Mitsubishi CL1XY4-DT1B2 User Manual

Side
IN
X
0 X
1 X
2 X
3
0
1
2
3
P W
L
R U
N
L E
R R
.
S T
A
T IO
N
N O
.
ON
1)
Installation Removal
2)
3)
4)
CL1XY4-DT1B2
Connector for CC-Link/LT interface
External power supply of the input part (24V DC)
Load power supply
. . .
DC DC
R
R
Y0 COM+ Y1 COM+ DC24V DC24G
10
16
15
14
13
12
11
9
NC NC
X0 COMB X1 COMB NC NC
1 2 3 4 5 6 7 8
DC24A DC24B
1
+24V
2
DA
3
DB
4
24G
Terminal block for I/O interface (positive common input)
Terminal block for I/O interface (sink output)
. . .
L
L
Isolation
B
Side
A
JAPANESE ENGLISH
Side
B
CL1XY4-DT1B2
CC-Link/LT Remote I/O Module
Please read this manual thoroughly before star ting to use the product and handle the product properly.
User’s Manual
MODEL CL1XY4-DT1B2 MANUAL Number JY997D05601 E Date September 2008

SAFETY PRECAUTIONS

Please read this m anual carefully a nd pay special atten tion to safely in order to handle this product properly. Also pay careful attention to safely and handle the module properly. These precautions apply onl y to Mitsubishi equipment. Refer to th e user’s manual of the CPU mo dule to use for a descr iption of the PLC system safety precautions. These ●SAFETY PRECAUTIONS● classify the safety precautions into two categories: "DANGER" and "CAUTION".
DANGER
CAUTION
Depending on c ircumstances, procedures ind icated by may also be linked to serious results. In any case, it is important to follow the directions for usage. Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIO NS]
• Configur e an interlock circuit in a sequence program so that the system operates on the safety side usi ng the communication status information in the event the data link falls into a communi cation problem. Otherwise, erroneous outp ut and malfunction may result i n accidents.
• Remote input and output can not be switched ON or OFF when a problem occurs in the remote I/O modules. Therefore build an exter nal monitoring circuit that will monitor any input signa ls that could cause a serious accident.
(Read these precautions before using )
Procedures which may lead to a dangerous c ondition and cause death or serious injur y if not carried out properly.
Procedures which may lead to a dangerous c ondition and cause superficial to medium injur y, or physical damage only, if not carried out properly.
DANGER
CAUTION
• Do not have control cables and communication ca bles bundled with or placed near by the main c ircuit and/or power cables. Wire thos e cables at least 100mm(3.94 inc h) away from the main circuit and/or p ower cables. It may cause malfunction du e to noise interference.
• Use the m odule and the flat cable de dicated to CC-Link/LT without applying any force on them. Otherwise, such cables may be broken or fail.
[INSTALLATION PRECAUTIONS]
CAUTION
• Use t he module in an environment that meets the general specifications contained in this manual . Using this module in an environment outside the range of the general specifications could result in electric shock, fire, erroneous operation, and damage to or deterio ration of the product.
• Do not directly touch the module 's conductive parts.Doing so could cause malfunction or trouble in the module.
• Tighten the module securely using DIN rail or installation screws within the specified torque range. If the screws are too lose, the m odule may drop from its installa tion position, shor t circuit, or malfunction. If the screws are too tight, the screws may be damaged, which may cau se the module to drop fro m its installation position or short circuit.
• Install the module on a flat surface. If the mounting surface has conc ave and/or convex, an excessive force may be applied on the module, and nonconformity may be cause d.
CAUTION
[WIRING PRECAUTIONS]
• Perform installation and wiring after discon necting the power supply at a ll phases externally. If the power is not disconnected at al l phases an electric shock or product damage may resul t.
DANGER
CAUTION
• Terminal screws which are not to be used must be tightene d always. Otherwise there will be a danger of short c ircuit against the bare sol derless terminals.
• Do no t perform wiring to an id le terminal "NC" outsid e the product. The product may be damaged by suc h external wiring.
• Perform correct wiring for the modul e according to the product’s rated voltage and terminal arrangement. Connecting to a power supply different from rating or miss-wiring may cause f ire, product failure or malfunctio n.
• Fix ter minal screws securely withi n the regulated torque. Loos e terminal screws may cause fire and/or malfunctio n. If the terminal screws are t oo tight, it may cause shor t circuit or erroneo us operation due to damage of the screws.
• Make sure foreign objects do not get inside the module, such as dir t and wire chips. It may cause fire, product failure or ma lfunction.
• Attach a warning label (hazar d symbol 417-IEC-5036) concerning the ele ctric shock to the location.
[STARTING AND MAINTENANCE PRECAUTIONS]
• Do no t touch the terminals when the power is ON. It may cause a n electric shock or malfunction.
• Perform cleaning th e module or retightenin g of terminal screws after turning OFF the all external power supply for sure. Failure to do so may cause failure or malfunction of the modules
DANGER
CAUTION
• Do no t disassemble or modify the module. Doing so may cause failure, malfunction, injur y, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock. A module damage may result.
• Make sure t o switch all phases of the exter nal power supply OFF before installing or removing the mod ule to/from the pane l. Failure to do so may cause failure or malfunction of th e modules.
[DISPOSAL PR ECAUTIONS]
• When d isposing of this produ ct, treat it as industri al waste.
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
• Dur ing transportation avoid any impact as the module is a precision instrument. Doing so cou ld cause trouble in the mod ule.
• If is n ecessary to check the ope ration of module after t ransportation, in cas e of any impact damage.

