Mircom FA-300, FA-301-12LW, FA-301-12LDW, FA-301-8LDW, FA-301-12LDR Installation And Operation Manual

...
Page 1
FA-300 Series
LED Fire Alarm Control Panel
Installation and Operation Manual
LT-905 Rev. 11.4 March 2018
Page 2
Page 3

Table of Contents

1.0 Industry Canada and FCC Notice 9
1.3 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A. .................................. 9
2.0 Introduction 11
2.1 Overall Features ............................................................................................................ 11
3.0 Conventions 12
3.1 Circuits ........................................................................................................................... 12
3.2 Zone ............................................................................................................................... 12
3.3 Display Points ................................................................................................................ 12
3.4 Wiring Styles .................................................................................................................. 12
4.0 System Components 13
4.1 Main Fire Control Panel ................................................................................................. 13
4.2 Relay Module: 12 Relays ............................................................................................... 14
4.3 Relay Modules: Six Relays ............................................................................................ 14
4.4 Polarity Reversal/City Tie ............................................................................................... 14
4.5 Remote Annunciator ...................................................................................................... 14
4.6 Smart Relay Module ...................................................................................................... 15
4.7 Input Class A converter: Six Circuits .............................................................................. 15
4.8 Output Class A converter: four circuits .......................................................................... 15
4.9 Output Class A converter: two circuits ........................................................................... 15
4.10 Active End-of-Line Resistors .......................................................................................... 16
4.11 RAM-216 Remote Annunciator ...................................................................................... 16
4.12 Additional Fire Alarm System Accessories .................................................................... 16
5.0 Mechanical Installation 17
5.1 Installing the Enclosure .................................................................................................. 17
5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 19
5.3 Installing the Adder Modules .......................................................................................... 20
6.0 Cable and Jumper Connections for Main Board and Adder Modules 21
6.1 Main Fire Alarm Board ................................................................................................... 21
3
Page 4
Table of Contents
6.2 ICAC-306 Input Class-A Converter Adder Module ......................................................... 22
6.3 OCAC-304/302 Output Class-A Converter Adder Module ............................................. 23
6.4 Relay Adder Modules ..................................................................................................... 23
6.5 Polarity Reversal and City Tie Module (Model PR-300) ................................................ 25
7.0 Field wiring 27
7.1 Main Fire Alarm Board Field Wiring ............................................................................... 27
7.2 Relay Adder Module Wiring .......................................................................................... 31
7.3 Connecting to a 3G4010 Interface Device for Canada .................................................. 32
7.4 Connecting to a 3G4010CF Interface Device outside Canada ...................................... 33
7.5 Polarity Reversal and City Tie Module (PR-300) Wiring ................................................ 34
7.6 Power supply connection ............................................................................................... 35
7.7 Wiring Tables and Information ....................................................................................... 36
7.8 Four-Wire Smoke Power ................................................................................................ 37
7.9 Supervised Auxiliary Power ........................................................................................... 37
7.10 Auxiliary Power .............................................................................................................. 37
8.0 Turning on the Panel 38
8.1 Before Connecting the Power ........................................................................................ 38
8.2 Power-up procedure ....................................................................................................... 38
8.3 Troubleshooting ............................................................................................................. 40
9.0 Indicators, Controls and Operations 41
9.1 Common Indicators ........................................................................................................ 42
9.2 Indicating Circuit Indicators ............................................................................................ 45
9.3 Signal Circuit Indicators ................................................................................................. 47
9.4 Common Controls .......................................................................................................... 47
9.5 Circuit (Zone) Disconnect Buttons ................................................................................. 49
9.6 Common Relays ............................................................................................................. 50
9.7 Circuit Types .................................................................................................................. 50
9.8 Indicating (Signal) Circuit Types .................................................................................... 52
9.9 Evacuation codes (Signal Rates) ................................................................................... 52
9.10 Single Stage Operation .................................................................................................. 53
9.11 Two-stage Operation ...................................................................................................... 54
10.0 Supported Protocols/Devices 56
10.1 Synchronous Strobes ..................................................................................................... 56
10.2 System Sensor’s i3 Devices ........................................................................................... 56
4
Page 5
Table of Contents
11.0 Configuration with the CFG-300 LCD Service Tool 59
11.1 Accessing Configuration Mode ...................................................................................... 60
11.2 Command Menu ............................................................................................................ 61
11.3 1. FA-300 CONFIG (Command-Menu) .......................................................................... 62
11.4 2. Config Info (Command-Menu ..................................................................................... 72
11.5 3. Set Time (Command-Menu) ...................................................................................... 73
11.6 4. Change password (Command-Menu) ........................................................................ 75
11.7 5. View Event Log (Command-Menu) ............................................................................ 75
11.8 6. Clear Event Log (Command-Menu) ........................................................................... 76
11.9 7. Walk Test (Command-Menu) ..................................................................................... 76
11.10 8. i3 Loop Test (Command-Menu) ................................................................................. 78
11.11 9. Dialer Config (Command-Menu) ................................................................................ 79
11.12 10. Test Dialer (Command-Menu) ................................................................................. 87
11.13 11. Exit (Command-Menu) ............................................................................................. 88
11.14 CFG-300 LCD service tool operation ............................................................................. 88
11.15 Zone messages ............................................................................................................. 89
11.16 AC Power Fail ................................................................................................................ 90
11.17 Battery trouble ................................................................................................................ 90
11.18 Ground Fault .................................................................................................................. 91
11.19 Remote Annunciator ...................................................................................................... 91
11.20 Four-wire Smoke Detector Supply ................................................................................. 91
11.21 Supervised Aux. Supply ................................................................................................. 92
11.22 City Tie Polarity reversal - PR-300/ Relay module ......................................................... 92
12.0 Appendix A: Compatible Receivers 94
13.0 Appendix B: Reporting 95
13.1 Ademco Contact-ID ........................................................................................................ 95
13.2 Security Industries Association SIA-DCS ...................................................................... 96
14.0 Appendix C: Specifications 97
15.0 Appendix D: Power Supply and Battery Calculations 100
16.0 Appendix E: Auxiliary Devices 101
17.0 Warranty and Warning Information 102
5
Page 6

List of Figures

Figure 1 FA-300 LED Series ........................................................................................................ 13
Figure 2 Box dimensions, surface mount ..................................................................................... 17
Figure 3 Box dimensions, semi-flush mounting and trim ring ....................................................... 18
Figure 4 Flush trim detail (from above) ........................................................................................ 18
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 19
Figure 6 Installation of Adder Modules ......................................................................................... 20
Figure 7 Main Fire Alarm Board cable connector and jumper settings ........................................ 21
Figure 8 ICAC-306 Input Class-A Converter Adder Module ......................................................... 22
Figure 9 OCAC-304/302 Output Class-A Converter Adder Module ............................................. 23
Figure 10 RM-312 twelve relay adder module ............................................................................... 24
Figure 11 RM-312/306 Relay programming ................................................................................... 24
Figure 12 RM-306 six relay adder module ..................................................................................... 25
Figure 13 Polarity reversal and city tie module .............................................................................. 25
Figure 14 Initiating circuit – Class B or Style B wiring .................................................................... 27
Figure 15 Initiating circuit– Class A or Style D wiring ..................................................................... 28
Figure 16 Indicating circuit – Class B or Style Y wiring .................................................................. 29
Figure 17 Indicating circuit –Class A or Style Z wiring ................................................................... 29
Figure 18 Four-wire smoke detector wiring .................................................................................... 30
Figure 19 Dialer wiring ................................................................................................................... 30
Figure 20 Relay per zone (RM-312) Terminal connection ............................................................. 31
Figure 21 Relay per zone (RM-306) Terminal connection ............................................................. 31
Figure 22 Connecting an FA-300 FACP to a 3G4010 Interface Device ........................................ 32
Figure 23 Connecting an FACP to a 3G4010CF Interface Device outside Canada ....................... 33
Figure 24 Polarity reversal and city tie module terminal connection .............................................. 34
Figure 25 Power supply connection ............................................................................................... 35
Figure 26 Battery connections ........................................................................................................ 39
Figure 27 LED indicators and control buttons ................................................................................ 41
Figure 28 Alarm Circuit Indicator .................................................................................................... 45
Figure 29 LAMP TEST ................................................................................................................... 49
Figure 30 Evacuation and Alert Codes ........................................................................................... 53
Figure 31 Open Circuit Trouble ...................................................................................................... 57
Figure 32 Communication Trouble ...............................................................................................
Figure 33 Dirty Device Trouble ....................................................................................................... 57
Figure 34 Out of sensitivity Trouble ................................................................................................ 57
Figure 35 Freeze Trouble ............................................................................................................... 58
Figure 36 FA-300 Configuration ..................................................................................................... 60
Figure 37 Enter passcode .............................................................................................................. 61
Figure 38 Command Menu ............................................................................................................. 61
Figure 39 FA-300 Config menu ...................................................................................................... 62
Figure 40 Feature Config menu ..................................................................................................... 63
Figure 41 The event log ................................................................................................................. 75
Figure 42 Select Log ...................................................................................................................... 76
Figure 43 Clear all the selected logs .............................................................................................. 76
.. 57
6
Page 7
List of Figures
Figure 44 Logs cleared .................................................................................................................. 76
Figure 45 Walk test confirmation .................................................................................................... 76
Figure 46 Walk test zones .............................................................................................................. 77
Figure 47 Walk test active .............................................................................................................. 77
Figure 48 i3 loop test confirmation ................................................................................................. 78
Figure 49 i3 test zones ................................................................................................................... 78
Figure 50 i3 test not ready ............................................................................................................. 78
Figure 51 The selected zone is not i3 type .................................................................................... 78
Figure 52 Dialer Config menu ........................................................................................................ 79
Figure 53 Detection circuit zone message ..................................................................................... 89
Figure 54 Indicating circuit zone message ..................................................................................... 89
Figure 55 AC Power Fail ................................................................................................................ 90
Figure 56 Battery Trouble .............................................................................................................. 90
Figure 57 Ground Fault .................................................................................................................. 91
Figure 58 Remote annunciator mismatch trouble .......................................................................... 91
Figure 59 Four-wire Power Supply ................................................................................................. 92
Figure 60 Aux. Power Supply ......................................................................................................... 92
Figure 61 City Tie module missing ................................................................................................. 93
Figure 62 City Tie trouble ............................................................................................................... 93
7
Page 8

List of Tables

Table 1 FA-300 LED Series Comparison Chart .......................................................................... 13
Table 2 Power Supply Ratings .................................................................................................... 35
Table 3 Initiating Circuit Wiring ................................................................................................... 36
Table 4 Indicating Circuit Wiring ................................................................................................. 36
Table 5 RS-485 Wiring to Annunciators and other Devices ........................................................ 37
Table 6 Alarm Circuit Indicators .................................................................................................. 45
Table 7 Supervisory Circuit Indicators ........................................................................................ 45
Table 8 Property and Building Safety Indicators ......................................................................... 46
Table 9 Trouble-Only Circuit Indicators ....................................................................................... 47
Table 10 Signal Circuit Indicators ................................................................................................. 47
Table 11 i3 Smoke Detector LEDs ................................................................................................ 58
Table 12 Settings permitted in CAN/ULCS527 ............................................................................. 59
Table 13 Settings permitted in UL864 ........................................................................................... 59
Table 14 Feature Config menu ..................................................................................................... 63
Table 15 i3 Detector Statuses ....................................................................................................... 79
Table 16 FA-300 LED Series Specifications ................................................................................. 97
Table 17 FA-300 LED System Modules and Annunciators ........................................................... 98
8
Page 9

1.0 Industry Canada and FCC Notice

!
i

1.1 Notice for all FA-300 Series Built-In UDACTs Sold in Canada

Mircom's F A-300 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units for Fire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for Fire Signal Receiving Centres and Systems). These Communicators should be installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction (AHJ).

1.2 Industry Canada Notice

Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper operation and for protection.
Caution: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or electrician, as appropriate

1.3 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A.

Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
Mircom's FA-300 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective Signalling Systems). These Communicators comply with the National Fire Protection Association (NFPA) performance requirements for DACTs and should be installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These Communicators should be installed in accordance with this manual; the National Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
9
Page 10

1.3.1 FCC Notice

This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the telco transformer of this equipment is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company. This equipment is capable of seizing the line. This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (central office implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect your service or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence number (REN); both of these items are listed on the equipment label. The sum of all of the REN’s on your telephone lines should be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable on a given line.
Industry Canada and FCC Notice
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they should be performed by Mircom Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page of this document.
10
Page 11

2.0 Introduction

i
Mircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP)-based
fire panel. The FA-300 provides a maximum of 12 supervised Class B or A (Style B or D) Initiating circuits, and maximum four supervised Class B or A (Style Y or Z) indicating circuits. All circuits are supervised for opens and ground faults, and indicating circuits are supervised for shorts. Optional modules include Relay, Polarity Reversal and City Tie and Class A Converters for initiating and indicating circuits. Semi-flush or surface mountable enclosures
can be used for retrofits and on new installations.
Note: Installation of the FA-300 series fire alarm control panel should be in accordance
with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ).

2.1 Overall Features

Basic unit has 12 Class B (Style B) initiating circuits, which may be configured as Class
A (Style D) using input Class A converter adder modules. Each initiating circuit can be configured as Alarm, Verified Alarm, Water flow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Property and Building Safety, or Trouble-Only circuits. There are two LEDs per circuit, one for Trouble (amber), and one dual color (amber/red) LED for Supervisory (amber) and Alarm (red).
Basic unit has four Power Limited Class B (Style Y) indicating circuits with individual
trouble indicators. Each indicating circuit may be configured as Class A (Style Z) using output Class A converter adder module. Each indicating circuit may be configured as Silenceable signal, non Silenceable signal, Silenceable strobe, non Silenceable strobe. The audible signal may be Steady, Temporal Code, California Code, or March Time.
Two Stage operation available.
A pushbutton associated with each initiating and indicating circuit can individually
disconnect the circuit.
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For UL installations, disable the auto signal silence timer.
Subsequent Alarm, Supervisory, and Trouble operation.
Four-wire resettable smoke power supply 300 mA maximum.
Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
RS-485 Interface for LCD Annunciators, RA-1000 Series Remote Multiplex
Annunciators and Smart relay adder.
Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
Extensive transient protection.
With or without built-in UDACT (Digital Alarm Communicator Transmitter).
Easy configuration of the panel and built-in UDACT using LCD service tool (CFG-300).
Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
Laptop programmer for direct configuration changing and log checking.
11
Page 12

3.0 Conventions

3.1 Circuits

Refers to an actual electrical interface for Initiating (Detection) and Indicating (Signal or NAC) or Relays.

3.2 Zone

Is a logical concept for a Fire Alarm Protected Area, and consists of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual circuit refers
only to a physical electrical loop.

3.3 Display Points

There is a display point associated with every initiating and indicating circuit of the FA-300 LED Series fire panel. For an initiating circuit there are 2 LEDs for every display point: one single color (amber) and one dual color (red/amber). For an indicating circuit there is only one LED: one single color (amber), for every display point.

3.4 Wiring Styles

Initiating and indicating circuits are Class B (style B and Y).
Changing the initiating circuits to Class A requires an ICAC-306 adder board which converts six initiating zones from Class B (style B) circuits to Class A (style D). This is done without decreasing the number of circuits, which remains the same as in Class B (style B).
Changing the indicating circuits to Class A requires an OCAC-304 adder board which converts four indicating zones from Class B (style Y) circuits to Class A (style Z) or an OCAC-302 adder board which converts two indicating zones from Class B (style Y) circuits to Class A (style Z).
12
Page 13

4.0 System Components

4.1 Main Fire Control Panel

Figure 1 FA-300 LED Series
All FA-300 LED Series Panels have the following features:
LED Display.
Two six zone ICAC-306 Input Class A Converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
One OCAC-304 Output Class A Converter adder module may be used for Class A
(Style Z) wiring of the Indicating circuits.
Contain Common Alarm, Common Supervisory & Common Trouble Relays, Auxiliary
Alarm Relay (disconnectable), an RS-485 Interface for Remote Annunciators and a Resettable Four Wire Smoke Detector Power Supply.
Used with Mircom BAT-12V12A (12 Amp-hour) batteries (two required).
Table 1 FA-300 LED Series Comparison Chart
Model # of zones # of initiating
circuits
FA-301-12LDW 12 12 yes white FA-301-12LDR 12 12 yes red FA-301-12LW 12 12 no white FA-301-12LR 12 12 no red FA-301-8LDW 88 yes white FA-301-8LW 88 no white
On board Dialer Door Color
FA-301-8LDR 88 yes red FA-301-8LR 88 no red
13
Page 14

4.2 Relay Module: 12 Relays

NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NC NO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
Mounting hole for
#6-32 screws
Mounting hole for #6-32 screws
FA-300 SERIES
Remote Annunciator
SYSTEM RESET
SIGNAL SILENCE
FIRE
DRILL
BUZZER SILENCE
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CP U FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
Advanced Li fe Safety Sol utions
System Components
Model Description

4.3 Relay Modules: Six Relays

Model Description
RM-306 Six relay adder module

4.4 Polarity Reversal/City Tie

Model Description
RM-312
12 relay adder module
14
PR-300 Polarity Reversal and/or City Tie Module

4.5 Remote Annunciator

Model Description
RAM-300LCDW
RAM-300LCDR
Remote Annunciator module, LCD display, white painted box
Remote Annunciator Module, LCD display, red painted box
Page 15

4.6 Smart Relay Module

REMOTE RELAY
Advanced Life Safety Sol utions
FR-320 SERIES
BLK RED
BLK REDBLK REDBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- DET6 OUT+
- DET1 RET+- DET2 RET+- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RET+
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG 2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG 4 RET+
BLK RED
BLK RED
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
Model Description
SRM-312W Smart Relay Module (12 relays) with white enclosure
SRM-312R Smart Relay Module (12 relays) with red enclosure

4.7 Input Class A converter: Six Circuits

Model Description
System Components
ICAC-306
Input Class A converter Module (six circuits). This
module has built in Active End-of-Line resistors.

