Figure 17: Locating the Walk Test Switch ........................................................................... 22
FA-262 Installation & Operator’s Manual
iii
FA-262 Installation & Operator’s Manual
1.0 Introduction
1.1 The FA-262 Fire Alarm Control Unit
General features
•Two initiating device circuits, class B / style B
•Two notification appliance circuits, class B / style Y (Power Limited)
[can be wired as one NAC, class A / style Z]
•One common alarm-actuated relay, form ‘C’
•One common trouble-actuated relay, form ‘C’
•AUX+ power output, 500 mA max. (Power Limited)
•Unswitched common and switched common auxiliary power returns
•Integral battery charger
•Cabinet with dead-front construction
•Transformer, mounted in the cabinet
Applications
The FA-262 two zone, fire alarm control panel is listed for use in the following applications.
•Protected Premises Fire Alarm System
•And for the following types of service:
A – automatic, M – Manual, SS – Sprinkler Supervisory, WF – Waterflow
1.2 Codes, Standards and Installation Requirements
Relevant codes and standards
The FA-262 fire alarm control panel is designed to meet the requirements of NFPA 72, 2002 edition, UL 864
Rev 9, Control Units for Fire Protective Systems, and in Canada, CAN/ULC-S527-99, Standard for Control
Units for Fire Alarm Systems.
Information provided with this unit is intended as a guide. Installation of this equipment, optional system
components, alarm initiating devices and notification appliances must follow the manufacturer’s guidelines as
contained in their respective installation documents, all applicable codes and the instructions of the Local
Authority Having Jurisdiction.
General Installation requirements
Manufacturer’s documents
When installing the FA-262 control panel, refer to this manual. When installing optional system components
refer to the installation documents included with those components. When installing compatible alarm initiating
devices or notification appliances, refer to the installation documents included with those products.
Field wiring
Field wiring recommendations in this document are intended as guidelines. All field wiring must be installed in
accordance with NFPA 70 National Electrical Code and in Canada with the standard for installation ULC/S
524, the most current Canadian Electrical Code, with all relevant local codes and standards, and the Authority
Having Jurisdiction.
Compatible devices
Use UL or ULC Listed smoke detectors and notification appliances that are compatible with the FA-262 Fire
alarm control panel from the lists included in this manual.
1
FA-262 Installation & Operator’s Manual
1.3 Technical Support and General Information
For technical support call 1-888-660-4655, or email techsupport@mircom.com.
For general product information visit the Mircom web site: www.mircom.com.
1.4 System Verification
The complete fire alarm system must be verified for proper installation and operation when:
•the initial installation is ready for inspection by the Local Authority Having Jurisdiction;
•any system component is added, changed or deleted;
•any programming changes are made;
•system wiring has been altered or repaired;
•system failure due to external influences such as lightning, water damage or extended power outages has
occurred.
1.5 Standby Power
The FA-262 provides standby battery support for lead-acid rechargeable batteries. The required capacity of
the standby batteries must be calculated using the charts and tables within this manual for the period as
required by national or local codes and standards. Even though the calculation table within this manual
includes a safety margin, lead-acid batteries commonly used for standby can have variable capacity as a
result of age and ambient conditions. Periodic inspection for damage and the batteries’ ability to support the
attached equipment is highly recommended.
1.6 Battery Maintenance
The two 12V sealed lead-acid batteries should be replaced after each period of 3 to 5 years of normal service.
If the Battery Trouble indicator activates, obtain required service.
2
2.0 Preparing to Install the FA-262 Fire Panel
2.1 Unpacking the FA-262
The basic FA-262 package includes the following components:
•Cabinet with hinged door
•Display and control plate c/w display and control printed circuit board.
•Zone label insert
•Battery compartment dead front plate
•Main control PCB
•Transformer
•Installation manual
•Hardware pack
-- 2 × NAC EOL resistors (4.7 K, 5%, ½ W)
-- 2 × Zone EOL resistors (4.7 K, 5%, ½ W)
-- 1 × Battery jumper wire
-- 1 × EGND terminal ring
-- 1 × EGND KEP nut
• Door keys (taped to outside of cabinet)
FA-262 Installation & Operator’s Manual
All components described above are factory assembled into the enclosure.
2.2 Optional Accessories
Model NumberNameDescription
Provides 3 relays that are jumper programmable to activate on
RM-263Relay module
UDACT-286Dual line dialer
MR-2844ProgrammerHandheld programmer for the UDACT-286 DACT.
RTI-265
RAM-265
Remote trouble
indicator
Remote trouble
indicator and alarm
indicator
common ‘alarm’, ‘supervisory’ or ‘trouble’. Mounts inside the
enclosure and plugs into the main board.
Communicates all alarms, supervisory and trouble conditions to a
Central Station using Contact ID, SIA or 10/20 BPS communication
formats. Programmable using the MR-2844 handheld programmer.
Mounts inside the enclosure and connects to the main panel using a
supplied 4-wire cable with connector.
Single gang plate complete with common trouble buzzer, trouble
visual indicator, ‘AC on’ visual indicator and a trouble silence / lamp
test switch. Mounts remotely to a single gang electrical box and is
connected to the main panel via the 4-wire ‘secur-bus’.
Two gang plate complete with common trouble buzzer, trouble
visual indicator, ‘AC on’ visual indicator and a trouble silence / lamp
test switch and red zone alarm visual indicators and yellow zone
supervisory indictors. Mounts to a standard 2 gang electrical box
and is connected to the panel via the 4-wire ‘secur-bus’.
3
FA-262 Installation & Operator’s Manual
Figure 1: FA-262 cabinet
with door closed
Figure 2: FA-262 display and controls
Figure 3: FA-262 Cabinet Overview
Figure 4: Zone Label
Insert
2.3 FA-262 Overview
CPU
FAULT
A zone label insert is installed in the zone window area. Reach behind
the display/control panel and remove the blank insert. Zone designations
can be written directly on the insert or can be created using Word for
Windows, printed on Avery label #5167 and applied to the insert.
Zone Label Insert
Note: Use Security Screw(SPAENAUR #381-064)
provided to meet UL 864 Rev 9 requirement
4
FA-262 Installation & Operator’s Manual
2.4 Planning Your Installation
Note:This system should be installed and serviced by qualified fire alarm installation professionals.
As a minimum, the following points should be considered to ensure that the installation will be successful and
proceed without delay.
•Consult with your local AHJ to ensure that the overall system will meet all requirements. Have your plans
reviewed and approved as required.
•Review the electrical specifications, mounting and wiring instructions in this manual and in the manuals of
all connected modules and devices.
•Using the chart in this manual, calculate the standby battery size that will meet the standby time required.
Include all components that will draw current from the standby battery when the panel is in the ‘standby’
mode.
•Determine the location of the control panel, all initiating and indicating devices and remote modules and
mark them on your system layout plan. An indicating device must be located in close proximity to the control
panel.
•Using the charts in this manual, determine the wire gauge and wire run distances for the connected
components. (initiating devices, indicating devices and ‘secur-bus’ connected components.)
•Review the programming section of this manual and determine the operating characteristics required of the
initiating zones, indicating zones and common panel features.
2.5 Electrical Specifications
CircuitRating
Primary AC
AUX+
SCOM 500 mA maximum (current sink)
COM500 mA maximum (current sink)
Relays (common alarm &
trouble)
NAC Outputs
Initiating Zone Inputs
Battery Charging Current270mA maximum
Low Battery Trouble
120 volts, 60 Hz. 1.5 Amps maximum/240 volts, 50 Hz. 1.0 Amps
maximum
500 mA maximum ~ Restoral of Aux Power Shorts requires removal of
all Aux Power loading
Form ‘C’ contact, 2 Amp, 30 V
24 volts, full-wave rectified DC, 1.5 Amps max. – Power limited. (3.0
Amps total for both NAC circuits) EOLR – 4.7K ohm, ½ W, 5%
DC, 60 mA max.(in alarm) – Supervisory current: 6.0 mA – max.
