Table 16 FA-300 LED Series Specifications ................................................................................. 97
Table 17 FA-300 LED System Modules and Annunciators ........................................................... 98
8
Page 9
1.0Industry Canada and FCC Notice
!
i
1.1 Notice for all FA-300 Series Built-In UDACTs Sold in Canada
Mircom's F A-300 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units for
Fire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for Fire
Signal Receiving Centres and Systems). These Communicators should be installed in
accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the
local Authority Having Jurisdiction (AHJ).
1.2 Industry Canada Notice
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
Caution:Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate
1.3 Notice for all FA-300 Series Built-in UDACTs Sold in the
U.S.A.
Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a
decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is
separately shown on the label.
Mircom's FA-300 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for DACTs and should be installed in
accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
9
Page 10
1.3.1 FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request
information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number and the
ringer equivalence number (REN); both of these items are listed on the equipment label. The
sum of all of the REN’s on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.
Industry Canada and FCC Notice
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.
10
Page 11
2.0Introduction
i
Mircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP)-based
fire panel. The FA-300 provides a maximum of 12 supervised Class B or A (Style B or D)
Initiating circuits, and maximum four supervised Class B or A (Style Y or Z) indicating circuits.
All circuits are supervised for opens and ground faults, and indicating circuits are supervised
for shorts. Optional modules include Relay, Polarity Reversal and City Tie and Class A
Converters for initiating and indicating circuits. Semi-flush or surface mountable enclosures
can be used for retrofits and on new installations.
Note:Installation of the FA-300 series fire alarm control panel should be in accordance
with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm
System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance
subject to the Local Authority Having Jurisdiction (AHJ).
2.1 Overall Features
•Basic unit has 12 Class B (Style B) initiating circuits, which may be configured as Class
A (Style D) using input Class A converter adder modules. Each initiating circuit can be
configured as Alarm, Verified Alarm, Water flow Alarm, Sprinkler Alarm, Latching or
Non-Latching Supervisory, Property and Building Safety, or Trouble-Only circuits. There
are two LEDs per circuit, one for Trouble (amber), and one dual color (amber/red) LED
for Supervisory (amber) and Alarm (red).
•Basic unit has four Power Limited Class B (Style Y) indicating circuits with individual
trouble indicators. Each indicating circuit may be configured as Class A (Style Z) using
output Class A converter adder module. Each indicating circuit may be configured as
Silenceable signal, non Silenceable signal, Silenceable strobe, non Silenceable strobe.
The audible signal may be Steady, Temporal Code, California Code, or March Time.
•Two Stage operation available.
•A pushbutton associated with each initiating and indicating circuit can individually
disconnect the circuit.
•Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For UL installations, disable the auto signal silence timer.
•Subsequent Alarm, Supervisory, and Trouble operation.
•Four-wire resettable smoke power supply 300 mA maximum.
•Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
•RS-485 Interface for LCD Annunciators, RA-1000 Series Remote Multiplex
Annunciators and Smart relay adder.
•Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
•Extensive transient protection.
•With or without built-in UDACT (Digital Alarm Communicator Transmitter).
•Easy configuration of the panel and built-in UDACT using LCD service tool (CFG-300).
•Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
•Laptop programmer for direct configuration changing and log checking.
11
Page 12
3.0Conventions
3.1 Circuits
Refers to an actual electrical interface for Initiating (Detection) and Indicating (Signal or NAC)
or Relays.
3.2 Zone
Is a logical concept for a Fire Alarm Protected Area, and consists of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual circuit refers
only to a physical electrical loop.
3.3 Display Points
There is a display point associated with every initiating and indicating circuit of the FA-300
LED Series fire panel. For an initiating circuit there are 2 LEDs for every display point: one
single color (amber) and one dual color (red/amber). For an indicating circuit there is only one
LED: one single color (amber), for every display point.
3.4 Wiring Styles
Initiating and indicating circuits are Class B (style B and Y).
Changing the initiating circuits to Class A requires an ICAC-306 adder board which converts
six initiating zones from Class B (style B) circuits to Class A (style D). This is done without
decreasing the number of circuits, which remains the same as in Class B (style B).
Changing the indicating circuits to Class A requires an OCAC-304 adder board which converts
four indicating zones from Class B (style Y) circuits to Class A (style Z) or an OCAC-302 adder
board which converts two indicating zones from Class B (style Y) circuits to Class A (style Z).
12
Page 13
4.0System Components
4.1 Main Fire Control Panel
Figure 1 FA-300 LED Series
All FA-300 LED Series Panels have the following features:
•LED Display.
•Two six zone ICAC-306 Input Class A Converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
•One OCAC-304 Output Class A Converter adder module may be used for Class A
(Style Z) wiring of the Indicating circuits.
•Contain Common Alarm, Common Supervisory & Common Trouble Relays, Auxiliary
Alarm Relay (disconnectable), an RS-485 Interface for Remote Annunciators and a
Resettable Four Wire Smoke Detector Power Supply.
•Used with Mircom BAT-12V12A (12 Amp-hour) batteries (two required).
Table 1FA-300 LED Series Comparison Chart
Model# of zones# of initiating
circuits
FA-301-12LDW1212yeswhite
FA-301-12LDR1212yesred
FA-301-12LW1212nowhite
FA-301-12LR1212nored
FA-301-8LDW88 yes white
FA-301-8LW88 nowhite
On board DialerDoor Color
FA-301-8LDR88 yesred
FA-301-8LR88 nored
13
Page 14
4.2 Relay Module: 12 Relays
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NCNO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
Mounting hole for
#6-32 screws
Mounting hole for
#6-32 screws
FA-300 SERIES
Remote Annunciator
SYSTEM
RESET
SIGNAL
SILENCE
FIRE
DRILL
BUZZER
SILENCE
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CP U FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
Advanced Li fe Safety Sol utions
System Components
ModelDescription
4.3 Relay Modules: Six Relays
ModelDescription
RM-306Six relay adder module
4.4 Polarity Reversal/City Tie
ModelDescription
RM-312
12 relay adder
module
14
PR-300Polarity Reversal and/or City Tie Module
4.5 Remote Annunciator
ModelDescription
RAM-300LCDW
RAM-300LCDR
Remote Annunciator module, LCD display, white
painted box
Remote Annunciator Module, LCD display, red
painted box
SRM-312WSmart Relay Module (12 relays) with white enclosure
SRM-312RSmart Relay Module (12 relays) with red enclosure
4.7 Input Class A converter: Six Circuits
ModelDescription
System Components
ICAC-306
Input Class A converter Module (six circuits). This
module has built in Active End-of-Line resistors.
4.8 Output Class A converter: four circuits
ModelDescription
OCAC-304Output Class A converter module (four circuits)
4.9 Output Class A converter: two circuits
ModelDescription
OCAC-302Output Class A converter module (two circuits)
15
Page 16
4.10 Active End-of-Line Resistors
BLACK
RED
A.C.ONCOMMON
TROUBLE
SIGNAL
SILEBCE
BUZZER
SILENCE
SIGNAL
SILENCE
LAMP
TEST
SYSTEM
RESET
SWITCH
ENABLE
FIRE ALARM
ANNUNCIATOR
The ELRX-300 are power-saving End-of-Line resistors that eliminate the need for an
additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
ModelDescription
ELRX-300Active end-of-line resistor without plate
ELRX-300RActive end-of-line resistor with end-of-line red plate
4.11 RAM-216 Remote Annunciator
ModelDescription
RAM-21616 Zone remote annunciator
System Components
RAM-2088 Zone remote annunciator
4.12 Additional Fire Alarm System Accessories
RAM-208Eight Zone Remote AnnunciatorULC and ULI Approved
RTI-1Remote Trouble IndicatorULC and ULI Approved
MP-300End-of-line resistor plate, 3.9K ohmULC and ULI Approved
MP-300REnd-of-line resistor plate, redULC Approved
BC-160External Battery CabinetULC and ULI Approved
RAM-1016TZDSRemote Annunciator with 16 bi-
coloured LEDs (DS model has 16
bi-coloured LEDs and 16 trouble
LEDs)
RAM -1032TZDSRemote Annunciator with 32 bi-
coloured LEDs (DS model has 16
bi-coloured LEDs and 32 trouble
LEDs)
PCS-100Passive Communications Interface
Board
UDACT-300AUniversal CommunicatorULC and ULI Approved
BK-RAMDeadfront bracket (ULC
requirement for RAM-1016 series
and RAM-1032 series)
ULC and ULI Approved
ULC and ULI Approved
ULC Approved
ULC Approved
16
Page 17
5.0Mechanical Inst allation
11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole
5.1 Installing the Enclosure
Install the FA-300 Series Fire Alarm Panel enclosure as shown below for the twelve-, eight-,
and six-zone models. Mount enclosure surface mount using the four mounting holes, as
shown and the screws provided.
Figure 2 Box dimensions, surface mount
The backbox may be semi-flush mounted using the trim ring model FA-UNIV-TRB (BLACK),
see Figure 3. Remove the door (also disconnect the ground strap), the dead front and semi-
17
Page 18
Mechanical Installation
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" i s the max imum
depth for semi -flus h
mounting usi ng the
flush tr im ri ng
1" is the mi nimum depth
above the wall required for
semi- flus h mounting usi ng the
flus h trim ri ng
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 300 backbox .
PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL S TUD
BACKBOX
flush mount the backbox into the wall. Peel the adhesive cover from the trim ring and stick to
the wall surface around the backbox, after wall is finished.
Figure 3 Box dimensions, semi-flush mounting and trim ring
Figure 4 shows a cross-section of the semi-flush mounted enclosure and the trim ring. Make
sure to allow a minimum depth of 1” above the wall surface for proper door opening.
Figure 4 Flush trim detail (from above)
18
Page 19
Mechanical Installation
26.0 "
14.5 "
4.2 "
External Dimensions
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View
5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation
The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a
built-in trim ring.
Dimensions of Enclosure (minus built in trim ring)14.5” x 4.2” x 26”
Distance between horizontal mounting screws12”
Distance between vertical mounting screws23.5”
Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
Mounting Dimensions
12.0 "
23.5 "
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions
19
Page 20
5.3 Installing the Adder Modules
Fuse and AC wiring terminal
S-+NCNOCNCNOCNCNOCNCNOC
+-+-COM(+)
COM(-)
TRLTRBRTRT
RTRT
RESCORE SC O
LINE1LINE2
WALK
TEST
REMOTE
TROUBLE
CPU FAULT
GROUND
FAULT
SIGNAL
SILENCE
FIRE
DRILL
AUTOMATIC
ALARM SIGNAL
CANCEL
GENERAL
ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP
TEST
ALM/SUP/TBL/BLDG
AUDIBLE SIL
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON
TROUBLE
BATTERY
TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCONNECT
ZONE-7
DISCONNECT
ZONE-9
DISCONNECT
ZONE-11
DISCONNECT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
ZONE-12
DISCONNECT
NAC-1
DISCONNECT
NAC-3
DISCONNECT
NAC-2
DISCONNECT
NAC-4
DISCONNECT
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DE T 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SI G 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR -300 MOD ULE
TO R M-312/RM-306 RELAY
MODULE
RS-
485
AUX. RELAYALARM
RELAY
SUP E RVIS O RY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-W I RE
SUPPLY
UNFILTERED
RTI
PORT
P1P
2
P3P
4
+
_
BATTERYSEC. TX
BATTERYBATTERY
CLASS -A conve rter
board for detection
circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter
board for detection
circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter
board for indicating
circui ts OCAC-304
(4 circuits )
Reverse po larity a nd city
tie modu le PR- 300.
Mounted on hex spacer
with two screws provide d
Relay Module RM-306
Mount relay module on the
left si de u sing tw o scre ws
provided .
Relay M odule RM-312
centre under main fire
alarm board using three
screws pro vided .
Transf orme r
Fuse andAC wirungterminal
MAIN FIR E PANEL BOAR D
Fuse and AC
wiring terminal
FA-300 Series Fire Alarm panels come pre-assembled with all components and boards except
for Adder Modules. Module installation locations are shown in Figure 6. Refer to Figure 7 on
the next page for jumper and DIP switch settings and see 7.7 Wiring Tables and
Information on page 36 for wiring specifications.
For front panel programming use CFG-300
configuration tool not UL- 864 or ULC-S527
listed. Please refer to Document LT-922 for
details
For PC pr ogramming use UIMA
interface module not UL-864 or
ULC-S 527 listed . Plea se refer to
Document LT-929 for details
AUTOMATIC ALARM SIGNAL CANCEL
ZONE-11
DISCONNECT
ZONE-12
DISCONNECT
NAC-3
DISCONNECT
NAC-4
DISCONNECT
[
[
[
JW6 - Open all the time
JW4 - Normally open
JW5-Normally Open
[
Trouble Relay LED
6.0Cable and Jumper Connections for
Main Board and Adder Modules
6.1 Main Fire Alarm Board
Figure 7 Main Fire Alarm Board cable connector and jumper settings
21
Page 22
Cable and Jumper Connections for Main Board and Adder Modules
BLK RED
BLK R E DBLK R E DBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 O UT+- D ET4 OUT+- DET 5 OUT+- DET6 OUT+
- DET1 RET+- D ET2 R ET+- DET3 R ET+- DET4 RET+- DE T5 RET+- DET6 RET+
mounting hol e for
#6-32 scr ews
All these pi ns comes wit h
red a nd black w ire s w h i ch
are con ne cted to the
detection circuit on the
mai n fire alarm board. Red
is pos i ti ve and bl ack i s
negative
ICAC-306
mounting hol e for
#6-32 screws
6.1.1 Connectors and Jumpers on the Main Fire Alarm Board
P5
P6
JW1
Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects
here. Otherwise not used.
Cable from connector P1 of the RM-312 or RM-306 Relay Adder Module
connects here. Otherwise not used.
On the Main Fire Alarm Module, this jumper must be removed if a PR-300
Polarity Reversal and City Tie Module is installed.
JW2Remove this jumper if an RM-312 or RM-306 Relay Adder Module is used.
JW3Removed all the time.
Normally open. Place jumper here and power down (AC and Batteries) then
JW4
power back to revert back to default password. Once the system has reset,
REMOVE the jumper from the pins at JW4. Leave normally open.
