13.1FX-2000 Series Compatible Addressable Loop Devices (UL) ....................................... 85
13.2FX-2000 Series Compatible Two-Wire Smoke Detectors (UL) ...................................... 86
13.3FX-2000 Series Compatible Four-Wire Smoke Detectors (UL Listed) ........................... 88
13.4FX-2000 Series Compatible Signalling Devices (UL Listed) .......................................... 88
13.5FX-2000 Series Compatible Addressable Loop Devices (ULC) ..................................... 89
13.6FX-2000 Series Compatible Hardwire Smoke Detectors (ULC) .................................... 90
13.7FX-2000 Series Compatible Synchronized Modules and Strobes ................................. 91
14.0Appendix C: Power Supply and Battery Calculations 92
15.0Appendix D: Remote Annunciator Panels 94
16.0Appendix E: DIP Switch Settings Summary 96
17.0Appendix F: Alarm Verification Timing 98
18.0Appendix G: Wiring For Supervised Output Module 99
19.0Appendix H: Label Requirements for Zone Identification 100
ii
1.0Introduction
1.1 About the FX-2000
Mircom's cost-effective FX-2000 Intelligent Analog Fire Alarm Control Panel (FACP) is a
flexible and easy-to-use analog system. The FX-2000 base panel consists of: one intelligent
analog loop controller capable of supporting 99 analog sensors and 99 addressable modules
that can be wired in Class A (Style 6 or 7) or Class B (Style 4). Analog sensors and
addressable modules consist of all compatibility listed devices including Advanced Protocol
devices. Loop adder modules are available for additional addressable (SLC) loops. The ALC198S provides one additional addressable loop, and the ALC-396S provides two addressable
loops each capable of supporting 99 analog sensors and 99 addressable modules. In addition,
the base panel supports up to 16 conventional adder modules such as the DM-1008A Initiating
Circuit Module, SGM-1004A NAC Circuit Module, and the RM-1008A Relay Circuit Module.
The base panel also includes 4 Class A/B (Style Z/Y) NAC circuits rated at 1.7 amperes each,
and either a 6- or 12-ampere power supply. The ALC-H16 adder board provides expansion for
16 additional conventional hardwire modules.
1.2 Overall Features
Introduction
•Large system capacity and modular design.
•Each Analog Loop is capable of supporting 99 analog sensors and 99 addressable
modules which can be wired as Class A (Style 6 or 7) or Class B (Style 4).
•The base system supports 16 conventional hardwire adder modules.
•6 or 12 Ampere Power Supply.
•Four Class A/B (Style Z/Y) NAC Circuits rated at 1.7 Amperes each, which can be
configured as Audible or Visual (silenceable or non-silenceable circuits). Audibles may
be steady, Temporal Code, California Code, or March Time.
•NAC circuits may be configured to provide additional auxiliary power or resettable
auxiliary power.
•Fault isolators are present on all in panel addressable loops.
•Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-
Man Walk Test.
•Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an
interface to the Mircom RTI Remote Trouble Indicator.
•RS-485 Interface for Remote Multiplex Annunciators.
•Three Level Password Protection with field settable definition which enables the installer
to determine what functions are accessible for each of the three levels of pass
•Four queues for Alarm ACK, Supervisory ACK, Trouble ACK, and BLDG (Monitor) ACK,
with LED indicators and selector keys.
•Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and
Common Trouble.
•RS-232 Port for remote system printer or “CRT terminal”.
•Two Event History Logs; one for Alarm related events and one for all events.
•Front Panel Auto-Configure and / or Personal Computer Configuration.
•Large 4 line by 20 character alphanumeric, back-lit LCD Display with user-friendly menu
system.
1
Introduction
•Common controls and indicators for System Reset, Lamp Test, Fire Drill, Signal Silence,
General Alarm,
•General Alarm Cancel, AC On, Pre-Alarm, and Ground Fault.
•Two Spare configurable Keys and LED Indicators.
•16 configurable LEDs (bi-coloured) with slide-in labels, available with the DSPL-420-
16TZDS display.
•Provides drift compensation for photoelectric smoke detectors.
•Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1
to 4 digits, each digit consisting of 1-15 pulses on the signal).
•Selection for Canadian (ULC) or USA (ULI) requirements for Smoke Sensor sensitivity.
•Extensive transient protection.
•Surface Mountable Enclosures with removable doors for easy installation and service.
Flush Trims available.
•Removable Terminal Blocks for easy wiring and service.
•Loop Adder modules ALC-198S and ALC-396S for expanding addressable loops by 1
The term circuits refers to an actual electrical interface, initiating (detection), NAC (signal), or
relay.
The term zone is a logical concept for a fire alarm protected area, and will consist of at least
one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual the term circuit
is used.
On the FX-2000, circuits can be hardwired inputs and outputs or addressable inputs and
outputs. Both hardwired inputs and outputs, and addressable inputs and outputs may be
grouped together to form logical zones.
2.2 Wiring Styles
Document Conventions
Initiating circuits are configured by default as Class B (Style B). They may be globally (all or
none) configured as Class A (Style D) as described in the system configurator. This operation
uses odd and even pairs of two-wire Class B (Style B) circuits to make one four-wire Class A
(Style D) circuit, thus cutting in half the number of available initiating circuits.
Notification Appliance Circuits (NAC) circuits (also known as NAC circuits) may be
individually wired as Class A (Style Z) or Class B (Style Y) without affecting the number of
circuits available.
Addressable Loops may be configured system wide as Class B (Style 4) or Class A (Style 6).
With the addition of isolators, a Class A (Style 6) will become a Class A (Style 7).
3
3.0System Components
FX-2000 Chassis Types
System Components
FX-2003-6DS (pictured on the left)FX-2017-12ADS
FX-2003-6DS-16LED (pictured on the right)FX-2017S-12ADS
FX-2003-12DS (pictured on the left)
FX-2009-12DSFX-2003-12XTDS
FX-2009S-12DS
ECX-0012 Expander Chassis
4
System Components
All FX-2000 Series Panels have the following features:
•Main Chassis with one analog loop
•4 Style Y or Z NAC Circuits
•4 line by 20 character back-lit LCD display
Table 1 details the specifics of each chassis type. Some models may not be available in all
markets. Verify with your local distributor.
Table 1 FX-2000 Chassis Types
ModelAmps
# of
Addressable
loops
# of
NACs
# of
Adder
Modules
# of
Conventional
Adder
Max # of
Display
Adders
Mounts into
Modules
FX-2003-6DS614332UB-1024DS
FX-2003-6DS-
16LED
FX-2003-12DS1214332UB-1024DS
FX-2003-12XTDS1214992
FX-2009-12DS12149163
FX-2009S-12DS12049163
FX-2017-12ADS121417163
FX-2017S-12ADS120417163
614332UB-1024DS
BBX-1024XT
or
BBX1024XTR
BB-5008 or
BB-5014
BB-5008 or
BB-5014
BBX-1072ADS
or BBX1072ARDS
BBX-1072ADS
or BBX1072ARDS
EXC-001212001202
3.1 Adder Modules
The following table describes the adder modules used with the FX-2000.
Table 2 FX-2000 Adder Modules
ModelsDescription
ALC-198S
Single Intelligent Analog Loop Controller
Module
BB-5008 or
BB-5014
5
Table 2 FX-2000 Adder Modules
ModelsDescription
System Components
ALC-396S
DM-1008A, SGM-1004A,
RM-1008A
DSPL-420-16TZDS
3.2 Auxiliary Modules
The following table describes the auxiliary modules used with the FX-2000.
Dual Intelligent Analog Loop Controller
Module
Conventional Circuit Adder Modules,
Detection, Signal and Relay.
Optional main display with 16
configurable bi-coloured LEDs.
This display is included in the
FX-2003-6DS-16LED chassis package.
Table 3 FX-2000 Auxiliary Modules
ModelDescription
PR-300Polarity Reversal and City Tie Module
UDACT-300ADigital Communicator/Dialer Module
IPS-2424DSProgrammable Input Switches Module
6
3.3 Enclosures
The following table describes the enclosures used with the FX-2000.
Table 4 FX-2000 Encl o su res
System Components
ModelDescription
BB-5008Backbox 36”H x 30”W x 7”D
BB-5014Backbox 60”H x 30”W x 7”D
7
Table 4 FX-2000 Enclosures
ModelDescription
System Components
UB-1024DS
DOX-1024DS
DOX-1024DSR
FX-2003-6DS16LED
UB-1024DS Universal Backbox
26”H x 14.5”w x 4.2”D
DOX-1024DS white door for universal backbox.
DOX-1024DSR red door or universal backbox.
Complete system with DSPL-420-16TZDS
display and UB-1024DS backbox and
DOX-1024DSR door.
8
Table 4 FX-2000 Encl o su res
ModelDescription
System Components
BBX-1024XT
BBX-1024XTR
BBX-1072ADS
Enclosure 35.5”H x 14.5”w x 5.25”D, white door
Enclosure 35.5”H x 14.5”w x 5.25”D, red door
Enclosure 24.8” x 32.5” x 6.4”, white door
BBX-1072ARDS
Enclosure 24.8” x 32.5” x 6.4”, red door
9
3.4 Flush Trim Ring
The following table describes the flush trim ring used with the FX-2000.
Table 5 FX-2000 Flush Trim Ring
System Components
ModelDescription
FA-XT-TRB
3.5 Remote Annunciators
The following table describes the remote annunciators used with the FX-2000.
Table 6 FX-2000 Remote Annunciators
Model
RA-1000
Series
Black flush trim ring for BBX-1024XT and
BBX-1024XTR.
Description
Remote multiplex annunciator panels. For Canada,
ULC-S527 Standard requires a Common Alarm,
Common Supervisory, and a Common Ground Fault
LED indicator on the Remote Annunciators. To meet
this requirement, use the FX-2000 Configurator to
correlate one LED for Common Alarm, one LED for
Common Supervisory and one LED for Common
Ground Fault.
10
RAM-208/216
Remote multiplex annunciator panels. For Canada,
ULC-S527 Standard requires a Common Alarm,
Common Supervisory, and a Common Ground Fault
LED indicator on the Remote Annunciators. To meet
this requirement, use the FX-2000 Configurator to
correlate one LED for Common Alarm, one LED for
Common Supervisory and one LED for Common
Ground Fault.
Table 6 FX-2000 Remote Annunciators
System Components
3.6 Batteries
The following table describes the batteries used with the FX-2000.
Model
MGD-32,
AGD-048
RAX-LCDRemote Shared Display Annunciator
Description
Remote graphic annunciator drivers. The AGD-048
must be installed in the same enclosure as the
MGD-032.
Table 7 Batteries
ModelDescription
Batteries10 to 55 AH
3.7 FX-2000 Accessories
Table 8 Accessorie s
ModelDescription
MP-300/R/SEnd-of-line Resistor Plate, Beige, R for red, S for stainless steel finish
RTI-1Remote Trouble Indicator (ULC and ULI listed)
BC-160External Battery Cabinet (ULC and ULI listed)
11
Mechanical and Chassis Installation
4.0Mechanical and Chassis Installation
The following chapter describes the Mechanical and Chassis installation for all FX-2000
FAC Ps.
4.1 Mechanical Installation Diagrams
Mechanical Installation Instructions for the following enclosures:
•BB-5008
•BB-5014
•UB-1024DS and DOX-1024DS/R
•BBX-1024XT
•BBX-1024XTR
•BBX-1072ADS
•BBX-1072ARDS
4.1.1 BBX-1072ADS and BBX-1072ARDS Mechanical Installation
The BBX-1072ADS and BBX-1072ARDS are suitable for flush or surface mounting, and have
a built-in trim ring.
Dimensions of Enclosure (minus built in trim ring)24.8” x 6.4” x 32.5”
Distance between horizontal mounting screws16”
Distance between vertical mounting screws23.6”
Complete Dimensions of Enclosures 26.4” x 7.7” x 34”
12
Mechanical and Chassis Installation
i
Figure 1 BBX-1072ADS and BBX-1072ARDS Flush or Surface Enclosure Installation
and Dimensions
Note:Leave bottom of box conduit free for batteries.
Figure 3 BB-5014 Installation Instructions and Dimensions
Note:Leave bottom of box conduit free for batteries.
15
Mechanical and Chassis Installation
26 ”
17”
23 1/2”
14 1/2”
5 5/8”
1 3/8”
4 1/4”
12”
28 ”
26 ”
1 3/4”
1 3/4”
6”
2”
9 1/2”
1 3/4”
1 3/4”
2”
2”
TOP VIEW
SIDE VIEW
SIDE VIEW
BACKBOX
DOOR
BACKBOX FRONT VIEW
UB-1024DS UNIVERSAL BACKBOX AND DOX-1024DS/R DOOR
KNOCKOUT LOCATIONS
Dimensions of backbox (minus built-in trim ring)
Horizontal distance between mounting screws
Vertical distance between mounting screws
Complete dimensions of enclosure with door
Size of Knockouts
26”H x 14 1/2”W x 4 1/4” D
12”
1”
23 1/2”
28”H x 17”W x 5 5/8”D
4.1.4 UB-1024DS and DOX-1024DS/R Mechanical Installation
The universal enclosure is suitable for flush or surface mounting, and have a built-in trim ring.
Dimensions of backbox (minus built in trim ring)26” x 14.5” x 4.25”
Distance between horizontal mounting screws12”
Distance between vertical mounting screws23.5”
Complete Dimensions of Enclosure with door28” x 17” x 5.6”
Figure 4 UB-1024DS and DOX-1024DS/R Installation Instructions and Dimensions
16
4.1.5 FX-2003-12XTDS Mechanical Installation
14.500
35.500
5.25
17.000
38.010
12.000
25.500
Front Door
(Inside View)
FA-XT-TRB
Trim Ring for
Flush Mounting
Backbox
Adhere trim ring to wall
surface around backbox.
Backbox
Mounting Holes
FX-2003-12XTDS is an expanded version of the FX-2003-12DS.
Dimensions14.76” wide by 35.8” long by 5.45”
16GA (0.059”) thick for backbox
14GA (0.075”) thick for door
FinishPainted except for hinges
Mechanical and Chassis Installation
Figure 5 BBX-1024XT/R Backbox Enclosure with Trim Ring
17
Mechanical and Chassis Installation
TRIM R ING
WALL
WOOD OR
METAL STUD
BACKBOX
4.1.6 Surface and Flush Mounting Views of the BBX-1024XT/R
5.45”0.7”
Figure 6 BBX-1024XT/R Surface and Flush Side Views
4.1.7 BBX-1024XT Flush Mounted Box with FA-XT-TRB Trim Ring
Figure 7 Cross section view of mounted BBX-1024XT/R enclosure
18
4.2 Chassis Installation
Chassis Installation Instructions for the following:
•FX-2003-6DS
•FX-2003-12DS
•FX-2003-12XTDS
•FX-2009-12DS
•FX-2009S-12DS
•FX-2017-12ADS
•FX-2017S-12ADS
•ECX-0012
For proper chassis installation do the following
1. Group the incoming wires through the top of the enclosure to prepare it for wiring the
modules. Do not run the wires in-between the modules since it could cause a short
circuit.
