Mircom BPS-602 Installation Manual

Page 1
BPS-602
NAC Power Extender
Installation Guide
(see Application Guide for additional information)
Rev. 042209
Page 2
BPS-602 - NAC Power Extender
Overview:
The Mircom BPS-602 is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system acces­sories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A, Style Z NAC loop circuits. Additionally, a separate 1.0A auxiliary output for four (4)-wire smoke detectors is available. The 6.5 amp max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A, Style Z and/or Class B, Style W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs.
Specifications:
Agency Listings:
• UL Listed Control Units and Accessories for Fire Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC 60 Hz, 4 amp.
• Two (2) Class A, Style Z or two (2) Class B, Style W, X, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• 24VDC @ 6.5 amp max total alarm current.
• 2.5 amp max current per output.
• Separate 1.0 amp auxiliary output.
• Two (2) outputs may be paralleled for more power on an indicating circuit (see 02 Application Guide).
• Programmable supervised indicating circuit outputs: Four (4) Class B, Style W, X, Y or Two (2) Class A, Style Z or One (1) Class A, Style Z and Two (2) Class B, Style W, X, Y (see 02 Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Charging voltage is 26.2-26.4VDC.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when AC Fails.
• Zero voltage drop when switching over to battery backup.
Supervision:
• AC fail supervision (form “C” contact, 1 amp / 28VDC). Factory set for 30 seconds with optional 2.5 to 3 hour delay setting (field selectable).
Supervision (cont’d):
• Instant local AC trouble reporting relay (form “C” contact, 1 amp / 28VDC).
• Battery presence and low battery supervision (form “C” contact, 1 amp / 28VDC).
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
• Sync protocols include Potter/Amseco, Faraday, Gentex
• Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
• Compatible with 12VDC or 24VDC fire panels.
• Output loop supervision steered to input 1 or input 2.
• Signal circuit trouble memory (helps identify intermittent loop problems).
• Common trouble input and output for external trouble signals tie-in.
• Ground fault detection.
• Unit includes power supply, red enclosure, cam lock, and battery leads.
®
, System Sensor®, and CooperWheelock®.
Enclosure Dimensions (approx. H x W x D):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
WARNING: To reduce the risk of fire or electric shock do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes.
- 2 - BPS-602
Page 3
Power Supply Specifications:
L N
line
ground
neutral
AC Input:
Output:
Battery
Stand-by/Alarm Current Consumption:
EOL Resistor (end of line): Ground fault maximum
test impedance:
120VAC 60Hz, 4 amp.
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total output current must not exceed current 6.5 amp in Alarm Condition.
Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH batteries connected in series.
90mA/175mA
2.2K (2200 ohm).
1000 ohm.
Stand-by Specifications:
Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24VDC/7AH 24 Hours 6.5 amp/5 minutes --­24VDC/12AH
(use two (2) 12VDC batteries in series) 24VDC/40AH 24 Hours 6.5 amp/5 minutes 1 amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
24 Hours 6.5 amp/5 minutes 50mA
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor dry use only. Carefully review:
Application Guide for BPS-602, BPS-802, BPS-1002 Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Status Indication Table (pg. 6)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 12). Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from 16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz) dedicated to the Fire Alarm System.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect battery to the terminals marked [+ BAT - ] on the Power Supply Board (battery leads included). Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and desired output signal type (Output Programming Selection Table, pg. 4).
6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the desired AL800LGK9E logic board outputs (see 02 Application Guide). Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability.
7. For connection of smoke detectors, digital dialer see Hookup Diagram, pg. 7.
Fig. 1
BPS-602 - 3 -
Page 4
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:
• For all Class B, Style W, X, Y, hookups SW1 & SW2 on the AL800LGK9E logic board must be open. For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK9E logic board must be closed.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output Follower Mode
Temporal Code 3 Mode 3 1, 2
Steady Mode 1, 2, 3
Switch Positions
ON OFF
1 2, 3
Descriptions
Output follows signal it receives from the corresponding input (i.e. FACP Sync module - maintains synchronization of notification appliance circuit).
Enables Temporal Code 3 signal generation output. This mode will accept a steady or a pulsing input.