JW5
Normally open to BLOCK remote
converter module or a CFG-300 Configuration Tool. Place jumper here to ALLOW
There are no jumpers or cables to set on this module, just wiring from the converter (wires are
fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For
example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the
positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
22
Page 23
Cable and Jumper Connections for Main Board and Adder Modules
- SIG1 OUT+- SIG2 OUT+
- SIG1 R ET+- SIG2 RET+
BLK RED
BLK RED
mounting ho l e for
#6-32 screws
OCAC-302
mounting ho l e for
#6-32 screws
- SIG1 O U T+- SIG2 OU T+
- SIG1 RET+- SIG2 R ET+
BLK RED
BL K RE D
- SIG3 OU T+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BL K RE D
mounting hol e for
#6-32 scr ews
OCAC-304
mounting ho le for
#6-32 scr ews
Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the
positive and negative terminals marked DET OUT and the circuit return wires are brought back
to the converter module to positive and negative terminals marked DET RET.
To convert all 12 initiating circuits of a FA-312 Fire Alarm Panel, two of these ICAC-306 Input
Class A Converter Adder Modules are required.
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For
example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the
Class A converter module to the positive and negative terminals of Indicating circuit 1 on the
Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the
signaling devices and then wired back to the SIGNAL RET positive and negative.
The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board.
The jumpers located above each relay on the RM-312 are used to configure the relays. The
23
Page 24
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
RELAY 8CREL AY 9
NO/NC C
RELAY 1 0
NO/NC C
RELAY 1 1
NO/NC C
RELAY 1 2
NO/NCNO/NC
Three mounting
holes for #6-32
screws
INDI VIDUAL
GREEN RELAY
STAT US LEDs
Connect to P6 on the
main fire alarm board
NO NC
SA
Z1
1&2
NO/ NCC
RELAY 1
NC/NO CONNECTION
NC: terminal provides normally closed contacts
NO: terminal provides normally open contacts
Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection
then the relay is not connected to the terminals
SUPV/ALARM SELECTION
S: Relay turns ON when common
supervisory is active
A: Relay turns ON when common
alarm is active
Defa ult: No jumper installed,
conn ecte d o n ce n ter p in o nl y
ZONE JUMPER
inst alled: turns ON relay when the zone
(1) is act ive
removed: does not turn ON the relay when
zone (1) i s a cti ve
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE
jumper installed: this relay 1 works in
conjunction w i t h r el ay 2
jumper removed: relay 1 does not
operate with the adjacent relay 2
chaining example: if jumper is installed
on 1&2 and 2&3 then all the three relays
will be ON if any one of relays 1,2 and 3 is
active
Default: No jumper installed, connected
on one pin only
NO/NCC
RELAY 12
RELAY
LED (GREEN)
i
jumpers located below the relays are used to select either normally open contacts or normally
closed contacts.
Figure 10 RM-312 twelve relay adder module
P1Cable from RM-312 Relay Adder Module connects to P6 on Main Fire Alarm
Board.
6.4.2 Programming the relays
24
A typical relay circuit is shown in Figure 11 with the jumper locations and descriptions.
Figure 11 RM-312/306 Relay programming
Note:Relay programming should be done before installing the board.
Page 25
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
mounting hol e
for #6-32 screws
mounting hol e
for #6-32 scr ews
INDIVIDUAL GREEN
RELAY STAT US LEDs
Connect to P 6 on the
main fire alarm board
i
6.4.3 RM-306 Six Relay Adder Module
Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers
located above each relay on the RM-306 are used to configure the relays. The jumpers
located below the relays are used to select either normally open contacts or normally closed
contacts.
Figure 12 RM-306 six relay adder module
P1Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm
Board.
6.4.4 Programming the relays
See explanation in Figure 11.
Note:Relay programming should be done before installing the board.
6.5 Polarity Reversal and City Tie Module (Model PR-300)
Mounting hole for
#6-32 screws
P1P2
Mounting hole for
#6-32 screws
+ | -+ | -+ | -
CITY
TIE
REVERSAL
POLARITY
ALARM
REVERSAL
POLARITY
SUPV
JW4
Figure 13 Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
25
Page 26
6.5.1 PR-300 jumper settings
Cable and Jumper Connections for Main Board and Adder Modules
P1
P2 & JW4
Cable connects to P5 on the Main Board
Not used. Jumper JW4 remains on board.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals resound and the City Tie Box is retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0 to
3 hours if this is the only system trouble.
26
Page 27
7.0Field wiring
!
+
-
STYLE B
WIRING
STYLE B
WIRING
INITIATING
CIRCUIT #1
INITIATING
CIRCUIT #2
INITIATING
CIRCUIT - 1
ALARM ZONE
INITIATING
CIRCUIT - 2
SUPERVISORY
ZONE
ION SMOKE
DETECTOR
PHOTO SMOKE
DETECTOR
HEAT
DETECTOR
PULL STATION
3.9K 1/2 WATT ELR
SUPERVISORY
FIRE ALARM MAIN BOARD
+
-
DET 1DET 2
NOTE: IF ACTIVE END OF LINE
RESISTORS ARE USED, THEY MUST
BE USED ON ALL INITIATING CIRCUITS.
i
7.1 Main Fire Alarm Board Field Wiring
Wire devices to the terminals as shown in the figures that follow. Refer to the Wiring Tables for
wire gauges and to Appendix A for specifications.
Caution:Do not exceed power supply ratings.
7.1.1 Initiating Circuit Wiring Class B
Wiring diagrams for the initiating circuits are shown below. The panel supports Class B (Style
B) and Class A (Style D) for the initiating circuits. The initiating circuits are supervised by a
3.9K End-of-Line Resistor or for power saving an Active-End-of-Line.
Figure 14 Initiating circuit – Class B or Sty le B wiring
Note:Depending on configuration, End-of-Line Resistors on initiating circuits must be
all 3.9K ohm resistors or all Active End-of-Line resistors.
27
Page 28
7.1.2 Initiating Circuit Wiring Class A
+
-
STYLE D
WIRING
STYLE D
WIRING
INITIATING
CIRCUIT # 1
INITIATING
CIRCUIT # 2
INITIATING
CIRCUIT - 1
ALARM
ZONE
INITIATING
CIRCUIT - 2
SUPERVI SORY
ZONE
ION SMOKE
DETECTOR
PHOTO
SMOKE
DETECTOR
HEAT
DETECTOR
PULL STAT ION
SUPER VISOR Y
4 MORE INITIATING
CIRCUITS NOT S HO WN
DCAC-306 CLASS A
CONVERTER MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- DE T1
OUT+
- DET2
OUT+
- DET1 RET+- DE T 2 R E T +
+
-
DET 1DET 2
ICAC
i
Field wiring
7.1.3 Indicating Circuit Wiring
Figure 15 Initiating circuit– Class A or Style D wiring
The FA-300 Series Fire Alarm supports Class B (Style Y) and Class A (Style Z) wiring for its
indicating circuits. Each circuit is supervised by a 3.9K End-of-Line resistor. Each indicating
circuit provides up to 1.7 A, 5 A maximum total if no auxiliaries are used.
Note:An Active End-of-Line resistor CANNOT be used with any indicating circuits.
Always use 3.9K End of Line resistors for indicating circuits.
28
Page 29
Field wiring
- SIG 1 +
STYLE Y
WIRING
STYLE Y
WIRING
INDICATING
CIRCUIT - 1
INDICATING
CIRCUIT - 2
BELLSTROBE3.9K 1/2 WATT ELR
INDICATING
CIRCUIT #1
INDICATING
CIRCUIT #2
HORN
FIRE ALARM MAIN BOARD
- SIG 2 +
BELL
STROBE
HORN
+
-
STYLE Z
WIRING
STYLE Z
WIRING
INDICA TING
CIRCUIT #1
INDICA TING
CIRCUIT #2
INDICATING
CIRCUIT 1
INDICATING
CIRCUIT 2
2 MORE INDICATING
CIRCU ITS NOT SHOWN
OCAC-304 CLASS A
CONVE RTE R MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- S IG 1 OU T+- SIG2 O UT+
- SIG1 RET+- S IG2 RET+
+
-
SIG 1SIG 2
Figure 16 Indicating circuit – Class B or Style Y wiring
Figure 17 Indicating circuit –Class A or Style Z wiring
29
Page 30
7.1.4 Four Wire Smoke Detector Wiring
POWER
DETECTION
++
++
--
--
1
4
2
3
5
6
TO INITIATING
CIRCUIT
RESETTABLE 4-WIR E SMOKE
DETECTOR POWER SUPPLY
22VDC, 200mA
MAX. CURRENT - 300mA
MAX. RIPPLE VOL. 5mV
(POWER LIMITED)
4-WIRE DETECTION DEVICE
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
+
-
4-WIRE
SUPPLY
3.9K 1/2 W ATT ELR
LEGEND
NOTES
ALL POWER LIMITED CIRCUITS
MUST USE TYPE FPL, FPLR,
OR FPLP POWER LIMITED
CABLE
FIRE ALARM MAIN BOARD
TIPTIP RINGRING
premi s e t el ephone
IF permitted
TIPTIP RINGRING
LINE-1
LINE-2
1
23
4
8
5
76
Public switch
Telephone company
wiring
TIP
RING
TIP
RING
RJ31X
BROWN
GREY
GREEN
RED
COCORESRES
Line 2 is Wired as shown for Line 1
FIRE ALARM MAIN BO AR D
Field wiring
7.1.5 Dialer Wiring
30
Figure 18 Four-wire smoke detector wiring
If you have Fire Alarm Panel Models FA-301-12LDW, FA-301-12LDR, and FA-301-8LDW
there is a dialer on board and terminals marked Line 1 and Line 2 must be wired as shown in
Figure 19 below.
Figure 19 Dialer wiring
Page 31
7.2 Relay Adder Module Wiring
C
C
NO/NC
NO/NC
C
NO/NC
ALL RELAY CONTACTS
28V DC, 1 AMP
RESISTIVE LOAD
RM-312 12 RELAY ADDER MODULE
NORMALLY OPEN OR
NORMALLY CLOSED
CONNECTION IS
SELECTED BY JUMPER
ON RELAY BOARD.
NOTE: ALL RELAY CIRCUITS ARE POWER
LIMITED AND MUST USE TYPE FPL, FPLR or
FPLP POWER LIMITED CABLE.
NORMALLY OPEN
CONNECTION
NORMALLY CLOSE
CONNECTION
RELAY
CIRCUIT #1
RELAY
CIRCUIT #2
RELAY
CIRCUIT #12
C
C
NO/NC
NO/NC
C
NO/NC
ALL RELAY CONTACTS
28V DC, 1 AMP
RESISTIVE LOAD
RM-306 6 RELAY ADDER MODULE
NORMALLY OPEN OR
NORMALLY CLOSED
CONNECTION IS
SELECTED BY JUMPER
ON RELAY BOARD.
NOTE: ALL RELAYS ARE POWER LIMITED
CIRCUITS AND MUST USE TYPE FPL, FPLR or
FPLP POWER LIMITED CABLE.
NORMALLY OPEN
CONNECTION
NORMALLY CLOSE
CONNECTION
RELAY
CIRCUIT #1
RELAY
CIRCUIT #2
RELAY
CIRCUIT #6
Wire relays on the relay adder modules RM-312 and RM-306 as shown in Figures 19 and 20.
Field wiring
Figure 20 Relay per zone (RM-312) Terminal connection
Figure 21 Relay per zone (RM-306) Terminal connection
31
Page 32
7.3 Connecting to a 3G4010 Interface Device for Canada
A
L
A
R
M
R
E
L
A
Y
S
P
V
R
E
L
A
Y
T
R
B
L
R
E
L
A
Y
Telephone
Line A
Connec tion
DC IN
E
O
L
To GS M/GPRS
T
yp
ic
a
l
In
st
a
ll
a
tio
n
in
Ca
n
a
d
a
Line 2Line 1
PCS-100
P
O
W
E
R
2
4
V
G
N
D
P
G
M
4
G
N
D
1
4V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
P
G
M
4
AUX SUPPLY
+
-
+
-
Internet
Com puter
Printer
SUR-GARD
SYSTEM IV
Internal IP: X.X.X.X
External IP: X.X.X.X
SG-Systems
Cons ole 2.1
Default Gateway: X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
N
O
C
N
O
C
N
O
C
C
O
M
Z
3
Z
2
Z
1
T
1
R
1
(
-)
(
+
)
Conventional input
configured as 3G4010
radio trouble
FA-300
3G4010
C.O.C.O.
Router
i
A typical connection is shown in Figure 22. The PCS-100 Passive Communications Interface
Board (sold separately) is required.
For information on Compatible DACR Receivers see 12.0 Appendix A: Compatible
Receivers on page 94.
FA-300 - 3G4010 Connection - Typical Diagram
Field wiring
3G4010 TRBL
Figure 22 Connecting an FA-300 FACP to a 3G4010 Interface Device
Note:The DSC interface device 3G4010 is required if the installation requires ULC
-
All units must be installed in the same room
All extended wiring must be in metallic conduit
-
-
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
Wiring between FACP and 3G4010: 18 m max.
-
Contact DSC to reprogram the zone inputs to match
the FACP as shown in this diagram
32
Page 33
Field wiring
Telephone
Line A
Connect ion
E
O
L
Line 2
C.O.
Line 1
C.O.
PCS -100
P
OW
E
R
2
4
V
G
N
D
P
G
M4
G
N
D
1
4
V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
AUX SUPPLY
+
-
+
-
To GSM/GPRS
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP: X.X.X.X
External IP : X.X.X.X
SG-Systems
Console 2 .1
Default Gateway: X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
Router
Conventional
input configured
as 3G4010CF
radio trouble
FA-300
3G4010CF
TRBL
A
L
A
R
M
R
E
L
A
Y
S
P
V
R
E
L
A
Y
T
R
B
L
R
E
L
A
Y
N
O
C
N
O
C
N
O
C
+
-
FA-300 - 3G4010CF Connection - Typical Diagram
Typical Installation outside Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010CF: 20 feet max.
- Contact DSC to reprogram the zone inputs to match the
FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086
3G4010CF
TRBL
PGM4
C
O
M
Z
3
Z
2
Z
1
T
1
R
1
N
C
C
O
M
N
O
DSC
RM-2
Relay
E
O
L
-
PS4086
Transformer
Battery
DC IN
+12V
COM
AC IN
+
ACT
LBT
N
C
C
O
M
N
O
DSC
RM-2
Relay
E
O
L
-
+
BAT+
BAT-
3G4010CF
3G4010CF
TRBL
+
-
+
-
Conventional
input configured
as AC failure
trouble
Conventional
input configured
as low battery
trouble
i
7.4 Connecting to a 3G4010CF Interface Device outside Canada
For information on Compatible Receivers see 12.0 Appendix A: Compatible Receivers on
page 94.
