Mircom FA-300, FA-300-6DDR, FA-300-6DR, FA-301-12DDR, FA-300-6DDR-CG Installation And Operation Manual

FA-300 Series
LCD Fire Alarm Control Panel
Installation and Operation Manual
LT-906 Rev. 10.2 June 2017

Table of Contents

1.0 Industry Canada and FCC Notice 9
2.0 Introduction 11
2.1 Overall Features ............................................................................................................ 11
3.0 Conventions 12
3.1 Circuits ........................................................................................................................... 12
3.2 Zone ............................................................................................................................... 12
3.3 Events ............................................................................................................................ 12
3.4 Wiring Styles .................................................................................................................. 12
4.0 System Components 13
4.1 Main Fire Control Panel ................................................................................................. 13
4.2 Relay Module: 12 Relays ............................................................................................... 14
4.3 Relay Modules: Six Relays ............................................................................................ 14
4.4 Polarity reversal/city tie .................................................................................................. 14
4.5 Remote Annunciator ...................................................................................................... 14
4.6 Smart Relay Module ...................................................................................................... 15
4.7 Input Class A converter: Six Circuits .............................................................................. 15
4.8 Output Class A converter: Four Circuits ........................................................................ 15
4.9 Output Class A converter: Two Circuits ......................................................................... 15
4.10 Active end-of-line resistor .............................................................................................. 16
4.11 RAM-216 Remote Annunciator ...................................................................................... 16
4.12 Additional Fire Alarm System Accessories .................................................................... 16
5.0 Mechanical Installation 17
5.1 Installing the Enclosure .................................................................................................. 17
5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 19
5.3 Installing the Adder Modules .......................................................................................... 20
6.0 Connections, DIP Switches, and Jumpers 22
6.1 Main Fire Alarm Board ................................................................................................... 22
6.2 ICAC-306 Input Class A Converter Adder Module ......................................................... 24
6.3 OCAC-304/302 Output Class A Converter Adder Module ............................................. 25
6.4 Relay Adder Modules (Models RM-312 and RM-306) ................................................... 25
3
Table of Contents
6.5 RM-306 Six Relay Adder Module .................................................................................. 27
6.6 Polarity Reversal and City Tie Module (Model PR-300) ................................................ 27
7.0 Field wiring 29
7.1 Main Fire Alarm Board Field Wiring ............................................................................... 29
7.2 Relay Adder Module Wiring ........................................................................................... 32
7.3 Connecting to a 3G4010CF Interface Device ................................................................ 34
7.4 Polarity Reversal and City Tie Module (PR-300) Wiring ................................................ 35
7.5 Power supply connection ............................................................................................... 36
7.6 Wiring Tables and Information ....................................................................................... 37
7.7 Supervised Auxiliary Power (regulated) ......................................................................... 38
7.8 Auxiliary Power (unregulated) ........................................................................................ 38
8.0 Turning on the Panel 39
8.1 Before Connecting the Power ........................................................................................ 39
8.2 Connecting the Power .................................................................................................... 40
8.3 Troubleshooting ............................................................................................................. 41
9.0 Indicators, Controls and Operations 42
9.1 Common Indicators ........................................................................................................ 42
9.2 Common Controls .......................................................................................................... 43
9.3 Common Relays ............................................................................................................. 44
9.4 Circuit Types .................................................................................................................. 45
9.5 Evacuation Codes .......................................................................................................... 48
9.6 Fire Alarm Operation ...................................................................................................... 48
10.0 Supported Protocols and Devices 50
10.1 Synchronous Strobes ..................................................................................................... 50
10.3 System Sensor’s i3 Devices ........................................................................................... 50
11.0 Configuration 52
11.1 Accessing Configuration Mode ...................................................................................... 53
11.2 Command Menu ............................................................................................................. 53
11.3 Panel Config (Command Menu) ..................................................................................... 55
11.5 Config. Info. (Command Menu) ...................................................................................... 62
11.6 Set Time (Command Menu) ........................................................................................... 63
11.7 Set Password (Command Menu) ................................................................................... 64
11.8 View EventLog (Command Menu) ................................................................................. 64
11.9 Clear EventLog (Command Menu) ................................................................................ 65
4
Table of Contents
11.10 Walk Test (Command Menu) ......................................................................................... 65
11.11 I3 Loop Test (Command Menu) ..................................................................................... 66
11.12 Dialer Config (Command Menu) .................................................................................... 67
11.13 Test Dialer (Command Menu) ........................................................................................ 73
11.14 Bypass Det Ckt (Command Menu) ................................................................................ 74
11.15 Bypass NAC Ckt (Command Menu) .............................................................................. 75
11.16 Aux. Disc. (Command Menu) ......................................................................................... 75
11.17 Exit (Command Menu) ................................................................................................... 75
12.0 Appendix A: Compatible Receivers 81
13.0 Appendix B: Reporting 82
13.1 Ademco Contact-ID ........................................................................................................ 82
13.2 Security Industries Association SIA-DCS ...................................................................... 83
14.0 Appendix C: Specifications 84
15.0 Appendix D: Power Supply and Battery Calculations 87
16.0 Warranty and Warning Information 89
5

