Mircom FA-1000 Installation And Operation Manual

FA-1000 SERIES
Microprocessor-Based Fire Alarm Control Panel
Installation and Operation Manual
For the latest compatability information visit www.mircom.com/deviceguide
LT-600 Rev. 18
March 2016
Table of Contents
1.0 Introduction 9
1.1 About this Manual .......................................................................................................... 9
1.2 About the FA-1000 ......................................................................................................... 9
1.2.1 Overall Features: ........................................................................................................... 9
1.2.2 Controls and Indicators .................................................................................................. 9
1.3 Contact Us ............................................. ... ... .... ...................................... .... ... ... ... ... ........ 10
1.3.1 General Inquiries ............................................................................................................ 10
1.3.2 Customer Service ........... .... ... ... ... .......................................... ... .... ................................. 10
1.3.3 Technical Support .. ... ... ... .... ... ... ... ... .... ... ... ... .... .......................................... ... ... .............. 10
1.3.4 Website ............................... ................................................................... ........................ 10
2.0 System Components 11
2.1 Chassis .......................................................................................................................... 11
2.2 Circuit Adder Modules ............................... ... .... ... ... ... .... ... ... ... ... .... ................................. 12
2.3 Auxiliary Models ............................................................................................................. 12
2.4 Enclosures ..................................................................................................................... 12
2.5 Flush Trim Rings ............................................................................................................ 13
2.6 Batteries .............................. ...................................... ....................................... .............. 13
2.7 Remote Annunciators .................................................................................................... 14
2.8 FA-1000 Fire Alarm Control Panel Kits .......................................................................... 14
2.9 FA-1000 Accessories ................................... .... ... ... ... .... ... ... .......................................... . 14
2.10 Maximum Number of Circuit Adder Modules that may be Installed ............................... 14
3.0 Mechanical Installation and Dimensions 16
3.1 BB-1024 Installation ....................................................................................................... 16
3.2 BB-1072 Installation ....................................................................................................... 17
3.3 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 18
3.4 Main Chassis Installation .......................................... .... ... ... ... ... .... ... .............................. 19
3.5 Main and Expander Chassis Installation ........................................................................ 20
4.0 Module Mounting Locations 21
4.1 BB-1024 and BB-1072 Main Chassis Mounting Locations ............................................ 22
4.2 BB-1072 Expansion Chassis Mounting Locations ......................................................... 23
4.3 Circuit Adder Mounting Details ...................................................................................... 24
5.0 Module Settings 25
5.1 Main Fire Alarm Module ................................................................................................. 25
3
Table of Contents
5.1.1 Jumpers ......................................................................................................................... 25
5.2 MCC-1024-6, MCC-1024-12 Main Display Module ........................................................ 26
5.2.1 Connectors ......................... .......................................... ....................................... ........... 27
5.3 Adder Display Module .. ... ... ............................................................................................ 28
5.3.1 Connectors ......................... .......................................... ....................................... ........... 28
5.4 DM-1008A Detection Adder Module .............................................................................. 29
5.4.1 Jumpers ......................................................................................................................... 29
5.5 SGM-1004A Signal Adder Module .. ... ... .... ... ... ... .... ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... ... ..... 30
5.5.1 Jumpers ......................................................................................................................... 30
5.5.2 Components ................................. .......................................... ........................................ 30
5.5.3 Operation ....................................................................................................................... 31
5.5.4 Jumpers for the Bell Cut Mode ....................................................................................... 31
5.6 RM-1008A Relay Adder Module .................................................................................... 32
5.7 UDACT-300A Digital Communicator Module ................................................................. 33
5.7.1 Jumper and connector ................................................................................................... 35
6.0 Field Wiring 36
6.1 Main Fire Alarm Module Terminal Connections ............................................................. 36
6.2 Detection Module (DM-1008A) Terminal Connections .............................. ... .... ... ... ...... .. 39
6.3 Signal Module (SGM-1004A) Terminal Connections .......................... ... ... ... .... ... ... ... ..... 40
6.4 Relay Module (RM-1008A) Terminal Connections ......................................................... 41
6.5 UDACT-300A Main Board Terminal Connections ........................ .................................. 42
6.6 PR-300 Polarity Reversal and City Tie Module Terminal Connections .......................... 43
6.7 Power Supply Connections ............................................................................................ 44
6.8 Connecting to a DCS SurGuard Receiver ...................................................................... 45
6.9 Wiring Tables and Information ....................................................................................... 46
7.0 System Checkout 47
7.1 Before Turning the Power On ........................................................................................ 47
7.2 Power-Up Procedure .................... ... ... ... .... ... ... ... .... ........................................................ 47
7.3 Troubleshooting ............................................................................................................. 47
8.0 Indicators, Controls, and Operation 49
8.0.1 Paper labels for buttons and indicators .......................................................................... 49
8.1 Common Indicators ...................................................................... ... .... ... ... ..................... 50
8.1.1 Buzzer ............................. ....................................................................... ........................ 50
