Mircom flexnet Installation And Operation Manual

Page 1
Network Intelligent Analog Fire Alarm and Audio System
Installation and Operation Manual
LT-894 Rev
!PRIL 201
Page 2
Page 3
FleX-NetTMInstallation and Operation Manual
Table of Contents
Introduction.............................................................................................................................. 1
Additional Features....................... ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... ... .... ... ... ... ... ........................ 3
Document Conventions............................. ... ... ... ... .... ... ... ... .... ... ... ... .... ... ... ... ... .... ... ... ... .... ... .... 3
System Components ............................................................................................................... 6
Mechanical Installation and Dimensions............................................................................... 14
Module Mounting Locations ................................................................................................... 22
Display and Adder Modules Mounting Locations................................................................. 24
Module Settings ....................................................................................................................... 27
Field Wiring............................................................................................................................... 44
Main Fire Alarm Module Terminal Connections .................................................................... 44
Analog Loop Wiring............................................................................................................... 46
FNC-2000 Fire Network Controller Module........................................................................... 52
FOM-2000-SP Fiber Optic Network Adder Module............................................................... 53
Detection Module (DM-1008A) Terminal Connections ......................................................... 54
Signal Module (SGM-1004A) Terminal Connections ............................................................ 55
Relay Module (RM-1008(A)) Terminal Connections ............................................................. 56
Polarity Reversal and City Tie Module (PR-300) Wiring ....................................................... 57
UDACT-300A Main Board Terminal Connections................................................................. 58
Power Supply Connections................................................................................................... 59
Wiring Tables and Information .............................................................................................. 60
System Checkout..................................................................................................................... 62
Indicators, Controls, and Operation....................................................................................... 63
Common Indicators............................................................................................................... 64
Common Controls ................................................................................................................. 65
Single Stage Operation......................................................................................................... 67
Two Stage Operation ............................................................................................................ 67
Pre-Signal Operation ............................................................................................................ 68
Circuit Types ......................................................................................................................... 69
Configuration............................................................................................................................ 72
Configuration Backup, Query and Fast-Forward .................................................................. 72
OPEN Graphic Navigator Software Package........................................................................ 72
Ethernet Port......................................................................................................................... 72
Boolean Logic Engine ........................................................................................................... 72
uBoot Based BootLoader...................................................................................................... 72
Typical FleX-NetTM System Layouts with Audio.................................................................. 73
System Components for the Integrated Fire/Audio Cabinet................................................ 75
Network Fire Alarm ............................................................................................................... 75
Network Controller Modules.................................................................................................. 75
Fiber Optics Module.............................................................................................................. 76
Adder Modules...................................................................................................................... 76
Auxiliary Modules.................................................................................................................. 76
Programmable Modules........................................................................................................ 76
FleXNetTM Mass Notification System (BBX-FXMNS) Enclosure......................................... 77
Integrated Fire/Audio Cabinet Mechanical Installation ........................................................ 81
Mechanical Installation for the Expansion Audio Cabinet................................................... 83
Integrated Fire/Audio Cabinet - Audio Module Placement and Internal Wiring ................. 85
Integrated Fire Alarm Connection .......................................................................................... 86
Battery Power ....................................................................................................................... 86
Transformer Power ............................................................................................................... 86
QBB-5001/R Expansion Audio Cabinet Module Placement ................................................. 87
QPS-5000N Power Supply Connection ................................................................................ 88
Installing and Removing Amplifiers....................................................................................... 88
Multiple QBB-5001/R Cabinet Connections...................... .... ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... . 89
i
Page 4
Table of Contents
Audio Network Card and Telephone Network Card............................................................. 90
Audio Amplifier Wiring ........................................................................................................... 91
QAA-5230-70/25 Amplifier Wiring ........................................................................................ 91
QAA-5230S-70/25 Amplifier Wiring...................................................................................... 92
QAA-5415-70 and QAA-5415-25 Amplifier Wiring ............................................................... 93
QAA-5160-70/25 .................................................................................................................. 97
Backup Amplifier .................................................................................................................. 99
Displays & Controls................................................................................................................ 100
Setup ........................................................................................................................................ 101
QBB-5001/R Amplifier Installation........................................................................................ 101
Before Turning the Power "ON"... ........................................................................................ 101
Audio Configuration................................................................................................................ 101
Lobby Enclosures................................................................................................................... 102
ANC-5000 Audio Network Controller Module ....................................................................... 103
ANC-5000 Wiring..................................................................................................................... 104
QMP-5101NV Vertical Paging Control Module...................................................................... 106
Paging Modules....................................................................................................................... 107
QMP-5101N Network Master Paging Control Module ......................................................... 107
QMP-5101N/V Network Paging Wiring................................................................................... 109
Paging Operation .................................................................................................................... 110
TNC-5000 Telephone Network Controller Module................................................................ 112
TNC-5000 Telephone Wiring................................................................................................... 116
QMT-5302NV Vertical Master Telephone............................................................................... 118
QMT-5302N Master Firefighters’ Telephone......................................... ....... ... ... ... .... ... ... ... ... 119
QMT-5302N Connections........................................................................................................ 120
QAZT-5302/DS Network Firefighters’ Telephone Selector Panel........................................ 121
Telephone Operation .............................................................................................................. 123
Appendix A: Specifications.................................................................................................... 124
Compliance .......................................................................................................................... 125
ULI/ULC Integrated Fire Alarm and Audio Panel Specifications .......................................... 126
Appendix B: Power Supply and Battery Calculations......................................................... 128
RAXN-LCD/RAXN-LCDG:.................................................................................................... 129
Appendix C: DIP Switch Settings .......................................................................................... 130
ANC-5000 Board with Ethernet Port, Address Setting (DIP SWITCH SW1) ....................... 131
ANC-5000 Board without Ethernet Port, Address Setting (DIP SWITCH SW1) .................. 131
ACN-792M Loop Adder Module (CPU) Address Setting (DIP SWITCH SW1) .................... 131
RAXN-LCD/RAXN-LCDG Remote Annunciator Address Setting (DIP SWITCH SW1) ....... 131
Appendix D: Alarm Verification Timing................................................................................. 131
Appendix E: Wiring for Addressable Supervised Output Module...................................... 132
Appendix F: ULC Compatible Speakers................................................................................ 133
Appendix G: ULI Compatible Speakers................................................................................. 134
Appendix H: Power Supply & Batteries for Audio ............................................................... 135
Appendix I - POWER-LIMITED WIRING SCHEME................................................................. 136
Appendix J FXMNS Used as a Mass Notification System (ACU)....................................... 137
Warranty & Warning Information........................................................................................... 142
ii
Page 5
FleX-NetTMInstallation and Operation Manual
Introduction
About the FleX-NetTM Network Fire and Emergency Communication System
Mircom’s FleX-NetTM Intelligent Fire Alarm and Audio Network offers modular components for network systems providing a wide variety of applications. Designed for peer to peer network communications, using industrial
TM
standard ARCnet protocol. FleX-Net a floor panel) while providing reliability and flexibility.
FleX-Net
TM
is based on the proven and reliable FX-2000 Fire Alarm Control Panel platform. Each base panel consists of one intelligent analog loop controller capable of supporting 99 analog sensors and 99 addressable modules. In addition, the base panel also consists of 4 Class A/B (Style Z/Y) Indicating Circuits (NACs) rated at 1.7 amperes each and a large 4 x 20 back-lit alphanumeric LCD display.
The FleX-Net
TM
configuration allows the FleX-NetTMFire Alarm Control Panels to be connected to a Mircom
network which provides additional input circuits, visual zones, programmable notification appliance circuits and
relays. In addition, a FleX-Net
TM
and/or integrated telephone system.
Mircom's FleX-Net
TM
Network system also provides zoned emergency multi-channel audio providing emergency paging and fire evacuation, and an optional firefighters’ telephone communication to and from CACF (Central Alarm and Control Facilities) location to all remote telephone handsets. The system consists of Integrated Fire and Audio Network Panel or FX-MNS nodes. Each Integrated Fire and Audio Network Panel or FX-MNS contains an audio portion which consists of a QMB-5000N motherboard and card cage which holds an ANC-5000 Audio Network Card, a TNC-5000 Telephone Network Card and up to 4 amplifiers, a fire alarm portion FX-2000ND Main Chassis, a PS-2040 power supply and batteries. The QBB-5001/R expansion audio cabinet (connected to a Integrated Fire and Audio Network Panel or FX-MNS node) contains a card cage motherboard which holds up to 7 amplifiers, has an audio power supply, battery charger and batteries all housed in an audio backbox enclosure.
allows for a maximum of 63 nodes (where a node can be a control center or
Integrated Fire and Audio panel can be used to provide a fully distributed audio
For communication and annunciation there is a microphone for paging, a paging selector panel, firefighters’ telephone and associated selector panels all housed in a central enclosure (CACF). The master paging and telephone modules are intended for installation in a CACF.
Note that the paging microphone and firefighters’ telephone may be used together or independently, connected to a
FleX-Net
TM
Network Central Alarm and Control Facility (CACF).
Overall Features
• Large System Capacity and Modular Design.
• Provides peer-to-peer network communications
• Supports up to 63 nodes (including lobby panel).
• Supports copper and/or fiber optic network cable.
• Each Analog Loop is capable of supporting 99 Digital or Analog Sensors and 99 Addressable Modules which can be wired as Class A (Style 6 or 7) or Class B (Style 4).
• 12 Ampere Power Supply.
• Four Class A/B (Style Z/Y) NACs rated at 1.7 Amperes each, which can be configured as Audible or Visual (silenceable or non-silenceable circuits). Audibles may be steady, Temporal Code, California Code, or March Time.
• Indicating circuits (NACs) may be configured to provide additional auxiliary power or resettable auxiliary power. NAC expansion using the INX-10A, INX-10ADS or INX-10AC.
• Fault isolators are present on all in-panel addressable loops.
• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-Man Walk Test.
• Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an interface to the Mircom RTI-1 Remote Trouble Indicator.
1
Page 6
Introduction
• RS-485 Interface for Remote Annunciators. Remote Annunciators do not occupy a node on the network. Up to seven annunciators can be connected per node.
• Three Level Password Protection with field settable definition which enables the installer to determine what functions are accessible for each level of password
• Four Queues for Alarm, Supervisory, Trouble, and Monitor, with LED indicators and selector keys.
• Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and Common Trouble.
• RS-232 Port for remote system printer or “CRT terminal”.
• Two Event History Logs; one for Alarm related events and one for all events.
• Large 4 line by 20 character alphanumeric, back-lit LCD Display with user-friendly menu system.
• Common Controls and Indicators for System Reset, Lamp Test, Fire Drill, Signal Silence, General Alarm, Acknowledge, AC On, Pre-Alarm, and Ground Fault.
• Two Spare configurable switches and LED Indicators.
• 16 Zone configurable LED (bi-coloured) Annunciator with slide-in labels for Zone Description.
• Provides drift compensation for ionization and photoelectric smoke detectors
• Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1 to 4 digits, each digit consisting of 1-15 pulses on the signal)
• Selection for Canadian (ULC) or USA (ULI) requirements for Smoke Sensor sensitivity.
• Extensive transient protection.
• Surface Mountable Enclosures with removable doors for easy installation and service. Flush Trims Available.
• Removable Terminal Blocks for easy wiring and service.
• Quad Loop Adder module ALCN-792M for expanding addressable loops by 2; with daughter board ALCN-792D expanding addressable loops by a total of 4.
Overall Audio Features:
• Supervises signal circuits while in use.
• Control of fire management operations (e.g. all-call paging and total evacuation signalling).
• Indication of all required fault conditions.
• Microprocessor-based operations with hardware and software watchdog timer to ensure reliable system operation.
• Supervised tone generators.
• Up to 100 audio zones per node, 1575 audio amplifiers per Network system.
• Up to 5 (analog) firefighters’ telephone zones per node and 315 (analog) telephone zones per Network system.
• 99 addressable telephone zones per loop, maximum of 29 addressable telephone loops per node, maximum of 144 addressable telephone zones per system.
• Easy configuration process.
• Operates from 24 VDC backup batteries in the event of a power failure.
• Removable terminal blocks for ease of installation and maintenance.
• Speaker circuits integrated with amplifier circuits.
• Maximum of 180 Watts per Integrated Fire and Audio Cabinet (BBX-2000) and FX-MNS.
• Maximum of 360 Watts per QBB-5001/R expansion cabinet and 1260 Watts of total power per Integrated Fire and Audio Panel (BBX-2000) or FX-MNS node with maximum expansion [180W +360W(3)=1260W].
• Optional redundant backup amplifier per node.
2
Page 7
FleX-NetTMInstallation and Operation Manual
Additional Features
Blackfin based Quad Loop Adder module ALCN-792M. The ALCN-792M is a 2 loop addressable adder module with provision to connect a daughter board ALCN-792D which contains an additional 2 addressable loops for a total of four addressable loops.
There are two additional main fire alarm panel displays:
DSPL-420 8 line LCD display narrow board
DSPL-2440 9 event, 24 line graphical display narrow board
The BBX-FXMNS enclosure is for the Integrated Fire and Audio consisting of a backbox, door and middle chassis. Part of this enclosure is the vertical mount telephone QMT-5302NV and the vertical mount paging microphone QMP-5101NV.
The ANC-5000 Audio Network Controller module includes ARCnet and an ethernet port. ARCnet reduces the wiring for audio and telephone to the ARCnet only or fiber optics (if used).
The QBC-5000N charger provides a dual voltage transformer for audio.
The RAXN-LCDG is a graphical display remote annunciator.
The FleXNet
Configuration options are provided for grouping inputs.
TM
is compatible with Coptir, Pinnacle, Acclimate and 4-20mA devices.
Panel supports previous, current and next configuration. Configuration automatically reverts back to previous or moves to future configuration through front-panel menu.
OPEN Graphic Navigator Software Package allows 3D graphic display of premises and devices. Use the
ethernet port on the main board to connect to OPEN graphics software.
Boolean logic functions are now available within the configuration software.
uBoot Based BootLoader program (inherent in the configuration) provides leading technology that allows a choice of multiple configuration files or firmware revisions to support site-specific requirements.
The FleXBoot system tuning and optimization.
TM
shell offers UNIX style commands for directory listing, log download, diagnostic probing and
Document Conventions
Circuits and Zones
The term circuits refers to an actual electrical interface, initiating (detection), indicating (signal), or relay. The term zone is a logical concept for a fire alarm protected area, and will consist of at least one circuit. Often the terms zone and circuit are used interchangeably, but in this manual the term circuit is used.
On the FleX-Net inputs and outputs, and addressable inputs and outputs may be grouped together to form logical zones.
Wiring Styles
Initiating circuits are configured by default as Class B (Style B). They may be configured as Class A (Style D) as described in System Configuration. This operation uses odd and even pairs of two-wire Class B (Style B) circuits to
make one four-wire Class A (Style D) circuit, thus cutting in half the number of available initiating circuits.
TM
, circuits can be hardwired inputs and outputs or addressable inputs and outputs. Both hardwired
Indicating circuits (NACs) may be individually wired as Class A (Style Z) or Class B (Style Y) without affecting the
number of circuits available.
Addressable Loops may be configured system wide as Class B (Style 4) or Class A (Style 6). With the addition of isolators, a Class A (Style 6) will become a Class A (Style 7).
3
Page 8
Document Conventions
RAXN-LCD in a BB-1001R
Node 5
FX-2003-12N in a BBX-1024R
RS-485
Node 3
FX-2017-12N in a BBX-1072RA
RAXN-LCD in a BB-1001R
RS-485
Node 1
FX-2017-12N in a BBX-1072RA
Node 2
FX-2003-12N in a BBX-1024R
TM
Class A wiring
Twisted Pair Wiring
RS-485
RAXN-LCD in a BB-1001R
CACF
Node 4
Typical FleX-Net Wiring Without Audio
4
FX-2009-12N in a BB-5008R
Page 9
Five Telephone
Five Telephone
RAXN-LCD in
BB-1001R
RAXN-LCD in
BB-1001R
Paging
ARCnet
Audio
Telephone
Internal RS-485
Audio
Typical FleX-Net Wiring With Audio
TM
IPS-2424
FDX-008
Fan Damper Controller
RAX-1048TZ
AGD-048
RAXN-LCD
Annunciator
FOM-2000-SP Fibre Optic
Network Module
ALCN-792D Analog Loop
Network Module
UDACT-300A Digital
Communicator Module
FX-2000N
Main Board
-2000
FDX-008
Fan Damper Controller
Conventional Devices
Addressable Devices
Addressable Devices
Node 2 - Floor Panel
Node1
Node 3 - Floor Panel
ANC-5000 & TNC-5000 in Audio Card Cage
Phone Line 1
Five Telephone
Circuits per TNC-5000
Handsets
Phone Line 2
FNC-2000 Network
Controller Module
Loop 2
Speakers
Paging Audio
Alert 1
RM-1008A
Relays
SGM-1004A
Signal
DM-1008A
Inputs
PTR-2000-1
AGD-048
IPS-2424
Zone Bypass
RAX-1048TZ
Graphic Driver
Display Adder
and/or
NOTES:
(5)
Annunciators RAXN-LCD and RAXN-LCDG can support a maximum of 41 frames each, which include
IPS-2424, FDX-008, AGD-048, RAX-1048TZ and QAZT-5302.
(4) The system supports a maximum of 7 annunciators per node.
(6) If high speed digitized audio is used only the ARCnet or Fiber Optic wiring is required between nodes.
plus ALCN-792D for a total of 29 loops per FX-2000N.
(1) The main board has two conventional loops, one SLC loop and 4 Class B (Style Y) NAC circuits.
(2) The main FX-2000N supports a maximum of 12 frames (a frame is a measure of display capacity).