List of Figures

Figure 1 FA-300 LCD ................................................................................................................... 13
Figure 2 Enclosure dimensions, surface mount ........................................................................... 17
Figure 3 Enclosure dimensions, semi-flush mounting and trim ring ............................................. 18
Figure 4 Flush trim detail (from above) ........................................................................................ 18
Figure 5 BBX-1024DS and BBX-1024DSR installation instructions and dimensions .................. 19
Figure 6 Installation of adder modules for FA-301 LCD ............................................................... 20
Figure 7 Installation of adder modules for FA-300 LCD ............................................................... 21
Figure 8 Main fire alarm board connections, DIP switches and jumpers for FA-301 LCD ........... 22
Figure 9 Main fire alarm board connections, DIP switches and jumpers for FA-300 LCD ........... 23
Figure 10 ICAC-306 Input Class A converter adder module .......................................................... 24
Figure 11 OCAC-304/302 Output Class A converter adder module .............................................. 25
Figure 12 RM-312 twelve relay adder module ............................................................................... 26
Figure 13 RM-312/306 Relay programming ................................................................................... 26
Figure 14 RM-306 six relay adder module ..................................................................................... 27
Figure 15 Polarity reversal and city tie module .............................................................................. 27
Figure 16 Initiating circuit – Class B or Style B wiring .................................................................... 29
Figure 17 Initiating circuit– Class A or Style D wiring ..................................................................... 30
Figure 18 Indicating circuit – Class B or Style Y wiring .................................................................. 30
Figure 19 Indicating circuit –Class A or Style Z wiring ................................................................... 31
Figure 20 Four-wire smoke detector wiring .................................................................................... 31
Figure 21 Dialer wiring ................................................................................................................... 32
Figure 22 Relay per zone (RM-312) Terminal connection ............................................................. 32
Figure 23 Relay per zone (RM-306) Terminal connection ............................................................. 33
Figure 24 Connecting an FACP to a 3G4010CF Interface Device ................................................. 34
Figure 25 Polarity reversal and city tie module terminal connection .............................................. 35
Figure 26 Power supply connection ............................................................................................... 36
Figure 27 Battery connections ........................................................................................................ 40
Figure 28 LCD Display and control buttons .................................................................................... 42
Figure 29 Lamp test ....................................................................................................................... 44
Figure 30 Evacuation Codes .......................................................................................................... 48
Figure 31 FA-300 main LCD display .............................................................................................. 52
Figure 32 Enter passcode ......................................................................................................
Figure 33 Command Menu ............................................................................................................. 54
Figure 34 FA-300 Config menu ...................................................................................................... 55
Figure 35 Feature Config menu ..................................................................................................... 55
Figure 36 The event log ................................................................................................................. 64
Figure 37 Walk test confirmation .................................................................................................... 65
Figure 38 Walk test zones .............................................................................................................. 65
Figure 39 Walk test active .............................................................................................................. 65
Figure 40 i3 loop test confirmation ................................................................................................. 66
Figure 41 i3 test zones ................................................................................................................... 66
Figure 42 i3 test not ready .............................................................................................................. 67
Figure 43 The selected zone is not i3 type ..................................................................................... 67
........ 53
6
List of Figures
Figure 44 Dialer Config menu ........................................................................................................ 67
Figure 45 Account Info menu ......................................................................................................... 68
Figure 46 Telephone Line menu .................................................................................................... 69
Figure 47 Report Options menu ..................................................................................................... 70
Figure 48 Time Parameter ............................................................................................................. 71
Figure 49 Dialer Test menu ............................................................................................................ 73
Figure 50 Detection circuit message .............................................................................................. 76
Figure 51 Indicating circuit message .............................................................................................. 76
Figure 52 AC Power Fail message ................................................................................................ 77
Figure 53 Battery trouble message ................................................................................................ 77
Figure 54 Ground Fault message .................................................................................................. 78
Figure 55 Remote Annunciator message ....................................................................................... 78
Figure 56 Four-wire smoke detector supply message ................................................................... 79
Figure 57 Supervised auxiliary supply message ............................................................................ 79
Figure 58 Module missing message .............................................................................................. 80
Figure 59 Module trouble message ................................................................................................ 80
7