4.8 Output Class A converter: four circuits

Model Description
OCAC-304 Output Class A converter module (four circuits)

4.9 Output Class A converter: two circuits

Model Description
OCAC-302 Output Class A converter module (two circuits)
15
Page 16

4.10 Active End-of-Line Resistors

BLACK
RED
A.C.ONCOMMON
TROUBLE
SIGNAL SILEBCE
BUZZER SILENCE
SIGNAL SILENCE
LAMP TEST
SYSTEM RESET
SWITCH ENABLE
FIRE ALARM ANNUNCIATOR
The ELRX-300 are power-saving End-of-Line resistors that eliminate the need for an additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
Model Description
ELRX-300 Active end-of-line resistor without plate
ELRX-300R Active end-of-line resistor with end-of-line red plate

4.11 RAM-216 Remote Annunciator

Model Description
RAM-216 16 Zone remote annunciator
System Components
RAM-208 8 Zone remote annunciator

4.12 Additional Fire Alarm System Accessories

RAM-208 Eight Zone Remote Annunciator ULC and ULI Approved RTI-1 Remote Trouble Indicator ULC and ULI Approved MP-300 End-of-line resistor plate, 3.9K ohm ULC and ULI Approved MP-300R End-of-line resistor plate, red ULC Approved BC-160 External Battery Cabinet ULC and ULI Approved RAM-1016TZDS Remote Annunciator with 16 bi-
coloured LEDs (DS model has 16 bi-coloured LEDs and 16 trouble LEDs)
RAM -1032TZDS Remote Annunciator with 32 bi-
coloured LEDs (DS model has 16 bi-coloured LEDs and 32 trouble LEDs)
PCS-100 Passive Communications Interface
Board
UDACT-300A Universal Communicator ULC and ULI Approved BK-RAM Deadfront bracket (ULC
requirement for RAM-1016 series and RAM-1032 series)
ULC and ULI Approved
ULC and ULI Approved
ULC Approved
ULC Approved
16
Page 17

5.0 Mechanical Inst allation

11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole

5.1 Installing the Enclosure

Install the FA-300 Series Fire Alarm Panel enclosure as shown below for the twelve-, eight-, and six-zone models. Mount enclosure surface mount using the four mounting holes, as shown and the screws provided.
Figure 2 Box dimensions, surface mount
The backbox may be semi-flush mounted using the trim ring model FA-UNIV-TRB (BLACK), see Figure 3. Remove the door (also disconnect the ground strap), the dead front and semi-
17
Page 18
Mechanical Installation
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" i s the max imum depth for semi -flus h mounting usi ng the flush tr im ri ng
1" is the mi nimum depth
above the wall required for semi- flus h mounting usi ng the flus h trim ri ng
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 300 backbox .
PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL S TUD
BACKBOX
flush mount the backbox into the wall. Peel the adhesive cover from the trim ring and stick to the wall surface around the backbox, after wall is finished.
Figure 3 Box dimensions, semi-flush mounting and trim ring
Figure 4 shows a cross-section of the semi-flush mounted enclosure and the trim ring. Make
sure to allow a minimum depth of 1” above the wall surface for proper door opening.
Figure 4 Flush trim detail (from above)
18
Page 19
Mechanical Installation
26.0 "
14.5 "
4.2 "
External Dimensions
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View

5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation

The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a built-in trim ring.
Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26” Distance between horizontal mounting screws 12” Distance between vertical mounting screws 23.5” Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
Mounting Dimensions
12.0 "
23.5 "
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions
19
Page 20

5.3 Installing the Adder Modules

Fuse and AC wiring terminal
S-+NC NOCNC NOCNC NOCNC NOC
+-+-COM(+)
COM(-)
TRLTRB RTRT
RTRT
RES CO RE S C O
LINE1LINE2
WALK TEST
REMOTE TROUBLE
CPU FAULT
GROUND FAULT
SIGNAL SILENCE
FIRE DRILL
AUTOMATIC ALARM SIGNAL CANCEL
GENERAL ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP TEST
ALM/SUP/TBL/BLDG
AUDIBLE SIL
A.C.
ON
COMMON ALARM
COMMON
SUPV
COMMON TROUBLE
BATTERY TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCONNECT
ZONE-7
DISCONNECT
ZONE-9
DISCONNECT
ZONE-11
DISCONNECT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
ZONE-12
DISCONNECT
NAC-1
DISCONNECT
NAC-3
DISCONNECT
NAC-2
DISCONNECT
NAC-4
DISCONNECT
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DE T 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SI G 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR -300 MOD ULE
TO R M-312/RM-306 RELAY
MODULE
RS-
485
AUX. RELAYALARM
RELAY
SUP E RVIS O RY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-W I RE
SUPPLY
UNFILTERED
RTI
PORT
P1P
2
P3P
4
+
_
BATTERY SEC. TX
BATTERY BATTERY
CLASS -A conve rter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter board for indicating circui ts OCAC-304
(4 circuits )
Reverse po larity a nd city tie modu le PR- 300. Mounted on hex spacer with two screws provide d
Relay Module RM-306 Mount relay module on the left si de u sing tw o scre ws provided .
Relay M odule RM-312 centre under main fire alarm board using three screws pro vided .
Transf orme r
Fuse and AC wirung terminal
MAIN FIR E PANEL BOAR D
Fuse and AC wiring terminal
FA-300 Series Fire Alarm panels come pre-assembled with all components and boards except
for Adder Modules. Module installation locations are shown in Figure 6. Refer to Figure 7 on
the next page for jumper and DIP switch settings and see 7.7 Wiring Tables and Information on page 36 for wiring specifications.
Mechanical Installation
20
Figure 6 Installation of Adder Modules
Page 21
S-+NC NOCNC NOCNC NOCNC NOC
+-+-
COM(+)
CO M(- )
TRLTRB RTRT
RTRT
RES CO RES CO
LINE1LINE2
WALK TEST
REMOTE TROUBLE
CPU FAIL
GROUND
FAULT
SIGNAL SILENCE
FIRE
DRILL
GENERAL
ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP TEST
ALM/SUP/TBL/
BLDG AUDIBLE SIL
A.C.
ON
COMMO N
ALARM
COMMO N
SUPV
COMMO N TROUBLE
BATTERY TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCON NECT
ZONE-7
DISCON NECT
ZONE-9
DISCON NECT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
NAC-1
DISCONNECT
NAC-2
DISCONNECT
JW3 JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SIG 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 M ODULE
TO RM-312/ RM-306 RELAY MODULE
RS-4 85AUX. RELAYAL ARM REL AY
SUPERVISO RY
RELAY
TROU BL E
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UNFIL TERED
RTI
PORT
P1 P2P3 P4
+
_
XT .CESYRETTAB
Telephone line #1
Telephone line #2
RS-485 for annunciators
Auxiliary Alarm Relay
Common Alarm Relay
Common Supervisory Relay
Common Trouble Rel ay
Auxiliary Supply
4-wire Supply
Unfiltered 24V supply
connect to Remote trouble indicator
Initiating zone 1 TO 12
Indicating zone 1 TO 4
Connect to RM-312/ RM306 Relay module
Connect to PR-300
To Battery
To secondary of AC
transformer
JW2 - ON- when RM312/RM306 not connected
JW1 - ON- when PR-300 not connected
JW3- Removed all the time
JW6-Open all the time
JW4 -Normally open
JW7
JW7 -Normally open
For front panel programming use CFG-300 configuration tool not UL- 864 or ULC-S527 listed. Please refer to Document LT-922 for details
For PC pr ogramming use UIMA interface module not UL-864 or ULC-S 527 listed . Plea se refer to Document LT-929 for details
AUTOMATIC ALARM SIGNAL CANCEL
ZONE-11
DISCONNECT
ZONE-12
DISCONNECT
NAC-3
DISCONNECT
NAC-4
DISCONNECT
[
[
[
JW6 - Open all the time
JW4 - Normally open
JW5-Normally Open
[
Trouble Relay LED
6.0 Cable and Jumper Connections for
Main Board and Adder Modules

6.1 Main Fire Alarm Board

Figure 7 Main Fire Alarm Board cable connector and jumper settings
21
Page 22
Cable and Jumper Connections for Main Board and Adder Modules
BLK RED
BLK R E DBLK R E DBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 O UT+- D ET4 OUT+- DET 5 OUT+- DET6 OUT+
- DET1 RET+- D ET2 R ET+- DET3 R ET+- DET4 RET+- DE T5 RET+- DET6 RET+
mounting hol e for #6-32 scr ews
All these pi ns comes wit h red a nd black w ire s w h i ch are con ne cted to the detection circuit on the mai n fire alarm board. Red is pos i ti ve and bl ack i s negative
ICAC-306
mounting hol e for #6-32 screws

6.1.1 Connectors and Jumpers on the Main Fire Alarm Board

P5
P6
JW1
Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects
here. Otherwise not used.
Cable from connector P1 of the RM-312 or RM-306 Relay Adder Module
connects here. Otherwise not used.
On the Main Fire Alarm Module, this jumper must be removed if a PR-300
Polarity Reversal and City Tie Module is installed.
JW2 Remove this jumper if an RM-312 or RM-306 Relay Adder Module is used.
JW3 Removed all the time.
Normally open. Place jumper here and power down (AC and Batteries) then
JW4
power back to revert back to default password. Once the system has reset,
REMOVE the jumper from the pins at JW4. Leave normally open.
JW5
Normally open to BLOCK remote converter module or a CFG-300 Configuration Tool. Place jumper here to ALLOW
configuration via modem, PC with a UIMA
any type of configuration.
JW6 Not used, open.
JW7 Not used, open.

6.2 ICAC-306 Input Class-A Converter Adder Module

Figure 8 ICAC-306 Input Class-A Converter Adder Module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
22
Page 23
Cable and Jumper Connections for Main Board and Adder Modules
- SIG1 OUT+- SIG2 OUT+
- SIG1 R ET+- SIG2 RET+
BLK RED
BLK RED
mounting ho l e for #6-32 screws
OCAC-302
mounting ho l e for #6-32 screws
- SIG1 O U T+- SIG2 OU T+
- SIG1 RET+- SIG2 R ET+
BLK RED
BL K RE D
- SIG3 OU T+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BL K RE D
mounting hol e for #6-32 scr ews
OCAC-304
mounting ho le for #6-32 scr ews
Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the positive and negative terminals marked DET OUT and the circuit return wires are brought back to the converter module to positive and negative terminals marked DET RET.
To convert all 12 initiating circuits of a FA-312 Fire Alarm Panel, two of these ICAC-306 Input Class A Converter Adder Modules are required.

6.3 OCAC-304/302 Output Class-A Converter Adder Module

6.4 Relay Adder Modules

6.4.1 RM-312 Twelve-Relay Adder Module

Figure 9 OCAC-304/302 Output Class-A Converter Adder Module
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the Class A converter module to the positive and negative terminals of Indicating circuit 1 on the Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then wired back to the SIGNAL RET positive and negative.
The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-312 are used to configure the relays. The
23
Page 24
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
RELAY 8CREL AY 9
NO/NC C
RELAY 1 0
NO/NC C
RELAY 1 1
NO/NC C
RELAY 1 2
NO/NC NO/NC
Three mounting holes for #6-32 screws
INDI VIDUAL GREEN RELAY STAT US LEDs
Connect to P6 on the main fire alarm board
NO NC
SA
Z1
1&2
NO/ NC C
RELAY 1
NC/NO CONNECTION NC: terminal provides normally closed contacts NO: terminal provides normally open contacts Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection then the relay is not connected to the terminals
SUPV/ALARM SELECTION S: Relay turns ON when common
supervisory is active A: Relay turns ON when common alarm is active Defa ult: No jumper installed, conn ecte d o n ce n ter p in o nl y
ZONE JUMPER inst alled: turns ON relay when the zone
(1) is act ive removed: does not turn ON the relay when zone (1) i s a cti ve
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE jumper installed: this relay 1 works in
conjunction w i t h r el ay 2 jumper removed: relay 1 does not operate with the adjacent relay 2 chaining example: if jumper is installed on 1&2 and 2&3 then all the three relays
will be ON if any one of relays 1,2 and 3 is active Default: No jumper installed, connected on one pin only
NO/NC C
RELAY 12
RELAY
LED (GREEN)
i
jumpers located below the relays are used to select either normally open contacts or normally closed contacts.
Figure 10 RM-312 twelve relay adder module
P1 Cable from RM-312 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.4.2 Programming the relays

24
A typical relay circuit is shown in Figure 11 with the jumper locations and descriptions.
Figure 11 RM-312/306 Relay programming
Note: Relay programming should be done before installing the board.
Page 25
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
mounting hol e for #6-32 screws
mounting hol e for #6-32 scr ews
INDIVIDUAL GREEN RELAY STAT US LEDs
Connect to P 6 on the main fire alarm board
i

6.4.3 RM-306 Six Relay Adder Module

Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-306 are used to configure the relays. The jumpers located below the relays are used to select either normally open contacts or normally closed contacts.
Figure 12 RM-306 six relay adder module
P1 Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.4.4 Programming the relays

See explanation in Figure 11.
Note: Relay programming should be done before installing the board.

6.5 Polarity Reversal and City Tie Module (Model PR-300)

Mounting hole for
#6-32 screws
P1 P2
Mounting hole for #6-32 screws
+ | - + | - + | -
CITY
TIE
REVERSAL
POLARITY
ALARM
REVERSAL
POLARITY
SUPV
JW4
Figure 13 Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
25
Page 26

6.5.1 PR-300 jumper settings

Cable and Jumper Connections for Main Board and Adder Modules
P1 P2 & JW4
Cable connects to P5 on the Main Board
Not used. Jumper JW4 remains on board.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active. This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals resound and the City Tie Box is retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0 to 3 hours if this is the only system trouble.
26
Page 27

7.0 Field wiring

!
+
-
STYLE B WIRING
STYLE B WIRING
INITIATING CIRCUIT #1
INITIATING CIRCUIT #2
INITIATING CIRCUIT - 1 ALARM ZONE
INITIATING CIRCUIT - 2 SUPERVISORY ZONE
ION SMOKE DETECTOR
PHOTO SMOKE DETECTOR
HEAT DETECTOR
PULL STATION
3.9K 1/2 WATT ELR
SUPERVISORY
FIRE ALARM MAIN BOARD
+
-
DET 1DET 2
NOTE: IF ACTIVE END OF LINE RESISTORS ARE USED, THEY MUST BE USED ON ALL INITIATING CIRCUITS.
i

7.1 Main Fire Alarm Board Field Wiring

Wire devices to the terminals as shown in the figures that follow. Refer to the Wiring Tables for
wire gauges and to Appendix A for specifications.
Caution: Do not exceed power supply ratings.