(3) Each FX-2000N supports a maximum of seven ALCN-792M Quad Addressable Loop Adder Module
1 twisted pair or 2 bre optic cables for
ARCnet Network , Fire Control, Paging
Audio and Telephone
FleX-NetTMInstallation and Operation Manual
5
Page 10
Mircom
A.C. LINE CIRCUIT BREAKER
ALARM QUEUE
SUPV. QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
A.C. ON
PRE-ALARM
GND FAULT
Mircom FX-2000
Fire Alarm Control Panel
Normal Condition
December 31, 1999
SIGNAL SILENCE
GENERAL
ALARM
2nd STAGE
AUTO CANCEL
FIRE DRILL
SYSTEM RESET
LAMP
TEST
ENTER
MENU
CANCEL
INFO
A.C. LINE CIRCUIT BREAKER
ALARM QUEUE
SUPV. QUEUE
TROUBLE QUEUE
MONITOR QUEUE
A.C. ON
PRE-ALARM
GND FAULT
Mircom FX-2000
Fire Alarm Control Panel
Normal Condition
December 31, 1999
SIGNAL SILENCE
GENERAL
ALARM
2nd STAGE AUTO CANCEL
FIRE DRILL
SYSTEM RESET
LAMP TEST
ENTER
MENU
CANCEL
INFO
ZONE BYPASS #1
ZONE BYPASS #2
ZONE BYPASS #4
ZONE BYPASS #3
ZONE BYPASS #5
ZONE BYPASS #6
ZONE BYPASS #8
ZONE BYPASS #7
ZONE BYPASS #9
ZONE BYPASS #10
ZONE BYPASS #12
ZONE BYPASS #11
ZONE BYPASS #17
ZONE BYPASS #18
ZONE BYPASS #20
ZONE BYPASS #19
ZONE BYPASS
#13
ZONE BYPASS
#14
ZONE BYPASS
#16
ZONE BYPASS
#15
ZONE BYPASS #21
ZONE BYPASS #22
ZONE BYPASS #24
ZONE BYPASS #23
ZONE BYPASS #1
ZONE BYPASS #2
ZONE BYPASS #4
ZONE BYPASS #3
ZONE BYPASS
#5
ZONE BYPASS
#6
ZONE BYPASS
#8
ZONE BYPASS
#7
ZONE BYPASS #9
ZONE BYPASS #10
ZONE BYPASS #12
ZONE BYPASS #11
ZONE BYPASS #17
ZONE BYPASS #18
ZONE BYPASS #20
ZONE BYPASS #19
ZONE BYPASS #13
ZONE BYPASS #14
ZONE BYPASS #16
ZONE BYPASS #15
ZONE BYPASS #21
ZONE BYPASS #22
ZONE BYPASS #24
ZONE BYPASS #23
A.C. LINE CIRCUIT BREAKER
ALARM QUEUE
SUPV. QUEUE
TROUBLE QUEUE
MONITOR QUEUE
A.C. ON
PRE-ALARM
GND FAULT
Mircom FX-2000
Fire Alarm Control Panel
Normal Condition
December 31, 1999
SIGNAL SILENCE
GENERAL
ALARM
2nd STAGE AUTO CANCEL
FIRE DRILL
SYSTEM RESET
LAMP TEST
ENTER
MENU
CANCEL
INFO
ZONE BYPASS #1
ZONE BYPASS #2
ZONE BYPASS #4
ZONE BYPASS #3
ZONE BYPASS #5
ZONE BYPASS #6
ZONE BYPASS #8
ZONE BYPASS #7
ZONE BYPASS #9
ZONE BYPASS #10
ZONE BYPASS #12
ZONE BYPASS #11
ZONE BYPASS #17
ZONE BYPASS #18
ZONE BYPASS #20
ZONE BYPASS #19
ZONE BYPASS
#13
ZONE BYPASS
#14
ZONE BYPASS
#16
ZONE BYPASS
#15
ZONE BYPASS #21
ZONE BYPASS #22
ZONE BYPASS #24
ZONE BYPASS #23
ZONE BYPASS #1
ZONE BYPASS #2
ZONE BYPASS #4
ZONE BYPASS #3
ZONE BYPASS
#5
ZONE BYPASS
#6
ZONE BYPASS
#8
ZONE BYPASS
#7
ZONE BYPASS #9
ZONE BYPASS #10
ZONE BYPASS #12
ZONE BYPASS #11
ZONE BYPASS #17
ZONE BYPASS #18
ZONE BYPASS #20
ZONE BYPASS #19
ZONE BYPASS #13
ZONE BYPASS #14
ZONE BYPASS #16
ZONE BYPASS #15
ZONE BYPASS #21
ZONE BYPASS #22
ZONE BYPASS #24
ZONE BYPASS #23
System Components
Chassis Types
FX-2003-12N
FX-2017-12NDS
Model Description
12 Amp Compact Main Chassis. This compact main chassis comes
complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a 4 line by 20 character back-lit LCD display, 16 zone LED annunciator and a 12 ampere power supply which charges 17-65 AH batteries. The FX­2003-12N supports the FNC-2000 Network Controller Module and 2 other adder modules. This unit mounts in the BBX-1024 black backbox/ white door or BBX-1024R black backbox/red door.
This model does not support any network audio.
12 Amp Mid-Size Main Chassis. This mid-size main chassis comes
complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a DSPL-420 4 line by 20 character LCD display and a 12 ampere power supply which charges 17-65 AH batteries. The FX-2017-12N supports the FNC-2000 Network Controller Module and two adder modules over the main board plus additional space in the chassis for 14 adder boards. This chassis mounts in the BBX-1072A/DS black backbox/white door or BBX-1072RA/ARDS black backbox/ red door.
FX-2017-12N FX-2017-12NDS
FX-2017-12NDS
6
This model does not support any network audio.
12 Amp Mid-Size Main Chassis. This mid-size main chassis comes
complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a 4 line by 20 character back-lit LCD display, 16 zone LED annunciator and a 12 ampere power supply which charges 17-65 AH batteries. The FX­2017-12N supports the FNC-2000 Network Controller Module and two adder modules over the main board plus additional space in the chassis for 14 adder boards. This chassis mounts in the BBX-1072A black backbox/white door or BBX-1072RA black backbox/ red door.
This model does not support any network audio.
12 Amp Mid-Size Main Chassis. This mid-size main chassis comes
complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a DSPL-420 4 line by 20 character LCD display, and a 12 ampere power supply which charges 17-65 AH batteries. The FX-2017-12NDS supports the FNC-2000 Network Controller Module and two adder modules over the main board plus additional space in the chassis for 14 adder boards. This chassis mounts in the BBX-1072A/DS black backbox/white door or BBX-1072RA/ARDS black backbox/ red door.
This model does not support any network audio.
Page 11
FX-2009-12N
ALARM QUEUE
SUPV. QUEUE
TROUBLE
QUEUE
MONITOR QUEUE
A.C. ON
PRE-ALARM
GND FAULT
Mircom FX-2000
Fire Alarm Control Panel
Normal Condition
December 31, 1999
SIGNAL
SILENCE
GENERAL ALARM
2nd STAGE
AUTO CANCEL
FIRE DRILL
SYSTEM RESET
LAMP TEST
ENTER
MENU
CANCEL
INFO
ZONE
BYPASS
#1
ZONE BYPASS
#2
ZONE BYPASS
#4
ZONE BYPASS
#3
ZONE BYPASS
#5
ZONE BYPASS
#6
ZONE BYPASS
#8
ZONE BYPASS
#7
ZONE BYPASS #9
ZONE BYPASS #10
ZONE BYPASS #12
ZONE BYPASS #11
ZONE
BYPASS
#17
ZONE
BYPASS
#18
ZONE
BYPASS
#20
ZONE
BYPASS
#19
ZONE BYPASS #13
ZONE BYPASS #14
ZONE BYPASS #16
ZONE BYPASS #15
ZONE BYPASS #21
ZONE BYPASS #22
ZONE BYPASS #24
ZONE BYPASS #23
Cutout to mount
display module
Cutout to mount
display module
FX-2009-12NDS
FleX-NetTMInstallation and Operation Manual
12 Amp Large Main Chassis. This large main chassis comes complete
with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a 4 line by 20 character back-lit LCD display, 16 zone LED annunciator and a 12 ampere power supply which charges 17-65 AH batteries. The FX­2009-12N supports the FNC-2000 Network Controller Module over the main board plus additional space in the chassis for 8 adder boards. This chassis mounts in the BB-5008 or BB-5014 black backbox/black door or BB-5008R black backbox/red door.
This is model does not support any network audio.
12 Amp Large Main Chassis. This large main chassis comes complete
with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) NACs (1.7 Amp each), a DSPL-420 4 line by 20 character back-lit LCD display, and a 12 ampere power supply which charges 17-65 AH batteries. The FX-2009-12NDS supports the FNC-2000 Network Controller Module over the main board plus additional space in the chassis for 8 adder boards. This chassis mounts in the BB-5008 or BB-5014 black backbox/black door or BB­5008R black backbox/red door.
FX-2000MNS
ECX-0012
This is model does not support any network audio.
Consists of a backplate which is mounted into the BBX-FXMNS backbox and a FX-2000N Fire Alarm Control board and a battery disconnect board.
Expander Chassis to use with the FX-2009-12N. It provides space for 12 adder modules and two display modules. This chassis mounts into the BB-5008(R) or BB-5014 backbox.
7
Page 12
System Components
- + S
- + S
- - + + - - + +
- - + +
+ -
P1
RX2
RX1
TX2
TX1
LOOP (3)
LOOP (4)
P1
To Main Board Connector P6
+ - + -
S S
+ - + -
B
A
A
B
COM (-)
Network Controller Modules
FNC-2000
Model Description
Provides network capability for the FX-2000N Fire Alarm panel. One module is required per one network node panel. The FNC-2000 Fire Network Controller module is mounted in position 2 over the FX-2000N main board.
*0
*0
*0
0.ETWORK23
0
0!-03)NTERFACE
Audio Network Controller module. The ANC-5000
*7
*7
0
*7 *7
023$EBUG
023
0(?3PEED!UDIO
*7
*7
*7
*7
*7
ANC-5000
Audio Network Controller module is mounted over a metal plate (which is packaged with the FX­2009-12N) and then the plate is mounted in a BB­5008 or BB-5014 backbox in positions marked 4 to 9 inclusive. The recommended plate mounting is sideways with LEDs across the top.
Telephone Network Controller module. The TNC­5000 Telephone Network Controller module is mounted over the ANC-5000 Audio Network
TNC-5000
Controller module and both are mounted on a metal plate and then the plate is mounted in a BB­5008 or BB-5014 backbox in positions marked 4 to 9 inclusive. The recommended plate mounting is sideways with LEDs across the top.
Fiber Optics Module (Optional)
FOM-2000-SP
Connects to the FNC-2000 Fire Alarm Network Controller Module and allows fiber optics cabling.
Adder Modules
ALCN-792M Quad Loop Adder board.
ALCN-792D
8
Model Description
Daughter board for ALCN-792M Quad Loop Adder
Page 13
FleX-NetTMInstallation and Operation Manual
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
Model Description
DM-1008A Eight Initiating Circuit Module
SGM-1004A Four NAC circuit Module
RM-1008A Eight Relay Circuit Module
PR-300 Polarity Reversal and City Tie Module
Display Modules
UDACT-300A Digital Communicator/Dialer Module
Model Description
FDX-008 Fan Damper Module
4 line by 20 charactor display which can be
DSPL-420
mounted into backboxes BBX-1072A(RA), BBX-1072ADS(ARDS), BB-5008(R), BB-5014 and the BBX-FXMNS Backbox.
Flexnet
Flexnet
System Normal
System Normal
DSPL-2440
Graphic display which can be mounted in backboxes BBX-1072A(RA), BBX-1072ADS(ARDS), BB-5008(R), BB-5014 and the BBX-FXMNS Backbox
9
Page 14
System Components
ZONE
BYPASS
#1
ZONE
BYPASS
#2
ZONE
BYPASS
#4
ZONE
BYPASS
#3
ZONE
BYPASS
#5
ZONE
BYPASS
#6
ZONE
BYPASS
#8
ZONE
BYPASS
#7
ZONE
BYPASS
#9
ZONE
BYPASS
#10
ZONE
BYPASS
#12
ZONE
BYPASS
#11
ZONE
BYPASS
#17
ZONE
BYPASS
#18
ZONE
BYPASS
#20
ZONE
BYPASS
#19
ZONE
BYPASS
#13
ZONE
BYPASS
#14
ZONE
BYPASS
#16
ZONE
BYPASS
#15
ZONE
BYPASS
#21
ZONE
BYPASS
#22
ZONE
BYPASS
#24
ZONE
BYPASS
#23
PAGE TO
ALERT
WARDEN
PAGE
ALL CALL
A.C. ON
PAGE READY
PRE-TONE ACTIVE
AMPLIFIER TROUBLE
MIC
TROUBLE
LAMP
TEST
PAGE CANCEL
PAGE TO EVAC
COMMON TROUBLE
ALL CALL MINUS
WARDEN PAGE
MIC ACTIVE
PRE-TONE ACTIVE
AMPLIFIER TROUBLE
MICROPHONE
TROUBLE
PAGE CANCEL
LAMP TEST
ALL-CALL MINUS
PAGE TO ALERT
PAGE TO EVAC
PAGE READY
A.C. ON
ALL CALL
Model Description
IPS-2424/DS
Programmable Input Switches Module (mounts with the FX-2009-12N and can also be part of the RAXN-LCD)
RAM-1032
RAM-1032TZ
RAM-1032TZDS
RAX-1048TZ
RAX-1048TZDS
Audio and Telephone Modules
QMP-5101N Network Master Paging Control Panel
Model RAM-1032 Main Chassis Remote Annunciator with 32 Bi-coloured LEDs. Model RAM-1032TZ/DS Main Chassis Remote Annunciator with 16 Bi-coloured LEDs and 32 trouble LEDs.
Model RAX-1048TZ/DS Adder Annunciator Chassis with 48 Bi-coloured LEDs and 48 trouble LEDs.
Model Description
QMP-5101NV
QMT-5302N Network Master Telephone Control Panel
10
Network Master Paging Control Panel (Vertical Mount) mounts within the BBX-FXMNS enclosure.
Page 15
FleX-NetTMInstallation and Operation Manual
Telephone
#1
Telephone
#2
Telephone
#3
Telephone
#4
Telephone
#5
Telephone
#6
Telephone
#7
Telephone
#8
Telephone
#9
Telephone
#10
Telephone
#11
Telephone
#12
Telephone
#13
Telephone
#14
Telephone
#15
Telephone
#16
Telephone
#17
Telephone
#18
Telephone
#19
Telephone
#20
Telephone
#21
Telephone
#22
Telephone
#23
Telephone
#24
INX-10A Board
Battery
Battery
Transformer
CALL CONTROL
TROUBLE
INCOMING CALL
ACTIVE
CALL CONTROL
DESELECT ALL
Booster Power Supply
Model Description
Network Master Telephone Control Panel
QMT-5302NV
(Vertical Mount) mounts within the BBX-FXMNS enclosure.
QAZT-5302/DS Zoned Paging and Telephone Selector Panel
Model Description
Addressable Booster Power Supply mounts to backboxes BB-5014 and BBX-FXMNS. Same
INX-10AC
unit as the INX-10A and INX-10ADS, except this model comes with a chassis for mounting. Refer to LT-899 manual for more detailed instructions.
Enclosures
B
Model Description
BBX-1024 white door black backbox (add suffix “R” for red door/black backbox)
BBX-1024DS white door black backox (add suffix “R” for red door/black backbox)
BBX-1072A white door black backbox (or BBX-1072RA for door/black backbox)
BBX-1072ADS white door black backbox (or BBX-1072RADS for door/black backbox)
BB-5008 black door and backbox (add suffix “R” for red door/black backbox)
BB-5014 black door and backbox Backbox 60”H x 30”W x 7”D
BBX-FXMNS Enclosure with Door Assembly (add suffix “R” for red door/black backbox)
Enclosure 26”H x 14.5”W x 4.5”D
Enclosure 27.5”H x 16.5”W x 5.5”D
Enclosure 32.5”H x 25”W x 6.5”D
Enclosure 34”H x 26.5”W x 7.7”D
Backbox 36”H x 30”W x 7”D
Backbox 61.5”H x 22”W x 9”D
11
Page 16
System Components
Flexnet
System Normal
Flexnet
System Normal
Flush Trim Rings
Model Description
Remote Annunciators
Mircom FX-2000N
Fire Control System
- System Normal -
Jan 01, 2011 12:21 AM
SUPV.
ALARM
TROUBLE
QUEUE
QUEUE
QUEUE
SIGNAL
GENERAL
SILENCE
ALARM
ACKNOW-
MONITOR
QUEUE
LEDGE
ENTER
A.C. ON
PRE-
ALARM
GROUND
FAULT
SYSTEM
FIRE
RESET
DRILL
FA-UNIV-TRB
FA-1072TR
MENU
CANCEL
INFO
Model Description
RAXN-LCD
LAMP TEST
Black flush trim ring for BBX-1024(R)
Black flush trim ring for BBX-1072A/RA/DS/ RDS.
Remote Shared Display Annunciator. Please refer to LT-895 RAXN-LCD manual for further information.
Remote Shared Graphical Display Annunciator.
RAXN-LCDG
Please refer to LT-6033 RAXN-LCDG manual for further information.
RAM-1016
RAM-1016TZ
RAM-1016TZDS
(RA-1000 Series)
Model RAM-1016 Main Chassis Remote Annunciator with 16 Bi-coloured LEDs. Model RAM-1016TZ/DS Main Chassis Remote Annunciator with 16 Bi-coloured LEDs and 16 trouble LEDs. Please refer to LT-617 RA-1000 Series Annunciator manual for further information.
MGD-32 Master Graphic Driver Annunciator Board
AGD-048 Adder Graphic Driver Board
RAM-216 Annunciator with 16 Bi-coloured LEDs.
12
Page 17
FleX-NetTMInstallation and Operation Manual
D 3
RAM-208 Annunciator with 8 Bi-coloured LEDs.
RTI-1
FX-LOC(R) Local Operating Console
FX-LOC(R) consists of:
FX-LOC Enclosure includes backbox, inner door and outer white door.
FX-LOCR, the R suffix represents a red door.
Main Display RAXN-LCD.
Selection control panel FDS-008 plus IM-10A Ten Input Monitor module.
Master paging microphone, model QMP-5101N.
Remote Trouble Indicator (single LED and trouble buzzer).
Model Description
The FX-LOC(R) Local Operating Console along
with the Mircom FleX-Net system facilitates a Mass Notification System.
The FX-LOC(R) provides critical emergency (as well as fire) information to be communicated within buildings.
Refer to LT-6039 FX-LOC(R) Installation Instruction Manual for further details and the LT-6042 Application Guide for Mass Notification information.
TM
Network Fire Alarm
Batteries
FleX-NetTM Accessories
Model Description
MP-300/R/S End-of-line Resistor Plate, R for red, S for stainless steel finish
BC-160 External Battery Cabinet (ULC and ULI listed)
Model Description
Batteries 17 to 65 AH
13
Page 18
Mircom
FA-UNIV-TRB
Adhere trim ring to wall surface around
backbox.
17.0"
28.5"
1.2"
1.2"
14.55"
3.7"
1.55"
1.55"
18"
0.2"
0.2"
Mechanical Installation and Dimensions
Install the enclosure as shown for the BBX-1024 in Figure 1 below. The BBX-1024DS install information is in Figure
2. For the BBX-1072A and BBX-1072ADS see Figure 3 and 4, on the following pages. Figure 5 demonstrate the BB-5008 backbox installaltion.
Figure 1: BBX-1024 Flush or Surface Enclosure Installation and Dimensions
FA-UNIV-TRB
Material: 18GA (0.048”) thick cold rolled steel Finish: Painted except for hinges
Note: Leave bottom of box conduit free for batteries.
14
Page 19
FleX-NetTMInstallation and Operation Manual
23 1/2”
5 3/4”
1 1/2”
4 1/4”
12”
LEFT SIDE VIEW
BACKBOX FRONT VIEW
17”
14 1/2”
28 ”
26 ”
BACKBOX
DOOR
1 3/4”
1 3/4”
6”
2”
9 1/2”
1 3/4”
1 3/4”
2”
2”
TOP VIEW
RIGHT SIDE VIEW
KNOCKOUT LOCATIONS
Dimensions of backbox (minus built-in trim ring)
Horizontal distance between mounting screws
Vertical distance between mounting screws
Complete dimensions of enclosure with door
Size of Knockouts:
Material of backbox and door: 16 GA (0.059”) thick cold rolled steel
Finish of backbox and door: Painted
26”H x 14 1/2”W x 4 1/4” D
12”
1”
23 1/2”
28”H x 17”W x 5 3/4”D
BBX-1024DS BACKBOX AND DOOR
Figure 2: BBX-1024DS Flush and Surface Enclosure Installation and Dimensions
15
Page 20
Mechanical Installation and Dimensions
Material: Cold rolled steel
16GA (0.059”) thick for backbox
14GA (0.075”) thick for door
Finish: Painted except for hinges
Figure 3: BBX-1072A Flush or Surface Enclosure Installation and Dimensions
Note: Leave bottom of box conduit free for batteries.