List of Tables

Table 1 FA-300 LCD Series Comparison Chart .......................................................................... 13
Table 2 Power Supply Ratings .................................................................................................... 36
Table 3 Initiating Circuit Wiring ................................................................................................... 37
Table 4 Indicating Circuit Wiring ................................................................................................. 37
Table 5 Troubleshooting ............................................................................................................. 41
Table 6 i3 detector LEDs ............................................................................................................. 51
Table 7 Feature Config menu ..................................................................................................... 56
Table 8 i3 Detector LEDs while in test mode .............................................................................. 67
Table 9 Compatible Receivers .................................................................................................... 81
Table 10 Ademco Event Code ...................................................................................................... 82
Table 11 SIA Event Codes ............................................................................................................ 83
Table 12 FA-300 LCD Series Specifications ................................................................................. 84
Table 13 FA-300 LCD System Modules and Annunciators ........................................................... 85
8

1.0 Industry Canada and FCC Notice

!
i

1.1 Notice for all FA-300 Series Built-In UDACTs Sold in Canada

Mircom's FA-300 SERIES BUILT-IN UDACT Communicator described in this manual is listed by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units for Fire Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems and Services). These Communicators should be installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction (AHJ).

1.1.1 Industry Canada Notice

Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the Earth Ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
Caution: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or electrician, as appropriate.

1.1.2 Notice for all FA-300 Series Built-in UDACTs Sold in the U.S.A.

Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
The REN for this product is part of the product identifier that has the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
Mircom's FA-300 SERIES BUILT-IN UDACT Digital Communicator described in this manual is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective Signalling Systems). These Communicators comply with the National Fire Protection Association (NFPA) performance requirements for DACTs and should be installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These Communicators should be installed in accordance with this manual; the National Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
9

1.1.3 FCC Notice

This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the telco transformer of this equipment is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company. This equipment is capable of seizing the line. This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (central office implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with the best service it can. In order to do this, it may occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect your service or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence number (REN); both of these items are listed on the equipment label. The sum of all of the REN’s on your telephone lines should be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable on a given line.
Industry Canada and FCC Notice
If Problems Arise: If any of your telephone equipment is not operating properly, you should immediately remove it from your telephone line, as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they should be performed by Mircom Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page of this document.
10

2.0 Introduction

i
Mircom's FA-300 Series Fire Alarm Control Panel is a Digital Signal Processor (DSP) based fire panel. The FA-300 provides a maximum of 12 supervised Class B or A (style B or D) Initiating circuits, and maximum of four supervised Class B or A (Style Y or Z) indicating circuits. All circuits are supervised for opens and ground faults, and indicating circuits are supervised for shorts. Optional modules include relay, polarity reversal and city tie and Class A Converters for initiating and indicating circuits. Semi-flush or surface mountable backboxes
can be used for retrofits and on new installations.
Note: Installation of the FA-300 series fire alarm control panel should be in accordance
with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ).