Mechanical and Chassis Installation
2. Use a wire tie to group wires for easy identification and neatness.
3. Be sure to connect a solid earth ground (from building system ground / to a cold water
pipe) to the chassis earth ground mounting lug, and to connect the earth ground wire
lugs from the main chassis to the ground screw on the backbox.
4. Mount chassis using the supplied hex nuts.
19
Mechanical and Chassis Installation
4.2.1 Mounting the Chassis into the BBX-1072ADS or BBX-1072ARDS
Enclosure
Mount chassis FX-2017-12ADS or FX-2017S-12ADS into backbox BBX-1072ADS or BBX1072ARDS using the supplied four #6 hex nuts (two at the top and two at the bottom) as
shown below. The transformer chassis is also mounted using four hex nuts.
20
8 #8 hex nuts, 4 for inner
chassis and 4 for the
transformer chassis.
Figure 8 Chassis Installation into BBX-1072ADS or BBX-1072ARDS Module Mounting
Locations
Mechanical and Chassis Installation
4.2.2 Mounting the Chassis into the BB-5008 or BB-5014
The chassis is mounted using the four #6 hex nuts provided. Two across the top portion and
two across the bottom of the chassis. The inner door is mounted using four hex nuts on the left
side and secured with two screws on the right side.
Figure 9 Chassis Installation into backbox BB-5008 and BB-5014
21
Mechanical and Chassis Installation
i
4.2.3 Mounting the Chassis into the UB-1024DS and DOX-1024DS/R Enclosure
The chassis is mounted using the six #8 hex nuts provided. Three across the top and three
across the bottom of the chassis. The inner door mounts over the chassis with two #8 hex
nuts.
22
Figure 10
Note:Leave bottom of box conduit free for batteries.
Chassis Installation into Universal Enclosure UB-1024DS and DOX-1024DS/R
5.0Module Mounting Locations
SCREWS
PROVIDED
M/F HEX SPACER
UDACT-300A
DIALER MODULE
OTHER ADDER
CIRCUIT MODULE
FX-2000
MAIN CHASSIS
OTHER ADDER
CIRCUIT MODULE
PR-300 CITY TIE MODULE
i
i
The FX-2003-6DS/12DS or FX-2017-12ADS Main Chassis come pre-assembled with a main
chassis, display components and boards. Install adder modules of different types as shown in
the diagrams on the following pages.
Module Mounting Locations
Figure 11 Module Mounting Loc ations View #1
Note:To enable communication from the main module to all of the adder modules, it is
necessary to add a continuity jumper on the last adder module in a chain (see the
appropriate module settings section to verify the location of the continuity jumper
on a particular circuit adder module). Only the last circuit adder module should
have a jumper plug on its continuity jumper; all others must be left without a
jumper plug.
Notes: Front plate is not shown. Reserved for PR-300 or UDACT-300A. Other circuit
adder modules may be:
• DM-1008A Detection Circuit Adder Module
• SGM-1004A Signal Circuit Adder Module
• RM-1008A Relay Circuit Adder Module
• ALC-198S Loop Adder Module
• ALC-396S Loop Adder Module
• ALC-H16 Hardwire Loop Controller Module
23
Provision for PR-300 or UDACT-300A
Module Mounting Locations
Figure 12 Module Mounting Locations View #2
24
Display and Adder Modules Mounting Locations
FX-2000 Main Board
123
Slot is reserved for
PR-300 or UDACT300A. If not
required, this slot
can be used to
mount any of the
adder modules.
Mounts in the UB-1024DS backbox and supports three circuit adder modules.
Exterior ViewInterior View
6.2 FX-2017(S)-12DS Mid-size Main Chassis
Mounts in the BBX-1072ADS or BBX-1072ARDS Enclosure, and supports three display
modules and 17 adder modules.
Exterior ViewInterior View
Slot is reserved for PR-300 or UDACT300A. If not required, this slot can be used
to mount any of the adder modules.
25
Display and Adder Modules Mounting Locations
Slot is reserved for PR-300 or UDACT300A. If not required, this slot can be used
to mount any of the adder modules.
Cutout to mount
display module
Cutout to mount
display module
6.3 FX-2009(S)-12DS Large Main Chassis
Mounts and occupies four display positions in BB-5008 or BB-5014 Enclosures, and supports
two display modules and nine adder modules.
Exterior ViewInterior View
Cutout to mount
display module
Cutout to mount
display module
Cutout to mount
display module
231
FX-2000 Main Board
6.4 ECX-0012 Expander Chassis for FX-2009-12DS
Mounts and occupies two display positions in BB-5008 or BB-5014 Enclosures, and supports
two display and 12 adder modules.
Exterior ViewInterior View
56
56
34
4
789
2
1
789101112
26
Display and Adder Modules Mounting Locations
Inside Chassis for mounting adder
modules. Three modules can be
mounted over the main re alarm
board and six above the main re
alarm board stacked three over
three.
Three adder modules
mounted over main re
alarm board.
Main Fire Alarm Board
3
4
5
6
7
8
9
2
1
6.5 Mounting the Boards to the BBX-1024XTChassis
The main board is mounted to the chassis and is shipped out this way. Mounts up to 9 adder modules
and one display module such as RAX-1048TZDS Programmable 48 Zone and Trouble LED display
module, IPS-2424DS Programmable Input Switches module and FDX-008W Fan Damper module.
Figure 13 FX-2003-12XT in a BBX-1024XT Enclosure
27
6.5.1 Adder Modules
CONNECT RIBBON
CABLE FROM P1
TO FIRE ALARM
CONTROL PANEL
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
Each adder module occupies one module slot and mounts inside the following chassis:
•FX-2017-12DS Mid-size Main Chassis and FX-2009-12DS Large Main Chassis
•ECX-0012 Expander Chassis for FX-2009-12DS
Display and Adder Modules Mounting Locations
ALC-198S
Single Intelligent
Analog Loop
Controller Module
SGM-1004A
Four NAC Circuit
Module
6.5.2 Display Modules
Each display module occupies one display position and mounts to the display cutouts on the
following chassis:
•FX-2003-6/FX-2003-12 Compact Main Chassis
•FX-2003-6DS/FX-2003-6DS-16LED/FX-2003-12DS Compact Main Chassis
•FX-2003-12XT/FX-2003-12XTDS Mid-size Main Chassis
•FX-2017-12DS Mid-size Main Chassis
•FX-2009-12DS Large Main Chassis
•ECX-0012 Expander Chassis for FX-2009-12
These modules can also be mounted in the standard BB-5000 cutouts (with brackets), and the
BBX-1000 enclosures (requires RAX-LCD as a driver).
ALC-396S
Dual Intelligent
Analog Loop
Controller Module
RM-1008A
Eight Relay
Circuit Module
ALC-H16
Hardwire Loop
Controller Module
UDACT-300A
Digital Alarm
Communicator
Module
DM-1008A
Eight Initiating
Circuit Module
PR-300
Polarity
Reversal/ City
Tie Module
RAX-1048TZDS
Programmable Zone LED
Annunciator Module
RAX-1048TZDS
Programmable Zone LED
IPS-2424DS
Programmable Input
Switches Module
FDX-008W
Fan Damper Module
Annunciator Module
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
28
7.0Module Settings
MAIN FIRE ALARM BOARD
FIELD WIRING TERMINALS
P9
P8
F1
P 10 P1 1 P12 P1 3
+ BDG- +BAT-
P7
JW1
P4
JW4
P14
P3
JW2
JW3
P5
P6
i
7.1 Main Fire Alarm Modules (MD-764 Part of Main Chassis)
JW1Remove jumper if a PR-300 or UDACT-300A is installed.
JW2 to JW4Jumpers are factory set and should not be changed.
P3Black RS-485 Connector connects to the Adder Loop ALC-198S, ALC-396S
or ALC-H16 if used (Address Loops 3, 4, etc)
P4Connector for PR-300 module or UDACT-300A.
P6Connector for first eight conventional hardwire circuit adder modules (Loop 0).
P5Connector for next eight conventional hardwire circuit adder modules (Loop1).
P7White BDM Connector for factory use only.
P8Power Connector for Adder Modules.
P9RS-232C for printer or CRT monitor.
P10, P11Factory connection to bridge rectifier.
P12, P13Connection to 24VDC battery. Observe correct polarity
Module Settings
P14Connector for display module.
F120 Amp slow blow non-replaceable fuse.
TO CONFIGURE THE FIRE ALARM PANEL USE THE RS-485 CONNECTOR P4 OF THE
LAST ADDER LOOP CONTROLLER MODULE INSTALLED.
Figure 14 Main Fire Alarm Board
Note:To enable communication from the Main Module to all of the Adder Modules, it is
necessary to add a Continuity Jumper on the last Adder Module in a chain (see
the appropriate Module Settings section to verify the location of the Continuity
Jumper on a particular Circuit Adder Module). Only the last circuit adder module
should have a jumper plug on its continuity jumper; all others must be left without
a jumper plug.
29
Module Settings
MAIN FIRE ALARM SUPER BOARD
FIELD WIRING TERMINALS
P9
P8
F1
P 10 P1 1 P12 P1 3
+BDG- +BAT-
P7
JW1
P4
JW4
P14
P3
JW2
JW3
i
7.2 Main Fire Alarm Super Module (MD-757 Part of “S” Version
Main Chassis)
This super main board does not have any addressable loops on it. For an addressable loop,
adder boards are required.
JW1Remove jumper if a PR-300 or UDACT-300A is installed.
JW2 to JW4Jumpers are factory set and should not be changed.
P3Black RS-485 Connector connects to the Adder Loop ALC-198S,
ALC-396S or ALC-H16 if used (Address Loops 3, 4, etc)
P4Connector for PR-300 module or UDACT-300A.
NO HARDWIRE CIRCUIT ADDER MODULES ARE CONNECTED TO
THIS MAIN FIRE ALARM SUPER MODULE
P7White BDM Connector for factory use only.
P8Power Connector for Adder Modules.
P9RS-232C for printer or CRT monitor.
P10, P11Factory connection to bridge rectifier.
P12, P13Connection to 24VDC battery. Observe correct polarity
P14Connector for display module.
F120 Amp slow blow non-replaceable fuse.
TO CONFIGURE THE FIRE ALARM PANEL USE THE RS-485 CONNECTOR P4 OF THE
LAST ADDER LOOP CONTROLLER MODULE INSTALLED.
Figure 15 Main Fire Alarm Super Module (MD-757 Part of “S” Version Main Chassis)
30
Note:To enable communication from the Main Module to all of the Adder Modules, it is
necessary to add a Continuity Jumper on the last Adder Module in a chain (see
the appropriate Module Settings section to verify the location of the Continuity
Jumper on a particular Circuit Adder Module). Only the last circuit adder module
should have a jumper plug on its continuity jumper; all others must be left without
a jumper plug.
7.2.1 DSPL-420 Main Display Module
i
i
P1Cable connects to P14 of main fire alarm module
P2Connection to P1 of any adder display module if used.
Figure 16 DSPL-420 Main Display Module
Module Settings
Note:The main display module comes with slide-in paper labels including both English
and French slide-ins, and laser printer-compatible blanks for zone labelling.
7.2.2 Optional DSPL-420-16TZDS Display Module
P1Cable connects to P14 of main fire alarm module
P2Connection to P1 of any adder display module if used.
Figure 17 DSPL-420-16TZDS Main Display Module with 16 Zone LEDs
Note:The main display module comes with slide-in paper labels including both English
and French slide-ins, and laser printer-compatible blanks for zone labelling.
31
7.3 RAX-1048TZDS Zone Display Module
P
2
P
1
i
P1Cable connects to P2 of previous display module.
P2Cable connects to P1 of next display module.
Module Settings
Figure 18 Zone Display Module (RAX-1048TZDS)
7.4 IPS-2424DS Programmable Input Switches Module
P1Cable connects to P2 of previous display module.
P2Cable connects to P1 of next display module.
Note:The zone display modules comes with laser printer-compatible slide-in paper
labels for zone labelling.
32
7.5 Fan Damper Control Display Module (FDX-008W/WKI)
OFF AUTO ON TROUBLE
PARKING GARAGE #1,
FANS 1, 2 , 3
There are two models of the Fan Damper Control Display modules available. The FDX-008W
provides switch control and LED indication of 8 fan damper zones. The FDX-008WKI provides
switch control of 7 fan damper zones with the eighth zone activated by keyswitch. LED
indication is provided for all 8 fan damper zones on the FDX-008WKI. Both the FDX-008W
and the FDX-008WKI are used in conjunction with a FX-2000 Fire Alarm Control Panel.
Module Settings
Figure 20 Fan Damper Control Display Module (FDX-008W/WKI)
7.5.1 Fan Damper Operation
The FDX-008W Fan Damper Control Display module has eight configurable output circuits,
each with a three position switch. The FDX-008WKI operates in the same manner as the FDX008W except zone 8 is controlled by a remote keyswitch. Each switch has an ON and OFF
position, plus an AUTO position. If the switch is placed in the AUTO position, the white AUTO
LED will illuminate steady and the output will activate as programmed or configured. The
output can be manually turned ON or OFF by placing the switch in the ON or OFF position,
respectively.
Basically each switch can be configured to operate multiple fans or dampers. For each switch,
there are 3 operations provided; outputs to turn ON, same outputs to turn OFF and inputs to
bypass.
An example of the most common use of the FDX-008W or FDX-008WKI Fan Damper Control
Display module is to operate exhaust fans and confirm fan operation (via monitor modules).
See FDX-008W Block Diagram on the next page for a block diagram of fan and monitor set up.
7.5.2 Example
As shown in the figure to the right, Parking Garage #1 has 3
exhaust fans. The three position switch is configured to operate
(to turn ON) fans 1, 2 and 3 in stairwell #1. The switch is set in the
AUTO position. Upon activation (via alarm or some other
programmed trigger) with the switch in AUTO, the 3 fans (1,2, and
3) in stairwell #1 are turned ON automatically. Monitor modules in
the Parking Garage #1 detect that all 3 fans are operating,
therefore the ON LED will illuminate steadily. If one of the fans did
not turn ON (due to malfunction), the ON LED will flash. The TRBL (trouble) LED will illuminate
33
Module Settings
OFF AUTO ON TROUBLE
FX-2000 FIRE
ALARM PANEL
FANS
OUTPUT MODULES
MONITOR MODULES
FDX-008W/WKI FAN/DAMPER CONTROL MODULE
i
i
steady amber based on feedback from the monitor module that one or more of the fans is not
working.
