3. Transporting the unit ................................................................................ 5
4. Installing the outdoor unit ......................................................................... 6
5. Installing the refrigerant piping ................................................................. 7
6. Drainage piping work ............................................................................. 11
1. Safety precautions
s Before installing the unit, make sure you read all the “Safety precautions”.
s This equipment does not comply with the relevant technical standard
for the limitation of flicker and this may cause adverse effects on other
electrical appliances. Please provide an exclusive circuit for the air conditioner and ensure, the max. impedance in this manual. Do not connect
other appliances to this circuit.
s Please report to or take consent by the supply authority before connec-
tion to the system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with R410A refrigerant.
The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure
of usual refrigerants. If pipe components not designed for R410A refrigerant
are used and the unit is not installed correctly, the pipes may burst and cause
damage or injuries. In addition, water leakage, electric shock, or fire may result.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appropriate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit breakers must be used. Power lines with insufficient capacity or incorrect electrical work may result in electric shock or fire.
7. Electrical work ........................................................................................ 11
8. Test run .................................................................................................. 12
9. Special Functions .................................................................................. 13
10. System control (Fig. 10-1) ...................................................................... 14
11. Information on rating plate ..................................................................... 14
After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the Operation Manual and perform the test run to ensure normal operation. Both the Installation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The connections must be made securely
without tension on the terminals. If the cables are connected or installed incorrectly, overheating or fire may result.
• The terminal block cover panel of the outdoor unit must be firmly attached. If
the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or fire may result.
• When installing or moving the air conditioner, use only the specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to install them. If accessories are incorrectly installed, water leakage, electric shock, or fire may result.
• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are
not performed correctly, water leakage, electric shock, or fire may result.
• The user should never attempt to repair the unit or transfer it to another location. If the unit is installed incorrectly, water leakage, electric shock, or fire
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.
1.1. Before installation
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, or areas where
the unit will be covered by snow, the performance can be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow,
or accumulate. If combustible gas accumulates around the unit, fire or explosion may result.
• The outdoor unit produces condensation during the heating operation. Make
sure to provide drainage around the outdoor unit if such condensation is
likely to cause damage.
1.2. Before installation (relocation)
Caution:
• Be extremely careful when transporting the units. Please read and fully understand “3. Transporting the unit” before transporting the unit. Wear protective gloves to remove the unit from the packaging and to move it, as you can
injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such
as nails and other metal or wooden parts may cause stabs or other injuries.
2
• When installing the unit in a hospital or communications office, be prepared
for noise and electronic interference. Inverters, home appliances, high-frequency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown. The air conditioner may also
affect medical equipment, disturbing medical care, and communications equipment, harming the screen display quality.
• The base and attachments of the outdoor unit must be periodically checked
for looseness, cracks or other damage. If such defects are left uncorrected,
the unit may fall down and cause damage or injuries.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too
much, the flare nut can break after an extended period and refrigerant can
leak out.
1800
900
780
1. Safety precautions
E
F
D
C
B
A
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables. If the
connections are loosened, the cables can snap or break and overheating or
fire may result.
1.4. Before starting the test run
Caution:
• Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation. The
refrigerant pipes are hot or cold depending on the condition of the flowing
refrigerant. If you touch the pipes, burns or frostbite may result.
1.5. Using R410A refrigerant air conditioners
Caution:
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to
page 7) Note the following if reusing existing pipes that carried R22 refrigerant.
• Do not use OL material for the ø22.2 pipes.
- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes. (Refer to page 7)
• Store the pipes to be used during installation indoors and keep both ends of
the pipes sealed until just before brazing. (Leave elbow joints, etc. in their
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil deterioration or compressor breakdown may result.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil
deterioration may result.
• Be sure to ground the unit. Do not connect the ground wire to gas or water
pipes, lighting rods, or telephone grounding lines. If the unit is not properly
grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and
molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.
• After stopping operation, be sure to wait at least five minutes before turning
off the main power switch. Otherwise, water leakage or breakdown may result.
• Do not use refrigerant other than R410A refrigerant. If another refrigerant is
used, the chlorine will cause the oil to deteriorate.
• Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant. Contact your
nearest dealer for any questions.
• Be sure to use the correct tools. If dust, debris, or moisture enters the refrigerant lines, refrigeration oil deterioration may result.
• Do not use a charging cylinder. If a charging cylinder is used, the composition of the refrigerant will change and the efficiency will be lowered.
1
2. Installation location
2
Fig. 1-1
Fig. 2-1
Fig. 2-2
(mm)
1.6. Accessories of outdoor unit (Fig. 1-1)
The parts show in the left are the accessories of this unit, which are affixed to the
inside of the service panel.
1 Flange joint ... ×1
2 Packing......... ×1
2.1. Refrigerant pipe (Fig. 2-1)
s Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are
within the limits shown below.
Models
RP200ø25.4ø9.52Max. 80 mMax. 40 mMax. of 15
RP250ø28.58ø12.7Max. 80 mMax. 40 mMax. of 15
• Height difference limitations are binding regardless of which unit, indoor or outdoor,
is positioned higher.
E Indoor unit
F Outdoor unit
A Pipe size (mm)
Gas side Liquid side (one way)difference
B Pipe lengthC HeightD Number of
bends (one way)
2.2. Choosing the outdoor unit installation location
• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience
neighbors.
• Avoid locations where the unit will be exposed to strong winds.
• Select a location permitting easy wiring and pipe access to the power source and
indoor unit.
• Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow
fall is anticipated, special precautions such as raising the installation location or
installing a hood on the air intake and air outlet must be taken to prevent the snow
from blocking the air intake or blowing directly against it. This can reduce the airflow
and a malfunction may result.
