Mircom FA-1025U Installation And Operation Manual

®
FA-1025U
Fire Alarm Control Panel
INSTALLATION and OPERATION MANUAL
LNOTICE
All information, documentation, and specifications contained in this manual are subject to change without prior notice by the manufacturer.
©1998 by Mircom Technologies Limited Printed in CANADA, Dec 2005
LT-536 Rev. 4
MODEL FA-1025U
FIRE ALARM CONTROL PANEL
TABLE OF CONTENTS
PAGE
1. INTRODUCTION . ................................. 1
2.MECHANICALINSTALLATION. .......................... 1
3. FUNCTION SELECTION .............................. 1
4. WIRING:
4.1DETECTIONZONES ........................... 2
4.2SIGNALZONES.............................. 2
4.3ALARMANDTROUBLERELAYS ..................... 2
4.4 REMOTE ANNUNCIATION ........................ 2
4.5A.C.POWERANDBATTERIES...................... 2
5. TROUBLE INDICATORS AND CONTROL:
5.1COMMONTROUBLELED ........................ 2
5.2COMMONTROUBLEBUZZER ...................... 2
5.3ZONETROUBLELED........................... 2
5.4TROUBLESILENCESWITCH....................... 2
5.5BATTERYFAULTLED .......................... 3
5.6GROUNDFAULTLED .......................... 3
5.7REMOTELAMPFAILLED ........................ 3
5.8SIGNALTROUBLELED.......................... 3
6. SEQUENCE OF OPERATION:
6.1NORMAL ................................. 3
6.2ALARM .................................. 3
6.3SIGNALSILENCE............................. 3
6.4 RESET .................................. 3
7.SYSTEMCHECKOUT ............................... 4
8.POWERUPANDTROUBLESHOOTING ...................... 4
FIGURES:
1.BACKBOX&FLUSHTRIMMOUNTINGDETAILS ............. 5
2. CIRCUIT BOARD LAYOUT ........................ 6
3. DETECTION AND SIGNAL WIRING INSTRUCTION ............ 7
4.WIRINGTABLEFORDETECTIONZONES................. 8
5.WIRINGTABLEFORBELLSANDHORNS ................ 9
6. ALARM AND TROUBLE RELAY CONTACTS AND
REMOTE ANNUNCIATION WIRING INSTRUCTION ............ 10
APPENDIX “A” 2-WIRE SMOKE DETECTOR
CONTROLPANELCOMPATIBILITY .................... 11
APPENDIX “B” BATTERY CALCULATIONS ..................... 14
1. INTRODUCTION
The FA-1025U is a supervised 5 zone 24VDC Fire Alarm Control Panel.
The panel provides the following features:
- 5 class B detection zones
- 2 class B signal zones, 1.25A per zone
- Alarm and trouble relay contacts
- Remote trouble indication
- Remote supervised alarm annunciation
- Individual zone silence/disconnect switches
- Trouble silence switch
- Subsequent alarm operation
- LED indicators for zone Alarm and Trouble, A.C. On, Battery Fault, Ground Fault, Remote Lamp Fail, Common Trouble, Signal Trouble and Signal Silenced
2. MECHANICAL INSTALLATION
The panel can be surface or flush mounted. Refer to Figure 1 for dimensions.
For surface mounting, mark the location of the four mounting holes. Install the top two screws into the wall and place the panel over the screws. Install the bottom screws, and tighten down all four screws.
For flush mounting, make the wall cut-out according to the panel dimensions. Remove the control panel door. Mount the flush mounting trim (MODEL FA-102TRU) to the back box using the screws and nuts provided with the flush mounting kit. Re-install the door on top of the flush trim. The cam lock may require a minor adjustment in order to compensate for the flush trim.
3. FUNCTION SELECTION
The following jumpers are available for function selection, refer to Figure 2 for location;
JW1 Cut for normally open trouble contacts. JW2 Cut for normally closed trouble contacts. JW3 Cut to enable common alarm relay to de-energize if signal silence switch is activated. JW6 Cut if 60 second signal silence inhibit is not required (Signals can be manually
silenced any time if cut).
JW7 Cut to enable lamp supervision for the remote annunciator alarm zones.
-1-
4. WIRING
4.1 DETECTION ZONES The system has 5 detection zones. Refer to Figure 3 for wiring instruction and to Figure 4 for wire size.
4.2 SIGNAL ZONE There are 2 signal zones available for bells and horns providing 1.25A per zone of signal power. Refer to Figure 3 for wiring instruction and to Figure 5 for wire size.
4.3 ALARM AND TROUBLE RELAYS Alarm and trouble relay contacts are provided. Refer to Figure 6 for contact location and designation.
4.4 REMOTE ANNUNCIATION Annunciation outputs are provided for alarm, remote trouble indicator and buzzer. Cut JW7 to enable lamp supervision for the remote annunciator alarm zones. Refer to Figure 6 for wiring instruction.
4.5 A.C. POWER AND BATTERIES The A.C. power is connected to the terminal block above the transformer. Use GEL CELL or SEALED LEAD-ACID type of batteries only. Connect the batteries after power up. Use 24V 4AH batteries for 24 hours standby and 5 minutes of alarm.
ELECTRICAL RATING: 120V, 60 Hz, 1A/ 240V, 50 Hz, 0.5A BATTERY CHARGER: 200mA MAXIMUM CHARGING CURRENT
5. TROUBLE INDICATORS AND CONTROL
Refer to Figure 2 for the location of indicators and control.
5.1 COMMON TROUBLE LED The yellow common trouble LED will flash for any trouble in the panel.
5.2 COMMON TROUBLE BUZZER The common trouble buzzer will sound intermittently for any trouble.
5.3 ZONE TROUBLE LED The yellow zone trouble LED will illuminate steadily for open loop in the zone wiring.
5.4 TROUBLE SILENCE SWITCH Operating this switch will silence the common trouble buzzer. If there is no trouble condition and the switch is in the silence position, the buzzer will sound continuously.
-2-