive to noises and
run them in parallel in the minimum distance.
(ground) cable should be of not less than the size
The overall wiring length for the connection to a single motor or multiple motors should be within 500m (with unshielded
wires).
(The wiring length should be within 100m for the operation under vector control or when using shielded wires.)
Total wiring length
500m or less
300m
300m
300m + 300m = 600m
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at
the motor terminals, deteriorating the insulation of the motor.
Refer to page 42 for measures against deteriorated insulation.
CAUTION
· Especially with the long-distance wiring and the wiring with shielded wires, the inverter may be affected by a charging current
caused by the stray capacitance from the wiring, leading to a malfunction of the overcurrent protective function or the fast response
current limit function, or an inverter fault. It may also lead to a malfunction or fault of the equipment connected on the inverter output
side. Stray capacitance from the wiring varies with its wiring conditions. The overall wiring length specified above is only a reference
value. If the fast-response current limit function malfunctions, disable this function. (For Pr. 156 Stall prevention operation selection, refer
to Chapter 4 of the Instruction Manual (Applied).)
· For explanation of the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) and sine wave filter (MT-BSL/BSC), refer to the
manual of each option.
· Do not connect a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) during the operation under vector control.
(4) Cable size of the control circuit power supply (terminal R1/L11, S1/L21)
· Terminal screw size: M4
· Cable size: 0.75mm
· Tightening torque: 1.5N·m
2
to 2mm
2
18
Main circuit terminal specifications
2.2.4When connecting the control circuit and the main circuit separately
to the power supply
<Connection diagram>When fault occurs, opening of the electromagnetic contactor (MC) on the
MC
Remove the jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
Inverter
inverter power supply side results in power loss in the control circuit,
disabling the fault output signal retention. Terminals R1/L11 and S1/L21 are
provided to hold a fault signal. In this case, connect the power supply
terminals R1/L11 and S1/L21 of the control circuit to the input side of the MC.
Do not connect the power cable to incorrect terminals. Doing so may
damage the inverter.
1)Remove the upper screws.
2)Remove the lower screws.
3)Pull the jumper toward you to
remove.
Connect the separate power supply
4)
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
R1/
L11
T/L3
S/L2
R/L1
MC
Main power supply
Power supply
terminal block for
the control circuit
S1/
L21
Power supply
terminal block
for the control circuit
FR-A721-5.5K to 15K
FR-A741-5.5K to 15K
3)
Power supply terminal block
for the control circuit
R1/L11
1)
2)
4)
FR-A721-18.5K to 55K
FR-A741-18.5K to 55K
S1/L21
2
CAUTION
· Do not turn off the control power (terminals R1/L11 and S1/L21) with the main circuit power (R/L1, S/L2, T/L3) on. Doing so may
damage the inverter. Make up a circuit which will switch off the main circuit power supply terminals R/L1, S/L2, T/L3 when the
control circuit power supply terminals R1/L11, S1/L21 are switched off.
· Be sure to use the inverter with the jumpers across terminals R/L1 and R1/L11 and across terminals S/L2 and S1/L21 removed
when supplying power from other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
input side of the MC.
· When separate power is supplied from R1/L11 and S1/L21, the power capacity necessary for the 15K or lower is 90VA, for the
18.5K or higher is 100VA.
· If the main circuit power is switched OFF (for 0.1s or more) then ON again, the inverter resets and a fault output will not be held.
WIRING
19
Control circuit specifications
2.3Control circuit specifications
2.3.1Control circuit terminals
indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to Chapter 4 of
the Instruction Manual (Applied).)
(1) Input signals
Terminal
Symbol
Type
STF
STR
STOP
RH,
RM, RL
JOG
RT
MRSOutput stop
RESReset
AU
Contact input
CS
SD
PC
Ter minal
Name
Forward
rotation start
Reverse
rotation start
Start selfholding
selection
Multi-speed
selection
Jog mode
selection
Pulse train
input
Second
function
selection
Terminal 4
input
selection
PTC input
Selection of
automatic
restart after
instantaneous
power failure
Contact input
common (sink)
(initial setting)
External
transistor
common
(source)
24VDC power
supply
common
External
transistor
common (sink)
(initial setting)
Contact input
common
(source)
24VDC power
supply
Description
Turn ON the STF signal to start forward
rotation and turn it OFF to stop.
Turn ON the STR signal to start reverse
rotation and turn it OFF to stop.
