Table 11 SIA Event Codes ............................................................................................................ 83
Table 12 FA-300 LCD Series Specifications ................................................................................. 84
Table 13 FA-300 LCD System Modules and Annunciators ........................................................... 85
8
1.0Industry Canada and FCC Notice
!
i
1.1Notice for all FA-300 Series Built-In UDACTs Sold in Canada
Mircom's FA-300 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units for Fire
Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems
and Services). These Communicators should be installed in accordance with this manual; the
Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction
(AHJ).
1.1.1 Industry Canada Notice
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
Caution:Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate.
1.1.2 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A.
Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a
decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is
separately shown on the label.
Mircom's FA-300 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for DACTs and should be installed in
accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
9
1.1.3 FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request
information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number and the
ringer equivalence number (REN); both of these items are listed on the equipment label. The
sum of all of the REN’s on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.
Industry Canada and FCC Notice
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.
10
2.0Introduction
i
Mircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP) based
fire panel. The FA-300 provides a maximum of 12 supervised Class B or A (style B or D)
Initiating circuits, and maximum of four supervised Class B or A (Style Y or Z) indicating
circuits. All circuits are supervised for opens and ground faults, and indicating circuits are
supervised for shorts. Optional modules include relay, polarity reversal and city tie and Class A
Converters for initiating and indicating circuits. Semi-flush or surface mountable backboxes
can be used for retrofits and on new installations.
Note:Installation of the FA-300 series fire alarm control panel should be in accordance
with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm
System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance
subject to the Local Authority Having Jurisdiction (AHJ).
2.1 Overall Features
•The basic unit has six Class B (Style B) initiating circuits, which may be configured as
Class A (Style D) using input Class A converter adder module. Each initiating circuit can
be configured as alarm, verified alarm, water flow alarm, sprinkler alarm, latching or
non-latching supervisory, monitor or trouble circuits.
•The basic unit has two power limited Class B (Style Y) indicating circuits. Each
indicating circuit may be configured as Class A (Style Z) using an output Class A
converter adder module. Each indicating circuit may be configured as silenceable
signal, non-silenceable signal, silenceable strobe, non-silenceable strobe. The audible
signal may be Steady, Temporal Code, California Code, or March Time.
•Each initiating and indicating circuit can be individually disconnected via the keypad and
LCD display with password access.
•Configurable signal silence inhibit, auto signal silence, and one-man walk test.
•Four-wire resettable smoke power supply 300 mA maximum.
•Relay contacts for common alarm, common supervisory and common trouble all non-
disconnect-able and auxiliary alarm relay (disconnectable).
•RS-485 interface for RA-1000 series remote multiplex Annunciators, LCD Annunciators
and smart relay adder.
•Optional modules for additional relay circuits, city tie and polarity reversal signaling.
•Extensive transient protection.
•With or without built-in UDACT (Digital Alarm Communicator Transmitter).
•Easy configuration of the panel using front LCD display and keypad.
•Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
•Laptop programmer for direct configuration changing and log checking.
11
3.0Conventions
3.1 Circuits
Refers to an actual electrical interface for initiating (detection) and indicating (signal or NAC)
or relays
3.2 Zone
Is a logical concept for a Fire Alarm Protected Area, and consists of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual circuit refers
only to a physical electrical loop.
3.3 Events
There are events associated with every initiating, indicating and common circuit of the fire
panel displayed via the LCD.
3.4 Wiring Styles
Initiating and indicating circuits are Class B (Style B and Y).
Changing the initiating circuits to Class A requires an ICAC-306 adder board which will convert
six initiating zones from Class B (Style B) circuits to Class A (Style D). This is done without
decreasing the number of circuits, which remains the same as in Class B (Style B).
Changing the indicating circuits to Class A requires an OCAC-304 adder board which will
convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z) or an OCAC302 adder board which will convert two indicating zones from Class B (Style Y) circuits to
Class A (Style Z).
12
4.0System Components
4.1Main Fire Control Panel
Figure 1 FA-300 LCD
All FA-300 LCD series panels have the following features:
•LCD display
•Two six-zone ICAC-306 Input Class A converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
•One OCAC-304 Output Class A converter adder module may be used for Class A
(Style Z) wiring of the indicating circuits.
•Common alarm, common supervisory and common trouble relays, auxiliary alarm relay
(disconnectable), an RS-485 interface for Remote Annunciators and a resettable four
wire smoke detector power supply.
•Used with BA-110 (10 Ah) (Sota Enertech model SA12120) batteries (two required).