A steady output signal will be generated. This mode will accept steady or pulsing input.
For the above modes Dip Switch 4 determines which Input controls the corresponding output: Switch 4 in the ON position causes output(s) to be controlled by Input 1. Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1)
(AL800LGK9E Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
and audible notification appliances (horns) via Input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. The FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the BPS-602 (NAC Power Extender) is connected.
Sync Mode Selection Table:
Function
Amseco Sync Mode*
Faraday Sync Mode*
Gentex Sync Mode*
Gentex is a registered trademark of Gentex Corporation.
®
System Sensor Sync Mode*
System Sensor is a registered trademark of Honeywell.
CooperWheelock Sync Mode*
CooperWheelock is a registered trademark of Cooper Wheelock.
Switch Positions
ON OFF
1, 3,
2, 4 1, 3
1, 2,
3, 4
®
1, 2, 4 3
®
2, 3, 4 1
Descriptions
This mode is designed to work with the Amseco series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
4
2
synchronizing the flash timing of the strobe, and silencing the horns of the horn/ strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns, strobes, and horn/ strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz­ing the flash timing of the strobe, and silencing the horns of the horn/strobe combi­nation over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
®
series of horns, strobes, and horn/ strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz­ing the flash timing of the strobe, and silencing the horns of the horn/strobe combi­nation over a two-wire circuit while leaving strobes active.
®
This mode is designed to work with the System Sensor
series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
- 4 - BPS-602
Page 5
*Note: The BPS-602 will only synchronize horns, horn/strobes and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be selected for all outputs
Amount of Notification Appliances per NAC:
Amseco 27 per NAC* System Sensor® 32 per NAC* Faraday 39 per NAC* CooperWheelock® 32 per NAC* Gentex® 32 per NAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:
AL800LGK9E Logic Board
Terminal Legend
IN1+, IN1­ IN2+, IN2­ (Supervised)
RET1+, RET1­ RET2+, RET2­ (Supervised)
Function/Description
These terminals connect to the 24VDC FACP notification appliance circuit outputs. (Class A, Style Z or Class B, Style W, X, Y) Input trigger voltage is 8-33VDC @ 5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances.
For (Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B, Style W, X, Y hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals.
C “DRY1” NC C “DRY2” NC (Dry input trigger)
+ OUT1 -- + OUT2 -­ + OUT3 -- + OUT4 -- (Supervised)
C “FAULT” NC (Common trouble input)
NC, C, NO (Common trouble output)
-- AUX+
An open across these inputs, will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming Selection Table, pg. 4). Note these inputs are unidirectional and will not report a trouble condition to the FACP.
Notification appliances are connected to these regulated outputs (see 02 Application Guide pg. 2-4). Each power-limited output will supply 2.5 amp. Two (2) outputs may be connected in parallel for a maximum NAC output capability of 4 amp. Total supply current is 6.5 amp (see note below). Outputs are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Programming Selection
An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail). (form “C” contact 1 amp / 28VDC) (Fig. 2, pg. 7).
These are dry contact trouble outputs that follow any general loop/system trouble conditions. (Typically used to trigger a digital communicator or other reporting device). (form “C” contact 1 amp / 28VDC 0.35 Power Factor) (Fig. 2, pg. 7) .
This separate 1 amp max auxiliary Special Application Power output circuit is typically used to power 4-wire smoke detectors. See attached list of devices (Appendix A, pgs. 10-12).
+ DC -- 24VDC from power supply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” pg. 3 for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
BPS-602 - 5 -
Page 6
Terminal Identification Table:
Power Supply Board*
Terminal Legend
L, G, N Connect 120 VAC to these terminals: L to hot, N to neutral.
- DC + 24VDC @ 6.5 amp in alarm non power-limited output.
AC FAIL NO, C, NC
Function/Description
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs termi­nals marked NO and C are closed, NC and C are open.
AC LOCAL NC, NO, C
BAT FAIL NO, C, NC
+ BAT - Stand-by battery input (leads provided) (Fig. 2, pg. 7).
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs termi­nals marked NO and C are closed, NC and C are open.