7.1.1 Initiating Circuit Wiring Class B

Wiring diagrams for the initiating circuits are shown below. The panel supports Class B (Style B) and Class A (Style D) for the initiating circuits. The initiating circuits are supervised by a
3.9K End-of-Line Resistor or for power saving an Active-End-of-Line.
Figure 14 Initiating circuit – Class B or Sty le B wiring
Note: Depending on configuration, End-of-Line Resistors on initiating circuits must be
all 3.9K ohm resistors or all Active End-of-Line resistors.
27
Page 28

7.1.2 Initiating Circuit Wiring Class A

+
-
STYLE D WIRING
STYLE D WIRING
INITIATING CIRCUIT # 1
INITIATING CIRCUIT # 2
INITIATING CIRCUIT - 1 ALARM ZONE
INITIATING CIRCUIT - 2 SUPERVI SORY ZONE
ION SMOKE DETECTOR
PHOTO SMOKE DETECTOR
HEAT DETECTOR
PULL STAT ION
SUPER VISOR Y
4 MORE INITIATING CIRCUITS NOT S HO WN
DCAC-306 CLASS A
CONVERTER MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- DE T1
OUT+
- DET2
OUT+
- DET1 RET+- DE T 2 R E T +
+
-
DET 1DET 2
ICAC
i
Field wiring

7.1.3 Indicating Circuit Wiring

Figure 15 Initiating circuit– Class A or Style D wiring
The FA-300 Series Fire Alarm supports Class B (Style Y) and Class A (Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line resistor. Each indicating
circuit provides up to 1.7 A, 5 A maximum total if no auxiliaries are used.
Note: An Active End-of-Line resistor CANNOT be used with any indicating circuits.
Always use 3.9K End of Line resistors for indicating circuits.
28
Page 29
Field wiring
- SIG 1 +
STYLE Y WIRING
STYLE Y WIRING
INDICATING CIRCUIT - 1
INDICATING CIRCUIT - 2
BELL STROBE 3.9K 1/2 WATT ELR
INDICATING CIRCUIT #1
INDICATING CIRCUIT #2
HORN
FIRE ALARM MAIN BOARD
- SIG 2 +
BELL
STROBE
HORN
+
-
STYLE Z WIRING
STYLE Z WIRING
INDICA TING CIRCUIT #1
INDICA TING CIRCUIT #2
INDICATING CIRCUIT 1
INDICATING CIRCUIT 2
2 MORE INDICATING CIRCU ITS NOT SHOWN
OCAC-304 CLASS A
CONVE RTE R MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- S IG 1 OU T+- SIG2 O UT+
- SIG1 RET+- S IG2 RET+
+
-
SIG 1SIG 2
Figure 16 Indicating circuit – Class B or Style Y wiring
Figure 17 Indicating circuit –Class A or Style Z wiring
29
Page 30

7.1.4 Four Wire Smoke Detector Wiring

POWER
DETECTION
++
++
--
--
1
4
2
3
5
6
TO INITIATING
CIRCUIT
RESETTABLE 4-WIR E SMOKE DETECTOR POWER SUPPLY 22VDC, 200mA MAX. CURRENT - 300mA MAX. RIPPLE VOL. 5mV (POWER LIMITED)
4-WIRE DETECTION DEVICE
END OF LINE RELAY LISTED S3403 MODEL A77-716B MANUFACTURED BY SYSTEM SENSOR
+
-
4-WIRE
SUPPLY
3.9K 1/2 W ATT ELR
LEGEND
NOTES
ALL POWER LIMITED CIRCUITS MUST USE TYPE FPL, FPLR, OR FPLP POWER LIMITED CABLE
FIRE ALARM MAIN BOARD
TIPTIP RINGRING
premi s e t el ephone
IF permitted
TIPTIP RINGRING
LINE-1
LINE-2
1
23
4
8
5
76
Public switch
Telephone company
wiring
TIP
RING
TIP
RING
RJ31X
BROWN
GREY
GREEN
RED
COCO RESRES
Line 2 is Wired as shown for Line 1
FIRE ALARM MAIN BO AR D
Field wiring

7.1.5 Dialer Wiring

30
Figure 18 Four-wire smoke detector wiring
If you have Fire Alarm Panel Models FA-301-12LDW, FA-301-12LDR, and FA-301-8LDW there is a dialer on board and terminals marked Line 1 and Line 2 must be wired as shown in Figure 19 below.
Figure 19 Dialer wiring
Page 31

7.2 Relay Adder Module Wiring

C
C
NO/NC
NO/NC
C
NO/NC
ALL RELAY CONTACTS
28V DC, 1 AMP
RESISTIVE LOAD
RM-312 12 RELAY ADDER MODULE
NORMALLY OPEN OR NORMALLY CLOSED CONNECTION IS SELECTED BY JUMPER ON RELAY BOARD.
NOTE: ALL RELAY CIRCUITS ARE POWER LIMITED AND MUST USE TYPE FPL, FPLR or FPLP POWER LIMITED CABLE.
NORMALLY OPEN
CONNECTION
NORMALLY CLOSE
CONNECTION
RELAY
CIRCUIT #1
RELAY
CIRCUIT #2
RELAY
CIRCUIT #12
C
C
NO/NC
NO/NC
C
NO/NC
ALL RELAY CONTACTS
28V DC, 1 AMP
RESISTIVE LOAD
RM-306 6 RELAY ADDER MODULE
NORMALLY OPEN OR NORMALLY CLOSED CONNECTION IS SELECTED BY JUMPER ON RELAY BOARD.
NOTE: ALL RELAYS ARE POWER LIMITED CIRCUITS AND MUST USE TYPE FPL, FPLR or FPLP POWER LIMITED CABLE.
NORMALLY OPEN
CONNECTION
NORMALLY CLOSE
CONNECTION
RELAY
CIRCUIT #1
RELAY
CIRCUIT #2
RELAY
CIRCUIT #6
Wire relays on the relay adder modules RM-312 and RM-306 as shown in Figures 19 and 20.
Field wiring
Figure 20 Relay per zone (RM-312) Terminal connection
Figure 21 Relay per zone (RM-306) Terminal connection
31
Page 32

7.3 Connecting to a 3G4010 Interface Device for Canada

A
L
A
R
M
R
E
L
A
Y
S
P
V
R
E
L
A
Y
T
R
B
L
R
E
L
A
Y
Telephone
Line A
Connec tion
DC IN
E
O
L
To GS M/GPRS
T
yp
ic
a
l
In
st
a
ll
a
tio
n
in
Ca
n
a
d
a
Line 2Line 1
PCS-100
P O W
E R
2 4 V
G N D
P G M 4 G
N D 1
4V
NC
C O M N O
T B L
R E L AY
J W
1
P
G
M
4
AUX SUPPLY
+
-
+
-
Internet
Com puter
Printer
SUR-GARD
SYSTEM IV
Internal IP: X.X.X.X External IP: X.X.X.X
SG-Systems
Cons ole 2.1
Default Gateway: X.X.X.X Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
N
O C
N
O C
N
O C
C
O
M
Z
3
Z
2
Z
1
T
1
R
1
(
-)
(
+
)
Conventional input configured as 3G4010 radio trouble
FA-300
3G4010
C.O. C.O.
Router
i
A typical connection is shown in Figure 22. The PCS-100 Passive Communications Interface Board (sold separately) is required.
For information on Compatible DACR Receivers see 12.0 Appendix A: Compatible Receivers on page 94.
FA-300 - 3G4010 Connection - Typical Diagram
Field wiring
3G4010 TRBL
Figure 22 Connecting an FA-300 FACP to a 3G4010 Interface Device
Note: The DSC interface device 3G4010 is required if the installation requires ULC
-
All units must be installed in the same room All extended wiring must be in metallic conduit
-
-
S559 certification. The DSC interface device 3G4010CF is required if the installation requires UL864 9th edition certification.
Wiring between FACP and 3G4010: 18 m max.
-
Contact DSC to reprogram the zone inputs to match the FACP as shown in this diagram
32
Page 33
Field wiring
Telephone
Line A
Connect ion
E
O
L
Line 2
C.O.
Line 1
C.O.
PCS -100
P OW
E R
2 4 V
G N D
P G M4
G N
D 1
4 V
NC
C O M N O
T B L
R E L AY
J W
1
AUX SUPPLY
+
-
+
-
To GSM/GPRS
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP: X.X.X.X External IP : X.X.X.X
SG-Systems
Console 2 .1
Default Gateway: X.X.X.X Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
Router
Conventional input configured as 3G4010CF radio trouble
FA-300
3G4010CF
TRBL
A
L
A
R
M
R
E
L
A
Y
S
P
V
R
E
L
A
Y
T
R
B
L
R
E
L
A
Y
N
O C
N
O C
N
O C
+
-
FA-300 - 3G4010CF Connection - Typical Diagram
Typical Installation outside Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010CF: 20 feet max.
- Contact DSC to reprogram the zone inputs to match the FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF enclosure above the PS4086
3G4010CF TRBL
PGM4
C
O
M
Z
3
Z
2
Z
1
T
1
R
1
N
C
C
O
M
N
O
DSC RM-2 Relay
E
O
L
-
PS4086
Transformer
Battery
DC IN
+12V
COM
AC IN
+
ACT
LBT
N
C
C
O
M
N
O
DSC RM-2 Relay
E
O
L
-
+
BAT+
BAT-
3G4010CF
3G4010CF TRBL
+
-
+
-
Conventional input configured as AC failure trouble
Conventional input configured as low battery trouble
i

7.4 Connecting to a 3G4010CF Interface Device outside Canada

For information on Compatible Receivers see 12.0 Appendix A: Compatible Receivers on page 94.
A typical connection is shown in Figure 23. The 3G4010CF is powered separately from the PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive Communications Interface Board (sold separately) is also required.
Figure 23 Connecting an FACP to a 3G4010CF Interface Device outside Canada
Note: The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the installation requires UL864 9th edition certification.
33
Page 34

7.5 Polarity Reversal and City Tie Module (PR-300) Wiring

1
1
2
2
S
S
CITY TIE LOCAL ENERGY
RATED - 24VDC FILTERED TRIP COIL - 14 Ohms, 250mA, 5mV RIPPLE
POLARITY REVERSAL ALARM
24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT
POLARITY REVERSAL SUPV.
24VDC OPEN 12VDC AT 3.5mA 8mA MAX. SHORT
PROTECTOR
1
1
2
2
S
S
1
1
2
2
S
S
PROCTECTOR
1
1
2
2
S
S
USE A SHORTING WIRE WHEN THE CITY TIE IS NOT USED
+
+
+
-
-
-
+
+
+
-
-
-
CONFIRMS TO NEMA STANDARD SB3-1969 INTENDED FOR CONNECTION TO POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVING UNIT HAVING COMPATIBLE RATINGS
DIN RAIL CONNECTION TO EARTH GROUND
DIN RAIL CONNECTION TO EARTH GROUND
POWER LIMITED
POWER LIMITED
POWER LIMITED
PR-300
PROCTECTEDPROCTECTED
UNPROCTECTEDUNPROCTECTED
POWER LIMITED CABLE TYPE FPL, FPLR or FPLP MUST BE USED FROM PR-300 TO PROTECTORS.
Wire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 24, below. See 12.0 Appendix A: Compatible Receivers on page 94 for module specifications. Power Limited cable type FPL, FPLR or FPLP must be used.
For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown.
For use in Canada, the Protective Device is not required but still recommended.
Field wiring
Figure 24 Polarity reversal and city tie module terminal connection
34
Page 35

7.6 Power supply connection

!
The power supply is part of the Main Chassis. The ratings are:
Table 2 Power Supply Ratings
Type Rating
Electrical Input rating 120VAC, 60Hz, 3A\ 240 VAC, 50 Hz, 1.5A
Power supply total current 6A maximum
Field wiring
Battery fuse on Main module
10A, slow blow micro fuse
Caution: Do not exceed power supply ratings.
Wire the power supply as shown in Figure 25 using the proper wire gauge. See Appendix C:
Specifications for power supply specifications.
blk
MODU LE
TO RM-312/RM-306 RELAY
JW1
TO PR-300 MODULE
BATTERY
_
+
P3 P4
red
blk
red
red
P1 P2
SEC. TX
SIG 3SIG 4
-+-+
red
_
+
_
+
Battery Battery
NOTE: TO PREVENT SPARKING, CONNECT BATTERIES AFTER THE
SYSTEM MAIN A.C. POWER IS TURNED ON
Figure 25 Power supply connection
yellow
red
blk
green
240 VAC 50Hz
120 VAC 60Hz
N
GND
35
Page 36

7.7 Wiring Tables and Information

i
i
Table 3 Initiating Circuit Wiring
Wire gauge Maximum wiring run to last device AWG Feet Meters
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
Notes: For Class A the maximum wiring run to the last device is divided by two.
Field wiring
Maximum loop resistance should not exceed 100 ohms.
Maximum capacitance of 0.5 μF total on each initiating circuit.
Table 4 Indicating Circuit Wiring
Total signal load in Amperes
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.20 118 36 185 56 300 91 425 129 1.5
1.50 94 29 150 46 240 73 343 105 1.2
Maximum wiring run to last device
18 AWG 16 AWG 14 AWG 12 AWG Feet Meters Feet Meters Feet Meters Feet Meters
Max. loop resistance in ohms
1.70 78 24 125 38 200 61 285 87 1.0
Notes: For Class A wiring the resistance in ohms is multiplied by two.
Maximum voltage drop should not exceed 1.8 volts.
36
Page 37
Table 5 RS-485 Wiring to Annunciators and other Devices
i
Wire gauge Maximum wiring run to last device AWG Feet Meters 22 2000 609.6 20 4000 1219.2 18 8000 2438.4
Notes: Use twisted shielded pair,
300mA power limited.
Maximum 40 ohm loop resistance

7.8 Four-Wire Smoke Power

Field wiring
4-wire smoke power is provided for 4-wire smoke detectors. This filtered supply is supervised therefore a short disconnects the power through the relay until the SYSTEM RESET button is pressed. This supply is rated at 22.3VDC Nominal/300mA max/1V voltage drop maximum.

7.9 Supervised Auxiliary Power

Supervised auxiliary power is used to power the remote annunciators and smart relay modules. This filtered circuit is supervised therefore a short disconnects the power through the relay until the SYSTEM RESET button is pressed. This supply is rated at 22.3VDC Nominal/ 500mA max/1V voltage drop maximum.

7.10 Auxiliary Power

This special application supply is not supervised. This supply is rated at 24VDC Nominal/1.7A max. If there is a short on this circuit, the auxiliary power does not recover automatically when the short is removed. The main power must be disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply. See Appendix E: Auxiliary Devices on page 101.
37
Page 38

8.0 Turning on the Panel

8.1 Before Connecting the Power

1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC
supply.

8.2 Power-up procedure

After completing the steps in 8.1 above:
1. Plug in the AC power.
The A.C. ON LED illuminates, the TRBL LED flashes, and the buzzer sounds.
2. Press the SYSTEM RESET button.
The buzzer continues to sound and the TRBL LED continues to flash.
3. Connect the batteries as shown in Figure 26 below. Observe the correct polarity: the red wire is positive (+) and black wire is negative (-).
38
Page 39
Turning on the Panel
i
blk
MODU LE
TO RM-312/RM-306 RELAY
JW1
TO PR-300 MODULE
BATTERY
_
+
P3 P4
red
blk
red
red
P1 P2
SEC. TX
SIG 3SIG 4
-+-+
red
_
+
_
+
yellow
red
blk
green
240 VAC 50Hz
120 VAC 60Hz
N
GND
Battery Battery
NOTE: TO PREVENT SPARKING, CONNECT BATTERIES AFTER THE
SYSTEM MAIN A.C. POWER IS TURNED ON
Figure 26 Battery connections
All indicators should be off except for the green A.C. ON LED and the green Trouble Relay LED on the left side of the main board. It is shown in Figure 7 on page 21
.
Note: The green Trouble Relay LED on the left side of the main board is illuminated
when the system is normal. This LED is for diagnostics and indicates that the Trouble Relay is in normal standby condition.
4. Configure the Fire Alarm Control Panel as described in 11.0 Configuration with the CFG­300 LCD Service Tool on page 59.
39
Page 40

8.3 Troubleshooting

Symptoms Possible Cause
Normally when a circuit trouble occurs, its designated trouble indicator is illuminated, as
well as the COMMON TROUBLE indicator and trouble buzzer. To correct the fault, Circuit Trouble
Remote Fail
Ground Fault
Battery Trouble
check for open wiring on that particular circuit loop, and check that the circuit is not
disconnected or bypassed. For information about disconnecting circuits, see 9.5 Circuit
(Zone) Disconnect Buttons on page 49.
Note: Disconnecting a Circuit causes a system trouble.
Remote Fail is indicated on the main panel display for any failure reported by, or failure
to communicate with a remote annunciator or other remote device.
This panel has a common ground fault detector. To correct the fault, check for any
external wiring touching the chassis or other Earth Ground connection.
Check for the presence of batteries and their conditions. Low voltage (below 20.4 V)
causes a battery trouble. If battery trouble condition persists, replace batteries as soon
as possible.
Turning on the Panel
Walk Test Mode
Common Trouble
If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode. See 11.9
7. Walk Test (Command-Menu) on page 76.
If only the COMMON TROUBLE LED is illuminated on the main panel and none of the
above confirming trouble indicators are on, check the following:
Any missing interconnection wiring.
Any Module missing that was part of the Configuration.
Improperly secured cabling.
40
Page 41

9.0 Indicators, Controls and Operations

WALK
TEST
REMO TE
TROUBLE
CP U FAULT
GRO UND
FAU LT
SIGNAL
SILENCE
FIRE
DRILL
GENE RA L
ALARM
SYSTEM
RES ET
AUX
DISC ONNE CT
LAMP
TEST (MENU)
ALM/SUP/TBL/
BLDG AUDIBLE
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON TROUBLE
BATTERY TROUBLE
ZONE-1
DISC ONNE CT
ZONE-3
DISC ONNE CT
ZONE-5
DISC ONNE CT
ZONE-7
DISC ONNE CT
ZONE-9
DISC ONNE CT
ZONE-11
DISC ONNE CT
ZONE-2
DISC ONNE CT
ZONE-4
DISC ONNE CT
ZONE-6
DISC ONNE CT
ZONE-8
DISC ONNE CT
ZONE-10
DISC ONNE CT
ZONE-12
DISC ONNE CT
NAC -1
DISC ONNE CT
NAC-3
DISC ONNE CT
NAC-2
DISC ONNE CT
NAC-4
DISC ONNE CT
0
2
4
6
8
*
1
3
5
7
9
#
ENTER
INFO
CANCEL
10 Q Z
2 A B C 3 D E F
4 G H I
5 J K L
6 M N O 7 P R S
8 T U V 9 W X Y
BACK SPACE Forward
SIL (MENU)
Use these buttons for configuration. Their functions are printed under the label.
Use these buttons for configuration. Their functions are printed under the label.
AUTOMATIC
ALARM SIGNAL
CANCEL
Refer to Figure 27 below for LED Indicator and Control Button locations.
Figure 27 LED indicators and control buttons
41
Page 42
Indicators, Controls and Operations
i
The Main Display Panel on the Main Fire Alarm Control Board consists of:
18 common LED Indicators (top half of display)
8 Common Buttons (top half of display)
Up to 12 Initiating Circuit Alarm LEDs and 12 Initiating Circuit Trouble LED Indicators
4 Indicating Circuit LEDs (labeled NAC - Notifying Appliance Circuit)
Up to 16 disconnect buttons (12 for initiating circuit and 4 for indicating circuits)
LED Indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates.
Fast flash (Supervisory)- 120 flashes per minute, 50% duty cycle
Trouble flash (Trouble)- 20 flashes per minute, 50% duty cycle
Note that each display is supplied with laser printer printable paper labels for sliding into the
plastic label template on the panel. For the Main Display, the paper label is Mircom# NP-2005;
this includes English and French versions.
Note: There are different labels for two stage operation.

