Mircom FA-300, FA-301-12LW, FA-301-12LDW, FA-301-8LDW, FA-301-12LDR Installation And Operation Manual

...
FA-300 Series
LED Fire Alarm Control Panel
Installation and Operation Manual
LT-905 Rev. 11.4 March 2018

Table of Contents

1.0 Industry Canada and FCC Notice 9
1.3 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A. .................................. 9
2.0 Introduction 11
2.1 Overall Features ............................................................................................................ 11
3.0 Conventions 12
3.1 Circuits ........................................................................................................................... 12
3.2 Zone ............................................................................................................................... 12
3.3 Display Points ................................................................................................................ 12
3.4 Wiring Styles .................................................................................................................. 12
4.0 System Components 13
4.1 Main Fire Control Panel ................................................................................................. 13
4.2 Relay Module: 12 Relays ............................................................................................... 14
4.3 Relay Modules: Six Relays ............................................................................................ 14
4.4 Polarity Reversal/City Tie ............................................................................................... 14
4.5 Remote Annunciator ...................................................................................................... 14
4.6 Smart Relay Module ...................................................................................................... 15
4.7 Input Class A converter: Six Circuits .............................................................................. 15
4.8 Output Class A converter: four circuits .......................................................................... 15
4.9 Output Class A converter: two circuits ........................................................................... 15
4.10 Active End-of-Line Resistors .......................................................................................... 16
4.11 RAM-216 Remote Annunciator ...................................................................................... 16
4.12 Additional Fire Alarm System Accessories .................................................................... 16
5.0 Mechanical Installation 17
5.1 Installing the Enclosure .................................................................................................. 17
5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 19
5.3 Installing the Adder Modules .......................................................................................... 20
6.0 Cable and Jumper Connections for Main Board and Adder Modules 21
6.1 Main Fire Alarm Board ................................................................................................... 21
3
Table of Contents
6.2 ICAC-306 Input Class-A Converter Adder Module ......................................................... 22
6.3 OCAC-304/302 Output Class-A Converter Adder Module ............................................. 23
6.4 Relay Adder Modules ..................................................................................................... 23
6.5 Polarity Reversal and City Tie Module (Model PR-300) ................................................ 25
7.0 Field wiring 27
7.1 Main Fire Alarm Board Field Wiring ............................................................................... 27
7.2 Relay Adder Module Wiring .......................................................................................... 31
7.3 Connecting to a 3G4010 Interface Device for Canada .................................................. 32
7.4 Connecting to a 3G4010CF Interface Device outside Canada ...................................... 33
7.5 Polarity Reversal and City Tie Module (PR-300) Wiring ................................................ 34
7.6 Power supply connection ............................................................................................... 35
7.7 Wiring Tables and Information ....................................................................................... 36
7.8 Four-Wire Smoke Power ................................................................................................ 37
7.9 Supervised Auxiliary Power ........................................................................................... 37
7.10 Auxiliary Power .............................................................................................................. 37
8.0 Turning on the Panel 38
8.1 Before Connecting the Power ........................................................................................ 38
8.2 Power-up procedure ....................................................................................................... 38
8.3 Troubleshooting ............................................................................................................. 40
9.0 Indicators, Controls and Operations 41
9.1 Common Indicators ........................................................................................................ 42
9.2 Indicating Circuit Indicators ............................................................................................ 45
9.3 Signal Circuit Indicators ................................................................................................. 47
9.4 Common Controls .......................................................................................................... 47
9.5 Circuit (Zone) Disconnect Buttons ................................................................................. 49
9.6 Common Relays ............................................................................................................. 50
9.7 Circuit Types .................................................................................................................. 50
9.8 Indicating (Signal) Circuit Types .................................................................................... 52
9.9 Evacuation codes (Signal Rates) ................................................................................... 52
9.10 Single Stage Operation .................................................................................................. 53
9.11 Two-stage Operation ...................................................................................................... 54
10.0 Supported Protocols/Devices 56
10.1 Synchronous Strobes ..................................................................................................... 56
10.2 System Sensor’s i3 Devices ........................................................................................... 56
4
Table of Contents
11.0 Configuration with the CFG-300 LCD Service Tool 59
11.1 Accessing Configuration Mode ...................................................................................... 60
11.2 Command Menu ............................................................................................................ 61
11.3 1. FA-300 CONFIG (Command-Menu) .......................................................................... 62
11.4 2. Config Info (Command-Menu ..................................................................................... 72
11.5 3. Set Time (Command-Menu) ...................................................................................... 73
11.6 4. Change password (Command-Menu) ........................................................................ 75
11.7 5. View Event Log (Command-Menu) ............................................................................ 75
11.8 6. Clear Event Log (Command-Menu) ........................................................................... 76
11.9 7. Walk Test (Command-Menu) ..................................................................................... 76
11.10 8. i3 Loop Test (Command-Menu) ................................................................................. 78
11.11 9. Dialer Config (Command-Menu) ................................................................................ 79
11.12 10. Test Dialer (Command-Menu) ................................................................................. 87
11.13 11. Exit (Command-Menu) ............................................................................................. 88
11.14 CFG-300 LCD service tool operation ............................................................................. 88
11.15 Zone messages ............................................................................................................. 89
11.16 AC Power Fail ................................................................................................................ 90
11.17 Battery trouble ................................................................................................................ 90
11.18 Ground Fault .................................................................................................................. 91
11.19 Remote Annunciator ...................................................................................................... 91
11.20 Four-wire Smoke Detector Supply ................................................................................. 91
11.21 Supervised Aux. Supply ................................................................................................. 92
11.22 City Tie Polarity reversal - PR-300/ Relay module ......................................................... 92
12.0 Appendix A: Compatible Receivers 94
13.0 Appendix B: Reporting 95
13.1 Ademco Contact-ID ........................................................................................................ 95
13.2 Security Industries Association SIA-DCS ...................................................................... 96
14.0 Appendix C: Specifications 97
15.0 Appendix D: Power Supply and Battery Calculations 100
16.0 Appendix E: Auxiliary Devices 101
17.0 Warranty and Warning Information 102
5

