Mitsubishi Electric City Multi PUHY-RP-YJM-B, City Multi PUHY-RP-YJM-B-BS Installation Manual

GB
PO HG SV CZ TR RU GR
P NL I E F D
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για ασφάλεια και σωστή χρήση, παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο εγκατάστασης πριν αρχίσετε την εγκατάσταση της μονάδας κλιματισμού.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
MONTAJ ELKİTABI
Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz.
PŘÍRUČKA K INSTALACI
V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci.
NÁVOD NA INŠTALÁCIU
Pre bezpečné a správne použitie si pred inštalovaním klimatizačnej jednotky, prosím, starostlivo prečítajte tento návod na inštaláciu.
TELEPÍTÉSI KÉZIKÖNYV
A biztonságos és helyes használathoz, kérjük, olvassa el alaposan ezt a telepítési kézikönyvet, mielőtt telepítené a légkondicionáló egységet.
PODRĘCZNIK INSTALACJI
W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem
instalacji.
PRIROČNIK ZA NAMESTITEV
Za varno in pravilno uporabo pred namestitvijo klimatske naprave skrbno preberite priročnik za namestitev.
INSTALLATIONSHANDBOK
Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras, för säker och korrekt användning.
PRIRUČNIK ZA UGRADNJU
Radi sigurne i ispravne uporabe, temeljito pročitajte ovaj priručnik prije ugradnje klimatizacijskog uređaja.
РЪКОВОДСТВО ЗА МОНТАЖ
За безопасна и правилна употреба, моля, прочетете внимателно това ръководство преди монтажа на климатизатора.
MANUAL CU INSTRUCŢIUNI DE INSTALARE
Pentru o utilizare corectă şi sigură, vă rugăm să citiţi cu atenţie acest manual înainte de a instala unitatea de aer condiţionat.
Air-Conditioners For Building Application OUTDOOR UNIT
PUHY-RP-YJM-B (-BS)
For use with R410A
2
(mm)
6
[Fig. 6.0.1]
[Fig. 7.0.1]
RP200 ~ RP350
7
(2)
(1)
(3)
(4)
[Fig. 6.0.2]
<A> : Top view <B> : Side view <C> : When there is little space up to an obstruction
A :Front B : Unit height C : Back D : Air outlet guide (Procured at the site)
A :Front B : Must be open C :Wall height (H)
15
*
15
*
450
*
300
*
<A>
A
100
*
450
*
50
*
50
*
<A>
A
A
B
<B>
500
H
h
h
H
240
45°
A
D
C
50
<C>
1000
30
450
*
300
*
C
BB
C
A
100
450
*
100
*
BB
C
C
A
450
*
100*
CC
B
A
A
A
B
450 450
15
*
C
AAA
450 450
900
300
*
300
*
BB
C
C
A
1000
*
900 300
*
B
B
C
A
(mm)
8m
8m
40°
3
8
[Fig. 8.1.1] <A> Without detachable leg
A : M10 anchor bolt procured at the site. B :Corner is not seated. C : Fixing bracket for hole-in anchor bolt (3 locations to fix
with screws).