24 V
Loop resistance: 100 ohms max. – EOLR: 4.7 K ohm, ½ W, 5%
Low Battery Trouble: 22.0 V
Low Battery Trouble Restore: 23.0 VDC
Critical Shutdown: 19±0.5 VDC
DC resistive, power limited source
DC
5
FA-262 Installation & Operator’s Manual
2.6 Module Current Ratings
Max. Alarm
Current (mA)
DC
Module
Standby Current
(mA) DC
Alarm Current
(mA) DC
FA-262Control panel90425(*)485
RTI-265 Remote trouble
indicator
RAM-265 R.T.I. and remote 5
zone annunciator
151515
1520(*)40
UDACT-286 DACT456060
RM-263 Relay module(**)02424
Note:*Current noted assumes ONE initiating zone is in alarm. The “Max. Alarm Current” assumes all
zones are in alarm.
**Values shown are for all relays set for activation on ‘Alarm’. Each relay set for activation on
‘trouble’ is normally energized and on ‘AC fail’ will draw 0 mA.
2.7 Standby Battery calculation chart
All components that draw current from the panel while it is in the ‘standby’ mode (AC OFF) must be
considered for the standby battery calculation. All components that draw current while in the ‘Alarm’ mode
must be considered for the alarm battery calculation.
1. The control panel will always draw the currents as shown in the chart.
2. Typically the alarm current is calculated assuming only one initiating zone is in alarm. If it is required that
more than one zone be considered, add 60 mA per zone in the Alarm column. Consult the smoke detector
manufacture’s installation sheet to determine the standby current of these devices. Write that number in
the ‘current per device’ column then multiply that number by the number of devices on the zone. Repeat for
each zone.
3. Consult the Notification Appliance installation sheet to determine the current draw for each device
connected to the NAC. For each NAC, calculate the total current in alarm and put that number (mA) in the
‘Alarm’ column.
Note:Each NAC can supply 1.5 Amps max.
4. For each added module in the system, multiply the number of modules times the module ‘standby’ and
‘alarm’ currents and write those totals in the ‘standby’ and ‘alarm’ columns.
5. Add up all the current drawn from the AUX+ output in the standby and alarm mode and put those totals in
the ‘standby’ and ‘alarm’ columns.
6. Add up all the currents in the ‘standby’ column and the ‘Alarm’ column.
7. Convert the ‘standby’ and ‘alarm’ currents from mA to Amps. (divide mA by 1000)
8. Write in the ‘standby’ time required. (24 or 60 Hr.)
9. Multiply the ‘standby’ Amps times the ‘standby’ time to get the ‘standby’ Amp-Hr. required.
10.Write in the ‘alarm’ time required in hours. (5 min. =.08 Hr.; 30 min. =0.5 Hr.)
11. Multiply the ‘alarm’ Amps times the ‘alarm’ time to get the ‘alarm’ Amp-Hr required.
12.Add the ‘standby’ Amp-Hr. to the ‘alarm’ Amp-Hr. for the total Amp-Hr. required.
13.Multiply the total Amp-Hr. times 1.20 for the minimum Amp-Hr. battery required to support the system for
the selected ‘standby time and the selected ‘alarm’ time.
Total Amp-Hr = standby Amp-Hr (9) + alarm Amp-Hr. (11):Amp-Hr.
Multiply the total Amp-Hr. by the safety margin:1.20
Total battery Amp-Hr required to support the system:
Note:Select a battery with an Amp-Hr. rating that is equal to or larger than the calculated minimum Amp-
Standby:0x=
Alarm:24x
Standby:x=
Alarm:x=
(0.08 or 0.5):
Hr.
Amp-Hr.
Hr. battery required.
7
FA-262 Installation & Operator’s Manual
3.0 Installing the FA-262 Fire Panel
3.1 Environmental Specifications
Consider the following conditions when selecting a mounting location for the FA-262 panel:
•Operating temperature: 32°F to 122°F / 0°C to 50°C
•Humidity: 95% RH non-condensing
•Close to a source of unswitched AC power
3.2 Panel Assembly and Modules Locations
The panel comes completely assembled from the factory. Remove the lower dead front for access to the
battery compartment. Remove display control panel for access to AC connections.
Figure 5: Panel Assembly and Modules Locations
Primary AC
240V 50Hz
120V 60Hz
N
GND
8
3.3 Mounting the FA-262
Dimensions in inches
Figure 6: Mounting Dimensions
FA-262 Installation & Operator’s Manual
Figure 7: Knockout Locations
9
FA-262 Installation & Operator’s Manual
4.0 Wiring the FA-262
4.1 Wiring Specifications
Figure 8: FA-262 Terminal Descriptions
Terminal
Label
NAC 1
(+, –)
NAC 2
(+, –)
AUX+
COM
SCOM
Description
Notification Appliance Circuit # 1
24 V
DC, Full-Wave Rectified voltage, 1.5 Amps max.
Programmable as Steady or Temporal output on alarm.
Supervised for opens, shorts and ground fault.
Power limited.
Notification Appliance Circuit # 2
24 V
DC, Full-Wave Rectified voltage, 1.5 Amps max.
Programmable as Steady or Temporal output on alarm.
Supervised for opens, shorts and ground fault.
Power limited
Auxiliary power output
24 V
DC, filtered and regulated, 500 mA max., 400 mV P-P ripple, power limited. Aux
power shorts must be restored by removing all Aux Power loading.
Auxiliary common power return, unswitched
24 V
DC, 500 mA max.
Auxiliary common power return, switched
(open circuit on system reset or on 4-wire smoke detector reset)
DC, 500 mA max. (Please refer to Appendix A for compatible 4-wire smoke
24 V
detectors.)
DATData line for remote module communications
CLKClock line for remote module communications
TRB NOCommon Trouble relay, Normally Open contact
TRB CCommon Trouble relay, Common contact
Common Trouble relay, Normally Closed contact
TRB NC
The Common Trouble relay is normally energized and is de-energized on trouble.
Contacts are shown in the de-energized state.
Contacts are rated 30 V
ALM NOCommon Alarm relay, Normally Open contact
ALM CCommon Alarm relay, Common contact
10
DC, 2 Amps.
FA-262 Installation & Operator’s Manual
Terminal
Label
Description
Common Alarm relay, Normally Closed contact
ALM NC
The Common Alarm relay is normally de-energized.
Contact is shown in the de-energized state.
Contacts are rated 30 V
DC, 2 Amps max.
Z1+Zone 1 positive input
Zone 1 negative input
DC nominal to power 2-wire smoke detectors. Maximum current
Z1-
Zone output is 24 V
draw is 60 mA in alarm and is limited by the zone circuitry. Zones may be configured to
monitor both 2-wire smoke detectors and initiating devices that employ dry contacts.
(manual stations & heat detectors)
Z2+Same as zone 1 positive
Z2-Same as zone 1 negative
Note: For each supervised installation wire, a separate terminal must be used.
* See “9.0 Appendix: Table of Compatible Smoke Detectors” on page 33 in this manual for a list of
compatible 2-wire smoke detectors
1. Maximum 30 smoke detectors per zone (100 µA each standby).
2. Manual station, heat detector.
3. Maximum total loop wire resistance = 100 ohms.
4. Program zone as:
Type 1 - Smoke and contact devices instant alarm (default)
Type 2 - Smoke auto-verify and contact as instant.
11
FA-262 Installation & Operator’s Manual
Figure 10: Connecting 4-Wire Smoke Detectors
1. Program as zone type 01, instant alarm.
2. Maximum total loop wire resistance is 100 ohms.
Zone Wiring Chart:
Wire
(Gauge)
187,6902,345
1612,1953,717
1419,2305,861
Distance
(feet)
Distance
(meters)
Maximum loop resistance is
100 ohms. Maximum current
in alarm is 60 mA.