List of Figures

Figure 1 FA-300 LED Series ........................................................................................................ 13
Figure 2 Box dimensions, surface mount ..................................................................................... 17
Figure 3 Box dimensions, semi-flush mounting and trim ring ....................................................... 18
Figure 4 Flush trim detail (from above) ........................................................................................ 18
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 19
Figure 6 Installation of Adder Modules ......................................................................................... 20
Figure 7 Main Fire Alarm Board cable connector and jumper settings ........................................ 21
Figure 8 ICAC-306 Input Class-A Converter Adder Module ......................................................... 22
Figure 9 OCAC-304/302 Output Class-A Converter Adder Module ............................................. 23
Figure 10 RM-312 twelve relay adder module ............................................................................... 24
Figure 11 RM-312/306 Relay programming ................................................................................... 24
Figure 12 RM-306 six relay adder module ..................................................................................... 25
Figure 13 Polarity reversal and city tie module .............................................................................. 25
Figure 14 Initiating circuit – Class B or Style B wiring .................................................................... 27
Figure 15 Initiating circuit– Class A or Style D wiring ..................................................................... 28
Figure 16 Indicating circuit – Class B or Style Y wiring .................................................................. 29
Figure 17 Indicating circuit –Class A or Style Z wiring ................................................................... 29
Figure 18 Four-wire smoke detector wiring .................................................................................... 30
Figure 19 Dialer wiring ................................................................................................................... 30
Figure 20 Relay per zone (RM-312) Terminal connection ............................................................. 31
Figure 21 Relay per zone (RM-306) Terminal connection ............................................................. 31
Figure 22 Connecting an FA-300 FACP to a 3G4010 Interface Device ........................................ 32
Figure 23 Connecting an FACP to a 3G4010CF Interface Device outside Canada ....................... 33
Figure 24 Polarity reversal and city tie module terminal connection .............................................. 34
Figure 25 Power supply connection ............................................................................................... 35
Figure 26 Battery connections ........................................................................................................ 39
Figure 27 LED indicators and control buttons ................................................................................ 41
Figure 28 Alarm Circuit Indicator .................................................................................................... 45
Figure 29 LAMP TEST ................................................................................................................... 49
Figure 30 Evacuation and Alert Codes ........................................................................................... 53
Figure 31 Open Circuit Trouble ...................................................................................................... 57
Figure 32 Communication Trouble ...............................................................................................
Figure 33 Dirty Device Trouble ....................................................................................................... 57
Figure 34 Out of sensitivity Trouble ................................................................................................ 57
Figure 35 Freeze Trouble ............................................................................................................... 58
Figure 36 FA-300 Configuration ..................................................................................................... 60
Figure 37 Enter passcode .............................................................................................................. 61
Figure 38 Command Menu ............................................................................................................. 61
Figure 39 FA-300 Config menu ...................................................................................................... 62
Figure 40 Feature Config menu ..................................................................................................... 63
Figure 41 The event log ................................................................................................................. 75
Figure 42 Select Log ...................................................................................................................... 76
Figure 43 Clear all the selected logs .............................................................................................. 76
.. 57
6
List of Figures
Figure 44 Logs cleared .................................................................................................................. 76
Figure 45 Walk test confirmation .................................................................................................... 76
Figure 46 Walk test zones .............................................................................................................. 77
Figure 47 Walk test active .............................................................................................................. 77
Figure 48 i3 loop test confirmation ................................................................................................. 78
Figure 49 i3 test zones ................................................................................................................... 78
Figure 50 i3 test not ready ............................................................................................................. 78
Figure 51 The selected zone is not i3 type .................................................................................... 78
Figure 52 Dialer Config menu ........................................................................................................ 79
Figure 53 Detection circuit zone message ..................................................................................... 89
Figure 54 Indicating circuit zone message ..................................................................................... 89
Figure 55 AC Power Fail ................................................................................................................ 90
Figure 56 Battery Trouble .............................................................................................................. 90
Figure 57 Ground Fault .................................................................................................................. 91
Figure 58 Remote annunciator mismatch trouble .......................................................................... 91
Figure 59 Four-wire Power Supply ................................................................................................. 92
Figure 60 Aux. Power Supply ......................................................................................................... 92
Figure 61 City Tie module missing ................................................................................................. 93
Figure 62 City Tie trouble ............................................................................................................... 93
7

