Mitsubishi Electric DXK09ZJ-S, DXK12ZJ-S, DXK18ZJ-S Technical Manual

RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER (Split system, air to air heat pump type)
DXK09ZJ-S DXK12ZJ-S DXK18ZJ-S
Manual No.'11•SRK-T-118
TECHNICAL MANUAL
-
1
-
'11 • SRK-T-118
CONTENTS
1. SPECIFICATIONS
........................................................................................ 3
(2) Outdoor units ....................................................................................... 7
....................................................... 18
(3) Remote controller
................................................................................ 9
......................................................................... 6
(1) Indoor units .......................................................................................... 6
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING .............................................................................. 11
(1) Indoor units .......................................................................................... 11
4. NOISE LEVEL ............................................................................................ 14
(2) Outdoor units ....................................................................................... 12
6. RANGE OF USAGE & LIMITATIONS
................................................................................... 20
7. CAPACITY TABLES
5. PIPING SYSTEM ...................................................................................... 17
.................................................................................. 21
8. APPLICATION DATA
(1) Installation of indoor unit ..................................................................... 21
(2) Installation of outdoor unit .................................................................... 25
9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............... 39
(6) 3D auto operation ............................................................................. 42
(7) Timer operation
.................................................................................. 43
....................................................... 40
(1) Operation control function by remote controller
(5) Flap and louver control ...................................................................... 41
(4) Custom cord switching procedure
......................................................................... 40(3) Auto restart function
(2) Unit ON/OFF button
........................................................................... 40
.................................. 39
(8) Installation location setting ................................................................. 43
(9) Outline of heating operation ................................................................ 44
(11) Outline of automatic operation ........................................................... 45
(10) Outline of cooling operation ............................................................... 45
(12) Protective control function
................................................................... 46
............................................................................... 53
10. MAINTENANCE DATA
..................... 54
(4) Troubleshooting procedure (If the air conditioner runs)
(3) Troubleshooting procedure
(If the air conditioner does not run at all)
........ 53
(1) Cautions
............................................................................................. 53
(2) Items to check before troubleshooting ................................................. 53
(5) Self-diagnosis table ............................................................................. 55
(6) Service mode (Trouble mode access function) ................................... 56
-
2
-
'11 • SRK-T-118
(10) How to make sure of wireless remote controller .................................. 70
(11) Outdoor unit inspection points .............................................................. 71
(8)
Phenomenon observed after shortcircuit, wire breakage on sensor
......... 68
(7) Inspection procedures corresponding to detail of trouble .................... 64
(9) Checking the indoor electrical equipment
........................................... 69
11.1 Instullation of wired remote controller (RC-E4) ............................... 74
11. OPTION PARTS ....................................................................................... 74
11.2 Interface kit (SC-BIKN-E) .................................................................... 80
11.3 Super link E board (SC-ADNA-E) ...................................................... 84
How to read the model name
Example: DXK 09 Z
Series code
Inveter type
Product capacity
Model name DXK : Wall mounted type
DXC : Outdoor unit
J-S
-
3
-
'11 • SRK-T-118
1. SPECIFICATIONS
D
RWA000Z225
GDWD
&23
1RLVH
+HDWLQJ
OHYHO
([WHULRUDSSHDUDQF
HTXLSPHQ
W
HTXLSPHQ
W
FRQWURO
GDW
D
$WWDFKHGOHQJWKRISLSLQJ
&RQQHFWLRQZLULQJ
1RWH 

3XUJLQJLVQRWUHTXLUHGHYHQIRUWKHVKRUWSLSLQJ
+HDWLQJFDSDFLW\ : 0LQᨺ0D[ 3RZHUVXSSO
\
N:
3KDVHᨺ9+]
2SHUDWLRQ
3RZHU &RROLQJ ᨺ FRQVXPSWLRQ +HDWLQJ
$
ᨺ
5XQQLQJ &RROLQJ
9
 FXUUHQW +HDWLQJ 9 ,QUXVKFXUUHQW 9
&RROLQJ  +HDWLQJ
G%
G%
G%$
G%$

6RXQGOHYH
O +L0H/R  3RZHUOHYHO   6RXQGOHYH
O +L0H/R  3RZHUOHYHO  
([WHULRUGLPHQVLRQV+HLJKW[:LGWK['HSWK
PP [[ ;;
H )LQHVQRZ 6WXFFRZKLWH
0XQVHOOFRORU
<QHDUHTXLYDOHQW <QHDUHTXLYDOHQW
1HWZHLJK
W NJ  
5HIULJHUDQ
W
&RPSUHVVRUW\SH4W\ 50%0'(5RWDU\W\SH[ 0RWRU6WDUWLQJPHWKRG  N: /LQHVWDUWLQJ 5HIULJHUDQWRLO ',$021')5((=(0$ 5HIULJHUDQW NJ 5$3UH&KDUJHGXSWRWKHSLSLQJOHQJWKRIP
+HDWH[FKDQJH
U /RXYHUILQVLQQHUJURRYHGWXELQJ 0ILQVLQQHUJURRYHGWXELQJ 5HIULJHUDQWFRQWURO &DSLOODU\WXEHV(OHFWURQLFH[SDQVLRQYDOYH 'HLFHFRQWURO 0LFURFRPSXWHUFRQWURO
$LUKDQGOLQJ
)DQW\SH4W\ 7DQJHQWLDOIDQ[ 3URSHOOHUIDQ[ 0RWRU
$LUIORZ
:
&00
  &RROLQJ +L0H/R  +HDWLQJ +L0H/R 
)UHVKDLULQWDN
H 1RWSRVVLEOH
$LUILOWHU4XDOLW\4XDQWLW\ 3RO\SURS\OHQHQHWZDVKDEOH[
6KRFNYLEUDWLRQDEVRUEH
U
&XVKLRQUXEEHUIRUFRPSUHVVRU
(OHFWULFKHDWHU
2SHUDWLRQ
2SHUDWLRQVZLWFK
:LUHOHVV5HPRWHFRQWUR
O
5RRPWHPSHUDWXUHFRQWURO
0LFURFRPSXWHUWKHUPRVWD
W
2SHUDWLRQ'LVSOD
\ 581*UHHQ7,0(5<HOORZ+,32:(5*UHHQ'$872*UHHQ
6DIHW\GHYLFHV
&RPSUHVVRURYHUKHDWSURWHFWLRQ2YHUFXUUHQWSURWHFWLRQ
)URVWSURWHFWLRQ6HULDOVLJQDOHUURUSURWHFWLRQ,QGRRUIDQPRWRUHUURUSURWHFWLRQ
+HDWLQJRYHUORDGSURWHFWLRQ+LJKSUHVVXUHFRQWURO&RROLQJRYHUORDGSURWHFWLRQ
,QVWDOODWLRQ
5HIULJHUDQWSLSLQJVL]H2' PP /LTXLGOLQHǾ*DVOLQHǾ FRQQHFWLQJPHWKRG
P
)ODUHFR
QQHFWLQJ
/LTXLGOLQH  
*DV/LQH 
,QVXODWLRQIRUSLSLQ
J
P
1HFHVVDU\%RWKVLGHVLQGHSHQGHQW 5HIULJHUDQWOLQHRQHZD\OHQJWK 0D[ 9HUWLFDOKHLJKWGLIIHUHQFHEHWZHHQ 0D[2XWGRRUXQLWLVKLJKHU RXWGRRUXQLWDQGLQGRRUXQLW 0D[2XWGRRUXQLWLVORZHU
'UDLQKRVH &RQQHFWDEOH93 ዙ 3RZHUFDEOH ዙ 5HFRPPHQGHGEUHDNHUVL]H $ 

6L]H[&RUHQXPEHU PP [FRUHV,QFOXGLQJHDUWKFDEOH &RQQHFWLQJPHWKR
G 7HUPLQDOEORFN6FUHZIL[LQJW\SH $FFHVVRULHVLQFOXGHG 0RXQWLQJNLW&OHDQILOWHU$OOHUJHQFOHDUILOWHU[3KRWRFDWDO\WLFZDVKDEOHGHRGRUL]LQJILOWHU[ 2SWLRQDOSDUW
V ,QWHUIDFHNLW6&%,.1( 7KHGDWDDUHPHDVXUHG
,WHP
DWWKHIROORZLQJFRQGLWLRQV 7KHSLSHOHQJWKLVP
,QGRRUDLUWHPSHUDWXUH 2XWGRRUDLUWHPSHUDWXUH
6WDQGDUGV
2SHUDWLRQ
'% :% '% :%
&RROLQJ
ഒ ഒ ഒ
ഒ
+HDWLQJ
ഒ ഒ

7KLVDLUFRQGLWLRQHULVPDQXIDFWXUHGDQGWHVWHGLQFRQIRUPLW\ZLWKWKH,6
2
 7KHRSHUDWLRQGDWDDUHDSSOLHGWRWKH9GLVWULFWVUHVSHFWLYHO\
7KHUHIULJHUDQWTXDQWLW\WREHFKDUJHGLQFOXGHVWKHUHIULJHUDQWLQPFRQQHFWLQJSLSLQJ
&RROLQJFDSDFLW\ : 0LQᨺ0D[
$GDSWHGWRRoHS GLUHFWLYH
DXK09ZJ-S
Indoor unit DXK09ZJ-S Outdoor unit DXC09ZJ-S
,627-,6&
&RROLQJ
ഒ
Model
Item
-
4
-
'11 • SRK-T-118
D
RWA000Z225
GDWD
&23
+HDWLQJ
([WHULRUDSSHDUDQF
HTXLSPHQ
W
HTXLSPHQW
FRQWURO
GDW
D
$WWDFKHGOHQJWKRISLSLQJ
&RQQHFWLRQZLULQJ
1RWH 

3XUJLQJLVQRWUHTXLUHGHYHQIRUWKHVKRUWSLSLQJ
3RZHUVXSSO\
N:
3KDVHᨺ9+]
2SHUDWLRQ
3RZHU &RROLQJ ᨺ FRQVXPSWLRQ +HDWLQJ
$
ᨺ
5XQQLQJ &RROLQJ
9 FXUUHQW +HDWLQJ 9 ,QUXVKFXUUHQW 9
&RROLQJ  +HDWLQJ  6RXQGOHYH
O +L0H/R  3RZHUOHYHO   6RXQGOHYH
O +L0H/R  3RZHUOHYHO  
([WHULRUGLPHQVLRQV+HLJKW[:LGWK['HSWK PP [[ ;;
H )LQHVQRZ 6WXFFRZKLWH
0XQVHOOFRORU <QHDUHTXLYDOHQW <QHDUHTXLYDOHQW
1HWZHLJKW NJ  
5HIULJHUDQW
&RPSUHVVRUW\SH4W\ 50%0'(5RWDU\W\SH[ 0RWRU6WDUWLQJPHWKRG N: /LQHVWDUWLQJ 5HIULJHUDQWRLO ',$021')5((=(0$ 5HIULJHUDQW NJ 5$3UH&KDUJHGXSWRWKHSLSLQJOHQJWKRIP +HDWH[FKDQJHU /RXYHUILQVLQQHUJURRYHGWXELQJ 0ILQVLQQHUJURRYHGWXELQJ 5HIULJHUDQWFRQWURO &DSLOODU\WXEHV(OHFWURQLFH[SDQVLRQYDOYH 'HLFHFRQWURO 0LFURFRPSXWHUFRQWURO
$LUKDQGOLQJ
)DQW\SH4W\ 7DQJHQWLDOIDQ[ 3URSHOOHUIDQ[ 0RWRU
$LUIORZ
:
&00
  &RROLQJ +L0H/R  +HDWLQJ +L0H/R 
)UHVKDLULQWDN
H 1RWSRVVLEOH
$LUILOWHU4XDOLW\4XDQWLW\ 3RO\SURS\OHQHQHWZDVKDEOH[
6KRFNYLEUDWLRQDEVRUEH
U &XVKLRQUXEEHUIRUFRPSUHVVRU
(OHFWULFKHDWHU
2SHUDWLRQ
2SHUDWLRQVZLWFK
:LUHOHVV5HPRWHFRQWURO