A typical connection is shown in Figure 23. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
Figure 23 Connecting an FACP to a 3G4010CF Interface Device outside Canada
Note:The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
33
Page 34
7.5 Polarity Reversal and City Tie Module (PR-300) Wiring
CONFIRMS TO NEMA STANDARDSB3-1969 INTENDED FOR
CONNECTION TO POLARITY
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS
DIN RAIL CONNECTION
TO EARTH GROUND
DIN RAIL CONNECTION
TO EARTH GROUND
POWER LIMITED
POWER LIMITED
POWER LIMITED
PR-300
PROCTECTEDPROCTECTED
UNPROCTECTEDUNPROCTECTED
POWER LIMITED CABLE TYPE
FPL, FPLR or FPLP MUST BE
USED FROM PR-300 TO
PROTECTORS.
Wire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 24, below.
See 12.0 Appendix A: Compatible Receivers on page 94 for module specifications. Power
Limited cable type FPL, FPLR or FPLP must be used.
For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model#24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown.
For use in Canada, the Protective Device is not required but still recommended.
Field wiring
Figure 24 Polarity reversal and city tie module terminal connection
34
Page 35
7.6 Power supply connection
!
The power supply is part of the Main Chassis. The ratings are:
Notes: For Class A wiring the resistance in ohms is multiplied by two.
Maximum voltage drop should not exceed 1.8 volts.
36
Page 37
Table 5RS-485 Wiring to Annunciators and other Devices
i
Wire gaugeMaximum wiring run to last device
AWGFeetMeters
222000609.6
2040001219.2
1880002438.4
Notes: Use twisted shielded pair,
300mA power limited.
Maximum 40 ohm loop resistance
7.8 Four-Wire Smoke Power
Field wiring
4-wire smoke power is provided for 4-wire smoke detectors. This filtered supply is supervised
therefore a short disconnects the power through the relay until the SYSTEM RESET button is
pressed. This supply is rated at 22.3VDC Nominal/300mA max/1V voltage drop maximum.
7.9 Supervised Auxiliary Power
Supervised auxiliary power is used to power the remote annunciators and smart relay
modules. This filtered circuit is supervised therefore a short disconnects the power through the
relay until the SYSTEM RESET button is pressed. This supply is rated at 22.3VDC Nominal/
500mA max/1V voltage drop maximum.
7.10 Auxiliary Power
This special application supply is not supervised. This supply is rated at 24VDC Nominal/1.7A
max. If there is a short on this circuit, the auxiliary power does not recover automatically when
the short is removed. The main power must be disconnected, then reconnected and the panel
reset to re-establish the auxiliary power supply. See Appendix E: Auxiliary Devices on
page 101.
37
Page 38
8.0Turning on the Panel
8.1 Before Connecting the Power
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC
supply.
8.2 Power-up procedure
After completing the steps in 8.1 above:
1. Plug in the AC power.
The A.C. ON LED illuminates, the TRBL LED flashes, and the buzzer sounds.
2. Press the SYSTEM RESET button.
The buzzer continues to sound and the TRBL LED continues to flash.
3. Connect the batteries as shown in Figure 26 below. Observe the correct polarity: the red
wire is positive (+) and black wire is negative (-).
38
Page 39
Turning on the Panel
i
blk
MODU LE
TO RM-312/RM-306 RELAY
JW1
TO PR-300 MODULE
BATTERY
_
+
P3P4
red
blk
red
red
P1P2
SEC. TX
SIG 3SIG 4
-+-+
red
_
+
_
+
yellow
red
blk
green
240 VAC 50Hz
120 VAC 60Hz
N
GND
BatteryBattery
NOTE: TO PREVENT SPARKING, CONNECT BATTERIES AFTER THE
SYSTEM MAIN A.C. POWER IS TURNED ON
Figure 26 Battery connections
All indicators should be off except for the green A.C. ON LED and the green Trouble Relay
LED on the left side of the main board. It is shown in Figure 7 on page 21
.
Note:The green Trouble Relay LED on the left side of the main board is illuminated
when the system is normal. This LED is for diagnostics and indicates that the
Trouble Relay is in normal standby condition.
4. Configure the Fire Alarm Control Panel as described in 11.0 Configuration with the CFG300 LCD Service Tool on page 59.
39
Page 40
8.3 Troubleshooting
SymptomsPossible Cause
Normally when a circuit trouble occurs, its designated trouble indicator is illuminated, as
well as the COMMON TROUBLE indicator and trouble buzzer. To correct the fault,
Circuit
Trouble
Remote Fail
Ground Fault
Battery
Trouble
check for open wiring on that particular circuit loop, and check that the circuit is not
disconnected or bypassed. For information about disconnecting circuits, see 9.5 Circuit
(Zone) Disconnect Buttons on page 49.
Note: Disconnecting a Circuit causes a system trouble.
Remote Fail is indicated on the main panel display for any failure reported by, or failure
to communicate with a remote annunciator or other remote device.
This panel has a common ground fault detector. To correct the fault, check for any
external wiring touching the chassis or other Earth Ground connection.
Check for the presence of batteries and their conditions. Low voltage (below 20.4 V)
causes a battery trouble. If battery trouble condition persists, replace batteries as soon
as possible.
Turning on the Panel
Walk Test
Mode
Common
Trouble
If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode. See 11.9
7. Walk Test (Command-Menu) on page 76.
If only the COMMON TROUBLE LED is illuminated on the main panel and none of the
above confirming trouble indicators are on, check the following:
• Any missing interconnection wiring.
• Any Module missing that was part of the Configuration.
• Improperly secured cabling.
40
Page 41
9.0Indicators, Controls and Operations
WALK
TEST
REMO TE
TROUBLE
CP U FAULT
GRO UND
FAU LT
SIGNAL
SILENCE
FIRE
DRILL
GENE RA L
ALARM
SYSTEM
RES ET
AUX
DISC ONNE CT
LAMP
TEST (MENU)
ALM/SUP/TBL/
BLDG AUDIBLE
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON
TROUBLE
BATTERY
TROUBLE
ZONE-1
DISC ONNE CT
ZONE-3
DISC ONNE CT
ZONE-5
DISC ONNE CT
ZONE-7
DISC ONNE CT
ZONE-9
DISC ONNE CT
ZONE-11
DISC ONNE CT
ZONE-2
DISC ONNE CT
ZONE-4
DISC ONNE CT
ZONE-6
DISC ONNE CT
ZONE-8
DISC ONNE CT
ZONE-10
DISC ONNE CT
ZONE-12
DISC ONNE CT
NAC -1
DISC ONNE CT
NAC-3
DISC ONNE CT
NAC-2
DISC ONNE CT
NAC-4
DISC ONNE CT
0
2
4
6
8
*
1
3
5
7
9
#
ENTER
INFO
CANCEL
10 Q Z
2 A B C3 D E F
4 G H I
5 J K L
6 M N O7 P R S
8 T U V9 W X Y
BACK SPACEForward
SIL (MENU)
Use these
buttons for
configuration.
Their functions
are printed under
the label.
Use these
buttons for
configuration.
Their functions
are printed
under the label.
AUTOMATIC
ALARM SIGNAL
CANCEL
Refer to Figure 27 below for LED Indicator and Control Button locations.
Figure 27 LED indicators and control buttons
41
Page 42
Indicators, Controls and Operations
i
The Main Display Panel on the Main Fire Alarm Control Board consists of:
•18 common LED Indicators (top half of display)
•8 Common Buttons (top half of display)
•Up to 12 Initiating Circuit Alarm LEDs and 12 Initiating Circuit Trouble LED Indicators
•Up to 16 disconnect buttons (12 for initiating circuit and 4 for indicating circuits)
LED Indicators may be amber, red, or green, and may illuminate continuously (steady), or at
one of two flash rates.
•Fast flash (Supervisory)- 120 flashes per minute, 50% duty cycle
•Trouble flash (Trouble)- 20 flashes per minute, 50% duty cycle
Note that each display is supplied with laser printer printable paper labels for sliding into the
plastic label template on the panel. For the Main Display, the paper label is Mircom# NP-2005;
this includes English and French versions.
Note:There are different labels for two stage operation.
9.1 Common Indicators
9.1.1 Buzzer
The buzzer is activated by any of the following events:
Fire AlarmSteady
Supervisory AlarmFast flash
TroubleTrouble flash rate
If the buzzer is turned on in response to a Non-Latching Trouble or Supervisory, it is turned off
if the condition causing it goes away and there is no other reason for it to be on.
9.1.2 A.C. ON LED
The green AC ON Indicator illuminates steadily as long as the main AC power is above
minimum level. The LED turns off when the level falls below the power-fail threshold and the
panel is switched to standby (battery) power.
9.1.3 COMMON ALARM LED
The red COMMON ALARM LED illuminates steadily whenever the panel detects an alarm
condition on any initiating circuit. Pressing the GENERAL ALARM button also turns on the
COMMON ALARM LED. The LED remains on until the SYSTEM RESET button is pressed.
42
Page 43
9.1.4 COMMON SUPERVISORY LED
i
The amber COMMON SUPERVISORY LED illuminates steadily when there is a Supervisory
Alarm in the panel caused by any Latching or Non-Latching Supervisory Circuit. The LED is
turned of when all Non-Latching Supervisory Circuits are restored and there are no active
Latching Supervisory Circuits. Latching Supervisory Alarms remain active until the SYSTEM
RESET button is pressed.
9.1.5 COMMON TROUBLE LED
The amber COMMON TROUBLE LED illuminates steadily when the panel detects any trouble
condition. It turns off when all Non-Latching Troubles are cleared.
9.1.6 REMOTE TROUBLE LED
The amber REMOTE TROUBLE LED flashes at the Trouble flash rate if there is trouble
detected at a City Tie or DACT, or if there is communication trouble detected with a Remote
Annunciator or if a Remote Annunciator reports a local trouble. It is turned off if these
conditions go away.
Indicators, Controls and Operations
9.1.7 FIRE DRILL LED
The amber FIRE DRILL LED illuminates steadily while Fire Drill is active.
9.1.8 AUTOMATIC ALARM SIGNAL CANCEL LED (or ALM/SUP/TBL/BLDG
AUDIBLE SIL LED for single stage systems)
If the panel is configured as a two-stage system, the AUTOMATIC ALARM SIGNAL CANCEL
(Acknowledge) LED illuminates steadily when the Alarm timer is canceled by the activation of
the AUTOMATIC ALARM SIGNAL CANCEL or SIGNAL SILENCE buttons. The LED goes out
when the SYSTEM RESET button is pressed.
This LED can be configured to flash amber at the fast rate while the Auto General Alarm timer
is running (see Table 14 on page 63). If the Auto General Alarm timer times out and puts the
panel into General Alarm, the LED turns off.
Note:If this LED is configured to flash (see section 11.3 on page 67), then the panel is
outside of UL/ULC certification acceptability. The authority having jurisdiction
must approve this selection.
If the panel is not configured as a two-stage system, this LED is ALM/SUP/TBL/BLDG
AUDIBLE SIL (buzzer silence). It flashes at the slow rate when the ALM/SUP/TBL/BLDG
AUDIBLE SIL button is pressed.
9.1.9 GENERAL ALARM LED
The red GENERAL ALARM LED illuminates steadily when the GENERAL ALARM button is
pushed, a General Alarm Initiating Circuit is activated, or the Auto General Alarm timer times
out. Once the GENERAL ALARM LED is on it stays on until the SYSTEM RESET button is
pressed.
43
Page 44
9.1.10 WALK TEST LED
The amber WALK TEST LED illuminates steadily to indicate that the panel is in Walk Test
Mode. If the panel is left in this mode for over an hour with no operator activity, the panel
returns to normal and the WALK TEST LED turns off.
9.1.11 CPU FAULT LED
The amber CPU FAULT LED flashes approximately ¼ second every 2 seconds to indicate a
processor failure on the main board. In addition, the buzzer sounds in time with the CPU
FAULT LED until the fault is corrected.
To test the CPU FAULT LED
1. Disconnect AC and batteries from the main board.
2. Connect AC and the batteries as described in section 8.0 on page 38.
If the CPU FAULT LED is functioning properly, it will flash once when the board powers
up.
9.1.12 AUXILIARY DISCONNECT LED
Indicators, Controls and Operations
The amber AUXILIARY DISCONNECT LED flashes at the Trouble rate when the AUXILIARY
DISCONNECT button is pressed. It turns off when the AUXILIARY DISCONNECT button is
pressed a second time. When it is flashing, the Auxiliary Alarm Relay is disconnected.
Depending on the configuration, the AUXILIARY DISCONNECT button can also disconnect
the Common Alarm Relay and Common Supervisory Relay (see section 11.0 Configuration
with the CFG-300 LCD Service Tool on page 59). When the AUXILIARY DISCONNECT LED
is flashing, the buzzer sounds.
9.1.13 SIGNAL SILENCE LED
The SIGNAL SILENCE LED flashes amber at the trouble rate when Indicating Circuits are
silenced either by the SIGNAL SILENCE button or by the Auto Signal Silence timer. It is turned
off when the signals are re-sounded by a subsequent alarm. For UL installations, disable the
auto signal silence timer.
9.1.14 BATTERY TROUBLE LED
The amber BATTERY TROUBLE LED flashes at the trouble rate when the battery is either low
(below 20.4 VDC) or disconnected.
9.1.15 GROUND FAULT LED
The amber GROUND FAULT LED flashes at the trouble rate when the Ground Fault Detector
detects a Ground Fault on any field wiring. It turns off when the Ground Fault is cleared.
44
9.1.16 SYSTEM RESET LED
This LED illuminates for a short time when the SYSTEM RESET button is pressed.
Page 45
9.2 Indicating Circuit Indicators
ZONE-1
DISC ONNE C T
Circuit Status LED
Circuit Trouble LED
Circuit
Disconnect
Button
The panel has 1 indicator for each of the 12 initiating circuits (shown in Figure 27). Each
indicator has a button and 2 LEDs, shown in Figure 28.
Figure 28 Alarm Circuit Indicator
The Circuit Disconnect Button is described in 9.5 Circuit (Zone) Disconnect Buttons on
page 49. The LEDs are described in the 4 sections below.
9.2.1 Alarm Circuit Indicators
Table 6 applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water
flow Alarm, Sprinkler Alarm, or General Alarm Circuits.