List of Tables

Table 1 FA-300 LED Series Comparison Chart .......................................................................... 13
Table 2 Power Supply Ratings .................................................................................................... 35
Table 3 Initiating Circuit Wiring ................................................................................................... 36
Table 4 Indicating Circuit Wiring ................................................................................................. 36
Table 5 RS-485 Wiring to Annunciators and other Devices ........................................................ 37
Table 6 Alarm Circuit Indicators .................................................................................................. 45
Table 7 Supervisory Circuit Indicators ........................................................................................ 45
Table 8 Property and Building Safety Indicators ......................................................................... 46
Table 9 Trouble-Only Circuit Indicators ....................................................................................... 47
Table 10 Signal Circuit Indicators ................................................................................................. 47
Table 11 i3 Smoke Detector LEDs ................................................................................................ 58
Table 12 Settings permitted in CAN/ULCS527 ............................................................................. 59
Table 13 Settings permitted in UL864 ........................................................................................... 59
Table 14 Feature Config menu ..................................................................................................... 63
Table 15 i3 Detector Statuses ....................................................................................................... 79
Table 16 FA-300 LED Series Specifications ................................................................................. 97
Table 17 FA-300 LED System Modules and Annunciators ........................................................... 98
8

1.0 Industry Canada and FCC Notice

!
i

1.1 Notice for all FA-300 Series Built-In UDACTs Sold in Canada

Mircom's F A-300 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527-11 (Standard for Control Units for Fire Alarm Systems) and CAN/ULC-S561-13 (Standard for Installation and Services for Fire Signal Receiving Centres and Systems). These Communicators should be installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction (AHJ).

1.2 Industry Canada Notice

Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper operation and for protection.
Caution: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or electrician, as appropriate

1.3 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A.

Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
Mircom's FA-300 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective Signalling Systems). These Communicators comply with the National Fire Protection Association (NFPA) performance requirements for DACTs and should be installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These Communicators should be installed in accordance with this manual; the National Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
9

1.3.1 FCC Notice

This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the telco transformer of this equipment is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company. This equipment is capable of seizing the line. This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (central office implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect your service or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence number (REN); both of these items are listed on the equipment label. The sum of all of the REN’s on your telephone lines should be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable on a given line.
Industry Canada and FCC Notice
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they should be performed by Mircom Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page of this document.
10

2.0 Introduction

i
Mircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP)-based
fire panel. The FA-300 provides a maximum of 12 supervised Class B or A (Style B or D) Initiating circuits, and maximum four supervised Class B or A (Style Y or Z) indicating circuits. All circuits are supervised for opens and ground faults, and indicating circuits are supervised for shorts. Optional modules include Relay, Polarity Reversal and City Tie and Class A Converters for initiating and indicating circuits. Semi-flush or surface mountable enclosures
can be used for retrofits and on new installations.
Note: Installation of the FA-300 series fire alarm control panel should be in accordance
with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ).

2.1 Overall Features

Basic unit has 12 Class B (Style B) initiating circuits, which may be configured as Class
A (Style D) using input Class A converter adder modules. Each initiating circuit can be configured as Alarm, Verified Alarm, Water flow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Property and Building Safety, or Trouble-Only circuits. There are two LEDs per circuit, one for Trouble (amber), and one dual color (amber/red) LED for Supervisory (amber) and Alarm (red).
Basic unit has four Power Limited Class B (Style Y) indicating circuits with individual
trouble indicators. Each indicating circuit may be configured as Class A (Style Z) using output Class A converter adder module. Each indicating circuit may be configured as Silenceable signal, non Silenceable signal, Silenceable strobe, non Silenceable strobe. The audible signal may be Steady, Temporal Code, California Code, or March Time.
Two Stage operation available.
A pushbutton associated with each initiating and indicating circuit can individually
disconnect the circuit.
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For UL installations, disable the auto signal silence timer.
Subsequent Alarm, Supervisory, and Trouble operation.
Four-wire resettable smoke power supply 300 mA maximum.
Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
RS-485 Interface for LCD Annunciators, RA-1000 Series Remote Multiplex
Annunciators and Smart relay adder.
Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.
Extensive transient protection.
With or without built-in UDACT (Digital Alarm Communicator Transmitter).
Easy configuration of the panel and built-in UDACT using LCD service tool (CFG-300).
Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
Laptop programmer for direct configuration changing and log checking.
11

3.0 Conventions

3.1 Circuits

Refers to an actual electrical interface for Initiating (Detection) and Indicating (Signal or NAC) or Relays.