5RRPWHPSHUDWXUHFRQWURO
0LFURFRPSXWHUWKHUPRVWDW
2SHUDWLRQ'LVSOD\ 581*UHHQ7,0(5<HOORZ+,32:(5*UHHQ'$872*UHHQ
6DIHW\GHYLFHV
&RPSUHVVRURYHUKHDWSURWHFWLRQ2YHUFXUUHQWSURWHFWLRQ
)URVWSURWHFWLRQ6HULDOVLJQDOHUURUSURWHFWLRQ,QGRRUIDQPRWRUHUURUSURWHFWLRQ
+HDWLQJRYHUORDGSURWHFWLRQ+LJKSUHVVXUHFRQWURO&RROLQJRYHUORDGSURWHFWLRQ
,QVWDOODWLRQ
5HIULJHUDQWSLSLQJVL]H2' PP
/LTXLGOLQHǾ*DVOLQHǾ
FRQQHFWLQJPHWKRG
P
)ODUHFR
QQHFWLQJ
/LTXLGOLQH  
*DV/LQH 
,QVXODWLRQIRUSLSLQ
J
P
1HFHVVDU\%RWKVLGHVLQGHSHQGHQW 5HIULJHUDQWOLQHRQHZD\OHQJWK 0D[ 9HUWLFDOKHLJKWGLIIHUHQFHEHWZHHQ 0D[2XWGRRUXQLWLVKLJKHU RXWGRRUXQLWDQGLQGRRUXQLW 0D[2XWGRRUXQLWLVORZHU
'UDLQKRVH &RQQHFWDEOH93 ዙ 3RZHUFDEOH ዙ 5HFRPPHQGHGEUHDNHUVL]H $ 
6L]H[&RUHQXPEHU PP

[FRUHV,QFOXGLQJHDUWKFDEOH
&RQQHFWLQJPHWKRG 7HUPLQDOEORFN6FUHZIL[LQJW\SH $FFHVVRULHVLQFOXGHG 0RXQWLQJNLW&OHDQILOWHU$OOHUJHQFOHDUILOWHU[3KRWRFDWDO\WLFZDVKDEOHGHRGRUL]LQJILOWHU[ 2SWLRQDOSDUW
V ,QWHUIDFHNLW6&%,.1( 7KHGDWDDUHPHDVXUHG
,WHP
DWWKHIROORZLQJFRQGLWLRQV 7KHSLSHOHQJWKLVP
,QGRRUDLUWHPSHUDWXUH 2XWGRRUDLUWHPSHUDWXUH
6WDQGDUGV
2SHUDWLRQ
'% :% '% :%
&RROLQJ
ഒ ഒ ഒ
ഒ
+HDWLQJ
ഒ ഒ

7KLVDLUFRQGLWLRQHULVPDQXIDFWXUHGDQGWHVWHGLQFRQIRUPLW\ZLWKWKH,6
2
 7KHRSHUDWLRQGDWDDUHDSSOLHGWRWKH9GLVWULFWVUHVSHFWLYHO\
7KHUHIULJHUDQWTXDQWLW\WREHFKDUJHGLQFOXGHVWKHUHIULJHUDQWLQPFRQQHFWLQJSLSLQJ
G%
G%
G%$
G%$
&RROLQJFDSDFLW\ +HDWLQJFDSDFLW\
:
:
0LQᨺ0D[
0LQᨺ0D[
$GDSWHGWRRoHS GLUHFWLYH
DXK12ZJ-S
Indoor unit DXK12ZJ-S Outdoor unit DXC12ZJ-S
&RROLQJ
,627-,6&
1RLVH OHYHO
ഒ
Model
Item
-
5
-
'11 • SRK-T-118
B
RWA000Z225
Model
Item
DXK18ZJ-S
Indoor unit DXK18ZJ-S Outdoor unit DXC18ZJ-S Cooling capacity (1) W 5000 (1600 (Min.)~5500 (Max.)) Heating capacity (1) W 5800 (1600 (Min.)~6600 (Max.)) Power supply 1 Phase, 220~240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
1.55 (0.40~2.20)
Heating 1.59 (0.42~2.10)
Running current
Cooling
A
7.1 / 6.8 / 6.5 (220/ 230/ 240 V)
Heating 7.3 / 7.0 / 6.7 (220/ 230/ 240 V)
Inrush current 7.3 / 7.0 / 6.7 (220/ 230/ 240 V)
COP
Cooling 3.23 Heating 3.65
Noise level
Cooling
Sound level dB(A) Hi : 46 Me : 37 Lo : 26 51 Power level dB 61 61
Heating
Sound level dB(A) Hi : 45 Me : 37 Lo : 31 53
Power level dB 61 63 Exterior dimensions (Height x Width x Depth) mm 294 x 798 x 229 640 x 800 (+71) x 290 Exterior appearance
(Munsell color)
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
Net weight kg 9.5 42
Refrigerant equipment
Compressor type & Q'ty 5RS132XAB21 (Rotary type) x 1 Motor (Starting method) kW 0.90 (Line starting) Refrigerant oil 0.37 (FV50S) Refrigerant (4) kg R410A 1.35 (Pre-Charged up to the piping length of 15m) Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Deice control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 38 34
Air flow
Cooling
CMM
Hi : 11.3 Me : 7.8 Lo : 5.3 36.0
Heating Hi : 13.5 Me : 10.2 Lo : 7.5 36.0
Fresh air intake Not possible
Air filter, Quality / Quantity Polypropylene net (washable) x 2 — Shock & vibration absorber Cushion rubber (for compressor) Electric heater
Operation control
Operation switch Wireless-Remote control
Room temperature control Microcomputer thermostat
Operation Display RUN : Green, TIMER : Yellow, HI POWER : Green, 3D AUTO : Green
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection (High pressure control), Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2")
Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.53 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent
Refrigerant line (one way) length
m
Max. 25
Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower) Drain hose Connectable (VP16) — Power cable — Recommended breaker size A 16
Connection wiring
Size x Core number 1.5mm2 x 4 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x 1, Photocatalytic washable deodorizing filter x 1)
Optional parts Interface kit (SC-BIKN-E)
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T 1, JI S C 961 2
Heating 20˚C 7˚C 6 ˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 15m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
Adapted to RoHS directive
-
6
-
'11 • SRK-T-118
2. EXTERIOR DIMENSIONS
(1) Indoor units
Models DXK09ZJ-S, 12ZJ-S, 18ZJ-S
Space for installation and service when viewing from the front
Wired - remote controller
Option
Notes1The model name label is attached
ޓޓ ޓ on the underside of the panel.
Wireless remote controller
ޓ 㧔2㧕It takes the interface kit 㧔SC-BIKN-E㧕 ޓޓ ޓ to connect the wired remote controller.
Outlet for down piping
Refer to the above view
Hole on wall for right rear piping Hole on wall for left rear piping
Gas piping
Outlet for wiring
Drain hose
Liquid piping
F
E
C D
B
Symbol
A
㧔Ǿ65
VP16
Ǿ6.3514"㧕㧔Flare
Content
㧔Ǿ65
09, 12 Ǿ9.5238"㧕㧔Flare
Outlet for pipingon both side
G
18 Ǿ12.712"㧕㧔Flare
Model
Unit:mm
غ120
19
60
150
17.3
G
790
6014.5
45
3160
45
798
294
229 3
45
609
100106.5585106.5
50
48.9
55
47
47
55
403.6
471.6
531.8
F
139 450 209
Unit
D
C
A
E
B
65
15
7.7279.17.2
Service space
Service space
Service space
Service space
Installation plate
a
RL A 000Z 051
-
7
-
'11 • SRK-T-118
L2
Intake
Outlet
Intake
L3
L1
Minimum installation space
Service space
( )
L4
L2
L3
L4
L1
100 100 250
Open
Open
250
80
280
280
Open
80
75
Examples of
Dimensions
installation
180
Open
80
Open
Content
C Pipe/ cable draw-out hole
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(igas side
M10×4places
Unit:mm
φ
20×2places
Service valve connection(iliquid side
D
φ9.5238")(Flare
φ6.3514")(Flare
Notes
(1)It must not be surrounded by walls on the four sides. (2)The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm. (3)Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(4)Leave 1m or more space above the unit. (5)A wall in front of the blower outlet must not exceed the units height. (6)The model name label is attached on the lower right corner of the front panel.
40°
40°
138.4 33.5
Terminal block
C
B
A
97.7
42.5
15.8
595
63.4
390.6
390.6
69.4
111.6
510 158.4
780 61.9
17.9
14.8 312.5 24.3
351.6
50.6
12
290
E
D
(2) Outdoor units
Models DXC09ZJ-S, 12ZJ-S
RC V 000Z 012
-
8
-
'11 • SRK-T-118
Model DXC18ZJ-S
RC T 000Z 005
L2
Intake
Outlet
Intake
L3
L1
Minimum installation space
Service space
( )
L4
L2 L3 L4
L1
100 100 250
Open
II
Open
250
80
280
III
280
Open
80
75
Examples of
Dimensions
installation
IV
180
Open
80
Open
φ12.712")(Flare
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connectiongas side
M10 × 4places
φ20 × 5places
Service valve connectionliquid side
φ6.3514")(Flare
Notes
1 It must not be surrounded by walls on the four sides.
2 The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more the 15mm. 3 Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
4 Leave 1m or more space above the unit.5 A wall in front of the blower outlet must not exceed the units height.6 The model name label is attached on the right side of the unit.
A
C
Terminal block
B
93 42.5
640
800
89 510 201
327.3
83.5
290
43.5
327.3 50.6
12
24.3312.514.8
71.2
17.9
40°
40°
33.5148.4
12.4
351.6
38.6
90.6
520.6 161
35.6
D
E
Unit:mm
-
9
-
'11 • SRK-T-118
(3) Remote controller
(a) Wireless remote controller
Unit: mm
60
17.3
150
-
10
-
'11 • SRK-T-118
(b) Wired remote controller (option parts)
PJZ000Z274
TEMP ON/OFF
48
غ120
L C D
Wall surface
Wiring
Electrical box
Not included
19
Wiring specifications
Exposed mounting
23
46
11.5 11
Remote control outline
120
45
83.5
42
120
Remote control installation dimensions
Wiring oulet
Installation hole
12×7 Slot hole
9.5×5 Slot hole 4places
1 Installation screw for remote control
M4 Screw (2 pieces)
44
(1) If the prolongation is over 100m, change to the size below. But, wiring in the remote controller case should be under 0.5mm2. Change the wire size outside of the case according to wire connecting. Waterproof treatment is necessary at the wire connecting section. Be careful about contact failure.
Length Wiring thickness
100 to 200m
0.5mm2×2 cores
0.75mm2×2 cores
1.25mm2×2 cores
2.0mm2×2 cores
Under 300m Under 400m Under 600m
Upper part
Lower part
Lower case
Sheath
Upper cace
Board
Wiring
Upper
Lower
X Y
Sheath
Upper cace
Board
Wiring
Upper
Lower
YX
Tighten the screws after cutting off the thin part of screw mounting part.
Embedded mounting
The peeling-off length of sheath
The peeling-off length
of sheath
In case of pulling out from
upper left
In case of pulling out from upper left
In case of pulling out from upper left
X wiring : 170mm Y wiring : 190mm
Pulling out from center
X wiring : 215mm Y wiring : 195mm
Pulling out from upper left
In case of pulling out from center
In case of pulling out from center
In case of pulling out from center
Wiring outlet Cut off the upper thin part of remote control lower case with a nipper or knife, and grind burrs with a file etc.
0.3mm2×2 cores.