Table 6Alarm Circuit Indicators
Indicators, Controls and Operations
EventCircuit Status LEDConfiguration
Circuit in AlarmSteady (red)
Verified Alarm
Pre-alarmFast flash rate (red)
Sprinkler Alarm
Water flow Alarm
Activated circuit reconnected (when you
press the Disconnect button a second
time)
Fast flash rate (red) for 5
seconds to indicate a
pending alarm
EventCircuit Trouble LEDConfiguration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Circuit in AlarmOFF
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Verified Alarm
Non-Verified Alarm
Water flow Alarm
Sprinkler Alarm
General Alarm
9.2.2 Supervisory Circuit Indicators
This operation applies to Initiating Circuits configured as Latching or Non-Latching
Supervisory Circuits. The following table summarizes the indications in response to different
events.
Ta ble 7Supervisory Circuit Indicators
EventCircuit Status LEDConfiguration
Latching Sup.
Circuit in AlarmSteady (amber)
Non-Latching Sup.
45
Page 46
Indicators, Controls and Operations
Table 7Supervisory Circuit Indicators (Continued)
Activated circuit reconnected (when you
press the Disconnect button a second
time)
Fast flash rate (red) for 5
seconds to indicate a
pending alarm
EventCircuit Trouble LEDConfiguration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Latching Sup.
Non-Latching Sup.
Circuit in AlarmOFF
9.2.3 Property and Building Safety Indicators
This operation applies to initiating circuits configured as property and building safety circuits.
The following table summarizes the indications in response to different events.
Table 8Property and Building Safety Indicators
EventCircuit Status LEDConfiguration
Circuit ActiveSteady (amber)
Activated circuit reconnected (when you
press the Disconnect button a second
time)
Fast flash rate (red) for 5
seconds to indicate a
pending alarm
Property and Building
Safety
EventCircuit Trouble LEDConfiguration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Property and Building
Safety
Circuit ActiveOFF
46
Page 47
Indicators, Controls and Operations
i
9.2.4 Trouble-only Circuit Indicators
This operation applies to initiating circuits configured as Trouble-only Circuits. The following
table summarizes the indications in response to different events.
Ta ble 9Trouble-Only Circuit Indicators
EventCircuit Trouble LEDConfiguration
Open circuit (Class B)
Open circuit or Style D/Class A trouble
Disconnected (Style D/Class A)
Short Circuit
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Trouble Only
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
9.3 Signal Circuit Indicators
This operation applies to indicating circuits of any type. The Circuit Trouble Indicator flashes
amber at the Trouble Rate to indicate short-circuit or open-circuit trouble, or if the circuit is
Disconnected.
Ta ble 10Signal Circui t In di ca to rs
EventCircuit Trouble LEDConfiguration
Open circuit
Short Circuit
Disconnected
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Flashes at the trouble rate
(amber)
Signal
9.4 Common Controls
Note:To activate a button, press and hold it for 3 seconds.
9.4.1 SYSTEM RESET Button
The SYSTEM RESET button resets the Fire Alarm Control Panel and all Circuits. In particular,
the SYSTEM RESET button does the following:
•Resets all Latching Trouble Conditions
•Resets all Initiating Circuits
•Resets 4-Wire Smoke Supply
47
Page 48
•Turns off all Indicating Circuits
•Turns off SIGNAL SILENCE, AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge),
and GENERAL ALARM Indicators
•Turns off Fire Drill
•Stops and resets all timers
•Processes inputs as new events
•Does not affect Auxiliary Disconnect
9.4.2 SIGNAL SILENCE Button
Press the SIGNAL SILENCE button when the panel is in alarm to turn on the SIGNAL
SILENCE LED and deactivate any Silenceable Indicating Circuits. Non-Silenceable Circuits
are unaffected. Signals resound if there is a subsequent alarm. Pressing SIGNAL SILENCE
again resounds all silenceable signals. This button does not function when the signal silence
inhibit timer is running (see Table 14 on page 63). It also does not function if the indicating
circuits are active as the result of a fire drill.
In a two-stage system, the SIGNAL SILENCE button silences the stage 1 and stage 2 alarms.
Indicators, Controls and Operations
9.4.3 FIRE DRILL Button
The FIRE DRILL button activates all Non-Disconnected Indicating Circuits, but does not
transmit any Alarms via the City Tie, Common Alarm Relay or Auxiliary Alarm Relay. Fire Drill
activates the signals in the evacuation code programmed. For example in the Temporal Code,
the signals pulse on for 0.5 seconds, off for 0.5 seconds in rounds of 3 and then pause for 1.5
seconds and repeat.
Fire Drill is canceled by pressing the button again, or if the Panel goes into a real alarm.
9.4.4 AUTOMATIC ALARM SIGNAL CANCEL Button (or ALM/SUP/TBL/BLDG
AUDIBLE SIL Button for single stage systems)
If the Panel is configured as a two-stage system, pressing the AUTOMATIC ALARM SIGNAL
CANCEL (Acknowledge) button while the Auto General Alarm timer is running (there is an
alarm in the panel, but it is still in the first stage), cancels the timer and illuminates the amber
AUTOMATIC ALARM SIGNAL CANCEL LED steadily, thereby acknowledging the alarm.
If the Panel is not configured as a two-stage system, this button becomes ALM/SUP/TBL/
BLDG AUDIBLE SIL (buzzer silence). Press this button to silence the buzzer.
9.4.5 GENERAL ALARM Button
Press the GENERAL ALARM button to immediately send the panel into General Alarm or total
evacuation. It also re-activates the signals if they have been silenced during General Alarm.
The General Alarm condition remains active until the SYSTEM RESET button is pressed.
48
9.4.6 AUXILIARY DISCONNECT Button
Press the AUXILIARY DISCONNECT button to disconnect the Auxiliary Alarm Relay. The
Common Alarm Relay, the Common Supervisory relay and all correlated alarm relays may be
disconnected as selected through configuration (see 11.0 Configuration with the CFG-300
LCD Service Tool on page 59). Pressing the AUXILIARY DISCONNECT button also causes
the COMMON TROUBLE LED to illuminate steadily, the common trouble relay to send a
Page 49
trouble message and the buzzer to flash at the trouble flash rate. Pressing the AUXILIARY
12DET/4SIG LED UDACT
Version 1.7.8
DISCONNECT button causes the system to return to normal.
9.4.7 LAMP TEST Button
Press the LAMP TEST button to cause all front panel LEDs (except the CPU FAULT LED) to
illuminate steadily and turn the buzzer on. If Lamp Test is active for more than 10 seconds,
Common Trouble is activated.
Press and hold the LAMP TEST for 3 seconds to show the information about the system and
the firmware version as shown below.
Figure 29 LAMP TEST
The first line shows the number of zones and panel type and the second line shows the
firmware version number.
Indicators, Controls and Operations
9.4.8 ALM/SUP/TBL/BLDG AUDIBLE SIL Button (or MENU for single stage
systems)
If the Panel is configured as a two-stage system, press the ALM/SUP/TBL/BLDG AUDIBLE
SIL (buzzer silence) button to silence the buzzer. The buzzer resounds if there is a
subsequent event. Pressing the button when the buzzer is not sounding has no effect.
If the Panel is configured as a single stage system, press the MENU button to select the
command menu when a CFG-300 Service Tool with LCD is connected. Otherwise, this button
has no effect.
9.5 Circuit (Zone) Disconnect Buttons
There are Circuit (Zone) Disconnect buttons for all initiating and indicating circuits on the Fire
Alarm Control Panel. These buttons are located beside their respective indicating LED.
Pressing a Circuit Disconnect button bypasses the associated circuit and turns on its Trouble
Indicator, activating Common Trouble. While a Circuit is disconnected, all changes in status
(alarms and troubles) on that circuit are ignored. The panel does not activate disconnected
indicating circuits. Circuit Disconnect buttons are toggle switches: pressing an activated switch
a second time reconnects the circuit.
Disconnecting an active Latching Initiating Circuit (including Alarms, Water flow Alarm,
Sprinkler Alarm, General Alarm, and Latching Supervisory) does not affect its status until the
SYSTEM RESET button is pressed. Disconnecting an active Non-Latching Initiating Circuit
(including Non-Latching Supervisory and Trouble-Only) causes them to behave as if the alarm
situation has disappeared. Disconnecting an active indicating circuit immediately deactivates
the circuit.
When an Initiating Circuit Disconnect button is pressed again in order to reconnect the circuit,
the panel checks the state of the circuit. If the circuit is active, the Status Indicator flashes for
10 seconds at the Fast Rate without processing the input. If the Circuit is not reconnected by
then, it is processed as a new input.
49
Page 50
Disconnect buttons are also used during Walk Test as described in 11.9 7. Walk Test
i
(Command-Menu) on page 76.
9.6 Common Relays
9.6.1 Auxiliary Alarm Relay
The Auxiliary Alarm Relay functions the same way as the Common Alarm Relay in every
respect except that it can be disconnected by Auxiliary Disconnect with or without other
correlated relays if it is programmed to do so (see Table 14 on page 63). When configured
(see Table 14 on page 63), the relay can also be disconnected if signal silence is active and
reconnected if signal silence is de-activated.
9.6.2 Common Alarm Relay
The Common Alarm Relay activates when the common alarm sequence is activated. On a
two-stage system the relay may be configured to operate either on the first stage or both the
first and second stage alarm (see Table 14 on page 63). The common alarm relay is
disconnected by Auxiliary Disconnect if programmed (see Table 14 on page 63). The relay
remains on until the SYSTEM RESET button is pressed.
Indicators, Controls and Operations
9.6.3 Common Supervisory Relay
The Common Supervisory Relay activates when the common supervisory sequence is
activated as the result of an alarm on any un-bypassed latching or non-latching supervisory
circuit. The relay is turned off if all non-latching supervisory circuits are restored and there are
no latching supervisory circuits active. The relay can be disconnected by Auxiliary Disconnect
if programmed (see Table 14 on page 63). The relay functions the same way as an alarm relay
if the supervisory relay is disabled (see Table 14 on page 63).
9.6.4 Common Trouble Relay
The Common Trouble relay is activated when the common trouble sequence is activated as
the result of the trouble condition being detected on the system. It is turned off when all
troubles are cleared.
Note:Some troubles are latching: once they are detected they remain active until the
SYSTEM RESET button is pressed. In this case the common trouble indicator
also remains active until the SYSTEM RESET button is pressed. The common
trouble is not bypassed by the Auxiliary Disconnect function.
9.7 Circuit Types
9.7.1 Initiating (Detection) Circuit Types
9.7.2 Non-Verified Alarm
A Non-Verified alarm can have pull stations, smoke detectors, or heat detectors attached to it.
Activation of any of these devices immediately results in an alarm condition in the Fire Alarm
Control Panel. An Alarm condition causes the associated Circuit Status LED and the
COMMON ALARM LED to illuminate red.
50
Page 51
9.7.3 Verified Alarm
i
i
Verified Alarms are verified by a reset and timing procedure, and may include smoke
detectors, heat detectors or pull stations. Activation of pull stations or heat detectors results in
an alarm condition in the Fire Alarm Control Panel within four seconds. Smoke detectors are
verified for a real alarm within 60 seconds, depending upon the startup time of the devices
being used. If four seconds is too long a response time for pull stations, then wire them
separately on a Non-Verified Alarm Circuit. An alarm condition causes the associated Circuit
Status LED and the COMMON ALARM LED to illuminate red.
Sprinkler Alarms are identical to normal Non-Verified Alarms unless Water flow retard
operation is enabled. If Water Flow Retard Operation is enabled, then these circuits are
sampled every one second. If ten samples are active within any 15-second interval, the
Sprinkler Alarm is confirmed and processed. An Alarm condition causes the associated Circuit
Status LED and the Common Alarm LED to illuminate red.
Note:Do not use Retard Operation with any external retarding device; maximum retard
may not exceed 120 seconds.
Indicators, Controls and Operations
9.7.5 Water Flow Alarm (Water flow Sensors)
Water Flow Alarms are identical to normal Non-Verified Alarms except that any indicating
circuits programmed to these circuits (all are by default) are Non-Silenceable. Also, if Water
Flow Retard Operation is enabled (see Table 14 on page 63), these circuits are sampled every
one second. If ten samples are active within any 15-second interval, the Water flow Alarm is
confirmed and processed. An alarm condition causes the associated Circuit Status LED and
the Common Alarm LED to illuminate red.
Note:Do not use Retard Operation with any external retarding device; maximum retard
Activation on these circuits causes the Circuit Status LED and the amber COMMON
SUPERVISORY LED to illuminate. The buzzer sounds at the fast rate. If the circuit activation
is removed, the Supervisory condition clears (as long as there are no other Supervisory
conditions in the system) and the Circuit Status LED turns off.
Activation on these circuits causes the Circuit Status LED and the amber COMMON
SUPERVISORY LED to illuminate. The buzzer sounds at fast rate. If the circuit activation is
removed, the Supervisory condition does NOT clear.
9.7.8 General Alarm
The General Alarm provides remote general alarm for remote key switches. In a two-stage
system these inputs perform exactly the same function as the Front Panel or Remote
51
Page 52
Annunciator General Alarm button. In a single stage system, these inputs act the same as
Non-Verified Alarms; however, if Correlations are enabled, General Alarm Initiating Circuits
are correlated to ALL indicating circuits.
9.7.9 Property and building safety
This is a supervised general-purpose non-latching input used mainly for correlating to a relay
circuit associated with property and building safety. No other system condition occurs as a
result of its activation (short circuit), although it is supervised for Trouble (open circuit).
9.7.10 T rouble-Only
The Trouble-Only circuit monitors a Trouble Condition from an external device such as QX5000 Audio System. Both open and short circuits generate a non-latching Trouble condition.
9.8 Indicating (Signal) Circuit Types
9.8.1 Silenceable Signal
The Silenceable Signal circuit is used for audible devices such as bells and piezo mini-horns
that may be silenced either manually or automatically. While sounding, these devices follow
the pattern appropriate for the condition: the configured Evacuation Code (default is Temporal
Code) during Single-Stage Alarm or Two-Stage General Alarm, or the Alert Code during the
alert (first) stage of a two-stage alarm.
Indicators, Controls and Operations
9.8.2 Non-Silenceable Signal
The Non-Silenceable Signal Circuit is used for audible devices such as bells and piezo mini-
horns that may not be silenced either manually or automatically. While sounding, these
devices follow the pattern appropriate for the condition: the configured Evacuation Code
(default is Temporal Code) during Single-Stage Alarm or Two-Stage General Alarm, or the
Alert Code during the alert (first) stage of a two-stage alarm.
9.8.3 Silenceable Strobe
Silenceable strobes are silenced when the SIGNAL SILENCE button is pressed. For
synchronous strobes see section 10.0 Supported Protocols/Devices on page 56. (Note:Strobes do not support any code pattern.)