ON LED shows steady for all outputs operating and confirmed.
OFF LED shows steady for all outputs NOT operating and confirmed.
TRBL LED shows steady for one or more outputs NOT operating and confirmed.
Figure 21 FDX-008W Block Diagram of Fan and Monitor Setup
Note:A bypass function always has priority, so that if a circuit is bypassed by moving
the switch manually or by loop bypass (FX-2000 Fire Alarm Panel), no other
action will operate this switch other then again moving the switch manually or by
un-bypassing the loop.
Before mounting the FDX-008WKI module, if a keyswitch is to be connected, wire the
keyswitch to terminals at TS1 as shown in Figure 22 on page 35.
Note:There are also terminals located behind TS1 on the other side of the board for
the convenience of wiring the keyswitch. The last fan damper zone in the bottom
right position of the FDX-008WKI is controlled by the keyswitch.
34
Module Settings
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLEOFF AUTO ON TROUBLE
TS1
P2
TERMINALS AT TS1 ARE WIRED TO A KEYSWITCH.
NOTE: IF FAN DAMPER MODULE IS MOUNTED TO
THE DOOR USE TERMINALS LOCATED AT THE
BACK OF THIS BOARD, BEHIND TS1.
P1
KEYSWITCH
CONTROLLED
CONNECTS TO
PREVIOUS DISPLAY
MODULE P2
Mount the FDX-008W and FDX-008WKI Fan Damper Control Display modules in any position
on the front part of the FX-2000 chassis.
Figure 22 FDX-008WKI Fan Damper Control Display Module
35
7.6 DM-1008A Hardwire Detection Adder Module
P1
P3
P4
FI ELD WIRI NG TERMINALS
P2
JW5
JW4
JW3
JW2
JW1
Data cable to P6 or P5 of
main fire alarm module or to
P12 or P13 of hardwire
loop controller module, or
previous adder module
Powe r connect or t o P8 of
main fire alarm mod ule,
or to P2 of ha rdwire lo op
controller module, or to
previou s adder module
Data connector for
next adder module
Powe r con nect or for
next adder module
i
JW1Install jumper for Class A (Style D) operation of initiating circuits 1 and 2.
JW2Install jumper for Class A (Style D) operation of initiating circuits 3 and 4.
JW3Install jumper for Class A (Style D) operation of initiating circuits 5 and 6.
JW4Install jumper for Class A (Style D) operation of initiating circuits 7 and 8.
Module Settings
JW5
Remove continuity jumper if there are any more adder modules installed.
Note:For Class A (Style D) operation the FX-2000 must be configured as Class A via
the configuration program.
36
7.7 SGM-1004A Hardwire NAC Signal Adder Module
i
JW1Remove continuity jumper if this is not the last adder module installed.
JW2Jumper pins for bell cut or isolators on Zone 1.
JW3Jumper pins for bell cut or isolators on Zone 2.
JW4Jumper pins for bell cut or isolators on Zone 3.
JW5Jumper pins for bell cut or isolators on Zone 4.
JW11For basic operation do not wire these terminals.
Module Settings
J11
ZONE 4
1 2 3
JW5
ZONE 3
JW4
ZONE 2
JW3
ZONE 1
FIELD WIRING TERMINALS
JW2
GREEN SIGNAL LEDs
Figure 24 Hardwire NAC Signal Adder Module (SGM-1004A)
Data cable to P6 or P5 of
main fire alarm module
or to previous adder module
P2
Data connector for
next adder module
JW1
P1
P4
Power connector to P8 of
main fire alarm module,
or to previous adder module
Power connector for
next adder module
P3
7.7.1 SGM-1004A Components
There are four green LEDs on the board, one for each signal zone. The LED will illuminate or
flash following the NAC signal rate sent to its zone. It will be off when the system is normal and
they will illuminate when a NAC signal zone is activated. The LED does not reflect what is
happening on the NAC signal zone, just that it is receiving data to activate that NAC signal
zone.
Note:Jumpers JW2, JW3, JW4 and JW5 are positioned on pins 2 and 3 (right two pins
with board orientation as shown above) from factory.
37
7.7.2 SGM-1004A Operation
!
!
There are three modes of operation for this module. The basic mode of operation does not
involve any bell cut relay or isolators connected to the signal zones. For this case, leave
jumpers JW2, JW3, JW4 and JW5 as they come on pins 2 and 3, and do not make any
connection to terminal block J11. The second mode provides bell cut operation which allows
the silencing of the bells. The third mode is used when isolators are to be connected to the
signal circuits. For further information on bell cut relays or isolators, please refer to the specific
fire alarm panel manual or the isolator instruction manual.
7.7.3 SGM-1004A Jumpers for the Bell Cut Mode
JW2Place jumper over pins 1 and 2 for the ability to remotely silence the bells on
Zone 1.
JW3Place jumper over pins 1 and 2 for the ability to remotely silence the bells on
Zone 2.
JW4Place jumper over pins 1 and 2 for the ability to remotely silence the bells on
Zone 3.
JW5Place jumper over pins 1 and 2 for the ability to remotely silence the bells on
Zone 4.
Module Settings
JW11Wire these terminals to a bell cut relay (for details see QRM-1001 Bell Cut
Module Installation and Operating Instructions, LT-666).
Attention: Discard jumpers on zones that are not configured for bell cut.
7.7.4 SGM-1004A Jumpers for the Isolator Mode
JW2Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 1.
JW3Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 2.
JW4Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 3.
JW5Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 4
JW11Wire these terminals to an alarm relay. These may be tapped if more signal
modules are used in this manner.
Attention: Discard jumpers on zones that are not configured for isolators.
38
7.8 RM-1008A Hardwire Relay Adder Module
P1
P3
P4
FIELD WIRING TERMINALS
P2
JW1
FIELD WIRING TERMINALS
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
I1
I2
I3
I4
I5
I6
I7
I8
P2Data cable to P6 or P5 of main fire alarm module, or to P12 or P13 of Hardwire
loop controller module, or to previous adder module.
P1Data connector for next adder module.
P4Power connector to P8 of main fire alarm module, or to P2 of Hardwire loop
controller or to previous adder module.
P3Power connector for next adder module.
JW1Remove continuity jumper if there are any more adder modules installed. If this
is the last module installed, leave JW1 on.
JP1-JP8Move jumpers from pins 1 and 2 to 2 and 3 to connect relay commons between
two or more relays.
.
Module Settings
Figure 25 Hardwire Relay Adder Module (RM-1008A)
39
7.9 Polarity Reversal and City Tie Module (Model PR-300)
i
Module Settings
+ | - + | - + | -
ALARM
SUPV
TIE
REVERSAL
REVERSAL
CITY
POLARITY
POLARITY
P1 P2
JW4
Mounting hole for
#6-32 screws
Mounting hole for
#6-32 screws
Figure 26 Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
P1Cable connects to P5 on the FX-2000 Main Fire Alarm Board
P2P2 is for connecting the UDACT-300A if both PR-300 and UDACT-300A are
installed on the FX-2000.
JW4If the PR-300 is used this is the last module jumper. JW1 on the main board
should be removed and JW4 on the PR-300 should be set. If both PR-300
and UDACT-300A are installed, then JW1 on the main board and JW4 on
the PR-300 should be removed.
Table 9 PR-300 jumper settings
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered. Please refer to the
Configurator for more information.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail. Please
refer to the Configurator for more information.
Note:Jumper JW1 on the FX-2000 main fire alarm board must be removed if a city tie
module is installed.
40
7.10 UDACT-300A Main Board
There are two jumpers on the UDACT-300A which are used for operation/configuration
purposes. Jumper JW1 is used to reset the default passcode. Jumper JW2 is required for
configuring
connections, pushbutton and LEDs. Table 2 following, provides a description of the user items
on the UDACT-300A.
the UDACT-300A. Refer to Figure 22 below for location of jumpers, cable
SYSTEM NORMAL
13:21 MON 2015-08-03
Module Settings
CONNECT RIBBON
CABLE FROM P1
TO MIRCOM FIRE
ALARM CONTROL
PANEL
P1Ribbon Cable for connecting to P4 of FX-2000 FACP main board.
P2RS-232C/RS-485 Connection for computer configuration.
U18Connector for CFG-300 Configuration Tool
Lamp Test buttonConnector for CFG-300 Configuration Tool
UR1 PotentiometerThis potentiometer is for adjustment of the CFG-300 LCD contrast.
41
Module Settings
i
The following table lists all the LEDs located on the UDACT-300A board and states the
function of each LED.
Table 11 UDACT-300A List of LEDs and their Functions
Cable ConnectorFunction
Relay Line 1Located below Line 1 terminal block. When Line 1 relay is energized, this green
LED will illuminate
Relay Line 2Located below Line 2 terminal block. When Line 2 relay is energized, this green
LED will illuminate.
RS-485Status LED for communication, will flash when RS-485 communication is
active.
Common TroubleSteady amber for any troubles on the Fire Alarm panel or UDACT-300A.
CPU Fail Steady amber for any on board CPU trouble.
Telephone Line 1Telephone status indicator LED; Red when the line is in use, Amber when there
is a line trouble.
Telephone Line 2Telephone status indicator LED; Red when the line is in use, Amber when there
is a line trouble.
Power ONGreen LED is ON steady when power is supplied to the board.
The following table lists the user jumpers available on the UDACT-300A and their functions.
The following table lists the user jumpers available on the UDACT-300A and their functions..
Table 12 UDACT-300A List of Jumpers for Operation and Configuration
Cable
Function
Connector
JW1Normally open. Place jumper here and power down the UDACT-300A by disconnecting
P1 or power down the fire alarm panel (AC and Batteries), then power back to revert to
default passcode. After reset, remove the jumper. Leave normally open.
JW2Normally open to BLOCK remote configuration via modem, PC with a UIMA converter
module or using the LCD and keypad at the UDACT-300A. Place jumper here to
ALLOW any type of configuration. Remove jumper once configuration is complete.
Note:Can be installed with the PR-300 City Tie but not in the same location. If using
this configuration the PR-300 must be installed on the left and it is recommended
that the UDACT-300A be installed in the middle, although it can be installed on
the right if needed.
See the UDACT-300A Installation and Operation Manual (LT-888) for more information.
42
Module Settings
7.11 ALC-198S Single Intelligent Analog Loop Controller Module
The ALC-198S Single Intelligent Analog Loop Controller module provides a single
addressable loop. It may be mounted over the main chassis of the FX-2000 Fire Alarm Panel
or on any chassis which supports adder boards. Refer to Module Mounting Locations View#2 on page 24. The module is mounted using four #6 screws and (if necessary) four 1 1/2"
spacers.
PowerThe power is supplied to the board via cable from the main chassis board
or from the previous loop controller module into the P1 Power IN connector.
The P2 Power OUT connector is connected to the next loop controller
module or other adder module. Two power cables are supplied with the
module.
RS-485The RS-485 cable comes attached at P3 and is connected to the main
chassis board or from the previous loop controller module or other adder
board. The RS-485 OUT at P4 is connected to the next loop controller
module if used or left without connection.
DIP switchesThe dip switches are used to set the address of the board. The address is
binary, with the SW-1 switch as the lowest significant digit and OFF being
active. For example an address of two is SW-1 ON, SW-2 OFF, and all the
other dip switches SW-3 to SW-8 ON. Refer to Appendix E: DIP SwitchSettings Summary on page 96 for more information.
Loop 1This is the addressable loop for all initiating devices. Wire the loop as
shown in Field Wiring on page 49.
JumpersA jumper is provided at JW2 for normal operation. To reset the board the
jumper is left at JW2 and the pins at position JW1 are shorted momentarily.
BDM PortThis connection is for factory use only.
43
Module Settings
1
8
RS-485
CABLE
RS-485
ADDRESS
DIP
SWITCH
BDM
PORT
JW2 - A
JUMPER IS
PLACED HERE
TO ENABLE
WATCHDOG
TIMER. THIS
IS JUMPER=S
NORMAL
LOCATION.
JW1 - JUMPER IS
PLACED HERE TO
RESET HARDWARE
POWER
CABLE
(OUT)
POWER
CABLE
(IN)
LOOP A
IN
OUT
+ - + -
B
A
DIP SWITCHES ARE FOR
THIS BOARD=S ADDRESS.
SW-1 IS THE LEAST
SIGNIFICANT DIGIT (BINARY).
ACTIVE POSITION IS OFF.
JW3 - JUMPER
FROM JW2 IS
PLACED HERE TO
BYPASS
WATCHDOG FOR
FACTORY
DOWNLOADING
USING BDM
P3
P4
P5
P1
P2
SHIELD
Figure 28 ALC-198S Single Intelligent Analog Loop Controller Module
Mount the ALC-198S Single Intelligent Analog Loop Controller module as described in the
section Display and Adder Modules Mounting Locations on page 25. The module may be
mounted over the main chassis board or in any position that an adder module is mounted.
44
Module Settings
7.12 ALC-396S Dual Intelligent Analog Loop Controller Module
The ALC-396S Dual Intelligent Analog Loop Controller module provides a two addressable
loops. It may be mounted over the main chassis of the FX-2000 Fire Alarm Panel or on any
chassis that supports adder boards. Refer to page Module Mounting Locations View #2 onpage 24 for mounting applications. The module is mounted using four #6 screws and (if
necessary) four 1 1/2" spacers.
PowerThe power is supplied to the board via cable from the main chassis board
or from the previous loop controller module into the P1 power in connector.
Connect the P2 power out connector to the next loop controller module or
other adder module. Two power cables are supplied with the module.
RS-485The RS-485 cable comes attached at P3 and is either connected to the
main chassis board or connected from the previous loop controller module
or other adder board. If the next loop controller module is used, connect the
RS-485 out at P4 to the next loop controller module; if it is not used, leave
without connection.
DIP switchesUse the DIP switches to set the binary address of the board. SW-1 is the
lowest significant digit and OFF is active. For example, an address of two
would be created by turning SW-1 on, SW-2 off and DIP switches SW-3 to
SW-8 on. Refer to Appendix E: DIP Switch Settings Summary on page 96
for DIP switch settings.
Loop 1This is the addressable loop for all initiating devices. Wire the loop as
shown in Single Loop Terminal Connections - Class B on page 54 or Single
Loop Terminal Connections - Style 7 on page 55 and Single Loop Terminal
Connections - Style 6 on page 56.
Loop 2This is the addressable loop for all initiating devices. Wire the loop as
shown in Single Loop Terminal Connections - Class B on page 54 or Single
Loop Terminal Connections - Style 7 on page 55 and Single Loop Terminal
Connections - Style 6 on page 56.
JumpersA jumper is provided at JW2 for normal operation. To reset the board, leave
the jumper at JW2 and momentarily short the pins at position JW1.
BDM PortThis connection is for factory use only.
45
Module Settings
1
8
RS-485
CABLE
RS-485
ADDRESS
DIP
SWITCH
BDM
PORT
JW2 - THE
JUMPER IS
KEPT HERE
FOR
NORMAL
OPERATION
JW1 - PINS ARE
SHORTED
MOMENTARILY TO
RESET
HARDWARE
JW3 - JUMPER
FROM JW2 IS
PLACED HERE TO
BYPASS
WATCHDOG FOR
FACTORY
DOWNLOADING
USING BDM
POWER
CABLE
POWER
CABLE
LOOP A
DIP SWITCHES ARE FOR
THIS BOARD=S ADDRESS.
SW-1 IS THE LEAST
SIGNIFICANT DIGIT (BINARY).
ACTIVE POSITION IS OFF.
+ - + -
B
A
P3
P2
P1
P5
P4
LOOP B
+ - + -
B
A
SHIELD
i
Figure 29 ALC-396S Dual Intelligent Analog Loop Controller Module
Mount the ALC-396S Dual Intelligent Analog Loop Controller module as shown in Module
Mounting Locations View #2 on page 24. The module may be mounted over the main chassis
board or in any position that an adder module is mounted.
46
Note:There are two addressable loops present on this board (ALC-396S) that are
wired in the same manner as shown in the wiring diagrams beginning with MainFire Alarm Module Terminal Connections on page 49. Although these drawings
show only Loop 1, Loop 2 is wired in the same way as Loop 1 is. Note that Loop
1 and Loop 2 do not have to be wired in the same class, such as Class A or
Class B or Style 7. Therefore Loop 1 may be wired as Class A and Loop 2 may
be wired as Class B.
7.13 ALC-H16 Hardwire Loop Controller Module
The ALC-H16 Hardwire Loop Controller module provides an interface in order to add 16
conventional adder boards. This board may be mounted over the main chassis of the FX-2000
Fire Alarm Panel or on any chassis which supports adder boards. Refer to page Module MountingLocations View #2 on page 24 for mounting applications. Mount the module using four #6 screws
and (if necessary) four 1 1/2" spacers.
PowerThe power is supplied to the board via cable from the main chassis board
or from the previous loop controller module into the P1 power in connector.
Connect the P2 power out connector to the next loop controller module or
other adder module. Two power cables are supplied with the module.
RS-485The RS-485 cable comes attached at P3 and is either connected to the
main chassis board or connected from the previous loop controller module
or other adder board. If the next loop controller module is used, connect the
RS-485 out at P4 to the next loop controller module; if it is not used, leave
without connection.
JumpersA jumper is provided at JW2 for normal operation. To reset the board, leave
the jumper at JW2 and momentarily short the pins at position JW1.
BDM PortThis connection is for factory use only.
P13 and P12
Connectors
Connect the P13 connector (via ribbon cable included with this module) to
the first module of the first group of eight conventional adder modules.
Connect the P12 connector (via ribbon cable included with this module) to
the first module of the second group of eight conventional adder modules
Module Settings
47
Module Settings
A
.
P12 IS USED TO CONNECT SECOND GROUP OF 8 ADDER MODULES
P13 IS USED TO CONNECT FIRST GROUP OF 8 ADDER MODULES
RS-485
P12
CAB LE
DDRESS
DIP
SWI TCH
RS- 4 8 5
P13
P4
ON
1
8
D I P SWI TCH ES ARE FO R
THIS BOARD= S ADDRESS.
SW- 1 IS TH E LEA ST
SIGNIFICANT DIGIT (BINARY).
ACTIVE POSITION IS OFF.
JW3 - JUM PER
FROM JW2 IS
PLACED HERE TO
BYPASS
WATCH DOG FOR
FA C T O R Y
DOWNLOADING
USING BDM
P3
P2
POWER
CAB LE
(OUT)
POWER
CAB LE
(IN)
BDM PORT
JW3
JW1
JW2
JW2 - THE
JUM PER IS
KEPT HERE
FOR
NORMAL
OPERATION
P1
JW1 - PINS ARE
SH ORT ED
MOMENTARILY TO
RESET
H A RD W A RE
Figure 30 ALC-H16 Hardwire Loop Controller Module
Mount the ALC-H16 Hardwire Loop Controller module as shown on Module Mounting
Locations View #2 on page 24 and ECX-0012 Expander Chassis for FX-2009-12DS on
page 26. The module may be mounted over the main chassis board or in any position that an
adder module is mounted.
There is no wiring at the ALC-H16 Hardwire Loop Controller module, but there is wiring at the
16 standard conventional adder modules. For conventional hardwire circuit wiring refer to
Hardwire Detection Module (DM-1008A) Terminal Connections on page 57, Hardwire Signal
Module Terminal Connections on page 58, and Hardwire Relay Module Terminal
Connections on page 59 for the specific module you are wiring.
48
8.0Field Wiring
!
i
COM
-
RS485
NO
NC
COM
TROUBLE
NO
NC
COM
SIG GND
or COM(-)
NO
NC
ALARM
USE TWISTED SHIELDED PAIR.
22 AWG UP TO 2000 FT.
20 AWG UP TO 4000 FT.
SUPV.
+
S
RS-485 INTERFACE TO
ANNUNCIATORS AND
OTHER DEVICES
(POWER LIMITED)
NOT USED
MUST BE
CONNECTED TO A
LISTED POWER
LIMITED SOURCE
OF SUPPLY
COMMON TROUBLE
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
AUXILIARY COMMON
SUPERVISORY
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
AUXILIARY COMMON
ALARM CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
S
8.1 Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in Figure 31 below. See Wiring Tables and Information on
page 63. See Appendix A: Specifications on page 79 and Appendix B: Compatible Devices onpage 85 for compatible devices..
Attention: Do not exceed power supply ratings:
Main Chassis FX-2003-6DS and FX-2003-6DS-16LED total current for NAC
circuits is 5A max.
Main Chassis FX-2003-12DS, FX-2003-12XTDS, FX-2017-12ADS or FX-
2017S-12ADS total current for NAC circuits is 10A max.
Main Chassis FX-2009-12DS and FX-2009S-12DS: total current for NAC
circuits is 10A max.
Notes: The terminal blocks are "depluggable" for ease of wiring.
Field Wiring
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
8.1.1 Main Fire Alarm Module Terminal Connections.
Figure 31 Main Fire Alarm Module Terminal Connections
49
BELL, HORN, OR
STROBE
Legend: See Appendix A for compatible devices.
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCUIT 1
(POWER
LIMITED)
IND1+ (Z)
STYLE Z
(CLASS A)
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
INDICATION
CIRCUIT 2
(POWER
LIMITED)
INDICATING CIRCUITS 3 & 4
ARE NOT SHOWN
STYLE Y
(CLASS B)
WIRING
SUPERVISED INDICATING CIRCUIT #1
ANALOG
LOOP 2
CONNECTIONS
(LOOP 0 AND
LOOP1 ARE
INTERNAL
ADDRESSES
FOR FIRST 8
CARDS AND
SECOND 8
CARDS
RESPECTIVELY
+
4-WIRE
POWER
SUPPLY
-
+
AUX.
POWER
-
TRB
RTI
INTERFACE
TRL
ANALOG LOOP FIELD WIRING
(CLASS A OR B)
SEE ANALOG LOOP WIRING SECTION
CONNECTION TO MIRCOM RTI
REMOTE TROUBLE INDICATOR
(SEE RTI INSTALLATION
INSTRUCTION) BLK TOTRB+ BLU
TO TRL-RED & WHT TO AUX.
POWER COM+
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
2
3
41
6
5
+
-
+
-
TO
INITIATING
CIRCUIT
+
-
+
-
POWER
+
-
DETECTION
4-WIRE
DETECTION
DEVICE
AUXILIARY POWER
FOR REMOTE ANNUNCIATORS
24 VDC UNFILTERED
1.7 AMPS MAXIMUM
RTI
BLK
BLU
RED & WHT
LOOP 2
B
A
+
+
-
+
-
-
+
+
+
-
-
i
i
Field Wiring
NAC
NAC
Figure 32 Main Fire Alarm Module Terminal Connections (continued)
Notes: The terminal blocks are "depluggable" for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
50
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Indicating (NAC) circuits are fully supervised and rated for 24 VDC unfiltered
1.7A max. Use wire size as stated in Table 15 NAC Circuit Wiring Table onpage 63.
8.2 Analog Loop Wiring
i
8.2.1 Loop Terminal Connections - Class B
Field Wiring
FX-2000
MAIN FIRE ALARM BOARD
ANALOG
LOOP
CONNECTIONS
COM ( - )
LOOP 2
B
A
+
+
-
NAC
INDICATING
CI RCUI TS
4-WIRE
RESET TA B L E
SUPPLY
+
-
IND1 + (Y/Z)
IND1 + (Z)
IND1 - (Z)
IND1 - (Y/Z)
S
S
TWO WIRES
S
SO
F
M
C
M
2 Pair
s
C
s
Conventional Heat Sensors
and Manual Pull Stations
C
C
s
s
TWO WIRES
H
F
H
H
S
F
LEGEND
Addr essabl e Smo ke Detect or
S
wi th St andar d An alog Base
Addr essable Thermal Sensor
H
wi th St andar d An alog Base
Convent ional Smo ke Sensor
C
s
Addressable Manual
F
Pull Station
End -Of -Li n e- Resist o r
Combination
Horn /St robe
Addressable
Monit or Module
M
Addressable Supvr.
SO
Out pu t M odu le
Figure 33 Loop Terminal Connections - Class B
Notes: Terminal blocks are “depluggable” for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Loop wiring: maximum loop resistance is 40 ohms total. These lines are fully
supervised.
Observe in and out polarity when using module and base isolators.
51
8.2.2 Loop Terminal Connections - Style 7
i
Field Wiring
TWO WIRES
FX-2000
MAIN FIRE ALARM BOARD
COM(-)
+
LOOP 2
ANALOG
LOOP
CONNECTIONS
4-WIRE
RESETTABLE
SUPPLY
AUXILIARY
POWER
SUPPLY
B
-
A
+
-
+
+
-
I
F
I
ADDRESSABLE
SMOKE DETECTOR
WITH ISOLATOR BASE
S
I
I
F
I
TWO WIRES
TWO WIRES
I
Conventional Heat Sensors
and Manual Pull Stations
M
C
I
s
I
H
ADDRESSABLE
THERMAL
SENSOR
WITH
ISOLATOR
BASE
STYLE 7: For Style 7 operation use isolator
bases for the detectors and use isolator modules
(front and back as shown in this diagram) for the
addressable pull stations, monitor modules, and
control modules
LEGEND
Addressable Smoke Detector
S
with Isolator Base
Addressable Thermal Sensor
H
with Isolator Base
52
Conventional Smoke Sensor
C
s
Addressable Manual Pull Station
F
Fault Isolator Module
I
Addressable Monitor Module
M
Figure 34 Loop Terminal Connections - Style 7
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Isolators need to be close nipple connected to the device being protected.
Loop wiring: maximum loop resistance is 40 ohms total. These lines are fully
supervised.
8.2.3 Loop Terminal Connections - Style 6 (Formerly Class A)
F
4-WIRE
RESETTABLE
SUPPLY
+
-
AUXILIARY
POWER
SUPPLY
+
-
ADDRESSABLE
THERMAL SENSOR
ADDRESSABLE
SMOKE DETECTORS
FX-2000
ANALOG
LOOP
CONNECTIONS
F
LEGEND
Addressable Smoke Detector
Addressable Thermal Sensor
Addressable Manual Pull Station
F
Addressable Monitor Module
RO
TWO WIRES
TWO WIRES
B
A
+
-
+
-
LOOP 2
S
H
S
S
H
Addressable
Relay Output Module
M
M
M
RO
COM(-)
MAIN FIRE ALARM BOARD
Conventional 4-Wire Smoke
Detectors, Heat Sensors
and Manual Pull Stations
Field Wiring
Figure 35 Loop Terminal Connections - Style 6 (Formerly Class A)
53
8.2.4 Single Loop Terminal Connections - Class B
Conventional Heat Sensors
and Manual Pull Stations
2 Pair
4-WIRE
RESETTABLE
SUPPLY
+
-
IND1 + (Y/Z)
IND1 + (Z)
IND1 - (Z)
IND1 - (Y/Z)
F
LEGEND
Addressable Smoke Sensor
with Standard Analog Base
Addressable Thermal Sensor
with Standard Analog Base
Conventional Smoke
Sensor
Addressable Manual
Pull Station
Combination
Horn/Strobe
Addressable
Monitor Module
Addressable Supvr.
Output Module
End-Of-Line-Resistor
TWO WIRES
TWO WIRES
S
H
S
C
s
C
s
C
s
F
F
HH
S
S
H
C
s
C
s
F
M
SO
M
TWO WIRES
M
SO
B
A
ANALOG
LOOP A
+
-
+
-
SHIELD
FX-2000
MAIN FIRE ALARM BOARD
ALC-198S SINGLE
LOOP MODULE
i
Field Wiring
54
Figure 36 Single Loop Terminal Connections - Class B
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Loop wiring: maximum loop resistance is 40 ohms total. These lines are fully
supervised.
8.2.5 Single Loop Terminal Connections - Style 7
LEGEND
Ad dr essabl e Smo ke
Sensor with Isolator Base
Addressable Thermal
Sensor with Isolator Base
Conventional Smoke Sensor
Addressable Manual Pull Station
Fault Isolator Module
Conventional Heat Sensors
and Manu al Pull St ati on s
F
C
s
F
ADDRESSABLE
THERMAL SENSOR
WITH ISOLATOR
BASE
ADDRESSABLE
SMOKE DETECTOR
WITH ISOLATOR
BASE
F
C
s
Addressable Monit or Module
H
S
S
H
TWO WIRES
TWO WIRES
TWO WIRES
TWO WIRES
I
I
I
I
I
I
I
I
M
M
I
B
A
ANALOG
LOOP A
+
-
+
-
ALC-198S SINGLE
LOOP MODULE
STYLE 7: For Style 7 operation use isolator
bases for the detectors and use isolator modules
(front and back as shown in this diagram) for the
addressable pull stations, monitor modules, and
control modules
i
Field Wiring
Figure 37 Single Loop Terminal Connections - Style 7
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Isolators need to be close nipple connected to the device being protected.
Loop wiring: maximum loop resistance is 40 ohms total. These lines are fully
supervised.
55
8.2.6 Single Loop Terminal Connections - Style 6
F
ADDRESSABLE
THERMAL SENSOR
ADDRESSABLE
SMOKE DETECTORS
F
LEGEND
Addr essabl e Smo ke Sensor
Addressable Thermal Sensor
Addressable Manual Pull Station
F
Addressable Monitor Module
TWO WIRES
S
S
H
Addressable Relay Output Module
S
H
M
M
RO
M
RO
B
A
+
-
+
-
ANALOG
LOOP A
ALC-198S SINGLE
LOOP MODULE
Conventional 4-Wire Smoke
Detectors, Heat Sensors
and Manual Pull Stations
i
Field Wiring
Figure 38 Single Loop Terminal Connections - Style 6
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Loop wiring: maximum loop resistance is 40 ohms total. These lines are fully
supervised.
SUPERVISED INITIATING CIRCUIT #3
( AL ARM ZO NE) SEE STYL E D N OTE ( PO WER LI M IT ED)
INI5+
INI5-
INI6+
INI6-
INI7+
INI7-
INI8+
INI8-
STY LE B/ D
INI4
STY LE B/ D
INI3
Style D Note: Initiating circuits in a series
FX-2000 must be either all Style B (Class B)
or Style D (Class A). If Style D is selected, the
number of circuits is cut in half.
i
Wire devices to terminals as shown in Figure 39. For further wiring information 8.8 Wiring
Tables and Information. For specifications 12.0 Appendix A: Specifications. For compatible
devices 13.0 Appendix B: Compatible Devices. Jumpers are required for Class A operation.
Notes: Terminal blocks are “depluggable” for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Initiating circuits are fully supervised and rated for 22 VDC, 3 mA standby, 5 mV
ripple, 50 mA max alarm. They may be configured as required. The alarm
threshold is 21 mA. Maximum loop resistance is 100 ohms, 50 ohms per side.
All conventional hardwire initiating circuits are Compatibility ID "A".
57
8.3 NAC Signal Module (SGM-1004A) Terminal Connections
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCU IT 1
(POWER
LIMI TED)
IND1+ (Z)
STY LE Z
( CLA SS A)
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
INDICATION
CIRCU IT 2
(POWER
LIMI TED)
STY LE Y
( CLA SS B)
WIRING
SUPERVISED INDICATING CIRCUIT #1
IND4+ (Z)
IND4- (Z)
IND4- (Y/Z)
SUPERVISED INDICATING CIRCUIT #4
INDICATION
CIRCU IT 3
(POWER
LIMI TED)
IND3+ (Z)
STY LE Z
( CLA SS A)
WIRING
IND3- (Y/Z)
IND3+ (Y/Z)
IND4+ (Y/Z)
IND3- (Z)
INDICATION
CIRCU IT 4
(POWER
LIMI TED)
STY LE Y
( CLA SS B)
WIRING
SUPERVISED INDICATING CIRCUIT #3
Legend: See Appendix B for compatible devices.
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300
MANUFACTURED BY MIRCOM
i
Wire devices to terminals as shown in Figure 40. For further wiring information 8.8 Wiring
Tables and Information. For specifications 12.0 Appendix A: Specifications. For compatible
devices 13.0 Appendix B: Compatible Devices.
Field Wiring
58
Figure 40 Hardwire Signal Module Terminal Connections
Notes: The terminal blocks are “depluggable” for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
SGM-1004A NAC circuits are fully supervised and rated for 24 VDC unfiltered
1.7A max. They must use wire size as stated in the wiring tables on page 63.
Notes: All relay circuits are power limited and must use type FPL, FPLR, or FPLP power
limited cable.
All relay circuits must be connected to a listed power limited source of supply.
Attention: Do not connect 120 VAC directly to these relays.
59
8.5 Polarity Reversal and City Tie Module (PR-300) Wiring
i
Wire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 42 below.
Power Limited cable type FPL, FPLR or FPLP must be used.
For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model#24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown.
For use in Canada, the Protective Device is not required but still recommended.
CONFIRMS TO NEMA STANDARDSB3-1969 INTENDED FOR
CONNECTION TO POLARITY
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS
+
Field Wiring
2
S
1
2
2
S
1
2
-
POWER LIMITED CABLE TYPE
FPL, FPLR or FPLP MUST BE
USED FROM PR-300 TO
S
S
DIN RAIL CONNECTION
TO EARTH GROUND
PROTECTORS.
Figure 42 Polarity reversal and city tie module terminal connection
Notes: Either the PR-300's city tie or polarity reversal interface may be used, but not
both. The city tie interface is not power limited. Plug PR-300 ribbon cable (P1)
into connector (P4) of the FX-2000 main fire alarm module. Cut jumper (JW1) on
the PR-300 module in order to transmit a trouble condition to the monitoring
station. Remove jumper plug from jumper JW4 on the main fire alarm module.
The polarity reversal interface is power limited and must use type FPL, FPLR, or
FPLP power limited cable. For polarity reversal operation, short the city tie
connection.
60
8.6 UDACT-300A Main Board Terminal Connections
i
Wire the two telephone lines to RJ31X Connector terminals as shown in Figure 43. The
UDACT-300A terminals are located on the top left hand corner of the board. If using a cellular
or wireless service, use the Line 2 interface connection only.
Field Wiring
1
23
76
8
BROWN
TTRR
Line 2 is Wired as shown for Line 1
TTRR
RED
GREEN
GREY
RESRESC.O.C.O.
LINE-1LINE-2
RJ31X
4
5
TIP
RING
Public switch
Telephone company
wiring
TIP
RING
premise telephone
IF permitted
UDACT-300A
Figure 43 Telephone Line Wiring Diagram
Note:Most Authorities Having Jurisdiction (AHJ) do not allow the connection of
premise telephones. see specifications for more information.
61
8.7 Power Supply Connections
P13
CONNECT GREEN
EARTH GROUND WIRE
TO MAIN MODULE PCB
MOUNTING SCREW.
N
G
GREEN
TO 24 VDC
BATTERY
BLACK
P11
P10
P12
+
BAT
RED
TO DEDICATED
BRANCH CIRCUIT
L
L
20 Amp
FAST ACTING FUSE
FUSE
!
The power supply is part of the main chassis. The ratings are outlined in Table 13.
Table 13 Power Supply Ratings
Field Wiring
ModelElectrical Input
FX-2003-6DS & FX-20036DS-16LED Main Chassis
FX-2003-12DS, FX-200312XTDS,FX-2017-12ADS &
FX-2017S-12ADS Main
Chassis
FX-2009-12DS & FX-2009S12DS Main Chassis
Using proper wire gauge, connect as shown in Figure 44. For specifications see 12.0
Appendix A: Specifications.
Ratings
120 VAC, 60 Hz, 2A /
240VAC, 50hz, 1A
120 VAC, 60 Hz, 2A /
240VAC, 50hz, 1A
120 VAC, 60 Hz, 2A /
240VAC, 50hz, 1A
Power Supply
Total Current
6 amps maximum
12 amps maximum
12 amps maximum
Battery Fuse on Main
Module
Replace with 20 Amp, 1-1/4"
Fuse
Replace with 20 Amp, 1-1/4"
Fuse
Replace with 20 Amp, 1-1/4"
Fuse
62
Figure 44 Power Supply Connections
Caution:To prevent sparking, connect batteries after the system’s main A.C. power is
turned ON. Do not exceed power supply ratings.
8.8 Wiring Tables and Information
i
i
Table 14 Wiring Table for Initiating Circuits
Wire GaugeMaximum Wiring Run to Last Device (ELR)
(AWG)ft.m
222990910
2047601450
1875602300
16120003600
14190005800
12304009200
Note:Maximum loop resistance should not exceed 100 Ohms.
Field Wiring
Main board NAC circuits are rated for 1.7 amps each. The SGM-1004A NAC circuits are rated
for 1.7 amps each.
Table 15 NAC Circuit Wiring Table
TOTAL
SIGNAL
LOAD
AmperesftmftmftmftmOhms
0.06235071637501143600018298500259130
0.121180360185056730009154250129615
0.30470143750229120036619005796
0.60235713751146001838502593
0.9015647250764001225701742
1.201183618556300914251291.5
1.5094291504624073343105 1.2
1.707824125382006128587 1.0
MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP
RESISTANCE
18AWG16AWG14AWG12AWG
Note:Maximum voltage drop should not exceed 1.8 volts.
63
Field Wiring
i
Table 16 Analog Loop Wiring
Wire Gaug eMaximum Wiring Run to Last Device (ELR)
(AWG)ftm
183132955
1649801518
1479712429
1210,0003049
Notes: Line capacitance shall not exceed 0.5 mF
Inductance shall not exceed 1 mH.
Resistance shall not exceed 40 ohms.
Power WiringUse Table 15 NAC Circuit Wiring Table on the previous page to see
the wiring information for the remote annunciator being used.
RS-485 WiringSee the wiring information for the remote annunciator being used.
4-Wire Smoke
Wiring
Shield for Analog
Loop Wiring
The maximum allowable current is 0.2 amperes. The maximum
allowed voltage drop is 1 volt. Refer to Table 15 NAC Circuit Wiring
Table on the previous page.
Only twisted pair is recommended, but if shielded twisted pair is used,
wire shield at the start and the end of the loop to the terminals marked
Shield at the loop adder board.
64
9.0System Checkout
i
9.1 Before Turning the Power On
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe).
Note:When using Class A and isolators on an addressable loop, configure system as
Class B, wire loop as Class A, except do not connect the last device back to the
panel. Do a system checkout. Then connect the return of the Class A circuit and
configure as Class A.
System Checkout
9.2 Power-Up Procedure
1. After completing the above procedures, power up the panel (AC only). The green AC On
LED and the Common Trouble LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the Battery
Trouble LED should illuminate, the trouble buzzer should sound intermittently, and the
Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity: the red wire is positive (+) and the
black wire is negative (-). All indicators should extinguish except for the AC On LED and
the LCD should show a normal status condition.
4. Auto-Configure or PC Configure the fire alarm control panel as described in the
configurator software.
9.3 Troubleshooting
Table 17 Troubleshooting
MessageDescription
Circuit TroubleNormally when a circuit trouble occurs, its designated trouble indicator
will be illuminated, as well as the Common Trouble indicator and
Trouble buzzer. To correct the fault, check for open wiring on that
particular circuit loop or see if the circuit disconnect switch is in the ON
or CLOSED position. Note: disconnecting a circuit will cause a system
trouble (off-normal position).
Ground FaultThe FX-2000 panel has a Ground Fault Detector. To correct the fault,
check for any external wiring touching the chassis or other earth ground
connection.
Battery TroubleCheck for the presence of batteries and their condition. Low voltage
(below 20.4V) will cause a battery trouble. If battery trouble condition
persists, replace the batteries as soon as possible.
65
10.0Indicators and Controls
Refer to Figure 45 and Figure 46 below for LED indicators, control buttons, and switch
locations associated with the main control displays.
Indicators and Controls
Indicators for AC On,
CPU Fault, and Ground
Fault
ACK controls and
indicators for Alarm,
Supervisory, Trouble,
and BLDG (Monitor)
LCD Display - four lines,
20 characters per line
ALM
ACK
SIGNAL
SILENCE
SUP
ACK
LAMP
TEST
TBL
ACK
SYSTEM
RESET
Controls & Indicators for Signal
Silence, Lamp Test, System
Reset, Fire Drill, General Alarm
(Two Stage only), General Alarm
Cancel (Two Stage only)
C u r s o r b u t t o n s a n d b u t t o n s f o r
M (MENU), X (CANCEL), ? (INFO)
and ENTER
BLDG
ACK
FIRE
DRILL
GENERAL
ALARM
GENERAL
ALARM
CANCEL
Two configurable
switches & amber LEDs
66
Figure 45 DSPL-420 Main Display Indicators and Controls
Indicators and Controls
16 congurable
bi-coloured zone
indicators and 16
trouble indicators
Queue controls and
indicators for Alarm,
Supervisory,
Trouble and Monitor
AC On
Indicator
CPU Fault
Indicator
Ground Fault
Indicator
LCD Display
4 lines
20 characters
Menu
Cancel
Info
Cursor buttons
and Enter button
Control and Indicators for Signal
Silence, General Alarm, General Alarm
Cancel, Fire Drill, System Reset, Lamp
Test and Spare programmable Buttons
ACK
GENERAL
ALARM
CANCEL
ACK
ACKACK
LAMP
TEST
i
Refer to Figure 46 below for main display model DSPL-420-16TZDS. This display is similar to
the DSPL-420 shown in Figure 45 except for the extra 16 configurable bi-coloured LED zone
indicators and 16 trouble LED indicators.
Figure 46 DSPL-420-16TZDS Main Display Indicators and Controls
LED indicators are amber (trouble or supervisory), red (alarm), or green (AC On), and may
illuminate continuously (steady) or at one of two flash rates:
Fast Flash120 flashes per minute, 50% duty cycle
Trouble Flash20 flashes per minute, 50% duty cycle
Note:The General Alarm LED and pushbutton, and the General Alarm Cancel LED
10.1 Paper Labels for Buttons and Indicators
Buttons and indicators are supplied with paper labels. These labels slide into the plastic label
templates on the face of the panel. Paper labels allow for easy English / French selection and
custom-printed zone information.
and pushbutton, are active only on a system configured for “Two Stage.”
67
Indicators and Controls
10.2 Common Indicators
Table 18 Common Indicators
IndicatorsDescription
BuzzerThe Buzzer is activated by any of the following
Fire Alarm - Steady
Supervisory Alarm - Fast Rate
Trouble - Trouble Rate
Monitor - Configurable to sound at Trouble Rate
If the Buzzer is turned on in response to a Non-Latching Trouble or
Supervisory, it will be turned off if the condition causing it goes away
and there is no other reason for it to be on.
AC On LEDThe AC On Indicator is activated steady green while the main AC power
is within acceptable levels. It is turned off when the level falls below the
power-fail threshold and the panel is switched to standby (battery)
power.
Alarm ACK LEDThe Common Alarm LED flashes red whenever the Panel is in Alarm.
An alarm results from any alarm on any point or input programmed as
Alarm or activation of the manual red General Alarm Button (if the Panel
is set for Two Stage Operation). The Alarm ACK LED will go steady,
once all alarms in the queue have been reviewed using the Alarm ACK
button. Since all Alarms are latched until the Panel is reset, the
Common Alarm LED will remain on until then.
Supervisory ACK LEDThe Common Supv. (Supervisory) LED flashes amber at the Fast Flash
Rate when there is a Supervisory Alarm in the Panel, as the result of
any Latching or Non-Latching Supervisory Circuit. The LED turns off if
all Non-Latching Supervisory Circuits are restored and there are no
Latching Supervisory Circuits active. The Supv. ACK LED will go
steady, once all supervisory alarms in the supervisory queue have been
reviewed using the Supv. ACK button. Latching Supervisory Alarms
remain active until the Panel is reset.
Trouble ACK LEDThe Common Trouble LED flashes amber at the Trouble Flash Rate
when there is any Trouble condition being detected on the panel. It is
turned off when all Non-Latching Troubles are cleared. The Trouble
ACK LED will go steady, once all troubles in the trouble queue have
been reviewed using the Trouble ACK button.
