(see Application Guide for additional information)
Rev. 042209
Page 2
BPS-602 - NAC Power Extender
Overview:
The Mircom BPS-602 is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be connected to
any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as
strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A, Style Z
NAC loop circuits. Additionally, a separate 1.0A auxiliary output for four (4)-wire smoke detectors is available. The 6.5
amp max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5
amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may
be programmed for Input to Output Follower Mode (output will follow input). An individual output of 4 amp is achieved
by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A, Style Z and/or Class B, Style
W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the steered input
(input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general
loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the
FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any
combination of the four (4) outputs.
Specifications:
Agency Listings:
• UL Listed Control Units and Accessories for
Fire Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC 60 Hz, 4 amp.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, X, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• 24VDC @ 6.5 amp max total alarm current.
• 2.5 amp max current per output.
• Separate 1.0 amp auxiliary output.
• Two (2) outputs may be paralleled for more power on an
indicating circuit (see 02 Application Guide).
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, X, Y or Two (2) Class A,
Style Z or One (1) Class A, Style Z and Two (2) Class B,
Style W, X, Y (see 02 Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Charging voltage is 26.2-26.4VDC.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when AC Fails.
• Zero voltage drop when switching over to battery backup.
Supervision:
• AC fail supervision (form “C” contact, 1 amp / 28VDC).
Factory set for 30 seconds with optional 2.5 to 3 hour
delay setting (field selectable).
Supervision (cont’d):
• Instant local AC trouble reporting relay
(form “C” contact, 1 amp / 28VDC).
• 2-wire horn/strobe Sync mode allows audible
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
• Sync protocols include Potter/Amseco, Faraday,
Gentex
• Temporal Code 3, Steady Mode, Input to Output
Follower Mode (maintains synchronization of
notification appliances circuit).
• Compatible with 12VDC or 24VDC fire panels.
• Output loop supervision steered to input 1 or input 2.
• Signal circuit trouble memory (helps identify
intermittent loop problems).
• Common trouble input and output for external trouble
signals tie-in.
• Ground fault detection.
• Unit includes power supply, red enclosure, cam lock,
and battery leads.
®
, System Sensor®, and CooperWheelock®.
Enclosure Dimensions (approx. H x W x D):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
WARNING: To reduce the risk of fire or electric shock do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
- 2 - BPS-602
Page 3
Power Supply Specifications:
L N
line
ground
neutral
AC Input:
Output:
Battery
Stand-by/Alarm Current
Consumption:
EOL Resistor (end of line):
Ground fault maximum
test impedance:
120VAC 60Hz, 4 amp.
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current.
One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised
total output current must not exceed current 6.5 amp in Alarm Condition.
Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH
batteries connected in series.
90mA/175mA
2.2K (2200 ohm).
1000 ohm.
Stand-by Specifications:
Stand-by Batteries Stand-by Time Total Amp/MinutesAlarm Output Current Aux. Output
24VDC/7AH24 Hours6.5 amp/5 minutes--24VDC/12AH
(use two (2) 12VDC batteries in series)
24VDC/40AH24 Hours6.5 amp/5 minutes1 amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp
total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
24 Hours6.5 amp/5 minutes50mA
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction.
Product is intended for indoor dry use only.
Carefully review:
Application Guide for BPS-602, BPS-802, BPS-1002
Power Supply Specifications (pg. 3)
Stand-by Specifications (pg. 3)
Output Programming Selection Table (pg. 4)
Sync Mode Selection Table (pg. 4)
Terminal Identification Table (pgs. 5-6)
LED Status Indication Table (pg. 6)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper
screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 12).
Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from
16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz)
dedicated to the Fire Alarm System.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect battery to the terminals marked [+ BAT - ] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and
desired output signal type (Output Programming Selection Table, pg. 4).
6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the desired AL800LGK9E logic board outputs (see 02 Application Guide).Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability.
7. For connection of smoke detectors, digital dialer see Hookup Diagram, pg. 7.
Fig. 1
BPS-602 - 3 -
Page 4
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:
• For all Class B, Style W, X, Y, hookups SW1 & SW2 on the AL800LGK9E logic board must be open.
