Mircom MS-700ID, MS-701ID(U), MS-702ID(U), MS-710ID(U), MS-701UD Operating Instructions Manual

ALPHA INTELLIGENT ADDRESSABLE MANUAL ST ATIONS MS-700ID SERIES
Features
Single or Dual Action• Key resettable• Permanently Attached Intelligent Addressable
Module High-gloss red enamel fi nish Plastic breakrod• Mounts on standard single gang box, Mircom’s
BB-700 surface metal backbox or BB-700WP
MS-710IDU
Intelligent Addressable
Dual Action Manual Station
MS-701UD
Intelligent Addressable
Single Action Manual Station
weather proof backbox Available in English and Bilingual versions
Description
Mircom’s MS-700ID Series Intelligent Fire Alarm Manual Stations are made of a high quality , die-cast metal and are available in either single or dual action confi gurations with one or two permanently attached addressable modules.
The addressable manual station has DIP switches which allow for address setting. Pulling the handle initiates the operation of the addressable module.
All models are available with CA T-30 keys and mount on a standard single gang backbox, Mircom model BB-700 interior surface metal backbox, or BB-700WP weather proof backbox.
Operation
The MS-700ID Series is operated by pulling the handle on the front of the station. The unit is reset by opening the station with the key , placing the handle in the normal upright position and relocking the station. On the dual action models, the push bar rotates inward allowing the Manual handle to be grasped in a one handed motion.
Specifi cations
The manual station shall be Mircom’s MS-700ID Series. Operating instructions shall be in raised English or English and French lettering and the unit shall be constructed of high quality die-cast metal and fi nished in red enamel paint to provide quick identifi cation. Pulling the handle shall initiate immediate operation of the intelligent addressable module. In addition, those stations installed in a two stage system shall come equipped with an internal key switch designed to operate the 2nd stage alarm initiating circuit.
All manual fi re alarm stations shall be installed to comply with the Canadian Electrical Code (CSA 22.1) and CAN/ULC-S524-01 Standard for Installation of Fire Alarm Systems. Final acceptance is subject to the local authority having jurisdiction.
S7005 S7005
CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifi cations and models and also to discontinue models.
5678
Specifi cations
Switch Rating: 1 Amp @ 30 VDC
0.1 Amp @ 125 VAC
Manual Station Dimensions: 4.9” H x 3.5” W x 2.0” D Color: Red with raised white letters, white Manual bar with raised black letters.
Surface Mount Backboxes
BB-700 Surface Mount Backbox
Dimensions:
5” H x 3.6” W x 2.0” D
Typical Wiring Diagram
RED
FROM PREVIOUS DEVICE
}
BLK
MS-701ID(U), MS-702ID(U) and MS-710ID(U)
- BLACK
+ RED
BLK
RED
PUR
WHI
DIL SWITCH FOR ADDRESS SETTING
~
BLK
RED
PUR
WHI
DIL SWITCH FOR ADDRESS SETTING
~
BB-700WP Weatherproof Surface Mount Backbox
Dimensions:
5” H x 3.6” W x 2.2” D
}
TO NEXT DEVICE
ADDRESSABLE MODULE
Ordering Information
Model Description
MS-701ID MS-702ID MS-710ID
Note: Add suffi x “U” for English only models.
BB-700 BB-700WP
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113
Web page: http://www.mircom.com Email: mail@mircom.com
Alpha Intelligent Addressable Key Resettable Single Action Single Stage Manual Station (Bilingual) Alpha Intelligent Addressable Key Resettable Single Action Two Stage Manual Station (Bilingual) Alpha Intelligent Addressable Key Resettable Dual Action Single Stage Manual Station (Bilingual)
Series 700 Interior Surface Mount Backbox, Red Finish Series 700 Weatherproof Surface Mount Backbox, Red Finish
NOT TO BE USED FOR INSTALLATION PURPOSES.
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113
N.O.
SWITCH
WHITE
KEY SWITCH
Distributed by:
CAT. 5678
Rev. 2
Loading...