4.2 Connecting NAC Devices (Class ‘A’ and Class ‘B’)
Figure 11: Connecting NAC Devices (Class ‘B’)
Figure 12: Connecting NAC Devices (Class ‘A’)
12
NAC Wiring Chart
240V 50Hz
120V 60Hz
GND
N
Primary AC
Note: The wire gauges must be
no less then the size required by
the Canadian Electrical Code
C22.1, Part 1, Section 32.
FA-262 Installation & Operator’s Manual
Maximu
m Total
Loop
(ohms)
Maximu
m
Current
(A)
18-Awg
Wire
16-Awg
Wire
14-Awg
Wire
ftmftmftmftm
8.000.256151889782971,5384692,500762
5.000.50308944881497692351,250381
2.700.752056332599513156833254
2.001.001544724474385117625191
1.601.25123381955930894500152
1.301.50103311635025678417127
Note: This chart is based on a minimum source voltage of 22 volts and a maximum line loss
of 2 volts thus leaving a minimum of 20 volts at the last notification appliance.
Figure 13: Connecting Batteries
12-Awg
Wire
Figure 14: Connecting AC Power
13
FA-262 Installation & Operator’s Manual
Figure 15: Connecting the Alarm and Trouble Relays
Figure 16: Connecting Optional Devices
See installation sheets for the remote devices for
detailed wiring and address setup.
1. Maximum of 4 MR-2605-T per panel.
2. Maximum of 4 MR-2605-AT per panel.
Secur-bus Wiring Chart
Current
(mA)*
152,5247696,4101,95410,1603,09816,0004,878
301,2623843,2009765,0801,5498,0002,439
458422562,1356513,3851,0325,3401,628
606311921,6004882,5407744,0001,220
755051541,2803902,0306193,200976
904211281,0653251,6905152,670814
1053611109152791,4504422,285697
120315968002441,2703872,000610
135281867102161,1253431,780543
150252776401951,0153091,600488
165229705801779202801,455444
180210645301628452581,335407
195194594901497802381,230375
22-awg Wire18-awg Wire16-awg Wire14-awg Wire
ftftftmftmftm
210180554551397252211,145349
225168514251306752061,065325
*See module current ratings chart for current drawn by each module attached to the securbus.
14
FA-262 Installation & Operator’s Manual
To calculate the wire run distance for any gauge wire and any maximum current value, use the following
formula:
1.25
Remix =
Immix
ohms
Amps
Remix × 1,000
Distance =
2(wire resistance in ohms per 1,000
feet
feet)
Secur-bus Capacitance
Maximum wire capacitance for proper operation of the Secur-bus is 90 nF (nanofarad). Typical wire
capacitance for 22 awg quad cable is 20 nF per 1,000 feet. Thus, for 22 awg quad cable, the maximum wire
run distance is ((90/20)× 1,000) = 4,500 feet. Other types of wire have different capacitance values. Consult
the wire manufacturer’s data sheets for typical capacitance values.
Note:Shielded wire has a much higher capacitance value and distances are severely reduced.
The following devices may be connected to the Secur-bus. All devices are supervised. See section for adding
and deleting devices on the Secur-bus.
DevicesDescription
MR-2605-T
MR-2605-AT
MR-2806
External to control panel.
Up to 4 of each device may be connected.
Mounted inside control panel. See diagram in “3.3
Mounting the FA-262” on page 9.
1. Do not run the Secur-bus adjacent to sources of high transient noise such as AC wiring, telephone cable bundles or computer wiring.
2. If the Secure-bus must go through a high transient area, use shielded cable.
3. If shielded cable is used, the distances in the chart above are cut in half.
15
FA-262 Installation & Operator’s Manual
5.0 Panel Operation
5.1 Operating Sequences
This section describes how the panel functions under various conditions. The choices you make in panel
programming will also affect how the panel operates. Please see for information on how to program the panel,
and descriptions of each of the programming options.
5.2 General Zone Fire Alarms
Zone alarms have priority over all other annunciation. When an alarm occurs, the following happens:
•The corresponding zone alarm LED begins flashing, the common alarm LED turns on steady, and the alarm
relay turns on.
•If a trouble was present on that zone then the zone trouble LED turns off. If the trouble buzzer is audible
then it also turns off.
•The NACs sound in a steady or temporal pattern, depending on the option selected (see “NAC Temporal/
Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25).
•If enabled, the silence inhibit timer begins counting down (see “Signal Silence Inhibit Timer” on page 26). If
the silence inhibit timer is enabled, the panel cannot be silenced for 60 seconds following the first fire alarm.
Subsequent fire alarms do not restart or extend this timer. While the signal silence inhibit timer is counting
down, if the Silence Alarm button is pressed the panel will sound a 1 second ‘error tone’ on the common
trouble buzzer.
•The NACs remain on until silenced with the Silence Alarm button, or if the automatic alarm silence is
enabled, until the thirty minute bell timer runs out (see “Automatic Signal Silence” on page 25). If the
automatic silence timer is enabled, the panel will automatically silence the NACs 30 minutes after the last
fire alarm. Each zone alarm will restart the timer, giving a full 30 minutes after the last alarm before the NACs
are silenced.
• Once the NACs are silenced the signals silenced LED turns on and any flashing zone alarm LEDs turn on
steady. The common trouble LED and trouble relay also turn on and, if the NACs have been silenced
automatically, the buzzer will sound at a rate of ½ second ON/OFF.
Note:A manual signal silence will not initiate the trouble buzzer. Only the common trouble LED and
signals silenced LED are turned on.
•Any additional zone alarms that occur while the panel is in alarm will reset the auto alarm silence timer and
turn on the NACs, but the panel will not restart the 60 second silence inhibit timer.
•The zone alarm LEDs, common alarm LED and alarm relay will remain on steady until a system reset is
performed.
5.3 Waterflow Alarms
If the Waterflow Silence option is turned off (see “Silence Waterflow Alarms” on page 26), when a waterflow
zone (type 03) initiates an alarm the NACs cannot be silenced until all waterflow zones are returned to normal.
If all waterflow zones return to normal after the 30 minute automatic signal silence timer has expired, then the
panel will silence the NACs.
If the Waterflow Silence option is turned on, then an alarm on a waterflow zone is treated like any other fire
alarm.
Waterflow alarms may be delayed by 60 seconds to prevent false alarms from surges in the sprinkler system.
The delay is common to all zones programmed as ‘waterflow’, type 03 zones. If the delay is not used, all
waterflow alarms will be instant.
16
FA-262 Installation & Operator’s Manual
5.4 Supervisory Zone Alarms
When an alarm occurs on a supervisory zone (type 04), the corresponding zone supervisory LED begins
flashing. The common supervisory LED and supervisory relay (supervisory relay is optional) turn on steady,
and the buzzer turns on steady. If there was a trouble on that zone, the zone trouble LED turns off. The buzzer
remains on until the trouble silence button is pressed. Once the buzzer is silenced any flashing zone
supervisory LEDs turn on steady. The zone supervisory LEDs, common supervisory LED and supervisory
relay remain on steady until a system reset is performed.
Subsequent Fire Supervisory
After silencing a fire supervisory, a subsequent fire supervisory from another zone will resound the trouble/
supervisory buzzer and the new zone supervisory LED flashes until the Silence Trouble button is pressed.
Supervisory / Trouble Priority
If a supervisory zone has a trouble and it goes into alarm, the zone trouble LED is extinguished until that zone
is restored and the panel has been reset. The common trouble LED will remain on steady until all supervisory
alarms have been restored and the panel reset. All other ‘common’ trouble indicators will operate normally.
Supervisory / Fire Alarm Priority
The supervisory zone LED, the common supervisory LED and the buzzer (in the steady supervisory mode)
function normally whether there is a fire alarm present or not.
5.5 Trouble Operation
When a trouble occurs, if there is a corresponding trouble LED it turns on steady. The common trouble LED
and the trouble relay also turn on. If no alarm is present on the system, the buzzer will sound at a rate of ½
second ON/OFF. The buzzer and trouble LEDs will remain on until the trouble is restored. If the Silence
Trouble button is pressed, the buzzer turns off. Subsequent troubles will resound the trouble buzzer.
Note:If there is no trouble present in the system then pressing the Silence Trouble button will result in a
1 second error tone.
Please see the following table for a list of system faults that will initiate a trouble.
17
FA-262 Installation & Operator’s Manual
System Troubles
System faults
Alarm zone open circuit – loss
of EOLR
NAC open circuit or short
circuit
Battery low voltage or
disconnected
Signals silenced automatically
Ground on extended
conductor
AC fails completely, or is low
for more than 10 seconds
(brownout)
Common
Trouble
LED
turns on
turns on
turns on
turns on
turns on
turns on
Buzzer
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
Trouble
Relay
deactivates
Other Indicators
Zone trouble LED
turns on steady
NAC1 or NAC2
deactivates
trouble LED turns
on
deactivates
deactivates
deactivates
Battery LED turns
on
Signals Silenced
LED turns on
Ground LED turns
on
deactivatesAC LED turns off
Installer Programming Mode
Active
flashes
Loss of Remote Trouble Unit turns on
Loss of Remote Alarm/
Trouble Unit
TLM on one or both
telephone lines (Dialer)
Failure to communicate
(Dialer)
turns on
turns on
turns on
Unsuccessful system resetturns on
Loss of Dialer moduleturns on
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
sounds ½
second on/
off
deactivatesAC LED turns off
deactivates
deactivates
deactivates
deactivates
deactivates
deactivates
18
FA-262 Installation & Operator’s Manual
5.6 System Reset Operation
To reset the system, press the ‘Reset System’ button. The panel will remove all power from the zones and the
switched auxiliary relay for 10 seconds. During this 10 second period, the buzzer will beep twice every 2
seconds.
The panel can only be reset if:
•the NACs have been silenced
•the supervisory buzzer has been silenced
•and all waterflow zones are restored (only applies if the Silence Waterflow option is turned off - see “Silence
Waterflow Alarms” on page 26).
If the panel is not in a condition to be reset, when the ‘Reset System’ button is pressed the panel will sound a
1 second error tone on the buzzer.
After the 10 second reset period, the panel will turn off the zone LED for any zones that have been restored. If
one or more zones is still in alarm after the reset period, the panel will activate the NACs as programmed. If
there are no alarms but one or more Supervisory zones is still ‘off-normal’ after the reset period, the panel will
sound the trouble buzzer in the Supervisory mode. If there are no alarms or supervisory conditions but a
trouble is present in the panel after the reset period, the panel will sound the trouble buzzer. After the reset
period, LEDs for any alarms, supervisory off-normal or trouble conditions will be on.
5.7 Lamp Test
The lamp test will check all of the panel and annunciator LEDs. To do a lamp test, press and hold the Lamp
Test button. All the LEDs will flash.
A lamp test will only work if the NACs are not active and the supervisory buzzer is not active. If a lamp test is
unsuccessful the buzzer will sound a 1 second error tone. If any trouble or zone has a state change during
lamp test, the lamp test will be cancelled and the panel will return to normal operation.
19
FA-262 Installation & Operator’s Manual
5.8 Walk Test (Installer function only)
To do a walk test, all zone alarms, troubles and relays must be in their normal state. You can program the walk
test to be either audible or silent (see “Audible Walk Test” on page 26).
1. To walk test the panel press the Walk Test button. The common trouble LED flashes and the buzzer
sounds one short beep. The panel will be in walk test mode for one hour, or until you press the Walk Test
button again.
2. As you test each part of the system, the panel will give the following indications:
Type of activationLEDsNACs*
Fire Alarm or Fire
Supervisory
Fire Alarm or Fire
Supervisory Restoral
Zone alarm/
Supv LED
turns on
Zone alarm/
Supv LED
turns off
1 squawk
1 squawk
Zone or
Zone or System Trouble
system
trouble LED
2 squawksSounds
turns on
Zone or
Zone or System Trouble
Restoral
system
trouble LED
2 squawks
turns off
Ground
Ground Fault
trouble LED
3 squawksSounds
turns on
Ground
Ground Fault Restoral
trouble LED
3 squawks
turns off
Trouble
Buzzer
Stops
sounding
Stops
sounding
*Only if Walk Test Audible option is turned on.
Zone LEDs operate normally except that alarms do not latch - the alarm LEDs will turn off when the zone is
restored and the auto-reset has been successful.
Alarm and trouble relays are NOT activated. If used, any remote connection is not activated.
3. To return the system to normal operation, press the Walk Test button. If you do not press the Walk Test
button, the system will return to normal operation after one hour. If any zones are in alarm at the end of the
walk test, the zones will indicate silenced signals.
Note:The Lamp Test button does not work while the panel is in Walk Test mode.
Walk Test Function available without AC power.
20
FA-262 Installation & Operator’s Manual
5.9 NAC operation
See also “NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25, and “NAC
Auto-silence and Strobe Programming - Section 2 (‘NAC2’ LED on steady)” on page 25 for more information.
Class ‘B’ operation selections:
•Steady (default) – On alarm the NAC will turn on steady. It will turn off on either a manual or automatic
signal silence.
•Temporal 3 – On alarm the NAC will turn on with the temporal 3 pattern and turn off on either a manual or
automatic signal silence.
•NAC2 Strobe – On alarm NAC2 will turn on steady. It will not turn off on a manual or automatic signal
silence. NAC2 set in this mode will only turn off on system reset if all zone fire alarms are restored. Only
NAC2 can be set in this mode.
Class ‘A’ operation selections
If the panel NACs are set for class ‘A’ operation then there is only one NAC. In this configuration the NAC
output can only be set for steady or temporal using the NAC1 programming options For class ‘A’, the NAC2
Strobe option is not available.
5.10 Relay Function
Alarm Relay
The panel activates the alarm relay upon any (non-supervisory) zone alarm. The panel deactivates the alarm
relay upon a successful system reset.
Trouble Relay
The panel deactivates the trouble relay upon any system trouble. The panel activates the trouble relay upon
the restoral of all system troubles.
Supervisory Relay (available with the MR-2602-R3 Relay Expander only)
The panel activates the supervisory relay upon any supervisory zone alarm. The panel deactivates the
supervisory relay upon a successful system reset.
21
FA-262 Installation & Operator’s Manual
6.0 Programming the FA-265System
6.1 How to Program the FA-265
You can program the panel using the controls and indicator LEDs. There are no DIP switches to set for
programming.
Once programmed, the operating modes selected are maintained in non-volatile memory that will retain the
programmed information even if all power is removed from the panel.
Entering the Programming mode
Note:All zone alarms must be reset prior to entering the programming mode. While the panel is in
programming mode, the annunciators will show a trouble condition.
1. Remove the lower front cover and locate the ‘Walk Test Switch’ behind the control panel PCB, as shown
below.
Figure 17: Locating the Walk Test Switch
2. Press and hold the Walk Test Switch for two seconds. The common trouble buzzer and common trouble
LED turn on and pulse ½ second on/off.
3. Press any button. The trouble buzzer is silent, and the zone 1 alarm LED turns on steady. The common
trouble LED continues to flash.
4. The panel is now ready to program.
Programming the Panel
The control panel has six different programming sections, which are shown in the table below. The Panel
Status LEDs indicate which programming section you are currently in.