For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK9E logic board must be closed.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output Follower
Mode
Temporal Code 3 Mode31, 2
Steady Mode1, 2, 3
Switch Positions
ONOFF
12, 3
Descriptions
Output follows signal it receives from the corresponding input
(i.e. FACP Sync module - maintains synchronization of
notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1)
(AL800LGK9E Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
and audible notification appliances (horns) via Input 2 (IN2). This allows audible
notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. The
FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the
BPS-602 (NAC Power Extender) is connected.
Sync Mode Selection Table:
Function
Amseco Sync
Mode*
Faraday
Sync Mode*
Gentex
Sync Mode*
Gentex is a registered
trademark of Gentex Corporation.
®
System Sensor
Sync Mode*
System Sensor is a registered
trademark of Honeywell.
CooperWheelock
Sync Mode*
CooperWheelock is a
registered trademark of
Cooper Wheelock.
Switch Positions
ONOFF
1, 3,
2, 41, 3
1, 2,
3, 4
®
1, 2, 43
®
2, 3, 41
Descriptions
This mode is designed to work with the Amseco series of horns, strobes, and
horn/strobes to provide a means of synchronizing the Temporal-coded horns,
4
2
synchronizing the flash timing of the strobe, and silencing the horns of the horn/
strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
®
series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
®
This mode is designed to work with the System Sensor
series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the one-second flash timing of the strobe, and silencing the horns of
the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the one-second flash timing of the strobe, and silencing the horns of
the horn/strobe combination over a two-wire circuit while leaving strobes active.
- 4 - BPS-602
Page 5
*Note: The BPS-602 will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be
selected for all outputs
Amount of Notification Appliances per NAC:
Amseco27 per NAC*System Sensor®32 per NAC*
Faraday39 per NAC*CooperWheelock®32 per NAC*
Gentex®32 per NAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:
AL800LGK9E Logic Board
Terminal
Legend
IN1+, IN1 IN2+, IN2 (Supervised)
RET1+, RET1 RET2+, RET2 (Supervised)
Function/Description
These terminals connect to the 24VDC FACP notification appliance circuit outputs.
(Class A, Style Z or Class B, Style W, X, Y) Input trigger voltage is 8-33VDC @ 5mA min.
Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause
the selected outputs chosen to drive notification appliances. The designated outputs are set by output
switches[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trouble condition on
an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An
alarm condition will always override trouble to drive notification appliances.
For (Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class
B, Style W, X, Y hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are
terminated at these terminals.
An open across these inputs, will cause the selected outputs chosen to drive notification appliances.
The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming Selection Table, pg. 4). Note these inputs are unidirectional and will not report a trouble condition
to the FACP.
Notification appliances are connected to these regulated outputs (see 02 Application Guide pg. 2-4).
Each power-limited output will supply 2.5 amp. Two (2) outputs may be connected in parallel for a
maximum NAC output capability of 4 amp. Total supply current is 6.5 amp (see note below). Outputs
are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Programming Selection
An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously signal a
trouble condition back to the FACP (Typically used to report AC or BAT Fail). (form “C” contact 1
amp / 28VDC) (Fig. 2, pg. 7).
These are dry contact trouble outputs that follow any general loop/system trouble conditions.
(Typically used to trigger a digital communicator or other reporting device).
(form “C” contact 1 amp / 28VDC 0.35 Power Factor) (Fig. 2, pg. 7) .
This separate 1 amp max auxiliary Special Application Power output circuit is typically used to
power 4-wire smoke detectors. See attached list of devices (Appendix A, pgs. 10-12).
+ DC -- 24VDC from power supply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” pg. 3 for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp
total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
BPS-602 - 5 -
Page 6
Terminal Identification Table:
Power Supply Board*
Terminal
Legend
L, G, NConnect 120 VAC to these terminals: L to hot, N to neutral.
- DC +24VDC @ 6.5 amp in alarm non power-limited output.
AC FAIL
NO, C, NC
Function/Description
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal conditions terminals marked NO and C are open, NC and C are closed. During a trouble condition terminals
marked NO and C are closed, and NC and C are open (Fig. 2, pg. 7).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut
jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power
Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).
A restored battery will report within 30 seconds.
LED Diagnostics:
Power Supply Board
Red (DC)Green (AC)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery is supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
* Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the
corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will
blink as well. Loop trouble will report within 30 seconds.
** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, [OUT1-OUT4]
will blink with a shorter and distinctly a different duration. The green input LEDs will be off (normal condition).
To reset the memory depress the reset button (Fig. 2c, pg. 7). The LED(s) will extinguish.
Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.
- 6 - BPS-602
Page 7
Non-power limited
Supervised
Non power-limited
NC CNOC "FAULT" NC
These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2
-- DC +
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
OUT1OUT3
OUT2OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
+ DC ---
BAT FAIL
NO C NC NO C NC
+ BAT ---
DC
AC FAIL
AC
15A
250V
Use separate knockout. Keep 1/4" spacing from
non power limited wiring
RESET
J2
Hookup Diagram:
Fig. 2
Fire
Alarm
Control
Panel
(FACP)
+
4-wire Smoke
Detector
--
Fig. 2a
Green Lead
unswitched 120VAC
power mains
(non-power limited)
Earth
Ground
5A
250V
line
neutral
Non-Supervised
-- AUX +
AC Local
Use separate knockout. Keep 1/4" spacing from
non power-limited wiring
Divider
-- DC +
RESET
OUT1 OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
Non-power limited
Supervised
Non power-limited
Green Lead
This connection is used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
Non-Supervised
EOL
Resistor
from
FACP
4-wire Smoke
Detector
EOL Power
Supervision Relay
(Not Supplied)
+
SW1
SW2
+ OUT1 --
--
Regulated Power-Limited Outputs
+ OUT2 --
2.5 amp max. per
output in alarm
(total= 6.5 amp)
(Supervised)
+ OUT3 --
+ OUT4 --
IN1--
IN2+
IN1+
IN2--
RET1--
RET2+
RET1+
RET2--
SupervisedNon-Supervised
C "DRY1" NC
C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
Addressable
Control Module
Trigger Output
See Note 2
NC CNOC "FAULT" NC
Trouble Memory
Common trouble output to
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts) (Non-Supervised)
Common trouble
Input/Output
Fig. 2b
Reset Button
Fig. 2c
BPS-602 - 7 -
Page 8
Optional Hookups:
1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to
report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. (see Power Board Parameter for use of AC Delay, pg. 6)
To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2a) to the
common trouble input.
2- Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an
addressable module (these inputs are unidirection and cannot report back to trigger module).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliary output (-AUX+) 24VDC at 1 amp max.
4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of
the trouble condition.
Note: If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be
shorted (connect jumper) to remain inactive. For optional hookups see Fig. 2b.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(26.2-26.4VDC recommended range).
Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at the battery terminal and at the board terminals marked [+ BAT - ] to ensure that there is no break in the battery connection wires.
Fuses: Check input fuse on the power supply board, replace if necessary. Input fuse rating is 5 amp @ 250V.
Note: Maximum charging current is 650mA.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
- 8 - BPS-602
Page 9
Battery Calculation Worksheet
Device
Number of
Devices
Current per Device
Stand-by
Current
Alarm
Current
For each device use this formula: This column x This column = EqualsCurrent per number of devices.
BPS-602
(Current draw from battery)
1
ABPS-602 Current
Stand-by:90mA90mA
Alarm: 175mA175mA
90mA175mA
Auxiliary Devices Refer to device manual for current ratings.
Alarm/Stand-bymAmAmA
Alarm/Stand-by
mA
mA mA
Alarm/Stand-bymAmAmA
BAuxiliary Devices Current (must not exceed 1 amp)
Refer to device manual for current ratings.
Alarm:mA0mAmA
Alarm:
mA
0mAmA
Alarm:mA0mAmA
Alarm:
mA0mAmA
C
Notification Appliances Current must not exceed 6.5 amp (6500mA) 0mAmA
D
Total alarm currentmAmA
E
Total current ratings converted to amperes (line D x .001)AA
F
Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5).H
G
Multiply lines E and F. Total stand-by AHAH
Alarm sounding period in hours.
H
(For example, 5 minutes = .0833 hours.)
I
Multiply lines E and H. Total alarm AHAH
J
Add lines G and I. Total stand-by and alarm AHAH
Multiply line J by 1.30.