2.1 Overall Features

The basic unit has six Class B (Style B) initiating circuits, which may be configured as
Class A (Style D) using input Class A converter adder module. Each initiating circuit can be configured as alarm, verified alarm, water flow alarm, sprinkler alarm, latching or non-latching supervisory, monitor or trouble circuits.
The basic unit has two power limited Class B (Style Y) indicating circuits. Each
indicating circuit may be configured as Class A (Style Z) using an output Class A converter adder module. Each indicating circuit may be configured as silenceable signal, non-silenceable signal, silenceable strobe, non-silenceable strobe. The audible signal may be Steady, Temporal Code, California Code, or March Time.
Each initiating and indicating circuit can be individually disconnected via the keypad and
LCD display with password access.
Configurable signal silence inhibit, auto signal silence, and one-man walk test.
Four-wire resettable smoke power supply 300 mA maximum.
Relay contacts for common alarm, common supervisory and common trouble all non-
disconnect-able and auxiliary alarm relay (disconnectable).
RS-485 interface for RA-1000 series remote multiplex Annunciators, LCD Annunciators
and smart relay adder.
Optional modules for additional relay circuits, city tie and polarity reversal signaling.
Extensive transient protection.
With or without built-in UDACT (Digital Alarm Communicator Transmitter).
Easy configuration of the panel using front LCD display and keypad.
Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing.
Laptop programmer for direct configuration changing and log checking.
11

3.0 Conventions

3.1 Circuits

Refers to an actual electrical interface for initiating (detection) and indicating (signal or NAC) or relays

3.2 Zone

Is a logical concept for a Fire Alarm Protected Area, and consists of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual circuit refers only to a physical electrical loop.

3.3 Events

There are events associated with every initiating, indicating and common circuit of the fire panel displayed via the LCD.

3.4 Wiring Styles

Initiating and indicating circuits are Class B (Style B and Y).
Changing the initiating circuits to Class A requires an ICAC-306 adder board which will convert six initiating zones from Class B (Style B) circuits to Class A (Style D). This is done without decreasing the number of circuits, which remains the same as in Class B (Style B).
Changing the indicating circuits to Class A requires an OCAC-304 adder board which will convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z) or an OCAC­302 adder board which will convert two indicating zones from Class B (Style Y) circuits to Class A (Style Z).
12

4.0 System Components

4.1 Main Fire Control Panel

Figure 1 FA-300 LCD
All FA-300 LCD series panels have the following features:
LCD display
Two six-zone ICAC-306 Input Class A converter adder modules may be used for
Class A (Style D) wiring of Initiating circuits.
One OCAC-304 Output Class A converter adder module may be used for Class A
(Style Z) wiring of the indicating circuits.
Common alarm, common supervisory and common trouble relays, auxiliary alarm relay
(disconnectable), an RS-485 interface for Remote Annunciators and a resettable four wire smoke detector power supply.
Used with BA-110 (10 Ah) (Sota Enertech model SA12120) batteries (two required).
Table 1 FA-300 LCD Series Comparison Chart
Model Number of
zones
FA-300-6DDR 6 6 y red
FA-300-6DR 6 6 n red
FA-301-12DDR 12 12 y red
Number of
initiating
circuits
On board Dialer Door Color
FA-300-6DDR-CG
Marine Fire Alarm Control Unit
66 y red
13

4.2 Relay Module: 12 Relays

NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 10
NO/NC
C
RELAY 11
NO/NC C
RELAY 12
NO/NC NO/NC
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC
C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC
POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
FA-300 SERIES
Remote Annunciator
SYSTEM RESET
SIGNAL SILENCE
FIRE
DRILL
BUZZER SILENCE
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
Advanced Li fe Safety Sol utions
System Components
Model Description

4.3 Relay Modules: Six Relays

Model Description
RM-306 Six relay adder module

4.4 Polarity reversal/city tie

Model Description
RM-312
12 relay adder module
14

4.5 Remote Annunciator

PR-300 Polarity reversal and/or city tie module
Model Description
RAM-300LCDW
RAM-300LCDR
Remote annunciator module, LCD display, white painted box
Remote annunciator module, LCD display, red painted box

4.6 Smart Relay Module

REMOTE RELAY
Advanced Life Safety Sol utions
FR-320 SERIES
BLK RED
BLK REDBLK REDBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- DET6 OUT+
- DET1 RET+- DET2 RET+- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RET+
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG 2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG 4 RET+
BLK RED
BLK RED
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
Model Description
SRM-312W Smart relay module (12 relays) with white enclosure
SRM-312R Smart relay module (12 relays) with red enclosure

4.7 Input Class A converter: Six Circuits

Model Description
System Components
ICAC-306
Input Class A converter module (six circuits). This module has built in active end-of-line resistors.

