Mitsubishi Electronics 1DM100 User Manual

Page 1
A975GOT-TBA/TBD(-B
)
)
A970GOT-TBA/TBD(-B
A970GOT-SBA/SBD
A970GOT-LBA/LBD
A960GOT-EBA/EBD
User’s Manual
(Hardware)
Thank you for buying the MELSEC-GOT Series.
thoroughly and familiarize yourself with the product.
MODEL A900GOT-U-JE MODEL
1DM100
CODE
IB(NA)-80032-H(0512)MEE
Mitsubishi Graphic Operation Terminal
Page 2
A

z SAFETY PRECAUTIONS z

(Read these precautions before using.)
When using this equipment, thoroughly read this manual. Also pay careful attention to safety and handle the module properly. These precautions apply only to this equipment. Refer to the user’s manual of the CPU module to use for a description of the PLC system safety precautions. These "Safety Precautions" classify the safety precautions into two categories: "DANGER" and "CAUTION".
Procedures which may lead to a dangerous condition and
DANGER
CAUTION
cause death or serious injury, if not carried out properly.
Procedures which may lead to a dangerous condition and cause superficial to medium injury, or physical damage only, if not carried out properly.
Depending on circumstances, procedures indicated by be linked to serious results. In any case, it is important to follow the directions for usage. Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
CAUTION
may also
[DESIGN PRECAUTIONS]
DANGER
z Some failures of the GOT main unit, communication module,
communication board or cable may keep the outputs on or off. An external monitoring circuit should be provided to check for output signals which may lead to a serious accident. Not doing so can cause an accident due to false output or malfunction.
z If a communication fault (including cable disconnection) occurs during
monitoring on the GOT, communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative. For bus connection: The CPU becomes faulty and the GOT inoperative. For other than bus connection: The GOT becomes inoperative. A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur. Not doing so can cause an accident due to false output or malfunction.
-1
Page 3
A
[DESIGN PRECAUTIONS]
DANGER
z Do not use the GOT as the warning device that may cause a serious
accident. An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning. Failure to observe this instruction may result in an accident due to incorrect output or malfunction.
z Incorrect operation of the touch switch(s) may lead to a serious accident if
the GOT backlight is gone out. When the GOT backlight goes out, the display section turns black and causes the monitor screen to appear blank, while the input of the touch switch(s) still remains active. This may confuse an operator in thinking that the GOT is in “screensaver” mode, who then tries to release the GOT from this mode by touching the display section, which may cause a touch switch to operate. Note that the following occurs on the GOT when the backlight goes out.
The monitor screen disappears even when the screensaver is not set.
The monitor screen will not come back on by touching the display section,
even if the screensaver is set.
CAUTION
z Do not bundle the control and communication cables with main-circuit,
power or other wiring. Run the above cables separately from such wiring and keep them a minimum of 100mm apart. Not doing so noise can cause a malfunction.
[MOUNTING PRECAUTIONS]
DANGER
z Before installing or removing the GOT main unit to or from an enclosure,
always switch off the GOT power externally in all phases. Not doing so can cause a module failure or malfunction.
z Before loading or unloading the communication board, communication
module, External I/O module or memory board to or from the GOT, always switch off the GOT power externally in all phases. Not doing so can cause a module failure or malfunction.
-2
Page 4
A
[MOUNTING PRECAUTIONS]
CAUTION
z The GOT should be used in the environment given in the general
specifications of this user's manual. Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
z When mounting the GOT main unit to an enclosure, tighten the mounting
screws in the specified torque range. Undertightening can cause a drop, short circuit or malfunction. Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or module.
z When loading the communication board, communication module or
External I/O module to the GOT main unit, fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range. Undertightening can cause a drop, failure or malfunction. Overtightening can cause a drop, failure or malfunction due to the damage of the screws or module.
z When loading the memory board into the GOT main unit, load it into its
corresponding GOT slot and tighten the mounting screws in the specified torque range. Undertightening can cause a malfunction due to a contact fault. Overtightening can cause a malfunction due to the damage of the screws or module.
z When loading the PC card into the GOT main unit, insert and push it into
its corresponding GOT slot until the PC card eject button comes up. Not doing so can cause a malfunction due to a contact fault.
z Before loading or unloading the PC card to or from the GOT, set the
memory card access switch to the OFF position. Not doing so can cause the PC card data to be corrupted.
z Be sure to support the PC card with your hand when removing it.
Otherwise, the PC card may drop, resulting in a failure or damage.
[WIRING PRECAUTIONS]
z Before starting wiring, always switch off the GOT power externally in all
phases. Not doing so may cause an electric shock, product damage or malfunction.
DANGER
-3
Page 5
A
[WIRING PRECAUTIONS]
CAUTION
z Please make sure to ground FG terminal, LG terminal, and protective
ground terminal of the GOT power supply unit by applying Class D Grounding (Class 3 Grounding Method) or higher which is used exclusively for the GOT. Not doing so may cause an electric shock or malfunction.
z Correctly wire the power supply module on the GOT after confirming the
rated voltage and terminal arrangement of the product. Not doing so can cause a fire or failure.
z Tighten the terminal screws of the GOT power supply section in the
specified torque range. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or module.
z Exercise care to avoid foreign matter such as chips and wire offcuts
entering the module. Not doing so can cause a fire, failure or malfunction.
z Plug the bus connection cable by inserting it into the connector of the
connected module until it "clicks". After plugging, check that it has been inserted snugly. Not doing so can cause a malfunction due to a contact fault.
z Plug the communication cable into the connector of the connected module
and tighten the mounting and terminal screws in the specified torque range. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or module.
[TEST OPERATION PRECAUTIONS]
DANGER
z Before performing test operation (bit device on/off, word device's present
value changing, timer/counter's set value and present value changing, buffer memory's present value changing) for a user-created monitor screen, system monitoring, special module monitoring or ladder monitoring, read the manual carefully to fully understand how to operate the equipment. During test operation, never change the data of the devices which are used to perform significant operation for the system. False output or malfunction can cause an accident.
-4
Page 6
A
[STARTUP/MAINTENANCE PRECAUTIONS]
DANGER
z When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
z Before starting cleaning or terminal screw retightening, always switch off
the power externally in all phases. Not switching the power off in all phases can cause a module failure or malfunction. Undertightening can cause a short circuit or malfunction. Overtightening can cause a short circuit or malfunction due to the damage of the screws or module.
CAUTION
z Do not disassemble or modify the module.
Doing so can cause a failure, malfunction, injury or fire.
z Do not touch the conductive and electronic parts of the module
directly. Doing so can cause a module malfunction or failure.
z The cables connected to the module must be run in ducts or clamped.
Not doing so can cause the module or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
z When unplugging the cable connected to the module, do not hold and pull
the cable portion. Doing so can cause the module or cable to be damaged or can cause a malfunction due to a cable connection fault.
-5
Page 7
A
[BACKLIGHT CHANGING PRECAUTIONS]
DANGER
z Before changing the backlight, always switch off the GOT power externally
in all phases (when the GOT is connected to the bus, the PLC CPU power must also be switched off externally in all phases) and remove the GOT main unit from the enclosure. Not switching the power off in all phases may cause an electric shock. Not removing the unit from the enclosure can cause injury due to a drop.
CAUTION
z While changing the backlight, do not touch the circuit boards and electronic
parts of the GOT. Doing so can cause a failure or malfunction.
z When changing the backlight, always note the following.
(1) Wear gloves or fingerstalls before starting the replacement of the
backlight. Not doing so can cause injury.
(2) Start changing the backlight more than 5 minutes after switching the
GOT power off. Not doing so can cause a burn due to the heat of the backlight.
[DISPOSAL PRECAUTIONS]
DANGER
z When disposing of the product, handle it as industrial waste.
-6
Page 8
A

