Mitsubishi Electric City Multi PUHY-P216TSKMU-A, City Multi PUHY-P120TKMU-A, City Multi PUHY-P96TKMU-A Datasheet

Model: PUHY-P216TSKMU-A
(Consists of One PUHY-P120TKMU-A, One PUHY-P96TKMU-A, and One CMY-Y100CBK3 Twinning Kit)
Job Name: Location:
Engineer Name: Contractor:
System No.: Date:
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
3-phase, 208/230V
Modular variable refrigerant flow (VRF) systems;
large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure; factory set to 0"WG
• Connects to CITY MULTI indoor units; controlled via CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
Specifications System Module 1 Module 2
Unit Type PUHY-P216TSKMU-A PUHY-P120TKMU-A PUHY-P96TKMU-A
Nominal Cooling Capacity Btu/h 216,000 120,000 96,000 Nominal Heating Capacity Btu/h 243,000 135,000 108,000
External Dimensions (H x W x D) In. / mm Refer to Module Data
Net Weight Lbs. / kg 1,220 / 557 697 / 316 532 / 241
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 208 / 230V, 3-phase, 60Hz**
Cooling Power Input kW 16.90
Heating Power Input kW 19.26 Cooling Current (208/230V) R.L.A. 52.1 / 47.1 Heating Current (208/230V) R.L.A. 59.4 / 53.7 Minimum Circuit Ampacity
(MCA)**
Maximum Breaker Size**
Maximum Overcurrent Protection** A Refer to Module Data** 73 / 67** 57 / 52**
Piping Diameter
From Twinning Kit to Indoor Units (Brazed) (In. / mm)
From Modules to Twinning Kit (Brazed) (In. / mm)
Indoor Unit
Sound Pressure Levels dB(A) 62.5 60.0 58.0
Fan
Type x Quantity Propeller Fan x 2 Propeller Fan x 1
Airflow Rate CFM 11,300 6,200 Direct-drive Inverter Motor Output kW 0.92 + 0.92 0.92 Compressor Operating Range 8% to 100% Refer to System Data
Compressor Type x Quantity
Compressor Motor Output kW 8.1 7.1 Compressor Crankcase Heater kW - ­Refrigerant Lubricant MEL32 High-pressure Protection Device Compressor / Fan Protection Device Overheat Protection / Thermal Switch Overh Inverter Protection Device Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants; ≥1μm thick; Salt Spray Test Method - no unusual rus
A Refer to Module Data** 45 / 42** 34 / 31**
A Refer to Module Data** 50** 40**
Liquid (High Pressure) 5/8 / 15.88
Gas (Low Pressure) 1-1/8 / 28.58
Liquid (High Pressure) Gas (Low Pressure) 1-1/8 / 28.58 7/8 / 22.2 Total Capacity 50 to 130% of ODUs
Model / Quantity P06 ~ P96 / 2 to 46
t development to 480 hours.
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P120TKMU-A
PUHY-P96TKMU-A
OPTIONAL PARTS
Twinning Kit*.…………………………………...…….CMY-Y100CBK3
T-Branch Joint (≤ 72,000 Btu/h)………………..........CMY-Y102SS-G2
T-Branch Joint (≤ 144,000 Btu/h)……………….…....CMY-Y102LS-G2
T-Branch Joint (≤ 234,000 Btu/h)……………….........CMY-Y202S-G2
Header (4-Branch; ≤ 72,000 Btu/h)........………………CMY-Y104C-G
Header (8-Branch; ≤ 144,000 Btu/h)......………………CMY-Y108C-G
Header (10-Branch; ≤ 234,000 Btu/h)....………………CMY-Y1010C-G
* Twinning Kit is necessary to combine the refrigerant ows of the modules and is sold separately.
65 x 68-29/32 x 29-5/23 /
1,650 x 1,750 x 740
Refer to System Data
Refer to System Data
Refer to System Data
1/2 / 12.7 3/8 / 9.52
Refer to System Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
601 psi / 4.15 MPa 601 psi / 4.15 MPa
65 x 488-1/16 x 29-5/32 /
1,650 x 1,220 x 740
R410A
eat Protection / Thermal Switch
Module : PUHY-P216TSKMU-A – DIMENSIONS
PUHY-P216TSKMU-A(-BS)
Outdoor unit 2
30(1-3/16)1750(68-29/32)
Intake
air
To indoor unit
To indoor unit
a
b
Gas Twinning pipe<optional parts>
Liquid Twinning pipe<optional parts>
e
f
c
d
Front view
Unit : mm(in.)
Outdoor unit 1
Discharge air
740(29-5/32) 1220(48-1/16)
Intake
air
1650(64-31/32)
Left view
Gas
d or fc or e
ø28.58(1-1/8)
ø22.2(7/8)
Liquid
ø12.7(1/2)
ø9.52(3/8)
P96
P120
Unit model
Twinning pipe~Outdoor unit
CMY-Y100CBK3
ø28.58(1-1/8)
ø15.88(5/8)
PUHY-P96TKMU-A(-BS)
PUHY-P120TKMU-A(-BS)
PUHY-P216TSKMU-A(-BS)
b
a
Gas
Liquid
Outdoor unit 2
Outdoor unit 1
Intake
air
Package unit name
Outdoor Twinning Kit(optional parts)
Indoor unit~Twinning pipe
Component unit name
Twinning pipe connection size
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm(19-11/16) of straight section
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).