9.1 Common Indicators

9.1.1 Buzzer

The buzzer is activated by any of the following events:
Fire Alarm Steady Supervisory Alarm Fast flash Trouble Trouble flash rate
If the buzzer is turned on in response to a Non-Latching Trouble or Supervisory, it is turned off if the condition causing it goes away and there is no other reason for it to be on.

9.1.2 A.C. ON LED

The green AC ON Indicator illuminates steadily as long as the main AC power is above minimum level. The LED turns off when the level falls below the power-fail threshold and the panel is switched to standby (battery) power.

9.1.3 COMMON ALARM LED

The red COMMON ALARM LED illuminates steadily whenever the panel detects an alarm condition on any initiating circuit. Pressing the GENERAL ALARM button also turns on the COMMON ALARM LED. The LED remains on until the SYSTEM RESET button is pressed.
42
Page 43

9.1.4 COMMON SUPERVISORY LED

i
The amber COMMON SUPERVISORY LED illuminates steadily when there is a Supervisory Alarm in the panel caused by any Latching or Non-Latching Supervisory Circuit. The LED is turned of when all Non-Latching Supervisory Circuits are restored and there are no active Latching Supervisory Circuits. Latching Supervisory Alarms remain active until the SYSTEM RESET button is pressed.

9.1.5 COMMON TROUBLE LED

The amber COMMON TROUBLE LED illuminates steadily when the panel detects any trouble condition. It turns off when all Non-Latching Troubles are cleared.

9.1.6 REMOTE TROUBLE LED

The amber REMOTE TROUBLE LED flashes at the Trouble flash rate if there is trouble detected at a City Tie or DACT, or if there is communication trouble detected with a Remote Annunciator or if a Remote Annunciator reports a local trouble. It is turned off if these conditions go away.
Indicators, Controls and Operations

9.1.7 FIRE DRILL LED

The amber FIRE DRILL LED illuminates steadily while Fire Drill is active.

9.1.8 AUTOMATIC ALARM SIGNAL CANCEL LED (or ALM/SUP/TBL/BLDG AUDIBLE SIL LED for single stage systems)

If the panel is configured as a two-stage system, the AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge) LED illuminates steadily when the Alarm timer is canceled by the activation of the AUTOMATIC ALARM SIGNAL CANCEL or SIGNAL SILENCE buttons. The LED goes out when the SYSTEM RESET button is pressed.
This LED can be configured to flash amber at the fast rate while the Auto General Alarm timer is running (see Table 14 on page 63). If the Auto General Alarm timer times out and puts the
panel into General Alarm, the LED turns off.
Note: If this LED is configured to flash (see section 11.3 on page 67), then the panel is
outside of UL/ULC certification acceptability. The authority having jurisdiction must approve this selection.
If the panel is not configured as a two-stage system, this LED is ALM/SUP/TBL/BLDG AUDIBLE SIL (buzzer silence). It flashes at the slow rate when the ALM/SUP/TBL/BLDG AUDIBLE SIL button is pressed.

9.1.9 GENERAL ALARM LED

The red GENERAL ALARM LED illuminates steadily when the GENERAL ALARM button is pushed, a General Alarm Initiating Circuit is activated, or the Auto General Alarm timer times out. Once the GENERAL ALARM LED is on it stays on until the SYSTEM RESET button is pressed.
43
Page 44

9.1.10 WALK TEST LED

The amber WALK TEST LED illuminates steadily to indicate that the panel is in Walk Test Mode. If the panel is left in this mode for over an hour with no operator activity, the panel returns to normal and the WALK TEST LED turns off.

9.1.11 CPU FAULT LED

The amber CPU FAULT LED flashes approximately ¼ second every 2 seconds to indicate a processor failure on the main board. In addition, the buzzer sounds in time with the CPU FAULT LED until the fault is corrected.
To test the CPU FAULT LED
1. Disconnect AC and batteries from the main board.
2. Connect AC and the batteries as described in section 8.0 on page 38.
If the CPU FAULT LED is functioning properly, it will flash once when the board powers up.

9.1.12 AUXILIARY DISCONNECT LED

Indicators, Controls and Operations
The amber AUXILIARY DISCONNECT LED flashes at the Trouble rate when the AUXILIARY DISCONNECT button is pressed. It turns off when the AUXILIARY DISCONNECT button is pressed a second time. When it is flashing, the Auxiliary Alarm Relay is disconnected. Depending on the configuration, the AUXILIARY DISCONNECT button can also disconnect the Common Alarm Relay and Common Supervisory Relay (see section 11.0 Configuration with the CFG-300 LCD Service Tool on page 59). When the AUXILIARY DISCONNECT LED is flashing, the buzzer sounds.

9.1.13 SIGNAL SILENCE LED

The SIGNAL SILENCE LED flashes amber at the trouble rate when Indicating Circuits are silenced either by the SIGNAL SILENCE button or by the Auto Signal Silence timer. It is turned off when the signals are re-sounded by a subsequent alarm. For UL installations, disable the auto signal silence timer.

9.1.14 BATTERY TROUBLE LED

The amber BATTERY TROUBLE LED flashes at the trouble rate when the battery is either low (below 20.4 VDC) or disconnected.

9.1.15 GROUND FAULT LED

The amber GROUND FAULT LED flashes at the trouble rate when the Ground Fault Detector detects a Ground Fault on any field wiring. It turns off when the Ground Fault is cleared.
44

9.1.16 SYSTEM RESET LED

This LED illuminates for a short time when the SYSTEM RESET button is pressed.
Page 45

9.2 Indicating Circuit Indicators

ZONE-1
DISC ONNE C T
Circuit Status LED Circuit Trouble LED
Circuit Disconnect Button
The panel has 1 indicator for each of the 12 initiating circuits (shown in Figure 27). Each indicator has a button and 2 LEDs, shown in Figure 28.
Figure 28 Alarm Circuit Indicator
The Circuit Disconnect Button is described in 9.5 Circuit (Zone) Disconnect Buttons on page 49. The LEDs are described in the 4 sections below.

9.2.1 Alarm Circuit Indicators

Table 6 applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water flow Alarm, Sprinkler Alarm, or General Alarm Circuits.
Table 6 Alarm Circuit Indicators
Indicators, Controls and Operations
Event Circuit Status LED Configuration
Circuit in Alarm Steady (red)
Verified Alarm
Pre-alarm Fast flash rate (red)
Sprinkler Alarm
Water flow Alarm Activated circuit reconnected (when you press the Disconnect button a second time)
Fast flash rate (red) for 5 seconds to indicate a pending alarm
Event Circuit Trouble LED Configuration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Circuit in Alarm OFF
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Verified Alarm
Non-Verified Alarm
Water flow Alarm
Sprinkler Alarm
General Alarm

9.2.2 Supervisory Circuit Indicators

This operation applies to Initiating Circuits configured as Latching or Non-Latching Supervisory Circuits. The following table summarizes the indications in response to different events.
Ta ble 7 Supervisory Circuit Indicators
Event Circuit Status LED Configuration
Latching Sup. Circuit in Alarm Steady (amber)
Non-Latching Sup.
45
Page 46
Indicators, Controls and Operations
Table 7 Supervisory Circuit Indicators (Continued)
Activated circuit reconnected (when you press the Disconnect button a second time)
Fast flash rate (red) for 5 seconds to indicate a pending alarm
Event Circuit Trouble LED Configuration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Latching Sup.
Non-Latching Sup.
Circuit in Alarm OFF

9.2.3 Property and Building Safety Indicators

This operation applies to initiating circuits configured as property and building safety circuits. The following table summarizes the indications in response to different events.
Table 8 Property and Building Safety Indicators
Event Circuit Status LED Configuration
Circuit Active Steady (amber) Activated circuit reconnected (when you
press the Disconnect button a second time)
Fast flash rate (red) for 5 seconds to indicate a pending alarm
Property and Building Safety
Event Circuit Trouble LED Configuration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Property and Building Safety
Circuit Active OFF
46
Page 47
Indicators, Controls and Operations
i

9.2.4 Trouble-only Circuit Indicators

This operation applies to initiating circuits configured as Trouble-only Circuits. The following table summarizes the indications in response to different events.
Ta ble 9 Trouble-Only Circuit Indicators
Event Circuit Trouble LED Configuration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Short Circuit
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Trouble Only
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)

9.3 Signal Circuit Indicators

This operation applies to indicating circuits of any type. The Circuit Trouble Indicator flashes amber at the Trouble Rate to indicate short-circuit or open-circuit trouble, or if the circuit is Disconnected.
Ta ble 10 Signal Circui t In di ca to rs
Event Circuit Trouble LED Configuration
Open circuit
Short Circuit
Disconnected
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Flashes at the trouble rate (amber)
Signal

9.4 Common Controls

Note: To activate a button, press and hold it for 3 seconds.

9.4.1 SYSTEM RESET Button

The SYSTEM RESET button resets the Fire Alarm Control Panel and all Circuits. In particular, the SYSTEM RESET button does the following:
Resets all Latching Trouble Conditions
Resets all Initiating Circuits
Resets 4-Wire Smoke Supply
47
Page 48
Turns off all Indicating Circuits
Turns off SIGNAL SILENCE, AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge),
and GENERAL ALARM Indicators
Turns off Fire Drill
Stops and resets all timers
Processes inputs as new events
Does not affect Auxiliary Disconnect

9.4.2 SIGNAL SILENCE Button

Press the SIGNAL SILENCE button when the panel is in alarm to turn on the SIGNAL SILENCE LED and deactivate any Silenceable Indicating Circuits. Non-Silenceable Circuits are unaffected. Signals resound if there is a subsequent alarm. Pressing SIGNAL SILENCE again resounds all silenceable signals. This button does not function when the signal silence inhibit timer is running (see Table 14 on page 63). It also does not function if the indicating circuits are active as the result of a fire drill.
In a two-stage system, the SIGNAL SILENCE button silences the stage 1 and stage 2 alarms.
Indicators, Controls and Operations

9.4.3 FIRE DRILL Button

The FIRE DRILL button activates all Non-Disconnected Indicating Circuits, but does not transmit any Alarms via the City Tie, Common Alarm Relay or Auxiliary Alarm Relay. Fire Drill activates the signals in the evacuation code programmed. For example in the Temporal Code, the signals pulse on for 0.5 seconds, off for 0.5 seconds in rounds of 3 and then pause for 1.5 seconds and repeat.
Fire Drill is canceled by pressing the button again, or if the Panel goes into a real alarm.

9.4.4 AUTOMATIC ALARM SIGNAL CANCEL Button (or ALM/SUP/TBL/BLDG AUDIBLE SIL Button for single stage systems)

If the Panel is configured as a two-stage system, pressing the AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge) button while the Auto General Alarm timer is running (there is an alarm in the panel, but it is still in the first stage), cancels the timer and illuminates the amber AUTOMATIC ALARM SIGNAL CANCEL LED steadily, thereby acknowledging the alarm.
If the Panel is not configured as a two-stage system, this button becomes ALM/SUP/TBL/ BLDG AUDIBLE SIL (buzzer silence). Press this button to silence the buzzer.

9.4.5 GENERAL ALARM Button

Press the GENERAL ALARM button to immediately send the panel into General Alarm or total evacuation. It also re-activates the signals if they have been silenced during General Alarm. The General Alarm condition remains active until the SYSTEM RESET button is pressed.
48

9.4.6 AUXILIARY DISCONNECT Button

Press the AUXILIARY DISCONNECT button to disconnect the Auxiliary Alarm Relay. The Common Alarm Relay, the Common Supervisory relay and all correlated alarm relays may be disconnected as selected through configuration (see 11.0 Configuration with the CFG-300 LCD Service Tool on page 59). Pressing the AUXILIARY DISCONNECT button also causes the COMMON TROUBLE LED to illuminate steadily, the common trouble relay to send a
Page 49
trouble message and the buzzer to flash at the trouble flash rate. Pressing the AUXILIARY
12DET/4SIG LED UDACT
Version 1.7.8
DISCONNECT button causes the system to return to normal.

9.4.7 LAMP TEST Button

Press the LAMP TEST button to cause all front panel LEDs (except the CPU FAULT LED) to illuminate steadily and turn the buzzer on. If Lamp Test is active for more than 10 seconds, Common Trouble is activated.
Press and hold the LAMP TEST for 3 seconds to show the information about the system and the firmware version as shown below.
Figure 29 LAMP TEST
The first line shows the number of zones and panel type and the second line shows the firmware version number.
Indicators, Controls and Operations

9.4.8 ALM/SUP/TBL/BLDG AUDIBLE SIL Button (or MENU for single stage systems)

If the Panel is configured as a two-stage system, press the ALM/SUP/TBL/BLDG AUDIBLE SIL (buzzer silence) button to silence the buzzer. The buzzer resounds if there is a subsequent event. Pressing the button when the buzzer is not sounding has no effect.
If the Panel is configured as a single stage system, press the MENU button to select the command menu when a CFG-300 Service Tool with LCD is connected. Otherwise, this button has no effect.

9.5 Circuit (Zone) Disconnect Buttons

There are Circuit (Zone) Disconnect buttons for all initiating and indicating circuits on the Fire Alarm Control Panel. These buttons are located beside their respective indicating LED.
Pressing a Circuit Disconnect button bypasses the associated circuit and turns on its Trouble Indicator, activating Common Trouble. While a Circuit is disconnected, all changes in status (alarms and troubles) on that circuit are ignored. The panel does not activate disconnected indicating circuits. Circuit Disconnect buttons are toggle switches: pressing an activated switch a second time reconnects the circuit.
Disconnecting an active Latching Initiating Circuit (including Alarms, Water flow Alarm, Sprinkler Alarm, General Alarm, and Latching Supervisory) does not affect its status until the SYSTEM RESET button is pressed. Disconnecting an active Non-Latching Initiating Circuit (including Non-Latching Supervisory and Trouble-Only) causes them to behave as if the alarm situation has disappeared. Disconnecting an active indicating circuit immediately deactivates the circuit.
When an Initiating Circuit Disconnect button is pressed again in order to reconnect the circuit, the panel checks the state of the circuit. If the circuit is active, the Status Indicator flashes for 10 seconds at the Fast Rate without processing the input. If the Circuit is not reconnected by then, it is processed as a new input.
49
Page 50
Disconnect buttons are also used during Walk Test as described in 11.9 7. Walk Test
i
(Command-Menu) on page 76.

9.6 Common Relays

9.6.1 Auxiliary Alarm Relay

The Auxiliary Alarm Relay functions the same way as the Common Alarm Relay in every respect except that it can be disconnected by Auxiliary Disconnect with or without other correlated relays if it is programmed to do so (see Table 14 on page 63). When configured (see Table 14 on page 63), the relay can also be disconnected if signal silence is active and reconnected if signal silence is de-activated.

9.6.2 Common Alarm Relay

The Common Alarm Relay activates when the common alarm sequence is activated. On a two-stage system the relay may be configured to operate either on the first stage or both the first and second stage alarm (see Table 14 on page 63). The common alarm relay is disconnected by Auxiliary Disconnect if programmed (see Table 14 on page 63). The relay remains on until the SYSTEM RESET button is pressed.
Indicators, Controls and Operations

9.6.3 Common Supervisory Relay

The Common Supervisory Relay activates when the common supervisory sequence is activated as the result of an alarm on any un-bypassed latching or non-latching supervisory circuit. The relay is turned off if all non-latching supervisory circuits are restored and there are no latching supervisory circuits active. The relay can be disconnected by Auxiliary Disconnect if programmed (see Table 14 on page 63). The relay functions the same way as an alarm relay if the supervisory relay is disabled (see Table 14 on page 63).

9.6.4 Common Trouble Relay

The Common Trouble relay is activated when the common trouble sequence is activated as the result of the trouble condition being detected on the system. It is turned off when all
troubles are cleared.
Note: Some troubles are latching: once they are detected they remain active until the
SYSTEM RESET button is pressed. In this case the common trouble indicator also remains active until the SYSTEM RESET button is pressed. The common trouble is not bypassed by the Auxiliary Disconnect function.

9.7 Circuit Types

9.7.1 Initiating (Detection) Circuit Types

9.7.2 Non-Verified Alarm

A Non-Verified alarm can have pull stations, smoke detectors, or heat detectors attached to it. Activation of any of these devices immediately results in an alarm condition in the Fire Alarm Control Panel. An Alarm condition causes the associated Circuit Status LED and the COMMON ALARM LED to illuminate red.
50
Page 51

9.7.3 Verified Alarm

i
i
Verified Alarms are verified by a reset and timing procedure, and may include smoke detectors, heat detectors or pull stations. Activation of pull stations or heat detectors results in an alarm condition in the Fire Alarm Control Panel within four seconds. Smoke detectors are verified for a real alarm within 60 seconds, depending upon the startup time of the devices being used. If four seconds is too long a response time for pull stations, then wire them separately on a Non-Verified Alarm Circuit. An alarm condition causes the associated Circuit Status LED and the COMMON ALARM LED to illuminate red.