9.8.4 Non-Silenceable Strobes
Non-Silenceable Strobes are not silenced when the SIGNAL SILENCE button is pressed. For
synchronous strobes see section 10.0 Supported Protocols/Devices on page 56. (Note:Strobes do not support any code pattern.)
9.9 Evacuation codes (Signal Rates)
9.9.1 Single stage codes
52
ContinuousOn 100% of the time
Temporal Code3 of 0.5 second on, 0.5 second off then, 1.5 second pause
Page 53
March Code0.5 second on, 0.5 second off
California Code5 seconds on, 10 seconds off
9.9.2 Two-step codes
Alert Code0.5 second on, 2.5 seconds off
General AlarmEvacuation Code as selected from above.
Indicators, Controls and Operations
Continuous
0.5s
0.5s
0.5s
0.5s
5s
10s
0.5s
2.5s
1.5s
Figure 30 Evacuation and Alert Codes
9.10 Single Stage Operation
In a single stage system all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, Water flow Alarm,
and General Alarm Circuits. If any of these alarm inputs occur when the panel is not already in
alarm, the following occurs:
•The buzzer sounds steadily
•If Fire Drill is active, it is canceled
•The Common Alarm Indicator turns on
Temporal Code
March Code
California Code
Alert Code
•The Common Alarm, Auxiliary Alarm and all correlated relays activate if Auxiliary
Disconnect is not active
•The Auto Signal Silence Timer, if configured, starts. For UL installations, disable the
auto signal silence timer
•The Signal Silence Inhibit Timer, if configured, starts
•All connected relays programmed to the input are activated (provided that Aux
Disconnect is not active)
•Non-disconnected strobes associated with the input are activated
•Non-disconnected signals associated with the input are activated at the evacuation rate
Pressing the General Alarm button on the panel also initiates a general alarm.
Subsequent alarms when the panel is already in alarm cause the following:
•The alert buzzer sounds steadily
53
Page 54
•If Signals have been silenced as a result of the Signal Silence button or the Auto Signal
Silence Timer, Signals are resounded as they were before Signal Silence, the Signal
Silence Indicator is turned off, and the Auto Signal Silence Timer, if configured, is
restarted. For UL installations, disable the auto signal silence timer
•Any additional non-disconnected strobes associated with the new input are activated
continuously
•Any additional non-disconnected signals associated with the new input are activated at
the evacuation rate
9.11 Two-stage Operation
In a Two-Stage System Alarm inputs are either First Stage (Alert) inputs or Second Stage
(General Alarm) inputs. First Stage inputs include inputs from the following types of circuits:
Non-Verified Alarm, Verified Alarm, Sprinkler Alarm, and Water flow Alarm. Second Stage
inputs include Alarms on General Alarm Circuits, activation of the General Alarm button, or
expiration of the Auto General Alarm Timer.
If any of these alarm inputs occur when the panel is not already in alarm, the following occurs:
Indicators, Controls and Operations
•The buzzer sounds steadily.
•If Fire Drill is active, it is canceled.
•The Common Alarm Indicator turns on.
•The Common Alarm, Auxiliary Alarm and all correlated relays activate if Auxiliary
Disconnect is not active.
•The Auto Signal Silence Timer, if configured, starts. For UL installations, disable the
auto signal silence timer.
•The Signal Silence Inhibit Timer, if configured, starts.
•All non-disconnected relays programmed to the input are activated provided that
Auxiliary Disconnect is not active.
If the alarm is a Second Stage alarm all connected strobe circuits are activated continuously,
all non-disconnected signal circuits are activated at the evacuation rate, and the GENERAL
ALARM LED is turned on.
If the alarm is a First Stage alarm, the following occurs:
•Non-disconnected strobe circuits programmed to that circuit are activated continuously.
•Non-disconnected signal circuits programmed to that circuit are activated with the Alert
Code (see 9.8 Indicating (Signal) Circuit Types on page 52).
•The Auto General Alarm Timer, if configured, starts.
54
•The AUTOMATIC ALARM SIGNAL CANCEL (Acknowledge) LED starts flashing if
programmed. See Table 14 on page 63.
Subsequent First Stage alarms when the panel is already in alarm cause the following:
•The buzzer sounds steadily.
•If Signals have been Silenced as a result of the SIGNAL SILENCE button or the Auto
Signal Silence Timer, Signals are resounded as they were before Signal Silence, the
SIGNAL SILENCE LED is turned off, and the Auto Signal Silence timer, if configured, is
restarted. For UL installations, disable the auto signal silence timer.
Page 55
Indicators, Controls and Operations
•If the panel is not already in General Alarm, additional non-Disconnected Signals
programmed to the new input are activated with the Alert Code (see 9.8 Indicating
(Signal) Circuit Types on page 52).
•If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL
CANCEL LED is on steady, indicating that the Auto General Alarm Timer has been
acknowledged, the timer is restarted and the AUTOMATIC ALARM SIGNAL CANCEL
LED is extinguished (or blinks if it has been configured to blink).
A Second Stage Alarm (General Alarm) when the panel is already in alarm causes the
following:
•The buzzer is sounded steady
•All non-disconnected signals are activated at the evacuation rate
•If the SIGNAL SILENCE LED is on, it is turned off and the Auto Signal Silence Timer, if
configured, is restarted. For UL installations, disable the auto signal silence timer
•The AUTOMATIC ALARM SIGNAL CANCEL LED if on, is turned off
Alarm inputs are latching, which means that they remain active until the SYSTEM RESET
button is pressed. Note that if the system is configured for Correlations, any Second Stage/General Alarm (caused by the Auto General Alarm Timer, the GENERAL ALARM button on
the Front Panel or Remote Annunciator, or by a General Alarm Initiating Circuit) condition
activates ALL Indicating Circuits, whether they are correlated or not.
55
Page 56
10.0Supported Protocols/Devices
i
10.1 Synchronous St robes
A separate compatibility list is available for different supported models.
Strobes can be configured as normal (not synchronized or any of the above; see 11.0
Configuration with the CFG-300 LCD Service Tool on page 59). Any selection made is system-
wide (that is, whatever is selected applies to all the circuits in the system, configured as
strobes).
10.1.1 Signal silence action on strobes
The signal silence action on strobes depends upon the configuration. The following describes
the signal silence action on non-silenceable and silenceable strobes.
10.1.2 Non Silenceable strobe
If the output zone is configured as Non-Silenceable Strobe and if the SIGNAL SILENCE LED
is flashing on the panel while the strobes are active, the horn is silenced. If the signal is
activated again, the panel activates the horn again.
10.1.3 Silenceable strobe
If the output circuit is configured as Silenceable Strobe, and if the SIGNAL SILENCE LED is
flashing on the panel, both the horn and strobe are completely turned off by turning off the
output circuit. Pressing the SIGNAL SILENCE button again turns them on again.
Note:Please see the strobes manufacturer’s data for details.
10.2 System Sensor’s i3 Devices
The FA-300 fire control panel supports System Sensor’s i3 devices. Only the two wire smoke
3
detectors are supported on the i
build in fixed temperature (135F / 57.2C) thermal detector and is capable of sensing a freeze
condition i.e. if the temperature is below 41F / 5 C.
The zones should be programmed to i
11.0). If the zone is not programmed as i
simply treated as a regular zone. The panel is capable of detecting multiple troubles; if
different devices have different troubles on the same zone, all troubles are reported. The
following troubles are reported for the i
zone, which are 2W-B and 2WT-B. Model 2WT-B features a
3
devices.
3
devices to be considered as i3 zone (see Chapter
3
zone and i3 devices are connected to the zone, it is
10.2.1 i3 Zone Troubles
The following troubles can be reported for a zone configured as i3 zone:
56
Page 57
•Open circuit trouble
Zone-1
Open Trb. 1/ 1
Zone-1
Communic. Trb 1/ 1
Zone-1
Dirty Dev. Trb 1/ 1
Zone-1
Out of Sens Trb 1/ 1
•Communication trouble
•Out of sensitivity: defective or dirty device
•Freeze trouble
10.2.2 Open Circuit Trouble
If the loop is broken the panel shows open loop trouble. The panel can still communicate with
the devices depending upon where the open occurs.
Figure 31 Open Circuit Trouble
10.2.3 Communication Trouble
If there is a fault in the line or the line is too noisy, the panel cannot communicate with the
devices. The panel shows a communication trouble in this case.
Supported Protocols/Devices
Figure 32 Communication Trouble
10.2.4 Dirty Device Trouble
If any of the devices on the i3 zone are dirty, the panel shows a Dirty Device trouble. The
device needs cleaning or be replaced with a new device.
Figure 33 Dirty Device Trouble
10.2.5 Out of sensitivity Tr ouble
If any of the devices on the i3 zone is out of sensitivity and cannot detect an alarm condition,
the panel shows out of sensitivity trouble. In this condition the device is not usable and should
be replaced.
Figure 34 Out of sensitivity Trouble
57
Page 58
10.2.6 Freeze T rouble
Zone-1
Freeze Trb. 1/ 1
If the device has detected a freeze condition, (e.g. the temperature is below 41F / 5 C) then
the panel displays a freeze trouble. Only model 2WT-B is capable of thermal detection; model
2W-B does not indicate any freeze trouble.
Figure 35 Freeze Trouble
Supported Protocols/Devices
The LEDs on the i
3
smoke detectors provide a local visual indication of the detector status.
The smoke detector LED status should be confirmed with the panel, since Out of Sensitivity
and a Dirty Device have the same LED indication on the detector and the only way to
distinguish between the two is to use the CFG-300 Configuration Tool and check the
messages as noted above.
Table 11i
i3 Detector Condition
3
Smoke Detector LEDs
Green LEDRed LED
Power-upBlinks every 10 secBlinks every 10 sec
Normal (Standby)Blinks every 5 secOFF
Out of sensitivity (defective or dirty)OFFBlinks every 5 sec
Freeze troubleOFFBlinks every 10 sec
AlarmOFFSolid
58
Page 59
11.0Configuration with the CFG-300 LCD
Service Tool
Table 12 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Auto signal silence
timer
Table 13 Settings permitted in UL864
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in UL864, Standard for Control Units and Accessories for Fire Alarm Systems, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Auto signal silence
timer
There are three methods of configuring the FA-300 LED Series Fire Alarm Panels:
•Using the CFG-300 LCD Tool. See this chapter.
•Using a PC or laptop computer with a UIMA converter module.
•Using a PC or laptop computer with remote connection (must use fire alarm with built-in
Permitted in CAN/
ULCS527? (Y/N)
Y
Permitted in UL864?
(Y/N)
N
UDACT).
Possible settings\methods
Disabled or 5, 10, 15, 20, or
30 minutes
Possible settings\methods
Disabled or 5, 10, 15, 20, or
30 minutes
Settings permitted in
CAN/ULCS527
All
Settings permitted in
UL864
Disabled
This chapter describes how to configure an FA-300 LED Series Fire Alarm Panel with the
CFG-300 LCD service tool.
59
Page 60
Configuration with the CFG-300 LCD Service Tool
WALK
TEST
REMOT E
TROUBLE
CP U FAULT
GROUND
FAUL T
SIGNAL
SILENCE
FIRE
DRILL
GENE RAL
ALARM
SYSTEM
RESE T
AUX
DISC ONNE CT
LAMP
TEST (MENU)
ALM/SUP/TBL/
BLDG AUDIBLE
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON
TROUBLE
BATTERY
TROUBLE
ZONE-1
DISC ONNE CT
ZONE-3
DISC ONNE CT
ZONE-5
DISC ONNE CT
ZONE-7
DISC ONNEC T
ZONE-9
DISC ONNE CT
ZONE-11
DISC ONNE CT
ZONE-2
DISC ONNE CT
ZONE-4
DISC ONNE CT
ZONE-6
DISC ONNE CT
ZONE-8
DISC ONNE CT
ZONE-10
DISC ONNE CT
ZONE-12
DISC ONNE CT
NAC-1
DISC ONNE CT
NAC-3
DISC ONNE CT
NAC-2
DISC ONNE CT
NAC-4
DISC ONNE CT
0
2
4
6
8
*
1
3
5
7
9
#
ENTER
INFO
CANCEL
10 Q Z
2 A B C3 D E F
4 G H I
5 J K L
6 M N O7 P R S
8 T U V9 W X Y
BACK SPACEFor ward
SIL (MENU)
Use these
buttons for
configuration.
Their functions
are printed under
the label.
Use these
buttons for
configuration.
Their functions
are printed
under the label.
AUTOMATIC
ALARM SIGNAL
CANCEL
Figure 36 shows the function of the buttons on the front panel display.
Figure 36 FA-300 Configuration
60
11.1Accessing Configuration Mode
To access configuration mode
1. Connect the CFG-300. See the document included with the CFG-300 for details.
2. On a single stage system, press the MENU button.
On a two stage system, press the LAMP TEST and ALM/SUP/TBL/BLDG AUDIBLE SIL
buttons simultaneously.
The CFG-300 displays the Main Menu.
3. Enter your passcode.
The minimum number of digits for the passcode is four and the maximum is ten. The
passcode must be numerical values only. The default passcode is 1111.
4. Press the ENTER button.
The main command menu appears.
Page 61
5. If the passcode is wrong, the system prompts you to re-enter the passcode. After three
Enter passcode
_
-Command Menu-
1. FA-300 Config
2. Config Info
3. Set Time
4. Set Password
5. View EventLog
6. Clear EventLog
7. Walk Test
8. I3 Loop test
9. Dialer Config
10.Test Dialer
11.Exit
tries the system takes you back to the normal message display.
Figure 37 Enter passcode
11.2 Command Menu
The command menu is shown in Figure 38. The first line of the LCD always displays
-Command Menu-, and the second line scrolls through different selections.
To scroll through the menu
•Use the up and down arrow buttons, and then press the ENTER button to make a
selection.
To exit from the command menu
Configuration with the CFG-300 LCD Service Tool
Select the Exit menu option, and then press the ENTER button.
Note:Close jumper JW5 on the main board to access Command Menu features 1 and
9. See Figure 7 on page 21.
Figure 38 Command Menu
11.2.1 Using the Keypad to Program the FA-300
1. Access the configuration mode as described in 11.0 Configuration with the CFG-300
LCD Service Tool above.
61
Page 62
Configuration with the CFG-300 LCD Service Tool
1. Features
2. Inp. Zone
3. I3 Zones
4. Opt. Zone
-FA-300 Config-
5. Correlation
6. Inp Zone Label
7. Opt Zone Label
8. Default Config
2. Press ENTER to select an option.
The corresponding menu appears.