4.8 Output Class A converter: Four Circuits

Model Description
OCAC-304 Output Class A converter module (four circuits)

4.9 Output Class A converter: Two Circuits

Model Description
OCAC-302 Output Class A converter module (two circuits)
15

4.10 Active end-of-line resistor

BLACK
RED
A.C.ONCOMMON
TROUBLE
SIGNAL SILEBCE
BUZZER SILENCE
SIGNAL SILENCE
LAMP TEST
SYSTEM RESET
SWITCH ENABLE
FIRE ALARM ANNUNCIATOR
The ELRX-300 are power-saving end-of-line resistors that eliminate the need for an additional battery cabinet or larger batteries in order to meet the 60 hour standby requirement.
Model Description
ELRX-300 Active end-of-line resistor without plate
ELRX-300R Active end-of-line resistor with end-of-line red plate

4.11 RAM-216 Remote Annunciator

Model Description
RAM-216 16 zone remote annunciator
System Components

4.12 Additional Fire Alarm System Accessories

RAM-208 Eight zone remote annunciator (ULC and ULI approved)
RTI-1 Remote trouble indicator (ULC and ULI approved)
MP-300
End-of-line resistor plate, 3.9 k
Ω
MP-300R End-of-line resistor plate, red (ULC approved)
BC-160 External battery cabinet (ULC and ULI approved)
(ULC and ULI approved)
16

5.0 Mechanical Installation

11"
14.5"
1.5"
20.5"
5.4"
4.5"
25.9"
Mounting Hole
Mounting Hole
Mounting Hole
Mounting Hole

5.1 Installing the Enclosure

Install the FA-300 series fire alarm panel enclosure as shown below for the 12 zone, eight zone, and six zone models. Mount enclosure surface mount using the four mounting holes, as shown and the screws provided.
Figure 2 Enclosure dimensions, surface mount
The enclosure may be semi-flush mounted using the trim ring model FA-UNIV-TRB (BLACK), see Figure 3. Remove the door (also disconnect the ground strap), the dead front and semi-
17
Mechanical Installation
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" i s the max imum depth for semi -flus h mounting usi ng the flush tr im ri ng
1" is the mi nimum depth
above the wall required for semi- flus h mounting usi ng the flus h trim ri ng
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 300 backbox .
PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX
TRIM RING
WALL
WOOD OR
METAL STUD
BACKBOX
flush mount the enclosure into the wall. Peel the adhesive cover from the trim ring and stick to the wall surface around the enclosure, after the wall is finished.
Figure 3 Enclosure dimensions, semi-flush mounting and trim ring
Figure 4 shows a cross-section of the semi-flush mounted enclosure and the trim ring. Make sure to allow
a minimum depth of 1” above the wall surface for proper door opening.
Figure 4 Flush trim detail (from above)
18
Mechanical Installation
26.0 "
14.5 "
4.2 "
External Dimensions
1.3 "
1.7 "
2.0 "
Top View
2.1 "
1.3 "
6.0 "
9.5 "
Side View

5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation

The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a built-in trim ring.
Dimensions of enclosure (minus built-in trim ring) 14.5” x 4.2” x 26”
Distance between horizontal mounting screws 12”
Distance between vertical mounting screws 23.5”
Complete dimensions of enclosures 16.3” x 5.5” x 27.5”
Mounting Dimensions
12.0 "
23.5 "
Figure 5 BBX-1024DS and BBX-1024DSR installation instructions and dimensions
19