8.1.2 AC ON LED ............................................................... ... ... .... ... ........................................ 50
8.1.3 Common Alarm LED .................................................................................... .... ... ........... 50
8.1.4 Common Supervisory LED ................. ... .... ..................................................................... 50
8.1.5 Common Trouble LED .... ... ... .... ... ... ... ... .... ... ... ............................................................... 50
8.1.6 Remote Failure LED ....................................................................................................... 50
8.1.7 Fire Drill LED .................................................................................................................. 50
4
8.1.8 Automatic Alarm Signal Cancel LED (Acknowledge) ....... ................ ................ .............. 50
8.1.9 General Alarm LED ........................................................................................................ 51
8.1.10 Configuration / Test Mode LED ...................................................................................... 51
8.1.11 Auxiliary Disconnect LED ............................................................................................... 51
8.1.12 Signal Silence LED ................................................ ... .... ... ... ... ... .... ... ... ... .... ... ... ... ... .... .... 51
8.1.13 Battery/Charger Trouble LED ........................................................................................ 51
8.1.14 Ground Fault LED .......................................................................................................... 51
8.1.15 CPU Fault LED .............................................................................................................. 51
8.2 Common Controls .......................................................................................................... 52
8.2.1 System Reset Button (White) ......................................................................................... 52
8.2.2 Signal Silence Button (Blue) .......................................................................................... 52
8.2.3 Fire Drill Button (Orange) ................................. ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... ... ........... 52
8.2.4 Automatic Alarm Signal Cancel Button (Yellow) ........... ................................................. 52
8.2.5 General Alarm Button (Red) .......................................................................................... 52
8.2.6 Auxiliary Disconnect Button (Orange) ............................................................................ 52
8.2.7 Lamp Test Button (Orange) ................................................ ... ... .... ... ... ... .... ... ... ... ... ........ 52
8.2.8 Alm/Sup/Tbl/Bldg Audible Sil Button (Blue) ................................................................... 53
8.3 Circuit Status Indicators .. .... ... ... ... ... .... ... ... ... .... ... .......................................... ... ... ........... 53
8.3.1 Alarm Circuit Indicators .......................... ........................................................................ 53
8.3.2 Supervisory Circuit Indicators ........................................................................................ 53
8.3.3 Property and Building Safety Circuit Indicators ...................... ............. ............. ............. . 53
8.3.4 Trouble-Only Circuit Indicators ...................................................................................... 54
8.3.5 Signal Circuit Indicators ...................................... ... ... .... ... ... ........................................... 54
8.3.6 Relay Circuit Indicators .................................................................................................. 54
8.4 Circuit (Zone) Disconnect Switches ........................................................................... ... . 54
8.5 Single Stage Operation .......................................... ... .... ... ... ... ... .... ................................. 54
8.6 Two Stage Operation ..................................................................................................... 55
8.7 Circuit Types ....................................................................... ... ... .... ... .............................. 56
8.7.1 Initiating (Detection) Circuit Types ................................................................................. 57
8.7.2 Indicating (Signal) Circuit Types .................................................................................... 58
8.7.3 Evacuation Codes .......................................................................................................... 58
9.0 System Configuration 60
9.1 Introduction to Configuration .......................................................................................... 60
9.1.1 Three buttons and LED indicators are used in configuration mode ............................... 61
9.2 Configuration DIP Switch Functions .............................................................................. 62
9.3 Entering Configuration Mode ......................................................................................... 63
9.4 Exiting Configuration Mode ................................. .......................................... ... ... ... .... ... . 64
9.5 Factory Default Configuration ........................................................................................ 64
9.6 Restore to Default/Resize (Class A or B) ....................................................................... 64
9.6.1 Class B (Style B) Restore Defaults ............................................................................ ... . 65
9.6.2 Class A (Style D) Restore Defaults ............................... ... ... ... ... .... ... ... ... .... ... ... ... ........... 65
9.7 Resize System (Set Circuit Adder Module Number and Type) ........ ... ... ........................ 65
9.8 Configuration Features .................................................................................................. 66
5
Table of Contents
9.9 Configuring Initiating and Indicating Circuits .................................................................. 68
9.10 Configuring Circuit Correlations ..................................................................................... 69
9.10.1 Correlation by Input Circuit ................. ... .... ... ... ... .... ... .......................................... ... ... ..... 70
9.10.2 Correlation by Output Circuit .......................................................................................... 70
9.11 Display Configuration ..................................................................................................... 71
10.0 Walk Test Operation 72
11.0 Appendix A: Compatible Receivers 73
12.0 Appendix B: RA-1000 Remote Annunciator Panels 74
12.1 RA-1000 Series .............................................................................................................. 74
12.1.1 Models ................................ .......... ...... .......... .......... ......... .......... .......... ......... .................. 74
12.1.2 Enclosures ..................................................................................................................... 74
13.0 Appendix C: Specifications 75
13.1 MCC-1024-6[SA] and MCC-1024-6ADS Specifications .. .... ... ... ... ... .... ... ... ... .... ... ... ... ..... 75
13.2 MCC-1024-12SA and MCC-1024-12ADS Specifications ............................................... 77
13.3 FA-1000 Expander Chassis and System Modules ......................................................... 78
14.0 Appendix D: Power Supply and Battery Calculations 80
15.0 Warranty & Warning Information 81
6