3. Press the up and down arrow buttons to scroll through the menu.
4. Press the left or right arrow buttons to select or unselect an option (selected = X). Use
the up and down arrows to scroll through the different options.
5. Once you have made the correct selection, press ENTER to confirm the change.
6. Press CANCEL to return to the previous menu.
11.3 1. FA-300 CONFIG (Command-Menu)
The FA-300 configuration menu is shown in Figure 39.
11.3.1 Command Menu/FA-300 Config-->Features
62
Figure 39 FA-300 Config menu
Page 63
Configuration with the CFG-300 LCD Service Tool
- Feature Config -
1 Man. Sig. Sil.
2 Fire Drill
3 Opt. Ckt. Corr
4 Wtr/Sprk. Retd
5 Aux Disc Prog
6 Sig-Sil Inh Tm
7 Aux Dis, Alm&Sup
8 Auto Sil. Tmr
9 Rem. Annun.
10 Alm. Xmit-Sil.
11 Pwr Fail Tmr.
12 Com. Supv. Rly
13 Sig-Sil. Isol.
14 Strobe Type
15 Signal Rate
16 Active EOL
17 Two Stage Op.
18 Gen-Alm Tmr
19 Com Alm Rly Op
Manual Sig. Silence
[X] ENABLE
Fire Drill
[X] ENABLE
Select Features to access the Feature Config menu shown in Figure 40.
Figure 40 Feature Config menu
Table 14 describes the options in the Feature Config menu.
FeatureDefault
Table 14Feature Config menu
Command Menu/FA-300 Config/Features/
1. Manual Signal Silence
Command Menu/FA-300 Config/Features/
2.Fire Drill
20 1st stage LED ind
[X] ENABLE->Default
[ ] DISABLE
[X] ENABLE ->Default
[ ] DISABLE
Name in the
Configuration Utility
Manual signal silence
Fire drill
FA-300
Description
Use this menu to enable or
disable the SIGNAL SILENCE
button. See 9.4.2 SIGNAL
SILENCE Button on page 48.
Use this menu to enable or
disable the FIRE DRILL button.
See 9.4.3 FIRE DRILL Button on
page 48.
63
Page 64
Table 14Feature Config menu
Opt. Ckt. Corr.
[X] DISABLE
Waterflow/Sprk. Retd
[X] DISABLE
Aux Disc Prog
[X] DISABLE
Sig-Sil. Inhibit Tmr
[X] DISABLE
FeatureDefault
Command Menu/FA-300 Config/Features/
3.Output Circuit Correlation
[X] DISABLE->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
4.Waterflow/Sprinkler Retard
Operation
[X] DISABLE ->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
5.Aux. disconnect, disconnects
Aux Alarm relay and all
programmed relays
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
6.Signal-Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
Signal correlations
Retard waterflow and
sprinkler circuit
"Aux Disconnect"
disconnects prog. relay
Signal silence inhibit
Timer
FA-300
Description
If enabled, the programmed
correlations (see 11.3.5
Command Menu/FA-300 Config->Correlation on page 70) are
effective. If disabled, the
programmed correlations are
ignored and all the output circuits
are correlated to all the input
circuits.
If disabled, all the initiating
circuits configured as water flow
or sprinkler act as non-verified
alarms. If enabled, retard
operation is performed for
initiating circuits configured as
water flow or sprinkler.
See 9.7.5 Water Flow Alarm
(Water flow Sensors) on page 51.
If disabled, only the Auxiliary
Alarm Relay is disconnected
when you press AUXILIARY
DISCONNECT (see 9.4.6
AUXILIARY DISCONNECT
Button on page 48).
If enabled, the Auxiliary Alarm
Relay and all correlated relays
are disconnected when you press
AUXILIARY DISCONNECT (see
9.4.6 AUXILIARY DISCONNECT
Button on page 48). Correlated
relays include: RM312/RM306
relays and SRM-312 relays.
Use this menu to inhibit the
SIGNAL SILENCE button for a
desired length of time. While this
timer is running, pressing the
SIGNAL SILENCE button has no
effect. See 9.4.2 SIGNAL
SILENCE Button on page 48.
According to the Canadian
National Building Code, this timer
should be set to one minute.
64
Page 65
Table 14Feature Config menu
Aux Dis,Dis Alm&Spv
[X] DISABLE
Auto Sig-Sil. Timer
[X] DISABLE
No. of Remote Annun.
[X] NONE
Alm. Xmit-Sil.
[X] DISABLE
AC Pwr Fail Dly Tmr.
[X] NONE
FeatureDefault
Command Menu/FA-300 Config/Features/
7. AUXILIARY DISCONNECT
disconnects Alarm Relay and
Supervisory Relay
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
8.Auto Signal Silence Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
Command Menu/FA-300 Config/Features/
9. Number of Remote
Annunciators or smart relays
[X] NONE->Default
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
Command Menu/FA-300 Config/Features/
10.Silence Alarm transmit
[X] DISABLE->Default
[ ] ENABLE
Command Menu/FA-300 Config/Features/
11.AC power fail delay timer
[X] NONE ->Default
[ ] 1 HRS
[ ] 2 HRS
[ ] 3 HRS
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
"Aux Disconnect"
disconnects alarm
relay
Signal silence Timer
Remote annunciators
Alarm transmit affected
by signal silence
FA-300
Description
If enabled, the Common Alarm
Relay and the Common
Supervisory Relay, in addition to
the Auxiliary Alarm Relay, are
disconnected when you press
AUXILIARY DISCONNECT (see
9.4.6 AUXILIARY DISCONNECT
Button on page 48). The PR-300
does not transmit a supervisory
or alarm event.
If disabled, pressing AUXILIARY
DISCONNECT has no effect on
the Common Alarm Relay, the
Common Supervisory Relay, and
the PR-300.
Use this menu to determine the
time period for which the
indicating circuits sound before
they are automatically silenced.
For UL installations, disable the
Auto Signal Silence Timer.
Use this menu to select the
number of remote annunciators.
Any combination of remote
annunciators or smart relays can
be used as long as the total
number does not exceed 6. The
annunciators’ addresses should
be without gaps and in sequence.
If disabled, the SIGNAL
SILENCE button does not silence
the Auxiliary Alarm Relay, but it
does silence the indicating
circuits. If enabled, the SIGNAL
SILENCE button silences the
Auxiliary Alarm Relay and the
indicating circuits. See 9.4.2
SIGNAL SILENCE Button on
page 48.
Use this menu to delay the AC
power fail trouble for the
programmed time period. If
disabled, the AC power fail is
reported right away.
65
Page 66
Table 14Feature Config menu
Common Supv. Relay
[X] DISABLE
Sig-Sil. Isolator
[X] DISABLE
Strobe Type
[X] NORMAL
Signal Rate
[X] TEMPORAL
Active EOL
[X] DISABLE
Two Stage Operation
[X] DISABLE
FeatureDefault
Command Menu/FA-300 Config/Features/
12.Common Supervisory Relay
[ ] ENABLE ->Default
[X] DISABLE
Command Menu/FA-300 Config/Features/
13.Signal Isolators
[ ] ENABLE
[X] DISABLE->Default
Command Menu/FA-300 Config/Features/
14.Strobe Type
[X] NORMAL ->Default
[ ] MIRCOM
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Command Menu/FA-300 Config/Features/
15.Signal Rate
[X] TEMPORAL->Default
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
Supervisory relay used
as alarm relay
Isolators on signal
circuits
Strobe
Signal rate
FA-300
Description
If enabled, the Common
Supervisory Relay behaves as a
common alarm relay. If disabled,
it behaves as a common
supervisory relay.
Enable this function only when
suite isolators are used (Canada
only).
Use this menu to select the
manufacturer of the strobes used
in the system. The selection is
system-wide and applies to all
indicating circuits configured as
strobes. For NORMAL strobes
there is no synchronization, while
other strobes are synchronized
and use manufacturer’s protocol
to synchronize the strobes.
Use this menu to set the rate at
which the indicating circuits
sound.
Command Menu/FA-300 Config/Features/
16. Active EOL
[X] DISABLE->Default
[ ] NO
Command Menu/FA-300 Config/Features/
17. Two-stage Operation
[X] DISABLE->Default
[ ] ENABLE
66
Active end-of-line
Second stage
Enable this function if using an
Active End-of-Line resistor.
Enable this function if you are
using the ICAC-306 (the ICAC306 has built in Active End-ofLine resistors).
Use this menu to allow the
system to perform a two-stage
operation. This selection also
sets the Auto General Timer to 5
minutes.
The user should always either
disable the Auto Signal Silence
Timer or set it to be greater than
the Auto General Alarm Timer.
Page 67
Table 14Feature Config menu
Auto Gen-Alarm Timer
[X] DISABLE
Common Alm Rly. Oper
[X] SECOND STAGE
1st stage LED indic.
[X] DISABLE
FeatureDefault
Command Menu/FA-300 Config/Features/
18. Auto General Alarm Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
Command Menu/FA-300 Config/Features/
19. Common Alarm Relay
Operation
[ ] BOTH STAGES>Default
[X] SECOND STAGE ONLY
Command Menu/FA-300 Config/Features/
20. First Stage LED
Configuration with the CFG-300 LCD Service Tool
Name in the
Configuration Utility
General alarm Timer
Alarm relay second
stage
FA-300
Description
This function is used for twostage systems only. This function
sets the time period for automatic
evacuation.
Use this menu to allow the
Common Alarm Relay to operate
in second stage only or to
operate in both stages.
When disabled, the AUTOMATIC
ALARM SIGNAL CANCEL LED
does not illuminate during the
first stage alarm.
[X] DISABLE->Default
[ ] ENABLE
When enabled, the AUTOMATIC
ALARM SIGNAL CANCEL LED
flashes at the fast rate during the
first stage alarm.
Note: If this option is enabled,
then the panel is outside of UL/
ULC certification acceptability.
The authority having jurisdiction
must approve this selection.
67
Page 68
Configuration with the CFG-300 LCD Service Tool
i
1 Zone-1
2 Zone-2
--
--
Initiating Zone
12 Zone12
Zone-1 Type
[X] NON-VERIF ALARM
Zone-12 Type
[X] NON-VERIF ALARM
[ ] Zone-1
[ ] Zone-2
--
--
I3 Detection Zones
[ ] Zone-12
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
1 1.3.2 Command Menu/FA-300 Config-->Inp Zone
This Inp Zone menu is used to program the process type for the initiating circuits. The
maximum number of initiating circuits is 12. Only those supported by the particular model are
shown in the CFG-300 Configuration Tool.
Command Menu/FA-300 Config/Ipt. Zone
1.Process Type (Initiating circuit)
[X] NON-VERIF ALARM
->Default
[ ] VERIF ALARM
[ ] SPRKL ALM
|
|
|
12.
[ ] WTR-FLOW ALM
[ ] NON-LATCH SUP
[ ] LATCH SUPV
[ ] GEN ALARM
[ ] BUILDING
[ ] TRB ONLY
1 1.3.3 Command Menu/FA-300 Config-->I3 Zone
[ ] Zone-1->Default
.
.
.
[ ] Zone-12->Default
Use this menu to select the
circuit type of each input
zone. See 9.7 Circuit
Types on page 50.
Use this menu if i3 devices
are present on a zone. See
10.2 System Sensor’s i3
Devices on page 56.
68
Page 69
Configuration with the CFG-300 LCD Service Tool
i
1 NAC-1
2 NAC-2
3 NAC-3
4 NAC-4
Indicating Zone
NAC-1 Type
[X] SIL-ABLE
NAC-4 Type
[X] SIL-ABLE
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
11.3.4 Command Menu/FA-300 Config-->Opt Zone
This menu is used to program the process type of the indicating circuits. The maximum
number of indicating circuits is 4. Only those supported by the particular model are shown in
the CFG-300 Configuration Tool.
Command Menu/FA-300 Config/Opt. Zone
1.Process Type (Indicating Circuits)
|
|
|
4.
[X] SIL-ABLE->Default
[ ] NON SIL-ABLE
[ ] SIL-ABLE STR
[ ] NON-SIL STR
Use this menu to program
the process type of each
indicating circuit. See 9.8
Indicating (Signal) Circuit
Types on page 52.
69
Page 70
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
i
Zone-1 Corr.
[X] NAC-1
Zone-12 Corr.
[X] NAC-1
i
1 Zone-1
2 Zone-2
--
--
Initiating Zone
12 Zone12
instructions on making menu selections.
1 1.3.5 Command Menu/FA-300 Config-->Correlation
Command Menu/FA-300 Config/Correlation
1.Correlation
Configuration with the CFG-300 LCD Service Tool
|
|
|
12.
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
1 1.3.6 Command Menu/FA-300 Config-->Inp Zone Label
[X] NAC-1 ->Default
[X] NAC-2 ->Default
[X] NAC-3 ->Default
[X] NAC-4 ->Default
instructions on making menu selections.
Use this menu to correlate
initiating circuits to
indicating circuits. By
default all the initiating
circuits are correlated to all
the indicating circuits.
70
Use the buttons described below for entering messages. These buttons are alternate functions
of bypass switches and are physically located in the same position as described following.
Page 71
Command Menu/FA-300 Config/Ipt. Zone Lab el
Zone-1 Label
Zone-1
Zone-12 Label
Zone-12
i
1 NAC-1
2 NAC-2
3 NAC-3
4 NAC-4
Indicating Zone
1.Initiating zone label
[Zone-1 ]->Default
[Zone-12 ]->Default
BYPASS SWITCH TRANSLATION
|
|
|
12.
KEY SEQ 1 2 3 4 KEY SEQ 1 2 3 4
--------------------------------------
Zone-1
Zone-3 2 A B C Zone-4 3 D E F
Zone-5 4 G H I Zone-6 5 J K L
Zone-7 6 M N O Zone-8 7 P R S
Zone-9 8 T U V Zone-10 9 W X Y
Zone-11 Back Space Zone-12 Forward
Configuration with the CFG-300 LCD Service Tool
0 Q Z Zone-2 1
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
11.3.7 Command Menu/FA-300 Config-->Opt Zone Label
71
Page 72
Use the buttons described below for entering messages. These buttons are alternate functions
NAC-1 Label
NAC-1
NAC-4 Label
NAC-4
i
Load the default
settings? Y
Default settings
have been loaded
i
of bypass switches and are physically located in the same position as described below.
Command Menu/FA-300 Config/Opt. Zone Lab el
1.Indicating zone label
[NAC-1 ]->Default
[NAC-4 ]->Default
BYPASS SWITCH TRANSLATION
|
|
|
4.