Revisions

*The manual number is given on the bottom right of the top cover.
Print Date *Manual Number Revision Jan., 1999 IB(NA)-80032-A First edition Jun., 1999 IB(NA)-80032-B
Jun., 2001 IB(NA)-80032-C
Feb., 2002 IB(NA)-80032-D
Jan., 2004 IB(NA)-80032-E
Mar., 2004 IB(NA)-80032-F
Aug., 2004 IB(NA)-80032-G
Dec., 2005 IB(NA)-80032-H
Partial correction
Section 5.1
Partial addition
Section 3.2, Section 3.3, Section 5.2
Addition
A970GOT-LBA/LBD
Partial correction
Chapter 2, Section 5.1, Section 5.2, Section 5.3
Addition
Appendix 2
Partial correction
SAFETY PRECAUTIONS
Partial correction
Chapter 1, Section 3.2
Addition
Section 5.4
Partial correction
Section 5.4
MODEL CODE change
Changed from 13JN45 to 1DM100.
Addition
Section 5.4, 5.5, 5.6
Partial correction
Section 5.7 corresponds to the former Section 5.4. About Manuals, Section 3.3, Appendix 1
Partial correction
Section 3.2
This manual does not warrant or license any industrial property rights and other rights. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential problems involving the industrial property rights which may arise as a result of the use of this equipment described in this manual.
© 1999 MITSUBISHI ELECTRIC CORPORATION
-7
Page 9
A

CONTENTS

1. Overview .......................................................................................................1
1.1 Packing List ..............................................................................................1
2. System Configuration ....................................................................................2
3. Specifications ................................................................................................3
3.1 General Specifications..............................................................................3
3.2 Performance specifications.......................................................................4
3.3 Power supply specifications......................................................................6
4. Name of the Parts ..........................................................................................7
5. Handling .......................................................................................................8
5.1 Handling instructions ................................................................................8
5.2 Installation method ...................................................................................8
5.3 Wiring diagram .......................................................................................11
5.4 The precautions on the wiring.................................................................12
5.5 Connecting to the GOT Power Section...................................................15
5.6 Connection Cable Wiring........................................................................16
5.7 Precautions for back light replacement...................................................17
Appendices ....................................................................................................18
Appendix 1 Outline dimension drawing.........................................................18
Appendix 2 Depth dimension for when mounting each type of module.........19