3.2 Zone

Is a logical concept for a Fire Alarm Protected Area, and consists of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual circuit refers
only to a physical electrical loop.

3.3 Display Points

There is a display point associated with every initiating and indicating circuit of the FA-300 LED Series fire panel. For an initiating circuit there are 2 LEDs for every display point: one single color (amber) and one dual color (red/amber). For an indicating circuit there is only one LED: one single color (amber), for every display point.

3.4 Wiring Styles

Initiating and indicating circuits are Class B (style B and Y).
Changing the initiating circuits to Class A requires an ICAC-306 adder board which converts six initiating zones from Class B (style B) circuits to Class A (style D). This is done without decreasing the number of circuits, which remains the same as in Class B (style B).
Changing the indicating circuits to Class A requires an OCAC-304 adder board which converts four indicating zones from Class B (style Y) circuits to Class A (style Z) or an OCAC-302 adder board which converts two indicating zones from Class B (style Y) circuits to Class A (style Z).
12

4.0 System Components

4.1 Main Fire Control Panel

Figure 1 FA-300 LED Series
All FA-300 LED Series Panels have the following features:
LED Display.
Two six zone ICAC-306 Input Class A Converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
One OCAC-304 Output Class A Converter adder module may be used for Class A
(Style Z) wiring of the Indicating circuits.
Contain Common Alarm, Common Supervisory & Common Trouble Relays, Auxiliary
Alarm Relay (disconnectable), an RS-485 Interface for Remote Annunciators and a Resettable Four Wire Smoke Detector Power Supply.
Used with Mircom BAT-12V12A (12 Amp-hour) batteries (two required).
Table 1 FA-300 LED Series Comparison Chart
Model # of zones # of initiating
circuits
FA-301-12LDW 12 12 yes white FA-301-12LDR 12 12 yes red FA-301-12LW 12 12 no white FA-301-12LR 12 12 no red FA-301-8LDW 88 yes white FA-301-8LW 88 no white
On board Dialer Door Color
FA-301-8LDR 88 yes red FA-301-8LR 88 no red
13

4.2 Relay Module: 12 Relays

NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NC NO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
Mounting hole for
#6-32 screws
Mounting hole for #6-32 screws
FA-300 SERIES
Remote Annunciator
SYSTEM RESET
SIGNAL SILENCE
FIRE
DRILL
BUZZER SILENCE
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CP U FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
Advanced Li fe Safety Sol utions
System Components
Model Description

4.3 Relay Modules: Six Relays

Model Description
RM-306 Six relay adder module

4.4 Polarity Reversal/City Tie

Model Description
RM-312
12 relay adder module
14
PR-300 Polarity Reversal and/or City Tie Module

4.5 Remote Annunciator

Model Description
RAM-300LCDW
RAM-300LCDR
Remote Annunciator module, LCD display, white painted box
Remote Annunciator Module, LCD display, red painted box

4.6 Smart Relay Module

REMOTE RELAY
Advanced Life Safety Sol utions
FR-320 SERIES
BLK RED
BLK REDBLK REDBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- DET6 OUT+
- DET1 RET+- DET2 RET+- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RET+
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG 2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG 4 RET+
BLK RED
BLK RED
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
Model Description
SRM-312W Smart Relay Module (12 relays) with white enclosure
SRM-312R Smart Relay Module (12 relays) with red enclosure

4.7 Input Class A converter: Six Circuits

Model Description
System Components
ICAC-306
Input Class A converter Module (six circuits). This
module has built in Active End-of-Line resistors.

