Installation manual for the E1000 series operator terminals
Foreword
The E1000 operator terminal is developed to satisfy the demands of humanmachine communication. Built-in functions such as displaying and controlling text,
dynamic indication, time channels, alarm and recipe handling are included.
The operator terminal work, for the most part, in an object-oriented way, making it
easy to understand and use. The configuration operation of the terminal is made in
a personal computer, using the configuration tool E-Designer. The project is then
transferred and stored in the operator terminal.
The operator terminal can be connected to many types of automation equipment,
such as PLCs, servos or drives. In this manual the expression “the controller“ is used
as a general term for the connected equipment.
This manual explains how to install the operator terminal. Please refer to the reference manual for further information.
The information in this document is subject to change without notice and is provided as available at the time
of printing. The manufacturer reserves the right to change any information without updating this publication.
assumes no responsibility for any errors that may appear in this document.
Read the entire installation manual prior to installing and using this equipment.
Only qualified personnel may install, operate or repair this equipment. The manufacturer is not responsible
for modified, altered or renovated equipment.
Because the equipment has a wide range of applications, users must acquire the appropriate knowledge to use
the equipment properly in their specific applications.
Persons responsible for the application and the equipment must themselves ensure that each application is in
compliance with all relevant requirements, standards and legislation in respect to configuration and safety.
Only parts and accessories manufactured according to specifications set by The manufacturer may be used.
THE MANUFACTURER SHALL NOT BE LIABLE TO ANYONE FOR ANY DIRECT, INDIRECT,
SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE
INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL BE THE REPAIR,
REPLACEMENT, OR REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE
REMEDY SHALL BE AT THE SOLE DISCRETION OF THE MANUFACTURER.
5.3 E1032 Text Strip ............................................................................ 19
Mitsubishi Electric, MA00816
Table of Contents
Mitsubishi Electric, MA00816
Safety Precautions
1Safety Precautions
Both the installer and the owner and/or operator of the operator terminal must read
and understand this installation manual.
1.1UL Installation
Power, input and output (I/O) wiring must be in accordance with Class 1, Division
2 wiring methods (Article 501-4 (b) of the National Electric Code, NFPA 70) and
in accordance with the authority having jurisdiction.
1.2General
– Only qualified personnel may install or operate the operator terminal.
– The operator terminal must be installed according to the installation instructions.
– The operator terminal is designed for stationary installation on a plane surface,
where the following conditions are fulfilled:
• no high explosive risks
• no strong magnetic fields
•no direct sunlight
• no large, sudden temperature changes
– Never allow fluids, metal filings or wiring debris to enter any openings in the
operator terminal. This may cause fire or electrical shock.
– The operator terminal fulfills the requirements of article 4 of EMC directive
89/336/EEC.
– Storing the operator terminal where the temperature is lower/higher than
recommended in this manual can cause the LCD display liquid to congeal/become
isotopic.
– The LCD display liquid contains a powerful irritant. In case of skin contact, wash
immediately with plenty of water. In case of eye contact, hold the eye open, flush
with plenty of water and get medical attention.
– The supplier is not responsible for modified, altered or reconstructed equipment.
– Use only parts and accessories manufactured according to specifications of the
supplier.
– Peripheral equipment must be appropriate for the application and location.
– The figures in this manual serves an illustrative purpose. Because of the many
variables associated with any particular installation, the supplier cannot assume
responsibility for actual use based on the figures.
– The supplier neither guarantees that the operator terminal is suitable for your
particular application, nor assumes responsibility for your product design,
installation or operation.
1.3During Use
– Keep the operator terminal clean.
– Emergency stop and other safety functions may not be controlled from the
operator terminal.
– Do not use too much force or sharp objects when touching the keys, display etc.
Mitsubishi Electric, MA008165
Safety Precautions
1.4Service and Maintenance
– Only qualified personnel should carry out repairs.
– The agreed warranty applies.
– Before carrying out any cleaning or maintenance operations, disconnect the
equipment from the electrical supply.
– Clean the display and surrounding front cover with a soft cloth and mild
detergent.
– Replacing the battery incorrectly may result in explosion. Only use batteries
recommended by the supplier.
1.5Dismantling and Scrapping
– The operator terminal or parts thereof shall be recycled according to local
regulations.
– The following components contain substances that might be hazardous to health
and the environment: lithium battery, electrolytic capacitor and display.
6Mitsubishi Electric, MA00816
2Installation
2.1Space Requirements
– Installation plate thickness: 1.5 - 7.5 mm (0.06 - 0.3 inch)
– Space requirements when installing the operator terminal:
100 mm
(4.0 inch)
Installation
187 mm
(7.36 inch)
50 mm
(2.0 inch)
100 mm
(4.0 inch)
202 mm
(7.95 inch)
Caution
The openings on the enclosure are for air convection. Do not cover these
openings.