KEY SEQ 1 2 3 4 KEY SEQ 1 2 3 4
--------------------------------------
Zone-1
Zone-3 2 A B C Zone-4 3 D E F
Zone-5 4 G H I Zone-6 5 J K L
Zone-7 6 M N O Zone-8 7 P R S
Zone-9 8 T U V Zone-10 9 W X Y
Zone-11 Back Space Zone-12 Forward
0 Q Z Zone-2 1
Configuration with the CFG-300 LCD Service Tool
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
Use this menu to load the default configuration in
Press the up and down arrow buttons to select
between Y/N. Press ENTER to restore the
default configuration.
the panel.
Warning: When you load the default
configuration, the previously programmed
configuration is lost permanently.
11.4 2. Config Info (Command-Menu
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
72
Page 73
Press the down arrow button to see
Configuration type:
Factory default
Job Name:
No job loaded
Technician ID:
Unknown
Cfg. Date and Time:
hh:mm day year:mm:dd
Configurator Version
x.x.x.x
i
1 Daylight Save
2 Time Clock
3 Compensation
Daylight Saving
[X] DISABLE
more information.
Press the down arrow button for further
information.
Configuration with the CFG-300 LCD Service Tool
Configuration type shows how the panel was configured.
Factory default means the panel has not been configured;
it is as it came from the factory.
Front Panel means it was configured at the panel.
Serial Port means the configuration was done from a
computer through the serial port.
Modem means the configuration was done remotely
through a modem.
If you upload a job configuration to the panel using the PC
configuration utility, the job name appears on this screen.
The job name can be up to a maximum of 20 characters.
If you upload a job to the panel using the FA-300
Configuration Utility, the technician’s name (ID) appears on
this screen. The technician ID can be up to a maximum of
10 characters.
This screen shows the date and time that the configuration
was last changed (if Time and Date have been set at the
panel).
Press the down arrow button for further
information.
This screen shows the version of the FA-300 Configuration
Utility. It displays 0.0.0.0 if the FA-300 Configuration Utility
was not used.
11.5 3. Set Time (Command-Menu)
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Command Menu/Set Time
1. Daylight saving time
[X] DISABLE ->Default
[ ] ENABLE
Use this menu to enable
daylight savings time.
73
Page 74
Configuration with the CFG-300 LCD Service Tool
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01
Daily Compensation:
0
Daily Compensation:
Panel Config Updated
Command Menu/Set Time
2. Set time and date
Command Menu/Set Time
2. Compensation
When value is entered the
following message appears
Default
00:00 MON 2000-01-01
Compensation value
can range from -15 to
+15 seconds.
Use this menu to set the
time and date. Use the left
and right arrow buttons to
move the cursor to the
desired location in the
display and use the up and
down arrow buttons to
increase or decrease the
values. Press ENTER to
accept the changes and
press CANCEL to ignore
the changes.
Note: time is in 24 hour
format
Use the up down arrow
buttons to select daily
compensation value and
press ENTER. For a fast
clock adjust negatively. For
a slow clock adjust
positively. For example: for
a clock which runs 5
minutes a month (based on
30 days) fast select -10
seconds.
74
Page 75
Configuration with the CFG-300 LCD Service Tool
i
Enter new passcode
[ ]
Re-enter passcode
[ ]
invalid passcode
Passcode updated
EAST LOBBY ENTRANCE
OPEN TRB 01/09
VERIFIED ALARM Z-01
2002/10/22 11:45.AM
ZONE
Message
EVENT
01 of 09
Process
Type
Physical
Zone No.
DATE
TIME
"INFO" Key
EVENT
type
ZONE
Message
EVENT
type
INFO
Process
Type
Physical
Zone No.
Time
11.6 4. Change password (Command-Menu)
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
If the passcode does not match, the
following message appears:
If the passcode is OK the following
message appears:
1 -> Default
11.7 5. View Event Log (Command-Menu)
The event log looks the same as the normal event queue (see 11.15 Zone messages on
page 89). Press the INFO button to see more information about the event. Figure 41 shows an
example of how the INFO button works.
Use this menu to change
the passcode. The minimum
number of digits is 4 and the
maximum is 10. Only
numeric digits are allowed.
Figure 41 The event log
The event log saves a maximum of 200 events.
75
Page 76
Configuration with the CFG-300 LCD Service Tool
i
-Select Log-
1 Alarm Log
2 General Log
3 All Logs
Clear all the
selected log(s)? Y
Log(s) cleared
i
Perform the
walk test? Y
11.8 6. Clear Event Log (Command-Menu)
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Use this menu to clear alarm logs, event logs, or both.
Figure 42 Select Log
1. Select the type of log to clear. Press the ENTER button. The system confirms before
clearing logs.
Figure 43 Clear all the selected logs
2. Press the ENTER button to confirm or the CANCEL button to cancel the operation.
Figure 44 Logs cleared
11.9 7. Walk Test (Command-Menu)
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
A walk test allows an installer to verify the initiating circuit wiring in a system. When walk test is
selected, the following screen appears:
76
Figure 45 Walk test confirmation
Page 77
Configuration with the CFG-300 LCD Service Tool
-WALK TEST ZONES-
[ ] Zone-1
-Walk test active-
Alarm:00 Trb:00
i
Press the ENTER button to activate the walk test and the CANCEL button to cancel the walk
test. The next screen allows zones to be selected for walk test. Use the up and down arrow
buttons to scroll through the zones and use the left and right arrow buttons to select a zone.
Press the ENTER button when you are done with all the selections.
Figure 46 Walk test zones
The walk test is now active.
Figure 47 Walk test active
The activation of any initiating circuit that has been selected for a walk test causes the Audible
Indicating Circuits (not Strobes) to activate briefly for a number of short bursts corresponding
to the selected circuit number. If the first selected circuit is activated, the indication circuits
sound for one burst. If the second selected circuit is activated, the indication circuits sound for
two bursts, and so on. This means that if, for example, circuits 1, 3 and 5 were selected for the
walk test, they would sound with one, two and three bursts respectively. The burst interval is
half a second on and half a second off. After the sounding pattern has been sent on the
indicating circuits, the initiating circuit is reset and tested again. If it is still active (in alarm) the
pattern is re-sent. Trouble on any initiating circuit selected for the walk test activates the
indicating circuits continuously for five seconds. Activation of a circuit also causes the alarm
count to increase while the trouble on the initiating circuit causes the trouble count to increase.
Alarm Verification and Water flow Alarm Retard Operations are disabled on circuits being walk
tested. All circuits not selected for the walk test continue to function normally. If a circuit was
disconnected before the walk-test mode was entered and is not selected for the walk-test, it
remains disconnected while the walk test is active. Walk test operation is disabled if the Fire
Alarm Control Panel is in alarm or goes into alarm while the walk test is active.
Notes: If a UDACT is used with the system, all walk-test events are reported to the
monitoring agency. The monitoring agency should be instructed to ignore
reported events during the walk-test.
IF THERE IS NO ACTIVITY FOR ONE HOUR, THE SYSTEM RETURNS TO
NORMAL OPERATION.
77
Page 78
11.10 8. i3 Loop Test (Command-Menu)
i
Perform the i3
Loop test? Y
-I3 TEST ZONES-
[ ]Zone-1
The selected zone
is not ready yet
The selected zone
is not i3 type
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
The i3 maintenance test is designed to test the devices on i3 zone. If there is noise on the line
or if the device is too far away from the panel, the devices may not respond to the panel
3
inquiries. An i
power-up or after pressing the reset. If the i
message appears on the screen:
maintenance test can be invoked from the command menu six minutes after
3
Configuration with the CFG-300 LCD Service Tool
maintenance test is selected, the following
Figure 48 i
If you select Y by pressing ENTER, the display asks you for which zone you want to perform
3
the i
test. Note that only one zone at a time can be in maintenance test. Select the zone by
pressing the up and down arrow buttons and then pressing the right arrow button to select the
device. After the device is selected press ENTER.
Figure 49 i
3
If the i
information message appears.
Figure 50 i
If a zone is selected that is not configured as an i
3
loop test confirmation
3
test zones
maintenance test is selected within six minutes after power-up or reset, the following
3
test not ready
3
zone, the following message appears:
78
Figure 51 The selected zone is not i
After the zone goes into the i
maintenance test takes five minutes. During this time you can walk through the device and
3
maintenance test, no other zone can be put into the test. The
3
type
Page 79
Configuration with the CFG-300 LCD Service Tool
i
1 Account Info
2 Telephone line
3 Report Options
4 Time Parameter
-Dialer Config-
5 Enable/Disable
make sure all the devices are working properly. The following table lists the status of the
devices while in walk test.
Tab le 15i3 Detector Statuses
i3 Detector Condition
Proper operationDouble blink every 5 secOFF
Out of sensitivityOFFDouble blink every 5 sec
Freeze conditionOFFDouble blink every10 sec
You can cancel the maintenance test either by pressing the SYSTEM RESET button or by
going into the configuration section and canceling the test.
Green LEDRed LED
11.11 9. Dialer Config (Command-Menu)
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
Figure 52 shows the Dialer Config menu.
Figure 52 Dialer Config menu
79
Page 80
Configuration with the CFG-300 LCD Service Tool
1 Account#1 ID
2 Account#1 Tel
3 Accnt#1 Format
4 Account#2 ID
- Account Info -
5 Account#2 Tel
6 Accnt#2 Format
Account#1 ID:
_
Account#1 Telnum:
_
1 1.11.1 Command Menu/Dialer Config-->Account Info
Command Menu/Dialer Config/Account Info
1.Account# 1 Identification
123456->Default
Command Menu/Dialer Config/Account Info
2.Account#1 Telephone Number
[101]->Default
Use this menu to set the
Account ID for the
monitoring station to which
the dialer reports events.
The maximum # of digits
allowed is six. For contact
ID, only the first four digits
are used; the last two are
truncated.
Unless you are using the
SIA protocol, the allowed
digits for the account ID are
simple digits 0 to 9 and
hexadecimal digits A to F
(the SIA protocol only
allows digits 0 to 9).
To enter hexadecimal digits,
press the INFO button. The
letter “A” appears. To scroll
through the rest of the
letters, press INFO
repeatedly. Press # to move
the cursor to the right or
press * to move it to the left.
Use this menu to set the
telephone number of the
monitoring station. The
maximum # of digits allowed
is 19 including “,” and
numerals. The “,” is a 1 sec
delay. To enter “,” press the
INFO button. Press # to
move the cursor to the right
or press * to move it to the
left. An example of a typical
telephone # is 9,,12345678.
80
Page 81
Command Menu/Dialer Config/Account Info
ACCNT#1 Format:
[X] Contact ID
Account#2 ID:
_
Account#2 Telnum:
_
ACCNT#2 Format:
[X] Contact ID
3.Account#1 Reporting Format
[X] CONTACT ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Command Menu/Dialer Config/Account Info
4. Account# 2 Identification
654321->DefaultSame as Account#1.
Command Menu/Dialer Config/Account Info
5.Account# 2 Telephone Number
[ 101 ]->DefaultSame as Account#1.
Configuration with the CFG-300 LCD Service Tool
Set the reporting format that
is recognized or preferred
by the monitoring station.
Command Menu/Dialer Config/Account Info
6.Account# 2 Reporting Format
[X] Contact ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Same as Account#1.
81
Page 82
Configuration with the CFG-300 LCD Service Tool
i
1 Line1 Dialtype
2 Line2 Dialtype
3 Line1 Dialtone
4 Line2 Dialtone
- Telephone Line -
5 Num of Retries
Line#1 Dialing Type:
[X] DTMF Dial
Line#2 Dialing Type:
[X] DTMF Dial
Line#1 Wait Dialtone
[X] ENABLE
Line#2 Wait Dialtone
[X] ENABLE
Number of Retries:
06
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
1 1.11.2 Command Menu/Dialer Config-->Telephone Line
Command Menu/Dialer-Config/Telephone Line
1. Line#1 Dialing Type
[X] DTMF Dial->Default
[ ] Pulse Dial
Command Menu/Dialer-Config/Telephone Line
2. Line#2 Dialing Type
[X] DTMF Dial->Default
[ ] Pulse Dial
Command Menu/Dialer-Config/Telephone Line
3. Line#1 wait for Dial tone
[X] ENABLE ->Default
[ ] DISABLE
Command Menu/Dialer-Config/Telephone Line
4.Line#2 wait for Dial tone
Set the dialing type for line
#1; this is the type
recognized or preferred by
the telephone company.
Same as Line#1.
Use this menu to let the
system know whether or not
to wait for a dial tone before
dialing. Cell phone setup for
the dialer requires that the
system not wait for dial tone
before dialing.
Command Menu/Dialer-Config/Telephone Line
5.Number of retries
82
[X] ENABLE ->Default
[ ] DISABLE
06 ->Default
Same as Line#1.
Set the number of retries for
both line#1 and line#2. This
function lets the dialer retry
on either line if it is busy or
not available. If the retry
count expires, the panel
reports a line trouble.
Page 83
Configuration with the CFG-300 LCD Service Tool
i
1 Alarm Prio.
2 Trouble Prio.
3 Supv. Prio.
4 Aux Dis Report
- Report Options -
5 Fire Panel
6 Operation Mode
7 Checksum Bits
Alarm Priority:
[X] Account 1
Trouble Priority:
[X] Account 1
SUPV Priority
[X] Account 1
AuxDis Alm/Supv Rpt.
[X] DISABLE
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
Use this menu to set the
account priority for reporting
alarms. If the priority is set
for account#1 then the
dialer tries account#1 first
for reporting.
Use this menu to set the
account priority for reporting
trouble. If the priority is set
for account#1 then the
dialer tries account#1 first
for reporting.
Use this menu to set the
account priority for reporting
supervisory troubles. If the
priority is set for account#1
then the dialer tries
account#1 first for reporting.
If this function is enabled,
pressing AUXILIARY
DISCONNECT (see 9.4.6
AUXILIARY DISCONNECT
Button on page 48) blocks
the alarm and supervisory
events from being reported
through the built-in dialer.
83
Page 84
Command Menu/Dialer-Config/Report Options
Fire Panel Type:
[X] FA-300 Panel
Dialer Oper. Mode:
[X] (U)DACT
Checksum Bits:
[X] 8 Bits
i
1 AC-Loss Delay
2 Cellphone Date
3 Auto-Test Time
-Time Parameter-
AC-Loss Delay(Hrs)
0
5.Fire Panel type
[X] FA-300 Panel->Default
[ ] FA-1000 Panel
[ ] FX-2000 Panel
Command Menu/Dialer-Config/Report Options
Configuration with the CFG-300 LCD Service Tool
Do not change this function;
keep it as default.