BLDG (Monitor) ACK LEDThe BLDG Trouble Indicator flashes amber at the Trouble Flash Rate
when there is any Monitor condition being detected on the panel. It is
turned off when all Monitors are cleared.
CPU Fault LEDThe CPU Fault Indicator is flashed yellow at the Trouble Flash Rate if
the CPU is faulty.
Fire Drill LEDThe Fire Drill Indicator turns on steady amber while Fire Drill is active.
68
Indicators and Controls
T able 18 Common Indicators
IndicatorsDescription
General Alarm CancelIf the Panel is configured as Two Stage, the General Alarm Cancel
Indicator flashes amber at the Fast Flash Rate while the Auto General
Alarm Timer is timing out. It turns on steady amber when that Timer is
cancelled by activating the General Alarm Cancel or Signal Silence
buttons. If the Auto General Alarm Timer times-out and puts the Panel
into General Alarm, the Indicator is turned off.
General Alarm LEDIn Two Stage Operation only, the General Alarm Indicator is activated
steady red when General Alarm is activated due to the red General
Alarm button being pushed, a General Alarm Initiating Circuit being
activated, or the Auto General Alarm Timer timing out. Once the
General Alarm Indicator has been turned on it will stay active until the
Panel is reset.
Signal Silence LEDThe Signal Silence indicator is flashed amber, at the trouble rate when
Indication Circuits are Silenced either by the Signal Silence button, or
by the Auto Signal Silence Timer. It is turned off when the Signals are
re-sounded by a subsequent Alarm.
Ground Fault LEDThe Ground Fault Indicator flashes amber at the Trouble Rate when the
Ground Fault Detector detects a Ground Fault on any field wiring. It
turns off immediately when the Ground Fault is cleared.
10.3 Common Controls
10.3.1 LCD Display
The display is a large 4 line by 20 character back-lit alphanumeric LCD. It displays information
on the panel and its devices. There are cursor buttons for menu selection and control.
Information provided by the LCD display is an alarm log, an event log, current levels, device
information, verification and maintenance reports.
10.3.2 ACK (Queue) Buttons
Use the ACK buttons to select a particular queue to acknowledge.
•Use the Alarm ACK button to view all alarms. Pressing this button will show the latest
alarm on the LCD display. Use and to view all previous alarms.
•Use the Supervisory ACK button to view all supervisory conditions. Pressing this
button will show the latest supervisory information on the LCD display. Use
and to view all previous supervisory conditions on the LCD display.
•Use the Trouble ACK button to view all trouble conditions. Pressing this button will
show the latest trouble condition on the LCD display. Use and to view any
previous troubles.
•Use the BLDG (monitor) ACK Button to show all monitor conditions. Pressing this
button will show the latest monitor information on the LCD display. Use and
to view all queued monitor conditions.
69
Indicators and Controls
ACK BUTTONS
CURSOR BUTTONS
FIRE
DRILL
SYSTEM
RESET
SIGNAL
SILENCE
LAMP
TEST
Queues are displayed on the screen according to a priority sequence. Queue priority ranking
from highest to lowest is as follows: alarm, supervisory, trouble, and monitor. If, for example,
you are viewing a monitor queue and an alarm occurs, the display will immediately display the
alarm condition. Also, if there is no activity on the system for 10 seconds after you have
pressed a queue button, the display will switch to the highest priority condition.
10.3.3 Cursor Buttons
These four buttons around the Enter
Button are used for up (previous), down
(latest), left, and right selection of items on
the LCD Display.
Enter Button
This button is used to select a displayed
item on the LCD Display.
Cancel Button
This button is used to cancel an operation.
Menu Button
This button is used to initiate the FX-2000 Menu System.
ALM
ACK
SUP
ACK
ENTER
TBL
ACK
BLDG
ACK
MENU
CANCEL
INFO
Info Button
This button is used to get more details about a displayed item.
10.3.4 Signal Silence Button
Activation of the Signal Silence button when the Panel is in Alarm, turns on the Signal Silence
Indicator and deactivates any Silenceable NAC Circuits. Non-Silenceable Circuits are
unaffected. Signals will re-sound upon any subsequent Alarm. This button does not function
during any configured Signal Silence Inhibit Timer period. It also does not function if the NAC
Circuits are active as the result of a Fire Drill. In a Two Stage System, if the Auto General
Alarm Timer has timed out, this Signal Silence button also performs the same function as the
General Alarm Cancel button.
70
10.3.5 Lamp Test Button
Activation of the Lamp Test button turns all front panel Indicators on steady in whichever
colour they would normally be activated and turns the buzzer on steady. If Lamp Test is active
for more than 10 seconds, Common Trouble is activated.
10.3.6 System Reset Button
The System Reset button causes the Fire Alarm Control Panel, and all Circuits, to be reset
•Resets all Latching, Trouble Conditions
•Resets all Initiating Circuits
•Resets 4-Wire Smoke Supply and Aux. Power Supply
•Turns off all NAC Circuits
•Turns off Signal Silence, Ack & GA Indicators
•Turns off Fire Drill
•Stops and resets all Timers
•Processes inputs as new events
•Aux Disconnect is not affected
Indicators and Controls
•Reset cannot be activated until the Signal Silence Inhibit timer has expired.
10.3.7 Signal Silence Button
Activation of the Signal Silence button when the Panel is in Alarm, turns on the Signal Silence
Indicator and deactivates any Silenceable NAC Circuits. Non-Silenceable Circuits are
unaffected. Signals will re-sound upon any subsequent Alarm. This button does not function
during any configured Signal Silence Inhibit Timer period. It also does not function if the NAC
Circuits are active as the result of a Fire Drill. In a Two Stage System, if the Auto General
Alarm Timer has timed out, this Signal Silence button also performs the same function as the
General Alarm Cancel button.
10.3.8 Fire Drill Button
The Fire Drill button activates all programmed and non-Disconnected NAC Circuits, but does
not transmit any Alarms via the City Tie, or Common Alarm Relay. Fire Drill may be
programmed to operate specific NAC Circuits. Fire Drill is cancelled by pressing the button
again (toggle switch), or if the Panel goes into a real Alarm.
10.3.9 General Alarm Cancel Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is
configured for Two Stage Operation, activation of the General Alarm Cancel (2 STAGE AUTO
CANCEL) button while the Auto General Alarm Timer is timing (there is an Alarm in the Panel,
but it is still in the First Stage), that timer is cancelled, and the General Alarm Cancel (2
STAGE AUTO CANCEL) Indicator is on steady amber.
10.3.10 General Alarm Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is
configured for Two Stage Operation, activation of the General Alarm button immediately sends
the Panel into Second Stage - General Alarm. It will also re-activate the Signals if they have
been Silenced during General Alarm. The General Alarm condition remains active until the
Panel is reset.
71
Operation
11.0Operation
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options
must be limited to specific values or not used at all as indicated below.
Program feature or optionPermitted in UL 864? (Y/N)Possible settingsSettings permitted in UL 864
4 seconds maximum (due
Delay Output TimerYES
to worst case loop delay of
6 seconds)
10 seconds
Monitor BuzzerNO
The following chapter describes operation of the FX-2000 Series FACPs including:
•Single Stage Operation
•Two Stage Operation
•Pre-Signal Operation
•UUKL Feature
•Output Circuit Delay Operation
•Circuit Types
•Initiating (Detection) Circuit Type
•NAC (Signal) Circuits Types
•Evacuation Codes
11.1 Single Stage Operation
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: non-verified alarm, verified alarm, sprinkler alarm, water-flow alarm, and
general alarm circuits. Any of these alarm inputs occurring when the panel is not already in
alarm cause the following:
Sounding at the Fast Rate
or OFF
OFF
72
•The buzzer sounds steadily
•If fire drill is active, it is cancelled
•The Common Alarm LED turns on
•The Common Alarm relay activates if Aux disconnect is not active
•The Auto Signal Silence timer, if configured, starts
•The Signal Silence Inhibit timer, if configured, starts
•All non-disconnected NAC programmed to the input are activated provided that Aux
disconnect is not active
•Non-disconnected strobes associated with the input are activated
•Non-disconnected signals associated with the input are activated at the evacuation rate
•Subsequent alarms when the panel is already in alarm, cause the following:
•The alert buzzer sounds steadily
•If Signals have been silenced, they are resounded, the Signal Silence LED turns off, and the
Auto Signal Silence timer, if configured, is restarted
•Any additional non-disconnected strobes associated with the input are activated continuously
•Any additional non-disconnected signals associated with the new input are activated at the
evacuation rate
11.2 Two Stage Operation
In a two stage system, alarm inputs are either first stage (alert) inputs or second stage (general
alarm) inputs. First stage inputs include inputs from the following types of circuits: non-verified
alarm, verified alarm, sprinkler alarm, and water-flow alarm. Second stage inputs include alarms on
the general alarm circuits, activation of the General Alarm button, or expiration of the Auto General
Alarm timer. Any of these alarm inputs occurring when the panel is not already in alarm cause the
following:
• The buzzer sounds steadily
• If fire drill is active, it is cancelled
• The Common Alarm LED turns on
Operation
• The Common Alarm relay activates if Aux disconnect is not active
• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• All Non-disconnected NAC programmed to the input are activated provided that Aux
disconnect is not active
If the alarm is a second stage alarm,
•All non-disconnected strobe circuits are activated continuously
•All non-disconnected signal circuits are activated at the evacuation rate
•The General Alarm LED turns on.
If the alarm is a First Stage alarm,
•Non-disconnected strobe circuits programmed to that circuit are activated continuously
•Non-disconnected signal circuits programmed to that circuit are activated with the alert code
•The Auto General Alarm timer, if configured, starts
•The General Alarm Cancel LED starts flashing.
Subsequent First Stage alarms when the panel is already in alarm, cause the following:
•The buzzer sounds steadily
•If signals have been silenced as a result of the silence button or the Auto signal silence timer,
signals are resounded as they were before signal silence, the Signal Silence LED turns off,
and the Auto Signal Silence timer, if configured, is restarted
•If the panel is not already in General Alarm, additional non-disconnected signals programmed
to the new input are activated with the Alert Code (see NAC (Signal) Circuit Types on
page 77).
•If the panel is not already in General Alarm and if the General Alarm Cancel LED is on steady
NAC that the Auto General Alarm timer has been acknowledged the timer is restarted and the
General Alarm Cancel LED is extinguished.
73
A second stage alarm (general alarm) when the panel is already in alarm causes the following:
i
i
• The buzzer sounds steadily
• All non-disconnected signals are activated at the evacuation rate
• If the Signal Silence LED is on, it turns off and the Auto Signal Silence timer, if
configured, is restarted
• The General Alarm Cancel LED if on, turns off
Alarm inputs are latching: they remain active until system reset.
Note:If the system is configured for correlations, any second stage / general alarm
condition activates all NAC circuits whether they are correlated or not.
11.3 Pre-Signal Operation
To configure the panel for pre-signal, all alarm inputs must be correlated to one NAC circuit
that is wired to a Notification Appliance in the Control Room that is constantly monitored by an
Operator. Using the FX-2000 Configurator, “Subsequent Alarm” in “Common System Status”
must be correlated to turn on the Remaining NAC circuits in the system. To confirm the alarm
(i.e. subsequent alarm) the operator can press the “General Alarm” button on the panel or
activate a Manual Station in the Control Room.
Operation
Note:Pre-Signal is not permitted to be used in Canada.
11.4 UUKL feature
The UUKL Feature on the FX-2000 Configurator is used only in conjunction with the FDG-008
and FDX-008W Fan Damper Controller modules.
In each UUKL relay/equipment set, the user could set up the “Any of” operation. If this option
is selected, the panel will still go into alarm directly if any detector is tripped. The only
difference is that if a relay which is part of the smoke control is configured for “any of”
operation, that relay will only activate after a configurable number of detectors are active.
This operation is meant to be used in an atrium where multiple detector operation is required
to start the smoke control operation but the signaling within the building is based upon the first
detector to activate.
For complete details refer to manual LT-966.
11.5 Output Circuit Delay Operation
The relay function associated with an alarm initiating circuit may be delayed. There is a Output
Delay timer associated with this, refer to Table below. This is programmed using the FX-2000
74
Configuration software. The Output Delay timer is limited to elevator recall purpose only and
has a maximum setting of 4 seconds
.
11.6 Circuit Types
The term circuits refers to an actual electrical interface, either initiating (detection) or NAC
(signal). The term zone is a logical concept for a fire alarm protected area, and will consist of
at least one circuit. Often the terms zone and circuit are used interchangeably, but in this
manual the term circuit is used.
11.6.1 Initiating (Detection) Circuit Type
Table 19 Initiating (Detection) Circuit Types
Operation
Initiating (Detection)
Description
Circuit Type
Non-Verified AlarmThis is a "normal" type of alarm which may have pull stations, smoke
detectors, or heat detectors attached. Any activation of these devices
will immediately result in an alarm condition in the fire alarm control
panel. An alarm condition causes the associated circuit Status LED and
the Common Alarm LED to illuminate red.
Verified AlarmThese alarms are verified by a reset and timing procedure, and may
have Manual Stations, smoke detectors attached. Any activation of
Manual Stations will result in an alarm condition in the fire alarm control
panel within four seconds. Smoke detectors will be verified for a real
alarm within 60 seconds depending upon the startup time of the smoke
detectors being used. If four seconds is too long a response time for pull
stations, then they should be wired separately on a non-verified alarm
circuit. An alarm condition causes the associated circuit Status LED and
the Common Alarm LED to illuminate red. Verified Alarm is not permitted
for heat detectors, 4-wire smoke detectors and smoke detectors with
built-in alarm verification. Refer to Appendix F: Alarm VerificationTiming on page 98 for details.
Water-Flow AlarmAn alarm for water-flow sensors. These alarms are identical to normal
non-verified alarms except that any NAC circuits programmed to these
circuits (all are by default) are non-silenceable. Also, if water-flow retard
operation is enabled, then these circuits are sampled every one second;
if ten samples are active within any 15 second interval, the water-flow
alarm is confirmed and processed. An alarm condition causes the
associated circuit Status LED and the Common Alarm LED to illuminate
red.
Note: Do not use the retard operation with any external retarding device;
maximum retard may not exceed 120 seconds.
Sprinkler AlarmAn alarm for sprinkler flow sensors. These alarms are identical to normal
non-verified alarms unless the water-flow retard operation is enabled. If
water-flow retard operation is enabled, then these circuits are sampled
every one second; if ten samples are active within any 15 second
interval, the sprinkler alarm is confirmed and processed. An alarm
condition causes the associated circuit Status LED and the Common
Alarm LED to illuminate red.
Note: Do not use the retard operation with any external retarding device;
maximum retard may not exceed 120 seconds.
General AlarmThese alarms provide remote general alarm such as for remote key
switches. In a two stage system, these inputs perform exactly the same
function as the front panel or remote annunciator general alarm button.