D : Detachable leg
30mm
A
B
C
9
9.2
[Fig. 9.2.1] [RP200 ~ RP350]
A : Outdoor unit B : First branch C : Indoor unit D : Cap E : Outdoor twinning kit
[RP400 ~ RP650]
[RP700 ~ RP900]
B
E
A
A2A1
A
B C D
e
a b c d
C
C
CC
C
unit 2
A
unit 1
E
A
A
2
A
1
A
unit 2
A
unit 1
B
a
b
c d e
C
D
CC
C
C
B
A
B C D
e
a b c d
C
C
CC
C
A
B
A
a
b
c d e
C
D
CC
C
C
A
B
B C D
e
a b c d
C
C
CCC
E
A3
A4
A2
unit 3
A
AA
unit 2unit 1
E
A1
A
E
A3
A4
A2
A
unit 3
A
AA
unit 2unit 1
E
A1
B
a
b
c d e
C
D
CC
C
C
A
[Fig. 8.1.2]
A : Screws
30mm
A
D
B
C D
<B> With detachable leg
4
A (mm) Å Outdoor model
RP200 RP250 RP300 RP350 RP400 RP450 RP500 RP550 RP600 RP650 RP700 RP750 RP800 RP850 RP900
unit1
-
-
-
­RP200 RP200 RP250 RP250 RP300 RP300 RP200 RP250 RP250 RP250 RP300
unit2
-
-
-
­RP200 RP250 RP250 RP300 RP300 RP350 RP250 RP250 RP250 RP300 RP300
unit3
-
-
-
-
-
-
-
-
-
­RP250 RP250 RP300 RP300 RP300
ı Liquid pipe
ø12.7 ø12.7
ø12.7 ø15.88 ø15.88 ø15.88 ø15.88 ø15.88 ø19.05 ø19.05 ø19.05 ø19.05 ø19.05 ø19.05 ø19.05
Ç Gas pipe
ø28.58*2
ø28.58 ø28.58 ø34.93 ø34.93 ø34.93 ø34.93 ø34.93 ø34.93 ø41.28 ø41.28 ø41.28 ø41.28 ø41.28 ø41.28
ı Liquid pipe
-
-
-
­ø9.52 ø9.52 ø9.52 ø9.52 ø12.7 ø12.7 ø9.52 ø9.52 ø9.52 ø9.52 ø12.7
Ç Gas pipe
-
-
-
­ø19.05 ø19.05
ø22.2 ø22.2 ø22.2 ø22.2
ø19.05
ø22.2 ø22.2 ø22.2 ø22.2
ı Liquid pipe
-
-
-
­ø9.52 ø9.52 ø9.52 ø12.7 ø12.7 ø12.7 ø9.52 ø9.52 ø9.52 ø12.7 ø12.7
Ç Gas pipe
-
-
-
-
ø19.05
ø22.2 ø22.2 ø22.2 ø22.2
ø28.58
ø22.2 ø22.2 ø22.2 ø22.2 ø22.2
ı Liquid pipe
-
-
-
-
-
-
-
-
-
­ø9.52 ø9.52 ø12.7 ø12.7 ø12.7
Ç Gas pipe
-
-
-
-
-
-
-
-
-
­ø22.2 ø22.2 ø22.2 ø22.2 ø22.2
ı Liquid pipe
-
-
-
-
-
-
-
-
-
­ø19.05 ø19.05 ø19.05 ø19.05 ø19.05
Ç Gas pipe
-
-
-
-
-
-
-
-
-
­ø34.93 ø34.93 ø34.93 ø34.93 ø34.93
Unit combination A A1 *1 A2 *1 A3 *1 A4
9.2
9
*1 The pipe sizes listed in columns A1 to A3 in this table correspond to the
sizes for the models listed in the unit 1, 2, and 3 columns. When the order of the models for unit 1, 2, and 3 change, make sure to use the appropriate pipe size.
*2 ø25.4 for R22
B, C, D (mm)
a, b, c, d, e (mm)
Ï Downstream unit model total
~ 200 201 ~ 400 401 ~ 650
Ó The 1st branch of P450 ~ P650
651 ~
È
The 1st branch of P700, P750, P800
Ì Joint CMY-Y102SS-G2 CMY-Y102LS-G2
CMY-Y202S-G2
CMY-Y302S-G2
Î Total capacity of indoor units
~ 80 81 ~ 160 161 ~ 330 331 ~ 480 481 ~ 630 631 ~
ı Liquid pipe
ø9.52 ø12.7
ø12.7 ø15.88 ø15.88 ø19.05
Ç Gas pipe
ø15.88 ø19.05
ø25.4 or ø28.58
ø31.75 or ø34.93
ø38.1 or ø34.93
ø41.28
Model number
15,20,25,32,40
50,63,71,80 100,125,140
200,250
ı Liquid pipe
ø6.35 ø9.52 ø9.52 ø12.7
Ç Gas pipe
ø12.7 ø15.88 ø19.05 ø28.58
Ô 4-Branching header
(Downstream unit
model total
=
200)
CMY-Y104-G
8-Branching header
(Downstream unit model total = 400)
CMY-Y108-G
Ò
10-Branching header
(Downstream unit
model total
=
650)
CMY-Y1010-G
Å Outdoor model
P400 ~ P650 P700 ~ P900
˜
Outdoor twinning kit CMY-RP100VBK CMY-RP200VBK
5
9.2
9
[Fig. 9.2.2]
A
C
F
B
C
F
<A> Make sure the pipes from the twinning pipe to the outdoor unit are
sloped downwards (towards the twinning pipes).