About Manuals

The following manuals are related to this product. Referring to this list, please order the necessary manuals.
Detailed Manual
Manual No.
Manual name
(Model code)
A985GOT/A975GOT/A970GOT/A960GOT
SH-4005
User’s Manual
(1DM099)
(Available as an Option)
Relevant Manuals
For relevant manuals, refer to the PDF manual stored within the drawing software.
-8
Page 10

1. Overview

e
This user's manual describes the system configuration, specifications, part names, handling and outline dimensions of the A975GOT/A970GOT/A960GOT Graphic operation terminal (Referred to as GOT, hereafter).
The following GOT types are available.
Item Type Display section
A975GOT
A975GOT-TBA,A975GOT-TBD TFT color liquid crystal A975GOT-TBA-B,A975GOT-TBD-B TFT color liquid crystal *1 A970GOT-TBA,A970GOT-TBD TFT color liquid crystal A970GOT-TBA-B,A970GOT-TBD-B TFT color liquid crystal *1
A970GOT
A970GOT-SBA,A970GOT-SBD D-STN color liquid crystal
STN monochrome liquid
A970GOT-LBA,A970GOT-LBD
crystal
A960GOT A960GOT-EBA,A960GOT-EBD EL
*1:This manual explains the GOT of function version B.
For specifications of GOTs of other function version, refer to A985GOT/ A975GOT/A970GOT/A960GOT User’s Manual.

1.1 Packing List

After unpacking, confirm that you have received the following products.
Product Quantity GOT main unit 1 Mounting fixture 4 Communication module securing fixture 3 Caution plate (seal) 1
*1: Affix a caution plate in a conspicuous position such as memory card
interface part. (Affix a caution plate on a communication module during its use)
When affixing a coution plate on the memory card interface
Caution plate
When affixing a coution plate on th communication module
Caution plate
*2: If the protective sheet needs to be replaced, please obtain the one that is to
be purchased separately.
1
Page 11

2. System Configuration

The overall configuration of the GOT is shown below.
GOT
Drawing software
Communication module, Communication board *1
Option Memory board Flash PC card *1 External I/O interface module *1 Backlight Protective sheet Debug stand
Others Audio output device (Commercially available) Printer (Commercially available) *1 Barcode reader (Commercially available) *1
*1: For details of the system configuration, refer to the GOT-A900 Series User’s
Manual (Connection System Manual).
2
Page 12

3. Specifications

3.1 General specifications

Item Specifications
Operating ambient temperature Storage ambient temperature Operating ambient humidity Storage ambient humidity
Conforms
Vibration resistance
Shock resistance
Operating atmosphere Operating altitude*4 Installation site Inside control box Overvoltage category *2 Contamination level *3
to JIS
B3502
and IEC
61131-2.
Display section
Other than display section
10 to 90%RH, non-condensing
10 to 90%RH, non-condensing
Frequency Acceleration Amplitude Sweep Count
In case of
intermittent
vibration
In case of
continuous
vibration
(147m/s2, 3 times in each of X, Y and Z directions)
10 to 57Hz
57 to
150Hz
10 to 57Hz
57 to
150Hz
Conforms to JIS B3502 and IEC 61131-2
No corrosive gas
-20 to 60°C
9.8m/s
4.9m/s
2000m max.
II or less
2 or less
2
2
0 to 40°C *1
0 to 55°C
0.075mm
0.035mm
10 times in
each of X, Y
and Z
directions
(for 80
minutes)
*1: For A975GOT-TBA/TBD (-B) and A970GOT-TBA/TBD (-B), it becomes 0 to
55°C.
*2: Indicates the element in the distribution system between the public
electricity grid and the mechanical equipment inside the premises that the relevant device is assumed to be connected to. Category II applies to devices such as those that draw their power supply from fixed installations. The surge voltage withstand capability of devices with ratings up to 300V is 2,500V.
*3: This index gives a measure of the incidence of conductive materials in the
environment in which the device is used. A contamination level of 2 indicates an environment in which there is only contamination by non-conducting materials, but due to occasional condensation, conductivity may occur.
*4: Please do not use or store GOT in an environment with atmospheric
pressure greater than the atmospheric pressure at sea level (0m). There is a possibility errors may occur if this point is not observed.
3
Page 13