9.7.4 Sprinkler Alarm (for Sprinkler Flow Sensors)

Sprinkler Alarms are identical to normal Non-Verified Alarms unless Water flow retard operation is enabled. If Water Flow Retard Operation is enabled, then these circuits are sampled every one second. If ten samples are active within any 15-second interval, the Sprinkler Alarm is confirmed and processed. An Alarm condition causes the associated Circuit
Status LED and the Common Alarm LED to illuminate red.
Note: Do not use Retard Operation with any external retarding device; maximum retard
may not exceed 120 seconds.
Indicators, Controls and Operations

9.7.5 Water Flow Alarm (Water flow Sensors)

Water Flow Alarms are identical to normal Non-Verified Alarms except that any indicating circuits programmed to these circuits (all are by default) are Non-Silenceable. Also, if Water Flow Retard Operation is enabled (see Table 14 on page 63), these circuits are sampled every one second. If ten samples are active within any 15-second interval, the Water flow Alarm is confirmed and processed. An alarm condition causes the associated Circuit Status LED and
the Common Alarm LED to illuminate red.
Note: Do not use Retard Operation with any external retarding device; maximum retard
may not exceed 120 seconds.

9.7.6 Non-Latching Supervisory (For Supervisory Circuits)

Activation on these circuits causes the Circuit Status LED and the amber COMMON SUPERVISORY LED to illuminate. The buzzer sounds at the fast rate. If the circuit activation is removed, the Supervisory condition clears (as long as there are no other Supervisory conditions in the system) and the Circuit Status LED turns off.

9.7.7 Latching Supervisory (For Supervisory Devices)

Activation on these circuits causes the Circuit Status LED and the amber COMMON SUPERVISORY LED to illuminate. The buzzer sounds at fast rate. If the circuit activation is removed, the Supervisory condition does NOT clear.

9.7.8 General Alarm

The General Alarm provides remote general alarm for remote key switches. In a two-stage system these inputs perform exactly the same function as the Front Panel or Remote
51
Page 52
Annunciator General Alarm button. In a single stage system, these inputs act the same as Non-Verified Alarms; however, if Correlations are enabled, General Alarm Initiating Circuits are correlated to ALL indicating circuits.

9.7.9 Property and building safety

This is a supervised general-purpose non-latching input used mainly for correlating to a relay circuit associated with property and building safety. No other system condition occurs as a result of its activation (short circuit), although it is supervised for Trouble (open circuit).

9.7.10 T rouble-Only

The Trouble-Only circuit monitors a Trouble Condition from an external device such as QX­5000 Audio System. Both open and short circuits generate a non-latching Trouble condition.

9.8 Indicating (Signal) Circuit Types

9.8.1 Silenceable Signal

The Silenceable Signal circuit is used for audible devices such as bells and piezo mini-horns that may be silenced either manually or automatically. While sounding, these devices follow the pattern appropriate for the condition: the configured Evacuation Code (default is Temporal Code) during Single-Stage Alarm or Two-Stage General Alarm, or the Alert Code during the alert (first) stage of a two-stage alarm.
Indicators, Controls and Operations

9.8.2 Non-Silenceable Signal

The Non-Silenceable Signal Circuit is used for audible devices such as bells and piezo mini-
horns that may not be silenced either manually or automatically. While sounding, these
devices follow the pattern appropriate for the condition: the configured Evacuation Code (default is Temporal Code) during Single-Stage Alarm or Two-Stage General Alarm, or the Alert Code during the alert (first) stage of a two-stage alarm.

9.8.3 Silenceable Strobe

Silenceable strobes are silenced when the SIGNAL SILENCE button is pressed. For
synchronous strobes see section 10.0 Supported Protocols/Devices on page 56. (Note: Strobes do not support any code pattern.)

9.8.4 Non-Silenceable Strobes

Non-Silenceable Strobes are not silenced when the SIGNAL SILENCE button is pressed. For
synchronous strobes see section 10.0 Supported Protocols/Devices on page 56. (Note: Strobes do not support any code pattern.)

9.9 Evacuation codes (Signal Rates)

9.9.1 Single stage codes

52
Continuous On 100% of the time
Temporal Code 3 of 0.5 second on, 0.5 second off then, 1.5 second pause
Page 53
March Code 0.5 second on, 0.5 second off
California Code 5 seconds on, 10 seconds off

9.9.2 Two-step codes

Alert Code 0.5 second on, 2.5 seconds off
General Alarm Evacuation Code as selected from above.
Indicators, Controls and Operations
Continuous
0.5s
0.5s
0.5s
0.5s
5s
10s
0.5s
2.5s
1.5s
Figure 30 Evacuation and Alert Codes

9.10 Single Stage Operation

In a single stage system all alarm inputs are treated in a similar manner. Alarm inputs include any of the following: Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, Water flow Alarm, and General Alarm Circuits. If any of these alarm inputs occur when the panel is not already in alarm, the following occurs:
The buzzer sounds steadily
If Fire Drill is active, it is canceled
The Common Alarm Indicator turns on
Temporal Code
March Code
California Code
Alert Code
The Common Alarm, Auxiliary Alarm and all correlated relays activate if Auxiliary
Disconnect is not active
The Auto Signal Silence Timer, if configured, starts. For UL installations, disable the
auto signal silence timer
The Signal Silence Inhibit Timer, if configured, starts
All connected relays programmed to the input are activated (provided that Aux
Disconnect is not active)
Non-disconnected strobes associated with the input are activated
Non-disconnected signals associated with the input are activated at the evacuation rate
Pressing the General Alarm button on the panel also initiates a general alarm.
Subsequent alarms when the panel is already in alarm cause the following:
The alert buzzer sounds steadily
53
Page 54
If Signals have been silenced as a result of the Signal Silence button or the Auto Signal
Silence Timer, Signals are resounded as they were before Signal Silence, the Signal Silence Indicator is turned off, and the Auto Signal Silence Timer, if configured, is restarted. For UL installations, disable the auto signal silence timer
Any additional non-disconnected strobes associated with the new input are activated
continuously
Any additional non-disconnected signals associated with the new input are activated at
the evacuation rate

9.11 Two-stage Operation

In a Two-Stage System Alarm inputs are either First Stage (Alert) inputs or Second Stage (General Alarm) inputs. First Stage inputs include inputs from the following types of circuits: Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, and Water flow Alarm. Second Stage inputs include Alarms on General Alarm Circuits, activation of the General Alarm button, or expiration of the Auto General Alarm Timer.
If any of these alarm inputs occur when the panel is not already in alarm, the following occurs:
Indicators, Controls and Operations
The buzzer sounds steadily.
If Fire Drill is active, it is canceled.
The Common Alarm Indicator turns on.
The Common Alarm, Auxiliary Alarm and all correlated relays activate if Auxiliary
Disconnect is not active.
The Auto Signal Silence Timer, if configured, starts. For UL installations, disable the
auto signal silence timer.
The Signal Silence Inhibit Timer, if configured, starts.
All non-disconnected relays programmed to the input are activated provided that
Auxiliary Disconnect is not active.
If the alarm is a Second Stage alarm all connected strobe circuits are activated continuously, all non-disconnected signal circuits are activated at the evacuation rate, and the GENERAL ALARM LED is turned on.
If the alarm is a First Stage alarm, the following occurs:
Non-disconnected strobe circuits programmed to that circuit are activated continuously.
Non-disconnected signal circuits programmed to that circuit are activated with the Alert
Code (see 9.8 Indicating (Signal) Circuit Types on page 52).
The Auto General Alarm Timer, if configured, starts.
54
The AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge) LED starts flashing if
programmed. See Table 14 on page 63.
Subsequent First Stage alarms when the panel is already in alarm cause the following:
The buzzer sounds steadily.
If Signals have been Silenced as a result of the SIGNAL SILENCE button or the Auto
Signal Silence Timer, Signals are resounded as they were before Signal Silence, the SIGNAL SILENCE LED is turned off, and the Auto Signal Silence timer, if configured, is restarted. For UL installations, disable the auto signal silence timer.
Page 55
Indicators, Controls and Operations
If the panel is not already in General Alarm, additional non-Disconnected Signals
programmed to the new input are activated with the Alert Code (see 9.8 Indicating (Signal) Circuit Types on page 52).
If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL
CANCEL LED is on steady, indicating that the Auto General Alarm Timer has been acknowledged, the timer is restarted and the AUTOMATIC ALARM SIGNAL CANCEL LED is extinguished (or blinks if it has been configured to blink).
A Second Stage Alarm (General Alarm) when the panel is already in alarm causes the following:
The buzzer is sounded steady
All non-disconnected signals are activated at the evacuation rate
If the SIGNAL SILENCE LED is on, it is turned off and the Auto Signal Silence Timer, if
configured, is restarted. For UL installations, disable the auto signal silence timer
The AUTOMATIC ALARM SIGNAL CANCEL LED if on, is turned off
Alarm inputs are latching, which means that they remain active until the SYSTEM RESET
button is pressed. Note that if the system is configured for Correlations, any Second Stage/ General Alarm (caused by the Auto General Alarm Timer, the GENERAL ALARM button on
the Front Panel or Remote Annunciator, or by a General Alarm Initiating Circuit) condition
activates ALL Indicating Circuits, whether they are correlated or not.
55
Page 56

10.0 Supported Protocols/Devices

i

10.1 Synchronous St robes

A separate compatibility list is available for different supported models.
Strobes can be configured as normal (not synchronized or any of the above; see 11.0
Configuration with the CFG-300 LCD Service Tool on page 59). Any selection made is system-
wide (that is, whatever is selected applies to all the circuits in the system, configured as strobes).

10.1.1 Signal silence action on strobes

The signal silence action on strobes depends upon the configuration. The following describes the signal silence action on non-silenceable and silenceable strobes.

10.1.2 Non Silenceable strobe

If the output zone is configured as Non-Silenceable Strobe and if the SIGNAL SILENCE LED is flashing on the panel while the strobes are active, the horn is silenced. If the signal is activated again, the panel activates the horn again.

10.1.3 Silenceable strobe

If the output circuit is configured as Silenceable Strobe, and if the SIGNAL SILENCE LED is flashing on the panel, both the horn and strobe are completely turned off by turning off the
output circuit. Pressing the SIGNAL SILENCE button again turns them on again.
Note: Please see the strobes manufacturer’s data for details.

10.2 System Sensor’s i3 Devices

The FA-300 fire control panel supports System Sensor’s i3 devices. Only the two wire smoke
3
detectors are supported on the i build in fixed temperature (135F / 57.2C) thermal detector and is capable of sensing a freeze condition i.e. if the temperature is below 41F / 5 C.
The zones should be programmed to i
11.0). If the zone is not programmed as i
simply treated as a regular zone. The panel is capable of detecting multiple troubles; if different devices have different troubles on the same zone, all troubles are reported. The
following troubles are reported for the i
zone, which are 2W-B and 2WT-B. Model 2WT-B features a
3
devices.
3
devices to be considered as i3 zone (see Chapter
3
zone and i3 devices are connected to the zone, it is

10.2.1 i3 Zone Troubles

The following troubles can be reported for a zone configured as i3 zone:
56
Page 57
Open circuit trouble
Zone-1
Open Trb. 1/ 1
Zone-1
Communic. Trb 1/ 1
Zone-1
Dirty Dev. Trb 1/ 1
Zone-1
Out of Sens Trb 1/ 1
Communication trouble
Out of sensitivity: defective or dirty device
Freeze trouble

10.2.2 Open Circuit Trouble

If the loop is broken the panel shows open loop trouble. The panel can still communicate with the devices depending upon where the open occurs.
Figure 31 Open Circuit Trouble

10.2.3 Communication Trouble

If there is a fault in the line or the line is too noisy, the panel cannot communicate with the devices. The panel shows a communication trouble in this case.
Supported Protocols/Devices
Figure 32 Communication Trouble

10.2.4 Dirty Device Trouble

If any of the devices on the i3 zone are dirty, the panel shows a Dirty Device trouble. The device needs cleaning or be replaced with a new device.
Figure 33 Dirty Device Trouble

10.2.5 Out of sensitivity Tr ouble

If any of the devices on the i3 zone is out of sensitivity and cannot detect an alarm condition, the panel shows out of sensitivity trouble. In this condition the device is not usable and should be replaced.
Figure 34 Out of sensitivity Trouble
57
Page 58

10.2.6 Freeze T rouble

Zone-1
Freeze Trb. 1/ 1
If the device has detected a freeze condition, (e.g. the temperature is below 41F / 5 C) then the panel displays a freeze trouble. Only model 2WT-B is capable of thermal detection; model 2W-B does not indicate any freeze trouble.
Figure 35 Freeze Trouble
Supported Protocols/Devices
The LEDs on the i
3
smoke detectors provide a local visual indication of the detector status.
The smoke detector LED status should be confirmed with the panel, since Out of Sensitivity and a Dirty Device have the same LED indication on the detector and the only way to distinguish between the two is to use the CFG-300 Configuration Tool and check the messages as noted above.
Table 11 i
i3 Detector Condition
3
Smoke Detector LEDs
Green LED Red LED
Power-up Blinks every 10 sec Blinks every 10 sec Normal (Standby) Blinks every 5 sec OFF Out of sensitivity (defective or dirty) OFF Blinks every 5 sec Freeze trouble OFF Blinks every 10 sec Alarm OFF Solid
58
Page 59
11.0 Configuration with the CFG-300 LCD
Service Tool
Table 12 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Auto signal silence timer
Table 13 Settings permitted in UL864
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in UL864, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Auto signal silence timer
There are three methods of configuring the FA-300 LED Series Fire Alarm Panels:
Using the CFG-300 LCD Tool. See this chapter.
Using a PC or laptop computer with a UIMA converter module.
Using a PC or laptop computer with remote connection (must use fire alarm with built-in
Permitted in CAN/ ULCS527? (Y/N)
Y
Permitted in UL864? (Y/N)
N
UDACT).
Possible settings\methods
Disabled or 5, 10, 15, 20, or 30 minutes
Possible settings\methods
Disabled or 5, 10, 15, 20, or 30 minutes
Settings permitted in CAN/ULCS527
All
Settings permitted in UL864
Disabled
This chapter describes how to configure an FA-300 LED Series Fire Alarm Panel with the CFG-300 LCD service tool.
59
Page 60
Configuration with the CFG-300 LCD Service Tool
WALK
TEST
REMOT E
TROUBLE
CP U FAULT
GROUND
FAUL T
SIGNAL
SILENCE
FIRE
DRILL
GENE RAL
ALARM
SYSTEM
RESE T
AUX
DISC ONNE CT
LAMP
TEST (MENU)
ALM/SUP/TBL/
BLDG AUDIBLE
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON TROUBLE
BATTERY TROUBLE
ZONE-1
DISC ONNE CT
ZONE-3
DISC ONNE CT
ZONE-5
DISC ONNE CT
ZONE-7
DISC ONNEC T
ZONE-9
DISC ONNE CT
ZONE-11
DISC ONNE CT
ZONE-2
DISC ONNE CT
ZONE-4
DISC ONNE CT
ZONE-6
DISC ONNE CT
ZONE-8
DISC ONNE CT
ZONE-10
DISC ONNE CT
ZONE-12
DISC ONNE CT
NAC-1
DISC ONNE CT
NAC-3
DISC ONNE CT
NAC-2
DISC ONNE CT
NAC-4
DISC ONNE CT
0
2
4
6
8
*
1
3
5
7
9
#
ENTER
INFO
CANCEL
10 Q Z
2 A B C 3 D E F
4 G H I
5 J K L
6 M N O 7 P R S
8 T U V 9 W X Y
BACK SPACE For ward
SIL (MENU)
Use these buttons for configuration. Their functions are printed under the label.
Use these buttons for configuration. Their functions are printed under the label.
AUTOMATIC
ALARM SIGNAL
CANCEL
Figure 36 shows the function of the buttons on the front panel display.
Figure 36 FA-300 Configuration
60

11.1 Accessing Configuration Mode

To access configuration mode
1. Connect the CFG-300. See the document included with the CFG-300 for details.
2. On a single stage system, press the MENU button.
On a two stage system, press the LAMP TEST and ALM/SUP/TBL/BLDG AUDIBLE SIL buttons simultaneously.
The CFG-300 displays the Main Menu.
3. Enter your passcode.
The minimum number of digits for the passcode is four and the maximum is ten. The
passcode must be numerical values only. The default passcode is 1111.
4. Press the ENTER button.
The main command menu appears.
Page 61
5. If the passcode is wrong, the system prompts you to re-enter the passcode. After three
Enter passcode
_
-Command Menu-
1. FA-300 Config
2. Config Info
3. Set Time
4. Set Password
5. View EventLog
6. Clear EventLog
7. Walk Test
8. I3 Loop test
9. Dialer Config
10.Test Dialer
11.Exit
tries the system takes you back to the normal message display.
Figure 37 Enter passcode

11.2 Command Menu

The command menu is shown in Figure 38. The first line of the LCD always displays
-Command Menu-, and the second line scrolls through different selections.
To scroll through the menu
Use the up and down arrow buttons, and then press the ENTER button to make a
selection.
To exit from the command menu
Configuration with the CFG-300 LCD Service Tool
Select the Exit menu option, and then press the ENTER button.
Note: Close jumper JW5 on the main board to access Command Menu features 1 and
9. See Figure 7 on page 21.
Figure 38 Command Menu

11.2.1 Using the Keypad to Program the FA-300

1. Access the configuration mode as described in 11.0 Configuration with the CFG-300 LCD Service Tool above.
61
Page 62
Configuration with the CFG-300 LCD Service Tool
1. Features
2. Inp. Zone
3. I3 Zones
4. Opt. Zone
-FA-300 Config-
5. Correlation
6. Inp Zone Label
7. Opt Zone Label
8. Default Config
2. Press ENTER to select an option.
The corresponding menu appears.
3. Press the up and down arrow buttons to scroll through the menu.
4. Press the left or right arrow buttons to select or unselect an option (selected = X). Use
the up and down arrows to scroll through the different options.
5. Once you have made the correct selection, press ENTER to confirm the change.
6. Press CANCEL to return to the previous menu.