X, Y Terminal block Attach M3 screw
with washer
Unit:mm
-
11
-
'11 • SRK-T-118
250V 3.15A
PRINTED
CNF CNE
CNX
CNG
4
CNU
1 3 65
12,18
CNY
M M M
5 5
U
2 8
2
t
o
CNS
CNM
M
5
TO OUTDOOR
S/N
J
L
G
1
CIRCUIT BOARD
INTERFACE KIT
RDBKWHYBL
WIRELESS
DISPLAY
BACK-UP SW
UNIT
BKWHRD
Y/G
HEAT
EXCHANGER
2/N
3
Y/G
HD
ONLY
t
o
2
t
o
R-AMP
2
HEAT
EXCHANGER
5
FM
I
SM
I
LM
1
LM
2
F
Va
Th
I
Th
2
Th
3
T
DS
Blue
BlackBK
Red
BL RD
WhiteWH
YellowGreenYG
ColorMark
Heat exch. sensor
Fan motor
Room temp. sensor
Flap motor
Diode stackDS FuseF
Connector
CNE-CNY FM
I
Terminal blockT
Description
Item
VaristorVa
LM
1,2
SM
I
Louver motor
Th
I
Th
2,3
YellowY
Humidity sensor
HD
Power Source 1 Phase 220230240V 50Hz
3. ELECTRICAL WIRING
(1) Indoor units
Models DXK09ZJ-S, 12ZJ-S, 18ZJ-S
a
RWA000Z226
-
12
-
'11 • SRK-T-118
Color
RD
Mark
OrangeOR
YellowGreenYG
BlackBK
YellowY
WhiteWH
Red
L
T
DescriptionItem
Connector
CNEEV20S
Electric expansion valvecoil
EEV
Fan motor
FMo
Reactor
Terminal block
Compressor motor
CM
Solenoid valve for 4 way valve
20S
Heat exchanger sensoroutdoor unit
TH1
Outdoor air temp.sensor
TH2
TH3
Discharge pipe temp.sensor
Model
Power cable, indoor-outdoor connecting wires
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit. Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen along the regulations in each country. The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.
9
2.0
32
1.5mm2 x 3 1.5mm
2
12
09
MAX running current
Power cable size
mm
2
A
Power cable length
m
indoor-outdoor
wire size x number
Earth wire size
BK㧕
WH
RD
PWB ASSY
TRANSISTOR
POWER
250V 20A
F2
W
W
V
V
U
U
P
N
M
M
CIRCUIT
SWITCHING POWER
250V 2A
250V 10A
CNEEV
PAM CIRCUIT
F1
F4
F3 250V 1A
CNFAN
FMo
CNTH
20S
CN20S
G1
C-2
NOISE FILTER
T2
L
L
N
T
TERMINAL BLOCK
T1
R. IN
S. IN
TH1
TH2
TH3
EEV
5 or 6 wires
OR
Y
BK
WH
RD
Y/G
Y/G
250V 15A
TO INDOOR UNIT
POWER WIRES
SIGNAL WIRE
POWER SOURCE 1220240V 50Hz1220V 60Hz
M
CM
3
(2) Outdoor units
Models DXC09ZJ-S, 12ZJ-S
a
RWC000Z238
-
13
-
'11 • SRK-T-118
b
RWC000Z228
Color
RD
Mark
OrangeOR
YellowGreenYG
BlackBK
BrownBR
YellowY
WhiteWH
Red
DescriptionItem
Connector
CNEEVCN20S
Electric expansion valvecoil
EEV
Fan motor
FMo
Reactor
L
Terminal block
T1,2
Compressor motor
CM
Solenoid valve for 4 way valve
20S
Heat exchanger sensoroutdoor unit
TH1
Outdoor air temp.sensor
TH2
TH3
Discharge pipe temp.sensor
POWER SOURCE 1220240V 50Hz1220V 60Hz
Model
Power cable, indoor-outdoor connecting wires
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit. Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen along the regulations in each country. The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.
14
2.0
18
1.5mm2 x 3 1.5mm
2
3
1
2
[ ]
N
18
M
T2
T1
S
BK
WH
RD
V
W
U
PWB ASSY MAIN
M
M
+ + +
R
TRANSISTOR
POWER
CIRCUIT
SWITCHING POWER
250V 2A
F1
250V 20A
F2
F3 250V 1A
W
V
U
P
NU NV NW
CNTH
CNEEV
CNFAN
t
3
ACTIVE FILTER UNIT
250V 20A
F8
OR
Y
S-2
tt
BK
WH
WH
BK
PWB ASSY SUB
S-1
CNSUB
CNMAIN
250V 10A
F10
S
R
R
BK
WH
G1
YG
BR
IN
IN
OUT
S
R
O
O
N
L
250V 20A
FUSE
2
1
N
3
YG
YG
CN20S
C-2
RD
20S
RD
T1
T2
TERMINAL
BLOCK
TH1 TH2 TH3
EEV
FMo
CM
BLOCK
TERMINAL
WH
TO INDOOR UNIT
POWER WIRES
SIGNAL WIRE
L
5 or 6 wires
MAX running current
Power cable size
mm
2
A
Power cable length
m
indoor-outdoor
wire size x number
Earth wire size
Model DXC18ZJ-S
-
14
-
'11 • SRK-T-118
Model DXK09ZJ-S
10
20
30
40
50
60
70
10
20
30
40
50
60
70
10
20
30
40
50
60
70
10
20
30
40
50
60
70
1000 2000 4000 800063 125 250 500
Sound Pressure Level (dB)
(standard 2×10
-5
Pa)
Sound Pressure Level (dB)
(standard 2×10
-5
Pa)
Mid Octave Band frequency (Hz)
1000 2000 4000 8000
63 125 250
500
Mid Octave Band frequency (Hz)
(Indoor Unit) Model DXK09ZJ-S
Noise
Level
Cooling 34 dB(A) Heating 39 dB(A)
×
......
Cooling
Heating
Condition ISO-T1, JIS C9612
N70
N60
N50
N40
N30
N20
N70
N60
N50
N40
N30
N20
(Outdoor Unit) Model DXC09ZJ-S
Noise
Level
Cooling 48 dB(A) Heating 47 dB(A)
×
......
Cooling
Heating
ISC10016
4. NOISE LEVEL
-
15
-
'11 • SRK-T-118
Model DXK12ZJ-S
10
20
30
40
50
60
70
10
20
30
40
50
60
70
10
20
30
40
50
60
70
10
20
30
40
50
60
70
1000 2000 4000 800063 125 250 500
Sound Pressure Level (dB)
(standard 2×10
-5
Pa)
Sound Pressure Level (dB)
(standard 2×10
-5
Pa)
Mid Octave Band frequency (Hz)
1000 2000 4000 8000
63 125 250
500
Mid Octave Band frequency (Hz)
(Indoor Unit) Model DXK12ZJ-S
Noise
Level
Cooling 45 dB(A) Heating 42 dB(A)
×
......
Cooling
Heating
Condition ISO-T1, JIS C9612
N70
N60
N50
N40
N30
N20
(Outdoor Unit) Model DXC12ZJ-S
Noise Level
Cooling 50 dB(A) Heating 50 dB(A)
×
......
Cooling
Heating
N70
N60
N50
N40
N30
N20
ISC10016
-
16
-
'11 • SRK-T-118
N50
N30
N40
N60
N70
N20
Sound Pressure Level (dB)
(standard 2×10
-5
Pa)
Mid Octave Band frequency (Hz)
10
20
30
40
50
60
70
10
20
30
40
50
60
70
63 125 250 500 1000 2000 4000 8000
N50
N30
N40
N60
N70
N20
Sound Pressure Level (dB)
(standard 2×10
-
5
P
a
)
Mid Octave Band frequency (Hz)
10
20
30
40
50
60
70
10
20
30
40
50
60
70
63 125
250
500
1000
2000
4000
8000
(Indoor Unit) Model DXK18ZJ-S
Noise
Level
Cooling 46 dB(A) Heating 45 dB(A)
×
......
Cooling Heating
Model DXK18ZJ-S
(Outdoor Unit) Model DXC18ZJ-S
Noise
Level
Cooling 51 dB(A) Heating 53 dB(A)
×
......
Cooling Heating
Condition ISO-T1,JIS C9612
-
17
-
'11 • SRK-T-118
5. PIPING SYSTEM
Indoor unit
Outdoor unit
Flare connection
Flare connection
Liquid pipe
(φ6.35)
Gas pipie
(φ12.7)
Service valve
Heat exchanger
Heat exchanger sensor
Electronic expansion valve
(Liquid)
Strainer
Receiver
Muffler
Capillary tube
Outdoor air temp. sensor
Muffler
Muffler
Compressor
Discharge pipe temp. sensor
Cooling cycle
Heating cycle
Check joint
4way valve
Service valve
Heat exchanger sensor
(Th3)
(TH3)
Room temp. sensor
(Th1)
(Th2)
(
Gas
)
(TH2)
Heat exchanger sensor
(TH1)
(EEV)
Capillary tube
Heat exchanger
Humidity sensor
(HD)
Model DXK18ZJ-S
Models DXK09ZJ-S, 12ZJ-S
Indoor unit
Outdoor unit
Flare connection
Flare connection
Liquid pipe
(φ 6.35)
Gas pipie (φ 9.52)
Service valve
Heat exchanger
Heat exchanger sensor
Electronic expansion valve
(Liquid)
Strainer Muffler
Capillary tube
Outdoor air temp. sensor
Muffler
Muffler
Compressor
Accumlator
Discharge pipe temp. sensor
Cooling cycle
Heating cycle
Check joint
4way valve
Service valve
Heat exchanger sensor
(Th3)
(TH3)
Room temp. sensor
(Th1)
(Th2)
(
Gas
)
(TH2)
Heat exchanger sensor
(TH1)
(EEV)
Capillary tube
Heat exchanger
Humidity sensor
(HD)
(35 only)
-
18
-
'11 • SRK-T-118
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
(3) Correction relative to frosting on outdoor heat exchanger during heating
How to obtain the cooling and heating capacity
=
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Air inlet temperature of
DXK12ZJ-S
outdoor unit in °C WB
Adjustment coefficient
-15
0.95 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1.00
-10 -9 -7 -5 -3 -1 1 3
5 or more
DXK12ZJ-S
3300 3217
RANGE OF USAGE & LIMITATIONS
Indoor return air temperature (Upper, lower limits)
Refrigerant line (one way) length
Power source voltage Rating ±10%
Voltage at starting Min. 85% of rating
Frequency of ON-OFF cycle
Max. 4 times/h
(Inching prevention 10 minutes)
Max. 7 times/h
(Inching prevention 5 minutes)
ON and OFF interval Min. 3 minutes
Outdoor air temperature (Upper, lower limits)
Vertical height difference between outdoor unit and indoor unit
Max. 15m Max. 25m
Max. 10m
(Outdoor unit is higher)
Max. 10m
(Outdoor unit is lower)
Max. 15m
(Outdoor unit is higher)
Max. 15m
(Outdoor unit is lower)
Item
Models
DXK09, 12ZJ-S DXK18ZJ-S
Cooling operation : Approximately 18 to 32 D.B. Heating operation : Approximately 10 to 27 D.B. (Refer to the selection chart)
Cooling operation : Approximately -15 to 46 D.B. Heating operation : Approximately -15 to 24 D.B. (Refer to the selection chart)
Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way.
Net capacity = Capacity shown on specication × Correction factors as follows.
(1) Coefcient of cooling and heating capacity in relation to temperatures
0.6
0.7
0.8
0.9
1.0
1.2
1.1
1.3
0
-5
-10
-15
24
26
20
25
30
35
40
46
10
15
20
25
27
Outdoor air W.B. temperature °C W.B.
-15 -10 -5 0 5 10 15
.
Cooling operation
Outdoor air D.B.
temperature
°C D. B.
Coefficient of cooling
&
Heating capacity in
relation to temperature
Heating operation
Indoor air D.B.
temperature
°C D. B.