5.3 Installing the Adder Modules

S-+NC N OCNC NOCNC NOCNC NOC
+-+-COM(+)
COM(-)
TRLTRB RTRT RTR T
RES CO RES CO
LINE1LINE2
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DE T 5DET 6DET 7DE T 8DET 9DET 10DET 11DET 12SI G 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 MODULE
TO RM -312/RM-306 RELAY
MODULE
RS-
485
AUX. RELA YALARM
RELAY
SUP E RVIS O R Y
RELAY
TROU BLE
RELAY
AUX
SUPPLY
4-W I R E
SUPPLY
UNFILTERED
RTI
PORT
P1P
2
P3P
4
+
_
BATTERY SEC. TX
BATTERY BATTERY
CLASS -A con verter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A con verter board for detection circui ts ICAC-306 (6
cir cuits )
CLASS -A con verter board for indicating circui ts OC AC-304
(4 circuits )
Reverse po larity a nd city tie module PR -300. Mounted on hex spacer with two screws provid ed
Relay Module RM-306 Mount relay module on the left side using two screws provided .
Relay M odule RM-312 centre under main fire alarm board using three screws pro vided .
Transformer
Fuse and AC wirung termina l
MAIN FIR E PANEL BOAR D
SYST EM RESET
SIGNAL SILEN C
E
FIR E
DRILL
BU ZZER SILEN C
E
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENT ER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALAR M SUPV TR BL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
LCD DISPLAY
Fuse and AC wiring terminal
FA-300 series fire alarm panels come pre-assembled with all components and boards except for adder modules. Module installation locations are shown in Figures 6 and 7. Refer to "6.1.1 Connectors and Jumpers on the Main Fire Alarm Board" on page 24 for jumper or DIP switch settings and see "7.6 Wiring Tables and Information" on page 37 for wiring information.
Mechanical Installation
20
Figure 6 Installation of adder modules for FA-301 LCD
Mechanical Installation
BATTERY BATTERY
CLASS-A converter board for detection circuits IC AC-306
(6 cir cuits )
CLASS-A con verte r board for indicating circuits O CA C-302
(2 cir cuits )
Reverse polarity an d city tie mo dule PR-300. Mounted on hex spacer with two screws provided
Relay Mo dule RM-306 Mount rela y module on the left side usin g two screw s provided .
LCD configuration tool - C FG-300 plugged i nto the socket sh own .
Transformer
Fuse and AC wirung termin al
MAIN FIRE PANEL BOARD
S-+NC N OCNC NOCNC NOCNC NOC
COM(+
)
COM(-)
TRLTRB
RTRT RT RT
RES CO RES CO
LINE1LINE2
JW2
JW1
-+-+-+-+-+-+-+-+-+-+
DET
1
DET
2
DET
3
DET
4
DET
5
DET
6
SIG 1SIG 2
TO PR-300
MODULE
TO RM-312/RM-306 RELAY
MODULE
RS-
485
AUX. REL AY
ALARM
RELAY
SUPERVISORY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-WIRE
SUP PLY
UNFI LTERED
RTI
PORT
P1 P 2P3 P4
+
_
BATTERY SEC. TX
SYST EM RESET
SIGNAL SILEN C E
FIRE
DRILL
BUZZER SILEN C E
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENT ER
MENU
CANCEL
INFO
ABC DEF
GHI
JK
L
MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
AUX
SUPPLY
P5 P6
JW3
JW4
JW5
JW7
LCD DISPLAY
Figure 7 Installation of adder modules for FA-300 LCD
21
S-+NC NOCNC NOCNC NOCNC NOC
+-+-
COM(+)
CO M(- )
TRLTRB RTRT RTRT
RES CO RES CO
LINE1LINE2
JW3 JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SIG 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 MODUL E
TO RM-312/RM-306 RELAY MODULE
RS-4 85AUX. RELAYAL ARM RE LA Y
SUPERVISO RY
RELAY
TRO UBL E
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UN FILTERED
RTI
PORT
P1 P 2P3 P4
+
_
BA TTER Y SEC. TX
Telephon e line #1
Telephon e line #2
RS-485 for annunciators
Auxiliary Relay
Alar m Relay
Supervisory Rela y
Troub le Relay
Auxiliary Supply
4-w ir e Su pp ly
Unfiltered 24V supply
conne ct to Remo te trouble indicator
Initiating zone 1 TO 12
Indicating zone 1 TO 4
Connect to RM-312/ RM306 Relay module
Connect to PR-3 00
To Batte ry To seco ndary of AC
transformer
JW2 - ON- when RM312/RM306 not connected
JW1 - ON- when PR- 300 not connected
JW3- Remove d all th e time
JW6 -Open all the time
JW5 -Normally Open
SYSTEM
RESET
SIGNAL SILENCE
FIRE
DRILL
BUZZER SILENCE
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
JW4 -No rmally Open
JW7
JW7- Normally Open
For PC programming use UIMA interface module not UL-864 or ULC-S527 listed. Please r efer to Document LT-929 for details
6.0 Connections, DIP Switches, and
Jumpers