List of Figures

List of Figures
Figure 1 BB-1024 Flush or Surface Enclosure Installation and Dimensions ............... ... ... ... .... ... . 16
Figure 2 BB-1072 Flush or Surface Enclosure Installation and Dimensions ............... ... ... ... .... ... . 17
Figure 3 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 18
Figure 4 Main Chassis Installation .................................................... ... ... .... ... ... ... .... ... ... ... ... .... .... 19
Figure 5 Expander Chassis Installation ............................. ... ... .... ... ... ... ... .... ... ... ... ........................ 20
Figure 6 BB-1024 and BB-1072 Main Chassis Mounting Locations ............................................ 22
Figure 7 BB-1072 Expansion Chassis Mounting Locations ......................................................... 23
Figure 8 Circuit Adder Mounting Details .............................. ... .... ... ... .......................................... . 24
Figure 9 Main Fire Alarm Module ............ ... ... .... ... ... ... .... ... ... .......................................... ... ... .... .... 25
Figure 10 Main Display Module (MCC-1024-6, MCC-1024-12) ..................................................... 26
Figure 11 Main Display Module (MCC-1024-6S, MCC-1024-12S) ................................................ 27
Figure 12 Adder Display Module (Part of Expander Chassis) ........................................................ 28
Figure 13 Detection Adder Module (Model DM-1008A) ................................................................. 29
Figure 14 Signal Adder Module (Model SGM-1004A) .................................................................... 30
Figure 15 Relay Adder Module (Model RM-1008A) ....................................................................... 32
Figure 16 Digital Communicator Module (Model UDACT-300A) ...................... ... ... .... ... ... ... ... .... ... . 33
Figure 17 Polarity Reversal and City Tie Module (Model PR-300) ................................................ 34
Figure 18 Main Fire Alarm Module Terminal Connections ..................................... .... ... ... ... ... .... .... 37
Figure 19 Main Fire Alarm Module Terminal Connections (continued) .................................. .... ... . 38
Figure 20 Detection Module (DM-1008A) Terminal Connections .................................................. 39
Figure 21 Signal Module (SGM-1004A) Terminal Connections ..................................................... 40
Figure 22 Relay Module Terminal Connections ............................................................................. 41
Figure 23 UDACT-300A Terminal Connections ............................................................................. 42
Figure 24 Polarity Reversal and City Tie Module Terminal Connections ....................................... 43
Figure 25 Power Supply Connections ............................................................................................ 44
Figure 26 Connecting an FA-1000 FACP to a DCS Surguard System Receiver ............. .............. 45
Figure 27 Indicators and Control Location ..................................................................................... 49
Figure 28 Evacuation Codes .......................................................................................................... 59
Figure 29 Configuration Indicators and Controls ............................................................................ 61
7

List of Tables

List of Tables
Table 1 Main Fire Alarm Module Circuit Details .......................................................................... 25
Table 2 Cable Connectors and Miscellaneous ............................................................................ 33
Table 3 UDACT-300A List of LEDs and their Functions ............................................................. 33
Table 4 Jumpers ....................... ... ... ... ....................................... ... .... ... ... ... ... .... ........................... 34
Table 5 Settings permitted in CAN/ULCS527 ............................................................................. 36
Table 6 Wiring Table for Input Circuits ...... .................................................................................. 46
Table 7 Wiring Table for Indicating Circuits ................................................................................ 46
Table 8 Initiating (Detection) Circuit Types ................................................................................. 57
Table 9 Indicating (Signal) Circuit Types .................................................................................... 58
Table 10 Settings permitted in UL864 ................................... ... ... ... .... ... ... ..................................... 60
Table 11 Settings permitted in CAN/ULCS527 ........................................ ... ... .... ........................... 60
Table 12 Configuration DIP Switch Functions .......................... .......................................... ... ... ... .. 62
Table 13 Configuration Features ....................... ... .... ... ... ... .... ... ... ... .... ... ... ..................................... 66
Table 14 Configuring Initiating and Indicating Circuits .................................................................. 69
Table 15 MCC-1024-6[SA] and MCC-1024-6ADS Specifications ......... ... ... ... .... ... ... ... .... ... ... ... ... .. 75
Table 16 MCC-1024-12[SA] and MCC-1024-12ADS Specifications ............................................. 77
Table 17 FA-1000 Expander Chassis and System Modules ......................................................... 78
8

1.0 Introduction

1.1 About this Manual

This installation and operation manual provides information on installing the FA-1000 Series Fire Alarm Control Panel.