22
FA-262 Installation & Operator’s Manual
When you first enter programming mode, the panel will be at zone programming (section 0). Each
programming section has one or more programming sub-sections (e.g. section 0 has sub-sections for zones 1
through 5). Use the Silence Trouble and Silence Alarm buttons to enter your programming choices:
1. Each sub-section in a section will have 2 or more programming settings, indicated by the panel Zone
Supervisory and Zone Trouble LEDs. To scroll through the programming settings, press the Silence Alarm
button. Please see “6.2 Programming Section Descriptions” on page 24 for descriptions of each section
and settings, and the LED indications for each setting.
2. When the LEDs show the setting you want for a sub-section, move to the next programming sub-section
by pressing the Silence Trouble button. The panel will save the indicated settings when you exit the
programming mode or go to the next programming section.
3. When you have programmed all the sub-sections in a section, the panel will move to the next programming
section when you press the Silence Trouble button.
Note:Pressing Silence Trouble will advance forward through each programming sub-section, and each
section.
Example: in the Zone 1 programming sub-section, pressing Silence Alarm will scroll through each zone type
setting (null zone, instant zone, auto-verify zone, etc.). When the panel shows the zone type you want for
zone 1, press Silence Trouble to move on to Zone 2 programming.
Exiting the Programming Mode
When you come to the end of all the programming sections, press Silence Trouble to exit the programming
mode.
To exit programming mode at any other point in the panel programming, press and hold the Walk Test switch
for two seconds.
Note:If 5 minutes elapse without any button presses, the panel will automatically exit the programming
mode. During the final 60 seconds before the exit, the panel will sound a warning tone on the
buzzer. Press any button to cancel the auto-exit and resume programming.
After you exit the programming mode, the panel performs a system reset for 10 seconds, during which the
buzzer sounds double beeps. When the beeping stops the panel returns to normal operating mode and all
programming choices are stored in memory.
23
FA-262 Installation & Operator’s Manual
6.2 Programming Section Descriptions
Zone Programming (Section 0)
In this zone programming section, the panel uses the zone alarm, supervisory, and trouble LEDs to
indicate the programming as follows:
CPU
FAULT
Zone type 00 – Null zone (Not used)
The zone is not used. The zone is not supervised, alarms and troubles are
ignored. The end-of-line resistor is not required.
Zone type 01 – Instant alarm for 2-wire smoke detectors and contact devices
Zone type 01 does not differentiate between 2-wire smoke detectors, contact
devices, or 4-wire smoke detectors. When a 2-wire smoke detector, 4 –wire
smoke detector or contact device goes into alarm:
1. The panel goes into alarm without any delay. If an instant zone goes into
alarm, any auto-verify sequence in progress on another zone will be
immediately cancelled and both zones will indicate an alarm condition.
Zone type 03 – Waterflow zone
This zone type is intended for waterflow alarm initiating contact devices only.
Do not mix other alarm initiating devices on this zone. For Waterflow delay,
use actuating devices with a built-in delay of 30 seconds or more. The overall
maximum waterflow alarm initiation delay allowed is 90 seconds. (NFPA A-5-
6.2 – 1996 edition) When the contact on a Waterflow alarm initialing device is
activated the control panel will go into alarm instantly.
Zone type 04 – Supervisory zone
When the contact on a Supervisory device is initiated:
1. The control panel will immediately indicate the Supervisory “off-normal”
condition.
2. The zone supervisory LED (yellow) will flash, the common ‘supervisory’
LED will come on steady and the common trouble buzzer will sound
steadily. Pressing the ‘trouble silence’ switch will silence the buzzer and
the zone supervisory LED will stop flashing and turn on steadily.
3. Fire supervisory zones are latching and can only be restored when the
initiating device is restored and a system reset is performed.
24
FA-262 Installation & Operator’s Manual
NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)
You can individually program both NAC1 and NAC2 to sound in either a temporal or steady pattern. By
default, both NAC outputs are programmed as steady.
Temporal
The NAC1 will sound the Temporal/ANSI Fire Pattern: 0.5 seconds ON, 0.5
seconds OFF, 0.5 seconds ON, 0.5 seconds OFF, 0.5 seconds ON, 1.5
seconds OFF, repeat.
The NAC2 will sound the Temporal/ANSI Fire Pattern: 0.5 seconds ON, 0.5
seconds OFF, 0.5 seconds ON, 0.5 seconds OFF, 0.5 seconds ON, 1.5
seconds OFF, repeat.
Steady
The NAC1 will sound continuously.
The NAC2 will sound continuously.
NAC Auto-silence and Strobe Programming - Section 2 (‘NAC2’ LED on steady)
Automatic Signal Silence
If Automatic Signal Silence is enabled, 30 minutes after the last fire alarm on
the system, the panel restores the NACs to normal (alarms are silenced).
If another alarm occurs after the NACs are silenced, the panel will restart the
timer for another 30 minute period.
If Automatic Signal Silence is disabled, the panel will not silence the NACs
automatically.
NAC2 Strobe
If this option is enabled, on alarm, NAC2 turns on steady and does not turn
off on automatic signal silence, or when the Silence Alarm button is pressed.
When NAC2 is set to this mode, it can only be turned off when all zone fire
alarms are restored, and the system is reset. Only NAC2 can be set to this
mode.
If this option is disabled, the panel will restore NAC2 to normal following an
automatic signal silence (see Automatic Signal Silence, above), or following
a press of the ‘Silence Alarm’ button.
25
FA-262 Installation & Operator’s Manual
Silence Inhibit and Walk Test Programming - Section 3 (‘Battery’ LED on steady)
Signal Silence Inhibit Timer
If the Signal Silence Inhibit Timer is enabled, when the first alarm is
activated, the panel will begin a 60 second countdown. During this 60
seconds, users will not be able to turn off the NACs by pressing the Silence
Alarm button. The timer is started on the first alarm only and is not restarted
on subsequent alarms.
If the Signal Silence Inhibit Timer is disabled, users will be able to turn off the
NACs at any time, by pressing the Silence Alarm button.
If NAC2 is set as a strobe, users will never be able to turn off NAC2 using the
Silence Alarm button. See “NAC2 Strobe” on page 28.
Audible Walk Test
You can set the One Man Walk Test to be either audible or silent. If the One
Man Walk Test is set for audible, then the following will occur:
•On a fire or Supervisory alarm/restoral the bells will pulse ONCE
•On a zone or system trouble/restoral, except ground fault, the bells will
pulse TWICE
•On any ground fault/restoral the bells will pulse THREE times.
If the One Man Walk Test is set for silent, the bells will not sound during the
walk test.
Waterflow Programming - Section 4 (‘Ground Fault’ LED on steady)
Silence Waterflow Alarms
If the Silence Waterflow Alarms option is turned on, Waterflow zones can be
silenced whether the zones are physically restored or not.
If the Silence Waterflow Alarms option is turned off, Waterflow zones cannot
be silenced until they are physically restored. This applies to both automatic
signal silence, and the Silence Alarm button. If there is a trouble on a
Waterflow zone following the alarm and alarm restore, the zone can be
silenced.
26
50/60 Hz Option - Section 5 (‘Signals Silence’ LED on steady)
1. Enter the installer programming mode, section 0
2. Press and hold the System Reset button for 2 seconds. The Z1 ALM
LED and TRB LED will be ON and all the System Trouble LEDs will
flash.
To Remove Module
Physically remove the module from the system and enter the reset section
programming as described above. Press the ‘Silence Alarm’ button until the
Z1 SUPV LED is ON. Press the ‘Silence Trouble’ button to exit this section.
Upon exit, the system will reset the ‘supervision’ field for all the modules
currently connected to the ‘secur-bus’.
To Add a Module
Just connect it to the system and it will auto-enroll within one minute.