50 mm
(2.0 inch)
(2.24 inch)
100 mm
(4.0 inch)
56.9 mm
2.2Installation Process
1. Unpack and check the delivery. If damage is found, notify the supplier.
Panel cut out 166 x 149 mm
(6.54 x 5.87 inch)
x4
Note:
Place the operator terminal on a stable surface during installation.
Dropping it or letting it fall may cause damage.
2. Place the panel cut out where the operator terminal is to be situated, draw along
the outer sides of the holes and cut according to the markings. If access to the
text strips is needed, add extra space at the left side.
For text strip
14.0 mm
(0.55 inch)
7.0 mm
(0.28 inch)
Mitsubishi Electric, MA008167
Installation
3. Secure the operator terminal in position, using all the fastening holes and the
provided brackets and screws:
x 4
0.5 - 1.0 Nm
4. Connect the cables in the specified order.
A
Use an M5 screw and a grounding conductor (as short as possible)
B
with a cross-section of minimum 2.5 mm
C
D
Caution
Ensure that the operator terminal and the controller system have the
same electrical grounding (reference voltage level), otherwise errors
in communication may occur.
2
.
Caution
- Use only shielded communication cables.
- Separate high voltage cables from signal and supply cables.
Caution
- The operator terminal must be brought to ambient temperature
before it is started up. If condensation forms, ensure that the
operator terminal is dry before connecting it to the power outlet.
- Ensure that the voltage and polarity of the power source is correct.
B
Power
Controller
RS422/
RS485
RS232
24V DC
C
24V DC
D
A
Ethernet
5. Carefully remove the laminated film over the operator terminal display, to avoid
static electricity that could damage the terminal.
8Mitsubishi Electric, MA00816
2.2.1Mode Switches
All mode switches must be in OFF position during operator terminal use.
The mode switches should not be touched unless by qualified personell.
1234
ON DIP
1234
ON DIP
Installation
2.2.2Connections to the Controller
For information about the cables to be used when connecting the operator terminal
to the controller, please refer to the help file for the driver in question.
2.2.3Other Connections and Peripherals
Cables, peripheral equipment and accessories must be suitable for the application
and its environment. For further details or recommendations, please refer to the
supplier.
Mitsubishi Electric, MA008169
Installation
10Mitsubishi Electric, MA00816
Technical Data
3Technical Data
ParameterE1032
Front panel, W x H x D 202 x 187 x 6 mm
Mounting depth56.9 mm (156.9 mm including clearance)
Front panel sealIP 66
Rear panel sealIP 20
Keyboard materialMembrane switch keyboard with metal domes. Overlay film
of Autotex F157 * with print on reverse side. 1 million
operations.
Reverse side materialPowder-coated aluminum
Weight0.875 kg
Serial port RS422/
RS485
Serial port RS232C9-pin D-sub contact, male with standard locking screws 4-40
EthernetShielded RJ 45
USBHost type A (USB 1.1), max output current 500 mA
Flash memory for
application
Real time clock±20 PPM + error because of ambient temperature and supply
Power consumption at
rated voltage
DisplayFSTN-LCD. 240 x 64 pixels, monocrome transflective.
Active area of display,
W x H
FuseInternal DC fuse, 2.0 AT, 5 x 20 mm
Power supply+24V DC (20 - 30V DC). 3-pin jack connection block.
Ambient temperatureVertical installation: 0 ° to +50 °C
Storage temperature-20 ° to +70 °C
Relative humidity5 - 85 % non-condensed
EMC tests on the
operator terminal
UL, cUL approvals
(when product or
packing is marked)
DNVCeritfication in progress
NEMA4x indoor use only
* See section Chemical Resistance for more information.
25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC.
UNC.
12 MB (incl. fonts)
voltage.
Tot al ma x er r or : 1 min/month at 25 °C
Minimum life of the real time clock battery: 3 years
Temperature coefficient: 0.004 ppm/°C
Normal: 0.15 A
Maximum: 0.35 A
LED backlight lifetime at the ambient temperature of
+25 °C: >50,000 h.
127.0 x 33.8 mm
CE: The power supply must conform with the requirements
for SELV or PELV according to IEC 950 or IEC 742.
UL: The power supply must conform with the requirements
for class II power supplies.
Horizontal installation: 0 ° to +40 °C
The operator terminal conforms with the essential protection
requirements in article 4 of the directive 89/336/EEC. Noise
tested according to EN61000-6-3 emission and EN61000-6-2
immunity.
UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only
2
Mitsubishi Electric, MA0081611
Technical Data
12Mitsubishi Electric, MA00816
Chemical Resistance
4Chemical Resistance
4.1Metal Casing
The frame and casing material is powder-coated aluminum. This powder paint
withstands exposure of up to 24 hours duration to the following chemicals without
visible change: