Table 11 FR-320 System Modules and Annunciators ................................................................... 102
10
1.0FCC Notice
i
1.0.1Notice for all FR-320 Series Built-in UDACTs Sold in the U.S.A.
Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a
decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is
separately shown on the label.
Mircom's FR-320 SERIES BUILT-IN UDACT Digital Communicator de scribed in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a listed Pre-action/Deluge and Agent Release Control Panel under Standard 864 (Control
Units for Fire Protective Signalling Systems). These Communicators comply with the National
Fire Protection Association (NFPA) performance requirements for DACTs and should be
installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System).
These Communicators should be installed in accordance with this manual; the National
Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
1.0.2FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to p arty lines se rvice is subject to st ate t arif fs.
T ele phone Company Procedures: The goal of the telephone compa ny is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request
information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number an d the
ringer equivalence number (REN ); both of th ese items are listed on the equipment label. The
sum of all of the REN’s on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
11
FCC Notice
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.
12
2.0Introduction
Mircom’s FR-320 Series Pre-Action/Deluge and Agent Release Control Panel performs the
function of fire suppression in a wide variety of applications. It is capable of being used in an
agent release sprinkler system or in a pre-action or deluge sprinkler system. It can be used in
single-hazard or dual-hazard applications with or without cross-zoning. The pa nel includes
common alarm, supervisory, and trouble relays, and provides regulated and unregulated
auxiliary power along with four-wire smoke power. It supports auxiliary relays and a city tie
module. The auxiliary relays are based on a hazard area status. The FR-320 has six input
zones and four output zones, allowing for flexibility in most single and dual-hazard applications
for both deluge and agent releasing applications.
2.1Panel Type
The panel can function as an agent release panel or as a pre-action/deluge panel, depending
on which of the available fixed configurations are chosen from the main programming menu.
2.1.1Deluge sprinkler system
In deluge sprinkler system open-valve sprin kle r heads terminate to a water supply that is
controlled by a single valve. When the system detects fire, it automatically opens the valve via
a releasing circuit, allowing the water to flow through all the sprinkler heads. Deluge sprinkler
systems are useful for applications in which simultaneous discharge of water through every
sprinkler is required.
2.1.2Pre- a ct ion sprinkler system
In a pre-action sprinkler system close-valve sprinkler heads are connected to pipes that are
supervised for air pressure. The pipes terminate directly to a water supply. Pre-action systems
are useful for applications in which the preven tion of an accidental discharge of water is
required.
2.1.3Agent release system
In an agent release system, an extinguishing agent (such as Argon, dry chemical, CO2, Halon,
etc.) is automatically released upon fire detection. An abort function is added to prevent the
false release of the extinguishing agent.
2.2Overall Features
•Basic unit has six Class B (Style B) initiating circuits, which may be configured as Class
A (Style D) using input Class A converter adde r modules. Each initiating circuit is preconfigured as Alarm, Supervisory (Latching or n on-latching), water-flow, Manual
Release Switch, or Abort Switch. There are two LEDs per circuit, one for Trouble
(amber), and one dual color (amber/red) LED for Supervisory (amber) and Alarm (red).
•Basic unit has 4 power limited class B (style Y) output circuits. Output circuits 1 & 2 are
indicating circuits while output circuits 3 & 4 are releasing circuits (circuit 4 can work as
an indicating circuit in some situations; check Pre-Programmed Modes on page 69 for
details). Each indicating circuit process type is pre-configured and can be silenceable.
The signal rates depend on the selected pre-programmed configuration.
•A pushbutton associated with each initiating, indicating and releasing circuit can
individually bypass the circuit.
•Configurable Signal Silence Inhibit and Auto Signal Silence Timers. For Canadian
installations, disable the Auto Signal Silence Timer.
13
Introduction
•Subsequent Alarm, Supervisory, and Trouble operation.
•Four wire reset-able smoke power supply.
•Relay Contacts for Common Alarm, Common Supervisory, Common Trouble, and
Auxiliary Alarm Relay (disconnectable).
•RS-485 Interface for RA-1000 Series Remote Multiplex Annunciators and Smart relay
Module.
•Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
•Extensive transie nt protection.
•Easy configuration of the panel using LCD service tool (CFG-300).
•Releasing circuit protection fro m false alarm by disconnecting the battery if the voltage
falls below 19V.
14
3.0Conventions
3.1Circuits
Refers to an actual electrical interface for initiating (detection), indicating (signal), and
releasing.
3.2Zone
Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.
Often the terms Zone and Circuit are used interch angeably, but in this Manual the term Circuit
is used.
3.3Display Points
There is a display point associated with every initiating and indicating circuit of the FR-320
LED Series fire panel. For an initiating circuit there are two LEDs for every display point: one
single color (amber) and one dual color (r ed/am ber ). F or an ind ica tin g cir cuit th er e is o nly one
LED: one single color (amber), for every display point.
3.4Wiring Styles
Initiating and indicating circuits are Class B (Style B and Y). Changing the initiating circuits to
Class A requires an ICAC-306 adder board which will convert SIX initiating zones from Class
B (Style B) circuits to Class A (Style D). This is done without penalizing the number of circuits,
which remains the same as in Class B (Style B). Changing the indicating circuits to Class A
requires an OCAC-302 adder board, which will convert TWO indicating zones from Class B
(Style Y) circuits to Class A (Style Z). Releasing circuits (Z) are Class B (Style B) only.
15
4.0System Components
4.1Main Pre-Action/Deluge and Agent Release Control Panel
The following models are part of the FR-320 Series:
•FR-320
•FR-320-W
•FR-320-R
•FR-320-DW
•FR-320-DR
16
Figure 1 FR-320 Panel
All FR-320 Panels have the following features:
•Six Zone Pre-Action/Deluge and Agent Release Control Panel with LED display (red or
white door, black b ox.
•six Class B (Style B) initiating circuits, and four Class B (Style Y) output circuits
•Output circuits 1 & 2 are Class B (Style B) indicating circuits that can be converted to
Class A (Style Z) using an OCAC-302 Output Class A Converter adder module.
•Output circuits 3 & 4 are Class B (Style B) only releasing circuits.
•Each output circuit can draw 1.7A current, 5A tot al. A si x zone ICAC-306 Input Class A
Converter adder module may be used for Class A (Style D) wiring of Initiating circuits.
•The FR-320 contains Common Alarm, Common Supervisory & Common Trouble
Relays, auxiliary alarm relay (disconnectable), an RS-485 Interface for Remote
Annunciators and a Resettable Four Wire Smoke Detector Power Supply.
•Two batteries are required.
Additionally:
•FR-320-DW/R panels contain a dialer.
•FR-320 uses a BBX-1024DS or BBX-1024DSR enclosure.
SRM-312WSmart Relay Module (12 relays) with white enclosure
SRM-312RSmart Relay Module (12 relays) with red enclosure
4.5Input Class A Converter: Six Circuits
ModelDescription
Input Class A converter Module (six
ICAC-306
circuits). This module has built-in active
EOL resistors.
17
4.6Output Class A Converter: Two Circuits
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG 2 RET+
BLK RED
BLK RED
A.C.ONCOMMON
TROUBLE
SIGNAL
SILEBCE
BUZZER
SILENCE
SIGNAL
SILENCE
LAMP
TEST
SYSTEM
RESET
SWITCH
ENABLE
FIRE ALARM
ANNUNCIATOR
BLACK
RED
ModelDescription
System Components
OCAC-302
4.7RAM-216 Ancillary Annunciator
ModelDescription
RAM-21616 Zone ancillary annunciator
4.8Active end-of-line
The ELRX-300R(W) are power-saving End-of-Line resistors that eliminate the need for an
additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
ModelDescription
ELRX-300Active end-of-line resistor without plate
Output Class A converter module (two
circuits)
ELRX-300RActive end-of-line resistor with end-of-line red plate
4.9Additional System Accessories
RAM-208Eight Zone Remote Annunciator(ULC and ULI Approved)
RTI-1Remote Trouble Indicator(ULC and ULI Approved)
RAM-1016/TZRemote Annunciator(ULC and ULI Approved)
RAM-1016TZDSRemote Annunciator(ULC and ULI Approved)
MP-300EOL resistor plate, 3.9KΩ(ULC and ULI Approved)
MP-300REOL resistor plate, red(ULC and ULI Approved)
BC-160External Battery Cabinet(ULC and ULI Approved)
MP-1500R/WCurrent Limiter(ULC and ULI Approved)
MP-320R/WSolenoid EOL Module(ULC and ULI Approved)
18
5.0Mechanical Inst allation
i
17"
22.5"
Adhere trim ring to
wall surfac e around
the FR-320 bac kbox.
PLACE FR-320 TRIM RI NG OVER BACKBOX
14.5"
4
.
5
"
11"
20.0"
1.5"
5.425"
14.5"
3.5"
1"
3.5" is the maximum depth
for semi -flus h mounting
using the fl ush trim ri ng
1" is the mini mum depth
above the wal l requi red
for semi -flush mounting
using the fl ush trim ri ng
4 Mounting
Holes for
Surf ace
Mounting
Note:Installation, use and maintenance should be in accord a nc e with the
manufacturer’s documents and the National Electrical Code, ANSI/NFPA 70, and
the National Fire Alarm Code ANSI/NFPA 72.
5.1Installing the Enclosure
Install the FR-320 Series panel enclosure as shown below. Mount enclosure surface mount
using the four mounting holes with the provided screws.
Figure 2 Box dimensions, semi-flush mounting and trim ring
Remove the door (also disconnect the gr ound str ap), the de ad front an d se mi-flush mo unt th e
backbox into the wall. Peel the adhesive cover from the trim ring and stick to the wall surface
around the backbox, after wall is finished.
19
Mechanical Installation
TRIM RING
MIN 1”
WALL
WOOD OR
METAL STUD
BACKBOX
Figure 3 shows a cross-section of the semi-flush mounted backbox and the trim ring. Make
sure to allow a minimum depth of 1” above the wall surface for proper door opening.
Figure 3 Flush Trim Detail
5.2BBX-1024DS and BBX-1024DSR Mechanical Installation
The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a
built-in trim ring.
Dimensions of Enclosure (minus built in trim ring)14 1/2” x 4 1/4” x 26”
Distance between horizontal mounting screws12”
Distance between vertical mounting screws23 1/2”
Complete Dimensions of Enclosures 16 3/4” x 5 1/2” x 28”
20
26.0 "
14.5 "
4.2 "
External Dimensions
23.5 "
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View
Mechanical Installation
Mounting Dimensions
12.0 "
Figure 4 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions
21
5.3Installing the Adder Modules
The FR-320 Series panel comes pre-assembled with all components and boards except for
adder modules. Module installation locations are shown below. Refer to Figure 6 on the next
page for Jumper or DIP Switch settings and see 7.8 Wiring Tables and Information on page 35
for wiring specifications.
DET 1DET 2DET 3DET 4DET 5DET 6
-+-+-+-+-+-+
Mechanical Installation
CLASS-A con verter
board for detection
circuits ICAC-306 (6
circuits )
Reverse pola rity and city
tie module PR-300.
Mounted on hex spacer
with two screws provided
JW4
RS-4 85AUX. RELAYAL ARM RE LAY
S-+NCNOCNCNOCNCNOCNCNOC
JW7
JW5
JW6
RELAY
SUPERVISO RY
RELAY
TROU BL E
JW1
TO PR-30 0 MO DULE
Relay Module RM-306
X
M
?
JW2
TO RM-306 RELAY MOD ULE
AC ON
COMMON ALARM
COMMON SUPV
COMMON TROUBLE
BATTERY TROUBLE
REMOTE TROUBLE
GROUND FAULT
CPU FAIL
ABORT
RELEASED
SYSTEM
RESET
SIGNAL
SILENCE
AUXILIARY
DISCONNECT
LAMP
TEST
ALM/SUP/TBL/
BLDG AUDIBLE SIL
PRE
RELEASE
P6
(ZONE 1)
(ZONE 2)
(ZONE 3)
(ZONE 4)
POWER SUPPLY
SIGNAL
P6P5
BAT TERY
+
P3
IAC1
(ZONE 1)
IAC2
(ZONE 2)
IAC3
(ZONE 3)
IAC4
(ZONE 4)
IAC5
(ZONE 5)
IAC6
(ZONE 1)
NAC1
NAC2
RAC1
RAC2
P4
POWER
-
RTI PORT
UNFLTD SPLY
COM- COM+TRB TRL
SEC TX
P1
SIG 1SIG 2SIG 3SIG 4
AUX
4-WIRE SPLY
-+-+-+-+-+-+
P2
CLASS-A con verter
board for indicating
circuits OC AC-302
(2 circuits)
Transformer
AC wiring terminal
22
BATTERYBATTERY
Figure 5 Installation of Adder Modules
6.0Cable and Jumper Connections for
Main Board, Core Board and Adder
Modules
6.1Main Pre-Action/Deluge and Agent Release Control Board
JW4 -Factory Use Only
Always Short
JW5- Factory Use Only
Always Open
JW4
Main Board
JW6-Normally Open
RS-485 for
annunciators
Auxiliary Relay
Alarm Re lay
Supervisory
Relay
Trouble Relay
JW1 - ON- when
PR-300 not connected
Connect to PR-300
JW4 -Normally Short
5JW -Normally Open
Connect to
RM306 Relay
module
JW4
RS-4 85AUX. RELAYAL ARM RE LAY
S-+NCNOCNCNOCNCNOCNCNOC
JW7
JW5
JW6
RELAY
SUPERVISO RY
RELAY
TRO UB LE
JW1
TO PR-300 MODULE
P3P4
TO RM-306 RELAY MODULE
Core Board
JW5
For front panel programming use CFG-300
configuration tool not UL-864 or ULC-S527
listed. Please refer to Document LT-922 for
details
AC ON
X
COMMON ALARM
COMMON SUPV
COMMON TROUBLE
M
BATTERY TROUBLE
REMOTE TROUBLE
?
GROUND FAULT
CPU FAIL
ABORT
RELEASE
SYSTEM
RESET
SIGNAL
SILENCE
AUXILIARY
DISCONNECT
LAMP
TEST
ALM/SUP/TBL/
BLDG AUDIBLE SIL
PRE
RELEASE
JW2
JW2 - ON- when
RM-306 not connected
control interface, including
AC power and battery supplies.
IAC1
(ZONE 1)
IAC2
(ZONE 2)
IAC3
(ZONE 3)
IAC4
(ZONE 4)
IAC5
(ZONE 5)
IAC6
(ZONE 1)
NAC1
(ZONE 1)
NAC2
(ZONE 2)
RAC1
(ZONE 3)
RAC2
(ZONE 4)
SIGNAL
POWER
Power supply and
UNFLTD SPLY
RTI PORT
COM- COM+TRB TRL
Unfiltered 24 V
supply
DET 1DET 2DET 3DET 4DET 5DET 6
-+-+-+-+-+-+
Initiating zones 1 to 6
SIG 1SIG 2SIG 3SIG 4
-+-+-+-+-+-+
AUX
4-WIRE SPLY
Indicating/Releasing zones 1 to 4
Figure 6 Main Control Board cable connector and jumper settings
23
Cable and Jumper Connections for Main Board, Core Board and Adder Modules
BLK RED
BLK REDBLK R E DBL K RE DBLK REDBLK RED
- DET1 OU T+- DET2 OUT+- DET3 OUT +- DET4 OUT+- DET5 OUT+- D ET6 OUT+
- DET1 RET+- DET2 RET+- DE T 3 RE T +- DET4 RET+- DET5 RET+- DET6 RET+
mounting hole for
#6-32 scr ews
All these pins comes with
red a nd black w i res w hi ch
are connected to the
detection circuit on the
main fire al arm boa rd . R e d
is p o s itive and black is
negati ve
ICAC-306
mounting ho l e for
#6-32 screws
6.1.1Connectors and Jumpers on the Main Fire Alarm Board
JW1
Remove this jumper if PR-300 is connected.
P4Cable from connector P1 of the RM-306 Relay Adder Module connects here.
Otherwise not used.
JW2
Remove this jumper if an RM-306 Relay Adder Module is used.
JW4Shorted if there is no external unit on RS485. This jumper works as ‘end of line’
jumper. If one or more units are connected on RS485, only short on the last
connected unit. JW4 on all other units should be left open.
JW5Normally open. To reset the password, place jumper here and power down the
panel (both AC power and batteries). Then power up the panel again, the
password is restored to the default after system startup. Once the system has
reset, REMOVE the jumper from the pins at JW5.
JW6Normally open to BLOCK configuration via modem, PC with a UIMA converter
module or a CFG-300 Configuration Tool. Place jumper here to ALLOW any type
of configuration.
There are no jumpers or cables to set on this module, just wiring from the converter (wires are
fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For
example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the
positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the
positive and negative terminals marked DET OUT and the circuit return wires are brought back
to the converter module to positive and negative terminals marked DET RET.
24
Cable and Jumper Connections for Main Board, Core Board and Adder Modules
Indicating circuits must be wired from the OCAC-302 to the main Fire Alarm board. For
example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the
Class A converter module to the positive and negative terminals of Indicating circuit 1 on the
Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the
signaling devices and then wired back to the SIGNAL RET positive and negative.
6.4RM-306 Relay Adder Module
Cable from P1 of the RM-306 is connected to P4 on the Main Fire Alarm Board. The jumpers
located above each relay on the RM-306 are used to configure the relays. The jumpers
located below the relays are used to select either normally open contacts or normally closed
contacts.
Figure 9 RM-306 six relay adder module
25
6.4.1RM-306 Jumpers
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
Mounting hole for
#6-32 screws
Mounting hole for
#6-32 screws
P1Cable from RM-306 Relay Adder Module connects to P4 on Main Fire Alarm
Board.
6.4.2RM-306 Correlations
The correlation of the relays are fixed and is as follows:
Relay1Relay2Relay3Relay4Relay5Relay6
Cable and Jumper Connections for Main Board, Core Board and Adder Modules
Active
State
Hazard 1
Alert
Hazard 1
Alarm
Hazard 1
Release
Hazard 2
Alert
Hazard 2
Alarm
Hazard 2
Release
6.5Polarity Reversal and City Tie Module (Model PR-300)
Figure 10 Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
6.5.1PR-300 jumper settings
26
P1
P2 & JW4
The Alarm Transmit sign al to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered. See 8. Alarm Xmit-Sil. on page 55 for more information.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0, 1
or 3 hours if this is the only system trouble. See 9. Pwr Fail Tmr on page 55 for more
information.
Cable connects to P3 on the Main Board
Not used. Jumper JW4 remains on board.
7.0Field Wiring
!
+
-
STYLE B
WIRING
STYLE B
WIRING
INITIATING
CIRCUIT #1
INITIATING
CIRCUIT #2
INITIATING
CIRCUIT - 1
ALARM ZONE
INITIATING
CIRCUIT - 2
SUPERVISORY
ZONE
ION SMOKE
DETECTOR
PHOTO SMOKE
DETECTOR
HEAT
DETECTOR
PULL STATION
3.9K 1/2 WATT ELR
SUPERVISORY
FIRE ALARM MAIN BOARD
+
-
DET 1DET 2
NOTE: ACTIVE END OF LINE
RESISTORS MAY BE USED, BUT
THEY MUST BE USED ON ALL THE
INITIATING CIRCUITS.
Table 1 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in CAN/
ULCS527? (Y/N)
System Reset and
Signal Silence on RAM-
N
208/216
7.1Main Board Field Wiring
Wire devices to the terminals as shown in the figures that follow. Refer to 7.8 Wiring Tables
and Information on page 35 for wire gauges and 17.0 Appendix E: Specifications on page 101
for specifications.
Caution:Do not exceed power supply ratings.
Possible settings\methods
JW4 (Orange Wire) Intact =
Buzzer silence & Lamp Test
local function only. System
Reset & Signal Silence are
disabled.
Cut Jumper (Orange Wire) to
have all remote functions
operate.
Settings permitted in
CAN/ULCS527
Leave JW4 intact on
RAM-208/216
7.1.1Initiating Circuit Wiring
Wiring diagrams for the initiating circuits are shown below. The panel supports Style B wiring
for the initiating circuits and Style D wiring for the indicating circuits. The initiating circuits are
supervised by a 3.9KΩ EOL resistor or an active EOL module.
Figure 11 Initiating circuit – Class B or Style B Wiring
27
Figure 12 Initiating circuit– Class A or Style D Wiring
+
-
STYLE D
WIRING
STYLE D
WIRING
INITIATING
CIRCUIT #1
INITIATING
CIRCUIT #2
INITIATING
CIRCUIT - 1
ALARM
ZONE
INITIATING
CIRCUIT - 2
SUPERVISORY
ZONE
ION SMOKE
DETECTOR
PHOTO
SMOKE
DETECTOR
HEAT
DETECTOR
PULL STAT I O N
SUPERVISORY
4 MORE INITIATIN G
CIRCUITS NOT SHOWN
DCAC-306 CLASS A
CONVERTER MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- DET1
OUT+
- DET2
OUT+
- DET1 RET+- DET2 RET+
+
-
DET 1DET 2
ICAC-306
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
3.9K 1/2 WAT T EL R
OR ELRX-300/R
3.9K 1/2 WAT T EL R
OR ELRX-300/R
MANUAL RELEASE
SWIT CH
Use MS-403 ,404
USE ONLY NO
CONTACT
ABORT SWIT CH
CONNECT A UL /ULC LISTED ABORT STATION ACCEPTABLE TO
THE AHJ, COMPLYING WITH THE FOLLOWING SPECIFICATIONS:
MAXI MUM IMPEDANCE = 1.4K O HMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24 V
Manual Release switches on separate circuits
Abort and Manual Release switches on separate circuits
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
3.9K 1/2 WAT T EL R
OR ELRX-300/R
3.9K 1/2 WAT T EL R
OR ELRX-300/R
7.2Abort and Manual Release Switch Wiring
Field Wiring
Wiring for the abort and manual release switches is shown in Figure 13 and Figure 14. The
Abort and Manual release switches must be on different circuits. DET5 is used for the Abort
switch and DET6 is used for the manual release switch.
28
Figure 13 Abort and Manual Release Switch Class B or Style B Wiring
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5
DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
MANUAL RELEASE
SWIT CH
USE MS -403 ,404
USE ONLY NO
CONTACT
ABORT SWITCH
CONNECT A UL /ULC LISTED ABORT STATION
ACCEPTABLE TO THE AHJ, COMPLYING WITH THE
FOLLOWING SPECIFICATIO NS:
MAXI MUM IMPEDANCE = 1.4K O HMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24V
Abort and Manual Release switches on separate circuits
.
BLK RED
BL K R ED
-DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
BLK RED
BL K R ED
-DET5 OUT+-DET6 OUT+
- DET5 RET+-DET6 RET+
ICAC-306
CLASS A
CONVERTER
MODULE
ICAC-306
CLASS A
CONVERTER
MODULE
Manual Release switches on separate circuits
Field Wiring
Figure 14 Abort and Manual Release Switch Class A or Style D Wiring
29
7.3Indicating Circuit Wiring
-SIG 1 +
STYLE Y
WIRING
STYLE Y
WIRING
INDICATING
CIRCUIT - 1
INDICATING
CIRCUIT - 2
BELLSTROBE3.9K 1/2 WATT ELR
INDICATING
CIRCUIT #1
INDICATING
CIRCUIT #2
HORN
FR-320 Panel
-SIG 2 +
BELLSTROBEHORN
+
-
STYLE Y
WIRING
STYLE Y
WIRING
INDICATING
CIRCUIT #1
INDICATING
CIRCUIT #2
INDICATING
CIRCUIT 1
INDICATING
CIRCUIT 2
OCAC-302 CLASS A
CONVERTER MODUL E
FR-320 Panel
BL K R ED
BL K R ED
-SIG1 OUT+-SIG2 OUT+
-SIG1 RET+-SIG2 RET+
+
-
SIG 1SI G 2
The FR-320 Series Fire Alarm supports Class B or Style Y and Class A Style Z wiring for its
indicating circuits. Each circuit is supervised by a 3.9KΩ EOL resistor or active EOL module.
Each indicating circuit provides up to 1.7 A, 5 A maximum total if no auxiliaries are used.
Field Wiring
Figure 15 Indicating circuit – Class B or Style Y wiring
30
Figure 16 Indicating circuit –Class A or Style Z wiring
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.