In a single stage system, these inputs act the same as non-verified
alarms, but if correlations are enabled, general alarm initiating circuits
are correlated to all NAC circuits.
Non-Latching SupervisoryThese alarms are for supervisory devices. An activation on these circuits
will cause the Circuit Status LED and the Common Supervisory LED to
illuminate amber. The buzzer will sound continuously. If the circuit
activation is removed, the supervisory condition will clear (so long as
there are no other supervisory conditions in the system) and the circuit
Status LED will extinguish.
Latching SupervisoryThese alarms are for supervisory devices. An activation on these circuits
will cause the Circuit Status LED and the Common Supervisory LED to
illuminate amber. The buzzer will sound continuously. If the circuit
activation is removed, the Supervisory condition will not clear.
MonitorThis is a supervised general purpose non-latching input used mainly for
correlating to a relay circuit. No other system condition occurs as a
result of its activation (short-circuit), although it is supervised for trouble
(open-circuit).
Trouble-OnlyThis circuit is used for monitoring a trouble condition from an external
device such as a Mircom QX-5000 Audio System. Both open and short
circuits generate a non-latching trouble condition.
76
11.6.2 NAC (Signal) Circuit Types
Table 20 NAC (Signalling) Circuit Type
Operation
NAC (Signalling)
Description
Circuit Type
Silenceable SignalFor audible devices such as bells and piezo mini-horns that may be
silenced either manually or automatically. While sounding, these follow
the pattern appropriate for the condition: the configured evacuation code
(default is temporal code) during single-stage alarm, or two stage
general alarm, or the alert code during a two stage system's alert (first)
stage.
Non-Silenceable SignalFor audible devices such as bells and piezo mini-horns that may not be
silenced either manually or automatically. While sounding, these follow
the pattern appropriate for the condition: the configured evacuation code
(default is temporal code) during single-stage alarm, or two-stage
general alarm, or the alert code during a two stage system's alert (first)
stage.
Coded SignalFor audible devices such as bells and piezo mini-horns that may be
activated in code. The code consists of 4 digits with each digit consisting
of 1-15 pulses on the signals. Each coded circuit can sound the
complete code 1 to 15 times after which signals go silent or revert to
programmed General Alarm rate.
Note: The NFPA-72 and ULC-S527 specify temporal tone. However, for
retrofits of systems that were previously approved, coded signalling is
allowed.
StrobeFor visual devices such as strobes that use no code patterns (they are
continuous).
77
1 1.6.3 Evacuation Codes
Single stage codes
ContinuousOn 100% of the time
Temporal Code3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code0.5 second on, 0.5 second off
California Code5 seconds on, 10 seconds off
Two-stage codes:
Alert Code0.5 second on, 2.5 seconds off
General AlarmEvacuation code as selected from above.
Operation
Continuous
0.5s
0.5s
0.5s
0.5s
s
5
10s
0.5s
2.5s
1.5s
Figure 47 Evacuation Codes
Temporal Code
March Code
California Code
Alert Code
78
Appendix A: Specifications
12.0Appendix A: Specifications
12.1 FX-2003-6DS and FX-2003-6DS-16LED Specifications
Table 21 FX-2003-6DS and FX-2003-6DS-16LED Specifications
FX-2003-6DS and FX-2003-6DS-16LED Chassis
Analog LoopOne Analog Loop capable of monitoring 99 Sensors and 99 Modules
Line voltage22 VDC, 400 mA max, max loop resistance 40
NAC Circuits4 Style Y or Z (Class B or A) NAC circuits, configured as strobes or audibles. Terminals
are labelled "IND".
RatingPower limited / 24 VDC unfiltered, 1.7 A @ 49°C per circuit
Max power allowed5A
Aux Power Supply for
remote annunciators
Resettable 4-Wire
Smoke Supply
RS-485 portFor Remote Annunciators or interface to Audio Systems. Terminals are labelled "RS-485".
Auxiliary relays
(resistive loads)
Electrical ratingsAC Line Voltage120V 60Hz / 240V, 50Hz
BatteryType24VDC, Gel-Cell/Sealed Lead-Acid
Terminals are labelled "AUX PWR".
RatingPower Limited 24 VDC unfiltered, 1.7 A @ 49°C
Terminals are labelled "4-WIRE".
Rating22 VDC, 400 mA max., 5mV ripple
RatingPower limited to 300 mA.
Terminals are labelled "ALARM, TROUBLE, SUPV".
Alarm/Supv/TroubleMust be connected to a Listed Power Limited Source of
Supply. Form C, 1 Amp, 28 VDC
2 Amps / 1 Amp (primary)
Power Supply ratings12 Amps. Max. (secondary)
Charging capability10-24 AH batteries
Charging current3A maximum
Current Consumptionstandby: 230 mA
alarm: 380 mA
OtherDisplays (incl LCD) and Controls for all Common Functions, and 16 Zone Displays.
Table 22 FX-2003-12DS, FX-2003-12XTDS, FX-2009-12DS, and FX-2009S-12DS
Specifications
FX-2003-12DS, FX-2003-12XTDS, FX-2009-12DS, and FX-2009S-12DS Chassis
Analog LoopOne Analog Loop capable of monitoring 99 Sensors and 99 Modules or 99 Advanced
Protocol (AP) devices and 99 AP Modules.
Line voltage22 VDC, 400 mA max, max loop resistance 40
NAC Circuits4 Style Y or Z (Class B or A) NAC circuits, configured as strobes or audibles. Terminals
are labelled "IND".
RatingPower limited / 24 VDC unfiltered, 1.7 A @ 49°C per circuit
Max power allowed10A
Aux Power Supply for
remote annunciators
Resettable 4-Wire
Smoke Supply
RS-485 portFor Remote Annunciators or interface to Audio Systems. Terminals are labelled "RS485".
Auxiliary relays
(resistive loads)
Electrical ratingsAC Line Voltage120V 60Hz / 240V, 50Hz
BatteryType24VDC, Gel-Cell/Sealed Lead-Acid
Terminals are labelled "AUX PWR".
RatingPower Limited 24 VDC unfiltered, 1.7 A @ 49°C
Terminals are labelled "4-WIRE".
Rating22 VDC, 400 mA max., 5mV ripple
RatingPower limited to 300 mA.
Terminals are labelled "ALARM, TROUBLE, SUPV".
Alarm/Supv/TroubleMust be connected to a Listed Power Limited Source of
Supply. Form C, 1 Amp, 28 VDC
4 Amps / 2 Amp (primary)
Power Supply ratings12 Amps. Max. (secondary)
Charging capability17-55 AH batteries
Charging current3A maximum
Current Consumptionstandby: 230 mA
alarm: 380 mA
OtherDisplays (incl LCD) and Controls for all Common Functions, and 16 Zone Displays.
Micro-controller based design.
Fully Configurable with PC software.
Full walk test function.
80
Appendix A: Specifications
12.3 FX-2017-12ADS and FX-2017S-12ADS Specifications
Table 23 FX-2017-12ADS and FX-2017S-12ADS Specifications
FX-2017-12ADS and FX-2017S-12ADS Chassis
Analog LoopOne Analog Loop capable of monitoring 99 Sensors and 99 Modules or 99 Advanced
Protocol (AP) devices and 99 AP Modules.
Line voltage22 VDC, 400 mA max, max loop resistance 40
NAC Circuits4 Style Y or Z (Class B or A) NAC circuits, configured as strobes or audibles. Terminals
are labelled "IND".
RatingPower limited / 24 VDC unfiltered, 1.7 A @ 49°C per circuit
Max power allowed10A
Aux Power Supply for
remote annunciators
Resettable 4-Wire
Smoke Supply
RS-485 portFor Remote Annunciators or interface to Audio Systems. Terminals are labelled
Auxiliary relays
(resistive loads)
Electrical ratingsAC Line Voltage120V 60Hz / 240V, 50Hz
BatteryType24VDC, Gel-Cell/Sealed Lead-Acid
Terminals are labelled "AUX PWR".
RatingPower Limited 24 VDC unfiltered, 1.7 A @ 49°C
Terminals are labelled "4-WIRE".
Rating22 VDC, 400 mA max., 5mV ripple
"RS485".
RatingPower limited to 300 mA.
Terminals are labelled "ALARM, TROUBLE, SUPV".
Alarm/Supv/TroubleMust be connected to a Listed Power Limited Source of
Supply. Form C, 1 Amp, 28 VDC
4 Amps / 2 Amp (primary)
Power Supply ratings12 Amps. Max. (secondary)
Charging capability17-55 AH batteries
Charging current3A maximum
Current Consumptionstandby: 230 mA
alarm: 380 mA
OtherDisplays (incl LCD) and Controls for all Common Functions, with capacity for 48 zone
displays, and 48
Micro-controller based design.
Fully Configurable with PC software.
Full walk test function.
configurable displays and controls.
81
Appendix A: Specifications
12.4 FX-2000 Specifications
Table 24 FX-2000 System Modules and Annunciator Specifications
FX-2000 System Modules and Annunciators
ALC-198SSingle Intelligent Analog Loop ModuleOne Analog Loop capable of monitoring 99
Sensors and 99 Modules or 99 Advanced
Protocol (AP) devices and 99 AP Modules.
Power limited22 VDC, 400 mA max
max loop resistance 40
Current ConsumptionStandby: 50 mA / Alarm: 60 mA
ALC-396SDual Intelligent Analog Loop ModuleTwo Analog Loops capable of monitoring 198
Sensors and 198 Modules or 198 Advanced
Protocol (AP) devices and 198 AP Modules.
Power limited: 22 VDC, 400 mA max, max loop resistance 40
Current Consumptionstandby:50 mA / alarm: 60 mA
ALC-H16Loop Controller ModuleProvides connection for adding up to 16 FA-
1000 style adders DM-1008A, SGM-1004A
and RM-1008A.
Current Consumptionstandby: 35 mA / alarm: 50 mA
SGM-1004ANAC Signal Adder ModuleFour Class B or A (Style Y or Z) NAC circuits;
configurable as strobes or audibles. Terminals
are labelled "IND".
Power Limited:24 VDC unfiltered max. 1.7 amps @ 49C per
circuit
Current Consumptionstandby: 60 mA / alarm: 258 mA
RM-1008A
(resistive loads)
PR-300Polarity Reversal and City Tie ModuleSupervised city tie--not power limited
Relay Adder ModuleMust be connected to a listed power limited
source of supply. Terminals are labelled "RLY".
Eight fully configurable Form C NAC.
Form C, 1 amp., 28 VDC (resistive loads)
Current Consumptionstandby: 25 mA / alarm: 150 mA
24VDC unfiltered, 210 mA max., Trip coil: 14
ohms.
82
Terminals are labelled "City Tie".
Polarity reversal power limited
Terminals are labelled "Polarity Reversal".
24VDC open
12VDC @ 3.5 mA, 8 mA max. (shorted)
Current Consumptionstandby: 35 mA / alarm: 300 mA
Appendix A: Specifications
Table 24 FX-2000 System Modules and Annunciator Specifications (Continued)
FX-2000 System Modules and Annunciators
DM-1008ADetection Adder ModuleEight supervised Class B (Style B) or four
Class A (Style D) NAC circuits; fully
configurable. Terminals are labelled "INI". NAC
circuits are Compatibility ID "A".
Current Consumptionstandby: 80 mA
alarm: 1 zone active: 125 mA
2 zone active: 170 mA
4 zone active: 275 mA
6 zone active: 370 mA
8 zone active: 465 mA
FDX-008WFan Damper Display Module24V DC nominal, range of 20 to 39V DC.
Interconnects via one ribbon cable to P2 of
previous display module. Provides eight
configurable output circuits or fan damper
controls.
Current Consumptionstandby: 15mA Max.
alarm (all LEDs ON): 35mA Max.
FDX-008WKIFan Damper Display Module with
Keyswitch
24V DC nominal, range of 20 to 39V DC.
Interconnects via one ribbon cable to P2 of
previous display module. Provides eight
configurable output circuits or fan damper
controls, 1 output controlled via keyswitch.
Current Consumptionstandby: 15mA Max.
alarm (all LEDs ON): 35mA Max.
RAX-1048TZDSAdder Annunciator Chassis48 Display Points and 48 trouble points.
Interconnect via one ribbon cable to RAM1032(TZ) or to previous RAX-1048(TZ).
Annunciation of up to 48 additional points (with
trouble annunciation on the TZ version).
Current Consumptionstandby: 22 mA
alarm: 1 zone LED active: 26 mA
2 zone LED active: 30 mA
3 zone LED active: 35 mA
IPS-2424DSProgrammable Input Switches
Module
Current Consumptionstandby: 5 mA
4 zone LED active: 39 mA
48 zone LED active: 262 mA
alarm: 22 mA maximum
83
Appendix A: Specifications
Table 24 FX-2000 System Modules and Annunciator Specifications (Continued)
FX-2000 System Modules and Annunciators
UDACT-300ADigital Communicator ModuleTransmit alarm, supervisory, and trouble to a
central monitoring station.
Current Consumptionstandby: 45 mA / alarm: 120 mA
12.5 Compliance
System ModelFX-2000 Series Fire Alarm Control Panel
System TypeLocal, auxiliary (using PR-300), remote protected premise station (using PR-300
or UDACT-300A), central station protected premises (using UDACT-300A).