F
C
2m
F
D
E
C
<B> When the piping on the outdoor unit side (from the twinning pipe)
exceeds 2 m, ensure a trap (gas pipe only) within 2 m.
<C> Slope of twinning pipes
±15°
F
G
<D> Pipe connection example
H
I
H
J
A : Downward slope B : Upward slope C : Indoor unit D :Trap (gas pipe only) E : Within 2 m F :Twinning pipe G :
Slope of the
twinning
pipe is at an angle within ±15° to the gro
und
H : Pipes on site I :Twinning kit J : Straight run of pipe that is 500 mm or more
6
2468
12345678 9
11 1 1 1 11 11 1 11 11 1 11 111
1357 9
10.2
10
[Fig. 10.2.1] [Fig. 10.2.3]
AB
A : Example of closure materials (field supply) B : Fill the gap at the site
No.
C Shape
No.
C Shape
PUHY-RP200YJM-B PUHY-RP250YJM-B PUHY-RP300YJM-B PUHY-RP350YJM-B
[Fig. 10.2.2]
<A> Front pipe routing
4567
<C>
A B
1
<C>
98
<C>
32
<C>
4567
<C>
23
<C>
A B
<B> Bottom pipe routing
ODø22.2
IDø25.4
IDø9.52
ODø9.52
ODø19.05
IDø25.4
ODø28.58
IDø25.4
IDø12.7
ODø12.7
<A> Front pipe routing <B> Bottom pipe routing <C> Included with outdoor unit
A Gas pipe (field supply required) B Liquid pipe (field supply required) C Shape
B
D
A
E
C
<A>
<B>
<A> Refrigerant service valve
(liquid side/brazed type)
<B> Refrigerant service valve
(gas side/brazed type)
A : Shaft B : Service port C : Cap D : Pinched connecting pipe severing portion E : Pinched connecting pipe brazing portion
IDø25.4
ODø25.4
<gas side> <gas side> <gas side> <liquid side>
<gas side> <gas side>
<liquid side>
<liquid side>
<liquid side>
ODø15.88
IDø25.4
ODø12.7
IDø9.52
IDø12.7
ODø34.93
7
[Fig. 10.3.1]
[Fig. 10.3.3]
[Fig. 10.3.2]
10.3
A
A : Nitrogen gas B :To indoor unit C : System analyzer D : Low knob E : Hi knob F :Valve G : Liquid pipe H : Gas pipe I : Outdoor unit J : Service port
A : System analyzer B : Low knob C : Hi knob D :Valve E : Liquid pipe F : Gas pipe G : Service port H : Three-way joint I :Valve J :Valve K : R410A cylinder L : Scale M :Vacuum pump N :To indoor unit O : Outdoor unit
A : Syphon pipe
D
C
C
B
B
E
F
G
H
I
J
A
LOW
HI
LOW
HI
B
A
K
J
L
H
M
C
D
EN
N
O
F
G
I
10.4
[Fig. 10.4.4]
[Fig. 10.4.3][Fig. 10.4.2]
C
A
B
D
E
[Fig. 10.4.1]
B
A
D
C
E
E
E
D
A
B
A B
<A> Inner wall (concealed)
A B
D
C
<B> Outer wall
A : Steel wire B : Piping C : Asphaltic oily mastic or asphalt D : Heat insulation material A E : Outer covering B
A : Liquid pipe B : Gas pipe C : Electric wire D : Finishing tape E : Insulator
D
F
G
B
<D> Floor (waterproofing)
E
I
B
<C> Outer wall (exposed)
F
H
D
B
G
<E> Roof pipe shaft
I
A
J
1m1m
<F> Penetrating portion on fire
limit and boundary wall
A : Sleeve B : Heat insulating material C : Lagging D : Caulking material E : Band F:Waterproofing layer G : Sleeve with edge H: Lagging material I : Mortar or other incombustible caulking J : Incombustible heat insulation material
B In case of the R410A cylinder having no syphon pipe.
Loading...