16
Page 21
FleX-NetTMInstallation and Operation Manual
Figure 4: BBX-1072ADS Flush and Surface Installation and Dimensions
Material: Cold rolled steel
16GA (0.059”) thick for backbox
14GA (0.075”) thick for door
Finish: Painted except for hinges
17
Page 22
Mechanical Installation and Dimensions
Backbox
BB-5008 Backbox
DOX-5008M Metal Door
Backbox with DOX-5008M Door
Figure 5: BB-5008 Enclosure Installation Instructions and Dimensions
Material: Cold rolled steel
16GA (0.059”) thick for backbox
14GA (0.075”) thick for door
Finish: Painted except for hinges
Note: Leave bottom of box conduit free for batteries. Mount the power supply in the same manner as shown
in Figure 7.
18
Page 23
FleX-NetTMInstallation and Operation Manual
Chassis Installation
1. Group the incoming wires through the top of the enclosure to prepare it for wiring the modules. Do not run the wires in-between the modules since it could cause a short circuit.
2. Use a wire tie to group wires for easy identification and neatness.
3. Be sure to connect a solid earth ground (from building system ground / to a cold water pipe) to the chassis earth ground mounting lug, and to connect the earth ground wire lugs from the main chassis to the ground screw on the backbox.
4. Mount chassis FX-2003-12N into backbox BBX-1024 using the supplied hexnuts as shown in Figure 6 below.
Figure 6: Chassis Installation into BBX-1024
14 1/2”
BACKBOX
Mircom FX-2000N
Fire Alarm Control Panel
Normal Condition December 31, 2009
TROUBLE
SUPV.
ALARM
QUEUE
QUEUE
QUEUE
A.C. ON
PRE-ALARM
26”
CHASSIS
GROUND
4 1/2”
MENU
ENTER
CANCEL
INFO
MONITOR
QUEUE
GND FAULT
SIGNAL
FIRE
SILENCE
DRILL
SYSTEM
GENERAL
RESET
ALARM
ACKNOW-
LAMP
LEDGE
TEST
MAIN CHASSIS
FX-2003-12N
EARTH GROUND LUG
#8 X 1/4” TYPE ‘B’ SCREW
Note: Leave bottom of box conduit free for batteries.
#8-32 HEXNUTS (4)
19
Page 24
Mechanical Installation and Dimensions
6
2012
Figure 7: Chassis Installation into BBX-1072A
Mount chassis FX-2017-12N into backbox BBX-1072A using the supplied hexnuts as shown below.
20
Page 25
FleX-NetTMInstallation and Operation Manual
Material:
Cold rolled steel 16GA (0.059”) thick for backbox 14GA (0.075”) thick for door
Finish: Painted except for
hinges
Figure 8: Installation Instructions and Dimensions for BB-5014
BB-5014 Backbox
Backbox
Backbox with DOX-5014M Door
DOX-5014M Metal Door
Note: Mount the power supply in the same manner as shown in Figure 7
21
Page 26
Mircom
MODEL: FX-20XX-12N/ DS
M A IN CHA SSIS
( SEE N OTE 1 )
SCREW
#6-32 x 1 1/2" M/F HEX SPACER
( SEE N OTE 2 )
( SEE N OTE 2 )
( SEE N OTE 3 )
OTHER CIRCUIT AD DER
#6-32 x 1 1/4"
( SEE N OTE 3 )
MODULE
PR-300 CITY TIE MODULE
OTHER CIRCUIT AD DER
UDACT-300A
DIALER MODULE
FNC-2000 or
Module Mounting Locations
The FX-2003-12N or FX-2017-12N Main Chassis come pre-assembled with a main panel, display components and boards. Install the adder modules of different types as shown in the diagrams on the following pages.
Notes: For many adder modules to enable communication from the main module to all of the adder modules, it is
necessary to add a continuity jumper on the last adder module in a chain (see the appropriate module settings section to verify the location of the continuity jumper on a particular circuit adder module). Only the last circuit adder module should have a jumper plug on its continuity jumper; all others must be left without a jumper plug.
Figure 9: Module Mounting Locations View #1
Notes:
22
1. Front plate is not shown.
2. Position reserved for PR-300 or UDACT-300A.
3. Other circuit adder modules may include:
• FNC-2000
• DM-1008A Detection Circuit Adder Module
• SGM-1004A Signal Circuit Adder Module
• RM-1008A Relay Circuit Adder Module
• ALCN-792M and ALCN-792D Loop Adder Modules
Page 27
Figure 10: Module Mounting Locations View #2
1
2
Main Chassis FX-20XX-12N/DS
Provision for PR-300 or UDACT-300A
FNC-2000 in position 2 and other Adder Module in position 1
MD-579
MD-575 Long Ribbon Cable MD-579 Short Power Cable MD-580 Long Power Cable
FleX-NetTMInstallation and Operation Manual
FNC-2000 Fire Network Controller Module
This module is required in the main lobby and one per node. It mounts over the main fire alarm board, preferably in position 2. Use the four 2” spacers and four screws to secure the FNC-2000 to the main fire alarm board.
23
Page 28
Mircom
ALARM QUEUE
SUPV. QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
A.C. ON
CPU FAULT
GND FAULT
SIGNAL SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE DRILL
SYSTEM RESET
LAMP TEST
ENTER
MENU
CANCEL
INFO
LED 0
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
CONFIGURABLE SWITCH/LED 3
CONFIGURABLE SWITCH/LED 7
Mircom FX-2000N
Fire Alarm Control Panel
Normal Condition
December 31, 2009
AC LINE
CIRCUIT
BREAKER
Slot 3 is reserved for PR-300 or UDACT-300A. If not required, this slot can be used to mount any of the adder modules.
The recommended mounting position is 2 for the FNC-2000. The FOM-2000-SP board, if used, is mounted over the FNC-2000 board.
FX-2000N Main Board
1
23
45
67
89101112
1314151617
FX-2000 Main Board
Display and Adder Modules Mounting Locations
FX-2003-12N Compact Main Chassis
Mounts in the BBX-1024 Enclosure and supports three adder modules.
Exterior View Interior View
123
FX-2000 Main Board
FX-2017-12N Mid-size Main Chassis
Mounts in the BBX-1072A Enclosure, and supports three display modules and 17 adder modules.
Exterior View Interior View
SYSTEM
CONFIGURABLE SWITCH/LED 7
MENU
CANCEL
INFO
FIRE
DRILL
RESET
LAMP TEST
Cutout to mount
display module
Cutout to mount
display module
Cutout to mount
display module
Mircom FX-2000N
Fire Alarm Control Panel
LED 0
LED 1
LED 2
LED 3
Normal Condition
December 31, 2009
SUPV.
ALARM
QUEUE
QUEUE
A.C. ON
CPU FAULT
LED 4
LED 5
LED 6
LED 7
TROUBLE QUEUE
GND FAULT
LED 8
LED 9
LED 10
LED 11
ENTER
MONITOR
QUEUE
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LED 12
LEDGE
LED 13
CONFIGURABLE SWITCH/LED 3
LED 14
LED 15
AC LINE CIRCUIT
BREAKER
24
FX-2000N Main Board
Slot 3 is reserved for PR-300 or UDACT­300A. If not required, this slot can be used to mount any of the adder modules.
The recommended mounting position is 2 for the FNC-2000. The FOM-2000-SP board, if used, is mounted over the FNC-2000 board.
Page 29
FleX-NetTMInstallation and Operation Manual
4
231
56
789
FX-2000 Main Board
FX-2000N Main Board
Slot 3 is reserved for PR-300 or UDACT-300A. If not required, this slot can be used to mount any of the adder modules.
The recommended mounting position is 2 for the FNC-2000. The FOM-2000-SP board, if used, is mounted over the FNC-2000 board. Positions 4 to 9 are replaced with the audio and telephone boards if used.
1
2
34
56
789101112
P1
RX2
RX1
TX2
TX1
FX-2009-12N Large Main Chassis
Mounts and occupies four display positions in BB-5008 or BB-5014 Enclosures, and supports two display modules and nine adder modules. This large chassis size can hold the integrated audio and/or telephone modules.
Exterior View Interior View
Mircom FX-2000N
Fire Alarm Control Panel
Normal Condition
December 31, 2009
ALARM QUEUE
A.C. ON
LED 0
LED 1
LED 2
LED 3
MONITOR
TROUBLE
SUPV.
QUEUE
QUEUE
QUEUE
CPU FAULT
GND FAULT
LED 8
LED 4
LED 5
LED 6
LED 7
LED 12
LED 13
LED 9
LED 10
LED 14
LED 15
LED 11
SIGNAL SILENCE
GENERAL
ALARM
ACKNOW-
CONFIGURABLE SWITCH/LED 3
MENU
ENTER
CANCEL
INFO
FIRE DRILL
SYSTEM
RESET
LAMP TEST
LEDGE
CONFIGURABLE SWITCH/LED 7
Cutout to mount
display module
Cutout to mount
display module
ECX-0012 Expander Chassis for FX-2009-12N
Mounts and occupies two display positions in BB-5008 or BB-5014 Enclosures, and supports two display and 12 adder modules.
Exterior View Interior View
Cutout to mount
display module
Cutout to mount
display module
NETWORK CONTROLLER MODULES
The FNC-2000 Fire Network Controller module is mounted in position 2 over the FX-2000N main board. The TNC­5000 Telephone Network Controller module is mounted over the ANC-5000 Audio Network Controller module and both are mounted on a metal plate and that plate is mounted in a BB-5008 or BB-5014 backbox in positions marked
4 to 9 inclusive, refer to previous drawing of large chassis.
FNC-2000
Fire Network Controller Module
FOM-2000-SP
Fiber Optics Module
Mounts over the
FNC-2000 Fire Network Controller Module
0
*0
*0
*0
*7
0.ETWORK23
023
*7
*7
*7
*7
*7
ANC-5000
0!-03)NTERFACE
Audio Network
*7
Controller
0
*7 *7
023$EBUG
0(?3PEED!UDIO
Module
0
TNC-5000
Telephone Network Controller Module
25
Page 30
Display and Adder Modules Mounting Locations
LOOP (3)
LOOP (4)
P1
To Main Board Connector P6
+ - + -
S S + - + -
B
A
A
B
COM (-)
POLARITY REVERSAL
ALARM
POLARITY REVERSAL
SUPV
CITY TIE
+ | - + | - + | -
JW4
P1 P2
Flexnet
System Normal
Flexnet
System Normal
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
Adder Modules
Each adder module occupies one module slot and mounts inside the following chassis:
• FX-2003-12N Compact Main Chassis
• FX-2017-12N Mid-size Main Chassis
• FX-2009-12N Large Main Chassis
• ECX-0012 Expander Chassis for FX-2009-12N
ALCN-792M
ALARM OUT
SS+ - + -
+ - + -
B
B
COM (-)
A
A
Loop 1
P4
Loop 2
Active LED
Active LED
P3
P5
P6
Daughter Board Connector
1
8
SW1
P2
Quad Intelligent Analog Loop Adder Module.
P1
ALCN-792D
Daughter Board Analog 2 Loop Adder Module.
DM-1008A
Eight Initiating Circuit Module
UDACT-300A
DIgital Alarm Communicator Module
SGM-1004A
Four NAC circuit Module
PR-300
Polarity Reversal/ City Tie Module
RM-1008A
Eight Relay Circuit Module
Mounts over ALCN-792M
Display Modules
Each display module occupies one display position and mounts to the display cutouts on the following chassis:
• FX-2003-12N Compact Main Chassis
• FX-2017-12N Mid-size Main Chassis
• FX-2009-12N Large Main Chassis
• ECX-0012 Expander Chassis for FX-2009-12N
These modules can also be mounted in the standard BB-5000 Series enclosures which have cutouts (with brackets), and the BBX-1000 Series enclosures (requires RAXN-LCD as a driver). “Frame” is a measure of display capacity, used in the programming of the system.
DSPL-420
Narrow Display Control(3 Frames)
RAM-1032/TZ/TZDS
Programmable Zone LED
Annunciator Module (3 Frames)
IPS-2424/DS
Programmable Input
Switches Module (2 Frames)
DSPL-2440
Graphic Display Control(3 Frames)
26
RAX-1048TZ/DS
Programmable Zone/Trouble LED
Annunciator Module (3 Frames)
FDX-008/KI
Fan Damper Module (1 Frame)
Page 31
FleX-NetTMInstallation and Operation Manual
Module Settings
Main Fire Alarm Module (MD-871A “N” Version Main Chassis)
This main board has one addressable loop and network capability.
JW1 Jumper is removed if a PR-300 or UDACT-300A is installed. JW2,JW4 Jumpers are Factory Set and should not be changed. JW5 Normally un-installed, add jumper to silence on-board buzzer. JW6 Normally installed, remove jumper to enable external power supply supervision. P1,2 Factory connection to Bridge Rectifier. P3 Black RS-485 Connector connects to the Adder Loop ALCN-792M if used (Address Loops 3 and 4) P4 Connector for PR-300 Module or UDACT-300A. P5 Connector for next 8 Conventional Hardwire Circuit Adder Modules (Loop 1). P6 Connector for first 8 Conventional Hardwire Circuit Adder Modules (Loop 0). P7 Ethernet jack. P8 Power Connector for Adder Modules. P9 RS-232C for Printer or “CRT” Monitor. P10,11 Connection to 24 VDC Battery. Observe Polarity. P14 Connector for Display Module. P15, P18, J1 Connectors for Factory Use. P16 High speed RS-485 audio link to ANC-5000 Audio Network Controller Module.
When connected provides ARCnet or Fibre Optic audio and telephone communication
P19 Connector for FNC-2000 Fire Network Controller Module. SW2 DIP Switch for node address. NAC PWR 24V FWR input terminals for additional power for signal adder modules.
F1 20 Amp slow blow non-replaceable fuse.
Note: To enable communication from the Main Module to all of the Adder Modules, it is necessary to add a Continuity
Jumper on the last Adder Module in a chain (see the appropriate Module Settings section to verify the location of the Continuity Jumper on a particular Circuit Adder Module). Only the last circuit adder module should have a jumper plug on its continuity jumper; all others must be left without a jumper plug.
TO CONFIGURE THE FIRE ALARM PANEL USE THE RS-485 CONNECTOR P4 OF THE LAST ADDER LOOP CONTROLLER MODULE INSTALLED OR IF NOT PRESENT, P3 ON THE FleX-Net
TM
MAIN FIRE ALARM MODULE.
Figure 11: Main Fire Alarm Module (MD-871A “N” Version Main Chassis)
JW5
P4
JW1
FIELD WIRING TERMINALS
P5
JW6
MAIN FIRE ALARM BOARD
JW4
P19
ON
P2
P1
8
J1
P15
P10 P11
+ BR - +BAT -
P6
P8
NAC PWR
F1
P7
P14
P9
P18
P3
P16
SW2
1
JW2
27
Page 32
Module Settings
SW2 DIP Switch Node Address Setting on Main Fire Alarm Module
Refer to table in Appendix for Node Address Setting. Available addresses are 1 to 63. DIP Switch SW2-1 is the least significant digit.
DSPL-420 Main Display Module
The DSPL-420 mounts into backboxes BB-5008(R), BB-5014(R) and BBX-FXMNS. This display is part of the following main fire alarm chassis: FX-2003-12NDS, FX-2003-12XTDS, FX-2009-12NDS, FX-2017-NDS, and FX­2000NDS.
Figure 12: DSPL-420 Main Display Module (Part of Main Chassis c/w Main Fire Alarm Module)
P1: Cable connects to P14 of the FX-2000N main fire alarm board (Figure 11). P2: Connection to P1 of any adder display module if used.
Note: The main display module comes with slide-in paper labels including both English and French slide-
ins, and laser printer-compatible blanks for zone labelling.
28
Page 33
FleX-NetTMInstallation and Operation Manual
DSPL-2440 Graphical Main Display Module
The DSPL-2440 is a separate item. It can be mounted into backboxes BB-5008(R), BB-5014(R) and BBX-FXMNS. It can replace the DSPL-420 found with the following models: FX-2003-12NDS, FX-2003-12XTDS, FX-2009­12NDS, FX-2017-NDS, and FX-2000NDS.
Figure 13: DSPL-2440 Graphical Main Display Module
MGC Network
Fire Control System
System Normal
P1: Cable connects to P14 of the FX-2000N main fire alarm board (Figure 11). P2: Connection to P1 of any adder display module if used.
Note: The main display module comes with slide-in paper labels including both English and French slide-
ins, and laser printer-compatible blanks for zone labelling.
29
Page 34
Module Settings
P1
P2
ALARM QUEUE
SUPV.
QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
A.C. ON
CPU FAULT
GND FAULT
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM
RESET
LAMP TEST
ENTER
MENU
CANCEL
INFO
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
LED 16
LED 17
LED 18
LED 19
LED 20
LED 21
LED 22
LED 23
CONFIGURABLE SWITCH/LED 3
SWITCH/LED 1
SWITCH/LED 2
SWITCH/LED 4
SWITCH/LED 5
SWITCH/LED 6
SWITCH/LED 0
CONFIGURABLE SWITCH/LED 7
MGC Network
Fire Control System
System Normal
March 7, 2013
Main Display Module
The display module shown in Figure 14 is part of the following chassis: FX-2003-12N, FX-2009-12N, FX-2017-12N and FX-2000ND.
Figure 14: Main Display Module (Part of Main Chassis)
P1: Cable connects to P14 of the FX-2000N main fire alarm board (Figure 11). P2: Connection to P1 of any adder display module if used.
Note: The main display module comes with slide-in paper labels including both English and French slide-
ins, and laser printer-compatible blanks for zone labelling.
30
Page 35
FleX-NetTMInstallation and Operation Manual
This cable connects to P19 on the FX-200X-XN Main Fire Alarm Board
FNC-2000 Fire Network Controller Module
An FNC-2000 Fire Network Controller module is required in each fire alarm node in the system. The FNC-2000 also provides a connection for an optional FOM-2000-SP Fiber Optics Module.
Figure 15: FNC-2000 Fire Network Controller Module
Table 1: FNC-2000 Module List of Connectors and Jumpers and Functions
CONNECTOR
OR JUMPERS
P6 P6 is for Factory Use Only. P10 P10 connects to P1 of the FOM-2000-SP Fiber Optic Network Adder Module if used.
JW1, JW2, JW4, JW7, JW8, JW11
JW5 and JW11 Leave both un-installed. Do not connect JW5 or JW11 (open) JW3, JW6, JW9,
JW12
Note: Network connection is through twisted cable from Line A, B, C and D. Refer to Figure 37 for specific
Jumpers for JW1, JW4, JW7, and JW10 equal Line Termination (always short). Jumpers for JW2 and JW8 equal Ground Fault (always short).