11.3 1. FA-300 CONFIG (Command-Menu)

The FA-300 configuration menu is shown in Figure 39.

11.3.1 Command Menu/FA-300 Config-->Features

62
Figure 39 FA-300 Config menu
Page 63
Configuration with the CFG-300 LCD Service Tool
- Feature Config -
1 Man. Sig. Sil.
2 Fire Drill
3 Opt. Ckt. Corr
4 Wtr/Sprk. Retd
5 Aux Disc Prog
6 Sig-Sil Inh Tm
7 Aux Dis, Alm&Sup
8 Auto Sil. Tmr 9 Rem. Annun.
10 Alm. Xmit-Sil.
11 Pwr Fail Tmr.
12 Com. Supv. Rly
13 Sig-Sil. Isol.
14 Strobe Type
15 Signal Rate
16 Active EOL
17 Two Stage Op.
18 Gen-Alm Tmr
19 Com Alm Rly Op
Manual Sig. Silence
[X] ENABLE
Fire Drill
[X] ENABLE
Select Features to access the Feature Config menu shown in Figure 40.
Figure 40 Feature Config menu
Table 14 describes the options in the Feature Config menu.
Feature Default
Table 14 Feature Config menu
Command Menu/FA-300 Config/Features/
1. Manual Signal Silence
Command Menu/FA-300 Config/Features/
2.Fire Drill
20 1st stage LED ind
[X] ENABLE->Default
[ ] DISABLE
[X] ENABLE ->Default
[ ] DISABLE
Name in the
Configuration Utility
Manual signal silence
Fire drill
FA-300
Description
Use this menu to enable or disable the SIGNAL SILENCE button. See 9.4.2 SIGNAL SILENCE Button on page 48.
Use this menu to enable or disable the FIRE DRILL button. See 9.4.3 FIRE DRILL Button on page 48.
63
Page 64
Table 14 Feature Config menu
Opt. Ckt. Corr.
[X] DISABLE
Waterflow/Sprk. Retd
[X] DISABLE
Aux Disc Prog
[X] DISABLE
Sig-Sil. Inhibit Tmr
[X] DISABLE
Feature Default
Command Menu/FA-300 Config/Features/
3.Output Circuit Correlation
[X] DISABLE->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
4.Waterflow/Sprinkler Retard Operation
[X] DISABLE ->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
5.Aux. disconnect, disconnects Aux Alarm relay and all programmed relays
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
6.Signal-Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
Signal correlations
Retard waterflow and sprinkler circuit
"Aux Disconnect" disconnects prog. relay
Signal silence inhibit Timer
FA-300
Description
If enabled, the programmed correlations (see 11.3.5 Command Menu/FA-300 Config-­>Correlation on page 70) are effective. If disabled, the programmed correlations are ignored and all the output circuits are correlated to all the input circuits.
If disabled, all the initiating circuits configured as water flow or sprinkler act as non-verified alarms. If enabled, retard operation is performed for initiating circuits configured as water flow or sprinkler.
See 9.7.5 Water Flow Alarm (Water flow Sensors) on page 51.
If disabled, only the Auxiliary Alarm Relay is disconnected when you press AUXILIARY DISCONNECT (see 9.4.6 AUXILIARY DISCONNECT Button on page 48).
If enabled, the Auxiliary Alarm Relay and all correlated relays are disconnected when you press AUXILIARY DISCONNECT (see
9.4.6 AUXILIARY DISCONNECT Button on page 48). Correlated relays include: RM312/RM306 relays and SRM-312 relays.
Use this menu to inhibit the SIGNAL SILENCE button for a desired length of time. While this timer is running, pressing the SIGNAL SILENCE button has no effect. See 9.4.2 SIGNAL SILENCE Button on page 48. According to the Canadian National Building Code, this timer should be set to one minute.
64
Page 65
Table 14 Feature Config menu
Aux Dis,Dis Alm&Spv
[X] DISABLE
Auto Sig-Sil. Timer
[X] DISABLE
No. of Remote Annun.
[X] NONE
Alm. Xmit-Sil.
[X] DISABLE
AC Pwr Fail Dly Tmr.
[X] NONE
Feature Default
Command Menu/FA-300 Config/Features/
7. AUXILIARY DISCONNECT disconnects Alarm Relay and Supervisory Relay
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
8.Auto Signal Silence Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
Command Menu/FA-300 Config/Features/
9. Number of Remote Annunciators or smart relays
[X] NONE->Default
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
Command Menu/FA-300 Config/Features/
10.Silence Alarm transmit
[X] DISABLE->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
11.AC power fail delay timer
[X] NONE ->Default
[ ] 1 HRS
[ ] 2 HRS
[ ] 3 HRS
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
"Aux Disconnect" disconnects alarm relay
Signal silence Timer
Remote annunciators
Alarm transmit affected by signal silence
FA-300
Description
If enabled, the Common Alarm Relay and the Common Supervisory Relay, in addition to the Auxiliary Alarm Relay, are disconnected when you press AUXILIARY DISCONNECT (see
9.4.6 AUXILIARY DISCONNECT Button on page 48). The PR-300 does not transmit a supervisory or alarm event.
If disabled, pressing AUXILIARY DISCONNECT has no effect on the Common Alarm Relay, the Common Supervisory Relay, and the PR-300.
Use this menu to determine the time period for which the indicating circuits sound before they are automatically silenced. For UL installations, disable the Auto Signal Silence Timer.
Use this menu to select the number of remote annunciators. Any combination of remote annunciators or smart relays can be used as long as the total number does not exceed 6. The annunciators’ addresses should be without gaps and in sequence.
If disabled, the SIGNAL SILENCE button does not silence the Auxiliary Alarm Relay, but it does silence the indicating circuits. If enabled, the SIGNAL SILENCE button silences the Auxiliary Alarm Relay and the indicating circuits. See 9.4.2
SIGNAL SILENCE Button on
page 48.
Use this menu to delay the AC power fail trouble for the programmed time period. If disabled, the AC power fail is reported right away.
65
Page 66
Table 14 Feature Config menu
Common Supv. Relay
[X] DISABLE
Sig-Sil. Isolator
[X] DISABLE
Strobe Type
[X] NORMAL
Signal Rate
[X] TEMPORAL
Active EOL
[X] DISABLE
Two Stage Operation
[X] DISABLE
Feature Default
Command Menu/FA-300 Config/Features/
12.Common Supervisory Relay
[ ] ENABLE ->Default
[X] DISABLE
Command Menu/FA-300 Config/Features/
13.Signal Isolators
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
14.Strobe Type
[X] NORMAL ->Default
[ ] MIRCOM
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Command Menu/FA-300 Config/Features/
15.Signal Rate
[X] TEMPORAL->Default
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
Supervisory relay used as alarm relay
Isolators on signal circuits
Strobe
Signal rate
FA-300
Description
If enabled, the Common Supervisory Relay behaves as a common alarm relay. If disabled, it behaves as a common supervisory relay.
Enable this function only when suite isolators are used (Canada only).
Use this menu to select the manufacturer of the strobes used in the system. The selection is system-wide and applies to all indicating circuits configured as strobes. For NORMAL strobes there is no synchronization, while other strobes are synchronized and use manufacturer’s protocol to synchronize the strobes.
Use this menu to set the rate at which the indicating circuits sound.
Command Menu/FA-300 Config/Features/
16. Active EOL
[X] DISABLE->Default
[ ] NO
Command Menu/FA-300 Config/Features/
17. Two-stage Operation
[X] DISABLE->Default [ ] ENABLE
66
Active end-of-line
Second stage
Enable this function if using an Active End-of-Line resistor. Enable this function if you are using the ICAC-306 (the ICAC­306 has built in Active End-of­Line resistors).
Use this menu to allow the system to perform a two-stage operation. This selection also sets the Auto General Timer to 5 minutes.
The user should always either disable the Auto Signal Silence Timer or set it to be greater than the Auto General Alarm Timer.
Page 67
Table 14 Feature Config menu
Auto Gen-Alarm Timer
[X] DISABLE
Common Alm Rly. Oper
[X] SECOND STAGE
1st stage LED indic.
[X] DISABLE
Feature Default
Command Menu/FA-300 Config/Features/
18. Auto General Alarm Timer
[X] DISABLE->Default [ ] 5 Min [ ] 10 Min [ ] 15 Min [ ] 20 Min [ ] 30 Min
Command Menu/FA-300 Config/Features/
19. Common Alarm Relay Operation
[ ] BOTH STAGES­>Default
[X] SECOND STAGE ONLY
Command Menu/FA-300 Config/Features/
20. First Stage LED
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
General alarm Timer
Alarm relay second stage
FA-300
Description
This function is used for two­stage systems only. This function sets the time period for automatic evacuation.
Use this menu to allow the Common Alarm Relay to operate in second stage only or to operate in both stages.
When disabled, the AUTOMATIC ALARM SIGNAL CANCEL LED does not illuminate during the first stage alarm.
[X] DISABLE->Default
[ ] ENABLE
When enabled, the AUTOMATIC ALARM SIGNAL CANCEL LED flashes at the fast rate during the first stage alarm.
Note: If this option is enabled, then the panel is outside of UL/ ULC certification acceptability. The authority having jurisdiction must approve this selection.
67
Page 68
Configuration with the CFG-300 LCD Service Tool
i
1 Zone-1
2 Zone-2
--
--
Initiating Zone
12 Zone12
Zone-1 Type
[X] NON-VERIF ALARM
Zone-12 Type
[X] NON-VERIF ALARM
[ ] Zone-1
[ ] Zone-2
--
--
I3 Detection Zones
[ ] Zone-12
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

1 1.3.2 Command Menu/FA-300 Config-->Inp Zone

This Inp Zone menu is used to program the process type for the initiating circuits. The
maximum number of initiating circuits is 12. Only those supported by the particular model are shown in the CFG-300 Configuration Tool.
Command Menu/FA-300 Config/Ipt. Zone
1.Process Type (Initiating circuit)
[X] NON-VERIF ALARM
->Default
[ ] VERIF ALARM
[ ] SPRKL ALM
| | |
12.
[ ] WTR-FLOW ALM
[ ] NON-LATCH SUP
[ ] LATCH SUPV
[ ] GEN ALARM
[ ] BUILDING
[ ] TRB ONLY

1 1.3.3 Command Menu/FA-300 Config-->I3 Zone

[ ] Zone-1->Default
.
.
.
[ ] Zone-12->Default
Use this menu to select the circuit type of each input zone. See 9.7 Circuit Types on page 50.
Use this menu if i3 devices
are present on a zone. See
10.2 System Sensor’s i3 Devices on page 56.
68
Page 69
Configuration with the CFG-300 LCD Service Tool
i
1 NAC-1
2 NAC-2
3 NAC-3
4 NAC-4
Indicating Zone
NAC-1 Type
[X] SIL-ABLE
NAC-4 Type
[X] SIL-ABLE
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

11.3.4 Command Menu/FA-300 Config-->Opt Zone

This menu is used to program the process type of the indicating circuits. The maximum number of indicating circuits is 4. Only those supported by the particular model are shown in the CFG-300 Configuration Tool.
Command Menu/FA-300 Config/Opt. Zone
1.Process Type (Indicating Circuits)
| | |
4.
[X] SIL-ABLE->Default
[ ] NON SIL-ABLE
[ ] SIL-ABLE STR
[ ] NON-SIL STR
Use this menu to program the process type of each indicating circuit. See 9.8 Indicating (Signal) Circuit Types on page 52.
69
Page 70
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
i
Zone-1 Corr.
[X] NAC-1
Zone-12 Corr.
[X] NAC-1
i
1 Zone-1
2 Zone-2
--
--
Initiating Zone
12 Zone12
instructions on making menu selections.

1 1.3.5 Command Menu/FA-300 Config-->Correlation

Command Menu/FA-300 Config/Correlation
1.Correlation
Configuration with the CFG-300 LCD Service Tool
| | |
12.
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed

1 1.3.6 Command Menu/FA-300 Config-->Inp Zone Label

[X] NAC-1 ->Default
[X] NAC-2 ->Default
[X] NAC-3 ->Default
[X] NAC-4 ->Default
instructions on making menu selections.
Use this menu to correlate initiating circuits to indicating circuits. By default all the initiating circuits are correlated to all the indicating circuits.
70
Use the buttons described below for entering messages. These buttons are alternate functions of bypass switches and are physically located in the same position as described following.
Page 71
Command Menu/FA-300 Config/Ipt. Zone Lab el
Zone-1 Label
Zone-1
Zone-12 Label
Zone-12
i
1 NAC-1
2 NAC-2
3 NAC-3
4 NAC-4
Indicating Zone
1.Initiating zone label
[Zone-1 ]->Default
[Zone-12 ]->Default
BYPASS SWITCH TRANSLATION
| | |
12.
KEY SEQ 1 2 3 4 KEY SEQ 1 2 3 4
--------------------------------------
Zone-1
Zone-3 2 A B C Zone-4 3 D E F
Zone-5 4 G H I Zone-6 5 J K L
Zone-7 6 M N O Zone-8 7 P R S
Zone-9 8 T U V Zone-10 9 W X Y
Zone-11 Back Space Zone-12 Forward
Configuration with the CFG-300 LCD Service Tool
0 Q Z Zone-2 1
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

11.3.7 Command Menu/FA-300 Config-->Opt Zone Label

71
Page 72
Use the buttons described below for entering messages. These buttons are alternate functions
NAC-1 Label
NAC-1
NAC-4 Label
NAC-4
i
Load the default
settings? Y
Default settings
have been loaded
i
of bypass switches and are physically located in the same position as described below.
Command Menu/FA-300 Config/Opt. Zone Lab el
1.Indicating zone label
[NAC-1 ]->Default
[NAC-4 ]->Default
BYPASS SWITCH TRANSLATION
| | |
4.
KEY SEQ 1 2 3 4 KEY SEQ 1 2 3 4
--------------------------------------
Zone-1
Zone-3 2 A B C Zone-4 3 D E F
Zone-5 4 G H I Zone-6 5 J K L
Zone-7 6 M N O Zone-8 7 P R S
Zone-9 8 T U V Zone-10 9 W X Y
Zone-11 Back Space Zone-12 Forward
0 Q Z Zone-2 1
Configuration with the CFG-300 LCD Service Tool
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

11 .3.8 Command Menu/FA-300 Config-->Default Configuration

Use this menu to load the default configuration in
Press the up and down arrow buttons to select between Y/N. Press ENTER to restore the default configuration.
the panel.
Warning: When you load the default
configuration, the previously programmed configuration is lost permanently.

11.4 2. Config Info (Command-Menu

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
72
Page 73
Press the down arrow button to see
Configuration type:
Factory default
Job Name:
No job loaded
Technician ID:
Unknown
Cfg. Date and Time:
hh:mm day year:mm:dd
Configurator Version
x.x.x.x
i
1 Daylight Save
2 Time Clock
3 Compensation
Daylight Saving
[X] DISABLE
more information.
Press the down arrow button for further information.
Configuration with the CFG-300 LCD Service Tool
Configuration type shows how the panel was configured.
Factory default means the panel has not been configured;
it is as it came from the factory.
Front Panel means it was configured at the panel. Serial Port means the configuration was done from a
computer through the serial port.
Modem means the configuration was done remotely
through a modem.
If you upload a job configuration to the panel using the PC configuration utility, the job name appears on this screen. The job name can be up to a maximum of 20 characters.
If you upload a job to the panel using the FA-300 Configuration Utility, the technician’s name (ID) appears on this screen. The technician ID can be up to a maximum of 10 characters.
This screen shows the date and time that the configuration was last changed (if Time and Date have been set at the panel).
Press the down arrow button for further information.
This screen shows the version of the FA-300 Configuration Utility. It displays 0.0.0.0 if the FA-300 Configuration Utility was not used.