FA-262 Installation & Operator’s Manual
To Default the System
ALARM
Do not
default (Z2)
(Factory default
Default to factory
program (Z2)
SUPV TRB
)
Enter the reset section programming as described above. Press the ‘Silence
Trouble’ button until the Z2 ALM LED is ON and Z2 TRB LED is ON. Press
the ‘Silence Alarm’ button until the Z2 SUPV LED is ON. Press the ‘Silence
Trouble’ to exit this section. Upon exit, the system will reset all of the panel
programmable parameters to their factory default state. Please note that the
‘supervision’ field will be reset as well.
6.3 Viewing the Event Buffer
1. Enter the programming mode by pressing and holding the Walk Test switch for 2 seconds.
2. Press any switch. To silence the trouble buzzer and enter the Section 0 programming.
3. Press and hold the Lamp Test switch for 2 seconds.
4. The Common Supervisory LED flashes to indicate the View Buffer mode.
5. Events are shown from the most recent to the oldest.
6. See the event table below which indicates the LED patterns used to indicate various events.
7. To advance to the next event press the Silence Trouble switch.
8. Once all 20 events have been viewed, the next Silence Trouble keypress will exit the view buffer mode
and return to the Section 0 programming. To exit the programming mode, press and hold for 2 seconds the
Walk Test switch.
9. Pressing the Silence Signal switch at any time will cause the system to exit the View Buffer mode. The
buzzer will sound. Press any button to go to the Section 0 programming mode.
27
FA-262 Installation & Operator’s Manual
Event Buffer Table
DisplayEvent
Steady Common Alarm LEDNull Event
Flashing Zone X Alarm LEDVerified Zone X Alarm
Steady Zone X Alarm LEDVerified Zone X Alarm Restore
Flashing Zone X Alarm LED and Flashing Zone X
Supervisory LED
Unverified Zone X Alarm
Flashing Zone X Supervisory LEDZone X Supervisory
Steady Zone X Supervisory LEDZone X Supervisory Restore
Flashing Zone X Trouble LEDZone X Trouble
Steady Zone X Trouble LEDZone X Trouble Restore
Flashing Common Trouble LEDExpansion Module Fault
Steady Common Trouble LEDExpansion Module Fault Restore
Flashing NAC1 Trouble LEDNAC 1 Trouble
Steady NAC1 Trouble LEDNAC 1 Trouble Restore
Flashing NAC2 Trouble LEDNAC 2 Trouble
Steady NAC2 Trouble LEDNAC 2 Trouble Restore
Flashing Battery Trouble LEDBattery Trouble
Steady Battery Trouble LEDBattery Trouble Restore
Flashing Ground Fault LEDGround Fault Trouble
28
Steady Ground Fault LEDGround Fault Restore
Flashing Signal Silenced Trouble LEDManual Signal Silence
Steady Signal Silenced Trouble LED(Successful) Reset
Flashing AC On LEDAC Failure
Steady AC On LEDAC Fail Restore
Steady AC On LED and Steady BAT TRB LEDCold Start
Flashing AC On LED and Flashing BAT TRB LEDWarm Start
Flashing (ALL) Zone Trouble LED’sWalk Test Start / Installer Mode Entry
Steady (ALL) Zone Trouble LED’sWalk Test End / Installer Mode Exit
FA-262 Installation & Operator’s Manual
7.0 Startup of the FA-265
7.1 Prior to power up
•Verify that all field wiring is free of shorts, opens and grounds and that end-of-line devices are connected
and are the proper value.
•Verify that all modules and internal cables are properly seated in their location.
•Verify that all metal components are bonded to the incoming ground. Should measure zero ohms between
any metal part and the incoming ground wire.
•Verify that the polarity between the panel and connected devices is correct.
7.2 Power up sequence
•Connect the AC power first before battery.
•The panel goes into the Reset mode immediately. This lasts for 10 seconds and the trouble buzzer will beep
during the reset period.
•After the reset period ends, the buzzer goes silent, the green AC indicator should be ON and all other LEDs
should be OFF.
•If any LED other than the AC LED is ON then there is a fault in the system. Troubleshoot and repair the fault
before proceeding.
•If the battery is not fully charged, the battery fault LED will come on after about 2 minutes. Verify that the
battery is connected properly and if it is, it may take up to 24 hours to recharge the batteries. Once the
battery is charged, the battery fault LED will go OFF.
7.3 Default Operation
•On first power up, all programmable features will be in the default mode.
•Do a ‘Lamp Test’ to verify that all the indicators function.
•It is suggested that an initial verification of operation be done before the panel is programmed. Verify that
each zone will go into alarm and that each NAC operates the Notification Appliances and that the zone
alarm indicator(s) function. Each zone is defaulted as an instant ‘fire alarm’ and each NAC is defaulted for
‘steady’ output on alarm. An Alarm, Silence, Reset cycle will also verify that the push-button function
properly.
•Verify that each zone indicates a trouble on a zone open and that a ground fault on the extended
conductors is properly indicated.
7.4 Programming the Panel
•Program the panel for the operational features desired. (section 6)
•Record your configuration choices for future reference. (section 8)
•Verify panel operations and feature selections by initiating alarms and troubles as described above.
7.5 Final Verification
•Verify system operation and fault detection as required by the local Authority Having Jurisdiction.
•Enable the ‘one-man’ walk test feature to test all the field devices and wiring.
29
FA-262 Installation & Operator’s Manual
8.0 Programming Worksheets
8.1 Entering Programming Mode
Please see “6.0 Programming the FA-265 System” on page 22 for complete instructions.
Note:All zone alarms must be reset prior to entering the programming mode. While the panel is in the
programming mode, the annunciators will show a trouble condition.
To enter the Programming mode:
1. Press and hold the Walk Test button for two seconds (located behind the display PCB).
2. Press any button to turn off the trouble buzzer.
3. Press Silence Alarm to scroll through the settings for each programming section (e.g. to change the zone
type, or to turn an option on or off).
4. Press Silence Trouble to move to the next programming section (e.g. to move from zone 1 to zone 2).
5. The panel will indicate the current programming section using the Common Trouble LEDs, as shown
below.
Please see “6.2 Programming Section Descriptions” on page 24 for detailed descriptions of each
programming section.
30
FA-262 Installation & Operator’s Manual
8.2 Zone Programming (Section 0)
Program each of the zones as one of the following types. (See “Zone Programming (Section 0)” on page 24.)
Record your programming choices in the table below.
ZONE
ALARM
LED On
11
22
Zone
No.
Type
(00 -
05)
Label
8.3 NAC Temporal/Steady Programming (Section 1)
Please see “NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25.
Please see “NAC Auto-silence and Strobe Programming - Section 2 (‘NAC2’ LED on steady)” on page 25.
ZONE
ALARM
LED On
1NAC Auto-silence
2NAC2 Strobe or Bell
* = Factory default
Programming Section
Enabled
Strobe
Settings
*Disabled
*Bell
31
FA-262 Installation & Operator’s Manual
8.5 Silence Inhibit and Walk Test Programming (Section 3)
Please see “Silence Inhibit and Walk Test Programming - Section 3 (‘Battery’ LED on steady)” on page 26.
ZONE
ALARM
LED On
1Signal Silence Inhibit Timer
2One Man Walk Test
* = Factory default
Programming Section
Enabled
*Audible
Settings
*Disabled
Silent
8.6 Waterflow Programming (Section 4)
Please see “Waterflow Programming - Section 4 (‘Ground Fault’ LED on steady)” on page 26.