1.2 About the FA-1000

Mircom's FA-1000 Fire Alarm Control Units provide a large capacity of supervised Class A or B (Style D or B) initiating circuits and supervised Class A or B (Style Z or Y) indicating circuits. All circuits are supervised for opens and ground faults, and indicating circuits are supervised for shorts. Optional modules include additional initiating and indicating circuits, relay, and polarity reversal and city tie. Flush or sur face mountable enclosures can be used fo r retrofits and on new installations.

1.2.1 Overall Features:

Basic unit has eight Class B (Style B) initiating circuits that may be configured as four
Class A (Style D) circuits. These are configurable as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, or Trouble-Only circuits. There are two LEDs per circuit: one for trouble (amber), and one for st atus (red/amber)
Basic unit has four power limited Class A/B (Style Z/Y) indicating circuits with individual
trouble indicators. Each circuit can be configured as Audible (Silenceable) or Visual (Non-Silenceable). Audibles may be configured as Steady, Temporal Code, California Code, or March Time
Initiating and indicating circuits may be individually disconnected by a DIP switch (slide
switch on "S" Versions for the U.S.A. market only)
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-
Man Walk Test For Canadian installations, disable Auto Signal Silence.
Subsequent Alarm, Supervisory, and Trouble operation
Two outputs for four-wire resettable smoke power supply (200 mA each max., 300 mA
total max.)
Auxiliary relay cont act s for Common Alarm and Common Supervisory (disconnect able),
and a Common Trouble relay
RS-485 interface for RA-1000 Series Remote Multiplex Annunciators
Optional modules for additional initiating, indicating, and relay circuits, and city tie and
polarity reversal signalling
Easy configuration via pushbuttons and switches
Extensive transient protection
Surface mountable enclosures, flush trims available
Introduction

1.2.2 Controls and Indicators

Eight pushbuttons, 16 common indicators, provision for up to 24 points (expansion chassis adds provision for up to another 48 points).
9

1.3 Contact Us

For General Inquiries, Customer Service and Technical Su pport you can contact us Monday to Friday 8:00 A.M. to 5:00 P.M. E.S.T.

1.3.1 General Inquiries

Introduction
Toll Free 1-888-660-4655 (North America Only) Local 905-660-4655 Email mail@mircom.com

1.3.2 Customer Service

Toll Free 1-888-MIRCOM5 (North America Only) Local 905-695-3535 Toll Free Fax 1-888-660-4113 (North America Only) Local Fax 905-660-4113 Email salessupport@mircom.com

1.3.3 Technical Support

Toll Free 1-888-MIRCOM5 (North America Only)
888-647-2665
International 905-647-2665
10
Email techsupport@mircom.com

1.3.4 Website

www.mircom.com

2.0 System Components

2.1 Chassis

Model Description
ECH-1048 48 zone extension chassis.
System Components
TEST/CONFIG
MODE
REMOTE
FAILURE
SYSTEM
RESET
FIRE
DRILL
AUTOMATIC
ALARM SIGNAL
CANCEL
GENERAL
ALARM1SILENCE
MCC-1024-6 (add suffix S for slide switch model)
COMMON
COMMON
TROUBLE
ALARM
COMMON
A.C. ON
SUPERVISORY
BATTERY
LAMP
TROUBLE
TEST
GROUND
FAULT
AUXILIARY
DISCONNECT
ALM/SUP/
TBL/BLDG
AUDIBLE SIL
SIGNAL
8141
8181
DET. ZONE
SIG. ZONE
DISCONNECT
DISCONNECT
8
ZONECONFIG.
ZONE
DISCONNECT
DISCONNECT
MCC-1024-12
Main Chassis with eight Style B / four Style D initiating circuits, four Style Y or Z indicating circuits, and a six ampere power su pply. For more information see 13.0 Appendix C: Specifications on page 75.
Same as MCC-1024-6, but with a 12 ampere power supply. For more information see 13.0 Appendix C: Specifications on page 75.
Same as MCC-1024-6, but with disconnect slide
A.C. LINE
CIRCUIT
BREAKER
MCC-1024-6S
switches instead of DIP switches. For the U.S.A. Market only.
Same as MCC-1024-12, but with disconnect slide
MCC-1024-12S
switches instead of DIP switches. For the U.S.A. Market only.
Main Chassis with eight Style B / four Style D initiating circuits, four Style Y or Z indicating
MCC-1024-6ADS
circuits, and a six ampere power su pply. For more information see 13.0 Appendix C: Specifications on page 75.
MCC-1024-12ADS
Same as MCC-1024-6ADS, but with a 12 ampere power supply. For more information see 13.0 Appendix C: Specifications on page 75.
11

2.2 Circuit Adder Modules

POLARITY
REVERSAL
ALARM
POLARITY
REVERSAL
SUPV
CITY
TIE
+ | - + | - + | -
JW4
P1 P2
BB-1024 BB-1072
Model Description
DM-1008A Eight detection circuit modules SGM-1004A Four signal circuit modules
RM-1008A Eight relay circuit modules

2.3 Auxiliary Models

Model Description
System Components

2.4 Enclosures

PR-300 Polarity Reversal and City Tie Module
Model Description
BB-1024 (add suffix “R” for red enclosure)
BB-1072 (add suffix “R” for red enclosure)
Surface enclosure 24 circuits
Surface enclosure 72 circuits
12
Model Description
W = 7 1/8"
H = 6 1/2"
D = 3"
BA-117
BA-110
D = 4"
H = 3 3/4"
W = 5 15/16"
BA-124
W = 6 1/2"
H = 5"
D =6 7/8"
BA-140
W = 7 5/8"
H = 6 7/8"
D = 6 3/8"
Figures Not Drawn to Scale
BBX-1024DS Universal Enclosure , white door.
BBX-1024DSR Universal Enclosure, red door.

2.5 Flush Trim Rings

Model Description
System Components

2.6 Batteries

FA-UNIV-TRB (add suffix “R” for red
Flush trim ring in Black
enclosure) FA-1072TR
(add another suffix R for red
Flush trim ring
enclosure)
Model Description
12-volt batteries (2 required for 24 volts)
10 to 40 AH
13

2.7 Remote Annunciators

UP TO
32 ZONES
UP TO
80 ZONES
UP TO
128 ZONES
Model Description
RA-1000 Series Remote multiplex annunciator panels

2.8 FA-1000 Fire Alarm Control Panel Kits

For any other sizes, etc., components are ordered separately.
Model Description
Expandable kit for the Canadian market. Eight Class B (or four Class A)
FA-1008KA
initiating and four (Class A or B) indicating circuits, Expandable to 24 circuits, six amp power supply (MCC-1024-6Main Chassis in a BB-1024 enclosure).
System Components
Expandable kit for the U.S.A. market. Eight Class B (or four Class A) initiating
FA-1008KUA
and four (Class A or B) indicating circuits. Expandable to 24 circuits, six amp power supply (MCC-1024-6 main chassis in a BB-1 02 4 R enc losure).

2.9 FA-1000 Accessories

Model Description
MP-300 End-of-line Resistor Plate MP-300R End-of-line Resistor Plate, red MP-300S End-of-line Resistor Plate, stainless steel finish

2.10 Maximum Number of Circuit Adder Modules that may be Installed

The maximum number of circuit adder modules that may be physically installed in a system is outlined in the table below.
Main Chassis Type Number of Adders
MCC-1024-6(S) or MCC-1024-12(S) Two circuit adder modules of any type. MCC-1024-6(S) or MCC-1024-12(S) and ECH-1048 Eight circuit adder modules of any type.
14
System Components
i
The "S" Version Chassis have slide switches instead of DIP switches for disconnects. The maximum number of each circuit adder module type is outlined in the following table.
Module Description Maximum Total per
System
DM-1008A
SGM-1004A
RM-1008A
Eight detection circuit modules (total of 64 initiating circuits in a system).
Four signal circuit modules (total of 24 initiating circuits in a system).
Eight relay circuit modules (total of 32 relay circuits in a system).
Notes: Any FA-1000 System may have a PR-300 or UDACT-300A and up to eight (8)
Remote Multiplex Annunciators externally. As good practice, it is recommended that circuit adder modules be installed in the order of detection modules, followed by signal modules, followed by relay modules.
All systems can carry a maximum of eight adder modules in the combinations permitted above.
764
316
432
15

Mechanical Installation and Dimensions

(SIDE VIEW)
BACKBOX
DOOR
BACKBOX
FLUSH TRIM
WALL
SURFACE FLUSH
(SIDE VIEW)
9
4
16
DOOR
WALL
1"
MATERIAL: 18GA (0.048") THICK
COLD ROLLED STEEL
FINISH: PAINTED
14.5"
4
.
5
"
11"
26"
1.5"
5.4"
20.5"
3.5"
1"
3.5" is the maximum depth for semi -flush mounting usi ng the flush tr im ring
1" is the minimum depth above the wall required for semi- flush mounting usi ng the flush tr im ring
17"
28.5"
Adhere tr im ri ng to
wall surfac e around
FA- 1000 backbox .
PLACE FA-UN IV-TRB TRI M RING O VER BACKBOX
TRIM RING
WALL
WOOD OR METAL S TUD
BACKBOX
3.0 Mechanical Installation and
Dimensions
Install the enclosure as shown for the BB-1024 in Figure 1, or for the BB-1072 in Figure 2 on page 17.

3.1 BB-1024 Installation

16
Figure 1 BB-1024 Flush or Surface Enclosure Installation and Dimensions

3.2 BB-1072 Installation

(SIDE VIEW)
DOOR
BACKBOX
7-9/16"
BACKBOX
FLUSH TRIM
WALL
SURFACE FLUSH
(SIDE VIEW)
DOOR
FLUSH TRIM
KNOCKOUTS
WALL
BACKBOX
16"
2"
2" TYP.
7/32" DIA.
MOUNTING
HOLE
2" SINGLE
KNOCKOUT
(MODEL FA-156TR)
15"
15"
33"
2" TYP.
MATERIAL:16GA (0.059") THICK COLD ROLLED STEEL
FINISH: PAINTED
DOOR
1-1/2"
1-1/4"
1-1/8" & 7/8"
22-1/4"
3-1/8"
8-3/4"
10-1/4"
2-1/2"
1-1/2"
7-1/2"
35-1/2"
24-3/4"
33-1/4"
22-13/16"
FLUSH TRIM MODE: FA-1072TR
Mechanical Installation and Dimensions
Figure 2 BB-1072 Flush or Surface Enclosure Installation and Dimensions
17
Mechanical Installation and Dimensions
26.0 "
14.5 "
4.2 "
External Dimensions
12.0 "
23.5 "
Mounting Dimensions
1.3 "
1.7 "
2.0 "
Top Vi ew
2.1 "
1.3 "
6.0 "
9.5 "
Side View

3.3 BBX-1024DS and BBX-1024DSR Mechanical Installation

The BBX-1024DS and BBX-1024DSR are suitable for flush or surface mounting, and have a built-in trim ring.
Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26” Distance between horizontal mounting screws 12” Distance between vertical mounting screws 23.5” Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
18
Figure 3 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions

3.4 Main Chassis Installation

To install the main chassis
1. Install the main chassis in the BB-1024 backbox as shown in Figure 4 below, using the supplied hex-nuts.
2. Group the incoming wires through the top of the enclosure to prep are them for wir ing the modules. Do not run the wires in-between the modules since this could cause a short circuit.
3. Use a wire tie to group wires for easy identification and neatness.
4. Be sure to connect a solid earth ground (from building system ground / to a cold water pipe) to the chassis earth ground mounting lug, and to connect the earth ground wire lugs from the main chassis to the ground screw on the backbox.
Mechanical Installation and Dimensions
Figure 4 Main Chassis Installation
19

3.5 Main and Expander Chassis Installation

i
To install the expander chassis
1. Install the main and expander chassis into the BB-1072 enclosure, as shown in Fig ure 5, using the supplied hex-nuts.
2. Group the incoming wires through the top of the enclosure to prep are them for wirin g the modules. Do not run the wires in-between the modules since this could cause a short circuit.
3. Use a wire tie to group wires for easy identification and neatness.
BACKBOX
Mechanical Installation and Dimensions
EXPANDER CHASSIS
#8-32 HEXNUTS (4X)
MAIN CHASSIS
1 814181818
EARTH GROUND LUG
#8 x 1/4" TYPE `B' SCREW
#8-32 HEXNUTS (4X)
Figure 5 Expander Chassis Installation
Note: Be sure to connect a solid earth ground (from building system ground / to a cold
water pipe) to the chassis earth ground mounting lug, and to connect the earth ground wire lugs from both the main chassis and the expander chassis to the ground screw on the backbox.
20
Module Mounting Locations
!

4.0 Module Mounting Locations

The main chassis in a BB-1024 or BB-1072 enclosure comes pre-assembled with all power supply, main panel, and display components and boards. The expander chassis is equipped with a pre-assembled display board. The PR-300 City Tie Module or the UDACT-300A Digital Communicator may be added on the left side, as shown in Figure 8 on page 24. These modules connect directly to the dedicated P2 connection in the upper-left corner of the main
fire alarm module.
Attention: There needs to be enough display points for each circuit on an adder
module. These display points are assigned during configuration (See System Configuration on page 60.) in the order in which the adder modules are electrically installed (the order in which they have their cables connected to each other). Both the number of points available for each display type and the number of points required for each circuit adder module type are described in 5.0 Module Settings on page 25.
As good practice, it is recommended that circuit adder modules are installed in the order of detection modules (DM-1008A) followed by signal modules (SGM-1004A), followed by relay modules (RM-1008A).
To enable communication from the main fire alarm module to all of the circuit adder modules, it is necessary to remove the continuity jumper on JW6 (near P5, the circuit adder module connector) on the main fire alarm module. This jumper plug must be installed on the continuity jumper on the last installed circuit adder module. To verify the location of the continuity jumper on a particular circuit adder module see 5.0 Module Settings on page 25
Note: Only the last circuit adder module should have a jumper plug on its continuity jumper - all others must be left without a jumper plug.
21
Module Mounting Locations
PR-300 city tie module (see Notes below)
UDACT-300A Dialer Module (see Notes below)
#6-32 x 1
1
/2” M/F hex
spacer
Other Circuit Adder Module
#6-32 x 1
1
/4” screw
Other Circuit Adder
i

4.1 BB-1024 and BB-1072 Main Chassis Mounting Locations

22
Figure 6 BB-1024 and BB-1072 Main Chassis Mounting Locations
Notes: Front plate is not shown. Other circuit adder modules may be:
DM-1008A Detection Circuit Module
SGM-1004A Signal Circuit Module
RM-1008A Relay Circuit Module
To Install Circuit adder modules
1. Install circuit adder modules from right to left using the supplied stand-offs (Figure 8 on page 24).
2. Plug the first module with its 26-pin ribbon cable into P5 on the main fire alarm module using the included MD-579 four-wire power cable (as described in 5.0 Module Settings on page 25).
3. You can connect a second circuit adder module by plugging its 26 pin cable into the matching socket on the module to its right, and by installing the supplied MD-579 four­wire power cable (as described in 5.0 Module Settings on page 25).
Module Mounting Locations
#6-32 X 1 1/4” screw
other circuit adder module (see Notes below)
#6-32 1
1
/2” M/F
hex spacer
other circuit adder modules (see
Notes below)
i

4.2 BB-1072 Expansion Chassis Mounting Locations

The BB-1072 enclosure with an ECH-1048 expander chassis is equipped with two long extension cables: one for the 26-pin ribbon cable (MD-575) and one for the four-wire power cable (MD-580). Circuit adder modules are installed from right to left in two tiers (back then front). These circuit adder modules are cabled in the same way as the main chassis, except that the first module on the back tier to the right connects (via the MD-575 and MD-580 extension cables) to the second module in the main chassis. The fourth module on the front tier to the right connects (via MD-575 and MD-580 extension cables) to the third module on the first tier to the left. In other words, follow a continuous right to left, bottom to top, and back to front installation order (see Figure 7).
Figure 7 BB-1072 Expansion Chassis Mounting Locations
Notes: Front plate is not shown. Other circuit adder modules may be:
DM-1008A Detection Circuit Module
SGM-1004A Signal Circuit Module
RM-1008A Relay Circuit Module
23
Main Chassis
MD-575 Long Ribbon Cable MD-579 Short Power Cable MD-580 Long Power Cable
MD-580
MD-575
MCC-1024-6 or
MCC-1024-12

4.3 Circuit Adder Mounting Details

Expander Chassis
ECH-1048
Provision for
PR-300 or
UDACT-300A
Place continuity jumper on last board
Module Mounting Locations
8
5
2
Figure 8 Circuit Adder Mounting Details
1
MD-579
7
4
6
3
MD-575
MD-580
24

5.0 Module Settings

MAIN FIRE ALARM BOARD
FIELD WIRING TERMINALSP1
P4
P5
P6
F1
P8 P7 P10 P9
-BDG+ -B
A
T+
P3
JW1
P2
JW4
JW2 JW3
JW5
JW6
RS-485 connection for future expansion
Connector for PR-300 Module or UDACT-300A
Connector for display module
(MCC-1024)
Connector for future
expansion
Factory connection to
Bridge Rectifier
Connection to
24VDC battery
Power connector for adder modules
Connector for circuit adder modules
Connector for future
expansion
Remove these jumpers to program Class B
i

5.1 Main Fire Alarm Module

Module Settings
Figure 9 Main Fire Alarm Module

5.1.1 Jumpers

JW1 Install jumper for Class A (Style D) operation of initiating circuits 3 and 4. JW2 Install jumper for Class A (Style D) operation of initiating circuits 5 and 6. JW3 Install jumper for Class A (Style D) operation of initiating circuits 7 and 8. JW4 Remove jumper if a PR-300 Module or UDACT-300A is installed. JW5 Install jumper for Class A (Style D) operation of initiating circuits 1 and 2. JW6 Remove continuity jumper if there are any circuit adder modules i nstalled, and
Note: The main display module (part of the main chassis) has four dedicated display
The main fire alarm module contains the following circuits, each requiring a certain number of display points:
Table 1 Main Fire Alarm Module Circuit Details
Chassis Type Initiating Circuits In di cating circuits Display Points Required
MCC-1024-6(S) 8 Style B / 4 Style D 4 Style Y or Z 8/4 (Style B / D) MCC-1024-12(S) 8 Style B / 4 Style D 4 Style Y or Z 8/4 (Style B / D)
install it on the last circuit adder module.
points for the four indicating circuits on the main fire alarm module.
25

5.2 MCC-1024-6, MCC-1024-12 Main Display Module

P2
Module Settings
TEST/CONFIG
MODE
REMOTE FAILURE
SYSTEM
RESET
FIRE
DRILL
AUTOMATIC
ALARM SIGNAL
CANCEL
GENERAL
ALARM
P1
COMMON TROUBLE
A.C. ON
LAMP
TEST
AUXILIARY
DISCONNECT
ALM/SUP/TBL/
BLDG AUDIBLE
SIL
SIGNAL
SILENCE
COMMON
ALARM
COMMON
SUPERVISORY
BATTERY/ CHARGER TROUBLE
CPU FAULT
GROUND FAULT
SIGNAL 1
TROUBLE
SIGNAL 2
TROUBLE
SIGNAL 3 TROUBLE
SIGNAL 4
TROUBLE
ZONE
1
ZONE
2
ZONE
3
ZONE
4
ZONE
5
ZONE
6
ZONE
7
ZONE
8
1814 18 18 18
CONFIG .
SIG. ZONE
DISCONNECT
DET. ZONE
DISCONNECT
ZONE
DISCONNECT
ZONE
DISCONNECT
26
Figure 10 Main Display Module (MCC-1024-6, MCC-1024-12)

5.2.1 Connectors

i
P1 Cable connects to P3 of main fire alarm module. P2 Connection to P1 of ECH-1048 display Module if used. SW1 to
SW5
Note: The main display module comes with a Label Sheet (NP-2854) including both
English and French slide-in labels. This sheet may be run through a laser printer for labelling purposes before being installed. The first slide-in section comes in two versions; one for single-stage systems, and one for two-stage systems.
The main display module provides four dedicated display points for the four indicating circuits on the main fire alarm module. It also provides the following general-purpose display points:
Chassis Type Display Points
MCC-1024-6 24 The main display has dedicated display points for MCC-1024-12 24
Module Settings
See 9.0 System Configuration on page 60 and 8.0 Indicators, Controls, and Operation on page 49.
the eight initiating circuits and four indicating circuits that are located on the main board.
On the MCC-1024-6S and MCC-1024-12S Chassis for the U.S.A. market only, the main display module is shown in Figure 11, below. The Disconnect DIP-switches are replaced by slide switches.
TEST/CONFIG
MODE
REMOTE FAILURE
SYSTEM
RESET
FIRE
DRILL
AUTOMATIC
ALARM SIGNAL
CANCEL
GENERAL
ALARM
1 8
1 8
COMMON
TROUBLE
A.C. ON
LAMP TEST
AUXILIARY
DISCONNECT
ALM/SUP/TBL/
BLDG AUDIBLE
SIL
SIGNAL
SILENCE
COMMON
ALARM
COMMON
SUPERVISORY
BATTERY/ CHARGER TROUBLE
CPU FAULT
GROUND FAULT
SIGNAL 1
TROUBLE
SIGNAL 2
TROUBLE
SIGNAL 3 TROUBLE
SIGNAL 4
TROUBLE
1
1
2
2
3
3
ZONE
1
ZONE
2
ZONE
3
ZONE
4
ZONE
5
ZONE
6
ZONE
7
ZONE
8
1
1
5
1
5
2
6
2
6
3
7
3
7
5
1
5
2
6
2
6
3
7
3
7
1
1
5
5
26
26
37
37
4
CONFIGURATION
CONFIGURATION
4
SIGNAL ZONE
SIGNAL ZONE
DISCONNECT
DISCONNECT
48
48
DETECTION ZONE
DETECTION ZONE
DISCONNECT
DISCONNECT
48
48
POINT/ZONE
POINT/ZONE
DISCONNECT
DISCONNECT
Figure 11 Main Display Module (MCC-1024-6S, MCC-1024-12S)
48
48
POINT/ZONE
POINT/ZONE
DISCONNECT
DISCONNECT
27
Loading...
+ 61 hidden pages