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal con­ditions terminals marked NO and C are open, NC and C are closed. During a trouble condition terminals marked NO and C are closed, and NC and C are open (Fig. 2, pg. 7).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed). A restored battery will report within 30 seconds.
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery is supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
AL800LGK9E - Logic Board
LED OFF ON BLINK (LONG)* BLINK (SHORT)**
ON Normal Alarm Condition Trouble Condition Trouble Condition Memory ON Normal Alarm Condition Trouble Condition Trouble Condition Memory OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory Input 1 Normal Alarm Condition Trouble Condition --­Input 2 Normal Alarm Condition Trouble Condition --­Fault Normal Alarm Condition --- ---
* Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will blink as well. Loop trouble will report within 30 seconds. ** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, [OUT1-OUT4] will blink with a shorter and distinctly a different duration. The green input LEDs will be off (normal condition). To reset the memory depress the reset button (Fig. 2c, pg. 7). The LED(s) will extinguish. Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.
- 6 - BPS-602
Page 7
Non-power limited
Supervised
Non power-limited
NC CNOC "FAULT" NC
These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2
-- DC +
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
+ DC ---
BAT FAIL
NO C NC NO C NC
+ BAT ---
DC
AC FAIL
AC
15A
250V
Use separate knockout. Keep 1/4" spacing from
non power limited wiring
RESET
J2
Hookup Diagram:
Fig. 2
Fire
Alarm
Control
Panel
(FACP)
+
4-wire Smoke
Detector
--
Fig. 2a
Green Lead
unswitched 120VAC
power mains
(non-power limited)
Earth
Ground
5A
250V
line
neutral
Non-Supervised
-- AUX +
AC Local
Use separate knockout. Keep 1/4" spacing from non power-limited wiring
Divider
-- DC +
RESET
OUT1 OUT3
INPUT SELECT
TEMPORAL STROBE SYNC IN > OUT SYNC
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
Non-power limited
Supervised
Non power-limited
Green Lead
This connection is used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2
Non-Supervised
EOL
Resistor
from
FACP
4-wire Smoke
Detector
EOL Power
Supervision Relay
(Not Supplied)
+
SW1
SW2
+ OUT1 --
--
Regulated Power-Limited Outputs
+ OUT2 --
2.5 amp max. per output in alarm (total= 6.5 amp)
(Supervised)
+ OUT3 --
+ OUT4 --
IN1--
IN2+
IN1+
IN2--
RET1--
RET2+
RET1+
RET2--
Supervised Non-Supervised
C "DRY1" NC
C "DRY2" NC
UPPER TERMINALS LOWER TERMINALS
Addressable Control Module Trigger Output See Note 2
NC CNOC "FAULT" NC
Trouble Memory
Common trouble output to Digital Communicator or Local Annunciator Dry output Contact (Form "C" contacts) (Non-Supervised)
Common trouble
Input/Output
Fig. 2b
Reset Button
Fig. 2c
BPS-602 - 7 -
Page 8
Optional Hookups:
1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. (see Power Board Parameter for use of AC Delay, pg. 6)
To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2a) to the common trouble input.
2- Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an addressable module (these inputs are unidirection and cannot report back to trigger module).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliary output (-AUX+) 24VDC at 1 amp max.
4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition.
Note: If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups see Fig. 2b.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(26.2-26.4VDC recommended range).
Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at the bat­tery terminal and at the board terminals marked [+ BAT - ] to ensure that there is no break in the battery connection wires.
Fuses: Check input fuse on the power supply board, replace if necessary. Input fuse rating is 5 amp @ 250V. Note: Maximum charging current is 650mA. Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
- 8 - BPS-602
Page 9
Battery Calculation Worksheet
Device
Number of Devices
Current per Device
Stand-by Current
Alarm Current
For each device use this formula: This column x This column = Equals Current per number of devices.
BPS-602 (Current draw from battery)
1
A BPS-602 Current
Stand-by: 90mA 90mA
Alarm: 175mA 175mA
90mA 175mA
Auxiliary Devices Refer to device manual for current ratings.
Alarm/Stand-by mA mA mA
Alarm/Stand-by
mA
mA mA
Alarm/Stand-by mA mA mA
B Auxiliary Devices Current (must not exceed 1 amp)
Refer to device manual for current ratings.