3.2 Performance specifications

×
Specifications
A975GOT-
Item
Type TFT color liquid crystal
Resolution 640 × 480 dots 640 × 400 dots Display
size Display section
Backlight
Life*1
Environmental protective structure*5
Outline dimensions
Panel cutting dimensions
Weight 1.8 (3.96) kg (lb) 1.9 (4.18) kg (lb) 1.6 (3.52) kg (lb)
Compatible software package*4
Display
color
Intensity
Display
angle
Display
section*2*3
Backlight
Touch key 1 million times or more (operating force 100g max.)
Built-in
memory
TBA(-B)
A975GOT-
TBD(-B)
256 color 16 color 8 color
TBA/TBD:250 cd/m
TBA/TBD-B:380 cd/m
(LCD only)
TBA/TBD:80 degrees
TBA/TBD-B:85 degrees
(right, left, up and down)
(Backlight OFF/screen saving time setting allowed) TBA/TBD:41,000h
TBA/TBD-B:43,000h
(Operating ambient
temperature: 25)
TBA/TBD:40,000h
TBA/TBD-B:43,000h
(Time when display luminance reaches 50% at the
297 (11.7) (W) × 208 (8.2) (H) × 46 (1.81) (D)
SW0D5C-GTWORKS-E
Version A or later,
SW1D5C-GOTRE-PACK
Version A or later
(The 8-step brightness
adjustment of the high
luminance model is
complied to with Version
C and above.)
*1: When parts must be changed, consult your sales representative. *2: The screen save and back light OFF functions of the GOT and operator detect sensor
function are used to prevent the display of the screen from being printed and prolong the service life of the back light.
*3: Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It
is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Please note that these dots appear due to its characteristic and are not caused by product detect.
A970GOT-
TBA(-B)
A970GOT-
TBD(-B)
211 (8.31) × 158 (6.23) mm (inch)
Cold cathode fluorescent tube backlight
operating ambient temperature of 25°C)
Number of write times: 100,000 times
Front section: Equivalent to IP67/NEMA4 Panel inside: IP2X
289 (11.38) (W) × 200 (7.88) (H)
A970GOT-
A970GOT-
D-STN color liquid crystal
2
2
50 degrees(right and left),
mm (inch)
mm (inch)
SW0D5C-
GTWORKS-E
Version A or
SW1D5C-
GOTRE-
Version A or
SBA
SBD
45 degrees(up),
40 degrees(down)
(Operating ambient
temperature: 25)
later,
PACK
later
A970GOT-LBA A970GOT-LBD
monochrome
liquid crystal
2 color
(monochrome)
250 cd/m
(LCD only)
50,000h
40,000h
SW0D5C-
GTWORKS-E
Version A or
SW1D5C-
GOTRE-
Version J or
STN
2
later,
PACK
later
A960GOT-EBA A960GOT-EBD
EL
192 (7.57)
(yellow orange, black)
(Initial luminance
268 (10.56) (W) ×
192 (7.56) (H) ×
49 (1.93) (D)
258 (10.17) (W) ×
183 (7.21) (H)
GTWORKS-E
Version A or
Version A or
120 (4.73)
mm (inch)
2 color
30,000h
70%,25°C)
mm (inch)
mm (inch)
SW0D5C-
later,
SW1D5C-
GOTRE-
PACK
later
4
Page 14
*4: GT Works2 and GT Designer2, are supported from the first version (Version1.00A). *5: The specifications differ depending on the version of GOT (hardware version, function
version).
(1) Specification differences by the version of GOT
The specifications of the GOT-A900 series differ depending on the version (hardware version, function version). The following shows specification differences of the GOT-A900 series by version.
(a) Environmental protective structure
The environmental protective structure (IP rating) differs depending on the hardware version of GOT.
Specification
Environmental protective structure
Item
Front section: Equivalent to IP65 Panel inside: IP2X Front section: Equivalent to IP67/NEMA4 Panel inside: IP2X
A975GOT-TBA(-B) A975GOT-TBD(-B) A970GOT-TBA(-B) A970GOT-TBD(-B)
Hardware version A or later
Hardware version N (Dec., 2001) or
A970GOT-SBA A970GOT-SBD A970GOT-LBA A970GOT-LBD
later
A960GOT-EBA A960GOT-EBD
Hardware
version K (Dec.,
2001) or later
5
Page 15

3.3 Power supply specifications

Specifications
A975GOT-TBA(-B)
Item
Input power supply voltage
Input frequency [Hz]
Using 100VAC
Communication board loaded:
Communication module loaded: Input max. apparent power
Input max. power - 40W
Inrush current
Permissible instantaneous power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance Applicable wire size 0.75 to 2mm Applicable solderless
terminal Applicable tightening torque (Terminal block terminal screw) External output Refer to *2
Using 200VAC
Communication board loaded:
Communication module loaded:
By noise simulator of 1,500Vp-p
noise voltage, 1μs noise width and
1500VAC for 1 minute across AC
A970GOT-TBA(-B)
A970GOT-SBA A970GOT-LBA A960GOT-EBA
100AC to 240V (+10%,-15%) 24VDC(+25%,-20%)
50/60 ± 3
50VA or less
60VA or less *1
63VA or less
75VA or less *1
40Ap max.
(264VAC, max. load)
20ms (100VAC or more) 1ms (19.2VDC or more)
25 to 60Hz noise frequency
external terminals and earth
10MΩ or larger by insulation resistance tester
RAV1.25–3, V2–S3.3, V2-N3A, FV2-N3A
59 to 88Nycm
A975GOT-TBD(-B) A970GOT-TBD(-B)
A970GOT-SBD
A970GOT-LBD
A960GOT-EBD
61Ap max.
(30VDC, max. load)
By noise simulator of
500Vp-p noise voltage,
1μs noise width and 25 to
60Hz noise frequency
500VAC for 1 minute
across DC external
terminals and earth
2
-
-
*1: When the communication module for bus connection (A9GT-BUSSU/A9GT-
BUS2SU/A9GT-QBUS2SU) is loaded, this value is equivalent to the input max. apparent power value when the communication board is loaded.
*2: For external outputs please refer to the A985GOT/A975GOT/A970GOT/
A960GOT User’s Manual that is to be purchased separately.
Remarks
Note that the power is reset if an instantaneous power failure occurs. However, if the instantaneous power failure is within 20ms when using 100 to 240VAC, or within 1ms when using 24VDC, the operation will be normal.
6
Page 16