Table 1 FA-300 LCD Series Comparison Chart
ModelNumber of
zones
FA-300-6DDR66yred
FA-300-6DR66nred
FA-301-12DDR1212yred
Number of
initiating
circuits
On board DialerDoor Color
FA-300-6DDR-CG
Marine Fire Alarm
Control Unit
66yred
13
4.2Relay Module: 12 Relays
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NCNO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
FA-300 SERIES
Remote Annunciator
SYSTEM
RESET
SIGNAL
SILENCE
FIRE
DRILL
BUZZER
SILENCE
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
Advanced Li fe Safety Sol utions
System Components
ModelDescription
4.3Relay Modules: Six Relays
ModelDescription
RM-306Six relay adder module
4.4Polarity reversal/city tie
ModelDescription
RM-312
12 relay adder
module
14
4.5Remote Annunciator
PR-300Polarity reversal and/or city tie module
ModelDescription
RAM-300LCDW
RAM-300LCDR
Remote annunciator module, LCD display, white
painted box
Remote annunciator module, LCD display, red
painted box
SRM-312WSmart relay module (12 relays) with white enclosure
SRM-312RSmart relay module (12 relays) with red enclosure
4.7Input Class A converter: Six Circuits
ModelDescription
System Components
ICAC-306
Input Class A converter module (six circuits). This
module has built in active end-of-line resistors.
4.8Output Class A converter: Four Circuits
ModelDescription
OCAC-304Output Class A converter module (four circuits)
4.9Output Class A converter: Two Circuits
ModelDescription
OCAC-302Output Class A converter module (two circuits)
15
4.10 Active end-of-line resistor
BLACK
RED
A.C.ONCOMMON
TROUBLE
SIGNAL
SILEBCE
BUZZER
SILENCE
SIGNAL
SILENCE
LAMP
TEST
SYSTEM
RESET
SWITCH
ENABLE
FIRE ALARM
ANNUNCIATOR
The ELRX-300 are power-saving end-of-line resistors that eliminate the need for an additional
battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
ModelDescription
ELRX-300Active end-of-line resistor without plate
ELRX-300RActive end-of-line resistor with end-of-line red plate
4.11RAM-216 Remote Annunciator
ModelDescription
RAM-21616 zone remote annunciator
System Components
4.12 Additional Fire Alarm System Accessories
RAM-208Eight zone remote annunciator(ULC and ULI approved)
RTI-1Remote trouble indicator(ULC and ULI approved)
BC-160External battery cabinet(ULC and ULI approved)
(ULC and ULI approved)
16
5.0Mechanical Installation
11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole
5.1Installing the Enclosure
Install the FA-300 series fire alarm panel enclosure as shown below for the 12 zone, eight
zone, and six zone models. Mount enclosure surface mount using the four mounting holes, as
shown and the screws provided.
Figure 2 Enclosure dimensions, surface mount
The enclosure may be semi-flush mounted using the trim ring model FA-UNIV-TRB (BLACK),
see Figure 3. Remove the door (also disconnect the ground strap), the dead front and semi-
17
Mechanical Installation
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" i s the max imum
depth for semi -flus h
mounting usi ng the
flush tr im ri ng
1" is the mi nimum depth
above the wall required for
semi- flus h mounting usi ng the
flus h trim ri ng
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 300 backbox .
PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL STUD
BACKBOX
flush mount the enclosure into the wall. Peel the adhesive cover from the trim ring and stick to
the wall surface around the enclosure, after the wall is finished.
Figure 3 Enclosuredimensions, semi-flush mounting and trim ring
Figure 4 shows a cross-section of the semi-flush mounted enclosure and the trim ring. Make sure to allow
a minimum depth of 1” above the wall surface for proper door opening.
Figure 4 Flush trim detail (from above)
18
Mechanical Installation
26.0 "
14.5 "
4.2 "
External Dimensions
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View
5.2BBX-1024DS and BBX-1024DSR Mechanical Installation
The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a
built-in trim ring.