ZONE
ALARM
LED On
1Silencing of Waterflow Alarms
* = Factory default
Programming Section
*Enabled
Settings
Disabled
8.7 50/60 Hz Option (Section 5)
ZONE
ALARM
LED On
1AC power 50Hz or 60Hz
* = Factory default
Programming Section
*60Hz
Settings
50Hz
32
FA-262 Installation & Operator’s Manual
9.0 Appendix: Table of Compatible Smoke Detectors
Panel
CID
0125System Sensor
0125System Sensor1451A
0125System Sensor2400AN/AN/A
0125System Sensor2400THAN/AN/A
0125System Sensor2400ATAN/AN/A
0125
Max. #
Detector
s
Manufacture
r
System
Sensor
Model
1400/
1400A
Model
CID
AN/AN/A
Base
B401
B401B
Base
CID
N/A
2400AITAN/AN/A
Description
Ionization type
smoke, 2-wire
DC
12/24V
Plug-in –
Ionization type
smoke detector
Photoelectric, 2wire, 12/24V
Photoelectric
with Thermal, 2wire, 12/24VDC
Photoelectric
with Thermal and
Horn, 2-wire,
DC
24V
DC
Photoelectric
with isolated
Thermal and
Horn, 2-wire,
24V
DC
0125
0125
0125
0125
0125
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
B401
2451A
B401B
N/A
DH400
2451THA
B401
B401B
N/A
1100AN/AN/A
2100AN/AN/A
2100TAN/AN/A
Plug-in –
Photoelectric
type smoke
detector
Plug-in –
Photoelectric
type smoke
detector with
Thermal
Ionization, 2wire, 12/24V
DC,
terminal strip
Photoelectric,
2-wire, 12/
DC,
24V
terminal strip
Photoelectric,
2-wire, 12/
DC,
24V
thermistor,
terminal strip
33
FA-262 Installation & Operator’s Manual
Panel
CID
Detector
0125
0125
0125
0125
0125
Max. #
s
Manufacture
r
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
Model
Model
CID
Base
Base
CID
2112/24TAN/AN/A
4451HT
4451HTA
A
B401
B401B
DH400
N/A
B401
5451A
B401B
N/A
DH400
1151
1151A
2151
2151A
A
A
B401
B401B
DH400
B401
B401B
DH400
N/A
N/A
Description
Photoelectric,
12/24V
DC,
terminal strip
Plug-in – High
Tem p H e at
88°C (190°F)
Plug-in – Fixed
Temp/Rate of
Rise Detector
Plug-in – Low
Profile Ion
Plug-in – Low
Profile Photo
0125
0125
0130
0130
System
Sensor
System
Sensor
System
Sensor
System
Sensor
2100SAN/AN/A
2100TSAN/AN/A
2100ATAN/AN/A
2100TRAN/AN/A
2-wire direct
wire
Photoelectric
2-wire direct
wire
Photoelectric
Thermal
2-wire direct
wire
Photoelectric
Audible
Thermal
2-wire direct
wire
Photoelectric
Thermal
Auxiliary Relay
34
9.1 Smoke Detector Bases
FA-262 Installation & Operator’s Manual
Max. #
Detectors
25
25
25
25
25
25
25
25
Manufacture
r
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
System
Sensor
Model
B401N/A2-wire standard base, 4”, 12/24V
Base
CID
Description
DC
B401BN/A2-wire standard base, 6”, 12/24VDC
B406BN/A2-wire base, 24VDC, form contact
B401BHN/A24V
B110LPN/A2-wire, flangeless, 12/24V
DC sounder base for use with B401
DC
B116LPN/A2-wire base, 24VDC, form contact
DH400N/ADuct Detector Mount
RMK400N/ARecessed mount kit for Series 400
9.2 Compatible 4-Wire Smoke Detectors
Manufacture
r
1124B2124B2124TB2124S2124TS2124R
2124TR2124AT2124ATR2124AITR14242424
System Sensor
Detection
Systems
Gentex
HochikiSIJ-24SLR-24SLR-24HSLR-835B--
DSC
2424TH2424AT1151*2151*--
2424AIT64241451**2451**22451TH**-
*Detector with B112LP Base **Detector with B402B Base
DS284DS284THDS284THSDS284THRDS284THSRDS284THCS
DS284THCDS284THEDS284ESDS284IS--
82408240T8240P8243P8240PH8243PH
8240PT8243PT----
MN240MN240TMN240RMN240RTMN240SMN240ST
MN240SRMN240SRT----
Models
ESL741U741UT----
35
FA-262 Installation & Operator’s Manual
9.3 Compatible Horns/Strobes
System SensorTypeCd
Voltage
(FWR)
P2415(W)(A)H/S1520-30
P241575(W)(A)H/S15/7520-30
P2475(W)(A)H/S7520-30
P24110(W)(A)H/S11020-30
S2415(W)(A)S1520-30
S241575(W)(A)S15/7520-30
S2475(W)(A)S7520-30
S24110(W)(A)S11020-30
H24(W)(A)H-20-30
MDL(W)(A)Module-20-30
No suffix = Red, suffix W = White, suffix A = Canadian
version
GentexTypeCd
Voltage
(FWR)
GEH24H-20-31
GES24-15S1520-31
GES24-15/75S15/7520-31
GES24-30S3020-31
GES24-60S6020-31
GES24-75S7520-31
GES24-110S11020-31
GEC24-15H/S1520-31
GEC24-15/75H/S15/7520-31
GEC24-30H/S3020-31
GEC24-60H/S6020-31
GEC24-75H/S7520-31
GEC24-110H/S11020-31
Available in Red and White.
36
FA-262 Installation & Operator’s Manual
WheelockTypeCd
Voltage
(FWR)
NS-2415W-FR(W)H/S1520-31
NS-241575W-FR(W)H/S15/7520-31
NS-2430W-FR(W)H/S3020-31
NS-2475W-FR(W)H/S7520-31
NS-24110W-FR(W)H/S11020-31
NS4-2415W-FR(W)H/S1520-31
NS4-241575W-FR(W)H/S15/7520-31
NS4-2430W-FR(W)H/S3020-31
NS4-2475W-FR(W)H/S7520-31
NS4-24110W-FR(W)H/S11020-31
NS = 2-wire, NS4 = 4-wire
AS-2415W-FR(W)S1520-31
AS-241575W-FR(W)S15/7520-31
AS-2430W-FR(W)S3020-31
AS-2475W-FR(W)S7520-31
AS-24110W-FR(W)S11020-31
AS4-2415C-FR(W)S1520-31
AS4-2430C-FR(W)S3020-31
AS4-2475C-FR(W)S7520-31
AS4-24110C-FR(W)S11020-31
AH-24-RH-20-31
AH-24-WP-RH-20-31
MT-24-RH20-31
MT4-24-RH20-31
MT-24-SL-VFRH/S1520-31
MT-24-SLM-VFRH/S15/7520-31
MT-24-MS-VFRH/S3020-31
MT-24-IS-VFRH/S7520-31
MT-24-WM-VFRH/S11720-31
37
FA-262 Installation & Operator’s Manual
FCC Compliance Statement
CAUTION: Changes or modifications not expressly approved by the manufacturer could void your authority to
use this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
•Re-orient the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/television technician for help.
The user may find the following booklet prepared by the FCC useful: “How to Identify and Resolve Radio/
Television Interference Problems”. This booklet is available from the U.S. Government Printing Office,
Washington D.C. 20402, Stock # 004-000-00345-4.
38
FA-262 Installation & Operator’s Manual
Warranty & Warning Information
Warning Please Read Carefully
Note to End Users: This equipment is subject to terms and conditions of sale as follows:
Note to Installers
This warning contains vital information. As the only individual in contact with system users, it is your
responsibility to bring each item in this warning to the attention of the users of this system. Failure to properly
inform system end-users of the circumstances in which the system might fail may result in over-reliance upon
the system. As a result, it is imperative that you properly inform each customer for whom you install the system
of the possible forms of failure.
System Failures
This system has been carefully designed to be as effective as possible. There are circumstances, such as fire
or other types of emergencies where it may not provide protection. Alarm systems of any type may be
compromised deliberately or may fail to operate as expected for a variety of reasons. Some reasons for system
failure include:
•Inadequate Installation
A Fire Alarm system must be installed in accordance with all the applicable codes and standards in order to
provide adequate protection. An inspection and approval of the initial installation, or, after any changes to the
system, must be conducted by the Local Authority Having Jurisdiction. Such inspections ensure installation has
been carried out properly.