4. Name of the Parts

)
1) 2) 3) 4) 5) 6) 7)
15)
When 9) is removed
17) 17)
18)
13) 12)11) 10)
9) 8)
17) 17)
14) 16)
No. Name Description
1)Display section Shows the screen
2)Reset button Used to reset the hardware of the GOT Used to set the condition of access to the PC card when it is loaded during power-on (Factory-set to
3)memory card access switch
OFF) OFF: Access from GOT to PC card inhibited ON : Access from GOT to PC card enabled Indicates whether the PC card may be loaded/unloaded or not
4)memory card LED
Off: PC card may be loaded/unloaded (When switch 3 is OFF) On: PC card must not be loaded/unloaded (When switch 3 is ON)
5)Communication module interface Interface for loading the communication module
6)memory card interface Interface for loading the PC card
7)memory card ejection button Button used to withdraw the PC card
8)Speech output terminal For external speaker connection
9)Slot cover Fixture to cover the slot
10)Printer interface For printer connection
11)RS-232C interface
For connection of personal computer For connecting the bar code reader
12)Option module interface For option module loading (for future extension)
13)Terminal block For power input and external output
14)Communication board slot Slot for communication board loading
15)Memory board slot Slot for memory board loading Screw hole for attaching memory
16
board
Screw hole used to attach the memory board
17)Mounting fixture fitting portion For mounting fixture fitting
18)Rating plate ⎯⎯⎯⎯
7
Page 17

5. Handling

5.1 Handling instructions

When mounting the main unit to a control box or the like, set the display section as shown below.
When the temperature inside the enclosure is 40 to 55°C or less, the mounting angle should be in the range 60 to 105 degrees.
GOT
Display
section
Enclosure, etc.
105°
60°
The GOT will be deteriorated earlier if it is used at the mounting angle other than the above. Therefore, the temperature inside the enclosure should be
within 40°C.
Tighten the screws in the following specified range.
Screw Location Tightening Torque Range Terminal block terminal screw (M3 screw) 59 to 88Nycm Mounting Fixture screw (M4 screw) Communication module mounting screw (M3 screw) Communication board mounting screw (M3 screw)
36 to 48Nycm Option module mounting screw (M3 screw) Case fixing screw (M3 screw) Memory board mounting screw (M2.6 screw) 25 to 35Nycm RS-232C connector mounting screw
20 to 28Nycm (#4-40 UNC (inch screw))

5.2 Installation method

(1) Mounting panel cutting dimensions
When mounting the GOT on a control box door, user-made mounting base or the like, the door or mounting base must be cut as indicated below.
A
Item A [mm](inch) B [mm](inch) A975GOT A970GOT
Panel opening
B
A960GOT
289 (11.39)
[+1.0(0.04), 0(0)]
258 (10.17)
[+1.0(0.04), 0(0)]
8
200 (7.88)
[+1.0(0.04), 0(0)]
183 (7.21)
[+1.0(0.04), 0(0)]
Page 18
(2) Mounting position
When mounting the GOT, the following clearances must be left from the other device.
(80mm (3.15 inch) or more)
C
D
(100mm
(3.94 inch)
or more)
Plate thickness within 2mm to 4mm (0.08inch to 0.16inch)
Other
device
BB
A
(50mm (1.97inch) or more)
(50mm
(1.97inch)
or more)
Part A size: As the GOT connection cable is led out downward, the
following clearance must be provided in consideration of the bending radius.
Item A [mm] (inch) A97*GOT + Communication board 130 (5.12) or more A960GOT + Communication board 140 (5.51) or more A97*GOT + A9GT-BUSSU/BUS2SU 15 (0.59) or more A960GOT + A9GT-BUSSU/BUS2SU 30 (1.18) or more
When using a cable prepared by user, please consider the connector cover to be used and the bending radius of the cable. When using a bar code reader, please consider the dimensions of the connector to be used and the bending radius of the cable.
Part B size: When using a PC card or an audio output device (for a
connected cable connector and a wire), a clearance of 100 mm (3.94 inch) or more is required. When removing a PC card by opening a cover of the memory card interface part, a clearance of 50 mm (1.97 inch) is required. (A clearance of 50 mm (1.97 inch) or more is required when an audio output device or a memory card is not used.) (A clearance of 50mm (1.97 inch) or more is required when these are not used.)
Part C size: Please allow a gap 80mm (3.15inch) or more from the
structure and other equipment in the upper part of the unit to often allow good ventilation.
Part D size: When installing a device that generates radiation noise
(contactor, etc.) or a device generating high levels of heat near the GOT, provide a clearance of 100mm (3.94 inch) behind the module to avoid the effect of the noise and heat.
9
Page 19
(3) Mounting method
(a) Put the GOT main unit into the panel opening, with its front face first. (b) Mount the GOT in the following four locations at its top and bottom.
(Top) (Bottom)
Mounting Position Mounting position
(c) How to mount and fix the mounting fixture is given below.
1) Insert the mounting fixture into the fixture fitting portion of the GOT main unit.
2) Tighten and fix the mounting screw in the specified torque range.
10
Page 20

