• 3. OUTLINES AND
DIMENSIONS has been modified in REVISED EDITION-A.
• Some descriptions have been
modified.
• Please void OCH462.
Note:
• This manual describes only
service data of the indoor
units.
• RoHS compliant products
have <G> mark on the spec
name plate.
CONTENTS
1. PART NAMES AND FUNCTIONS
2. SPECIFICATION
3. OUTLINES AND DIMENSIONS
4. WIRING DIAGRAM
5. REFRIGERANT SYSTEM DIAGRAM
6. MICROPROCESSOR CONTROL
7. TROUBLESHOOTING
8. DISASSEMBLY PROCEDURE
.....................................
.................................
..........................
.............
..........
..............
..........
...........
2
4
6
7
8
9
14
21
PARTS CATALOG (OCB462)
Use the specifi ed refrigerant only.
Never use any refrigerant other than that specifi ed.
Doing so may cause a burst, an explosion, or fi re when the unit is being used, serviced, or disposed of.
Correct refrigerant is specifi ed in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to
follow the instructions.
1
PART NAMES AND FUNCTIONS
Indoor unit
Filter
Air inlet
Air outlet
Wirelessremote controller
display
OPERATION MODE display
Operation mode display indicates which
operation mode is in effect.
The vertical direction of air flow is indicated.
FAN SPEED display indicates which fan
speed has been selected.
The unit is turned ON and OFF alternately
each time the button is pressed.
Used to change the fan speed.
Used to switch the operation mode between
cooling, drying, fan, heating and auto mode.
+ In case the outdoor unit is cool only type,
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
Used to change the air flow
display
display
ON/OFF button
FAN SPEED SELECT button
MODE SELECT button
the heating and auto mode are not
available.
CHECK-TEST RUN button
VANE CONTROL button
Vane
Louver
CHECK
TEST RUN
CHECK and TEST RUN display indicate that
the unit is being checked or test-run.
Blinks when model is selected.
display
MODEL SELECT
display
CHECK
MODEL SELECT
NOT AVAILABLE
ON/OFF TEMP
VAN E
MODE
LOUVER
CHECK
TEST RUN
RESETSETCLOCK
TEST RUN
FAN
°F
°C
AMPM
AMPM
AUTO STOP
AUTO START
h
min
2
Front grille
Emergency
switch
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
SET TEMP. display indicates the s et desired
temperature.
Displays the current time.
Displays when in timer operation or when
setting timer.
Displays the order of timer operation.
Displays whether timer is on or off.
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is
set, the air conditioner will be automatically
stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
Buttons used to set the “hour and minute” of
the current time and timer settings.
Changes left/right airflow direction.
(Not available for this model.)
operation
display
display
CLOCK display
TIMER display
“ ” “ ” display
“ ” “ ” display
button
h and min buttons
LOUVER button
CLOCK button
RESET button
SET button
Wiredremote controller
Display Section
For purposes of this explanation,
all parts of the display are shown.
During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displays if the airflow is set to
Low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
at which time the airflow direction
also changes.
Room Temperature display
Shows the room temperature. The room
temperature display range is 46–102°F.
The display blinks if the temperature
is less than 46°F or 102°F or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displays when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
cover
Note:
●
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
●
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
33
ON/OFF
FILTER
CHECK
OPERATION
Built-in temperature sensor
CLEAR
TEST
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
2
SPECIFICATION
2-1. Specifi cations
Model
Power source
Cooling capacity
(Nominal)
Power input
Heating capacity
(Nominal )
External finish
External dimension H × W × D
Net weight
Heat exchanger
Fan
Noise level (Low-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
refrigerant pipe
Field drain pipe size
Standard
attachment
Optional parts
Remarks
Current input
Power input
Current input
Type × Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-High)
Liquid
Gas
Document
Accessory
External heater adapter
Installation
*1
*1
*2
*2
(R410A)
(R22)
(R410A)
(R22)
kW
Btu/h
kW
A
kW
Btu/h
kW
A
mm
in.
kg (lb)
Pa
mmH
2
kW
3
/min
m
L/s
cfm
dB <A>
mm (in.)
mm (in.)
mm (in.)
PKFY-P24NKMU-E
PKFY-P30NKMU-E
1-phase 208-230V 60Hz
7.0
24,000
0.04
0.29
7.9
27,000
0.04
0.29
8.8
30,000
0.06
0.43
10.0
34,000
0.06
0.43
Plastic, MUNSELL (1.0Y 9.2/0.2)
365 × 1170 × 295
14-3/8" × 46-1/16" × 11-5/8"
21 (46)
Cross fin (Aluminum fin and copper tube)
Line flow fan × 1
0
O
0
DC motor
0.056
Direct-drive
16 - 20
267 - 333
570 - 710
39 - 45
20 - 24
333 - 400
710 - 850
43 - 49
Polyethylene sheet
PP honeycomb
Fuse
LEV
R410A, R22 CITY MULTI
ø9.52 (ø3/8")
ø9.52 (ø3/8")
ø15.88 (ø5/8")
ø15.88 (ø5/8")
Flare
Flare
Flare
Flare
ø9.52 (ø3/8")
ø9.52 (ø3/8")
ø15.88 (ø5/8")
ø15.88 (ø5/8")
Flare
Flare
Flare
Flare
I.D. 16mm (5/8")
Installation Manual, Instruction Book
PAC-YU25HT
Details on foundation work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
Note :
Pipe length :
Level difference :
* Due to continuing improvement, above specification may be subject to change without notice.
*1 Nominal cooling conditions
Indoor :
Outdoor :
80°FDB/67°FWB (26.7°CDB/19.4°CWB)
95°FDB (
25 ft. (7.6 m)
0 ft (
35°CDB)
0 m)
*2 Nominal heating conditions
70°FDB(21°CDB)
47°FDB/43°FWB (8.3°CDB/6.1°CWB)
25 ft. (7.6 m)
0 ft (0 m)
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
3
cfm = m
lb = kg/0.4536
*Above specification data is
subject to rounding variation.