K
(30% extra insurance to meet desired performance)
AH
Total ampere - hours required
Units are capable of recharging 40AH battery max. If total ampere - hour required exceeds 40AH,
decrease AUX current to provide enough stand-by time for the application.
H
BPS-602 - 9 -
Page 10
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with BPS-602 AUX output.
Smoke Detector/Base
Detector Type
Max Standby
Current (mA)
Alarm
Current (mA)
FenWal CPD-7021 (w/70-201000-005 Base)Ionization0.10*
FenWal PSD-7125Photoelectric0.10*
FenWal PSD-7125 (w/70-201000-005 Base)Photoelectric0.10*
Fire-Lite BLP-12-4WBase**
Gentex 824Photoelectric0.50*
Gentex 824TPhotoelectric0.50*
Gentex 824CPPhotoelectric0.50*
Gentex 824CPTPhotoelectric0.50*
Hochiki HSC-4RBase**
Hochiki SPB-24Projected Beam0.25*
System Sensor B112LPBase0.1236
System Sensor B114LPBase**
System Sensor B404BBase**
System Sensor DH100ACDCPhotoelectric0.150.70
System Sensor DH100ACDCLPPhotoelectric0.150.70
System Sensor DH100ACDCLPWPhotoelectric0.150.70
System Sensor DH400ACDCIIonization Duct2595
System Sensor DH400ACDCPPhotoelectric Duct2595
System Sensor 1112/24/DIonization0.0550
System Sensor 1424Ionization0.1041
System Sensor 1451 (w/B402B Base)Ionization0.1039
System Sensor 2112/24ATRPhotoelectric0.5060/70
System Sensor 2112/24AITRPhotoelectric0.5060/70
System Sensor 2112/24/DPhotoelectric0.0550
System Sensor 2112/24RPhotoelectric0.5060/70
System Sensor 2112/24TRPhotoelectric0.5060/70
o
System Sensor 2112/24T/D
System Sensor 2112/24TSRB
Photoelectric w/135
Thermal
Photoelectric w/135
Thermal Supervisory Relay
0.0550
o
1545
System Sensor 2312/24TBPhotoelectric0.1250
System Sensor 2412 (12 volt)Photoelectric0.1277
System Sensor 2412AT (12 volt)Photoelectric0.1258
System Sensor 2412TH (12 volt)Photoelectric0.1277
System Sensor 2424Photoelectric0.1041
System Sensor 2424THPhotoelectric0.1041
System Sensor 2451Photoelectric0.1039
System Sensor 2451TH (with/B402B Base)Photoelectric0.1039
System Sensor 2W-MOD
Loop Test/Maintenance
Mod.
3050
- 10 - BPS-602
Page 11
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base
Detector Type
System Sensor 4W-B (12/24 volt)Photoelectric I
System Sensor 4WT-B (12/24 volt)Photoelectric I
System Sensor 4WTA-B (12/24 volt)I
System Sensor 4WTR-B (12/24 volt)I
System Sensor 4WTR-B (12/24 volt)
System Sensor 4WITAR-B (12/24 volt)
System Sensor 2W-MOD2
System Sensor RRS-MOD
3
Photo w/Therm/Sounder.0535
3
Photo w/Therm/Relay.0535
3
Photo w/Therm/
I
Sounder/Relay
3
Photo w/Isolated Therm/
I
Sounder/Relay
3
Loop Test/Maintenance
I
3
Reversing Relay/Sync
I
3
w/Therm.0523
Mod.
Module
Max Standby
Current (mA)
3
.0523
.0550
.0550
.05*
.05*
Alarm
Current (mA)
System Sensor 6424Projected Beam1028.4
System Sensor Beam 1224(S)Projected Beam1738.5
* Contact manufacturer for current draws
A.2 Door Holders
Table A-2 below lists door holders compatible with BPS-602 AUX output.
ManufacturerModelTypeCurrent (mA)
EdwardsDH150AFloor Mount96
EdwardsDH154AFloor Mount96
EdwardsDH158ASurface Mount96
Rixon FiremarkFM-980Floor Mount, single68
Rixon FiremarkFM-996Surface Wiring68
Rixon FiremarkFM-998Concealed Wiring68
A.3 Relays
Table A-3 below lists relays compatible with BPS-602 AUX output.