Jumpers for JW3, JW6, JW9, JW12 shall be present between pins 1 and 2 (far right) and
remain as is.
wiring and cable information.
Function
31
Page 36
Module Settings
Figure 16: FOM-2000-SP Fiber Optic Network Module
RX2
One of these modules is required at each panel where fiber optics will be used between them. The FOM-2000-SP will be mounted over the FNC-2000 Network board (over the field wiring terminals) with two #6 Phillips screws and two Hex spacers.
P1
RX1
TX2
TX1
Table 2: FOM-2000-SP Fiber Optic Network Module Cable Connection
Connector Function
P1 P1 cable attaches to P10 of the FNC-2000 Fire Network Controller Module.
RAX-1048/TZ/TZDS Zone Display Module
Figure 17: Zone Display Module (RAX-1048 or RAX-1048TZ/DS)
P2
P1
Table 3: RAX-1048/TZ/TZDS Zone Display Module Cable Function
Connector Function
P1 P1 Cable connects to P2 of previous display module. P2 P2 Cable connects to P1 of next display module
Note: The zone display module comes with laser printer-compatible slide-in paper labels for zone labelling.
32
Page 37
FleX-NetTMInstallation and Operation Manual
P2
P1
ZONE
BYPASS
#1
ZONE
BYPASS
#2
ZONE
BYPASS
#4
ZONE
BYPASS
#3
ZONE
BYPASS
#5
ZONE
BYPASS
#6
ZONE
BYPASS
#8
ZONE
BYPASS
#7
ZONE
BYPASS
#9
ZONE
BYPASS
#10
ZONE
BYPASS
#12
ZONE
BYPASS
#11
ZONE
BYPASS
#17
ZONE
BYPASS
#18
ZONE
BYPASS
#20
ZONE
BYPASS
#19
ZONE
BYPASS
#13
ZONE
BYPASS
#14
ZONE
BYPASS
#16
ZONE
BYPASS
#15
ZONE
BYPASS
#21
ZONE
BYPASS
#22
ZONE
BYPASS
#24
ZONE
BYPASS
#23
Figure 18: IPS-2424/DS Programmable Input Switches Module
Table 4: IPS-2424/DS Programmable Input Switches Module Cable Function
Connector Function
P1 P1 Cable connects to P2 of previous display module. P2 P2 Cable connects to P1 of next display module
Note: The IPS-2424/DS module comes with laser printer-compatible slide-in paper labels for zone labelling.
33
Page 38
Module Settings
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
P1
P2
OFF AUTO ON TROUBLE
PARKING GARAGE #1, FANS 1, 2 , 3
Figure 19: Fan Damper Control Display Module (FDX-008/KI)
There are two models of the Fan Damper Control Display modules available. The FDX-008 provides switch control and LED indication of 8 fan damper zones. The FDX-008KI provides switch control of 7 fan damper zones with the eighth zone activated by keyswitch. LED indication is provided for all 8 fan damper zones on the FDX-008KI. Both the FDX-008 and the FDX-008KI are used in conjunction with an FX-2000N Fire Alarm Control Panel.
Fan Damper Operation
The FDX-008 Fan Damper Control Display module has eight configurable output circuits, each with a three position switch. The FDX-008KI operates in the same manner as the FDX-008 except zone 8 is controlled by a remote keyswitch. Each switch has an ON and OFF position, plus an AUTO position. If the switch is placed in the AUTO position, the output will activate as programmed or configured. The output can be manually turned ON or OFF by placing the switch in the ON or OFF position, respectively.
Basically each switch can be configured to operate multiple fans or dampers. For each switch, there are 3 operations provided; outputs to turn ON, same outputs to turn OFF and inputs to bypass.
An example of the most common use of the FDX-008 or FDX-008KI Fan Damper Control Display module is to operate exhaust fans and confirm fan operation (via monitor modules). See FDX-008 Block Diagram on the next page for a block diagram of fan and monitor set up.
Example
As shown in the figure to the right, Parking Garage #1 has 3 exhaust fans. The three position switch is configured to operate (to turn ON) fans 1, 2 and 3 in stairwell #1. The switch is set in the AUTO position. Upon activation (via alarm or some other programmed trigger) with the switch in AUTO, the 3 fans (1,2, and 3) in stairwell #1 are turned ON automatically. Monitor modules in the Parking Garage #1 detect that all 3 fans are operating, therefore the ON LED will illuminate steadily. If one of the fans did not turn ON (due to malfunction), both the ON and OFF LEDs will flash at the slow trouble rate. The TRBL (trouble) LED will illuminate steady amber based on feedback from the monitor module that one or more of the fans is not working.
ON LED shows steady for all outputs operating and confirmed.
OFF LED shows steady for all outputs NOT operating and confirmed.
TRBL LED shows steady for one or more outputs NOT operating and confirmed.
34
Page 39
FleX-NetTMInstallation and Operation Manual
OFF AUTO ON TROUBLE
FX-2000N FIRE
ALARM PANEL
FANS
OUTPUT MODULES
MONITOR MODULES
FDX-008/KI FAN/DAMPER CONTROL MODULE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE
OFF AUTO ON TROUBLE OFF AUTO ON TROUBLE
TS1
P2
P1
KEYSWITCH CONTROLLED
CONNECTS TO PREVIOUS DISPLAY MODULE P2
Note: A bypass function always has priority, so that if a circuit is bypassed by moving the switch
manually or by loop bypass (FX-2000N Fire Alarm Panel), no other action will operate this switch other than again moving the switch manually or by un-bypassing the loop.
Figure 20: FDX-008 Block Diagram of Fan and Monitor Set-up
Before mounting the FDX-008KI module, if a keyswitch is to be connected, wire the keyswitch to terminals at TS1 as shown in Figure 21below. Mount the FDX-008 and FDX-008KI Fan Damper Control Display modules in any position on the front part of the FX-2000N chassis and backbox.
Figure 21: FDX-008KI Fan Damper Control Display Module
Note: There are also terminals located behind TS1 on the other side of the board for the convenience of
wiring the keyswitch. The last fan damper zone in the bottom right position of the FDX-008KI is controlled by the keyswitch.
35
Page 40
Module Settings
UUKL with FDX-008 and FDX-008KI
The models FDX-008 and FDX-00KI can be effectively use to provide an automatic and manual control system for smoke. Refer to document number LT-966 for extensive instructions regarding UUKL applications.
Figure 22: Hardwire Detection Adder Module (DM-1008A)
P2
P4
JW4
JW3
Data cable to P6 or P5 of main fire alarm module or to P13 or P12 of hardwire loop controller module, or previous adder module
Pow er connect or t o P8 of main f ire alarm module, or to P2 of hardwire loop cont roller modu le, or to previous adder module
JW2
Dat a c on ne cto r f or next adder module
Powe r c on ne c t or fo r next adder module
JW1
FI ELD WI RING TERM INALS
P1
JW5
JW1: Install jumper for Class A (Style D) operation of initiating circuits 1 and 2. JW2: Install jumper for Class A (Style D) operation of initiating circuits 3 and 4. JW3: Install jumper for Class A (Style D) operation of initiating circuits 5 and 6. JW4: Install jumper for Class A (Style D) operation of initiating circuits 7 and 8. JW5: Remove continuity jumper if there are any more adder modules installed
Note: For Class A (Style D) operation the FX-2000N must be configured as Class A via the configuration
program.
.
P3
36
Page 41
Figure 23: Hardwire Signal Adder Module (SGM-1004A)
P1
P3
P4
FIELD WIRING TERMINALS
P2
JW1
JW5
JW4
JW3
JW2
J11
1 2 3
GREEN SIGNAL LEDs
ZONE 4
ZONE 3
ZONE 2
ZONE 1
Data cable to P6 or P5 of main re alarm module or to P13 or P12 of loop controller module, previ­ous adder module
Power connector to P8 of main re alarm module, or to P2 of loop controller module, or to previous adder module
Power connector for next adder module
Data connector for next adder module
1
2
Basic Mode
Jumpers on the SGM-1004A Signal Adder Module and their functions:
FleX-NetTMInstallation and Operation Manual
JW1: Remove continuity jumper if this is not the last adder module installed. JW2, JW3, JW4, and JW5: Leave these jumpers open, on positions 2 and 3. J11 Terminals: Not connected.
Components
There are four green LEDs on the board, one for each signal zone. The LED will illuminate or flash following the signal rate sent to its zone. It will be off when the system is normal and they will illuminate when a signal zone is activated. The LED does not reflect what is happening on the signal zone, just that it is receiving data to activate
that signal zone.
Operation
There are two modes of operation for this module. The basic mode of operation does not involve any isolators connected to the signal zones. For this case, leave jumpers JW2, JW3, JW4 and JW5 as they come on pins 2 and 3, and do not make any connection to terminal block J11. The second mode provides mode is used when isolators are to be connected to the signal circuits. For further information on bell cut relays or isolators, please refer to the specific fire alarm panel manual or the isolator instruction manual.
Isolator Mode Jumpers for the Isolator Mode
JW2: Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 1. JW3: Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 2. JW4: Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 3.
JW5: Place jumper over pins 2 and 3 for the ability to connect an isolator on Zone 4.
J11: Wire these terminals to an alarm relay. These may be tapped if more signal modules are used in this manner.
Note: Jumpers JW2, JW3, JW4 and JW5 are positioned on pins 2 and 3 (right two pins with board
orientation as shown above) from factory.
ATTENTION: Discard jumpers on zones that are not configured for isolators.
37
Page 42
Module Settings
P1
P3
P4
FIELD WIRING TERMINALS
P2
JW1
FIELD WIRING TERMINALS
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
I1
I2
I3
I4
I5
I6
I7
I8
Figure 24: Hardwire Relay Adder Module (RM-1008A)
P2: Data cable to P6 or P5 of main fire alarm module, or to previous adder module. P1: Data connector for next adder module. P4: Power connector to P8 of main fire alarm module, or to previous adder module. P3: Power connector for next adder module. JW1: Remove continuity jumper if there are any more adder modules installed. If this is the last module installed, leave JW1 on. JP1-JP8: Move jumpers from pins 1 and 2 to 2 and 3 to connect relay commons between two or more relays.
Polarity Reversal and City Tie Module (Model PR-300)
Figure 25: Polarity reversal and city tie module
P1 P2
The following hardware configuration must be performed before installing the PR-300.
Table 5: PR-300 jumper settings
P1 Cable connects to P4 on the FX-2000N Main Fire Alarm Board
P2
JW4 Jumper JW4 is always left intact.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active (Not allowed by UL 864 refer to Configuration section). This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals will resound and the City Tie Box will be retriggered. Please refer to the Configurator for more information.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail. Please refer to the Configurator for more information.
Note: Jumper JW4 on the FX-2000N main fire alarm board must be removed if a city tie module is installed.
38
Not used. If a UDACT-300A is used in conjunction with a PR-300, then the UDACT-300A ribbon cable P1 is connected to header P2 of the PR-300.
JW4
Mounting hole for #6-32 screws
Mounting hole for
#6-32 screws
+ | - + | - + | -
ALARM
SUPV
TIE
CITY
REVERSAL
POLARITY
REVERSAL
POLARITY
Page 43
FleX-NetTMInstallation and Operation Manual
13:21 MON 2013-02-04
CONNECT RIBBON CABLE FROM P1 TO MIRCOM FIRE ALARM CONTROL PANEL
SYSTEM NORMAL
UDACT-300A MAIN BOARD:
There are two jumpers on the UDACT-300A which are used for operation/configuration purposes. Jumper JW1 is used to reset the default passcode. Jumper JW2 is required for configuring Configurator Software) the UDACT-300A. Refer to Figure 26 below for location of jumpers, cable connections, pushbutton and LEDs. Table 6 following, provides a description of the user items on the UDACT-300A.
(which can be done using the FX-2000N
Figure 26: UDACT-300A Board Layout
39
Page 44
Module Settings
Table 6: UDACT-300A Cable Connectors and Miscellaneous
Cable Connector Function
P1
P2 RS-232C/RS-485 Connection for computer configuration. U18 Connector for CFG-300 Configuration Tool Lamp Test button Press and hold this button to test all the UDACT-300A LEDs UR1 Potentiometer This potentiometer is for adjustment of the CFG-300 LCD contrast.
The following table lists all the LEDs located on the UDACT-300A board and states the function of each LED.
Ribbon Cable for connecting to P4 of FX-2000N main fire alarm module or to P2 header on the PR-300 if used.
Table 7: UDACT-300A List of LEDs and their Functions.
LEDs LED Function
Relay Line 1
Relay Line 2
RS-485 Status LED for communication, will flash when RS-485 communication is active. Common Trouble Steady amber for any troubles on the Fire Alarm panel or UDACT-300A.
Located below Line 1 terminal block. When Line 1 relay is energized, this green LED will illuminate
Located below Line 2 terminal block. When Line 2 relay is energized, this green LED will illuminate.
CPU Fail Steady amber for any on board CPU trouble.
Telephone Line 1
Telephone Line 2
Power ON Green LED is ON steady when power is supplied to the board.
The following table lists the user jumpers available on the UDACT-300A and their functions.
Telephone status indicator LED; Red when the line is in use, Amber when there is a line trouble.
Telephone status indicator LED; Red when the line is in use, Amber when there is a line trouble.
Table 8: UDACT-300A List of Jumpers for Operation and Configuration
Jumper Number Jumper Function
Normally open. Place jumper here and power down the UDACT-300A by
JW1
JW2
disconnecting P1 or power down the fire alarm panel (AC and Batteries), then power back to revert to default passcode. After reset, remove the jumper. Leave normally open.
Normally open to BLOCK remote configuration via modem, PC with a UIMA converter module or using the LCD and keypad at the UDACT-300A. Place jumper here to ALLOW any type of configuration. Remove jumper once configuration is complete.
Note: This module cannot be installed if a city tie module is used.
See the UDACT-300A Installation and Operation Manual L T-888 for more information.
40
Page 45
FleX-NetTMInstallation and Operation Manual
ALCN-792M Quad Loop Adder Module with ALCN-792D Daughter Board
The new Quad Loop Adder module provides two addressable loops plus an additional two loops as part of the daughter board ALCN-792D which is mounted over the ALCN-792M. The Quad Loop Adder module may be mounted over the main chassis of the FX-2000N Fire Alarm Panel or on any chassis that supports adder boards. Refer to the Display and Adder Modules section for mounting applications. This module is mounted using four #6 screws and (if necessary) four 1 1/2" spacers.
The power is supplied to the board via cable from the main fire alarm board or from
Power
RS-485:
DIP Switches:
Loop 1:
the previous loop controller module into the P1 POWER IN connector. Connect the P2 POWER OUT connector to the next loop controller module or other adder module. One power cable is supplied with this module.
The RS-485 cable comes attached at P3 and is either connected to P3 of the main fire alarm controller module or connected from the previous loop controller module or other adder board. If the next loop controller module is used, connect the RS-485 out at P4 to the next loop controller module; if it is not used, leave without connection.
Use the DIP switches to set the binary address of the board. SW1-1 is the lowest significant digit and ON is active. For example, an address of two would be created by turning SW1-1 OFF, SW1-2 ON and DIP switches SW1-3 to SW1-8 OFF. Refer to Appendix C for DIP switch settings.
This is the addressable loop for all initiating devices. Wire the loop as shown in
Figures 34, 35 and 36.
Loop 2:
Jumpers:
This is the addressable loop for all initiating devices. Wire the loop as shown in
Figures 34, 35 and 36.
A jumper is provided at JW2 for normal operation. To reset the board, leave the jumper at JW2 and momentarily short the pins at position JW1.
RS-232 Debug Interface: This connection if for factory use only. JTAG Port: This connection is for factory use only.
41
Page 46
Module Settings
The ALCN-792D Daughter Board provides another two addressable loops when connected to the ALCN-792M Quad Loop Adder Board. This daughter board is mounted over the ALCN-792M. Wire the two addressable loops on the ALCN-792D Daughter Board in the same manner the ALCN-792M addressable loops are wired.
Figure 27: ALCN-792D Daughter Board
Four mounting holes (mount to ALCN-792M board with screws and spacers provided)
+ - + -
LOOP (3)
S S + - + -
B
A
COM (-)
B
A
LOOP (4)
Connect ribbon cable from this board to the ALCN-792M board P6
P1
To Main Board Connector P6
Notes for ALCN-792D:
• All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines power-limited and fully supervised.
42
Page 47
Wire the ALCN-792M Quad Loop Adder module as shown in Figure 28 below.
Figure 28: ALCN-792M Quad Loop Adder Module
DIP SWITCHES ARE FOR THIS BOARD’S ADDRESS. SW1-1 IS THE LEAST SIGNIFICANT DIGIT (BINARY). ACTIVE POSITION IS ON.
Green ashing RS-485 heartbeat LED
ADDRESS DIP SWITCH
SW1
LOOP 1
+ - + -
B
81
A
Loop 1Active LED Loop 2 Active LED
LOOP 2
SS + - + -
COM (-)
RS-485
OUT
P4
JW2
- normally shorted, a jumper is here to enable watchdog timer.
FleX-NetTMInstallation and Operation Manual
B
A
GND FAULT
RS-485 CABLE IN
POWER CABLE
P5
P2
(OUT)
Wiring The Addressable Loops
There are two addressable loops present on this board that are wired in the same manner as shown in the wiring diagrams beginning with Figure 34. Although these drawings show only Loop 1;Loop 2 is wired in the same way as Loop 1 is.
Notes for ALCN-792M:
• All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines power-limited and fully supervised.
JW1
- normally open, pins are momentarily shorted to reset hardware.
P1
POWER CABLE (IN)
43
Page 48
Field Wiring
Field Wiring
Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in below. Refer to Appendix A for specifications and to LT-1023 for compatible devices.
ATTENTION: Do not exceed power supply ratings:
Main Chassis FX-2003-12N/DS or FX-2017-12N/DS: total current for NACs is 10A max.
Main Chassis FX-2009-12N/DS total current for NACs is 10A max.
Notes:
The terminal blocks are removable for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Figure 29: Main Fire Alarm Controller Board Field Terminal Connections
FX-2000N Main Fire Alarm Controller board
P3
RS485
TROUBLE
ALARM
P4
+
-
S
S
COM
NO
NC
COM
NO
NC
Shield one end of the RS-485 LOOP ONLY
RS-485 INTERFACE TO ANNUNCIATORS AND OTHER DEVICES (POWER LIMITED)
USE TWISTED SHIELDED PAIR 22 AWG UP TO 2000 FT. 20 AWG UP TO 4000 FT.
COMMON TROUBLE CONTACTS 24 VDC, 1 AMP RESISTIVE LOAD
AUXILIARY COMMON ALARM CONTACTS 24 VDC, 1 AMP RESISTIVE LOAD
MUST BE CONNECTED TO A LISTED POWER LIMITED SOURCE OF SUPPLY
SUPV.