4.8 Output Class A converter: four circuits

Model Description
OCAC-304 Output Class A converter module (four circuits)

4.9 Output Class A converter: two circuits

Model Description
OCAC-302 Output Class A converter module (two circuits)
15

4.10 Active End-of-Line Resistors

BLACK
RED
A.C.ONCOMMON
TROUBLE
SIGNAL SILEBCE
BUZZER SILENCE
SIGNAL SILENCE
LAMP TEST
SYSTEM RESET
SWITCH ENABLE
FIRE ALARM ANNUNCIATOR
The ELRX-300 are power-saving End-of-Line resistors that eliminate the need for an additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
Model Description
ELRX-300 Active end-of-line resistor without plate
ELRX-300R Active end-of-line resistor with end-of-line red plate

4.11 RAM-216 Remote Annunciator

Model Description
RAM-216 16 Zone remote annunciator
System Components
RAM-208 8 Zone remote annunciator

4.12 Additional Fire Alarm System Accessories

RAM-208 Eight Zone Remote Annunciator ULC and ULI Approved RTI-1 Remote Trouble Indicator ULC and ULI Approved MP-300 End-of-line resistor plate, 3.9K ohm ULC and ULI Approved MP-300R End-of-line resistor plate, red ULC Approved BC-160 External Battery Cabinet ULC and ULI Approved RAM-1016TZDS Remote Annunciator with 16 bi-
coloured LEDs (DS model has 16 bi-coloured LEDs and 16 trouble LEDs)
RAM -1032TZDS Remote Annunciator with 32 bi-
coloured LEDs (DS model has 16 bi-coloured LEDs and 32 trouble LEDs)
PCS-100 Passive Communications Interface
Board
UDACT-300A Universal Communicator ULC and ULI Approved BK-RAM Deadfront bracket (ULC
requirement for RAM-1016 series and RAM-1032 series)
ULC and ULI Approved
ULC and ULI Approved
ULC Approved
ULC Approved
16

5.0 Mechanical Inst allation

11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole

5.1 Installing the Enclosure

Install the FA-300 Series Fire Alarm Panel enclosure as shown below for the twelve-, eight-, and six-zone models. Mount enclosure surface mount using the four mounting holes, as shown and the screws provided.
Figure 2 Box dimensions, surface mount
The backbox may be semi-flush mounted using the trim ring model FA-UNIV-TRB (BLACK), see Figure 3. Remove the door (also disconnect the ground strap), the dead front and semi-
17
Mechanical Installation
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" i s the max imum depth for semi -flus h mounting usi ng the flush tr im ri ng
1" is the mi nimum depth
above the wall required for semi- flus h mounting usi ng the flus h trim ri ng
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 300 backbox .
PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL S TUD
BACKBOX
flush mount the backbox into the wall. Peel the adhesive cover from the trim ring and stick to the wall surface around the backbox, after wall is finished.
Figure 3 Box dimensions, semi-flush mounting and trim ring
Figure 4 shows a cross-section of the semi-flush mounted enclosure and the trim ring. Make
sure to allow a minimum depth of 1” above the wall surface for proper door opening.
Figure 4 Flush trim detail (from above)
18
Mechanical Installation
26.0 "
14.5 "
4.2 "
External Dimensions
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View

5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation

The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a built-in trim ring.
Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26” Distance between horizontal mounting screws 12” Distance between vertical mounting screws 23.5” Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
Mounting Dimensions
12.0 "
23.5 "
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions
19

