Energy Saving Control
Enables Energy Saving Control with the use of our new PI controller.
(Registration of “Energy Save” licence is required.)
To perform energy saving, the capacity of the outdoor unit is
controlled.
Charge Calculation
Enables charge calculation for each tenant and output as CSV file
Dimension: 200(W) x 120(H) x 45(D) mm
: 7-7/8(W) x 4-3/4(H) x 1-13/16(D) in.
No more PLCs are needed!
Our new PI controller makes it possible to perform energy
saving without PLC, which is cost saving.
Maximum of 4 measurement meter (WHM, gas meter, water
meter, calorie meter) can be connected to the PI controller
and can be used also for charge calculation.
*24 VDC power needs to be provided on site.
System Structure
Remote monitoring via a
Web browser
PI Controller PAC-YG60MCA
System Structure
Maximum Capacity at 80%
Capacity
Capacity
Value
With energy-savining effectsNo energy-saving
effects
80%
Time
Amount of saved energy
.
Control level setting
.
Monitors current state
.
Monitors demand level
.
Monitors electric power
Registration of
“Energy Save” license
.
Outdoor unit control
- Capacity control
(60/70/80/90%)
.
Indoor unit control
- +- 2
˚C control
- Fan control
- Stop control
TG-2000A collects operation
and electric power data from
AG-150A and PI controller and
does apportion calculation.
AG-150A monitors every minute
and stores operation data
necessary for charging.
PI controller counts pulse output from
the watt-hour meter.
Watt-hour meter
Max. 4
PI controller
M-NETLAN
M-NET
LAN
Watt-hour meter
PI controller
Centralized
Remote Controller
*Please note that when using an energy saving control,
there are no warranties to failures such as usage over the contracted electricity.
AG-150A
Registration of
“Charge Calculation” license
AG-150A
Centralized controller GB-50A
The Web Server Function enables Remote Operation or Scheduling Via a
Web Browser on a Personal Computer! Up to 50 indoor units can be
controlled!
Web Browser
Enables monitoring and operation of indoor units using a PC with
Microsoft
®
Internet Explorer (Ver.5 or upper) (Web browser function is
an optional and needs license registration.)
*Use a security device such as a VPN (Virtual Private Network) router when
connecting the GB-50A to the Internet to prevent unauthorized access.
Using “Dial-up Connection”
• Enables monitoring and operation from a remote place
• Enables error notification by e-mails to a PC or to a mobile phone
Annual / Weekly Schedule
Enables Weekly and Annual scheduling with a registering
license
• ON/OFF, operation mode, temperature setting, prohibit remote
controller operation can be set.
• For annual schedule, it is possible to set 50 day-long settings up to
24 months into the future.
• Dimensions:250 (W) x 130 (H) x 38 (D) mm
:9-7/8 (W) x 5-1/8 (H) x 1-1/2 (D) in.
GB-50A (without display)
System Structure
GB-50A
M-NETLAN
HUB
Remote monitoring via a
Web browser
Web
license
Operation
Example of display icons (air conditioner icons)
Stop
Occurrence of
abnormality
Operation/
Occurrence of a filter sign
In timer operation
Lossnay on
Under energy-saving
control
ON
8:00
(Start)
12:00
(Lunchtime)
13:00
(Energy saving)
15:00 17:00
(Overtime)
22:00
OFF
1 42 63 5
Public telephone
line
Provider
Router
Transmits abnormality mail.
Scheduling example in the office
27˚C [81˚F] Cooling
Up to 12 operation settings per day in 1-minute increment
29˚C [84˚F] Cooling
All operations
permitted
All operations
permitted
All operations
prohibited
All operations
prohibited
Temperature
adjustment
prohibited
Temperature
adjustment
prohibited
Controllable unit
Dimension W x H x D
ON / OFF
Mode selection
Temperature setting
Air flow direction setting
Timer operation / Schedule
Permit / Prohibit function
Indoor return air temperature
Error
Test run
Ventilation interlock
Function
Description
GB-50A (web browser)
[ ] For PEFY/PFFY by setting DipSW 7-1 to ON and limits to NI6H fan speed only.
*NOTE: Operation and displayed content vary depending on the indoor unit model.
Up to 50 units/groups.
250 (9-7/8) x 130 (5-1/8) x 38 (1-1/2) mm (in)
Run and Stop operation
Cool / Dry / Auto / Fan / Heat mode varies depending on the indoor unit.
Range of temperature setting
Cool/Dry:19-30˚C [14-30˚C] / 67-87˚F [57-87˚F]
Heat :17-28˚C [17-28˚C] / 63-83˚F [63-83˚F]
Auto :19-28˚C [17-28˚C] / 67-83˚F [63-83˚F]
✻Range of temperature settings vary depending on model.
Air flow direction angles, 4-angle or 5-angle Swing, Auto (Louver cannot be set)
Annual/weekly/day schedule can be set. (Up to 12 events can be set per day for each group.) *License required.
Individually prohibit operation of each local remote control function
Displays the measured intake temperature from each group
When an error is currently occurring on an air conditioner unit, the afflicted unit and the error code are displayed.
-
The ventilation unit (LOSSNAY) is able to automatically start its operation when operation of the interlocked indoor unit starts.
Power supply unit
PAC-SC51KUA