ISO-T1 Standard Condition
Depends on installed situation
ISO-T1 Standard Condition
2220181614
Indoor air W.B. temperature °C W.B
Applicable range
Cooling
Heating
6. RANGE OF USAGE & LIMITATIONS
-
19
-
'11 • SRK-T-118
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
(3) Correction relative to frosting on outdoor heat exchanger during heating
How to obtain the cooling and heating capacity
=
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Air inlet temperature of
DXK12ZJ-S
outdoor unit in °C WB
Adjustment coefficient
-15
0.95 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1.00
-10 -9 -7 -5 -3 -1 1 3
5 or more
DXK12ZJ-S
3300 3217
-
20
-
'11 • SRK-T-118
7. CAPACITY TABLES
2.70
Heat Mode
Indoor air temp
Air flow Outdoor 21 ℃DB 23 ℃DB 26 ℃DB 27 ℃DB 28 ℃DB 31 ℃DB 33 ℃DB
Outdoor
air temp. 14 ℃WB 16 ℃WB 18 ℃WB 19 ℃WB 20 ℃WB 22 ℃WB 24 ℃WB
Air flow air temp. Indoor air temp
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
16 DB 18 DB 20 DB 22 DB 24 DB
10 2.82 2.22 2.95 2.19 3.06 2.27 3.11 2.24 3.16 2.21 3.26 2.28 3.34 2.21
-15WB 1.97 1.93 1.88 1.84 1.80
12 2.77 2.20 2.90 2.16 3.01 2.25 3.07 2.22 3.12 2.20 3.22 2.27 3.31 2.20
-10WB 2.23 2.19 2.16 2.10 2.06
14 2.71 2.17 2.85 2.14 2.97 2.23 3.03 2.20 3.08 2.17 3.18 2.25 3.28 2.19
-5WB 2.41 2.38 2.33 2.30 2.27
16 2.66 2.14 2.80 2.12 2.92 2.20 2.98 2.18 3.04 2.15 3.15
2.24 3.24 2.18
Hi 0WB 2.53 2.49 2.45 2.42 2.38
18 2.60 2.12 2.74 2.09 2.88 2.18 2.94 2.16 2.99 2.14 3.11 2.22 3.20 2.16
11.0 5WB 3.22 3.19 3.17 3.10 3.06
20 2.55 2.09 2.68 2.06 2.83 2.17 2.89 2.15 2.95 2.12 3.07 2.21 3.17 2.15
(
m
3
/
min
)
6WB 3.27 3.24 3.20 3.16 3.12
Hi 22 2.49 2.06 2.63 2.04 2.78 2.15 2.84 2.13 2.90 2.11 3.02 2.19 3.13 2.14
10WB 3.48 3.45 3.42 3.38 3.34
7.9 24 2.43 2.03 2.57 2.01 2.72 2.13 2.80 2.11 2.85 2.09 2.98 2.18 3.08 2.12
15WB 3.79 3.75 3.73 3.69 3.65
(
m3/min
)
26 2.37 2.00 2.51 1.98 2.67 2.10 2.74 2.09 2.80 2.07 2.93 2.16 3.04 2.11
20WB 4.07 4.04 4.02 3.97 3.94
28 2.31 1.97 2.44 1.95 2.61 2.08 2.69 2.07 2.75 2.05 2.89 2.14 3.00 2.09 30 2.24 1.94 2.38 1.92 2.56 2.05 2.64 2.04 2.70 2.03 2.84 2.12 2.95 2.08 32 2.18 1.91 2.31 1.90 2.50 2.03 2.58 2.02 2.64 2.01 2.79 2.11 2.90 2.07 34 2.11 1.88 2.25 1.86 2.44 2.00 2.53 2.00 2.59 1.98 2.74 2.09 2.85 2.05 35 2.08 1.86 2.21 1.85 2.41 1.99 2.50 1.99 2.56 1.97 2.71 2.08 2.83 2.04 36 2.04 1.85 2.18 1.84 2.38 1.98 2.47 1.98 2.53 1.96 2.69 2.07 2.80 2.03 38 1.97 1.81 2.11 1.80 2.32 1.95 2.41 1.95 2.47 1.94 2.63 2.05 2.75 2.02 39 1.94 1.80 2.07 1.79 2.28 1.94 2.38 1.94 2.44 1.93 2.61 2.05 2.72 2.00
Heat Mode
Indoor air temp
Air flow Outdoor 21 ℃DB 23 ℃DB 26 ℃DB 27 ℃DB 28 ℃DB 31 ℃DB 33 ℃DB
Outdoor
air temp. 14 ℃WB 16 ℃WB 18 ℃WB 19 ℃WB 20 ℃WB 22 ℃WB 24 ℃WB
Air flow air temp. Indoor air temp
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
16 DB 18 DB 20 DB 22 DB 24 DB
10 3.72 3.01 3.89 2.96 4.04 3.09 4.10 3.04 4.17 3.01 4.30 3.11 4.41 3.01
-15WB 2.46 2.41 2.35 2.30 2.25
12 3.65 2.98 3.83 2.93 3.98 3.06 4.05 3.02 4.12 2.99 4.25 3.08 4.37 3.00
-10WB 2.79 2.74 2.70 2.63 2.58
14 3.58 2.95 3.76 2.90 3.92 3.04 3.99 3.00 4.07 2.96 4.20 3.06 4.33 2.98
-5WB 3.02 2.97 2.91 2.88 2.83
16 3.51 2.90 3.69 2.86 3.86 3.01 3.94 2.98 4.01 2.94 4.15 3.05 4.28 2.97
Hi 0WB 3.16 3.12 3.06 3.02 2.98
18 3.44 2.87 3.62 2.83 3.80 2.98 3.88 2.95 3.95 2.92 4.10 3.03 4.23 2.96
12.8 5WB 4.03 3.98 3.96 3.88 3.83
20 3.36 2.84 3.54 2.80 3.73 2.95 3.82 2.93 3.89 2.90 4.05 3.01 4.18 2.94
(
m
3
/
min
)
6WB 4.09 4.04 4.00 3.95 3.90
Hi 22 3.29 2.80 3.47 2.77 3.66 2.92 3.75 2.90 3.83 2.87 3.99 3.00 4.13 2.93
10WB 4.35 4.31 4.28 4.22 4.18
10.1 24 3.21 2.76 3.39 2.73 3.59 2.90 3.69 2.87 3.77 2.85 3.93 2.98 4.07 2.91
15WB 4.73 4.69 4.66 4.61 4.56
(
m3/min
)
26 3.13 2.72 3.31 2.70 3.52 2.86 3.62 2.85 3.70 2.82 3.87 2.96 4.02 2.89
20WB 5.09 5.05 5.02 4.96 4.92
28 3.04 2.69 3.23 2.66 3.45 2.84 3.55 2.82 3.63 2.79 3.81 2.93 3.96 2.87 30 2.96 2.64 3.14 2.62 3.38 2.80 3.48 2.80 3.56 2.77 3.75 2.91 3.90 2.85 32 2.87 2.60 3.05 2.58 3.30 2.77 3.41 2.76 3.49 2.74 3.68 2.89 3.83 2.83 34 2.79 2.56 2.96 2.54 3.22 2.74 3.34 2.74 3.42 2.71 3.62 2.87 3.77 2.81 35 2.74 2.54 2.92 2.52 3.18 2.71 3.30 2.72 3.38 2.68 3.58 2.85 3.73 2.80 36 2.69 2.52 2.87 2.51 3.14 3.26 2.69 3.34 2.67 3.55 2.84 3.70 2.78 38 2.60 2.48 2.78 2.46 3.06 2.67 3.18 2.66 3.26 2.64 3.48 2.81 3.63 2.77 39 2.56 2.45 2.73 2.45 3.01 2.65 3.14
2.65 3.22 2.63 3.44 2.80 3.60 2.76
Model DXK09ZJ-S
Cool Mode
Model DXK12ZJ-S
Cool Mode
ISC09165
Air flow
outdoor air temp.
indoor air temp
16˚CDB 18˚CDB 20˚CDB 22˚CDB 24˚CDB
Hi
13.5
(m3/min)
-15˚CWB 3.57 3.49 3.41 3.34 3.26
-10˚CWB 4.04 3.97 3.91 3.81 3.73
-5˚CWB 4.37 4.31 4.22 4.18 4.11
0˚CWB 4.59 4.52 4.44 4.39 4.32
5˚CWB 5.84 5.77 5.74 5.63 5.55
6˚CWB 5.94 5.87 5.80 5.73 5.66
10˚CWB
6.31 6.25 6.21 6.12 6.06
15˚CWB 6.86 6.80 6.76 6.68 6.62
20˚CWB
7.38 7.32 7.28 7.20 7.14
Heat Mode
Model DXK18ZJ-S
Cool Mode
Air flow
Outdoor air temp.
Indoor air temp
21˚CDB 23˚CDB 26˚CDB 27˚CDB 28˚CDB 31˚CDB 33˚CDB
14˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
TC SHC TC
SHC TC SHC
TC SHC TC SHC
TC SHC TC
SHC
Hi
11.3
(m3/min)
10 5.63 4.09 5.90 4.02 6.11 4.12 6.22 4.05 6.32 3.99 6.51 4.05 6.69 3.92
12 5.53 4.03 5.80 3.97 6.03 4.07 6.14 4.01 6.25 3.96 6.44 4.02 6.62 3.89
14 5.43 3.98 5.70 3.91 5.94 4.03 6.05 3.98 6.16 3.92 6.37 4.00 6.55 3.86
16 5.32 3.92 5.59 3.86 5.85 3.98 5.96 3.93 6.08 3.88 6.29 3.96 6.48 3.84
18 5.21 3.85 5.48 3.80 5.75 3.94 5.88 3.90 5.99 3.84 6.21 3.93 6.41 3.81
20 5.10 3.79 5.37 3.74 5.65 3.89 5.78 3.85 5.90 3.80 6.13 3.90 6.33 3.78
22 4.98 3.73 5.25 3.68 5.55 3.84 5.69 3.81 5.80 3.76 6.05 3.86 6.25 3.75
24 4.86 3.67 5.14 3.62 5.45 3.79 5.59 3.76 5.71 3.72 5.96 3.83 6.17 3.72
26 4.74 3.60 5.01 3.56 5.34 3.74 5.49 3.71 5.61 3.67 5.87 3.79 6.08 3.69
28 4.61 3.54 4.89 3.50 5.23 3.69 5.39 3.67 5.50 3.63 5.78 3.76 5.99 3.66
30 4.49 3.46 4.76 3.43 5.11 3.64 5.28 3.62 5.40 3.58 5.68 3.72 5.90 3.62
32 4.35 3.40 4.63 3.37 5.00 3.58 5.17 3.57 5.29 3.54 5.58 3.68 5.81 3.59
34 4.22 3.33 4.49 3.31 4.88 3.52 5.06 3.52 5.18 3.49 5.48 3.64 5.71 3.55
35 4.15 3.29 4.42 3.27 4.82 3.49 5.00 3.49 5.12 3.45 5.43 3.62 5.66 3.53
36 4.08 3.26 4.35 3.24 4.76 3.47 4.94 3.46 5.06 3.43 5.37 3.60 5.61 3.50
38 3.94 3.19 4.21 3.18 4.63 3.42 4.82 3.42 4.94 3.39 5.27 3.54 5.50 3.47
39 3.87 3.15 4.14 3.14 4.57 3.39 4.76 3.39 4.88 3.36 5.21 3.52 5.45 3.45
a
ISC09106
-
21
-
'11 • SRK-T-118
R410A REFRIGERANT USED
WALL TYPE AIR CONDITIONER
INSTALLATION MANUAL FOR INDOOR UNIT
RLA012A012B
WARNING
• Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as
water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except the by qualified installer.
• Install the system in full accordance with the installation manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric
shocks and fire.
• Be sure to use only for household and residence.
If this appliance is installed in inferior environment such as machine shop
and etc., it can cause malfunction.
• Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water
leaks, electric shocks, fire and personal injury.
• Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause
material damage and personal injury.
• Ventilate the working area well in the event of refrigerant leakage during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is
produced.
• When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and
install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
• After completed installation, check that no refrigerant leaks from the system.
If refrigerant leaks into the room and comes into contact with an oven or
other hot surface, poisonous gas is produced.
• Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and
serious accidents due to burst of the refrigerant circuit.
• Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and
refrigerant leakage after a long period.
• The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work” and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by
improper work can cause electric shocks and fire.
• Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or
incorrect function of equipment.
• Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production
or fire.
• This appliance must be connected to main power supply by means of a circuit breaker or switch (fuse:16A) with a contact separation of at least 3mm.
• When plugging this appliance, a plug conforming to the norm IEC60884-1 must be used.
• Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat
production or fire.
• Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
• Be sure to switch off the power supply in the event of installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit
failure or personal injury due to the unexpected start of fan.
• Be sure to wear protective goggles and gloves while at work.
• Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
CAUTION
• Use the circuit breaker of correct capacity. Circuit breaker should be the one that disconnect all poles under over current.
Using the incorrect one could cause the system failure and fire.
• Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
• Be sure to install indoor unit properly according to the installation manual in order to run off the drainage smoothly.
Improper installation of indoor unit can cause dropping water into the room
and damaging personal property.
• Install the drainage pipe to run off drainage securely according to the installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the
room and damaging personal property.
• Be sure to install the drainage pipe with descending slope of 1/100 or more, and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure
the space for inspection and maintenance.
• Secure a space for installation, inspection and maintenance specified in the manual.
Insufficient space can result in accident such as personal injury due to
falling from the installation place.
• For installation work, be careful not to get injured with the heat exchanger, piping flare portion or screws etc.
• Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
damage on the ceiling, floor, furniture and any other valuables.
• When perform the air conditioner operation (cooling or drying opera­tion) in which ventilator is installed in the room. In this case, using the air conditioner in parallel with the ventilator, there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status. Therefore, set up the opening port such as incorporate the air into the room that may appropriate to ventila­tion (For example; Open the door a little). In addition, just as above, so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc.
• Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant
leakage in the small room, lack of oxygen can occur, which can cause serious accidents.
• Do not install the unit in the locations listed below.
• Locations where carbon fiber, metal powder or any powder is floating.
• Locations where any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur.
• Vehicles and ships.
• Locations where cosmetic or special sprays are often used.
• Locations with direct exposure of oil mist and steam such as kitchen and machine plant.
• Locations where any machines which generate high frequency harmonics are used.
• Locations with salty atmospheres such as coastlines.
• Locations with heavy snow (If installed, be sure to provide base flame and snow hood mentioned in the manual).
• Locations where the unit is exposed to chimney smoke.
• Locations at high altitude (more than 1000m high).
• Locations with ammonic atmospheres.
• Locations where heat radiation from other heat source can affect the unit.
• Locations without good air circulation.
• Locations with any obstacles which can prevent inlet and outlet air of the unit.
• Locations where short circuit of air can occur (in case of multiple units installation).
• Locations where strong air blows against the air outlet of outdoor unit.
• Locations where something located above the unit could fall.
It can cause remarkable decrease in performance, corrosion and damage
of components, malfunction and fire.
• Do not install the indoor unit in the locations listed below (Be sure
to install the indoor unit according to the installation manual for each model because each indoor unit has each limitation).
• Locations with any obstacles which can prevent inlet and outlet air of the unit.
• Locations where vibration can be amplified due to insufficient strength of structure.
• Locations where the infrared receiver is exposed to the direct sunlight or the strong light beam (in case of the infrared specification unit).
• Locations where an equipment affected by high harmonics is placed (TV set or radio receiver is placed within 1m).
• Locations where drainage cannot run off safely.
It can affect performance or function and etc.
• Do not install the unit near the location where leakage of
combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fire.
• Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can accumulate or collect, or where volatile combustible substances are handled.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
parts and etc. And combustible gas can cause fire.
• Do not use the indoor unit at the place where water splashes may occur such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.
• Do not install nor use the system close to the equipment that generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency
equipments and telecommunication equipments can affect the system, and cause malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.
• Do not place any variables which will be damaged by getting wet under the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged,
condensation or drainage water can drop and it can cause the damage of valuables.
• Do not install the remote control at the direct sunlight.
It can cause malfunction or deformation of the remote control.
• Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.
It can cause the damage of the items.
• Do not use any materials other than a fuse with the correct rating in the location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause
unit failure and fire.
• Do not touch any buttons with wet hands.
It can cause electric shocks.
• Do not touch any refrigerant pipes with your hands when the system is in operation.
During operation the refrigerant pipes become extremely hot or extremely
cold depending the operating condition, and it can cause burn injury or frost injury.
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults
such as electric shocks due to short-circuiting.
• Do not put the drainage pipe directly into drainage channels where poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and
seriously affect the user’s health and safety. This can also cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
• Ensure that no air enters in the refrigerant circuit when the unit is installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.
• Do not processing, splice the power cord, or share a socket with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting
insulation and over-current etc.
• Do not bundling, winding or processing for the power cord. Or, do not deforming the power plug due to tread it.
This may cause fire or heating.
• Do not vent R410A into the atmosphere : R410A is a fluorinated greenhouse gas, covered by the Kyoto Protocol with Groval Warming Potential (GWP)=1975.
• Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can cause
personal injury due to entrapment, burn or electric shocks.
• Do not perform any change of protective device itself or its setup condition.
The forced operation by short-circuiting protective device of pressure
switch and temperature controller or the use of non specified component can cause fire or burst.
WARNING
SAFETY PRECAUTIONS
• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order to protect yourself.
• The precautionary items mentioned below are distinguished into two levels,
and . : Wrong installation would cause serious consequences such
as injuries or death.
: Wrong installation might cause serious consequences
depending on circumstances.
Both mentions the important items to protect your health and safety so strictly
follow them by any means.
• Be sure to confirm no anomaly on the equipment by commissioning after com­pleted installation and explain the operating methods as well as the maintenance methods of this equipment to the user according to the owner’s manual.
• Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user.
• For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform the installation works.
• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:
Never do it under any circumstances.
Always do it according to the instruction.
CAUTIONWARNING
CAUTION
WARNING
• This installation manual illustrates the method of installing an indoor unit.
• For electrical wiring work, please see instructions set out on the backside.
• For outdoor unit installation and refrigerant piping, please refer to the installation manual that comes with your outdoor unit.
• A wired remote control unit is supplied separately as an optional part.
• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
a
8. APPLICATION DATA
(1) Installation of indoor unit
Models DXK09ZJ-S, 12ZJ-S, 18ZJ-S
-
22
-
'11 • SRK-T-118
Necessary tools for the installation work
1
2
3
4
5
6
7
8
9
10
11
12
13
1
1
1
1
1
1
Q’ty
Option parts
Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover (for insulation of connection piping)
Plus headed driver
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench
Hole core drill (65mm in diameter)
Wrench key (Hexagon) [4m/m]
Flaring tool set
Gas leak detector
Pipe bender
Gauge for projection adjustment Used when flare is made by using conventional flare tool
( )
( )
14.0 ~ 61.0N·m (1.4 ~ 6.1kgf·m)
(
Designed specifically
for R410A
)
Piping in the left direction
Piping in the right rear directionPiping in the left rear direction
Piping in the right direction
INSTALLATION SPACE (INDOOR UNIT)
(FRONT VIEW)
Piping is possible in the rear, left, left rear, left downward, right or downward direction.
Right
Rear
Downward
Left rear
Left downward
Left
Wireless remote control
Remote control holder
Wood screws
BEFORE INSTALLATION
Before installation check that the power supply matches the air conditioner.
SELECTION OF INSTALLATION LOCATION
INSTALLATION OF INDOOR UNIT
Indoor unit
Relation between setting plate and indoor unit
Installing the support of piping
(Install at location that meets the following conditions, after getting approval from the customer)
Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed. A solid place where the unit or the wall will not vibrate. A place where there will be enough space for servicing. (Where space mentioned below can be secured) Where wiring and the piping work will be easy to conduct. The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting. A place where it can be easily drained. A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.) Places where this unit is not affected by the high frequency equipment or electric equipment. Avoid installing this unit in place where there is much oil mist. Places where there is no electric equipment or household under the installing unit.
Wireless remote control
In case of piping in the right rear direction
A place where the air conditioner can be received the signal surely during operating the wireless remote control. Places where there is no affected by the TV and radio etc. Do not place where exposed to direct sunlight or near heat devices such as a stove.
Sufficient care must be taken not to damage the panel when connecting pipes.
[Top view]
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
• Matters of special notice when piping from left or central/rear of the unit.
Left-hand-side piping Right-hand-side piping
Installation of Installation board
Drilling of holes and fixture of sleeve (Option parts)
Level position (2 locations)
Mating mark for level surface
Fixing on concrete wall
Use of nut anchor Use of bolt anchor
Shaping of pipings Taping of the exterior
Pipings
Drain hose
Top
Nut (M6)
Mounting board
Mounting board
Max.10
Thickness of the wall + 1.5cm
5
ø65
Indoor side Outdoor sideIndoor side Outdoor side Installed state
Turn to tighten
b
b
c
a
Bolt (M6 12)
5 cm minimum from the wal
l
10 cm
m
inimum
from the wal
l
Installation board
Sleeve
(sold separately)
6.5 cm minimum from the ceiling
R410A REFRIGERANT USED
WALL TYPE AIR CONDITIONER
INSTALLATION MANUAL FOR INDOOR UNIT
RLA012A012B
In case of rear piping draw out, cut off the lower
and the right side portions of the sleeve collar.
Drill a hole with whole core drill.
Hold the bottom of the piping and fix direction before stretching it and shaping it.
Tape only the portion that goes through the wall.
Always tape the wiring
with the piping.
[Drain hose changing procedures]
1. Remove the drain hose 2. Remove the drain cap.
Remove it with hand or pliers. Remove the screw and drain hose,
making it rotate.
3. Insert the drain cap. 4. Connect the drain hose.
Insert the drain cap which was removed
at procedure “2” securely using a hexagonal wrench etc. Note: Be careful that If it is not Inserted
securely, water leakage may occur.
Insert the drain hose securely, making
rotate. And install the screw. Note: Be careful that If it is not Inserted
securely, water leakage may occur.
Adjustment of the installation board in the horizontal direction is to be conducted with four screws in a temporary tightened state.
Adjust so the board will be
level by turning the board with the standard hole as the center.
450
Look for the inside wall structures (Intermediats support or pillar and firmly install the unit after level surface has been checked.)
Standard hole
Piping for Liquid (09 to 18 type) : ø6.35 Piping for Gas (09 to 12 type) : ø9.52
(18 type) : ø12.7
CAUTION
Completely seal the hole on the wall with putty. Otherwise, furniture, or other, may be wetted by leaked water or dewing.
putty
putty
1
1
1
5
2
2
2
2
1
Q’ty
Standard accessories (Installation kit)
Accessories for indoor unit
Installation board (Attached to the rear of the indoor unit)
Wireless remote control
Remote control holder
Battery [R03 (AAA, Micro) 1.5V]
Air-cleaning filters
Filter holders (Attached to the front panel of indoor unit)
Insulation (#486 50 x 100 t3)
Tapping screws (for installation board ø4 X 25mm)
Wood screws (for remote control switch holder ø3.5 X 16mm)
1
2
3
4
5
6
7
8
9
( )
Designed specifically
for R410A
Space for service Space for service
Indoor unit
Installation board
Piping hole (ø65)
Drain hose (ø16)
Piping for Liquid
Piping for Gas
Piping hole (ø65)
Space for service
48.947
65
139 450 209
106.5 585 106.5
50 100
7.2 7.7279.1
4715 Space for service
55
531.8
471.6
403.6
55
Indoor side Outdoor side
WARNING
Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as
water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except the by qualified installer.
Install the system in full accordance with the installation manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric
shocks and fire.
Be sure to use only for household and residence.
If this appliance is installed in inferior environment such as machine shop
and etc., it can cause malfunction.
Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water
leaks, electric shocks, fire and personal injury.
Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause
material damage and personal injury.
Ventilate the working area well in the event of refrigerant leakage during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is
produced.
When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and
install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
After completed installation, check that no refrigerant leaks from the system.
If refrigerant leaks into the room and comes into contact with an oven or
other hot surface, poisonous gas is produced.
Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and
serious accidents due to burst of the refrigerant circuit.
Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and
refrigerant leakage after a long period.
The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work” and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by
improper work can cause electric shocks and fire.
Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or
incorrect function of equipment.
Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production
or fire.
This appliance must be connected to main power supply by means of a circuit breaker or switch (fuse:16A) with a contact separation of at least 3mm.
When plugging this appliance, a plug conforming to the norm IEC60884-1 must be used.
Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat
production or fire.
Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
Be sure to switch off the power supply in the event of installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit
failure or personal injury due to the unexpected start of fan.
Be sure to wear protective goggles and gloves while at work.
Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
CAUTION
Use the circuit breaker of correct capacity. Circuit breaker should be the one that disconnect all poles under over current.