For factory use only.
6.Dialer operation mode
[X] (U)DACT ->Default
[ ] DACT
Command Menu/Dialer-Config/Report Options
7.Checksum Bits
[X] 8 Bit ->Default
[ ] 16 Bits
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
Use this menu to select the
functionality of the dialer. In
DACT mode only common
trouble/alarm/supervisory
are reported while in
UDACT mode all point
information is reported
Do not change this function;
keep it as default
For factory use only.
Command Menu/Dialer-Config/Time Parameter
1.AC Loss delay
84
0 ->Default
Use this menu to delay the
reporting of AC loss trouble
on the dialer for the
programmed time period.
Page 85
Command Menu/Dialer-Config/Time Parameter
Cellular Report Date
0
Auto-Test Time
00:30
Configuration with the CFG-300 LCD Service Tool
2.Cellular report date
0 ->Default
Command Menu/Dialer-Config/Time Parameter
3.Auto test time
00:30 ->Default
Use this menu to set the
test report date for the cell
phone setup. Set this menu
to 0 if there is no test
reporting for a cell phone,
or if the phone line is a
regular line. Set this menu
from 01 to 28 to schedule a
test for Line 2 on a certain
day of the month. See
section 11.11.5 for more
information.
When a cell phone service
is employed for the panel, it
should only be connected
to telephone line #2 CO
interface. Also, the dial
tone detection feature of
Line 2 should be disabled
for cell phone application.
Use this function to set the
time for the automatic test.
When this test is
performed, the test report is
sent to the monitoring
station. This test must be
performed at least once a
day. The time is in 24 hour
format, which means 00:30
is 30 minutes after
midnight.
The Auto test time can be
configured to:
12:00 a.m. to 5:59 a.m.:
test every 24 hours
6:00 a.m. to 11:59 a.m.:
test every 6 hours
12:00 p.m. to 23:59 p.m.:
test every 12 hours
If the Cellular report date is
set to 0, then the test
alternates between Line 1
and Line 2. See section
11.11.5 for more
information.
85
Page 86
Configuration with the CFG-300 LCD Service Tool
i
Dialer Ena/Dis
[X] ENABLE
------Warning-------
Dialer Disabled!!!
11.11.5 Auto Test Time and Cellular Report Date
If the Cellular report date is set to 0, then the dialer alternates between Lines 1 and 2 when
performing the automatic test. If the Cellular report date is not set to 0, then the automatic test
is performed on Line 1 except on the Cellular report date, when it is performed on Line 2. See
examples in the following table.
Cellular Report DateAuto Test TimeLine 1 TestedLine 2 Tested
000:30
06:006:00 a.m. and 6:00 p.m.12:00 p.m. and 12:00 a.m.
012:0012:00 p.m.12:00 a.m.
1500:30
156:00
1512:00
Note:Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
12:30 a.m. every other day
(alternates with Line 2)
12:30 a.m. every day
except on the 15th of the
month
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. every
day except on the 15th of
the month
12:00 p.m. and 12:00 a.m.
every day except on the
15th of the month
12:30 a.m. every other day
(alternates with Line 1)
12:30 a.m. on the 15th of
the month
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. on
the 15th of the month
12:00 p.m. and 12:00 a.m.
on the 15th of the month
Use this menu item to
select the number of rings
on which the panel’s
modem answers. The
default number of rings is
five. The maximum number
of rings you can define is
eight.
If you select the “Disabled”
option, the modem is
disabled and the panel
does not pick up the
incoming call.
11.12.1 Dialer Test Messages
The following messages appear during the test processes of Lines #1 and #2. The messages
that appear depend on the status of the dialer and the test results that are found.
Press Enter to test Line #1. Press Cancel
to exit this menu. For a description of test
messages, see 11.12.1 Dialer Test
Messages below.
Press Enter to test Line #2. Press Cancel
to exit this menu. For a description of test
messages, see 11.12.1 Dialer Test
Messages below.
This feature flushes all reportable events
from the buffer. Press ENTER to reset the
dialer. Press CANCEL to exit this menu.
The dialer is checking the line for voltage. This
message automatically displays when Manual Test is
selected.
No DC line voltage. The line is dead or no phone line
is connected.
The dialer is waiting for a dial tone.
87
Page 88
Configuration with the CFG-300 LCD Service Tool
Failed: No Dialtone
Dialing Receiver Now
No DTMF tone
Waiting for Acktone
Failed No Acktone
Reporting Event Now
Waiting for Kissoff
No Kissoff
Passed: Manual test
This message may indicate a noisy telephone line.
The dial tone was received and telephone number
dialing is in process.
This message indicates that the dialer failed to send
a DTMF tone.
Waiting for availability of the receiver. The receiver
confirms the availability by sending an
acknowledgement tone.
This message indicates that either the telephone
number may be wrong or the receiver is not
available.
When sending events to the receiver, the display
toggles between this message and “Waiting for
Kissoff“ for all events sent.
The dialer is waiting for the kissoff tone. The kissoff
tone indicates that the receiver has received the
event reports.
No Kissoff means receiver has not received any
event reports.
The line passed the test; everything is OK.
11.13 11. Exit (Command-Menu)
Press ENTER after selecting EXIT from the main menu to return the panel to normal
operation.
11.14 CFG-300 LCD service tool operation
If an LCD service tool is connected to the panel, you can view the latest message but you
cannot scroll through the messages. In order to see all of the messages, enter the
programming menu and view the event logs. The logs are arranged so that the most recent
message is shown first. Listed below are the different kinds of messages that can appear on
the LCD service tool.
88
Page 89
11.15 Zone messages
EAST LOBBY ENTRANCE
OPEN TRB 01/09
VERIFIED ALARM Z-01
18:01 TUE 2003-04-04
ZONE
Message
EVENT
01 of 09
Process
Type
Physical
Zone No.
DATE
TIME
"INFO " Key
EVENT
type
EAST WING LOBBY
SHORT TRB 02/09
SILENCE-ABLE NAC-1
18:01 TUE 2003-02-02
"INFO " Key
ZONE
Message
EVENT
type
EVENT
02 of 09
Process
Type
Physical
Zone No.
DATE
TIME
Point annunciation is indicated on the LCD display. There are no separate queues for
TROUBLE, ALARM, SUPERVISORY and BUILDING; instead there is only one queue that
indicates all the events. The respective TROUBLE, ALARM, SUPERVISORY and BUILDING
LEDs flash if at least one of the given types is in the queue.
The CFG-300 LCD service tool shows only the first alarm or trouble. If a trouble happens first
and then an alarm happens, the alarm appears. Any further events change the total number of
events, shown in the right hand corner of the LCD display. The order of priority is alarm,
supervisory, trouble and property and building safety.
11.15.1 Example 1 (detection circuit):
Event 01 of 09, OPEN TRB on initiating circuit Z-01 in the EAST LOBBY ENTRANCE with
process type as VERIFIED ALARM and the event occurred on 2003/02/02 at 18:01TUESDAY.
Configuration with the CFG-300 LCD Service Tool
Figure 53 Detection circuit zone message
11.15.2 Example 2 (indicating circuit):
Event 02 of 09, SHORT TRB on indicating circuit NAC-01 in the EAST WING LOBBY with
process type as SILENCEABLE and the event occurred on 2003/02/02 at 18:01 TUESDAY.
Figure 54 Indicating circuit zone message
Other common messages are described below.
89
Page 90
11.16 AC Power Fail
AC Power Fail
Active 1/ 1
Trb:0x03 Info:0x0004
00:07 SAT 2000-01-01
Trouble Type
EVENT
01 of 01
DATE
TIME
"INFO " Key
Trouble codeTrouble Info
"INFO " Key
Battery Trouble
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0008
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
The AC power fail trouble is generated when the power drops below the UL specified value.
The trouble is restored when the power returns to the normal value.
Figure 55 AC Power Fail
Configuration with the CFG-300 LCD Service Tool
11.17 Battery trouble
The battery trouble is generated when the battery voltage drops below the specified value.
The trouble is restored when the voltage returns to the normal value.
Figure 56 Battery Trouble
90
Page 91
11.18 Ground Fault
"INFO " Key
Ground Fault
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
i
RAU num mismatch
trouble 1/ 1
Trb:0x03 Info:0x0001
11:45 SAT 2003-02-03
Trouble Type
EVENT
01 of 09
DATE
TIME
"INFO " Key
Trouble code
Trouble info
Figure 57 Ground Fault
Note:The trouble code and info is for trained service personnel only.
Configuration with the CFG-300 LCD Service Tool
11.19 Remote Annunciator
Troubles related to the annunciator can have two possibilities: either the main panel and
annunciator failed to communicate with each other, or an un-configured remote annunciator is
responding to the main panel. In both the cases, the following trouble message is displayed:
Figure 58 Remote annunciator mismatch trouble
11.20 Four-wire Smoke Detector Supply
The four-wire smoke detector supply is supervised for shorts. When a short is detected on a
four-wire smoke supply the power is cut off and a trouble message is generated. Press the
SYSTEM RESET button to restore the power the system. If the short is removed, the panel
returns to normal; otherwise the trouble message remains.
91
Page 92
Configuration with the CFG-300 LCD Service Tool
"INFO " Key
4Wire Pwr. Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
i
"INFO " Key
Aux. Power Supply
short 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
Figure 59 Four-wire Power Supply
Note:The trouble code and info is for trained service personnel only.
11.21 Supervised Aux. Supply
The supervised auxiliary supply is supervised for shorts. When a short is detected on
supervised auxiliary supply the power is cut off and a trouble message is generated. Press the
SYSTEM RESET button to restore the power the system. If the short is removed, the panel
returns to normal; otherwise the trouble message remains.
Figure 60 Aux. Power Supply
11.22 City Tie Polarity reversal - PR-300/ Relay module
92
The city tie or polarity reversal module is supervised for open and whether or not the PR-300
is plugged in. The relay module is supervised for whether or not it is plugged in.
If any of the modules are not plugged in, the following trouble message appears:
Page 93
Configuration with the CFG-300 LCD Service Tool
"INFO " Key
CtyTie/RMxxx missing
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
"INFO " Key
City Tie trouble
Active 1/ 1
Trouble Type
EVENT
01 of 01
Trb:0x03 Info:0x0001
00:07 SAT 2000-01-01
DATE
TIME
Trouble codeTrouble Info
Figure 61 City Tie module missing
If there is an open detected on the city tie output, the following trouble message appears:
Figure 62 City Tie trouble
93
Page 94
12.0Appendix A: Compatible Receivers
i
The dialers that are built into select models of the FA-300 Series Fire Alarm Control Panels are
compatible with the following Digital Alarm Communicator Receivers (DACR):
DACR Receiver ModelProtocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved)SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved)SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI approved)SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved)SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved)SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved)SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved)SIA-DCS and Ademco Contact ID
DSC SurGard System III Receiver (ULC, ULI Approved)*SIA Contact ID
DSC SurGard System IV Receiver (ULC, ULI Approved)*SIA Contact ID
Note:* When used with DSC 3G4010 or 3G4010CF Universal Wireless Alarm
System TypeLocal, Auxiliary (using PR-300), Remote Protected
Premises Station (using PR-300 or FA-301-12LDR,
FA-301-12LDW, or FA-301-8LDW) Central Station
Protected Premises (using FA-301-12LDR, FA-30112LDW, or FA-301-8LDW).
Type of ServiceA, M, WF, SS
Type of SignallingNon-Coded
Applicable StandardsNFPA 70 and 72, UL 864 Rev. 9, ULC-S524, ULC-
S527-11, ULC-S559-13
FA-300 LED Series Modules and Annunciators
RM-312/306Relay Adder ModuleMust be connected to a listed power-limited
source of supply.
Contact rating NO / NC / 28VDC per contact / 1A resistive
load max
Current consumptionstandby 0mA, alarm 80mA
ICAC-306Input Class A Converter modulestandby: 0mA / alarm: 0mA
OCAC-304Output Class A Converter Modulestandby: 0mA / alarm: 0mA
OCAC-302Output Class A Converter moduleStandby 0mA / alarm 0mA
SRM-312
Smart Relay Module
Contact rating FormC/ 28VDC per contact / 1A resistive load
Current consumptionstandby 30mA, alarm 140mA
Must be connected to a listed power-limited
source of supply
Use the form below to determine the required secondary power supply (batteries).
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer
to Appendix A for specifications.
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model NumberDescriptionQtyStandby Total Standby Alarm To ta l A lar m
Fire Alarm
Control Panel, 12 Det,
FIXED ELR/ACTIVE ELR
Fire Alarm Control Panel, 12 Det
with UDACT
FIXED ELR/ACTIVE ELR
Fire Alarm
Control Panel, 8 Det
FIXED ELR/ACTIVE ELR
Fire Alarm Control Panel, 8 Det
with UDACT
FIXED ELR/ACTIVE ELR
Det Class A Converter Adder
Module
Sig Class A Converter Adder
Module--4 Circuits
Sig Class A Converter Adder
Module--2 Circuits
Polarity Reversal and City Tie
Module
12 Relay or 6 Relay Adder
Module
X0.164/0.104
X0.164/0.104
X0.136/0.096
X0.136/0.096
X0.000
X0.000
X0.000
X0.050
X0.000
= 0.424/0.364=
= 0.424/0.364=
= 0.366/0.326=
=0.366/0.326=
= 0.000=
= 0.000=
= 0.000=
= 0.300=
= 0.160/0.080=
=0.140=
=0.065=
=0.090=
=0.035=
=* 0.090 = 0.090
Four-Wire Smoke Detectors X
Signal Load (bells, horns, strobes, and etc.)X
Auxiliary Power Supply for Annunciators, etc.
Total currents (Add above currents)STANDBY
==
=
ALARM
(A)(B)
* Assume three Initiating Circuits are in alarm.
' Use 0.084 for five minutes of alarm as a multiplier figure.
Using the Mircom MPD-65P 2-wire photoelectric smoke detector. See Device Compatibility Guide LT1007.
Total Current Requirement:ALARM (B)______ Amp. (Value obtained from column B)
Battery Capacity Requirement:
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [Alarm in Hr.] _____) = (C) ______AH
Total Alarm Current: Must be 6 Amperes or less for FA-300 Series. Indicating Circuits must not to exceed 5 Amperes.
Battery Selection: Multiply (C) by 1.20 to derate battery.
100
=
=
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.