
Model: PUHY-P168TSJMU-A
(Consists of One PUHY-P96TJMU-A, One PUHY-P72TJMU-A, and One CMY-Y100VBK2 Twinning Kit)
Job Name: Location:
Engineer Name: Contractor:
System No.: Date:
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
• 3-phase, 208/230V
• Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure;
factory set to 0"WG
• Maximum Total Refrigerant Piping Length: 3,280'; Maximum
Refrigerant Line Length: 541'; Maximum Control Wiring Length:
1,650'
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
Specifications System Module 1 Module 2
Unit Type PUHY-P168TSJMU-A PUHY-P96TJMU-A PUHY-P72TJMU-A
Nominal Cooling Capacity Btu/h 168,000 96,000 72,000
Nominal Heating Capacity Btu/h 188,000 108,000 80,000
External Dimensions (H x W x D) In. / mm Refer to Module Data
Net Weight Lbs. / kg 938 / 425 497 / 225 441 / 200
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 208 / 230V, 3-phase, 60Hz**
Cooling Power Input kW 13.62
Heating Power Input kW 14.65
Cooling Current (208/230V) R.L.A. 42.0 / 37.9
Heating Current (208/230V) R.L.A. 45.1 / 40.8
Minimum Circuit Ampacity
(MCA)**
Recommended Fuse/Breaker
Size**
Maximum Fuse Size** A Refer to Module Data** 50 / 50** 30 / 30**
Piping Diameter
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
From Modules to Twinning Kit
(Brazed) (In. / mm)
Indoor Unit
Sound Pressure Levels dB(A) 61.0 58.0 58.0
Fan
Type x Quantity Propeller Fan x 1 Propeller Fan x 1
Airflow Rate CFM 6,180 6,180
Direct-drive Inverter Motor Output kW 0.92 0.92
Compressor Operating Range 8% to 100% Refer to System Data
Compressor Type x Quantity
Compressor Motor Output kW 6.8 5.1
Compressor Crankcase Heater kW 0.045 0.035
Refrigerant
Lubricant MEL32
High-pressure Protection Device
Compressor / Fan Protection Device Overheat Protection / Thermal Switch
Inverter Protection Device Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulos
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
A Refer to Module Data** 36 / 34** 25 / 24**
A Refer to Module Data** 40** 30**
Liquid (High Pressure) 5/8 / 15.88
Gas (Low Pressure) 1-1/8 / 28.58
Liquid (High Pressure)
Gas (Low Pressure) 7/8 / 22.2 3/4 / 19.05
Total Capacity 50 to 130% of ODUs
Model / Quantity P06 ~ P96 / 1 to 36
e- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P96TJMU-A
PUHY-P72TJMU-A
OPTIONAL PARTS
□ Twinning Kit*.…………………………………...…….CMY-Y100VBK2
□ T-Branch Joint (≤ 72,000 Btu/h)………………..........CMY-Y102S-G2
□ T-Branch Joint (≤ 144,000 Btu/h)……………….…....CMY-Y102L-G2
□ T-Branch Joint (≤ 234,000 Btu/h)……………….........CMY-Y202-G2
□ Header (4-Branch; ≤ 72,000 Btu/h)........………………CMY-Y104-G
□ Header (8-Branch; ≤ 144,000 Btu/h)......………………CMY-Y108-G
□ Header (10-Branch; ≤ 234,000 Btu/h)....………………CMY-Y1010-G
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is sold separately.
65 x 48-1/16 x 29-15/16 /
1,650 x 1,220 x 760
Refer to System Data
Refer to System Data
Refer to System Data
3/8 / 9.52 3/8 / 9.52
Refer to System Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
R410A
601 psi / 4.15 MPa 601 psi / 4.15 MPa
65 x 36-1/4 x 29-15/16 /
1,650 x 920 x 760
Overheat Protection / Thermal Switch