Mircom BL-10B, BL-6B Quick Start Manual

MOTORIZED STEEL BELLS BL-6B/BL-10B
Features
Low current draw (20 mA)
6 and 10 inch diameter steel shells for long term
reliability
RFI and EMF suppression prevents noise
problems to the re alarm control panel
Polarized for DC supervision
Pigtail connection
Standard 4 inch square electrical box
mounting
Weatherproof backbox available for outdoor
applications
Red nish
Description
Mircom’s BL-6B and BL-10B Motorized Steel Bells
are designed for today’s re alarm applications. The durable steel construction provides loud resonant tones necessary for re alarm installations.
The BL-6B and BL-10B bells use a varistor suppression element to prevent RFI and EMF noise problems to modern re alarm control panels.
The motor used on the BL-6B and BL-10B bells operate at a very low current (20 mA) to maximize the number of bells per circuit. Both models are equipped with a pigtail connection for wiring.
Both the BL-6B and BL-10B mount on a standard 4” square electrical box for indoor use or on a BB-206WP weatherproof backbox for outdoor applications. Mounting on a 4” octagon outlet box requires the MP-101 Universal Mounting Plate.
Dimensions
S5375 S5375
7135-1477:152
CATALOG NUMBER
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specications and models and also to discontinue models.
NOT TO BE USED FOR INSTALLATION PURPOSES.
5261
Installation Instructions
WIRING (REAR VIEW)
HORIZONTAL AXIS
4“ SQUARE OUTLET BOX
STRIKER
HEX-BOLT
GONG
5"
GASKET FOR MOUNTING ON SURFACE OR WEATHERPROOF BACKBOX
BB-206WP
WEATHERPROOF
BACKBOX
D.C. BELLS (OBSERVE POLARITY)
NO MORE THAN -6dB
NO MORE THAN -6dB
Installation Instructions:
1. Remove the bell.
2. Wire the bell in the circuit.
3. Mount ball mechanism on 4” square standard outlet box with the striker facing down.
4. Replace the bell.
5. The bell must be mounted a minimum of 8 ft. above the oor, or as close to the ceiling as possible.
6. Polarized bell provides red(+) and black(-) lead wires. When you install the bell, polarity must be observed.
Caution:
When electrical supervision is required, use in and out leads as shown.
Notes:
1. Observe polarity.
2. Red wires positive (+).
3. Black wires negative (-).
4. For installation in Canada, installation must comply to Canadian Electrical Code, Part 1, ULC-S524-01, the standard for the installation of re alarm system, and only subject to nal acceptance of local AHJ.
5. For indoor use: Motor re bell only.
6. For outdoor use: Motor re alarm bell attached to waterproof box only.
7. Mounting to a 4” octagon box requires MP-101 mounting plate.
Specications
Model Description Voltage Rated Current Sound Level at 10 ft. dB
BL-6B 6” Motorized Steel Bell 24 VDC 20 mA 86
BL-10B 10” Motorized Steel Bell 24 VDC 20 mA 90
Ordering Informtion
Model Description
BL-6B 6” Motorized Steel Bell
BL-10B 10” Motorized Steel Bell
Accessories
BB-206WP Weatherproof Backbox
MP-101 Universal Mounting Plate
M-1995 Yard Hood
SG-210 Grill for 10” Bell Backbox
NOT TO BE USED FOR INSTALLATION PURPOSES.
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113
Web page: http://www.mircom.com Email: mail@mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113
Distributed by:
CAT. 5261
Rev. 3
Loading...