6.1 Main Fire Alarm Board

22
Figure 8 Main fire alarm board connections, DIP switches and jumpers for FA-301 LCD
Connections, DIP Switches, and Jumpers
S-+NC NOCNC NOCNC NOCNC NOC
CO M(+ )
CO M(- )
TRLTRB
RTRT RTRT
RES CO RES CO
LINE1LINE2
JW2
JW 1
-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6
SIG 1SIG 2
TO PR-300 MO DULE TO RM-312/RM-306 RELAY MODULE
RS-4 85AUX. RELAYAL ARM RE LA Y
SUPERVISORY
RELAY
TROU BL E
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UNFIL TERED
RTI
PORT
P1 P 2P3 P4
+
_
BA TTERY SEC. T X
Teleph one line #1
Teleph one line #2
RS-48 5 for annunciators
Auxiliary Rela y
Alarm Rela y
Superviso ry Rela y
Trouble Relay
Initiating zone 1 TO 6
To Batte ry To secondary of AC
tran sformer
JW2 - ON- when RM312/RM306 not connected
JW1 - ON- when PR-300 not connected
SYSTEM
RESET
SIGNAL
SILENCE
FIRE DRILL
BUZZER
SILENCE
LAMP TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
AUX
SUPPLY
P5 P6
JW 3
JW3 Remo ved all the time
JW4
JW5
JW7
JW7 Normally open
JW4 - Nor mally Open
JW5 - Nor mally Open
For PC progr amming use UIMA interface module not UL-864 or ULC-S527 listed . Please refer to Document LT-929 for details
Signal Circuit- 1
Signal Circuit- 2
Auxilia ry Supply
4-w ir e S up pl y
Unfiltered 24V supply
Connect to Remote Troub le Indicator
Figure 9 Main fire alarm board connections, DIP switches and jumpers for FA-300 LCD
23
Connections, DIP Switches, and Jumpers
BLK RED
BLK REDBLK REDBLK REDBLK REDBLK RED
- DET1 OUT+- DET2 OUT+- DET3 OUT+- DET4 OUT+- DET5 OUT+- DET6 OUT+
- DET1 RET+- DET2 RE T+- DET3 RET+- DET4 RET+- DET5 RET+- DET6 RE T+
mounting hole for #6-32 screws
All these pins comes with red and black wires which are connected to the detection circuit on the main fire alarm board. Red is positive and black is negative
ICAC-306
mounting hole for #6-32 screws

6.1.1 Connectors and Jumpers on the Main Fire Alarm Board

P5 Cable from P1 of the PR-300 polarity reversal and city tie module connects here.
Otherwise not used.
P6 Cable from connector P1 of the RM-312 or RM-306 relay adder module connects
here. Otherwise not used.
JW1
Remove this jumper if a PR-300 polarity reversal and city tie module is installed.
JW2
JW3
Remove this jumper if an RM-312 or RM-306 relay adder module is installed.
Removed all the time.
JW4 Normally open. Place jumper here and power down (AC and batteries) then power
back to restore the default passcode (1111 ). After the system restarts, remove the jumper from JW4.
JW5 Normally open to prevent configuration with a modem, a PC with a UIMA
converter module, or a CFG-300 configuration tool. Place a jumper here to allow any type of configuration.
JW6
JW7
Not used, open.
Not used, open.

6.2 ICAC-306 Input Class A Converter Adder Module

24
Figure 10 ICAC-306 Input Class A converter adder module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the ICAC-306 module to the Main Fire Alarm board. For example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm Board. From the ICAC-306 converter Initiating circuits are wired out to the devices from the
Connections, DIP Switches, and Jumpers
i
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
mounting hole for #6-32 screws
OCA C-302
mounting hole for #6-32 screws
- SIG1 O UT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BLK RED
mounting hol e for #6-32 scr ews
OCA C -304
mounting hol e for #6-32 screws
positive and negative terminals marked DET OUT and the circuit return wires are brought back to the converter module to positive and negative terminals marked DET RET.
To convert all 12 initiating circuits of a FA-312 Fire Alarm Panel, two of these ICAC-306 input Class A converter adder modules are required.
Note: This module has built in active end-of-line resistors and so the fire alarm system
should be configured to enable active end-of-line. See "11.0 Configuration" on page 52.