•Power Failure
Control units, smoke detectors and many other connected devices require an adequate power supply for proper
operation. If the system or any device connected to the system operates from batteries, it is possible for the
batteries to fail. Even if the batteries have not failed, they must be fully charged, in good condition and installed
correctly. If a device operates only by AC power, any interruption, however brief, will render that device
inoperative while it does not have power. Power interruptions of any length are often accompanied by voltage
fluctuations which may damage electronic equipment such as a fire alarm system. After a power interruption
has occurred, immediately conduct a complete system test to ensure that the system operates as intended.
•Failure of Replaceable Batteries
Systems with wireless transmitters have been designed to provide several years of battery life under normal
conditions. The expected battery life is a function of the device environment, usage and type. Ambient
conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. While each transmitting device has a low battery monitor which identifies when the
batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance
will keep the system in good operating condition.
•Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include metal objects placed on or near
the radio path or deliberate jamming or other inadvertent radio signal interference.
•System Users
A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary
physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is important
that all system users be trained in the correct operation of the alarm system and that they know how to respond
when the system indicates an alarm.
•Automatic Alarm Initiating Devices
Smoke detectors, heat detectors and other alarm initiating devices that are a part of this system may not
properly detect a fire condition or signal the control panel to alert occupants of a fire condition for a number of
39
FA-262 Installation & Operator’s Manual
reasons, such as: the smoke detectors or heat detector may have been improperly installed or positioned;
smoke or heat may not be able to reach the alarm initiating device, such as when the fire is in a chimney, walls
or roofs, or on the other side of closed doors; and, smoke and heat detectors may not detect smoke or heat
from fires on another level of the residence or building.
•Software
Most Mircom products contain software. With respect to those products, Mircom does not warranty that the
operation of the software will be uninterrupted or error-free or that the software will meet any other standard of
performance, or that the functions or performance of the software will meet the user’s requirements. Mircom
shall not be liable for any delays, breakdowns, interruptions, loss, destruction, alteration or other problems in
the use of a product arising our of, or caused by, the software.
Every fire is different in the amount and rate at which smoke and heat are generated. Smoke detectors cannot
sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by
carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing with matches or arson.
Even if the smoke detector or heat detector operates as intended, there may be circumstances when there is
insufficient warning to allow all occupants to escape in time to avoid injury or death.
•Alarm Notification Appliances
Alarm Notification Appliances such as sirens, bells, horns, or strobes may not warn people or waken someone
sleeping if there is an intervening wall or door. If notification appliances are located on a different level of the
residence or premise, then it is less likely that the occupants will be alerted or awakened. Audible notification
appliances may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners
or other appliances, or passing traffic. Audible notification appliances, however loud, may not be heard by a
hearing-impaired person.
•Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time.
Also the telephone lines may be compromised by such things as criminal tampering, local construction, storms
or earthquakes.
•Insufficient Time
There may be circumstances when the system will operate as intended, yet the occupants will not be protected
from the emergency due to their inability to respond to the warnings in a timely manner. If the system is
monitored, the response may not occur in time enough to protect the occupants or their belongings.
•Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to
function as intended due to the failure of a component.
•Inadequate Testing
Most problems that would prevent an alarm system from operating as intended can be discovered by regular
testing and maintenance. The complete system should be tested as required by national standards and the
Local Authority Having Jurisdiction and immediately after a fire, storm, earthquake, accident, or any kind of
construction activity inside or outside the premises. The testing should include all sensing devices, keypads,
consoles, alarm indicating devices and any other operational devices that are part of the system.
•Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system
also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize
the harmful effects of an emergency situation.
IMPORTANT NOTE: End-users of the system must take care to ensure that the system, batteries, telephone
lines, etc. are tested and examined on a regular basis to ensure the minimization of system failure.
40
FA-262 Installation & Operator’s Manual
Limited Warranty
Mircom Technologies Ltd. warrants the original purchaser that for a period of two years from the date of
manufacture, the product shall be free of defects in materials and workmanship under normal use. During the
warranty period, Mircom Technologies Ltd. shall, at its option, repair or replace any defective product upon
return of the product to its factory, at no charge for labor and materials. Any replacement and/or repaired parts
are warranted for the remainder of the original warranty or ninety (90) days, whichever is longer. The original
owner must promptly notify Mircom Technologies Ltd. in writing that there is defect in material or workmanship,
such written notice to be received in all events prior to expiration of the warranty period.
International Warranty
The warranty for international customers is the same as for any customer within Canada and the United States,
with the exception that Mircom Technologies Ltd. shall not be responsible for any customs fees, taxes, or VAT
that may be due.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:
•damage incurred in shipping or handling;
•damage caused by disaster such as fire, flood, wind, earthquake or lightning;
•damage due to causes beyond the control of Mircom Technologies Ltd. such as excessive voltage, mechanical
shock or
•water damage;
•damage caused by unauthorized attachment, alterations, modifications or foreign objects;
•damage caused by peripherals (unless such peripherals were supplied by Mircom Technologies Ltd.);
•defects caused by failure to provide a suitable installation environment for the products;
•damage caused by use of the products for purposes other than those for which it was designed;
•damage from improper maintenance;
•damage arising out of any other abuse, mishandling or improper application of the products.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to the point of purchase. All
authorized distributors and dealers have a warranty program. Anyone returning goods to Mircom Technologies
Ltd. must first obtain an authorization number. Mircom Technologies Ltd. will not accept any shipment
whatsoever for which prior authorization has not been obtained. NOTE: Unless specific pre-authorization in
writing is obtained from Summit management, no credits will be issued for custom fabricated products or parts
or for complete fire alarm system. Summit will at its sole option, repair or replace parts under warranty. Advance
replacements for such items must be purchased.
Note: Mircom Technologies Ltd.’s liability for failure to repair the product under this warranty after a reasonable
number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of
warranty.
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether
expressed or implied (including all implied warranties of merchantability or fitness for a particular purpose) And
of all other obligations or liabilities on the part of Mircom Technologies Ltd. neither assumes nor authorizes any
other person purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other
warranty or liability concerning this product. This disclaimer of warranties and limited warranty are governed by
the laws of the province of Ontario, Canada.
41
FA-262 Installation & Operator’s Manual
WARNING: Mircom Technologies Ltd. recommends that the entire system be completely tested on a
regular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering or
electrical disruption, it is possible for this product to fail to perform as expected.
NOTE: Under no circumstances shall Mircom Technologies Ltd. be liable for any special, incidental, or
consequential damages based upon breach of warranty, breach of contract, negligence, strict liability,
or any other legal theory. Such damages include, but are not limited to, loss of profits, loss of the
product or any associated equipment, cost of capital, cost of substitute or replacement equipment,
facilities or services, down time, purchaser’s time, the claims of third parties, including customers, and
injury to property.
MIRCOM MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE
WITH RESPECT TO ITS GOODS DELIVERED, NOR IS THERE ANY OTHER WARRANTY, EXPRESSED OR
Out of Warranty Repairs
Mircom Technologies Ltd. will at its option repair or replace out-of-warranty products which are returned to its
factory according to the following conditions. Anyone returning goods to Mircom Technologies Ltd. must first
obtain an authorization number. Mircom Technologies Ltd. will not accept any shipment whatsoever for which
prior authorization has not been obtained.
Products which Mircom Technologies Ltd. determines to be repairable will be repaired and returned. A set fee
which Mircom Technologies Ltd. has predetermined and which may be revised from time to time, will be
charged for each unit repaired.
Products which Mircom Technologies Ltd. determines not to be repairable will be replaced by the nearest
equivalent product available at that time. The current market price of the replacement product will be charged
for each replacement unit.
42
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113