Dimensions of enclosure (minus built-in trim ring)14.5” x 4.2” x 26”
Distance between horizontal mounting screws12”
Distance between vertical mounting screws23.5”
Complete dimensions of enclosures16.3” x 5.5” x 27.5”
Mounting Dimensions
12.0 "
23.5 "
Figure 5 BBX-1024DS and BBX-1024DSR installation instructions and dimensions
19
5.3Installing the Adder Modules
S-+NCN OCNCNOCNCNOCNCNOC
+-+-COM(+)
COM(-)
TRLTRBRTRT RTR T
RESCORESCO
LINE1LINE2
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DE T 5DET 6DET 7DE T 8DET 9DET 10DET 11DET 12SI G 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 MODULE
TO RM -312/RM-306 RELAY
MODULE
RS-
485
AUX. RELA YALARM
RELAY
SUP E RVIS O R Y
RELAY
TROU BLE
RELAY
AUX
SUPPLY
4-W I R E
SUPPLY
UNFILTERED
RTI
PORT
P1P
2
P3P
4
+
_
BATTERYSEC. TX
BATTERYBATTERY
CLASS -A con verter
board for detection
circui ts ICAC-306 (6
cir cuits )
CLASS -A con verter
board for detection
circui ts ICAC-306 (6
cir cuits )
CLASS -A con verter
board for indicating
circui ts OC AC-304
(4 circuits )
Reverse po larity a nd city
tie module PR -300.
Mounted on hex spacer
with two screws provid ed
Relay Module RM-306
Mount relay module on the
left side using two screws
provided .
Relay M odule RM-312
centre under main fire
alarm board using three
screws pro vided .
Transformer
Fuse andAC wirungterminal
MAIN FIR E PANEL BOAR D
SYST EM
RESET
SIGNAL
SILEN C
E
FIR E
DRILL
BU ZZER
SILEN C
E
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENT ER
MENU
CANCEL
INFO
ABCDEF
GHIJKLMNO
PRS
TUV
WXY
QZ
A.C. ON ALAR M SUPVTR BL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
LCD DISPLAY
Fuse and AC
wiring terminal
FA-300 series fire alarm panels come pre-assembled with all components and boards except
for adder modules. Module installation locations are shown in Figures 6 and 7. Refer to "6.1.1
Connectors and Jumpers on the Main Fire Alarm Board" on page 24 for jumper or DIP switch
settings and see "7.6 Wiring Tables and Information" on page 37 for wiring information.
Mechanical Installation
20
Figure 6 Installation of adder modules for FA-301 LCD
Mechanical Installation
BATTERYBATTERY
CLASS-A
converter board
for detection
circuits IC AC-306
(6 cir cuits )
CLASS-A con verte r
board for indicating
circuits O CA C-302
(2 cir cuits )
Reverse polarity an d city
tie mo dule PR-300.
Mounted on hex spacer
with two screws provided
Relay Mo dule RM-306
Mount rela y module on the
left side usin g two screw s
provided .
LCD configuration tool -CFG-300plugged into thesocket shown.
Transformer
Fuse and AC wirung
termin al
MAIN FIRE PANEL BOARD
S-+NCN OCNCNOCNCNOCNCNOC
COM(+
)
COM(-)
TRLTRB
RTRT RT RT
RESCORESCO
LINE1LINE2
JW2
JW1
-+-+-+-+-+-+-+-+-+-+
DET
1
DET
2
DET
3
DET
4
DET
5
DET
6
SIG 1SIG 2
TO PR-300
MODULE
TO RM-312/RM-306 RELAY
MODULE
RS-
485
AUX. REL AY
ALARM
RELAY
SUPERVISORY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-WIRE
SUP PLY
UNFI LTERED
RTI
PORT
P1 P 2P3 P4
+
_
BATTERYSEC. TX
SYST EM
RESET
SIGNAL
SILEN C E
FIRE
DRILL
BUZZER
SILEN C E
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENT ER
MENU
CANCEL
INFO
ABCDEF
GHI
JK
L
MNO
PRS
TUV
WXY
QZ
A.C. ONALARMSUPVTRBLCPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
AUX
SUPPLY
P5P6
JW3
JW4
JW5
JW7
LCD DISPLAY
Figure 7 Installation of adder modules for FA-300 LCD
- DET1 RET+- DET2 RE T+- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RE T+
mounting hole for
#6-32 screws
All these pins comes with
red and black wires which
are connected to the
detection circuit on the
main fire alarm board. Red
is positive and black is
negative
ICAC-306
mounting hole for
#6-32 screws
6.1.1 Connectors and Jumpers on the Main Fire Alarm Board
P5Cable from P1 of the PR-300 polarity reversal and city tie module connects here.
Otherwise not used.
P6Cable from connector P1 of the RM-312 or RM-306 relay adder module connects
here. Otherwise not used.
JW1
Remove this jumper if a PR-300 polarity reversal and city tie module is installed.
JW2
JW3
Remove this jumper if an RM-312 or RM-306 relay adder module is installed.
Removed all the time.
JW4Normally open. Place jumper here and power down (AC and batteries) then power
back to restore the default passcode (1111 ). After the system restarts, remove the
jumper from JW4.
JW5Normally open to prevent configuration with a modem, a PC with a UIMA
converter module, or a CFG-300 configuration tool. Place a jumper here to allow
any type of configuration.