5.3 Installing the Adder Modules

Fuse and AC wiring terminal
S-+NC NOCNC NOCNC NOCNC NOC
+-+-COM(+)
COM(-)
TRLTRB RTRT
RTRT
RES CO RE S C O
LINE1LINE2
WALK TEST
REMOTE TROUBLE
CPU FAULT
GROUND FAULT
SIGNAL SILENCE
FIRE DRILL
AUTOMATIC ALARM SIGNAL CANCEL
GENERAL ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP TEST
ALM/SUP/TBL/BLDG
AUDIBLE SIL
A.C.
ON
COMMON ALARM
COMMON
SUPV
COMMON TROUBLE
BATTERY TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCONNECT
ZONE-7
DISCONNECT
ZONE-9
DISCONNECT
ZONE-11
DISCONNECT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
ZONE-12
DISCONNECT
NAC-1
DISCONNECT
NAC-3
DISCONNECT
NAC-2
DISCONNECT
NAC-4
DISCONNECT
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DE T 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SI G 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR -300 MOD ULE
TO R M-312/RM-306 RELAY
MODULE
RS-
485
AUX. RELAYALARM
RELAY
SUP E RVIS O RY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-W I RE
SUPPLY
UNFILTERED
RTI
PORT
P1P
2
P3P
4
+
_
BATTERY SEC. TX
BATTERY BATTERY
CLASS -A conve rter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A conve rter board for indicating circui ts OCAC-304
(4 circuits )
Reverse po larity a nd city tie modu le PR- 300. Mounted on hex spacer with two screws provide d
Relay Module RM-306 Mount relay module on the left si de u sing tw o scre ws provided .
Relay M odule RM-312 centre under main fire alarm board using three screws pro vided .
Transf orme r
Fuse and AC wirung terminal
MAIN FIR E PANEL BOAR D
Fuse and AC wiring terminal
FA-300 Series Fire Alarm panels come pre-assembled with all components and boards except
for Adder Modules. Module installation locations are shown in Figure 6. Refer to Figure 7 on
the next page for jumper and DIP switch settings and see 7.7 Wiring Tables and Information on page 36 for wiring specifications.
Mechanical Installation
20
Figure 6 Installation of Adder Modules
S-+NC NOCNC NOCNC NOCNC NOC
+-+-
COM(+)
CO M(- )
TRLTRB RTRT
RTRT
RES CO RES CO
LINE1LINE2
WALK TEST
REMOTE TROUBLE
CPU FAIL
GROUND
FAULT
SIGNAL SILENCE
FIRE
DRILL
GENERAL
ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP TEST
ALM/SUP/TBL/
BLDG AUDIBLE SIL
A.C.
ON
COMMO N
ALARM
COMMO N
SUPV
COMMO N TROUBLE
BATTERY TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCON NECT
ZONE-7
DISCON NECT
ZONE-9
DISCON NECT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
NAC-1
DISCONNECT
NAC-2
DISCONNECT
JW3 JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SIG 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 M ODULE
TO RM-312/ RM-306 RELAY MODULE
RS-4 85AUX. RELAYAL ARM REL AY
SUPERVISO RY
RELAY
TROU BL E
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UNFIL TERED
RTI
PORT
P1 P2P3 P4
+
_
XT .CESYRETTAB
Telephone line #1
Telephone line #2
RS-485 for annunciators
Auxiliary Alarm Relay
Common Alarm Relay
Common Supervisory Relay
Common Trouble Rel ay
Auxiliary Supply
4-wire Supply
Unfiltered 24V supply
connect to Remote trouble indicator
Initiating zone 1 TO 12
Indicating zone 1 TO 4
Connect to RM-312/ RM306 Relay module
Connect to PR-300
To Battery
To secondary of AC
transformer
JW2 - ON- when RM312/RM306 not connected
JW1 - ON- when PR-300 not connected
JW3- Removed all the time
JW6-Open all the time
JW4 -Normally open
JW7
JW7 -Normally open
For front panel programming use CFG-300 configuration tool not UL- 864 or ULC-S527 listed. Please refer to Document LT-922 for details
For PC pr ogramming use UIMA interface module not UL-864 or ULC-S 527 listed . Plea se refer to Document LT-929 for details
AUTOMATIC ALARM SIGNAL CANCEL
ZONE-11
DISCONNECT
ZONE-12
DISCONNECT
NAC-3
DISCONNECT
NAC-4
DISCONNECT
[
[
[
JW6 - Open all the time
JW4 - Normally open
JW5-Normally Open
[
Trouble Relay LED
6.0 Cable and Jumper Connections for
Main Board and Adder Modules

6.1 Main Fire Alarm Board

Figure 7 Main Fire Alarm Board cable connector and jumper settings
21
Cable and Jumper Connections for Main Board and Adder Modules
BLK RED
BLK R E DBLK R E DBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 O UT+- D ET4 OUT+- DET 5 OUT+- DET6 OUT+
- DET1 RET+- D ET2 R ET+- DET3 R ET+- DET4 RET+- DE T5 RET+- DET6 RET+
mounting hol e for #6-32 scr ews
All these pi ns comes wit h red a nd black w ire s w h i ch are con ne cted to the detection circuit on the mai n fire alarm board. Red is pos i ti ve and bl ack i s negative
ICAC-306
mounting hol e for #6-32 screws

6.1.1 Connectors and Jumpers on the Main Fire Alarm Board

P5
P6
JW1
Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects
here. Otherwise not used.
Cable from connector P1 of the RM-312 or RM-306 Relay Adder Module
connects here. Otherwise not used.
On the Main Fire Alarm Module, this jumper must be removed if a PR-300
Polarity Reversal and City Tie Module is installed.
JW2 Remove this jumper if an RM-312 or RM-306 Relay Adder Module is used.
JW3 Removed all the time.
Normally open. Place jumper here and power down (AC and Batteries) then
JW4
power back to revert back to default password. Once the system has reset,
REMOVE the jumper from the pins at JW4. Leave normally open.
JW5
Normally open to BLOCK remote converter module or a CFG-300 Configuration Tool. Place jumper here to ALLOW
configuration via modem, PC with a UIMA
any type of configuration.
JW6 Not used, open.
JW7 Not used, open.