SIG GND or COM(-)
44
COM
NO
NC
AUXILIARY COMMON SUPERVISORY CONTACTS 24 VDC, 1 AMP RESISTIVE LOAD
NOT USED
Page 49
FleX-NetTMInstallation and Operation Manual
Figure 30: Main Fire Alarm Control board Field Terminal Connections (continued)
ANALOG LOOP 2 CONNECTIONS (LOOP 0 AND LOOP1 ARE INTERNAL ADDRESSES FOR FIRST 8 CARDS AND SECOND 8 CARDS RESPECTIVELY
AUX. POWER
(POWER-LIMITED)
(POWER-LIMITED)
4-WIRE POWER SUPPLY
RTI INTERFACE
NAC 0 INDICATION
CIRCUIT 1
LOOP 2
+
B
-
A
+
-
+
-
+
-
TRB
TRL
+
+
-
-
ANALOG LOOP FIELD WIRING (CLASS A OR B) SEE ANALOG LOOP WIRING SECTION POWER-LIMITED, 22V DC, 400 mA MAX Maximum Loop Resistance 40 ohms
POWER-LIMITED, REGULATED
22V DC, 400 mA MAX 5 mV Ripple
BLK
D
BLU
RED & WHT
RTI
AUXILIARY POWER FOR REMOTE ANNUNCIATORS 24 VDC SPECIAL APPLICATION
1.7 AMPS MAXIMUM
POWER-LIMITE
SUPERVISED NAC # 0
TO INITIATING CIRCUIT
CONNECTION TO MIRCOM RTI REMOTE TROUBLE INDICATOR (SEE RTI INSTALLATION INSTRUCTION) BLK TO TRB+ BLU TO TRL-RED & WHT TO AUX. POWER COM+
END OF LINE RELAY LISTED S3403 MODEL A77-716B MANUFACTURED BY SYSTEM SENSOR
+
3
-
+
-
2
41
6
STYLE Y (CLASS B)
+
-
4-WIRE DETECTION DEVICE
+
DETECTION
-
+
POWER
-
WIRING
5
NAC 1 INDICATION
CIRCUIT 2
(POWER-LIMITED)
NAC 2 INDICATION CIRCUIT 1
(POWER-LIMITED)
NAC 3 INDICATION
CIRCUIT 2
(POWER-LIMITED)
NAC External Power Connection
E+
I+
_
+
+
-
SUPERVISED NAC # 1
STYLE Z (CLASS A)
WIRING
-
+
+
SUPERVISED NAC # 2
-
STYLE Y (CLASS B) WIRING
-
+
+
SUPERVISED NAC # 3
-
STYLE Z (CLASS A)
WIRING
-
Legend:
BELL, HORN, OR STROBE
3.9K 1/2W ELR LISTED S5434 MODEL MP-300 MANUFACTURED
BY MIRCOM
TS2
TS2 Terminal Block is located on the bottom right corner of the main re alarm board
+
NOT
_
USED
Notes:
• All circuits are power limited (unless marked otherwise) and must use type FPL, FPLR, or FPLP power limited cable.
• NACs are fully supervised and rated for 24 VDC special application, 1.7A max. They must be wired as
shown in the Wiring Tables and Information section.
45
Page 50
Field Wiring
Analog Loop Wiring
Figure 31: Loop Terminal Connections - Class B
S
S
FX-2000N
MAIN FIRE ALARM BOARD
+
LOOP 2
B
ANALOG LOOP CONNECTIONS
-
A
+
-
TWISTED PAIR WIRE
S
SO
F
M
C
M
s
C
s
TWO WIRES
H
F
H
2 Pair
Conventional Heat Sensors
and Manual Pull Stations
C
C
s
H
s
S
F
4-WIRE
RESET TA B L E
SUPPLY
+
-
+
INDICATING CIRCUIT
NAC 0
Notes:
• Terminal blocks are “depluggable” for ease of wiring.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power limited and fully supervised.
• Observe in and out polarity when using module and base isolators.
+
-
-
LEGEND
Addr essabl e Smo ke Detect or
S
wi th St andar d An alog Base
Addr essab le Therm al Sensor
H
wi th St andar d An alog Base
Conventional Smoke Sensor
C
s
Addressable Manual
F
Pull Station
End -Of - Lin e- Resist o r
Combination Hor n/ Str obe
Addressable Monit or Module
M
Addressable Supvr.
SO
Out pu t M od ule
46
Page 51
Figure 32: Loop Terminal Connections - Style 7
E
I
FX-2000N
F
I
ADDRESSABLE SMOKE DETECTOR WITH ISOLATOR BASE
FleX-NetTMInstallation and Operation Manual
TWISTED PAIR WIRE
S
I
I
F
I
MAIN FIRE ALARM BOARD
+
LOOP 2
B
ANALOG LOOP CONNECTIONS
4-WIRE
RESET TA B L E
SUPPLY
-
A
+
-
+
-
TWISTED PAIR WIRE
TWISTED PAIR WIRE
I
Conventional Heat Sensors and Manu al Pull Stat ion s
M
C
I
s
I
STYLE 7: For Style 7 operation use isolator bases for the detectors and use isolator modules (front and back as shown in this diagram) for the addressable pull stations, monitor modules, and control modules
LEGEND
Addr essabl e Smok e Detect or
S
with Isolator Base
Ad dr essab l e The rm al Sen sor
H
with Isolator Base
Conventional Smoke Sensor
C
s
Addressable Manual Pull Station
F
Fault Isolator Module
I
Addressable Monitor Module
M
H
ADDRESSABL THERMAL SENSO R WITH ISOLATOR BASE
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Isolators need to be close nipple connected to the device being protected.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power- limited and fully supervised.
47
Page 52
Field Wiring
F
ADDRESSABLE THERMAL SENSOR
ADDRESSABLE SMOKE DETECTORS
F
LEGEND
Addressable Smoke Det ector
Add ressabl e Th ermal Sensor
Addressable Manual Pull Station
F
Addressable Monitor Module
RO
TWISTED PAIR WIRE
TWISTED PAIR WIRE
S
H
S
S
H
Addressable Relay Output Module
M
M
M
RO
Conventional 4-Wire Smoke Detectors, Heat Sensors and Manual Pull Stations
ANALOG LOOP CONNECTIONS
LOOP 2
B
A
+
-
+
-
FX-2000N
MAIN FIRE ALARM BOARD
Figure 33: Loop Terminal Connections - Style 6 (Formerly Class A)
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines power-limited and fully supervised.
48
Page 53
Figure 34: Quad Loop Terminal Connections - Class B
Conventional Heat Sensors and Manual Pull Stations
2 Pair
F
LEGEND
Addressable Smoke Sensor with Standard Analog Base
Addressable Thermal Sensor with Standard Analog Base
Conventional Smoke Sensor
Addressable Manual Pull Station
Combination Horn/Strobe
Addressable Monitor Module
Addressable Supvr. Output Module
End-Of-Line-Resistor
TWO WIRES
S
H
S
C
s
C
s
C
s
F
F
H H
S
S
H
C
s
C
s
F
M
M
TWISTED PAIR WIRE
TWISTED PAIR WIRE
M
ANALOG LOOP 2
B
A
ANALOG LOOP 1
+
-
+
-
4-WIRE
RESETTABLE
SUPPLY
+
+ +
-
-
-
INDICATING CIRCUIT
NAC 0
FX-2000N MAIN FIRE ALARM BOARD
ALCN-792M QUAD LOOP ADDER MODULE
S
S
B
A
+
-
+
-
ANALOG LOOP 4
B
A
ANALOG LOOP 3
+
-
+
-
S
S
B
A
+
-
+
-
ALCN-792D DAUGHTER BOARD
SO
SO
This board is mounted over the ALCN-792M loop adder module to provide four adder loops total.
Wire loops 3 and 4 in the same manner as loops 1 and 2.
FleX-NetTMInstallation and Operation Manual
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power-limited and fully supervised.
49
Page 54
Field Wiring
LEGEND
Addressable Smoke Sensor with Isolator Base
Addressable Thermal Sensor with Isolator Base
Conventional Smoke Sensor
Addressable Manual Pull Station
Fault Isolator Module
Conventional Heat Sensors and Manual Pull Stations
F
Cs
F
ADDRESSABLE THERMAL SENSOR WITH ISOLATOR BASE
ADDRESSABLE SMOKE DETECTOR WITH ISOLATOR BASE
F
Cs
Addressable Monitor Module
H
S
S
H
TWISTED PAIR WIRE
TWISTED PAIR WIRE
TWISTED PAIR WIRE
TWISTED PAIR WIRE
I
I
I
I
I
I
I
I
M
M
I
STYLE 7: For Style 7 operation use isolator bases for the detectors and use isolator modules (front and back as shown in this diagram) for the addressable pull stations, monitor modules, and control modules
TWISTED SHIELDED PAIR WIRE IS NOT RECOMMENDED. IF USED THE SHIELD SHOULD BE TERMINATED AT THE TERMINALS MARKED SHIELD
ALCN-792M QUAD LOOP ADDER MODULE
ALCN-792D DAUGHTER BOARD
This board is mounted over the ALCN-792M to provide and additional two loops, for a total of four loops.
Wire loops 3 and 4 in the same manner as loops 1 and 2.
ANALOG LOOP 2
B
A
ANALOG LOOP 1
+
-
+
-
S
S
B
A
+
-
+
-
ANALOG LOOP 4
B
A
ANALOG LOOP 3
+
-
+
-
S
S
B
A
+
-
+
-
Figure 35: Quad Loop Adder Module Terminal Connections - Style 7
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Isolators need to be close nipple connected to the device being protected.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power-limited and fully supervised.
50
Page 55
FleX-NetTMInstallation and Operation Manual
Figure 36: Quad Loop Adder Module Terminal Connections - Style 6
M
ALCN-792M QUAD LOOP
F
H
ADDRESSABLE THERMAL SENSOR
F
ADDER MODULE
ANALOG LOOP 1
ANALOG LOOP 2
+
B
-
A
+
-
S
S
+
B
-
A
Conventional 4-Wire Smoke Detectors, Heat Sensors and Manual Pull Stations
M
S
ADDRESSABLE SMOKE DETECTORS
+
-
TWISTED PAIR WIRE
RO
S
TWISTED SHIELDED PAIR WIRE IS NOT RECOMMENDED. IF USED THE SHIELD SHOULD BE TERMINATED AT THE TERMINALS MARKED SHIELD
ALCN-792D DAUGHTER BOARD
ANALOG LOOP 3
ANALOG LOOP 4
+
B
-
A
+
-
S
S
+
B
-
A
+
-
This board is mounted over the ALCN-792M loop adder module to provide an addition two loops, for a total of four loops.
Wire loops 3 and 4 in the same manner as loops 1 and 2.
LEGEND
Addressable Smoke Sensor
S
Addressable Thermal Sensor
H
Addressable Manual Pull Station
F
Addressable Monitor Module
M
Addressable Relay Output Module
RO
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Loop wiring: maximum loop resistance is 40 ohms total. These lines are power-limited and fully supervised.
51
Page 56
Field Wiring
Line B
Line A
Line A
Line A
Line A
Line A
Line A
Line A
Line B
Line B
Line B
Line B
Line B
Line B
FNC-2000 Lobby Panel
FNC-2000
FNC-2000
FNC-2000
FNC-2000
FNC-2000
FNC-2000
STYLE 7 WIRING
RECOMMENDED CABLE:
BELDEN 5320 UJ or 5320UM Tyco Pyro CIC Draka Lifeline All above cables are 2x18AWG unshielded, low capacitance
FNC-2000 Fire Network Controller Module
The FNC-2000 Fire Network Controller modules are wired from terminals marked Line A, positive and negative (see
specific cable recommended in Figure 37) to the Line B terminals of the next FNC-2000 module. Use of shielded cable is not recommended. Wire from Line B terminals to Line A of the next FNC-2000 module. Start from the
lobby panel and wire to all the FNC-2000, wiring the last FNC-2000 back to Line B of the first FNC-2000 at the lobby panel for Class A.
Figure 37: Style 7 Wiring for the FNC-2000 Module
Network Wiring Specifications
Power-Limited and Supervised
Voltage: 9V Max
Current: 800mA
Frequency: 625K Hz
Line Loss: 25 ohms
4000 feet MAX wiring distance with twisted pair 18 gauge wire.
52
Page 57
FleX-NetTMInstallation and Operation Manual
TX 1RX 1
RX 1
RX 1
RX 1
TX1
TX1
TX 1RX 2
TX 2
TX 2
RX 2
RX 2
RX 2
RX 2
TX 2 RX 2
RX 2
TX 2
TX 2
TX 2
TX 2
RX 1
TX 1
TX 1
TX 1
RX 1
RX 1
FOM-2000-SP Lobby Panel
FOM-2000-SP
FOM-2000-SP
FOM-2000-SP
FOM-2000-SP
FOM-2000-SP
FOM-2000-SP
STYLE 7 WIRING
NODE 1
NODE 2
LAST NODE 63
NODE 3
NODE 6
NODE 4
NODE 5
Maximum Attenuation:
6.5dB or 2000m for 62.5/125
FOM-2000-SP Fiber Optic Network Adder Module
The FOM-2000-SP Fiber Optic Network Adder Module is wired with fiber optic cable. It is wired OUT through the transmit connectors marked TX and IN through the receive connectors marked RX.
Figure 38: FOM-2000-SP Fiber Optic Network Adder Module Wiring
53
Page 58
Field Wiring
Detection Module (DM-1008A) Terminal Connections
Wire devices to terminals as shown below. See wiring tables, and Appendix A for electrical specifications and
document LT-1023 for compatible devices.
Figure 39: Hardwire Detection Module (DM-1008A) Terminal Connections
STYLE B/D INI 1
STYLE B/D INI 2
STYLE B/D INI 3
STYLE B/D INI 4
INI 1+
INI 1-
INI 2+
INI 2-
INI 3+
INI 3-
INI 4+
INI 4-
INI 5+
INI 5-
INI 6+
INI 6-
INI 7+
INI 7-
INI 8+
SUPERVISED INITIATING CIRCUIT #1 (ALARM ZONE) (POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #2 (SUPERVISORY OR WATERFLOW ZONE) (POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #3
(ALARM ZONE) SEE STYLE D NOTE (POWER LIMITED)
STYLE D NOTE: Initiating circuits of the NK-DM-8A must be either all Style B (Class B) or all Style D (Class A). If Style D is selected, the number of circuits is cut in half.
Legend:
SMOKE DETECTOR
HEAT DETECTOR
SUPERVISORY OR WATERFLOW SWITCH (NO)
3.9K 1/2W ELR UL LISTED
STYLE B (CLASS B) WIRING
STYLE B (CLASS B) WIRING
STYLE D (CLASS A) WIRING
54
INI 8-
PULL STATION
Note:
• Terminal blocks are “depluggable” for ease of wiring.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Initiating circuits are fully supervised and rated for 22 VDC, 3 mA standby, 5 mV ripple, 50 mA max alarm. They may be configured as required. The alarm threshold is 21 mA. Maximum loop resistance is 100 ohms, 50 ohms per side.
• All conventional hardwire initiating circuits are Compatibility ID "A".
Page 59
FleX-NetTMInstallation and Operation Manual
Signal Module (SGM-1004A) Terminal Connections
Wire devices to terminals as shown in Figure 40 below. See Appendix A for signal module specifications, and
LT-1023 for compatible devices.
Figure 40: Hardwire Signal Module Terminal Connections
SGM-1004A NAC BOARD
IND 1+ (Y/Z)
NAC 1
(POWER LIMITED)
NAC 2
(POWER LIMITED)
NAC 3
(POWER LIMITED)
NAC 4
(POWER
LIMITED)
IND 1+ (Z)
IND 1- (Z)
IND 1- (Y/Z)
IND 2+ (Y/Z)
IND 2+ (Z)
IND 2- (Z)
IND 2- (Y/Z)
IND 3+ (Y/Z)
IND 3+ (Z)
IND 3- (Z)
IND 3- (Y/Z)
IND 4+ (Y/Z)
IND 4+ (Z)
IND 4- (Z)
SUPERVISED NAC #1
SUPERVISED NAC #2
SUPERVISED NAC #3
SUPERVISED NAC #4
STYLE Y (CLASS B)
WIRING
STYLE Z (CLASS A)
WIRING
STYLE Y (CLASS B) WIRING
STYLE Z (CLASS A)
WIRING
IND 4- (Y/Z)
Notes:
• The terminal blocks are “depluggable” for ease of wiring.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• SGM-1004A NACs are fully supervised and rated for 24 VDC special application, 1.7A max. They must be wired as shown in the Wiring Tables on page 60.
Legend:
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434 MODEL MP-300 MANUFACTURED BY MIRCOM
55
Page 60
Field Wiring
AUX RELAY 1 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 5 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 6 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 7 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 8 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 2 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 3 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
AUX RELAY 4 CONTACTS 28 VDC, 1 AMP RESISTIVE LOAD
RLY 1
RLY 5
RLY 6
RLY 7
RLY 8
RLY 2
RLY 3
RLY 4
RM-1008A Relay Module
COM
COM
COM
COM
NC
NC
NC
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
NO
NO
NO
Relay Module (RM-1008(A)) Terminal Connections
Relays are available as shown below.
Figure 41: Hardwire Relay Module Terminal Connections
Notes:
• All relay circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
• All relay circuits must be connected to a listed power limited source of supply.
ATTENTION:
• Do not connect 120 VAC directly to these relays.
56
Page 61
FleX-NetTMInstallation and Operation Manual
1
1
2
2
S
S
CITY TIE LOCAL ENERGY
POLARITY REVERSAL ALARM
POLARITY REVERSAL SUPV.
PRO TECT OR
1
1
2
2
S
S
1
1
2
2
S
S
1
1
2
2
S
S
+
+
+
-
-
-
+
+
+
-
-
-
DIN RA IL CONNECT IO N TO EARTH GROUND
DIN RA IL CONNECT IO N TO EARTH GROUND
POWER L IMIT ED
POWER L IMIT ED
PR-300
POWER LIMITED CABLE TYPE FPL, FPLR or FPLP MUST BE USED
FROM PR-300 TO PROTECTORS.
PRO TECT OR
PRO TECT OR
PRO TECT ED
PRO TECT ED
UNPROTECTED
UNPROTECTED
RATED - 24VDC FILTERED TRIP COIL - 14 Ohms, 250mA 5mV RIPPLE
24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT
24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT
CONFORMS TO NEMA STANDARD 2011 INTENDED FOR CONNECTION TO POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVING UNIT HAVING COMPATIBLE RATINGS
USE A SHORTING WIRE WHEN THE CITY TIE IS NOT USED
Polarity Reversal and City Tie Module (PR-300) Wiring
Wire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 42 below. Power Limited cable type FPL, FPLR or FPLP must be used.
For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown.
For use in Canada, the Protective Device is not required but still recommended.
Figure 42: Polarity reversal and city tie module terminal connection
Notes:
• Either the PR-300's city tie or polarity reversal interface may be used, but not both.
• The city tie interface is not power limited.
• Plug PR-300 ribbon cable (P1) into connector (P4) of the FX-2000N main fire alarm module.
• Cut jumper (JW1) on the PR-300 module in order to transmit a trouble condition to the monitoring station.
• Remove jumper plug from jumper JW4 on the main fire alarm module.
• The polarity reversal interface is power limited and must use type FPL, FPLR, or FPLP power limited cable.
• For polarity reversal operation, short the city tie connection.