11.5 3. Set Time (Command-Menu)

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Command Menu/Set Time
1. Daylight saving time
[X] DISABLE ->Default
[ ] ENABLE
Use this menu to enable daylight savings time.
73
Page 74
Configuration with the CFG-300 LCD Service Tool
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01
Daily Compensation:
0
Daily Compensation:
Panel Config Updated
Command Menu/Set Time
2. Set time and date
Command Menu/Set Time
2. Compensation
When value is entered the following message appears
Default
00:00 MON 2000-01-01
Compensation value can range from -15 to +15 seconds.
Use this menu to set the time and date. Use the left and right arrow buttons to move the cursor to the desired location in the display and use the up and down arrow buttons to increase or decrease the values. Press ENTER to accept the changes and press CANCEL to ignore the changes.
Note: time is in 24 hour
format
Use the up down arrow buttons to select daily compensation value and press ENTER. For a fast clock adjust negatively. For a slow clock adjust positively. For example: for a clock which runs 5 minutes a month (based on 30 days) fast select -10 seconds.
74
Page 75
Configuration with the CFG-300 LCD Service Tool
i
Enter new passcode
[ ]
Re-enter passcode
[ ]
invalid passcode
Passcode updated
EAST LOBBY ENTRANCE
OPEN TRB 01/09
VERIFIED ALARM Z-01
2002/10/22 11:45.AM
ZONE
Message
EVENT
01 of 09
Process
Type
Physical
Zone No.
DATE
TIME
"INFO " Key
EVENT
type
ZONE
Message
EVENT
type
INFO
Process
Type
Physical
Zone No.
Time

11.6 4. Change password (Command-Menu)

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
If the passcode does not match, the following message appears:
If the passcode is OK the following message appears:
1 -> Default

11.7 5. View Event Log (Command-Menu)

The event log looks the same as the normal event queue (see 11.15 Zone messages on page 89). Press the INFO button to see more information about the event. Figure 41 shows an example of how the INFO button works.
Use this menu to change the passcode. The minimum number of digits is 4 and the maximum is 10. Only numeric digits are allowed.
Figure 41 The event log
The event log saves a maximum of 200 events.
75
Page 76
Configuration with the CFG-300 LCD Service Tool
i
-Select Log-
1 Alarm Log
2 General Log
3 All Logs
Clear all the
selected log(s)? Y
Log(s) cleared
i
Perform the
walk test? Y

11.8 6. Clear Event Log (Command-Menu)

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Use this menu to clear alarm logs, event logs, or both.
Figure 42 Select Log
1. Select the type of log to clear. Press the ENTER button. The system confirms before clearing logs.
Figure 43 Clear all the selected logs
2. Press the ENTER button to confirm or the CANCEL button to cancel the operation.
Figure 44 Logs cleared

11.9 7. Walk Test (Command-Menu)

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
A walk test allows an installer to verify the initiating circuit wiring in a system. When walk test is selected, the following screen appears:
76
Figure 45 Walk test confirmation
Page 77
Configuration with the CFG-300 LCD Service Tool
-WALK TEST ZONES-
[ ] Zone-1
-Walk test active-
Alarm:00 Trb:00
i
Press the ENTER button to activate the walk test and the CANCEL button to cancel the walk test. The next screen allows zones to be selected for walk test. Use the up and down arrow buttons to scroll through the zones and use the left and right arrow buttons to select a zone. Press the ENTER button when you are done with all the selections.
Figure 46 Walk test zones
The walk test is now active.
Figure 47 Walk test active
The activation of any initiating circuit that has been selected for a walk test causes the Audible Indicating Circuits (not Strobes) to activate briefly for a number of short bursts corresponding to the selected circuit number. If the first selected circuit is activated, the indication circuits sound for one burst. If the second selected circuit is activated, the indication circuits sound for two bursts, and so on. This means that if, for example, circuits 1, 3 and 5 were selected for the walk test, they would sound with one, two and three bursts respectively. The burst interval is half a second on and half a second off. After the sounding pattern has been sent on the indicating circuits, the initiating circuit is reset and tested again. If it is still active (in alarm) the pattern is re-sent. Trouble on any initiating circuit selected for the walk test activates the indicating circuits continuously for five seconds. Activation of a circuit also causes the alarm count to increase while the trouble on the initiating circuit causes the trouble count to increase.
Alarm Verification and Water flow Alarm Retard Operations are disabled on circuits being walk tested. All circuits not selected for the walk test continue to function normally. If a circuit was disconnected before the walk-test mode was entered and is not selected for the walk-test, it remains disconnected while the walk test is active. Walk test operation is disabled if the Fire
Alarm Control Panel is in alarm or goes into alarm while the walk test is active.
Notes: If a UDACT is used with the system, all walk-test events are reported to the
monitoring agency. The monitoring agency should be instructed to ignore reported events during the walk-test.
IF THERE IS NO ACTIVITY FOR ONE HOUR, THE SYSTEM RETURNS TO NORMAL OPERATION.
77
Page 78

11.10 8. i3 Loop Test (Command-Menu)

i
Perform the i3
Loop test? Y
-I3 TEST ZONES-
[ ]Zone-1
The selected zone
is not ready yet
The selected zone
is not i3 type
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
The i3 maintenance test is designed to test the devices on i3 zone. If there is noise on the line or if the device is too far away from the panel, the devices may not respond to the panel
3
inquiries. An i
power-up or after pressing the reset. If the i message appears on the screen:
maintenance test can be invoked from the command menu six minutes after
3
Configuration with the CFG-300 LCD Service Tool
maintenance test is selected, the following
Figure 48 i
If you select Y by pressing ENTER, the display asks you for which zone you want to perform
3
the i
test. Note that only one zone at a time can be in maintenance test. Select the zone by pressing the up and down arrow buttons and then pressing the right arrow button to select the device. After the device is selected press ENTER.
Figure 49 i
3
If the i information message appears.
Figure 50 i
If a zone is selected that is not configured as an i
3
loop test confirmation
3
test zones
maintenance test is selected within six minutes after power-up or reset, the following
3
test not ready
3
zone, the following message appears:
78
Figure 51 The selected zone is not i
After the zone goes into the i maintenance test takes five minutes. During this time you can walk through the device and
3
maintenance test, no other zone can be put into the test. The
3
type
Page 79
Configuration with the CFG-300 LCD Service Tool
i
1 Account Info
2 Telephone line
3 Report Options 4 Time Parameter
-Dialer Config-
5 Enable/Disable
make sure all the devices are working properly. The following table lists the status of the devices while in walk test.
Tab le 15 i3 Detector Statuses
i3 Detector Condition
Proper operation Double blink every 5 sec OFF Out of sensitivity OFF Double blink every 5 sec Freeze condition OFF Double blink every10 sec
You can cancel the maintenance test either by pressing the SYSTEM RESET button or by going into the configuration section and canceling the test.
Green LED Red LED

11.11 9. Dialer Config (Command-Menu)

Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Figure 52 shows the Dialer Config menu.
Figure 52 Dialer Config menu
79
Page 80
Configuration with the CFG-300 LCD Service Tool
1 Account#1 ID
2 Account#1 Tel
3 Accnt#1 Format
4 Account#2 ID
- Account Info -
5 Account#2 Tel
6 Accnt#2 Format
Account#1 ID:
_
Account#1 Telnum:
_

1 1.11.1 Command Menu/Dialer Config-->Account Info

Command Menu/Dialer Config/Account Info
1.Account# 1 Identification
123456->Default
Command Menu/Dialer Config/Account Info
2.Account#1 Telephone Number
[101]->Default
Use this menu to set the Account ID for the monitoring station to which the dialer reports events. The maximum # of digits allowed is six. For contact ID, only the first four digits are used; the last two are truncated.
Unless you are using the SIA protocol, the allowed digits for the account ID are simple digits 0 to 9 and hexadecimal digits A to F (the SIA protocol only allows digits 0 to 9).
To enter hexadecimal digits, press the INFO button. The letter “A” appears. To scroll through the rest of the letters, press INFO repeatedly. Press # to move the cursor to the right or press * to move it to the left.
Use this menu to set the telephone number of the monitoring station. The maximum # of digits allowed is 19 including “,” and numerals. The “,” is a 1 sec delay. To enter “,” press the INFO button. Press # to move the cursor to the right or press * to move it to the left. An example of a typical telephone # is 9,,12345678.
80
Page 81
Command Menu/Dialer Config/Account Info
ACCNT#1 Format:
[X] Contact ID
Account#2 ID:
_
Account#2 Telnum:
_
ACCNT#2 Format:
[X] Contact ID
3.Account#1 Reporting Format
[X] CONTACT ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Command Menu/Dialer Config/Account Info
4. Account# 2 Identification
654321->Default Same as Account#1.
Command Menu/Dialer Config/Account Info
5.Account# 2 Telephone Number
[ 101 ]->Default Same as Account#1.
Configuration with the CFG-300 LCD Service Tool
Set the reporting format that is recognized or preferred by the monitoring station.
Command Menu/Dialer Config/Account Info
6.Account# 2 Reporting Format
[X] Contact ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Same as Account#1.
81
Page 82
Configuration with the CFG-300 LCD Service Tool
i
1 Line1 Dialtype
2 Line2 Dialtype
3 Line1 Dialtone
4 Line2 Dialtone
- Telephone Line -
5 Num of Retries
Line#1 Dialing Type:
[X] DTMF Dial
Line#2 Dialing Type:
[X] DTMF Dial
Line#1 Wait Dialtone
[X] ENABLE
Line#2 Wait Dialtone
[X] ENABLE
Number of Retries:
06
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

1 1.11.2 Command Menu/Dialer Config-->Telephone Line

Command Menu/Dialer-Config/Telephone Line
1. Line#1 Dialing Type
[X] DTMF Dial->Default
[ ] Pulse Dial
Command Menu/Dialer-Config/Telephone Line
2. Line#2 Dialing Type
[X] DTMF Dial->Default
[ ] Pulse Dial
Command Menu/Dialer-Config/Telephone Line
3. Line#1 wait for Dial tone
[X] ENABLE ->Default
[ ] DISABLE
Command Menu/Dialer-Config/Telephone Line
4.Line#2 wait for Dial tone
Set the dialing type for line #1; this is the type recognized or preferred by the telephone company.
Same as Line#1.
Use this menu to let the system know whether or not to wait for a dial tone before dialing. Cell phone setup for the dialer requires that the system not wait for dial tone before dialing.
Command Menu/Dialer-Config/Telephone Line
5.Number of retries
82
[X] ENABLE ->Default
[ ] DISABLE
06 ->Default
Same as Line#1.
Set the number of retries for both line#1 and line#2. This function lets the dialer retry on either line if it is busy or not available. If the retry count expires, the panel reports a line trouble.
Page 83
Configuration with the CFG-300 LCD Service Tool
i
1 Alarm Prio.
2 Trouble Prio.
3 Supv. Prio.
4 Aux Dis Report
- Report Options -
5 Fire Panel 6 Operation Mode
7 Checksum Bits
Alarm Priority:
[X] Account 1
Trouble Priority:
[X] Account 1
SUPV Priority
[X] Account 1
AuxDis Alm/Supv Rpt.
[X] DISABLE
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

11.11.3 Command Menu/Dialer Config-->Report Options

Command Menu/Dialer-Config/Report Options
1.Alarm priority
Command Menu/Dialer-Config/Report Options
2.Trouble priority
Command Menu/Dialer-Config/Report Options
3.Supervisory priority
Command Menu/Dialer-Config/Report Options
4.Aux Disconnect, Cancels Alarm & Supv Reporting Thru dialer
[X] Account 1->Default
[ ] Account 2
[X] Account 1->Default
[ ] Account 2
[X] Account 1->Default
[ ] Account 2
[ ] ENABLE
[X] DISABLE ->Default
Use this menu to set the account priority for reporting alarms. If the priority is set for account#1 then the dialer tries account#1 first for reporting.
Use this menu to set the account priority for reporting trouble. If the priority is set for account#1 then the dialer tries account#1 first for reporting.
Use this menu to set the account priority for reporting supervisory troubles. If the priority is set for account#1 then the dialer tries account#1 first for reporting.
If this function is enabled, pressing AUXILIARY DISCONNECT (see 9.4.6 AUXILIARY DISCONNECT Button on page 48) blocks the alarm and supervisory events from being reported through the built-in dialer.
83
Page 84
Command Menu/Dialer-Config/Report Options
Fire Panel Type:
[X] FA-300 Panel
Dialer Oper. Mode:
[X] (U)DACT
Checksum Bits:
[X] 8 Bits
i
1 AC-Loss Delay
2 Cellphone Date
3 Auto-Test Time
-Time Parameter-
AC-Loss Delay(Hrs)
0
5.Fire Panel type
[X] FA-300 Panel->Default
[ ] FA-1000 Panel
[ ] FX-2000 Panel
Command Menu/Dialer-Config/Report Options
Configuration with the CFG-300 LCD Service Tool
Do not change this function; keep it as default.
For factory use only.
6.Dialer operation mode
[X] (U)DACT ->Default
[ ] DACT
Command Menu/Dialer-Config/Report Options
7.Checksum Bits
[X] 8 Bit ->Default
[ ] 16 Bits
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.

1 1.11.4 Command Menu/Dialer Config-->Time Parameters

Use this menu to select the functionality of the dialer. In DACT mode only common trouble/alarm/supervisory are reported while in UDACT mode all point information is reported
Do not change this function; keep it as default
For factory use only.
Command Menu/Dialer-Config/Time Parameter
1.AC Loss delay
84
0 ->Default
Use this menu to delay the reporting of AC loss trouble on the dialer for the programmed time period.
Page 85
Command Menu/Dialer-Config/Time Parameter
Cellular Report Date
0
Auto-Test Time
00:30
Configuration with the CFG-300 LCD Service Tool
2.Cellular report date
0 ->Default
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
00:30 ->Default
Use this menu to set the test report date for the cell phone setup. Set this menu to 0 if there is no test reporting for a cell phone, or if the phone line is a regular line. Set this menu from 01 to 28 to schedule a test for Line 2 on a certain day of the month. See section 11.11.5 for more information.
When a cell phone service is employed for the panel, it should only be connected to telephone line #2 CO interface. Also, the dial tone detection feature of Line 2 should be disabled for cell phone application.
Use this function to set the time for the automatic test. When this test is performed, the test report is sent to the monitoring station. This test must be performed at least once a day. The time is in 24 hour format, which means 00:30 is 30 minutes after midnight. The Auto test time can be configured to: 12:00 a.m. to 5:59 a.m.: test every 24 hours 6:00 a.m. to 11:59 a.m.: test every 6 hours 12:00 p.m. to 23:59 p.m.: test every 12 hours
If the Cellular report date is set to 0, then the test alternates between Line 1 and Line 2. See section
11.11.5 for more information.
85
Page 86
Configuration with the CFG-300 LCD Service Tool
i
Dialer Ena/Dis
[X] ENABLE
------Warning-------
Dialer Disabled!!!

11.11.5 Auto Test Time and Cellular Report Date

If the Cellular report date is set to 0, then the dialer alternates between Lines 1 and 2 when performing the automatic test. If the Cellular report date is not set to 0, then the automatic test is performed on Line 1 except on the Cellular report date, when it is performed on Line 2. See examples in the following table.
Cellular Report Date Auto Test Time Line 1 Tested Line 2 Tested
0 00:30
0 6:00 6:00 a.m. and 6:00 p.m. 12:00 p.m. and 12:00 a.m.
0 12:00 12:00 p.m. 12:00 a.m.
15 00:30
15 6:00
15 12:00
Note: Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
12:30 a.m. every other day (alternates with Line 2)
12:30 a.m. every day except on the 15th of the month
6:00 a.m., 12:00 p.m., 6:00 p.m., and 12:00 a.m. every day except on the 15th of the month
12:00 p.m. and 12:00 a.m. every day except on the 15th of the month
12:30 a.m. every other day (alternates with Line 1)
12:30 a.m. on the 15th of the month
6:00 a.m., 12:00 p.m., 6:00 p.m., and 12:00 a.m. on the 15th of the month
12:00 p.m. and 12:00 a.m. on the 15th of the month

1 1 .11.6 Command Menu/Dialer Config-->Dialer Enable/Disable

86
[X] ENABLE ->Default
[ ] DISABLE
The dialer is enabled by default. When the dialer is enabled or disabled, a warning message appears.
Warning: The dialer cannot
report any event to the monitoring station if it is disabled.
Page 87
Configuration with the CFG-300 LCD Service Tool
[X]5
-Ring Detect Number-
-Dialer Test-
1. L#1 Manual test
2. L#2 Manual test
3. Reset Dialer
1.L#1 Manual test
2.L#2 Manual test
3 Reset Dialer
.
Dialer idle now
No DC Volt
Waiting for Dialtone

11.11.7 Command Menu/Dialer Config-->Ring Detect

[ ] Disabled [ ] 1 [ ] 2 [ ] 3 [ ] 4 [X] 5->Default [ ] 6 [ ] 7 [ ] 8

11.12 10. Test Dialer (Command-Menu)

Use this menu item to select the number of rings on which the panel’s modem answers. The default number of rings is five. The maximum number of rings you can define is eight.
If you select the “Disabled” option, the modem is disabled and the panel does not pick up the incoming call.