Alarm: mA 0mA mA
Alarm:
mA
0mA mA
Alarm: mA 0mA mA Alarm:
mA 0mA mA
C
Notification Appliances Current must not exceed 6.5 amp (6500mA) 0mA mA
D
Total alarm current mA mA
E
Total current ratings converted to amperes (line D x .001) A A
F
Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5). H
G
Multiply lines E and F. Total stand-by AH AH
Alarm sounding period in hours.
H
(For example, 5 minutes = .0833 hours.)
I
Multiply lines E and H. Total alarm AH AH
J
Add lines G and I. Total stand-by and alarm AH AH
Multiply line J by 1.30.
K
(30% extra insurance to meet desired performance)
AH
Total ampere - hours required
Units are capable of recharging 40AH battery max. If total ampere - hour required exceeds 40AH, decrease AUX current to provide enough stand-by time for the application.
H
BPS-602 - 9 -
Page 10
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with BPS-602 AUX output.
Smoke Detector/Base
Detector Type
Max Standby
Current (mA)
Alarm
Current (mA)
FenWal CPD-7021 (w/70-201000-005 Base) Ionization 0.10 * FenWal PSD-7125 Photoelectric 0.10 * FenWal PSD-7125 (w/70-201000-005 Base) Photoelectric 0.10 * Fire-Lite BLP-12-4W Base * * Gentex 824 Photoelectric 0.50 * Gentex 824T Photoelectric 0.50 * Gentex 824CP Photoelectric 0.50 * Gentex 824CPT Photoelectric 0.50 * Hochiki HSC-4R Base * * Hochiki SPB-24 Projected Beam 0.25 * System Sensor B112LP Base 0.12 36 System Sensor B114LP Base * * System Sensor B404B Base * * System Sensor DH100ACDC Photoelectric 0.15 0.70 System Sensor DH100ACDCLP Photoelectric 0.15 0.70 System Sensor DH100ACDCLPW Photoelectric 0.15 0.70 System Sensor DH400ACDCI Ionization Duct 25 95
System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112/24/D Ionization 0.05 50 System Sensor 1424 Ionization 0.10 41 System Sensor 1451 (w/B402B Base) Ionization 0.10 39 System Sensor 2112/24ATR Photoelectric 0.50 60/70 System Sensor 2112/24AITR Photoelectric 0.50 60/70 System Sensor 2112/24/D Photoelectric 0.05 50 System Sensor 2112/24R Photoelectric 0.50 60/70 System Sensor 2112/24TR Photoelectric 0.50 60/70
o
System Sensor 2112/24T/D
System Sensor 2112/24TSRB
Photoelectric w/135
Thermal
Photoelectric w/135
Thermal Supervisory Relay
0.05 50
o
15 45
System Sensor 2312/24TB Photoelectric 0.12 50 System Sensor 2412 (12 volt) Photoelectric 0.12 77 System Sensor 2412AT (12 volt) Photoelectric 0.12 58 System Sensor 2412TH (12 volt) Photoelectric 0.12 77 System Sensor 2424 Photoelectric 0.10 41 System Sensor 2424TH Photoelectric 0.10 41 System Sensor 2451 Photoelectric 0.10 39 System Sensor 2451TH (with/B402B Base) Photoelectric 0.10 39
System Sensor 2W-MOD
Loop Test/Maintenance
Mod.
30 50
- 10 - BPS-602
Page 11
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base
Detector Type
System Sensor 4W-B (12/24 volt) Photoelectric I System Sensor 4WT-B (12/24 volt) Photoelectric I System Sensor 4WTA-B (12/24 volt) I System Sensor 4WTR-B (12/24 volt) I
System Sensor 4WTR-B (12/24 volt)
System Sensor 4WITAR-B (12/24 volt)
System Sensor 2W-MOD2
System Sensor RRS-MOD
3
Photo w/Therm/Sounder .05 35
3
Photo w/Therm/Relay .05 35
3
Photo w/Therm/
I
Sounder/Relay
3
Photo w/Isolated Therm/
I
Sounder/Relay
3
Loop Test/Maintenance
I
3
Reversing Relay/Sync
I
3
w/Therm .05 23
Mod.