Type of ServiceA, M, WF, SS (with PR-300 or UDACT-300A)
Type of SignallingCoded and Non-coded
Applicable StandardsNFPA 70 and 72, UL-864 Rev.9, ULC S-524, ULC S-527-99
InstallationIntended for indoor use, dry locations
84
13.0Appendix B: Compatible Devices
13.1 FX-2000 Series Compatible Addressable Loop Devices (UL)
Table 25 UL Compatible FX-2000 Series Addressable Loop Devices
Make Model / BaseDescription
Mircom
MIX-1251Low-Profile Analog Ionization Smoke Sensor
MIX-1251APAdvanced Protocol Ionization Smoke Sensor
MIX-2251(B)/T(B)Low-Profile Analog Photoelectronic Smoke Sensor/plus Thermal
MIX-2251AP/TAPAdvanced Protocol Photoelectronic Smoke Sensor/plus Thermal
MIX-2251TM(B)Low-Profile Acclimate™ Intelligent Photoelectric Thermal Sensor
MIX-2251TMAPAdvanced Protocol Photoelectric Thermal Sensor
MIX-7251(B)Pinnacle™ Intelligent Laser Smoke Sensor
MIX-5251P/RPLow-Profile Analog Thermal Sensor/Rate of Rise
MIX-5251(B)/R(B)Low Profile Intelligent Thermal Sensor/Rate of Rise
MIX-M500MBMonitor Module (Universal)
MIX-M500MAPAdvanced Protocol Monitor Module
MIX-5251HLow Profile Intelligent Thermal Sensor
MIX-M500CHAddressable Control Module
MIX-M501MAddressable Mini-Monitor Module
MIX-M501MAPAdvanced Protocol Mini-Monitor Module
MIX-M502MUniversal Monitor Module
MIX-M502MAPAdvanced Protocol Universal Mini-Monitor Module
MIX-M500RAddressable Relay Output Module
MIX-M500RAPAdvanced Protocol Relay Output Module
MIX-M500SAddressable Supervised Output Module
MIX-M500SAPAdvanced Protocol Supervised Output Module
MIX-M500DMAddressable Dual Input Monitor Module
MIX-DH200PLIntelligent Smoke Detector
MIX-DH200RPLIntelligent Smoke Detector (with relay)
MIX-210LP200 Series Low Profile Intelligent Base
MIX-B501BH200 Series Low Profile Intelligent Base with Horn
MIX-B501BHT200 Series Low Profile Intelligent Base with Horn (Temporal Code)
Appendix B: Compatible Devices
System Sensor
FTX-P1Filtrex™ Intelligent Photoelectric Smoke Sensor
M500XFault Isolator Module
IM-10Ten Input Monitor Addressable Module
CR-6Six Relay Control Module
SC-6Six Supervised Control Module
B254BIAnalog Base with Isolator
B501BAnalog Base
B210LP200 Series Low Profile Intelligent Base
B501B-FTXFiltrex Base
85
Table 25 UL Compatible FX-2000 Series Addressable Loop Devices
i
Make Model / BaseDescription
System Sensor continued
B501BH200 Series Low Profile Intelligent Base with Horn
B501BHT200 Series Low Profile Intelligent Base with Horn (Temporal Code)
CZ-6Six Addressable Universal Zone Module
BEAM200Intelligent Addressable Beam Detector
BEAM200SIntelligent Addressable Beam Detector (with Sens Test)
13.2 FX-2000 Series Compatible Two-Wire Smoke Detectors (UL)
Notes: Whether mixing different models of compatible smoke detectors or using the
same model on the same circuit, total standby current of all detectors must not
exceed 3 mA.
The below listed smoke detectors are compatible with initiating circuits having
Compatibility Identifier "A".
Appendix B: Compatible Devices
Table 26 FX-2000 Series Compatible Two-Wire Smoke Detectors (UL Listed)
Smoke Detector Make
Model / Base
Compatibility
Identifier Head /
Base
Rated
Standby
Current
Smoke Detector Make
Model / Base
Compatibility
Identifier Head /
Base
Rated Standby
Current
ApolloSentrol - ESL
55000-225 / 45681-251, 255, -256, -258
55000-325 / 45681-251, 255, -256, -258
Detection Systems Inc.
DS250B - N/A0.10 mA429CRTS11A - N/A0.10 mA
DS250THB - N/A0.10 mA
DS282B - N/A0.10 mA
DS282THB - N/A0.10 mA
Hochiki
DCD-135/NS6-220HD-3/HB-720.035mA
DCD-135/NS4-220HD-3/HB-30.035mA721UT / 702E, 702US10A - S000.10 mA
DCD-135/HSC-220RHD-3/HB-30.035mA722U / 702E, 702US10A - S000.10 mA
DCD-190/NS6-220HD-3/HB-30.035mA
DCD-190/NS4-220HD-3/HB-30.035mA721UT / 702E, 702US10A - S000.10 mA
DCD-190/HSC-220RHD-3/HB-30.035mA721UT / 702E, 702US10A - S000.10 mA
Table 26 FX-2000 Series Compatible Two-Wire Smoke Detectors (UL Listed)
Smoke Detector Make
Model / Base
Compatibility
Identifier Head /
Base
Rated
Standby
Current
Smoke Detector Make
Model / Base
Compatibility
Identifier Head /
Base
Rated Standby
Current
Hochiki continuedSystem Sensor
SIJ-24/NS6-220HD-3/HB-720.040mA
SIJ-24/NS4-220HD-3/HB-30.040mA4451HT / B401***A - A0.12 mA
SIJ-24/HSC-220RHD-3/HB-30.040mA5451 / B401B***A - A0.12 mA
SLR-24/NS6-220HD-3/HB-720.045mA5451 / B401***A - A0.12 mA
SLR-24/NS4-220HD-3/HB-30.045mA2451 / B401B***A - A0.12 mA
SLR-24/HSC-220RHD-3/HB-30.045mA2451 / B406B***A - A0.12 mA
SLR-24H/NS6-220HD-3/HB-30.045mA2451 / DH400***A - N/A0.12 mA
SLR-24H/NS4-220HD-3/HB-30.045mA2451TH / B406B***A - A0.12 mA
SLR-24H/HSC-220RHD-3/HB-720.045mA2451 / B401***A - A0.12 mA
SLR-835/NS6-220HD-3/HB-30.045mA2451TH / B401***A - A0.12 mA
SLR-835/NS4-220HD-3/HB-30.045mA4451HT / B401B***A - A0.12 mA
SLR-835/HSC-220RHD-3/HB-720.045mA4451HT / B406B***A - A0.12 mA
SLR-835B-2HD-6
NAPCO
FW-2HD-6
55μa @
24VDC
55μA @
24VDC
1100***A - N/A0.12 mA
1151/ B110LP***A - A0.12 mA
1151/ B116LP***A - A0.12 mA
Mircom
MIR-525UFDT-10.10 mA1451/B401***A - A0.12 mA
MIR-525TUFDT-10.10 mA1451/ B401B***A - A0.12 mA
MIR-752L / MIR-B6**WHC60 / WB020.2 mA1451/ B406B***A - A0.12 mA
MIR-752L / MIR-B44**WHC60 / WB040.2 mA1451DH/ DH400***A - A0.12 mA
MIR-752HL / MIR-B6**WHC60 / WB02/0.2 mA2100***A - N/A0.12 mA
MIR-752HL / MIR-B44**WHC60 / WB040.2 mA2100T***A - N/A0.12 mA
1400***A - N/A0.10 mA
2151/ B110LP***A - A0.12 mA
5451 / B406B***A - A0.12 mA
2151/ B116LP***A - A0.12 mA
2400***A - N/A0.12 mA
2400TH***A - N/A0.12 mA
2WTA-B*A - N/A0.1 mA
2WTR-B*A - N/A0.1 mA
2W-B, 2WT-BA - N/A0.1 mA
Notes: Maximum number of devices per circuit is 30 unless otherwise noted. If item is
identified by a single asterisk (*) the maximum number of devices is 1. If item is
identified by a double asterisk (**) the maximum number of devices is 21. If item
is identified by a triple asterisk (***) the maximum number of devices is 25.
87
Appendix B: Compatible Devices
13.3 FX-2000 Series Compatible Four-Wire Smoke Detectors (UL
Listed)
Table 27 FX-2000 Series Compatible Four-Wire Smoke Detectors (UL Listed)
Make & Model# of Devices /CircuitMake & Model# of Devices/
Circuit
MircomSystem Sensor
MIR-545U30142425
MIR-545TU30642430
Sentrol-ESL
541CN/AA77-716B
541CXTN/ADH400ACDCI8
709-MV-21N/ADH400ACDCP8
709-24V-21N/ADH400ACDCIHT8
741U WITH 702U or 702E BaseN/A
449AT, 449C, 449CT, 449CRT, 449CST,
Notes: * Strobes and horns must be connected to separate circuits since the horn is a
non-synchronized audible appliance.
Do not mix and match sync module with strobes from different manufacturers
because each manufacturer uses different synchronization protocols.
FHS-340R/W,
FHS-240-110
15
91
Appendix C: Power Supply and Battery Calculations
14.0Appendix C: Power Supply and Battery
Calculations
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power
without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-
current circuit protection that complies with the local codes. Refer to Appendix A: Specifications on page 79
for specifications.
Power Requirements (All currents are in amperes)
Model NumberDescriptionQtyStandby
FX-2003-6DS/-12DS/
-12XTDS/-16LED
FX-2017(S)-12ADSMain Chass1is (12 Amps)
FX-2009(S)-12DSLarge Main Chassis (12A)
ALC-198SSingle Analog Loop
ALC-396SDouble Analog Loop
ALC-H16Adder Controller
DM-1008A8 initiating circuit Module
SGM-1004A4 NAC circuit Module
RM-1008A8 Relay circuit Module
FDX-008W/WKIFan Damper Control Module
Main Chassis (6A/12A)
0.230=0.380=
X
0.230=0.380=
X
0.230=0.380=
X
0.050=0.060=
X
0.050=0.060=
X
0.035=0.050=
X
0.080=
X
0.060=0.258=
X
0.025=0.150=
X
0.015=0.035=
X
Total
Standby
Alarm
1 zone active: 0.125
2 zone active: 0.170
4 zone active: 0.275
6 zone active: 0.370
8 zone active: 0.465
Total
Alarm
=
UDACT-300ADialer Module
PR-300City Tie Module
IPS-2424DS
RAX-1048TZDSAdder Annunciator Chassis
RAM-1032TZDSMain Remote Annunciator
MGD-32
92
Programmable Input
Switches Module
Master Graphic Drive
Module
0.045=0.120=
X
0.035=0.300=
X
0.005=0.022 maximum=
X
1 zone active: 0.026
2 zone active: 0.030
0.022=
X
0.050=32 zone active: 0.300=
X
0.035=
X
3 zone active: 0.035
4 zone active: 0.039
48 zone active: 0.262
__(# of LEDs) x 4mA
(Refer to LT-847 if
using lamps)
=
Appendix C: Power Supply and Battery Calculations
AGD-048
Two-Wire Smoke Detectors
MIX-1251/A Analog Ion Smoke Detector
MIX-2251B/A Analog Photo Smoke Detector
5551A/RA Analog Thermal Sensor
MIX-M500MA/MB, MIX-M501MA/MB Monitor
MIX-M500S/R Monitor Module
M500X Fault Isolator Module
B254BI/A Analog Base with Isolator
Four-Wire Smoke Detectors
Signal Load (bells, horns, strobes, and etc.)
Auxiliary Power Supply for Remote Annunciators
Total currents (Add above currents)STANDBY
Adder Graphic Driver
Module
0.035=
X
♦
X
X
X
X
X
X
X
X
0.0001
200μA=0.0065=
230μA=0.0065=
200μA=0.007=
400μA=0.0051/0.0055=
300μA=0.0051=
450μA=450μA=
450μA=0.005=
X
X
__(# of LEDs) x 4mA
(Refer to LT-847 if
using lamps)
=
==
* 0.090
=
Alarm
=
= 0.090
=
=
(A)(B)
Total Current Requirement: ALARM (B)______ Amps.
Battery Capacity Requirement:
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [
♣
Alarm in Hr.] _____) = (C) ______AH
Main Chassis Selection: Select FX-2003-6DS or FX-2003-6DS-16LED or FX-2009(S)-12DS or
FX-2017(S)-12DS if (B) value is less than 12 Amps.
Battery Selection: Multiply (C) by 1.20 to derate battery.
Batteries: BA-110(10AH), BA-117(17AH) will fit in the UB-1024DS
BA-124 (24AH) will fit in the BBX-1072ADS/ARDS, BB-5008, or the BB-5014
BA-140(40AH) will fit in the BC-160 battery cabinet
* Assuming three initiating circuits in alarm.
♣
Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
♦
Using the System Sensor 2W-B (or C2W-BA) 2-wire smoke detector. See Appendix B: Compatible Devices on
page 85 for other available smoke detectors.
93
Appendix D: Remote Annunciator Panels
15.0Appendix D: Remote Annunciator Panels
15.1 RA-1000 & RAM-200 Series
The RA-1000 Series of remote annunciators are units with electrical modules and enclosures
matching the configurations of the FX-2000 Series Fire Alarm Control Panels. For detailed
information see Mircom Documents RA-1000 Manual LT-617, RAM-208 Manual LT-648, RAM216 Manual LT-658 and MGD-32 Manual LT-847.
15.1.1 RA-1000 & RAM-200 Models
RAM-1032TZDSMain Annunciator Chassis with common indicators and controls, and 32-
circuit capacity.
RAX-1048TZDSAdder Annunciator Chassis with 48 circuit capacity.
RAM-1016Non-Expandable Annunciator Chassis with common indicators and
controls, and 16-circuit capacity.
RAM-208/RNon-Expandable Annunciator Chassis with limited common indicators
and controls, and eight-circuit capacity. Standard beige colour RAM-208,
RAM-208R is red.
RAM-216/RNon-Expandable Annunciator Chassis with limited common indicators
and controls, and 16-circuit capacity. Standard beige colour RAM-216,
RAM-216R is red.
15.1.2 Graphic Annunciators
MGD-32Main Graphic Annunciator Chassis with common indicators and controls,
and 32-circuit capacity.
AGD-048Adder Graphic Annunciator Chassis with 48-circuit capacity.
15.1.3 Enclosures
BB-1001/RCapacity for one annunciator chassis.
BB-1002/RCapacity for two annunciator chassis.
BB-1003/RCapacity for three annunciator chassis.
BB-1008/RCapacity for eight annunciator chassis.
BB-1012/RCapacity for twelve annunciator chassis.
15.2 RAX-LCD
The RAX-LCD Remote Shared Display is a remote annunciator that provides the same
functions as the main display on the fire alarm control panel, less 16 zone LEDs. It is equipped
with a large 4 line x 20 character backlit alphanumeric LCD display which uses a simple menu
system complete with a directional key pad and switches for Enter, Menu, Cancel and Info. For
more information see Mircom document LT-856.
94
15.2.1 Models
RAX-LCDMain Annunciator Chassis with Common Indicators and Controls.
RAX-1048TZDSAdder Annunciator Chassis with 48 Circuit Capacity.
IPS-2424Programmable Input Switches module with 48 display points and 24
15.2.2 Enclosures
Enclosures are:
•Finish painted, textured, off-white (standard), suffix R for red (for other paint available
colours and finishes, please contact factory).
•Material 8 G.A. cold roll steel (CRS).
BB-1001/RCapacity for one annunciator chassis.
BB-1002/RCapacity for two annunciator chassis.
BB-1003/RCapacity for three annunciator chassis.
Put in "OFF" position for firmware restore to defaults during power up. At all other times
put in "ON" state.
ADDRSW1-1SW1-2SW1-3SW1-4JP-1
33ONOFFOFFOFFJUMPER ON Pins 2&3 when
34OFFONOFFOFF
35ONONOFFOFF
36OFFOFFONOFF
37ONOFFONOFF
38OFFONONOFF
39ONONONOFF
RAM-208 or RAM-216
40 OFFOFFOFFON
used with FX-2000 version
2.X.X or higher(16 bit
checksum). JUMPER ON
Pins 1&2 when used with FX2000 version 0.X.X(8 bit
checksum). Firmware of 208/
216 must be 1.0.6 or higher to
accommodate 16 bit
97
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.