57
Page 62
Field Wiring
UDACT-300A Main Board Terminal Connections
Wire the two telephone lines to RJ31X Connector terminals as shown in Figure 43 below. The UDACT-300A terminals are located on the top left hand corner of the board. If using a cellular or wireless service, use the Line 2
interface connection only.
Note: Most Authorities Having Jurisdiction (AHJ) do not allow the connection of premise telephones, see specifications for more information.
Figure 43: Telephone Line Wiring Diagram
1
23
76
8
BROWN
TTRR
Line 2 is Wired as shown for Line 1
TTRR
RED
GREEN
GREY
RES RESC.O. C.O.
LINE-1 LINE-2
RJ31X
4
5
TIP
RING
Public switch
Telephone company
wiring
TIP
RING
premise telephone
IF permitted
UDACT-300A
58
Page 63
FleX-NetTMInstallation and Operation Manual
P13
CONNECT GREEN EARTH GROUND WIRE TO MAIN MODULE PCB MOUNTING SCREW.
N
G
GREEN
TO 24 VDC BATTERY
BLACK
P11
P10
P12
+
BAT
RED
TO DEDICATED BRANCH CIRCUIT
L
L
20 Amp, 1 1/4” IN-LINE FAST ACTING FUSE
20 Amp, 1 1/4” SLOW BLOW FUSE
FUSE
GND
Power Supply Connections
The power supply is part of the main chassis. The ratings are outlined in the table below.
Model Electrical Input Ratings
FX-2003-12N/DS & FX-2017­12N/DS Main Chassis
FX-2009-12N/DS Main Chassis
All Chassis’ IN-LINE 20 Amp, 1 1/4” Fast Acting Fuse, positive side of Battery Connection
See Appendix A for more power supply specifications. Wire as shown below with proper gauge wire.
120 VAC, 60 Hz, 2A / 240VAC, 50hz, 1A
120 VAC, 60 Hz, 2A / 240VAC, 50hz, 1A
Power Supply
Total Current
12 amps maximum
12 amps maximum
Battery Fuse on Main
Module
20 Amp, 1-1/4" Slow Blow Non-replaceable Fuse
20 Amp, 1-1/4" Slow Blow Non-replaceable Fuse
Figure 44: Power Supply Connections
CAUTION:
• To prevent sparking, connect batteries after the system’s main A.C. power is turned ON.
• Do not exceed power supply ratings.
• Adhere to voltage markings as specified on labels.
59
Page 64
Field Wiring
Wiring Tables and Information
Table 9: Wiring Table for Initiating Circuits.
Wire Gauge Maximum Wiring Run to Last Device (ELR)
(AWG) ft. m
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
Note: Maximum loop resistance should not exceed 100 Ohms.
Table 10: Wiring Table for NACs
Main board NACs are rated for 1.7 amps each. The SGM-1004A NACs are rated for 1.7 amps each.
Total Signal
Load
18AWG 16AWG 14AWG 12AWG 0hms
Amperes ft. m ft. m ft. m ft. m Ohms
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.20 118 36 185 56 300 91 425 129 1.5
1.50 94 29 150 46 240 73 343 105 1.2
1.7 78 24 125 38 200 61 285 87 1.0
Maximum Wiring Run to Last Device (ELR)
Max Loop
Resistance
Note: Maximum voltage drop should not exceed 1.8 volts.
60
Page 65
Table 11: Analog Loop Wiring
FleX-NetTMInstallation and Operation Manual
Wire Gauge (use
twisted pair)
Loop Total (Out and In) Maximum
Twisted Pair Wire Run
(AWG) ft. m
12 10,000 3049
14 7971 2429
16 4980 1518
18 3132 955
Note:
• Line capacitance shall not exceed 0.5 mF.
• Inductance shall not exceed 1 mH.
• Resistance shall not exceed 40 ohms.
Power Wiring: Use Table 10: Wiring Table for NACs on the previous page to see the wiring information for the
remote annunciator being used.
RS-485 Wiring: See the wiring information for the remote annunciator being used. 4-Wire Smoke Wiring: The maximum allowable current is 0.2 amperes. The maximum allowed voltage drop is 1
volt. Refer to Table 10: WIring for NACs on the previous page.
Shield for Analog Loop Wiring: Only twisted pair is recommended, but if shielded twisted pair is used, wire shield
at the start and the end of the loop to the terminals marked Shield at the loop adder board.
61
Page 66
System Checkout
System Checkout
Before Turning the Power On
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the
main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe). Refer to NFPA 70.
8. Make sure to close the front cover plate before powering the system from main AC supply.
Note: When using Class A and isolators on an addressable loop, configure system as Class B, wire loop as
Class A, except do not connect the last device back to the panel. Do a system checkout. Then connect the return of the Class A circuit and configure as Class A.
Power-Up Procedure
1. After completing the above procedures, power up the panel (AC only). The green AC On LED and the Common Trouble LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the Battery Trouble LED should illuminate, the trouble buzzer should sound intermittently, and the Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity: the red wire is positive (+) and the black wire is negative (-). All indicators should extinguish except for the AC On LED and the LCD should show a normal status condition.
4. Auto-Configure or PC Configure the fire alarm control panel as described in the Configurator Guide.
Troubleshooting
Message Description
Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as well as the Common Trouble indicator and Trouble buzzer. To correct the fault, check
Circuit Trouble
Ground Fault
Battery Trouble
for open wiring on that particular circuit loop or see if the circuit disconnect switch is in the
ON or CLOSED position. Note: disconnecting a circuit will cause a system trouble (off-
normal position).
The FX-2000N panel has a Common Ground Fault Detector. To correct the fault, check for any external wiring touching the chassis or other earth ground connection.
Check for the presence of batteries and their condition. Low voltage (below 20.4V) will cause a battery trouble. If battery trouble condition persists, replace the batteries as soon as possible.
62
Page 67
Indicators, Controls, and Operation
LCD Display - four lines, 20 characters per line
Cursor buttons,
ENTER, MENU, CANCEL, INFO
Queue controls and indicators for Alarm, Supervisory, Trouble, and Monitor
Indicators for AC On, CPU Fault, and Ground Fault (GND FAULT)
Controls & Indicators for Signal Silence, General, Alarm, Acknowledge, Fire Drill, System Reset, Lamp Test
16 configurable bi-coloured zone indicators and 16 trouble indicators
Two configurable switches & amber LEDs
Refer to Figure 45 below for LED indicators, control buttons, and switches locations.
Figure 45: Indicators and Control Location
FleX-NetTMInstallation and Operation Manual
MGC Network
Fire Alarm Control Panel
Normal Condition
June 17, 2014
ALARM
QUEUE
A.C. ON
LED 8
LED 9
LED 10
LED 11
SUPV.
QUEUE
LED 12
LED 13
LED 14
LED 15
TROUBLE
CPU FAULT
MONITOR
QUEUE
QUEUE
GND FAULT
LED 16
LED 17
LED 18
LED 19
LED 20
LED 21
LED 22
LED 23
ENTER
SIGNAL
SILENCE
SWITCH/LED 0
GENERAL
ALARM
SWITCH/LED 1
ACKNOW-
LEDGE
SWITCH/LED 2
CONFIGURABLE
SWITCH/LED 3
MENU
CANCEL
INFO
FIRE
DRILL
SWITCH/LED 4
SYSTEM
RESET
SWITCH/LED 5
LAMP TEST
SWITCH/LED 6
CONFIGURABLE
SWITCH/LED 7
LED indicators are amber (trouble or supervisory), red (alarm), or green (AC On), and may illuminate continuously (steady) or at one of two flash rates:
Fast Flash: 120 flashes per minute, 50% duty cycle
Trouble Flash: 20 flashes per minute, 50% duty cycle
Note: The General Alarm LED and pushbutton, and the Acknowledge LED and pushbutton, are active only
on a system configured for “Two Stage.”
Paper Labels for Buttons and Indicators
Buttons and indicators are supplied with paper labels. These labels slide into the plastic label templates on the face of the panel. Paper labels allow for easy English / French selection and custom-printed zone information.
63
Page 68
Mircom
Common Indicators
Indicators Description
The Buzzer is activated by any of the following
Fire Alarm - Steady Supervisory Alarm - Fast Rate
Buzzer
AC On LED
Alarm Queue LED
Supervisory Queue LED
Trouble Queue LED
Monitor Queue LED
CPU Fault LED
Fire Drill LED The Fire Drill Indicator turns on steady amber while Fire Drill is active.
Acknowledge LED
General Alarm LED
Signal Silence LED
Ground Fault LED
Trouble - Trouble Rate Monitor - Configurable to sound at Trouble Rate
If the Buzzer is turned on in response to a Non-Latching Trouble or Supervisory, it will be turned off if the condition causing it goes away and there is no other reason for it to be on.
The AC On Indicator is activated steady green while the main AC power is within acceptable levels. It is turned off when the level falls below the power-fail threshold and the panel is switched to standby (battery) power.
The Common Alarm LED flashes red whenever the Panel is in Alarm. An alarm results from any alarm on any point or input programmed as Alarm or activation of the manual red General Alarm Button (if the Panel is set for Two Stage Operation). The Alarm Queue LED will go steady, once all alarms in the queue have been reviewed using the Alarm Queue button. Since all Alarms are latched until the Panel is reset, the Common Alarm LED will remain on until then.
The Common Supv. (Supervisory) LED flashes amber at the Fast Flash Rate when there is a Supervisory Alarm in the Panel, as the result of any Latching or Non­Latching Supervisory Circuit. The LED turns off if all Non-Latching Supervisory Circuits are restored and there are no Latching Supervisory Circuits active. The Supv. Queue LED will go steady, once all supervisory alarms in the supervisory queue have been reviewed using the Supv. Queue button. Latching Supervisory Alarms remain active until the Panel is reset.
The Common Trouble LED flashes amber at the Trouble Flash Rate when there is any Trouble condition being detected on the panel. It is turned off when all Non­Latching Troubles are cleared. The Trouble Queue LED will go steady, once all troubles in the trouble queue have been reviewed using the Trouble Queue button.
The Monitor Trouble Indicator flashes amber at the Trouble Flash Rate when there is any Monitor condition being detected on the panel. It is turned off when all Monitors are cleared.
The CPU Fault Indicator is flashed yellow at the Trouble Flash Rate if the CPU is faulty.
If the Panel is configured as Two Stage, the Acknowledge Indicator flashes amber at the Fast Flash Rate while the Auto General Alarm Timer is timing out. It turns on steady amber when that Timer is cancelled by activating the Acknowledge or Signal Silence buttons. If the Auto General Alarm Timer times-out and puts the Panel into General Alarm, the Indicator is turned off.
In Two Stage Operation only, the General Alarm Indicator is activated steady red when General Alarm is activated due to the red General Alarm button being pushed, a General Alarm Initiating Circuit being activated, or the Auto General Alarm Timer timing out. Once the General Alarm Indicator has been turned on it will stay active until the Panel is reset.
The Signal Silence indicator is flashed amber, at the trouble rate when Indication Circuits are Silenced either by the Signal Silence button, or by the Auto Signal Silence Timer. It is turned off when the Signals are re-sounded by a subsequent Alarm.
The Ground Fault Indicator flashes amber at the Trouble Rate when the Ground Fault Detector detects a Ground Fault on any field wiring. It turns off immediately when the Ground Fault is cleared.
64
Page 69
FleX-NetTMInstallation and Operation Manual
ENTER
MENU
CANCEL
INFO
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM
RESET
LAMP TEST
CONFIGURABLE
SWITCH/LED 3
CONFIGURABLE
SWITCH/LED 7
Common Controls
LCD Display:
The display is a large 4 line by 20 character back-lit alphanumeric LCD. It displays information on the panel and its devices. There are cursor buttons for menu selection and control. Information provided by the LCD display is an alarm log, an event log, current levels, device information, verification and maintenance reports.
Queue Buttons
Use the queue buttons to select a particular queue to review.
•Use the Alarm Queue button to view all alarms. Pressing this button will show the latest alarm on the LCD
display. Use and to view all previous alarms.
•Use the Supervisory Queue button to view all supervisory conditions. Pressing this button will show the latest
supervisory information on the LCD display. Use and to view all previous supervisory conditions on
the LCD display.
•Use the Trouble Queue button to view all trouble conditions. Pressing this button will show the latest trouble
condition on the LCD display. Use and to view any previous troubles.
• Use the Monitor Queue Button to show all monitor conditions. Pressing this button will show the latest monitor
information on the LCD display. Use and to view all queued monitor conditions.
Queues are displayed on the screen according to a priority sequence. Queue priority ranking from highest to lowest is as follows: alarm, supervisory, trouble, and monitor. If, for example, you are viewing a monitor queue and an alarm occurs, the display will immediately display the alarm condition. Also, if there is no activity on the system for 10 seconds after you have pressed a queue button, the display will switch to the highest priority condition.
Cursor Buttons
These four buttons around the Enter Button are used for up (previous), down (latest), left, and right selection of items on the LCD Display.
Enter Button
This button is used to select a displayed item on the LCD Display.
Cancel Button
This button is used to cancel an operation.
Menu Button
This button is used to initiate the FX-2000N Menu System.
Info Button
This button is used to get more details about a displayed item.
65
Page 70
Indicators, Controls, and Operation
System Reset Button
The System Reset button causes the Fire Alarm Control Panel, and all Circuits, to be reset
• Resets all Latching, Trouble Conditions
• Resets all Initiating Circuits
• Resets 4-Wire Smoke Supply and Aux. Power Supply
• Turns off all NACs
• Turns off Signal Silence, Ack & GA Indicators
• Turns off Fire Drill
• Stops and resets all Timers
• Processes inputs as new events
• Aux Disconnect is not affected
• Reset cannot be activated until the Signal Silence Inhibit timer has expired.
Signal Silence Button
Activation of the Signal Silence button when the Panel is in Alarm, turns on the Signal Silence Indicator and deactivates any Silenceable NACs. Non-Silenceable Circuits are unaffected. Signals will re-sound upon any subsequent Alarm. This button does not function during any configured Signal Silence Inhibit Timer period. It also does not function if the NACs are active as the result of a Fire Drill. In a Two Stage System, if the Auto General Alarm Timer has timed out, this Signal Silence button also performs the same function as the Acknowledge button.
Fire Drill Button
The Fire Drill button activates all programmed and non-Disconnected NACs, but does not transmit any Alarms via the City Tie, or Common Alarm Relay. Fire Drill may be programmed to operate specific NACs. Fire Drill is cancelled by pressing the button again (toggle switch), or if the Panel goes into a real Alarm.
Acknowledge Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is configured for Two Stage Operation, activation of the Acknowledge button while the Auto General Alarm Timer is timing (there is an Alarm in the Panel, but it is still in the First Stage), that timer is cancelled, and the Acknowledge Indicator is on steady amber.
General Alarm Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is configured for Two Stage Operation, activation of the General Alarm button immediately sends the Panel into Second Stage - General Alarm. It will also re-activate the Signals if they have been Silenced during General Alarm. The General Alarm condition remains active until the Panel is reset.
Lamp Test Button
Activation of the Lamp Test button turns all front panel Indicators on steady in whichever colour they would normally be activated and turns the buzzer on steady. If Lamp Test is active for more than 10 seconds, Common Trouble is activated.
66
Page 71
FleX-NetTMInstallation and Operation Manual
Single Stage Operation
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include any of the following: non-verified alarm, verified alarm, sprinkler alarm, water-flow alarm, and general alarm circuits. Any of these alarm inputs occurring when the panel is not already in alarm cause the following:
• The buzzer sounds steadily
• If fire drill is active, it is cancelled
• The Common Alarm LED turns on
• The Common Alarm relay activates if Aux disconnect is not active
• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• All non-disconnected NACs programmed to the input are activated provided that Aux disconnect is not active
• Non-disconnected strobes associated with the input are activated
• Non-disconnected signals associated with the input are activated at the evacuation rate
Subsequent alarms when the panel is already in alarm, cause the following:
• The alert buzzer sounds steadily
• If Signals have been silenced, they are resounded, the Signal Silence LED turns off, and the Auto Signal Silence timer, if configured, is restarted
• Any additional non-disconnected strobes associated with the input are activated continuously
• Any additional non-disconnected signals associated with the new input are activated at the evacuation rate
Two Stage Operation
In a two stage system, alarm inputs are either first stage (alert) inputs or second stage (general alarm) inputs. First stage inputs include inputs from the following types of circuits: non-verified alarm, verified alarm, sprinkler alarm, and water-flow alarm. Second stage inputs include alarms on the general alarm circuits, activation of the General Alarm button, or expiration of the Auto General Alarm timer. Any of these alarm inputs occurring when the panel is not already in alarm cause the following:
• The buzzer sounds steadily
• If fire drill is active, it is cancelled
• The Common Alarm LED turns on
• The Common Alarm relay activates if Aux disconnect is not active
• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• All Non-disconnected indicating programmed to the input are activated provided that Aux disconnect is not active
If the alarm is a second stage alarm,
• All non-disconnected strobe circuits are activated continuously
• All non-disconnected signal circuits are activated at the evacuation rate
• The General Alarm LED turns on.
If the alarm is a First Stage alarm,
• Non-disconnected strobe circuits programmed to that circuit are activated continuously
• Non-disconnected signal circuits programmed to that circuit are activated with the alert code
• The Auto General Alarm timer, if configured, starts
• The Acknowledge LED starts flashing.
Subsequent First Stage alarms when the panel is already in alarm, cause the following:
67
Page 72
Indicators, Controls, and Operation
• The buzzer sounds steadily
• If signals have been silenced as a result of the silence button or the Auto signal silence timer, signals are resounded as they were before signal silence, the Signal Silence LED turns off, and the Auto Signal Silence timer, if configured, is restarted
• If the panel is not already in General Alarm, additional non-disconnected signals programmed to the new input
are activated with the Alert Code (see Indicating (Signal) Circuit Types section).
• If the panel is not already in General Alarm and if the Acknowledge LED is on steady indicating that the Auto General Alarm timer has been Acknowledged the timer is restarted and the Acknowledge LED is extinguished.
A second stage alarm (general alarm) when the panel is already in alarm causes the following:
• The buzzer sounds steadily
• All non-disconnected signals are activated at the evacuation rate
• If the Signal Silence LED is on, it turns off and the Auto Signal Silence timer, if configured, is restarted
• The Acknowledge LED if on, turns off
Alarm inputs are latching: they remain active until system reset.
Note: If the system is configured for correlations, any second stage / general alarm condition activates all
NACs whether they are correlated or not.
Pre-Signal Operation
To configure the panel for pre-signal, all alarm inputs must be correlated to one NAC circuit that is wired to a Notification Appliance in the Control Room that is constantly monitored by an Operator. Using the FX-2000N Configurator, “Subsequent Alarm” in “Common System Status” must be correlated to turn on the Remaining NAC circuits in the system. To confirm the alarm (i.e. subsequent alarm) the operator can press the “General Alarm”
button on the panel or activate a Manual Station in the Control Room.
Note: Pre-Signal is not permitted to be used in Canada, unless approved by the AHJ.
68
Page 73
FleX-NetTMInstallation and Operation Manual
Circuit Types
The term circuits refers to an actual electrical interface, either initiating (detection) or indicating (signal). The term zone is a
logical concept for a fire alarm protected area, and will consist of at least one circuit. Often the terms zone and circuit are used interchangeably, but in this manual the term circuit is used.