Module
Max Standby
Current (mA)
3
.05 23
.05 50
.05 50
.05 *
.05 *
Alarm
Current (mA)
System Sensor 6424 Projected Beam 10 28.4 System Sensor Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws
A.2 Door Holders
Table A-2 below lists door holders compatible with BPS-602 AUX output.
Manufacturer Model Type Current (mA)
Edwards DH150A Floor Mount 96
Edwards DH154A Floor Mount 96
Edwards DH158A Surface Mount 96
Rixon Firemark FM-980 Floor Mount, single 68
Rixon Firemark FM-996 Surface Wiring 68
Rixon Firemark FM-998 Concealed Wiring 68
A.3 Relays
Table A-3 below lists relays compatible with BPS-602 AUX output.
Manufacturer Model Current (mA)
Air Products &
Controls, LTD
MR-101/C MR-201/C PAM-1 PAM-2 PAM-SD
A77-716B
15 35 15 15 15
20
Manufacturer Model Current (mA)
System Sensor
PR-1 PR-2 PR-3 EOLR-1 R-10T R-14T R-20T R-24T R-10E R-14E R-20E
R-24E
15 30 30 30 23 23 40 40 23 23 40 40
BPS-602 - 11 -
Page 12
A.4 Strobes
Table A-4 below lists strobes compatible with BPS-602 NAC output.
Wheelock Devices:
Sychronizing Horns
AH-12 AH-12WP HS-24 NH-12/24 ZNH
HNR AH-24AH-24 AH-24WP MIZ-24S HNW
Sychronizing Horn Strobes
AS-121575W AS-24MCW AS-24MCWH AS-2415C AS-2475C ASWP-2475W NS4-121575W HS4-241575W HS4-24MCW
HS4-24MCWH HS4-24185W ZNS-MCW ZNS-MCWH HSR AS-241575W AS-24MCC AS-24MCCH AS-2430C
AS-24100C NS-121575W NS-2-41575W NS-24MCW HS4-24150C HSW
Sychronizing Strobes
RSS-121575W RSS-241575W RSS-24MCW RSS-24MCC RSS-2415C RSS-2430C RSS-2475C RSS-24100C RSS-2415CR RSS-2430CR
RSS-2475CR RSS-24100CR RSS-24150C RSS-24177C RSS-24150W RSS-24177W RSS-24185W RSS-24150CR RSS-24177CR RSSWP-2475W
Appliances with Sychronizing Strobes
AMT-241575W AMT-2475W AMT-241575W-NYC AMT-2475W-NYC MT-12575W MT-241575W MTWP-2475W CH70-24MCW CH70-24MCC CH70-2415C CH70-2430C CH70-2475C CH70-24100C CH70-24150C CH70-24177C CH70-24150W CH70-24MCWH CH70-24185W E70-24MCW
E70-24MCC E70-2415C E70-2430C E70-2475C E70-24100C E70-24150C E70-24177C E70-24150W E70-24MCWH E70-24185W ET70-24MCW ET70-24MCC ET70-2415C ET70-2430C ET70-2475C ET70-24100C ET70-24150C ET70-24177C ET70-24150W
ZRS-MCW ZRS-MCWH STR RSSP-121575W RSSP-241575W RSSP-24MCW RSSP-24150W RSSP-24177W RSSP-24185W STW
ET70-24MCWH ET70-24185W SA-70-24-SL SA-70-24-SLM AMT4-241575W AMT4-2475W AMT4-241575W-NYC AMT4-2475W-NYC MT-2475W ET70WP-2475W CH90-24MCW CH90-24MCC CH90-2415C CH90-2430C CH90-2475C CH90-24100C CH90-24150C CH90-24177C CH90-24150W
CH90-24MCCH CH90-24185W E90-24MCW E90-24MCC E90-2415C E90-2430C E90-2475C E90-24100C E90-24150C E90-24177C E90-24150W E90-24MCCH E90-24185W ET90-24MCW ET90-24MCC ET90-2415C ET90-2430C SA-90-24-SL SA-90-24-SLM
- 12 - BPS-602
Page 13
A.4 Strobes (cont.)