Notification of CE marking

This notification does not guarantee that an entire mechanical modul e produced in accordance with the contents of the notification comply with the following standards. C ompliance to EMC standards of the ent ire mechani cal module should be checked by the user / ma nufacturer.
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module Models : Products manufactured:
from February 1st , 2003 to April 30th, 2006 are compliant with EN61000-6-4 and E N61131-2:1994+A11:19 96+A12:2000 after May 1st, 2006 are compl iant with EN61131-2:200 3
Electromagnetic Compatibility
EN61000-6-4:2001
Electromagnetic compatibilit y
-Generic standards - Emission standard for Industrial environment
EN61131-2:1994/A11:1 996/A12:2000
Programmable controllers
-Equipment requirements and tests
EN61131-2: 2003
Programmable controllers
-Equipment requirements and tests
For more details please conta ct the local Mitsubishi Ele ctric sales site.
- Notes For compliance to EMC re gulation. It is necessary to install th e CL1 series module in a shielded metal control panel.
Standards (EMC)
DANGER
CAUTION
Remark
Compliance with all relevant aspects of the standard. (Radiated Emissions and M ains Terminal Voltage Emissions)
Compliance with all relevant aspects of the standard. (RF Immunity, Fast transients, ESD and Damped oscillator y wave)
Compliance with all relevant aspects of the standard. (Radiated Emissions, Mains Terminal Voltage Emissions, RF immunity, Fast Transients, ESD, Surge, Voltage drops and interruptions, Conduct ed and Power magnetic fields)

1. Outline of Product

This product is a terminal block type composite I/O module connecte d to CC-Link/LT. This product has four input points (24 VDC) and four output points (transistor output).

2. Name and Setting of Each Part and Terminal Arrangement

DIP switch
DIP switch assignment
40 20 10 8 4 2 1
ON
Connector for CC-Link/LT interface
Connector terminal assignment
24G
4 3
DB DA
2
+24V
1
Orange color
HLD
Status indicator
CL1XY4-DT1B2
LINK/PW
2-φ4.5 mounting hole (M4 mounting screw)
Terminal arrangement (Terminal number and Signal name)
1
DC
DC24A
24A
2
DC24B
PW
X0
X1
Y0
Y1
3X05X17NC9NC11Y013Y115
X0 X1 NC Y1
X0 X1
4
DC
X0 X1 NC Y1
COMB6COMB8NC
24B
Name Description
PW ON while the power is supplied.
L RUN ON while normal operation is executed.
ON:When a communication erro r or DIP switch
setting error occurred
Flickering at a constant inter val: Status indicator LEDs
I/O operation indicator LEDs
Connector for CC­Link/LT interface
Terminal block for I/O interface
Station number setting switches
When the setting of the DIP switch was changed
while the power was supplied (even while the LED is
flickering, the operation continues. The new setting
L ERR.
becomes valid when the power is turned OF F once,
then ON again.)
Flickering at a intermittent inter val:
When a terminal resis tor is not attached or when the
module or a connection cable is affected by noise
ON while the input or output is ON. Extinguished while the input or output is OFF.
Connector for CC-Link/LT communication line/module power supply (24G/DB/DA/+24V)
Terminal block to connect input signals, output signals, I/O power supply and load power supply
Set the 10's digit of the station No. using "STATIO N NO. 10", "STATION NO. 20" and "STATION NO. 40". Set the 1's dig it of the station No. using "STATION NO. 1", "STATION NO. 2", "STATION NO. 4" and "STATION NO. 8". Factory default = All bits are OFF. Make sure to set the station No. in the range from 1 to 64. If any station No. outside the range from 1 to 64 is set, it is regarded as an error and the L ERR. LED lights.
Example: When setting the station No. to "32", set the DIP switch as follows.
Station
No.
32 ONOFFONOFF ON OFF OFF
Input operation indicator LEDs
Input/output is ON: Lit
LEDs
Input/output is OFF : Extinguished
ON
IN
OUT
Terminal block for I/O interface
Hook for installation to DIN rail
NC NCNCY0
COMB NC
40 20 10 8 4 2 1
10 12
Input operation
indicator
10's digit 1's digit
0101
Output operation indicator LEDs
01L RUN L ERR.
01
40 2010 8 4 2 1
DC
DC24V
24V
COM+Y1COM+
COM+14COM+16DC24GNC
01 01
Output operation
indicator
DC 24G
Name Description
Response time setting switch
Holds the output ( when an error ha s occurred).
HLD
ON: Holds the output. OFF: Clears the output.