5.3 Wiring diagram

(1) 100AC to 240V
(2) DC24V
INPUT 100-240VAC
INPUT 24VDC
(LG) (FG)
+-
OUTPUT
RUN
L L
LL
+-
DC12/24V
12/24VDC 0.1A
+
-
INPUT 24VDC
-
+
(LG) (FG)
RUN
L L
OUTPUT
12/24VDC 0.1A
+
-
LL
-
+
DC12/24V
* For application of external outputs of RUN OUTPUT, please refer to
the[A985GOT/A975GOT/A970GOT/A960GOT User’s Manual]
11
Page 21

5.4 The Precautions on the Wiring

DANGER
z Completely turn off the externally supplied power used in the system when
installing or placing wiring. Not completely turning off all power could result in electric shock, damage to the product.
CAUTION
z Be sure to ground the FG terminal and LG terminal of the GOT power
supply section to the protective ground conductor. Not doing so could result in electric shock or erroneous operation.
z When wiring in the GOT power section, be sure that it is done correctly by
checking the product's rated voltage and the terminal layout. Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or erroneous operation.
z Tighten the terminal screws of the GOT power supply section within the
specified torque range. If the terminal screws are loose, it could result in short circuits, erroneous operation or erroneous operation. Tightening the terminal screws too far may cause damages to the screws and/or the module, resulting in fallout, short circuits, or erroneous operation.
z Be sure there are no foreign substances such as sawdust or wiring debris
inside the modle GOT main unit.
y General view of noise countermeasures
There are two types of noise: radiated noise, which is transmitted through the air, and conducted noise, which is transmitted through a connection wire. In noise countermeasures, the both two types of noise should be taken into account. As the noise countermeasures, there are the following three methods. (1) Block noise
(a) Keep signal wires away from a possible noise source as power wires
or high-power driving circuits.
(b) Shield signal wires.
(2) Reduce generated noise
(a) Reduce the noise generated from high-power motor drive circuits.
(3) Ground noise without fail
(a) Earth the grounding wire to the ground without fail. (b) Use a grounding wire as thick and short as possible to ensure low
grounding impedance.
(c) Separate the grounding between power and control systems.
12
Page 22
(1) Power supply wiring
y Separate the GOT's power supply line from the lines for I/O devices and
power devices as shown below. When there is much noise, connect an insulation transformer.
Power supply wiring diagram
Insulation
Transformer
GOT
T1
I/O equipment
Main circuit equipment
200VAC
Main power supply
GOT power supply
I/O power supply
Main circuit equipment
y 100VAC, 200VAC and 24VDC wires should be twisted as dense as
possible. Connect the modules with the shortest distance. Also, to reduce the voltage drop to the minimum, use the thickest wires possible (0.75 to 2mm
2
). Use a solderless terminal for M3 screw. Also, be sure to tighten the M3 screw within tightening torque 0.55 to 0.88 Nym in order not to cause trouble.
y Do not bundle the 100VAC, 200VAC and 24VDC wires with, or run them
close to, the main circuit (high voltage, large current) and I/O signal lines. Reserve a distance of at least 100 mm from adjacent wires.
y As a countermeasure to power surge due to lightening, connect a surge
absorber for lightening as shown below.
Lightening surge absorber connection diagram
AC
E1
Surge absorber for lightening
GOT
E2
POINT
(1) Separate the ground of the surge absorber for lightening (E1) from
that of the GOT (E2).
(2) Select a surge absorber for lightening whose power supply voltage
does no exceed the maximum allowable circuit voltage even at the time of maximum power supply voltage elevation.
13
Page 23
(2) Grounding
y For grounding, perform the following:
Use a dedicated grounding wire as far as possible. (Grounding resistance of 100
or less.)
y When a dedicated grounding cannot be performed, use (2) Common
Grounding shown below. Also, be sure to take noise countermeasures other than grounding.
GOT
Grounding
(Class 3 grounding)
(1) Independent grounding Best
Power equipment
GOT
Grounding
(Class 3 grounding)
(2) Common grounding Good (3) Joint grounding Not allowed
Power equipment
y For grounding a cable, use the cable of 2 mm2 or more.
Position the ground-contact point as closely to the sequencer as possible, and reduce the length of the grounding cable as much as possible.
(a) An example of independent grounding
Power equipment (Servo, etc.)
CN1A CN1B
CN2
CN3
Connection cable
FG LG
GOT
Power equipment
FG
FG
GOT
LG
Panel grounding
Grounding for
Grounding terminal block
Grounding for control system
Grounding terminal block
power system
* For control system grounding, apply single-point grounding for one
system. Especially for the devices communicating each other, be sure to earth the grounding wire at one point.
14
Page 24
(b) An example of common grounding
A
Power equipment (Servo, etc.)
CN1A CN1B
CN2 CN3
FG
FG LG
Connection cable
FG
GOT
LG
Panel grounding
Use a grounding wire as thick and short as possible.
Grounding terminal block
* Apply single-point grounding for one system.