6.3 OCAC-304/302 Output Class A Converter Adder Module

Figure 11 OCAC-304/302 Output Class A converter adder module
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the Class A converter module to the positive and negative terminals of Indicating circuit 1 on the Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then wired back to the SIGNAL RET positive and negative.

6.4 Relay Adder Modules (Models RM-312 and RM-306)

6.4.1 RM-312 Twelve Relay Adder Module

The ribbon cable from P1 of the RM-312 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-312 are used to configure the relays. The
25
jumpers located below the relays are used to select either normally open contacts or normally
NO/NC C
RELAY 1
NO/NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/NC C
RELAY 6
NO/NC C
RELAY 7
NO/NC C
RELAY 8CRELAY 9
NO/NC C
RELAY 1 0
NO/NC C
RELAY 1 1
NO/NC C
RELAY 1 2
NO/NC NO/NC
Three mounting holes for #6-32 screws
INDIVIDUAL GREEN RELAY STATUS LEDs
Connect to P6 on the main fire alarm board
NO NC
SA
Z1
1&2
NO/ NC C
RELAY 1
NC/NO CONNECTION NC: terminal provides normally closed contacts NO: terminal provides normally open contacts Default: jumper is installed on normally open (NO)
Note: if the jumper is not installed on any selection then the relay is not connected to the terminals
SUPV/ALARM SELECTION S: Relay turns ON when common
supervisory is active A: Relay turns ON when common alarm is active Default: No jumper installed, con nect e d on cent e r pin o nly
ZONE JUMPER installed: turns ON relay when the zone
(1) i s act i ve removed: does not turn ON the relay when zone (1) i s act ive
Default: Jumper is installed
LOGICAL OR WITH ADJACENT ZONE jumper installed: this relay 1 works in
conjunction with relay 2 jumper removed: relay 1 does not operate with the adjacent relay 2 chaining example:if jumper is installed on 1&2 and 2&3 then all the three relays will be ON if any one of relays 1,2 and 3 is active Default: No jumper installed, connected on one pin only
NO/ NC C
RELAY 12
RELAY
LED (G RE EN)
i
closed contacts.
Figure 12 RM-312 twelve relay adder module
P1 Cable from RM-312 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.4.2 Programming the relays

Connections, DIP Switches, and Jumpers
26
A typical relay circuit is shown in Figure 13 with the jumper locations and descriptions.
Figure 13 RM-312/306 Relay programming
Note: Relay programming should be done before installing the board.

6.5 RM-306 Six Relay Adder Module

NO/ NC C
RELAY 1
NO/ NC C
RELAY 2
NO/NC C
RELAY 3
NO/NC C
RELAY 4CRELAY 5
NO/ NC C
RELAY 6
NO/NC
mounting hole for #6-32 screws
mounting hole for #6-32 screws
INDIVIDUAL GREEN RELAY STAT US LEDs
Connect to P 6 on the main fire alarm board
i
Cable from P1 of the RM-306 is connected to P6 on the Main Fire Alarm Board. The jumpers located above each relay on the RM-306 are used to configure the relays. The jumpers located below the relays are used to select either normally open contacts or normally closed contacts.
Connections, DIP Switches, and Jumpers
Figure 14 RM-306 six relay adder module
P1 Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm
Board.

6.5.1 Programming the relays

See the explanation in Figure 13.
Note: Relay programming should be done before installing the board.

6.6 Polarity Reversal and City Tie Module (Model PR-300)

Mounting hole for
#6-32 screws
P1 P2
Mounting hole for #6-32 screws
+ | - + | - + | -
TIE
ALARM
SUPV
CITY
REVERSAL
POLARITY
REVERSAL
POLARITY
JW4
Figure 15 Polarity reversal and city tie module
27
The following hardware configuration must be performed before installing the PR-300.

6.6.1 PR-300 jumper settings

Connections, DIP Switches, and Jumpers
P1
P2 & JW4
Cable connects to P3 on the Main Board
Not used. Jumper JW4 remains on board.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active. This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals will resound and the City Tie Box will be retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0, 1 or 3 hours if this is the only system trouble.
28
Loading...
+ 64 hidden pages