Using the incorrect one could cause the system failure and fire.
Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
Be sure to install indoor unit properly according to the installation manual in order to run off the drainage smoothly.
Improper installation of indoor unit can cause dropping water into the room
and damaging personal property.
Install the drainage pipe to run off drainage securely according to the installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the
room and damaging personal property.
Be sure to install the drainage pipe with descending slope of 1/100 or more, and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure
the space for inspection and maintenance.
Secure a space for installation, inspection and maintenance specified in the manual.
Insufficient space can result in accident such as personal injury due to
falling from the installation place.
For installation work, be careful not to get injured with the heat exchanger, piping flare portion or screws etc.
Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture
damage on the ceiling, floor, furniture and any other valuables.
When perform the air conditioner operation (cooling or drying opera- tion) in which ventilator is installed in the room. In this case, using the air conditioner in parallel with the ventilator, there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status. Therefore, set up the opening port such as incorporate the air into the room that may appropriate to ventila- tion (For example; Open the door a little). In addition, just as above, so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc.
Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant
leakage in the small room, lack of oxygen can occur, which can cause serious accidents.
Do not install the unit in the locations listed below.
Locations where carbon fiber, metal powder or any powder is floating.
Locations where any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur.
Vehicles and ships.
Locations where cosmetic or special sprays are often used.
Locations with direct exposure of oil mist and steam such as kitchen and machine plant.
Locations where any machines which generate high frequency harmonics are used.
Locations with salty atmospheres such as coastlines.
Locations with heavy snow (If installed, be sure to provide base flame and snow hood mentioned in the manual).
Locations where the unit is exposed to chimney smoke.
Locations at high altitude (more than 1000m high).
Locations with ammonic atmospheres.
Locations where heat radiation from other heat source can affect the unit.
Locations without good air circulation.
Locations with any obstacles which can prevent inlet and outlet air of the unit.
Locations where short circuit of air can occur (in case of multiple units installation).
Locations where strong air blows against the air outlet of outdoor unit.
Locations where something located above the unit could fall.
It can cause remarkable decrease in performance, corrosion and damage
of components, malfunction and fire.
Do not install the indoor unit in the locations listed below (Be sure
to install the indoor unit according to the installation manual for each model because each indoor unit has each limitation).
Locations with any obstacles which can prevent inlet and outlet air of the unit.
Locations where vibration can be amplified due to insufficient strength of structure.
Locations where the infrared receiver is exposed to the direct sunlight or the strong light beam (in case of the infrared specification unit).
Locations where an equipment affected by high harmonics is placed (TV set or radio receiver is placed within 1m).
Locations where drainage cannot run off safely.
It can affect performance or function and etc.
Do not install the unit near the location where leakage of
combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fire.
Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can accumulate or collect, or where volatile combustible substances are handled.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
parts and etc. And combustible gas can cause fire.
Do not use the indoor unit at the place where water splashes may occur such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Do not install nor use the system close to the equipment that generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency
equipments and telecommunication equipments can affect the system, and cause malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.
Do not place any variables which will be damaged by getting wet under the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged,
condensation or drainage water can drop and it can cause the damage of valuables.
Do not install the remote control at the direct sunlight.
It can cause malfunction or deformation of the remote control.
Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.
It can cause the damage of the items.
Do not use any materials other than a fuse with the correct rating in the location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause
unit failure and fire.
Do not touch any buttons with wet hands.
It can cause electric shocks.
Do not touch any refrigerant pipes with your hands when the system is in operation.
During operation the refrigerant pipes become extremely hot or extremely
cold depending the operating condition, and it can cause burn injury or frost injury.
Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults
such as electric shocks due to short-circuiting.
Do not put the drainage pipe directly into drainage channels where poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and
seriously affect the users health and safety. This can also cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Ensure that no air enters in the refrigerant circuit when the unit is installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.
Do not processing, splice the power cord, or share a socket with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting
insulation and over-current etc.
Do not bundling, winding or processing for the power cord. Or, do not deforming the power plug due to tread it.
This may cause fire or heating.
Do not vent R410A into the atmosphere : R410A is a fluorinated greenhouse gas, covered by the Kyoto Protocol with Groval Warming Potential (GWP)=1975.
Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can cause
personal injury due to entrapment, burn or electric shocks.
Do not perform any change of protective device itself or its setup condition.
The forced operation by short-circuiting protective device of pressure
switch and temperature controller or the use of non specified component can cause fire or burst.
WARNING
SAFETY PRECAUTIONS
Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order to protect yourself.
The precautionary items mentioned below are distinguished into two levels,
and . : Wrong installation would cause serious consequences such
as injuries or death.
: Wrong installation might cause serious consequences
depending on circumstances.
Both mentions the important items to protect your health and safety so strictly
follow them by any means.
Be sure to confirm no anomaly on the equipment by commissioning after com- pleted installation and explain the operating methods as well as the maintenance methods of this equipment to the user according to the owners manual.
Keep the installation manual together with owners manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user.
For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform the installation works.
Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
If unusual noise can be heard during operation, consult the dealer.
The meanings of “Marks” used here are shown as follows:
Never do it under any circumstances.
Always do it according to the instruction.
CAUTIONWARNING
CAUTION
WARNING
This installation manual illustrates the method of installing an indoor unit.
For electrical wiring work, please see instructions set out on the backside.
For outdoor unit installation and refrigerant piping, please refer to the installation manual that comes with your outdoor unit.
A wired remote control unit is supplied separately as an optional part.
When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
a
-
23
-
'11 • SRK-T-118
• Flaring work
Measurement B
Flaring block
Copper pipe
Finishing work and fixing
Connection wiring, Earth wiring
Outer tape
Refrigerant piping
Drain hose
Wood screw
Clamp
Cover the exterior portion with outer tape and shape the piping so it will match the contours of the route that the piping to take. Also fix the wiring and pipings to the wall with clamps.
RLA012A012B
Open/close and detachment/attachment of the air inlet panel
To open, pull the panel at both ends of lower part
and release latches, then pull up the panel until you feel resistance. (The panel stops at approx. 60° open position)
To close, hold the panel at both ends of lower
part to lower downward and push it slightly until the latch works.
To remove, pull up the panel to the position
shown in right illustration and pull it toward you.
To install, insert the panel arm into the slot on the
front panel from the position shown in right illustration, hold the panel at both ends of lower part, lower it downward slowly, then push it slightly until the latch works.
How to remove and fit the front panel
Removing
Remove the air inlet panel.
Remove the 2 set screws.
Remove the 3 latches in the upper section.
Move the lower part of the panel forward and
push upwards to remove.
1
2
3
4
Fitting
Do remove the air filter.
Cover the body with the front panel.
Fit the 3 latches in the upper section.
Tighten the 2 set screws.
Fit the air filter.
Fit the air inlet panel.
1
2
3
4
5
6
Set screws
Install the removed flared nuts to the pipes to be connected,
then flared the pipes.
Remove the flared nuts. (on both liquid and gas sides)
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
CONNECTION OF REFRIGERANT PIPINGS
Preparation
(Do not turn)
Press
Remove
A
90 ± 0.5˚
Dimension A Liquid side ø6.35 : 9.1 (mm) Gas side ø9.52 : 13.2 (mm)
ø12.7 : 16.6 (mm)
CAUTION
Do not apply refrigerating machine oil to the flared surface.
Indoor
Copper pipe diameter
Use a flare tool designed for R410A or a conventional flare tool. Please note that measurement B (protrusion from the flaring block) will vary depending on the type of a flare tool in use. If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value.
Clutch type flare tool for R410A
Conventional (R22) flare tool
ø6.35
ø9.52
ø12.7
0.0 - 0.5
0.0 - 0.5
0.0 - 0.5
1.0 - 1.5
1.0 - 1.5
1.0 - 1.5
1.5 - 2.0
1.5 - 2.0
2.0 - 2.5
Measurement B (mm)
Clutch type Wing nut type
CAUTION
Do not apply excess torque to the flared nuts. Otherwise, the flared nuts may check depending.
Arrange the drain hose in a downward angle. Avoid the following drain piping.
Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor. When the extended drain hose is indoor, securely insulate it with a heat insulator available in the market.
CAUTION
Wall
Gutter
Pipe accommodating section
Since this air conditioner has been designed to collect dew drops on the rear surface to the drain pan, do not attach the power cord above the gutter.
Drainage
Go through all installation steps and check if the drainage is all right. Otherwise water leak may occur.
Higher than specified The drain hose
tip is in water.
Wavy The drain hose
tip is in the gutter.
The gap to the ground is 5 cm or less.
Odor from the gutter
2
1
Installation Steps
Pass the pipe through the hole in the wall, and hook the upper part of the indoor unit to the installation board.
Gently push the lower part to secure the unit.
• How to remove the indoor unit from the installation board
Fixing of indoor unit
Push up at the marked portion of the indoor unit base lower latch, and slightly pull it toward you. (both right and left hand sides) (The indoor unit base lower latch can be removed from the installation board) Push up the indoor unit upward. So the indoor unit will be removed from the installation board.
1
2
The marked portion of the indoor unit base lower latch.
Indoor unit
Installation board
Installation board
Indoor unit base latch
Wall
Latch (2 locations)
Connect the pipes on both liquid and gas sides. Tighten the nuts to the following torque.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m) Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m)
Connection Insulation of the connection portion
Indoor
Liquid side Gas side
(Do not turn)
• Cover the indoor unit s flare-connected joints, after they are checked for a gas leak, with an indoor unit heat insulating material and then wrap them with a tape with an attached insulation pad placed over the heat insulating material’s slit area.
Cover the coupling with insulator and then cover it with tapes.
Vinyl tape
Use an attached insulation pad for heat insulation.
Position it so that the slit area faces upward.
-
24
-
'11 • SRK-T-118
• Flaring work
Measurement B
Flaring block
Copper pipe
Finishing work and fixing
Connection wiring, Earth wiring
Outer tape
Refrigerant piping
Drain hose
Wood screw
Clamp
Cover the exterior portion with outer tape and shape the piping so it will match the contours of the route that the piping to take. Also fix the wiring and pipings to the wall with clamps.
RLA012A012B
Open/close and detachment/attachment of the air inlet panel
To open, pull the panel at both ends of lower part
and release latches, then pull up the panel until you feel resistance. (The panel stops at approx. 60° open position)
To close, hold the panel at both ends of lower
part to lower downward and push it slightly until the latch works.
To remove, pull up the panel to the position
shown in right illustration and pull it toward you.
To install, insert the panel arm into the slot on the
front panel from the position shown in right illustration, hold the panel at both ends of lower part, lower it downward slowly, then push it slightly until the latch works.
How to remove and fit the front panel
Removing
Remove the air inlet panel.
Remove the 2 set screws.
Remove the 3 latches in the upper section.
Move the lower part of the panel forward and
push upwards to remove.
1
2
3
4
Fitting
Do remove the air filter.
Cover the body with the front panel.
Fit the 3 latches in the upper section.
Tighten the 2 set screws.
Fit the air filter.
Fit the air inlet panel.
1
2
3
4
5
6
Set screws
Uncover the wireless remote control, and mount the batteries
[R03 (AAA, Micro), ×2 pieces] in the body regularly. (Fit the poles with the indication marks, & without fail)
Conventionally, operate the wireless remote control by holding
in your hand.
Avoid installing it on a clay wall etc.
Cover
CAUTION
Wood screws ø3.5 X 16
Wireless remote control
Battery
INSTALLATION OF WIRELESS CONTROL
Mounting method of battery
Fixing to pillar or wall
Do not use new and old batteries together.
2
6
5
Remove the lid. Remove the terminal cover. Remove the wiring clamp. Connect the connecting wire securely to the terminal block.
1) Connect the connection wire securely to the terminal block. If the wire is not affixed completely, contact will be poor, and it is dangerous as the terminal block may heat up and catch fire.
2) Take care not to confuse the terminal numbers for indoor and outdoor connections.
Fix the connecting wire by wiring clamp. Attach the terminal cover. Attach the lid.
1
2
3
4
5
6
7
ELECTRICAL WIRING WORK
CAUTION
In case of faulty wiring connection, the indoor unit stops, and then the run lamp turns on and the timer lamp blinks.