Initiating (Detection) Circuit Type
Initiating (Detection) Circuit
Type
Non-Verified Alarm
Verified Alarm
Water-Flow Alarm
Description
This is a "normal" type of alarm which may have pull stations, smoke detectors, or heat detectors attached. Any activation of these devices will immediately result in an alarm condition in the fire alarm control panel. An alarm condition causes the associated circuit Status LED and the Common Alarm LED to illuminate red.
These alarms are verified by a reset and timing procedure, and may have Manual Stations, smoke detectors attached. Any activation of Manual Stations will result in an alarm condition in the fire alarm control panel within four seconds. Smoke detectors will be verified for a real alarm within 60 seconds depending upon the start-up time of the smoke detectors being used. If four seconds is too long a response time for pull stations, then they should be wired separately on a non-verified alarm circuit. An alarm condition causes the associated circuit Status LED and the Common Alarm LED to illuminate red. Verified Alarm is not permitted for heat detectors, 4-wire smoke detectors and smoke detectors with built-in alarm verification. Refer to Appendix D Alarm Verification for details.
An alarm for water-flow sensors. These alarms are identical to normal non-verified alarms except that any NACs programmed to these circuits (all are by default) are non­silenceable. Also, if water-flow retard operation is enabled, then these circuits are sampled every one second; if ten samples are active within any 15 second interval, the water-flow alarm is confirmed and processed. An alarm condition causes the associated circuit Status LED and the Common Alarm LED to illuminate red.
Note: Do not use the retard operation with any external retarding device; maximum retard may not exceed 120 seconds.
Sprinkler Alarm
General Alarm
Non-Latching Supervisory
Latching Supervisory
An alarm for sprinkler flow sensors. These alarms are identical to normal non-verified alarms unless the water-flow retard operation is enabled. If water-flow retard operation is enabled, then these circuits are sampled every one second; if ten samples are active within any 15 second interval, the sprinkler alarm is confirmed and processed. An alarm condition causes the associated circuit Status LED and the Common Alarm LED to illuminate red.
Note: Do not use the retard operation with any external retarding device; maximum retard may not exceed 120 seconds.
These alarms provide remote general alarm such as for remote key switches. In a two stage system, these inputs perform exactly the same function as the front panel or remote annunciator general alarm button. In a single stage system, these inputs act the same as non-verified alarms, but if correlations are enabled, general alarm initiating
circuits are correlated to all NACs.
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit Status LED and the Common Supervisory LED to illuminate amber. The buzzer will sound continuously. If the circuit activation is removed, the supervisory condition will clear (so long as there are no other supervisory conditions in the system) and the circuit Status LED will extinguish.
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit Status LED and the Common Supervisory LED to illuminate amber. The buzzer will sound continuously. If the circuit activation is removed, the Supervisory condition will
not clear.
69
Page 74
Indicators, Controls, and Operation
Initiating (Detection) Circuit
Type
Monitor
Trouble-Only
This is a supervised general purpose non-latching input used mainly for correlating to a relay circuit. No other system condition occurs as a result of its activation (short-circuit), although it is supervised for trouble (open-circuit).
This circuit is used for monitoring a trouble condition from an external device such as a Mircom Series 500 Audio System. Both open and short circuits generate a non-latching trouble condition.
Description
Indicating (Signal) Circuits Types
Indicating (Signal) Circuit Type Description
For audible devices such as bells and piezo mini-horns that may be silenced either manually or automatically. While sounding, these follow the pattern appropriate for the
Silenceable Signal
Non-Silenceable Signal
condition: the configured evacuation code (default is temporal code) during single-stage alarm, or two stage general alarm, or the alert code during a two stage system's alert (first) stage.
For audible devices such as bells and piezo mini-horns that may not be silenced either manually or automatically. While sounding, these follow the pattern appropriate for the condition: the configured evacuation code (default is temporal code) during single-stage alarm, or two-stage general alarm, or the alert code during a two stage system's alert (first) stage.
For audible devices such as bells and piezo mini-horns that may be activated in code. The code consists of 4 digits with each digit consisting of 1-15 pulses on the signals.
Coded Signal
Strobe For visual devices such as strobes that use no code patterns (they are continuous).
Each coded circuit can sound the complete code 1 to 15 times after which signals go silent or revert to programmed General Alarm rate.
Note: The NFPA-72 and ULC-S527 specify temporal tone. However , for retrofit s of systems that were previously approved, coded signalling is allowed.
70
Page 75
Evacuation Codes
0.5s
0.5s
1.5s
0.5s
0.5s
5s 10s
CONTINOUS
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
0.5s
2.5s
ALERT CODE
Single stage codes
Continuous On 100% of the time Temporal Code 3 of 0.5 second on, 0.5 second off then, 1.5 second pause March Code 0.5 second on, 0.5 second off California Code 5 seconds on, 10 seconds off
Two-stage codes:
Alert Code 0.5 second on, 2.5 seconds off
General Alarm Evacuation code as selected from above.
Figure 46: Evacuation Codes
FleX-NetTMInstallation and Operation Manual
71
Page 76
Configuration
Configuration
The FleX-NetTM network system which includes FX-2003-12N/DS, FX-2009-12N/DS, FX-2017-12N/DS, FX-2000ND/S and FX-2000MNS is configured using Mircom software MSW-025.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature or option Permitted in UL 864? (Y/N) Possible settings Settings permitted in UL 864
Alarm Transmit Silence No Enabled or Disabled Disabled or unchecked
Configuration Backup, Query and Fast-Forward
The panel supports previous, current and next configuration. The panel can be load configured without taking the panel off-line. Configuration reverts back to previous or moves to future configuration through front-panel menu.
OPEN Graphic Navigator Software Package
This software package (OPEN GN) allows 3D graphic display of premises and devices. It provides unlimited floor plans and events, node and job support. It supports input file formats for floors such as .svg, .dxf, .pdf, .png, .wmf, .jpeg. Device icons and state animations can be customized.
Ethernet Port
Integrated TCP/IP Stack, Hardware based MAC address. Provides a fully configurable IP address. Use this ethernet port to connect to OPEN graphics software. This port also provides web server for diagnostic and system report via LAN or WAN connection on-site or remotely.
Boolean Logic Engine
Boolean logic functions are now available within the configuration software. Sophisticated logic functions such as:
AND, OR, NOT, ANY n of m, >, <, >=, <>
Built-in timers or user configurable timers and intervals and schedules available to support UUKL operations.
uBoot Based BootLoader
This program (inherent in the configuration) provides leading technology that allows a choice of multiple configuration files or firmware revisions to support site-specific requirements.
The FleXBoot system tuning and optimization.
TM
shell offers UNIX style commands for directory listing, log download, diagnostic probing and
72
Page 77
FleX-NetTMInstallation and Operation Manual
1 twisted pair for ARCnet Network, Audio and Telephone
Node 1
CACF Central Alarm and Control Facility
-addressable re alarm control
-master telephone handset
- telephone zone selector modules
-master paging microphone
-paging zone selector modules
-bypass switch modules
-fan damper control modules
-LED annunciator modules
Five Telephone Audio Channels
Audio Channels for paging, pre-recorded messages and tones
Addressable Loop
Five Telephone Audio Channels
Audio Channels for paging, pre-recorded messages and tones
Addressable Loop
MMX-BB-1001R
MMX-QBB-5001R
MMX-QBB-5001R
M
Typical FleX-NetTM System Layouts with Audio
The following figures show two typical applications for the FleX-NetTM system with audio.
Figure 48 below shows a typical FleX-Net combination Fire Alarm and Audio Network systems as Node 2 and 3. The diagram also shows addressable fire alarm loops, paging and telephone connections and audio cabinets.
Figure 48: Typical FleX-NetTM System with Audio Nodes
TM
system layout with the main lobby control panel as Node 1 and the
73
Page 78
Typical FleX-NetTM System Layouts with Audio
CACF Node 1
Node 2
Node 3
Node 4
RAXN-LCD in a BB-1003R
RS-485
RS-485
RAXN-LCD in a BB-1001R
Node 5
BBX-2000R
FX-2017-12N in a BBX-1072AR
FX-2003-12N in a BBX-1024R
BBX-2000R
Optional 1 pair for Paging Audio 1 pair for Telephone Audio
1 pair for ARCnet Network
Class A Wiring
NOTE: Wiring for ARCnet Network, Audio and Telephone can be as shown (3 pairs) or 1 pair as shown in Figure 46
Figure 49 below shows the FleX-Net
TM
fire alarm and audio shown within the Integrated Network Fire/Audio cabinet
as Node 2 and 3. Paging and telephone devices are hooked up to Nodes 2 and 3.
Figure 49: Typical FX-2000N Network System with Audio and Non-Audio Nodes
74
Page 79
FleX-NetTMInstallation and Operation Manual
System Components for the Integrated Fire/Audio Cabinet
Network Fire Alarm
Model Description
12 Amp Large Main Chassis. This large main
chassis comes complete with one Analog Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amp each), a 4 line by 20 character back-lit LCD display, 16 zone LED annunciator and a 12
FX-2000ND
ampere power supply which charges 17-65 AH batteries. The Integrated Fire and Audio system supports the FNC-2000 Network Controller Module, the ANC-5000 Audio Network Controller Module and the TNC-5000 Telephone Network Controller Module. This chassis mounts in the BBX-2000 backbox.
Network Controller Modules
FX-2000NDS Same as above. Different front panel appearance.
Model Description
Provides network capability for the FX-2000N Fire Alarm panel. One module is required per
FNC-2000
one network node panel. The FNC-2000 Fire Network Controller module is mounted in position 2 over the FX-2000ND main board.
Audio Network Controller module. The ANC­5000 Audio Network Controller module is
ANC-5000
mounted on a metal plate (which is packaged with the FX-2000ND) and then the plate is mounted into BBX-2000 backbox in position 1 of the QMB-5000N Card Cage.
TNC-5000
Telephone Network Controller module. The TNC-5000 Telephone Network Controller module is mounted below the ANC-5000 Audio Network Controller module and both are mounted on a metal plate and then the plate is mounted into the BBX-2000 backbox in position 1 of the QMB-5000N Card Cage.
75
Page 80
System Components for the Integrated Fire/Audio Cabinet
Fiber Optics Module
Model Description
Adder Modules
Auxiliary Modules
FOM-2000-SP
Model Description
DM-1008A, SGM-1004A, RM-1008A
Model Description
PR-300 Polarity Reversal and City Tie Module
Connects to the FNC-2000 Fire Alarm Network Controller Module and allows fiber optics cabling.
Loop and Circuit Adder Modules
Programmable Modules
UDACT-300A Digital Communicator/Dialer Module
Model Description
FDX-008 Fan Damper Module
Programmable Input Switches Module (mounts
IPS-2424/DS
with the FX-2009-12N/DS and can also be part of the RAXN-LCD)
76
Page 81
FleX-NetTMInstallation and Operation Manual
FleXNetTM Mass Notification System (BBX-FXMNS) Enclosure
This enclosure can accommodate all existing modules, except the QMP-5101N Network Master Paging Control module and the QMT-5302N Master Firefighters’ Telephone. New models, QMP-5101NV vertical mounting master paging microphone and QMT-5302NV Master Telephone panels are used instead to mount within the BBX-FXMNS Enclosure. The BBX-FXMNS enclosure includes a backbox and a two part door and display deadfront chassis.
Figure 50: BBX-FXMNS Enclosure
22.4”
*/$0.*/(
$0..0/5&-
."45&35&-
$"--
5306#-&
5306#-&
$0//&$5
$-&"3"--
62.7”
7.6”
61.1”
'"/%".1&3
9”
20”
Notes: When using the BBX-FMNS as a Mass Notification System (ACU) refer to Appendix J.
77
Page 82
FleXNetTM Mass Notification System (BBX-FXMNS) Enclosure
16.5”
25”
33.5”
BBX-FXMNS Backbox
Dimensions between mounting holes
QMB-5000N Audio Card Cage (Space for an ANC-5000 Audio module, TNC-5000 Telephone module and four amplifiers)
FX-2000MNS Main Fire Alarm Board and backplate (3 adder modules may be mounted over the main board, similar to the FX-2003-12N, see page 21)
PS-2040 Power Supply
Mounting Holes
Mounting position for 2 adder modules.
Mounting positions for 2 adder modules in each spot.
Mounting Holes
Mounting Holes
Transformer and Card Cage Connection
Transformer and AC IN Connection
Battery Disconnect Board
Transformer and FX-2000MNS Alarm Board Connection
Batteries (maximum 40 AH)
The BBX-FXMNS backbox supports the QMB-5000N amplifier backplane and card cage which holds up to four amplifiers, the FX-2000MNS Fire Alarm main board chassis and PS-2040 Power Supply.
Figure 51: BBX-FXMNS Backbox Dimensions and Contents
78
Page 83
Figure 52: BBX-FXMNS Enclosure Complete View
BBX-FXMNS FRONT DOORS AND DEADFRONT CHASSIS
FleX-NetTMInstallation and Operation Manual
BBX-FXMNS BACKBOX
79
Page 84
FleXNetTM Mass Notification System (BBX-FXMNS) Enclosure
Door Hinge
Door Hinges
Door Hinge
Modules are mounted from the backside of the middle door using the screws provided
Back side of BBX-FXMNS inner door
Figure 53: Mounting Vertical Microphone and Telephone Modules in the BBX-FXMNS
80
Page 85
FleX-NetTMInstallation and Operation Manual
16.5”16.5”
25” 25”
33.5” 33.5”
BBX-2000 Enclosure
QMB-5000N Audio Card Cage
FX-2000ND Main Chassis with provision to mount FNC-2000 Network Controller Module and 2 adder modules/loop controllers
PS-2040 Power Supply and space to mount 6 adder modules/ loop controllers
Batteries (maximum 40 AH)
Metal plate with ANC-5000 and TNC-5000 modules aboard fit into position 1 of the QMB­5000N Audio Card Cage
QAA Amplifiers fit into slot positions 2, 3, 4 and 5.
Integrated Fire/Audio Cabinet Mechanical Installation
The Integrated Fire/Audio Cabinet is the network fire alarm and audio floor or node panel. It is mounted into the BBX-2000 backbox and door. Mount the backbox onto the wall using six #8 screws to secure the backbox to the wall. The backbox is surface mounted only; the dimensions for the mounting holes are shown in Figure 54 below. The Integrated Fire/Audio Cabinet consists of the Audio Card Cage, FX-2000ND Deep Chassis with FX-2000N Main Control board/2 Amp Battery Charger, and PS-2040 10 Amp Fire Alarm/30 Amp Audio Power Supply. Batteries are mounted in the tray located at the bottom of the enclosure.
Figure 54: BBX-2000 Enclosure with the Integrated Fire and Audio System
81
Page 86
Integrated Fire/Audio Cabinet Mechanical Installation
Each part has to be mounted into the backbox by the user. The QMB-5000N Audio Card Cage is mounted in the top left side of the backbox over the four studs with the #8 Hex nuts provided. The FX-2000ND Main Chassis is mounted below the audio card cage over the four studs provided using four #8 Hex nuts. The PS-2040 power supply is mounted under the main chassis with #10 Hex nuts, the power supply cover is mounted over the transformer and over the two studs using the #6 hex nuts and the batteries are placed on the battery tray which comes mounted at the bottom of the backbox.
Figure 55: Perspective View of BBX-2000 Enclosure with Integrated Fire and Audio System
7.75”
20”
82
60”
Page 87
FleX-NetTMInstallation and Operation Manual
QBB-5001(R)
MATERIAL: 16 GA (0.069") CRS
FINISH: DOOR PAINTED WHITE OR RED BACLBOX PAINTED BLACK
ENCLOSURE
WIDTH
HEIGHT
DEPTH
24 1/4" 41" 8"
FLUSH TRIM WIDTH HEIGHT
QBB-5001TR 26 13/16" 43 9/16"
MATERIAL: 16 GA (0.069") CRS
FINISH: PAINTED BLACK
DOOR
MATERIAL: 14 GA (0.075") CRS
QBB-5001TR FLUSH TRIM
BACKBOX
Mechanical Installation for the Expansion Audio Cabinet
QBB-5001/R Expansion Audio Cabinet Installation
Expansion audio cabinets are mounted as shown in Figure 56 below. The QBB-5001/R is the backbox and door. The QBB-5001/R backbox may be flush or surface mounted. The QBB-5001TR is the metal flush trim. Install all cabinets and enclosures empty. Pull all required wiring in through the conduit holes provided (must be punched out). Do not mount the modules until mechanical installation is complete and all wires have been fed into the cabinets and enclosures.
Figure 56: Expansion Audio Cabinet Mechanical Installation
Notes:
• It is extremely important to connect the audio cabinets earth-ground point (chassis ground) to the earth ground.
• The power supply mounts on the bottom left-hand corner of the backbox and the batteries are placed on the bottom to the right of the power supply. Conduits should be brought in only through the conduits provided at the bottom right hand corner of the cabinet.
83
Page 88
Mechanical Installation for the Expansion Audio Cabinet
ALARM QUEUE
SUPV.
QUEUE
TROUBLE
QUEUE
MONITOR QUEUE
A.C. ON
CPU FAULT
GND FAULT
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM RESET
LAMP
TEST
ENTER
MENU
CANCEL
INFO
LED 0
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
CONFIGURABLE SWITCH/LED 3
CONFIGURABLE SWITCH/LED 7
Mircom FX-2000
Fire Alarm Control Panel
Normal Condition
April 25, 2003
AC LINE CIRCUIT
BREAKER
23 1
5
6 4
8
9 7
FX-2000ND FIRE ALARM MAIN BOARD
Slot 3 is reserved for PR-300 or UDACT-300A only. If not required, this slot can be used to mount (3) any of the adder modules.
The recommended mounting position is 2 for the FNC-2000. The FOM-2000-SP board if used, is mounted over the FNC-2000 board.
Slot 3 is reserved for PR-300 or UDACT-300A only. If not required, this slot can be used to mount (3) any of the adder modules.
The recommended mounting position is 2 for the FNC-2000. The FOM-2000-SP board if used, is mounted over the FNC-2000 board.
FX-2000ND Fire Alarm Chassis Layout
Exterior View Interior View
The FX-2000ND mounts into the BBX-2000 below the QMB-5000N Audio Card Cage and above the PS-2040 Power Supply (view Figure 54).
FX-2000NDS Fire Alarm Chassis Layout
Exterior View Interior View
The FX-2000NDS mounts into the BBX-2000 below the QMB-5000N Audio Card Cage and above the PS-2040 Power Supply (view Figure 54).
84
23 1
6 4
9 7
5
8
FX-2000NDS FIRE ALARM MAIN BOARD
Page 89
FleX-NetTMInstallation and Operation Manual
Integrated Fire/Audio Cabinet - Audio Module Placement and Internal Wiring
The modules that mount into the Integrated Fire/Audio Cabinet audio card cage are the amplifier modules. Up to four amplifiers may be installed in each Integrated Fire/Audio Cabinet with one of the four as a backup. Slot #1 is used for the ANC-5000 and/or TNC-5000 modules.
Figure 57: Integrated Fire/Audio Cabinet Internal Power Wiring.