Wheelock Devices:
Coded Audible Appliances
AMT - 12/24 AMT - 12/24-NYC CH70 CSX10-24-DC MT-12/24
AMT4 - 12/24 AMT4 - 12/24-NYC CH90 CSXG10-24-DC MT4-12/24
Non-Synchronizing Appliances
MB-G6-12 MB-G10-12 MIZ-TC12
MB-G6-24 MB-G10-24 MIZ-TC24
Gentex Devices:
Models
GE3 Series GES/GEC Series GCS/ GCC Series
SSPK Wall and Ceiling Mount Series GX93 Series WGE and color lense units.
System Sensor Devices:
Wall Horn/Strobes
P2R P2RH P2RK P2RHK P2W P2WH
P4R P4RH P4RK P4RHK P4W P4WH
Wall Strobes
SR SRH SRK
SRHK SW SWH
Ceiling Horn/Strobes
PC2R PC2RH PC2RK PC2RHK PC2W PC2WH
PC4R PC4RH PC4RK PC4RHK PC4W PC4WH
Ceiling Strobes
SCR SCRH SCRK
SCRHK SCW SCWH
Horns
HR HRK HW
BPS-602 - 13 -
Page 14
A.4 Strobes (cont.)
Amseco Devices:
Models
H24R H24W HP-25T MH12/24 MH-120 RSD24-153075 RSD24W75110 SAD-24-153075 SAD2475110
Faraday Devices:
Models
HS-MC-R HS-MC-W HS-HMC-R HS-HMC-W HS-R HS-W NS-MC-CR NS-MC-CW NH-CR NH-CW SET-MC-R SET-MC-W SET-HMC-R SET-HMC-W SET-S17R-WP SET-S17-W-WP SET-S17-CW-WP SET-MC-CW SET-MC-CR SET-HMC-CW SET-HMC-CR SET-177-CR-WP SET-177-CW-WP SET-185-R-WP SET-185-W-WP SEF-MC-R SEF-MC-W SEF-HMC-R
SCM24C-177 SCM24W075110 SCM24W-153075 SCM24W3075110 SH24C-177 SH24C-3075110 SH24W-1530 SH24W3975110 SH24W-75110
SEF-HMC-W SEF-MC-CW SEF-HMC-CW ZH-MC-R ZH-MC-W ZH-HMC-R ZH-HMC-W ZH-R ZH-W ZH-MC-CR ZH-MC-CW ZH-HMC-CR ZH-HMC-CW ZR-MC-CW ZR-MC-CW ZR-HMC-CR ZR-HMC-CW ZBB-R ZBB-W MTH-R MTH-W MTH-MC-R MTH-MC-W MTH-75-R-WP MTH-15-115-R-WP MTH-HMC-CR-WP MTH-HMC-R-WP MTH-HMC-W-WP
SHB/SLB120-75 SHB/SLB24-75 SHB2475 SL24C-177 SL24C-3075110 SL24W-1530 SL24W-75110 SLB24-75
SE-MC-R SE-MC-W SE-HMC-R SE-HMC-W SE-CR SE-CW SE-MC-CR SE-HMC-CW SE-CR SE-CW SE-MC-CR SE-MC-CW SE-HMC-CR SE-HMC-CR AS-MC-R AS-MC-W AS-HMC-R AS-HMC-W AS-MC-CR AS-MC-CW AS-HMC-CR AS-HMC-CW AS-75-R-WP AS-75-CR-WP AH-R AH-W AH-WP
- 14 - BPS-602
Page 15
Notes:
Page 16
Enclosure Dimensions:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.1”
(27.94mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
(393.7mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.1”
(27.94mm)
1.5”
(38.1mm)
0.79”
(20.06mm)
1.75”
(44.45mm)
1.25”
(31.75mm)
5.0”
(127.0mm)
Mircom is not responsible for any typographical errors
USA - 4575 Witmer Industrial Estates, Niagara Falls, NY 14305, Canada - 25 Interchange Way, Vaughan (Toronto), ON L4K5W3, 888-660-4655 • fax: 888-660-4113 web site: www.mircom.com
- 16 - BPS-602
IIBPS-602 K23O
Loading...