Use cables for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required field cables.
H05RNR4G1.5 (example) or 245IEC57 H Harmonized cable type 05 300/500 volts R Natural-and/or synth, rubber wire insulation N Polychloroprene rubber conductors insulation R Stranded core 4or5 Number of conductors G One conductor of the cable is the earth conductor (yellow/green)
1.5 Section of copper wire (mm2)
Preparation of indoor unit
Mounting of connecting wires
Terminal block
Lid
Terminal cover
Clamp
The screws of the lid and the terminal cover are tightened securely.
1 3
2 N
• Forced cooling operation Turn on a power supply again after a while after turn off a power supply. Then press continually the ON/OFF button 5 seconds or more.
Install the removed flared nuts to the pipes to be connected,
then flared the pipes.
Remove the flared nuts. (on both liquid and gas sides)
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
CONNECTION OF REFRIGERANT PIPINGS
Preparation
(Do not turn)
Press
Remove
A
90 ± 0.5˚
Dimension A Liquid side ø6.35 : 9.1 (mm) Gas side ø9.52 : 13.2 (mm)
ø12.7 : 16.6 (mm)
CAUTION
Do not apply refrigerating machine oil to the flared surface.
Indoor
Copper pipe diameter
Use a flare tool designed for R410A or a conventional flare tool. Please note that measurement B (protrusion from the flaring block) will vary depending on the type of a flare tool in use. If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value.
Clutch type flare tool for R410A
Conventional (R22) flare tool
ø6.35
ø9.52
ø12.7
0.0 - 0.5
0.0 - 0.5
0.0 - 0.5
1.0 - 1.5
1.0 - 1.5
1.0 - 1.5
1.5 - 2.0
1.5 - 2.0
2.0 - 2.5
Measurement B (mm)
Clutch type Wing nut type
CAUTION
Do not apply excess torque to the flared nuts. Otherwise, the flared nuts may check depending.
Arrange the drain hose in a downward angle. Avoid the following drain piping.
Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor. When the extended drain hose is indoor, securely insulate it with a heat insulator available in the market.
CAUTION
Wall
Gutter
Pipe accommodating section
Since this air conditioner has been designed to collect dew drops on the rear surface to the drain pan, do not attach the power cord above the gutter.
Drainage
Go through all installation steps and check if the drainage is all right. Otherwise water leak may occur.
Higher than specified The drain hose
tip is in water.
Wavy The drain hose
tip is in the gutter.
The gap to the ground is 5 cm or less.
Odor from the gutter
2
1
Installation Steps
Pass the pipe through the hole in the wall, and hook the upper part of the indoor unit to the installation board.
Gently push the lower part to secure the unit.
• How to remove the indoor unit from the installation board
Fixing of indoor unit
Push up at the marked portion of the indoor unit base lower latch, and slightly pull it toward you. (both right and left hand sides) (The indoor unit base lower latch can be removed from the installation board) Push up the indoor unit upward. So the indoor unit will be removed from the installation board.
1
2
The marked portion of the indoor unit base lower latch.
Indoor unit
Installation board
Installation board
Indoor unit base latch
Wall
Latch (2 locations)
CONCERNING TERMINAL CONNECTION FOR AN INTERFACE
Remove the front panel and lid of control. Remove the control. There is a terminal (respectively marked with CNS) for the indoor control board. In connecting an interface, connect to the respective terminal securely with the connection harness supplied with an optional “Interface connection kit SC-BIKN-E” and fasten the connection harness onto the indoor control box with the clamp supplied with the kit. For more details, please refer to the user’s manual of your “Interface connection kit SC-BIKN-E”.
1
2
3
INSTALLATION TEST CHECK POINTS
After installation
The power supply voltage is correct as the rating.
No gas leaks from the joints of the operation valve.
Power cables and crossover wires are securely fixed to the terminal board.
The screws of the lid and the terminal cover are tightened securely.
Operation valve is fully open.
The pipe joints for indoor and outdoor pipes have been insulated.
Air conditioning operation is normal.
No abnormal noise.
Water drains smoothly.
Protective functions are not working.
The remote control is normal.
Operation of the unit has been explained to the customer.
(Three-minutes restart preventive timer) When the air conditioner is restarted or when changing the operation, the unit will not start operating for approximately 3 minutes. This is to protect the unit and it is not a malfunction.
Test run
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly. At the same time, explain to the customer how to use the unit and how to take care of the unit following the user’s manual.
Connect the pipes on both liquid and gas sides. Tighten the nuts to the following torque.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m) Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m)
Connection Insulation of the connection portion
Indoor
Liquid side Gas side
(Do not turn)
• Cover the indoor unit s flare-connected joints, after they are checked for a gas leak, with an indoor unit heat insulating material and then wrap them with a tape with an attached insulation pad placed over the heat insulating material’s slit area.
Cover the coupling with insulator and then cover it with tapes.
Vinyl tape
Use an attached insulation pad for heat insulation.
Position it so that the slit area faces upward.
Installing the air-cleaning filters
Filter holder
Air-cleaning filter
1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders. In the air conditioner.
• Each air-cleaning filter can be installed in the left or right filter holder.
3. Install the air filters and close the inlet panel.
Connect charge hose to check joint of outdoor unit. Liquid side : Close the liquid valve with hexagon wrench key. Gas side : Fully open the gas valve. Carry out cooling operation. (If indoor temperature is low, operate forced cooling operation.) After low pressure gauge become 0.01MPa, stop cooling operation and close the gas valve.
1
2
3
<How to pump down>
In order to protect the environment, be sure to pump down (recovery of refrigerant). Pump down is the method of recovering refrigerant from the indoor unit to the
outdoor unit when the pipes are removed from the unit.
HOW TO RELOCATE OR DISPOSE OF THE UNIT
Unit ON/OFF button
Indoor unit PCB
CNS terminal
Lid of control
-
25
-
'11 • SRK-T-118
Notabilia as a unit designed for R410A
Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant. A cylinder containing R410A has a pink indication mark on the top.
A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure. Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.
Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
In charging refrigerant, always take it out from a cylinder in the liquid phase.
All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
1. HAULAGE AND INSTALLATION
CAUTION
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position. If not properly balanced, the unit can be thrown off-balance and fall.
1) Delivery
Deliver the unit as close as possible to the installation site before removing it from the packaging.
When you have to unpack the unit for a compelling reason before you haul it to the installation point, hoist the unit with nylon slings or ropes and protection pads so that you may not damage the unit.
2) Portage
The right hand side of the unit as viewed from the front (diffuser side) is heavier. A person carrying the right hand side must take heed of this fact. A person carrying the left hand side must hold with his right hand the handle provided on the front panel of the unit and with his left hand the corner column section
3) Selecting the installation location
Be careful of the following conditions and choose an installation place.
Where air is not trapped.
Where the installation fittings can be firmly installed.
Where wind does not hinder the intake and outlet pipes.
Out of the heat range of other heat sources.
A place where stringent regulation of electric noises is applicable.
Where it is safe for the drain water to be discharged.
Where noise and hot air will not bother neighboring residents.
Where snow will not accumulate.
Where strong winds will not blow against the outlet pipe.
A place where no TV set or radio receiver is placed within 5m.
(If electrical interference is caused, seek a place less likely to cause the problem)
If a operation is conducted when the outdoor air temperature is -5lower, the outdoor unit should be installed
at a place where it is not influenced by natural wind.
Where it is likely that the unit is subjected to strong winds, provide wind guards according to the following guidelines Strong winds can cause performance degradation, an accidental stop due to a rise of high pressure and a broken fan
1.Place the unit outlet pipe perpendicular to the wind direction.
INSTALLATION MANUAL FOR OUTDOOR UNIT
• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order to protect yourself.
• The precautionary items mentioned below are distinguished into two levels, and .
: Wrong installation would cause serious consequences such as injuries or death. : Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance methods of this equipment to the user according to the owner’s manual.
• Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user.
• For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform the installation works.
• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:
• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to the respective installation manuals supplied with the units.
• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
SAFETY PRECAUTIONS
WARNING
Never do it under any circumstances. Always do it according to the instruction.
CAUTIONWARNING
CAUTION
WARNING
• Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except the by qualified installer.
• Install the system in full accordance with the installation manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.
• Be sure to use only for household and residence.
If this appliance is installed i n inferior environment such as machine shop and etc., it can cause malfunction.
• When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
• Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water leaks, electric shocks, fire and personal injury.
• Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
• Ensure the unit is stable when installed, so that it can withstand earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
• Ventilate the working area well in the event of refrigerant leakage during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is produced.
• Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.
• Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and refrigerant leakage after a long period.
• Do not open the operation valves for liquid line and gas line until completed refrigerant piping work, air tightness test and evacuation.
If the compressor is operated in state of opening operation valves before completed connection of refriger ant piping work, air can be sucked into refrigerant circuit, which can cause bust or personal injury due to anomalously high pressure in the refrigerant.
• The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work” and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire.
• Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment.
• Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
• This appliance must be connected to main power supply by means of a
circuit breaker or switch (fuse:16A) with a contact separation of at least 3mm.
• Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
• Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production or fire.
• Be sure to fix up the service panels.
Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.
• Be sure to switch off the power supply in the event of installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.
• Stop the compressor before removing the pipe after shutting the service valve on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
• Only use prescribed optional parts. The installation must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire.
• Be sure to wear protective goggles and gloves while at work.
• Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
• Ensure that no air enters in the refrigerant circuit when the unit is installed and removed.
If air enters in th e refrigerant circuit, the pres sure in the refrigerant circuit becomes too high, w hich can cause burst and person al injury.
Do not processing, splice the power cord, or share a socket with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.
• Do not bundling, winding or processing for the power cord. Or, do not deforming the power plug due to tread it.
This may cause fire or heating.
• Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric shocks.
• Do not perform any change of protective device itself or its setup condition.
The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non specified component can cause fire or burst.
RWC012A030C
Model 09, 12
R410A REFRIGERANT USED
a
(2) Installation of outdoor unit
Models DXC09ZJ-S, 12ZJ-S
-
26
-
'11 • SRK-T-118
2. REFRIGERANT PIPING WORK
1) Restrictions on unit installation and use
Check the following points in light of the indoor unit specifications and the installation site.
Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation
Additional refrigerant charge is not required at all.
2) Determination of pipe size
Determine refrigerant pipe size pursuant to the following guidelines based on the
  indoor unit specifications.
Notabilia as a unit designed for R410A
Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant. A cylinder containing R410A has a pink indication mark on the top.
A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure. Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.
Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
In charging refrigerant, always take it out from a cylinder in the liquid phase.
All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
1. HAULAGE AND INSTALLATION
CAUTION
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position. If not properly balanced, the unit can be thrown off-balance and fall.
1) Delivery
Deliver the unit as close as possible to the installation site before removing it from the packaging.
When you have to unpack the unit for a compelling reason before you haul it to the installation point, hoist the unit with nylon slings or ropes and protection pads so that you may not damage the unit.
2) Portage
The right hand side of the unit as viewed from the front (diffuser side) is heavier. A person carrying the right hand side must take heed of this fact. A person carrying the left hand side must hold with his right hand the handle provided on the front panel of the unit and with his left hand the corner column section
3) Selecting the installation location
Be careful of the following conditions and choose an installation place.
Where air is not trapped.
Where the installation fittings can be firmly installed.
Where wind does not hinder the intake and outlet pipes.
Out of the heat range of other heat sources.
A place where stringent regulation of electric noises is applicable.
Where it is safe for the drain water to be discharged.
Where noise and hot air will not bother neighboring residents.
Where snow will not accumulate.
Where strong winds will not blow against the outlet pipe.
A place where no TV set or radio receiver is placed within 5m. (If electrical interference is caused, seek a place less likely to cause the problem)
If a operation is conducted when the outdoor air temperature is -5lower, the outdoor unit should be installed
at a place where it is not influenced by natural wind.
Where it is likely that the unit is subjected to strong winds, provide wind guards according to the following guidelines
Strong winds can cause performance degradation, an accidental stop due to a rise of high pressure and a broken fan
1.Place the unit outlet pipe perpendicular to the wind direction.
2.Install so the direction of the air from the blowing outlet will be perpendicular to the direction of the wind.