JW6
JW7
Not used, open.
Not used, open.
6.2ICAC-306 Input Class A Converter Adder Module
24
Figure 10 ICAC-306 Input Class A converter adder module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are
fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For
example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the
positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the
Connections, DIP Switches, and Jumpers
i
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
mounting hole for
#6-32 screws
OCA C-302
mounting hole for
#6-32 screws
- SIG1 O UT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BLK RED
mounting hol e for
#6-32 scr ews
OCA C -304
mounting hol e for
#6-32 screws
positive and negative terminals marked DET OUT and the circuit return wires are brought back
to the converter module to positive and negative terminals marked DET RET.
To convert all 12 initiating circuits of a FA-312 Fire Alarm Panel, two of these ICAC-306 input
Class A converter adder modules are required.
Note:This module has built in active end-of-line resistors and so the fire alarm system
should be configured to enable active end-of-line. See "11.0 Configuration" on
page 52.
6.3OCAC-304/302 Output Class A Converter Adder Module
Figure 11 OCAC-304/302 Output Class A converter adder module
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For
example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the
Class A converter module to the positive and negative terminals of Indicating circuit 1 on the
Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the
signaling devices and then wired back to the SIGNAL RET positive and negative.
6.4Relay Adder Modules (Models RM-312 and RM-306)
6.4.1 RM-312 Twelve Relay Adder Module
The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board.
The jumpers located above each relay on the RM-312 are used to configure the relays. The
25
jumpers located below the relays are used to select either normally open contacts or normally
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 1 0
NO/NC C
RELAY 1 1
NO/NC C
RELAY 1 2
NO/NCNO/NC
Three mounting
holes for #6-32
screws
INDIVIDUAL
GREEN RELAY
STATUS LEDs
Connect to P6 on the
main fire alarm board
NO NC
SA
Z1
1&2
NO/ NCC
RELAY 1
NC/NO CONNECTION
NC: terminal provides normally closed contacts
NO: terminal provides normally open contacts
Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection
then the relay is not connected to the terminals
SUPV/ALARM SELECTION
S: Relay turns ON when common
supervisory is active
A: Relay turns ON when common
alarm is active
Default: No jumper installed,
con nect e d on cent e r pin o nly
ZONE JUMPER
installed: turns ON relay when the zone
(1) i s act i ve
removed: does not turn ON the relay when
zone (1) i s act ive
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE
jumper installed: this relay 1 works in
conjunction with relay 2
jumper removed: relay 1 does not
operate with the adjacent relay 2
chaining example:if jumper is installed
on 1&2 and 2&3 then all the three relays
will be ON if any one of relays 1,2 and 3 is
active
Default: No jumper installed, connected
on one pin only
NO/ NCC
RELAY 12
RELAY
LED (G RE EN)
i
closed contacts.
Figure 12 RM-312 twelve relay adder module
P1Cable from RM-312 Relay Adder Module connects to P6 on Main Fire Alarm
Board.
6.4.2 Programming the relays
Connections, DIP Switches, and Jumpers
26
A typical relay circuit is shown in Figure 13 with the jumper locations and descriptions.
Figure 13 RM-312/306 Relay programming
Note:Relay programming should be done before installing the board.
6.5RM-306 Six Relay Adder Module
NO/ NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/ NC C
RELAY 6
NO/NC
mounting hole
for #6-32 screws
mounting hole
for #6-32 screws
INDIVIDUAL GREEN
RELAY STAT US LEDs
Connect to P 6 on the
main fire alarm board
i
Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers
located above each relay on the RM-306 are used to configure the relays. The jumpers
located below the relays are used to select either normally open contacts or normally closed
contacts.
Connections, DIP Switches, and Jumpers
Figure 14 RM-306 six relay adder module
P1Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm
Board.
6.5.1 Programming the relays
See the explanation in Figure 13.
Note:Relay programming should be done before installing the board.
6.6Polarity Reversal and City Tie Module (Model PR-300)
Mounting hole for
#6-32 screws
P1 P2
Mounting hole for
#6-32 screws
+ | - + | - + | -
TIE
ALARM
SUPV
CITY
REVERSAL
POLARITY
REVERSAL
POLARITY
JW4
Figure 15 Polarity reversal and city tie module
27
The following hardware configuration must be performed before installing the PR-300.
6.6.1 PR-300 jumper settings
Connections, DIP Switches, and Jumpers
P1
P2 & JW4
Cable connects to P3 on the Main Board
Not used. Jumper JW4 remains on board.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0, 1
or 3 hours if this is the only system trouble.
28
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.