3. Installation

The CL1XY4-DT1B2 can be installed to DIN rail or directly installed using mounting screws. Each installation proc edure is described b elow.

3.1 Installation to DIN rail

Align the upper DIN rail installation groove in the module with the DIN rail
1), and press the mod ule in that status 2). When removing the module, pull the hook downward for installation to DIN rail 3), then remove the module 4).
DIN rail mounting screw pitch
When installing the module to the DIN rail, tighten the mounting screws at the pitch of 200mm(7 .87") or less.
Applicable DIN rail TH35-7.5Fe and TH35-7.5AI

3.2 Direct installation

Screw-tighten the module by attaching M4 screws to the upper and lower mounting holes (two hole s in all) provided in the modu le. Install the module so that the clearance of 1 to 2mm (0.04" to 0.08") is assured for each module.
Applicable screw
0.7mm(0.03") × 16mm(0.63") or more
M4
×
(Tightening torque range: 78 to 108 N⋅cm)

4. Wiring

4.1 External wiring

The input terminals of the CL1XY4-DT1B2 can be wired as positive common or negative common depending on the used sensor. (The output wiring is fixed to the sink o utput.)
Positive common
IN
X
0 X
1 X
2 X
3
0
1
2
3
P W
L
R U
N
L E
R R
.
S T
A
T IO
N
N O
.
ON
1)
Installation Removal
2)
3)
4)
CL1XY4-DT1B2
Connector for CC-Link/LT interface
External power supply of the input part (24V DC)
Load power supply
. . .
DC DC
R
R
Y0 COM+ Y1 COM+ DC24V DC24G
10
16
15
14
13
12
11
9
NC NC
X0 COMB X1 COMB NC NC
1 2 3 4 5 6 7 8
DC24A DC24B
1
+24V
2
DA
3
DB
4
24G
Terminal block for I/O interface (positive common input)
Terminal block for I/O interface (sink output)
. . .
L
L
Isolation
Negative common
2 - φ4.5(0.18") mounting hole (M4 mounting screw)
Center of DIN rail
49(1.93")
4.5 (0.18")
40(1.58")
40(1.58")
10(0.40")
80(3.15")
22(0.87")
71.5(2.82") ± 0.6(0.03")
6(0.24") 6.5(0.26")
41(1.62")
±
0.4(0.02")
Unit: mm(inches)
4
T
External power supply of the input part (24V DC)
Terminal block for I/O interface (Negative common input/sink output)
DC24A
1 2
DC24B
Wire nothing to the NC ter minal (idle term inal).