CAUTION
The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.
Main pipe length
Elevation difference between indoor and outdoor units
Outdoor unit connected
Refrigerant piping (branch pipeL)
Indoor unit connected
3) Refrigerant pipe wall thickness and material
Select refrigerant pipes of the table shown on the right wall thickness and material as specified for each pipe size.
NOTE
Select pipes having a wall thickness larger than the specified
minimum pipe thickness.
Accessories for outdoor unit
• Model name and power source
• Refrigerant piping length
• Piping, wiring and miscellaneous small parts
• Indoor unit installation manual
Necessary tools for the installation work
Wrench key (Hexagon) [4m/m] Vacuum pump Vacuum pump adapter (Anti-reverse flow type) (Designed specifically for R410A) Gauge manifold (Designed specifically for R410A) Charge hose (Designed specifically for R410A) Flaring tool set (Designed specifically for R410A) Gas leak detector (Designed specifically for R410A) Gauge for projection adjustment (Used when flare is made by using conventional flare tool)
9
10
11
12 13 14 15
16
Plus headed driver Knife Saw Tape measure Hammer Spanner wrench Torque wrench [14.0~62.0N·m (1.4~6.2kgf·m)] Hole core drill (65mm in diameter)
1 2 3 4 5 6 7 8
Grommet (Heat pump type only) Drain elbow (Heat pump type only)
Q’ty
1 1
1 2
Option parts
Sealing plate Sleeve Inclination plate Putty Drain hose (extension hose) Piping cover (for insulation of connection piping)
Q’ty
1 1 1 1 1
1
Check before installation work
a b c d e
f
INSTALLATION MANUAL FOR OUTDOOR UNIT
Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order to protect yourself.
The precautionary items mentioned below are distinguished into two levels, and .
: Wrong installation would cause serious consequences such as injuries or death. : Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance methods of this equipment to the user according to the owners manual.
Keep the installation manual together with owners manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user.
For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform the installation works.
Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
If unusual noise can be heard during operation, consult the dealer.
The meanings of “Marks” used here are shown as follows:
This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to the respective installation manuals supplied with the units.
When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
SAFETY PRECAUTIONS
WARNING
Never do it under any circumstances. Always do it according to the instruction.
CAUTIONWARNING
CAUTION
WARNING
CAUTION
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.
Installation must be carried out by the qualified installer.
If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except the by qualified installer.
Install the system in full accordance with the installation manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.
Be sure to use only for household and residence.
If this appliance is installed i n inferior environment such as machine shop and etc., it can cause malfunction.
When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
Use the original accessories and the specified components for installation.
If parts other than those prescribed by us are used, It may cause water leaks, electric shocks, fire and personal injury.
Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
Ensure the unit is stable when installed, so that it can withstand earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
Ventilate the working area well in the event of refrigerant leakage during installation.
If the refrigerant comes into contact with naked flames, poisonous gas is produced.
Use the prescribed pipes, flare nuts and tools for R410A.
Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.
Tighten the flare nut by torque wrench with specified method.
If the flare nut were tightened with excess torque, this may cause burst and refrigerant leakage after a long period.
Do not open the operation valves for liquid line and gas line until completed refrigerant piping work, air tightness test and evacuation.
If the compressor is operated in state of opening operation valves before completed connection of refriger ant piping work, air can be sucked into refrigerant circuit, which can cause bust or personal injury due to anomalously high pressure in the refrigerant.
The electrical installation must be carried out by the qualified electrician in accordance with the norm for electrical work and national wiring regulation, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire.
Be sure to shut off the power before starting electrical work.
Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment.
Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
This appliance must be connected to main power supply by means of a
circuit breaker or switch (fuse:16A) with a contact separation of at least 3mm.
Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production or fire.
Be sure to fix up the service panels.
Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.
Be sure to switch off the power supply in the event of installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.
Stop the compressor before removing the pipe after shutting the service valve on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
Only use prescribed optional parts. The installation must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire.
Be sure to wear protective goggles and gloves while at work.
Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
Ensure that no air enters in the refrigerant circuit when the unit is installed and removed.
If air enters in th e refrigerant circuit, the pres sure in the refrigerant circuit becomes too high, w hich can cause burst and person al injury.
Do not processing, splice the power cord, or share a socket with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.
Do not bundling, winding or processing for the power cord. Or, do not deforming the power plug due to tread it.
This may cause fire or heating.
Do not run the unit with removed panels or protections.
Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric shocks.
Do not perform any change of protective device itself or its setup condition.
The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non specified component can cause fire or burst.
• Use the circuit breaker for all pole correct capacity. Circuit breaker should be the one that disconnect all poles under over current.
Using the incorrect circuit breaker, it can cause the unit malfunction and fire.
• Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
• After maintenance, all wiring, wiring ties and the like, should be returned to their original state and wiring route, and the necessary clearance from all metal parts should be secured.
• Secure a space for installation, inspection and maintenance specified in the manual.
Insufficient space can result in accident such as personal injury due to falling from the installation place.
• Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more persons. Do not carry by the plastic straps, always use the carry handle when carrying the unit by hand. Use gloves to minimize the risk of cuts by the aluminum fins.
• Dispose of any packing materials correctly.
Any remaining packing materials can cause personal injury as it contains nails and wood. And to avoid dan ger of suffocation, be sure to keep t he plastic wrapper away from children and to dispose after tear it up.
• Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.
Insufficient insulation ca n cause condensation, which can lead to mois ture damage on the ceiling, flo or, furniture and any other valua bles.
• When perform the air conditioner operation (cooling or drying operation) in which ventilator is installed in the room. In this case, using the air conditioner in parallel with the ventilator, there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status. Therefore, set up the opening port such as incorporate the air into the room that may appropriate to ventilation (For example; Open the door a little). In addition, just as above, so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc.
• Do not install the unit in the locations listed below.
•Locations w here carbon fiber, metal powder or any powder is floating.
•Locations w here any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur.
•Vehicles and ships.
•Locations w here cosmetic or special sprays are often used.
•Locations w ith direct exposure of oil mist and steam such as kitchen and machine plant.
•Locations w here any machines which generate high frequency harmonics are used.
•Locations w ith salty atmospheres such as coastlines.
•Locations w ith heavy snow (If installed, be sure to provide base flame and snow hood mentioned in the manual).
•Locations w here the unit is exposed to chimney smoke.
•Locations a t high altitude (more than 1000m high).
•Locations w ith ammonic atmospheres.
•Locations w here heat radiation from other heat source can affect the unit.
•Locations w ithout good air circulation.
•Locations w ith any obstacles which can prevent inlet and outlet air of the unit.
•Locations w here short circuit of air can occur (in case of multiple units installation).
•Locations w here strong air blows against the air outlet of outdoor unit.
•Locations w here something located above the unit could fall.
It can cause remarkable decrease in performance, corrosion and damage of components, malfunction and fire.
• Do not install the outdoor unit in the locations listed below.
Locations where discharged hot air or operating sound of the outdoor unit c an
bother neighborhood.
Locations where outlet air of the outdoor unit blows directly to an animal or plants. The outlet air can affect adversely to the plant etc.
Locations where vibration can be amplified and transmitted due to insuffici ent strength of structure.
Locations where vibration and operation sound generated by the outdoor unit can affect seriously (on the wall or at the place near bed room).
Locations where an equipment affected by high harmonics is placed (TV set o r radio receiver is placed within 5m).
Locations where drainage cannot run off safely.
It can affect surrounding environment and cause a claim.
• Do not install the unit near the location where leakage of combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fire.
• Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can accumulate or collect, or where volatile combustible substances are handled.
Corrosive gas can caus e corrosion of heat exchanger, breakage of plasti c parts and etc. And combustib le gas can cause fire.
• Do not install nor use the system close to the equipment that generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency equipments and telecommunication equipments can affect the system, and cause malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.
Do not inst all the outdoor unit in a location where insects and small
animals can inhabit.
Insects and small animals can enter the electric parts and cause damage or fire. Instruct the user to keep the surroundings clean.
Do not use the base flame for outdoor unit which is corroded or damaged
due to long periods of operation.
Using an old and damage base flame can cause the unit falling down and cause personal injury.
Do not use any materials other than a fuse with the correct rating in the
location where fuses are to be used.
Connecting the circ uit with copper wire or other m etal thread can cause unit failure and fire.
Do not touc h any buttons with wet hands. It can cause electric shocks.
Do not touch any refrigerant pipes with your hands when the system is in
operation.
During operation the refrigerant pipes become extremely hot or extremely cold depending the operating condition, and it can cause burn injury or frost injury.
Do not touc h the suction or aluminum fin on the outdoor unit. This may cause injury.
Do not put anything on the outdoor unit and operating unit. This may cause damage the objects or injury due to falling to the object.
Do not use the unit for special purposes such as storing foods, cooling
precision instruments and preservation of animals, plants or art.
Do not clea n up the unit with water.
RWC012A030C
Model 09, 12
R410A REFRIGERANT USED
a
-
27
-
'11 • SRK-T-118
Notabilia as a unit designed for R410A
Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.
A cylinder containing R410A has a pink indication mark on the top.
A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure. Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.
Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
In charging refrigerant, always take it out from a cylinder in the liquid phase.
All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
1. HAULAGE AND INSTALLATION
(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)
②
Notabilia for installation
Intake
The height of a wall is 1200mm or less.
(
service space
)
Intake
Outlet
Fasten with bolts
(M10-12)
Use a thicker block toanchor deeper.
Use a long block to extend the width.
CAUTION
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position. If not properly balanced, the unit can be thrown off-balance and fall.
1) Delivery
Deliver the unit as close as possible to the installation site before removing it from the packaging.
When you have to unpack the unit for a compelling reason before you haul it to the installation point, hoist the unit with nylon slings or ropes and protection pads so that you may not damage the unit.
2) Portage
The right hand side of the unit as viewed from the front (diffuser side) is heavier. A person carrying the right hand side must take heed of this fact. A person carrying the left hand side must hold with his right hand the handle provided on the front panel of the unit and with his left hand the corner column section
.
3) Selecting the installation location
Be careful of the following conditions and choose an installation place.
Where air is not trapped.
Where the installation fittings can be firmly installed.
Where wind does not hinder the intake and outlet pipes. Out of the heat range of other heat sources.
A place where stringent regulation of electric noises is applicable.
Where it is safe for the drain water to be discharged.
Where noise and hot air will not bother neighboring residents.
Where snow will not accumulate.
Where strong winds will not blow against the outlet pipe.
A place where no TV set or radio receiver is placed within 5m. (If electrical interference is caused, seek a place less likely to cause the problem)
If a operation is conducted when the outdoor air temperature is -5℃lower, the outdoor unit should be installed
at a place where it is not influenced by natural wind.
Where it is likely that the unit is subjected to strong winds, provide wind guards according to the following guidelines
.
Strong winds can cause performance degradation, an accidental stop due to a rise of high pressure and a broken fan
.
4) Installation space
Walls surrounding the unit in the four sides are not acceptable.
There must be a 1-meter or larger space in the above.
When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service space. In order to facilitate servicing of controllers, please provide a sufficient space between units so that their top plates can be removed easily.
Where a danger of short-circuiting exists, install guide louvers.
When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur
.
Where piling snow can bury the outdoor unit, provide proper snow guards.
1.Place the unit outlet pipe perpendicular to the wind direction.
L3
L
2
L
4
L
1
Model 09, 12
Example installation
Size
L1 L2 L3 L4
Open
100 100 250
280
75 80
Open
280
Open
80
250
180
Open
80
Open
(mm)
①
Anchor bolt fixed position
In installing the unit, fix the unit’s legs with bolts specified on the left.
The protrusion of an anchor bolt on the front side must be kept within 15 mm.
Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
Refer to the above illustrations for information regarding concrete foundations.
Install the unit in a level area. (With a gradient of 5 mm or less.) Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
Heavy
Wind direction
Wind direction
2.Install so the direction of the air from the blowing outlet will be perpendicular to the direction of the wind.
5) Installation
Pad
Over 500mm
Intake
Outlet
312.5
24.314.8
288.8
111
510 157.8
351.6
Loading...
+ 85 hidden pages