Turn ON the STOP signal to self-hold the start signal.*2
Multi-speed can be selected according to the combination of RH,
RM and RL signals.
Turn ON the JOG signal to select Jog operation (initial setting)
and turn ON the start signal (STF or STR) to start Jog operation.
JOG terminal can be used as pulse train input terminal. To use as
pulse train input terminal, the Pr. 291 setting needs to be changed.
k
(maximum input pulse: 100
Turn ON the RT signal to select second function.
When the second function such as "second torque boost" and
"second V/F (base frequency)" are set, turning on the RT signal
selects these functions.
Turn ON the MRS signal (20ms or more) to stop the inverter output.
Use to shut off the inverter output when stopping the motor by
electromagnetic brake.
Used to reset fault output provided when fault occurs.
Turn ON the RES signal for more than 0.1s, then turn it OFF.
Initial setting is for reset always. By setting Pr. 75, reset can be set
to enabled only at fault occurrence. Recover about 1s after reset
is cancelled.
Terminal 4 is valid only when the AU signal is turned ON. (The
frequency setting signal can be set between 4 and 20mADC.)
Turning the AU signal ON makes terminal 2 (voltage input) invalid.
AU terminal is used as PTC input terminal (thermal protection of
the motor). When using it as PTC input terminal, set the AU/PTC
switch to PTC.
When the CS signal is left ON, the inverter restarts automatically
at power restoration. Note that restart setting is necessary for this
operation. In the initial setting, a restart is disabled.
(Refer to Pr. 57 Restart coasting time in Chapter 4 of
Instruction Manual (Applied).)
Common terminal for contact input terminal (sink logic) and terminal
FM.
When connecting the transistor output (open collector output),
such as a programmable controller, when source logic is
selected, connect the external power supply common for
transistor output to this terminal to prevent a malfunction caused
by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (PC
terminal).
Isolated from terminals 5 and SE.
When connecting the transistor output (open collector output), such
as a programmable controller, when sink logic is selected, connect
the external power supply common for transistor output to this
terminal to prevent a malfunction caused by undesirable currents.
Common terminal for contact input terminal (source logic).
Can be used as 24VDC 0.1A power supply.
pulses/s)
When the STF and STR
signals are turned ON
simultaneously, the stop
command is given.
the
Rated
Specifications
Input resistance
4.7kΩ
Voltage at opening:
21 to 27VDC
Contacts at shortcircuited: 4 to
6mADC
Input resistance
2kΩ
Contacts at shortcircuited: 8 to
13mADC
Input resistance
4.7kΩ
Voltage at opening:
21 to 27VDC
Contacts at shortcircuited: 4 to
6mADC
--------------- -----—
Power supply
voltage range 19.2
to 28.8VDC
Permissible load
current 100mA
Refer to
page
92
94
*2
*2
*2
*2
141
98
*2
*2
24
20
Control circuit specifications
Terminal
Symbol
Typ e
10E
10
2
4
Frequency setting
1
5
*1Set Pr. 73, Pr. 267, and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage signal with voltage/current input switch ON (current input is selected) or a current signal with switch OFF (voltage input is
selected) could cause component damage of the inverter or analog circuit of signal output devices.
*2Refer to Chapter 4 of
Terminal
Name
Frequency
setting power
supply
Frequency
setting
(voltage)
Frequency
setting
(current)
Frequency
setting
auxiliary
Frequency
setting
common
the Instruction Manual (Applied).
Description
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications of terminal 2 when connecting it
to terminal 10E. (Refer to Pr. 73 Analog input selection in Chapter 4 of
the Instruction Manual (Applied).)
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes input
and output proportional. Use Pr. 73 to switch from among input 0
to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.
Set the voltage/current input switch in the ON position to select
current input (0 to 20mA).
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA makes input and output
proportional. This input signal is valid only when the AU signal is
ON (terminal 2 input is invalid).
Use Pr. 267 to switch from among input 4 to 20mA (initial setting),
0 to 5VDC, and 0 to 10VDC.
Set the voltage/current input switch in the OFF position to select
voltage input (0 to 5V/0 to 10V).
(Refer to Chapter 4 of the Instruction Manual (Applied).) Use Pr.
858 to switch terminal functions.
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use Pr. 73 to switch between the
input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Use Pr. 868 to switch terminal functions.
Common terminal for frequency setting signal (terminal 2, 1 or 4)
and analog output terminal AM. Do not earth (ground).
