Mircom QMT-5300A, QMT-5302, QZT-5302 User Manual

Advanced Life Safety Solutions
QMT-5300A, QMT-5302 and QZT-5302
Firefighters’ Telephone System
COMMON TEL. TROUBLE
MASTER TEL.
TROUBLE
INCOMING CALL
CONNECT/ CLEAR ALL
LAMP TEST
Installation & Operation Instructions
LT-674 Rev. 2 Dec 2007
QMT-5300A, QMT-5302 and QZT-5302 Installation and Operation Instructions
QMT-5300A, QMT-5302 and QZT-5302 Instructions
Introduction
MIRCOM’s Fire Fighters’ Telephone may be used either alone as a Single Zone System (using the QMT-5300A or QMT-5302 Master Telephone by itself), or as a Multi-Zoned System (with the QZT-5302 Zone Adders).
Mounting
The modules mount in any of the BB-1000 Series Remote Annunciator enclosures except for the QMT-5302 Master Telephone which mounts into a BB-5008 or BB-5014 backbox. For the QMT-5300A Master Telephone, the included extended window module must be installed in place of the existing window. In any BB-1000 enclosure, the QMT­5300A is mounted bottom-most, and one to five QZT-5302s above, for a total of 60 Telephone Zones. In any BB­5008 enclosure, the QMT-5302 should be mounted below the QZT-5302s and beside the master telephone for ease of ribbon cable installation.
Labels
Two slide-in labels are supplied with the QMT-5300A ; the NP-735 is used for Single Zone and the NP-736 for Multi­Zone. Slide-in label NP-896 is provided with the QMT-5302, use the Connect for Single Zone or Clear All label for Multi-Zone. The QZT-5302 includes blank labels for Telephone Zone information.
Chassis Ground
Connect one of the BB-1000 Series Backbox, BB-5008 or BB-5014 Earth-Ground points (Chassis Ground) to Earth Ground (cold water pipe).
Power Supply
Only the telephone master QMT-5300A or QMT-5302 module requires power. It can be powered with a 24 VDC, 200 mA external DC power source (filtered or un-filtered, such as 4-wire smoke or auxiliary power from a Fire Alarm Control Panel), see Fig.1
Jumpers
There are three jumpers on the QMT-5300A and QMT-5302 PCB showing at the top of the black chassis. For a Single-Zoned System JW1 and JW2 have jumpers installed, JW3 does not. For a Multi-Zoned system with QZT­5302s, JW1 & JW2 jumpers are removed, and JW3 is installed. There is one jumper, JW1, on each QZT-5302 Zone Adder, and a jumper is installed only on the last QZT-5302.
Connectors
On the QMT-5300A and QMT-5302, P1 is used only for Multi-Zoned Systems. P2 is the connection for the Master Telephone Handset. On the QZT-5302, P1 connects to the QMT-5300A, QMT-5302 or previous QZT-5302, and P2 connects to the next QZT-5302.
1
QMT-5300A, QMT-5302 and QZT-5302 Instructions
QMT-5300A/QMT-5302 Master Telephone Wiring
Figure 1 shows the wiring for QMT-5300A and QMT-5302. A Fire Alarm Control Panel’s Detection Zone (should be configured as Trouble-Only or Non-Latching Supervisory) is used to annunciate Telephone Trouble. This is connected to the QMT-5300A or QMT-5302 TROUBLE terminals (polarity does not matter), and the ELR device for that zone is connected to the QMT-5300A or QMT-5302 ELR terminals. DC Power (24 V DC, filtered or unfiltered at 200 mA) is connected to the 24 V DC terminals.
If the Master Telephone is being used alone as a Single-Zone System, the NP-735 Label is used or Connect label from NP-896, and Jumpers are placed on JW1 and JW2 only. The one Telephone Zone connects to the TEL-CKT terminals. The 10 Kohm ELR resistor that is shipped with this unit is connected after the last Remote Telephone on the Zone and the negative black jumper is removed for Class B. For Class A wiring, remove both red and black jumper wires and wire from OUT + - to the remote telephones and back to RET + -.
If the Master Telephone is being used as a Multi-Zoned System with QZT-5302s, the NP-736 Label is used or Clear All label from NP-896, and a Jumper is placed on JW3 only. The TEL-CKT terminals are left as is. Telephone Zone wiring is done via the QZT-5302s.
Figure 1: QMT-5300A/QMT-5302 Master Telephone Wiring
QMT-5300A or QMT-5302
APPROVED ELR END- OF-LINE
ELR
DEVICE FOR CONNECTED FIRE ALARM PANEL
TRANSMIT
TROUBLE
OUT
RET
TELEPHONE CIRCUIT
LAMP TEST
EXT AUDIO
+
-
+
-
LT
COM
+
-
RED
REMOVE BOTH JUMPERS WHEN WIRING AS CLASS A
BLK
NOT USED
NOT USED
CLASS A RETURN FOR
TO DETECTION ZONE OF CONNECTED FIRE ALARM PANEL, TO BE USED TO ANNUNCIATE TELEPHONE TROUBLE
TELEPHONE CIRCUIT SINGLE ZONE SYSTEM:
OTHER COMPATIBLE REMOTE TELEPHONES. REMOVE THE NEGATIVE BLACK JUMPER FROM OUT - and RET -TERMINALS. CONNECT A 10K ELR RESISTOR AFTER THE LAST REMOTE TELEPHONE. FOR CLASS A WIRING OF TELEPHONE ZONE, WIRE OUT + - AND BACK FROM LAST TELEPHONE TO RET + -.
MULTI-ZONE SYSTEM:
AND LEAVE RED AND BLACK WIRES CONNECTED AS SHOWN.
SINGLE ZONE
TO LAMP TEST TERMINAL ON QMP-5100A OR QMP-5101 AUDIO CONTROL MODULE
TO EXT AUDIO TERMINAL ON QMP-5100A AUDIO CONTROL MODULE
SYSTEM
CLASS B TELEPHONE ZONE FOR FT-300 OR
DO NOT CONNECT ANY REMOTE TELEPHONES
+
24 VDC
16 or 18 AWG ONLY
-
2
FROM 20.4V DC LOW BATTERY TO 29V DC UNFILTERED HIGH AC LINE