6.2 ICAC-306 Input Class-A Converter Adder Module

Figure 8 ICAC-306 Input Class-A Converter Adder Module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
22
Cable and Jumper Connections for Main Board and Adder Modules
- SIG1 OUT+- SIG2 OUT+
- SIG1 R ET+- SIG2 RET+
BLK RED
BLK RED
mounting ho l e for #6-32 screws
OCAC-302
mounting ho l e for #6-32 screws
- SIG1 O U T+- SIG2 OU T+
- SIG1 RET+- SIG2 R ET+
BLK RED
BL K RE D
- SIG3 OU T+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BL K RE D
mounting hol e for #6-32 scr ews
OCAC-304
mounting ho le for #6-32 scr ews
Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the positive and negative terminals marked DET OUT and the circuit return wires are brought back to the converter module to positive and negative terminals marked DET RET.
To convert all 12 initiating circuits of a FA-312 Fire Alarm Panel, two of these ICAC-306 Input Class A Converter Adder Modules are required.

6.3 OCAC-304/302 Output Class-A Converter Adder Module

6.4 Relay Adder Modules

6.4.1 RM-312 Twelve-Relay Adder Module

Figure 9 OCAC-304/302 Output Class-A Converter Adder Module
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the Class A converter module to the positive and negative terminals of Indicating circuit 1 on the Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then wired back to the SIGNAL RET positive and negative.
The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-312 are used to configure the relays. The
23
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
RELAY 8CREL AY 9
NO/NC C
RELAY 1 0
NO/NC C
RELAY 1 1
NO/NC C
RELAY 1 2
NO/NC NO/NC
Three mounting holes for #6-32 screws
INDI VIDUAL GREEN RELAY STAT US LEDs
Connect to P6 on the main fire alarm board
NO NC
SA
Z1
1&2
NO/ NC C
RELAY 1
NC/NO CONNECTION NC: terminal provides normally closed contacts NO: terminal provides normally open contacts Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection then the relay is not connected to the terminals
SUPV/ALARM SELECTION S: Relay turns ON when common
supervisory is active A: Relay turns ON when common alarm is active Defa ult: No jumper installed, conn ecte d o n ce n ter p in o nl y
ZONE JUMPER inst alled: turns ON relay when the zone
(1) is act ive removed: does not turn ON the relay when zone (1) i s a cti ve
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE jumper installed: this relay 1 works in
conjunction w i t h r el ay 2 jumper removed: relay 1 does not operate with the adjacent relay 2 chaining example: if jumper is installed on 1&2 and 2&3 then all the three relays
will be ON if any one of relays 1,2 and 3 is active Default: No jumper installed, connected on one pin only
NO/NC C
RELAY 12
RELAY
LED (GREEN)
i
jumpers located below the relays are used to select either normally open contacts or normally closed contacts.
Figure 10 RM-312 twelve relay adder module
P1 Cable from RM-312 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.4.2 Programming the relays

24
A typical relay circuit is shown in Figure 11 with the jumper locations and descriptions.
Figure 11 RM-312/306 Relay programming
Note: Relay programming should be done before installing the board.
Cable and Jumper Connections for Main Board and Adder Modules
NO/NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
mounting hol e for #6-32 screws
mounting hol e for #6-32 scr ews
INDIVIDUAL GREEN RELAY STAT US LEDs
Connect to P 6 on the main fire alarm board
i

6.4.3 RM-306 Six Relay Adder Module

Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-306 are used to configure the relays. The jumpers located below the relays are used to select either normally open contacts or normally closed contacts.
Figure 12 RM-306 six relay adder module
P1 Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.4.4 Programming the relays

See explanation in Figure 11.
Note: Relay programming should be done before installing the board.

6.5 Polarity Reversal and City Tie Module (Model PR-300)

Mounting hole for
#6-32 screws
P1 P2
Mounting hole for #6-32 screws
+ | - + | - + | -
CITY
TIE
REVERSAL
POLARITY
ALARM
REVERSAL
POLARITY
SUPV
JW4
Figure 13 Polarity reversal and city tie module
The following hardware configuration must be performed before installing the PR-300.
25

6.5.1 PR-300 jumper settings

Cable and Jumper Connections for Main Board and Adder Modules
P1 P2 & JW4
Cable connects to P5 on the Main Board
Not used. Jumper JW4 remains on board.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active. This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals resound and the City Tie Box is retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0 to 3 hours if this is the only system trouble.
26

7.0 Field wiring

!
+
-
STYLE B WIRING
STYLE B WIRING
INITIATING CIRCUIT #1
INITIATING CIRCUIT #2
INITIATING CIRCUIT - 1 ALARM ZONE
INITIATING CIRCUIT - 2 SUPERVISORY ZONE
ION SMOKE DETECTOR
PHOTO SMOKE DETECTOR
HEAT DETECTOR
PULL STATION
3.9K 1/2 WATT ELR
SUPERVISORY
FIRE ALARM MAIN BOARD
+
-
DET 1DET 2
NOTE: IF ACTIVE END OF LINE RESISTORS ARE USED, THEY MUST BE USED ON ALL INITIATING CIRCUITS.
i

7.1 Main Fire Alarm Board Field Wiring

Wire devices to the terminals as shown in the figures that follow. Refer to the Wiring Tables for
wire gauges and to Appendix A for specifications.
Caution: Do not exceed power supply ratings.