4.2 Connection to sensor

Positive common (NPN)
• When using a two-wire type sensoryWhen using a three-wire type sensor
Connected to DC 24A terminal
Bleeder resistor *1
Detection circuit
Sensor (NPN)
• When us ing a three-wire type se nsor (when using the power supp ly for sensor other than 24V DC)
Detection circuit
X *
COMB
X *
COMB
Negative common (PNP)
• When using a two-wire type sensoryWhen using a three-wire type sensor
Connected to DC 24A terminal Connected to DC 24A terminal
Bleeder resistor *1
Detection circuit
Sensor (PNP)
• When us ing a three-wire type se nsor (when using the power supp ly for sensor other than 24V DC)
Detection circuit
X *
COMB COMB
X *
COMB
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment containing a parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less. If the leakage current is more than 1.7mA, connect a bleeder resistor obtained in the following calculation formula.
Circuit image
R(kΩ) < 1.7(mA) / Leakage current(mA) - 1.7( mA) x 5.6(kΩ)
The power capacity W of the bleeder resistor R is as follows: W = (Input voltage)
• Make sur e that both the ON and OFF time of the input s ignal are 1.5ms or more.
Leakage
Unit
24V DC
current
R
2
/R
Sensor (NPN)
Detection circuit
Connected to DC 24A terminal
Detection circuit
Detection circuit
Input impedance
5.6 k
1.7 mA or less
R: Bleeder resistor
X *
COMB
X *

4.3 Crimp-style terminal

For I/O wiring, use crimp- style terminals of the following dimensions.
φ
3.2 (0.13")
Crimp-style terminal
6.2 mm (0.24" )
Terminal
2
or less
Terminal screw
6.2 mm (0.24" ) or less
When wiring one cable to one terminal When wiring two cables to one terminal
Terminal scre w
Terminal
Applicable crimp­style terminal
Applicabl e wire size
• RAV1.25-3
• V 1.25-3 (manufactured by JST M fg. Co., Ltd.)
• 1.2 5-3 and TG1.25-3 (manufactured by NICHIFU Co., Ltd.)
0.3 to 1.25 mm
φ
3.2 (0.13")
Crimp-style terminal
Use a crimp-style termi nal in a status in which no force is applied on the cable.

4.4 Module terminal screw

Tighten the termina l screws (M3 screws) on the terminal block with a tigh tening torque of 42 to 58 N⋅cm.

5. Specifications

5.1 General specifications

Item Specification
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating ambience
Operating altitude
Installation location
Overvo ltage category
Pollution level
Notes:
*1 The module cannot be used in an environment pres surized above the
atmospheric pressur e which can be generated arou nd the altitude of 0 m. If the module is used in such an environmen t, it may fail.
*2 The module can be used in any environment even outside the con trol panel as
far as the requir ements of the ambient op erating temp erature, the a mbient operating humidity, etc. are satisfied.
*3 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution network and the machinery within premises. Category ΙΙ applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
0 to 55°C (32 to 131°F)
-25 to 75°C (-13 to 167°F)
5 to 95%RH: Dew condensation shall not be considered.
5 to 95%RH: Dew condensation shall not be considered.
When intermittent vibration is present
Frequency
10 to 57Hz
57 to 150Hz
Acceleration Half amplitude
0.075mm
2
9.8m/s
When continuous vib ration is present
Frequency
10 to 57Hz
57 to 150Hz
147 m/s
Acceleration Half amplitude
0.035mm
2
4.9m/s
2
, 3 times in each of X, Y and Z directions
Number of times of sweep
10 times in each of X, Y and Z directions (for 80 min)
Corrosive gas shall not be present.
2,000m(6561'8") or less (*1)
Inside control panel (*2)
or less (*3)
ΙΙ
2 or less (*4)
*4 This index indicates th e degree of conductive generating subst ances in the
environment in which the module is used. The degree of contamination 2 indicates that contamination is caused by generation of only non-conductive substances. In this degree, however, temporary conduction may be caused by accidental condensation.

5.2 Input specifications

Input method
Item Specification
Number of inputs
Isolation method
Rated input voltage
Rated input curren t
Operating voltage range
Max. simultaneous ON input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response time
OFF→ON
ON→OFF
Common wiring method
DC input (external I/O power supply)
2 points
Isolation with photocoupler
24V DC
Approx. 4 mA
20.4 to 28.8V DC (24V DC -15% to +20% ) Ripple ratio: Within 5%
100% (at 24V DC)
19 V or more/3 mA or more
11 V or less/1.7 mA or less
5.6 k
1.5 ms or less (at 24V DC)
1.5 ms or less (at 24V DC)
2 points/1 common (2 points) (terminal block two-wire type)

5.3 Output sp ecification s

Output method
Item Specification
Number of outputs
Isolation method
Rate d load voltage
Operating load voltage range
Max. load current
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Response time
OFF→ON
ON→OFF
Surge suppression
Common wiring method
Internal protection for outputs
Transistor output (external I/O power supply) (sink)
2 points
Isolation with photocoupler
12/24V DC
10.2 to 28.8V DC ( Ripple ratio: Within 5 %)
0.1A/point, 0.4A/1commo n
0.4A/10 ms
0.1mA or less/30V DC
0.3V or less (typical)/0.1A
0.6V or less (max.)/0.1A
1.0ms or less
1.0ms or less
Zener diode
2 points/1 common (2 points) (terminal block two-wire type)
Internal protect ion circuit none Please connect the fuse in the connec ted load outside.

