Mitsubishi A1S62TCRTBW-S2, A1S62TCRT-S2, A1S62TCTT-S2, A1S62TCTTBW-S2 User Manual

Thank you for purchasing the Mitsubishi general-purpose programmable controller MELSEC-A series.
Prior to use, please read this manual thoroughly and familiarize yourself with the product.
z
zz
z SAFETY PRECAUTIONS z
zz
z
When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in the manual. Also, pay careful attention to safety and handle the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the CPU module user's manual for a description of the PC system safety precautions.
These zSAFETY PRECAUTIONSz classify the safety precautions into two categories: "DANGER" and "CAUTION".
Procedures which may lead to a dangerous condition and cause death or serious injury if not carried out properly.
Procedures which may lead to a dangerous condition and cause superficial to medium injury, or physical damage only, if not carried out properly.
Depending on circumstances, procedures indicated by
CAUTION
may also be linked to serious results. In any case, it is important to follow the directions for usage. Store this manual in a safe place so that you can take it out and read
it whenever necessary. Always forward it to the end user.
[Design precautions]
DANGER
z Configure a safety circuit external to the PC, so that the entire system
operates safety even if there is an external power error or if the PC is malfunctioning.
CAUTION
z Do not bu ndle, or near the control cables and communicati on cables
with the main circuit and power cables. Keep them at least 100mm (3.94inc h) away from such cables. N oise may cause malfuncti on.
[Installation precautions]
CAUTION
z Use the PC in the env iro nme nt g i ven in the ge ner a l spec if ica ti o ns of
the this manual. Using the PC outside the range of the general specifications may result in electric shock, fire or malfunctioning. or may damage or degrade the module.
z Insert the tabs at th e bot tom of th e mod ul e int o th e mou nt ing ho l es in
the base module before installing the module, and after tightening the module fixing screws with specified torque. If the connector is not property installed and tightened. If may result in malfunctioning, failure or cause the module to lam out.
Tightening the screws too far may cause damage to the screw and/or
the module, resulting in fall out, short circuit or malfunctions.
z Do not direct ly touc h t h e modu le ’ s conduc t iv e part s o r el ect ro nic
components. Doing so could cause malfunction or fa ilu re i n t he module.
z Insert the wire breakage detection connector installation screw into the
mounting holes in the module, and after tightening the connector installation screw with specified toque. If the connect or is not pro perty installed and tightened, it may result in error detetion of wire breakage.
[Wiring precautions]
CAUTION
z Be sure to ground the shield wire with a special PC ground of Type III
or above. Not do ing so co uld r esu lt i n malf un ct io n.
z When wiring in th e P C, be su re t hat it is don e cor r ect l y by chec k ing t he
product's rated voltage and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or failure.
z Tighten the termina l s crews with s pecified torque. Loose t erminal
screws may cause a short circuit, fire, or m alfu nct ion.
Tighteni ng the terminal screws too far may cause damage to the screw
and/or the module, resulting in short ci rc uit, o r m alfu nct ions.
z Be sure that cuttings, wire chips, or ot her fo rei gn matt e r do not e nt er
the modul e. Foreign matt er may start a fire or ca use failure or malfunctions.
z Be sure to fix communication cables and power cables leading from
the modul e by placing them in the d uc t or clamping them. Cabl es not placed in the duct or without clamping may hang or shift, allowing them to be accident al l y pul led, whic h may res ult i n a modu le ma lf unc t ion and cable damage.
z When det ac hing the comm unication cable from t he module, do not pull
the cable portion. For cables with connectors, hold the connector at the junction to the module, then detach it. For cables wit hout connectors, first loosen the screw at th e ju nct ion, t h en detach t o th e cable. Pul ling the c abl e po rt ion whi le it is con nec t ed to th e mod ul e may cause a m alfunction or damage to the module and cable.
[Starting and maintenance precautions]
CAUTION
z Do not touch the terminal while the power is on. It may cause malfunction. z Make sure to switch all phases of the external power supply off before
cleaning or re-tightening the terminal screws. If you do not switch off the external power supply, it will cause failure or malfunction of the module.
z Never disassemble or modify the module. This may cause failure,
malfunctioning, injury and/or fire.
z Make sure to switch all phases of the external power supply off before
mounting or r emov i ng t he m od ul e. I f y ou d o not s witc h of f t he e xt ern al power supply, it will cause failure or malfunction of the module.
[Disposal precaution]
CAUTION
z When dis posing of this product, handle it as i ndustrial was te.
DANGER
CAUTION
A1S62TCRT-S2 Heating-Cooling
Temperature Control Module
A1S62TCRTBW-S2 Heating-Cooling
Temperature Control Module with Wire
Breakage Detection Function
Mitsubishi General-Purpose Programmable Controller
User’s Manual
(Hardware)
C 1997 MITSUBISHI ELECTRIC CORPORATION
Type A1S62TCRT-U-HW-E Type
Code
13JL33
IB(NA)-66801-C(0210)MEE
About This Manual
The following product manuals are available. Please use this table as a reference to request the appropriate manual as necessary.
Detailed manual
Manual name
Manual No.
(Model Code) A1S62TCRT-S2 Heating-Cooling Temperature Control Module A1S62TCRTBW-S2 Heating-Cooling Temperature Control Module with Wire Breakage Detection Function User's Manual
SH-3644 (13JL36)
Please read A1S62TCRT-S2 Heating-Cooling Temperature Control Module A1S62TCRTBW-S2 Heating-Cooling Temperature Control Module with Wire Breakage Detection Function User's Manual (Detailed edition) when using this unit.