5.5 Connecting to the GOT Power Section

The following diagram shows the wiring example of power lines, grounding lines, etc. to the GOT power section.
C
100/110VAC
Fuse
AC DC
24VDC
When using 100VAC
GOT
INPUT
100-240VAC
LG FG
When using 24VDC
GOT
INPUT
24VDC
LG FG
Grounding wire
Grounding
15
Page 25
POINT
(1) Use the thickest possible (max. 2 mm2 (14 AWG)) wires for the
100/200 VAC and 24 VDC power cables. Be sure to twist these wires starting at the connection terminals. To prevent a short-circuit should any screws loosen, use solderless terminals with insulation sleeves.
(2) When the LG terminals and FG terminals are connected, be sure to
ground the wires. Do not connect the LG terminals and FG terminals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PLC may be susceptible to noise. In addition, since the LG terminals have potential, the operator may receive an electric shock when touching metal parts.

5.6 Connection Cable Wiring

Do not bind connection cables with the main circuit (high voltage, heavy current) or I/O signal cables, or lay them close to each other.
When using A8GT-C
(1) When using A8GT-C
PLC
FG LG
N L
EXSS-1 or A8GT-C BS, ground wires as below.
EXSS-1 cable
Disconnected
(A8GT-EXCNB)
6)
3)
(A8GT-C BS)
2SQ wire FG terminal, 28 cm or less
5)
OUT
FGLG
NL
4)
GOT
2)
1) Connect the LG and FG terminals of GOT unit power to the ground through the terminal block with one wire.
2) Use FG wires of 28 cm or less for the A8GT-C
BS cable.
3) Do not connect the FG grounding wire of A8GT-EXCNB cable.
4) Connect the A8GT-C
BS cable’s FG wire to FG of the GOT unit power
terminal block.
5) Connect the A8GT-C
BS cable’s FG wire on the PLC side to FG of the
PLC power supply module.
6) Connect the LG and FG terminals of the terminal block on the PLC to ground with one wire.
(2) When using A8GT-C
Connect the A8GT-C
BS cable
BS cable’s FG wires on the both sides to the FG
terminals on the power terminal block of the both side GOTs.
IN
1)
16
Page 26

5.7 Precautions for back light replacement

Use the following back lights for the GOT that includes this manual.
Type Model
A975GOT-TBA (Hardware version D (JAN,1998) or later), A975GOT-TBD (Hardware version B (JAN,1998) or later)
A975GOT
A975GOT-TBA-B (Function version B (JAN,2004) or later), A975GOT-TBD-B (Function version B (JAN,2004) or later) A970GOT-TBA (Hardware version D (JAN,1998) or later), A970GOT-TBD (Hardware version B (JAN,1998) or later) A970GOT-TBA-B
A970GOT
(Function version B (JAN,2004) or later), A970GOT-TBD-B (Function version B (JAN,2004) or later) A970GOT-SBA, A970GOT-SBD, A970GOT-LBA, A970GOT-LBD
Replacement back
light
A9GT-70LTTB
A9GT-70LTTBW
A9GT-70LTTB
A9GT-70LTTBW
A9GT-70LTS
The GOT hardware version and function version can be checked from the rating plate, which is situated on the backside of the GOT.
GRAPHIC OPERATION TERMINAL
MODEL
IN 100-240VAC 50/60Hz
POWER
C
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
BACKLIGHT A9GT-70LTTBW
A970GOT-TBA-B
MAX 115VA 0401 AW
US LISTED
Rating plate
DATE
80M1 IND.CONT.EQ.
BD992C189H02
B
Function version
0401 AW
Hardware version
Production date
Conformed standard
Back light model (The applicable back light model is described.)
The applicable back light differs with the GOT hardware version and function version. For more information, refer to A985GOT/A975GOT/A970GOT/A960GOT User’s Manual.
17
Page 27

Appendices

A
A
A

Appendix 1 Outline dimension drawing

L
C
M
F
GG
BI
K
J
D A
H
E
Unit: mm(inch)
Item A B C D E F G H I J K L M
975GOT, 970GOT
960GOT
297
(11.70)
268
(10.56)
208
(8.20)
192
(7.56)
235
(9.26)
204
(8.04)
229
(9.02)
198
(7.80)
288
(11.35)
257
(10.13)
199
(7.84)10(0.40)46(1.81)40(1.58)6(0.24)34(1.34)31(1.22)
182
(7.17)10(0.40)49(1.94)43(1.69)6(0.24)35(1.38)32(1.26)
15.4
(0.61)
15.4
(0.61)
18
Page 28