5.4 Performance specifications

Item Specification
Vol t a ge
Current consumption
Module power supply
Number of stations occupied
Initial current
Max. allowable
momentary power
failure period
Noise durability
Withstand voltage
Isolation resistance
Protection class
I/O part connection method
Module installation method
Mass (weight)
20.4 to 28.8V DC (24V DC -15% to +20%) Ripple ratio: Within 5%
55mA (when all points are ON)
70mA
PS1:1ms
4-, 8- or 16-poi nt mode: 1 station
500Vp-p Noise width: 1µs Cycle: 25 to 60 Hz (by noise simulator)
DC type: 500V AC for 1 min
10 MΩ or more between primary area (external DC terminal) and seconda ry area (internal c ircuit) by 500 VDC megger
IP2X
Connection with term inal block
DIN rail installation, mounted by screws of type M4 × 0.7mm(0.03") × 16mm(0.63") or larger Can be installed in six directions
0.1kg(0.22lbs)

6. Outside Dimensions

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredict able by Mitsubishi ; damages to pro ducts other th an Mitsubishi products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/TelCountry/Region Sales office/Tel
U.S.A.
Mitsubishi Electric Automation, Inc. 500 Corporate Woods Parkway, Vernon Hills, IL 60061 U.S.A. Tel : +1-847-478-2100
Brazil
MELCO-TEC Av. Paulista 1439, conj.74, Bela Vista CEP: 01311-200 Sao Paulo-SP-Brazil Tel : +55-11-3285-1840
Germany
Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8, D-40880 Ratingen, Germany Tel : +49-2102-486-0
U.K.
Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Hertfordshire., AL10 8XB, U.K. Tel : +44-1707-276100 Mitsubishi Electric Europe B.V. Italian
Italy
Branch VIALE COLLEONI 7-20041 Agrate Brianza (Milano), Italy Tel : +390-39-60531 Mitsubishi Electric Europe B.V. Spanish
Spain
Branch Ctra. de Rub 76-80-AC. 420, E-08190 Sant Cugat del Valles (Barcelona), Spain Tel : +34-93-565-3131 Mitsubishi Electric Europe B.V. French
France
Branch 25, Boulevard des Bouvets, F-92741 Nanterre Cedex, France Tel: +33-1-55685568 Mitsubishi Electric Europe B.V. Moscow
Russia
Representative Office 52, bld. 5, Kosímodamianskaya nab, RU-115054, Moscow, Russia Tel: +7-495-721-2070
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Hong Kong
Mitsubishi Electric Automation (Hong Kong) Ltd. 10th Floor., Manulife Tower, 169 Electric Road, North Point, HongKong Tel : +852-2887-8870
China
Mitsubishi Electric Automation (Shanghai) Ltd. 17F, ChuangXing Financial Center, No. 288 West Nanjing Road, Shanghai China 200003 Tel : +86-21-2322-3030
Tai wa n
Setsuyo Enterprise Co., Ltd. 6F No.105 Wu Kung 3rd RD, Wu-Ku Hsiang, Taipei Hsien, 248, Taiwan Tel : +886-2-2299-2499
Korea
Mitsubishi Electric Automation Korea Co., Ltd. 3F, 1480-6, Gayang-Dong, Gangseo-Gu, Seoul, 157-200, Korea Tel : +82-2-3660-9552
Singapore
Mitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02 Mitsubishi Electric Building, Singapore 159943 Tel : +65-6470-2460
Thailand
Mitsubishi Electric Automation (Thailand) Co., Ltd. Bang-Chan Industrial Estate No.111, Soi Serithai 54, T.Kannayao, A.Kannayao, Bangkok 10230 Tel : +66-2-517-1326
India
Messung Systems Pvt. Ltd. Sapphire House EL-3 J-Block MIDC Bhosari Pune 411026, India Tel : +91-20-27102000
Australia
Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, Rydalmere, N.S.W 2116, Australia Tel : +61-2-9684-7777
South Africa
Circuit Breaker Industries Ltd. Private Bag 2016, ZA-1600 Isando, South Africa Tel : +27-11-9282000
Specifications subject to change without notice.