1. General Description
This user's manual describes the specification, name of each part, wiring, etc. of the A1S62TCRT-S2 Heating-Cooling Temperature Control Module (Hereafter abbreviated as A1S62TCRT-S2 ) A1S62TCRTBW-S2 Heating-Cooling Temperature Control Module with Wire Breakage Detection Function (Hereafter abbreviated as A1S62TCRTBW-S2) A1S62TCRT-S2 and A1S62TCRTBW-S2 abbreviated as A1S62TC. After unpacking, confirm that there is the following products.
Item
A1S62TCRT-S2
Main body
A1S62TCRTBW-S2
Main body
A1S62TCRT-S2 1 -
A1S62TCRTBW-S2 - 1
2. Performance Specification
The A1S62TC performance specification is indicated in Table 2.1.
Table 2.1 A1S62TC performance specification
Specification
Item
A1S62TCRT-S2 A1S62TCRTBW-S2 Control output Transistor output Temperature input points 2-channel/module Supported platinum tem pe rat ur e­measuring resistor
Refer to Table 2.2.
Ambient temperature: 23
5
Full scale ( 0.3%) 1 digit*1
Specification accuracy
Ambient temperature: 0 to 55
Full scale ( 0.7%) 1 digit*1
Sampling period
0.5s/2-channel (It is not connected with the
number of channels used) Heating control output period Cooling control output period
1 to 100s Sensor current 0.25mA
Allowable input wire resistor effects
Less than 20 Input filter 0 to 100s (0: input filter off) Sensor compensation value setting -50.00 to 50.00% Operation when sensor input is disconnected
Upscale processing Temperature control method PID on/off pulse
PID constant setting Auto-tuning setting is possible Heating proportional band (Ph) Cooling proportional band (Pc)
0.1 to 1000.0%
Integral time (I) 1 to 3600s
PID constant range
Derivative time (D) 0 to 3600s (0: PI control)
Set value setting range
Within the temperature range set by the
platinum temperature-measuring resistor
to be used. Cooling method setting Air cooling/water cooling
Output signal ON/OFF pulse Rated load voltage 10.2 to 30.0VDC (peak voltage : 30.0VDC)
Maximum load current
0.1A/1 point
0.4A/common Max i mu m i nr u sh c ur r en t 0.4A 10ms Maximum current when OFF
Less than 0.1mA
Maximum voltage drop when ON
1.0VDC (TYP) 0.1A
2.5VDC (MAX) 0.1A
Transistor output
Response time
OFF
ON: Less than 2ms
ON
OFF: Less than 2ms (resistor load)
Insulation method
Between the input and grounding: transformer insulation Between the input and channel: transformer insulation
Table 2.1 A1S62TC performance specification (continued)
Specification
Item
A1S62TCRT-S2 A1S62TCRTBW-S2
Current sensor
URD manufactured current sensor*2 CTL-12-S36-8 (0.0 to 100.0A) CTL-6-P-H (0.00 to 20.00A) (Former mode l, CTL-6-P is also applicable.)
Input method
Multiplex method A/D conversion
Heater wire breakage disconnection specification
Number of alert delays
-
3 to 255
I/O occupied points Special 32 points Connection terminal 20 po ints terminal block Supported cable size (mm) [inch] 0.7 5 to 1.5 [0 .0 3 0 t o 0 .0 5 9] Supported solder-less terminal R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A Internal consumed current (5VDC) [A]
0.19 0.28
Weight (kg) [lb] 0.25 [0.55] 0.28 [0.62]
For the noise resistance, dielectric withstand voltage, and insulation resistance for the PC system which uses this module, refer to the power module specification found in the CPU Module User’s Manual.
*1: “
1 digit” error depends on the input range.
For setting unit of 1
, 1 For setting unit of 0.1 , 0.1
*2: Only the URD International, Ltd. current sensor can be used.
Sales channels for current sensors manufactures by URD International Ltd. are listed as follows:
U.S.A. Julia Industries Inc.
Tel:949-831-0111
BRAZIL Ananda Industial Lt da.
Tel:011-5584-0959 UNITED KINGDOM Omni Components
Tel:024-7622-5757 GERMANYAllied Electronics Gm bH
Tel:0221-497-3084 FRANCE Diltronic S.A.
Tel:01-34-51-33-00 ITALY ELNET s.n.c.
Tel:041-50-19-939
KOREA Joyang Trading Co.
Tel:02-521-2294 Sewon Tech Co.,Ltd. Tel:02-868-9355/9356 Keum Ho Corporation Tel:51-319-4155/4156
HONG-KONG Weltronics Components Ltd.
Tel:2410-0623
TAIWAN Tope Co.,Ltd.
Tel:886-2-8228-0658
INDIA AmtechElectronics PVT.Ltd.
Tel:02712-25324
Table 2.2 The types of supported platinum temperature-measuring
resistor and the measured temperature range
°F
Platinum
temperature-
measuring
resistor
Measured
temperature
range
Data
resolution
Measured
temperature range
Data
resolution
-300 to 1100 1
Pt 100
-200.0 to 600.0
-200.0 to 200.0
0.1
-300.0 to 300.0 0.1
-300 to 900 1
JPt100
-200.0 to 500.0
-200.0 to 200.0
0.1
-300.0 to 300.0 0.1
For the general specifications, refer to the User’s Manual for the PC CPU used.