7.1.1 Initiating Circuit Wiring Class B

Wiring diagrams for the initiating circuits are shown below. The panel supports Class B (Style B) and Class A (Style D) for the initiating circuits. The initiating circuits are supervised by a
3.9K End-of-Line Resistor or for power saving an Active-End-of-Line.
Figure 14 Initiating circuit – Class B or Sty le B wiring
Note: Depending on configuration, End-of-Line Resistors on initiating circuits must be
all 3.9K ohm resistors or all Active End-of-Line resistors.
27

7.1.2 Initiating Circuit Wiring Class A

+
-
STYLE D WIRING
STYLE D WIRING
INITIATING CIRCUIT # 1
INITIATING CIRCUIT # 2
INITIATING CIRCUIT - 1 ALARM ZONE
INITIATING CIRCUIT - 2 SUPERVI SORY ZONE
ION SMOKE DETECTOR
PHOTO SMOKE DETECTOR
HEAT DETECTOR
PULL STAT ION
SUPER VISOR Y
4 MORE INITIATING CIRCUITS NOT S HO WN
DCAC-306 CLASS A
CONVERTER MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- DE T1
OUT+
- DET2
OUT+
- DET1 RET+- DE T 2 R E T +
+
-
DET 1DET 2
ICAC
i
Field wiring

7.1.3 Indicating Circuit Wiring

Figure 15 Initiating circuit– Class A or Style D wiring
The FA-300 Series Fire Alarm supports Class B (Style Y) and Class A (Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line resistor. Each indicating
circuit provides up to 1.7 A, 5 A maximum total if no auxiliaries are used.
Note: An Active End-of-Line resistor CANNOT be used with any indicating circuits.
Always use 3.9K End of Line resistors for indicating circuits.
28
Field wiring
- SIG 1 +
STYLE Y WIRING
STYLE Y WIRING
INDICATING CIRCUIT - 1
INDICATING CIRCUIT - 2
BELL STROBE 3.9K 1/2 WATT ELR
INDICATING CIRCUIT #1
INDICATING CIRCUIT #2
HORN
FIRE ALARM MAIN BOARD
- SIG 2 +
BELL
STROBE
HORN
+
-
STYLE Z WIRING
STYLE Z WIRING
INDICA TING CIRCUIT #1
INDICA TING CIRCUIT #2
INDICATING CIRCUIT 1
INDICATING CIRCUIT 2
2 MORE INDICATING CIRCU ITS NOT SHOWN
OCAC-304 CLASS A
CONVE RTE R MODULE
FIRE ALARM MAIN BOARD
BLK RED
BLK RED
- S IG 1 OU T+- SIG2 O UT+
- SIG1 RET+- S IG2 RET+
+
-
SIG 1SIG 2
Figure 16 Indicating circuit – Class B or Style Y wiring
Figure 17 Indicating circuit –Class A or Style Z wiring
29

7.1.4 Four Wire Smoke Detector Wiring

POWER
DETECTION
++
++
--
--
1
4
2
3
5
6
TO INITIATING
CIRCUIT
RESETTABLE 4-WIR E SMOKE DETECTOR POWER SUPPLY 22VDC, 200mA MAX. CURRENT - 300mA MAX. RIPPLE VOL. 5mV (POWER LIMITED)
4-WIRE DETECTION DEVICE
END OF LINE RELAY LISTED S3403 MODEL A77-716B MANUFACTURED BY SYSTEM SENSOR
+
-
4-WIRE
SUPPLY
3.9K 1/2 W ATT ELR
LEGEND
NOTES
ALL POWER LIMITED CIRCUITS MUST USE TYPE FPL, FPLR, OR FPLP POWER LIMITED CABLE
FIRE ALARM MAIN BOARD
TIPTIP RINGRING
premi s e t el ephone
IF permitted
TIPTIP RINGRING
LINE-1
LINE-2
1
23
4
8
5
76
Public switch
Telephone company
wiring
TIP
RING
TIP
RING
RJ31X
BROWN
GREY
GREEN
RED
COCO RESRES
Line 2 is Wired as shown for Line 1
FIRE ALARM MAIN BO AR D
Field wiring

7.1.5 Dialer Wiring

30
Figure 18 Four-wire smoke detector wiring
If you have Fire Alarm Panel Models FA-301-12LDW, FA-301-12LDR, and FA-301-8LDW there is a dialer on board and terminals marked Line 1 and Line 2 must be wired as shown in Figure 19 below.
Figure 19 Dialer wiring
Loading...
+ 76 hidden pages