Use wire ties secured to the backbox, in positions as shown, to assure that these NON POWER­LIMITED wires remain at least 1/4 inches away from wires that are connected to POWER­LIMITED circuits.
Gray Area marks the location for all non-power limited wiring.
Battery Disconnect Board has a replaceable fuse: F1 is a fast acting 32V 40A Fuse.
Orange-White-Orange Wires connected from the transformer to this terminal block
Battery Fuse F1 32V, 40A MAX Fast-acting
CONNECTORS FOR MULTIPLE
QMB- 5000N EXPANSION CARD CAGES
SLOT #1 CONNECTOR
FOR TNC-5000 AND
ANC-5000 BOARDS
IN OUT
CONNECTOR AND TERMINALS NOT USED
Battery Disconnect Board
BATTERY
Red
+
+
SLOTS #2 - #5
CONNECTORS FOR
QAA- STYLE AMPLIFIERS
Red (positive) and Black (negative) wires from the Amplier backplane (soldered on board) are connected to lug terminals on the Battery Disconnect board
TRANSFORMER
-
Orange-White-Orange
(MUST BE IN CORRECT ORDER)
-
+
+
-
-
Two brown wires
-
+
connected from the transformer to the bridge rectier.
Drawing is shown for clarity of connections. Required separation of non-power limited and power limited wiring must be provided with barriers or nonconductive sleeving.
Right side of box is reserved for all power limited wiring.
AC Power IN G N 120VAC or 240VAC Wire as per label.
Drawing not to scale. Boards enlarged to show required wiring.
Green (GND), black (N), red (120V AC) and yellow (240V AC) wires connected from the transformer to the AC Input Terminals.
Black
12 VDC BATTERY
-
Connected to Batteries
+
Red
12 VDC BATTERY
85
Page 90
Integrated Fire Alarm Connection
Integrated Fire Alarm Connection
The FX-2000ND/S Chassis consists of the Network Fire Alarm main board and chassis.
Battery Power
The power cable is used to provide power from the batteries to the FX-2000ND/S Fire Alarm main board and the audio card cage motherboard. Power from the batteries is first directed to the Battery Disconnect Board, from this board the power is connected to the main fire alarm board and the audio card cage. The red and black wires are soldered on the audio card cage and the spade ends are connected to the red (+) and black (-) connectors on the Battery Disconnect Board. The extra positive and negative wires (from the Y power cable) are connected to the spades on the main fire alarm board and the spade connectors from the bottom of the Battery Disconnect Board are hooked up to the batteries, red (+) and black (-). Refer to Figure 57.
Transformer Power
The orange, white, orange wires are soldered on the audio card cage motherboard. They are connected to the terminal block located on the power supply cover (which covers the transformer) in the order left to right, orange­white- orange. The orange-white-orange wires from the transformer are connected to the top terminals located on the power supply cover in the same order (orange-white-orange). The yellow wire is connected to the 240V terminal, the red wire from the transformer (120V) is connected to the 120V terminal on the fire alarm chassis, the black wire (from the transformer) connects to the N terminal and the green wire (from the transformer) to the G (Ground) terminal all located on the fire alarm chassis. If using 240V supply connect the yellow wire to the 240V terminal, but do not connect the 120V red wire. The brown wires are connected to the bridge located on the fire alarm chassis. Refer to Figure 57.
86
Page 91
FleX-NetTMInstallation and Operation Manual
12 VDC BATTERY
12 VDC BATTERY
INLINE FUSE 50A
- BATTERY +
XFORMER
Black
Black
120 or 240 VAC Input
IN OUT
Red
Red
QBC-5000N
QMB-5000B Motherboard
BATTERY
CHARGER
CONNECTORS FOR MULTIPLE QMB-5000B MOTHERBOARDS
SLOT #1 CONNECTOR IS NOT USED
SLOTS #2 - #8
CONNECTORS FOR
QAA- STYLE AMPLIFIERS
CONNECTOR FOR QBC-5000N
BATTERY CHARGER
QPS-5000N
POWER SUPPLY
SECURE QPS-5000N POWER SUPPLY TO BACKBOX WITH LUGS AND NUTS PROVIDED
TS1
JW1
Orange-Yellow-Orange (MUST BE IN CORRECT ORDER)
This represents the Battery Disconnect Relay located on the left side of the box.
Battery Disconnect Relay
L N
QBB-5001/R Expansion Audio Cabinet Module Placement
The modules that mount into the QBB-5001/R expansion audio cabinet include the QPS-5000N Power Supply, the QMB-5000B Motherboard, and the QBC-5000N Battery Charger. Module interconnects are shown in Figure 58. There is no module installed into Slot #1 of the QMB-5000B Motherboard, as shown below.
Up to seven Amplifier Modules (Models QAA-5230-70/25, QAA-5230S-70/25, QAA-5415-70, QAA-5415-25 and/or QAA-5160-70/25) may be installed into Slots #2 to #8 on the QMB-5000B motherboard. The total maximum wattage per expansion audio cabinet is 360 Watts.
Figure 58: QBB-5001/R Expansion Audio Cabinet Module Placement
Components on the amplifiers should be facing left when inserted into motherboard. Make sure connections for the power supply and battery charger are as shown above. Place all amplifier modules from left to right in slot positions two to eight. Connect cable MD-525 from the QMB-5000N (inside the BBX-FXMNS or Integrated Fire/Audio Cabinet) to the IN connector at the top left corner of the QMB-5000B Motherboard. Connect cable MD-525 from the QMB-5000B Motherboard (connection marked OUT in the top left corner) to the next expansion audio cabinet QMB-5000B Motherboard (connection marked IN) if another audio cabinet is used. Daisy chain all other expansion audio motherboards used, up to a total of three.
87
Page 92
Installing and Removing Amplifiers
QPS-5000N Power Supply Connection
Two jumpers are provide as shown in figure below for 120 VAC connection. For 240 VAC application, remove both jumpers and replace one jumper between the two middle terminals. The two terminals on the right are N (neutral), L (live) for AC voltage connection. The three terminals on the left are connected from the QMB-5000N motherboard as orange-white-orange (left to right) in that order.
Neutral (White)
Ground Braid
120 VAC or 240 VAC
Ground
Connect AC ground to Earth Ground stud located in the QBB-5001 Backbox.
Earth Ground stud in QBB-5001 Backbox
120/240 VAC SELECTION
120 VAC Select
Default Jumper Positions
L N
OR
240 VAC Select Discard unused Jumper
L N
Orange- White-Orange Wires connected to QMB-5000B Motherboard
QPS-5000N
Live (Black)
L N
Installing and Removing Amplifiers
ATTENTION: Improper installation or excessive force will damage the motherboard and modules being
installed or removed.
Installing QAA Amplifier Modules
1. Hold the amplifier to be installed by the backplate edges. Do not handle, push or pull any of the components on
the amplifier (especially not the transformer) as this will damage those components.
2. Line up the amplifier being installed with the two plastic runners on the card cage and slide the amplifier back to the point where the amplifier just about touches the pins on the QMB-5000N/B motherboards.
3. Make sure that the amplifier is square with the motherboard.
4. Gently push the amplifier forward to line up the amplifier connector with the motherboard pins. Once you have a sense of feel that the amplifier connector and the motherboard pins are properly lined up, place one thumb on the top edge of the backplate and the other thumb on the bottom of the backplate and carefully push the
amplifier in. You should hear a slight thud sound when the amplifier is snapped into place.
Note: If the amplifier connector is not properly lined up with the motherboard pins, or if excessive force is
used, the pins on the motherboard can be damaged.
Removing the QAA Amplifier Modules
1. Disconnect all cables connected to the amplifier. Do not handle, push or pull any of the components on the
amplifier (especially not the transformer) as this will damage those components.
2. Place the forefinger of one hand on the top inside edge of the front heat sink (the heat sinks are the two long silver channel-like metal covers opposite the backplate) and the forefinger of the other hand on the bottom edge of the backplate behind the card cage frame.
3. Carefully pull and rock the amplifier forward until the amplifier connector is disconnected from the motherboard pins.
4. Holding the amplifier firmly by the backplate edges, slide the amplifier forward and completely remove it from the card cage.
ATTENTION: Power should be disconnected before removing and inserting modules.
88
Page 93
FleX-NetTMInstallation and Operation Manual
Multiple QBB-5001/R Cabinet Connections
When multiple QBB-5001/R audio cabinets are used in an installation, each has its own QPS-5000N Power Supply, QBC-5000N Battery Charger, and batteries. A total of three audio cabinets may be used by simply interconnecting with Mircom MD-525 Extension Cables from the QMB-5000N "Out" Connector, to the "In" Connector on the next QMB-5000B motherboard.
QMB-5000B Motherboards #1, #2, and #3
Up to a maximum of three QBB-5001/R Audio Cabinets may be connected to a BBX-FXMNS or Integrated Fire/ Audio Cabinet. The first QMB-5000N “Node” Motherboard has a connection from the FX-2000ND or FX-2000MNS. The next three QBB-5001/R Audio Cabinets contain QMB-5000B Motherboards #1, #2 and #3 which are connected with the regular ribbon cable MD-525. The MD-525 cable is connected from the output connector on the QMB­5000N “node” motherboard to the input connector on QMB-5000B motherboard #1. Another MD-525 cable is connected from the output connector on motherboard #1 to the input connector on motherboard #2 (see Figure 59 below). Again another MD-525 cable is connected from the output connector on motherboard #2 to the input connector on motherboard #3.
Figure 59: Interconnecting Extra QMB Motherboard
Ampliers are dened as in slot positions 2 to 5 for the Node Motherboard QMB-5000N
IO
A M P 1
A
A
A
M
M
M
P
P
P
4
2
3
Regular MD-525 Ribbon Cable
Regular MD-525 Ribbon Cable
Special MD-525 Ribbon Cable
JW1
IO
JW1
IO
JW1
IO
JW1
ANC-5000 and/or TNC-5000
QMB-5000N
NODE MOTHERBOARD
A
A
A
M
M
M
P
P
P
1
2
3
NOT USEDNOT USED
QMB-5000B
EXPANSION MOTHERBOARD #1
A
A
A
M
M
M
P
P
P
1
2
3
QMB-5000B
EXPANSION MOTHERBOARD #2
A
A
M
M
P
P
1
2
NOT USED
QMB-5000B
EXPANSION MOTHERBOARD #3
A
A M P 4
A M P 4
A M P 3
A
A
M
M
M
P
P
P
6
7
5
A
A
A
M
M
M
P
P
P
6
7
5
A
A M P 4
A
A
M
M
M
P
P
P
6
7
5
Ampliers are dened as in slot positions 2 to 7 for the Expansion Motherboards QMB-5000B
Note: Jumper JW1 (located in the bottom left-hand corner of the backplane) is installed for expansion
cabinets #1 to 3.
89
Page 94
Audio Network Card and Telephone Network Card
ANC-5000
FX-2009-12N Front Door
Partial Interior View
(to right of main board)
TNC-5000
ALARM
QUEUE
SUPV.
QUEUE
TROUBLE
QUEUE
MONITOR
QUEUE
A.C. ON
CPU FAULT
GND FAULT
SIGNAL
SILENCE
GENERAL
ALARM
ACKNOW-
LEDGE
FIRE
DRILL
SYSTEM
RESET
LAMP
TEST
ENTER
MENU
CANCEL
INFO
LED 0
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
CONFIGURABLE
SWITCH/LED 3
CONFIGURABLE
SWITCH/LED 7
MGC Network
Fire Alarm Control Panel
Normal Condition
April 20, 2012
5
6 4
8
9 7
Metal plate mounts
over positions 4 to 9
inclusive
TNC-5000 board
mounts over ANC-5000
board
Audio Network Card and Telephone Network Card
Each Integrated Fire/Audio Cabinet requires an ANC-5000 Audio Network Controller Card. The TNC-5000 Telephone Controller Network card is necessary only if Telephone circuits are required. Below is a diagram for mounting both audio and telephone cards into the large network fire alarm chassis, FX-2009-12N/DS.
90
Page 95
FleX-NetTMInstallation and Operation Manual
10K, 2W ELR MODEL MP-301 MANUFACTURED BY MIRCOM
SPEAKER
ZONE A
Class A or B
30 WATTS MAX
CLASS B WIRING EXAMPLE
1
2
3
4
5
6
7
8
ZONE B
Class A or B
30 WATTS MAX.
QAA-5230-70/25
TERMINAL BLOCK
SPEAKER
CLASS A WIRING EXAMPLE
-
+
-
-
-
+
+
+
Audio Amplifier Wiring
There are five types of amplifiers available:
Amplifier Description
QAA-5230-70/25 Two 30 watt individually supervised speaker outputs, 70V or 25V QAA-5230S-70/25 Two 30 watt split into four 15 watt supervised speaker outputs, 70V or 25V QAA-5415-70 Four 15 watt individually supervised speaker circuits, 70V QAA-5415-25 Four 15 watt individually supervised speaker circuits, 25V QAA-5160-70/25 One 60 watt supervised speaker circuit, 70V or 25V
QAA-5230-70/25 Amplifier Wiring
The QAA-5230-70/25 dual 30 watt amplifier is made up of two 30 watt supervised speaker outputs. Each circuit may be wired as Class A or Class B. Amplifier is set to 70V, if 25V is required, remove orange molex connector cable labelled MD-787 and replace with blue molex connector cable labelled MD-788.
Figure 60: QAA-5230-70/25 Wiring
Notes:
• All circuits are power limited and supervised.
• Cut jumper J1 when using an isolator.
• There are two fuses on this board. Both are 4A fast blow.
• See speaker wiring chart for wire gauge selection.
91
Page 96
Audio Amplifier Wiring
1
2
3
4
5
6
7
8
QAA-5230S-525-70/25
TERMINAL BLOCK
1/2 OF
ZONE A 25 Watts
1/2 OF
ZONE A 5 Watts
1/2 OF
ZONE B 5 Watts
1/2 OF ZONE B 25 Watts
-
+
-
-
-
+
+
+
CLASS B 30 WATTS MAX EACH ZONE
CLASS B 30 WATTS MAX EACH ZONE
22 K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22 K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22 K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22 K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
SPEAKER
SPEAKER
SPEAKER
SPEAKER
Figure 61: Using a Speaker Isolator
CUT JUMPER JP1 WHEN USING A SPEAKER ISOLATOR
JP1
Note: When using a speaker isolator (SIS-204 or SISA-
204 for use in Canada only), jumper JP1 (top left­hand corner, component side) must be cut on the QAA-5230-70/25 and on the QAA-5160-70/25.
18
QAA-5230-70/25 AND QAA-5160-70/25 AMPLIFIERS
QAA-5230S-70/25 Amplifier Wiring
QAA-5230S-70/25 dual 30 watt amplifier has two 30 watt amplifiers. Each amplifier has two Class B 15 watt supervised speaker circuits. Each circuit is wired to provide two separate speaker zones on the same floor. Amplifier is set to 70V, if 25V is required, remove orange molex connector cable labelled MD-787 and replace with blue molex connector cable labelled MD-788.
Figure 62: QAA-5230S-70/25 Wiring
Notes:
• All circuits are power limited and supervised.
• There are six fuses on this board. Two are 8A fast blow and four are 1/2A fast blow for the 70V version
• See speaker wiring chart for wire gauge selection.
and two are 8A fast blow and four are 1.25 A fast blow for the 25V
92
Page 97
FleX-NetTMInstallation and Operation Manual
1
2
3
4
5
6
7
8
QAA-5415-70 OR QAA-5415-25 TERMINAL BLOCK
ZONE D
ZONE C
ZONE B
ZONE A
22K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
22K, 1W ELR MODEL MP-302 MANUFACTURED BY MIRCOM
SPEAKER
SPEAKER
SPEAKER
SPEAKER
CLASS B WIRING
15 WATTS MAX EACH
QAA-5415-70 and QAA-5415-25 Amplifier Wiring
QAA-5415-70 quad 15 watt amplifier has four 15 watt amplifiers. Each amplifier has one Class B 15 watt supervised speaker circuit. Each circuit is wired such as to provide one separate speaker zone. The QAA-5415-70 may be wired as Class A by using a QAA-4CLA Class A converter, see Figure 65. The QAA-5415-25 is the same quad amplifier as the QAA-5415 but instead of 70 Volts it is 25 Volts.
Figure 63: QAA-5415-70 or QAA-5415 Wiring
Notes:
• All circuits are power limited and supervised.
• There are four 3A fast blow fuses on this board.
• See speaker wiring chart for wire gauge selection.
93
Page 98
Audio Amplifier Wiring
Figure 64: Using a Speaker Isolator with the QAA-5415-70 or QAA-5415-25 Amplifiers
QAA-5415-70/25 AMPLIFIER
U3
CUT JU MPER OVER U3 WH EN
JUMPER
USING A SPEAKER ISOLATOR
1
8
Note: When using a speaker isolator (SISA-204 or SISA-204 for use in Canada only), jumper JP1 (top left-
hand corner, component side) must be cut on the QAA-5230-70/25 and on the QAA-5160-70/25.
94
Page 99
FleX-NetTMInstallation and Operation Manual
O4 +
O4 +
R4 +
R4 -
O4 -
O3 +
R3 +
R3 -
O3 -
O2 +
R2 +
R2 -
O2 -
O1 +
R1 +
R1 -
O1 -
J1
J2
J3
J4
SPEAKER
SPEAKER
SPEAKER
SPEAKER
QAA-5415-70 and QAA-5415-25 AMPLIFIER
QAA-4CLA
REMOVABLE TERMINAL BLOCK
QAA-4CLA
TERMINAL BLOCK
TO WIRE QAA-4CLA, REMOVE TERMINAL FROM
QAA-5415-70 or QAA-5415-25 AMPLIFIER, CONNECT
TO QAA-4CLA AND SCREW DOWN. WIRE THE FOUR
CLASS A CIRCUITS TO THE 16 TERMINALS AS
SHOWN IN DIAGRAM AT RIGHT.
ALL CIRCUITS ARE POWER LIMITED.
15 WATTS MAX. PER ZONE.
NOTES:
1.
2.
3.
Figure 65: QAA-4CLA Class A Converter For QAA-5415-70/25 Amplifier
95
Page 100
Audio Amplifier Wiring
O4 +
O4 +
R4 +
R4 -
O4 -
O3 +
R3 +
R3 -
O3 -
O2 +
R2 +
R2 -
O2 -
O1 +
R1 +
R1 -
O1 -
O1 -
J1
J2
J3
J4
SPEAKER
SPEAKER
SPEAKER
SPEAKER
QAA-5230S-70/25 AMPLIFIER
QAA-4CLAS
REMOVABLE TERMINAL BLOCK
QAA-4CLAS
TERMINAL BLOCK
TO WIRE QAA-4CLAS, REMOVE TERMINAL FROM
QAA-5230S-70/25 AMPLIFIER, CONNECT TO QAA-
4CLAS AND SCREW DOWN. WIRE THE FOUR CLASS
A CIRCUITS TO THE 16 TERMINALS AS SHOWN IN
DIAGRAM AT RIGHT.
ALL CIRCUITS ARE POWER LIMITED.
15 WATTS MAX. PER ZONE.
NOTES:
1.
2.
3.
Figure 66: QAA-4CLAS Class A Converter For QAA-5230S-70/25 Amplifier
96
Loading...