Appendix 2 Depth dimension for when mounting each type of module

(1) A97*GOT
Communication board loading
B
A
Installed communication module A [mm] (inch) B [mm] (inch) A9GT-QBUSS, A9GT-BUSS 40 (1.57) 85 (3.35) A9GT-QBUS2S, A9GT-BUS2S 62 (2.44) 85 (3.35) A9GT-BUSSU, A9GT-BUS2SU 74 (2.91) 15 (0.59) A9GT-RS2(T) 40 (1.57) *1 A9GT-RS4 40 (1.57) 115 (4.53) A7GT-J71AP23, A7GT-J71LP23 74 (2.91) *2 A7GT-J71AR23, A7GT-J71BR13 74 (2.91) *3 A7GT-J71AT23B 96 (3.78) ­A8GT-J61BT13, A8GT-J61BT15 79 (3.11) ­A9GT-J71E71-T 70.2 (2.76) ­A9GT-70KBF 82.6 (3.25) -
Communication module/Option module loading
B
A
(2) A960GOT
Installed communication module A [mm] (inch) B [mm] (inch) A9GT-QBUSS, A9GT-BUSS 43 (1.69) 100 (3.94) A9GT-QBUS2S, A9GT-BUS2S 65 (2.56) 100 (3.94) A9GT-BUSSU, A9GT-BUS2SU 77 (3.03) 30 (1.18) A9GT-RS2(T) 43 (1.69) *1 A9GT-RS4 43 (1.69) 130 (5.12) A7GT-J71AP23, A7GT-J71LP23 77 (3.03) *2 A7GT-J71AR23, A7GT-J71BR13 77 (3.03) *3 A7GT-J71AT23B 99 (3.90) ­A8GT-J61BT13, A8GT-J61BT15 82 (3.23) ­A9GT-J71E71-T 73.2 (2.88) ­A9GT-70KBF 85.6 (3.37) -
*1 Depends on the dimensions of the converter and cable used. *2 This dimension is between 195mm (7.68) maximum and 80mm (3.15)
minimum depending on the optional fiber cable and connector connected.
*3 This dimension is between 80mm (3.15) maximum and 73mm (2.87)
minimum depending on the coaxial cable connected.
19
Page 29
MEMO
20
Page 30

Warranty

Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
For safe use
y This product has been manufactured as a general-purpose part for general industries, and
has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
y Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
y This product has been manufactured under strict quality control. However, when installing
the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A Mitsubishi Electric Automation Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061 Tel : +1-847-478-2100 Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda.
Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar Paraiso, Sao Paulo, SP Brazil
Tel : +55-11-5908-8331 Germany Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8 D-40880 Ratingen, GERMANY Tel : +49-2102-486-0 U.K Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Herts., AL10 8XB,UK Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2 Via Paracelso 12, 20041 Agrate B., Milano, Italy Tel : +39-039-6053344
Spain Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rubi 76-80 08190 Sant Cugat del Valles, Barcelona, Spain Tel : +34-93-565-3131
France Mitsubishi Electric Europe B.V. French Branch 25 Boulevard des Bouvets, F-92741 Nanterre Cedex, France TEL: +33-1-5568-5568 South Africa Circuit Breaker Industries LTD.
Tripswitch Drive, Elandsfontein Gauteng, South Africa Tel : +27-11-928-2000
Country/Region Sales office/Tel
Hong Kong Ryoden Automation Ltd. 10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong
Tel : +852-2887-8870 China Ryoden Automation Shanghai Ltd.
3F Block5 Building Automation
Instrumentation Plaza 103 Cao Bao Rd.
Shanghai 200233 China Tel : +86-21-6120-0808 Taiwan Setsuyo Enterprise Co., Ltd. 6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan Tel : +886-2-2299-2499 Korea HAN NEUNG TECHNO CO.,LTD. 1F Dong Seo Game Channel Bldg., 660-11, Deungchon-dong Kangsec-ku, Seoul, Korea
Tel : +82-2-3660-9552 Singapore Mitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building Singapore 159943 Tel : +65-6473-2308 Thailand F. A. Tech Co.,Ltd.
898/28,29,30 S.V.City Building,Office Tower 2,Floor 17-18 Rama 3 Road, Bangkpongpang, Yannawa, Bangkok 10120
Tel : +66-2-682-6522 Indonesia P.T. Autoteknindo SUMBER MAKMUR Jl. Muara Karang Selatan Block a Utara No.1 Kav. No.11 Kawasan Industri/ Pergudangan Jakarta - Utara 14440 Tel : +62-21-663-0833 India Messung Systems Put,Ltd. Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026, India Tel : +91-20-712-2807 Australia Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia Tel : +61-2-9684-7777
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100 -8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.
Loading...