*1
*1
Rated
Specifications
10VDC
Permissible load
current 10mA
5VDC
Permissible load
current 10mA
Voltage input:
Input resistance
10kΩ ± 1kΩ
Maximum
permissible voltage
20VDC
Current input:
Input resistance
245Ω ± 5Ω
Maximum
permissible current
30mA
Voltage/current
input switch
switch1
switch2
Input resistance
10kΩ ± 1kΩ
Maximum
permissible voltage
± 20VDC
4
------------- -------------
2
Refer to
page
*2
88, 96
88, 96
90, 98
*2
2
(2) Output signals
Terminal
Symbol
Type
A1,
B1,
C1
Relay
A2,
B2,
C2
Terminal
Name
Relay output 1
(alarm output)
Relay output 21 changeover contact output*2
Description
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Fault: No conduction between B and C (conduction between A
and C)
Normal: Conduction between B and C (No conduction between
A and C)
Switched low when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5Hz). Switched
high during stop or DC injection brake operation.
Switched low when the output
frequency reaches within the range of
±10% (initial value) of the set frequency.
Switched high during acceleration/
deceleration and at a stop.*1
Switched low when stall prevention is
activated by the stall prevention
function. Switched high when stall
prevention is cancelled.
*1
Switched low when an instantaneous
power failure and under voltage
protections are activated.
*1
Switched low when the inverter output
frequency is equal to or higher than the
*1
Alarm code (4bit)
output
Permissible load
24VDC (27VDC
maximum) 0.1A
(A voltage drop is
2.8V maximum
when the signal is
on.)
*1 Low is when the
open collector
output transistor is
ON (conducts).
High is when the
transistor is OFF
(does not
conduct).
preset detected frequency and high
when less than the preset detected
frequency.
*1
C o m m o n t e r m i n a l f o r t e r m i n a l s R U N , S U , O L , I P F, F U-------------------------
Permissible load
current 2mA
1440pulses/s at
60Hz
Maximum output
pulse: 50kpulses/s
Permissible load
current : 80mA
Output signal 0 to
10VDC
Permissible load
current 1mA
(load impedance
Select one e.g. output frequency from
monitor items. Not output during
inverter reset.
The output signal is proportional to the
magnitude of the corresponding
monitoring item.
To set a full-scale value for monitoring
the output frequency and the output
current, set Pr. 56 and Pr.158.
*2
Output item:
Output frequency
(initial setting)
Signals can be output
from the open
collector terminals by
setting Pr. 291.
Output item:
Output frequency
(initial setting)
10kΩ or more)
Resolution 8 bit
*2
*2
*2
*2
*2
*2
*2
*2
*2 Refer to Chapter 4 of the Instruction Manual (Applied).
(3) Communication
Type
RS-485
USB
Terminal
Symbol
--------------- -----
TXD+
TXD-
RXD+
RXD-
RS-485 terminals
SG
--------------- -----
Terminal
Name
PU
connector
Inverter
transmission
terminal
Inverter
reception
terminal
Earth (Ground)
USB
connector
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485 (RS-485)
. Transmission format: Multidrop link
. Communication speed : 4800 to 38400bps
. Overall length: 500m
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed : 300 to 38400bps
Overall length: 500m
The FR Configurator can be used by connecting the inverter to the personal
computer through USB.
Interface:Conforms to USB1.1
Transmission speed:12Mbps
Connector:USB B connector (B receptacle)
Description
Refer to
page
26
26
27
22
Control circuit specifications
2.3.2Changing the control logic
The input signals are set to sink logic (SINK) when shipped from the factory.
To change the control logic, the jumper connector on the back of the control circuit terminal block must be moved to the
other position.
(The output signals may be used in either the sink or source logic independently of the jumper connector position.)
1) Loosen the two installation screws in both ends of the control circuit terminal block. (These screws cannot be
removed.)
Pull down the terminal block from behind the control circuit terminals.
2) Change the jumper connector set to the sink logic (SINK) on the rear panel of the control circuit terminal block to
source logic (SOURCE).
Jumper connector
3) Using care not to bend the pins of the inverter's control circuit connector, reinstall the control circuit terminal block
and fix it with the mounting screws.
CAUTION
1. Make sure that the control circuit connector is fitted correctly.
2. While power is ON, never disconnect the control circuit terminal block.
2
WIRING
23
Loading...
+ 229 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.