• Avoid locations exposed to oil, steam, or sulfuric gas.
2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)
3
2. Installation location
1
2
3
4
6
5
2
1
hH
14
2
3
3
3
1
22
1
2332
1
hH
2
1
1
3
Min. 100
Min. 450
Min. L1Min. L2
Fig. 2-3
Min. 45°
Min. 1000
Min. 300
Fig. 2-4Fig. 2-5
Min. L1Min. L2
Min. 45Min. 45
(mm)
1 As viewed from the top.
2 As viewed from the
side.
3 Front.
4 Front intake port (Open,
if possible)
5 Rear intake port (Open,
if possible)
6 Top intake port (Open,
if possible)
(mm)
(mm)
1 Front
2 No wall height restric-
tions (both right and left)
3 As viewed from the
side.
2.4. Ventilation and service space
2.4.1. When installing a single outdoor unit.
When installing a part that is sold separately, make sure to provide the required space
for that part as indicated in its manual.
(1) Basic information for determining required space (Fig. 2-3)
The required space for the back of the unit is determined by the air intake port;
100 mm or more is required. However, providing the same amount of space as at
the front of the unit, approximately 450 mm, will make servicing the unit easier.
(2) Overhead obstacles (Fig. 2-4)
1 If there is little space between the unit and the obstruction (Fig. 2-5)
2 Provide outlet blower guide. (Procure locally.)
(3) If the intake air enters from the right and left sides (Fig. 2-6)
• The front and rear wall height, expressed as “H,” shall be the same height or
lower than the overall height of the unit.
• If this height exceeds that of the overall height of the unit, add the dimension
shown as “h” in the drawing on the left to L1 and L2 on Table 1.
Table 1(mm)
L1L2
450100
Min. L1Min. L2
Min.90Min.90Min.
Min. 45
Min. 45
Min.90Min.90Min.
90
Fig. 2-6
Min. L1Min. L2
(mm)
1 Front
2 Front panel (Front side)
3 Rear panel
4 As viewed from the side
(4) When there are walls around the unit (Fig. 2-7)
• When the front and rear wall height, shown as “H,” is the same or lower than the
front and rear panels of the unit.
• If the panel height exceeds that of the overall height of the unit, add the dimension shown as “h” in the drawing on the left to L1 and L2 on Table 2.
Table 2(mm)
L1L2
450100
Example: If “h” is 100 mm, the “L1” dimension will be
450 mm + 100 mm = 550 mm.
Fig. 2-7
Min.90Min.
Min.
1000
Min.90Min.90Min.
Min.
90
90
Min. 250*
Min. 450*
90
Min. 250*
(mm)
1 Wall height (H)
2 Front side
3 Leave open
90
900
Min.
2.4.2. When installing multiple outdoor units (Fig. 2-8)
• When installing multiple units, make sure to take into consideration factors such as
providing enough space for people to pass through, ample space between blocks
of units and sufficient space for air flow as shown in the drawing on the left.
* 250 mm or more is required behind the unit, but providing 450 mm or more of space
behind the unit will make servicing easier.
Min.90Min.90Min.
4
Min.
90
1000
Min.90Min.90Min.
90
Fig. 2-8
Min. 250*
2. Installation location
3
2
1
1
22322
22
3
1
4
222
4
5
3
2
1
1
2
3
Min.
1000
Min.
Min.
450*
450
Min.90Min.90Min.
Min.90Min.90Min.
(mm)
Min.
Min.
Min.
450
450
Min.
1000
Min. 45
Min.90Min.
Min.90Min.
90
90
Min.
450
250*
90
Min. 250*
900
Min.
90
1 Wall height (H)
2 Front side
3 Leave open
4 No wall height restriction
• Leave open in two directions.
• If the wall height (H) exceeds the overall height of the unit, add the dimension
shown as “h” to the dimension shown as “*”. (h: Wall height (H) - overall unit height)
• When there is a wall in front of the units, limit the maximum number of units con-
nected together to 4 and allow 1,000 mm of space or more between every 4 units to
provide space for airflow and space for people to pass through.
Fig. 2-8
3. Transporting the unit
Fig. 3-1
1 Square-shaped opening
for inserting the forks.
2 Forklift
3 Forklift forks
4 Protective cover
5 Wood slats (Provide these
for the unit to rest against
when the forks are tilted
back for transport.)
1 Space for inserting the
forks of a pallet truck.
2 Pallet truck
3 Insert
Use care in the following areas when handling the units.
When using a forklift or similar equipment to load or unload the units, always insert
the forks of the forklift into the square-shaped openings provided (as shown in the
illustration on the left) and transport. It is dangerous to insert the forks from the side
as the unit has a center of gravity that is not at the center of the unit. It may tilt away
from its center of gravity and become unstable.
3.1. Transporting by forklift (Fig. 3-1)
• When transpor ting the unit by forklift, always insert the forks into the square-shaped
openings at the base of the unit.
Note:
1. Always use care when transporting a unit by forklift on rainy days as slip-
page can occur.
2. Never use dangerous sudden movements, such as accelerating or applying
the brakes suddenly or turning the steering wheel quickly, when transporting
the unit by forklift.
3.2. Transporting by pallet truck (Fig. 3-2)
• When using a pallet truck to transport the unit, insert the forks from the side of the
unit.
Note:
The center of gravity of the unit is not at the dimensional center of the unit.
Therefore, make sure that the forks of the pallet truck pass completely under
the unit and extend out the opposite side before lifting the unit for transport.
Fig. 3-2
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.