11.12.1 Dialer Test Messages

The following messages appear during the test processes of Lines #1 and #2. The messages that appear depend on the status of the dialer and the test results that are found.
Press Enter to test Line #1. Press Cancel to exit this menu. For a description of test messages, see 11.12.1 Dialer Test Messages below.
Press Enter to test Line #2. Press Cancel to exit this menu. For a description of test messages, see 11.12.1 Dialer Test Messages below.
This feature flushes all reportable events from the buffer. Press ENTER to reset the dialer. Press CANCEL to exit this menu.
The dialer is checking the line for voltage. This message automatically displays when Manual Test is selected.
No DC line voltage. The line is dead or no phone line is connected.
The dialer is waiting for a dial tone.
87
Page 88
Configuration with the CFG-300 LCD Service Tool
Failed: No Dialtone
Dialing Receiver Now
No DTMF tone
Waiting for Acktone
Failed No Acktone
Reporting Event Now
Waiting for Kissoff
No Kissoff
Passed: Manual test
This message may indicate a noisy telephone line.
The dial tone was received and telephone number dialing is in process.
This message indicates that the dialer failed to send a DTMF tone.
Waiting for availability of the receiver. The receiver confirms the availability by sending an acknowledgement tone.
This message indicates that either the telephone number may be wrong or the receiver is not available.
When sending events to the receiver, the display toggles between this message and “Waiting for Kissoff“ for all events sent.
The dialer is waiting for the kissoff tone. The kissoff tone indicates that the receiver has received the event reports.
No Kissoff means receiver has not received any
event reports.
The line passed the test; everything is OK.

11.13 11. Exit (Command-Menu)

Press ENTER after selecting EXIT from the main menu to return the panel to normal operation.

11.14 CFG-300 LCD service tool operation

If an LCD service tool is connected to the panel, you can view the latest message but you cannot scroll through the messages. In order to see all of the messages, enter the programming menu and view the event logs. The logs are arranged so that the most recent message is shown first. Listed below are the different kinds of messages that can appear on the LCD service tool.
88
Page 89

11.15 Zone messages

EAST LOBBY ENTRANCE
OPEN TRB 01/09
VERIFIED ALARM Z-01
18:01 TUE 2003-04-04
ZONE
Message
EVENT
01 of 09
Process
Type
Physical
Zone No.
DATE
TIME
"INFO " Key
EVENT
type
EAST WING LOBBY
SHORT TRB 02/09
SILENCE-ABLE NAC-1
18:01 TUE 2003-02-02
"INFO " Key
ZONE
Message
EVENT
type
EVENT
02 of 09
Process
Type
Physical
Zone No.
DATE
TIME
Point annunciation is indicated on the LCD display. There are no separate queues for TROUBLE, ALARM, SUPERVISORY and BUILDING; instead there is only one queue that indicates all the events. The respective TROUBLE, ALARM, SUPERVISORY and BUILDING LEDs flash if at least one of the given types is in the queue.
The CFG-300 LCD service tool shows only the first alarm or trouble. If a trouble happens first and then an alarm happens, the alarm appears. Any further events change the total number of events, shown in the right hand corner of the LCD display. The order of priority is alarm, supervisory, trouble and property and building safety.

11.15.1 Example 1 (detection circuit):

Event 01 of 09, OPEN TRB on initiating circuit Z-01 in the EAST LOBBY ENTRANCE with process type as VERIFIED ALARM and the event occurred on 2003/02/02 at 18:01 TUESDAY.
Configuration with the CFG-300 LCD Service Tool
Figure 53 Detection circuit zone message

11.15.2 Example 2 (indicating circuit):

Event 02 of 09, SHORT TRB on indicating circuit NAC-01 in the EAST WING LOBBY with process type as SILENCEABLE and the event occurred on 2003/02/02 at 18:01 TUESDAY.
Figure 54 Indicating circuit zone message
Other common messages are described below.
89
Page 90

11.16 AC Power Fail

AC Power Fail
Active 1/ 1
Trb:0x03 Info:0x0004
00:07 SAT 2000-01-01
Trouble Type
EVENT
01 of 01
DATE
TIME
"INFO " Key
Trouble code Trouble Info
"INFO " Key
Battery Trouble
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0008
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
The AC power fail trouble is generated when the power drops below the UL specified value. The trouble is restored when the power returns to the normal value.
Figure 55 AC Power Fail
Configuration with the CFG-300 LCD Service Tool

11.17 Battery trouble

The battery trouble is generated when the battery voltage drops below the specified value. The trouble is restored when the voltage returns to the normal value.
Figure 56 Battery Trouble
90
Page 91

11.18 Ground Fault

"INFO " Key
Ground Fault
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
i
RAU num mismatch
trouble 1/ 1
Trb:0x03 Info:0x0001
11:45 SAT 2003-02-03
Trouble Type
EVENT
01 of 09
DATE
TIME
"INFO " Key
Trouble code
Trouble info
Figure 57 Ground Fault
Note: The trouble code and info is for trained service personnel only.
Configuration with the CFG-300 LCD Service Tool

11.19 Remote Annunciator

Troubles related to the annunciator can have two possibilities: either the main panel and annunciator failed to communicate with each other, or an un-configured remote annunciator is responding to the main panel. In both the cases, the following trouble message is displayed:
Figure 58 Remote annunciator mismatch trouble

11.20 Four-wire Smoke Detector Supply

The four-wire smoke detector supply is supervised for shorts. When a short is detected on a four-wire smoke supply the power is cut off and a trouble message is generated. Press the SYSTEM RESET button to restore the power the system. If the short is removed, the panel returns to normal; otherwise the trouble message remains.
91
Page 92
Configuration with the CFG-300 LCD Service Tool
"INFO " Key
4Wire Pwr. Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
i
"INFO " Key
Aux. Power Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
Figure 59 Four-wire Power Supply
Note: The trouble code and info is for trained service personnel only.

11.21 Supervised Aux. Supply

The supervised auxiliary supply is supervised for shorts. When a short is detected on supervised auxiliary supply the power is cut off and a trouble message is generated. Press the SYSTEM RESET button to restore the power the system. If the short is removed, the panel returns to normal; otherwise the trouble message remains.
Figure 60 Aux. Power Supply

11.22 City Tie Polarity reversal - PR-300/ Relay module

92
The city tie or polarity reversal module is supervised for open and whether or not the PR-300 is plugged in. The relay module is supervised for whether or not it is plugged in.
If any of the modules are not plugged in, the following trouble message appears:
Page 93
Configuration with the CFG-300 LCD Service Tool
"INFO " Key
CtyTie/RMxxx missing
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
"INFO " Key
City Tie trouble
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble code Trouble Info
Figure 61 City Tie module missing
If there is an open detected on the city tie output, the following trouble message appears:
Figure 62 City Tie trouble
93
Page 94

12.0 Appendix A: Compatible Receivers

i
The dialers that are built into select models of the FA-300 Series Fire Alarm Control Panels are compatible with the following Digital Alarm Communicator Receivers (DACR):
DACR Receiver Model Protocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI approved) SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
DSC SurGard System III Receiver (ULC, ULI Approved)* SIA Contact ID
DSC SurGard System IV Receiver (ULC, ULI Approved)* SIA Contact ID
Note: * When used with DSC 3G4010 or 3G4010CF Universal Wireless Alarm
Communicator through wireless IP connection.
94
Page 95

13.0 Appendix B: Reporting

13.1 Ademco Contact-ID

13.1.1 FA-300 Event Codes

Event Description Event Family Qualifier Code Group # Contact #
Phone Line #1 trouble detected Trouble New event 1 351 00 000
Phone Line #2 trouble detected Trouble New event 1 352 00 000
Phone Line #1 trouble restored Trouble Restore 3 351 00 000
Phone Line #2 trouble restored Trouble Restore 3 352 00 000
Failure to report to an Account Trouble New event 1 354 Acct # Acct #
Report to an Account successful Trouble Restore 3 354 Acct # Acct #
Periodic (24 hr) Test Event (NORMAL) Test New event 1 602 00 000
Periodic (24 hr) Test Event (OFF NORMAL)
Manually initiated dialer test Test New event 1 601 00 000
Zone Fire Alarm Alarm New event 1 110 00 000
Zone Fire Alarm restored Alarm Restore 3 110 00 000
Zone Trouble detected Trouble New event 1 300 00 000
Zone Trouble restored Trouble Restore 3 300 00 000
Zone Supervisory condition Supervisory New event 1 200 00 000
Zone Supervisory restored Supervisory Restore 3 200 00 000
Waterflow Alarm New event 1 113 00 000
Waterflow restored Alarm Restore 3 113 00 000
Indicating Zone Trouble Trouble New event 1 320 00 000
Indicating Zone Trouble restored Trouble Restore 3 320 00 000
AC power lost Trouble New event 1 301 00 000
AC power restored Trouble Restore 3 301 00 000
Test New event 1 608 00 000
Battery Low Trouble New event 1 302 00 000
Battery Low restored Trouble Restore 3 302 00 000
Ground Fault Trouble New event 1 310 00 000
Ground Fault restored Trouble Restore 3 310 00 000
95
Page 96

13.2 Security Industries Association SIA-DCS

SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/ Restore.

13.2.1 FA-300 Event Codes

Appendix B: Reporting
Event Description Event Family Qualifier SIA Event
Code
Phone Line #1 trouble detected Trouble New event LT 001
Phone Line #2 trouble detected Trouble New event LT 002
Phone Line #1 trouble restored Trouble Restore LR 001
Phone Line #2 trouble restored Trouble Restore LR 002
Failure to report to an Account Trouble New event RT Acct #
Report to an Account successful Trouble Restore YK Acct #
Periodic (24 hr) Test Event (Normal) Test New event RP 000
Periodic (24 hr) Test Event (Off-normal) Test New event RY 000
Manually initiated dialer test Test New event RX 000
Zone Fire Alarm Alarm New event FA 000
Zone Fire Alarm restored Alarm Restore FH 000
Zone Trouble detected Trouble New event FT 000
Zone Trouble restored Trouble Restore FJ 000
Parameter
Zone Supervisory condition Supervisory New event FS 000
Zone Supervisory restored Supervisory Restore FR 000
Waterflow alarm Alarm New event WA 000
Waterflow alarm restored Alarm Restore WH 000
Indicating Zone Trouble (*) Trouble New event UT 000
Indicating Zone Trouble restored (*) Trouble Restore UR 000
AC power lost Trouble New event AT 000
AC power restored Trouble Restore AR 000
Battery Low Trouble New event YT 000
Battery Low restored Trouble Restore YR 000
Ground Fault Trouble New event YP 000
Ground Fault restored Trouble Restore YQ 000
96
Page 97

14.0 Appendix C: Specifications

Table 16 FA-300 LED Series Specifications
FA-300 LED Fire Control Panel Chassis
General Digital Signal Processor based design. Fully configurable using front panel LCD
display with Password Access.
Indicating (NAC) Circuits
Initiating Circuits 12 supervised style B (Class B) initiating circuits, configurable (normal or
RS-485 Connection For Remote Annunciators. Terminals are labelled RS485. Electrical ratings AC line voltage 120 VAC 60 Hz 3 Amp \ 240 VAC 50 Hz 1.5Amp
4 supervised Style Y (Class B) and Style Z (Class A) indicating circuits,
configured as strobes or audibles. Terminals are labelled SIG.
Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit
verified). Terminals are labelled DET. Compatibility ID A
Power limited / 19VDC reg. / 3mA for detectors / 0.15Vp-p ripple / 40mA max (alarm short)
(primary)
Power Supply Rating 6 Amp maximum panel (loading) Max power allowed 5Amp (Total NAC loading)
1.7Amp (aux power unfiltered)
0.5Amp (aux power filtered)
0.3Amp (resettable auxiliary power)
Panel Current consumption
Standby: 283mA
Alarm: 560mA
Unfiltered supply
(full wave rectified)
Aux supply (non resettable)
4-wire smoke supply (resettable)
Auxiliary relays (resistive loads)
Special Application
Power limited / 24VFWR unfiltered / 1.7Amp max at 49C
See Appendix E: Auxiliary Devices on page 101.
Special Application
Power limited / 22.3VDC nominal / 500mA max
See Appendix E: Auxiliary Devices on page 101.
Special Application
Power limited / 22.3VDC nominal / 300mA max
See FA-100 section for compatible Four Wire Smoke Detectors in LT-1007 ­Device Compatibility Guide
Must be connected to a listed power limited source of supply. Terminals are labelled ALARM, TROUBLE, SUPV and AUX.
Common Alarm Form C, 1 A max, 28 VDC Common Supv Form C, 1 A max, 28 VDC Common Trouble Form C, 1 A max, 28 VDC Aux Relay Form C, 1 A max, 28 VDC
97
Page 98
Table 16 FA-300 LED Series Specifications (Continued)
F A-300 LED Fire Control Panel Chassis
Appendix C: Specifications
Ground Fault Impedance
Battery Type 24VDC Sealed Lead Acid, 12 AH
Compliance System Model FA-300 Series LED Version Fire Alarm Control
Table 17 FA-300 LED System Modules and Annunciators
2 k
Charging capability 1.25 Amp Protection 10A on board (F1) slow blow micro fuse
Panel
System Type Local, Auxiliary (using PR-300), Remote Protected
Premises Station (using PR-300 or FA-301-12LDR, FA-301-12LDW, or FA-301-8LDW) Central Station Protected Premises (using FA-301-12LDR, FA-301­12LDW, or FA-301-8LDW).
Type of Service A, M, WF, SS Type of Signalling Non-Coded Applicable Standards NFPA 70 and 72, UL 864 Rev. 9, ULC-S524, ULC-
S527-11, ULC-S559-13
FA-300 LED Series Modules and Annunciators
RM-312/306 Relay Adder Module Must be connected to a listed power-limited
source of supply.
Contact rating NO / NC / 28VDC per contact / 1A resistive
load max
Current consumption standby 0mA, alarm 80mA
ICAC-306 Input Class A Converter module standby: 0mA / alarm: 0mA OCAC-304 Output Class A Converter Module standby: 0mA / alarm: 0mA OCAC-302 Output Class A Converter module Standby 0mA / alarm 0mA SRM-312
Smart Relay Module
Contact rating FormC/ 28VDC per contact / 1A resistive load
Current consumption standby 30mA, alarm 140mA
Must be connected to a listed power-limited source of supply
Contact rating FormC/ 28VDC per contact /
1A resistive load max, zoned
Current consumption standby 30mA / alarm
140mA
max, zoned
RAM-300 Remote LCD Annunciator Standby 56mA / alarm 65mA RAM-208 8 Zone Remote Annunciator Standby 35mA / alarm 90mA
98
Page 99
Appendix C: Specifications
Table 17 FA-300 LED System Modules and Annunciators (Continued)
FA-300 LED Series Modules and Annunciators
PR-300 Polarity Reversal and City Tie Module
City Tie power limited / 24VDC unfiltered / 250mA max
/14Ohms trip coil
Polarity Reversal power limited / 24VDC open / 12VDC at
3.5mA / 8.5mA max (shorted)
Polarity Reversal Supv. Terminal 24VDC (normal) / -24VDC (supervisory) / 0V
(trouble)
Polarity Reversal Alarm Terminal 24VDC (normal) / -24VDC (alarm) / 0V
(trouble)
Current Consumption standby 50mA / alarm 300mA (city tie in use) /
alarm 70mA (city tie not in use)
RTI Remote Trouble Indicator Standby 35mA / alarm 35mA
99
Page 100
15.0 Appendix D: Power Supply and
Battery Calculations
Use the form below to determine the required secondary power supply (batteries).
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer
to Appendix A for specifications.
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number Description Qty Standby Total Standby Alarm To ta l A lar m
FA-301-12LW
FA-301-12LD(W/R)
FA-301-8LW
FA-301-8LDW
ICAC-306
OCAC-304
OCAC-302
PR-300
RM-312/ RM-306
SRM-312 12 Relay Smart Relay Module X 0.030
RAM-300LCD Smart Remote Annunciator X 0.056 RAM-208/216 Remote Annunciators X 0.035
RTI-1 Remote Trouble Indicator X 0.035
Two-Wire Smoke Detectors X 0.00011
Fire Alarm Control Panel, 12 Det, FIXED ELR/ACTIVE ELR Fire Alarm Control Panel, 12 Det with UDACT FIXED ELR/ACTIVE ELR Fire Alarm Control Panel, 8 Det FIXED ELR/ACTIVE ELR Fire Alarm Control Panel, 8 Det with UDACT FIXED ELR/ACTIVE ELR Det Class A Converter Adder Module Sig Class A Converter Adder Module--4 Circuits Sig Class A Converter Adder Module--2 Circuits Polarity Reversal and City Tie Module 12 Relay or 6 Relay Adder Module
X 0.164/0.104
X 0.164/0.104
X 0.136/0.096
X 0.136/0.096
X 0.000
X 0.000
X 0.000
X 0.050
X 0.000
= 0.424/0.364 =
= 0.424/0.364 =
= 0.366/0.326 =
= 0.366/0.326 =
= 0.000 =
= 0.000 =
= 0.000 =
= 0.300 =
= 0.160/0.080 =
=0.140=
=0.065=
=0.090=
=0.035= = * 0.090 = 0.090
Four-Wire Smoke Detectors X
Signal Load (bells, horns, strobes, and etc.) X
Auxiliary Power Supply for Annunciators, etc.
Total currents (Add above currents) STANDBY
= =
=
ALARM
(A) (B)
* Assume three Initiating Circuits are in alarm. ' Use 0.084 for five minutes of alarm as a multiplier figure.
Using the Mircom MPD-65P 2-wire photoelectric smoke detector. See Device Compatibility Guide LT1007.
Total Current Requirement:ALARM (B)______ Amp. (Value obtained from column B) Battery Capacity Requirement: ([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [Alarm in Hr.] _____) = (C) ______AH Total Alarm Current: Must be 6 Amperes or less for FA-300 Series. Indicating Circuits must not to exceed 5 Amperes. Battery Selection: Multiply (C) by 1.20 to derate battery.
100
=
=
Loading...